Carrier 39NX user guide manual

With Product Integrated Controls (PIC)
Installation, Operation, and
Start-Up Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ...................2
GENERAL ...................................2
INSTALLATION .............................2-64
Service Area Requirements ...................2
• REMOTE CONTROL BOX CONDENSATE PREVENTION
Make Electrical Connections ..................3
Variable Frequency Drives ...................38
Water Valve Assemblies .....................38
• VALVE WIRING
Duct Static Pressure Probe (VAV Units) ......39
Space Temperature Sensor ..................40
Outdoor-Air Temperature Sensor .............42
Mixed-Air Temperature Sensor ...............42
• CONTROL RANGES
Supply-Air Temperature Sensor ..............44
Return-Air Temperature Sensor ..............44
Heat Interlock Relay .........................45
Fan Relay ..................................45
Wall-Mounted Relative Humidity Sensor ......46
Duct-Mounted Relative Humidity Sensor ......47
• LOCATION FOR OUTSIDE AIR RELATIVE HUMIDITY
• LOCATION FOR RETURN AIR RELATIVE HUMIDITY
Airflow Switch ..............................48
Low-Temperature Thermostat ................48
Filter Status Switch .........................49
High-Pressure Switch .......................49
Air Quality Sensors .........................49
Constant Outside Air (OAC) Control ..........50
• PROBE INSTALLATION
• OAC CALIBRATION
• USING OAVP VALUES TO DETERMINE DUCT AIRFLOW
• FIELD-SUPPLIED OR HIGH-VELOCITY PRESSURE TRANSDUCERS
• REMOTE LOCAL INTERFACE DEVICE (HSIO)
• RETURN-AIR TEMPERATURE SENSOR, OUTDOOR-AIR TEMPERATURE SENSOR, ENTHALPY SWITCH, AND MIXED-AIR TEMPERATURE SENSOR
• SPACE TEMPERATURE SENSOR (SPT)
• DAMPER ACTUATORS
• SMOKE CONTROL OPTION
• ANALOG DEVICE FOR ANALOG OUTPUT TEMPERATURE CONTROL
39L,NX
Central Station Air-Handling Units
• DEVICE UNDER DISCRETE OUTPUT TEMPERATURE CONTROL
• DISCRETE OUTPUT DEVICE UNDER TIMECLOCK CONTROL
• HUMIDIFICATION DEVICES
• AIR QUALITY SENSOR
• OUTSIDE AIR VELOCITY PRESSURE (OAVP) SENSOR
• FAN VOLUME CONTROL
• ELECTRIC HEATER
• CARRIER COMFORT NETWORK INTERFACE
• OUTDOOR-AIR THERMOSTAT
CONTROL SYSTEM .......................64-68
Processor (PSIO Master) and Option (PSIO Slave)
Modules .................................65
Relay (DSIO) Module .......................65
Local Interface Device (HSIO) ...............67
CONTROL OPERATION ...................69-91
Accessing Functions and Subfunctions .....69
Display Functions ..........................69
• SUMMARY DISPLAY
• STATUS FUNCTION
• HISTORY FUNCTION
• TEST FUNCTION
Programming Functions ...................81
• SERVICE FUNCTION
• SET POINT FUNCTION
• SCHEDULE FUNCTION
CONTROL OPERATING SEQUENCE .......92-102
Constant Volume and Variable Air
Volume Units ............................92
Constant Volume Units Only ................96
Variable Air Volume Units Only .............99
START-UP ..............................103-108
Initial Check ..............................103
Quick Test ................................103
Electronic Valve Actuator Field Test ........108
CONTROL LOOP CHECKOUT ............108,109
To Check Operation of Analog Outputs .....108
VALVE TROUBLESHOOTING .............109-111
General ...................................109
1
⁄2-in. Through 11⁄4-in. Electric Hot Water/Steam
All
Valve Assemblies .......................109
All 11⁄2-in. Through 3-in. Valve Assemblies ..110 CONTROL MODULE
TROUBLESHOOTING ..................111,112
General ...................................111
Module Replacement (PSIO, DSIO) .........112
UNIT TROUBLESHOOTING ...............113-115
METRIC CONVERSION CHART .............116
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 3 Tab 1b
PC 201 Catalog No. 533-913 Printed in U.S.A. Form 39L,NX-2SI Pg 1 3-96 Replaces: 39L,NX-1SI
IMPORTANT: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with these instructions may cause radio interference. It has been tested and found to com­ply with the limits of a Class A computing device as defined by FCC regulations, Subpart J of Part 15, which are designed to provide reasonable protection against such interference when operated in a commercial environment.
SAFETY CONSIDERATIONS
Installation and start-up of air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, start up, or service air-conditioning equipment.
When working on air-conditioning equipment, observe pre­cautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes, including ANSI (American National Standards Institute) Z223.1 (latest version). Wear safety glasses and work gloves.
Disconnect all power to the unit before performing main­tenance or service. Unit may automatically start if power is not disconnected. Electrical shock and personal in­jury could result.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
GENERAL
The Product Integrated Control (PIC) option is available for 39L and 39NX indoor units with a draw-thru configu­ration. The PIC control box can be supplied as part of a dedi­cated PIC section; it is factory-installed and wired and has the same hand (orientation) as the fan section. The control box can also be shipped separately for remote mounting with­out a PIC section. For the remote control box option, all con­nections from the control box to the unit are made to a junc­tion box in the unit’s fan section.
The control box includes electronic modules, fuses, re­lays, transformers, terminal blocks, low-limit air tempera­ture protection (optional), static pressure transducer (VAV
[Variable Air Volume] units only) and high-pressure switch (VAV units). An ON/OFF switch is included to shut off the power to the control box.
PIC environmental limitations are as follows:
Shipping Temperature — −20 to 165 F Shipping Humidity — 10 to 95% Operating Temperature — 32 to 125 F Operating Humidity — 30 to 90%
INSTALLATION
Follow all basic installation instructions for 39L or 39NX units as described in the 39L or 39NX Installation, Start-Up, and Service Instructions shipped with the unit. To verify the PIC and PIC option configurations according to the model numbers, see Fig. 1 and 2.
Leave protective coverings on the unit until it is installed inside and protected from the elements, construction debris, and dirt.
Use one of the keys provided in the 39L or 39NX instal­lation packet (located in fan section) to open the control box door.Visually inspect all components and wiring for any dam­age. Remove the valve assembly packages and the sensor packages from the fan section. For units with PIC sections, remove protective plastic caps from the bulkhead fittings (located on the top edge of the control box) and discard.
Verify that the 10.0 amp ON/OFF switch located on the PIC control box door is in the OFF position. Do not turn the
power supply on at this time.
NOTE: The 39NX and 39L air handlers are designed for in­door applications. Modified units are available for outdoor applications on pier or slab mounts (not curb mounts). Prod-
uct integrated controls are not available for outdoor appli­cations. Consult your Carrier sales representative for further
details.
ServiceArea Requirements — Article 110-16 of the
NEC (National Electrical Code) describes electrical instal­lation.All 39L and 39NX PIC installations must comply with the minimum clearances required for electrical installation as listed in Table 110-16(a) of the code. Make sure to pro­vide the necessary clearance from the PIC unit to any ad­joining wall. Refer to the base unit installation instructions for detailed dimensions for each unit section.
Remote Control Box Option — This option allows
the PIC control box to be mounted away from the unit; the remote control box (Fig. 3) must be wired to the supply fan section. Mount the remote control box assembly to the mechanical room wall near the unit using field-supplied Unistrut metal framing or equivalent supports. The control box has 4 mounting holes in the back of the enclosure for this purpose.
2
Mount the remote control box as follows:
1. Loosen and remove the 4 nuts securing the control panel in the control box.
2. Remove the control panel from the box; set the panel and nuts aside for reassembly later.
3. Mount the control box to the Unistrut support using field­supplied fasteners.
4. Locate, mark, and drill pilot holes on the top of the box for each of the following:
Motor starter wiring
Actuator and sensor wires to fan section junction box
Supply power wires (ac)
Valve wiring or tubing (water valves, field-supplied
sensors, or other devices)
5. Expand the pilot holes as required. Recommended sizes are as follows:
Motor starter wiring —3⁄4in. (5 wires)
Actuator and sensor wires to fan section junction
box —
3
⁄4in. to 1 in. (number of wires and hole di-
ameter determined by application)
Supply power wires (ac) —
1
⁄2in. or3⁄4in.
Valve wiring or tubing — size as required
Fan section panels are provided with pilot holes that can be drilled or punched to accomodate an electrical conduit for the remote control box wiring. Where possible, install the conduit in a panel that will not be removed, such as the discharge panel. See Fig. 4.
REMOTE CONTROL BOX CONDENSATE PREVEN­TION — When the remote control box is installed, precau­tions must be taken to prevent condensation from forming inside the junction box mounted in the unit’s supply fan sec­tion. Standard installation practice is to mount the remote control box adjacent to the air handling unit and then to en­close the Class II wiring in flexible conduit between the con­trol box and the junction box in the fan section.
The sheet metal housing of the control box is not airtight, therefore warm, moist air can migrate through the flexible conduit to the junction box in the fan section. Condensate can form inside the junction box and possibly on the termi­nal lugs.
To prevent moist air from migrating through the conduit, seal the control wires inside the conduit at the remote con­trol box enclosure. See Fig. 4. Use a nonconductive, non­hardening sealant. Permagum (manufactured by Schnee Morehead) or sealing compound, thumb grade (manufac­tured by Calgon), are acceptable materials.
MakeElectrical Connections — 39L and 39NX units
have internal control wiring for the operation of the PIC sec­tion and its control devices. The control system requires a dedicated 120 vac or 230 vac (50 or 60 Hz) power circuit capable of providing a minimum of 10 amps (but not greater than 20 amps) to the control box. The actual number of con­trols on one power source depends on the installation and power circuit requirements. Do not run PIC power wiring in the same conduit as sensor wiring or control wiring of field­installed devices.
IMPORTANT: To ease installation, control wiring is located on the service side of the unit with electrical connectors provided at all unit separation points. If a unit is separated into pieces for installation, rejoin all connectors in their original alpha-numeric sequence upon reassembly. Connectors for vertical fan sections that are shipped out of the normal operating position must also be joined at final assembly.
For units with an integral PIC section, all unit factory con­trol wiring is internal. Only a small number of wires must be field-installed. All internal wiring consists of plenum wires which enter the rear of the control box through sealed fit­tings. Control wiring is 18 to 20 gage, 2-conductor twisted pair.
The electrical power disconnect and fan motor starter are field-supplied and installed. Connections are provided in the control box to wire a field-supplied HOA (HANDS/OFF/ AUTOMATIC) switch. If an HOA switch is used, it must be field-installed in the supply and return fan motor starter cir­cuit. The factory-wired high-pressure switch (variable air vol­ume only) and low-temperature thermostat options are en­ergized when the supply fan circuit is powered.
See Fig. 5-7 for control box component arrangements and Fig. 8 for fan motor wiring. PIC input and output points are listed in Table 1. Consult the wiring diagram located in the control box or Fig. 9-12 for further details.
Power is present in the PIC control box in the motor starter circuit even when the dedicated power to the PIC control box is off.
The supply and return fan starter circuits are independent from each other. Either circuit and its related control box interface can have 24 vac, 120 vac, or 240 vac power.
All options that require a factory-installed transformer are fused with 3.2 amp fuses on the secondary of each transformer.
When the control box is shipped separately for remote mount­ing, all unit wiring terminates in a junction box located in the fan section. Refer to Fig. 12 for the applicable wiring diagram and Table 2 for junction box connections.
If the unit is provided with a factory-installed smoke con­trol option, refer to the section titled Field-Wiring Connec­tions, Smoke Control Option, page 54.
All PIC electrical components are UL (Underwriters’Labo­ratories) listed. The electronic modules are approved under UL HVACEquipment Standard 873. PIC units are listed and labeled by ETL (Engineering Testing Laboratory) to comply with UL Standard 1995 for heating and cooling units, and comply with NFPA (National Fire Protection Association) Standard 90A.
3
LEGEND
ABX — Air Blender AF Airfoil CV Constant Volume IGV Inlet Guide Vanes FC Forward-Curved FMB — Filter Mixing Box MXB — Mixing Box PIC Product Integrated Controls VAV — Variable Air Volume
*The cv capacity rating is the flow (gpm) through a valve at 1 psi pres-
sure drop.
Fig. 1 — Basic PIC Order Number
4
LEGEND
AF Airfoil CV Constant Volume DX Direct Expansion FC Forward-Curved FMB — Filter Mixing Box MXB — Mixing Box N.C. — Normally Closed N.O. — Normally Open PIC Product Integrated Controls VAV — Variable Air Volume
*The cv capacity rating is the flow (gpm) through a
valve at 1 psi pressure drop.
Fig. 2 — PIC Option Order Number
5
NOTE: Dimensions in [ ] are in millimeters.
Fig. 3 — Control Box for Remote Mounting
Fig. 4 — Sealing Control Wiring in Flexible Conduit
6
LEGEND (Fig. 5-12, Table 2)
AFS Airflow Switch AO Analog Output AOTC — Analog Output Temperature Control AQ AQ C—Contactor
Air Quality Sensor, No. 1
1
Air Quality Sensor, No. 2
2
CCW Counterclockwise CH Channel CR Control Relay CUST Condensing Unit Status CV Constant Volume CW Clockwise CWV Chilled Water Valve DHH Duct High Humidity DO Discrete Output DOTC — Discrete Output Temperature Control DSIO Control Module, Electric Heat and/or DX DTCC Discrete Time Clock Control DX Direct Expansion DXS DX Cooling Stage DXSD Direct Expansion Cooling Shutdown EHS Electric Heaters ELEC Electric ENT Enthalpy Switch EQUIP — Equipment EVAC Smoke Evacuation Input EXD Exhaust Air Damper Actuator FLTS Filter Status Switch FSD Fire Shutdown Device FU Fuse GND Ground HIR Heat Interlock Relay HOA Hand-Off-Auto. Switch HPS High-Pressure Switch HSIO Keyboard and Display Module HT Heat HUM Humidifier HWV Hot Water Valve IGV Inlet Guide Vane Actuator LTT Low Temperature Thermostat MAD Mixed-Air Damper Actuator MAT Mixed-Air Temperature MPSIO — Master Processor Module
(Processor Module)
OAD Outdoor-Air Damper Actuator OARH — Outdoor-Air Relative Humidity OAT Outdoor-Air Temperature OAVP — Outdoor-Air Velocity Pressure
OT Outside-Air Thermostat PH Preheat PL Plug Assembly PRESS — Smoke Pressurization Input PSIO Processor Module PURG Smoke Purge Input RAD Return-Air Damper Actuator RAT Return-Air Temperature RFAN Return Fan RFR Return Fan Relay RFVC Return Fan Volume Control RH Relative Humidity RVP Return Velocity Pressure SAT Supply-Air Temperature SF Fan Status Relay SFAN Supply Fan SFR Supply Fan Relay SMK Smoke SNB Snubber SP Static Pressure Transducer SPSIO — Slave Processor Module
(Option Module)
SPT Space Temperature SVP Supply Velocity Pressure SW Switch TB Terminal Block Terminal TEMP Temperature TRAN Transformer VAV Variable Air Volume W/ With WO/ Without
Marked Wire or Cable Terminal (Marked) Terminal (Unmarked)
Terminal Block Splice (Factory)
Splice (Field) Wiring Factory
Wiring Field Control Wiring Field Power Option or Accessory Common Potential
NOTES:
1. Use copper conductors only.
2. Wire is in accordance with National Electrical Code (NEC).Forlocalcodes, replace original wires with 90 C wire or its equivalent.
3. Replace wires fromIGV, FLTS,MAT,SAT,OAD,RAD,andELEC HTwith 125 C plenum cable conductor as required.
4. Input channel numbers and points for configuration of the optional analog output temperature control (AOTC) follow:
CHANNEL SENSOR DESCRIPTION
1 SAT Supply-Air Temperature 2 OAT Outdoor-Air Temperature 3 MAT Mixed-Air Temperature 6 SPT Space-Air Temperature 7 RAT Return-Air Temperature
34 TEMP Preheat or Optional Carrier Sensor
5. Reference for wire markers, where ‘X’ represents a numeral:
X — Item number on wiring harness BX — Box wire CX — Cable KX — Accessory kit wire
7
ARRANGEMENT FOR SIZES 03 AND 06
ARRANGEMENT FOR SIZES 08 THROUGH 35
Fig. 5 — PIC Section Control Box Component Arrangements, 39L
8
Fig. 6 — PIC Section Control Box Component Arrangement, 39NX Sizes 07-21
9
Fig. 7 — PIC Section Control Box Component Arrangement, 39NX Sizes 26-92
10
Fig. 8 — Fan Motor Starter Circuit and PIC Control Wiring Interface — PIC Power for
Control Circuit From Dedicated Source
11
MODULE,
DEFAULT ADDRESS
PSIO (Processor) ADDRESS 1
PSIO (Option) ADDRESS 31
DSIO (Electric Heat) ADDRESS 19
DSIO (DX without Electric Heat) ADDRESS 19
DSIO (DX with Electric Heat) ADDRESS 49
Table 1 — Input and Output Points
INPUT
SAT AI 1 IGV* AO 13 OAT AI 2 MIXD AO, DO† 14 MAT AI 3 HWC AO 15 RH AI 4 CWC AO 16 LTT DI 5 SF DO 17 SPT AI 6 HIR* DO 18 RAT AI 7 — SP* AI 8 — AFS DI 9 — FLTS DI 10 — OARH AI 11 — ENT DI 12 — SVP* AI 31 RFVC* AO 43 RVP* AI 32 HUM1 AO, DO 44 DHH DI 33 HUM2 DO 45 TEMP AI 34 AOTC AO 46 PRES DI 35 DOTC DO 47 EVAC DI 36 DTCC DO 48 PURG DI 37 — FSD DI 38 — AQ1 AI 39 — AQ2 AI 40 — OAVP* AI 41 — METER DI 42 — — EHS1 DO 23 — EHS2 DO 24 — EHS3 DO 25 — EHS4 DO 26 — EHS5 DO 27 — EHS6 DO 28 — EHS7 DO 29 — EHS8 DO 30 CUST DI 19 DXS1 DO 23 DXSD DI 20 DXS2 DO 24 — DXS3 DO 25 — DXS4 DO 26 — DXS5 DO 27 — DXS6 DO 28 — DXS7 DO 29 — DXS8 DO 30 CUST DI 49 DXS1 DO 53 DXSD DI 50 DXS2 DO 54 — DXS3 DO 55 — DXS4 DO 56 — DXS5 DO 57 — DXS6 DO 58 — DXS7 DO 59 — DXS8 DO 60
INPUT
TYPE
CHANNEL
NUMBER
OUTPUT
OUTPUT
TYPE
CHANNEL
NUMBER
AFS Airflow Switch (Supply Fan AI Analog Input
AO Analog Output AOTC — Analog Output Temperature
AQ1, 2 — Air Quality Sensors 1, 2 CUST Condensing Unit Status
CWC Chilled Water Coil DI Discrete Input DHH Duct High Humidity DO Discrete Output DOTC — Discrete Output Temperature
DTCC — Discrete Output Timeclock
*Available on VAV only. †Discrete output with two-posi ion damper control.
Status Switch)
Control
(Outdoor Air Thermostat)
Control Control
LEGEND
DXS1-8 Direct Expansion Cooling DXSD Direct Expansion Cooling EHS1-8 Electric Heater Stages 1-8
ENT Enthalpy Switch EVAC Evacua ion FLTS Filter Status Switch FSD Fire Shutdown HIR Heat Interlock Relay HWC Hot Water Coil HUM1, 2 — Humidity Stages 1, 2 IGV Inlet Guide Vanes LTT Low Temperature Thermostat
MAT Mixed-Air Temperature METER Meter (Pulsed Dry-Contact
Stages 1-8 Shutdown
(also labelled FRZ)
Input)
12
MIXD — Mixed-Air Dampers OARH — Outdoor-Air Relative Humidity OAT Outdoor-Air Temperature OAVP — Outdoor-Air Velocity Pressure PRES — Pressurization PURG — Purge RAT Return-Air Temperature RFVC — Return Fan Volume Control RH Relative Humidity RVP Return Velocity Pressure SAT Supply-Air Temperature SF Supply Fan Relay SP Static Pressure SPT Space Temperature SVP Supply Velocity Pressure TEMP — Optional Temperature Input
13
Fig. 9 — Unit Wiring Schematic, 39L Sizes 03-35 (115 v, Typical)
14
Fig. 9 — Unit Wiring Schematic, 39L Sizes 03-35 (115 v, Typical) (cont)
15
Fig. 9 — Unit Wiring Schematic, 39L Sizes 03-35 (115 v, Typical) (cont)
Fig. 9 — Unit Wiring Schematic, 39L Sizes 03-35 (115 v, Typical) (cont)
16
Fig. 9 — Unit Wiring Schematic, 39L Sizes 03-35 (115 v, Typical) (cont)
17
Fig. 9 — Unit Wiring Schematic, 39L Sizes 03-35 (115 v, Typical) (cont)
18
19
Fig. 10 — Unit Wiring Schematic, 39NX Sizes 07-21 (115 v, Typical)
20
Fig. 10 — Unit Wiring Schematic, 39NX Sizes 07-21 (115 v, Typical) (cont)
21
Fig. 10 — Unit Wiring Schematic, 39NX Sizes 07-21 (115 v, Typical) (cont)
Fig. 10 — Unit Wiring Schematic, 39NX Sizes 07-21 (115 v, Typical) (cont)
22
Fig. 10 — Unit Wiring Schematic, 39NX Sizes 07-21 (115 v, Typical) (cont)
23
Fig. 10 — Unit Wiring Schematic, 39NX Sizes 07-21 (115 v, Typical) (cont)
24
25
Fig. 11 — Unit Wiring Schematic, 39NX Sizes 26-92 (115 v, Typical)
26
Fig. 11 — Unit Wiring Schematic, 39NX Sizes 26-92 (115 v, Typical) (cont)
27
Fig. 11 — Unit Wiring Schematic, 39NX Sizes 26-92 (115 v, Typical) (cont)
Fig. 11 — Unit Wiring Schematic, 39NX Sizes 26-92 (115 v, Typical) (cont)
28
Fig. 11 — Unit Wiring Schematic, 39NX Sizes 26-92 (115 v, Typical) (cont)
29
Fig. 11 — Unit Wiring Schematic, 39NX Sizes 26-92 (115 v, Typical) (cont)
30
31
Fig. 12 — Unit Wiring Schematic, 39L and 39NX PIC with Remote Control Box
32
Fig. 12 — Unit Wiring Schematic, 39L and 39NX PIC with Remote Control Box (cont)
33
Fig. 12 — Unit Wiring Schematic, 39L and 39NX PIC with Remote Control Box (cont)
Fig. 12 — Unit Wiring Schematic, 39L and 39NX PIC with Remote Control Box (cont)
34
Fig. 12 — Unit Wiring Schematic, 39L and 39NX PIC with Remote Control Box (cont)
35
Fig. 12 — Unit Wiring Schematic, 39L and 39NX PIC with Remote Control Box (cont)
36
Table 2 — Junction Box Connections for Optional Remote Control Box
REMOTE
CONTROL BOX
LOCATION
MPSIO 2 SAT — BLK 1 MPSIO 3 SAT — RED 2 MPSIO 8 MAT — BLK 3 MPSIO 9 MAT — RED 4
TB3 10 FLTS — BLK 5
MPSIO 28 FLTS — RED 6
TB3 10 LTT — K3 7
MPSIO 13 LTT — K1 8
TB2 19 OAD — BLK 9 TB2 20 OAD — WHT 10 TB2 6 OAD — GRN 11
MPSIO 40 OAD — RED 12
TB2 21 RAD — BLK 13 TB2 22 RAD — WHT 14 TB2 7 RAD — GRN 15 TB2 6 RAD — RED 16 TB2 27 EXD — BLK 17 TB2 28 EXD — WHT 18 TB2 8 EXD — GRN 19 TB2 7 EXD — RED 20 TB2 15 SFAN1 — BLK 21
TB2 16 SFAN1 — WHT 22 MPSIO 38 SFAN1 — GRN 23 MPSIO 37 SFAN1 — RED 24
TB2 17 SFAN2 — BLK 25
TB2 18 SFAN2 — WHT 26
TB2 23 RFAN1 — BLK 27
TB2 24 RFAN1 — WHT 28
SPSIO 38 RFAN1 — GRN 29 SPSIO 37 RFAN1 — RED 30
TB2 25 RFAN2 — BLK 31
TB2 26 RFAN2 — WHT 32
SPSIO 12 PH — BLK 33 SPSIO 11 PH — RED 34
NOTES:
1. Pneumatic tubing to connect the airflow sensor in the fan to the remote control box is bundled with the internal PIC wiring to the junction box, but does not enter the box. Route tube directly to remote control box along with conduit containing wiring from junction box to remote control box.
