Carrier 40QA024-060 User Manual

Page 1
40QA024-060
Ceiling-Suspended Fan Coil Units
Installation, Start-Up and Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
Step 1 — Complete Pre-Installation
Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
• UNPACK UNIT
• INSPECT SHIPMENT
• BEFORE INSTALLATION
Step 2 — Select Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
• WOODEN STRUCTURE
• NEWLY BUILT CONCRETE SLAB
• METAL STRUCTURE
• PREVIOUSLY BUILT CONCRETE SLAB
• TO MOUNT UNIT
• TO INSTALL THERMOSTAT
Step 4 — Connect Refrigerant Piping. . . . . . . . . . . . . . . . 7
Step 5 — Connect Condensate Drain Line . . . . . . . . . . .8
Step 6 — Make Electrical Connections . . . . . . . . . . . . .10
Step 7 — Install Thermostat . . . . . . . . . . . . . . . . . . . . . . . . 12
Step 8 — Make Connections Between
Indoor and Outdoor Units . . . . . . . . . . . . . . . . . . . . . . . .15
• CHECK ACCURATOR METERING DEVICE
• COOLING ONLY SYSTEMS
• HEAT PUMP SYSTEMS
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18,19
After Extended Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . .18
Seasonal Changeovers . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Operating Mode Memory . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Automatic Operation (Auto.) Mode. . . . . . . . . . . . . . . . . .18
•FAN OPERATION
• COOLING MODE OPERATION
• HEAT PUMP OPERATION
• DEFROST (Heat Pump Only)
• SYSTEM SAFETIES
• SPECIAL OPERATION, HEATING
CLEANING AND MAINTENANCE . . . . . . . . . . . . . . . . 19,20
Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Air Filters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
• REMOVE AIR FILTERS
• CLEAN OR REPLACE FILTERS
Clean Indoor Unit Bottom Panel . . . . . . . . . . . . . . . . . . . .20
Clean Outdoor Coil (Outdoor Unit). . . . . . . . . . . . . . . . . .20
Clean Condensate Drains . . . . . . . . . . . . . . . . . . . . . . . . . .20
• CLEAN OR REPLACE DRAIN PAN
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Before Calling for Service . . . . . . . . . . . . . . . . . . . . . . . . . .20
• IF SYSTEM FAILS TO OPERATE
FRESH AIR INSTALLATION OPTION . . . . . . . . . . . . . . . .20
Ventilation-Air Accessory . . . . . . . . . . . . . . . . . . . . . . . . . .20
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . .CL1, CL-2
SAFETY CONSIDERATIONS
Installing and servicing air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install or service air-conditioning equipment.
Untrained personnel can perform basic maintenance, such as cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on air­conditioning equipment, observe precautions in literature and on tags and labels attached to unit.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly. Consult local building codes and National Electrical Code (NEC) for special installation requirements.
Before installing or servicing system, always turn off main power to system. There may be more than one dis­connect switch. Turn off accessory heater power if appli­cable. Electrical shock can cause personal injury.
INSTALLATION
Installation instructions for fan coil units (Fig. 1) are con­tained in this manual. Refer to this manual for proper installa­tion of the complete system. Note that the outdoor units are shipped with installation and service instructions for basic in­stallation of the outdoor section. Be sure to make the connec­tions in Cooling Only Systems and Heat Pump Systems sec­tions on page 15 of this literature so that the unit will operate properly.
Refer to Table 1 for proper system matches.
Fig. 1 — Ceiling-Suspended Fan Coil Unit
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 3 d 2 c
Catalog No. 02-40QA0007-SI Printed in U.S.A. Form 40QA-7SI Pg 1 706 3-06 Replaces: 40QA-5SI
Page 2
Table 1 — System Matches
SYSTEM TYPE INDOOR SECTION NUMBER OUTDOOR SECTION NUMBER
40QAC 38HDR-3,5,6
024* 018 024 024
Cooling Only
Heat Pumps
Heating/Cooling
*Units must be field reconfigured for 11/2 ton (18,000 Btuh) operation. See Before Installation sec-
tion on page 3 for details.
NOTE: Numbers in ( ) indicate quantities when there is more than one fan coil unit in the system.
036 030 036 036 048 048 060 060
40QAQ 38QRR-3,5,6
024* 018 024 024 036 030 036 036 048 048 060 060
40QAQ 38HDR-3,5,6
024* 018 024 024 036 030 036 036 048 048 060 060
Ensure unit operation within the application guidelines shown in Table 2. When installing the outdoor unit, for cooling operation when the outdoor-air temperature is below 55 F, the following accessories are required:
• low ambient kit
• crankcase heater
• winter start kit
• isolation relay (38QRR heat pump units only)
This will provide cooling operation down to 40 F ambient temperature. For operation down to –20 F ambient tempera­ture, a field-installed wind baffle will also be required.
To complete installation of the system, the following items must be field-supplied for connection of the indoor and outdoor units:
• refrigerant piping
• condensate drain piping
• thermostat
• power and control wiring
For some applications, a fresh air intake, power vent fan, and/or condensate pump kit may be required.
Table 2 — Application Range
COOLING
Maximum Minimum
Indoor Outdoor Indoor Outdoor
95 F DB
71 F WB
Maximum Minimum
Indoor Outdoor Indoor Outdoor
80 F DB
71 F WB
LEGEND
DB Dry Bulb WB Wet Bulb
*This value is for single-zone systems and may be equipped with an
accessory low-ambient control or winter start kit that will allow operation down to –20 F.
