Site address: .......................................................................................................................................................................................................................................
Equipment type and serial No: 50TZ/YZ ...........................................................................................................................................................................................
* Based on an outdoor air dry bulb temperature of 35°C and an indoor air wet bulb temperature of 19°C.
** The refrigerant charge given is for the complete system, but does not include the connection lines.
*** Based on an outdoor air dry bulb temperature of 35°C and a dewpoint suction temperature of 7°C.
Indoor section (40BZ)Copper tubes, pretreated aluminium fins
Face aream
Rows ... fin spacingmm3 ... 1.823 ... 1.823 ...1.823 ... 1.823 ... 1.593 ... 2.124 ... 2.12
Test pressurebar30303030303030
Outdoor section (38BZ)Copper tubes, pretreated aluminium fins
Face aream
Rows ... fin spacingmm4 ... 1,824 ... 1.824 ... 1.825 ... 1.825 ...1.595 ... 2.126 ... 2.12
Test pressurekPa30303030303030
Indoor fan (40BZ)One ... dual inlet, centrifugal
Nominal air flowl/s40056567067095013201365
Nominal air flow rangel/s340-460480-650570-770570-770760-10901050-15201100-1570
Nominal static pressure (dry/wet) Pa50-4060-5060-5060-5090-80120-110120-110
Outdoor fan (38BZ)One ... dual inlet, centrifugal
Nominal air flowl/s530800865865135016501875
Nominal air flow rangel/s450-600680-900730-940730-9701085-14751320-18001500-2150
Nominal static pressurePa30303040505050
Indoor air filterOne filter, thickness 7 mm, filter class M1
Width x heightmm312 x 336352 x 378387 x 394387 x 394397 x 434542 x 524542 x 524
2
0.200.300.350.390.410.610.61
2
0.310.380.450.530.600.700.76
* Based on an outdoor air dry bulb temperature of 35°C and an indoor air wet bulb temperature of 19°C.
** Based on an outdoor air wet bulb temperature of 6°C and an indoor dry bulb temperature of 20°C.
*** The refrigerant charge given is for the complete system, but does not include the connection lines.
4
Table 3 - Electrical data
50TZ (40TZ/BZ + 38BZ)024036042048060072084
Nominal voltage (± 10%)*V230400230400230400230400230400230400230400
Nominal power input**kW2.902.903.993.994.684.685.075.077.377.3710.0810.0810.7510.75
Nominal current drawn**A13.336.3012.508.7415.5811.5016.9812.2325.4918.5430.1217.4133.1919.18
Effective power inputkW2.902.903.893.894.544.544.934.936.966.969.399.399.999.99
Effective current drawnA13.336.3012.198.5215.1111.1616.5111.8924.0717.5128.0616.2230.6717.73
Maximum power input***kW3.243.244.534.535.235.235.715.718.008.0010.7410.7411.9511.95
Maximum current drawn***A14.887.0414.199.9217.4212.8619.1313.7827.6720.1332.0918.5535.9320.77
* The unit power supply is three phase (except size 024, 230 V, which is single-phase). The fan power supply is single phase, except for sizes 072 and 084 which are three phase.
** Based on an outdoor air dry bulb temperature of 35°C and an indoor temperature of 19°C wet bulb and 27°C dry bulb.
*** Based on an outdoor air dry bulb temperature of 46°C and an indoor air wet bulb temperature of 21°C.
Note: The effective power input is according to EUROVENT.
Condensing unit 38FZ024036042048060072084
Nominal voltage (± 10%)*V230400230400230400230400230400230400230400
Nominal power input**kW2.452.453.633.634.044.044.514.516.496.498.528.529.169.16
Nominal current drawn**A11.255.3211.377.9513.459.9315.1110.8922.4516.3325.4614.7228.2716.34
Effective power inputkW2.452.453.633.634.044.044.514.516.266.268.248.248.858.85
Effective current drawnA11.265.3211.387.9513.459.9315.1010.8821.6515.7524.6214.2327.3115.79
Maximum power input***kW3.023.024.144.144.664.665.385.387.607.6010.0610.0610.7510.75
Maximum current drawn***A13.96.613.09.115.511.518.013.026.319.130.117.433.1919.18
* The unit power supply is three phase (except size 024, 230 V, which is single-phase). The fan power supply is single phase, except for sizes 072 and 084 which are three phase.
** Based on an outdoor air dry bulb temperature of 35°C and a dewpoint suction temperature of 7°C.
*** Based on an outdoor air dry bulb temperature of 46°C and a dewpoint suction temperature of 12°C.
Note: The effective power input is according to EUROVENT.
Table 4 - Electrical data
50YZ (40BZ + 38BZ)024036042048060072084
Nominal voltage (± 10%)*V230400230400230400230400230400230400230400
Nominal current drawnA
Cooling**12.776.0413.8910.0615.7911.4017.1012.4325.2918.0630.0017.3433.6519.45
Heating***11.215.3012.008.8714.1410.6015.7611.6524.0917.5727.5915.9530.7917.80
Effective power inputkW
Cooling2.742.744.104.104.564.564.904.907.167.169.419.4110.1610.16
Heating2.352.353.413.413.863.864.414.416.566.568.388.388.828.82
Effective current drawnA
Cooling12.766.0413.569.8215.3211.0616.6312.0923.9217.0827.9616.1631.1418.00
Heating11.205.3011.668.6213.6510.2315.2811.3022.6816.5425.5014.7428.2816.35
Maximum current drawn***A
Cooling****14.176.7014.8610.5417.2412.2818.2312.9127.1019.0332.8719.0035.9420.78
Heating*****12.796.0513.019.2315.2910.8916.3911.6125.2617.7431.3218.1135.4420.48
* The unit power supply is three phase (except size 024, 230 V, which is single-phase). The fan power supply is single phase, except for sizes 072 and 084 which are three phase.
