Carrier 40QA user guide manual

Ceiling-Suspended Fan Coil Units
Installation, Start-Up
and Service Instructions
40QA024-060
CONTENTS
Page
SAFETY CONSIDERATIONS ................. 1
INSTALLATION ............................1-13
Step 1 − Complete Pre-Installation Checks ...3
• UNPACK UNIT
• BEFORE INSTALLATION
Step 2 − Select Location ....................4
Step 3 − Mount Unit ........................6
• TO MOUNT UNIT
• TO INSTALL REMOTE THERMOSTAT
Step 4 − Connect Refrigerant Piping ........7
Step 5 − Connect Condensate Drain Line ...10
Step 6 − Make Electrical Connections ......11
Step 7 − Install Remote Thermostat ........12
Step 8 — Make Connections Between
Indoor and Outdoor Units ................12
• COOLING ONLY SYSTEMS
• HEAT PUMP SYSTEMS
START-UP ...............................13-15
After Extended Shutdown ..................13
Seasonal Changeovers .....................13
Adjusting Airflow ..........................14
Operating Mode Memory ...................14
Automatic Operation (Auto.) Mode ..........14
Operating Sequence .......................14
• FAN OPERATION
• COOLING MODE OPERATION
• HEAT PUMP OPERATION (40QAE ONLY)
• DEFROST (40QAE ONLY)
• SYSTEM SAFETIES
• SPECIAL OPERATION, HEATING
CLEANING AND MAINTENANCE ...........15,16
Lubrication ................................15
To Remove and Clean or Replace
Air Filters ...............................15
• TO REMOVE AIR FILTERS
• TO CLEAN OR REPLACE FILTERS
To Clean Indoor Unit Bottom Panel .........16
To Clean Indoor Coil .......................16
To Clean Outdoor Coil (Outdoor Unit) .......16
To Clean Condensate Drains ................16
• TO CLEAN OR REPLACE DRAIN PAN
SERVICE ..................................16
Before Calling for Service ..................16
• IF SYSTEM FAILS TO OPERATE
FRESH AIR INSTALLATION OPTIONS .......16
Ventilation-Air Accessory ...................16
TROUBLESHOOTING .....................17-20
START-UP CHECKLIST ..............CL-1, CL-2
SAFETY CONSIDERATIONS
Installing and servicingair-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install or service air-conditioning equipment.
Untrained personnel can perform basic maintenance, such as cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in lit­erature and on tags and labels attached to unit.
Follow all safetycodes. Wearsafety glasses and work gloves. Use quenching cloth for brazing operations. Have fire ex­tinguisher available. Read these instructions thoroughly.Con­sult local building codes and National Electrical Code (NEC) for special installation requirements.
Before installing or servicing system, always turn off main power to system. There may be more than one dis­connect switch. Turn off accessory heater power if ap­plicable. Electrical shock can cause personal injury.
INSTALLATION
The 40QAB ceiling-suspended fan coil unit (Fig. 1) is typi­cally installed with the 38HDC or 38HDS outdoor condens­ing unit, and the 40QAE unit is typically installed with the 38QRC heat pump.
NOTE: The 40QAE unit can also be installed with either the 38HDC or HDS condensing units. Refer to Table 1 to make sure the correct indoor unit(s) is installed with the correct outdoor unit.
Installation instructions for 40QA fan coil units are con­tained in this manual. Refer to this manual for proper in­stallation of the complete system. Note that the outdoor units are shipped with installation and service instructions for ba­sic installation of the outdoor section. Be sure to make the connections in Cooling-Only Systems and Heat Pump Sys­tems sections on page 12 of this literature so that the unit will operate properly with the 40QA mircoprocessor control system.
Fig. 1 — 40QA Ceiling-Suspended Fan Coil Unit
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 3d 2d
PC 111 Catalog No. 534-052 Printed in U.S.A. Form 40QA-3SI Pg 1 4-96 Replaces: 40QA-1SI
Table 1 — Acceptable System Combinations for Indoor and Outdoor Units
OUTDOOR UNIT INDOOR UNIT
Type Model Number 38 Type Model Number 40QA
HDC018 HDC024 B024 HDC030 B036 HDC036 B036 HDC048 B048
Cooling Only
Cooling Only
Multi-Split*
Heat Pump
*Multi-split systems can accommodate up to 4 fan coil units of vari-
ous types with one condensing unit.The combinations listed in this tableare those combinations which use only ceiling-suspendedunits (not combined with any other type of fan coil unit). Refer to system presale literature or Price Pages for more details on other system combinations.
†Units must be field reconfigured for 1
tion. See Before Installation section on page 3 for details.
HDC060 B060 HDC018 HDC024 E024 HDC030 E036 HDC036 E036 HDC048 E048 HDC060 E060 HDS024
HDS048
HDS024
HDS048
QRC018 QRC024 E024 QRC030 E036 QRC036 E036 QRC048 E048 QRC060 E060
1
⁄2ton (18,000 Btuh) opera-
B024
Cooling Only
E024
Heat Pump
(2) B024†
Cooling Only
Heat Pump
Heat Pump
**One circuit (2 units) unit must be field reconfigured for 1
(18,000 Btuh) operation. See Before Installation section on page 3 for details.
NOTES:
1. If your particular application requires a heat pump outdoor unit matched with a cooling-only fan coil unit, contact your local rep­resentative for more details.
2. Numbers in ( ) indicate quantities when there is morethan one fan coil unit in the system.
(4) B024† (3) B024** (2) B024 (2) E024† (4) E024† (3) E024** (2) E024
E024
1
⁄2ton
Be sure unit will be operated within the application guide­lines shown in Table 2. When installing the 38QRC or HDC units, note that for cooling operation when the outdoor-air temperature is below 55 F,the accessory low ambient or win­ter start kit will be required. Systems using 38HDS units can operate down to 40 F outdoor-airtemperature as shipped from the factory. If operation at outdoor ambients between 40 F and −20 F is desired, an accessory winter start kit will be required for the 38HDS unit.
To install this system, you will need:
• 1 (or more)* 40QAB or 40QAE fan coil unit(s) with stand-
ard remote thermostat
• 1 38HDC, HDS, or QRC outdoor unit
• 1 low ambient kit or 1 winter start kit (if required for your
application)
• 1 power ventilation kit (if required for your application)
• 1 condensate pump kit (if required for your application) *More than 1 fan coil unit may be used with the 38HDS
multi-split units. Refer to 38HDS unit Price Pages for com­plete details.
NOTE: Refrigerant pipe, drain pipe, wire, etc., are also re­quired to install unit and are field-supplied.
Be sure you have the required parts before beginning instal­lation. The 40QA unit utilizes a standard 24 v control sys­tem (see Tables 3Aand 3B) for ultimate flexibility while de­livering optimal levels of comfort and efficiency. Be sure to follow these instructions carefully to obtain proper function­ing of the unit.
Table 2 — Application Range
COOLING
Maximum Minimum
Indoor Outdoor Indoor Outdoor
95FDB 125FDB 67FDB 55FDB* 71FWB 57FWB 40FDB†
HEATING (Heat Pump Systems Only)
Maximum Minimum
Indoor Outdoor Indoor Outdoor
80FDB 75FDB 55FDB 220FDB 71FWB 65FWB
LEGEND
DB — Dry Bulb WB — Wet Bulb
*This value is for 38HDC, QRC systems. The 38HDC or QRC unit
may be equipped with an accessory low-ambient control or winter start kit that will allow operation down to 220 F.
