Table III: Technical data of electric heaters (if installed)
Mod.004H004008H008010012016020
Electric heater capacitykW1.50.51.5+1.0
Supply voltage (ph) V
Max. power inputA6.502.110.82.110.87.57.57.5
Safety thermostat
Power supply cablesmm23 x 1.5 3 x 1.53 x 2.5 3 x 2.5 3 x 2.5 5 x 1.5 5 x 1.55 x 1.5
Recommended fuse (Type gL)A88121212101010
(*) In areas with a 2 kW limit for single-phase electric heaters it is possible to divide the power supply on two phases and
neutral of a three phase supply with neutral.
Use cable type HO7 RN-F - 4 x 1.5 mm
230 (1 ph) 230 (1 ph)
N° 1 Thermostat with automatic reset ST1 60°C
N° 1 Thermostat with manual reset(electric) ST2 100°C
2
- 400V 2N~
230 (*)
0.25+0.25
230 (1 ph)
1.5+1.02x1 + 2x0.5
230 (*) 400 400 400
POWER INPUT
WA WA
ENGLISH
IMPORTANT:
The electric heater must
always be factory
(mod. 42GWE/H...).
The use of other eletric
heaters is absolutely
prohibited.
Failure to follow this
safety requirement
causes unit damage and
voids the warranty.
installed
Table IV:
Material supplied
DescriptionQ.tyUse
Installation instructions1Unit installation
Fresh air intake baffle1Air renewal
T able V : Operating limits
Water circuitWater- side maximum pressureMinimum entering water temperature: + 4°C
1400 kPa (142 m w.c.)Maximum entering water temperature: + 80°C
Room airMinimum temperature: 5°C (1)
Maximum temperature 32°C
Power supply
Notes: (1) If the room temperature can go down to 0°C, it is advisable to empty the water circuit to avoid damage caused by ice (see paragraph
on water connections).
Nominal single phase voltage230V ~ 50Hz60Hz Special Export Market
Operating voltage limitsmin. 198V – max. 264Vmin. 187V – max. 253V
Nominal three phase voltage400V 3N~ 50Hz
Operating voltage limitsmin. 342V – max. 462V
Table VI: Accessories
DescriptionSize / Code
004-008-010012-016-020
2-pipe valve42GW900342GW9007
4-pipe valve42GW900442GW9008
Primary air42GW900542GW9006
Air disch. closing
Active carbon filter40GK-900---002-4040GK-900---012-40
Electrostatic filter40GK-900---001-4040GK-900---011-40
Drain pan42GW900942GW9010
Not to be used on units equipped with electric heater (mod.42GWE)
*
40GK-900---003-4040GK-900---013-40
*
DescriptionSize / Code
004-008-010-012-016-020
Water discharge pump40GKX9001
Control42GW9014
Control42GW9015
Control42GW9016
Control42GW9017
Control CRC33DFS-RM
Auxiliary board42GW9013
GB - 3
Page 5
42 GW
General Information
Unit installation
Read this instruction manual thoroughly before starting
installation.
• This unit complies with the low-voltage (EEC/73/23) and
electromagnetic compatibility (EEC/ 89/336) directives.
• The installation should be carried out by a qualified installer.
• Follow all current national safety code requirements.
In particular ensure that a properly sized and connected ground
wire is in place.
• Check that the voltage and frequency of the mains power supply
are as required for the unit to be installed; the available power
source must be adeguate to operate all other appliances
connected to the same line.
Also ensure that national safety code requirements have been
followed for the main supply circuit.
• Where necessary, use field-supplied 25 mm I.D. PVC pipe of
appropriate length and with the correct thermal insulation for the
condensate drain extension.
• After installation thoroughly test system operation and explain all
system functions to the owner.
• Use this unit only for factory approved applications: the unit
cannot be used in laundry or steam pressing premises.
Choosing the installation site
Positions to avoid:
• Exposure to direct sunlight.
• Areas close to heat sources.
• On damp walls or in positions that may be exposed to water
hazard.
• Where curtains or furniture may obstruct free air circulation.
Recommendations:
• Choose an area free from obstructions which may cause uneven
air distribution and/or return.
• Consider using an area where installation is easy.
• Choose a position that allows for the clearances required.
• Look for a position in the room which ensures the best possible air
distribution.
• Install unit in a position where condensate can easily be piped to an
appropriate drain.
WARNING:
Disconnect the mains power supply switch before servicing
the system or handling any internal parts of the unit.
