Carrier 40QNQ, 40QNC User Manual

40QNC / 38HDF 40QNQ / 38QRF High---Wall Du ct Free Split System Sizes 018 to 036
Installation Instructions
40QNC, QNQ Unit
NOTE: Read the entire instruction manual before starting the
installation.
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury or equipment damage.
Puron refrigerant systems operate at higher pressures than standard R--22 systems. To avoid damage to the unit or possible personal injury, do not use R--22 service equipment or components on Puron refrigerant equipment.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and current editions of the National Electrical Code ( NEC ) NFPA 70. In Canada, refer to current editions of the Canadian electrical code CSA 22.1.
Recognize safety information. This is the safety--alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words; DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
WARNING
!
!
CAUTION
PERSONAL INJURY AND EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in personal injury and / or equipment damage.
DO NOT operate the unit without a filter or with grille removed.
DIMENSIONS -- INDOOR
A08433
Model Size
In. (mm)
18k 42.5 (1080) 11.6 (295) 7.9 (201) 31 (14.1) 24k 42.5 (1080) 11.6 (295) 7.9 (201) 31 (14.1) 30k 57.5 (1461) 13.4 (340) 9.5 (241) 51 (23.2) 36k 57.5 (1461) 13.4 (340) 9.5 (241) 51 (23.2)
DIMENSIONS -- OUTDOOR
(FIELD PROVIDED AND INSTALLED)
W
H
In. (mm)
D
In. (mm)
Operating Weight
lb (kg)
Fig. 1 -- 40QNC,QNQ Unit Dimensions
FEMALE SWEAT CONN.*
* Male flare connection for Heat Pumps
UNIT MODELS
38HDF
Unit Size
018 018
024,030 024 0.6
036 030,036 1.0
NOTE: Dimensions shown in feet-inches. Dimensions in ( ) are millimeters.
38QRF
Unit Size
CHASSIS
SIZE
(Reference)
0
ABCD EF G H J KL NP
1
2′-1
/8″ 3′-015/16″ 1′-29/16″ 1′-4″ 1′-117/16″ 1′-5
(638.2) (938.2) (369.9) (406.4) (595.3) (436.6) (435) (559.1) (330.2) (168.3) (285.8) (75) (152.4)
1
-7
/8″ 3′-015/16″ 1′-2
2 (790.6) (938.2) (369.9) (406.4) (595.3) (436.6) (587.4) (711.5) (355.6) (171.5) (295.3) (75) (152.4)
3
3-1
/16″ 3′-89/16″ 1′-51/16″1′-67/16″ 2′-61/
(944.6) (1131.9) (433.4) (468.3) (774.7) (498.5) (741) (865.5) (347.7) (206.4) (403.2) (88) (165.4)
UNIT SIZE
38HDF
38QRF
3
1
1′-5
1-10″1′-1″ 0′
/
16
8
″1-111/8″2′-4 1′-2″0′-63/
16
/8″ 2′-53/16″2′
-10
9
/
1′-41′
16
/
3
7
-11
/16″ 1
/
-5
5
1-7
2
Fig. 2 -- 38HDF, QRF Unit Dimensions
2
018
024
030
036
018
024
030
036
1
″1′-111/16″ 0
/
16
M OPERATING W T
in. mm lb kg
5
/815.88 166 75.3
5
/815.88 176 79.8
3
/419.05 187 84.8
3
/419.05 250 113.4
5
/815.88 166 75.3
5
/815.88 176 79.8
3
/419.05 187 84.8
3
/419.05 232 105.2
5
1
/8″0′-11
-6
-8
/4″0′-215/
16
5
/8″ 0
15
-2
/16″0-6
0-11
4
1
/8″1-37/8″ 0′-37/16″ 0′-61/
0-6
2
A08434
CLEARANCES -- INDOOR
4in.
min.
4in.
min.
80 in.
min.
CLEARANCES -- OUTDOOR
A
8in.
min.
A08357
Fig. 3 -- 40QNC,QNQ Unit Clearances
Air-outlet
D
B
UNIT Coil Facing Wall --- in. (mm )
A 24 (610) B 36 (914) C 36 (914) D 6 (152) E 6 (152)
Fig. 4 -- Outdoor Unit Clearance
E
C
Air-inlet
A08436
Fan Facing Wall --- in. (mm)
24 (610) 36 (914)
8 (203) 8 (203)
36 (914)
3
These installation instructions cover the installation of the matched systems listed in table 2.
Parts List
Indoor Unit
The following items are included with the indoor unit:
Table 1 – Installation Materials
Description Qty Usage
Wall Mounting Bracket
Screws, 4XL10 2
Screws, 5XL25 5/14*
Remote Control 1 For Controlling Unit Remote Control
Holder
* 5 screws for unit sizes 18 a nd 24. 14 screws for unit sizes 30 and 36.
Outdoor Unit
The following items are included with the outdoor unit:
1 For Indoor Unit Installation
For Attaching The Remote Control Holder To The Wall
For Attaching The Mounting Bracket To The Wall
1 Holder For Remote C ontrol
38HDF018-036
A09499
Fig. 5 -- 38HDF018--036
SYSTEM REQUIREMENTS
Clearances
Allow sufficient space around the indoor and outdoor unit for proper airflow circulation and servicing. Refer to Fig. 3 and Fig. 4 for minimum required clearances.
Piping: Piping and insulation is field supplied.
Piping Lengths
The minimum length between the indoor and outdoor units is 10 ft (3 m). Refer to table 3 for the maximum lengths allowed.
Table 3 – Maximum Refrigerant LineLengths
Unit Size
18K 200 ( 61) 65 (19.8) 200 (61) 24K 200 ( 61) 65 (19.8) 200 (61) 30K 200 ( 61) 65 (19.8) 200 (61) 36K 200 ( 61) 65 (19.8) 200 (61)
Note: For lengths greater than 25 ft (7.6 m), refer to the Duct Free Long
Pipe Sizes
Refer to table 4 for pipe sizes.