125 F DB 67 F DB
HEATING (Heat Pump Systems Only)
75 F DB
65 F WB
57 F WB
55 F DB –20 F DB
55 F DB*
40 F DB
2
Page 3
Table 3A — Physical Data, Under Ceiling Cooling Only Units
SYSTEM SIZE 018* 024 030 036 048 060 NOMINAL CAPACITY (tons) 1 NOMINAL SIZE (Btuh) 18,000 24,000 30,000 36,000 48,000 60,000 OPERATING WEIGHT (lb) 108 108 117 117 149 179 MOISTURE REMOVAL WEIGHT
(Pints/Hr) FINISH GM Motorhome White with Black Trim REFRIGERANT R-410A
Control (Cooling) AccuRater Control
INDOOR FAN Direct Drive Centrifugal
Rpm...Cfm High 862...500 1050…600 1275...840 1275...840 1435...1200 1275...1600 Rpm...Cfm Medium 690...400 690...400 972...740 972...740 1388...1160 972...1220 Rpm...Cfm Low 552...320 552...320 830...640 830...640 1315...1100 830...1040 High Speed Watts 92 92 282 282 425 564 Motor Quantity 111122
Blowers — No. ...Size (in.) 2...6x8 2…6x8 2…6x8 2…6x8 3…6x8 4…6x8
INDOOR COIL Copper Tube, Aluminum Fin
Face Area (sq ft) 2.2 2.2 2.6 2.6 3.0 4.0 No. of Rows 444444 Fins/in. 14.9 14.9 14.9 14.9 14.9 14.9 Circuits 444488
FILTERS Cleanable
Quantity 445568
AIRSWEEP
Horizontal User select ON/OFF Vertical Manual
CONTROLS
Control Voltage 24 V Auto Restart Ye s Fan Speed High/Medium/Low Condensate Pump Safety Yes (Accessory) Indoor Coil Freeze Protection Standard shutoff at 28 F Filter Change Indication 250 Hours of Indoor Fan Operation
REFRIGERANT LINES
Connection Type Flare
Liquid Line OD (in.) Vapor Line OD (in.)
Max Line Length For maximum line lengths see condensing unit instructions.
CONDENSATE DRAIN CONNECTION
CONDENSATE DRAIN SIZE (in.)
*Field reconfigured to 18,000 Btuh (11/2 tons). See Before Installa-
tion section on this page for details.
1
/
2
4.0 7.3 6.0 9.0 13.0 14.5
5
/
8
23345
3
/
1
/8 inch.
8
3
/
4
3
/
4
7
/
8
7
/8†
5
/
8
3
/
4
Pipe Thread (MPT)
† The valve connection size is 7/8 inch. The recommended line size
is 1
Step 1 — Complete Pre-Installation Checks
UNPACK UNIT — Store fan coil unit in the original packag­ing until it is moved to the final site for installation. When re­moving unit from carton, lift unit by its 4 corners; DO NOT lift unit by its plastic parts.
INSPECT SHIPMENT — Upon receipt of shipment, check fan coil unit for damage. Forward claim papers directly to the transportation company. Manufacturer is not responsible for damage incurred in transit.
Check all items; if any item is missing, notify your dealer. To prevent loss or damage, leave all parts in original packages until installation.
BEFORE INSTALLATION — Perform the following steps before installing indoor fan coil unit. Place the indoor unit up­side down on the floor, then:
1. Remove side panels by sliding forward, then away from sides of unit (Fig. 2). Reinstall prior to unit start­up.
2. Remove air filters from inlet grilles; then remove and retain screws securing inlet grilles to indoor unit. Rein­stall prior to unit start-up.
NOTE: Dimensions shown in brackets [ ] are in mm.
Fig. 2 — Removal of Mounting Brackets
from Indoor Unit
3
Page 4
Table 3B — Physical Data, Under Ceiling Heat Pump Units
UNIT SIZE 018* 024 030 036 048 060 NOMINAL CAPACITY (tons) 1 NOMINAL SIZE (Btuh) 18,000 24,000 30,000 36,000 48,000 60,000 OPERATING WEIGHT (lb) 110 110 119 119 151 181 MOISTURE REMOVAL WEIGHT
(Pints/Hr) FINISH GM Motorhome White with Black Trim REFRIGERANT R-410A
Control (Cooling) AccuRater Control
INDOOR FAN Direct Drive Centrifugal
Rpm...Cfm High 900…480 1050…550 1275...840 1275...840 1435...1130 1275...1600 Rpm...Cfm Medium 862...400 900…480 972...740 972...740 1388... 975 972...1220 Rpm...Cfm Low 770...320 862...400 830...640 830...640 1315... 820 830...1040 High Speed Watts 92 92 282 282 425 564 Motor Quantity 111122
Blowers — No. ...Size (in.) 2...6x8 2...6x8 2...6x8 2...6x8 3...6x8 4...6x8
INDOOR COIL Copper Tube, Aluminum Fin
Face Area (sq ft) 2.2 2.2 2.6 2.6 3.0 4.0 No. of Rows 444444 Fins/in. 14.9 14.9 14.9 14.9 14.9 14.9 Circuits 444488
FILTERS Cleanable
Quantity 445568 HEATERS (kW) 2.0 2.0 3.0 3.0 4.0 5.0 AIRSWEEP
Horizontal User select ON/OFF
Ver tical Manual CONTROLS
Control Voltage 24 V
Defrost Method Timed
Dehumidification Ye s
Auto Restart Ye s
Fan Speed High/Medium/Low
Condensate Pump Safety Yes (Accessory)
Filter Change Indication 250 Hours of Indoor Fan Operation
Freeze Protection Indoor coil less than 28 F, resets at 50 F. REFRIGERANT LINES
Connection Type Flare
Liquid Line OD (in.) Vapor Line OD (in.)
Max Line Length For maximum line lengths see condensing unit instructions. CONDENSATE DRAIN
CONNECTION CONDENSATE DRAIN SIZE (in.)
*Field reconfigured to 18,000 Btuh (11/2 tons). See Before Installa-
tion section on page 3 for details.
1
/
2
4.0 7.3 6.0 9.0 13.0 14.5
5
/
8
23345
TXV
3
/
5
/
8
3
/
4
Pipe Thread (MPT)
†The valve connection size is 7/8 inch. The recommended line size
is 11/8 inch.
8
3
/
4
3
/
4
7
/
8
7
/8†
3. Remove inlet grilles from indoor unit by sliding for­ward. Reinstall prior to unit start-up.
IMPORTANT: If necessary, reconfigure the 24,000 Btuh fan coil unit to 18,000 Btuh. Unplug the fan motor at the control box harness and plug into the 40QA018 marked connector.
Step 2 — Select Location — Consult local building
codes and NEC for special installation requirements. See Fig. 3 and 4 for unit dimensions and required clearances.
There are several ways the unit may be installed to different types of ceiling construction. These instructions do not cover all installation methods. As a typical installation, these instruc­tions focus primarily on mounting the unit to metal in new
construction. Plan the installation carefully before you begin. Listed below are some guidelines that should be followed when determining location for the unit.
1. Place unit adjacent to an outside wall if fresh air is required, ensuring that location allows for complete air distribution.
2. Locate the thermostat in an area that is not subjected to drafts or direct sunlight through windows. Locate the thermostat on an internal wall whenever possible.
3. Allow sufficient clearance for airflow, wiring, refriger­ant piping, and servicing unit (Fig. 3 and 4).
4. Make sure the unit is easily accessible to electrical power.
4
Page 5
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Standard unit clearances are as follows:
•0″ on top and rear
•3″ on left side
•12″ on right side
•36″ on bottom
(When facing unit discharge.)