** Based on an outdoor air dry bulb temperature of 35°C and an indoor temperature of 19°C wet bulb.
*** Based on an outdoor air wet bulb temperature of 6°C and an indoor temperature of 20°C dry bulb.
**** Based on an outdoor air dry bulb temperature of 46°C and an indoor air wet bulb temperature of 21°C.
***** Based on an outdoor air wet bulb temperature of 18°C.
Note: The effective power input is according to EUROVENT.
5
50TZ/YZ 024
Fig. 1 - Dimensions, mm
View on indoor air supply/return
Evaporator access panel
Compressor access panel
Control box access panel
Evaporator air inlet
Evaporator air outlet
Condenser air inlet
Plan view
View on outdoor air supply/return
Condenser air outlet
Drain, 3/4" MPT
Unit supports
Cable entry
Main disconnect switch
Note: Standard air supply and return
When designing an installation, always use up-to-date drawings, available from your local Carrier office.
6
50TZ/YZ 036
Fig. 2 - Dimensions, mm
View on indoor air supply/return
Evaporator access panel
Compressor access panel
Control box access panel
Evaporator air inlet
Evaporator air outlet
Condenser air inlet
Plan view
View on outdoor air supply/return
Condenser air outlet
Drain, 3/4" MPT
Unit supports
Cable entry
Main disconnect switch
Note: Standard air supply and return
When designing an installation, always use up-to-date drawings, available from your local Carrier office.
7
50TZ/YZ 042
Fig. 3 - Dimensions, mm
View on indoor air supply/return
Evaporator access panel
Compressor access panel
Control box access panel
Evaporator air inlet
Evaporator air outlet
Condenser air inlet
Plan view
View on outdoor air supply/return
Condenser air outlet
Drain, 3/4" MPT
Unit supports
Cable entry
Main disconnect switch
Note: Standard air supply and return
When designing an installation, always use up-to-date drawings, available from your local Carrier office.
8
50TZ/YZ 048
Fig. 4 - Dimensions, mm
View on indoor air supply/return
Evaporator access panel
Compressor access panel
Control box access panel
Evaporator air inlet
Evaporator air outlet
Condenser air inlet
Plan view
View on outdoor air supply/return
Condenser air outlet
Drain, 3/4" MPT
Unit supports
Cable entry
Main disconnect switch
Note: Standard air supply and return
When designing an installation, always use up-to-date drawings, available from your local Carrier office.
9
50TZ/YZ 060
Fig. 5 - Dimensions, mm
View on indoor air supply/return
Evaporator access panel
Compressor access panel
Control box access panel
Evaporator air inlet
Evaporator air outlet
Condenser air inlet
Plan view
View on outdoor air supply/return
Condenser air outlet
Drain, 3/4" MPT
Unit supports
Cable entry
Main disconnect switch
Note: Standard air supply and return
10
When designing an installation, always use up-to-date drawings, available from your local Carrier office.
50TZ/YZ 072
Fig. 6 - Dimensions, mm
View on indoor air supply/return
Evaporator access panel
Compressor access panel
Control box access panel
Evaporator air inlet
Evaporator air outlet
Condenser air inlet
Plan view
View on outdoor air supply/return
Condenser air outlet
Drain, 3/4" MPT
Unit supports
Cable entry
Main disconnect switch
Note: Standard air supply and return
When designing an installation, always use up-to-date drawings, available from your local Carrier office.
11
50TZ/YZ 084
Fig. 7 - Dimensions, mm
View on indoor air supply/return
Evaporator access panel
Compressor access panel
Control box access panel
Evaporator air inlet
Evaporator air outlet
Condenser air inlet
Plan view
View on outdoor air supply/return
Condenser air outlet
Drain, 3/4" MPT
Unit supports
Cable entry
Main disconnect switch
Note: Standard air supply and return
12
When designing an installation, always use up-to-date drawings, available from your local Carrier office.
38FZ/BZ 024
Fig. 8 - Dimensions, mm
View on refrigerant line connection side
Refrigerant line connection
Compressor access panel
Control box access panel
Suction line ø 5/8"
Liquid line ø 3/8"
Condenser air inlet
Plan view
View on outdoor air supply/return
Condenser air outlet
Drain, 3/4" MPT
Unit supports
Cable entry
Main disconnect switch
Note: Standard air supply and return
When designing an installation, always use up-to-date drawings, available from your local Carrier office.
13
38FZ/BZ 036
Fig. 9 - Dimensions, mm
View on refrigerant line connection side
Refrigerant line connection
Compressor access panel
Control box access panel
Suction line ø 5/8"
Liquid line ø 3/8"
Condenser air inlet
Plan view
View on outdoor air supply/return
Condenser air outlet
Drain, 3/4" MPT
Unit supports
Cable entry
Main disconnect switch
Note: Standard air supply and return
14
When designing an installation, always use up-to-date drawings, available from your local Carrier office.
38FZ/BZ 042
Fig. 10 - Dimensions, mm
View on refrigerant line connection side
Refrigerant line connection
Compressor access panel
Control box access panel
Suction line ø 5/8"
Liquid line ø 3/8"
Condenser air inlet
Plan view
View on outdoor air supply/return
Condenser air outlet
Drain, 3/4" MPT
Unit supports
Cable entry
Main disconnect switch
Note: Standard air supply and return
When designing an installation, always use up-to-date drawings, available from your local Carrier office.
15
38FZ/BZ 048
Fig. 11 - Dimensions, mm
View on refrigerant line connection side
Refrigerant line connection
Compressor access panel
Control box access panel
Suction line ø 5/8"
Liquid line ø 3/8"
Condenser air inlet
Plan view
View on outdoor air supply/return
Condenser air outlet
Drain, 3/4" MPT
Unit supports
Cable entry
Main disconnect switch
Note: Standard air supply and return
16
When designing an installation, always use up-to-date drawings, available from your local Carrier office.