†This value is for38HDS systems. The 38HDSunit may be equipped
with an accessory winter start kit that will allow operation down to
−20 F.
2
Table 3A — Physical Data, 40QAB Cooling-Only Units
UNIT 40QAB 024* 024 036 048 060 NOMINAL CAPACITY (Tons) 1
1
2
23 4 5
NOMINAL SIZE (Btuh) 18,000 24,000 36,000 36,000 60,000 OPERATING WEIGHT (lb) 108 108 117 149 179 MOISTURE REMOVAL RATE (Pints/Hr) 5.8 7.1 9.5 13.4 15.1
FINISH GM Motorhome White with Black Trim REFRIGERANT R-22
Control (Cooling) AccuRaterT Piston in Fan Coil Unit/TXV in Condensing Unit System Charge Required (lb)† 3.7 5.5 5.6/5.4** 7.4 13.6
INDOOR FAN Direct Drive Centrifugal
Rpm...Cfm High 862...500 862...500 1275...840 1435...1200 1275...1600 Rpm...Cfm Medium 690...400 690...400 972...740 1388...1160 972...1220 Rpm...Cfm Low 552...320 552...320 830...640 1315...1100 830...1040 High Speed Watts 92 92 282 425 564 Quantity...Motor Hp 1...
Blowers — No. ...Size (in.) 2...6 x 8 2...6 x 8 2...6 x 8 3...6 x 8 4...6 x 8
INDOOR COIL Copper Tube, Aluminum Fin
Face Area (sq ft) 2.2 2.2 2.6 3.0 4.0 No. of Rows 44 4 4 4 Fins/in. 14.9 14.9 14.9 14.9 14.9 Circuits 44 4 8 8
FILTERS Cleanable
(Quantity) Size (in.) (4) 12 x 8
AIRSWEEP
Horizontal Vertical Automatic
CONTROLS
Control Voltage 24-v Provided in Control Auto. Restart Yes Fan Speed High/Medium/Low Condensate Pump Safety Yes (Accessory) Outdoor Coil High Temperature (Cooling Modes) Outdoor Coil Temperature greater than 144 F; Resets at 104 F Filter Change Indication 250 Hours of Indoor Fan Operation (through thermostat)
REFRIGERANT LINES
Connection Type Flare Liquid Line OD (in.) Vapor Line OD (in.) Maximum Length (ft) 200/50 \ Maximum Lift Fan Coil (Above Outdoor) (ft) 65/30 \ Maximum Lift Fan Coil (Below Outdoor) (ft) 150/30 \
1
15
5
8
1...1⁄
3
4
15
5
8
1...1⁄
6
(5) 105⁄8x83⁄
3
8
3
4
4
2...1⁄
15
(4) 105⁄8x83⁄
(2) 12 x 83⁄
7
⁄8††
4
4
2...1⁄
6
(6) 12 x 83⁄
7
⁄8††
CONDENSATE DRAIN CONNECTION Pipe Thread (MPT) CONDENSATE DRAIN SIZE (in.)¶
LEGEND
TXV — Thermostatic Expansion Valve
*Field reconfigured to 18,000 Btuh (1
tion section on this page for details.
†Outdoor unit is shipped with a full charge for the smallest system
configuration. Refer to unit nameplate (on the unit) for details on specific system charge required.
**When matched with a size 030 outdoor unit/when matched with a
size 036 outdoor unit.
1
⁄2tons). See Before Installa-
††The valve connection size is
7
is
⁄8inch.
\ Whenmatched with a 38HDC coolingonly unit/when matched with
a 38HDS multi-split unit.
¶ Flexible tubing (
is used.
3
4
3
⁄4inch. The recommended line size
5
⁄8in.)isrequired when accessory condensate pump
4
Step 1 — Complete Pre-Installation Checks
UNPACK UNIT — Store fan coil unit in the original pack­aging until it is moved to the final site for installation. When removing unit from carton, lift unit by its 4 corners; DO NOT lift unit by its plastic parts.
INSPECT SHIPMENT — Upon receipt of shipment, check fan coil unit for damage. Forward claim papers directly to the transportation company. Manufacturer is not responsible for damage incurred in transit.
Check all items; if any item is missing, notify your Car­rier distributor. To prevent loss or damage, leave all parts in original packages until installation.
BEFORE INSTALLATION — Perform the following steps before installing indoor fan coil unit. Place the indoor unit upside down on the floor, then:
1. Remove side panels by sliding forward, then away from
sides of unit (Fig. 2). Reinstall prior to unit start-up.
2. Remove air filters from inlet grilles; then remove and re-
tain screws securing inlet grilles to indoor unit. Reinstall prior to unit start-up.
NOTE: Dimensions shown in brackets [ ] are in mm.
Fig. 2 — Removal of Mounting Brackets
from Indoor Unit
3
Table 3B — Physical Data, 40QAE Heat Pump Units
UNIT 40QAE 024* 024 036 048 060 NOMINAL CAPACITY (Tons) 1
1
2
23 45
NOMINAL SIZE (Btuh) 18,000 24,000 36,000 48,000 60,000 OPERATING WEIGHT (lb) 110 110 119 151 181 MOISTURE REMOVAL RATE (Pints/hr) 5.8 7.1 9.5 13.4 15.1 FINISH GM Motorhome White with Black Trim REFRIGERANT R-22
Control (Cooling) AccuRater® Piston in Fan Coil Unit Control (Heating) AccuRater Piston in Outdoor Unit Holding Charge (lb)† 2.0 2.0 2.0/2.5** 2.5 2.5
INDOOR FAN Direct Drive Centrifugal
Rpm...Cfm High 862...480 862...480 1275...870 1435...1130 1275...1600 Rpm...Cfm Medium 690...400 1200...480 972...750 1388...975 972...1220 Rpm...Cfm Low 552...320 1050...400 830...630 1315...820 830...1040 High Speed Watts 92 92 282 425 564 Motor Quantity...Hp 1... Blowers Quantity...Size (in.) 2...6 x 8 2...6 x 8 2...6 x 8 3...6 x 8 4...6 x 8
INDOOR COIL Copper Tube, Aluminum Fin
Face Area (sq ft) 2.2 2.2 2.6 3.0 4.0 No. of Rows 44 4 4 4 Fins/in. 14.9 14.9 14.9 14.9 14.9 Circuits 44 4 8 8
FILTERS Cleanable
Quantity...Size (in.) 4...12 x 8
AIRSWEEP
Horizontal Vertical
1
15
3
1...1⁄
15
4
4...12 x 83⁄45...105⁄8x83⁄
1...1⁄
6
4
2...1⁄
15
4...105⁄8x83⁄
2...12 x 83⁄
4
4
2...1⁄
6
6...12 x 83⁄
4
Automatic
HEATER (kW) 2.0 2.0 3.0 4.0 5.0 CONTROLS
Defrost Method Timed Manual Defrost Diagnostics Yes Dehumidification Yes Auto. Restart Yes Control Voltage 24-v Provided in Control High Indoor Coil Temperature Indoor Coil Temperature greater than 144 F; Resets at 104 F Fan Speed High/Medium/Low Freeze Protection Indoor Coil Less than 28 F, Resets at 50 F Condensate Pump Safety Yes (Accessory) Outdoor Coil High Temperature (Cooling Modes) Outdoor Coil Temperature greater than 144 F; Resets at 104 F Filter Change Indication 250 Hours of Indoor Fan Operation (through thermostat)
REFRIGERANT LINES
Connection Type Flare Liquid Line OD (in.) Vapor Line OD (in.) Maximum Length (ft) 200 Maximum Lift (Fan Coil Above) (ft) 65 Maximum Lift (Fan Coil Below) (ft) 150
5
8
5
8
3
8
3
4
7
⁄8††
7
⁄8††
CONDENSATE DRAIN CONNECTION Pipe Thread (MPT) CONDENSATE DRAIN SIZE (in.) |
*Field reconfigured to 18,000 Btuh 11⁄2tons. See Before Installation
section on page 3 for details.
