Carrier 50VZ, 50PZ, 38PZ, 40PZ, 38VZ Installation, Operation And Maintenance Instructions

Page 1
1
50VZ/PZ 38VZ/PZ+40PZ
Vertical Air-Cooled Split-System Cooling Units and Heat Pumps
Installation, operation and maintenance instructions
Page 2
2
CONTENTS
START-UP CHECKLIST................................................................................................................................................................. 3
PHYSICAL DATA............................................................................................................................................................................. 4
ELECTRICAL DATA....................................................................................................................................................................... 5
DIMENSIONS ................................................................................................................................................................................... 6
Service area, mm ............................................................................................................................................................................... 13
Centre of gravity, mm........................................................................................................................................................................ 14
Weight distribution, kg ...................................................................................................................................................................... 15
Repositioning unit air discharge........................................................................................................................................................ 16
FAN PERFORMANCE ...................................................................................................................................................................18
SAFETY CONSIDERATIONS ...................................................................................................................................................... 26
INSTALLATION ............................................................................................................................................................................. 26
Siting the unit .................................................................................................................................................................................... 26
Ductwork (indoor air discharge)........................................................................................................................................................ 27
Condensate drainage .......................................................................................................................................................................... 27
ELECTRICAL CONNECTIONS .................................................................................................................................................28
Refrigerant line connections (38VZ/PZ and 40PZ)........................................................................................................................... 29
Refrigerant line selection ................................................................................................................................................................... 29
Sizing .................................................................................................................................................................................................30
REFRIGERANT CHARGE........................................................................................................................................................... 31
START-UP ........................................................................................................................................................................................31
REFRIGERANT SYSTEM DESCRIPTION............................................................................................................................... 31
COMPRESSOR REPLACEMENT .............................................................................................................................................. 31
DESCRIPTION OF UNIT PROTECTION DEVICES ..............................................................................................................32
Operating limits ................................................................................................................................................................................. 32
OPTIONS AND ACCESSORIES .................................................................................................................................................. 32
Hot water heating coil ....................................................................................................................................................................... 32
Electric resistance heaters ..................................................................................................................................................................33
GENERAL MAINTENANCE .......................................................................................................................................................34
SERVICE ......................................................................................................................................................................................... 34
TRANSFORMATION TO SPLIT SYSTEM (50VZ/PZ units) ................................................................................................... 35
FINAL RECOMMENDATIONS ................................................................................................................................................... 35
TROUBLESHOOTING CHART .................................................................................................................................................. 36
Page 3
START-UP CHECK LIST Start up date: ...................................................................
Equipment sold by: ..................................................................................................................................... Contract No: .................................................
Installed by: .................................................................................................................................................. Contract No: .................................................
Site address: .............................................................................................................................................................................................................................
Equipment type and serial No: 50VZ/PZ...........................................................................................................................................................................
38VZ/PZ............................................................................................................................................................................
40PZ..................................................................................................................................................................................
ELECTRICAL DATA:
Supply voltage Ph 1: .
........................ Volts Ph 2: .................... Volts Ph 3 .......................Volts
Nominal voltage:
.............................................. Volts % network voltage: ................................................................................................................
Current draw Ph 1: .................................... Amperes Ph 2: ............................... Amperes Ph 3: .......................................... Amperes
Control circuit voltage:
................................... Volts Control circuit fuse: ........................................................................................ Amperes
Main circuit breaker rating:
............................................................................................................................................................................................................
PHYSICAL DATA:
Outdoor unit : Indoor unit:
Entering air temp.:
................................................................
o
C Entering air temp.: ..............................................................oC
Leaving air temp.:
................................................................
o
C Leaving air temp.: ..............................................................oC
Pressure drop (air):
.............................................................. kPa Pressure drop (air): ............................................................. kPa
Discharge air pressure:
....................................................... Pa Discharge air pressure: ...................................................... Pa
Fan motor input: Ph. 1:
........................................... Volts Fan motor input: Ph. 1: .......................................... Volts
Ph. 2:
........................................... Volts Ph. 2: .......................................... Volts
Ph. 3:
........................................... Volts Ph. 3: .......................................... Volts
SAFETY DEVICE SETTING:
High pressure switch: cut-out: ............................................. kPa cut-in: ............................................................... kPa
Low pressure switch: cut-out:
............................................. kPa cut-in: ................................................................. kPa
Step controller: cut-out 1st step:
...............................
o
C cut-in 1st step: .................................................. oC
cut-out 2nd step:
..............................
o
C cut-in 2 nd step: ...............................................
o
C
Oil level:
.............................................................................................................................................................................................................................................
Oil visible in sight glass? .................................................................................................................................................................................................................
ACCESSORIES:
Commissioning engineer (name):
.................................................................................................................................................................................................
Customer agreement
Name:
.......................................................................................... Date: ......................................................................................................................
Remarks:
Note: Complete this start-up list at the time of installation
3
Page 4
4
Table 1 - Physical data
50VZ (40PZ/38VZ) 015 025 030 031 040 045 055 065 075
Nom. cooling capacity* kW 14.60 22.74 29.75 27.80 35.05 45.21 53.90 63.89 74.35
Unit weight kg
50VZ 230 390 402 410 618 842 894 943 1033 40PZ 78 140 150 150 230 297 317 335 365 38VZ 152 250 252 260 388 545 577 608 668
Compressor Hermetic reciprocating Scroll Oil charge l 1.8 3.9 3.9 1.8 x 2 4 x 2 4 x 2 4 x 2 4 x 2 6.6 x 2 Oil type Maneurop 160PZ Mobil EAL Arctic 22CC Maneurop 160SZ
Refrigerant R-407C Refrigerant charge** kg 3.80 6.62 7.43 3.80 x 2 4.70 x 2 6.70 x 2 8.80 x 2 9.40 x 2 11.0 x 2
Evaporator section (40PZ) Copper tubes, aluminium fins Face area m
2
0.34 0.64 0.69 0.69 0.84 1.10 1.10 1.34 1.34 Rows...fins/m 3...551 4...472 4...472 4...472 4...472 4...551 6...472 6...551 6...551 Test pressure bar 30 30 30 30 30 30 30 30 30
Condenser section (38VZ) Copper tubes, aluminium fins Face area m
2
0.49 0.87 0.87 0.87 1.19 1.73 1.73 2.12 2.12 Rows...fins/m 5...551 4...551 5...551 5...551 5...551 5...551 6...551 6…551 6...551 Test pressure bar 30 30 30 30 30 30 30 30 30
Evaporator fan (40PZ) Double inlet centrifugal type Quantity 1 2 2 2 2 2 2 2 2 Nominal air flow l/s 960 1490 1690 1690 2190 2640 2910 3140 3530 Air flow range l/s 768-1152 1192-1788 1352-2028 1352-2028 1752-2628 2112-3168 2328-3492 2512-3768 2824-4236 Nominal static pressure (dry/wet) Pa 90/70 90/70 120/100 120/100 140/120 170/150 180/160 200/180 210/180
Condenser fan (38VZ) Double inlet centrifugal type Quantity 1 2 2 2 2 2 2 2 2 Nominal air flow l/s 1470 3020 2780 2780 3610 4580 5080 6030 6890 Air flow range l/s 1176-1764 2416-3624 2224-3336 2224-3336 2888-4332 3664-5496 4064-6096 4824-7236 5512-8268 Nominal static pressure Pa 50 50 60 60 60 75 100 100 100
Air filter Filter class M1 Quantity 1 2 2 2 2 3 3 3 3 Width x height mm 800x443 596x540 596x590 596x590 716x590 676x587 616x587 749x587 749x587 Thickness mm 15 15 15 15 15 15 15 15 15
Condensing unit 38VZ*** 015 025 030 031 040 045 055 065 075
Nom. cooling capacity kW 13.47 19.97 27.02 24.80 32.54 40.30 48.21 59.13 71.10
* Based on an outdoor air temperature of 35°C db and an indoor air temperature of 19°C wb ** The refrigerant charge given is for the complete system, but excludes the connection lines. *** Based on an outdoor air dry bulb temperature of 35°C and a dewpoint suction temperature of 7°C.
