Carrier 38EN User Manual

Page 1
38EN
HEATING A COOLING
Installation and Start-Up Instructions
SAFETY CONSIDERATIONS
Installing and servicing air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install or service air conditioning equipment.
Untrained personnel can perform basic maintenance, such as cleaning and replacing filters. All other opera tions should be performed by trained service personnel. When working on air conditioning equipment, observe precautions in literature and on tags and labels attached to unit.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instruc tions thoroughly. Consult local building codes and National Electrical Code (NEC) for special installation requirements.
A WARNING
Before installing or servicing system, always turn
off main power to system. There may be more than one disconnect switch. Turn off accessory heater power if applicable. Electrical shock can cause personal injury.
Air-Cooled Condensing Units
#

Step 1 — Check Equipment and Jobsite —

Install on a solid, level mounting pad. It is not recom mended that unit be attached to pad using tiedown bolts. Fasten unit to pad using holes provided in unit mounting
feet. See Fig. 1.
When installing, allow sufficient space for airflow
clearance, wiring, refrigerant piping and service. Main tain a minimum of 4 ft clearance from obstructions above and 18 in. on 3 sides of unit (12 in. on fourth side). Main tain a distance of 24 in. between condensing units. Posi tion so water or ice from roof or eaves cannot fall directly on unit.

Step 2 — Replace Indoor AccuRater™ Piston, if required.

REPLACE ACCURATER REFRIGERANT CON TROL PISTON in the indoor coil, if required, before connecting refrigerant lines. Refer to Table 2 for proper piston size.
Step 3 — Make Piping Connections — Outdoor units may be connected to indoor sections using Carrier accessory tubing package (refer to Service Data) or field-supplied tubing of refrigerant grade, correct size (see Table 1) and condition. For tubing requirements beyond 50 ft, obtain information from your local distributor.
Outdoor Units Connected to Carrier-Approved Indoor Units — Outdoor units contain correct system
refrigerant charge for operation with indoor unit of the same size when connected by 25 ft of field-supplied or
Carrier accessory tubing. Check refrigerant charge for maximum efficiency (see Refrigerant Charging, page 4 and Service Data).
Certified dimension drawings avaiiabie upon request
Fig. 1 — Dimensions, Connections and
Mounting Pad (Refer to Table 1)
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without Incurring obligations.
Book И |4 PC101 Catalog No 563-825 PrintedinUSA Form38EN-3SI Pg 1 485 12-84 Replaces: 38EN-2SI
Tab |3a|2a
Pnr rAnlar^AmArtt Млтв iiea
Page 2
^ 38EN
HEATING A COOLING
Air-Cooled Condensing Units
Table 1 — Physical Data (Refer to Fig. 1)
MODEL 38EN OPER WT (lb)* REFRIGERANT
Control
COND FAN
Air Discharge Air Qty (cfm) Motor Rpm (60 Hz)
COND COIL (fins/in.)
Tube Diam Rows Face Area (sq ft)
Outer Row Inner Row
DIMENSIONS (ft-in.)
Diameter A Height B
CONN (in. ODF)
Suction Liquid
REFRIG LINES (in. ODF)
Suction Liquid
*Add 10 lbs for louvered casing (If so equipped) Weight Increases slightly
with addition of any accessories
t38EN048,060 require a I'/s-ln suction line for optimum performance. A
%- X 1'/8-in connection adapter accessory (Carrier Part No. 28AU900061) is available If a %-in accessory tubing package is used, expect a 3% capacity loss
015 018
94 111
024 030 036
142
111
AccuRater'“ (Installed In I.D. Coil)
Propelle
ir Type, Direct Drive
1950 1650
20
% in -
8 15
1- 5'/2
2- 1
Compatible F
%
Vertical
2800 1 4800
12 37
1-9’/2
tting (Suction and Liquid)
% 1 % 1 '/e 1 1’/at
042 048
146 182 200
22
1100
'/2
in , E-coil
1
17 11
2-7
%
%
%
060
228
16
2
17.11
2-5'/4
RETAINER
FLARE CONNECTION
Fig. 2 — AccuRater (Bypass Type)
Components
CUT HERE-J
FLARE NUT
,0-RING

A CAUTION

DO NOT BURY MORE THAN 3 FT OF RE FRIGERANT TUBING IN GROUND. If any section of tubing is buried, there must be a 6-in. vertical rise to the valve connections on the outdoor unit. If more than the recommended length is buried, refrigerant may migrate to cooler buried section during extended periods of unit shutdown, causing refrigerant slugging and possibly compressor damage at start-up.