Note: Both lin es need to be insulated using at least 1/2 inch closed foam
Max Line
Length ft(m)
Line Guide.
Max Elevation (ID
over OD) ft(m)
Max Elevation (OD
over OD) ft(m)
Table4–PipeSizes
Unit Size M i x P h a s e --- i n Vapo r --- i n
18K 3/8 5/8 24K 3/8 5/8 30K 3/8 3/4 36K 3/8 3/4
insulation.
Pipe Sizes (in)
Fig. 6 -- 38QRF018--036
Model Filter Drier
38HDF n n n n 38QRF n n (qty 2) n n (qty 3)
* Multiple pistons. Quantity varies with size.
Piston
Cap
Pistons*
Connector
Table 2 – Matched Systems
System
Ty pe
Cooling
Only
Heat
Pump
Nominal
Capacity
018 3 8 H D F 0 1 8 --- --- --- 3 40QNC018024--- --- --- 3 024 3 8 H D F 0 2 4 --- --- --- 3 40QNC018024--- --- --- 3 030 3 8 H D F 0 3 0 --- --- --- 3 4 0 QNC030 --- --- --- 3 036 38HDF036 ------ --- 3/5/6 4 0 QNC036 --- --- --- 3 018 3 8 Q R F 0 1 8 --- --- --- 3 40QN Q 0 1 8 --- --- --- 3 024 3 8 Q R F 0 2 4 --- --- --- 3 40QN Q 0 2 4 --- --- --- 3 030 3 8 Q R F 0 3 0 --- --- --- 3 40QN Q 0 3 0 --- --- --- 3 036 38QRF036--- --- ---3/5/6 4 0 Q N Q036 --- --- --- 3
Outdoor
Unit
Indoor
Unit
Condensate Drain Pipe Sizes
Refertotable5fortherequiredsizes.
Table 5 – Drain Pipe Sizes
Unit Size Outside Diameter --- in Inside Diameter --- in
18K 5/8 7/16 24K 5/8 7/16 30K 3/4 5/9 36K 3/4 5/9
Note: Do not trap condensate pipe.
A09500
Flare
4
Refrigerant Charge
The 38HDF and 38QRF units can be matched with multiple outdoor units and thus additional charge might be required when matched with the 40QNC or 40QNQ units.
Table 6 – Additional Charge
Unit Size 38HDF 38QRF
018 1.2 (0.55) 0.8 (0.36) 024 1.0 (0.45) 0.5 (0.23) 030 2.4 (1.1) 0
Note: The above additional charge is required amount for line lengths up to 25 ft (7.6 m). For line lengths exceeding 25 ft (7.6 m), additional charge will be required. Refer to the Duct Free Splits Long Line Guide.
036 0 0
Additional Charge lb (kg)
Metering Device
The metering device(s) for these systems is a type B Accurator installed with the outdoor unit. One Accurator is required for the cooling only system and two are required for the heat pump systems. The Accurators are supplied with the outdoor unit. However, since the same outdoor unit can be matched with multiple indoor units, the correct Accurator must be selected. Refer to Table 7 for the correct Accurator size.
Table 7 – Accurator Sizes
System Type Size
018 49 ---
Cooling Only
Heat Pumps
024 55 --­030 63 --­036 70 --­018 49 45 024 55 49 030 63 53 036 70 63
Cooling
Accurator
Heating
Accurator
Power and Connecting Cables -- Field Supplied
Power:
S The indoor and outdoor units require a dedicated power supply. S Consult local building codes, NEC (National Electric Code) or
CEC (Canadian Electric Code) for any special requirements.
S Use Table 8 for the electrical requirements for the outdoor units
and Table 9 for the indoor units to correctly size the cables and disconnect switches.
Control Wiring
Thermostat wires should be used for control wiring between the indoor and outdoor units. A two conductor cable is required for the cooling only units and a seven conductor cable is required on heat pumps. 18 AWG is recommended for any length up to 50 ft (15.2 m). 16 AWG is recommended for lengths between 50 and 200 ft (15.2 and 61.0 m).
User Interface
The indoor unit is supplied with a wireless remote control. The following accessories are also available
S Wall mounted control. Up to 6 units can be daisy chained and
controlled by one wired control.
S Zone manager capable of controlling up to 32 units divided up
to 8 different zones.
Operating Range
Ensure that the system operates within the application guidelines shown in Table 10.
Cooling Operating Range
Maximum Minimum
Outdoor
Unit
Indoor
Unit
DB ° F (° C) WB ° F (° C) DB ° F (° C) WB ° F (° C)
125 (51.7) --- --- 55 (12.8) --- ---
90 (32.2) 74 (23.3) 62 (17.0) 56 (13)
Heating Operating Range
Maximum Minimum
Outdoor
Unit
Indoor
Unit
DB ° F (° C) WB ° F (° C) DB ° F (° C) WB ° F (° C)
75 (23.9) 67 (19.4) 17 (---8.3) --- ---
81 (27.2) --- --- 62 (17.0) --- ---
Accessories
An extensive list of field installed accessories is available for both indoor and outdoor units. Identify what accessories, if any, are required for the application at hand and consult the separate installation instructions for the accessories. Some of the accessories, especially on the indoor units, can be installed much easier if planned ahead.
Table 8 – 38HDF / QRF Electrical Requirements
Unit Size
018 208/230 ---1 ---60 12.1/20 12.1/20 024 208/230 ---1 ---60 16.8/25 16.8/25 030 208/230 ---1 ---60 18.4/30 18.4/30 036 208/230 ---1 ---60 23.8/40 23.8/40 036 208/230 ---3 ---60 18.0/30 18.0/30 036 46 0 --- 3 --- 6 0 8.3/15 8.3/15
Volt age
38HDF 38QRF
Min Ckt Amps/
Fuse HACR Bkr
Amps
Min Ckt Amps/
Fuse HACR Bkr
Amps
Table 9 – 40QNC / QNQ Electrical Requirements
Unit Size
018 208/230 ---1 ---60 0.48/15 0.48/15 024 208/230 ---1 ---60 0.48/15 0.48/15 030 208/230 ---1 ---60 0.48/15 0.48/15 036 208/230 ---1 ---60 0.55/15 0.55/15
Volt age
40QNC 40QNQ
Min Ckt Amps/
Fuse HACR Bkr
Amps
Fuse HACR Bkr
Min Ckt Amps/
Amps
5
INSTALLATION
Complete Pre--installation Checks
1. Unpack Unit -- Store the indoor and outdoor units in the
original packaging until it is moved to the final site for in­stallation.