2. See Legend on page 7.
CONTROL
BOX
TERMINAL
FAN SECTION
JUNCTION BOX
SIGNAL
JUNCTION
BOX
TERMINAL
37
Variable-Frequency Drives — The input signal for
the inverter must be 4 to 20 mA. Use a 2-conductor 20 AWG (American Wire Gage) cable (single twisted pair, unshielded) to connect the input of the inverter to the output of the PIC control terminals. See Fig. 8.
Wire the inverter so that if it is placed in the manual or bypass mode the low temperature thermostat and the high­pressure switch (if supplied) are still in the motor control circuit to protect the unit.
Adjust the minimum inverter speed to provide at least 10% airflow when inlet guide vanes are at 0% (4 mA) and maxi­mum design airflow when inlet guide vanes are at 100% (20 mA). Use the local interface device to verify that the
supply fan status ( ) shows the fan is ON and that the supply fan is operating at the lowest airflow adjustment. In-
crease inverter minimum speed as required. For additional information, see the Quick Test section on page 103.
Water Valve Assemblies — Water valve assemblies
(Fig. 13) are shipped inside the fan section for field instal­lation. All valve assemblies have electrically powered ac­tuators. Each actuator has an external junction box for field wiring.The junction box contains 24 vac power wires (WHITE/ BLUE, BLACK) and 4 to 20 mA signal wires (1RED,
−GREEN). The actuators operate the valve through a linear stroke; if power is lost, a return spring reverses the stroke and returns the valve stem to the normal position.
VAL VE ACTUATOR
ACTUATOR LINKAGE
VALVE BODY
To prevent electric shock and equipment damage, dis­connect the power to the control box before installing valve assemblies. Turn power switch located on control box door to OFF.
On installations where valve mounting space is limited, use unions to couple valve assemblies to water lines. If unions do not provide sufficient clearance, refer to the Valve Troubleshooting section, page 109.
On chilled water applications or hot water applications with
1
⁄2to 3-in. valves, the valve actuators can be mounted in
1 any position above the centerline of the valve body.For steam applications or hot water applications with1⁄2to 11⁄4-in. valves that have actuators and high-temperature linkage exten­sions, mount the actuator above the centerline of the valve body and 45 degrees from vertical. This position helps to prevent actuator exposure to direct heat convection.
DO NOT install valve assembly where excessive mois­ture, corrosive fumes, and/or vibration are present.
INSTALL all 2-way valve assemblies so that they close against system flow. An arrow on the valve body indi­cates the proper flow direction.
ALWAYS install 3-way mixing valve with 2 inlet flows and one outlet. Normal flow will be from port B to port AB with stem up. See Fig. 14.
Fig. 13 — Valve Assembly (T ypical)
Fig. 14 — Three-Way Mixing Valve — Normal Flow,
T ypical Piping
38
VALVE WIRING
Valves MUST be connected to the correct processor mod­ule terminal to operate properly. Damage to the actuator may occur if the valve is improperly connected.
Hot WaterValves (Fig. 15) — Using a 4-conductor 20AWG cable (two twisted pairs, no shield), connect the hot water valve actuator as follows:
1. Using twist-on wire connectors, connect the BLACK and WHITE/BLUE leads inside the actuator junction box to the 24 vac power wires of the cable. Connect the other ends of the power wires to TB2, pins 11 and 12, in the PIC control box.
2. Using twist-on wire connectors, connect the RED ( ) and GREEN (−) leads inside the actuator junction box to the other 2 wires in the cable. Note the polarity of each wire.
3. Connect the positive signal wire (connected to the RED lead) to pin 43 on the processor module. Connect the nega­tive signal wire (connected to the GREEN lead) to pin 44 on the processor module.
Chilled Water Valves (Fig. 16) — Using a 4-conductor 20 AWG cable (two twisted pairs, no shield), connect the chilled water valve actuator as follows:
1. Using twist-on wire connectors, connect the BLACK and WHITE/BLUE leads inside the actuator junction box to the 24 vac power wires of the cable. Connect the other ends of the power wires to TB2, pins 9 and 10, in the PIC control box.
2. Using twist-on wire connectors, connect the RED ( ) and GREEN (−) leads inside the actuator junction box to the other 2 wires in the cable. Note the polarity of each wire.
3. Connect the positive signal wire (connected to the RED lead) to pin 46 on the processor module. Connect the nega­tive signal wire (connected to the GREEN lead) to pin 47 on the processor module.
Duct Static Pressure Probe (VAV Units) — The
duct static pressure probe is shipped inside the control box.
Select a location in the ductwork where the static pressure will be representative of the static pressure to be monitored and maintained (typically 2/3 of the distance down the duct from the fan). Install the probe with the tip facing the air­flow. See Fig. 17.
Use
1
⁄4-in. OD approved polyethylene tubing for up to 50 ft (3⁄8-in. OD for 50 to 100 ft) to connect the probe to the 39L or 39NX unit. Route the tubing back to the mechanical room and connect the tubing to the bulkhead fitting labelled H (HIGH), located on the bottom edge of the 39L control box or top edge of the 39NX control box.
NOTE: If the probe is more than 100 ft from the control box, it is recommended that the static pressure sensor be re­moved from the control box and mounted remotely.The sen­sor should be mounted closer to the probe and then rewired to the original connections in the control box.
NOTE: Connections for 39NX with integral PIC shown. See wiring diagrams in Fig. 9 and 12 for terminal connections in 39L control box and all remote-mount control boxes.
Fig. 15 — Hot Water Valve Wiring
39
FACTORY WIRING FIELD WIRING
NOTE: Connections for 39NX with integral PIC shown. See wiring diagrams in Fig. 9 and 12 for terminal connections in 39L control box and all remote-mount control boxes.
Fig. 16 — Chilled Water Valve Wiring
Space TemperatureSensor (Fig. 18) — The space
temperature sensor (SPT) is packaged and shipped inside the fan section. It is installed on a building interior wall to mea­sure room air temperature.
The wall plate accommodates both the NEMA (National Electrical Manufacturers’ Association) standard and the European use of a junction box to accommodate the wiring is recom­mended for installation. The sensor can be mounted directly on the wall, if acceptable by local codes.
DO NOT mount the sensor in drafty areas such as near heating or air conditioning ducts, open windows, fans, or over heat sources such as baseboard heaters or radiators. Sensors mounted in these areas produce inaccurate readings.
1
⁄4DIN (Deutsche Industrie Norm) standard. The
Fig. 17 — Duct Static Pressure Probe
Avoid corner locations. Allow at least 3 ft between the sensor and any corner. Airflow near corners tends to be re­duced, resulting in erratic sensor readings.
The sensor should be mounted approximately 5 ft up from the floor, in the area representing the average temperature.
Install the sensor as follows:
1. Remove sensor cover. Using a small blade screwdriver,
insert blade into sensor cover latch slot on bottom of slat. Gently push upward on the screwdriver to release the cover latch. Rotate the cover forward as the screwdriver is re­moved.
2. Snap off the wall plate from the base assembly.
3. Feed the wires from the electrical box through the sensor
base assembly.
5
4. Using two 6-32 x
⁄8-in. flat screws, mount the sensor base
assembly to the electrical box.
5. Dress the wires down and inside the perimeter of the sen-
sor base.
6. Attach the wall plate by snapping it onto the sensor base
assembly.
7. Replace the cover by inserting the top inside edge of the
cover over the tab on top of the sensor base assembly and rotating the cover down. Snap cover on.
Refer to Field Wiring Connections section, page 52 for wiring instructions and details. See Table 3 for Thermistor Resistance vs. Temperature Values.
NOTE: Clean sensor with damp cloth only. Do not use solvents.
40
NEMA — National Electrical Manufacturers’ Association
Fig. 18 — Space Temperature Sensor (P/N HH51BX001)
Table 3 — Thermistor Resistance vs. Temperature Values for Space Temperature Sensor, Return-Air
Temperature Sensor, and Supply-Air Temperature Sensor
RESISTANCE
(Ohms)
173,631.0 −30 38,308.7 22 10,698.1 74 3602.5 126 1409.7 178 168,222.0 −29 37,304.0 23 10,459.4 75 3533.4 127 1386.3 179 162,998.0 −28 36,328.8 24 10,226.8 76 3465.9 128 1363.3 180 157,954.0 −27 35,382.1 25 10,000.0 77 3399.8 129 1340.7 181 153,083.0 −26 34,463.0 26 9,778.9 78 3335.2 130 1318.6 182 148,378.0 −25 33,570.7 27 9,563.4 79 3272.0 131 1296.9 183 143,833.0 −24 32,704.2 28 9,353.1 80 3210.1 132 1275.6 184 139,442.0 −23 31,862.8 29 9,148.2 81 3149.6 133 1254.8 185 135,200.0 −22 31,045.7 30 8,948.4 82 3090.4 134 1234.3 186 131,101.0 −21 30,252.0 31 8,753.5 83 3032.5 135 1214.2 187 127,139.0 −20 29,481.1 32 8,563.4 84 2975.8 136 1194.5 188 123,310.0 −19 28,732.2 33 8,378.0 85 2920.3 137 1175.1 189 119,609.0 −18 28,004.6 34 8,197.1 86 2866.0 138 1156.1 190 116,031.0 −17 27,297.7 35 8,020.7 87 2812.9 139 1137.5 191 112,571.0 −16 26,610.8 36 7,848.6 88 2760.9 140 1119.2 192 109,226.0 −15 25,943.4 37 7,680.6 89 2710.0 141 1101.3 193 105,992.0 −14 25,294.7 38 7,516.8 90 2660.2 142 1083.7 194 108,863.0 −13 24,664.2 39 7,356.9 91 2611.4 143 1066.4 195
99,837.3 −12 24,051.4 40 7,200.9 92 2563.7 144 1049.4 196 96,910.2 −11 23,455.6 41 7,048.6 93 2516.9 145 1032.8 197 94,078.4 −10 22,876.5 42 6,900.0 94 2471.2 146 1016.5 198 91,338.6 −9 22,313.4 43 6,755.0 95 2426.4 147 1000.4 199 88,687.3 −8 21,765.9 44 6,613.4 96 2382.5 148 984.7 200 86,121.6 −7 21,233.5 45 6,475.2 97 2339.5 149 969.2 201 83,638.4 −6 20,715.7 46 6,340.3 98 2297.5 150 954.0 202 81,234.8 −5 20,212.2 47 6,208.5 99 2256.3 151 939.1 203 78,908.0 −4 19,722.4 48 6,079.9 100 2215.9 152 924.5 204 76,655.3 −3 19,245.9 49 5,954.3 101 2176.4 153 910.1 205 74,474.2 −2 18,782.4 50 5,831.7 102 2137.7 154 896.0 206 72,362.1 −1 18,331.5 51 5,712.0 103 2099.8 155 882.2 207 70,316.7 0 17,892.8 52 5,595.0 104 2062.6 156 868.6 208 68,335.6 1 17,465.9 53 5,480.8 105 2026.3 157 855.2 209 66,416.7 2 17,050.4 54 5,369.2 106 1990.6 158 842.1 210 64,557.9 3 16,646.1 55 5,260.2 107 1955.7 159 829.2 211 62,756.9 4 16,252.6 56 5,153.7 108 1921.5 160 816.6 212 61,012.0 5 15,869.6 57 5,049.7 109 1887.9 161 804.1 213 59,321.1 6 15,496.8 58 4,948.1 110 1855.1 162 791.9 214 57,682.4 7 15,133.8 59 4,848.8 111 1822.9 163 779.9 215 56,094.3 8 14,780.4 60 4,751.8 112 1791.3 164 768.2 216 54,554.9 9 14,436.4 61 4,657.0 113 1760.4 165 756.6 217 53,062.2 10 14,101.3 62 4,564.4 114 1730.1 166 745.2 218 51,615.9 11 13,775.1 63 4,473.8 115 1700.4 167 734.0 219 50,213.1 12 13,457.3 64 4,385.3 116 1671.3 168 723.1 220 48,853.0 13 13,147.9 65 4,298.9 117 1642.7 169 712.3 221 47,533.9 14 12,846.4 66 4,214.3 118 1614.7 170 701.7 222 46,254.7 15 12,552.8 67 4,131.7 119 1587.3 171 691.3 223 45,013.9 16 12,266.8 68 4,050.9 120 1560.4 172 681.0 224 43,810.3 17 11,988.1 69 3,971.9 121 1534.1 173 671.0 225 42,642.6 18 11,716.6 70 3,894.6 122 1508.2 174 661.1 226 41,509.8 19 11,452.0 71 3,819.1 123 1482.9 175 651.4 227 40,410.5 20 11,194.2 72 3,745.3 124 1458.0 176 641.8 228 39,343.9 21 10,943.0 73 3,673.1 125 1433.6 177 632.4 229
TEMP
(F)
RESISTANCE
(Ohms)
TEMP
(F)
RESISTANCE
(Ohms)
TEMP
(F)
RESISTANCE
(Ohms)
TEMP
(F)
RESISTANCE
(Ohms)
TEMP
(F)
41
Outdoor-Air Temperature Sensor (Fig. 19) —
The outdoor-air temperature (OAT) sensor is shipped inside the fan section. The OAT sensor continuously monitors the temperature of the air outside the building. The integral shield prevents ice formation on the sensor conductors. A field­supplied conduit junction box is required for installation. See Fig. 20.
Position the OAT sensor so that it accurately senses only the outdoor-air temperature. The sensor must be located up­stream from outside air dampers and located where it is un­affected by interior and duct temperatures. During the unoc­cupied (fan off) period the sensor’s location should have a minimal effect on its readings.
Do not mount the sensor in direct sunlight. Inaccurate read­ings may result. It may be necessary to field-fabricate a shield to protect the sensor from direct sunlight.
Do not mount the sensor near the exhaust from air­handling units or compressors, or near leakage drafts of in­door air, or near shrubbery or trees. Inaccurate readings may result. Do not mount under direct water runoff. Water may freeze around the sensor in winter and produce a false reading.
If sensor wire is shielded, strip back the sensor shield and tape it to prevent contact.
Position the sensor with the slotted end pointed downward.
The field-supplied junction box housing must be threaded to screw onto a male conduit adaptor.The assembledbox and sensor mustbe mounted parallel to the building wall. See Fig. 20. The sensor can also be installed on a roof or other location.
For distances up to 500 ft, use 2-conductor 20 AWGcable to connect the sensor to the PIC terminals. Refer to the Field Wiring Connections section, page 52 for further wiring in­structions. See Table4 for thermistor resistance according to temperature value.
Table 4 — Thermistor Resistance vs
Temperature Values for Outdoor-Air
RESISTANCE
(Ohms)
168,250 −40 5,000.0 77 121,350 −31 4,028.5 86
88,500 −22 3,265.0 95 65,200 −13 2,663.3 104 48,535 −4 2,185.0 113 36,476 5 1,801.5 122 27,665 14 1,493.0 131 21,165 23 1,244.0 140 16,325 32 1,041.5 149 12,695 41 876.0 158
9,950 50 739.5 167 6,245 68 627.5 176
1
⁄2-in. NPT electrical metal tubing (EMT)
Temperature Sensor
TEMPERATURE
(F)
RESISTANCE
(Ohms)
TEMPERATURE
(F)
Fig. 20 — Outdoor-Air Temperature
Sensor Installation
Mixed-Air Temperature Sensor — The optional
mixed-air temperature sensor (MAT) is factory wired and installed on all units with a factory-installed mixing box (MXB), filter mixing box (FMB), or air blender (AMX). On units without an AMX, MXB, or FMB, the optional MAT is pack­aged and shipped inside the fan section for field installation.
The field-installed MAT should be mounted downstream of the return air duct and filters, but as close as possible to the 39L or 39NX unit.
AVOID repeated bending of copper tubing, as this will place stress on the sensor element and lead to eventual breakage.
DO NOT fold or crimp copper tubing. USE CARE in forming and securing the element. STRIP back and tape the shield in order to prevent
contact.
Mount field-installed MAT as follows (Fig. 21):
1. Punch a 1-in. diameter hole in the duct and feed the sen-
sor element through the hole. Mount the utility box on the outside of the duct.
2. Bend the copper tubing surrounding the sensor element
to conform to the area of the duct. Do not bend it to less
1
than 2
⁄2in. diameter on any turn. The sensor element should be evenly distributed over the entire cross sec­tional area of the duct.
Existing support structures may be used for the sensor element, as long as there is no metal-to-metal contact with the copper tubing, and the mounting does not interfere with other functions.
3. Use a field-supplied plastic spacer, clamp, and screws to secure the sensor in the airstream. See Detail A, Fig. 21.
4. Using 2-conductor 20 AWG plenum-rated cable, connect the sensor to the PIC control box terminals.
Fig. 19 — Outdoor-Air Temperature Sensor
(P/N HH79NZ023)
42
NOTE:This sensor uses a resistance temperature device (RTD) element. Polarity is not a consideration.
When space does not allow working inside the duct, mount
as follows (Fig. 22):
1. Open a duct penetration on the opposite side of the sen­sor junction box.
3
2. Wrap the element around a
⁄4-in. PVC pipe, cut holes near the center of the duct on both sides and feed the pipe with sensor element through the hole.
3. Secure the seal around the PVC pipe. NOTE: If local codes do not permit the use of PVC, use
EMT instead.
Refer to Field Wiring Connections section, page 52 for wiring instructions and details. See Table 5 for RTD resis­tance vs temperature values.
Table 5 — RTD Resistance vs Temperature Values
for Mixed-Air Temperature Sensor
RESISTANCE
(Ohms)
693 −40 940 50 1223 140 719 −30 970 60 1257 150 745 −20 1000 70 1290 160 772 −10 1031 80 1325 170 799 0 1062 90 1360 180 827 10 1093 100 1395 190 854 20 1125 110 1430 200 883 30 1157 120 — 912 40 1190 130
TEMP
(F)
RESISTANCE
(Ohms)
TEMP
(F)
RESISTANCE
(Ohms)
TEMP
(F)
Enthalpy Switch (Fig. 23) — The enthalpy switch and
mounting template are located in a box shipped inside the fan section.
The enthalpy switch is normally mounted in a horizontal position with the sensing element exposed to freely circu­lating outdoor air.
DO NOT install enthalpy switch in locations where ex­cessive moisture, corrosive fumes, and/or vibration are present.
Fig. 22 — Alternate Mixed-Air Temperature
Sensor Installation
Mount the switch as follows:
1. Position mounting template on duct. Remove adhesive backing and press template onto outside air duct.
2. Drill four
1
⁄8-in. mounting holes as indicated on the
template.
3. Cut out center portion of duct as outlined on template.
4. Mount controller to duct using screws provided.
If no outside air duct is present, mount the enthalpy switch on a field-supplied and installed plate upstream of the out­side air damper.
Connect the red and blue wires of the enthalpy switch to the PIC control box terminals. Refer to Field Wiring Connections section, page 52 for further details.
CONTROLRANGES — See Fig. 24 for control settings and intermediate settings.
Fig. 21 — Mixed-Air Temperature Sensor
(P/N HH79NZ021) Installation
43
MOUNTING HOLES
Y E L
R E D
B L U
A
Fig. 23 — Enthalpy Switch (P/N HH57AC076)
D
C
B
DIAL
SETTING
A
B
C
D
CONTROL SETTINGS
RELATIVE
HUMIDITY (%)
20 50 80
78 F
(26 C)
73 F
(23 C)
68 F
(20 C)
62 F
(17 C)
73 F
(23 C)
68 F
(20 C)
63 F
(17 C)
58 F
(14 C)
68 F
(20 C)
63 F
(17 C)
59 F
(15 C)
53 F
(12 C)
4. Remove the adhesive backing from the gasket; attach the gasket to the outside of the junction box, aligning the holes in the gasket with the holes in the box.
5. Attach the junction box to the duct with the 2 screws provided.
6. Insert the probe assembly through the compression fit­ting and into the duct. Tighten screws one half-turn past finger tight. Do not overtighten.
For distances up to 500 ft, use 2-conductor 20 AWGcable to connect the sensor to the PIC control box terminals. Refer to Field Wiring Connections section, page 32 for further de­tails. See Table 3 for thermistor resistance vs. temperature values.
CONTROL
CURVE
A B C D
Fig. 24 — Enthalpy Control Settings
Supply-Air TemperatureSensor (Fig. 25) — The
supply-air temperature sensor (SAT) measures the tempera­ture of the air as it leaves the supply fan. The sensor is factory­installed on the fan scroll.
Return-Air Temperature Sensor (Fig. 25) — The
return-air temperature sensor (RAT)is shipped inside the fan section. It measures the temperature in the return air duct. Mount the sensor in the middle of the return air duct ap­proximately 4 to 5 ft from the return air damper. The sen­sor’s probe tip must be within a straight length of duct.
Mount the sensor as follows:
1. Remove the cover of the sensor junction box.
5
2. Drill or punch a turn air duct as indicated in Fig. 26.
3. Drill or punch 2 holes through the sensor gasket into the fan scroll.
⁄16-in. hole on the centerline of the re-
Fig. 25 — Supply/Return Air Temperature Sensor
(P/N HH79NZ019)
Fig. 26 — Return-Air Temperature Sensor
Installation
44
Heat Interlock Relay (Fig. 27) — The heat interlock
relay (HIR) is factory wired and installed on VAV units only. It is a single-pole, double-throw (SPDT) relay that provides normally-open and normally-closed contacts to interface with air terminal units. It allows the air terminals to open when the PIC unit goes into the heating mode. The contacts are silver cadmium oxide and are rated as follows:
48 va at 24 vac and .25 power factor 125 va at 115 vac and .25 power factor 125 va at 230 vac and .25 power factor
The contact terminations are no. 6 screw terminals.
NOTE: The HIR is not used in digital air volume control (DAV) applications.
SDA 2 02 0
NC
2
COI L
DO NOT install the duct high humidity switch in lo­cations where excessive moisture, corrosive fumes, and/or vibration are present. Be sure to allow minimum dimen­sions from the elbows or junctions as indicated in Fig. 29.
Mount the DHH as follows:
1. Position the mounting template on the duct. Remove ad­hesive backing and press template onto duct.
2. Drill four template.
3. Cut out center portion of duct as outlined on template.
4. Mount DHH to duct using screws provided.
For distances up to 500 ft, use 2-conductor 20 AWG cable to connect the switch to the PIC control box terminals. Refer to Field Wiring Connections section, page 52 for fur­ther details.
The DHH adjustment knob provides settings from 15 to 95% relative humidity, The scale range is marked on the face of the switch. The high humidity set point should be at least 65%.
NOTE: The duct high humidity switch has a relative humid­ity differential of 5%.
1
⁄8-in. mounting holes as indicated on the
1
COM
Fig. 27 — Relay (P/N HK35AB001)
NO
Fan Relay — Thefan relay is factory wired and installed
on all 39L and 39NX units. It is a SPST relay that provides a normally-open contact. The relay interfaces with the mo­tor starter circuit and automatically starts/stops the fan when the HOA switch is in the AUTO mode. The contacts are sil­ver cadmium oxide and are rated as follows:
48 va at 24 vac and .25 power factor 125 va at 115 vac and .25 power factor 125 va at 230 vac and .25 power factor
The contact terminations are factory wired to TB1.
Duct High Humidity Switch (Fig. 28) — The duct
high humidity switch (DHH) is shipped inside the fan sec­tion. It is used as a safety input when the humidity control options have been ordered. The DHH adjustment knob pro­vides settings from 15 to 95% humidity.
Locate the DHH control element in the duct, downstream of the humidifier. Adjust the DHH to the ASHRAE (American Society of Heating, Refrigeration, and Air Con­ditioning Engineers) recommended maximum setting of 80%. Settings higher than 80% are not recommended.
The DHH is normally mounted in a horizontal position on the outside surface of the duct with the sensing element ex­posed to freely circulating air.
Fig. 28 — Duct High Humidity Switch
(P/N HL38ZG024)
45
Fig. 29 — Duct High Humidity Switch
Locations
Wall-MountedRelative Humidity Sensor (Fig.30) —
The wall-mounted relative humidity sensor is packaged and shipped inside the fan section. It is installed on interior walls to measure the relative humidity of the air within the occupied space.
The use of a junction box to accommodate the wiring is recommended for installation. The sensor may be mounted directly on the wall, if acceptable by local codes.
DO NOT mount the sensor in drafty areas such as near heating or air conditioning ducts, open windows, fans, or over heat sources such as baseboard heaters or radiators. Sensors mounted in those areas will produce inaccurate readings.
Avoid corner locations. Allow at least 3 ft between the sensor and any corner. Airflow near corners tends to be re­duced, resulting in erratic sensor readings.
Sensor should be vertically mounted approximately 5 ft up from the floor, beside the space temperature sensor.
Install the sensor using 2 screws and 2 hollow wall an­chors (if required); do not overtighten screws. See Fig. 31. Sensor must be mounted with terminals ACIN and OUT located at the top of the sensor as shown in Fig. 32.
For distances up to 500 ft, use 4-conductor 20 AWG cable (2 twisted pairs, no shield) to connect the sensor to the PIC control box terminals and power supply. Refer to Field Wiring Connections section, page 52 for wiring instructions and details.
The PIC controller has a space relative humidity default set point of 40%.
Never attempt to clean or touch the sensing element with chemical solvents, as permanent damage to the sensor will occur.