Table 2 — AccuRater™ Selection Chart

COND UNIT
38EN
(1- and 3-Ph)
015-0 018-0 024-0 030-0 030-2 036-0 042-0 048-0 060-0 060-1
Factory-installed piston Obtain replacement pistons through local Carrier distributor
018 024
015
46
■ 52 52 TXV
57
_
__
— — 78

Fig. 3 — Repair of Mechanicai Connection

CONNECT REFRIGERANT LINES to fittings on outdoor unit suction and liquid service valves (Fig. 1). Unit Compatible Fittings permit mechanical (quick­connect) or sweat connections.
Models 38EN048,060 — When using 1-1/8-in. field­supplied refrigerant suction line, sweat-connect suction line to 1-1/8-in. end of required connection adapter.
Be sure to provide a heat sink at the service valve to prevent damage during sweating operation. Connect 3/4-in. end of adapter to unit suction line Compatible
Fitting. Connect liquid refrigerant line to unit. When a 7/8-in. field-supplied suction line is used, provide a field­supplied 3/4-in. to 7/8-in. suction line adapter (not necessary if 38LS accessory tubing is used).
ACCURATER'“ PISTON NO.
Evap Size (Coil or Fan Coil)
036 042 048 060
030
TXV
-
57
m
631
TXV
TXV
65
70 TXV
m
060
78 TXV
_
98
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Bookll |4 PC101 Catalog No 563-825 PrIntedInUSA Form38EN-3SI Pg 2 12-84 Replaces: 38EN-2SI
Page 3
38EN
HEATING A COOLING
Mechanical Connection — Mate one set of connec
tions at a time.
1. Loosen nut on Compatible Fitting one turn. Do not remove.
2. Remove plug and be sure O-ring is in the groove inside the Compatible Fitting.
3. Cut tubing to correct length, deburr and size as necessary.
4. Insert tube into Compatible Fitting until it bottoms.
Tighten nut until it bottoms on shoulder of fitting or valve. Keep tube bottomed in Compatible Fitting
while tightening nut.

A CAUTION

If undersized, damaged or elliptically-shaped
tubing is used when making Compatible Fitting,
leaks may result.
Sweat Connection — Use refrigerant grade tubing.
1. Remove locking nut, rubber O-ring and Schrader core
and cap from valve service port.
2. Cut tubing to correct length, deburr and size as necessary.
3. Insert tube in Compatible Fitting until it bottoms. NOTE: Wrap top and bottom of service valves in wet
cloth to prevent damage by heat. Solder with low­temperature (430 F) silver alloy solder.
4. Replace Schrader core and cap.
5. Evacuate or purge system using field-supplied refrigerant.
Air-Cooled Condensing Units

