Carrier 38HDL018, 38HDL024, 38HDL030, 38HDL036, 38HDL048 Installation, Start-up And Service Instructions Manual

...
Page 1
Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ...................1
INSTALLATION ..............................1-6
Step 1 — Complete Pre-Installation
Checks ....................................1
• INSPECT SHIPMENT
• CONSIDER SYSTEM REQUIREMENTS
Step 2 — Rig and Mount Unit .................3
• MOUNTING ON GROUND
• MOUNTING ON ROOF
• RIGGING
Step 3 — Complete Refrigerant Piping
Connections ...............................3
• CHECK ACCURATERt CONTROL
• MAKE PIPING SWEAT CONNECTIONS
• PROVIDE SAFETY RELIEF
Step 4 — Make Electrical Connections ........4
• POWER WIRING
• CONTROL CIRCUIT WIRING
• CONNECTIONS TO DUCT-FREE FAN COIL UNITS
Step 5 — Accessory Installation ..............4
START-UP ...................................7
SERVICE ...................................7-9
MAINTENANCE .............................10
TROUBLESHOOTING ........................11
SAFETY CONSIDERATIONS
Install and servicing air-conditioning equipment can be haz­ardous due to system pressure and electrical components. Only trained and qualified service personnel should installor serv­ice air-conditioning equipment
Untrained personnel may perform basic maintenance such as cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe safety precautions in literature, and on tags and labels attached to unit.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have a fire extinguisher available. Read these instructions thor­oughly.Consult local building codes and National Electrical Code (NEC) for special installation requirements.
INSTALLATION
Before installing or servicing system, always turn off main power to system. There maybe more than one dis­connect switch. Turn off accessory heater power if applicable. Electrical shock can cause personal injury.
Step 1 — Complete Pre-Installation Checks
UNPACK UNIT — Move unit to final location. Remove car­ton from unit, being careful not to damage service valves or grilles.
INSPECT SHIPMENT — File claim with shipping com­pany if shipment is damaged or incomplete. Check unit name­plate to ensure unit matches job requirements.
CONSIDER SYSTEM REQUIREMENTS — Consult local building codes and NEC for special installation requirements.
Allow sufficient space for airflow clearance, wiring, refrigerant piping, and servicing unit. See Fig. 1 and 2. Unit can be mounted on a level pad directly on base legs or mounted on raised pads at support points. See Fig. 2for cen­ter of gravity.
COOLING
Fig. 1 — 38HDL Condensing Unit
38HDL018-060
Light Commercial Condensing Units
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 3a 2a
PC 111 Catalog No. 563-885 Printed in U.S.A. Form 38HDL-2SI Pg 1 1-99 Replaces: 38HDL-1SI
Page 2
UNIT SIZE
38HDL
ABCDEFGHJKLM
OPERATING
WEIGHT
ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm lb kg
018 2-1
1
⁄8638.2 3-015⁄16938.2 1-29⁄16369.9 1-4 406.4 1-117⁄16595.3 1-53⁄16436.6 1-51⁄2444.5 1-81⁄8511.2 1-1 330.2 0-65⁄8168.3 0-111⁄4285.8 0-05⁄815.88 130 58.9
024 2-1
1
⁄8638.2 3-015⁄16938.2 1-29⁄16369.9 1-4 406.4 1-117⁄16595.3 1-53⁄16436.6 1-51⁄2444.5 1-81⁄8511.2 1-1 330.2 0-63⁄4171.5 0-115⁄8295.3 0-05⁄815.88 136 61.6
030 2-1
1
⁄8638.2 3-015⁄16938.2 1-29⁄16369.9 1-4 406.4 1-117⁄16595.3 1-53⁄16436.6 1-51⁄2444.5 1-81⁄8511.2 1-1 330.2 0-63⁄4171.5 0-115⁄8295.3 0-03⁄419.05 161 73.0
036 2-1
1
⁄8638.2 3-015⁄16938.2 1-29⁄16369.9 1-4 406.4 1-117⁄16595.3 1-53⁄16436.6 1-51⁄2444.5 1-81⁄8511.2 1-1 330.2 0-63⁄4171.5 0-115⁄8295.3 0-03⁄419.05 185 83.9
048 3-1
3
⁄16944.6 3-89⁄161131.9 1-51⁄16433.4 1-67⁄16468.3 2- 61⁄2774.7 1-75⁄8498.5 2-55⁄8752.5 2-83⁄16817.6 1-17⁄8352.4 0-81⁄4209.5 0- 4 406.4 0-07⁄822.22 222 100.5
060 3-1
3
⁄16944.6 3-89⁄161131.9 1-51⁄16433.4 1-67⁄16468.3 2- 61⁄2774.7 1-75⁄8498.5 2-55⁄8752.5 2-83⁄16817.6 1-111⁄16347.7 0-81⁄8206.4 0- 37⁄8403.2 0-07⁄822.22 249 112.9