• The manufacturer declines any liability for damage resulting
from modifications or errors in the electrical or water
connections.
Failure to observe the installation instructions, or use of the
unit under conditions other than those indicated in Table
"Operating limits" of the unit installation manual, will
immediately invalidate the unit warranty.
• Failure to observe electric safety codes may cause a fire hazard in
the event of short circuits.
• Inspect equipment for damage during transport. In case of
damage file an immediate claim with the shipping company.
Do not install or use damaged units.
• In case of malfunction turn the unit off, disconnect the mains
power supply and contact a qualified service engineer.
• Maintenance must only be carried out by qualified personnel.
• All of the manufacturing and packaging materials used for
this appliance are biodegradable and recyclable.
• Dispose of the packaging material in accordance with local
requiremements.
GB - 4
Page 6
42 GW
Avoid...
MAX 3 m
... any obstruction of the unit air intake or supply grilles.
ENGLISH
MAX 3 m
... exposure to direct sunshine, when the unit is operating in the
cooling mode; always use shutters or shades.
... positions too close to heating sources which may damage the unit.
... exposure to oil vapours.
... installation in areas with high frequency waves.... only partial insulation of the piping.
MAX. 200 mm
... connecting condensate piping to sewage system drain without
appropriate trap. Trap height must be calculated according to the
unit discharge head in order to allow sufficient and continuous
water evacuation.
Non-level installation which will cause condensate dripping.
... ascending sections of condensate drain piping.
These may only be used near the unit with a maximum height
difference of 200 mm from the top of the unit.
... horizontal sections or curves of condensate drain piping with less
than 2% slope.
... flattening or kinking the refrigerant pipes or condensate pipes.
...slack on electrical connections.
GB - 5
Page 7
42 GW
Installation
Max. 2 louvres closed
Heating: louvre position for
correct air flow.
Cooling: louvre position for
correct air flow.
• Install the unit as centrally as possible in the room, the air flow
direction can be controlled by manually regulating the louvres
position, according to the operating mode (cooling or heating): this
will ensure optimum distribution of the air in the room.
• During cooling mode operation the best position for the deflecting
louvres is one which allows air diffusion close to the ceiling
(Coanda effect). In heating mode, the louvres should be
positioned so that the air is directed towards the floor, in order to
prevent layers of hot air forming in the upper part of the room.
• In order to allow easy and rapid installation and maintenance,
make sure that in the selected position it is possible to remove
the ceiling panels or, if the ceiling is constructed of masonry,
that access to the unit is guaranteed.
ATTENTION:
Only restrict the air outlets as indicated in the drawing.
Prior to installation
Warning: To close one or two air outlets use the special kit
If plaster board ceiling panels are installed the maximum
dimensions of the unit housing must not exceed 660 x 660 mm
(mod. 004 - 008 - 010) and 900 x 900 mm (mod. 012 - 016 - 020).
In rooms with high humidity, brackets should be insulated by self
adhesive insulation supplied.
Installation
Mark the position of the hangers, connection lines and condensate
drain pipe, power supply cables and remote control cable (see
dimensions); the cardboard template (supplied with the kit) may
be of assistance for this operation. Depending on the type of
ceiling the hangers can be fixed as shown in the drawing.
It is advisable to place the unit as close as possible to the installation site
before removing it from the packaging. The grille panel and the control
are separately packed for maximum protection.
IMPORTANT:
Do not lift the unit by the condensate drain discharge pipe;
hold it by its four corners only.
Unit installation will be facilitated using a stacker.
Once the threaded hangers have been positioned, do not tighten
the nuts, and insert the washers as shown in the drawing.
Page 8
42 GW
Installation
Threaded hangers
"T" bar
First position the connection lines , as described in the chapter
"Water connections".
Remove the "T" bar in order to facilitate installation operations.
(to be removed)
ENGLISH
Condensate drain pipe
2%
50
Suspension brackets
Carefully lift the unit (without the frame) using the four
suspension brackets (or the four corners), inserting it into the
false ceiling.
If the "T" bar cannot be removed the unit may need to be tilted
(this operation may only be carried out with false ceilings with a
minimum height of 300 mm).
mm
• To ensure correct condensate water flow, the drain pipe should
have a gradient of 2% without obstructions. Furthermore an
odour trap of at least 50 mm depth should be made to prevent
unpleasant odours from reaching the room.