†Outdoor unit is shipped with a holding charge. Refer to unit name-
plate (on unit) for details on specific system charge required.
**When matched with 030 outdoor unit/when matched with 036 out-
door unit.
††The valve connection size is3⁄4inch. The recommended line size
is7⁄8inch.
\ Flexible tubing (5⁄8in.) is required when the accessory condensate
pump is used.
3
4
3. Remove inlet grilles from indoor unit by sliding forward. Reinstall prior to unit start-up.
4. If necessary, reconfigure the 24,000 Btuh fan coil unit to 18,000 Btuh as follows:
a. The plug to the motor is located just outside the con-
trol box. Refer to the label diagram on the plug for wiring for both 18,000 Btuh and 24,000 Btuh units.
b. Remove the black, blue, yellow, and red wires from
the plug. The white wire is the common and remains
in the same position. c. Insert the blue wire into pin number 1. d. Insert the yellow wire into pin number 2. e. Insert the red wire into pin number 3. f. Insert the black wire into pin number 4. g. Check all connections to ensure they are secure.
h. Reinstall grilles using the screws removed in Step b. i. Reinsert filters removed in Step a.
Step 2 — Select Location — Consult local building
codes and NEC for special installation requirements. See Fig. 3 and 4 for unit dimensions and required clearances.
There are several ways the unit may be installed to dif­ferent types of ceiling construction. These instructions do not cover all installation methods. As a typical installation, these instructions focus primarily on mounting the unit to metal in new construction. Plan your installation carefully before you begin. Listed below are some guidelines that should be followed when determining location for the unit.
1. Place unit adjacent to an outside wall if fresh air is
required, ensuring that location allows for complete air distribution.
4
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Standard unit clearances are as follows:
•09on top and rear
•39on left side
•129on right side
•369on bottom
(When facing unit discharge)
WEIGHT (lb) A B E F G
UNIT
40QA
QAB QAE ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm
024 108 110 4- 2 036 117 119 4-10 048 149 151 5-11 060 179 181 7- 8 2336 7- 3 2211 7- 6
15
⁄161294 3-10 1169 4- 15⁄81260 1- 95⁄8549
13
⁄161493 4- 57⁄81368 4- 91⁄21459 2- 11⁄2648
9
⁄161817 5- 65⁄81692 5-101⁄41783 1- 97⁄8555 3- 31⁄16992
5
⁄82302 1-115⁄8601 4-119⁄161512
Fig. 3 — 40QA Base Unit Dimensions
5
Fig. 4 — 40QA Clearances
2. Locate the thermostat in an area which is not subjected to drafts or direct sunlight through windows. Locate ther­mostat on an interior wall whenever possible.
3. Allow sufficient clearance for airflow, wiring, refrigerant piping, and servicing unit (Fig. 3 and 4).
4. Make sure the unit is easily accessible to electrical power.
5. Run refrigerant piping as directly as possible, and avoid any unnecessary turns or bends.
6. Condensate piping can be directed through the inside wall to an approved drain or straight outside.
NOTE: The piping hole for condensate line must slope at a minimum pitch of
1
⁄4in. per foot to ensure proper drain­age. If proper pitch cannot be achieved, install accessory condensate pump at this time.
Step 3 — Mount Unit — Refer to Fig. 4 for clearances
and dimensions. Use mounting template included inside box to locate mounting bolt holes, piping holes, electrical con­nections, and accessory outdoor-air intake, if used.
Select proper type of hardware from the guidelines below.
See Fig. 5.
Solid structure in ceiling must be used due to the weight of the unit.
Wooden Structure — Install hanging bolts on a square wooden piece placed over beams.
Newly Built Concrete Slab — Install hanging bolts with in­serts, embedded bolts, etc.
Metal Structure — Install hanging bolts utilizing an existing angle or by installing a new support angle.
Previously Built Concrete Slab — Install hanging bolts with expansion anchor.
Fig. 5 — 40QA Unit Mounting Methods
(Hardware is Field Supplied)
TO MOUNT UNIT:
1. Remove mounting bracket and reinstall the 2 hex-head bolts (factory supplied) into each side of indoor unit as shown in Fig. 6. Allow approximately 3/8-in. space be­tween bolt head and unit.
2. Determine installation position, paying particular atten­tion to piping lengths, wiring connections, clearances, etc. See Fig. 3 for connection locations, Fig. 4 for clearances, and Fig. 7 and 8 for bolt locations.
3. Open knockout if right-side piping connections are re­quired (Fig. 9), by removing the pre-slit portion in the rear of the right side panel with a saw or cutter knife.
NOTE: If accessory fan coil unit louver guard is used, in­stall at this time. Refer to installation instructions packaged with this accessory.
4. Mount hanging brackets on ceiling (Fig. 10) for either concealed or exposed bolt hanging position.
6
Fig. 6 — Installing Hex-Head Mounting Bolts
in 40QA Unit
DIMENSIONS (in.)
UNIT 40QA A B C
024 50 036 5813⁄ 048 719⁄ 060 92 87 905⁄
15
16 16
16
46 495⁄
537⁄
8
665⁄
8
571⁄ 701⁄
Fig. 7 — 40QA Unit Hanging Dimensions
5. Lift the unit into place, and fit the hex-head bolts on sides of indoor unit into mounting slots of mounting brackets (Fig. 11). Ensure unit is mounted level to assure proper drainage.
6. Tighten indoor unit hex-head bolts securely.
TO INSTALL REMOTE THERMOSTAT: If there is at least 3/8 in. of space between the back of indoor
unit and wall:
1. Route remote thermostat wires (field supplied) through slot in right side of rear panel of indoor unit (Fig. 3).
2. Route wires over refrigerant and drain piping as shown in Fig. 12.
IMPORTANT: Do not route wires under the piping, or wires could impede air filter removal.
If there is less than 3/8 in. of space between back of indoor unit and wall:
1. Cut rear bottom of the right-side panel.
2. Route remote thermostat wires through new opening.
See Step 7 — Install Remote Thermostat section on page 12
for remainder of remote thermostat installation details.
Step 4 — Connect Refrigerant Piping — Fan coil
8 2 4 8
units may be connected to outdoor units using field-supplied refrigerant grade piping. Refer to Tables 3A and 3B for the correct size piping. The length of refrigerant pipe depends on the unit placement and building structure; run pipes as directly as possible. For piping requirements over 50 ft of total run, or more than 25 ft of lift, consult the long line application guidelines in the System Product Data literature.
DIMENSIONS (in.)
UNIT 40QA B C
024 46 49 036 537⁄ 048 665⁄ 060 87 905⁄
*Exposed mounting holes.
†Reverse bracket holes (concealed mounting).
