Installation and servicing of air conditioning
equipment can be hazardous due to system pressure
and electrical components. Only trained and quali
fied service personnel should install, repair or
service air conditioning equipment.
Untrained personnel can perform basic mainten
ance functions of cleaning coils and filters and re
placing filters. All other operations should be
performed by trained service personnel. When
working on air conditioning equipment, observe
precautions in the literature, tags and labels attached
to the unit and other safety precautions that may
apply.
Follow all safety codes. Wear safety glasses and
work gloves. Use quenching cloth for brazing opera-
tions. Have fire extinguisher available for all brazing
operations.
WARJ^iKG; Before performitsg $ervice or
maiatesjaBce operatjojjs vam off
nsBiirt po’»er swiich. to indoor »nfi and outdoor
unit. Turn, off accessory heater poTser switch if
applicable- Electrical siioolc could cause persortal irgnry.
Table 1 — Physical Data (Refer to Fig. 1.)
MODEL 38EC
OPER WT (lb)
DIMENSlbNS (ft-in.)
Diameter A
Height B
CONNECTIONS (in.)
Suction (DDF)
Liquid (DDF)
REFRIG LINES
Suction (in DDF)
Liquid (in DDF)
*Fora1-1/8in suction line on 38EC048,060, a 3/4-in x 1-1/8 in suction
valve connection adapter is available as an accessory See Table 3
018 024
116 130137165
2-2-3/8 1 2-8
INSTALLATION
Step 1 — Check Equipment and Jobsite
UNPACK UNIT — Move to final location. Slide
from carton taking special care not to damage serv
ice valves or grilles.
INSPECT EQUIPMENT — File claim with ship
ping company if damaged or incomplete.
COMPLETE OR CONSIDER SYSTEM RE
QUIREMENTS before installation:
Consult local building codes and National Elec
trical Code (NEC) for special installation
requirements.
When installing, allow sufficient space for airflow
clearance, wiring, refrigerant piping and service.
Maintain a minimum of 4 ft clearance from obstruc
tions above and 18 in. on sides of unit. Maintain a
distance of 24 in. between condensing units. Posi
tion so water from roof or eaves does not flow
directly on unit.
Install on a solid, level mounting pad. It is not
necessary to attach unit to pad but if desired or
required by local code, position tiedown bolts in
pad. Fasten unit to pad using 2 holes provided in unit
base. See Fig. 1.
4-0 OVERHEAD SPACE REQUIRED
FOR SERVICE AND AIRFLOW
LIQUID VALVE SERVICE PORT
CONDENSER AIRFLOW
liDIAM HOLE
FOR POWER
WIRING
r-6 AIRFLOW
AND SERVICE
CLEARANCE
SUCTION VALVE SERVICE PORT
orator i^^if^field replacement of piston. Refer to
Table 2. Replace piston, if required, before connect
ing refrigerant lines. Piston replacement instructions
are ineluded in evaporator installation book. After
system installation is complete, use Charging Chart
to check and/or adjust refrigerant charge.
Condensing Units Connected to Carrier-Approved
Evaporators — Condensing units contain correct
system refrigerant charge for operation with evap
orator of the same size when connected by 25 ft
of field-supplied or Carrier accessory tubing.
Check refrigerant charge for maximum efficiency
(see Refrigerant Charging, page 6).
Table 2 — Optimization Chart
(Outdoor air design temperature. db-F.
100 F and below)
COND
UNIT
38EC
018
024
030
036
042
048
060
014018
—
——
—
——
——
———
—
Factory-installed piston Obtain replacement pistons thru
local Carrier distributor
ACCURATER™ piSTON NO.
Evap Size (Coil or Fan Coil)
024030
46
—
—
TXV
52
SS
—
——
—
—
57
63
—— ■■■■
——
036
—
TXV
65
67
--
042
048060
——
———
_
TXV
70
TXV
7678
—
S382
— ■ ; 64
—
—
TXV
*CONCRETE PAD SHOULD WEIGH I5 TO 2 TIMES WEIGHT OF UNIT
Certified dimension drawings available on request
Fig. 1 — Dimensions. Connections and
Mounting Pad (Refer to Table 1.)