UNIT SIZE
38HDL
MINIMUM MOUNTING PAD DIMENSIONS
Support Feet
ft-in. mm
018,024,030 and 036 1-11 x 3-6 584.2 x 1066.8
048 and 060 2- 0 x 4-2 609.6 x 1270.0
NOTES:
1. Required clearances: With coilfacing wall, allow 69 (156.4mm) minimum clearance on coil side and coil end, and 3 ft (914.4 mm) minimum clearance on compressor end and fan side. With fan facing wall, allow 89 (203.2 mm) minimum clearanceon fanside andcoil end,and 3ft (914.4 mm) minimum clearance on compressor end and coil side.With multi-unitapplication, arrangeunits sodischarge of one does not enter inlet of another.
2. Dimensions in parenthesis are in millimeters.
3. Center of gravity .
Fig. 2 — 38HDL018-060 — Dimensional Drawing
2
Page 3
Step 2 — Rig and Mount Unit
MOUNTING ON GROUND — Mount unit on a solid, level concrete pad. Position unit so water or ice from roof does not fall directly into unit. Accessory stacking kits can be used when units are to be stacked. If conditions or local codes require unit to be fastened to a pad, 6 field-supplied tiedown bolts should be used and fastened through slots provided in unit mounting feet.
MOUNTING ON ROOF — Mount unit on level platform or frame at least 6 in. above roof surface. Isolate unit and tub­ing from structure.
RIGGING
Be sure unit panels are securely in place prior to rigging.
Keep unit upright. Lift unit using sling. Use cardboard or padding under sling, and spreader bars to prevent sling dam­age to unit. See Fig. 3. See Fig. 2 for center of gravity ref­erence. Install unit so coil does not face into prevailing winds. If this is not possible and constant winds above 25 mph are expected, use accessory wind baffle.
NOTE: Accessory wind baffles should be used on all units with accessory low-ambient control.
Units may also be wall mounted using the accessory wall mounting kit.
Step 3 — CompleteRefrigerant Piping Connec­tions —
Outdoor units may be connected to indoor units using field-supplied tubing of refrigerant grade and condi­tion. Do not use less than 10 ft of interconnecting tubing.
DO NOT BURY MORE THAN 36 IN. OF REFRIG­ERANT PIPE IN THE GROUND. If any sectionofpipe is buried, there must be a 6 in. vertical rise to the valve connections on the outdoor unit. If more than the rec­ommended length is buried, refrigerant may migrate to the cooler, buried section during extended periods of sys­tem shutdown. This causes refrigerant slugging and could damage compressor at start-up.
When more than 50 ft of interconnecting tubing and more than 30 ft of vertical lift is used, refer to Part 3 of the Carrier System Design Manual for design details, or contact your local distributor.
If either refrigerant tubing or indoor coil is exposed to at­mospheric conditions for longer than 5 minutes, it must be evacuated to 1000 microns to eliminate contamination and moisture in the system.
Run refrigerant tubes as directly as possible, avoiding un­necessary turns and bends. Suspendrefrigerant tubes so they do not damage insulation on vapor tube and do not transmit vibration to the structure.Also,whenpassingrefrigeranttubes through the wall, seal opening so that vibration is not trans­mitted to structure. Leave some slack inrefrigerant tubes be­tween structure and outdoor unit to absorb vibration. Refer to separate indoor unit installation instructions for addi­tional information.
CHECK ACCURATERt CONTROL — The correct AccuRater (bypass type) refrigerant control is required for cooling system capacity optimization.AnAccuRater device with field-replaceable piston should be supplied with the
indoor unit. Refer toAccuRatermeteringdevicetableinsepa­rate indoor unit installation instructions to determine thecor­rect AccuRater piston size required for the condenser/ evaporator system being installed.