8 8
571⁄ 701⁄
5
8 2 4 8
Fig. 8 — Mounting Template Included
with 40QA Unit
Fig. 9 — Removing Rear Knockout in Side Panel
If Right-Side Piping Connection in Used
DO NOT BURY MORE THAN 36 IN. OF REFRIG­ERANT PIPE IN THE GROUND. If any section of pipe is buried, there must be a 6-in. vertical rise to the valve connections on the outdoor unit. If more than the rec­ommended length is buried, refrigerant may migrate to the cooler, buried section during extended periods of unit shutdown, causing refrigerant slugging and possible com­pressor damage at start-up.
To connect piping:
1. Install insulation. Insulate supply and return refrigerant lines on heat pumps (38QRC) and mult-split condensing (38HDS) units to prevent condensation. It is extremely important that all refrigerant lines and the AccuRatert metering device be insulated on heat pumps. On 38HDC cooling only units, the liquid line may be left uninsu­lated. Use any acceptable heat resistant closed-cell foam insulation (minimum 3/8-in. wall thickness). When insu­lating piping, cap ends and slide insulation over the pip­ing. Insulation can also be cut and placed over piping.
2. Run liquid and gas refrigerant piping. a. Run pipes as directly as possible, and avoid any un-
necessary turns and bends.
b. Suspend refrigerant pipes so that the insulation is
not damaged and vibrations are not transmitted to the structure.
c. Leave slack in the refrigerant pipe between the struc-
ture and the unit to absorb vibrations.
d. For 38HDC and QRC systems only, install flare con-
nection on tubing to liquid line at fan coil unit. A pis­ton is shipped in the AccuRater device body (Fig. 13) with the 40QA unit. Use Tables 4-6 to verify that you have the required piston size for the system being installed.
7
Fig. 10 — Mounting Hanging Brackets
MOUNTING SLOT
Fig. 11 — Hanging 40QA Unit
HEX-HEAD BOLT
*Factory supplied.
Fig. 12 — Routing Wires Over Piping
IMPORTANT: The factory-supplied piston MUST be installed as shown in Fig. 13.
NOTE: DO NOT install a piston on 38HDS systems. Re­frigerant control is handled by a TXV (thermostatic ex­pansion valve) in the 38HDS unit in these systems.
For special applications, such as long lines or raised el­evations, consult the Application Data section of the Prod­uct Data literature for specific system requirements. The arrow on theAccuRatert device body must face away from the indoor coil.
e. On heat pump (38QRC) installations, install factory-
supplied piston (enclosed in a bag taped inside the out­door unit) into the AccuRater metering device located in the service valve on the outdoor unit (Fig. 14).
IMPORTANT:The factory-supplied piston MUST be installed as shown in Fig. 14.
Make sure Teflon seal on the piston faces toward the outdoor unit. Use Table 5 to verify you have the re­quired piston size for the system being installed. For special applications, such as long lines or raised eleva­tions, consult the Application Data section of the Prod­uct Data literature for specific system requirements.
8
NOTE: Arrow onAccuRater® body points in from the indoor coil.
free flow
direction away
Fig. 13 — AccuRater Metering Device in Liquid
Line (Bypass Type Components), 38HDC and QRC
Systems Only
f. Refer to 38HDC, 38HDS, and 38QRC Installation,
Start-Up and Service Instructions for additional out­door unit installation information.
g. Install a liquid line filter drier near the 38HDC or QRC
outdoor unit. On heat pump systems, a bi-flow filter drier must be used.
3. Insulate and caulk wall openings to reduce air infiltration and refrigerant pipe vibrations on structure.
4. Evacuate piping, if necessary. If either refrigerant piping or the indoor coil is exposed to atmospheric conditions, it must be evacuated to 1000 microns to eliminate con­tamination and moisture in the system. Refer to Carrier’s Standard Service Techniques Manual, Chapter 1, Sec­tions 1-7.
Table 4 — Required Piston Size for AccuRater Metering Device, Cooling-Only Systems
NOTE: Teflon Seal must face toward the outdoor heat pump unit.
Fig.14 —AccuRaterMetering Deviceat ServiceValve
(Bypass Type Components),
38QRC Systems Only)
INDOOR
UNIT 40QAB
024† 018 53 3.7 024 024 57 5.5
036 048 048 84 7.4
060 060 93 13.6
*Charge is based on 25 ft of interconnecting tubing. Charge may need to be added for longer tubing runs or when used with certain fan coil units.
†Unit is field reconfigured for 18,000 Btuh operation. See Before Installation section on page 3 for reconfiguration details. Check outdoor unit name-
plate for required charge.
NOTES:
1. All pistons are Chattleff 9B9 type.
2. All cooling units have a full factory charge for the smallest possible system combination.
3. Service valves are front-seating type.
OUTDOOR
UNIT 38HDC
030 65 5.6 036 70 5.4
PISTON SIZE
REQUIRED
REQUIRED SYSTEM
CHARGE (lb)*
Table 5 — Required Piston Size for AccuRater Metering Device, Heat Pump Systems
INDOOR
UNIT 40QAE
024† 018 55 49 4.3 024 024 55 49 6.3
036 048 048 84 78 10.0
060 060 96 82 11.9
*Charge is based on 25 ft of interconnecting tubing. Charge may need to be added for longer tubing runs or when used with certain fan coil units.
Check outdoor unit nameplate for required charge.
†Unit is field reconfigured for 18,000 Btuh operation. See Before Installation section on page 3 for reconfiguration details. Check outdoor unit
nameplate for required charge.
**Single phase/3 phase.
NOTES:
1. All pistons are Chatleff 9B9 type.
2. All heat pumps have a holding charge only as shipped from the factory.
OUTDOOR
UNIT 38QRC
030 63 55 6.4 036 63 61 7.5/8.7**
INDOOR PISTON SIZE (COOLING)
OUTDOOR PISTON
SIZE (HEATING)
REQUIRED SYSTEM
CHARGE (lb)*
9
Step 5 — Connect Condensate Drain Line
Observe all local sanitary codes when installing conden-
sate drains. Refer to Fig. 3 and 15 for drain pipe connection from indoor unit.
1. Use hardpolyvinyl chloride (PVC) pipe material with nomi­nal ID of 3/4 in. to connect at drain line. Use pipe insu­lation 1/4-in. thick, such as Armaflex insulation, on ex­posed piping inside the conditioned space.
2. To ensure regular flow of condensate water,the drain pipe should be pitched toward an open drain or sump at a down­ward slope of at least 1/4-in. per ft.
3. Attach plate with screws under piping hole.
4. Attach drain pipe with nylon wire tie passing through hole (Fig. 16).
NOTE: Do not fasten nylon wire ties tight enough to de­form the insulation, as this affects its performance.
5. Insulate condensate drain line(s) that are located in or above an occupied area with a condensate-proof material such as polyurethane or neoprene.
6. Install an external trap at the end of the condensate line. NOTE: Should your particular installation require one,
a condensate pump may be ordered as a field-installed accessory.
Table 6 — Required Piston Size for AccuRaterT Metering Device, Cooling-Only Condensing Units With
Heat Pump Fan Coil Units
INDOOR
UNIT 40QAE
024† 018 52 3.6 024 024 53 6.2**
036 048 048 84 7.4
060 060 93 13.6
*Charge is based on 25 ft of interconnecting tubing. Charge may need to be added for longer tubing runs or when used with certain fan coil units.
Check outdoor unit nameplate for required charge.
†Unit is field reconfigured for 18,000 Btuh operation. See Before Installation section on page 3 for reconfiguration details. Check outdoor unit
nameplate for required charge.
