Carrier 42EQV user guide manual

INSTALLATION MANUAL
AIR CONDITIONER (SPLIT TYPE)
ENGLISH
Indoor unit 42EQV025M, 035M
Outdoor unit 38EYV025M, 035M
1115551125
CONTENTS
EN GR
ΠΕΡΙΕXOΜΕΝΑ
PRECAUTIONS FOR SAFETY ............................................. 1
INSTALLATION DIAGRAM OF INDOOR AND
OUTDOOR UNITS ................................................................ 2
Optional Installation Parts .................................................. 2
INDOOR UNIT .......................................................................
Installation Place................................................................ 3
Cutting a Hole and Mounting Installation Plate .................. 3
Electrical Work ................................................................... 3
Wiring Connection ............................................................. 4
How to Connect Remote Controller for Wire Operation..... 4
Piping and Drain Hose Installation .................................... 5
Indoor Unit Fixing............................................................... 6
Drainage ............................................................................ 6
OUTDOOR UNIT ...................................................................
Installation Place................................................................ 6
Precautions about Installation in Regions with Snowfall
and Cold
Temperatures ..................................................... 6
Refrigerant Piping Connection ........................................... 7
Evacuating ........................................................................ 7
Wiring Connection ............................................................. 8
OTHERS ................................................................................ 8
Gas Leak Test .................................................................... 8
Remote Control A-B Selection ........................................... 8
Test Operation .................................................................. 8
Auto Restart Setting .......................................................... 8
ΠΡOΦΥΛΑΞΕΙΣ ΑΣΦΑΛΕΙΑΣ ................................................ 1
ΔΙΆΓΡΑΜΜΑ ΕΓΚΑΤΆΣΤΑΣΗΣ ΤΗΣ ΕΣΩΤΕΡΙΚΉΣ ΚΑΙ
ΕΞΩΤΕΡΙΚΉΣ ΜOΝΆΔΑΣ ................................................... 2
Προαιρετικά Eξαρτήματα Eγκατάστασης ......................... 2
3
ΕΣΩΤΕΡΙΚΉ ΜOΝΆΔΑ ........................................................ 3
Σημείο Eγκατάστασης ....................................................... 3
Κψιμο Τρύπας και Τοποθέτηση Πλάτης Εγκατάστασης ... 3
Ηλεκτρικές Εργασίες ........................................................ 3
Σύνδεση Καλωδίωσης ....................................................... 4
Σύνδεση τoυ τηλεχειριστηρίoυ για την Ενσύρματη λειτουργία
Εγκατάσταση Σωλήνωσης και Eύκαμπτου Σωλήνα
Aποστράγγισης
.................................................................. 5
Στερέωση Εσωτερικής Μoνάδας ...................................... 6
Απoστράγγιση .................................................................... 6
6
ΕΞΩΤΕΡΙΚΉ ΜOΝΆΔΑ ........................................................ 6
Σημείo Εγκατάστασης ....................................................... 6
Πρoφυλάξεις σχετικά με την εγκατάσταση σε
περιoχές με χιoνπτωση και χαμηλές θερμoκρασίες
Σύνδεση Ψυκτικών Σωληνώσεων ...................................... 7
Εκκένωση .......................................................................... 7
Σύνδεση Καλωδίωσης ....................................................... 8
ΛOΙΠΑ ................................................................................... 8
Έλεγχoς Διαρρoής Αερίoυ ................................................ 8
Επιλογή Α-Β τoυ τηλεχειριστηρίoυ ................................... 8
Δoκιμή Λειτoυργίας ........................................................... 8
Auto Restart Ρύθμιση ....................................................... 8
.. 4
....... 6
PRECAUTIONS FOR SAFETY
PRECAUTIONS FOR SAFETY
• Before installation, please read these precautions for safety carefully.
• Be sure to follow the precautions provided here to avoid safety risks. The symbols and their meanings are shown below.
WARNING : It indicates that incorrect use of this unit may cause severe injury or death. CAUTION : It indicates that incorrect use of this unit may cause personal injury (*1), or property damage (*2).
*1: Personal injury means a slight accident, burn, or electrical shock which does not require admission or repeated hospital treatment. *2: Property damage means greater damage which affects assets or resources.