Note that one of 2 types of the AccuRater devices can be found on the indoor unit. See Fig. 4. Do notinterchangecom­ponents between AccuRater device types. Matching of out­door unit with indoor unit may require field replacement of piston. Replace piston, if required, before connecting refrig­erant lines. Piston replacement instructions are included in the indoor unit installation instructions. After system in­stallation is complete, see Refrigerant charging section on page 8 to check and/or adjust refrigerant charge.
The 38HDL018-060 units may also be installedwith units using a thermostatic expansion valve (TXV). If a TXV is used, be sure to remove the piston from the indoor coil. See installation instructions shipped with the TXV for proper po­sitioning and adjustment.
MAKE PIPING SWEATCONNECTIONS — Remove plas­tic caps from liquid and suction service valves. Use refrig­erant grade tubing. Service valves are closed from the fac­tory and ready for brazing.After wrapping the service valve
Fig. 3 — Lifting Unit with Sling
NOTE: Arrow on AccuRater body points in free-flow direction, away from the indoor coil.
Fig. 4 — AccuRater Metering Device Components
TYPE A (BYPASS TYPE)
TYPE B
3
Page 4
with a wet cloth, the tubing set can be brazed to the service valve using either silver bearing or non-silver bearing braz­ing material. Consult local code requirements. Refrigerant tubing and indoor coil are ready for leak testing.
NOTE: Unit is shipped with R-22 full factory charge indi­cated on nameplate.
Pass nitrogen or other inert gas throughpiping while braz-
ing to prevent formation of copper oxide.
To avoid damage while brazing, service valves should be wrapped in a heat-sinking material such as a wet cloth.
When brazing tubing sets to the service valves, a braz­ing shield must be used to prevent damagetothe painted unit surface.
PROVIDE SAFETY RELIEF — A fusible plug is located in unit suction line; do not cap this plug. If local code requires additional safety devices, install as directed.
Step 4 — Make Electrical Connections
Unit cabinet must have an uninterrupted, unbroken elec­trical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected totheunitground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC, ANSI/NFPA (American National Standards Institute/National Fire Protection Association) 70, and local electrical codes. Failure to follow this warning could result in the installer being liable for personal injury to others.
Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation will invalidate any applicable Carrier warranty.
POWER WIRING — Unit is factory-wired for voltage shown on nameplate. Provideadequate,fuseddisconnectswitchwithin sight of unit, readily accessible but out of reach of children. Provision for locking the switch open (off) is advisable to
prevent power from being turned on while unit is being serviced. Disconnect switch, fuses, and field wiring must be in compliance with NEC and applicable local codes. Use mini­mum 60 C wire for field power connection.
Route power wires through opening in the unit side panel and connect in unit control box as shown on unit label dia­gram and Fig. 5 and 6. Unit must be grounded.
CONTROL CIRCUIT WIRING — Control voltage is 24 v. See Fig. 5 and unit label diagram for field-supplied wiring details. Route control wire through opening in the unit side panel to connection in unit control box.
NOTE: For wire runs up to 50 ft (15 m), use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire. For more than 75 ft, use no. 14 AWG insulated wire.
NOTE: Operation of unit on improper line voltage consti­tutes abuse and could affect Carrier warranty. See Table 2. Do not install unit in system where voltage may fluctuate above or below permissible limits.
See Table 2 for recommended fuse sizes. When making electrical connections, provide clearance at unit for refrig­erant piping connections.
Use indoor unit transformer as 24-v (40-va minimum) supply for system as shown in Fig. 5 or use accessory transformer.
Before performing service or maintenance, be sure the
indoor unit main power switch is off and indoor blower
has completely stopped. Failure to do so may result in
electrical shock or injury from rotating fan blades.
CONNECTIONS TO DUCT-FREE FAN COIL UNITS — The 38HDL units are designed for easy match-up to 40QAB, 40QKB, and 40QNB018,024 duct-free fan coils. These units provide 24-v power for the outdoor unit from the fan coil. Connect the Y and C terminals of the indoor unit to the blue and brown wires of the outdoor unit with 20 gage (mini­mum) thermostat wire.