False ceiling
Spirit level
Align and level the unit by adjusting the nuts and locknuts on
the threaded hangers, maintaining a distance of 25 -30 mm
between the sheet metal body and the underside of the false
ceiling.
Reposition the "T" bar and align the unit in relation to the bar by
tightening the nuts and locknuts.
After connection of the condensate drain line and the refrigerant
lines, carry out a final check to make sure that the unit is level.
• Condensate may be discharged at a maximum height of 200 mm
above the unit, as long as the ascending tube is vertical and
aligned with the drainage flange.
• If it is necessary to discharge the condensate from a level
above 200 mm, install an auxiliary water discharge pump and
float valve.
A float valve is recommended to stop the flow switch if there is
a fault at the auxiliary pump.
• The condensate pipe must be insulated with a condensationproof material such as polyurethane, propylene or neoprene of
5 to 10 mm thickness.
• If more than one unit is installed in the room, the drain system can
be made as shown in the drawing.
GB - 7
Page 9
42 GW
Installation
Frame pre-hooking support
Safety belt
Frame fixing screw
Installation of grille/frame assembly
Carefully unpack the assembly and check for damage sustained in
transit. Attach the assembly to the unit by using the two hooks.
Use the screws supplied to fix the frame in position.
A. Gasket "A"
B. Gasket "B"
A B
Air discharge
Ensure that the frame is not distorted by excessive tightening,
that it is aligned with the false ceiling and above all that there is
a seal between the air inlet and outlet.
In the drawing gasket "A" prevents return air from mixing with
the supply air and gasket "B" prevents the supply air from
leaking into the ceiling void.
On completion, the gap between the unit frame and the false
ceiling must not be more than 5 mm.
W ater connections
Water connections are fixed to the unit body to avoid damage
when pipes are connected; it is advisable to tighten the
connection with a spanner.
The upper coil connection is supplied with an air purge valve,
the lower connection with a water purge valve, suitable for a
10 mm wrench or screw-driver.
(The coil is only partially drainable; it it is advisable to
blow air into the coil for complete drainage).
ModelsConnections
0043/4"
0083/4"
0103/4"
004
010
dimension (Ø)
*
*
1/2"
1/2"
ModelsConnections
0121"
0161"
0201"
020
Hot water circuits, four-pipe version
*
dimension (Ø)
*
3/4"
It is necessary, when the installation is made, to insulate the
valve and the connection pipes with anti-condensate material
of polyethylene type or expanded neoprene.
Checking
Before unit operation pour a quantity of water into the external
auxiliary drain pan. Verify that the water flows into the internal
condensate drain pan and that the pump regularly drains the
liquid.
Otherwise check the pipe slope and look for possible
obstructions. Water connections are fixed to the unit body to
avoid damage when pipes are connected; it is advisable to
tighten the connection with a spanner.
Water inlet
Water outlet
Air purge valve
Water purge valve
GB - 8
Page 10
42 GW
Motorized valve and control
• The unit control circuit only allows opening of the motorized
valve when the fan motor is working.
(See wiring diagrams)
• When the thermostat asks for cooling, terminal 1 of TB3 (cold
water) is supplied with 230V.
When it asks for heating, terminal 2 of TB3 (hot water or
electric heater) is supplied with 230V.
• The control circuit ensures that the condensate discharge
pump works continuously while the thermostat, asking for
cooling, keeps the cold water regulating valve open.
WARNING :
The valve is not only necessary to control the room
temperature, but also to stop the cold water flow to the coil
in case of an abnormal condensing water level rise in the
drain pan.
• If there is an abnormal condensing water rise in the drain pan
(for example: possible defective drain, pump malfunction, fan
motor not working) causing the opening of the float switch
contact (FS), the control circuit either operates the c
ondensate drain pump, or at the same time closes the
regulating valve, stopping the cold water flow towards the
coil and avoiding further condensation.
Control
The water flow has to be controlled:
• by installing the motorized thermo-electric valves supplied
as accessory
or
• by installing motorized field supplied valves.
Motorized thermo-electric valve assembly and components
AB
C
F
G
E
Water inlet Water outlet
004012004020
Mod. 42GW008016010
010020
2-pipe4-pipe
Ref. Descriptionq.tyq.tyq.tyq.ty
AAdaptor 3/4 " gas with O-ring2
Adaptor 1" gas with O-ring +2+
Adaptor 3/4" gas with O-ring +
BSelf tapping screw3333
CClip3333
DValve 1" gas pre-assembled1
Valve 1" gas pre-assembled +1+
Valve 3/4" gas pre-assembled1
D1 Valve 3/4" gas pre-assembled1
Instructions for mounting of motorized
thermo-electric valve assembly
(see "Components" table)
• The thermo-electric valve must be mounted on the unit after
the unit installation.