50PZ (40PZ/38PZ) 015 025 030 031 040 045 055 065 075
Nom. cooling capacity* kW 13.42 21.81 28.50 27.70 34.36 43.60 52.51 61.94 72.58
Nom. heating capacity** kW 15.76 25.02 30.58 30.20 39.15 50.18 57.43 66.60 83.06
Unit weight kg
50PZ 238 400 412 427 638 864 919 968 1058 40PZ 78 140 150 150 230 297 317 335 365 38PZ 160 260 262 277 408 567 602 633 693
Compressor Hermetic reciprocating Scroll Oil charge l 1.8 3.9 3.9 1.8 x 2 4 x 2 4 x 2 4 x 2 4 x 2 6.6 x 2 Oil type Maneurop 160PZ Mobil EAL Arctic 22CC Maneurop 160SZ
Refrigerant R-407C Refrigerant charge*** kg 4.02 7.20 7.71 3.94 x 2 5.40 x 2 7.50 x 2 9.20 x 2 9.50 x 2 11.20 x 2
Indoor section (40PZ) Copper tubes, aluminium fins Face area m
2
0.34 0.64 0.69 0.69 0.84 1.10 1.10 1.34 1.34 Rows...fins/m 3...551 4...472 4...472 4...472 4...472 4...551 6...472 6...551 6...551 Test pressure bar 30 30 30 30 30 30 30 30 30
Outdoor section (38PZ) Copper tubes, aluminium fins Face area m
2
0.49 0.87 0.87 0.87 1.19 1.73 1.73 2.12 2.12 Rows...fins/m 5...551 4...551 5...551 5...551 5...551 5...551 6...551 6…551 6...551 Test pressure bar 30 30 30 30 30 30 30 30 30
Indoor fan (40PZ) Double inlet centrifugal type Quantity 1 2 2 2 2 2 2 2 2 Nominal air flow l/s 960 1490 1690 1690 2190 2640 2910 3140 3530 Air flow range l/s 768-1152 1192-1788 1352-2028 1352-2028 1752-2628 2112-3168 2328-3492 2512-3768 2824-4236 Nominal static pressure (dry/wet) Pa 90/70 90/70 120/100 120/100 140/120 170/150 180/160 200/180 210/180
Outdoor fan (38PZ) Double inlet centrifugal type Quantity 1 2 2 2 2 2 2 2 2 Nominal air flow l/s 1470 3020 2780 2780 3610 4580 5080 6030 6890 Air flow range l/s 1176-1764 2416-3624 2224-3336 2224-3336 2888-4332 3664-5496 4064-6096 4824-7236 5512-8268 Nominal static pressure Pa 50 50 60 60 60 75 100 100 100
Air filter Filter class M1 Quantity 1 2 2 2 2 3 3 3 3 Width x height mm 800x443 596x540 596x590 596x590 716x590 676x587 616x587 749x587 749x587 Thickness mm 15 15 15 15 15 15 15 15 15
* Based on an outdoor air temperature of 35°C db and an indoor air temperature of 19°C wb ** Based on an outdoor air temperature of 6°C wb and an indoor air temperature of 20°C db. *** The refrigerant charge given is for the complete system, but excludes the connection lines.
Page 5
5
Table 2 - Electrical data
50VZ (40PZ/38VZ) 015 025 030 031 040 045 055 065 075
Nominal voltage ±10%* V 230 400 230 400 230 400 230 400 230 400 230 400 230 400 230 400 230 400
Nominal power input** kW 7.3 7.3 11.1 11.1 14.0 14.0 14.6 14.6 18.1 18.1 21.4 21.4 25.4 25.4 30.0 30.0 37.6 37.6
Nominal current drawn** A 23.8 13.8 33.1 19.1 39.4 22.8 44.9 26.0 52.6 30.4 64.9 37.5 74.3 43.0 87.8 50.8 122.1 67.1
Effective power input kW 6.8 6.8 10.2 10.2 13.0 13.0 13.6 13.6 16.8 16.8 19.0 19.0 22.2 22.2 26.1 26.1 33.1 33.1
Effective current drawn A 21.6 12.5 30.5 17.6 37.0 21.4 41.9 24.2 56.5 32.6 57.9 33.4 70.0 40.5 76.6 44.3 102.0 59.0
Starting current A 139.5 80.0 174.1 106.3 219.0 133.3 165.9 95.3 235.2 134.0 278.4 156.7 329.1 187.8 384.5 219.0 450.1 256.0
Maximum power input*** kW 7.9 7.9 12.2 12.2 15.5 15.5 16.1 16.1 21.8 21.8 25.2 25.2 29.6 29.6 35.0 35.0 44.2 44.2
Maximum current drawn*** A 24.2 14.0 35.5 20.5 43.2 25.0 49.5 28.6 66.6 38.5 73.1 42.2 88.8 51.3 99.7 57.6 129.5 74.8
Condensing unit 38VZ 015 025 030 031 040 045 055 065 075
Nominal voltage ±10%* V 230 400 230 400 230 400 230 400 230 400 230 400 230 400 230 400 230 400
Nominal power input
+
kW 6.5 6.5 10.1 10.1 12.8 12.8 13.2 13.2 16.7 16.7 19.4 19.4 23.0 23.0 26.9 26.9 34.7 34.7
Nominal current drawn+A 20.6 11.9 29.9 17.3 36.6 21.2 37.8 21.9 56.2 32.5 59.4 34.3 72.7 42.0 79.1 45.7 106.6 61.6
Effective power input kW 6.3 6.3 9.6 9.6 12.3 12.3 12.7 12.7 16.0 16.0 18.3 18.3 21.4 21.4 25.0 25.0 32.5 32.5
Effective current drawn A 20.1 11.6 28.5 16.5 35.4 20.4 36.4 21.1 54.0 31.2 56.0 32.4 67.6 39.1 73.5 42.5 99.9 57.7
Starting current A 136.7 78.4 170.1 104.0 214.1 130.5 161.1 92.5 226.9 129.2 270.9 151.2 319.2 180.9 372.2 211.9 434.2 246.8
Maximum power input++kW 7.7 7.7 11.5 11.5 14.9 14.9 15.3 15.3 20.6 20.6 24.0 24.0 29.1 29.1 33.8 33.8 43.9 43.9
Maximum current drawn++A 23.5 13.6 33.5 19.4 41.4 23.9 42.5 24.5 62.9 36.4 69.4 40.1 87.4 50.5 96.2 55.6 128.5 74.3
* All units are built for 3-phase, 50 Hz supply. ** Based on an outdoor air dry bulb temperature of 35°C and an indoor air wet bulb temperature of 19°C. *** Based on an outdoor air dry bulb temperature of 46°C and an indoor air wet bulb temperature of 21°C.
+
Based on an outdoor air dry bulb temperature of 35°C and a dewpoint suction temperature of 7°C.
++
Based on an outdoor air dry bulb temperature of 46°C and a dewpoint suction temperature of 12°C.
50PZ (40PZ/38PZ) 015 025 030 031 040 045 055 065 075
Nominal voltage ±10%* V 230 400 230 400 230 400 230 400 230 400 230 400 230 400 230 400 230 400
Nominal power input kW
Cooling** 7.2 7.2 11.2 11.2 13.6 13.6 14.6 14.6 18.1 18.1 21.6 21.6 25.4 25.4 30.2 30.2 38.5 38.5 Heating*** 6.6 6.6 11.1 11.1 12.4 12.4 12.7 12.7 17.5 17.5 20.8 20.8 23.7 23.7 27.1 27.1 34.3 34.3
Nominal current drawn A Cooling** 23.7 13.7 33.2 19.2 38.4 22.2 46.0 26.6 55.0 31.8 66.1 38.2 73.3 42.4 88.0 50.9 118.5 68.6 Heating*** 22.5 13.0 33.2 19.2 35.8 20.7 41.5 24.0 52.2 30.2 63.7 36.8 70.7 40.9 82.0 47.4 109.8 63.5
Effective power input kW Cooling 6.7 6.7 10.3 10.3 12.5 12.5 13.6 13.6 16.8 16.8 19.1 19.1 22.2 22.2 26.3 26.3 34.1 34.1 Heating 6.1 6.1 10.3 10.3 11.4 11.4 11.6 11.6 16.2 16.2 18.4 18.4 20.5 20.5 23.2 23.2 29.8 29.8
Effective current drawn A Cooling 22.1 12.7 30.5 17.7 35.3 20.4 42.8 24.8 51.0 29.5 59.4 33.8 64.1 37.1 76.6 44.3 105.0 60.8 Heating 20.8 12.0 30.8 17.8 32.9 19.0 37.9 21.9 48.3 28.0 56.4 32.6 61.2 35.4 70.2 40.6 95.4 55.2
Starting current A 139.5 80.0 174.1 106.3 219.0 133.3 165.9 95.3 235.2 134.0 278.4 156.7 329.1 187.8 384.5 219.0 450.1 256.0
Maximum power input kW
Cooling
+
8.0 8.0 12.4 12.4 15.2 15.2 16.3 16.3 21.6 21.6 25.3 25.3 30.4 30.4 34.9 34.9 44.5 44.5
Heating
++
7.5 7.5 13.1 13.1 15.8 15.8 14.4 14.4 20.3 20.3 23.7 23.7 28.1 28.1 32.8 32.8 41.6 41.6
Maximum current drawn A Cooling
+
26.3 15.2 36.8 21.3 42.9 24.8 51.4 29.7 65.6 37.9 77.4 44.7 87.7 50.7 101.7 58.8 137.0 79.3
Heating
++
25.6 14.8 39.2 22.7 45.6 26.4 47.1 27.2 60.6 35.0 72.6 41.9 83.8 48.5 99.2 57.4 133.2 77.0
* All units are built for 3-phase, 50 Hz supply. ** Based on an outdoor air dry bulb temperature of 35°C and an indoor air wet bulb temperature of 19°C. *** Based on an outdoor air wet bulb temperature of 6°C and an indoor air dry bulb temperature of 21°C.