**Combination may require charge in addition to what is factory supplied.
NOTES:
1. All pistons are Chattleff 9B9 type.
2. All cooling units have a full factory charge for the smallest possible system combination.
3. Service valves are front-seating type.
OUTDOOR
UNIT 38HDC
030 63 5.6 036 65 5.6
PISTON SIZE
REQUIRED
REQUIRED SYSTEM
CHARGE (lb)*
1—Air Delivery Louvers 2—Air Filters 3—Remote Thermostat 4—Drain Pipe 5—Interconnecting Tubing and Wire 6—Outdoor Unit (38HDC Shown) 7—Outdoor Unit Disconnect Switch 8—Indoor Unit Disconnect Switch
Fig. 15 — Component Location (Typical Ceiling-Suspended System)
10
Fig. 16 — Routing Drain Piping
Step 6— Make Electrical Connections — Be sure
field wiring complies with local building codes and NEC, and unit voltage is within limits shown in Table 7.
Contact local power company for correction of improper
line voltage.
To avoid personal injury or damage to unit, do not make electrical connections until all power sources are shut down, locked out, and tagged off. Failure to do so could result in personal injury or unit damage.
Operation of unit on improper line voltage constitutes abuse and could affect warranty. Refer to Table 7 for permissible operating limits. Do not install unit in sys­tem where voltage may fluctuate above or below per­missible limits.
NOTE: Use copper wire only between disconnect switch(es) and unit.
NOTE: Install branch circuit disconnect of adequate size to handle unit starting current per NEC. Locate disconnect within sight from and readily accessible from unit, per Section 440-14 of NEC. Some codes allow indoor unit to share disconnect with outdoor unit if disconnect can be locked; check local code before installing in this manner.
1. Route ground and power wires.
According to NEC and most local codes, the unit must have an uninterrupted, unbroken ground to minimize per­sonal injury if an electric fault should occur. The ground may consist of electrical wire or metal conduit when in­stalled in accordance with existing electrical codes. Fail­ure to follow this warning could result in an electric shock, fire, or death.
2. Route line power leads (see Fig. 17) from indoor discon­nect to the fan coil unit. Place wire through hole on the control box (Fig. 18). Connect wire to high voltage ter­minal board (TB1) and ground screw. When routing the wire in the unit, use care to keep the wire away from re­frigerant and condensate piping and any sharp edges. The 208/230 V units are factory wired for 230 V to 24-V trans­former operation. For 208 V to 24-V operation, inter­change blue (208 V) and red (230 V) wires. Cap any un­used wires with wire nuts.
Table 7 — Electrical Data
UNIT
40QA
B024†
B036
B048 B060 208/230 187 253 1.3
E024† 208/230 187 253 0.5 E036 208/230 187 253 1.3 E048 208/230 187 253 1.0 E060 208/230 187 253 1.3
AWG American Wire Gage FLA Full Load Amps MCA Minimum Circuit Amps per NEC Section 430-24 MOCP — Maximum Overcurrent Protection NEC National Electrical Code
*Permissible limits of the voltage range at which units will operate satisfactorily.
†Electrical data is the same for both the 24,000 Btuh 024 unit and the 024 unit which has been field-reconfigured for 18,000 Btuh. Refer to Before
Installation section on page 3 for reconfiguration details.
Volts
(Single-Ph,
60 Hz)
115 104 127 1.2
208/230 187 253 0.5
115 104 127 4.0
208/230 187 253 1.3
115 104 127 2.2
208/230 187 253 1.1
MINIMUM
OPERATING
VOLTAGE*
LEGEND
MAXIMUM
OPERATING
VOLTAGE*
Motor 1 Motor 2
FLA Hp FLA Hp kW FLA MCA MOCP FLA
FAN
1
15
1.50 15 1.20 14
1
15
0.63 15 0.50 14
1
6
5.00 15 4.00 14
1
6
1.60 15 1.30 14
1
15
1.01⁄
1
15
0.51⁄
1
⁄61.3
1
15
1
6
1
15
1
⁄61.3
1
2.00 8.66 9.29 15 11.29 14
3.00 13.00 17.70 20 14.30 14
0.51⁄154.00 17.40 23.80 25 19.00 12
1
HEATER POWER
15
4.00 15 3.20 14
15
2.00 15 1.60 14
6
3.30 15 2.60 14
⁄65.00 21.70 28.70 30 24.30 10
MIN
WIRE
SIZE
(AWG)
11
Step 7— Install Remote Thermostat— The 40QA
unit is equipped with a remote thermostat which operates the system. The thermostat monitors the system operation and controls the operating mode. To change settings or modes of operation, use the thermostat (see Fig. 19).
Mount thermostat to a wall in the occupied space using 2 field-supplied screws. Locate the thermostat in an area which is not subjected to drafts or direct sunlight through windows. Locate thermostat on an interior wall whenever possible.
Step 8 — Make Connections Between Indoor and Outdoor Units —
TB — Terminal Block
Fig. 17 — Line Power Connections
The thermostat is wired
between the indoor and outdoor units to make the system complete.
Wirethermostat to fancoil unit according to Fig. 20 (cooling­only systems or condensing units matched with heat pump fan coil units) or Fig. 21 (heat pump only systems). Refer to Cooling-Only Systems and Heat Pumps Systems sections be­low to wire thermostat from fan coil unit to outdoor unit.
COOLING ONLY SYSTEMS — The following connec­tions must be made to the 38HDC or HDS unit for it to op­erate as a system with the indoor unit:
Route 2 wires of field-supplied 18-gage AWG (American Wire Gage) thermostat cable between the low-voltage ter­minal block of the fan coil unit and the 38HDC unit low­voltage terminal block. Connect the wires Y1 to Y and C to C. See Fig. 20.
HEAT PUMPSYSTEMS —The following connections must be made to the 38QRC unit for it to operate as a system with the indoor unit:
Route 6 wires of field-supplied 18-gage AWG thermostat cable between the low-voltage terminal block of the fan coil and the 38QRC unit low-voltage terminal block. Connect Y1 to Y, R to R, O to O, G1 to G, W2 to W2, and C to C with the wires. See Fig. 21.
The 38QRC heat pump unit uses a timed defrost method. The timed defrost can be field set for 30, 50, or 90 minutes. The timed defrost is factory set for 90 minutes.
ASM Air Sweep Motor ASR Air Sweep Relay EQUIP GND — Equipment Ground FL Fuse Link FPT Freeze Protection Thermostat HP Heat Pump HR Heater Relay HTR Heater HTT Heater Temp. Thermostat IFM Indoor-Fan Motor
NOTES:
1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
2. Wire in accordance with NEC and local codes.
NEC National Electrical Code PCB Printed Circuit Board PL Plug TB Terminal Board TRAN — Transformer
Terminal (Marked) Terminal (Unmarked)
Splice
Fig. 18 — Control Circuit Connections Arrangement
Terminal Block Factory Wiring
Field Power Wiring Field Control Wiring
Printed Circuit Board Accessory or Optional Wiring
3. Transformer is thermally protected and will reset automatically.
4. Indoor-fan motor(s) are inherently thermally protected.
12
Mode
Fan
Air Sweep
Day/Night
Fig. 19 — Remote Thermostat
START-UP
Never operate unit without a filter or with grille re­moved; damage to the unit or personal injury may re­sult.
Make the followingchecks and complete the Start-Up Check­list on pg CL-1 before system start-up. Refer to 38HDC, 38HDS, or 38QRC Installation, Start-Up and Service In­structions for system start-up instructions and refrigerant charging methods.