Compatible Fitting Repair

MECHANICAL CONNECTION — Frontseat unit service valves. Relieve refrigerant pressure froni tubing. Back off locknut from Compatible Fitting onto tube. Cut fitting between threads and O-ring. See Fig. 3. Remove tubing section remaining in threaded portion of fitting. Discard locknut.
Clean, flux and insert new tube end into remaining
portion of Compatible Fitting. Wrap valve in wet rag to
prevent damaging factory-made joints. Heat and apply
low-temperature (430 F) solder. SWEAT CONNECTION — Frontseat unit service
valves. Relieve refrigerant pressure from tubing. Clean and flux area around leak. Repair, using low-temperature (430 F) solder.
Evacuate or purge evaporator coil and tubing system.
Add refrigerant charge. See Refrigerant Charging in
structions, page 4.
Step 4 — Make Electrical Connections — Be sure field wiring complies with loeal and national fire, safety and electrical codes, and voltage to system is within limits shown in Table 3. Contact local power company for correction of improper line voltage.
NOTE: Operation of unit on improper line voltage con stitutes abuse and could affect Carrier warranty. See Table 3. Do nOt install unit in system where voltage may fluctuate above or below permissible limits.
See Table 3 for recommended fuse sizes. When making electric connections, provide clearanee at unit for refrigerant piping connections.
Table 3 — Electrical Data (60 Hz)
OUTDOOR UNIT 38EN
015-3 018-3 024-3 030-3 036-3 042-3
048-3 060-3
030-5 036-5 042-5 048-5 060-5
036-6 042-6 048-6 060-6
FLA — Full Load Amps HACR — Heating, Air Conditioning, Refrigeration LRA — Locked Rotor Amps MCA — Minimum Circuit Amps RLA — Rated Load Amps
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Bookh |4 PC101 Catalog No 563-825 PrintedinUSA Form38EN-3SI Pg3 485 12-84 Replaces: 38EN-2SI
V/PH
208-230/1
230/1
208-230/3Í
460/3Í
OPER VOLTS*
Max Min
254 197
254 197
254 187
508 414
COMPR FAN
LRA
36 0 6.9 53 0 10 1
65.0
88.0 97 0 21 0
118.0 24.2
110.0
150.0
70.0 103 2 1 78 0 128 90 0 15.4
105.0 18.3
136.0 20.6 39 0 6 1 1 1
45.0
35.0 49 0 10.4
RLA
130 187
25.0
35.3
83 8 8
'Permissible limits of the voltage range at which unit will operate
satisfactorily. (Time-delay fuse (3-Phase available only with base unit and SM option unit
NOTE: Control circuit is 24 v on all units and requires external power source
FLA
1.6
1.6
1.6
2.1 2 1
2.5 32 7
2.5
2.5
2.1 18.1
2.5
2.5
2.5
1 3 1 3
1.3
MCA
100
14.0 20
17.9 24 6
28.4 45
33 8 46 7
14.9 25
21.7 35
25.4 40
28.2 45 87
11.7
12.3
14.3
MAX FUSEf OR
HACR TYPE
CKT BKR AMPS
15 30
35 50
50 60
30
15 20 20 20
Page 4
38EN
HEATING A COOLING
INSTALL BRANCH CIRCUIT DISCONNECT PER NEC of adequate size to handle unit starting current. Locate disconnect within sight from and readily acces sible from unit, per Section 440-14 of National Electrical Code (NEC).
ROUTE LINE POWER LEADS — Extend leads from disconnect through power wiring hole provided (see Fig. 1) and into unit splice area. Remove control box cover to gain access to unit wiring.
CONNECT GROUND LEAD AND POWER WIRING — Connect ground lead to ground connection in control
box for safety. Then connect power wiring. See Fig. 4. Splice line power leads to yellow and black pigtails. Use wire nuts and tape at each connection. Connect unit wiring to copper power wiring only.
CONNECT CONTROL POWER WIRING — Route 24-v control wires through control wiring hole and connect to pigtails supplied with unit (Fig. 1). Splice control leads to brown and blue pigtails on all units. See Fig. 5.
Use furnace or fan coil transformer as 24-v (40-va minimum) supply for system as shown in Fig. 5, or use accessory transformer (refer to Service Data).
NOTE: Some 38EN units are equipped with a fan time delay. This permits indoor fan to continue to operate for 90 seconds, which provides additional cooling after compressor has eyeled off. Refer to separate installation instructions packaged with fan time delay (shipped with unit).

A WARNING

Air-Cooled Condensing Units

Refrigerant Charging (Refer to Fig. 6 and Table 5)

A CAUTION

To prevent personal injury, wear safety glasses and gloves when handling refrigerant. Do not overcharge system. This can cause compressor flooding.
I-PHASE
-GROUND LEAD
CONN. TO DISCONNECT
PER NEC
r__________________
3-PHASE CONN. TO
DISCONNECT PER NEC
--GROUND LEAD --J-SGROUNDING LUG
-C®1grounding lug
- — BLK
----------------
YEL-
1- PHASE
COND UNIT
BLK -
BLU-
• YEL -
To avoid personal injury, be sure indoor blower has stopped before attempting service
or maintenance.