UNIT SIZE
024 108 110 4- 2 036 117 119 4-10 048 149 151 5-11 060 179 181 7- 8 2336 7- 3 2211 7- 6
WEIGHT (lb) A B E F G
Cooling Only Heat Pump ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm
15
/161294 3-10 1169 4- 15/81260 — 1- 95/8549
13
/161493 4- 57/81368 4- 91/21459 — 2- 11/2648
9
/161817 5- 65/81692 5-101/41783 1- 97/8555 3- 31/16992
5
/82302 1-115/8601 4-119/161512
Fig. 3 — Base Unit Dimensions
5
Page 6
Fig. 4 — Fan Coil Unit Clearances
5. Run refrigerant piping as directly as possible and avoid any unnecessary turns or bends.
6. Condensate piping can be directed through the inside wall to an approved drain or straight outside.
NOTE: The piping hole for condensate line must slope at a minimum pitch of
1
/4 in. per foot to ensure proper drainage. If proper pitch cannot be achieved, install accessory condensate pump at this time.
Step 3 — Mount Unit — Refer to Fig. 4 for clearances
and dimensions. Use mounting template included inside box to locate mounting bolt holes, piping holes, electrical connec­tions, and accessory outdoor-air intake, if used.
Select proper type of hardware from the guidelines below.
See Fig. 5.
Solid structure in ceiling must be used due to the weight of the unit.
WOODEN STRUCTURE — Install hanging bolts on a square wooden piece placed over beams.
NEWLY BUILT CONCRETE SLAB — Install hanging bolts with inserts, embedded bolts, etc.
METAL STRUCTURE — Install hanging bolts utilizing an existing angle or by installing a new support angle.
PREVIOUSLY BUILT CONCRETE SLAB — Install hang­ing bolts with expansion anchor.
TO MOUNT UNIT:
1. Remove mounting bracket and reinstall the 2 hex-head bolts (factory-supplied) into each side of indoor unit as shown in Fig. 6. Allow approximately between bolt head and unit.
3
/8-in. space
Fig. 5 — Fan Coil Unit Mounting Methods
(Hardware is Field-Supplied)
2. Determine installation position, paying particular attention to piping lengths, wiring connections, clear­ances, etc. See Fig. 3 for connection locations, Fig. 4 for clearances, and Fig. 7 and 8 for bolt locations.
3. Open knockout if right-side piping connections are required (Fig. 9), by removing the pre-slit portion in the rear of the right side panel with a saw or cutter knife.
4. Mount hanging brackets on ceiling (Fig. 10) for either concealed or exposed bolt hanging position.
5. Lift the unit into place, and fit the hex-head bolts on sides of indoor unit into mounting slots of mounting brackets (Fig. 11). Ensure unit is mounted with a slight tilt to the right rear side for properly drainage.
6. Tighten indoor unit hex-head bolts securely.
6
Page 7
Fig. 6 — Installing Hex-Head Mounting Bolts
in Fan Coil Unit
TO INSTALL THERMOSTAT: If there is at least
3
/8 in. of space between the back of indoor
unit and wall:
1. Route thermostat wires (field-supplied) through slot in right side or rear panel of indoor unit (Fig. 3).
2. Route wires over refrigerant and drain piping as shown in Fig. 12.
IMPORTANT: Do not route wires under the piping, or wires could impede air filter removal.
Step 4 — Connect Refrigerant Piping — Fan coil
units may be connected to outdoor units using field-supplied refrigerant grade piping. Refer to Tables 3A and 3B for the cor­rect size piping. The length of refrigerant pipe depends on the unit placement and building structure; run pipes as directly as possible. For piping requirements over 50 ft of total run, or more than 25 ft of lift, consult the Residential Long Line Appli­cation Guide.
DIMENSIONS (in.)
UNIT SIZE A B C
024 50 036 5813/ 048 719/ 060 92 87 905/
15
/
16 16
16
46 495/ 537/
8
665/
8
Fig. 7 — Fan Coil Unit Hanging Dimensions
DIMENSIONS (in.)
UNIT SIZE B C
024 46 49 036 537/ 048 665/ 060 87 905/
*Exposed mounting holes.
†Reverse bracket holes (concealed mounting).
8 8
Fig. 8 — Mounting Included with
Fan Coil Unit
571/ 701/
571/ 701/
5
/
8 2 4 8
DO NOT BURY MORE THAN 36 IN. OF REFRIGER­ANT PIPE IN THE GROUND. If any section of pipe is buried, there must be a 6-in. vertical rise to the valve con-
8 2 4 8
nections on the outdoor unit. If more than the recommended length is buried, refrigerant may migrate to the cooler, bur­ied section during extended periods of unit shutdown, caus­ing refrigerant slugging and possible compressor damage at start-up.
To connect piping:
1. Install insulation. It is extremely important that all refrigerant lines and the metering device be insulated on heat pumps and multi-splits. On cooling only units, the liquid line may be left uninsulated. Use any accept­able heat resistant closed-cell foam insulation (mini-
3
mum
/8-in. wall thickness). When insulating piping, cap ends and slide insulation over the piping. Insula­tion can also be cut and placed over piping.
2. Run liquid and gas refrigerant piping. a. Run pipes as directly as possible, and avoid any
unnecessary turns and bends.
b. Suspend refrigerant pipes so that the insulation is
not damaged and vibrations are not transmitted to the structure.
c. Leave slack in the refrigerant pipe between the
structure and the unit to absorb vibrations.
d. A piston is shipped in the factory-installed meter-
ing device body (Fig. 13) with the indoor unit. Use Tables 4A-4C to verify that you have the required
piston size for the system being installed.
IMPORTANT: The metering device is factory­installed and only needs to be replaced for long line applications or if the system combination requires it. See Tables 4A-4C. See Fig. 13.
Fig. 9 — Removing Rear Knockout in Side Panel
if Right-Side Piping Connection is Used
e. For special applications such as long lines or raised
elevations, consult the Residential Long Line Application Guide for specific system require­ments. The arrow on the metering device body must face away from the indoor coil.
7
Page 8
f. Refer to the outdoor unit Installation, Start-Up and
Service Instructions for additional information.
g. Install a factory-supplied filter drier near the out-
door unit. On heat pump systems, a bi-flow filter drier must be used.