1. Check condensate drainage system:
a. Remove grille and frame from the unit. b. On the opposite side of the drain connection, insert a
water bottle up into the fan coil unit and fill drain pan. Refer to Fig. 22.Watermust flow steadily; if not, check the pipe slope or inspect for any pipe restrictions.
TB — Terminal Block *Heat pump units only.
Fig. 20 — CoolingOnly Systems or Condensing Unit Matched with Heat Pump Fan Coil Unit Thermostat
Wiring
2. Make sure that all wiring connections are correct and that they are tight.
3. Check that all barriers, covers, and panels are in place. Ensure that the filters and return-air grilles have been installed and that the discharge louvers are positioned correctly.
After Extended Shutdown — If the system has been
turned off for more than 12 hours, turn on the indoor and outdoor unit disconnect switches to supply power to the sys­tem for 12 hours BEFORE starting the system.
SeasonalChangeovers — When changing heat pump
system from cooling to heating or heating to cooling, or be­fore starting cooling only system after it has been out of use for the winter season, perform the following steps BEFORE starting the system:
1. Inspect and clean the outdoor unit, particularly the coil.
2. Clean or replace the air filters in the indoor unit.
3. Clean the indoor unit drain pan and drain pipe, and re­move any obstructions.
4. Turn on indoor and outdoor unit disconnect switches to supply power to the system 12 hours before starting the system.
13
LEGEND
DFB — Defrost Board DFT — Defrost Thermostat TB Terminal Block
Fig. 21 — Heat Pump System Thermostat Wiring
Fig. 22 — Inserting Water into Drain Pan
Adjusting Airflow
AUTOMATIC AIR SWEEP — All units are equipped with an automatic air sweep feature which automatically directs the airflow louvers up and down to provide optimum room air circulation. If the auto. sweep feature is not desired, tem­porarily start the auto. sweep using the remote thermostat (press Air Sweep button). When the louvers are in the de­sired position, turn the auto. sweep off (press Air Sweep but­ton again) to hold them in that position.
OperatingMode Memory — After the system is turned
off or after a power failure, the system remains in the last operating mode selected. When the system is turned back on, or when power is automatically restored, operation con­tinues in the same operating mode as when the system shut down.
AutomaticOperation (Auto.) Mode— If auto. mode
is selected, the system automatically switches over the 40QAE operating mode from heating to cooling, or from cooling to heating (heat pump system only) depending on the selected temperature.Auto. mode also controls fan speed if not manu­ally overridden.
NOTE: Between the cooling cycle and the heating cycle there is a neutral zone of approximately 2° F above and 2° F be­low the selected temperature when only the fan is operating.
OperatingSequence — Ceiling-suspended fan coil units
have a relay board which controls system operation in re­sponse to a room thermostat. The user may manually select any one of 3 fan speeds for unit operation. Ceiling-suspended systems may be equipped with an accessory power ventila­tion kit and/or condensate pump.
FAN OPERATION — Fan speed can be selected by press­ing the fan button (high, medium, or low speed choices). The fan(s) is capable of operation when unit mode is set on either cooling, heating, or auto. mode. When the fan(s) is operating in medium or high speed and the unit is equipped with the power ventilation kit, the ventilation fan will op­erate to provide fresh air. If the mode is set to the AUTO. position, then the fan will operate with the outdoor unit com­pressor.
COOLING MODE OPERATION — When the room ther­mostat senses a demand for cooling, the fan coil relay board is energized. The indoor fan(s) will start in the selected speed (if it is not already operating). The reversing valve (40QAE only) will energize and switch to the cooling position.
The internal condensate pump (if so equipped) runs when­ever the reversing valve is energized (40QAE only) and/or the unit is in cooling. As long as the condensate float switch and freeze protection thermostat are closed, the cooling re­lays in the fan coil unit will close. This energizes the com­pressor and outdoor fan in the outdoor unit.
The compressor will continue to operate until the room thermostat is satisfied. When the cooling demand is satis­fied, the compressor and outdoor fan will stop. If the out­door unit is equipped with accessory Time Guardt device, the unit will not allow a new call for cooling for 5 minutes. If the system is in the AUTO. position, the indoor fan will stop with the compressor. If the unit has the accessory ven­tilation kit, the ventilation fan will operate whenever the in­door fan is set for medium or high speed.
HEAT PUMPOPERATION (40QAE Only) — When the room thermostat senses a demand for heating, the fan coil relay board is energized. The indoor fan will start in the selected speed (if not already operating), and the reversing valve will not be energized. The internal condensate pump (if sup­plied) and freeze protection thermostat are not operated dur­ing heating operation. The control relay (CR2) closes, and the compressor and outdoor fan are energized through the defrost board (DFB), which is located in the outdoor unit. The microprocessor logic in the DFB is energized when the compressor starts, and the defrost timer runs. Once every 90 minutes (factory default setting) of compressor run time, the DFB logic checks the defrost thermostat (DFT). If the DFT is open, the unit continues in heating operation. If the DFT is closed, the DFB switches the unit to defrost mode. The timing on the DFB may be set at either 30, 50, or 90 minutes.
14
DEFROST (40QAE Only) — The DFB energizes the RVS (reversing valve solenoid), and the reversing valve switches to the cooling position. The K1 relay on the DFB opens and the outdoor fan stops. The W2 contact on the DFB is also energized, which in turn energizes the defrost relay on the fan coil relay board, turns off the electric heater and stops the indoor fan.
The DFB logic checks the 10-minute defrost timer and the DFT. If the DFT opens in less than 10 minutes, the DFB switches the unit back to normal heating operation. If the DFT remains closed, the DFB switches the unit back to heat­ing operation after 10 minutes. When the DFB changes back to heating mode, the RVR (reversing valve relay) is deen­ergized and the reversing valve switches back to heating op­eration. Both the outdoor and indoor fans come back on, and if necessary, the electric heater also turns on.
SYSTEM SAFETIES — The system is equipped with the following safety devices to protect system components:
A. Indoor coil freeze protection thermostat (40QAE unit cool-
ing cycle only) — If a coil temperature of 28 F or lower is sensed, the compressor and outdoor fan will be shut down until the coil temperature exceeds 28 F. The in­door fan will continue to run.
B. Condensate float switch (40QA units equipped with ac-
cessory condensate pump, cooling cycle only) — If the level of condensate in the drain pan rises too high, the condensate float switch will turn off the compressor and outdoor fan until the condensate level returns to normal. The indoor fan will continue to run.
C. Outdoor Unit Safeties — These units are protected by
the following devices:
• high-pressure switch
• low-pressure switch (condensing units only)
• compressor internal overloads
• outdoor-fan motor internal overload NOTE: Outdoor units with scroll compressors are also
protected by a high discharge gas temperature sensor and a 2-minute timer to prevent possible reverse rotation of the compressor.
Should any of these devices trip after the compressor is energized, the Cycle-LOC™ protection device will lock out the outdoor unit (turn it off) to prevent cycling on a safety device.
SPECIALOPERATION,HEATING— Outdoorcooling units may be matched with heat pump ceiling-suspended fan coil units to provide supplemental electric heat. All other opera­tion is the same as a cooling-only system, except these units have heating capability as follows:
When the room thermostat initiates a call for heating, the electric heater is turned on. The indoor unit fan will start at the same time if it was not already running.
When the heating requirement is satisfied, the room ther­mostat will open, and the heater will turn off.
CLEANING AND MAINTENANCE
Do not wash filter in water over 120 F (to avoid shrink­age). Do not expose filter to fire (to avoid fire damage). Do not expose filter to direct sunlight. Clean filter more frequently when air is extremely dirty.
