Carrier 38YSA048 SERIES310, 38YSA042 SERIES300, 38YSA036 SERIES300 Installation Guide

H_.AllI_I &CO01JI_G
Visit www.camer.com
Installation and Start-Up Instructions
NOTE: Read the entire instruction manual before starting the
installation.
This symbol --4 indicates a change since the last issue.
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage, Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations. Have fu'e extinguisher available. Read these instructions thor-
oughly and follow all warnings or cautions included in literature
and attached to the unit. Consult local building codes and National
Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety-alert symbol _.
When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU- TION. These words are used with the safety-alert symbol. DAN- GER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which
could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installtion, reliability, or operation.
Before installing, modifying, or servicing system, main elec-
trical disconnect switch must be in the OFF position. There
may be more than 1 disconnect switch. Lock out and tag
switch with a suitable warning label, Electrical shock can cause personal injury or death.
INSTALLATION RECOMMENDATIONS
NOTE: In some cases noise in the living area has been Iraced to gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where unit
operation sounds may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate to capacity of unit.
3. Run refrigerant tubes as directly as possible by avoiding unnecessary tarns and bends.
4. Leave some slack between structure and unit to absorb vibration.
5. When passing refrigerant tubes through the wall, seal opening
with RTV or other pliable silicon-based caulk. (See Fig. 2.)
38YSA
Split-System Heat Pump
A98516
Fig. 1--Model 38YSA
6. Avoid direct tubing contact with water pipes, duct work, floor
joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing.
(See Fig. 2.)
8. Ensure that tubing insulation is pliable and completely sur- rounds vapor tube.
9. When necessary, use hanger straps which are 1 in. wide and
conform to shape of tubing insulation. (See Fig. 2.)
10. Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation.
When outdoor unit is connected to factory-approved indoor unit, outdoor unit contains system refrigerant charge for operation with indoor unit of the same size when connected by 15 ft of field-supplied or factory accessory tubing. For proper unit opera- tion. check refrigerant charge using charging information located
on control box cover. IMPORTANT: Maximum liquid line size is 3/8-in. O.D. for all
residential applications including long line.
IMPORTANT: Always install a liquid-line filter drier. Refer to Product Data Digest for appropriate part number. Obtain filter
drier from service parts or your distributor or branch.
INSTALLATION
Step l_heck Equipment and Job Site
UNPACK UNIT Move to final location. Remove carton taking care not to damage
unit.
Manufacturer reserves the right to discont_lue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 101 Catalog No. 533-80022 Pnnted in U.S.A.
Form 38YSA-4SI
1 02-02 Replaces: 38YSA3S}
Pg
NOTE:Avoidcontactbeiween tubingandstmctum
OUTDOOBWALL-- INDOOBWAL 7
KNOCKOUTSiN BASEPAN
12)PLACES
CAULK_ LIQUIDTUBE
SULATION
.._ L-..VAPOR TUBE
THROUGHTHE WALL
E_\ j-- INSULATION
i _VAPOR TUBE
k #•
1 MIN. _ _ _
LIQUtDTUBE
SUSPENSION
A94028
Fig. 2--Connecting Tubing Installation
INSPECT EQUIPMENT
F'de claim with shipping company prior to installation if shipment
is damaged or incomplete. Locate unit rating plate on unit comer panel. It contains information needed to properly install unit. Check rating plate to be sure unit matches job specifications.
Step 2--Install on a Solid, Level Mounting Pad
If conditions or local codes require the unit be attached m pad, tie down bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit mounting patternin Fig. 3
to determine base pan size and knockout hole location.
On rooftop applications, mount on level platform or frame 6 in. above roof surface.. Place unit above a load-hearing wall and isolate unit and tubing set from structure. Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications.
Roof mounted units exposed to winds above 5 mph may require wind baffles to achieve adequate defrost. Consult Low-Ambinnt
Guideline for wind baffle construction.
NOTE: Unit must be level to within _+ 2 ° (_+3/8 inJft) per
compressor manufacturer specifications.
A
VIEW FROM TOP
83/16 _
A97548
Dimensions (in.)
MINIMUMMOUNTING
UNIT LOCATIONS
SIZE
PAD DIMENSIONS
Support Snow
Feet Stand
024-042 4 9-3/4
048 5-5/16 11-13/16
26 X 32 31 X 35
34X42 36X46
TIEDOWN KNOCKOUT
A B
Fig. 3_Mounting Unit to Pad
Step 4-----Operating Ambients
The minimum outdoor operating ambient in cooling mode is 55°F,
and the maximum outdoor operating ambient in cooling mode is
125°F. The maximum outdoor operating ambient in beating mode
is 66°F.
Step 5_Elevate Unit
IriX[,-_._
Accumulation of water and ice in base pan may cause
equipment damage.
Elevate unit per local climate and code requirements to provide clearance above estimated snowfall level and ensure adequate drainage of unit. Fig. 4 shows unit with accessory support feet installed. Use accessory snow stand in areas where prolonged freezing temperatures are encountered. Refer to separate Installa- tion Instructions packaged with accessories.
Step 3_Clearancs Requirements
When installing, allow sufficient space for airflow clearance. wiring, refrigerant piping, and service. Allow 30-in. clearance to service end of unit and 48 in. above unit. For proper airflow, a 6-in. clearance on I side of unit and 12 in. on all remaining sides must
be maintained. Maintain a distance of 24 in. between units.
Position so water, snow, or ice from roof or eaves cannot fall directly on unit.
On rooftop applications, locate unit at least 6 in. above roof surface.