+
Based on an outdoor air dry bulb temperature of 46°C and an indoor air wet bulb temperature of 21°C.
++
Based on an outdoor air dry bulb temperature of 18°C.
Effective power input in accordance with EUROVENT.
Page 6
6
Fig. 1 - Dimensions, mm
50VZ/PZ 015
38VZ/PZ 015
Optional discharge
40PZ 015
Optional discharge
Power connection
Drain 3/4" gas
Cable inlet
Optional discharge
Transport skid
Drain
Cable inlet
Transport skid
Transport skid
When designing an installation, always use up-to-date drawings, available from your local Carrier office
Page 7
7
Fig. 2 - Dimensions, mm
50VZ/PZ 025
38VZ/PZ 025 Optional discharge
40PZ 025
Optional discharge
Power connection
Optional discharge
Drain 3/4" gas
Cable inlet
Transport skid
Drain
Cable inlet
When designing an installation, always use up-to-date drawings, available from your local Carrier office
Transport skid
Transport skid
Page 8
8
Fig. 3 - Dimensions, mm
50VZ/PZ 030
Optional discharge
38VZ/PZ 030
Optional discharge
40PZ 030
Optional discharge
Power connection
Drain 3/4" gas
Cable inlet
Transport skid
Drain
Cable inlet
When designing an installation, always use up-to-date drawings, available from your local Carrier office
Transport skid
Transport skid
Page 9
9
Fig. 4 - Dimensions, mm
50VZ/PZ 031
38VZ/PZ 031
Optional discharge
40PZ 031
Optional discharge
Power connection
Drain 3/4" gas
Cable inlet
Optional discharge
Transport skid
Drain
Cable inlet
When designing an installation, always use up-to-date drawings, available from your local Carrier office
Transport skid
Transport skid
Page 10
10
Fig. 5 - Dimensions, mm
50VZ/PZ 040
Optional discharge
38VZ/PZ 040
Optional discharge
40PZ 040
Optional discharge
Power connection
Cable inlet
Drain 3/4" gas
Cable inlet
Drain
Transport skid
When designing an installation, always use up-to-date drawings, available from your local Carrier office
Transport skid
Transport skid
Page 11
11
Fig. 6 - Dimensions, mm
50VZ/PZ 045-055
Optional discharge
38VZ/PZ 045-055
Optional discharge
40PZ 045-055
Optional discharge
Power connection
Cable inlet
Drain 3/4" gas
Cable inlet
Drain
Transport skid
When designing an installation, always use up-to-date drawings, available from your local Carrier office
Transport skid
Transport skid
Page 12
12
Fig. 7 - Dimensions, mm
50VZ/PZ 065-075
Optional discharge
38VZ/PZ 065-075
Optional discharge
40PZ 065-075
Optional discharge
Power connection
Cable inlet
Drain 3/4" gas
Cable inlet
Drain
Transport skid
When designing an installation, always use up-to-date drawings, available from your local Carrier office
Transport skid
Transport skid
Page 13
13
Fig. 8 - Service area, mm
50VZ/PZ
* Service space behind the unit depends on whether or not the unit is installed with outdoor air ducts. It is also necessary to leave space for cleaning and inspection of the outdoor heat
exchanger.
** Space for removal of the air filter and the indoor or outdoor section belt and pulley transmission is required on the right and left hand side.
38VZ/PZ
40PZ
Page 14
Fig. 9 - Centre of gravity, mm (approx.)
50VZ/PZ (all sizes)
Fig. 10 - Centre of gravity, mm (approx.)
38VZ/PZ (all sizes)
Fig. 11 - Centre of gravity, mm (approx.)
40PZ (all sizes)
50VZ/PZ 015 025 030 031 040 045 055 065 075
XG 381 6 27 639 7 23 858 1116 1122 1324 1359 YG 583 772 758 743 703 755 773 767 781 ZG 526 434 448 444 450 525 527 521 527
Measured from point
38VZ/PZ 015 025 030 031 040 045 055 065 075
XG 349 583 595 707 831 1081 1085 1289 1313 YG 382 552 518 509 498 512 509 495 489 ZG 586 479 493 485 463 542 556 566 577
Measured from point
40PZ 015 025 030 031 040 045 055 065 075
XG 499 771 776 776 982 1261 1257 1453 1510 YG 230 296 314 314 308 341 338 337 333 ZG 301 286 307 307 389 452 417 360 364
Measured from point
11
11
1
11
11
1
11
11
1
▲
X
▲
Y
▲
Z
▲
Z
X
▲
▲
Y
Page 15
Fig. 12 - Weight distribution, kg (approx.)
50VZ/PZ (all sizes)
Fig. 13 - Weight distribution, kg (approx.)
38VZ/PZ (all sizes)
Control box
Control box
Support 50VZ
points 015 025 030 031 040 045 055 065 075
45 70 68 106 164 178 190 215 235 81 106 127 125 178 267 281 276 302 37 84 72 82 132 158 171 198 217 67 130 135 97 144 239 252 254 279
Support 50PZ
points 015 025 030 031 040 045 055 065 075
47 72 70 110 169 184 196 221 241 83 109 130 129 183 272 287 282 308 39 86 74 87 137 164 178 205 224 69 133 138 101 149 244 258 260 285
Support 38VZ
points 015 025 030 031 040 045 055 065 075
38 62 63 66 115 131 134 151 166 49 82 80 81 128 146 151 164 180 35 58 59 60 83 136 154 152 167 30 48 50 53 62 132 138 141 155
Support 38PZ
points 015 025 030 031 040 045 055 065 075
40 64 65 70 120 136 141 157 172 51 84 82 85 133 151 157 170 186 37 61 62 64 88 142 160 158 173 32 51 53 58 67 138 144 148 162
Fig. 14 - Weight distribution, kg (approx.)
40PZ (all sizes)
Air filters
Support 40PZ
points 015 025 030 031 040 045 055 065 075
14 32 35 35 54 45 50 56 64 27 34 36 36 55 48 54 55 63 14 36 39 39 59 103 107 113 120 23 38 40 40 62 101 106 111 118
Page 16
16
Indoor air discharge (50VZ/PZ)
The 50VZ/PZ units leave the factory with the indoor unit air discharge set to vertical, as indicated in the dimensional figures. It can be changed to horizontal discharge by following the steps below:
Change from vertical to horizontal discharge without changing the position of the motor
a. Detach the side access panels . b. Remove the drive belt(s) (only sizes 50VZ/PZ 015,
045, 055, 065, 075). c. Detach rear blanking plate and fan supply air ducts . d. Detach the fans from the reinforcement flanges of the
upper panel and from the U-bracket . e. Detach the U-bracket from the angle iron attached to
the base . Remove the U-bracket . f. Install the fans, attaching them to the reinforcement
flanges of the rear panel and base support . g. Install strengthening support , attaching it between the
fan and the roof (only sizes 50VZ/PZ 045-055-065-075). h. Install blanking plate in the upper panel and fan supply
air ducts in the unit rear panel. i. Replace the drive belt(s) and ensure that the tension and
alignment are correct (only sizes 50VZ/PZ 015, 045, 055,
065, 075). j. Replace the access panels .
See figures 15 and 16.
Change from vertical to horizontal discharge with changing the position of the motor
a. Detach the side access panels . b. Remove the drive belt(s) . c. Detach rear blanking plate and fan supply air ducts . d. Detach the fans from the reinforcement flanges of the
upper panel and from the U-bracket . e. Detach the U-bracket from the angle iron attached to
the base . Remove the U-bracket . f. For units 50VZ/PZ 025, 030, 031 and 040 change the
motor to the other fan. g. For units 50VZ/PZ 045, 055, 065 and 075 detach the drive
base together with the motor and reposition it on the
opposite side. h. Remove the fan pulley and reposition it on the other
side. i. Install the fans, attaching them to the reinforcement
flanges of the rear panel and base support . j. Install strengthening support , attaching it between the
fan and the roof (only sizes 50VZ/PZ 045-055-065-075). k. Install blanking plate in the upper panel and fan supply
air ducts in the unit rear panel. l. Replace the drive belt(s) and ensure that the tension and
alignment are correct. m. Replace the access panels .