2. Inspect Shipment -- Upon receipt of shipment, check the
indoor and outdoor units for damage. If there is any dam­age, forward claim papers directly to the transportation company. Manufacturer is not responsible for damage in­curred in transit.
3. Inspect Parts Supplied With Units – Check all items
against parts list (see Table 1). If any items are missing, noti­fy your distributor or Carrier office. To prevent loss or damage, leave all parts in original packages until installa­tion.
Consider System Requirements
1. Consult local building codes and NEC for special installa­tion requirements.
2. When deciding the location of the indoor and outdoor units, ensure that the piping run does not exceed the allowed dis­tances listed in Table 3.
3. Make sure the indoor and outdoor units are easily accessible to electrical power.
4. Allow sufficient clearances for airflow, wiring, refrigerant piping, and servicing the unit. See Fig. 3 and Fig. 4.
5. Condensate piping can be directed through the inside wall to an approved drain or straight outside.
INSTALL INDOOR UNIT
Plan the installation carefully before you begin.
1. Select indoor unit location.
a. A location that can bear the weight of the unit.
b. Do not install indoor units near a direct source of heat
such as direct sunlight or a heating appliance.
c. Do not install units too close to humid conditions.
2. Install Mounting Plate The factory supplied mounting plate will look like one of the following depending on the size of the unit.
2.1"
(53.3)
1"
(25.4)
2"
A
(50.8)
2.8"
(71.1)
Note: Numbers in ( ) = mm
35.4” (899.2)
14.9" (378.5)
2.8"
(71.1)
13.8" (130.5)
Fig. 7 -- 40QNC, QNQ018,024 Mounting Plate
7.7" (195.6)
(129.5)
3.5"
(88.9)
5.1”
2.1"
(53.3)
B
A09046
a. Carefully remove the mounting plate which is attached
to the back of the unit by removing any screws and pushing at the indicated pressure points at the bottom of the unit.
Remove Screw
Fig. 9 -- Mounting Plate Screw Location
b. The mounting plate should be located horizontally and
level on the wall. All minimum spacing shown below should be maintained.
5” (127) min.
12”
(304.8)
min.
Note: Numbers in ( ) = mm
Plumb line
18”
(457.2)
min.
Fig. 10 -- Minimum Spacing
c. Install the wall mounting bracket in a location that is
strong enough to withstand the weight of the unit.
d. If the wall is block, brick, concrete or similar material,
drill 0.2 in (5 mm) diameter holes and insert anchors for the appropriate mounting screws.
e. Fasten the wall hanging bracket to the wall with 4 or
more screw anchors through the holes near the outer edge of the bracket.
f. Install the wall hanging bracket flush to the wall, and
ensure the bracket does not move.
3. Drill hole in wall for interconnecting piping, drain, and wir­ing
Refrigerant Line Routing
Piping for indoor units can be routed as shown in Fig. 11.
A09048
A09049
27.1”
(688.3)
Measurements in ( ) = mm
27.2”
(690.9)
8.4” (213)
A09047
Fig. 8 -- 40QNC, QNQ030, 036 Mounting Plate
Before mounting the 40QNC, QNQ unit on the wall mounting bracket, consider how the refrigerant piping will be routed.
Complete the following when installing the wall mounting bracket:
A08358A
Fig. 11 -- Refrigerant Line Routing
Rear Piping
Determine the pipe hole position using the mounting plate as a template. Drill a 2--1/2 inch (63.5 mm) diameter hole in the wall at
6
point A or B as shown in Fig. 12 or Fig. 13. Drill the hole at a slope so that the outside end is 1/2 inch (13 mm) lower than inside end to ensure optimal drainage. Refer to Fig. 14.
Side Or Bottom Piping
Remove the knockout in the unit and drill a 2--1/2 inch (63.5 mm) hole where the pipe penetrates the structure using the guides given above.
2.1"
(53.3)
1"
(25.4)
2"
A
(50.8)
2.8"
(71.1)
Note: Numbers in ( ) = mm
35.4” (899.2)
14.9" (378.5)
2.8"
(71.1)
13.8" (130.5)
Fig. 12 -- 40QNC, QNQ018, 024 Mounting Plate
7.7" (195.6)
(129.5)
3.5"
(88.9)
5.1”
2.1"
(53.3)
B
A09046
INSTALL OUTDOOR UNIT
The outdoor units can be installed on the ground, on the roof, or mounted on a wall.
NOTE: Install the unit so that the coil does not face into prevailing winds. If this is not possible and constant wind winds above 25 mph are expected, use accessory wind baffle. See installation instructions provided with accessory kit. Wind baffles should also be used on all units with accessory low ambient temperature control.
Mounting on Ground
1. Mount unit on a solid level concrete pad.
2. If a heat pump is being installed, use a field-- provided snow stand or ice rack where prolonged subfreezing temperatures or heavy snow occurs.
3. Position unit so water or ice from roof does not fall directly onto unit.
4. On cooling only units, an accessory stacking kit can be used when units are to be stacked. See installation instructions provided with the accessory kit.
Mounting on Roof
CAUTION
A
2" 5.1"
Fig. 13 -- 40QNC, QNQ030, 036 Mounting Plate
1/2 in. (13 mm)
Min.