For general public use
Power supply cord and connecting cable of appliance use shall be at least polychloroprene sheathed fl exible cord (design H07RN-F) or cord designation 60245 IEC66. (Shall be installed in accordance with national wiring regulations.)
EN
CAUTION
New refrigerant air conditioner installation
THIS AIR CONDITIONER USES THE NEW HFC REFRIGERANT (R410A), WHICH DOES NOT DESTROY THE OZONE LAYER.
R410A refrigerant is apt to be affected by impurities such as water, oxidizing membranes, and oils because the pressure of R410A refrigerant is approx.
1.6 times of refrigerant R22. As well as the adoption of this new refrigerant, refrigerating machine oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating machine oil does not enter the refrigeration cycle of a new-refrigerant air conditioner.
To avoid mixing refrigerant and refrigerating machine oil, the sizes of charging port connecting sections on the main unit are different from those for the
conventional refrigerant, and different size tools are also required. For connecting pipes, use new and clean piping materials with high pressure withstand capabilities, designed for R410A only, and ensure that water or dust does not enter. Moreover, do not use any existing piping as its pressure withstand may be insuffi cient and may contain impurities.
DANGER
• FOR USE BY QUALIFIED PERSONS ONLY.
• TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
• CONNECT THE CONNECT NG CABLE CORRECTLY. IF THE CONNECT NG CABLE IS CONNECTED WRONGLY, ELECTRIC PARTS MAY BE DAMAGED.
• CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
• TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEATERS, FURNACE, STOVES, ETC.
• WHEN MOVING THE AIR CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT (R410A) WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS.
• IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS IS HEATED BY FIRE OR SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.
WARNING
• Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock switches.
• Do not install in a place which cannot bear the weight of the unit.
Personal injury and property damage can result if the unit falls.
• Before doing the electrical work, attach an approved plug to the power supply cord.
Also, make sure the equipment is properly earthed.
• Appliance shall be installed in accordance with national wiring regulations.
If you detect any damage, do not install the unit. Contact your dealer immediately.
• Do not use any refrigerant different from the one specifi ed for complement or replacement.
Otherwise, abnormally high pressure may be generated in the refrigeration cycle, which may result in a failure or explosion of the product or an injury to
your body.
CAUTION
• Exposure of unit to water or other moisture before installation could result in electric shock.
Do not store it in a wet basement or expose to rain or water.
• After unpacking the unit, examine it carefully for possible damage.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify the noise level of the unit or where noise and discharged air might disturb neighbors.
• To avoid personal injury, be careful when handling parts with sharp edges.
• Please read this installation manual carefully before installing the unit. It contains further important instructions for proper installation.
• The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual.
REQUIREMENT OF REPORT TO THE LOCAL POWER SUPPLIER
Please make absolutely sure that the installation of this appliance is reported to the local power supplier before installation. If you experience any problems or if the installation is not accepted by the supplier, the service agency will take adequate countermeasures.
1
INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS
INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS
For the rear left and left piping
170 mm or more
Air fi lter
(Attach to the front panel.)
Filter
5
Filter
6
(
Battery cover
&
Flat head wood crew
The provided Remote Controller is a wireless type, which also can be used as a wire. Please see “How to Connect The Remote Controller for Wired Operation”, in case of wired control is required.
38EYV025M 38EYV035M
600 600
C
D 400 600
E 45 100
F 100 100
Remark :
• Detail of accessory and installation parts can see in the accessory sheet.
• Some pictures might be different from the actual parts.
8
Flat head wood crew
3
Batterie
F mm or more
8
Flat head wood crew
2
Wirele remote control
D mm or more
65 mm or more
Hook
Remote control
4
holder
Vinyl tape Apply after carrying out a drainage te t.
C mm or more
E mm or more
Hook
1
170 mm or more
Shield pipe
Saddle
Exten ion drain ho e (Not available, provided by in taller)
C mm or more
In tallation plate
Wall
Insert the cushion between the indoor unit and wall, and tilt the indoor unit for better operation.
Do not allow the drain hose to get slack.
Cut the piping hole sloped slightly.
Make sure to run the drain hose sloped downward.
The auxiliary piping can be connected to the left, rear left, rear right, right, bottom right or bottom left.