Fig. 30 — Wall-Mounted Relative Humidity Sensor
(P/N HL39ZZ001)
Fig. 31 — Wall-Mounted Relative Humidity
Sensor Installation
Fig. 32 — Wall-Mounted Relative Humidity
Sensor Positioning
46
Duct-Mounted Relative Humidity Sensor — The
duct-mounted relative humidity sensor and mounting tem­plate are packaged and shipped inside the fan section. The sensor is installed in either the return air ductwork or in the outside air ductwork. If 2 relative humidity sensors are or­dered for differential enthalpy control, then the sensors must be installed in both the return air and outside air ducts. If the sensor is used for control of a humidifier, install the sensor in the return air duct.
The PIC controller has a return air relative humidity de-
fault set point of 40%. LOCATION FOR OUTSIDE AIR RELATIVE HUMIDITY
— Locate the sensor where it accurately measures outdoor conditions, yet is protected from the elements. During the unoccupied (fan off)period, the sensor’slocation should have a minimal effect on its readings.
LOCATION FOR RETURN AIR RELATIVE HUMIDITY — Locate the sensor at least 6 in. upstream or 15 in. down­stream of a 90 degree turn in the ductwork. The best loca­tion is 15 in. downstream of the 90 degree turn of the duct. The probe should be mounted in the center of the duct. See Fig. 33.
Mount the relative humidity sensor (Fig. 34) as follows.
1. Position mounting template on duct.
1
2. Drill four template.
3. Punch a 1 template.
4. Mount sensor to duct using four no. 8 screws. Install 9-in. sensor probe into the 1
⁄8-in. mounting holes as indicated on the
1
⁄8-in. hole as indicated on the mounting
1
⁄8-in. hole.
Fig. 33 — Duct-Mounted Relative Humidity
Sensor Locations
Never attempt to clean or touch the sensing element with chemical solvents, as permanent damage to the sensor will occur.
MixingBox Linkage — On units with mixing box (MXB)
or filter mixing box (FMB), the actuator and linkage are fac­tory installed. The actuator is directly linked to the outdoor­air damper and holds the damper closed. No adjustment is necessary.
For shipping purposes, the secondary linkage rod con­necting the outdoor-air and return-air dampers is factory set for a closed return-air damper.
Adjust the secondary linkage as follows:
1. Open the door of the MXB or FMB to access the return
air damper crankarm. NOTE: On MXB/FMB with top outdoor-air damper, it
may be necessary to remove the vertical panel holding the return-air damper to access the return-air damper crankarm.
2. Loosen the setscrew on the return-air damper crankarm.
3. Move the damper to its full open position.
4. Secure the setscrew on the return-air damper crankarm.
5. Close the MXB or FMB access door.
Fig. 34 — Duct-Mounted Relative Humidity Sensor
(P/N HL39ZZ002) Installation
47
Airflow Switch — The airflow switch (AFS) is a snap-
acting SPDT switch that is factory installed in the PIC con­trol box. It senses the air supplied by the 39L or 39NX unit and provides the microprocessor module with a 24 vac dis­crete signal for fan status. See Fig. 35.
Alength of plenum tubing connects the switch to the probe
located on the fan side plate.
The airflow switch range is 0.05 to 2.0 in. wg with a dead­band of 0.02 in. wg at minimum set point and 0.1 in. wg at maximum set point.
Low-Temperature Thermostat (Fig. 36 ) — The
optional low-temperature thermostat (LTT) is factory wired and installed. It is used to protect the chilled water coil from freezing whenever abnormally cold air passes through the coil.
The LTT consists of a 20-ft capillary tube that is serpen­tined in the airstream on the entering side of the chilled wa­ter coil. It has a range of 34 to 60 F and is factory set at 35 F.
The LTT is wired in series with the motor starter fan relay. If any 1-ft section of the capillary tube senses cold air at or below the thermostat setting, the fan shuts down.Amanual reset is provided to restart the fan after the abnormal prob­lem is fixed. The temperature setting is field-adjustable.
To adjust the temperature set point, turn the adjustment screw (located on the top of the case) until the position in­dicator is at the desired temperature. (A clockwise rotation increases the set point.)
DO NOT set low-temperature thermostat below 35 F. Damage to freezestat may result.
If the temperature exceeds the set point by5Formore, the reset button will restore the circuit.
Outdoor-Air Thermostat (Fig. 37) — Also called
the condensing unit status (CUST) switch, the outdoor air thermostat is a temperature-actuated switch used in systems with direct-expansion cooling. The thermostat is field­installed in the outdoor condensing unit to prevent the sys­tem from operating when the outdoor-air temperature is lower
than the condensing unit’s minimum temperature. When in­stalled, the thermostat must be set to the minimum operating temperature of the condensing unit. If the condensing unit has an optional low-ambient control (Motormaster device), an outdoor-air thermostat is not required.
The outdoor-air thermostat is an SPST switch; the con­tacts open on temperature rise and the set point is adjustable from 45 to 75 F (7.2 to 23.9 C). To increase the set point, turn the indicator clockwise. See Fig. 37 for thermostat set point adjustment and mounting hole locations. Thermostat should be mounted inside condensing unit control box where it can sense the outdoor air temperature but is protected from rain and snow.
TURN SCREW CLOCKWISE TO INCREASE AIRFLOW
TURN SCREW COUNTER­CLOCKWISE TO DECREASE AIRFLOW
NORMALLY CLOSED CONTACT
NORMALLY OPEN CONTACT
CLOSED CONTACT
SPDT SNAP ACTING SWITCH
MOUNTING BRACKET
HIGH­PRESSURE INLET
LOW­PRESSURE INLET
SPDT — Single-Pole, Double Throw
Fig. 35 — Airflow Switch (P/N HK06WC030)
ADJUSTMENT SCREW
MANUAL RESET BUTTON
Fig. 36 — Low-Temperature Thermostat
(P/N HH22CZ001)
Fig. 37 — Outdoor-Air Thermostat (Condensing Unit
Status Switch)
48
Filter Status Switch — The filter status switch (FLTS)
is factory-installed in the filter section on all PIC-equipped units. The switch is a snap-acting SPDT switch. When dirty filter elements cause the pressure drop across the filter me­dia to exceed the switch setting, the switch closes and sends an alarm signal to the PIC.
The 39L units use a single switch. In 39NX units, up to 3 switches can be connected in parallel. When the switches are wired in parallel, it is not possible to isolate an alarm signal to a single switch.
The FLTS has an operating range of 0.05 to 2.0 in. wg. Factory settings for the switch are as follows:
Filter Type
Setting (in. wg)
Flat 0.5 Bag/Cartridge 1.0 Final 1.5
The FLTS electrical ratings are as follows: 300 va pilot duty at 115 to 277 vac
10 amps non-inductive to 277 vac Rated for NO (normally open) and NC (normally closed) contacts.
High-Pressure Switch (Fig. 38) — The high-
pressure switch (HPS) is factory installed in the PIC control box on VAV units only. It is a snap-acting SPDT switch with manual reset that is used to shut down the supply fan when­ever the duct pressure reaches the switch setting. The manual reset is used to restart the fan after the problem has been corrected.
The switch is factory set at 3.0 in. wg. It has a range of
1.4 to 5.5 in. wg and can be field adjusted for specific applications.
Adjust the high-pressure switch setting as follows:
1. Loosen conduit enclosure retaining screw, pull firmly on
the bottom end and snap off cover.
2. Raise set point by turning slotted adjustment screw
(located at top of range spring housing) clockwise. Turn adjustment screw counterclockwise to lower set point.
3. To change or check calibration, use a T assembly with 3 rubber tubing leads. Attach one lead to the HPS and another to an accurate manometer with the appropriate range. Apply pressure through the third lead and ap­proach set point slowly.
4. Adjust set point to at least 0.5 in. wg greater than con­figured static pressure set point.
Air Quality Sensors (Fig. 39) — The air quality (AQ)
sensors are shipped inside the fan section for field installa­tion. Two types of sensors are supplied; one sensor monitors the conditioned air space, and the other sensor monitors the return air duct. Both sensors use infrared technology to de­tect the levels of CO2present in the air.
Sensor descriptions and part numbers are shown in Table 6. To mount the sensor, refer to the installation in­structions shipped with the sensor.
Table6—CO
2
Sensor Accessories
CO2SENSOR ACCESSORY
PART NUMBERS
DESCRIPTION
CGCDXSEN001A00 Wall Mount Sensor (No Display) CGCDXSEN002A00 Wall Mount Sensor with Display CGCDXSEN003A00 Duct Mount Sensor (No Display) CGCDXGAS001A00 Sensor Cal bration Service Kit CGCDXPRM001A00 User Interface Program (UIP)
The CO2sensors listed in Table 6 are all factory set for a range of 0 to 2000 ppm and a linear voltage output of 2 to 10 vdc. Fig. 40 shows ventilation rates for various CO2set points when outside air with a typical CO2level of 350 ppm is used to dilute the indoor air. Refer to the instructions sup­plied with the CO2sensor for electrical requirements and terminal locations.
Any changes to the sensor’s factory configuration require the purchase of the User Interface Program (UIP) or Sensor Calibration Service Kit, which also contains the UIP.
To accurately monitor the quality of the air in the condi­tioned air space, locate the sensor near the return air grille so it senses the concentration of CO
2
leaving the space. The sensor should be mounted at least 1 ft above or 1 ft below the thermostat to avoid direct breath contact.
Do not mount the space sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources. Al­low at least 3 ft between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return air stream.
To accurately monitor the quality of the air in the return air duct, locate the sensor at least 6 in. upstream or 15 in. downstream of a 90 degree turn in the duct. The downstream location is preferred. Mount the sensor in the center of the duct.
If the sensor is mounted in the return air duct, readjust the mixed-air dampers to allow a small amount of air to flow past the return air damper whenever the mixing box is fully open to the outside air. If the damper is not properly ad­justed to provide this minimum airflow, the sensor may not detect the indoor-air quality during the economizer cycle.
Fig. 38 — High-Pressure Switch (P/N HH02WC001)
49
Fig. 39 — Air Quality (CO2) Sensor
IN
24 Vac.
OUT
-
+
PRESSURE
LO
HI
SPAN
ZERO
PRESSURE TRANSDUCER :
Part Number :
Range : 0 -
0 . 1 in.
of water
CARRIER
CORPORATION
T40 - 001C - 04 - 012
9A32201
(Wall Mount Version Shown)
CO2CONCENTRATION (PPM)
Fig. 40 — Ventilation Rates Based on CO2Set Point
Constant Outside Air (OAC) Control — This fea-
ture ensures a continuous supply of outside air to the unit and occupied space. The OAC control monitors the outside air velocity pressure (OAVP) with a probe and pressure trans­ducer.The pressure transducer is factory-installed; the probe is factory-supplied for field installation in the outside air ducts. See Fig. 41 and 42.
PROBE INSTALLATION — Locate each probe in a straight portion of the outside air duct with any dampers, elbows, or fittings at least 2 diameters away. The probe should be in a portion of the duct where the airflow is uniform, so that the probe senses the average air velocity in the duct. The probe must also be located so that measurements at the probe are not influenced by the opening or closing of the outdoor-air dampers.
Install the probe at a 90 degree angle to the airflow and ensure that the holes in the probe are facing and in line with the airflow. The probe tube that is closest to the incoming airflow measures velocity pressure; the rear tube measures duct static pressure. Use approved plenum tubing to connect the probe to the bulkhead fittings on top of the control box. For runs up to 150 ft, use 150 ft, use3⁄8-in. OD tubing. Use at least 25 ft of tubing to prevent pulsations and erratic operation. Coil any extra tub­ing if necessary.
If the outside air duct is large, additional probes can be installed in the duct and manifolded to obtain a more accu­rate velocity pressure reading for the entire duct. Manifold tubing must be larger than the plenum tubing connecting the manifold to the control box. See Fig. 43 and the preceding for recommended tube sizes.
1
⁄4-in. OD tubing. For runs over
Fig. 41 — OAVP Transducer (P/N HK05ZG004)
Fig. 42 — OAVP Probe (P/N 35DN40007001)
NOTE:High-pressuremanifoldconnectionsshown. Low-pressure con­nections are identical and must duplicate high-pressure connections.
Fig. 43 — Probe Manifolding
50
OAC CALIBRATION — Once the probe and tubing are in­stalled, input the set point to match the probe readings. Be­fore adjusting the OAVP probe, ensure that the supply-air fan is providing the maximum design airflow and that the outside-air dampers are adjusted for the design outdoor airflow intake.
To calibrate the PIC processor to match the probe loca­tion, use a precision manometer to measure the velocity pres­sure in the outdoor air duct at design conditions. Use the HSIO (local interface device) or Building Supervisor to in­put the value as the OAVP set point.
Note that the probe does not measure true velocity pres­sure; when positioned as recommended, the probe measures
a velocity pressure 1.563 times that of the velocity pressure in the duct. This multiplier (magnification) factor varies with the probe’s location, and can even be negative if the probe is located at an elbow or turn. All OAVPvalues displayed on the HSIO incorporate the multiplier factor to show the true duct velocity pressure.
If a precision manometer is not available, read the veloc­ity pressure value at the HSIO when the system is running at maximum design airflow and input that value as the set point. During normal operation, the velocity pressure is held constant as the supply fan modulates.
USING OAVP VALUES TO DETERMINE DUCT AIR­FLOW — It is possible to determine the airflow (cfm) in the outside air duct based on the readings obtained by the OAVP probe. See the following procedure.
Use the HSIO and status function ( ) to display the outside air velocity pressure (Pv) at the transducer.
If the airflow obtained by the preceding method is differ­ent from the design airflow or a measurement obtained with a balancer, the OAVP probe is not sensing the average duct velocity and/or the probe’s multiplier factor is effectivelynot
1.563. To match the design or measured airflow to the air­flow determined with the preceding formulas, relocate the probe as recommended or use the HSIO and service
function ( ) to change the probe multiplier factor.
FIELD-SUPPLIED OR HIGH-VELOCITY PRESSURE TRANSDUCERS — The default pressure transducer in­stalled at the factory (P/N HK05ZG004) has a range of 0.00 to 0.05 in. wg, which matches an air velocity range of ap­proximately 225 to 680 fpm. The maximum velocity for op­timum OAC operation and response, however, is 620 fpm. If the average duct air velocity is greater than 620 fpm, use one of the alternate transducers shown in Table 7.
For a field-supplied pressure transducer, use the service function ( ) to configure the OAC control with the transducer’s specifications:
OALV = Transducer minimum output voltage OAHV = Transducer maximum output voltage OALR = Transducer low pressure
(range minimum output) value
OAHR = Transducer high pressure
(range maximum output) value
Find the average velocity (V) in the duct, in fpm:
4005
=Pv = V
Obtain the cross-sectional area of the duct in sq ft. (A). To
determine the airflow (F) in the duct, in cfm:
VxA=F
Table 7 — OAC Pressure Transducers
INDICATED VELOCITY
CARRIER
PART NO.
HK05ZG004 T40-005C-04-013 0.00 — 0.05 0.013 — 0.037 0.005 — 0.045 0.008 — 0.024 0.003 — 0.029 360 — 620 225 — 680 HK05ZG005 T40-001C-04-012 0.00 — 0.10 0.025 — 0.075 0.010 — 0.090 0.016 — 0.048 0.006 — 0.057 505 — 875 320 — 960 HK05ZG006 T40-003C-04-015 0.00 — 0.30 0.075 — 0.225 0.030 — 0.270 0.048 — 0.144 0.019 — 0.173 875 — 1520 555 — 1665
MODUS PART
NO.
RANGE (in. wg)
PRESSURE AT
TRANSDUCER (in. wg)
Optimum
Range
Theoretical
Range
TRUE VELOCITY PRESSURE
IN DUCT (in. wg)
Optimum
Range
Theoretical
Range
VELOCITY IN DUCT
(fpm)
Optimum
Range
Theoretical
Range
51
Field Wiring Connections — All field wiring must
comply with National Electric Code (NEC) and all local re­quirements. The recommended wiring is as follows:
Dampers, actuators, 4-conductor 20 AWG cable and valves (2 twisted pairs, unshielded) Sensors 2-conductor 20 AWG cable
(one twisted pair, unshielded)
Refer to Table 8 for recommended brands and part
numbers.
Table 8 — Recommended Sensor and
Device Wiring
MANUFACTURER
PART NUMBER
Regular* Plenum*
Alpha 1895 American A21501 A48301 Belden 8205 88442 Columbia D6451 Manhattan M13402 M64430 Quabik 6130
*Within a building. NOTE: Wiring is 20 gage, 2-conductor twisted cable.
REMOTE LOCAL INTERFACE DEVICE (HSIO) — When ordered as part of a 39L or 39NX unit, the HSIO is factory­installed and fully wired.
To reinstall the HSIO in a remote location away from the control box, refer to the factory wiring connections in Fig. 9-12 and proceed as follows:
1. Use a 20 AWG 2-conductor twisted wire pair (Belden
No. 8205 or equivalent) to supply power to the HSIO mod­ule. Use a 20AWG 3-conductor cable shielded with drain wire (Belden No. 8772 or equivalent) for communication with the HSIO. Cable length must not exceed 1000 ft.
2. Pull the 2 cables (power and signal) through the electri-
cal conduit to the NEMA standard box or HSIO. Leave approximately 4 ft of wire in the PIC control box for terminations.
3. Route the cables from the PIC control box to the HSIO
bracket. Secure the HSIO cables to the existing cables using either tie wraps or by twisting the HSIO cables around the existing cables. Strip back the jacket 6 in. on each cable after cutting off the excess. Connect the power cable at the PIC control box to the existing 3-pin connector hang­ing at the HSIO bracket. The wires should be terminated in the screw-type locking clamps on Terminals 1 and 2.
4. Connect the signal cable at the PIC control box to the
existing 4-pin communications connector hanging at the HSIO bracket. The wires should be terminated in the lock­ing clamps on Terminals 1, 2, and 3. The shield should be terminated at the HSIO bracket (ground). Be sure to note the color coding used on the cable for later reference when terminating the other end of the cable.
5. At the NEMA standard box or HSIO, connect the power
conductors to Pin 1 and 2 of the 3-pin plug. Using the color coding from the above step, connect the signal cable to Pin 1, Pin 2, and Pin 3 of the 4-pin communications connector. Remove the shield and drain wire from this end of the cable.
6. After the HSIO is installed inside the remote cover, con-
nect the 4-pin and 3-pin plugs to the HSIO.
RETURN-AIR TEMPERATURE SENSOR, OUTDOOR­AIR TEMPERATURE SENSOR, ENTHALPY SWITCH, AND MIXED-AIR TEMPERATURESENSOR — Wires are to be connected to the proper terminals on the processor mod­ule. See Fig. 44 for details.
Select a 20 AWG twisted pair, no shield cable. Connect as
per table below:
SENSOR
PROCESSOR
MODULE
PIN NO.
Return-air temperature sensor (RAT) 20 and 21 Outside-air temperature sensor (OAT) 5 and 6 Enthalpy switch (ENT) 34 and TB2-3 Mixed-air temperature sensor (MAT) 8 and 9 Space temperature sensor (SPT) 17 and 18
NOTE: The MAT is factory wired on all units with a factory-installed mixing box, filter mixing box, or air blender.
SPACETEMPERATURESENSOR (SPT) —The space tem­perature sensor cover includes terminal block TB1, a jumper between Pin E2 and Pin E3, and an RJ11 female connector. The RJ11 female connector connects the service tool with the Carrier Comfort Network.
Jumper MUST be in place between Pin E2 and Pin E3 or inaccurate readings could result. Ensure that the jumper is in place before installing the sensor.
Using a 20 AWG twisted pair conductor cable rated for the application, connect one wire of the twisted pair to Terminal T1 and connect the other wire to Terminal T2 on TB1. See Fig. 45.
The other ends of the wires are connected to the processor (PSIO master) module. As polarity is not a consideration, connect one wire to Terminal 17 and one wire to Terminal 18 of the processor module.
RJ11 Plug Wiring — Refer to the Carrier Comfort Network Interface, page 64, for communication bus wiring and cable selection. The cable selected must be identical to the CCN communication bus wire used for the entire network.
Cut the CCN wire and strip the ends of the RED, WHITE, and BLACK conductors. Insert and secure the RED ( ) wire to Pin J2 of the SPT terminal strip TB1. Insert and secure the WHITE (ground) wire to Pin J3 of the SPT terminal strip TB1. Insert and secure the BLACK (−) wire to Pin J5 of SPT terminal strip TB1.
The other end of the communication bus cable must be connected to the remainder of the CCN communication bus at the COMM1 plug on the processor (PSIO master) mod­ule. Refer to Carrier Comfort Network Interface section, page 64, for more details.
DAMPERACTUATORS— The PIC processor can activate a field-installed modulating exhaust/relief damper. This is achieved by wiring the factory-supplied damper actuator in series with the factory-supplied and field-installed mixing box damper actuator.
The PIC processor can also activate a field-installed damper actuator mounted in a field-supplied mixing box. These ac­tuators are available from the factory when ordered as an option with the unit.
See Table 9 for recommended actuators. NOTE: The actuator selected must be capable of receiving
a 4 to 20 mA signal and must have a total impedance of less than 250 ohms. Wire should be 20 gage minimum, twisted­pair type and rated for the application.
52
For factory-supplied actuators that are field-installed, the 24 vac power source is included with the unit wired in the control box. For field-supplied actuators, a 24 vac power source must be field-supplied and installed for each actuator.
To prevent equipment damage: Power must NOT be con­nected to an earth ground; actuator case must NOT be connected to control input terminals.
Field-Supplied Exhaust Damper — Wire the 4 to 20 mAsig­nal of the factory-supplied exhaust damper actuator as fol­lows (Fig. 46):
1. Select a 20 AWG twisted pair conductor cable rated for the application. Identify the positive ( ) and negative (−) signal contacts on the actuator.
2. Install cable from the actuator to the PIC control box.
3. Remove jumper no. 84 from between terminals TB2, 7 and 8. Connect positive ( ) lead to terminal 8 of TB2. Connect negative (−) lead to terminal 7 of TB2.
Field-Supplied Modulating Mixing Box — Wire the 4 to 20 mA signal of the factory-supplied damper actuator as fol­lows (Fig. 47):
1. Select a 20 AWG twisted pair conductor cable rated
for the application. Identify the positive ( ) and negative (−) signal contacts on the actuator.
2. Install cable from the actuator to the PIC control box.
3a. For the outside-air damper (OAD) actuator, connect the
positive ( ) lead to pin 40 of the processor module. Con­nect the negative (−) lead to terminal 6 of terminal block 2 (TB2).
b. If the actuator is factory-supplied, connect the actua-
tor’s 24 vac power wires to TB2, terminals 19 and 20. If the actuator is field-supplied, connect the power wires to a separate, isolated 24 vac power source.
LEGEND
ENT — Enthalpy Switch MAT — Mixed-Air Temperature Sensor OAT — Outside-Air Temperature Sensor RAT — Return-Air Temperature Sensor SPT — Space Temperature Sensor
Field Wiring
NOTE: Connections for 39NX with integral PIC shown. See wiring diagrams in Fig. 9 and 12 for terminal connections in 39L control box and all remote-mount control boxes.
Fig. 44 — Field Wiring of Sensors
IMPORTANT: Jumper may be connected from E1 to E3. Move jumper to connect E2and E3 before installingsensor,otherwise incorrectspacetem­perature values are generated.
Fig. 45 — Space Temperature Sensor Wiring
53
Table 9 — Recommended Actuators
PART
NO.
VOLTAGE (50/60 Hz)
VA (24 vac)
IMPEDANCE
(Ohms)
SIGNAL INPUT
(mA)
DAMPER AREA
(sq ft)
TORQUE
(in.-lb)
STROKE
Parallel Opposed
HF27BB006 24 18 82.5 4 to 20 8.4 10.8 15 2 in. HY27BB001* 24 60 250.0 4 to 20 42 54 50 180° HF27BB010 24 44 82.5 4 to 20 106 137 190 3
1
⁄2in.
*Shipped with drive HF39CB001, which must be field-installed on actuator. NOTES:
1. All actuators are spring return.
2. Damper arearatings are nominal and arebased on standard (NOTlow leak) dampers at 1.0 in. wg pressure and 2000 fpm velocity.
3. Actuator wire coding is as follows: HF27BB006 - BLACK and WHITE (24 vac)
RED ( signal) GREEN (− signal)
HY27BB001 - BLACK and WHITE (24 vac)
ORANGE ( signal) BLUE (− signal)
HF27BB010 - WHITE/BLUE and BLACK (24 vac)
RED ( signal) GREEN (− signal)
4. Actuator HH27BB006 is equipped with 20 ft of plenum cable. Wires for ac­tuators HY27BB001 and HF27BB010 are in the actuator junction box.
5. Actuators are available as an option when ordered with the unit.
4a. For the return-air damper (RAD) actuator, connect the
positive ( ) lead to TB2, terminal 6. Connect the nega­tive (−) lead to TB2, terminal 7.
b. If the actuator is factory-supplied, connect the actua-
tor’s 24 vac power wires to TB2, terminals 21 and 22. If the actuator is field supplied, connect the power wires to a separate, isolated 24 vac power source.