Step 5 — Accessory Installation — Install all unit
accessories per accessory installation instructions prior to start-up.
Do not use accessory Time Guardt II device when com­bining a 38HDL unit with 40QNB indoor units.
When ambient temperature will fall below 55 F, acces­sory low ambient controller is required. When accessorylow ambient controller kit is used, unit should also be equipped with accessory winter start kit and accessory wind baffles.
4
Page 5
Table 1 — Physical Data
UNIT 38HDL 018 024 030 036 048 060 NOMINAL CAPACITY (Btuh) 18,000 24,000 30,000 36,000 48,000 60,000 UNIT OPERATING WEIGHT (lb) 130 136 161 185 222 249 COMPRESSOR Hermetic
Type Copeland Copeland Copeland Tecumseh Copeland Copeland
Scroll Scroll Scroll Reciprocating Scroll Scroll
Model ZR18KC-PFV ZR24KC-PFV ZR28KC-PFV AV5535G ZR47KC-PFV ZR57KC-PFV Oil (oz) Initial/Recharge 25/21 25/21 38/34 54/50 42/38 56/52
OUTDOOR FAN Propeller Type, Direct Drive, Horizontal
Rpm 850 850 850 850 850 850 Diameter (in.)...No. of Blades 18...3 18...3 18...3 18...3 24...3 24...3 Fan Pitch (Deg) 25 27 27 31 24 24 Motor Hp
1
⁄
8
1
⁄
8
1
⁄
8
1
⁄
8
1
⁄
4
1
⁄
4
Nominal Airflow (Cfm) 1720 1720 1720 1720 3900 3900
OUTDOOR COIL Copper Tube, Aluminum Plate Fin
Face Area (sq ft)...No. of Rows 6.1...1 6.1...1.5 6.1...2 6.1...2 12.3...1.5 12.3...1.75 Fins per in. 20 20 20 20 20 20
CONTROLS PRESSURESTAT
SETTINGS
Low Pressure
Cutout (psig) 7±3 Cut-In (psig) 22±5
Fusible Plug 210 F
5
Page 6
LEGEND
C—Contactor (12-va) HC — Heating Control IFM — Indoor-Fan Motor IFR — Indoor-Fan Relay TRANS — Transformer
Field Wiring Factory Wiring
*The IFR and IFM are located in indoor unit on heating-cooling
applications. If accessory IFR is required for cooling-only applic­tions, locate (IFR) in fan coil.
NOTE: Refer to unit wiring label for wire colors: BRN to BLU and C to Y connections.
Fig.5—Typical Control Circuit Connections
Fig. 6 — Line Power Connections
LEGEND
NEC — National Electrical Code TB — Terminal Board
TB Connections Field Wiring
Factory Wiring
6
Page 7
START-UP
Preliminary Checks
1. Check that all internal wiring connections are tight and that barriers, covers, and panels are in place.
2. Make certain field electrical power source agrees with unit nameplate rating.
3. Open all service valves.
LeakT est— Field piping and fan coilmust be leak tested
by pressure method described in Carrier Standard Service Techniques Manual, Chapter 1, Section 1-6. Use R-22 at approximately 25 psig backed up with an inert gas to a total pressure not to exceed 245 psig.
Evacuate and Dehydrate — Field piping and fan coil
must be evacuated and dehydrated by either of the methods described in Carrier Standard Service Techniques Manual, Chapter 1, Section 1-7.
Charge System — Release factory charge into sys-
tem by opening (backseating) liquid and suction line service valves. Add charge amount as required for the total system. Refer to separate indoor unit installation instructions for the required total system charge when connected to the indoor unit.
To Start Unit
NOTE: When using in conjunction with 40QAB, 40QKB, or 40QNB fan coils, refer to start-up instructions included with fan coil for correct start-up procedures.
Be sure that field disconnect is closed. Set room thermo­stat below ambient temperature. Operate unit for 15 min­utes, then check system refrigerant charge. See Refrigerant Charging section on page 8.
Unit compressor starts after a 5-minute delay if equipped with accessory Time Guardt II device.
SERVICE
Before performing recommended maintenance, be sure unit main power switch is off. Failure to do so may result in electrical shock or injury from rotating fan blade.