See figures 15 and 16.
Indoor air discharge (40PZ)
The 40PZ units leave the factory with the air discharge set to horizontal, as indicated in the dimensional figures. It can be changed to vertical discharge by following the steps below:
Change from horizontal to vertical discharge without changing the position of the motor
a. Detach the side access panels . b. Remove the drive belt(s) (only sizes 40PZ 015, 045,
055, 065, 075). c. Detach top blanking plate and fan supply air ducts . d. Detach strengthening support between the fan and the
roof (only sizes 40PZ 045-055-065-075). Discard the
support. e. Detach the fans from the reinforcement flanges of the rear
panel and from base support . f. Install U-bracket , included with the unit, by attaching it
to base support . g. Install the fans, attaching them to the reinforcement
flanges of the upper panel and to U-bracket . h. Install blanking plate in the rear panel and fan supply
air ducts in the upper unit panel. i. Replace the drive belt(s) and ensure that the tension and
alignment are correct (only units 40PZ 015, 045, 055, 065,
075).
j. Replace the access panels .
See figures 15 and 16.
Change from horizontal to vertical discharge with changing the position of the motor
a. Detach the side access panels . b. Remove the drive belt(s) . c. Detach top blanking plate and fan supply air ducts . d. Detach strengthening support between the fan and the
roof (only sizes 40PZ 045-055-065-075). Discard the
support. e. Detach the fans from the reinforcement flanges of the rear
panel and from base support . f. Install U-bracket , included with the unit, by attaching it
to base support . g. For units 40PZ 025, 030, 031, 040 change the motor to the
other fan. h. For units 40PZ 045, 055, 065, 075 detach the drive base
together with the motor and reposition it on the opposite
side. i. Remove the fan pulley and reposition it on the other
side. j. Install the fans, attaching them to the reinforcement
flanges of the upper panel and to U-bracket . k. Install blanking plate in the rear panel and fan supply
air ducts in the upper unit panel. l. Replace the drive belt(s) and ensure that the tension and
alignment are correct. m. Replace the access panels .
See figures 15 and 16.
Page 17
17
Fig. 15 - Repositioning unit air discharge
(50VZ/PZ 025, 030, 031, 040
40PZ 025, 030, 031, 040)
Legend
Side access panel Rear discharge panel Top panel Angle iron attached to the base U-bracket Blanking plate Fan supply air ducts Drive belt(s) Fan pulley
Fig. 16 - Repositioning unit air discharge
(50VZ/PZ 015, 045, 055, 065, 075
40PZ 015, 045, 055, 065, 075)
Legend
Side access panel Rear discharge panel Top panel Angle iron attached to the base U-bracket Blanking plate Fan supply air ducts Drive belt(s) Fan pulley Strengthening support
Front view
Front view
Rear view
Side view (vertical discharge) Side view (horizontal discharge)
Rear view
Side view (vertical discharge) Side view (horizontal discharge)
Page 18
18
Fan performance
50VZ/PZ 015 indoor fan (40PZ 015) standard transmission
50VZ/PZ 015 indoor fan (40PZ 015) optional larger transmission
50VZ/PZ 015 outdoor fan (38VZ/PZ 015) standard transmission
Indoor fan Outdoor fan
Curve Pulley open Standard Superior Standard Superior
r/s r/s r/s r/s
0 Closed 19.6 23.08 1 1 18.75 22.18 2 2 18.33 21.28 3 3 17.67 20.38 4 4 17 19.5 5 5 16.33 18.6 Factory 3.5 17.33 15.25
Available static pressure, Pa
Available static pressure, Pa
Available static pressure, Pa
Air flow, l/s
Power input, kW
Air flow, l/s
Power input, kW
Air flow, l/s
Power input, kW
Page 19
19
Fan performance
50VZ/PZ 025 indoor fan (40PZ 025) standard transmission
50VZ/PZ 025 indoor fan (40PZ 025) optional larger transmission
50VZ/PZ 025 outdoor fan (38VZ/PZ 025) standard transmission
Indoor fan Outdoor fan
Curve Pulley open Standard Superior Standard Superior
r/s r/s r/s r/s
0 Closed 19.8 20.5 17.42 19.33 1 1 18.33 19.83 16.66 18.46 2 2 17.58 19.16 15.92 17.6 3 3 16.83 18.5 15.16 16.73 4 4 16.08 17.83 14.42 15.86 5 5 15.33 17.16 13.66 15 Factory 3.5/2* 16.45 15.92
* The first value is for the indoor unit pulley; the second value is for the outdoor unit pulley
Available static pressure, Pa
50VZ/PZ 025 outdoor fan (38PV/PZ 025) optional larger transmission
Air flow, l/s
Power input, kW
Available static pressure, Pa
Air flow, l/s
Power input, kW
Available static pressure, Pa
Air flow, l/s
Power input, kW
Available static pressure, Pa
Air flow, l/s
Power input, kW
Page 20
20
Fan performance
50VZ/PZ 030/031 indoor fan (40PZ 030/031) standard transmission
50VZ/PZ 030/031 indoor fan (40PZ 030/031) optional larger transmission
50VZ/PZ 030/031 outdoor fan (38VZ/PZ 030/031) standard transmission
Indoor fan Outdoor fan
Curve Pulley open Standard Superior Standard Superior
r/s r/s r/s r/s
0 Closed 19.33 21.76 18.2 20.5 1 1 18.5 20.76 17.36 19.58 2 2 17.66 19.76 16.53 18.66 3 3 16.92 18.76 15.7 17.75 4 4 15.83 17.76 14.86 16.83 5 5 14.92 16.76 14.03 15.92 Factory 2.5/2* 17.29 16.53
* The first value is for the indoor unit pulley; the second value is for the outdoor unit pulley
50VZ/PZ 030/031 outdoor fan (38PV/PZ 030/031) optional larger transmission
Available static pressure, Pa
Air flow, l/s
Power input, kW
Available static pressure, Pa
Air flow, l/s
Power input, kW
Available static pressure, Pa
Air flow, l/s
Power input, kW
Available static pressure, Pa
Air flow, l/s
Power input, kW
Page 21
21
Fan performance
50VZ/PZ 040 indoor fan (40PZ 040) standard transmission
50VZ/PZ 040 indoor fan (40PZ 040) optional larger transmission
50VZ/PZ 040 outdoor fan (38VZ/PZ 040) standard transmission
Indoor fan Outdoor fan
Curve Pulley open Standard Superior Standard Superior
r/s r/s r/s r/s
0 Closed 21.92 24.33 15 17 1 1 21.08 23.42 14.5 16.33 2 2 20.25 22.5 14 15.66 3 3 19.42 21.58 13.5 15 4 4 18.5 20.66 13 14.33 5 5 17.58 19.75 12.5 13.66 Factory 2.5/2.5* 19.84 13.75
* The first value is for the indoor unit pulley; the second value is for the outdoor unit pulley
50VZ/PZ 040 outdoor fan (38PV/PZ 040) optional larger transmission
Available static pressure, Pa
Air flow, l/s
Power input, kW
Available static pressure, Pa
Air flow, l/s
Power input, kW
Available static pressure, Pa
Air flow, l/s
Power input, kW
Available static pressure, Pa
Air flow, l/s
Power input, kW
Page 22
22
Fan performance
50VZ/PZ 045 indoor fan (40PZ 045) standard transmission
50VZ/PZ 045 indoor fan (40PZ 045) optional larger transmission
50VZ/PZ 045 outdoor fan (38VZ/PZ 045) standard transmission
Indoor fan Outdoor fan
Curve Pulley open Standard Superior Standard Superior
r/s r/s r/s r/s
0 Closed 19.5 21.33 12.25 12.83 1 1 18.66 20.58 11.75 12.33 2 2 17.92 19.83 11.25 11.83 3 3 17.16 19.08 10.75 11.33 4 4 16.42 18.33 10.25 10.83 5 5 15.66 17.58 9.75 10.33 Factory 3/3* 17.16 10.75
* The first value is for the indoor unit pulley; the second value is for the outdoor unit pulley
50VZ/PZ 045 outdoor fan (38PV/PZ 045) optional larger transmission
Available static pressure, Pa
Air flow, l/s
Power input, kW
Available static pressure, Pa
Air flow, l/s
Power input, kW
Available static pressure, Pa
Air flow, l/s
Power input, kW
Available static pressure, Pa
Air flow, l/s
Power input, kW
Page 23
23
Fan performance
50VZ/PZ 055 indoor fan (40PZ 055) standard transmission
50VZ/PZ 055 indoor fan (40PZ 055) optional larger transmission
50VZ/PZ 055 outdoor fan (38VZ/PZ 055) standard transmission
Indoor fan Outdoor fan
Curve Pulley open Standard Superior Standard Superior
r/s r/s r/s r/s
0 Closed 21.16 22.75 13 15 1 1 20.42 22 12.5 14.5 2 2 19.66 21.16 12 14 3 3 18.92 20.42 11.5 13.5 4 4 18.16 19.58 11 13 5 5 17.42 18.83 10.5 12.5 Factory 4/2* 18.16 12
* The first value is for the indoor unit pulley; the second value is for the outdoor unit pulley
50VZ/PZ 055 outdoor fan (38PV/PZ 055) optional larger transmission
Available static pressure, Pa
Air flow, l/s
Power input, kW
Available static pressure, Pa
Air flow, l/s
Power input, kW
Available static pressure, Pa
Air flow, l/s
Power input, kW
Available static pressure, Pa
Air flow, l/s
Power input, kW
Page 24
24
Fan performance
50VZ/PZ 065 indoor fan (40PZ 065) standard transmission
50VZ/PZ 065 indoor fan (40PZ 065) optional larger transmission
50VZ/PZ 065 outdoor fan (38VZ/PZ 065) standard transmission
Indoor fan Outdoor fan
Curve Pulley open Standard Superior Standard Superior
r/s r/s r/s r/s