Field-Supplied Two-Position Damper — The factory­supplied SPDT relay must be field-installed and wired. The relay contacts are rated as follows:
48 va at 24 vac and .25 service factor 125 va at 115 vac and .25 service factor 125 va at 230 vac and .25 service factor
The relay provides a set of contacts (normally open and nor­mally closed) using no. 6 screw terminals; the 24 vdc coil connections are through
1
⁄4-in. quick connects.
Using a 20AWG twisted cable, connect the relay coil con­tacts 1 and 2 to the processor module pins 41 and 42. See Fig. 48.
To connect the field-supplied two-position damper actua­tor (Fig. 48): Connect one contact of the actuator to the normally-open contact of the relay .Connectthe common con­tact of the relay to one leg of the power source. Connect the other contact of the actuator to the other leg of the power source.
SMOKE CONTROL OPTION — The smoke control option includes 3 relays which control the 4 different modes of the option. These relays are factory wired.Terminalblock 5 (TB5) provides an easy means to wire the field-supplied smoke con­trol panel to the PIC controller on the 39L or 39NX unit. See Fig. 49 and 50.
The approved building fire alarm system must provide 4 different normally-open dry contact closures. A field­supplied 24 vac, double-pole, double-throw (DPDT) fire shut­down (FSD) relay rated for the application (240 vac with a 10 amp minimum) is required.
All power going through the smoke control panel dry con­tacts and the FSD relay coil is furnished by the PIC control box. A 24 vac fused power source uses a factory-installed 3 amp in-line fuse. See Fig. 49 or 50 for smoke control op­tion wiring details.
Wire as follows:
1. Disconnect all power at the unit, PIC control box, return fan (if applicable), and fire panel.
2. Wire the supply fan motor starter per Fig. 8.
3. If applicable, wire the return fan as shown in Fig. 49 or
50. NOTE: Return fan power may be different from supply
fan power.
4. Connect leads from the return fan HOA switch to terminals 9 and 10 of TB5.
5. Wire the first set of contacts of the DPDT FSD. For fire shutdown of the unit from a local smoke detector, wire ONLYthe normally-closed contacts (NEC, class 1 power rated) to the hot leg of the fan power supply and ter­minal 2 of TB1.
6. Terminal 8 of TB5 is internally connected to ground. Connect one side of the EVAC, PURG, and PRES dry contacts of the smoke control panel to terminal 8 of TB5.
7. Connect the other side of the PRES dry contact to ter­minal 3 of TB5. Connect the other side of the PURG dry contact to terminal 4 of TB5. Connect the other side of the EVAC dry contact to terminal 5 of TB5.
8. Connect the normally-open dry contacts of the FSD de­vice (smoke detector with auxilary relay and/or smoke control panel dry contact set) to terminal 1 and 2 of TB5.
9. Connect the 24 vac relay coil of the FSD relay to ter­minals 1 and 8 of TB5.
10. Connect the second pole of the FSD relay to the hot leg of the return fan power supply and to terminal 11 of TB5.
Refer to Fig. 49 or 50 for point-to-point wiring of the smoke
control option inside the PIC control box.
Fig. 46 — Exhaust Damper Actuator Wiring (Smoke
Control Option or Modulating Dampers)
LEGEND
Field Wiring
EXD — Exhaust Air
Damper Actuator
54
LEGEND
OAD — Outside Air Damper RAD — Return Air Damper
NOTE: Connections for 39NX with integral PIC shown. See wiring diagrams in Fig. 9 and 12 for terminal connections in 39L control box and all remote-mount control boxes.
Actuator Actuator
Factory Wiring Field Wiring
Fig. 47 — Field-Supplied Mixing Box Actuator Signal Wiring
*Field-installed if only outside air damper is used.
LEGEND
OAD — Outside Air Damper
Actuator Field Wiring
Fig. 48 — Field-Supplied Two-Position Damper Relay and Actuator Wiring
55
LEGEND
AO Analog Output EVAC — Evacuation EXD Exhaust Air Damper Actuator FSD Fire Shut Down HOA HAND/OFF/AUTO Switch HPS High-Pressure Switch LTT Low Temperature Thermostat OAD Outside Air Damper Actuator PRES — Pressurization RAD Return Air Damper Actuator
NOTE: The return fan power circuit may be different than the supply fan starter power.
RFR Return Fan Relay SF Supply Fan Contactor SFR Supply Fan Relay TB Terminal Block TRAN — Transformer
Fig. 49 — Smoke Control Option Wiring Schematic (39L)
56
Remove Jumper Factory Wiring
Field Wiring
LEGEND
AO Analog Output EVAC — Evacuation EXD Exhaust Air Damper Actuator FSD Fire Shut Down HOA HAND/OFF/AUTO Switch HPS High-Pressure Switch LTT Low Temperature Thermostat OAD Outside Air Damper Actuator PRES — Pressurization RAD Return Air Damper Actuator
*Factory installed and wired if ordered with exhaust box. NOTE: Return fan power circuit may be different than the supply fan
starter power.
RFR Return Fan Relay SF Supply Fan Contactor SFR Supply Fan Relay TB Terminal Block TRAN — Transformer
Fig. 50 — Smoke Control Option Wiring Schematic (39NX)
57
Factory Wiring Field Wiring
ANALOG DEVICE FOR ANALOG OUTPUTTEMPERA­TURE CONTROL — The analog controlled device selected must be capable of receivinga4to20mAsignal. Its internal impedance must not exceed 600 ohms.
The power supply of the analog device must be field in-
stalled.
Using a 20 AWG twisted wire pair, wire the control signal
as follows (Fig. 51).
1. Connect the positive ( ) contact to pin 46 of the option module.
2. Connect the negative (−) contact to pin 47 of the option module.
DEVICE UNDER DISCRETE OUTPUT TEMPERATURE CONTROL—The factory-supplied SPDT relay must be field installed and wired. See Fig. 52. The relay contacts are rated as follows:
48 va at 24 vac and .25 power factor 125 va at 115 vac and .25 power factor 125 va at 230 vac and .25 power factor
The relay provides a set of contacts (normally open and nor­mally closed) using no. 6 screw terminals while the 24 vdc coil connections are through
1
⁄4-in. quick connects.
Using a 20AWG twisted cable, connect the relay coil con­tacts 1 and 2 to the option module pins 50 and 51. Connect the device to be controlled to the normally-open or normally­closed contacts of the relay. Pay close attention to the con­tact ratings listed above. See Fig. 53.
DISCRETE OUTPUT DEVICE UNDER TIMECLOCK CONTROL—The factory-supplied SPDT relay must be field installed and wired. (Fig. 52.) The relay contacts are rated as follows:
48 va at 24 vac and .25 power factor 125 va at 115 vac and .25 power factor 125 va at 230 vac and .25 power factor
The relay provides a set of contacts (normally open and nor­mally closed) using no. 6 screw terminals while the 24 vdc coil connections are through
1
⁄4-in. quick connects.
Using a 20AWG twisted cable, connect the relay coil con­tacts to the option module pins 53 and 54. Connect the de­vice to be controlled to the normally-open or normally­closed contacts of the relay.Pay close attention to the contact ratings listed above. See Fig. 54.
Field Wiring
Fig. 51 — Wiring of Analog Device for Analog Output Temperature Control
NC
SDA 2 02 0
COM
NO
1
COI L
2
Fig. 52 — Single-Pole, Double-Throw (SPDT) Relay
58
HUMIDIFICATION DEVICES Modulating Valve for Analog Output Humidity Control
(Fig. 55) — Valve selected must be able to receivea4to 20 mA signal and must NOTexceed an impedance of600 ohms. Valve power supply must be field-installed and isolated.
Install valve on humidifier piping and connect actuator power supply.Using a 20 AWG twisted wire pair, connect the posi­tive ( ) contact of the valve actuator to pin 40 of the option module. Connect the negative (−) contact of the valve ac­tuator to pin 41 of the option module.
Two-Stage Humidification Control Relays — Two SPDT relays with silver cadmium contacts are shipped with the unit when 2-stage humidification control is requested. See Fig. 52. The relays are rated as follows:
48 va at 24 vac and .25 power factor 125 va at 115 vac and .25 power factor 125 va at 230 vac and .25 power factor
The relays must be field installed within a field-supplied en­closure rated for the application.
Wire the stage 1 relay as follows: Connect the 24 vac coil contacts 1 and 2 to pins 41 and 42 of the option module. The stage 1 relay is intended to open a normally-closed steam valve and not energize the spray pump. See Fig. 56 for field wiring of the stage 1 valve and steam pump.
Wire the stage 2 relay as follows: Connect the 24 vac coil contacts 1 and 2 to pins 44 and 45 of the option module. The stage 2 relay is intended to open a second normally-closed steam valve. See Fig. 56 for field wiring of the stage 2 valve.
Duct High Humidity Switch — The humidistat is factory sup­plied and field installed. It is shipped (with a template) in its own box.
All wiring must comply with applicable local codes and ordinances. Wire the DHH as follows:
1. Turn switch on PIC control box to OFF.
Turn switch on PIC control box to OFF before con­necting DHH wiring, otherwise electrical shock or equipment damage can result.
2. Connect wire from terminal 3 of terminal block 2 (TB2)
to the terminal labeled ORANGE on the DHH sensor. See Fig. 57.
3. Connect wire from pin 7 of the option module to the sen-
sor screw terminal labelled RED.
During humidification, the duct high humidity switch must be set to the maximum humidity level desired in the supply duct (80% minimum).
Duct Mounted/Wall Mounted Relative Humidity Transmit­ter (Fig. 58) — Identify the power terminal block (ACIN) and signal terminal block (OUT). See Fig. 59 and 60. Using 20 AWG twisted wire pair, connect the 24 vac power to the terminal labeled ACIN.
Field Wiring
NOTE: The relay furnished is a SPDT relay with silver cadmium ox­ide contacts, rated as follows:
48 va at 24 vac and .25 power factor 125 va at 115 vac and .25 power factor 125 va at 230 vac and .25 power factor
Fig. 53 — Wiring of Device Under Discrete Output
Temperature Control
Field Wiring
NOTE: The relay furnished is a SPDT relay with silver cadmium ox­ide contacts, rated as follows:
48 va at 24 vac and .25 power factor 125 va at 115 vac and .25 power factor 125 va at 230 vac and .25 power factor
Fig. 54 — Wiring of Discrete Output Device
Under Timeclock Control
Field Wiring
Fig. 55 — Wiring of the Modulating Valve for
Analog Output Humidity Control
59
The 24 vac power source(s) to both duct mounted and wall mounted relative humidity transmitters MUST be isolated. Connecting either side to a ground will per­manently damage the sensor.
The power for the relative humidity transmitters may be sourced from the valve 24 vac power source at wire no. 6 and 7 or at wire no. 4 and 5.
Connect the signal wires as follows: Secure one wire to the terminal labelled OUT (located at the right of terminal block OUT). Secure the other wire to the negative signal output terminal (terminal adjacent to the terminal labelled OUT ). Run the twisted pair of signal wires to the PIC control box. Observe all local code requirements.
Outdoor Relative Humidity Transmitter: Connect the posi­tive ( ) wire to pin 31 of the processor module. Connect the negative (−) wire to pin 32 of the processor module.
Return Air or Space Relative Humidity Transmitter; Connect the positive ( ) wire to pin 10 of the processor mod­ule. Connect the negative (−) wire to pin 11 of the processor module. See Fig. 61.
Field Wiring
NOTE: The relay furnished is a SPDT relay with silver cadmium oxide contacts, rated as follows:
48 va at 24 vac and .25 power factor 125 va at 115 vac and 25 power factor 125 va at 230 vac and .25 power factor
Fig. 56 — Wiring of Two-Stage Humidification Control Relays
Field Wiring
NOTE: Connections for 39NX with integral PIC shown. See wiring diagrams in Fig. 9 and 12 for terminal connections in 39L control box and all remote-mount control boxes.
Fig. 57 — Wiring of the Duct
High Humidity Switch
Fig. 58 — Field-Installed Relative
Humidity Transmitters
60
Field Wiring
Fig. 59 — Duct Mounted Relative Humidity
Transmitter Wiring
Fig. 60 — Wall Mounted Relative Humidity
Transmitter Wiring
LEGEND
RH — Relative Humidity
Field Wiring
Fig. 61 — Wiring of Relative Humidity Transmitters
61
AIR QUALITY SENSOR — Air quality (AQ) sensors are CO2sensors shipped inside the fan section for field instal­lation. To wire the sensors after they are mounted in the con­ditioned air space and return air duct, see Fig. 62 and the instructions shipped with the sensors. For each sensor, use two 2-conductor 20 AWG twisted-pair cables (unshielded) to connect the separate 24 vac power source to the sensor and the sensor to the option module (PSIO slave) terminals. To connect each AQ sensor to the option module, identify the positive ( ) and negative (−) terminals on the sensor; connect AQ1 to terminals 25 and 26 and connect AQ2 to terminals 28 and 29.
OUTSIDE AIR VELOCITY PRESSURE (OAVP) SEN­SOR — The OAVP sensor is factory installed and wired. As shown in Fig. 62, the sensor’s power wiring is connected to TB2, 9 and 10 for 39L units or TB2, 29 and 30 for 39NX units; the signal leads are connected to terminals 31 and 32 in the option module.
FAN VOLUME CONTROL (Fig. 63) Airflow Monitoring Stations are field-selected and field-
installed in the supply and return air ducts; see Fig. 63. Install each monitoring station in a straight portion of the duct with any upstream or downstream elbows or fittings at least 2.5 diameters away.
Use approved plenum tubing to connect each monitoring station to the bulkhead fittings on top of the control box. For runs up to 50 ft, use
1
⁄4-in. OD tubing. For runs over 50 ft,
use3⁄8-in. OD tubing. DifferentialPressure Transducers for fan volume control are
factory-installed in the control box (two are supplied). The power supply for the transducers is also factory installed. Both transducers have pressure ranges of 0.0 to 1.0 in. wg and produce 2 to 10 vdc signals. See Fig. 64 for wiring details.
Note that if the velocity pressure of the supply and/or re­turn air is below 0.75 in. wg, the system may require trans­ducers with lower ranges than those of the default factory­supplied transducers. As a general rule, size transducers so that the maximum air velocity pressure is 75% of the transducer’s maximum value. For example, if the 39L or 39NX unit produces a maximum air velocity pressure of
0.15 in. wg, a transducer with a maximum value of
0.20 in. wg can be used. Sizing the transducers according to these guidelines ensures that they have good resolution.
Factory-Supplied Return Fans with Inlet Guide Vanes (IGVs) are factory wired except for the air supply control signal from the airflow monitoring stations, which is con­nected in the field to the bulkhead fitting.
Return Fans with Field-Supplied IGVActuators must be able to receivea4to20mAsignal and may NOT have an im­pedance of more than 600 ohms. An isolated power source must be field-supplied and installed. See Table 9 for recommended actuators.
To install actuators, see Fig. 65. Using a 2-conductor 20AWG conductor cable (one twisted pair, unshielded) rated for the application, connect the positive ( ) wire to terminal 37 in the option module. Connect the negative (−) wire to terminal 38. Connect the 24 vac power leads to TB2, terminals 23 and 24.
Field-Supplied Return Fans with Variable Frequency Drives must have 4 to 20 mA signal input boards and their own field-supplied and installed power sources.
To install return fans with variable frequency drives, see Fig. 66. Using a 2-conductor 20 AWG conductor cable (one twisted pair, unshielded) rated for the application, con­nect the positive ( ) signal wire to terminal 37 in the option module. Connect the negative signal (−) wire to terminal 38.
The supply fan minimum set point must be equal to the return fan minimum airflow, plus the delta airflow that is to be maintained.
LEGEND
AQ Air Quality Sensor OAVP — Outside Air Velocity Pressure Sensor
Field Wiring Factory Wiring
NOTE: See unit label diagram or Fig. 12 for remote-mount control box connections.
Fig. 62 — Air Quality and OAVP Sensor Wiring
IGV — Inlet Guide Vane
Field Wiring
NOTE: Air monitoring stations are field supplied and installed; pres­sure transducers are factory supplied and installed.
Fig. 63 — Field-Installed Fan Volume Control
62
LEGEND
RVP — Return Velocity Pressure Transducer SVP — Supply Velocity Pressure Transducer
NOTE: Connections for 39NX with integral PIC shown. See wiring diagrams in Fig. 9 and 12 for terminal connections in 39L control box and all remote-mount control boxes.
Field Tubing
Fig. 64 — Fan Volume Control — Differential Pressure Transducer (P/N HK05ZG007) Factory Wiring
Field Wiring
NOTE: Connections for 39NX with integral PIC shown. See wiring diagrams in Fig. 9 and 12 for terminal connections in 39L control box and all remote-mount control boxes.
Fig. 65 — Wiring of Return Fan Volume Control
with IGVs
Fig. 66 — Wiring of Return Fan Volume Control
with Variable Frequency Drive
63
Pulse-Type Meter (Fig. 67) — Monitors power usage, which is passed through the Carrier Comfort Network (CCN) for use by the loadshed module of the Building Supervisor. The meter must provide a dry contact signal (not exceeding 4 Hz maximum). Using a 2-conductor 20 AWG shielded twisted­pair conductor cable, connect one wire to terminal 35 of the option module and the other wire to terminal 36. Connect the drain wire to the ground lug inside the PIC control box and remove the drain wire and shield on the meter end of the cable. Tape to insulate, if required.
ELECTRIC HEATER—The electric heater is factory wired and installed and is controlled by the PIC processor and DSIO. There is no field wiring or installation required.
CARRIER COMFORT NETWORK INTERFACE — The Carrier Comfort Network (CCN) communication bus wiring is supplied and installed by the electrical contractor. It con­sists of shielded, 3-conductor cable with drain wire.
The system elements are connected to the communication bus in a daisy-chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system element on either side of it; the negative pins must be wired to the negative pins; the sig­nal ground pins must be wired to signal ground pins. See Fig. 68 for location of the CCN communication plug (COMM1) on the processor module.
NOTE: Conductors and drain wire must be 20 AWG mini­mum, stranded tinned copper.Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyeth­ylene.An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of −20 C to 60 C is required. See Table below for cables that meet the requirements.
MANUFACTURER CABLE NO.
Alpha 2413 or 5463
American A22503
Belden 8772
Columbia 02525
When connecting the CCN communication bus to a sys­tem element, a color code system for the entire network is recommended to simplify installation and checkout. The fol­lowing color code is recommended:
SIGNAL
TYPE
CCN BUS CONDUCTOR
INSULATION COLOR
COMM1 PLUG
PIN NO.
RED 1
Ground WHITE 2
BLACK 3
If a cable with a different color scheme is selected, a simi-
lar color code should be adopted for the entire network.
At each system element, the shields of its communication bus cables must be tied together. If the communication bus is entirely within one building, the resulting continuous shield must be connected to ground at only one point. See Fig. 69. If the communication bus cable exits from one building and enters another, the shields must be connected to ground at the lightning suppressor in each building where the cable enters or exits the building (one point only).
To connect the 39L or 39NX unit to the network, proceed as follows (Fig. 69):
1. Turn power to the PIC control box to OFF.
2. Remove the COMM1 plug from the processor module.
3. Cut the CCN wire and strip the ends of the RED, WHITE,
and BLACK conductors.
4. Using a wire nut, connect the 2 drain wires together.
5. Insert and secure the 2 RED wires to terminal 1 of the
COMM1 plug.
6. Insert and secure the 2 WHITE wires to terminal 2 of the
COMM1 plug.
7. Insert and secure the 2 BLACK wires to terminal 3 of the
COMM1 plug.
OUTDOOR-AIR THERMOSTAT — Use field-supplied, 2-conductor 20 AWG wire to connect the thermostat to the DSIO and terminal block in the PIC control box. See Fig. 70. Connect one wire between the thermostat and J3-1 on the DSIO. For 39NX units, connect a second wire be­tween the other thermostat terminal and TB3-9 (TB2-10 for 39L units). For 39NX units, connect a third wire between J3-2 on the DSIO and TB4-10 (TB2-9 on 39L units).
CONTROL SYSTEM
The control system consists of a processor module (Fig. 71), sensors, and controlled devices. Available options include a processor option module (Fig. 71), relay modules (Fig. 72), and local interface device.
Field Wiring
Fig. 67 — Pulse-Type Meter Wiring
Fig. 68 — CCN Sensor Plug and Communication
Plug Locations
64
Fig. 69 — CCN Communication Wiring
All system software and operating intelligence is in the processor (PSIO master) module, which controls the unit. This module monitors and controls conditions through input and output ports and through the option (PSIO slave) and relay (DSIO) modules.
The machine operator communicates with the PSIO mas­ter through the local interface device (HSIO). Communica­tions between the PSIO and other modules is accomplished by a 3-wire sensor bus that runs in parallel between mod­ules. See Fig. 73.
On the sensor bus terminal strips, terminal 1 of the PSIO module is connected to terminal 1 of each of the other mod­ules (see Fig. 73). Terminals 2 and 3 are connected in the same manner. If a terminal 2 wire is connected to terminal 1, the system does not work.
The PSIO master and slave and DSIO are all powered from a 21 vac power source connected to terminals 1 and 2 of the power input connector on each module. Refer to the 39L or 39NX unit wiring diagram for transformer locations and wiring.
Processor(PSIO Master)and Option(PSIO Slave) Modules (Fig. 71) —
tors and controls components such as the supply fan, cool­ing and heating coil valves, inlet guide vanes, and mixed-air dampers. The PSIO slave module provides additional inputs and outputs to the PSIO master for options such as return fan volume, humidifier, smoke, and air quality control. The processor and option modules are factory installed.
Each PSIO input and output channel has 3 terminals; only 2 of the terminals are used. The unit application de­termines the terminal connections. Refer to the unit wiring diagram for terminal numbers.
The PSIO address switches are factory set at address 01 (master) and 31 (slave). Use a local or remote HSIO or the CCN to change the unit address. Do NOT change the address switches on the PSIO modules.
The PSIO master module moni-
Relay (DSIO) Module (Fig. 72) — The DSIO mod-
ule provides additional inputs and outputs to the PSIO mas­ter for electric heater and direct expansion coil staging. The DSIO module is factory installed. If only one DSIO module is used for electric heat or DX cooling, the DSIO address switches are factory-set at 19. If 2 DSIO modules are used for electric heat and DX cooling, the heat module is set to address 19 and the cooling module is set to address 49. See Table 1.
The DSIO inputs on strip J3 are discrete (ON/OFF) in­puts. When 24 vac are applied across the 2 terminals, the corresponding channel reads one state. When no power is applied across the terminals, the channel reads the opposite state.
IMPORTANT: The 24 vac inputs on J3 of the DSIO module are polarized, with one side tied to earth ground. The grounded side of the signal must be connected to the even-number pins.
Terminal strips J4 and J5 are internal relays whose coils are powered on and off by a signal from the microprocessor. The relays switch the circuit to which they are connected. Only Class II power should be applied to these connections.
IMPORTANT: Use only the normally-open contacts on DSIO modules. These contacts have internal snub­bers that protect the control modules from destructive arcing produced by switching inductive loads. NEVER use the normally-closed contacts.
65
LEGEND
AHU Air Handling Unit CUST — Condensing Unit Status DSIO — Relay Module DX Direct Expansion OAT Outdoor Air Thermostat PIC Product Integrated Control
Factory Wiring Field Wiring
Fig. 70 — Outdoor Air Thermostat/DSIO Wiring
66
Local Interface Device (HSIO) (Fig. 74) — The
HSIO consists of a keyboard with 6 function keys, 5 opera­tive keys, 10 numeric keys (0-9), and an alphanumeric 8-character liquid crystal display (LCD). Key use is ex­plained in Table 10. Each function has one or more subfunc­tions as shown in Table 11. These functions are described in greater detail in the Control Operation section of this book. The HSIO can be factory-or field-installed, and can be re­motely mounted if necessary.