Outdoor Fan — A reinforced wire mount holds theout-
door fan assembly in place. See Fig. 7 for proper mounting positions.
High-Pressure Relief Valve — Valve is located in
compressor. Relief valve opens at a pressure differential of approximately 450 ± 50 psig between suction (low side) and discharge (high side) to allow pressure equalization.
InternalCurrentandT emperatureSensitiveOver­load —
Control resets automatically when internal com­pressor motor temperature drops to a safe level (overloads may require up to 45 minutes to reset). When an internal overload is suspected of being open, checkby using an ohm­meter or continuity tester. If necessary, refer to Carrier Stand­ard Systems Techniques Manual, Chapter 2, for complete information.
PumpdownProcedure — The system may be pumped
down in order to make repairs on low side without losing complete refrigerant charge.
To pumpdown:
1. Attach pressure gage to suction service valve gage port.
2. Frontseat the liquid line valve.
The 38HDL unitcoilsholdonlythefactory-designated amount ofrefrigerant.Additionalrefrigerantmaycause units to relieve pressure through compressor inter­nal pressure relief valve (indicated by sudden rise of suction pressure) before suction pressure reaches 5 psig. If this occurs, shut offunit immediately, then frontseat the suction valve and remove and recover excess refrigerant following accepted practice.
3. Start unit and run until suction pressure reaches 5 psig.
4. Shut unit off and frontseat suction valve.
5. Depressurize low side of unit and recover refrigerant fol-
lowing accepted practice.
DIMENSIONS (in.)
38HDL018 38HDL024-036 38HDL048-060
0.433 0.709 0.16
Fig. 7 — Condenser Fan Mounting Positions
7
Page 8
Table 2 — Electrical Data
UNIT SIZE
38HDL
V-PH-Hz
OPERATIONAL
VOLTAGE*
COMPRESSOR POWER SUPPLY
Min Max RLA LRA Fan FLA MCA
Max Fuse† or HACR-Type
Ckt Bkr Amps
018
208/230-1-60 187 254
10.7 47.0 .70 14.1 25
024 13.2 59.0 .70 17.2 30 030 15.7 73.0 .70 20.3 35 036 14.2 86.7 .70 18.5 30 048 24.3 131.0 1.45 31.8 50 060 28.6 170.0 1.45 37.2 65
LEGEND
FLA — Full Load Amps HACR — Heating, Air Conditioning, Refrigeration LRA — Locked Rotor Amps MCA — Minimum Circuit Amps per NEC Section 430-24 NEC — National Electrical Code RLA — Rated Load Amps (Compressor)
*Permissible limits of the voltage range at which unit will operate
satisfactorily.
†Time-delay fuse. NOTES:
1. Control circuit is 24 v on all units and requires an external power source.
2. All motors and compressors contain internal overload protection.
3. In compliance with NEC requirements for multimotor and combi­nation load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.
4. Motor RLAvalues are established in accordance with UL (Under­writers’ Laboratories) Standard 465.
Low Pressure Switch — This switch, mounted on the
suction line, has fixed non-adjustable settings. Tocheck pres­sure switch, attach pressure gage to suction service valve gage port. Slowly close liquid shutoff valve and allow compres­sor to pump down. Do not allow compressor to pump down below 2 psig. Compressor should shut down when suction pressure drops to cutout pressure in Table 1, and should re­start when pressure builds up to cut-in pressure shown after accessory CLO (compressor lockout) switch has been reset and accessory Time Guardt II device has completed its tim­ing cycle.
ServiceValves — The servicevalves in the outdoor unit
come from the factory frontseated. This means the refrig­erant charge is isolated from the line-set connection ports. To prevent damage to the valve, use a wet cloth or other acceptable heat sink material on the valve before brazing.
The service valves must be backseated (turned counter­clockwise until seated) before the service port caps can be removed and the hoses of the gage manifold connected. In this position, refrigerant has access from the through out­door and indoor unit. The service valve cannot be field re­paired; only a complete valve or valve stem seal and service port caps are available for replacement.
AccuRaterT (Bypass Type) Device — See Fig. 4
for bypass type AccuRater device components. The piston has a refrigerant metering hole through it.Theretainerforms a stop for the piston in the refrigerant bypass mode and a sealing surface for liquid line flare connection. To check, clean or replace piston:
1. Shut off power to unit.
2. Pump down using Pumpdown Procedure section on
page 7.