3. Insulate and caulk wall openings to reduce air infiltra­tion and refrigerant pipe vibrations on structure.
4. Evacuate piping, if necessary. If either refrigerant pip­ing or the indoor coil is exposed to atmospheric condi­tions, it must be evacuated to 1000 microns to eliminate contamination and moisture in the system.
Step 5 — Connect Condensate Drain Line —
Observe all local sanitary codes when installing condensate drains. Refer to Fig. 3 and 14 for drain pipe connection from indoor unit.
1. Use hard polyvinyl chloride (PVC) pipe material with nominal ID of insulation exposed piping inside the conditioned space.
3
/4 in. to connect at drain line. Use pipe
1
/4-in. thick, such as Armaflex insulation, on
Table 4A — Piston and Charge Combinations — Cooling Only Systems
2. To ensure regular flow of condensate water, the drain pipe should be pitched toward an open drain or sump at a downward slope of at least
1
/4-in. per ft.
3. Attach plate with screws under piping hole.
4. Attach drain pipe with nylon wire tie passing through hole (Fig. 15).
NOTE: Do not fasten nylon wire ties tight enough to deform the insulation, as this affects its performance.
5. Insulate condensate drain line(s) that are located in or above an occupied area with a condensate-proof mate­rial such as polyurethane or neoprene.
6. Install an external trap at the end of the condensate line.
NOTE: Should the installation require one, a conden­sate pump may be ordered as a field-installed accessory.
COOLING
INDOOR UNIT SIZE
024
036
048 048 80 12.2 060 060 90 12.5
OUTDOOR UNIT
38HDR
018 57 7.0 024 57 7.75 030 65 10.1 036 70 8.9
PISTON
SIZE
CHARGE (lb)
Table 4B — Piston and Charge Combinations — Heat Pump Systems
HEAT PUMP
INDOOR UNIT SIZE
024
036
048 048 82 73 12.2 060 060 —* 80 12.8
*Size 060 indoor heat pump systems use a TXV (thermostatic expansion valve), part no. EA36YD250.
OUTDOOR UNIT
38QRR
018 49 40 7.5 024 55 43 7.8 030 65 55 12 036 70 63 13
PISTON SIZE
INDOOR
PISTON SIZE
OUTDOOR
CHARGE (lb)
Table 4C — Piston and Charge Combinations — Heat and Cool Systems
HEAT PUMP
INDOOR UNIT SIZE
024
036
048 048 80 12.2 060 060 —* 12.5
*Size 060 indoor heat pump systems use a TXV (thermostatic expansion valve), part no. EA36YD250.
OUTDOOR UNIT
38HDR
018 57 7.0 024 57 7.75 030 65 10.1 036 70 8.9
PISTON
SIZE
CHARGE (lb)
8
Page 9
Fig. 10 — Mounting Hanging Brackets
Fig. 11 — Hanging Fan Coil Unit
NOTE: Teflon Seal must face toward the outdoor heat pump unit.
Fig. 13 — AccuRater Metering Device at Service
Valve (Bypass Type Components),
Heat Pump Systems Only
*Field-supplied.
Fig. 12 — Routing Wires Over Piping
9
Page 10
Step 6 — Make Electrical Connections — Be sure
field wiring complies with local building codes and NEC, and unit voltage is within limits shown in Table 5.
Contact local power company for correction of improper
line voltage.
To avoid personal injury or damage to unit, do not make electrical connections until all power sources are shut down, locked out, and tagged off. Failure to do so could result in personal injury or unit damage.
Operation of unit on improper line voltage constitutes abuse and could affect warranty. Refer to Table 5 for permissible operating limits. Do not install unit in system where voltage may fluctuate above or below permissible limits.
NOTE: Use copper wire only between disconnect switch(es) and unit.
NOTE: Install branch circuit disconnect of adequate size to handle unit starting current per NEC. Locate disconnect within sight of, and readily accessible from, unit, per Section 440-14 of NEC. Some codes allow indoor unit to share disconnect with
Table 5 — Electrical Data*
outdoor unit if disconnect can be locked; check local code before installing in this manner.
1. Route ground and power wires.
According to NEC and most local codes, the unit must have an uninterrupted, unbroken ground to minimize personal injury if an electric fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes. Failure to follow this warning could result in an electric shock, fire, or death.
2. Route line power leads (see Fig. 16) from indoor dis­connect to the fan coil unit. Place wire through hole on the control box (Fig. 17). Connect wire to high voltage terminal board (TB1) and ground screw. When routing the wire in the unit, use care to keep the wire away from refrigerant and condensate piping and any sharp edges. The 208/230-v units are factory wired for 230-v to 24-v transformer operation. For 208-v to 24-v operation, interchange blue (208-v) and red (230-v) wires. Cap any unused wires with wire nuts.
SYSTEM
TYPE
COOLING ONLY
HEAT PUMP
AWG American Wire Gage FLA Full Load Amps MCA Minimum Circuit Amps per NEC Section 430-24 MOCP — Maximum Overcurrent Protection NEC National Electrical Code
UNIT SIZE
024† 0.5 0.53 15 0.50 14 036 1.3 1.60 15 1.30 14 048 1.1 0.5 2.00 15 1.60 14 060 1.3 1.3 3.30 15 2.60 14 024† 0.5 2.00 8.66 9.29 15 9.16 14 036 1.3 3.00 13.00 17.70 20 14.30 14 048 1.0 0.5 4.00 17.40 23.80 25 19.00 12 060 1.3 1.3 5.00 21.70 28.70 30 24.30 10
Motor 1 FLA Motor 2 FLA kW FLA MCA MOCP FLA
LEGEND *All units are 208/230-1-60. Minimum operating voltage is 187, max-
FAN HEATER POWER
MIN WIRE SIZE
(AWG)
imum is 253. Units will operate satisfactorily within this voltage range.
†Electrical data is the same for both the 24,000 Btuh 024 unit and
the 024 unit that has been field-reconfigured for 18,000 Btuh. Refer to Before Installation section on page 3 for reconfiguration details.
10
Page 11
LEGEND
φ Phase
NEC — National Electrical Code
*Standard.
†Accessory item.
**Field supplied.
††Insulate for heat pump application.
Piping Line Voltage 24 V
Thermistor
Fig. 14 — Component Location (Typical Ceiling-Suspended System)
NOTES:
1. All piping must follow standard refrigerant piping techniques.
2. All wiring must comply with the applicable local and national codes.
3. Liquid line need not be insulated (cooling only units).
4. Wiring and piping shown are general points-of-connection guides only and are not intended for a specific installation.