Table 10 — Local Interface Device Key Usage
FUNCTION
KEYS
OPERATIVE
KEYS
USE
Status — Display diagnostic codes and current operating information about the machine
Quick Test — Check inputs and outputs for proper operation
History — Check latest service dates and alarms in order of occurrence
Service — Enter specific unit configuration information
Set Point — Enter operating set points and day/time/date, holiday, and daylight savings time information
Schedule — Enter occupied/unoccupied sched­ules for unit operation
USE
Expand Display — Display a non-abbreviated expansion of the display
Clear — Clear the screen of all displays Up Arrow — Return to previous display position
Down Arrow — Advance to next display position
Enter data
Fig. 72 — Relay Module (DSIO)
Fig. 71 — Processor Module (PSIO Master/Slave)
LID — Local Interface Device
Fig. 73 — Sensor Bus Wiring (Communications)
Fig. 74 — Local Interface Device
67
Table 11 — Functions and Subfunctions
SUB-
FUNCTION
NUMBER
1 Current alarms Alarm history Occupied mode 2 Current operating 3 Current operating 4 System inputs Period 3 5 System outputs Period 4 6 Period 5 7 Period 6 8 Period 7
9 Period 8 10 Occupied mode 11 Period 1 12 Period 2 13 Period 3 14 Period 4 15 Period 5 16 Period 6 17 Period 7 18 Period 8 19 Loadshed 20 Fan tracking 21 Humidity 22 Alarms limits 23 Analog temperature 24 Discrete temperature 25 Service history 26 Service maintenance 27 Timed override
DX — Direct Expansion
Status History Schedule Service Set Point Test
override sched 1 modes set points
Maintenance history
Period 2
Period 1
of schedule 1
of schedule 1
of schedule 1
of schedule 1
of schedule 1
of schedule 1
of schedule 1
of schedule 1
override sched 2
of schedule 2
of schedule 2
of schedule 2
of schedule 2
of schedule 2
of schedule 2
of schedule 2
of schedule 2
FUNCTION
Log on and Log off
Software version
Factory configuration
English/metric system
User configuration
Heating coil configuration
Cooling coil configuration
DX cooling configuration
Inlet guide vanes configuration
Mixed-air damper configuration
Electric heat configuration
Nighttime free cooling configuration
Night purge configuration
OAVP configuration
Air quality configuration 1
Air quality configuration 2
Optimal start/stop configuration
Space temperature reset configuration
configuration configuration configuration configuration configuration configuration configuration configuration history
System set points Quick test of Demand limits Quick test of Current time Quick test of Daylight savings
time configuration Holiday
configuration ——
—— —— —— —— —— —— —— —— —— —— —— —— —— —— —— —— —— —— —— —— ——
inputs outputs electric heat
Quick test of DX cooling
Exit quick test
68
CONTROL OPERATION
Accessing Functions and Subfunctions —
See Table 12. Refer also to Table 11, which shows the 6 func­tions (identified by name) and the subfunctions (identified by number). Table13 shows the sequence of all the elements in a subfunction.
Table 12 — Accessing Functions and Subfunctions
OPERATION KEYBOARD
To access a function, press the subfunction number and the function name key. The display shows the subfunction group
To move to the other elements, scroll up or down using the arrow keys
When the last element in a subfunction has been displayed, the first element is repeated
To move to the next subfunction, it is not necessary to use the subfunction number. Pressing the function name key advances the display through all sub­functions within a function and then back to the first
Display Functions
SUMMARY DISPLAY — Whenever the keyboard has not been used for 10 minutes, the display automatically switches to an alternating summary display. This display has 3 parts (day/time, mode, and alarms), shown below, which alternate in continuously rotating sequence.
Display Expansion TUE 12:45 TODAY IS TUE, TIME IS 12:45
MODE 23 UNOCCUPIED HEATING 2 ALARMS THERE ARE 2 ALARMS DETECTED
Return to the previous display at any time by pressing
.
ENTRY
DISPLAY DESCRIPTION
SETPOINT System set points
OHSP X Occupied heating set point OCSP X Occupied cooling set point UHSP X Unoccupied heating set point UCSP X Unoccupied cooling set point
DEMAND Demand limit set points
TIME
DAYLIGHT Daylight savings time
Time of day and day of week display
To move to another function, either depress the function name key for the desired function (display shows the first subfunction)
or
Access a particular subfunction by using the subfunction number and the func­tion name key
HOLIDAY Holiday display
SETPOINT System set points
X ALARMS X alarms detected
SETPOINT Current operating set points
69
Table 13 — Keyboard Directory
STATUS
Keyboard Entry Display Description
ALARMS Current alarm display ALARM X 1st alarm ALARM X 2nd alarm ALARM X 3rd alarm ALARM X 4th alarm ALARM X 5th alarm ALARM X 6th alarm ALARM X 7th alarm ALARM X 8th alarm ALARM X 9th alarm ALARM X 10th alarm ALARM X 11th alarm ALARM X 12th alarm ALARM X 13th alarm ALARM X 14th alarm ALARM X 15th alarm ALARM X 16th alarm ALARM X 17th alarm ALARM X 18th alarm ALARM X 19th alarm ALARM X 20th alarm ALARM X 21st alarm ALARM X 22nd alarm ALARM X 23rd alarm ALARM X 24th alarm ALARM X 25th alarm ALARM X 26th alarm ALARM X 27th alarm ALARM X 28th alarm ALARM X 29th alarm ALARM X 30th alarm ALARM X 31st alarm ALARM X 32nd alarm
STATUS
Keyboard Entry Display Description
MODES Current operating modes MODE X Mode 1 MODE X Mode 2
SETPOINT Current operating set points
OHSP X Occupied heating set point OCSP X Occupied cooling set point
UHSP X Unoccupied heating set point
UCSP X Unoccupied cooling set point
SPSP X Static pressure set point
SASP X Supply air set point
CFSP X Delta CFM set point
HUSP X Humidity set point
AOSP X Analog temperature control set point DOSP X Discrete temperature control set point
Q1SP X Air quality 1 set point
Q2SP X Air quality 2 set point
OASP X
Outdoor air velocity pressure set point
70
Table 13 — Keyboard Directory (cont)
STATUS
Keyboard Entry Display Description
INPUTS System inputs
SPT X Space temperature SAT X Supply air temperature RAT X Return air temperature OAT X Outside air temperature OAT X Outside air temperature forced
SP X Static pressure
SFS X Supply fan status ENT X Enthalpy switch status ENT X Enthalpy switch status forced
RH X Relative humidity RH X Relative humidity forced
FRZ X Freezestat status MAT X Mixed air temperature
OARH X Outside air relative humidity OARH X Outside air relative humidity forced
FLTS X Filter status FLTS X Filter status forced
TEMP X Temperature input
RVP X Return velocity pressure SVP X Supply velocity pressure DHH X Duct high humidity
EVAC X Evacuation PRES X Pressurization PURG X Smoke purge
FSD X Fire shutdown
MTR X Meter OAVP X Outdoor air velocity pressure OAVP X Outdoor air velocity pressure
AQ1 X Air quality 1
AQ1 X Air quality 1
AQ2 X Air quality 2
AQ2 X Air quality 2
CUST X Condensing unit status CUST X Condensing unit status
DXSD X DX cooling shutdown DXSD X DX cooling shutdown
OUTPUTS System outputs
IGV X Inlet guide vanes
DX — Direct Expansion
(x = forced value)
(x = forced value)
(x = forced value)
(x = forced value)
(x = forced value)
(x = forced value)
(x = forced value)
(x = forced value)
(x = forced value)
(x = forced value)
STATUS
Keyboard Entry Display Description
IGV X MIXD X Mixed air damper MIXD X
HCV X Heating coil valve HCV X CCV X Cooling coil valve CCV X
SF X Supply fan start/stop
SF X HIR X Heat interlock relay HIR X
EHS1 X Electric heat stage 1 EHS2 X Electric heat stage 2 EHS3 X Electric heat stage 3 EHS4 X Electric heat stage 4 EHS5 X Electric heat stage 5 EHS6 X Electric heat stage 6 EHS7 X Electric heat stage 7
EHS8 X
RFVC X Return fan volume RFVC X HUM1 X Humidifier first stage HUM1 X HUM2 X Humidifier 2nd stage HUM2 X AOTC X Analog temperature AOTC X DOTC X Discrete temperature DOTC X DTCC X Discrete time clock DTCC X DXS1 X DX cooling stage 1
DXS2 X DX cooling stage 2 DXS3 X DX cooling stage 3 DXS4 X DX cooling stage 4 DXS5 X DX cooling stage 5 DXS6 X DX cooling stage 6 DXS7 X DX cooling stage 7 DXS8 X DX cooling stage 8
Inlet guide vanes forced (x = forced value)
Mixed air damper forced (x = forced value)
Heating coil valve forced (x = forced value)
Cooling coil valve forced (x = forced value)
Supply fan start/stop forced (x = forced value)
Heat interlock relay forced (x = forced value)
Electric heat stage 8 (NOTE: Only the actual number of heater stages applicable to the unit are provided.)
Return fan volume forced (x = forced value)
Humidifier first stage forced (x = forced value)
Humidifier 2nd stage forced (x = forced value)
Analog temperature forced (x = forced value)
Discrete temperature forced (x = forced value)
Discrete time clock forced (x = forced value)
71
Table 13 — Keyboard Directory (cont)
SCHEDULE
Keyboard Entry Display Description
OVRD X Number of hours to extend
PERIOD 1 Define period 1 of time
OCC X Start of occupied time UNO X Start of unoccupied time MON X Monday flag (x = entry code)
TUE X Tuesday flag (x = entry code)
WED X Wednesday flag (x = entry code)
THU X Thursday flag (x = entry code)
FRI X Friday flag (x = entry code)
SAT X Saturday flag (x = entry code)
SUN X Sunday flag HOL X Holiday flag
OVRD X Number of hours to extend
PERIOD 1 Define period 1 of time
OCC X Start of occupied time UNO X Start of unoccupied time MON X Monday flag (x = entry code)
TUE X Tuesday flag (x = entry code)
WED X Wednesday flag (x = entry code)
THU X Thursday flag (x = entry code)
FRI X Friday flag (x = entry code)
SAT X Saturday flag (x = entry code)
SUN X Sunday flag HOL X Holiday flag
CV Constant Volume DX Direct Expansion VAV — Variable Air Volume
(same elements as period 1, schedule 1)
(same elements as period 1, schedule 2)
occupied mode of schedule 1
schedule 1
(1 = yes, .0 or CLR = no)
(1 = yes, .0 or CLR = no)
(1 = yes, .0 or CLR = no)
(1 = yes, .0 or CLR = no)
(1 = yes, .0 or CLR = no)
(1 = yes, .0 or CLR = no)
Time periods 2-8 of schedule 1
occupied mode of schedule 2
schedule 2
(1 = yes, .0 or CLR = no)
(1 = yes, .0 or CLR = no)
(1 = yes, .0 or CLR = no)
(1 = yes, .0 or CLR = no)
(1 = yes, .0 or CLR = no)
(1 = yes, .0 or CLR = no)
Time periods 2-8 of schedule 2
SERVICE CONFIGURATIONS
Keyboard Entry Display Description
LOG ON Enter password to log on LOGGEDON Log on okay
When finished with configuration, log off as follows:
LOGGEDON LOG OFF LOGD OFF
VERSION Software version XXX-XX-X Software version number
FACT CFG Factory configuration TYPE X Unit type (0 = CV,1=VAV) COOL X Cooling (0 = none, 1 = coil) DXST X
HEAT X
EHST X MIXD X IAQT X Indoor-air quality type
MATP X Mixed air temperature protection BUS X ADR X PSW X Password XXXX
UNITS X
USER CFG User configuration NTEN X HUEN X Humidity configuration OHEN X Occupied heating configuration RSEN X DLEN X Demand limiting configuration FTEN X Fan tracking configuration OAEN X Constant outside air NPEN X Night purge AQEN X Indoor air quality IAQP X Indoor air quality priority level OSEN X Optimal start/stop configuration TSCH X Timed override schedules TOVR X Timed override values
HEATCOIL Configuration of heating coil MPG X Master proportional gain MIG X Master integral gain MDG X Master derivative gain SMG X Submaster gain SCV X Submaster center value FOV X Fan off value SMR X Submaster reference value SMR X Submaster reference value forced
Shows that configurations are available
Log off okay; configurations again password protected
DX cooling stages 0-8 (enter number)
Heating (0 = none, 1 = hot/steam, 2 = electric heat coil)
Electric heat stages 0-8 (enter number)
Mixed air damper (0 = none, 1 = yes, 2 = 2-position)
Bus number (factory default set=0)
Element address (factory set default = 1)
English/metric system (0 = English, 1 = metric)
Nighttime free cooling configuration
Space temperature reset configuration
72
Table 13 — Keyboard Directory (cont)
SERVICE CONFIGURATIONS
Keyboard Entry Display Description
COOLCOIL MPG X Master proportional gain MIG X Master integral gain MDG X Master derivative gain SMG X Submaster gain SCV X Submaster center value HHL X High humidity limit SMR X Submaster reference value SMR X Submaster reference value forced
DXCOOL Configure DX cooling SMG X Submaster gain SMG X Submaster gain forced MSR X Minimum submaster reference DX1G X Stage 1 Time GuardT device DX2G X Stage 2 Time Guard DX3G X Stage 3 Time Guard DX4G X Stage 4 Time Guard DX5G X Stage 5 Time Guard DX6G X Stage 6 Time Guard DX7G X Stage 7 Time Guard DX8G X Stage 8 Time Guard DX1T X Stage 1 logic type DX2T X Stage 2 logic type DX3T X Stage 3 logic type DX4T X Stage 4 logic type DX5T X Stage 5 logic type DX6T X Stage 6 logic type DX7T X Stage 7 logic type DX8T X Stage 8 logic type
INLET GV Configuration of inlet guide vanes MPG X Master proportional gain MIG X Master integral gain MDG X Master derivative gain SMG X Submaster gain SCV X Submaster center value SMR X Submaster reference value SMR X Submaster reference value forced
DX Direct Expansion OAVP — Outside Air Velocity Pressure
Configuration of cooling (chilled water coil or DX)
SERVICE CONFIGURATIONS
Keyboard Entry Display Description
MIXADMPR Configuration of mixed air damper MPG X Master proportional gain
MIG X Master integral gain MDG X Master derivative gain SMG X Submaster gain SCV X Submaster center value MDP X Minimum damper position SMR X Submaster reference value SMR X Submaster reference value forced DPSP X Damper set point DPSP X Damper set point forced OAE X Outside air enthalpy RAE X Return air enthalpy CNTRL X Damper controlled by
ELECHEAT Configuration of electric heat MPG X Master proportional gain
MIG X Master integral gain MDG X Master derivative gain SMG X Submaster gain SMR X Submaster reference value SMR X Submaster reference value forced
NTFC
NTLO X
NPURGE Configuration of night purge NPMN X Night purge duration
NPDL X NPDH X MDP X Minimum damper position
OAC
MPG X Master proportional gain MIG X Master integral gain MDG X Master derivative gain SMG X Submaster gain SMG X Submaster gain forced OALV X OAVP sensor low voltage point OAHV X OAVP sensor high voltage point OALR X OAVP sensor low voltage reference OAHR X OAVP sensor high voltage reference PMF X OAVP sensor probe multiplier factor MDP X Minimum damper position SMR X Submaster reference value SMR X Submaster reference value forced
Configuration of nighttime free cooling (NTFC) NTFC lockout temperature (minimum outside air temperature to operate NTFC)
Night purge low temperature damper position
Night purge high temperature damper position
Configuration of constant outside air
73
Table 13 — Keyboard Directory (cont)
SERVICE CONFIGURATIONS
Keyboard Entry Display Description
AIRQUAL1
MPG X Master proportional gain MIG X Master integral gain XDP X Maximum damper position Q1LV X Q1HV X Q1LR X Q1HR X MDP X Minimum damper position
AIRQUAL2
MPG X Master proportional gain MIG X Master integral gain XDP X Maximum damper position Q2LV X Air quality sensor 2 low voltage point Q2HV X Air quality sensor 2 high voltage point Q2LR X Air quality sensor 2 low voltage reference Q2HR X Air quality sensor 2 high voltage reference MDP X Minimum damper position
AOSS X Configuration of optimal start/stop BLDF X Building factor UOCF X 24 hour occupied factor SETB X Set point bias OSMT X Maximum allowable stop time
SPRESET Configuration of space temperature reset RTIO X Reset ratio X LIMT X Reset limit X
LOADSHED Configuration of loadshed LSGP X Loadshed group number (1-16)
FANTRACK Configuration of fan tracking SVUL X Supply velocity upper limit RVUL X Return velocity upper limit SDAR X Supply duct area RDAR X Return duct area MPG X Master proportional gain MIG X Master integral gain MDG X Master derivative gain SMG X Submaster gain SCV X Submaster center value SMR X Submaster reference value
SMR X Submaster reference value forced
Configuration of indoor air quality and AQ sensor no. 1
Air quality sensor 1 low voltage point
Air quality sensor 1 high voltage point
Air quality sensor 1 low voltage reference
Air quality sensor 1 high voltage reference
Configuration of indoor air quality and AQ sensor no. 2
SERVICE CONFIGURATIONS
Keyboard Entry Display Description
HUMIDITY Configuration of humidity MPG X Master proportional gain MIG X Master integral gain MDG X Master derivative gain SMG X Submaster gain SCV X Submaster center value SMR X Submaster reference value
SMR X Submaster reference value forced
ALRMLIMT Configuration of alarm limits SPLO X SPHO X SPLU X SPHU X SALO X SAHO X SALU X SAHU X RALO X RAHO X RALU X RAHU X TLO X THO X TLU X THU X OATL X Outside air temperature low alarm limit OATH X Outside air temperature high alarm limit MATL X Mixed air temperature low alarm limit MATH X Mixed air temperature high alarm limit RHL X Relative humidity low alarm limit RHH X Relative humidity high alarm limit ORHL X ORHH X SPL X Static pressure low alarm limit SPH X Static pressure high alarm limit SVPL X Supply velocity pressure low alarm limit SVPH X Supply velocity pressure high alarm limit RVPL X Return velocity pressure low alarm limit RVPH X Return velocity pressure high alarm limit CFML X Delta CFM x 100 low alarm limit CFMH X Delta CFM x 100 high alarm limit Q1H X Air quality sensor 1 high alarm limit Q2H X Air quality sensor 2 high alarm limit
Space temperature low alarm limit/ occupied
Space temperature high alarm limit/ occupied
Space temperature low alarm limit/ unoccupied
Space temperature high alarm limit/ unoccupied
Supply air temperature low alarm limit/ occupied
Supply air temperature high alarm limit/ occupied
Supply air temperature low alarm limit/ unoccupied
Supply air temperature high alarm limit/ unoccupied
Return air temperature low alarm limit/ occupied
Return air temperature high alarm limit/ occupied
Return air temperature low alarm limit/ unoccupied
Return air temperature high alarm limit/ unoccupied
Temperature input low alarm limit/ occupied
Temperature input high alarm limit/ occupied
Temperature input low alarm limit/ unoccupied
Temperature input high alarm limit/ unoccupied
Outside air relative humidity low alarm limit
Outside air relative humidity high alarm limit
74
Table 13 — Keyboard Directory (cont)
SERVICE CONFIGURATIONS
Keyboard Entry Display Description
AO CTRL MPG X Master proportional gain
MIG X Master integral gain MDG X Master derivative gain SMG X Submaster gain SCV X Submaster center value FOV X Fan off value SEN X Controlling temperature sensor SMR X Submaster reference value SMR X Submaster reference value forced
DO CTRL Configuration of discrete output control SEN X Controlling temperature sensor TYP X Discrete output logic type HYS X Hysteresis
SERVHIST Service history SDAY X Number of starts in the last 24 hours STX Total number of starts FH X Total number of fan run hours DOW HH:MM Day of week and time of the last Start DOW HH:MM Day of week and time of the last Stop
SRV/MTN SMAL X
SMEH X
OVRDHIST History of timed overrides OHR X Hours of timed overrides
Configuration of analog temperature/ preheat coil control
Configuration of service/maintenance alarms
Service/maintenance alarm limit (hours x 1000)
Service/maintenance elapsed hours (hours x 1000)
SET POINT
Keyboard Entry Display Description
SETPOINT System set points OHSP X Occupied heating set point OCSP X Occupied cooling set point UHSP X Unoccupied heating set point UCSP X Unoccupied cooling set point SPSP X Static pressure set point SASP X Supply air set point CFSP X Delta CFM set point HUSP X Humidity set point AOSP X Analog temperature control set point DOSP X Discrete temperature control set point Q1SP X Air quality 1 set point Q2SP X Air quality 2 set point OVSP X Outside air velocity pressure set point
DEMAND Demand limit set points DL1 X Demand limit set point 1 DL2 X Demand limit set point 2
TIME Configuration of current time and date DAY.HH.MM Current day of the week and time MM.DD.YY Current date
DAYLIGHT Configuration of daylight savings time ENM X Daylight savings time starts—month END X Daylight savings time starts—day ENT X Daylight savings time starts—time LVM X Daylight savings time ends—month LVD X Daylight savings time ends—day LVT X Daylight savings time ends—time
HOLIDAY Configuration of holidays MM.DD.DUR MM.DD.DUR MM.DD.DUR MM.DD.DUR MM.DD.DUR MM.DD.DUR MM.DD.DUR MM.DD.DUR MM.DD.DUR MM.DD.DUR MM.DD.DUR MM.DD.DUR MM.DD.DUR MM.DD.DUR MM.DD.DUR MM.DD.DUR MM.DD.DUR MM.DD.DUR
Holiday month, day & duration (days long) Holiday month, day & duration (days long) Holiday month, day & duration (days long) Holiday month, day & duration (days long) Holiday month, day & duration (days long) Holiday month, day & duration (days long) Holiday month, day & duration (days long) Holiday month, day & duration (days long) Holiday month, day & duration (days long) Holiday month, day & duration (days long) Holiday month, day & duration (days long) Holiday month, day & duration (days long) Holiday month, day & duration (days long) Holiday month, day & duration (days long) Holiday month, day & duration (days long) Holiday month, day & duration (days long) Holiday month, day & duration (days long) Holiday month, day & duration (days long)
75
Table 13 — Keyboard Directory (cont)
QUICK TEST
Keyboard Entry Display Description
INPUTS Factory/field test of inputs SAT X Supply air temperature OAT X Outside air temperature SPT X Space temperature RAT X Return air temperature ENT X Enthalpy switch status SFS X Airflow switch status FRZ X Freezestat SP X Static pressure RH X Return air relative humidity MAT X Mixed air temperature OARM X Outside air relative humidity FLTS X Filter status TEMP X Temperature input RVP X Return velocity pressure SVP X Supply velocity pressure DHH X Duct high humidity EVAC X Evacuation PRES X Pressurization PURG X Smoke purge FSD X Fire shutdown MTR X Wattmeter OAVP X Outside air velocity pressure AQ1 X Air quality 1 AQ2 X Air quality 2 CUST X Condensing unit status DXSD X DX cooling shutdown
QUICK TEST
Keyboard Entry Display Description
OUTPUTS Factory/field test of outputs HCV X Entering heating coil valve test HCV TEST Testing heating coil valve CCV X Entering cooling coil valve test CCV TEST Testing cooling coil valve MIXD X Entering mixed air damper test MIXD TEST Testing mixed air dampers IGV X Entering inlet guide vanes test IGV TEST Testing inlet guide vanes SF X Entering supply fan test FAN TEST Testing supply fan HIR X Entering heat interlock relay test HIR TEST Testing heating interlock relay RFVC X Entering return fan volume test RFVCTEST Testing return fan volume HUM1 X Entering humidifer stage 1 test HUM1TEST Testing humidifer stage 1 HUM2 X Entering humidifier stage 2 test HUM2TEST Testing humidifier stage 2 AOTC X AOTCTEST DOTC X DOTCTEST DTCC X DTCCTEST
Entering analog temperature control output test
Testing analog temperature control output
Entering discrete temperature control output test
Testing discrete temperature control output
Entering discrete time clock control output test
Testing discrete time clock control output
DX — Direct Expansion
76
Table 13 — Keyboard Directory (cont)
QUICK TEST
Keyboard Entry Display Description
ELE HEAT Factory/field test of electric heat EHS1 X Stage 1 test STG1 TST Testing of electric heat stage 1 EHS2 X Stage 2 test STG2 TST Testing of electric heat stage 2 EHS3 X Stage 3 test STG3 TST Testing of electric heat stage 3 EHS4 X Stage 4 test STG4 TST Testing of electric heat stage 4 EHS5 X Stage 5 test STG5 TST Testing of electric heat stage 5 EHS6 X Stage 6 test STG6 TST Testing of electric heat stage 6 EHS7 X Stage 7 test STG7 TST Testing of electric heat stage 7 EHS8 X Stage 8 test STG8 TST Testing of electric heat stage 8
HISTORY
Keyboard Entry Display Description
ALARMHST Alarm history ALARM X Latest alarm ALARM X Previous alarm ALARM X Previous alarm ALARM X Previous alarm ALARM X Previous alarm ALARM X Previous alarm ALARM X Previous alarm ALARM X Previous alarm ALARM X Previous alarm
MTMN/HIS Maintenance history MM.DD.YY Latest service date
DXCOOL Factory/field test of DX cooling DXS1 X Stage 1 test STG1TEST Testing DX cooling stage 1 DXS2 X Stage 2 test STG2TEST Testing DX cooling stage 2 DXS 3 X Stage 3 test STG3TEST Testing DX cooling stage 3 DXS4 X Stage 4 test STG4TEST Testing DX cooling stage 4 DXS5 X Stage 5 test STG5TEST Testing DX cooling stage 5 DXS6 X Stage 6 test STG6TEST Testing DX cooling stage 6 DXS7 X Stage 7 test STG7TEST Testing DX cooling stage 7 DXS8 X Stage 8 test STG8TEST Testing DX cooling stage 8
EXIT TEST Exit quick test TST CMPL Test completed
DX — Direct Expansion
77
STATUS FUNCTION — The status function shows the cur­rent status of alarm (diagnostic) codes, operating modes, set points, all measured system temperatures, output values, and input values. These subfunctions are defined on pages 78-80. Refer to Table 11 for additional information.