INDOOR
OUTDOOR
Fig. 14 -- Drill Hole at Slope
4. Relocate drain connection if necessary -- Determine if the installation requires a left or a right hand drain exit and relo­cate the drain hose if necessary as shown in Fig. 15.
A09050
A07371
B
PERSONAL INJURY AND/OR EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in personal injury and / or equipment damage. Be sure unit panels are securely in place prior to rigging.
1. Rig the unit. Keep the unit upright and lift using a sling. Use cardboard or padding under the sling, and spreader bars to prevent sling damage to the unit. See Fig 16. See Fig. 2 for center of gravity reference
2. Mount unit on a solid concrete pad or platform.
3. Isolate unit and piping from structure
4. If a heat pump is being installed, use a field-- provided snow stand or ice rack where prolonged subfreezing temperatures or heavy snow occurs.
5. On cooling only units, an accessory stacking kit can be used when units are to be stacked. See installation instructions provided with accessory kit.
Drain Cap
Drain Hose
A08362
Fig. 15 -- Drain Hose and Cap Location
NOTE: If the condensate pump accessory is to be used, the drain
hose can be cut to provide space for the space for the condensate pump reservoir in the back of the unit. The reservoir must be installed at this time. Please refer to installation instructions provided with the condensate pump accessory.
5. Place unit on a clean surface until you are ready to connect the piping and wiring.
A07396
Fig. 16 -- Lifting Unit with Sling
7
Mounting Unit on Wall
The units can also be mounted on the wall using the accessory mounting kit.
Complete Outdoor Refrigerant Piping Connec­tions
Follow the following general guidelines:
1. Use refrigerant grade field – supplied tubing. Refer to Table 4 for the correct line sizes.
2. Do not use less than 10 ft (93.05 m) of interconnecting tubing.
38HDF Units:
1. Assemble the connector tube to the factory supplied filter drier by:
a. Braze the field supplied connector to the inlet of the
filter drier (see Fig. 17)
b. Braze the factory supplied flare connector to the outlet
end of the filter drier (see Fig.17)
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
If any section of pipe is buried, there must be a 6 in. (152.4 mm) vertical rise to the valve connections on the outdoor unit. If more than the recommended length is buried, refrigerant may migrate to cooler, buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at start--up.
When more than 80 ft (24.4 m) of interconnecting tubing is used, consult the Duct--Free Split System Long Line Application Guide for required accessories.
3. Insulate both lines. A minimum of 1/2 inch foam pipe insu­lation is recommended.
4. Run the refrigerant tubes as directly as possible and avoid unnecessary turns and bends.
5. Suspend refrigerant tubes to avoid damage to insulation or tubes so they do not transmit vibration to the structure.
6. When passing refrigerant tubes through the wall, seal the opening so rain and insects do not enter the structure. Leave some slack in refrigerant tubes between structure and out­door unit to absorb vibration.
NOTE: A fusible plug is located in unit suction line; do not cap this plug. If local codes require additional safety devices, install as directed.
CAUTION
Connection at Outdoor Unit
A09499
Fig. 17 -- 38HDF018--036 Connector Tube Assembly
2. Assemble the Accurator body (see Fig. 18) using the correct factory supplied piston (refer to Table 7) .
NOTE: Arrow on AccuRater body points in free flow direction, away from the indoor coil.
A09501
Fig. 18 -- AccuRater (bypass type) Metering Device
Components
3. Attach the complete Accurator assembly to the flare connec­tion end of the filter drier
4. Braze the completed filter drier/Accurator assembly to the liquid service valve.
5. Connect the field supplied line set to the filter drier/Accura­tor assembly and the suction valve. A sweat connection is required at the suction valve and flareconnection is required for the mixed phase line.
6. Insulate any exposed areas between the line set and the li­quid valve.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
To prevent damage to unit or service valves observe the following:
S A brazing shield MUST be used. S Wrap service valves with wet cloth or use a heat sink
material.
CAUTION
8
38QRF Units
1. Assemble the connector tubes to the factory supplied filter drier by brazing the factory supplied flare connectors to the inlet and outlet for the filter drier (see Fig. 19)
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation could void any applicable Carrier warranty.
A09507
Fig. 19 -- 38QRF018--036 Connector Tube Assembly
2. Perform step 2 and 3 from the 38HDF section.
3. Remove the plastic cap from the liquid and suction service valve on the 38QRF unit and assemble the heating piston and piston cap supplied with the outdoor unit as shown in Fig. 20.
A07407
Fig. 20 -- AccuRater (bypass type)
Metering Device Components
NOTE: The Teflon seal on the piston should point towards the
liquid service valve. The size of the factory supplied piston might have to be adjusted for long line applications (over 80 ft / 24.4 m). Refer to the Duct Free Long Line Application Guide for additional information.
4. Attach the flare end of the filter drier assembly to the piston cap (see Fig. 20).
5. Connect the field supplied line set to the filter drier as­semblyandtothesuctionvalve.
6. Insulate any exposed areas between filter drier and liquid valve.
Complete Outdoor Power and Control Wiring
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes.
WARNING
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before performing service or maintenance, be sure indoor unit main power switch is turned OFF and indoor blower has stopped.
Lock out and tag switch with a suitable warning label.
Power Wiring
1. Mount outdoor power disconnect. The unit is factory wired for the voltage shown on the unit nameplate. The fused dis­connect switch must be provided within sight of the unit, readily accessible, but out of reach of children. Provisions for locking the disconnect switch on the OFF (open) posi­tion is advisable. The disconnect switch must comply with NEC and local codes. Protect the unit and wiring using only the recommended fuse/circuit breaker size. See Table 10..
2. Run power wiring from main box to disconnect per NEC and local codes.
3. Run power wiring from the disconnect switch to outdoor unit. Use only minimum 60_C copper conductors between the disconnect switch and the unit for field power connec­tion.
4. Route the field power wires through the conduit connection opening in the unit side panel and connect in junction box as shown in Fig 21. The unit and power wiring must be grounded.