0 Closed 21.5 22.66 12.75 14.33 1 1 20.66 21.9 12.25 13.83 2 2 19.83 21.13 11.75 13.33 3 3 19 20.36 11.25 12.73 4 4 18.16 19.6 10.83 12.33 5 5 17.33 18.83 10.42 11.83 Factory 3.5/2* 18.58 11.75
* The first value is for the indoor unit pulley; the second value is for the outdoor unit pulley
50VZ/PZ 065 outdoor fan (38PV/PZ 065) optional larger transmission
Available static pressure, Pa
Air flow, l/s
Power input, kW
Available static pressure, Pa
Air flow, l/s
Power input, kW
Available static pressure, Pa
Air flow, l/s
Power input, kW
Available static pressure, Pa
Air flow, l/s
Power input, kW
Page 25
25
Fan performance
50VZ/PZ 075 indoor fan (40PZ 075) standard transmission
50VZ/PZ 075 indoor fan (40PZ 075) optional larger transmission
50VZ/PZ 075 outdoor fan (38VZ/PZ 075) standard transmission
Indoor fan Outdoor fan
Curve Pulley open Standard Superior Standard Superior
r/s r/s r/s r/s
0 Closed 22.66 23.58 14.33 15 1 1 21.9 22.75 13.83 14.5 2 2 21.13 21.92 13.33 14 3 3 20.36 21.08 12.83 13.5 4 4 19.6 20.25 12.33 13 5 5 18.83 19.42 11.83 12.5 Factory 3/2.5* 20.36 13.08
* The first value is for the indoor unit pulley; the second value is for the outdoor unit pulley
50VZ/PZ 075 outdoor fan (38PV/PZ 075) optional larger transmission
Available static pressure, Pa
Air flow, l/s
Power input, kW
Available static pressure, Pa
Air flow, l/s
Power input, kW
Available static pressure, Pa
Air flow, l/s
Power input, kW
Available static pressure, Pa
Air flow, l/s
Power input, kW
Page 26
26
SAFETY CONSIDERATIONS
Installation and servicing of air conditioning equipment can be hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install, start-up or service air conditioning equipment. Untrained personnel can perform the basic maintenance functions of cleaning and replacing filters.
All other operations should be performed by trained service personnel.
When working on air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for unbrazing operations.
WARNING: Before performing service or maintenance operations on the unit, turn off the main power switch to the unit. Electrical shock could cause personal injury.
All units are designed for ducted installation (indoor and/or outdoor air discharge). If ducts are not used the installer must place a protection grille in the discharge.
Only for use when repairing "Original Spare Parts". For repairs, special attention must be paid to the correct installation of the spare parts. The parts must always be installed in their original position.
During unit operation, some of the refrigerant circuit elements could reach a temperature in excess of 70°C so only trained or qualified personnel should access areas protected by access panels.
This unit should not be installed in an explosive atmosphere.
The unit can operate in normal radioelectric atmospheres in residential, commercial and light industrial installations. For other applications, please consult Carrier.
INSTALLATION
1. Inspect shipment. Inspect the unit. If it is damaged, or if the shipment is incomplete, immediately file a claim with the shipping company.
2. Check that the local power supply agrees with the specification on the unit nameplate.
Siting the unit
Check the following points:
- The location must be able to support the unit operating weight (see Table 1).
- Allow sufficient space for servicing and air flow around the unit (see Fig. 8).
- Select a location free of dust or foreign matter which may cause coil clogging.
- When installing the unit on the ground, select a site which is not subject to flooding (outdoor unit).
- Consult all applicable rules and standards which govern the installation of air conditioning equipment.
- Both the indoor and the outdoor unit are supplied with transport skids. These skids must be removed, except when vibration absorbers are installed.
Rigging
1. When rigging, use spreaders to prevent damage to the panels. Avoid violent movements.
2. To prevent damage while in transit, do not remove the unit from the skid until it is at its final location.
3. Never roll or tip the unit more than 15°.
IMPORTANT: Make sure that all unit panels are fixed in place before moving. Raise and set down the unit carefully.
Fig. 17 - Rigging (50VZ/PZ)
A
Page 27
27
Fig. 18 - Rigging (38VZ/PZ) Ductwork (indoor air discharge)
The ductwork dimensions should be determined in accordance with the air flow to be carried, and the available static pressure of the unit. The different air flows and static pressures which each unit can supply, are shown in the fan performance tables.
It is recommended to observe the following considerations:
- Whatever type of ductwork is used, it should not be made of materials which are flammable, or which give off toxic gases in the event of a fire. The internal surfaces should be smooth, and not contaminate the air which passes through. It is recommended to use sheet metal ducts which are adequately insulated to avoid condensation and thermal leakage.
- At the points where the ducts join the unit, it is recommended to use flexible connections which absorb vibrations, prevent noise inside the ductwork and allow access to the unit.
- Bends near the unit outlet should be avoided as much as possible. If unavoidable, they should be as slight as possible, and internal deflectors should be used when the duct has large dimensions.
NOTE: All duct sizing and design work should be carried out by qualified technicians.
Condensate drainage 50VZ/PZ and 38VZ/PZ units
The indoor unit evacuates condensate water via the condensate pan of the outdoor heat exchanger (38VZ/PZ) which incor­porates two male ø 3/4" gas drain connections, one for each side of the unit. Depending on the installation site, either of these drains can be used, and the unused drain should be plugged.
40PZ units
These units incorporate a condensate pan with a drain pipewith an outside diameter of 25 mm.
The connection to the drain pipe can be vertical (Fig. 20) or horizontal (Fig. 21).
• Vertical drain: Remove the prepunched knockout(s) in the unit base.
• Horizontal drain: Remove the prepunched knockout(s) in the side of the unit base.
Fig. 20 - Vertical drain (40PZ)
Fig. 19 - Rigging (40PZ)
IMPORTANT: The unit should be correctly levelled.
Field-supplied
Drain pipe OD 25 mm
Drain pan
Unit base
A
A
A
Page 28
28
Electrical connections
WARNING: To prevent electrical shock or equipment damage, make sure disconnects are open before electrical connections are made. If this action is not taken, personal injury may occur.
The unit power supply cables must not be lighter than normal flexible polychloroprene covering cable (designation H05 RN-F).
Route all cables through the conduits incorporated in the unit (50VZ/PZ or 38VZ/PZ) to the main disconnect switch terminals (see wiring diagram).
Voltage to the unit must be within 2% of the voltage and 10% of the current indicated on the nameplate. Contact your local power company for correction of an incorrect line voltage.
Take special care when making the earth connection. This cable must be connected first and it must be longer than the power cable.
WARNING: Operation of the unit on improper line voltage constitutes abuse and is not covered by the Carrier warranty.
IMPORTANT: To ensure the correct power supply, it is necessary to first determine the cable section. This must take into account the unit electrical data (see electrical data table) and the line length (max. permissible voltage drop 5%).
If the unit includes electric heat, this must be taken into account for the supply line sizing.
Never operate a unit if the voltage imbalance exceeds 2%. The following formula must be used to determine the percentage of voltage imbalance.
Voltage imbalance % =
Largest deviation from average voltage
Average voltage
Fig. 21 - Horizontal drain (40PZ)
Field-supplied
Drain pipe OD 25 mm
Drain pan
Unit base
Example:
Nominal supply: 400-3-50
AB = 404 V BC = 399 V AC = 394 V
Average voltage = 404 + 399 + 394 = 399 = 400 V
3
Determine maximum deviation from average voltage:
AB = 404 - 400 = 4 BC = 400 - 399 = 1 AC = 400 - 394 = 6
Largest deviation is 6 volts. Percentage voltage imbalance is therefore:
6 x 100 = 1.5% 400
VERY MPORTANT: The installer must protect the unit power supply line with automatic disconnect devices, a thermal­magnetic switch and a differential disconnect switch, suitable for the installation and in according with applicable legislation.