(Alarms) — Alarms are messages that one or more
faults have been detected. Each fault is assigned a code num­ber which is reported with the alarm. (See Table 14 for code definitions.) The codes indicate failures that cause the unit to shut down, terminate an option (such as reset), or result in the use of a default value as the set point.
Up to 32 alarm codes can be stored at once. To view
them in numerical sequence, press to enter the alarm display and then press to move to the individual
alarm displays. Press after a code has been displayed and the meaning of the code will scroll across the screen.
See Example 1.
If an input or output point which has generated an alarm resets (returns to a range within its limits), the alarm code is deleted from the list.
A historical sequence of the last 9 alarms can be found using the key. See Display Functions, History Func-
tion section for more details.
-----------------------------------------------­(Modes) — The operating mode codes are dis-
played to indicate the current operating status of the unit. (See Table 14)
To enter the MODES subfunction, press and use the key to determine if more than one mode applies.
See Example 2 to read current mode with expansion.
Example 1 — Reading Alarm Codes
KEYBOARD
ENTRY
DISPLAY
RESPONSE
TUE 12:45 MODE 23 3 ALARMS
3 ALARMS 3 alarms detected ALARM 71 First alarm code
SPACE TEMPERATURE
LOW LIMIT ALARM 76 Second alarm code
RETURN AIR TEMPERATURE
HIGH LIMIT ALARM 83 Third alarm code
RELATIVE HUMIDITY LOW LIMIT
Keyboard has not been used for at least 10 minutes; alternating summary display appears on screen
Explanation of alarm code
Explanation of alarm code
Explanation of alarm code
COMMENTS
The modes are explained below: Temperature Reset (21) — Indicates that the unit is using
temperature reset to adjust the supply-air set point. The set point is modified based on space temperature (VAV units only). Unit must be configured for space temperature
reset ( ). (This mode is enabled by .) Demand Limit (22) — On CV (constant volume) units, this
mode indicates that the fan is being held off by the De­mand Limit option. On VAV units, it indicates that the max­imum IGV position is being limited by the Demand Limit option. Units must be configured for demand limiting
( ). This mode is enabled by , and is only available on units connected to the Carrier Comfort
Network (CCN). Unoccupied Heating (23) — Indicates that the space tem-
perature is below the Unoccupied Heating set point and the unit is on. When the space temperature rises above the set point the unit is turned off.
Unoccupied Cooling (24) — Indicates that the space tem­perature is above the Unoccupied Cooling set point and the unit is on. When the space temperature falls below the set point the unit is turned off.
Optimal Start (26) — Indicates that the unit is operating in the Optimal Start mode and is trying to achieve the Occupied set point. On VAV units this is referred to as morn­ing warm-up. Unit must be configured for optimal start
( ). This mode is enabled by .) Unoccupied Mode (27) — Indicates that the unit is in the
Unoccupied mode as determined by its time schedule. In this mode the unit is turned off.
Optimal Stop (29) — Indicates that the unit is being con­trolled to its expanded Occupied set points. The space tem­perature is allowed to drift to its expanded Occupied set points during the last portion of the Occupied period.
Unit must be configured for Optimal Start ( ). Optimal Stop mode is only applicable to CV units.
Occupied Heating (30) — Indicates that the unit is in the Heating mode to satisfy its Occupied Heating set point.
Units must be configured for Occupied Heating
().
Occupied Heating is available on VAV units only.
Example 2 — Reading Current Operating Modes
KEYBOARD
ENTRY
DISPLAY
RESPONSE
TUE 12:45 MODE 31
MODE MODE 31 Mode 31 is in effect OCCUPIED COOLING Explanation of code 31
COMMENTS
Keyboard has not been used for at least 10 min­utes; alternating summary display appears on screen.
Modes subfunction of status function
MODE 22 Mode 22 is in effect DEMAND LIMIT Explanation of code 22
NOTE: The first mode is the primary operating mode. The second mode is the secondary operating mode, if applicable.
78
Occupied Cooling (31) — Indicates that the unit is in the Cooling mode to satisfy its Occupied Cooling set point.
Occupied Fan Only (32) — Indicates that the unit is main­taining set point by using a mixture of outside and return air only. No mechanical heating or cooling is being used.
Nighttime Free Cooling (33) — Indicates that the supply fan is on and using outside air to precool the space served by the unit. Unit must be configured for nighttime free cool-
ing ( ). (This mode is enabled by .) Smoke Pressurization (34) — Indicates that the unit is in the
Pressurization mode. This mode is issued from the fire system panel. Refer to Table 15 for the state of the items controlled.
Smoke Evacuation (35) — Indicates that the unit is in the Smoke Evacuation mode. This mode is issued from the system panel. Refer to Table 15 for the state of the items controlled.
Smoke Purge (36) — Indicates that the unit is in the Smoke Purge mode. This mode is issued from the fire system panel. Refer to Table 15 for the state of the items controlled.
Fire Shutdown (37) — Indicates that the unit is in the Fire Shutdown mode. This mode is issued from the fire system panel or local smoke detector. Refer to Table 15 for the state of the items controlled.
Quick Test (38) — Indicates that the unit is in the Quick Test mode. It allows the user to test all inputs and outputs con­nected to the PIC controller. All control routines are deac­tivated when the unit is in this mode. This mode can only be initiated manually when the supply fan status is OFF. (HOA switch is in OFF position.) In order to reactivate all
the configured control routines, press and then press
.
Timed Override (39) — Indicates that the unit operation has been extended by the user. Unit must be configured for
TimedOverride schedule and timed override hours ( ).
Table 14 — Display Codes
FORCE STATES
Display Description
1 Fire mode force 2 Internal safety force 3 Quick Test/Service tool force 4 HSIO/Building Supervisor force 5 Remote Building Supervisor force 6 Loadshed minimum offtime force 7 Data transfer force 8 BEST (Building Environmental Systems
Translator) force
9 Temperature override force
10 Loadshed force
OPERATING MODES
Display Description
21 Temperature Reset in effect 22 Demand Limit in effect 23 Unoccupied Heating mode 24 Unoccupied Cooling mode 26 Optimal Start mode 27 Unoccupied mode 29 Optimal Stop mode 30 Occupied Heating mode 31 Occupied Cooling mode 32 Occupied Fan Only mode 33 Nighttime Free Cooling mode 34 Pressurization mode 35 Evacuation mode 36 Smoke Purge mode 37 Fire Shutdown mode 38 Quick Test mode 39 Timed Override mode
ALARMS
Display Description
60 Air quality 1 high limit 61 Air quality 2 high limit 62 Air quality/constant outside air suspended 63 (Not used) 64 DX cooling shutdown 65 Pressurization 66 Evacuation 67 Smoke purge 68 Fire shutdown 69 Service/maintenance required 70 Linkage failure 71 Space temperature low limit 72 Space temperature high limit 73 Supply-air temperature low limit 74 Supply-air temperature high limit 75 Return-air temperature low limit 76 Return-air temperature high limit 77 Mixed-air temperature low limit 78 Mixed-air temperature high limit 79 Outside-air temperature low limit 80 Outside-air temperature high limit 81 Static pressure low limit 82 Static pressure high limit 83 Relative humidity low limit 84 Relative humidity high limit 85 Fan status 86 Freezestat 87 Analog temperature control sensor low limit 88 Analog temperature control sensor high limit 89 Outside-air relative humidity low limit 90 Outside-air relative humidity high limit 91 Supply velocity pressure low limit 92 Supply velocity pressure high limit 93 Return velocity pressure low limit 94 Return velocity pressure high limit 95 Delta CCFM low limit 96 Delta CCFM high limit 97 Filter status 98 Duct high humidity
CCFM — Cfm x 100
79
Table 15 — State of Items Controlled
MODE (DISPLAY
CODE)
Pressurization (34) Off On Open Close Close Open to
Purge (36) On On Open Close Open Open to
Evacuation (35) On Off Close Close Open Close Open Off Off Fire Shutdown (37) Off Off Close Open Close Close Close Off Off
(Set point) — This subfunction displays the current
operating system set points.
To view set points, depress , then use the key
to display the occupied heat set point. Continue to depress
to display all the various system set points. Table 13
shows the order of the various set points.
------------------------------------------------
RETURN
FAN
SUPPLY
FAN
OUTDOOR-
AIR
DAMPER
RETURN-
AIR
DAMPER
EXHAUST
DAMPER
------------------------------------------------
SUPPLY FAN
INLET GUIDE
VANES (IGV)
Static Pressure
Set Point
Static Pressure
Set point
RETURN FAN IGV
Close On Off
Open to
B D cfm
HEAT
INTERLOCK
RELAY
On Off
ELECTRIC HEAT ALL
STAGES
(Outputs) — The output subfunction displays or
forces the output value percentage of the inlet guide vanes, mixed air damper and heating and cooling valves. It also displays or forces the ON/OFF status of the supply fan and heat interlock relay,displays the status of electric heat stages, and displays optional output status for return fan volume con­trol, analog output temperature control, discrete output tem­perature control, discrete output time clock, and humidifier
(Inputs) — The inputs subfunction displays the read-
ings at the various temperature sensors, fan status, static pres­sure sensors, enthalpy switch, and freezestat. It also allows the outside-air temperature sensor, enthalpy switch, return­air relative humidity sensor, outside-air relative hu­midity sensor, and filter status to be forced to a user deter-
stages.
To read a system output value, enter , then scroll
to the desired output using the key. To force a system output value, see Example 4. Table 13 shows the order of
the output values.
mined value or status. The forced value overrides the value that the control system actually reads. This permits opera­tion in the event of a faulty sensor.
To read a sensor, enter , then scroll to the de-
sired sensor reading using the key. To force an input, see Example 3. Table 13 shows the order of the readouts.
Example 3 — Forcing An Input Value
KEYBOARD
ENTRY
8 0
DISPLAY
RESPONSE
INPUTS System inputs
Scroll past:
SPT X Space temperature SAT X Supply air temperature RT X Return air temperature MAT X Mixed air temperature OAT 60 Outside air temperature
Outside air temperature value
OAT 80/FORCED
OAT 60
forced to 80. NOTE: Forced value toggles between value and word forced
Outside air temperature forced value removed. Display no longer flashes
COMMENTS
Example 4 — Forcing An Output Value
KEYBOARD
ENTRY
DISPLAY
RESPONSE
OUTPUTS System Outputs
Scroll past:
IGV X Inlet guide vanes MIXD X Mixed air damper HCV X Heating coil valve CCV X Cooling coil valve SF OFF Supply fan off
Supply fan forced ON.
SF ON/FORCED
SF OFF
NOTE: Supply fan forced value toggles between value (SF ON) and word FORCED
Supply fan forced value re­moved. Display no longer flashes
COMMENTS
HISTORY FUNCTION
— Displays the 9 latest alarms generated by the
unit in the order of their occurrence. If 9 alarms are dis­played, the occurrence of a 10th alarm shifts the first alarm off the display.
------------------------------------------------
80
— Displays the latest service date on the local in-
terface device. The last 2 service dates are displayed at the Building Supervisor.
TEST FUNCTION — The test function operates the Quick Test diagnostic program.
— Displays the status of all inputs.
-----------------------------------------------­— Tests the outputs.
-----------------------------------------------­— Tests the electric heaters. Unit must be config-
ured for electric heat to access this subfunction. See Example 5.
-----------------------------------------------­— Tests the stages of direct expansion (DX) cool-
ing. Unit must be configured for DX cooling to access this subfunction.
-----------------------------------------------­— Takes the unit out of Quick Test.
------------------------------------------------
NOTE: The unit must not be operating during the Quick Test function. Set HOA switch to OFF and follow the test pro­cedure. Set HOA switch to AUTO only as required during testing.
To reach a particular test, enter its subfunction number
and then scroll to the desired test by pressing . A test can be terminated by pressing ; pressing after a test
has started terminates the current test and advances the sys­tem to the next test. Once in the next step, you may start
the test by pressing , advance past it by pressing , or back up by pressing . When testing is complete, exit the
Quick Test by pressing and then ; this MUST be done to restore the unit software to automatic control.
If the keyboard is not used for 10 minutes, the display
returns to the rotating default display. Press and
to exit Quick Test and then press to restart the test
procedure.
Example 5 — Using Quick Test
KEYBOARD
ENTRY
DISPLAY
RESPONSE
ELEC HT EHS1 Stage 1 test
STG1 TST Pressing ENTR starts the fan test.
EHS2 Pressing the down arrow key
EXIT TST If no other test is desired, exit Quick
TST CMPL
Factory test of electric heat subfunction of test function
Fan automatically starts. There is an 11-second delay while the inlet guide vanes open and the heat stage is enabled. When the electric heat stage should be running, the display shows EHS ON. Test remains on until another key is pressed
advances the system to stage 2 test. Any stage may be selected. Press
the key until the desired stage is displayed, then press ENTR to start
the test Test. Fan shuts off, last electric heat
stage shuts off, and IGVs close Test is completed. Unit resumes
automatic control
COMMENTS
Programming Functions
SERVICE FUNCTION — The service function allows the operator to verify or change factory and field configu­rations. The service subfunctions are listed below. (See T able13 for details.) Refer to T able16 for configuration value ranges and defaults.
— Use this subfunction to log on before perform-
ing any subfunction in Factory Configurations ( ), and to log off after completing service subfunctions. See
Example 6.
Example 6 — Logging On and Logging Off
Service Function
KEYBOARD
ENTRY
TO LOG ON:
TO LOG OFF:
DISPLAY
RESPONSE
LOG ON LOGGEDON
LOG OFF Ready for operator to log off LOGD OFF
COMMENTS
Ready for password to be entered
Operator can now use service functions
Logged off — password protection enabled
81
Table 16 — Service Configuration Ranges and Defaults
SERVICE
SUBFUNCTION
NUMBER
3
4 English/Metric System (0 = English, 1 = Metric) 0/1 0
5
6
7
8
9
10
11
12 NTFC Lock Out Temperature (F) 40 to 70 50
LEGEND
CV Constant Volume DX Direct Expansion NTFC — Nighttime Free Cooling VAV VariableAir Volume
*Value varies and is automatically calculated by the control. Override this feature by forcing the value.
Unit Type (0 = CV, 1 = VAV) 0/1 0 Cooling Type (0 = none, 1 = chilled water coil,2=DX) 0to2 1 DX Cooling Stages 0 to 8 2 Heating Type (0 = none, 1 = hot water/steam coil, 2 = electric heater) Electric Heater Stages 0 to 8 0 Mixed Air Dampers (0 = none, 1 = analog, 2 = 2-position) Indoor-Air Quality Type (1 = single gas, 2 = differen ial/2 gases) 1/2 1 Mixed-Air Temperature Protection Yes/No Yes Bus Number 0 to 239 0 Element Address 0 to 239 1 Password 0 to 9999 1111
Nighttime Free Cooling Enabled/Disabled Disabled Humidity Control (0 = none, 1 = analog, 2 = discrete) 0 to 2 0 Occupied Heating Enabled/Disabled Disabled Space Temperature Reset Enabled/Disabled Disabled Demand Limit Enabled/Disabled Disabled Fan Tracking Enabled/Disabled Disabled Constant Outside Air Enabled/Disabled Disabled Night Purge Enabled/Disabled Disabled Indoor Air Quality Enabled/Disabled Disabled Indoor Air Quality Priority Level (high = 1, low = 2, none = 3) 1 to 3 2 Adaptive Optimal Start/Stop Enabled/Disabled Disabled Timed Override Schedules 1 to 3 1 (1 = Time schedule no. 1, 2 = Time schedule no. 2, 3 = Both) Timed Override Hours 0 to 4 0
Heating Coil Master Proportional Gain 0 to 20.0 8 0 Heating Coil Master Integral Gain 0 to 2.0 0 3 Heating Coil Master Derivative Gain 0 to 20.0 0 0 Heating Coil Submaster Gain −20 0 to 20.0 −7.5 Heating Coil Submaster Center Value (%) 0 to 100 50 Heating Coil Fan ‘‘Off’’ Value (F) 35 to 65 40
Cooling Master Proportional Gain 0 to 20.0 8 0 Cooling Master Integral Gain 0 to 2.0 0 3 Cooling Master Derivative Gain 0 to 20.0 0 0 Cooling Coil Submaster Gain −20 0 to 20.0 −7.5 Cooling Coil Submaster Center Value (%) 0 to 100 80 Cooling High Humidity Limit (%) 0 to 99 99
DX Cooling Submaster Gain 2.0 to 25.0 * DX Cooling Minimum Submaster Reference 0 to 60 40 DX Cooling Stage 1 Time Guard Device (0 = disabled, 1 = enabled) DX Cooling Stage 2 Time Guard (0 = disabled, 1 = enabled) Enabled/Disabled Enabled DX Cooling Stage 3 Time Guard (0 = disabled, 1 = enabled) Enabled/Disabled Enabled DX Cooling Stage 4 Time Guard (0 = disabled, 1 = enabled) Enabled/Disabled Enabled DX Cooling Stage 5 Time Guard (0 = disabled, 1 = enabled) Enabled/Disabled Enabled DX Cooling Stage 6 Time Guard (0 = disabled, 1 = enabled) Enabled/Disabled Enabled DX Cooling Stage 7 Time Guard (0 = disabled, 1 = enabled) Enabled/Disabled Enabled DX Cooling Stage 8 Time Guard (0 = disabled, 1 = enabled) Enabled/Disabled Enabled DX Cooling Stage 1 Logic Type (0 = normal, 1 = inverted) Normal/Inverted Normal DX Cooling Stage 2 Logic Type (0 = normal, 1 = inverted) Normal/Inverted Normal DX Cooling Stage 3 Logic Type (0 = normal, 1 = inverted) Normal/Inverted Normal DX Cooling Stage 4 Logic Type (0 = normal, 1 = inverted) Normal/Inverted Normal DX Cooling Stage 5 Logic Type (0 = normal, 1 = inverted) Normal/Inverted Normal DX Cooling Stage 6 Logic Type (0 = normal, 1 = inverted) Normal/Inverted Normal DX Cooling Stage 7 Logic Type (0 = normal, 1 = inverted) Normal/Inverted Normal DX Cooling Stage 8 Logic Type (0 = normal, 1 = inverted) Normal/Inverted Normal
Inlet Guide Vanes Master Proportional Gain 0 to 5.0 0 5 Inlet Guide Vanes Master Integral Gain 0 to 2.0 0 3 Inlet Guide Vanes Master Derivative Gain 0 to 5.0 0 0 Inlet Guide Vanes Submaster Gain −10.0 to 10.0 5 0 Inlet Guide Vanes Submaster Center Value (%) 0 to 100 50
Mixed-Air Damper Master Proportional Gain 0 to 20.0 8 0 Mixed-Air Damper Master Integral Gain 0 to 2.0 0 3 Mixed-Air Damper Master Derivative Gain 0 to 20.0 0 0 Mixed-Air Damper Submaster Gain −20 0 to 20.0 −7.5 Mixed-Air Damper Submaster Center Value (%) 0 to 100 50 Mixed-Air Damper Minimum Position (%) 0 to 100 10
Electric Heat Master Propor ional Gain 0 to 20.0 8 0 Electric Heat Master Integral Gain 0 to 2.0 0 3 Electric Heat Master Derivative Gain 0 to 20.0 0 0 Electric Heat Submaster Gain 0 to 15.0 5 0
CONFIGURATION VALUE RANGE
FACTORY DEFAULT
VALUE
0to2 1
0to2 1
Enabled/Disabled Enabled
82
Table 16 — Service Configuration Ranges and Defaults (cont)
SERVICE SUBFUNCTION
NUMBER
13
14
15
16
17
18
20
21
22
23
24
26
AOTC — Analog Output Temperature Control OAVP — Outside Air Velocity Pressure
LEGEND
Night Purge Duration (minutes) 5 to 240 15 Night Purge Low Temperature Damper Position (% output) 0 to 100 10 Night Purge High Temperature Damper Position (% output) 0 to 100 35
Constant Outside Air Master Proportional Gain 0.0 to 5.0 0.3 Constant Outside Air Master Integral Gain 0.0 to 5.0 1.0 Constant Outside Air Master Derivative Gain 0.0 to 5.0 0.0 Constant Outside Air Submaster Gain 60 to 600 * OAVP Sensor Low Voltage Point 0 to 2 2 OAVP Sensor High Voltage Point 5 to 10 10 OAVP Sensor Low Voltage Reference 0.0 to 2.0 0.0 OAVP Sensor High Voltage Reference 0.01 to 5.00 0.05 OAVP Sensor Probe Mul iplier Factor 0.100 to 9.999 1.564
Air Quality Sensor 1 Master Proportional Gain 0.01 to 1.00 0.10 Air Quality Sensor 1 Master Integral Gain 0.01 to 1.00 0.03 Air Quality Sensor 1 Maximum Damper Position (%) 0 to 100 50 Air Quality Sensor 1 Low Voltage Point 0 to 2 2 Air Quality Sensor 1 High Voltage Point 5 to 10 10 Air Quality Sensor 1 Low Voltage Reference 0 to 2000 0 Air Quality Sensor 1 High Voltage Reference 0 to 2000 2000
Air Quality Sensor 2 Master Proportional Gain 0.01 to 1.00 0.10 Air Quality Sensor 2 Master Integral Gain 0.01 to 1.00 0.03 Air Quality Sensor 2 Maximum Damper Position (%) 0 to 100 50 Air Quality Sensor 2 Low Voltage Point 0 to 2 2 Air Quality Sensor 2 High Voltage Point 5 to 10 10 Air Quality Sensor 2 Low Voltage Reference 0 to 2000 0 Air Quality Sensor 2 High Voltage Reference 0 to 2000 2000
Building Factor (%) 1 to 100 10 24 hour Unoccupied Factor 0 to 99 15 Set Point Bias (F) 0 to 10 2 Maximum Allowable Stop Time 0 to 120 60
Reset Ratio 0 to 10 3 Reset Limit 0 to 20 10
Supply Velocity Upper Limit (in. wg) 0 to 3.0 2.0 Return Velocity Upper Limit (in. wg) 0 to 3.0 2.0 Supply Duct Area 0 to 50 0 Return Duct Area 0 to 50 0 Fan Tracking Master Proportional Gain 0.0 to 2.0 0.5 Fan Tracking Master Integral Gain 0.0 to 2.0 0.5 Fan Tracking Master Derivative Gain 0.0 to 5.0 0.0 Fan Tracking Submaster Gain −20.0 to 20.0 10.0 Fan Tracking Submaster Center Value (%) 0 to 100 50
Humidity Master Proportional Gain 0.0 to 10.0 2.0 Humidity Master Integral Gain 0.0 to 2.0 0.3 Humidity Master Derivative Gain 0.0 to 10.0 0.0 Humidity Submaster Gain −20.0 to 20.0 7.5 Humidity Submaster Center Value (%) 0 to 100 50
Space Temperature Low Alarm Limit — Occupied (F) −10 to 245 65 Space Temperature High Alarm Limit — Occupied (F) −10 to 245 80 Space Temperature Low Alarm Limit — Unoccupied (F) −10 to 245 45 Space Temperature High Alarm Limit — Unoccupied (F) −10 to 245 100 Supply Air Temperature Low Alarm Limit — Occupied (F) −10 to 245 45 Supply Air Temperature High Alarm Limit — Occupied (F) −10 to 245 120 Supply Air Temperature Low Alarm Limit — Unoccupied (F) −10 to 245 35 Supply Air Temperature High Alarm Limit — Unoccupied (F) −10 to 245 180 Return Air Temperature Low Alarm Limit — Occupied (F) −10 to 245 60 Return Air Temperature High Alarm Limit — Occupied (F) −10 to 245 90 Return Air Temperature Low Alarm Limit — Unoccupied (F) −10 to 245 35 Return Air Temperature High Alarm Limit — Unoccupied (F) −10 to 245 120 Temperature Input Low Alarm Limit — Occupied (F) −10 to 245 −10 Temperature Input High Alarm Limit — Occupied (F) −10 to 245 245 Temperature Input Low Alarm Limit — Unoccupied (F) −10 to 245 −10 Temperature Input High Alarm Limit — Unoccupied (F) −10 to 245 245 Outside Air Temperature Low Alarm Limit (F) −40 to 245 −40 Outside Air Temperature High Alarm Limit (F) −40 to 245 120 Mixed Air Temperature Low Alarm Limit (F) 0 to 250 0 Mixed Air Temperature High Alarm Limit (F) 0 to 250 250 Relative Humidity Low Alarm Limit (%) 0 to 100 0 Relative Humidity High Alarm Limit (%) 0 to 100 100 Outside Air Relative Humidity Low Alarm Limit (%) 0 to 100 0 Outside Air Relative Humidity High Alarm Limit (%) 0 to 100 100 Static Pressure Low Alarm Limit (in. wg) 0 to 5.0 1.0 Static Pressure High Alarm Limit (in. wg) 0 to 5.0 2.5 Supply Velocity Low Alarm Limit (in. wg) 0 to 3.0 0.0 Supply Velocity High Alarm Limit (in. wg) 0 to 3.0 3.0 Return Velocity Low Alarm Limit (in. wg) 0 to 3.0 0.0 Return Velocity High Alarm Limit (in. wg) 0 to 3.0 3.0 Delta CFM x 100 (CCFM) Low Alarm Limit 0 to 250 0 Delta CFM x 100 (CCFM) High Alarm Limit 0 to 250 250 Air Quality Sensor 1 High Alarm Limit (ppm) 0 to 2000 800 Air Quality Sensor 2 High Alarm Limit (ppm) 0 to 2000 800
Preheat Coil/AOTC Master Proportional Gain 0.0 to 20.0 5.0 Preheat Coil/AOTC Master Integral Gain 0.0 to 2.0 0.3 Preheat Coil/AOTC Master Derivative Gain 0.0 to 20.0 0.0 Preheat Coil/AOTC Submaster Gain −20.0 to 20.0 −5.0 Preheat Coil/AOTC Submaster Center Value (%) 0 to 100 F 50 Preheat Coil/AOTC Fan/Off Value (F) 35 to 65 40 Preheat Coil/AOTC Sensor 0 to 128 0
Discrete Temperature Control Sensor 0 to 128 0 Discrete Temperature Control Logic 0 to 1 0 Discrete Temperature Control Hysteresis (F) 0 to 20 2
Service/Maintenance Limits (hours x 1000) 0 to 99 0 Service/Maintenance Elapsed Hours (hours x 1000) 0 to 99 0
CONFIGURATION VALUE RANGE
FACTORY DEFAULT
VALUE
83
— Used to verify software version.