38FZ/BZ 060
Fig. 12 - Dimensions, mm
View on refrigerant line connection side
Refrigerant line connection
Compressor access panel
Control box access panel
Suction line ø 5/8"
Liquid line ø 3/8"
Condenser air inlet
Plan view
View on outdoor air supply/return
Condenser air outlet
Drain, 3/4" MPT
Unit supports
Cable entry
Main disconnect switch
Note: Standard air supply and return
When designing an installation, always use up-to-date drawings, available from your local Carrier office.
17
38FZ/BZ 072
Fig. 13 - Dimensions, mm
View on refrigerant line connection side
Refrigerant line connection
Compressor access panel
Control box access panel
Suction line ø 5/8"
Liquid line ø 3/8"
Condenser air inlet
Plan view
View on outdoor air supply/return
Condenser air outlet
Drain, 3/4" MPT
Unit supports
Cable entry
Main disconnect switch
Note: Standard air supply and return
18
When designing an installation, always use up-to-date drawings, available from your local Carrier office.
38FZ/BZ 084
Fig. 14 - Dimensions, mm
View on refrigerant line connection side
Refrigerant line connection
Compressor access panel
Control box access panel
Suction line ø 5/8"
Liquid line ø 3/8"
Condenser air inlet
Plan view
View on outdoor air supply/return
Condenser air outlet
Drain, 3/4" MPT
Unit supports
Cable entry
Main disconnect switch
Note: Standard air supply and return
When designing an installation, always use up-to-date drawings, available from your local Carrier office.
19
40BZ 024
Fig. 15 - Dimensions, mm
View on refrigerant line connection side
Refrigerant line connection
Compressor access panel
Suction line ø 5/8"
Liquid line ø 3/8"
Condenser air inlet
Plan view
View on indoor air supply/return
Condenser air outlet
Drain, 3/4" MPT
Unit supports
Cable entry
20
Note: Standard air supply and return
When designing an installation, always use up-to-date drawings, available from your local Carrier office.
40BZ 036
Fig. 16 - Dimensions, mm
View on indoor air supply/return
Compressor access panel
Suction line ø 5/8"
Liquid line ø 3/8"
Condenser air inlet
Refrigerant line connection
Plan view
View on refrigerant line connection side
Condenser air outlet
Drain, 3/4" MPT
Unit supports
Cable entry
Note: Standard air supply and return
When designing an installation, always use up-to-date drawings, available from your local Carrier office.
21
40BZ 042
Fig. 17 - Dimensions, mm
View on indoor air supply/return
Compressor access panel
Suction line ø 5/8"
Liquid line ø 3/8"
Condenser air inlet
Refrigerant line connection
Plan view
View on refrigerant line connection side
Condenser air outlet
Drain, 3/4" MPT
Unit supports
Cable entry
22
Note: Standard air supply and return
When designing an installation, always use up-to-date drawings, available from your local Carrier office.
40BZ 048
Fig. 18 - Dimensions, mm
View on indoor air supply/return
Compressor access panel
Suction line ø 5/8"
Liquid line ø 3/8"
Condenser air inlet
Refrigerant line connection
Plan view
View on refrigerant line connection side
Condenser air outlet
Drain, 3/4" MPT
Unit supports
Cable entry
Note: Standard air supply and return
When designing an installation, always use up-to-date drawings, available from your local Carrier office.
23
40BZ 060
Fig. 19 - Dimensions, mm
View on indoor air supply/return
Compressor access panel
Suction line ø 5/8"
Liquid line ø 3/8"
Condenser air inlet
Refrigerant line connection
Plan view
View on refrigerant line connection side
Condenser air outlet
Drain, 3/4" MPT
Unit supports
Cable entry
24
Note: Standard air supply and return
When designing an installation, always use up-to-date drawings, available from your local Carrier office.
40BZ 072
Fig. 20 - Dimensions, mm
View on indoor air supply/return
Compressor access panel
Suction line ø 5/8"
Liquid line ø 3/8"
Condenser air inlet
Refrigerant line connection
Plan view
View on refrigerant line connection side
Condenser air outlet
Drain, 3/4" MPT
Unit supports
Cable entry
Note: Standard air supply and return
When designing an installation, always use up-to-date drawings, available from your local Carrier office.
25
40TZ/BZ 084
Fig. 21 - Dimensions, mm
View on indoor air supply/return
Compressor access panel
Suction line ø 5/8"
Liquid line ø 3/8"
Condenser air inlet
Refrigerant line connection
Plan view
View on refrigerant line connection side
Condenser air outlet
Drain, 3/4" MPT
Unit supports
Cable entry
26
Note: Standard air supply and return
When designing an installation, always use up-to-date drawings, available from your local Carrier office.
In these units the air discharge and supply (indoor and outdoor)
is factory-set as shown in Fig. 31. Alternative positions are
possible, as follows (Fig. 32):
Fig. 31 - Standard air supply and discharge
Fig. 32 - Alternative air supply and discharge (except
outdoor unit model 084)
A = Alternative
S = Standard
NOTE: In the 50TZ/YZ 060 and 40BZ 060 units the standard
indoor air discharge is through this panel.
a)Detach discharge panel and access panel .
b)Remove the fan/motor assembly , loosening it from the
unit base. In sizes 50TZ/YZ 060 and 40BZ 060 remove
the duct.
c)Unscrew the angle irons in the fan/motor assembly .
d)Turn the fan/motor assembly by 180° and attach the
angle irons previously removed.
e)Fasten the fan/motor assembly in its new position.
f)Install the discharge panel and the access panel in
their new positions.
g)Remove filter panel and access panel .
h)Exchange the position of panels and .