SINGLE-PHASE CONN TO DISCONNECT PER NEC
THREE-PHASE CONN TO DISCONNECT PER NEC
LEGEND NEC -- National Electrical Code
-- Splice (field) Field Wiring Factory Wiring
GROUND LEAD
GROUND LEAD
Fig. 21 -- Line Power Connections
NOTE: Operating unit on improper line voltage constitutes abuse
and could affect Carrier warranty. Do not install unit in a system where voltage may fluctuate above or below permissible limits.
GROUNDING LUG
BLK
BLK
SINGLE-PHASE UNIT
BLK
BLU
YEL
GROUNDING LUG
THREE-PHASE UNIT
A08251
9
Control Wiring
The control circuit is 24 volts AC (minimum 40VA) supplied from the indoor unit.
1. Make sure you have enough control wires to cover the dis­tance between the indoor and outdoor unit.
Indoor
Indoor
Terminal
Terminal
Board
Board
Indoor
Indoor
Board
Board
Outdoor
Outdoor
Terminal
Terminal
Board
Board
2. Route one end of the control wiring through the opening provided in the unit side panel and connect to the control terminal strip using either Fig. 21 for 38HDF units and Fig. 22 for 38QRF units.
Indoor
Indoor
Board
Board
Indoor
Indoor
Terminal
Terminal
Board
Board
Outdoor
Outdoor
Terminal
Terminal
Board
Board
A09509
Fig. 22 -- 38HDF Control Terminal Strip
A09508
Fig. 23 -- 38QRF Control Terminal Strip
NOTE: Use No. 18 AWG color--coded, insulated (35_C minimum) wire. If the distance between the indoor and outdoor unit is greater than
100 ft. (30.5 m), as measured along the control voltage wires, use No. 16 AWG color--coded wire to avoid excessive voltage drop.
10
Table 10 – 38HDF / 38QRF Electrical Data
38HDF /
38QRF
UNIT
SIZE
018 208/230---1 ---60 187 253 9.0 48.0 0.80 0.125 0.09 12.1 20
024 208/230---1 ---60 187 253 12.8 58.3 0.80 0.125 0.09 16.8 25
030 208/230---1 ---60 187 253 14.1 73.0 1.50 0.25 0.19 18.4 30
035
036
V --- P H --- H z
208/230---1 ---60 187 253 16.7 79.0 1.50 0.25 0.19 22.3 35
208/230---3 ---60 187 253 10.4 79.0 1.50 0.25 0.19 14.5 20
4 6 0 --- 3 --- 6 0 414 506 5.8 79.0 0.80 0.25 0.19 8.7 15
208/230---1 ---60 187 253 17.9 112.0 1.45 0.25 0.19 23.8 40
208/230---3 ---60 187 253 13.2 88.0 1.45 0.25 0.19 18.0 30
4 6 0 --- 3 --- 6 0 414 506 6.0 44.0 0.80 0.25 0.19 8.3 15
VOLTAGE RANGE*
Min Max
COMPRESSOR OUTDOOR FAN MOTOR
RLA LRA FLA NEC Hp kW Out
MIN CKT
AMPS
Table 11 – 40QNC, QNQ Fan Coil Electrical Data
UNIT SIZE V --- P H --- H z
40QNC01824 208/230--- 1--- 60 187 253 0.38 64 0.48 15
40QNC030 208/230 --- 1 ---60 187 253 0.38 74 0.48 15
40QNC036 208/230 --- 1 ---60 187 253 0.44 74 0.55 15
40QNQ018 208/230 ---1 ---60 187 253 0.38 64 0.48 15
40QNQ024 208/230 ---1 ---60 187 253 0.38 64 0.48 15
40QNQ030 208/230 ---1 ---60 187 253 0.38 74 0.48 15
40QNQ036 208/230 ---1 ---60 187 253 0.44 74 0.55 15
VOLTAGE RANGE* FAN POWER
Min Max FLA
Motor Power
(Watts)
MIN CKT
AMPS
FUSE/CKT BKR AMPS
FUSE/ HACR
BKR
AMPS
LEGEND:
FLA --- Fu l l L o a d A m p s LRA --- L o c k e d R o t o r A m p s NEC -- - National Electrical Code
RLA --- RatedLoadAmps(compressor)
* Permissible limits of the voltage range at which the unit will operate satisfactorily
NOTES:
1. Control circuit is 24 ---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
2. All motors/compressors contain internal overload protection.
3. In compliance with NEC (USA Standard) requirements for multimo­tor and combination load equipment (refer to NEC Articles 430 and
440), the over current protective device for th e unit shall be fuse.
4. Motor RLA values are established in accordance with UL (Under­writers’ Laboratories) Standard 465 (USA Standard).
5. 38QRF018 ---030 units are only available in single ---phase voltage.
6. Unbalanced 3---Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent-
age of voltage imbalance:
= 100 X
EXAMPLE: S u p p l y v o l t a ge is 4 6 0 --- 3 --- 6 0
max voltage deviation from average
AB = 452v BC = 464v AC = 455v
Average Voltage = 452 + 464 + 455
average
=
=
1371
3
457
voltage
3
Determine ma ximum deviation from average voltage: (AB) 457 ---452 = 5v (BC) 464 ---457 = 7v
(AC) 457 ---455 = 2v Maximum deviation is 7v.
Determinepercentageofvoltageimbalance
% of voltage imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable of 2%.
IMPORTANT: Contact your local electric utility company immediately if the supply voltage phase imbalance is more than 2%.
7
57
11
Fig. 24 -- 40QNC01824 Matched with 38HDF Typical Wiring Schematic
12
A08367
Optional on 38QRF018/024 Models
Fig. 25 -- 40QNQ018,024 Matched with 38QRF Typical Wiring Schematic
A08368
13
Fig. 26 -- 40QNC030, 036 Matched with 38HDF Typical Wiring Schematic
14
A08369
Optional on 38QRF0036 Models Standard on 38QRF030
Fig. 27 -- 40QNQ030, 036 Matched with 38QRF Typical Wiring Schematic
15
A08370
Run Power Wiring for Indoor Unit
Be sure field wiring complies with local building codes and NEC, and unit voltage is within limits shown in Table 11.