Carrier Cooling System Capacity Optimization —
AccuRater™ (bypass type) refrigerant control, with
field-replaceable piston (see Fig. 2), is supplied on
evaporator. Use Optimization Chart, Table 2, to
find AecuRater piston size required for eondenser/
evaporator system being installed. Pistons are correetly sized for an evaporator of the same capacity as
the condensing unit, so piston change is not neces
sary. Mix-matching of condensing unit with evap-
Fig. 2 — AccuRater (Bypass Type)
Components
■Step 2 — Make Piping Connections — Con
densing units may be conneeted to evaporator sec
tions using Carrier accessory tubing package (Table
3) or field-supplied tubing of refrigerant grade,
correct size and condition (Table 1). For tubing
requirements beyond 50 ft, obtain information from
local Carrier distributor.
WARNING if
ùt
If 1-1/8 in. tubing is used (38EC048,060), braze
it to theaecessory 1-1 / 8 x 3/4-in. suction eonnection
adapter (Carrier Part No. 28VQ900011) or to eor-
rectly sized field-supplied adapter, then make Com
patible Fitting connections.
Page 3
Table 3 — Accessories
PART NO
HH01AD040
HH93AZ040
HH07AT170
Low-Voltage Control Honeywell Deluxe Thermostat
Thermostat Subbase
Low-Voltage Control
DESCRIPTION
&
HH07AT174
HH93AZ176
HH01AD042
HH93AZ042
HH01YA192
HH93YZ194
38GS900102Indoor Fan Relay (Six HN61KJ210)
38GS900212
28VQ900011
09WQ036.060Refrigerant-to-Water Heat Exchanger for Chilled Water SystemsAll
‘For maximum capacities, use suction line sizes recommended in
Table 1 Use of accessory tubing packages smaller than recom
mended may result in slight capacity loss (see Note 2)
tSuction line is insulated and has a 90 degree bend at one end
JFor 5/8-in evaporator connection, cut off 3/4-in end
Length
Honeywell Thermostat
Thermostat Subbase
Low-Voltage Control Honeywell Thermostat
Thermostat Subbase
Low-Voltage Control Grayson Thermostat
Thermostat Subbase
Low-Voltage Transformer (Six 38GS900091)
Twelve 3/4- x 1-1/8 in Connection Adapters
TUBING
Liquid
(ft)
153/83/8
203/83/8
253/8
305/16
355/16
405/16
50
153/8
203/8
253/8
30
403/83/83/43/43/4
503/8
153/83/8
20
253/8
303/8
353/8
403/8
503/8
OD
(in.)
1/4
3/83/83/43/43/4030, 036
3/83/87/83/4
Tube End
OD (in.)
3/8
3/85/8
3/85/8
3/85/83/4t
3/85/8
3/83/43/43/4
3/8
3/83/43/43/4
3/8
3/8
3/87/83/4
3/87/83/4
3/87/8
3/87/83/4
3/87/83/4
*
Suctionf
OD
(in )
5/8
5/83/4t5/8
5/83/4t5/8
3/4
3/43/43/4
3/4
7/8
NOTES
1 Do not cut 3/8-in OD liquid lines to a length shorter than 10
feet Do not cut 5/1 6-or 1/4-in liquid line Do not cut 7/8-in
OD suction lines
2 Field-supplied 1-1/8 in suction line is recommended on
38EC048 and 060 If accessory tubing package is used, a
capacity reduction can result
Tube End
OD (in.)
EvapCond
3/4t
3/4t5/8
3/4t5/8
3/4t
3/43/4
3/4
3/4
3/43/4
MODEL
38EC
All
048, 060
MODEL
38EC
5/8
018, 024
5/8
5/8
3/4
3/4
3/4
3/4
3/4
3/4
3/4
■ WAHNiKO' IK> HOI Et'RY LiNESETS. if
is for exsojaSod peraaisi. dint
ing vmtn westiher. rdVigoraoi may to
the cookr boiieii ssetioo catismg
sltsggisig m A sksn ruo of kss
3 Ci of Uoesei may in pousni but ihore mmi fee
a 6 m vetiicai rise lo ifee valve cotmociiona oo
tire condeosiog sale.
Isolate interconnecting tubing from framing and
ductwork or where tubing runs thru stud spaces, en
closed ceilings or pipe chases. Use isolation type
hanger (Fig. 3) since rigid fastening transmits pulsa
tions to structure, creating objectionable sound.
For maximum capacity on 38EC048 and 060 sys
tems use 1-1/8 in. suction line. A capacity reduction
results if Carrier accessory tubing is used on these
systems. (Example: When a 25-ft accessory tubing
package is used on a 38EC048 system, the smaller
suction line results in a 3% capacity reduction.)