-----------------------------------------------­— Used to verify and change factory configura-
tion. Requires password entry in . See Example 7. NOTE: When more than one unit is connected to the
Carrier Comfort Network, the element address must be changed on all but one unit. The element address system default is 1, and element address numbers cannot be repeated. Element address must be changed at the local interface device.
------------------------------------------------
Example 7 — Reading and Changing
Factory Configurations
KEYBOARD
ENTRY
DISPLAY
RESPONSE
FACT CFG TYPE CV Unit type is constant volume UNIT TYPE IS CV TYPE VAV Unit type is changed to VAV COOL COI Cooling type is coil DXST 2 DX cooling stage quantity is 2 HEAT HCL HEAT NON Changed to no heat unit HEAT ELE Changed to electric heat HEAT COI EHST 0 Electric heater stages = 0 EHST N MIXD ALG Unit with mixed air dampers MIXD NON Changed to without dampers IAQT 1 MATP YES BUS 0 Bus number = 0 ADR 1 Element address = 1 ADR 2 Element address changed to 2
Factory configuration sub­function of service function
Explanation is scrolled across screen
Heating type is hot water/ steam coil
Heating type is changed back to hot water/steam coil
Electric heater stages = N, where N = number of stages
Indoor air quality type is single gas sensor
Mixed air temperature protection enabled
COMMENTS
Example 8 — Configuration of Measurements
KEYBOARD
ENTRY
DISPLAY
RESPONSE
UNIT 0 UNIT 1 UNIT 0
COMMENTS
Measurements are displayed using English (0 = English, 1 = Metric)
Measurements are now displayed using the Metric system
Measurements are returned to English
Example 9 — User Configurations
KEYBOARD
ENTRY
DISPLAY
RESPONSE
USER CFG User configurations NTEN DSB NTFC is disabled NTEN EN NTFC is enabled
NTEN DSB NTFC is disabled
HUEN 0 Humidifier control is none HUEN 1 HUEN 0
OHEN DSB RSEN DSB Space temperature reset (disabled) DLEN DSB FTEN DSB Fan tracking (disabled) OAEN DSB Constant outside air (disabled) NPEN DSB Night purge (disabled) AQEN DSB Indoor air quality (disabled) IAQP DSB OSEN DSB Optimal start is disabled OSEN EN Optimal start is enabled
OSEN DSB Optimal start is disabled
TSCH 1 Time schedule No. 1 is enabled TSCH 2 Time schedule No. 2 is enabled TSCH 1 TOVR 0 Time override value=0hrs
Unit changed to analog humidifier control
Humidifier control is changed back to none
Scroll past occupied heating (disabled)
Scroll past demand limiting (disabled)
Indoor air quality priority level (disabled)
Time schedule is changed back to No. 2
COMMENTS
PSW XXXX Password
— Used to change the HSIO display of the measure-
ments from English to Metric. See Example 8.
------------------------------------------------
— Used to read or change factory configuration of
user options. See Example 9.
------------------------------------------------
TOVR 1 Time override value=1hr TOVR 0 Time override value=0hrs
NTFC — Nighttime Free Cooling
84
— Used to read or change factory configuration
of heating coil. See Example 10.
Example 10 — Configuration of Heating Coil
KEYBOARD
ENTRY
NOTE: The subfunctions to configure the cooling coil , inlet guide vanes , mixed air damper , and electric
heaters , are performed in the same manner as Example 10.
------------------------------------------------
DISPLAY
RESPONSE
HEATCOIL MPG 8.0 Master proportional gain
MPG N Master proportional gain value is
MIG 0.3 Scroll past master integral gain MDG 0.0 Master derivative gain
MDG 0.0 Master derivative gain value
SMG −7.5 Submaster gain SCV 50% Submaster center value FOV 40 Fan off value SMR N SMR X SMR N
Heat coil field configuration subfunction of service function
changed to N, where N = new value within the allowable range
remains 0.0 (old value is still displayed). N value is not within the allowable range
Display of submaster reference value
The submaster reference value has been forced
The submaster reference value force has been removed
COMMENTS
— Used to read or change factory configuration of
cooling (chilled water coil or direct expansion).
-----------------------------------------------­— Used to read or change configuration of direct
expansion cooling options.
-----------------------------------------------­— Used to read or change factory configuration of
inlet guide vanes.
------------------------------------------------
— Used to read or change configuration of
mixed air dampers.
------------------------------------------------
— Used to read or change configuration of elec-
tric heater.
------------------------------------------------
— Used to read or change factory configura-
tion of Nighttime Free Cooling (NTFC) option.
------------------------------------------------
— Used to read or change configuration of
night purge option.
-----------------------------------------------­— Used to read or change configuration of
constant outside air option and outside air velocity pressure sensor.
-----------------------------------------------­— Used to read or change configuration of in-
door-air quality option and AQ1 sensor.
-----------------------------------------------­— Used to read or change configuration of in-
door-air quality option and AQ2 sensor.
-----------------------------------------------­— Used to read or change factory configura-
tion of Adaptive Optimal Start/Stop.
-----------------------------------------------­— Used to read or change factory configura-
tion of space temperature reset. See Example 11.
-----------------------------------------------­— Used to read or change loadshed group
and number. See Example 12.
------------------------------------------------
Example 11 — Configuration of Space
Temperature Reset
KEYBOARD
ENTRY
DISPLAY
RESPONSE
SPCRESET Space temperature reset field
configuration subfunction of
service function RTIO 3 Reset ratio set at 3 RTIO N Ratio changed to N, where
N = new value within the
allowable range LIMT 10 Reset limit set at 10 LIMT N Reset limit changed to N,
where N = new value between
0 and 20
COMMENTS
Example 12 — Configuration of Loadshed
KEYBOARD
ENTRY
DISPLAY
RESPONSE
LOADSHED Loadshed field configuration
subfunction of service function LSGP 1 Loadshed group 1
LSGP 2 Loadshed group changed to 2
COMMENTS
85
— Used to read or change field configuration
of fan tracking. See Example 13.
-----------------------------------------------­— Used to read or change factory configura-
tion of humidity control.
-----------------------------------------------­— Used to read or change factory configura-
tion of alarm limits. See Example 14.
-----------------------------------------------­— Used to read or change field configuration
of analog temperature control. See Example 15.
------------------------------------------------
— Used to read or change field configuration
of discrete temperature control. See Example 16.
------------------------------------------------
Example 13 — Configuration of Fan Tracking
KEYBOARD
ENTRY
DISPLAY
RESPONSE
FANTRACK Fan tracking field configuration
SVUL 1.5 SVUL 2.0 RVUL 1.5 SDAR 0 Supply duct area = 0
SDAR 8 Supply duct area changed to
RDAR 6 MPG 0.5 MIG 0.5 MDG 0.0 Master derivative gain MDG 4 SMG 10 Scroll past submaster gain SCV 50
SMR N Submaster reference value
SMR X SMR N
subfunction of service function Supply velocity upper limit
= 1.5 in. wg Supply velocity upper limit
changed to 2.0 in. wg Scroll past return velocity upper
limit (1.5 in. wg)
8 sq ft. (Enter whole numbers; decimals not accepted)
Scroll past return duct area (6 sq ft)
Scroll past master proportional gain
Scroll past master integral gain
Master derivative gain changed to 4
Scroll past submaster gain center value
(calculated and updated by the software)
Submaster reference value forced to X value
Submaster reference value force is removed
COMMENTS
Example 14 — Configuration of Alarm Limits
KEYBOARD
ENTRY
DISPLAY
RESPONSE
ALRMLIMT SPLO 65 SPHO 80 SPLU 45 SPHU 100 SALO 45
SALO N Supply-air temperature low limit
Alarm limit field configuration of subfunction of service function
Scroll past space temperature low limit (occupied mode)
Scroll past space temperature high limit (occupied mode)
Scroll past space air temperature low limit (unoccupied mode)
Scroll past space air temperature high limit (unoccupied mode)
Supply-air temperature low limit set at 45 F (occupied mode)
changed to N, whereN=new value within allowable range (−10 F to 245 F)
COMMENTS
Example 15 — Configuration of Analog
Temperature Control
KEYBOARD
ENTRY
DISPLAY
RESPONSE
AO CTRL Analog temperature control
MPG 5.0 MIG 0.3 Scroll past master integral gain MDG 0.0 Scroll past master derivative gain SMG −5.0 Scroll past submaster gain SCV 50 FOV 40 Scroll past fan OFF value SEN 0
SEN 1 Controlling temperature sensor
SMR X Submaster reference value SMR N
SMR X Force removed from submaster
configuration subfunction of service function
Scroll past master proportional gain
Scroll past submaster center value
Controlling temperature sensor (none configured)
configured to sensor 1. Sensor codes as follows:
1 - Supply-air temperature sensor
2 - Outdoor-air temperature
3 - Mixed-air temperature sensor
6 - Space temperature sensor
7 - Return-air temperature sensor
34 - Other optional sensor
Submaster reference value forced to N value
reference value. Display shows last value prior to force
COMMENTS
(standard)
sensor (standard)
(optional)
(standard)
(standard)
86
Example 16 — Configuration of Discrete
Temperature Control
Example 18 — Service/Maintenance
Alarm Configuration
KEYBOARD
ENTRY
DISPLAY
RESPONSE
DO CTRL Discrete temperature control
SEN 1 Controlling temperature sensor
SEN 34 Controlling temperature sensor is
TYP 0
configuration subfunction of service function
configured to sensor 1. Sensor codes as follows:
1 - Supply-air temperature sensor 2 - Outdoor-air temperature 3 - Mixed-air temperature sensor 6 - Space temperature sensor 7 - Return-air temperature 34 - Other optional sensors
34, where sensor 34 is one of 2 optional sensor types (space temperature sensor or duct temperature sensor)
Discrete output control logic (0 = normal logic, 1 = reverse logic)
COMMENTS
(standard) sensor (standard) (optional) (standard) (standard)
— Used to read service history. See Example 17.
-----------------------------------------------­— Used to read or change field configuration
of service maintenance alarm duration and to read elapsed time. See Example 18.
-----------------------------------------------­— Used to read timed override history. See
Example 19. NOTE: The key is used to enable or turn on certain
functions; the CLR key is used to disable these functions. The key may also be used to disable the functions.
SET POINT FUNCTION — Set points are entered through the keyboard. Set points can be changed within the upper and lower limits, which are fixed. See Table 17.
Example 17 — Service History Configuration
KEYBOARD
ENTRY
DISPLAY
RESPONSE
SERVHIST SDAY 2 ST 20 FH 240
4.06.30
4.19.00
COMMENTS
Service history configuration subfunction of service function
The unit had 2 starts within the last 24 hours
The unit had a total of 20 starts since the unit was manufactured
The fan has run for 240 hours since unit manufacture.
The unit was last started on Thursday at 6:30 am
The unit was last stopped on Thursday at 7:00 pm
KEYBOARD
ENTRY
DISPLAY
RESPONSE
SRV/MTN Service/Maintenance alarm
SMAL 2 SMAL 5 Service/Maintenance alarm
SMEH 3 Service/Maintenance elapsed
configuration subfunction of service function
Service/Maintenance alarm limit is 2000 hrs (hours x 1000)
limit is changed to 5000 hrs (This represents the cumulative number of hours the fan must be energized before a service/maintenance alarm is generated) (NOTE: Entering a . disables the alarm function)
hours is 3000 (This is the amount of time elapsed from the start of the service/maintenance alarm interval)
COMMENTS
Example 19 — Timed Override History
KEYBOARD
ENTRY
DISPLAY
RESPONSE
OVRDHIST OHR 3 Within the current 24 hour period
Timed override history subfunction of service function
(beginning at midnight), the unit operated for 3 hours in the timed override mode (mode 39)
COMMENTS
— Displays system set points. See Table 13 for
sequence of set points.
-----------------------------------------------­— Displays demand limit set points.
-----------------------------------------------­— Displays time of day and day of week.
-----------------------------------------------­— Displays Daylight Savings Time.
-----------------------------------------------­— Displays holidays (month, day, and duration).
Table 17 — Set Point Ranges and Defaults
SET POINT
Occupied Heating Set Point (F) 40 to 90 68 Occupied Cooling Set Point (F) 45 to 99 78 Unoccupied Heating Set Point (F) 40 to 90 55 Unoccupied Cooling Set Point (F) 70 to 99 90 Static Pressure
Set Point (in. wg)
Supply-Air Temperature
Set Point (F)
Delta CFM Set Point 0 to 250 0 Humidity Set Point (%) 0 to 100 40 Analog Temperature
Control Set Point (F)
Discrete Temperature
Control Set Point (F)
Air Quality Sensor 1
Set Point (ppm)
Air Quality Sensor 2
Set Point (ppm)
Outside Air Velocity Pressure
Set Point (in. wg)
ALLOWABLE
RANGE
0 to 5.0 1.5
35 to 65 55
40 to 100 40
−40 to 245 0 0 to 2000 650 0 to 2000 650
0.0 to 5.0 0.08
DEFAULT
87
Reading and Changing Set Points — Example 20 shows how to read and change system set points. Other set points can be changed by following the same procedure. Refer to Table 13 for the display sequence of set points in each sub­function.To adjust any parameter after enabling the func-
tion, press until desired parameter is displayed. Key in new value and press . If input is within the allowable range, the display shows the parameter and new value. If
the input is not within the allowable range, the old value remains displayed.
Example 20 — Reading and Changing
System Set Points
KEYBOARD
ENTRY
DISPLAY
RESPONSE
SETPOINT System set points OHSP 68.0 OHSP 70.0 Key in 70 and press ENTR, display
OCSP 78.0 Present occupied cooling set point OCSP 78.0 Key in 30 and press ENTR, display
OCSP 75.0 Key in 75 and press ENTR, display
Present occupied heating set point is 68.0
shows new occupied heating set point is 70, which is within the allowable range
is 78.0 still shows occupied cooling set point
as 78.0 because 30 is not within the allowable range. See Table 15
shows new occupied cooling set point is 75.0, which is within the allowable range
COMMENTS
Reading and Changing Time and Date Display — Time is entered and displayed in 24-hour (military) time. The day of the week is entered as a number: 1 = MON, 2 = TUE...7 = SUN. The month is also entered as a number:1=JAN,2=
FEB...12 = DEC. The key is used as the colon when entering the time and date. See Example 21.
Reading and Changing Daylight Savings Time — Example 22 shows how to read and change daylight savings time. The month is entered as a number: 1 = January, 2 = February...12 = December. The day of week and time of day are entered as explained in Reading and Changing Time and Date Display above.
Example 21 — Setting of Time and Date
KEYBOARD
ENTRY
DISPLAY
RESPONSE
TIME Time display
MON 16:00 Current setting
TUE 13:05 New setting of
JAN 01 96 Current setting
FEB 27 96 New setting of
COMMENTS
subfunction of set point function
is Monday, 4:00 pm
Tuesday, 1:05 pm is entered and displayed
is January 1, 1996
February 27, 1996 is entered and displayed
Example 22 — Setting Daylight Savings Time
KEYBOARD
ENTRY
DISPLAY
RESPONSE
DAYLIGHT Daylight savings time field
ENM X Month when daylight savings ENM 4 Daylight savings time
END X Day of month when daylight END 16 Daylight savings time
ENT X Time of day when daylight ENT 2.00 Daylight savings time
LVM X Month when daylight savings LVM 11 Daylight savings time
LVD X Day of month when daylight LVD 12 Daylight savings time
LVT X Time of day when daylight LVT 2.00 Daylight savings time
COMMENTS
configuration of set point function
time begins configured to start Month 4
(April) savings time begins configured to start on the
16th of the month savings time begins configured to start at 2:00 am
on the 16th of April time ends configured to end Month 11
(November) savings time ends configured to end on the 12th
of November savings time ends configured to end at 2:00 am
on November 12
88
Reading and Changing Holidays — Example 23 explains how to set holidays. Up to 18 holiday periods can be set for one calendar year. When the calendar year changes the holidays must be reconfigured for the new year.
Example 23 — Setting of Holidays
KEYBOARD
ENTRY
DISPLAY
RESPONSE
COMMENTS
HOLIDAY Holiday field config-
uration subfunction of set point function
NEW
First holiday configuration
JUL 04 01 The first holiday is
configured to start Month 7 (July), day 4 (July 4) and last for one day
NOV 23 02 The second holiday
is configured to start Month 11 (Novem­ber), day 23 and last for 2 days.
SCHEDULE FUNCTION — Two schedules are provided with the PIC system. Schedule I automatically switches the unit from an occupied mode to an unoccupied mode. Sched­ule II automatically changes the optional discrete output from occupied to unoccupied mode.
Each schedule consists of from one to 8 occupied time periods, set by the operator.These time periods can be flagged to be in effect or not in effect on each day of the week. The day begins at 00.00 and ends at 24.00. The unit is in unoc­cupied mode unless a scheduled time period is in effect. If an occupied period is to extend past midnight, it must be programmed in the following manner: Occupied period must end at 24:00 hours (midnight); a new occupied period must be programmed to begin at 00:00 hours on the next day.
The time schedule can be overridden to keep the unit or optional discrete output in the occupied mode for 1, 2, 3, or 4 hours on a one-time basis.
The air handler can be configured for an applicable holiday/ shutdown schedule. This function can only be used if the PIC is connected to the Carrier Comfort Network. The net­work will send a holiday message (flag) to the unit on the appropriate holiday. The unit then uses the schedule that has been set for the holiday period. The unit automatically re­turns to its normal schedule after the holiday period is complete.
Figure 75 shows a Schedule I example for an officebuild­ing with the unit operating on a set point schedule. The schedule is based on building occupancy with 3-hour off­peak cool down period from midnight to 3 am following week­end shutdown. To learn how this sample schedule can be programmed, see Example 24. The same scheduling proce­dures can be used to set optional discrete output
Schedule II. Subfunctions through define schedule of air handler (Schedule I). Subfunctions
through define schedule of optional
discrete output (Schedule II).
Fig. 75 — Schedule I Sample Time Schedule
89
Example 24 — Using the Schedule Function
Example 24 — Using the Schedule Function (cont)
KEYBOARD
ENTRY
PROGRAMMING PERIOD 1:
DISPLAY
RESPONSE
PERIOD 1 Define schedule period 1 OCC 00.00 Start of occupied time.
UNO 00.00 Start of unoccupied time
UNO 3.00 MON NO Monday is not flagged
MON YES Monday is now flagged
TUE YES For this example, period 1
TUE NO Tuesday is now flagged
COMMENT
For this example, first period should start here (at midnight) so no entry is needed
(end of period). For this example, period 1 should end at 3:00 am
Period 1 ends at 3:00 am
for period 1. To put period 1 into effect on Monday, Monday must be flagged yes
for period 1 to be in effect
is to be in effect on Monday only. All other days must be checked to be sure that they are flagged no. If any day is flagged yes, change to no
no for period 1
KEYBOARD
ENTRY
PROGRAMMING PERIOD 2:
For this example, period 2 is used on Monday and Tuesday.
DISPLAY
RESPONSE
PERIOD 2 OCC 00.00 Start of occupied time
OCC 7.00 Occupied time will UNO 00.00 Start of unoccupied
UNO 18.00 MON NO Monday is not flagged
MON YES Monday is now flagged
TUE NO Tuesday is not flagged
TUE YES Tuesday is now flagged
WED YES For this example,
WED NO Wednesday is now
COMMENT
Define scheduling period 2
start at 7:00 am time (end of period)
for this example, period 2 should end at 18:00 (6:00 pm)
Period 2 ends at 18:00 (6:00 pm)
for period 2. To put period 2 into effect on Monday, Monday must be flagged yes
for period 2 to be in effect
for period 2. To put period 2 into effect on Tuesday, Tuesday must be flagged yes
for period 2 to be in effect
period 2 is to be in effect only on Monday and Tuesday. All other days must be checked to be sure that they are flagged no. If a day is flagged yes, change to no
flagged no for period 2
90
Example 24 — Using the Schedule Function (cont)
Example 24 — Using the Schedule Function (cont)
KEYBOARD
ENTRY
PROGRAMMING PERIOD 3:
For this example, Period 3 is used on Wednesday only.
Period 4 and 5 can be programmed in the same manner, flagging Thursday and Friday yes for period 4 and Saturday yes for period 5. For this example, periods 7 and 8 are not used; they should be pro­grammed OCC 00.00, UNO 00.00.
NOTE: When a day is flagged yes for 2 overlapping periods, occu­pied time will take precedence over unoccupied time. Occupied times can overlap in the schedule with no consequence.
To extend an occupied mode beyond its normal termination for a one-time schedule override, program as shown below:
DISPLAY
RESPONSE
OCC 00.00 Start of occupied time OCC 7.00
UNO 00.00 Start of unoccupied
UNO 21.30 MON NO Check to be sure that
TUE NO WED NO Wednesday is flagged
WED YES Wednesday is now
THU NO Check to be sure that
FRI NO SAT NO SUN NO HOL NO
COMMENT
Occupied time will start at 7:00 am
time (end of period 3). For this example, period 3 should end at 21:30 (9:30 pm)
Period 3 ends at 21:30 (9:30 pm)
Monday and Tuesday are flagged no for period 3
no. Change to yes flagged yes for
period 3 all other days are
flagged no
KEYBOARD
ENTRY PROGRAMMING PERIOD 6: For this example, Period 6 is used for holiday only.
DISPLAY
RESPONSE
OCC 00.00 Start of occupied time OCC 20.00
UNO 00.00 Start of unoccupied
UNO 21.00 MON NO Check to be sure that
TUE NO WED NO THU NO FRI NO SAT NO SUN NO HOL NO HOL YES
COMMENT
Occupied time will start at 20:00 (8:00 pm)
time (end of period 6). For this example, period 6 should end at 21:00 (9:00 pm)
Period 6 ends at 21:00 (9:00 pm)
Monday through Sunday are flagged no for period 6
Holiday is flagged no. Change to yes
Holiday is now flagged yes for period 6
OVRD 0
OVRD 3
Override is set for 0; enter the number of hours of override desired
Unit will now remain in occupied mode for an additional 3 hours
91
CONTROL OPERATING SEQUENCE
Constant Volumeand VariableAirVolumeUnits
TWO-POSITION DAMPER CONTROL — Two-position damper control opens or closes field-supplied and installed two-position outdoor-air dampers in order to provide mini­mum outdoor air ventilation.
If the supply fan is OFF, the damper is closed. If the sup­ply fan is ON, the control determines if the unit is in the OCCUPIED mode. If unit is in the OCCUPIED mode, the dampers open. If unit is in the UNOCCUPIED mode, the dampers close.
FILTERST ATUS CONTROL — This control sequence moni­tors one or more airflow switches which measure the dif­ferential pressure between the upstream and downstream side of a filter.
When the filter becomes dirty or needs to be replaced, the airflow switches send a discrete signal to the processor mod­ule. This, in turn, generates an alarm at the Local Interface Device or Building Supervisor.
F ANCONTROL — The supply fan is started or stopped based on the occupancy schedule, adaptive optimal start, night­time free cooling, unoccupied heating, unoccupied cooling, demand limiting, night purge, or timed override.
The start of an occupied period is determined by either the occupancy schedule or optimal start. If optimal start is not selected, the supply fan starts at the occupied time en­tered in the occupancy schedule. If optimal start is selected, the fan starts at the calculated start time. The fan stops at the unoccupied time entered in the occupancy schedule. (Timed override may be used to extend the occupied period between 1 and 4 hours.)
During the unoccupied period, whenever the space tem­perature falls below the unoccupied heating set point or rises above the unoccupied cooling set point, the supply fan en­ergizes and runs until the space temperature returns to within the required limits.
The supply fan can also run between the hours of 3:00 am and 7:00 am when the unit is in the Nighttime Free Cooling mode to pre-cool the space prior to the Occupied period.