Right
Rear right
Bottom right
Rear left
Left
Bottom left
Insulate the refrigerant pipes separately with insulation, not together.
6 mm thick heat resisting polyethylene foam
Optional Installation Parts
Part
code
Refrigerant piping Liquid side : Ø6.35 mm
A
Gas side : Ø9.52 mm
Pipe insulating material
B
(polyethylene foam, 6 mm thick)
Putty, PVC tapes
C
Parts name Q’ty
One
each
1
One
each
Fixing bolt arrangement of outdoor unit
• Secure the outdoor unit with fi xing bolts and nuts if the unit is likely to be exposed to a strong wind.
• Use Ø8 mm or Ø10 mm anchor bolts and nuts.
• If it is necessary to drain the defrost water, attach drain nipple 9 and cap water proof ! to the bottom plate of the outdoor unit before installing it.
108 mm
28 mm
86 mm
320 mm
Air outlet
600 mm
280 mm
500 mm
Air inlet
97 mm
Ø25 mm
53 mm
Air outlet
38EYV025M 38EYV035M
Drain outlet
2
125 mm
Air inlet
Ø25 mm
102 mm
90 mm
Drain outlet
INDOOR UNIT
INDOOR UNIT
Installation Place
• A place which provides the spaces around the indoor unit as shown in the diagram.
• A place where there are no obstacles near the air inlet and outlet.
• A place which allows easy installation of the piping to the outdoor unit.
• A place which allows the front panel to be opened.
• The indoor unit shall be installed as top of the indoor unit comes to at least 2 m height. Also, it must be avoided to put anything on the top of the indoor unit.
CAUTION
• Direct sunlight to the indoor unit’s wireless receiver should be avoided.
• The microprocessor in the indoor unit should not be too close to RF
noise sources.
(For details, see the owner’s manual.)
Remote control
• A place where there are no obstacles such as a curtain that may block the signal from the indoor unit.
• Do not install the remote control in a place exposed to direct sunlight or close to a heating source such as a stove.
• Keep the remote control at least 1 m apart from the nearest TV set or stereo equipment. (This is necessary to prevent image disturbances or noise interference.)
• The location of the remote control should be determined as shown below.
(Side view) (Top view)
Indoor unit
57 °
Reception range
Remote control
Indoor unit
Reception range
54 °
45°
Remote control
When the installation plate is directly mounted on the wall
1. Securely fi t the installation plate onto the wall by screwing it in the upper and lower parts to hook up the indoor unit.
2. To mount the installation plate on a concrete wall with anchor bolts, use the anchor bolt holes as illustrated in the below fi gure.
3. Install the installation plate horizontally in the wall.
CAUTION
When installing the installation plate with a mounting screw, do not use the anchor bolt holes. Otherwise, the unit may fall down and result in personal injury and property damage.
In tallation plate (Keep horizontal direction.)
Anchor bolt
Projection
5 mm dia. hole
Clip anchor (local part )
7
Mounting crew Ø4 x 25R
15 mm or le
CAUTION
Failure to fi rmly install the unit may result in personal injury and property damage if the unit falls.
• In case of block, brick, concrete or similar type walls, make 5 mm dia. holes
in the wall.
• Insert clip anchors for appropriate mounting screws 7.
EN
Cutting a Hole and Mounting
Installation Plate
Cutting a hole
When installing the refrigerant pipes from the rear
80 100 180
Pipe hole
65 mm
The center of the pipe hole is above the arrow.
1. After determining the pipe hole position on the mounting plate (¨), drill the
pipe hole (Ø65 mm) at a slight downward slant to the outdoor side.
NOTE
• When drilling a wall that contains a metal lath, wire lath or metal plate, be sure to use a pipe hole brim ring sold separately.
Mounting the installation plate
Anchor bolt holes
Hook
100 mm
62
82.5
NOTE
• Secure four corners and lower parts of the installation plate with 4 to 6 mounting screws to install it.
Electrical Work
1. The supply voltage must be the same as the rated voltage of the air
conditioner.