5. Insulate condensate line if run above a conditioned space.
7. Metering device is provided.
11
Page 12
Step 7 — Install Thermostat — These systems use a
3-speed thermostat. The thermostat monitors the system opera­tion and controls the operating mode. To change settings or re­fer to the thermostat Operating Instructions.
Mount thermostat to a wall in the occupied space using 2 field-supplied screws. Locate the thermostat in an area that is not subjected to drafts or direct sunlight through windows. Locate thermostat on an interior wall whenever possible. Figure 18 shows available thermostats.
LEGEND
TB — Terminal Block
Fig. 16 — Line Power Connections
Fig. 15 — Routing Drain Piping
12
Page 13
Step 8 — Make Connections Between Indoor and Outdoor Units —
the indoor and outdoor units to make the system complete. CHECK ACCURATER METERING DEVICE — The cor-
rect AccuRater (bypass type) refrigerant control is required for system capacity optimization. An AccuRater device (see Fig. 19) is supplied with the outdoor unit. Refer to Tables 4A-4C to determine the correct AccuRater piston size and charge combination required for the condenser/evaporator system being installed.
Piston style as shown in Fig. 19 is shipped with the unit. Do not interchange components between the AccuRater device types.
COOLING ONLY SYSTEMS The following connec- tions must be made to the outdoor unit for it to operate as a sys- tem with the indoor unit:
The thermostat is wired between
Route 2 wires of field-supplied 18-gage AWG (American Wire Gage) thermostat cable between the low-voltage terminal block of the fan coil unit and the blue and brown low-voltage wires in the outdoor unit low voltage terminal block. Connect the wires Y1 to Y and C to C. See Fig. 19.
HEAT PUMP SYSTEMS The following connections must be made to the outdoor unit for it to operate as a system with the indoor unit:
Route 5 wires of field-supplied 18-gage AWG thermostat cable between the low-voltage terminal block of the fan coil and the outdoor unit low-voltage terminal block. Connect Y1 to Y, R to R, O to O, W2 to W2, and C to C with the wires. See Fig. 20.
The heat pump unit uses a timed defrost method. The timed defrost can be field set for 30, 50, or 90 minutes. The timed de- frost is factory set for 90 minutes.
LEGEND
ASM Air Sweep Motor ASR Air Sweep Relay EQUIP GND — Equipment Ground FL Fuse Link FPT Freeze Protection Thermostat HP Heat Pump HR Heater Relay HTR Heater HTT Heater Temp. Thermostat IFM Indoor-Fan Motor
NOTES:
1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
2. Wire in accordance with NEC and local codes.
3. Transformer is thermally protected and will reset automatically.
4. Indoor-fan motor(s) are inherently thermally protected.
NEC National Electrical Code PL Plug TB Terminal Board TRAN — Transformer
Terminal (Marked)
Terminal (Unmarked)
Splice
Fig. 17 — Control Circuit Connections Arrangement
Terminal Block
Factory Wiring
Field Power Wiring
Field Control Wiring
Printed Circuit Board
Accessory or Optional Wiring
13
Page 14
AUTO
COOL
HEAT
FLAT THERMOSTAT (FLATSTAT)
CARRIER
COOLING ONLY
HEAT & COOL
(53DFS250-FS)
5-1-1 PROGRAMMABLE THERMOSTAT
COOL
AUTO
HEAT
CARRIER
COOLING ONLY
HEAT & COOL (53DFST2-NP)
Fig. 18 — Thermostats
SLIMLINE THERMOSTAT
CARRIER
HEAT PUMP
COOLING ONLY
HEAT & COOL
(53DFS250-SL)
14
Page 15
Step 8 — Make Connections Between Indoor and Outdoor Units —
the indoor and outdoor units to make the system complete. CHECK ACCURATER METERING DEVICE — The cor-
rect AccuRater (bypass type) refrigerant control is required for system capacity optimization. An AccuRater device (see Fig. 19) is supplied with the outdoor unit. Refer to Tables 4A-4C to determine the correct AccuRater piston size and charge combination required for the condenser/evaporator system being installed.
Piston style as shown in Fig. 19 is shipped with the unit. Do not interchange components between the AccuRater device types.
COOLING ONLY SYSTEMS — The following connec­tions must be made to the outdoor unit for it to operate as a sys­tem with the indoor unit:
Route 2 wires of field-supplied 18-gage AWG (American Wire Gage) thermostat cable between the low-voltage terminal block of the fan coil unit and the blue and brown low-voltage wires in the outdoor unit low voltage terminal block. Connect the wires Y1 to Y and C to C. See Fig. 20.
HEAT PUMP SYSTEMS — The following connections must be made to the outdoor unit for it to operate as a system with the indoor unit:
Route 5 wires of field-supplied 18-gage AWG thermostat cable between the low-voltage terminal block of the fan coil and the outdoor unit low-voltage terminal block. Connect Y1 to Y, R to R, O to O, W2 to W2, and C to C with the wires. See Fig. 21.
The thermostat is wired between
The heat pump unit uses a timed defrost method. The timed defrost can be field set for 30, 50, or 90 minutes. The timed de­frost is factory set for 90 minutes.
38HDR018-060
38QRR018-060
Fig. 19 — AccuRater (Bypass Type)
Metering Device Components
15
Page 16
Fig. 20 — Cooling System Wiring Diagram
16
Page 17
Fig. 21 — Heat Pump Wiring Diagram
17
Page 18
START-UP
Never operate unit without a filter or with grille removed; damage to the unit or personal injury may result.
Make the following checks and complete the Start-Up Checklist on page CL-1 before system start-up. Also refer to the condensing unit Installation, Start-Up and Service Instruc­tions for system start-up instructions and refrigerant charging methods.
1. Check condensate drainage system: a. Remove grille and frame from the unit.
b. On the opposite side of the drain connection, insert
a water bottle up into the fan coil unit and fill drain pan. Refer to Fig. 22. Water must flow steadily; if not, check the pipe slope or inspect for any pipe restrictions.
2. Make sure that all wiring connections are correct and that they are tight.
3. Check that all barriers, covers, and panels are in place. Ensure that the filters and return-air grilles have been installed and that the discharge louvers are positioned correctly.
After Extended Shutdown — If the system has been
turned off for more than 12 hours and a crankcase heater is be­ing used, turn on the indoor and outdoor unit disconnect switches to supply power to the system for 12 hours BEFORE starting the system.