For this operation follow figures, depending on model.
• Insert the clips supplied in the unit side slots.
Assembly
For models 42GWD (4-pipe), the valve assembly for the
cold water coil must be installed first.
•Gently grease the O-rings before fitting them into their
seats.
Sizes 004 - 008 - 010
Sizes 012 - 016 - 020
• Connect the valve assemble to the coil and fix it by a 30Nm
torque.
• Insulate the valve assembly.
• For 4-pipe hot water coil, repeat all the operations with gas
adaptors, as per the table.
• Pass cables through the cable holder G and fix them to the
case using the already pre-assembled screws.
• Mount the drain pan below the valve assembly, inserting the
discharge pipe into the special hole; align and fix it to the 3
clips previously assembled using the three screws supplied.
• Insulate the 3 screws and the drain pan lower part using the
insulating material F.
• To connect the steel pipes to the system, ensure they are
aligned and supported to avoid excess strain on the unit. If
the system is filled with water, check all fitting seals.
NOTE:
The seal efficiency of the valve assembly is factory tested.
Any system losses are therefore due to an incorrect
installation.
Electric connections
• To connect valves to the electric panel pass cables through
the electric panel grommet and connect them to the terminal
board TB3 as per the wiring diagrams.
Ring nut
O-ring
Coil coupling
See diagram supplied with
the kit..
Adaptor
O-ring
Coil coupling
Fit the reducers and O-rings
towards the coil connection.
GB - 9
Page 11
42 GW
Motorized valve and control
Automatic operation position
Thermo-electric valve
head
Valve body
004 - 008 - 010
012 - 016 - 020
Operation of the thermo-electric valve
• This 3-way valve is an ON-OFF type with a very slow stroke.
It is not a modulating valve so it has no PTC.
This valve is driven, as a sensible element, by the ambient
thermostat of the “cassette” unit.
• The thermo-electric valve is normally closed towards the coil
and open towards the bypass.
When the room temperature does not satisfy the thermostat,
an electric heater activates the heating of a thermostatic
element which causes the down-stroke of the piston; the
valve opens after about 3 minutes about to allow water to
circulate in the coil.
• If the room temperature satisfies the thermostat or if the
electric power has been switched off, the valve is closed after
about 3 minutes towards the coil and is opened towards the
bypass.
• If an emergency occurs, the valve may be manually opened,
removing the electric head, unscrewing the ring nut.
ON-OFF valves (230V)
• In this case the cold water valve must be controlled by the ONOFF signal from terminal 1 of TB3 and the hot water valve from
terminal 2 of TB3.
ON-OFF valves with other voltages than 230V
• If a room control listed in the accessories table is used, follow
the instructions in the previous paragraph and install two
230V relay at TB3 terminals 1, 2, 4 and 5 which will control
the valve opening.
230V valve connection or
230V valve relay connection
C
H
H Heating valve or heating valve relay
C Cooling valve or cooling valve relay
• If a low voltage control is used or if the control is not listed in
the accessories table, the connections must be made on the
unit terminal board.
When the emergency ends, remember to reset the valve to
automatic operation, repositioning the electric head;
failure to do this can result in condensate formation due
the water pipes, even if the unit is switched off.
Instructions for field supplied valves
Water connection
• Install valves following manufacturer's instructions; refer to the
relevant figures for connection to the unit.
• Carefully insulate pipes, valve assemblies and coil connections
(cold water side) to avoid condensation forming on the pipes
and dripping on the false ceiling.
Electrical wiring
• Connect the room control following instructions for the control
used.
WARNING:
Pass cables through the control panel cable-conduit.
• Connect valves as per the following instructions, using the
wiring diagram in this chapter.
• Valves, closing the unit water inlet when there is no
power supply, must be used.
Control connection
Fan speed
H = high speed
M = medium speed
L = low speed
Heat
Cool
GB - 10
Page 12
42 GW
Motorized valve and control
• If these connections are not made as described the drain
pan condensate may overflow.
• Valves should only open when the fan motor is working, i.e.
when one of TB1 terminals 1 or 2 or 3 is supplied from TB1
terminal 4.