NOTE: In the 50TZ/YZ 060 and 40BZ 060 units the standard
indoor air discharge is through this panel.
Outdoor unit change
a)Detach discharge panel and access panel .
b)Remove the fan/motor assembly , loosening it from the
unit base and remove the duct .
c)Unscrew the angle irons in the fan/motor assembly .
d)Turn the fan/motor assembly by 180° and attach the
angle irons previously removed.
e)Fasten the fan/motor assembly in its new position.
f)Install the discharge panel and the access panel in
their new positions.
g)Remove supply air panel and access panel !.
h)Exchange the position of panels and !.
See Figs. 31 and 32.
See Figs. 31 and 32.
30
Fan performance curves
50TZ/YZ024 ventilador exterior (38BZ/FZ024)
0
10
20
30
40
50
60
70
450475500525550575600
Caudal de aire, l/s
240
260
280
300
320
340
360
380
Consumo, W
Presión estática disponible, Pa
1
1
2
2
50TZ/YZ036 ventilador exterior (38BZ/FZ036)
0
10
20
30
40
50
60
70
80
90
650700750800850900
Caudal de aire, l/s
475
525
575
625
675
Consumo, W
Presión estática disponible, Pa
1
2
2
1
50TZ/YZ 024 indoor fan (40BZ 024)
50TZ/YZ024 ventilador interior (40BZ024)
80
1
70
2
60
50
40
30
20
Available static pressure, Pa
10
Presión estática disponible, Pa
0
340360380400420440460
50TZ/YZ 036 indoor fan (40BZ 036)
50TZ/YZ036 ventilador interior (40BZ036)
120
100
80
60
40
20
Available static pressure, Pa
Presión estática disponible, Pa
0
475500525550575600625650
3
Caudal de aire, l/s
Air flow, l/s
Caudal de aire, l/s
Air flow, l/s
50TZ/YZ 024 outdoor fan (38BZ/FZ 024)
350
325
1
300
275
2
250
3
225
Consumo, W
200
175
150
Power input, W
Available static pressure, Pa
Air flow, l/s
Power input, W
50TZ/YZ 036 outdoor fan (38BZ/FZ 036)
600
550
500
450
400
350
300
Consumo, W
Power input, W
Available static pressure, Pa
Air flow, l/s
Power input, W
50TZ/YZ 042 indoor fan (40BZ 042)
50TZ/YZ042 ventilador interior (40BZ042)
120
100
1
80
2
60
40
3
20
Available static pressure, Pa
Presión estática disponible, Pa
0
550600650700750800
Caudal de aire, l/s
Air flow, l/s
50TZ/YZ048 ventilador interior (40BZ048)
120
1
100
80
2
60
40
3
20
Available static pressure, Pa
Presión estática disponible, Pa
0
550600650700750800
Caudal de aire, l/s
Air flow, l/s
50TZ/YZ 042 outdoor fan (38BZ/FZ 042)
50TZ/YZ042 ventilador exterior (38BZ/FZ042)
625
1
575
2
525
3
475
425
Power input, W
Consumo, W
375
325
650
1
600
550
2
500
3
450
Power input, W
Consumo, W
400
350
120
100
1
80
60
2
40
20
Available static pressure, Pa
Presión estática disponible, Pa
0
700750800850900950
50TZ/YZ 048 outdoor fan (38BZ/FZ 048)50TZ/YZ 048 indoor fan (40BZ 048)
50TZ/YZ048 ventilador exterior (38BZ/FZ048)
120
1
100
80
2
60
40
1
20
Available static pressure, Pa
2
Presión estática disponible, Pa
0
7007508008509009501000
Caudal de aire, l/s
Air flow, l/s
Caudal de aire, l/s
Air flow, l/s
1
2
750
700
650
600
550
500
450
750
700
650
600
Consumo, W
550
Power input, W
500
450
31
Power input, W
Consumo, W
Fan performance curves
50TZ/YZ 060 indoor fan (40BZ 060)50TZ/YZ 060 outdoor fan (38BZ/FZ 060)
50TZ/YZ060 ventilador interior (40BZ060)
200
1
180
160
2
140
120
3
100
80
60
40
Available static pressure, Pa
20
Presión estática disponible, Pa
0
750800850900950100010501100
50TZ/YZ 072 indoor fan (40BZ 072)50TZ/YZ 072 outdoor fan (38BZ/FZ 072)
50TZ/YZ072 ventilador interior (40BZ072)
250
200
150
100
50
Available static pressure, Pa
Presión estática disponible, Pa
0
110012001300140015001600
Air flow, l/s
Caudal de aire, l/s
Caudal de aire, l/s
Air flow, l/s
1150
1100
1
1050
2
1000
3
950
900
850
800
750
700
650
1400
1350
1300
1250
1200
1150
1100
1050
1000
950
900
50TZ/YZ060 ventilador exterior (38BZ/FZ060)
200
180
1
160
Power input, W
Consumo, W
140
120
100
2
80
60
40
Available static pressure, Pa
20
Presión estática disponible, Pa
0
11001150120012501300135014001450
Caudal de aire, l/s
1
2
Air flow, l/s
50TZ/YZ072 ventilador exterior (38BZ/FZ072)
180
160
140
120
100
80
Power input, W
Consumo, W
60
40
Available static pressure, Pa
20
Presión estática disponible, Pa
0
130014001500160017001800
Air flow, l/s
Caudal de aire, l/s
1500
1450
1400
1350
1300
1250
1200
1150
1100
1050
1000
1600
1550
1500
1450
1400
1350
1300
1250
1200
1150
Power input, W
Consumo, W
Power input, W
Consumo, W
50TZ/YZ 084 indoor fan (40TZ/BZ 084)50TZ/YZ 084 outdoor fan (38BZ/FZ 084)
50TZ/YZ084 ventilador interior (40TZ/BZ084)
250
200
150
100
Available static pressure, Pa
50
Presión estática disponible, Pa
0
110012001300140015001600
Models 025 to 060
CurveSpeed
1High
2Medium
Air flow, l/s
Caudal de aire, l/s
1400
1350
1300
1250
1200
1150
1100
1050
1000
950
900
50TZ/YZ084 ventilador exterior (38BZ/FZ084)
160
140
120
100
80
Power input, W
Consumo, W
60
40
Available static pressure, Pa
20
Presión estática disponible, Pa
0
15001600170018001900200021002200
4
Caudal de aire, l/s
50TZ/YZ 084 (38BZ/FZ 084)
CurvePulley openingSpeed r/s
0Closed15.33
11 turn14.83
22 turns14.33
33 turns13.83
44 turns13.33
Factory setting1 turn14.83
Air flow, l/s
0
1
2
3
3
4
0
1
2
1700
1600
1500
1400
1300
1200
1100
1000
900
Consumo, W
Power input, W
32
SAFETY CONSIDERATIONS
Installation and servicing of air conditioning equipment can be
hazardous due to system pressure and electrical components.