Constant volume units that are subject to demand limiting stop the supply fan whenever a loadshed command is re­ceived from the CCN Loadshed option. The supply fan re­mains OFF until the loadshed command is cleared or the in­ternal maximum loadshed timer expires.
NIGHTTIME FREE COOL (NTFC) — Nighttime free cool­ing is used to start the supply fan to precool the building’s interior using outside air. This delays the need for mechani­cal cooling when the system enters the Occupied mode.
The system determines if the outside conditions (tempera­ture and enthalpy) are suitable for outside cooling. If so, the supply fan is energized and the dampers modulate open. Once the space has been sufficiently cooled, the fan stops.
If the outside air conditions are not suitable, the fan remains OFF.
The unit must have mixed-air dampers to operate NTFC.
NTFC is scheduled to run only between the hours of
3:00 am and 7:00 am. NIGHT PURGE — During the unoccupied period, this fea-
ture starts the fans and opens the mixed-air dampers to re­move stagnant air and airborne pollutants from the building space.
If the current time is within the configured night purge duration, the control reads the outdoor air temperature and determines the mixed-air damper position. If the outdoor air temperature is less than the configured NTFC lockout tem­perature, the system sets the mixed-air dampers at the con­figured low temperature position. If the outdoor-airtemperature is greater than the NTFC set point, or the enthalpy is high, the system sets the dampers at the configured high tempera­ture position.
When the outside-air temperature is below the NTFC set point and the low temperature night purge damper position is set to zero, night purge is not performed. Also, when the outside air temperature is above the NTFC set point and en­thalpy is high, if the high temperature night purge damper position is set to zero, night purge is not performed.
Night purge ends when the occupied time period begins. QUICK TEST — The Quick Test is initiated and controlled
at the local interface device (HSIO). It allows the service person or building owner to test all inputs and outputs of the PIC controls. When used, it displays all current values of input channels and allows the user to exercise all output channels.
Quick test suspends all process algorithms and forces all outputs with a service priority.
All service forces are removed when Quick Test is exited and control is returned to the process algorithms.
ANALOG OUTPUT TEMPERATURE CONTROL/ PREHEAT COIL CONTROL — The analog output tem­perature control adjusts an analog output to a fixed set point, based on any analog temperature sensor connected to the unit. (Applicable sensors are: space temperature sensor, outside­air temperature sensor,mixed-air temperature sensor,supply­air temperature sensor, and return-air temperature sensor.)
If the fan is ON, the control identifies the controlling tem­perature sensor, reads the sensor and compares the tempera­ture to the configurable set point. It then calculates the tem­perature required to satisfy the conditions.
The calculated value is compared to the actual tempera­ture and the corresponding output is modulated to the required position.
The preheat coil control adjusts the steam or hot water valve. The valve is modulated to raise the temperature of incoming outside air. The control uses a sensor downstream from the preheat coil to monitor the air temperature.
If the supply fan is OFF, the heating valve is modulated to maintain the desired minimum duct temperature (fan off value).
If the supply fan is on and the entering-air temperature is below the set point value, the heating valve is modulated to obtain the desired leaving-air temperature.
92
DISCRETE OUTPUT/ANALOG INPUTCONTROL— The discrete output is controlled as a function of a temperature sensor connected to the 39L or 39NX unit. (Applicable sen­sors are: space temperature sensor, outside-air temperature sensor, mixed-air temperature sensor, supply-air tempera­ture sensor, and return-air temperature sensor.) The discrete output is turned ON/OFF as required to maintain the user configured set point.
The controlling sensor is identified and its value is read. The control determines which user-configurable control logic (normal or reverse) is required.
The control compares the sensor value to the configured set point.
If normal logic is used, the discrete output is turned ON when the sensor value is equal to or greater than the set point. This output is turned OFF when the sensor value is less than the set point decreased by a user configurable hysteresis.
If reverse logic is used, the discrete output is turned ON whenever the sensor value is less than the set point. This output is turned OFF when the sensor value is greater than the set point increased by a user configurable hysteresis.
DISCRETE OUTPUT, TIMECLOCK CONTROL — This control sequence turns ON an output channel when the cur­rent time of day is greater than or equal to the Occupied time and less than the next Unoccupied time. This discrete output is OFF at all other times. The output can be used for lighting control, pump control, or to control other devices which have to be ON during the Occupied period and OFF during the Unoccupied period. This control sequence operates under its own time schedule (Schedule II).
Using the local interface device or building supervisor,the output may be overridden to extend the occupied period be­tween 1 and 4 hours.
The control determines the output that is under time­clock control. The current time of day is compared to the Occupied time and to the next Unoccupied time. If the current time of day is equal to or within the Occupied time period, the discrete output is turned ON. If the current time of day is equal to or within the Unoccupied time period, the discrete output is turned OFF.
HUMIDITY (ANALOG OUTPUT) CONTROL — The hu­midity analog output control adjusts the steam valve of the steam grid humidifier. The valve is modulated to maintain the desired space or desired return-air humidity set point, depending on whether a wall-mounted or duct-mounted hu­midity sensor is used. A duct high humidity switch is also monitored and provides a user adjustable high limit safety.
If the supply fan is OFF, the steam valve is held closed. If the supply fan is ON, and the unit is in the Unoccupied
mode, the valve is held closed.
If the supply fan is ON and the unit is in the Occupied mode, the system determines the status of the duct high hu­midity switch. If the duct humidity is above the switch set point, the valve is held closed. If the duct humidity is less than the switch set point, the control reads the humidity sen­sor, compares the value to the set point and modulates the output as required to satisfy conditions.
HUMIDITY(DISCRETE OUTPUT) CONTROL — The hu­midity control sequentially adjusts a 2-stage humidifier.The humidifier is controlled to maintain a desired space or return­air humidity, depending on whether a wall-mounted or duct­mounted humidity transmitter is used.
The first stage of humidification energizes the humidifier spray pump (if applicable) along with the first stage of the humidifier.The second stage of humidification energizes the second stage of the humidifier.
A duct high humidity switch is also monitored and pro­vides a user adjustable duct high humidity limit safety.
If the fan status is ON and the unit is in the Occupied mode, the control reads the space or return-air humidity sen­sor. If the humidity is 2% less than the humidity set point, the first stage is turned ON.
If the humidity is 5% less than the humidity set point, both stages are turned ON.
As the humidity increases, the stages are turned OFF as follows: When the humidity is within 2% of the set point, the second stage of the humidifier is turned OFF. When the humidity is greater than or equal to the set point, both stages are turned OFF. If the high humidity switch is tripped, all stages of the humidifier are turned OFF.
93
INDOOR-AIR QUALITY (IAQ) — This function main­tains the correct occupied ventilation rate using CO2as an indicator of occupancy level or controls the levels of volatile organic compounds (VOCs) or other indoor air pollutants by modulating the mixed air dampers. Varyingquantities of out­door air are admitted during the Occupied period to main­tain the ventilation rate at its set point or pollutants at or below the configured set points of the air-quality (AQ) sen­sors. See Fig. 76.
sensors are available from the factory as options for
CO
2
field installation. VOC or other types of sensors can be field­supplied and installed. Sensors used with the IAQ feature can be configured several different ways:
• One sensor can be installed in either the space or return air stream to continuously monitor a single gas.
• Two sensors (monitoring the same gas) can be installed in different locations to provide separate inputs. For ex­ample, one sensor can be located in an occupied space and another in the return air duct, or each sensor can be in­stalled in a different occupied space.
• Two sensors (typically VOC sensors monitoring the same gas) can be installed inside and outside the occupied space for comparative measurements. The control is configured to modify the damper position based on the value of the sensor in the occupied space, but before admitting outside air, the control performs a differential check to determine if the value of the sensor measuring the outside air is higher. If the outside sensor has a higher value, the damper does not change position.
Systems with One AQ Sensor — During the unoccupied period, the minimum damper position maintained by the IAQ control is 0. During the occupied period, the control
reads the AQ1 sensor input and compares it to the config­ured set point. The control then calculates the minimum damper position to maintain the set point. If no other control is at­tempting to adjust the dampers to a more fully open position than the IAQ control, the damper is adjusted to the position determined by the IAQ control. Otherwise, the damper is positioned by the superseding control routine or at its con­figured minimum position.
Systems with TwoAQ Sensors (Separate Readings) — The preceding sequence for the AQ1 sensor also applies to the AQ2 sensor, but the damper position is determined by either the AQ1 or the AQ2 sensor according to which sensor value demands the more fully open damper position.
Systems with TwoAQ Sensors (Differential Check) — If dif­ferential sensing is configured for two VOC sensors, the con­trol reads the AQ2 (outside air) sensor to determine if its value is greater or less than that of the AQ1 (indoor air) sen­sor. If the AQ2 value is greater than the value of the AQ1 sensor, the mixed-air damper position is set to 0. If the AQ2 value is less than the AQ1 value (by at least 1% of the con­figured minimum sensor value), the control uses the AQ1 value to modulate the dampers and maintain the AQ set point.
IAQ System Protection — To protect the system against coil freeze-up in cold climates or high heat and humidity in warm climates, the system provides several user-selectable fea­tures to override or modify the IAQ functions. An adjustable maximum position for the mixed-air damper is provided for each AQ sensor, and a selection is available to maintain the minimum mixed-air temperature at approximately 45 F.Space temperature and humidity protection can temporarily sus­pend IAQ functions until the temperature and humidity con­ditions return to the desired set points. On VAV systems dur­ing cooling, the IAQ function can be limited to maintain the required supply-air temperature.
94
Fig. 76 — Indoor-Air Quality (IAQ) Control Operation
95
LEGEND
AQ Air Quality Sensor IAQ — Indoor-Air Quality MAT — Mixed-Air Temperature OAT — Outdoor-Air Temperature RH Relative Humidity SAT — Supply-Air Temperature SPT — Space Temperature VAV — Variable Air Volume
SMOKE CONTROL — When the 39L or 39NX unit is equipped with an optional smoke control and a fire system is installed, 4 modes are provided to control smoke within areas serviced by the air-handling unit. Each mode must be energized individually from the approved building fire alarm system, and the corresponding alarm is then generated at the local interface device or Building Supervisor.
The system must include a separate return fan and an ex-
haust air damper witha4to20mAactuator.
The building fire alarm system must provide 4 normally­open dry contact closures and a double-pole, double-throw (DPDT) relay (24 vac coil, contacts rated 10 amps at 240 vac) for the Fire Shutdown mode.
Fire Shutdown Mode — The fire alarm system must provide a normally-open dry contact closure which, when activated, energizes the Fire Shutdown mode.
When the Fire Shutdown mode is energized, the supply and return fans stop, the outside and exhaust air dampers close, and the return-air dampers open.
This mode remains in effect as long as the input signal is maintained at the fire system panel. An alarm is generated from this input and sent to the Building Supervisor. In order for this mode to be initiated, the input signal must be main­tained for no less than 2 seconds.
Evacuation Mode — The building fire alarm system must pro­vide a normally-open dry contact closure which, when ac­tivated, energizes the Evacuation mode. When the Evacuation mode is energized, the supply fan shuts down, the return fan starts, the outside-air and return-air dampers close, and the exhaust air dampers open.
This mode remains in effect for as long as the input signal is maintained at the fire system panel. An alarm is generated from this input and sent to the Building Supervisor. In order for this mode to be initiated, the input signal must be main­tained for no less than 2 seconds.
Pressurization Mode — The building fire alarm system must provide a normally-open dry contact closure which, when activated, energizes the Pressurization mode. When the Pressurization mode is energized, the supply fan starts, the return fan shuts down, the outside dampers open, and the exhaust and return-air dampers close.
This mode remains in effect as long as the input signal is maintained at the fire system panel. An alarm is generated from this input and sent to the Building Supervisor. In order for this mode to be initiated, the input signal must be main­tained for no less than 2 seconds.
Smoke Purge Mode — The building fire alarm system must provide a normally-open dry contact closure which, when activated, energizes the smoke purge mode.
When the smoke purge mode is energized, the supply fan starts, the return fan starts, the outside air and exhaust air dampers open and the return-air dampers close.
This mode remains in effect as long as the input signal is maintained at the fire system panel. An alarm is generated from this input and sent to the Building Supervisor. In order for this mode to be initiated, the input signal must be main­tained for no less than 2 seconds.
ADAPTIVE OPTIMAL START — Optimal Start is used to heat up or cool down the space prior to occupancy. The pur­pose is to have the space temperature approach and then achieve the occupied set point by time of occupancy. The control uses outdoor-air temperature, space temperature, occupied
set point, and a ‘K’ factor in minutes/degrees to calculate a start time offset, which is the time in minutes that the system should be started in advance of the occupied time. The con­trol monitors its results and adjusts the K factor to assure that the Occupied set point is achieved at time of occupancy.
Constant Volume Units Only
HEATINGCOILCONTROL — The heating coil control ad­justs the steam or hot water valve. The valve is modulated to prevent the space temperature from falling below the de­sired set point.
If the supply fan is OFF, the heating valve is modulated
to maintain a desired minimum duct temperature (fan off value).
If the fan is ON, the system reads the space sensor and computes the supply-air temperature required to satisfy conditions.
Once the required supply-air temperature has been calculated, it is compared to the actual supply-air tempera­ture and the heating coil valve modulates to the required position.
CHILLED WATER COIL COOLING CONTROL — The cooling coil control adjusts the chilled water valve. The valve is modulated to prevent space temperature from exceeding the desired set point. The valve holds its normal position if the space temperature is below the set point or the supply fan is OFF.
If the fan is ON, the control reads the humidity sensor (if supplied) and compares the value to the high humidity limit.
If the humidity is higher than the high humidity limit, the chilled water valve fully opens.
If the humidity is below the high humidity limit, the con­trol reads the space temperature sensor and computes the supply­air temperature required to satisfy conditions.
Once the required supply-air temperature has been cal­culated, it is compared to the actual supply-air temperature and the chilled water valve modulates to the position re­quired to maintain desired conditions.
See Fig. 77 for cooling coil operation flow chart. DIRECT EXPANSION COOLING CONTROL — The
direct expansion (DX) cooling control regulates the DX cool­ing system. The DX cooling stages are energized and deen­ergized to prevent the space temperature from exceeding the desired set point. The stages remain off if the space tem­perature is below the set point or the supply fan is OFF.
If the supply fan is ON, the control reads the humidity sensor (if supplied) and compares the value to the high humidity limit. If the humidity is higher than the high hu­midity limit, the DX cooling stages are energized to main­tain a minimum supply-air temperature. If the humidity is below the limit, the control reads the space temperature sen­sor and computes the supply-air temperature required to sat­isfy conditions.
Once the required supply-air temperature has been cal­culated, it is compared to the actual supply-air temperature and the required DX cooling stages are energized to main­tain the desired conditions.
See Fig. 77 for cooling operation and Fig. 78 for DX sub­master gain operation. For more complete information, refer to the Application Data book for Product Integrated Con­trols with DX Cooling.
96
Fig. 77 — Cooling (DX and Chilled Water) Control Operation
97
LEGEND
CCV — Cooling Coil Valve CV Constant Volume DX Direct Expansion RAT — Return-Air
Temperature
RH Relative Humidity
DX Direct Expansion MAT — Mixed-Air Temperature RAT — Return-Air Temperature SAT — Supply-Air Temperature
Fig. 78 — DX Submaster Gain Control Operation
98
LEGEND
MIXED-AIR DAMPER CONTROL — The mixed-air damper control adjusts modulating outside-air, return-air,and exhaust­air dampers. When outside air conditions are unsuitable for atmospheric cooling, the dampers are held to an adjustable minimum outside air position. When outside air conditions are suitable for atmospheric cooling, the mixed-air dampers are modulated to maintain a space temperature that is be­tween the heating and cooling set points in an effort to mini­mize the need for heating or mechanical cooling. The damper set point is automatically adjusted as a function of outdoor­air temperature or can be set to a fixed value by the user.
If the supply fan is OFF, the mixed-air dampers are kept
closed to outside air and open to return air.
If the fan is ON, the system checks to see if the system is in the HEATmode. If system is in the HEATmode, the mixed­air dampers are held in the minimum position.
If the system is not in the HEAT mode, it determines if the outside conditions are suitable for atmospheric cooling. The control compares the outdoor-air temperature to the space temperature. If the outdoor-air temperature is less than the space temperature, the system does either an enthalpy check (using an outside-air enthalpy switch) or a differential en­thalpy check. (Return-air temperature is compared to return­air relative humidity for return-air differential enthalpy.Outside­air temperature is compared to outside-air relative humidity for outside-air differential enthalpy.)
The control then determines if the outdoor-air tempera­ture is below the Nighttime Free Cool Lockout (NTLO). If so, the damper set point is changed to 1.0 degree less than the Occupied Cooling set point, allowing the system to use return air during the heating mode.
If the outdoor-air temperature is higher than 68 F, the con­trol sets the damper set point to 1.0 degree higher than the Occupied Heating set point to provide cooling, allowing the system to use outside air.
If the outdoor-air temperature is higher than NTLO but less than 68 F, the system sets the damper set point halfway between the Occupied Heating and Occupied Cooling set points to provide ventilation.
If outside conditions are suitable, the control compares the space temperature to the damper set point and computes the supply-air temperature required to satisfy conditions.
Once the required supply-air temperature has been cal­culated, it is compared to the mixed-air temperature sensor value (if installed), otherwise the supply-air temperature sen­sor determines the damper position. The damper adjustment rate is limited to 5% per minute if the outside-air tempera­ture is less than 40 F. This rate limit prevents nuisance low temperature thermostat tripping.
ELECTRIC HEATER CONTROL — Electric heater stag­ing regulates the electric heater. The heater is staged to pre­vent the space temperature from falling below the desired set point. (The number of heat stages is factory set for each unit’s heater.)
If the supply fan is OFF, all stages of electric heat are turned off.
If the fan is ON, the control reads the space temperature sensor and calculates the supply-air temperature required to satisfy conditions.
Once the required supply-air temperature has been cal­culated, it is compared to the actual supply-air temperature to determine the number of heat stages required to satisfy conditions. The required stages are energized one at a time, with 2-second intervals between stages.
ADAPTIVE OPTIMALSTOP—Optimal stop allows the space temperature to drift to an expanded occupied set point dur­ing the last portion of an occupied period. The control cal­culates a stop time offset, which is the time in minutes prior to the scheduled unoccupied time, during which expanded set points can be used. Adaptive optimal stop utilizes space temperature, an expanded Occupied set point, and a K factor to calculate stop time offset. The amount to expand the Oc­cupied set point is user configurable. Like adaptive optimal start, the control corrects itself for optimal operation by ad­justing the K factor.
TWO-STEP DEMAND LIMITING (Available on Units Connected to the Carrier Comfort Network Only) — If the Demand Limit option is enabled, the control receives and accepts redline alert and loadshed commands from the Network Loadshed option. See the CCN Loadshed manual for additional information.
When a redline alert is received, the Control decreases the Occupied Heating set point by 2° F and increases the Oc­cupied cooling set point by 2° F.
When a loadshed command is received, the supply fan turns OFF.
The maximum loadshed timer prevents the system from remaining in loadshed, should the control lose communica­tions with the Loadshed option. If the timer expires be­fore the loadshed command is cleared by the Loadshed op­tion, the control clears the loadshed command itself and returns to normal control. The loadshed timer is factory set at 60 minutes.
Variable Air Volume Units Only
CONSTANT OUTSIDE AIR (OAC) — During Occupied periods, this feature provides a continuous flow of outside air into the building. The OAC control modulates the mixed­air damper to a configurable minimum open position to en­sure outside air is admitted. During Unoccupied periods, the control signals the dampers to fully close.
To monitor the outside airflow during Occupied periods, the OAC control reads the outside-air velocity pressure (OA VP) sensor, compares its value to the OAVP set point, and ad­justs the mixed-air dampers to the position required to achieve the configured velocity pressure.
If a control routine (other than OAC) or the configured minimum damper position require the dampers to be more fully open than the OAC setting, that routine or position over­rides the OAC control. To protect against coil freeze-up in colder climates, the PIC provides selectable low tempera­ture protection to limit the minimum mixed-air temperature to approximately 45 F.
See Fig. 79 for OAC control flowchart.
99
HEATINGCOILCONTROL — The heating coil control ad­justs the steam or hot water valve. Heat is primarily used for morning warm-up or Occupied Heating with the valve modu­lated to maintain desired return-air temperature.
If the supply fan is OFF, the heating valve is modulated
to maintain a desired minimum duct temperature (fan off value).
If the fan is ON, the system determines if it is in the morn­ing warm-up mode. If it is, the return-air sensor is read and compared to the Occupied Heating set point. If heating is required, the control calculates the supply-air temperature required to satisfy conditions.
Once the required supply-air temperature has been cal­culated, it is compared to the actual supply-air temperature and the heating coil valve modulates to the required position.
The heat interlock relay is energized whenever there is a need for heat.
Once morning warm-up is completed, heat is activated again unless Occupied Heat has been selected.
During cooling or fan-only operation, heat can also be pro­vided to maintain the supply-air temperature when the amount of cold outside air admitted by the IAQ or OAC controls causes the temperature to fall below the supply-air set point.
CHILLED WATER COIL COOLING CONTROL — The cooling coil control adjusts the chilled water valve. The valve is modulated to maintain desired supply-air temperature set point. The valve is held in its normal position whenever the system is in Nighttime Free Cooling or whenever the supply fan is OFF.
If the fan is ON, the control reads the humidity sensor and compares the value to the high humidity limit.
If the humidity is higher than the humidity limit, the chilled
water valve fully opens.
If the humidity is below the high humidity limit, or if no humidity sensor is supplied, the control reads the supply-air sensor and computes the supply-air temperature required to satisfy conditions, provided that return-air temperature is greater than the Occupied Cooling set point.
Once the required supply-air temperature has been cal­culated, it is compared to the current supply-air temperature and the chilled water valve modulates to the position re­quired to maintain desired conditions.
See Fig. 77 for cooling operation flowchart. STATICPRESSURE CONTROL — The static pressure con-
trol adjusts the inlet guide vanes (IGVs) or the supply-fan motor inverter in a variable air volume system in order to maintain the duct static pressure set point.
If the supply fan is OFF, the IGVs remain closed or the minimum signal is sent to the inverter.
If the fan is ON, the system reads the duct static pressure sensor and computes the static pressure required to satisfy conditions. The system compares the duct static pressure to the computed value and calculates the required signal that is output to the IGV actuator or the inverter.
FAN VOLUME CONTROL — Fan volume control adjusts the inlet guide vanes or inverter in a VAV system. The return fan IGVs or inverters are modulated to maintain a constant differential cfm value between the supply and return fans in the system.
If the supply fan is OFF, the return fan inlet guide vanes
are closed and no signal is sent to the return fan inverter.
If the supply fan is ON, the control reads the supply fan differentialpressure transmitter and computes the supply cfm. The desired return cfm is calculated by subtracting the dif­ferential cfm set point from the calculated supply cfm. The return cfm is read and the return fan differential pressure re­quired to satisfy conditions is calculated.
The calculated return fan differential pressure is com­pared to the current differential pressure. The signal required to satisfy conditions is sent to the return fan inlet guide vane actuator or return fan inverter.
DIRECT EXPANSION COOLING CONTROL — The di­rect expansion (DX) cooling control regulates the DX cool­ing system. The DX cooling stages are energized and deen­ergized to maintain the desired supply-air temperature set point. Whenever the system is in Nighttime Free Cooling mode or whenever the supply fan is off,the DX cooling stages remain off.
If the supply fan is on, the control reads the humidity sen­sor (if supplied) and compares the value to the high humid­ity limit. If the humidity is higher than the high humidity limit, the DX cooling stages are energized to maintain a mini­mum supply-air temperature. If the humidity is below the limit, the control reads the space temperature sensor and com­putes the supply-air temperature required to satisfy conditions.
Once the required supply-air temperature has been cal­culated, it is compared to the actual supply-air temperature and the required DX cooling stages are energized to main­tain the desired conditions.
See Fig. 77 for cooling operation and Fig. 78 for DX sub­master gain operation. For more complete information, refer to the Application Data book for Product Integrated Controls with DX Cooling
ELECTRIC HEATER CONTROL — Electric heater stag­ing regulates the electric heater. The heater is primarily used for morning warm-up or Occupied Heating, with the heater staged to maintain desired return air temperature. (The num­ber of heat stages is factory set for each unit heater.)
If the supply fan is OFF, all stages of electric heat are turned off.
If the fan is ON, the control determines if the system is in morning warm-up. If it is, the return-air sensor is read and compared to the Occupied Heating set point. If heat is re­quired, the control calculates the supply-air temperature re­quired to satisfy conditions.
Once the required supply-air temperature has been cal­culated, it is compared to the supply-air temperature to de­termine the number of heat stages required to satisfy con­ditions. The required stages are energized sequentially with 2-second intervals between stages and the heat interlock re­lay is energized. For VAV units, the number of stages turned on is limited by the PIC IGV output.
Once the morning warm-up is completed, heat is not ac­tivated again unless OCCUPIED HEAT has been selected.
100
Loading...