• The optional electric heater (mod. 42GWE) which can only be
factory installed, must only be energized when the fan is
working.
• The optional electric heater which must be factory installed on
model 42GWE, works only if TB1 terminals 5-6 are supplied
from TB1 terminal 4.
Electrical connections
We recommend to remove the main board from the electric
panelboard for better access to electric connections.
ST ANDARD version unit - Control panel
ENGLISH
• The water discharge pump should work every time the
cold water valve is opened, supplying TB1 terminal 7 and
8 from TB1 terminal 4.
• When the system is filled with water, verify all couplings
for tightness.
• The manufacturer does not accept responsibility for the
tightness of the field - installed valve assembly and this
is not tested in the factory. He declines any responsibility
for non functioning of these assemblies and for damage
due to dripping.
Holes for panel fixing screws
Auxiliary board (accessory)
CV
Fan connector
Float connector
CG
CP
Pump connector
A. Electric heater supply connection
B. Unit power supply connection
C. Polarised connector
GB - 11
Page 13
42 GW
Electrical connections
The control panel can be reached by opening the grille and
removing the metal covers using the 3 or 4 screws.
IMPORTANT for units with electric heaters;
The unit is equipped with two thermostats: one with automatic
reset and one with manual (electric) reset that can be
reactivated by switching the power supply off and then on.
IMPORTANT:
• Make ground connection prior to any other electrical
connections.
• If the unit is fitted with an electric heater, this must have a
separate power supply.
Ensure that the mains supply connection is made through a
switch that disconnects all poles, with a contact gap of at least 3
mm.
• Fix the power cable of the electric resistance heaters under the
single cable clamp. Make certain that the YELLOW/GREEN
cable is stripped back further than the others.
Connect the power cables to terminal box connectors in
accordance with the wiring diagram and tighten firmly.
Wiring diagram legend
Factory wiring
Field wiring
Connector
Terminal on terminals
Normally closed contact
Normally open contact
Capacitor
FC Fan capacitor
FS Safety switch float
IFM Fan motor indoor unit
PR Drain pump relay
PS Drain pump
C1-3 Connectors
HR Heating relay
CR Cooling relay
CEV Electric valve (cooling)
HEV Electric valve (heating)
PCB Relay board
HTR Electric heater
ST Safety thermostat
T Timer
TB Terminal board
Low speed
Medium speed
High speed
Power supply line
Heating selection
Common thermostat (heating)
Cooling selection
Common thermostat (cooling)
Neutral fan
Neutral in
Neutral out
Neutral
Heating out
Cooling out
Model004-008-010 012-016-020
Ø A mm150150
B mm120120
Ø Cmm70100
Insulated flexible duct
Fresh air intake
Conditioned air supply to an
adjacent room
Polystyrene partition
Baffle
Frame
• Side knockouts allow connection of fresh air inlet ducts and ducts
to deliver conditioned air to an adjacent room.
• Remove the external prepunched anti-condensate insulation and
take away the knockout panels using a punch.
Air distribution to adjacent room
With a pencil, trace a line on the polystyrene around the inside
edges of the panel that was previously removed.
Cut away the polystyrene with a knife, taking care not to damage
the heat exchange coil.
Fresh air intake
Remove the polystyrene partition.
Introduce the baffle supplied after the frame has been hooked as
per above figure (ref. ).
Following that tighten the assembly frame/grille using the 4 screws.
• Use locally purchased material, suitable for operating
temperatures of 60 °C (continuous).
Conduits can be of flexible polyester (with spiral core) or
corrugated aluminium, externally covered with anti-condensate
material (fibre glass of 12 +/- 25 mm thickness).
• To complete the installation, all non-insulated ducts must be
covered with anti-condensate insulation (ex. expanded neoprene,
6 mm thickness).
If these instructions are not observed, condensate may drip;
the manufacturer will not be held responsible for any damage
caused.
• The two prepunched side knockouts must not be used at the
same time to deliver conditioned air to an adjacent room.
• The return and supply duct lengths can be calculated in
accordance with the "air distribution to an adjacent room" and
"fresh air renewal" diagrams (also taking into account the
pressure drop through air diffusers, grilles and fresh air filters),
as well as the increase in noise caused by these ducts.