Do not attempt to clean or service components in con­trol box.
For proper system operation, perform the cleaningand main-
tenance operations in Table 8.
Lubrication— The indoor-fan, automatic air sweep, and
the outdoor-fan motors are factory lubricated and require no oiling.
To Remove and Clean or Replace Air Filters (Fig. 23)
Operating your system with dirty air filters may damage the indoor unit and, in addition, can cause reduced cool­ing performance, intermittent system operation, frost build-up on the indoor coil, and blown fuses. Inspect and clean or replace the air filters monthly.
TO REMOVE AIR FILTERS — Remove filters by pulling them straight out.
Fig. 23 — Cleaning Filters
To avoid the possibility of electric shock, before per­forming any cleaning and maintenance operations, al­ways turn off power to the system by pressing the mode button on the remote thermostat until the display shows ‘‘OFF,’’ and turning off the outdoor disconnect switch located near the outdoor unit. If the indoor unit is on a separate switch, be sure to turn this disconnect off as well.
15
Table 8 — Cleaning and Maintenance Schedule
TASK MONTHLY QUARTERLY YEARLY
INDOOR UNIT
Clean Air Filters X Clean Drain Pipe X Clean Condensate Drain Pan X Clean Indoor Coil X Clean Indoor Unit Front Panel X
OUTDOOR UNIT
Clean the Fins From Outside X Open the Unit and Clean Fins Inside X Remove Dust From Electrical Parts X Check Electrical Connections are Tight X Clean Outdoor Fan X Clean Outdoor Coil X Check that Outdoor Fan Assembly is Tight X Clean Drain Pan X
NOTE: Maintenance procedures for the outdoor units are in the 38HDC, HDS, and QRC installation instructions.
TO CLEAN OR REPLACE FILTERS — Filters can be vacu­umed or washed in warm water. Shake filter to remove any excess water, and replace by sliding filter behind grille until filter snaps in place.
If the filter has begun to break down or is torn, replace it. Replacement filters are available through your Carrier distributor.
To Clean Indoor Unit Bottom Panel — If the bot-
tom panel of the unit becomes dirty or smudged, wipe the outside of the panel with a soft dry cloth. Use a mild liquid detergent and wipe off carefully with a dry cloth.
To Clean Indoor Coil — To clean the coil, remove in-
door unit bottom panel and vacuum the coil fins, using care not to bend or damage fins.
To Clean Outdoor Coil (Outdoor Unit)
Some metal parts and sharp fins of outdoor unit coil can cause personal injury during cleaning. Clean coil care­fully.
To clean the outdoor coil:
1. Remove any dirt or obstruction from discharge opening.
2. Use a garden hose to spray water on the coil. Debris that
collects between coil fins inhibits heat transfer — direct the water spray between coil fins to flush out debris.
ToClean Condensate Drains — Clean all drains and
drain pans at the start of each cooling season. Check the flow by pouring water into the drain.
TO CLEAN OR REPLACE DRAIN PAN
1. Place a plastic sheet on the floor to catch any water that
may spill from drain pan.
2. Remove the intake grille and distribution assembly (at-
tached). See Fig. 23.
3. Remove the condensate water in the drain pan by letting
water drain into a 3-gallon bucket.
4. Remove the 4 screws holding the drain pan.
5. Carefully hold the drain pan to remove it from the assembly.
SERVICE
When servicing unit, turn off all electric power to unit to avoid shock hazard or injury from rotating parts.
Do not vent refrigerant to atmosphere when servicing unit. Recover refrigerant during system repair or unit removal.
Before Calling for Service — You may save the cost
of a service call by doing the following:
1. Be sure main power to system is turned on.
2. Press Mode button until OFF is displayed. Wait 5 minutes.
3. Press Mode button until either COOL or HEAT is dis­played (as desired).
4. Adjust remote thermostat set point to desired room tem­perature. If system starts within a few minutes, you may not need service. If system does not operate properly,check Table 9 for typical solutions.
IF SYSTEM FAILS TO OPERATE — Be sure:
• unit ON/OFF switch is in ON position
• fuse or circuit breaker is not tripped
FRESH AIR INSTALLATION OPTION
The 40QA units have an installation option which allows for field installation of fresh air ventilation. Plan your in­stallation carefully. Before you begin, measure carefully and follow acceptable building practices, NEC, and local codes.
Ventilation-AirAccessory — Referto ventilation air
accessory installation instructions (also see Fig. 24).
Do not use a screwdriver to pry drain pan out of assembly — it could damage the pan.
16
TROUBLESHOOTING
If the under-ceiling fan coil unit fails to start or operate properly,sometimes the problem is minor and can be handled without a service call. Refer to Table 9 for some common
problems, causes, and typical solutions. See Fig. 25 and 26 for additional system troubleshooting details. If the problem cannot be corrected, contact your local Carrier representa­tive for further assistance.
Table9—Troubleshooting
PROBLEM CAUSE TYPICAL SOLUTION
System does
not start.
System does not
cool properly.
System does not
heat properly.
Ice or frost has
formed on
indoor coil.†
Insufficient
airflow
Blown fuse or circuit breaker tripped at building power entry.
Indoor and/or outdoor unit disconnect switch is off. Turn on disconnect switch(es).
Thermostat is set to night mode. Cancel mode using Day/Night button on thermostat. Power failure. Restore power.
Unit is in off mode. Compressor three-minute timer is running. Wait for 3 minutes.
Temperature is above or below the selected temperature. Select new temperature using the thermostat. Air filter(s) in indoor unit is dirty or needs to be replaced. Clean or replace air filter(s).
Temperature is set too high or too low. Outdoor unit outdoor coil restricted. Remove obstruction. Fan speed is set too low. Air filter(s) in indoor unit is dirty or needs to be replaced. Clean or replace air filter(s). Temperature is set too high or too low. Outdoor unit outdoor coil restricted. Remove obstruction. Fan speed is set too low.
Outdoor unit outdoor coil is frosted up. Low outdoor-air temperature. Run system in fan-only mode until frost is gone.
Air filter(s) in indoor unit is dirty or needs to be replaced.
Air filter(s) in indoor unit is dirty or needs to be replaced.
Fan coil unit coil is blocked.
Replace fuse or reset circuit breaker.*
Press Mode button on thermostat until thermostat displays the desired unit mode.
Reset temperature to desired comfort setting using the thermostat.
Adjust fan speed to high or auto. using the Fan button on the thermostat.
Reset temperature to desired comfort setting using the thermostat.
Adjust fan speed to high or auto. using the Fan button on the thermostat
Check manual defrost timer setting and adjust as necessary.
Clean or replace air filter(s). Clean or replace air filter(s).
Clean air discharge louvers.
*If fuse blows or circuit breaker trips again after firststart attempt, DO
NOT attempt to start system again. Contact your local Carrier rep­resentative for assistance.
NOTE: See Fig. 3 for dimensions.
Fig. 24 — Field Installation of Ventilation-Air Accessory
†When outdoor temperature is approximately 55 F or below, indoor
REAR VIEW
coil frosting may occur when system is operated in cooling or maxi­mum dehumidification mode.