2. Prepare the power source for exclusive use with the air conditioner.
NOTE
• Wire type : More than H07RN-F or 60245 IEC66 (1.5 mm² or more)
CAUTION
• This appliance can be connected to the mains in either of the following
two ways. (1) Connection to fi xed wiring: A switch or circuit breaker which disconnects all poles and has a
contact separation of at least 3 mm must be incorporated in the fi xed
wiring. An approved circuit breaker or switches must be used. (2) Connection with power supply plug: Attach power supply plug with power cord and plug it into wall outlet.
An approved power supply cord and plug must be used.
NOTE
• Perform wiring works so as to allow a general wiring capacity.
170
85
Pipe hole
Indoor unit
Hook
Thread
Weight
Hook
Pipe hole
Mounting screw
7
1
Installation plate
2 m or more from fl oor
3
Wiring Connection
How to connect the connecting cable
Wiring of the connecting cable can be carried out without removing the front panel.
1. Remove the air inlet grille. Open the air inlet grille upward and pull it toward you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (according to the local cords) into the pipe hole on the wall.
4. Take out the connecting cable through the cable slot on the rear panel show as fi gure below.
5. Insert the connecting cable fully into the terminal block and secure it tightly with screws.
6. Tighten fi rmly but not over 1.2 N·m (0.12 kgf·m)
7. Secure the connecting cable with the cord clamp.
8. Fix the terminal cover, rear plate bushing and air inlet grille on the indoor unit.
CAUTION
• Be sure to refer to the wiring system diagram labeled inside the front panel.
• Check local electrical cords and also any specifi c wiring instructions or limitations.
Connecting cable
Terminal block
about 20 cm
Cord clamp
7. Set the control wire throughout at slot on front cover of Display unit then
reassembly Display with main casing by reverse process of fi gure 2 and 3. Make sure the control wire must not be pressed by front and rear cover of Display unit.
8. Set the control wire out from indoor unit same portion as power supply
and connecting cable as shown on fi gure 6.
9. Reassembly the indoor unit by reverse process of 1 to 3.
Air inlet grille
1
Front panel
23
Di play unit
* Wire ize 28-22AWG
or 0.08-0.32 mm
Outer diameter not over 4.7 mm,
control wire length 30 m. or le .
2
70 mm
5 mm
Di play board
4
Notch for wire out
Screw
Terminal cover
Screw
100 mm
10 mm
10 mm
Stripping length of the connecting cable
90 mm
Earth line
NOTE
• Use stranded wire only.
• Wire type : More than H07RN-F or 60245 IEC66 (1.5 mm² or more)
How to Connect Remote Controller
for Wire Operation
Indoor unit
Control wire
Remote controller
65
Tighten fi rmly but not over 0.12 N·m (0.01 kgf·m)
Terminal
Control wire
Control wire
For remote controller
1. Remove cover of remote controller by sliding down and take it out.
2. If batteries are exist, please take them out. The combination of using wire controller and batteries may cause of batteries explosion.
3. Make hole for insert control wire by use screwdriver break the polyester sheet as shown on fi gure 7.
4. Insert control wire from rear side of remote controller as shown on gure 8.
5. Fix control wire which arrange as shown on fi gure 9 and ! to terminal by provided screws (tighten fi rmly but not over 0.25 N·m (0.03 kgf·m)).
6. Set control wire through gutter way at rear side of remote controller as shown on fi gure ".
7. Fix provided screw (Ø3.1×16L) on the wall to hang remote controller as shown on fi gure #.
8. Mark and arrange hole for fi x below screw (Ø3.1×25L) as shown on gure #.
9. Assembly battery cover which provided with accessory bag then use provide screw (Ø3.1×25L) to fi x battery cover together with wall as shown on fi gure $ (tighten fi rmly but not over 0.15 N·m (0.02 kgf·m)).
10. Reassembly cover of remote controller.
For indoor unit
1. Open the air inlet grille upward.
2. Securely remove two screws at the front panel.
3. Slightly open the lower part of the front panel then pull the upper part of the front panel toward you to remove it from the rear plate as shown on gure 1.
4. After removing the front panel, remove the Display unit and open the cover as shown on fi gure 2 and 3.
5.
Arrange the control wire as detail and specifi cation as shown on fi gure
6. Securely connect the control wire to terminal of Display unit board as shown on fi gure 5 (tighten fi rmly but not over 0.12 N·m (0.01 kgf·m)).
4.
78
Polye ter heet clo e hole for in ert control wire
Control wire
4