Seasonal Changeovers — When changing heat pump
system from cooling to heating or heating to cooling, or before starting cooling only system after it has been out of use for the winter season, perform the following steps BEFORE starting the system:
1. Inspect and clean the outdoor unit, particularly the coil.
2. Clean or replace the air filters in the indoor unit.
3. Clean the indoor unit drain pan and drain pipe, and remove any obstructions.
4. If the outdoor unit is equipped with a crankcase heater, turn on indoor and outdoor unit disconnect switches to supply power to the system 12 hours before starting the system.
Adjusting Airflow
AUTOMATIC AIR SWEEP — All units are equipped with an air sweep feature which directs the airflow louvers up and down to provide optimum room air circulation. The air sweep function can be controlled by the toggle switch located on the lower right corner of the unit. If using a thermostat with an air sweep switch, see Fig. 20 and 21 for wiring modifications.
Operating Mode Memory — After the system is
turned off or after a power failure, the system remains in the last operating mode selected. When the system is turned back on, or when power is automatically restored, operation contin­ues in the same operating mode as when the system shut down.
Automatic Operation (Auto.) Mode — If auto.
mode is selected, the system automatically switches over the operating mode from heating to cooling, or from cooling to heating (heat pump system only) depending on the selected temperature. Auto. mode also controls fan speed if not manual­ly overridden.
NOTE: Between the cooling cycle and the heating cycle there is a neutral zone of approximately 2° F above and 2° F below the selected temperature when only the fan is operating.
Operating Sequence — Ceiling-suspended fan coil
units have a relay board which controls system operation in re­sponse to a room thermostat. The user may manually select any one of 3 fan speeds for unit operation. Ceiling-suspended sys­tems may be equipped with an accessory power ventilation kit and/or condensate pump.
FAN OPERATION — Fan coils are capable of 3-speed opera­tion. See thermostat instructions for fan speed selection. When the fan(s) is operating in medium or high speed and the unit is equipped with the power ventilation kit, the ventilation fan will operate to provide fresh air.
COOLING MODE OPERATION — When the room ther­mostat senses a demand for cooling, the fan coil relay board is energized. The indoor fan(s) will start in the selected speed (if it is not already operating). The reversing valve (heat pump only) will energize for cooling operation.
The internal condensate pump (if so equipped) runs when­ever the reversing valve is energized (heat pump only) and/or the unit is in cooling. As long as the condensate float switch and freeze protection thermostat are closed, the cooling relays in the fan coil unit will close. This energizes the compressor and outdoor fan in the outdoor unit. The compressor will con­tinue to operate until the room thermostat is satisfied. When the cooling demand is satisfied, the compressor and outdoor fan will stop. If the system is in the AUTO. position, the indoor fan will stop with the compressor. If the unit has the accessory ven­tilation kit, the ventilation fan will operate whenever the indoor fan is set for medium or high speed.
HEAT PUMP OPERATION — When the room thermostat senses a demand for heating the indoor fan will start in the selected speed (if not already operating), and the reversing valve will not be energized. The internal condensate pump (if supplied) and freeze protection thermostat are not operated during heating operation. The control relay (CR2) closes, and the compressor and outdoor fan are energized through the de­frost board (DFB), which is located in the outdoor unit. The microprocessor logic in the DFB is energized when the com­pressor starts, and the defrost timer runs. Once every 90 min­utes (factory default setting) of compressor run time, the DFB logic checks the defrost thermostat (DFT). If the DFT is open, the unit continues in heating operation. If the DFT is closed, the DFB switches the unit to defrost mode. The timing on the DFB may be set at either 30, 50, or 90 minutes.
DEFROST (Heat Pump Only) — The DFB energizes the RVS (reversing valve solenoid), and the reversing valve switches to the cooling position. The K1 relay on the DFB opens and the outdoor fan stops. The W2 contact on the DFB is also energized, which in turn energizes the defrost relay on the fan coil relay board, turns off the electric heater and stops the indoor fan.
The DFB logic checks the 10-minute defrost timer and the DFT. If the DFT opens in less than 10 minutes, the DFB switches the unit back to normal heating operation. If the DFT remains closed, the DFB switches the unit back to heating op­eration after 10 minutes. When the DFB changes back to heat­ing mode, the RVR (reversing valve relay) is deenergized and the reversing valve switches back to heating operation. Both the outdoor and indoor fans come back on, and if necessary, the electric heater also turns on.
SYSTEM SAFETIES — The system is equipped with the following safety devices to protect system components:
Indoor coil freeze protection thermostat — If a coil temper­ature of 28 F or lower is sensed, the compressor and outdoor fan will be shut down until the coil temperature exceeds 28 F. The indoor fan will continue to run.
Condensate float switch (units equipped with accessory condensate pump, cooling cycle only) — If the level of con­densate in the drain pan rises too high, the condensate float switch will turn the system off.
18
Page 19
SPECIAL OPERATION, HEATING — Outdoor cooling units may be matched with heat pump ceiling-suspended fan coil units to provide supplemental electric heat. All other operation is the same as a cooling-only system, except these units have heating capability as follows:
When the room thermostat initiates a call for heating, the electric heater is turned on. The indoor unit fan will start at the same time, if it was not already running.
When the heating requirement is satisfied, the room thermo­stat will open, and the heater will turn off.
CLEANING AND MAINTENANCE
To avoid the possibility of electric shock, before performing any cleaning and maintenance operations, always turn off power to the system by pressing the mode button on the remote thermostat until the display shows “OFF,” and turn­ing off the outdoor disconnect switch located near the out­door unit. If the indoor unit is on a separate switch, be sure to turn this disconnect off as well.
Do not wash filter in water over 120 F (to avoid shrinkage). Do not expose filter to fire (to avoid fire damage). Do not expose filter to direct sunlight. Clean filter more frequently when air is extremely dirty.
For proper system operation, perform the cleaning and maintenance operations in Table 6.
Lubrication — The indoor-fan, automatic air sweep, and the
outdoor-fan motors are factory lubricated and require no oiling.
Fig. 22 — Inserting Water into Drain Pan
Air Filters (Fig. 23)
Operating the system with dirty air filters may damage the indoor unit and, in addition, can cause reduced cooling per­formance, intermittent system operation, frost build-up on the indoor coil, and blown fuses. Inspect and clean or replace the air filters monthly.
REMOVE AIR FILTERS — Remove filters by pulling them straight out.
CLEAN OR REPLACE FILTERS — Filters can be vacu­umed or washed in warm water. Shake filter to remove any ex­cess water, and replace by sliding filter behind grille until filter snaps in place. Refer to Fig. 23.