3. Remove liquid line flare connection from AccuRater
device.
4. Pull retainer out of body, being careful not to scratch flare
sealing surface. If retainer does not pull out easily, care­fully use locking pliers to remove retainer.
5. Slide piston out by inserting a small soft wire, with small
kinks, through metering hole. Ensure metering hole,seal­ing surface around piston cones, and flutedportion of pis­ton are not damaged.
6. Clean piston refrigerant metering hole.
7. Replace retainer O-ring before reassembling AccuRater device (O-ring part no. 99CC501052).
Refrigerant Charging
To prevent personal injury, wear safety glassesandgloves when handling refrigerant. Do not overcharge system — this can cause compressor flooding.
NOTE: Do not vent or depressurize unit refrigerant toatmos­phere. Remove and recover refrigerant following practice.
SUPERHEAT METHOD (COOLING, NON-TXV) — To check and adjust charge during cooling season, use Tables 3 and 4 and the following procedure:
1. Operate unit a minimum of 15 minutes before checking charge.
2. Measure suction pressure by attaching a gage to suction valve service port.
3. Measure suction line temperature by attaching a service thermometer to unit suction line near suction valve. In­sulate thermometer for accurate readings.
4. Measure outdoor coil inlet-air dry bulbtemperaturewith a second thermometer.
5. Measure indoor coil inlet-air wet bulb temperature with a sling psychrometer.
6. Refer to Table 3. Find air temperature entering outdoor coil and wet-bulb temperature entering indoor coil. At this intersection, note the superheat temperature.
7. Refer to Table 4. Find superheat temperature and suc­tion pressure and note suction line temperature.
8. If unit has higher suction line temperature than charted temperature, add refrigerant until charted temperature is reached.
9. If unit has lower suction line temperature than charted temperature, remove and recover refrigerant until charted temperature is reached.
10. If air temperature entering outdoor coil or pressure at suction valve changes, charge to new suction line tem­perature indicated on chart.
NOTE: The above procedure is independent of indoor air quantity.
8
Page 9
SUBCOOLING METHOD (COOLING, TXV) — To check and adjust charge during cooling season, use Table 5 and the following procedure:
1. Operate unit a minimum of 15 minutes before checking charge.
2. Measure liquid line temperature near liquid line service valve, and measure liquid pressure at liquid line service valve. Use a digital thermometer for all temperature measurements. DO NOT use mercury or dial-type thermometers.
3. Refer to Table 5. Find temperature point at which the re­quired subcooling temperature intersects the measured liq­uid line pressure.
4. If the measured liquid line temperature does not agree with the required liquid line temperature, ADD refriger­ant to lower the temperature, or REMOVE refrigerant to raise the temperature (allow a tolerance of±3F).
Table 3 — Superheat Charging Table
(Superheat Entering Suction Service Valve)
OUTDOOR
TEMP (F)
INDOOR COIL ENTERING AIR (F) WB
50 52 54 56 58 60 62 64 66 68 70 72 74 76
55 9 12141720232629323537404245 60 7 10121518212427303335384043 65 * 6 10 13 16 19 21 24 27 30 33 36 38 41 70 * * 71013161921242730333639 75 * * * 6 9 12 15 18 21 24 28 31 34 37 80 ****581215182125283135 85 ******811151922263033 90 ******59131620242731
95 *******6101418222529 100 ********81215202327 105 ********5913172226 110 *********611152025 115 **********8141823
LEGEND
WB — Wet Bulb *Do not attempt to charge system under these conditions or refrig-
erant slugging may occur.