-Consult all applicable rules and standards which govern
the installation of air conditioning equipment.
-Vibration absorbers should be provided throughout the
installation to prevent noise transmission.
Only trained and qualified service personnel should install,
start-up or service air conditioning equipment. Untrained
personnel can perform the basic maintenance functions of
cleaning and replacing filters.
All other operations should be performed by trained service
personnel.
When working on air conditioning equipment, observe
precautions in the literature, tags and labels attached to the unit
and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use a quenching cloth for unbrazing operations.
WARNING: Before performing service or maintenance
operations on the unit, turn off the main power switch to the
unit. Electrical shock could cause personal injury.
All units are designed for ducted installation (indoor and/or
outdoor air discharge). If ducts are not used the installer must
place a protection grille in the discharge.
Only use "Original Spare Parts" for repairs. Special attention
must be paid to the correct installation of the spare parts. The
parts must always be installed in their original position.
Rigging
1.When rigging, use spreaders to prevent damage to the
panels (see Fig. 33). Avoid violent movements.
2.To prevent damage while in transit, do not remove the unit
from the skid until it is at its final location.
3.Never roll or tip the unit more than 15o.
IMPORTANT: Make sure that all unit panels are fixed in place
before moving. Raise and set down the unit carefully.
Fig. 33 - Rigging
During unit operation, some of the refrigerant circuit elements
could reach a temperature in excess of 70oC so only trained or
qualified personnel should access areas protected by access
panels.
This unit should not be installed in an explosive atmosphere.
The unit can operate in normal radioelectric atmospheres in
residential, commercial and light industrial installations. For
other applications, please consult Carrier.
INSTALLATION
1.Inspect shipment. Inspect the unit. If it is damaged, or if
the shipment is incomplete, immediately file a claim with
the shipping company.
2.Check that the local power supply agrees with the
specification on the unit nameplate.
Siting the unit
Check the following points:
-The location must be able to support the unit operating
weight (see Tables 1 and 2).
-Allow sufficient space for servicing and air flow around
the unit (see Figs. 22, 23 and 24).
-Select a location free of dust or foreign matter which may
cause coil clogging.
-When installing the unit on the ground, select a site which
is not subject to flooding (outdoor units).
Rigging hook
IMPORTANT: The unit should be correctly levelled to avoid
drainage problems.
Ductwork (indoor air discharge)
The ductwork dimensions should be determined in accordance
with the air flow to be carried, and the available static pressure
of the unit.
It is recommended to observe the following considerations:
-Whatever type of ductwork is used, it should not be made
of materials which are flammable, or give off toxic gases in
the event of a fire. The internal surfaces should be smooth,
and not contaminate the air which passes through. It is
recommended to use sheet metal ducts, adequately insulated to avoid condensation and thermal leakage.
-At the points where the ducts join the unit, it is recommended to use flexible connections to absorb vibrations, prevent
noise inside the ductwork and allow access to the unit.
-Bends near the unit outlet should be avoided as much as
possible. If unavoidable, they should be as slight as
possible, and internal deflectors should be used when the
duct has large dimensions.
33
NOTE: All duct sizing and design work should be carried out
by qualified technicians.
Condensate and rainwater drainage
The units are supplied with a condensate drain pan with a drain
pipe (outside diameter 23 mm). This tube leaves the factory
separately wrapped so it is easy to check them.
-Take great care with the drain pipes; these must always be
below the connection and be inclined to facilitate drainage
(Fig. 34).
ATTENTION: Do not make any holes in the unit base, as this
may perforate the condensate pan.
Fig. 34 - Drain
Drain pipe OD 23 mm
Drain pan
Voltage imbalance % =
Largest deviation from average voltage
Average voltage
Example: Nominal supply: 400-3-50
ABC
AB = 404 V
BC = 399 V
AC = 394 V
Motor
Average voltage =404 + 399 + 394= 399 400 V
3
Determine maximum deviation from average voltage:
AB = 404 - 400 = 4
BC = 400 - 399 = 1
AC = 400 - 394 = 6
Largest deviation is 6 volts. Percentage voltage imbalance is
therefore:
Unit base
Field-supplied
Electrical connections
WARNING: To prevent electrical shock or equipment damage,
make sure disconnects are open before electrical connections
are made. If this action is not taken, personal injury may occur.
Field wiring must comply with all applicable codes.
Voltage to the unit must be within 10% of the voltage and 10%
of the current indicated on the nameplate. Contact your local
power company for correction of an incorrect line voltage.
Check the voltage before selecting supply wiring fuses and
controls.