17
LEGEND AND NOTES (Fig. 25 and 26)
ASM Air Sweep Motor ASR Air Sweep Relay ASW Air Sweep Switch C—Contactor CAP Capacitor CLO Compressor Lockout COMP Compressor Motor CR Control Relay CT Current Transformer DFB Defrost Board (Outdoor Unit) DFT Defrost Thermostat DR Defrost Relay DTS Discharge Temperature Sensor EQUIP GND — Equipment Ground FL Fuse Link FPT Freeze Protection Thermostat FR Fan Relay FU Fuse GND Ground HP Heat Pump HPS High-Pressure Switch HR Heater Relay HTR Heater HTT Heater Temperature Thermostat IFM Indoor-Fan Motor LLPS Liquid Low Pressure Switch OFM Outdoor-Fan Motor OFR Outdoor-Fan Relay
NOTES:
1. If any of the original wire furnished must be replaced, it must be replaced with type 90° C wire or its equivalent.
2. Wire in accordance with National Electrical Code (NEC) and local codes.
3. Transformer is thermally protected and will reset automatically.
LEGEND
OL Overload PCB Printed Circuit Board PDR Pump Delay Relay PL Plug PM Pump Motor PSS Pump Shutoff Switch RVS Reversing Valve Solenoid SC Start Capacitor SR Start Relay SSDR — Safety Switch Delay Relay TB Terminal Block TDR Time-Delay Relay TRAN — Transformer
Terminal (Marked) Terminal (Unmarked) Splice
Terminal Block Factory Wiring
Field Control Wiring Field Power Wiring Printed Circuit Board Accessory or Optional Wiring
4. The IFM(S), OFM and COMP have internal thermal protection.
5. The CLO locks out the COMP to prevent short cycling on COMP overloads and safety devices. Before replacing CLO check these devices. Minimum one amp turn required to hold contacts closed.
6. Two 508 long low voltage wiring cables provided with unit.
18
*Heat pump fan coil units only.
Fig. 25 — Typical System Wiring; Cooling-Only Systems or Condensing Unit with
Heat Pump Fan Coil Unit Systems
19
Fig. 26 — Typical System Wiring; Heat Pump Systems
20
PACKAGED SERVICE TRAINING
Our packaged service training programs provide an excellent way to increase your knowledge of the
equipment discussed in this manual. Product programs cover:
• Unit Familiarization • Maintenance
• Installation Overview • Operating Sequence
A large selection of product, theory, and skills programs is available. All programs include a video cassette and/or slides and a companion booklet. Use these for self teaching or to conduct full training sessions.
For a free Service Training Material Catalog (STM), call 1-800-962-9212. Ordering instructions are included.
Copyright 1996 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 3d 2d
PC 111 Catalog No. 534-052 Printed in U.S.A. Form 40QA-3SI Pg 22 4-96 Replaces: 40QA-1SI
I. PRELIMINARY INFORMATION
START-UP CHECKLIST
OUTDOOR UNIT: MODEL NO. INDOOR UNIT: MODEL NO.
ACCESSORIES: __________________________________________________________________________________
PISTONS (38HDC and 38QRC SYSTEMS ONLY): INDOOR SIZE: OUTDOOR SIZE (38QRC SYSTEMS ONLY):
REFRIGERANT PIPING: EQUIVALENT LINE LENGTH: (IF OVER 50 FT)* LIFT: FAN COIL ABOVE OUTDOOR UNIT (IF OVER 25 FT)*?
FAN COIL BELOW OUTDOOR UNIT (IF OVER 25 FT)*?
*APPLIES ONLY TO 38HDC AND 38QRC UNITS USING LONG-LINES APPLICATIONS. MAXIMUM EQUIVALENT
LINE LENGTH FOR 38HDS SYSTEMS IS 50 FT. MAXIMUM LIFT ON 38HDS APPLICATIONS IS 30 FT FROM LOWEST SYSTEM POINT TO HIGHEST SYSTEM POINT.
SERIAL NO. SERIAL NO.
PRE-START-UP
INDOOR UNIT (REFER TO OUTDOOR UNIT INSTALLATION INSTRUCTIONS FOR OUTDOOR UNIT PRE-START-UP FUNCTIONS)
IS THERE ANY SHIPPING DAMAGE? IF YES, WHERE? WILL THIS DAMAGE PREVENT UNIT START-UP? IS POWER SUPPLY CORRECT? (115-V FOR 40QAB024-048, 115 V UNITS; OR 208/230 V FOR
40QAB024-048, 208/230 V UNITS AND ALL 40QAB060 AND 40QAE024-060 UNITS. ALL SYSTEMS REQUIRE SINGLE-PHASE POWER)
HAS GROUND WIRE BEEN CONNECTED? HAS THE CORRECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED? ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? IS THE DISCONNECT SWITCH INSTALLED IN SIGHT FROM THE UNIT? IS THE LOW-VOLTAGE CABLE (INDOOR TO OUTDOOR UNIT) RUN AND CONNECTED PROPERLY? HAS CONDENSATE DRAIN BEEN RUN, SLOPED, AND TRAPPED PROPERLY? IS AIR FILTER(S) IN PLACE? IS UNIT MOUNTED LEVEL? IS COOLING PISTON INSTALLED (FIG. 13), THE CORRECT SIZE, AND IN THE CORRECT DIRECTION
(38HDC AND 38QRC SYSTEMS ONLY)? IS HEATING PISTON INSTALLED (FIG. 14), THE CORRECT SIZE, AND IN THE CORRECT DIRECTION
(38QRC SYSTEMS ONLY)?
PIPING
IS A LIQUID LINE SOLENOID INSTALLED IF REQUIRED BY LONG-LINE APPLICATIONS (38HDC AND 38QRC SYSTEMS ONLY)?
IS FILTER DRIER INSTALLED AT THE OUTDOOR UNIT (38HDC AND 38QRC SYSTEMS ONLY)? HAVE LEAK CHECKS BEEN MADE AT THE COMPRESSOR, OUTDOOR UNIT, FLARE CONNECTIONS, FILTER
DRIERS, AND FUSIBLE PLUGS WITH A LEAK DETECTOR?† †FIELD PIPING AND ALL TUBING CONNECTIONS MUST BE LEAK TESTED BY THE PRESSURE METHOD DE-
SCRIBED IN CARRIER GENERAL TRAINING FOR AIR CONDITIONING MANUAL (GTAC2), MODULE 5. USE R-22 ATAPPROXIMATELY 25 PSIG BACKED UP WITH AN INERT GAS TO REACH A TOTALSYSTEM PRESSURE NOT TO EXCEED 245 PSIG.
CL-1
START-UP CHECKLIST (cont)
HAS PIPING SYSTEM BEEN EVACUATED TO 1000 MICRONS (IF REQUIRED)? HAS SYSTEM CHARGE BEEN WEIGHED IN (IF REQUIRED)? HAVE SERVICE VALVES BEEN FULLY BACKSEATED? CHECK VOLTAGE: IS VOLTAGE WITHIN RANGE SHOWN FOR UNIT (WITH UNIT OPERATING)?
OUTDOOR INDOOR
START-UP
IF UNIT HAS A CRANKCASE HEATER, HAS IT BEEN ON FOR 24 HOURS? MEASURE AND RECORD THE:
AIR ENTERING OUTDOOR UNIT: AIR ENTERING INDOOR UNIT:
DISCHARGE LINE TEMPERATURE: VAPOR LINE TEMPERATURE:
MEASURE AND RECORD THE:
VAPOR LINE PRESSURE: DISCHARGE PRESSURE:
F
F
F
F
PSIG
PSIG
Copyright 1996 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 3d 2d
PC 111 Catalog No. 534-052 Printed in U.S.A. Form 40QA-3SI CL-2 4-96 Replaces: 40QA-1SI
Loading...