Electrical connection between the units (38VZ/PZ and 40PZ)
The general power supply for the complete system (indoor and outdoor unit) must be made via the outdoor unit (38VZ/PZ).
Consult the wiring diagram that is supplied with the units. This will show all power connections to be made between the 38VZ/ PZ unit and the 40PZ unit.
The unit connection cables must not be lighter than normal flexible polychloroprene covering cable (designation H05 RN-F) with a wire section that is adequate for the 40PZ unit power consumption.
The power supply for the electric heater of the indoor unit must be provided from the main disconnect switch.
Thermostat connection
Thermostat/unit connection must be via a loom (wire section 1 mm2) manufactured in accordance with the wiring diagram accompanying the unit.
Follow the instructions supplied with the control for thermostat assembly and handling.
The general rules below should be taken into account:
Page 29
29
NOTE 1: This control is compatible with any kind of electromechanical or electronic control (without anticipation resistors) with the following features:
- Voltage at 24 V AC
50VZ units standard connections:
R Connection to 24 V L Protection device indication C Common 24 V G Ventilation Y1 First stage cooling Y2 Second stage cooling W1 First stage heating (option) W2 Second stage heating (option)
50PZ units standard connections:
R Connection to 24 V L Protection device indication C Common 24 V G Ventilation Y1 First stage (cooling/heating) Y2 Second stage (cooling/heating) W1 First stage heating (option) O Reversing valve*
* The O connection is activated in cooling.
NOTE 2: If the thermostat wiring is incorrect, the control will be blocked (red LED on) and all the outlets will be deactivated when unit power is supplied. NOTE 3: The thermostat cables should be separate from any 220 V or 380 V cable.
Refrigerant line connections (38VZ/PZ and 40PZ)
To guarantee correct unit performance ensure that the line length and number of bends are kept to a minimum. Avoid pipe kinking by using large radius bends.
IMPORTANT: Always use refrigerant-grade deoxidized and dehydrated copper tubing between the indoor and outdoor units.
Before connecting the refrigerant lines carefully follow the steps below:
- Remove the nitrogen holding charge from the refrigerant circuits.
- Select the diameter of the copper tubing according the the units installed and according to the distance between the indoor and outdoor units.
- Use silver alloy rod for soldering purposes, and ensure that this work is done in a nitrogen atmosphere.
- To avoid oxidation insulate the refrigerant lines adequately.
- Pull a vacuum in the refrigerant circuit until a pressure of
6.9 Pa is maintained for at least 2 hours.
- Charge the refrigerant circuit with the necessary amount of R-407C refrigerant (in accordance with table 1 and the length of the refrigerant lines).
- Check there are no refrigerant leaks.
Refrigerant line selection
General
When designing refrigerant lines the following must be kept in mind:
- Depending on the unit arrangement:
Fig. 22 - Refrigerant lines option A
Heat pump (discharge line)
Outdoor unit
Indoor unit
Heat pump
Liquid line
Cooling
Gas line
Cooling (suction line)
Suction/discharge line:
- A siphon at the base of the vertical pipe run and inter­mediate siphons every 8 m or oil separators are needed.
- Most unfavourable condition: the suction speed in the vertical pipe run must be more than 6 m/s.
Fig. 23 - Refrigerant lines option B
Heat pump (discharge line)
Outdoor unit
Indoor unit
Heat pump
Liquid line
Cooling
Gas line
Cooling (suction line)
Suction/discharge line:
- For heat pumps a siphon is required in the base of the vertical pipe run.
- The intermediate siphon can be omitted.
- For cooling only units siphons are not required.
- Most unfavourable condition: the suction/discharge speed in the vertical pipe run must be more than 6 m/s.
Page 30
30
For both option A (Figure 22) and option B (Figure 23) the following conditions should be observed:
- The maximum speed permitted in any line is 15 m/s.
- Suction line must be insulated and have a 2% slope towards the compressor and the horizontal pipe run.
- In long pipe runs it may be necessary to adjust the oil charge.
- If the liquid line flow is downward, it is necessary to install pressure equalizer for heights above 10 m.
- The liquid should be subcooled by at least 1 K at the restrictor inlet. In this case, if the liquid line flow is upward and the pipe is longer than 15 m, it must be subcooled by 1 K for each 3.5 m in excess of 15 m.
- Subcooling can be contained in the liquid and suction lines (maximum 15 m) of the units.
- For each metre of refrigerant pipe installed, refrigerant has to be added in accordance with table 3.
Table 3 - Refrigerant charge (g/m)
Diameter 1/2" 5/8" 3/4" 7/8" 1-1/8" 1-3/8"
Liquid line 75 120 180 250 420 645
Suction line 14 23 34 47 81 123
Sizing
Suction/discharge line
The gas line is the suction line in cooling and the discharge line in heat pump operation. Its diameter is calculated for the most unfavourable condition. This can be as a suction or as a discharge line and has to be checked afterwards for the other line type.
For example, in the configuration shown in option A (the suction speed will produce the most unfavourable condition, and the gas line diameter will be calculated for suction. Afterwards, the calculation should be checked for discharge. The diameter calculation for suction and discharge lines is done in the same way using the corresponding drawing (see Figs. 24 and 25).
Fig. 24 - Suction line
Fig. 25 - Discharge line
Legend:
38VZ/PZ 015 + 40PZ 015 38VZ/PZ 031 + 40PZ 031
38VZ/PZ 040 + 40PZ 040
38VZ/PZ 025 + 40PZ 025 38VZ/PZ 045 + 40PZ 045
38VZ/PZ 030 + 40PZ 030 38VZ/PZ 055 + 40PZ 055
38VZ/PZ 065 + 40PZ 065
38VZ/PZ 075 + 40PZ 075
Legend:
38VZ/PZ 015 + 40PZ 015 38VZ/PZ 031 + 40PZ 031
38VZ/PZ 040 + 40PZ 040
38VZ/PZ 025 + 40PZ 025 38VZ/PZ 045 + 40PZ 045
38VZ/PZ 030 + 40PZ 030 38VZ/PZ 055 + 40PZ 055
38VZ/PZ 065 + 40PZ 065
38VZ/PZ 075 + 40PZ 075
From Figures 24 and 25, for the selected unit we can obtain the pressure drop corresponding to 10 m of equivalent length for each diameter.
For other equivalent lengths, the pressure drop is obtained in direct proportion. The total pressure drop for the line (sum corresponding to the vertical and horizontal pipe runs) must not be higher than 20 kPa.
Liquid line:
The liquid line diameter can be selected using table 4.
Table 4 - Liquid line
Models Total equivalent length
Up to 10 m From 10-30 m From 30-50 m
38VZ/PZ 015 + 40PZ 015 5/8" 5/8" 5/8" 38VZ/PZ 025 + 40PZ 025 5/8" 5/8" 3/4" 38VZ/PZ 030 + 40PZ 030 5/8" 3/4" 3/4" 38VZ/PZ 031 + 40PZ 031 5/8" 5/8" 5/8" 38VZ/PZ 040 + 40PZ 040 5/8" 5/8" 5/8" 38VZ/PZ 045 + 40PZ 045 5/8" 5/8" 3/4" 38VZ/PZ 055 + 40PZ 055 5/8" 3/4" 3/4" 38VZ/PZ 065 + 40PZ 065 5/8" 3/4" 7/8" 38VZ/PZ 075 + 40PZ 075 3/4" 7/8" 7/8"
Necessary checks/precautions before start-up
- Ensure that all electrical connections are properly tightened.
- Ensure that the unit is level and well-supported.
- Check the condition of the ductwork in case damage has occurred during installation.
- The air filter should be clean and in place.
- All the panels should be fitted and firmly secured with the corresponding screws.
- Make sure that there is sufficient space for servicing and maintenance purposes.
SPEED (m/s)
SPEED (m/s)
Page 31
31
- Check the drain connections.
- Ensure that there are no refrigerant leaks.
- Confirm that the electrical power source agrees with the unit nameplate rating.
- Make sure that compressors float freely on the mounting springs.
WARNING: The compressors are mounted on vibration isolators. Do not loosen or remove the support mounting bolts.
- Check for proper fan rotation.
Refrigerant charge
Gas tightness testing and dehydration
50VZ/PZ units are shipped fully charged with refrigerant R-407C ready for operation. If, when the unit is run, symptoms of loss of charge (for example, low pressure switch tripping or abnormally low cooling capacities) are detected, first conduct a leak test followed, if necessary, by a gas tightness test using compressed nitrogen. For the latter all refrigerant must be removed from the circuit. Transfer the refrigerant to a storage tank and then rinse the circuit. For your information, we are listing here some precautions that need to be taken into consideration, when working with these units.