If the filter has begun to break down or is torn, replace it.
Replacement filters are available through your dealer.
Table 6 — Cleaning and Maintenance Schedule
TASK MONTHLY QUARTERLY YEARLY
INDOOR UNIT
Clean Air Filters X Clean Drain Pipe X Clean Condensate Drain Pan X Clean Indoor Coil X Clean Indoor Unit Front Panel X
OUTDOOR UNIT
Clean the Fins From Outside X Open the Unit and Clean Fins Inside X Remove Dust From Electrical Parts X Check Electrical Connections are Tight X Clean Outdoor Fan X Clean Outdoor Coil X Check that Outdoor Fan Assembly is Tight X Clean Drain Pan X
NOTE: Maintenance procedures for the outdoor units are in the individual unit installation instructions.
19
Page 20
Clean Indoor Unit Bottom Panel — If the bottom panel
of the unit becomes dirty or smudged, wipe the outside of the panel with a soft dry cloth. Use a mild liquid detergent and wipe off carefully with a dry cloth.
Clean Indoor Coil — To clean the coil, remove indoor unit
bottom panel and vacuum the coil fins, using care not to bend or damage fins.
Clean Outdoor Coil (Outdoor Unit)
Some metal parts and sharp fins of outdoor unit coil can cause personal injury during cleaning. Clean coil carefully.
To clean the outdoor coil:
1. Remove any dirt or obstruction from discharge opening.
2. Use a garden hose to spray water on the coil. Debris that collects between coil fins inhibits heat transfer — direct the water spray between coil fins to flush out debris.
Clean Condensate Drains — Clean all drains and drain
pans at the start of each cooling season. Check the flow by pouring water into the drain.
CLEAN OR REPLACE DRAIN PAN
1. Place a plastic sheet on the floor to catch any water that may spill from drain pan.
2. Remove the intake grille and distribution assembly (attached).
3. Remove the condensate water in the drain pan by let­ting water drain into a 3-gallon bucket.
Do not use a screwdriver to pry drain pan out of assembly — it could damage the pan.
4. Remove the 4 screws holding the drain pan.
5. Carefully hold the drain pan to remove it from the assembly.
SERVICE
When servicing unit, turn off all electric power to unit to avoid shock hazard or injury from rotating parts.
Do not vent refrigerant to atmosphere when servicing unit. Recover refrigerant during system repair or unit removal.
Fig. 23 — Cleaning Filters
Before Calling for Service —
call by doing the following:
1. Be sure main power to system is turned on.
2. Press Mode button until OFF is displayed. Wait 5 min­utes.
3. Press Mode button until either COOL or HEAT is dis­played (as desired).
4. Adjust thermostat set point to desired room tempera­ture. If system starts within a few minutes, service may not be necessary. If system does not operate properly, check Table 7 for typical solutions.
IF SYSTEM FAILS TO OPERATE — Be sure:
• unit ON/OFF switch is in ON position
• fuse or circuit breaker is not tripped
Save the cost of a service
FRESH AIR INSTALLATION OPTION
The units have an installation option, which allows for field installation of fresh air ventilation. Plan the installation careful­ly. Before beginning, measure carefully and follow acceptable building practices, NEC, and local codes.
Ventilation-Air Accessory — Refer to ventilation air
accessory installation instructions.
TROUBLESHOOTING
If the under-ceiling fan coil unit fails to start or operate properly, sometimes the problem is minor and can be handled without a service call. Refer to Table 7 for some common prob­lems, causes, and typical solutions. See Fig. 20 and 21 for addi­tional system troubleshooting details. If the problem cannot be corrected, contact a local dealer for further assistance.
20
Page 21
Table 7 — Troubleshooting
PROBLEM CAUSE TYPICAL SOLUTION
System Does Not Start. Blown fuse or circuit breaker tripped at building
System Does Not Cool Properly. Air filter(s) in indoor unit is dir ty or needs to be
System Does not Heat Properly. Air filter(s) in indoor unit is dirty or needs to be
Ice or frost has Formed on Indoor Coil.†
Insufficient Airflow. Air filter(s) in indoor unit is dirty or needs to be
*If fuse blows or circuit breaker trips again after first start attempt, DO NOT attempt to start system again.
Contact your local dealer for assistance.
†When outdoor temperature is approximately 55 F or below, indoor coil frosting may occur when system is
operated in cooling or maximum dehumidification mode. Units are not intended to operate below 55 F without appropriate accessories.
power entry. Indoor and/or outdoor unit disconnect switch is off. Turn on disconnect switch(es). Thermostat is set to night mode. Cancel mode using Day/Night button on thermostat. Power failure. Restore power. Unit is in off mode. Press Mode button on thermostat until thermostat
Three-minute time delay is running. Wait for 3 minutes. Temperature is above or below the selected
temperature.
replaced. Temperature is set too high or too low. Reset temperature to desired comfort setting using
Outdoor unit outdoor coil restricted. Remove obstruction. Fan speed is set too low. Adjust fan speed to high or auto. using the Fan
replaced. Temperature is set too high or too low. Reset temperature to desired comfort setting using
Outdoor unit outdoor coil restricted. Remove obstruction. Fan speed is set too low. Adjust fan speed to high or auto. using the Fan
Outdoor unit outdoor coil is frosted up. Check manual defrost timer setting and adjust as
Low outdoor-air temperature. Run system in fan-only mode until frost is gone. Air filter(s) in indoor unit is dirty or needs to be
replaced.
replaced. Fan coil unit coil is blocked. Clean air discharge louvers.
Replace fuse or reset circuit breaker.*
displays the desired unit mode.
Select new temperature using the thermostat.
Clean or replace air filter(s).
the thermostat.
button on the thermostat. Clean or replace air filter(s).
the thermostat.
button on the thermostat.
necessary.
Clean or replace air filter(s).
Clean or replace air filter(s).
21
Page 22
START-UP CHECKLIST
Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including:
A large selection of product, theory, and skills programs are available, using popular video-based formats and materials. All include video and/or slides, plus companion book.
Classroom Service Training which includes “hands-on” experience with the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting and fewer callbacks. Course descriptions and schedules are in our catalog.