GB - 14
Page 16
42 GW
30
20
10
0
0
100
200
300400
010/012
004
008
410
020
016
40
Fresh air renewal and conditioned air supply to an adjacent room
Fresh air renewal
• The optional supplementary fan for fresh air intake (field
supplied) has to be connected to terminal block as per
diagrams enclosed.
Fan motor operation is parallel to the thermo-electric control
valve, and the motor stops when the valve shuts off.
• For winter operation with fresh air intake, an anti-freeze
thermostat set at 2°C is recommended, with the bulb placed
on the water outlet pipe, before the supplementary fan.
• The fresh air flow must be less than 10% of the total air flow,
to avoid operating problems or eccessive noise.
For higher air flow a "primary air kit" is available which uses
the prepunched hole for air ducting to an adjacent room and a
baffle so that the fresh air is introduced into the room through
Conditioned air supply to an adjacent room
• Air supply to an adjacent room requires that the outlet
corresponding with the duct is closed, using the air
supply outlet obstruction kit supplied.
The kit cannot be used in units equipped with electric
heater (mod. 42GWE).
An air inlet grille must be fitted (if possible near the floor)
between the air conditioned room (where the unit is situated)
and the adjacent room or, alternatively, the door must be
undercut, as shown in the drawing.
• The duct lengths can be calculated in accordance with the “air
distribution to an adjacent room” diagram, also taking into
account the pressure drop through air diffusers and fresh air
filters.
ENGLISH
a diffuser.
• DO NOT use active carbon or electrostatic filter kits for
• Install an air inlet grille with filter inspection port to prevent
ducts towards adjacent rooms.
dust and dirt from entering and fouling the unit heat
exchanger.
Filter installation also makes the installation of a duct closing
damper during shut-down periods unnecessary.
Winter operation diagram with
fresh air intake
230V ~ 60Hz
TB2
L
N
Diagram of conditioned air supply to an
adjacent room: one louvre closed
Available static pressure - Pa
Air flow m3/h
TB3
5
4
3
2
1
Terminal board
Antifreeze thermostat
Speed controller
Fresh air fan motor
Relay 230V
Supply air duct to adjacent room
In case of two louvres closed, the fresh air flow towards the
adjacent room is 50% higher compared with only one louvre
closed (with equal static external pressure)
GB - 15
Page 17
42 GW
Maintenance and owner's guide
Maintenance
Cleaning and maintenance operations must be carried out by
specially trained personnel.
Before performing any service or maintenance operations,
turn OFF the main power switch.
To open the unit grille:
Turn the two screws through 90° (1/4 turn).
Filter cleaning
Clean filters in accordance with the actual operating
conditions and times (approximately every 6 months).
• The acrylic air filter is washable in water.
Electrostatic and active carbon filters (which can be used on
the unit) are not washable but must be replaced.
Additional maintenance
• The electric panel is easily accessible by removing the cover
panel.
The inspection or replacement of internal components such as:
fan motor, coil, condensate discharge pump, float switch, electric
heater (if fitted), involve the removal of the condensate drain pan.
Condensate drain pan removal
• During the removal operation of the condensate drain pan
protect the floor with a plastic sheet under the unit.
• Remove the frame-grille assembly by loosening the screws;
drain the condensate water contained in the drain pan into
a bucket of at least 10 litres capacity, using the special
drain with a rubber plug.
• Remove the electrical panel cover and disconnect the electric
connections, connectors C
ground wire (see drawing in “electrical connections”
section).
V, CG, CP and the yellow-green
Extract the filter.
Acrylic fibre
First vacuum clean the filter, then wash under tap water and
finally dry.
Replace the filter in the correct position.
Prolonged shutdown:
• Remove the four fixing screws on the side of the drain pan and
carefully remove the condensate drain pan.
Guide for the owner
When installation and tests are completed instruct the Owner on the
main operating modes of the air conditioner, such as:
• Turning the unit ON and OFF.
• Changing the operation modes.
• Temperature selection.
Leave the installation manual with the owner for future use during maintenance operations or for any other needs.
• Before starting the air conditioner:
- clean or replace the unit air filters.
- check and clean the drain pan and the condensate discharge of
the unit
- check tightness of electric connections.
GB - 16
Page 18
L010122H22 - 0405
Via R. Sanzio, 9 - 20058 Villasanta (MI) Italy - Tel. 039/3636.1
The manufacturer reserves the right to change any product specifications without notice.
Order No. 14207-74M10, April 2005. Supersedes Order No. 14207-74M10, December 2004. Printed in Italy
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.