Contact local power company for correction of improper line voltage.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation could void any applicable Carrier warranty.
NOTE: Use copper wire only between disconnect switch(es) and unit.
NOTE: Install branch circuit disconnect of adequate size to handle unit starting current per NEC. Locate disconnect within sight of, and readily accessible from, unit, per section 440--14 of NEC. Some codes allow indoor unit to share disconnect with outdoor unit if disconnect can be locked; check local code before installing in this manner.
The 40QNC/QNQ units require their own power supply.
1. Locate the indoor power supply.
2. Locate and install disconnect switch per NEC and local codes.
3. Run power supply wiring to disconnect switch.
4. Run power wiring from disconnect switch to wall mount area.
5. If any accessories are being installed, refer to the individual accessory instructions for guidance on wire routing at this time.
WARNING
CAUTION
Install All Power, Interconnecting Wiring, Piping and Drain Hose to Indoor Unit
1. Run control wiring from the outdoor unit through theaccess hole in the wall and make sure you have enough wire to reach the control box of the unit once hung on the mounting plate.
2. It is a recommended that flare connections is located on the outside of the wall where the indoor unit is to be mounted. If an extension pipe is required to facilitate this location, measure, fabricate and install the extension pipes to the in­door unit before hanging the unit on the mounting bracket.
3. If piping connections are on the outside wall, pass the pipes (refrigerant and drain) through the wall sleeve and then hook the indoor unit body on top of the wall hanging brack­et. Support the unit away from the bottom using a tool or a piece of wood.
NOTE: Tie together the refrigerant piping, the drain hose, and the electrical connection wires and ensure that the drain hose is at the bottom as shown in Fig. 28.
Fig. 28 -- Location of Piping, Hose, and Wiring
4. If required make the flare connections.
5. Route the power and control wiring through the back side of the unit and to the control box area. If the wired remote or zone manger accessory are to be used, perform any modi­fications required at this time. Refer to the Accessory install­ation instructions).
6. Remove the control box cover and finish all indoor unit wiring connections as shown on the wiring diagram or in the accessory installation instructions. Replace the control box cover.
7. Fix the bottom part of the unit to the wall mounting bracket and push it carefully until the two bracket hooks fit into the marked places at the base of the unit until it snaps into place. See Fig. 29.
.
2
3
2
3
A08364
16
Wall Hanging Bracket
Retainer C lip
Hook
Hole
UNIT SIZE
40QNC01824 13.4 10.6
40QNC030 12.2 12.2
40QNC036 12.2 12.2
40QNQ018 13.4 10.6
40QNQ024 13.4 10.6
40QNQ030 12.2 12.2
40QNQ036 12.2 12.2
DIMENSION
AB
Retainer Clip
USER INTERFACE
The indoor unit includes a wireless remote control to operate the unit (an Owner’s Manual is supplied with the unit). If you have two units installed in the same space and they need to work independently, the remote controls and the units need to be configured as follow:
Unit Configuration
Turn the unit off by pressing the . Press and hold the and
buttons of the remote control for more than 5 seconds. The display will be cleared and the time segments will display the first configuration item (rAdr=remote address) and the temperature segments will display the default value of this configuration item
(Ab=control of both indoor units). Press
and to change the
A
B
A08365
Fig. 29 -- Wall Mounting Details
8. If the refrigerant piping connections are located outside the wall, tighten the flare connections as shown in Fig. 30. Insu­late all exposed refrigerant lines and secure to the wall and fill any void spaces in the hole.
1
3
Adjustable wrench or torque wrench Outdoor end Indoor end
Fig. 30 -- Tightening Connections
2
A07201
default value to the new value of (a) or (b). Press the
transmit the new configuration to the unit. Press the
button to
button to
leave the configuration menu.
Remote Control Configuration
Turn the unit off by pressing the button. Press and hold the
and buttons for more than 5 seconds. The display will be cleared and the time segments will display the first configuration item (CH=remote address) and the temperature segments will display the default value of this configuration item (Ab=control of both indoor units).
Press
or (b). Press the
unit. Press the
and to change the default value to the new value of (a)
button to transmit the new configuration to the
button to leave the configuration menu.
NOTE: When 30 seconds have elapsed and no buttons have been pressed, the remote control will automatically exit the configuration menu and resume its normal operation.
A wall mounted control or zone manager can be used to control a unit or multiple units.
Wired Control
If a wall mounted wired control is required the following steps
should be performed at the same time the indoor control and power wiring are being connected:
1. Unplug the connector on J5.
2. Remove the wire harness from the wired control box
3. Plug one end of the wire harness into the J5 connector on the board
4. Route the other end of the wire harness to the back of the unit along the low voltage wiring
5. Connect the other end of the wire harness to the field sup­plied wiring between the indoor unit and the wired control as shown in wired control installation instructions and Fig.
31.
17
A09512
Fig. 31 -- Control Wiring Between Indoor and Outdoor Units
Up to six units can be daisy--chained and controlled from one wired control.
*
* 100 ohm Resistor
Fig. 32 -- Multiple Unit Control Wiring
18
A09513
Zone Manager
If a Zone Manager is required, the following steps should be performed at the same time the indoor control and power wiring are being connected:
1. Plug the communication board to the J8 as shown in Fig. 33
2. Connect one end of the wire harness supplied with the Zone Manager to the communication board.
3. Route the other end of the wire harness along the voltage control to the back of the unit.
4. Connect the other end of the wire harness to the field sup­plied wiring that will be connected to the zone manager as shown in Fig. 33. (Shielded cables are required. Refer to Zone Manager Installation Instructions for further informa­tion.)