SERVICE TRAINING
• Unit Familiarization • Maintenance
• Installation Overview • Operating Sequence
CALL FOR FREE CATALOG 1-800-644-5544
[ ] Packaged Service Training [ ] Classroom Service Training
Copyright 2006 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 3 d 2 c
Catalog No. 02-40QA0007-SI Printed in U.S.A. Form 40QA-7SI Pg 22 706 3-06 Replaces: 40QA-5SI
Page 23
I. PRELIMINARY INFORMATION
START-UP CHECKLIST
OUTDOOR UNIT: MODEL NO. ___________________
INDOOR UNIT: MODEL NO. _____________________
ACCESSORIES: __________________________________________________________________________________
PISTONS: INDOOR SIZE: ____________ OUTDOOR SIZE: ____________
REFRIGERANT PIPING: EQUIVALENT LINE LENGTH: ____________
LIFT: FAN COIL ABOVE OUTDOOR UNIT? ____________
FAN COIL BELOW OUTDOOR UNIT? ____________
SERIAL NO. ___________________________________
SERIAL NO. ___________________________________
II. PRE-START-UP
INDOOR UNIT (REFER TO OUTDOOR UNIT INSTALLATION INSTRUCTIONS FOR OUTDOOR UNIT PRE-START-UP FUNCTIONS)
IS THERE ANY SHIPPING DAMAGE? ____________
IF YES, WHERE? ____________________________________
WILL THIS DAMAGE PREVENT UNIT START-UP? ____________
IS POWER SUPPLY CORRECT? ____________
HAS GROUND WIRE BEEN CONNECTED? ____________
HAS THE CORRECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED? ____________
ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? ____________
IS THE DISCONNECT SWITCH INSTALLED WITHIN SIGHT OF THE UNIT? ____________
IS THE LOW-VOLTAGE CABLE (INDOOR TO OUTDOOR UNIT) RUN AND CONNECTED PROPERLY? ____________
HAS CONDENSATE DRAIN BEEN RUN, SLOPED AND TRAPPED PROPERLY? ____________
IS FILTER(S) IN PLACE? ____________
IS UNIT MOUNTED LEVEL? ____________
IS HEATING PISTON INSTALLED (FIG. 13), THE CORRECT SIZE, AND IN THE CORRECT DIRECTION? ____________
III. PIPING
IS A LIQUID LINE SOLENOID INSTALLED IF REQUIRED BY LONG-LINE APPLICATIONS ? ____________
IS FILTER DRIER INSTALLED AT THE OUTDOOR UNIT? ____________
HAVE LEAK CHECKS BEEN MADE AT THE COMPRESSOR, OUTDOOR UNIT, FLARE CONNECTIONS, FILTER DRIERS, AND FUSIBLE PLUGS WITH A LEAK DETECTOR?* ____________
*FIELD PIPING AND ALL TUBING CONNECTIONS MUST BE LEAK TESTED BY THE PRESSURE METHOD DE-
SCRIBED IN CARRIER GENERAL TRAINING FOR AIR CONDITIONING MANUAL (GTAC2), MODULE 5. USE R-22 AT APPROXIMATELY 25 PSIG BACKED UP WITH AN INERT GAS TO REACH A TOTAL SYSTEM PRESSURE NOT TO EXCEED 245 PSIG.
CL-1
Page 24
-
START-UP CHECKLIST (cont)
HAS PIPING SYSTEM BEEN EVACUATED TO 1000 MICRONS (IF REQUIRED)? ____________
HAS SYSTEM CHARGE BEEN WEIGHED IN (IF REQUIRED)? ____________
HAVE SERVICE VALVES BEEN FULLY BACKSEATED? ____________
CHECK VOLTAGE: IS VOLTAGE WITHIN RANGE SHOWN FOR UNIT (WITH UNIT OPERATING)?
OUTDOOR ____________ INDOOR ____________
IV. START-UP
IF UNIT HAS A CRANKCASE HEATER, HAS IT BEEN ON FOR 24 HOURS? ____________
MEASURE AND RECORD THE:
AIR ENTERING OUTDOOR UNIT: ____________ F
AIR ENTERING INDOOR UNIT: ____________ F
DISCHARGE LINE TEMPERATURE: ____________ F
VAPOR LINE TEMPERATURE: ____________ F
MEASURE AND RECORD THE:
VAPOR LINE PRESSURE: ____________ PSIG
DISCHARGE PRESSURE: ____________ PSIG
START-UP CHECKLIST
I. PRELIMINARY INFORMATION
OUTDOOR UNIT: MODEL NO. SERIAL NO. INDOOR UNIT: MODEL NO. SERIAL NO.
ACCESSORIES: __________________________________________________________________________________
PISTONS (38HDC and 38QRC SYSTEMS ONLY): INDOOR SIZE: OUTDOOR SIZE (38QRC SYSTEMS ONLY):
REFRIGERANT PIPING: EQUIVALENT LINE LENGTH: (IF OVER 50 FT)* LIFT: FAN COIL ABOVE OUTDOOR UNIT (IF OVER 25 FT)*?
FAN COIL BELOW OUTDOOR UNIT (IF OVER 25 FT)*?
*APPLIES ONLY TO 38HDC AND 38QRC UNITS USING LONG-LINES APPLICATIONS. MAXIMUM EQUIVALENT
LINE LENGTH FOR 38HDS SYSTEMS IS 50 FT. MAXIMUM LIFT ON 38HDS APPLICATIONS IS 30 FT FROM LOW­EST SYSTEM POINT TO HIGHEST SYSTEM POINT.
PRE-START-UP
INDOOR UNIT (REFER TO OUTDOOR UNIT INSTALLATION INSTRUCTIONS FOR OUTDOOR UNIT PRE-START-UP FUNCTIONS)
IS THERE ANY SHIPPING DAMAGE? IF YES, WHERE? WILL THIS DAMAGE PREVENT UNIT START-UP? IS POWER SUPPLY CORRECT? (115-V FOR 40QAB024-048, 115 V UNITS; OR 208/230 V FOR 40QAB024-
048, 208/230 V UNITS AND ALL 40QAB060 AND 40QAE024-060 UNITS. ALL SYSTEMS REQUIRE SINGLE-PHASE POWER)
HAS GROUND WIRE BEEN CONNECTED? HAS THE CORRECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED? ARE POWER WIRES
TO THE UNIT SIZED AND INSTALLED PROPERLY? IS THE DISCONNECT SWITCH IN-
STALLED IN SIGHT FROM THE UNIT?
IS THE LOW-VOLTAGE CABLE (INDOOR TO OUTDOOR UNIT) RUN AND CONNECTED PROPERLY?
Copyright 2006 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 3 d 2 c
Catalog No. 02-40QA0007-SI Printed in U.S.A. Form 40QA-7SI Pg CL-2 706 3-06 Replaces: 40QA-5SI
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - -
Loading...