Step 5 — Start-Up

1. Energize crankease heater a minimum of 24 hours before starting unit. To energize heater only, set thermostat at OFF position and close electrical dis connect to outdoor unit.
2. Backseat (open) liquid and suction line serviee valves.
3. Set thermostat selector switch at OFF.
4. Set room thermostat at desired temperature. Be sure set point is below indoor ambient temperature.
5. Close electrieal diseonnects to energize system.
6. Set room thermostat at COOL and fan switch at FAN
or AUTO, as desired. Operate unit for 15 minutes. Check system refrigerant charge. See Refrigerant Charging, below.
Motors and controls are designed to operate satis­faetorily in the voltage range shown in Table 3. If necessary to use manifold gages for servicing, refer to Carrier Standard Service Techniques Manual, Chapter 1, Refrigerants, page 1 - 5, Fig. 8, for bypass method of returning charge to system. Removal of liquid line eharging hose without following these precautions could result in some loss of charge.
fr-i— SPLICE CONNECTIONS
--------------
--------------
FIELD WIRING
FACTORY WIRING
3-PHASE COND UNIT
Fig. 4 — Line Power Connections
Table 4 — Service Data
MODEL
38EN
015300 015310 AK8515E 018300 018310
024300, H21B243ABCA
030300 030320
036300, H21A373ABCA
042300
048300 PC5316BD 76
060300,
030500 036500 H21A373DBD 042500 H21A463DBD 50
048500 PY5316AD
060500, PY6716AF
036600 042600 048600
060600,
'Factory refrigerant charge is adequate when indoor unit and outdoor unit
are the same size and are connected with 25 ft or iess of fieid-suppiied tubing of recommended size or Carrier accessory tubing
COMPRESSOR
REK3-0125-PFV H21B193ABCA
RES3-0175
310
H21A313ABCA MD3215GG
320
H21A463ABCA 50 47
PC6716AG 76 PC6716AG
310
H21A313DBD 40
PY6716AF 76
510
H21A373DBE H21A463DBE PH5316AD PH6716AF
610
PH6716AF
OIL
CHARGE (oz)
Recharge
Initial
24 17 40 37 24 20 40
40 46
50
76
50 47
76 76
50 50 76 76 76 62
R-22
CHG* (lb)
20 15 3 20
37
37 44 47
62 62 62
37 47 7 20
62 62 62
47 47 62 62
3 60 3 60 1650
3 70 3 80
5 60 6 70 5 80
7 20 7 60 9 60
12.50 5 60
5 80 7 60
9 60
12.50 5 80
7 20 7 60 9 60
12 50
OUTDOOR
FAN RPM
1100
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book|1 |4 PC 101 Catalog No. 563-825 PrintedinUSA Form38EN-3SI Pg4 485 12-84 Replaces: 38EN-2SI
Page 5
38EN
HEATING A COOLING
THERMOSTAT SUBBASE
THERMOSTAT SUBBASE
ARRANGEMENT B-ONE TRANSFORMER (COOLING AND ONE-STAGE HEATING)
THERMOSTAT SUBBASE
99TZ90036I20
Air-Cooled Condensing Units
Table 5 — 38EN Chargemaster® Charging
OUTDOOR
TEMP
Chart (AccuRater™ System)
EVAPORATOR TEMPERATURE (F)
(F)
60 32 40 51 62 30 38 39 64 28 37 47 60
66 68 70 72 31 39 50 74 76 78 80 82
86 88 90 92 94 96
98 100 102 104 39 46 106 45 51 108 43 110 41 112 114
21 I 25 I 28 I 31 I 34 I 37 I 4045 | 48
Suction Line Temperature ^)
27
35 45 57 34 43 54 32 41 52
67 64
61 72 30 37 48 58 69 29 36 27 35 26 33 42
46 56
66
44 54 63
52
61
75ii 72::
32 40 50 59 68
35 34 33
46
55 63 73
44
53 61 42 51 41
49 57 39 47
38
45 53 61
44
36
42
41
59 68
55 63 72
51 59 49 57 48 55
29 37
Example
70 81
65 75
53 61
49 57 47 46
85
78 90
86
83 70 80 67 77 65 75 63
73
70 59 68
65 55 63 53 61 50
59
(COOLING AND TWO-STAGE HEATING)
*IFR and IFM are located In furnace on heating-cooling applica
tions If accessory IFR is required for cooling-only applications, locate (IFR) in fan coil
C — Contactor (12-va)
HC — Heating Control IFM — Indoor Fan Motor IFR — Indoor Fan Relay
Trans — Transformer
NOTE Refer to unit wiring label for wire colors: C to G andCto Y
connections
________ ________

Fig. 5 — Control Circuit Connections

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book II 14 PC 101 Catalog No 563-825 Printed inUS A Form38EN-3SI Pg 5 12-84 Replaces: 38EN-2SI
Tah li^alPa
Field Splice Field Wiring Factory Wiring
Fig. 6 — 38EN Charging Chart
(AccuRater™ System)
For renlacement IteniA iiao ('.ntrlar Parte
Page 6
38EN
HEATING A COOLING
Air-Cooled Condensing Units
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.
Bookll 14 PC 101 Catalog No 563-825 PrintedinUSA Form 38EN-3SI Pg6 485 12-84 Replaces; 38EN-2SI
For reolacement items use Carrier Soecified Parts
Loading...