A98533
Fig. 4_Accessory Support Feet
2
Step 6--Thermostatic Expansion Valve
For proper unit operation and reliability, units must be installed with field-supplied hard shutoff TXV. Do not install with evaporator coils having capillary robe metering devices
or pistons.
Due to system design, this unit must be installed with a factory-listed indoor section. Non-approved coils could cause performance and rehahility problems. Refer to pre-sale litera-
ture for approved indoor sections.
The outdoor section is factory equipped with a hard shut-off TXV for metering refrigerant during heating mode. See Fig. 5 and 6 for
location of TXV and sensing bulb. This heat pump must be
matched with an approved indoor fan coil equipped with a hard
shut-off TXV. See Product Data literature for approved indoor units.
Step 7_heck Defrost Thermostat
Check defrost thermostat to ensure it is properly located and securely attached. There is a liquid header with a brass distributor and feeder robe going into outdoor coil. At the end of 1 of the feeder tubes, there is a 3/8-in. O.D. stub tube approximately 3 in. long. (See Fig. 7.) The defrost thermostat should be located on stub tube. Note that there is only l stub tube used with liquid header,
and on most units it is the bottom circuit.
Step 8--Make Piping Connections
Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death.
Use all service ports and open all flow-control devices, including solenoid valves.
DEFROST
THERMOSTAT
A9_17
Fig. 7--Defrost Thermos_t Location
To prevent damage to unit or service valves observe the following:
Use a brazing shield.
Wrap service valves with wet cloth or use a heat sink
material.
Outdoor units may be connected to indoor section using accessory tubing package or field-supplied refrigerant grade tubing of correct size and condition. For tubing requirements beyond 50 It, substan- tial capacity and performance losses can occur. Following the recommendations in the Residential Split System Long-Line
Application Guideline will reduce these losses. Refer to Table 1 for field tubing equivalent fine length. Refer to Table 2 for
accessory requirements.
o'o og, LocK7
"_" SUCTION TU
8 O'CLOCK
7/aIN.OD & SMALLER
Fig, 5--Positioning of Sensing Bulb
SENSING
4 O'CLOCK
LARGER THAN 7/sIN. OD
A81032
SENSING BULB---_
STRAINER TX_
A96433
Fig. 6_TXV Location on Outdoor Section
3
Table 1--Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (In.)
UNIT LIQUID VAPOR VAPOR (LONG LINE)
SIZE Connection Diameter Tube Diameter Connection Diameter Tube Diameter Connection Diameter Tube Diameter
024 3/8 3/8 5/8 5/8 5/8 3/4
030, 036 3/8 3/8 314 3/4 3/4 7/8 042, 048 3/8 3/8 7/8 7/8 7/8 7/8
NOTES:
1. Tube diameters are for lengths up to 50 ft. For tubing lengths greater than 50 ft, consult Residential Split System L0ng-Line Application Guideline.
2. Do not apply capillaw tube indoor coils to these units.
For buried-line applications greater than 36 in., consult your local distributor.
If refrigerant tubes or indoor coil are exposed to atmosphere, they must be evacuated to 500 microns to eliminate contamination and
moisture in the system.
OUTDOOR UNIT CONNECTED TO FACTORY-APPROVED
INDOOR UNIT
Outdoor unit contains correct system refrigerant charge for opera-
don with indoor unit of same size when connected by 15 ft of
field-supplied or factory-accessory tubing. Check refrigerant charge for maximum efficiency.
REFRIGERANT TUBING
Connect tubing to fittings on outdoor unit vapor and liquid service
valves. (See Table 1.) Use refrigerant grade tubing.
SWEAT CONNECTION
Service valves are closed from factory and ready for brazing. After
wrapping service valve with a wet cloth, tubing set can be brazed
to service valve using either silver bearing or non-silver bearing
brazing material. Consult local code requirements. Refrigerant
tubing and indoor coil are now ready for leak testing. This check
should include all field and factory joints.
IMPORTANT: Check to be certain factory tubing on both indoor
and outdoor unit has not shifted during shipment. Ensure tubes are
not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are
secure and tight.
Step 9_Make Electrical Connections
To avoid personal injury or death, do not supply power to unit with compressor terminal box cover removed.
Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate, Contact local power company for correction of improper voltage. See unit rating plate for recommended circuit
protection device.
NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit rating plate. Do not install unit in system where voltage may fluctuate above or below
permissible limits.
NOTE: Use copper wire only between disconnect switch and
unit.
NOTE: Install branch circuit disconnect of adequate size per
NEC to handleunit starting current.Locatedisconnectwithin sight
from and readily accessible from unit, per Section 440-14 of NEC. ROUTE GROUND AND POWER WIRES
Remove access panel and control box cover to gain access to unit
wiring. Extend wires from disconnect through power wiring hole provided and into unit control box.
Table 2--Accessory Usage
REQUIRED FOR REQUIRED FOR
ACCESSORY LOW-AMBIENT LONG-LINE
Crankcase Heater Yes Yes
Evaporator Freeze Thermostat Yes No
Accumulator No No
Compressor Start Assist
Capacitor and Relay Yea Yes
MotorMaete_ Control,
Low-Ambient Pressure Switch
Liquid-Line Solenoid Valve See Long-Line
Ball Bearing Fan Motor Yes t No
For tubinglinesets between50 and 175 ft. refer to ResidentialSplitSystem Lor_j-LineApplicationGuideline. _:RequiredforLow-AmbientControllerIfollmodulation feature)and MotorMasterControl only.
or Yes No
Wind Baffle See Low-Ambient Instructions No
Support Feet Recommended No
or No Application
Hard Shutoff TXV Guideline
APPLICATIONS APPLICATIONS*
(BELOW 55"F) (OVER 50 FT)
Loading...
+ 8 hidden pages