Table 4 — Required Suction-Tube Temperature (F)
(Entering Suction Service Valve)
SUPERHEAT
TEMP (F)
SUCTION PRESSURE AT SERVICE PORT (psig)
61.5 64.2 67.1 70.0 73.0 76.0 79.2 82.4 85.7
0 35 36 39 41 43 45 47 49 51 2 37 39 41 43 45 47 49 51 53 4 39 41 43 45 47 49 51 53 55 6 41 43 45 47 49 51 53 55 57
8 43 45 47 49 51 53 55 57 59 10 45 47 49 51 53 55 57 59 61 12 47 49 51 53 55 57 59 61 63 14 49 51 53 55 57 59 61 63 65 16 51 53 55 57 59 61 63 65 67 18 53 55 57 59 61 63 65 67 69 20 55 57 59 61 63 65 67 69 71 22 57 59 61 63 65 67 69 71 73 24 59 61 63 65 67 69 71 73 75 26 61 63 65 67 69 71 73 75 77 28 63 65 67 69 71 73 75 77 79 30 65 67 69 71 73 75 77 79 81 32 67 69 71 73 75 77 79 81 83 34 69 71 73 75 77 79 81 83 85 36 71 73 75 77 79 81 83 85 87 38 73 75 77 79 81 83 85 87 89 40 75 77 79 81 83 85 87 89 91
9
Page 10
MAINTENANCE
Before performing recommended maintenance, be sure unit main power is off. Failure to do so may result in electrical shock or injury from rotating fan blades.
Lubrication
FAN-MOTOR BEARINGS — Oiling holes are provided at each end of the condenser-fanmotor. Remove fan motor and lubricate motor with 32 drops (16drops per hole) of SAE-10 (Society of Automotive Engineers) non-detergent oil at in­tervals described below:
• Annually, when environment is very dirty, ambient tem­perature is higher than 105 F, and average unit operating time exceeds 15 hours a day, or
• Every three years, when environment is reasonably clean, ambient temperature is less than 105 F, and unit operating time averages 8 to 15 hours per day, or
• Every 5 years when environment is clean, ambient tem­perature is less than 105 F, and unit operating time aver­ages less than 8 hours per day.
COMPRESSOR — Compressor contains factory oil charges; replace oil when lost. See Table 1 for oil recharge and refer to Carrier Standard Service Techniques Manual, Chapter 1, pages 1 to 21 for oil recharging procedure. See Table 6 for recommended compressor oils.
Cleaning Coils — Coil should be washed out with wa-
ter or blown out with compressed air. Note that the blow­thru design causes dirt and debris to build up on the inside of the coils.
Clean coil annually or as required bylocation and outdoor air conditions. Inspect coil monthly and clean as required. Fins are NOT continuous through coil sections. Dirt and de­bris may pass through the first section, become trapped be­tween the rows of fins, and restrict condenser airflow. Use a flashlight to determine if dirt ordebris has collected between coil sections. Clean coil as follows:
1. Turn off unit power.
2. Use a garden hose or other suitable equipment to flush
coil from the outside to remove dirt. Be sure to flush all dirt and debris from drain holes in the base of unit. Fan motors are waterproof.
Table 5 — Required Liquid Line Temperature (F) (At Service Valve)
REQUIRED
SUBCOOLING (F)
LIQUID PRESSURE AT SERVICE VALVE (PSIG)
134 141 148 156 163 171 179 187 196 205 214 223 233 243 253 264 274 285 297 309 321 331 346 359
0 76 79 82 85 88 91 94 97 100 103 106 109 112 115 118 121 124 127 130 133 136 139 142 145
5 71 74 77 80 83 86 89 92 95 98 101 104 107 110 113 116 119 122 125 128 131 134 137 140 10 66 69 72 75 78 81 84 87 90 93 96 99 102 105 108 111 117 120 123 126 129 129 132 135 15 61 64 67 70 73 76 79 82 85 88 91 94 97 100 103 106 109 112 115 118 121 124 127 130 20 56 59 62 65 68 71 74 77 80 83 86 89 92 95 98 101 104 107 110 113 116 119 122 125 25 51 54 57 60 63 66 69 72 75 78 81 84 87 90 93 96 99 102 105 108 111 114 117 120
Table 6 — Recommended Compressor Oils
RECOMMENDED
OIL
UNIT 38HDL
018 024 030 036 048 060
3GS
Calumet RO-15
Sontex 200LT •••
•
•
••
10
Page 11
TROUBLESHOOTING
TROUBLESHOOTING CHART — COOLING CYCLE
11
Page 12
Copyright 1999 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 3a 2a
PC 111 Catalog No. 563-885 Printed in U.S.A. Form 38HDL-2SI Pg 12 1-99 Replaces: 38HDL-1SI