Fig. 33 -- Wiring for Zone Manager
A09514
19
START--UP
t
Preliminary Checks
1. Check condensate drainage system; on the opposite side of the drain connection, insert a water bottle up into the fan coil unit and fill the drain pan. Water must flow steadily; if not, check the pipe slope or inspect for any pipe restrictions.
2. Make sure all wiring connections are correct and they are tight.
3. Field electrical power source must agree with unit name plate rating.
4. Check that all barriers, covers, and panels are in place. En­sure that the filters and return--air grilles on the indoor unit have been installed and that the discharge louvers are posi­tioned correctly.
5. All service valves must be closed.
6. On units with crankcase heaters, ensure belly--band heaters are tight around the compressor.
Evacuate and Dehydrate the System
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Never use the system compressor as a vacuum pump.
Using Vacuum
1. Completely tighten flare nuts A, B, C, D, connect manifold gage charge hose to a charge port of the low side service valve. (See Fig. 34.)
2. Connect charge hose to vacuum pump.
3. Fully open the low side of manifold gage. (See Fig. 35)
4. Start vacuum pump
5. Evacuate using either deep vacuum or triple evacuation method.
6. After evacuation is complete, fully close the low side of manifold gage and stop operation of vacuum pump.
7. The factory charge contained in the outdoor unit is good for up to 25 ft. (8 m) of line length. For refrigerant lines longer than 25 ft (8 m), add 0.3 oz. per foot of extra piping up to the maximum allowable length.
8. Disconnect charge hose from charge connection of the low side service valve.
9. Fully open service valves B and A.
10. Securely tighten caps of service valves.
Outdoor Unit
CAUTION
Pump
Refrigerant
Low Side
A
High Side
B
Indoor Uni
C
D
Manifold Gage
500 microns
Low side valve
Charge hose
High side valve
Charge hose
Vacuum pump
Low side valve
A07361
Fig. 35 -- Manifold
Deep Vacuum
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water. (See Fig. 36)
5000 4500 4000 3500 3000 2500 2000
MICRONS
1500 1000
500
Method
LEAK IN SYSTEM
VACUUM TIGHT TOO WET
TIGHT DRY SYSTEM
01234567
MINUTES
Fig. 36 -- Deep Vacuum Graph
A95424
Service Valve
Fig. 34 -- Service Valve
A07360
20
Triple Evacuation
Method
The triple evacuation method should only be used when vacuum pump is only capable of pumping down to 28 in. of mercury vacuum and system does not contain any liquid water. Refer to Fig. 37 and proceed as follows:
1. Pump system down to 28 in. of mercury and allow pump to continue operating for an additional 15 minutes.
2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and open until system pressure is 2 psig.
4. Close service valve and allow system to stand for 1 hr. Dur­ing this time, dry nitrogen will be able to diffuse throughout the system absorbing moisture.
5. Repeat this procedure as indicated in Fig. 37. System will then be free of any contaminants and water vapor.
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS DEEP VACUUM)
RELEASE CHARGE INTO SYSTEM
A95425
Fig. 37 -- Triple Evacuation Method
To Start the Unit:
1. If the outdoor unit is equipped with a crankcase heater, turn on the indoor and outdoor disconnect switches to supply power the system 12 hours before starting the system.
2. Release charge into the system by opening (back--seating) liquid and suction line service valves.
3. Set the wireless remote control or wired remote control be­low ambient temperature. Operate the unit for 15 minutes.
4. Refer to Table 6 to determine if additional charge is re­quired. Also, if you have a long line application, refer to the Duct Free Long Line Application Guide to determine the additional charge that is required beyond 25 ft (7.6 m).
5. Calculate the total additional charge required and weigh in.
6. Charge should be added as liquid (not gas) slowly and care­fully to low side to avoid liquid slugging.
7. Start unit with operation test. In test mode the unit will run in cooling and heating (on heat pumps) regardless if there is demand or not.
Set Unit in Test Mode Using Wireless Control
Turn power on to the unit. Insert batteries in remote control. Press
and the buttons on the remote control for 5 seconds.
the The remote control will be cleared and the time segment will
display the Src1=service test mode. Press the
button to
transmit the service test signal to the unit. After the test has
completed press the
button to leave the test menu.
NOTE: When 30 seconds have elapsed and no buttons have been pressed, the remote control will automatically exit the test menu and resume its normal operation.
SetUnitinTestModeUsingWiredControl
There is a hidden service test mode that is initiated through a combination of button presses when the remote is off. The following combination must be pressed within a 6 second period:
“DOWN--FAN--UP--FAN--MODE” Once in service test mode, the service test mode message will be
sent and “Sr” will be displayed in the temperature icons until the “DOWN” button is pressed.
During Service Test mode, all the icons are off. the only button that is active is the “DOWN” button.
To cancel Service Test mode, press the “DOWN” button to send a normal message with “OFF” mode.
Service Test mode automatically times out after 30 minutes and the remote will operate normally.
Test Mode Sequence of Operation
Once unit is in TEST MODE, all remote control messages are ignored except for a message to turn the unit OFF. Buzzer will beep twice.
When in TEST MODE, the unit will operate as follows:
1. The unit Status (Green) and Timer (Yellow) LEDs will blink every 2 seconds
GREEN
Fig. 38 -- LED Display
2. Indoor fan will operate according to user – selected speed. If Autofanisselected,thefanwillruninHighspeed
3. Cooling only system
a. Unit will operate in cool mode with demand
b. Louver will operate according to user -- selected posi-
tion or in cool position if louvers are set to Auto
4. Heat pump system
a. Unit will run in cooling mode with demand for 3
minutes
b. Unit will run in heat pump mode with demand for 2
minutes or until indoor coil temperature is greater than 104_F(40_C). If coil temperature reaches 104_F (40_C), the unit will run in cool mode until test mode is exited.
c. Louver will operate according to user -- selected posi-
tion or in cool/heat position if louvers are set to Auto.