Refrigerant guidelines for R-407C
Refrigerant R-407C consists of a non-azeotropic blend of 23% of R-32, 25% of R-125 and 52% of R-134a, and is character­ised by the fact that at the time of the change in state the temperature of the liquid/vapour mixture is not constant. All checks must be pressure tests, and the appropriate pressure/ temperature ratio table must be used for the interpretation of the values.
Leak detection is especially important for units charged with refigerant R-407C. Depending on whether the leak occurs in the liquid or the vapour phase, the proportion of the different components in the mixture remaining in the unit is not the same.
The following basic guidelines must be observed:
• Leaks must be repaired immediately by qualified personnel.
• Refrigerant must never be discharged to the atmosphere.
• Use a refrigerant reclaim unit.
• Any loss of oil from the system during maintenance must be stopped immediately and the collected oil must by removed in accordance with applicable regulations
38VZ/PZ and 40PZ units are supplied with a nitrogen holding charge. This must be removed before soldering the connecting refrigerant lines to the unit. Once the soldering has been completed, the complete refrigerant circuit must be evacuated then the correct quantity of R-407C refrigerant for each system must be charged.
WARNING: If any brazing is to be done the refrigerant circuit must be filled with nitrogen. Combustion of refrigerant produces toxic phosgene gas.
VERY IMPORTANT:
- Never use the compressor as a vacuum pump.
- If more refrigerant is needed add gas very slowly via the suction line. Liquid refrigerant must never be introduced into the suction line.
- Do not overcharge with refrigerant.
START-UP
Actual start-up should only be done under the supervision of a qualified refrigeration mechanic. These units include the Master Link II electronic control. The operation of the control is explained in the instructions accompanying each unit.
Initial checks
With the unit in operation, ensure that the values shown on the high and low pressure gauges are within the normal limits. It is advisable to simulate unit shutdown due to high and low pressure, in order to make sure that the pressurestats work properly. To do so, proceed as follows:
- High pressure shutdown: Completely cover the outdoor air inlet, or disconnect the outdoor fan and motor. The unit should stop at a pressure of 2844 kPa.
- Low pressure shutdown: Cover the indoor air inlet, or dis- connect the indoor fan and motor. Observe the low
pressure
gauge. The unit should stop at a pressure of 265 kPa.
In both cases, after a reasonable time, reset the unit through the remote control as previously indicated.
Check that the motor and compressor consumptions are approximately the same as those shown on the unit nameplate. Consumption data is also given in Table 2.
Refrigerant system description
The refrigerant circuit incorporates the following primary elements:
- Refrigerant-air heat exchanger: made of high quality copper tubes and pretreated aluminium fins, for extra corrosion resistance and greater protection than offered by copper fins.
- Refrigerant lines: made completely of high quality copper.
- Expansion valve or metering device.
- Compressors: hermetic reciprocating or scroll
compressors depending on model, cooled by suction gas. They incorporate internal protection.
- Filter drier and Schrader valves.
- Safety elements: high, low pressurestat.
- All units are supplied with the correct refrigerant charge.
- The split system units are supplied with a nitrogen holding charge which must be evacuated and replaced with the right refrigerant charge for the unit size and the connection lines.
Compressor replacement
When an internal fault occurs, the compressor must be replaced. This must be done as detailed below:
- Disconnect the unit from the electrical supply.
- Remove the panels.
Page 32
32
Table 7 - Heat pump operation
Zone Air temperature
Dry bulb Wet bulb
Indoor
Maximum 27°C-
Outdoor
Maximum 24°C18°C Minimum -15°C-
OPTIONS AND ACCESSORIES
Option Accessory
Head pressure control kit x x Electric heating x x Compressor crankcase heater (standard on 50PZ) x x Hot water coil x x Economizer x Outdoor air filter x x User interface x Protection grille x x Minimum opening potentiometer x x Volt-free contacts x Optional communications x x Return air sensor x x Superior drive x 38VZ/PZ for vertical discharge x
Hot water heating coil
This option/accessory consists of the water heating coil, the air flow equalising plate, the side access panel and fixing components.
The heating coil performances are in accordance with Eurovent conditions and are shown in tables 8 and 9.
Table 8
Unit 015 025 030 031 040 045 055 065 075
Heating capacity kW* 9.6 17.5 19.6 19.6 27.3 33.4 35.3 41 43.8 Water flow l/s 0.46 0.84 0.94 0.94 1.31 1.60 1.69 1.96 2.09 Pressure drop kPa 13 20 14.5 14.5 13.5 21 23 33.5 37.5
* Indoor air temperature 20°C and entering/leaving water temperature 50°C/45°C.
Table 9
Unit 015 025 030 031 040 045 055 065 075
Heating capacity kW* 15.2 27.9 30.4 30.4 43.4 51.5 54.6 63.9 68.5 Water flow l/s 0.36 0.67 0.72 0.72 1.04 1.23 1.31 1.52 1.64 Pressure drop kPa 9 13 9 9 9 13 14.5 21 24
* Indoor air temperature 20°C and entering/leaving water temperature 70°C/60°C.
Water connection
The entering and leaving water connections are all threaded male gas connections with the diameters shown in Table 10.
Table 10
Unit 015 025 030 031 040 045 055 065 075
Ø connection 1” 1” 1-1/4” 1-1/4” 1-1/4” 1-1/2” 1-1/2” 1-1/2” 1-1/2”
- Remove the gas from the refrigerant circuit using recovery equipment to avoid harming the atmosphere.
- Electrically disconnect the compressor.
- Unbraze or unscrew the suction and discharge lines, taking care not to damage the rest of the components.
- Remove the fastenings from the compressor.
- Replace the compressor, ensuring that it contains sufficient oil.
- Braze or screw in the lines.
- Connect the compressor according to the wiring diagram.
- Evacuate the compressor.
- Fill in the refrigerant charge indicated on the nameplate, plus the required charge for the refrigerant connection lines, if the system is a split system.
NOTE: This operation must be done by a qualified technician.
Description of unit protection devices
The unit includes the following unit protection devices:
- Internal compressor protector to avoid overheating.
- Short-cycle protection (included in the main electronic board).
- Outdoor fan motor thermomagnetic switch.
- Indoor fan motor thermomagnetic switch.
- High pressurestat - This protects the unit against excessive condensing pressure. The high pressurestat has factory-fixed non-adjustable settings. To check, see section Initial checks.
- Low pressurestat - This protects the unit against excessive low pressure in the evaporator. The low pressurestat has factory fixed non-adjustable settings. To check, see section Initial checks.
CAUTION: When any of these cuts out, the unit stops and will not re-start until the contacts have been reclosed after rectification of the fault.
Table 5 - Pressure switch settings
Cut-out Cut-in Reset
High pressurestat *2844 kPa 1863 kPa Automatic Low pressurestat *265 kPa 363 kPa Automatic
* Factory-fitted
WARNING: Alteration of factory settings other than the design set-point, without manufacturer's authorisation, may void the warranty.
Operating limits
These units have been designed to operate within the following limits:
Table 6 - Cooling operation
Zone Air temperature
Dry bulb Wet bulb
Indoor
Maximum 35°C21°C Minimum 19°C14°C
Outdoor
Maximum 46°C­Minimum 19°C* -
* With the optional head pressure control, the unit can operate with temperatures below 19°C.
Page 33
33
Installation
The standard installation of the water heating coil is made by positioning the connection manifolds on the same side as the motor of the evaporator unit. If necessary, it can be connected to the opposite side. In this case the coil must be turned by 180°.
The installation sequence is as follows: a. Disconnect the power supply to the unit. b. Remove the side access panels. c. Loosely screw in the 4 screws provided to attach the
heating coil to the headers of the evaporator coil (leaving a free space of 3-4 mm untightened).
d. Install the heating coil, inserting the semi-attached screws
in the grooves of the headers. e. Fix the 4 screws provided to attach the heating coil. f. Install the perforated plate in the upper part of the coil,
covering the space that remains between the coil and the
unit top panel. g. Connect heating coil sensor BT4 to terminals 39 and 40 of
the indoor unit terminal box, and from here to terminals
39 and 40 of the outdoor unit. h. Change the position of dipswitch 3 on the main board AO
to position “ON”. i. For water heating coils with a proportional valve an
extension board A2 must be installed and connected in
accordance with the wiring diagram for this option. In all
cases, both for the all-or-nothing control valve and for
the proportional valve the elctrical conections must be
made in accordance with the wiring diagram.
j. Install the blanking plate, supplied with the coil, on the cor-
responding side, after punching out the prepunched holes for
the entering and leaving water connections of the manifolds.