Take special care when making the earth connection.
WARNING: Operation of the unit on improper line voltage
constitutes abuse and is not covered by the Carrier warranty.
IMPORTANT: To ensure the correct unit power supply (cable
entry, conductor cross section, protection devices etc.), consult
the electrical data table, the wiring diagram supplied with the
unit and the applicable standards concerning the installation of
air conditioning equipment.
The protective earth conductor must be slightly longer than the
phases.
6x 100 = 1.5 %
400
CAUTION: The installer must provide line protection devices,
as required by the applicable legislation.
Run the power supply cables to the main disconnect switch of
the 50TZ/YZ or 38FZ/BZ unit, and install airtight cable
conduits through the knockouts provided for this purpose.
Electrical connection between the units (38FZ/BZ and
40TZ/BZ)
Make the electrical connection between the 38FZ/BZ outdoor
unit and the 40TZ/BZ indoor unit, using correctly sized copper
cables for the power supply of the 40TZ/BZ. Refer to the
wiring diagram.
Thermostat connection
Thermostat/unit connection must be via a loom (wire section
1 mm2) manufactured in accordance with the wiring diagram
accompanying the unit. Follow the instructions supplied with
the control for thermostat assembly and handling. The general
rules below should be taken into account:
Never operate a unit if the voltage imbalance exceeds 10%.
The following formula must be used to determine the
percentage of voltage imbalance.
34
* The O connection is activated in cooling.
NOTE 1: If the thermostat wiring is incorrect, the control will
be blocked (red LED on) and all the outlets will be deactivated
when unit power is supplied.
NOTE 2: The thermostat cable should be independent and
separate from any 230 V or 400 V cable.
Suction line:
-A siphon at the base of the vertical pipe run and intermediate siphons every 8 m or oil separators are needed.
-Most unfavourable condition: the suction speed in the
vertical pipe run must be more than 6 m/s.
Refrigerant line connections (38FZ/BZ and 40TZ/BZ)
To guarantee correct unit performance ensure that the line
length and number of bends are kept to a minimum. Avoid pipe
kinking by using large radius bends.
IMPORTANT: Always use refrigerant-grade deoxidized and
dehydrated copper tubing between the indoor and outdoor
units.
Before connecting the refrigerant lines carefully follow the
steps below:
-Remove the nitrogen holding charge from the refrigerant
circuits.
-Select the diameter of the copper tubing according the the
units installed and according to the distance between the
indoor and outdoor units.
-Use silver alloy rod for soldering purposes, and ensure
that this work is done in a nitrogen atmosphere.
-To avoid oxidation insulate the refrigerant lines
adequately.
-Pull a vacuum in the refrigerant circuit until a pressure of
0.7 mm water column is maintained for at least 2 hours.
-Charge the refrigerant circuit with the necessary amount
of R-407C refrigerant (in accordance with tables 1 and 2
and the length of the refrigerant lines).
-Check there are no refrigerant leaks.
Refrigerant line selection
General
When designing refrigerant lines the following must be kept in
mind:
-Depending on the unit arrangement:
Fig. 35 - Refrigerant lines option A
Fig. 36 - Refrigerant lines option B
Indoor unit
Heat pump
(discharge)
Heat pump
Liquid line
Cooling
Gas
Cooling
(suction line)
Outdoor unit
Suction line:
-The intermediate siphon can be omitted.
-Most unfavourable condition: the suction speed in the
vertical pipe run must be more than 6 m/s.
For both option A (Figure 34) and option B (Figure 35) the
following conditions should be observed:
-The maximum speed permitted in any line is 15 m/s.
-Suction line must be insulated and have a 2% slope towards
the compressor and the horizontal pipe run.
-
In long pipe runs it may be necessary to adjust the oil charge.
-If the liquid line flow is downward, it is necessary to
install pressure equalizer for heights above 10 m.
-The liquid should be subcooled by at least 1 K at the
restrictor inlet. In this case, if the liquid line flow is
upward and the pipe is longer than 15 m, it must be
subcooled by 1 K for each 3.5 m in excess of 15 m.
-For each metre of refrigerant pipe installed, refrigerant has
to be added in accordance with table 5.
From Figure 38, for the selected unit we can obtain the pressure drop corresponding to 10 m of equivalent length for each
diameter.
WARNING: The compressors are mounted on vibration
isolators. Do not loosen or remove the support mounting bolts.
Refrigerant charge
Gas tightness testing and dehydration
50TZ/YZ units are shipped fully charged with refrigerant R-407C
ready for operation. If, when the unit is run, symptoms of loss
of charge (for example, low pressure switch tripping or
abnormally low cooling capacities) are detected, first conduct a
leak test followed, if necessary, by a gas tightness test using
compressed nitrogen. For the latter all refrigerant must be
removed from the circuit. Transfer the refrigerant to a storage
tank and then rinse the circuit. For your information, we are
listing here some precautions that need to be taken into
consideration, when working with these units.
Refrigerant guidelines for R-407C
Refrigerant R-407C consists of a non-azeotropic blend of 23%
of R-32, 25% of R-125 and 52% of R-134a, and is characterised by the fact that at the time of the change in state the
temperature of the liquid/vapour mixture is not constant. All
checks must be pressure tests, and the appropriate pressure/
temperature ratio table must be used for the interpretation of
the values.
For other equivalent lengths, the pressure drop is obtained in
direct proportion. The total pressure drop for the line (sum
corresponding to the vertical and horizontal pipe runs) must not
be higher than 20 kPa.
36
Leak detection is especially important for units charged with
refigerant R-407C. Depending on whether the leak occurs in
the liquid or the vapour phase, the proportion of the different
components in the mixture remaining in the unit is not the
same.
The following basic guidelines must be observed:
•Leaks must be repaired immediately by qualified
personnel.