5. Following will cancel Test Mode:
a. Unit is turned off by controller
b. Power is cycled during Test Mode
c. 30 minutes elapsed
d. Fail Mode
YELLOW
A09594
21
SERVICE
Refrigerant Charging
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
WARNING
Pump--down Procedure
The system may be pumped down in order to make repairs on the low side without losing complete refrigerant charge.
1. Attach pressure gage to suction service valve gage port.
2. Front--seat the mixed phase line valve.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
The unit coils hold only the factory--designated amount of refrigerant. Additional refrigerant may cause units to relieve pressure through the compressor internal pressure relief valve (indicated by a sudden rise of suction pressure) before suction pressure reaches 20 psig. If this occurs, shut off unit immediately then front--seat the suction valve and remove and recover excess refrigerant following accepted practices.
CAUTION
!
PERSONAL INJURY AND/OR EQUIPMENT DAMAGE HAZARD
Failure to follow this warning could result in personal injury and/or equipment damage.
Wear safety glasses and gloves when handling refrigerant. Do not overcharge system -- this can cause compressor flooding.
All units are shipped with the refrigerant charge listed on nameplate.
NOTE: Do not vent or depressurize unit refrigerant to atmosphere. Remove and recover refrigerant following accepted practices.
WARNING
3. Start unit and run until suction pressure reaches 5 psig.
4. Shut unit off and front--seat suction valve.
5. Depressurize low side of unit and recover refrigerant fol­lowing accepted practices.
Filter Drier
Whenever the filter drier is exposed to the atmosphere it must be replaced. Only use factory specified liquid--line filter driers with rated working pressures less than 600 psig.
NOTE: Do not install a suction--line filter drier in the mixed phase line.
22
TROUBLESHOOTING
See Table 12 and Table 13 for troubleshooting information.
Fault Code
Once a failure occurs with the indoor unit in operation, the green LED on the indoor unit flashes at intervals of 0.5 seconds. The fault code is deduced from the number of times the green LED flashes, blocking unit operation. Between one flash cycle and the next one, a pause of 3 seconds elapses.
Table 12 – Green LED (Indoor Unit Fault)
CODE DESCRIPTION
3 RoomAirSensorFault 4 Indoor Unit Coil Sensor Fault
14 OutdoorUnitAirSensorFault
Table 13 – Troubleshooting
PROBLEM POSSIBLE CAUSE SOLUTION
Compressor and Fan of the Outdoor Unit Will Not Start
Compressor Will Not Start, But Out­door Fan is Operating
Compressor Stops Due to Over- --tem­perature
Compressor Runs Continuously
F r e q u e n t I c e --- B u i l d --- U p o n O u t d o o r Coil
Discharge Pressure Too High
Discharge Pressure Too Low
Suction Pressure Too High
Suction Pressure Too Low
Outdoor Fan Cycling Due to Over --­Te m p e r a t u r e P r o t e c t i o n
Unit not energized Check the main power connection. Main switch is set to OFF CheckandputittoONposition. Main switch fuses are blown Replace fuses. Compressor cycling protection is on Wait for 3 minutes. Main power voltage is too low Check and set to the correct voltage. Electrical connections are too loose or are wrong Check and tighten or correct connections. Electrical connections of compressor are loose or wrong Compressor burnt out; seized or protection deviceonCheck for the cause and replace compressor if neces-
Wrong refrigerant charge in unit (excessive or low) or air or other non --- condensable gasses in the circuit Main voltage is too high or too low Check voltage setting and adjust if necessary. Condenser coil obstructed Remove obstruction. Outdoor fan off Check cause an d resume operation or repair. Wrong indoor unit thermistors Replace thermistors. Refrigerant circuit clogged Check and remove obstructions. Reversing valve f a ulty on heat pump models Replace reversing valve.
Expansion device clogged or covered with ice
Unit selected is too small for application requir e­ments Indoor temperature setting too low or too high Check temperature setting. Outdoor unit fan faulty Replace outdoor fan.
Air or other non --- condensable gasses in the cir­cuit
Obstructions at air intake or dirty indoor unit fil ters Remove obstruction and/or clean filter.
Outdoor fan is stopped Check cause an d repair.
Outdoor coil dirty or obstructed Clean or remove obstructions. Condenser fan faulty Replace condenser fan. Indoor temperature setting too low or too high Check temperature setting.
Air or other non --- condensable gasses in the cir­cuit
Indoor temperature setting too high or too low Check temperature setting. Outdoor coil dirty or obstructed Clean or remove obstructions. Indoor unit air filter dirty Clean filter. Indoor temperature setting too high or too low Check temperature setting. Reversing valve faulty or internal leak Replace rever sing valve. Indoor temperature setting too high or too low Check temperature setting.
Evaporator coil covered with ice
Expansion device or suction line clogged Check and repair. Outdoor fan does not stop during defrost periods Check electrical parts. Electrical connection loose Check connections. Fan motor burn out Replace. Fan bearing seized Check and repair.
Expansion device clogged or covered with ice
Check and tighten or repair compressor.
sary. Drain refrigerant, evacuate and recharge. CAUTION: Do not vent refrigerant to the atmosphere; use refrigerant
recovery equipment.
Drain refrigerant, evacuate and recharge. CAUTION: Do not vent refrigerant to the atmosphere; use refrigerant recovery equipment. Contact a qualified service technician for a system evalu­ation.
Drain refrigerant, evacuate and recharge. CAUTION: Do not vent refrigerant to the atmosphere; use refrigerant recovery equipment.
Drain refrigerant, evacuate and recharge. CAUTION: Do not vent refrigerant to the atmosphere; use refrigerant recovery equipment.
Air circulation on the evaporator not sufficient; check and repair.
Drain refrigerant, evacuate and replace. CAUTION: Do not vent refrigerant to the atmosphere; use refrigerant recovery equipment.
23
Copyright 2009 Carrier Co rp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 09/09
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
24
C a t a l o g N o : 4 0 Q N C --- Q --- 9 S I
Replaces: 40QN--- 8SI
Loading...