Table 11
Model Unit 015 025 030 031 040 04 5 055 065 075
6 kW Cooling only x
Heat pump x
12 kW Cooling only xxx
Heat pump xxxxx
15 kW Cooling only xx
Heat pump xxxx
18 kW Cooling only
Heat pump xxxx
18 (9+9) kW* Cooling only xx
Heat pump
24 (12+12) kW* Cooling only xxxx
Heat pump
* 2-stage heating
Fig. 26
Electric resistance heaters
This option/accessory consists of a frame with shielded electric heaters and a control box, incorporated in the same frame, with all electrical and protection components required to guarantee total safety. For the available capacities see Table 11.
Fig. 27
Installation
The standard installation of the electric heating coil is made by positioning the control box on the same side as the motor of the evaporator unit.
If necessary, it can be positioned on the opposite side. In this case the coil must be turned by 180°.
VERY IMPORTANT: If the coil is installed on the opposite side, it is NECESSARY to change the position of the two thermal protectors to the opposite longitudinal beam, i.e. the thermal protectors must always be positioned in the upper part of the coil.
The installation sequence is as follows: a. Disconnect the power supply to the unit. b. Remove the side access panels. c. Loosely screw in the 4 screws provided to attach the
electric heater to the headers of the evaporator coil (leaving a free space of 3-4 mm untightened).
d. Install the electric heater, inserting the semi-attached
screws in the grooves of the headers. e. Fix the 4 screws provided to attach the electric heater. f. Make all electrical connections in accordance with the
wiring diagram supplied with this option. g. Install the blanking plates in their correct positions.
Page 34
34
SERVICE
Indoor fan air adjustment
The drive is factory set in accordance with the tables on pages 18-25. When indoor pressure and air flow requirements differ from nominal ratings, the motor pulley can be adjusted for different available static pressure values.
To change the fan speed (see Fig. 28):
1. Move the motor along its track in order to remove the belt.
2. Loosen the pulley setscrews and rotate as necessary.
3. Tighten the setscrews .
4. Replace the belt(s) in the channel of the pulley.
5. Tighten the belt(s), using the tension screw nut and washer .
To align fan and motor pulleys:
1. Loosen fan pulley setscrews. Slide fan pulley along the pulley shaft and align with the motor using a ruler, making sure that it is parallel to the belt.
2. Tighten the fan pulley setscrews.
To adjust the belt tension, loosen the motor mounting plate bolts and slide the motor mounting plate until the belt is as shown in Fig. 29.
Fig. 28 - Fan speed adjustment
Legend 1 Motor support 2 Motor pulley 3 Setscrews 4 Motor 5 Belt 6 Tensioning screw 7 Fan pulley 8 Fan scroll
GENERAL MAINTENANCE
ATTENTION: Before starting any servicing or maintenance operation on the unit, make sure that the power supply has been disconnected. A current discharge could cause personal injury.
In order to obtain maximum performance from the unit special attention should be paid to the following points:
- Electrical connections: The supply voltage should be
±10% of the nominal voltage limits.
Ensure that no faulty contacts exist in the terminal blocks, contactor boards, etc. Make sure that all the electrical connections are properly tightened, and that all the electrical components (contactors, relays, etc) are firmly secured to the corresponding rails. Pay special attention to the condition of the connecting cables between the control elements and the electrical box, and to that of the unit power supply cable. They should not be twisted and there should be no slits or notches in the insulation. Check the starting and running consumptions are within the limits specified in the corresponding technical information.
- Drainage: Frequently check that the drain is not
obstructed, and that the condensate pan is clean and level.
- Inlet air filter: This should be cleaned periodically. The
frequency depends on the purity of the entering air. The filter may be cleaned with a household vacuum cleaner, or by immersing it in water.
- Refrigerant circuit: Ensure that there is no leakage of
refrigerant or oil from the compressor. Check that the high and low side operating pressures are normal. Make sure that the coils are not dirty. If necessary an optional filter may be placed at the outdoor air inlet. Check for unusual compressor noise.
- Controls: Check the operation of all electric controls,
high and low pressurestats, etc.
Page 35
35
1 Fixed flange 2 Setscrews 3 Movable flange 4 Straight-edge must be parallel with belt 5 Motor and fan shafts must be parallel 6 Pulleys 7 Motor and fan shafts must be parallel
Fig. 29 - To align fan and motor pulleys
Lubrication
Both the motors and the fans have factory lubricated and sealed bearings, and need no further lubrication.
The compressor has its own oil supply and oil should not be added unless a leak has occurred.
Servicing recommendations
- Before replacing any of the elements in the cooling circuit, ensure that the entire refrigerant charge is removed from both the high and low pressure sides of the unit.
- The control elements of the cooling system are highly sensitive. If they need to be replaced, care should be taken not to overheat them with blowlamps whilst soldering. A damp cloth should be wrapped around the component to be soldered, and the flame directed away from the component body.
- Silver alloy soldering rods should always be used.
- If the total unit gas charge has to be replaced, the quantity should be as given on the nameplate and the unit should be properly evacuated beforehand.
- During unit operation all panels should be in place, including the electrical box access panel.
- If it is necessary to cut the lines of the refrigerant circuit, tube cutters should always be used and never tools which produce burrs. All refrigerant circuit tubing should be of copper, specially made for refrigeration purposes.
Transformation to split system (50VZ/PZ units)
All units can be changed from a packaged to a split system, as described below:
- Disconnect the unit from the power supply.
- Remove the compressor access panel(s) and the indoor unit access panel(s).
- Recover the complete refrigerant charge from the high and low pressure sides of each refrigerant circuit, and then create a light vacuum to prevent possible accidents.
- From the indoor unit at the conduit drill hole remove the neoprene insulation from the suction line(s) until you find the welded joint of both line sections (approximately 70 mm from the base of the indoor unit). Similarly locate the welded joint of the liquid line sections. Separate both lines (suction and liquid lines) by unsoldering them. After completing this operation, plug the ends of both lines to avoid the possible entry of foreign matter.
- Loosen the indoor fan motor supply cable sleeve. Remove the sleeve.
- Remove the air filters.
- Loosen the screws and nuts that join the two sections (indoor and outdoor) inside the unit and separate them carefully, to avoid damaging the refrigerant line ends.
- Connect the refrigerant lines as described earlier in the text.
- Make the electrical connections.
FINAL RECOMMENDATIONS
The unit you have purchased has undergone strict quality control procedures before leaving the factory.
All components, including the control systems and electrical equipment, etc., are certified by our Quality Control Department, and tested under the harshest possible operating conditions in our laboratories. However, after leaving the factory, it is possible that one or more of these elements may be damaged due to causes beyond our control. In such an event,
the user should not work on any of the internal components, or subject the unit to operating conditions which are not specified in this manual, since serious damage may result and
the guarantee would be invalidated. Repair and maintenance work should always be left to the installer.
All recommendations concerning unit installation are intended to be as a guideline. The installer should carry out the installation according to the design conditions and should comply with all applicable regulations for air conditioning and refrigeration installations.
NOTE: The manufacturer does not accept responsibility for any malfunctions resulting from misuse of the equipment.
Page 36
Order No. 15021-20, 11.2000. Supersedes order No.: New Printed on Totally Chlorine-Free Paper. Manufacturer reserves the right to change any product specifications without notice. Printed in the Netherlands
AM-036918
TROUBLESHOOTING CHART
A list of possible faults, as well as the probable cause and suggested solutions is shown in Table 12. In the event of a unit malfunction it is recommended to disconnect the power supply and ascertain the cause.
Table 12 - Troubleshooting chart
Symptoms Cause Remedy
Unit does not start No power supply Connect power supply
Main switch open Close switch Low line voltage Check voltage and remedy the deficiency A protection has tripped Reset Contactor stuck open Replace contactor Seized compressor Replace compressor
Unit starts and stops frequently Defective compressor contactor Replace contactor
Defective compressor Replace compressor Refrigerant losses Reclaim the charge, pull a vacuum, recharge
the system with the quantity indicated on the name plate
Unit continuously cuts out at Defective low pressurestat Replace pressurestat low pressure Refrigerant losses Check and add the necessary quantity
Indoor fan does not operate Check fan motor
Unit continuously cuts out at COOLING CYCLE: high pressure Defective high pressurestat Replace pressurestat
Blocked filter drier Replace filter Outdoor fan does not operate Check fan motor
HEATING CYCLE:
Defective high pressurestat Replace pressurestat Indoor fan does not operate Check fan motor
Abnormal system noise Piping vibration Support piping
Noisy compressor Check and change if necessary Badly fitting panels Install correctly
Compressor loses oil Leak in system Repair leak
Water loss Defective drainage connections Check and tighten if necessary
Loading...