•Refrigerant must never be discharged to the atmosphere.
•Use a refrigerant reclaim unit.
•Any loss of oil from the system during maintenance must
be stopped immediately and the collected oil must by
removed in accordance with applicable regulations
38FZ/BZ and 40TZ/BZ units are supplied with a nitrogen
holding charge. This must be removed before soldering the
connecting refrigerant lines to the unit. Once the soldering has
been completed, the complete refrigerant circuit must be
evacuated then the correct quantity of R-407C refrigerant for
each system must be charged.
WARNING: If any brazing is to be done the refrigerant circuit
must be filled with nitrogen. Combustion of refrigerant
produces toxic phosgene gas.
VERY IMPORTANT:
-Never use the compressor as a vacuum pump.
-If more refrigerant is needed add gas very slowly via the
suction line. Liquid refrigerant must never be introduced
into the suction line.
-Do not overcharge with refrigerant.
START-UP
Actual start-up should only be done under the supervision of a
qualified refrigeration mechanic.
These units incorporate the electronic Master Link II control.
The operation and handling of this control is explained in the
specific instructions accompanying each unit.
Initial checks
With the unit in operation, ensure that the values shown on the
high and low pressure gauges are within the normal limits. It is
advisable to simulate unit shutdown due to high and low
pressure, in order to make sure that the pressurestats work
properly. To do so, proceed as follows:
-High pressure shutdown: Completely cover the outdoor
air inlet, or disconnect the outdoor fan and motor. The unit
should stop at a pressure of 2844 kPa.
-Low pressure shutdown: Cover the indoor air inlet, or
disconnect the indoor fan and motor. Observe the low
pressure gauge. The unit should stop at a pressure of
265 kPa.
In both cases it is possible to reset the unit through the remote
control as previously indicated.
Check that the motor and compressor consumptions are
approximately the same as those shown on the unit nameplate.
Consumption data is also given in Tables 3 and 4.
Refrigerant system description
The refrigerant circuit incorporates the following primary
elements:
-Refrigerant-air heat exchanger: made of high quality
copper tubes and pretreated aluminium fins, for extra
corrosion resistance and greater protection than offered by
copper fins.
-Refrigerant lines: made completely of high quality
copper.
-Metering device.
-Compressors: hermetic compressors for all units, cooled by
suction gas. They incorporate internal protection.
-Filter drier and Schrader valves.
-Safety elements: high, low pressurestat.
-The packaged units are supplied with the exact refrigerant
charge.
-The split-system units are supplied with a nitrogen holding charge which must be evacuated and replaced with the
right refrigerant charge for the unit size and the connection
lines.
Compressor replacement
When an internal fault occurs, the compressor must be
replaced. This must be done as detailed below:
-Disconnect the unit from the electrical supply.
-Remove the panels.
-Remove the gas from the refrigerant circuit using recovery
equipment to avoid harming the atmosphere.
-Electrically disconnect the compressor.
-Unbraze or unscrew the suction and discharge lines,
taking care not to damage the rest of the components.
-Remove the fastenings from the compressor.
-Replace the compressor, ensuring that it contains
sufficient oil.
-Braze or screw in the lines.
-Connect the compressor according to the wiring diagram.
-Evacuate the compressor.
-Fill the refrigerant charge indicated on the nameplate, plus
the required charge for the refrigerant connection lines.
NOTE: This operation must be done by a qualified technician.
Description of unit protection devices
The unit includes the following compressor protection devices:
-Internal compressor protection device to avoid superheat.
-Short-cycle protection (included on the main electronic
board).
-Outdoor fan motor thermomagnetic switch.
-High pressurestat: This protects the unit against
excessive condensing pressure. The high pressurestat has
factory-fixed non-adjustable settings. To check, see
section Initial checks.
-Low pressurestat: This protects the unit against
excessive low pressure in the evaporator. The low
pressurestat has factory fixed non-adjustable settings. To
check, see section Initial checks.
CAUTION: When any of these cuts out, the unit stops and will
not re-start until the contacts have been reclosed after
rectification of the fault.
37
GENERAL MAINTENANCE
Table 7 - Pressure switch settings
Cut-outCut-inReset
High pressurestat*2844 kPa*1863 kPaAutomatic
Low pressurestat*265 kPa*363 kPaAutomatic
* Factory-calibrated
WARNING: Alteration of factory settings other than the design
set-point, without manufacturer's authorisation, may void the
warranty.
Operating limits
These units have been designed to operate within the following
limits:
Table 8 - Cooling operation
ZoneAir temperature
Dry bulbWet bulb
Indoor
Maximum+35°C+21°C
Minimum+19°C+14°C
Outdoor
Maximum+46°CMinimum+19°C*-
* With the optional head pressure control, the unit can operate with temperatures below 19°C.
Table 9 - Heating operation
ZoneAir temperature
Dry bulbWet bulb
Indoor
Maximum+27°C-
Outdoor
Maximum+24°C+18°C
Minimum-15°C*-
ATTENTION: Before starting any servicing or maintenance
operation on the unit, make sure that the power supply has
been disconnected. A current discharge could cause personal
injury.
In order to obtain maximum performance from the unit special
attention should be paid to the following points:
-Electrical connections: The supply voltage should be
within the limits permitted by the compressor. Ensure that
no faulty contacts exist in the terminal blocks, contactor
boards, etc. Make sure that all the electrical connections
are properly tightened, and that all the electrical
components (contactors, relays, etc) are firmly secured to
the corresponding rails.
Pay special attention to the condition of the connecting
cables between the control elements and the electrical box,
and to that of the unit power supply cable. They should
not be twisted and there should be no slits or notches in
the insulation. Check the starting and running
consumptions are within the limits specified in the
corresponding technical information.
-Drainage: Frequently check that the drain is not
obstructed, and that the condensate pan is clean and level.
-Inlet filter: This should be cleaned periodically. The
frequency depends on the purity of the entering air. The
filter may be cleaned with a household vacuum cleaner, or
by immersing it in water.
-Refrigerant circuit: Ensure that there is no leakage of
refrigerant or oil from the compressor. Check that the high
and low side operating pressures are normal. Make sure
that the coils are not dirty. If necessary a filter may be
installed in the outdoor air inlet. Check for unusual
compressor noise.
-Controls: Check the operation of all electric controls,
high and low pressurestats, etc.
Control sequence
The unit is started and stopped by the remote control N1. If the
remote control N1 requires cooling or heating, the built-in
compressor short-cycle protection starts counting 3 seconds.
After this time (if high-low pressurestats, indoor and outdoor
fan thermal protectors are not tripped) the unit starts up.
OPTIONS/ACCESSORIES
-Head pressure control (option/accessory)
-Electric resistance heater (option/accessory)
-Hot water coil (option/accessory)
-Outdoor air filter (option/accessory)
-Crankcase heater (option/accessory) - only for 50TZ and
38FZ units.
SERVICE
Lubrication
Both the motors and the fans have factory lubricated and sealed
bearings, and need no further lubrication.
The compressor has its own oil supply and oil should not be
added unless a leak has occurred.
38
Servicing recommendations
FINAL RECOMMENDATIONS
-Before replacing any of the elements in the cooling
circuit, ensure that the entire refrigerant charge is removed
from both the high and low pressure sides of the unit.
-The control elements of the cooling system are highly
sensitive. If they need to be replaced, care should be taken
not to overheat them with blowlamps whilst soldering. A
damp cloth should be wrapped around the component to
be soldered, and the flame directed away from the
component body.
-Silver alloy soldering rods should always be used.
-If the total unit gas charge has to be replaced, the quantity
should be as given on the nameplate and the unit should
be properly evacuated beforehand.
-During unit operation all panels should be in place,
including the electrical box access panel.
-If it is necessary to cut the lines of the refrigerant circuit,
tube cutters should always be used and never tools which
produce burrs. All refrigerant circuit tubing should be of
copper, specially made for refrigeration purposes.
Transformation to split system (50TZ/YZ)
All units can be changed from a packaged to a split system, as
described below:
-Remove the compressor access panel(s) and the indoor
unit access panel(s).
-Recover the complete refrigerant charge from the high
and low pressure sides of each refrigerant circuit, and
then create a light vacuum to prevent possible
accidents.
-From the indoor unit at the conduit drill hole remove the
neoprene insulation from the suction line(s) until you find
the welded joint of both line sections (approximately 70 mm
from the base of the indoor unit). Similarly locate the
welded joint of the liquid line sections. Separate both lines
(suction and liquid lines) by unsoldering them. After
completing this operation, plug the ends of both lines to
avoid the possible entry of foreign matter.
-Loosen the indoor fan motor supply cable sleeve. Remove
the sleeve.
-Remove the support that links the two units; there are four
screws for the lower part.
-Loosen the screws and nuts that join the two sections
(indoor and outdoor) inside the unit and separate them
carefully, to avoid damaging the refrigerant line ends.
-Connect the refrigerant lines as described earlier in the
text.
The unit you have purchased has undergone strict quality
control procedures before leaving the factory.
All components, including the control systems and electrical
equipment, etc., are certified by our Quality Control
Department, and tested under the harshest possible operating
conditions in our laboratories. However, after leaving the
factory, it is possible that one or more of these elements may be
damaged due to causes beyond our control. In such an event,
the user should not work on any of the internal components,
or subject the unit to operating conditions which are not
specified in this manual, since serious damage may result and
the guarantee would be invalidated. Repair and maintenance
work should always be left to the installer.
All recommendations concerning unit installation are intended
to be as a guideline. The installer should carry out the
installation according to the design conditions and should
comply with all applicable regulations for air conditioning and
refrigeration installations.
NOTE: The manufacturer does not accept responsibility for
any malfunctions resulting from misuse of the equipment.
39
TROUBLESHOOTING CHART
A list of possible faults, as well as the probable cause and suggested solutions is shown in Table 10. In the event of a unit
malfunction it is recommended to disconnect the power supply and ascertain the cause.
Table 10 - Troubleshooting chart
SymptomsCauseRemedy
Unit does not startNo power supplyConnect power supply
Main switch openClose switch
Low line voltageCheck voltage and remedy the deficiency
A protection has trippedReset
Contactor stuck openReplace contactor
Seized compressorReplace compressor
Unit starts and stops frequentlyDefective compressor contactorReplace contactor
Defective compressorReplace compressor
Refrigerant lossesCheck and add the necessary quantity
Unit continuously cuts out atCOOLING CYCLE:
low pressureDefective low pressurestatReplace pressurestat
Refrigerant lossesCheck and add the necessary quantity
Indoor fan does not operateCheck fan motor
Unit continuously cuts out atCOOLING CYCLE:
high pressureDefective high pressurestatReplace pressurestat
Blocked filter drierReplace filter
Outdoor fan does not operateCheck fan motor
HEATING CYCLE:
Defective high pressurestatReplace pressurestat
Indoor fan does not operateCheck fan motor
Abnormal system noisePiping vibrationSupport piping
Noisy compressorCheck and change if necessary
Badly fitting panelsInstall correctly
Compressor loses oilLeak in systemRepair leak
Water lossDefective drainage connectionsCheck and tighten if necessary
40
Order No. 15031-20, 11.2001. Supersedes order No.: NewPrinted on Totally Chlorine-Free Paper.
Manufacturer reserves the right to change any product specifications without notice.Printed in the Netherlands
Manufacturer: Carrier, Guadalajara, Spain
AM-036920
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.