Length of interconnecting tubing may necessitate
refrigerant charge adjustment. Follow special re
quirements described in Start-Up, Refrigerant
Charging, page 6. Do not use less than 10 ft of inter
connecting tubing. On Carrier accessory tubing
packages, do not cut 5/ 16-in. or 1/4-in. liquid line or
7/8-in. suction line. These tubing packages have
swaged ends that, if cut, will not fit into refrigerant
line fittings. Bend or coil excess tubing to fit.
Do not use damaged, undersized or contaminated
tubing. Always evacuate or purge evaporator coil
and tubing system. When purging, use field-supplied
refrigerant, not unit holding charge refrigerant.
Page 4
When making tubing connections, be sure to pro
vide clearance at unit for electrical connections.
REPLACE THE ACCURATER™ REFRIG
ERANT CONTROL PISTON IN THE INDOOR
COIL, if required, before connecting refrigerant
lines. See Carrier Cooling System Capacity Optimi
zation, page 2.
CONNECT REFRIGERANT LINES to fittings on
eondensing unit suction and liquid service valves
(Fig. 1). Unit Compatible Fittings permit mechanical
(quick connect) or sweat connections.
Model 38EC048,060 — When using 1 -1 / 8 in. fieldsupplied suction line, use accessory suction line
adapter. Braze refrigerant suction line to 1-1/8 in.
end of adapter. Allow adapter to cool before insert
ing into valve. Do not allow heat to reach valve as
O-ring damage may result. Connect 3/4-in. end of
adapter to unit suetion line Compatible Fitting.
Connect liquid refrigerant line to unit. If a 7/8-in.
field-supplied suction line is used, provide a fieldsupplied 3/ 4-in. to 7/ 8-in. suction line adapter. (Not
necessary if 38LS accessory tubing is used.)
Mechanical Connection — (Mate one set of connec
tions at a time.)
1. Loosen nut on Compatible Fitting one turn. Do
not remove.
2. Remove plug and be sure O-ring is in the groove
inside the Compatible Fitting.
3. Cut tubing to correct length. Deburr tubing.
4. Insert tube into Compatible Fitting until it
bottoms. Keep tube bottomed in Compatible
Fitting while tightening nut. Tighten nut until it
bottoms on shoulder of fitting or valve.
Sweat Connection or Repair — (Use refrigerant
grade tubing.)
1. Remove locking nut, rubber O-ring and Schrader
core and cap from valve service port.
2. Cut tubing to correct length. Deburr tubing.
3. Insert tube in Compatible Fitting until it bottoms.
Wrap top and bottom of service valves in wet
cloth to prevent damage by heat. Solder with lowtemperature (430 F) solder.
4. Replace Schrader core and cap.
5. Evacuate or purge system using field-supplied
refrigerant.
f
Table 4 — Electrical Data (60 Hz)
COND
UNIT
38EC
018300419 114
0243005913 3
030300
036300
042310108
048300
048310
060300
03050060
0365007411 712
042510
048500
04851080163
060500136
036600
042610
048600
048610408 1
06060049
AWG — American \A/ire Gage
FLA — Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
RLA — Rated Load Amps
‘Permissible limits of the voltage range at which the unit will
operate satisfactorily
fCopper wire sizes based on 60C Use copper or copper-clad
aluminum wire only Use latest NEC for copper-clad aluminum
conductor sizing
V/PH
208-230/1
230/1
208-230/3
460/3
OPER
VOLTAGE*
Max
Min
254
197
254207
254
197
506414
CompressorFanMin Wire
LRARLA
6916.210
93
145
105
22 9
35 3
150
74
120
415 9
386 5
60741 2
FLA
Size (AWG)t
1 212
20 2
21 7
25 7
208
20
941 2
120
20
148
20 4
10212
BRANCH CIRCUIT
Max Wire
(ft)
31 51420
32 71230
46.01035
10
8
8
6
14
12
10
10
10
14106 91415
1498 91415
1487 61415
12
^Required when using nonmetallic conduit
“Maximum dual element size
NOTES
1 Fan motors are 230 v, single phase
2 All units have 24-v control circuit which requires external
power source
35 7
49 9
44.886034.5
41 0
51 3
35 31420
40 7
42 9
55 0
50 4
41 2
129 2122011 3
97 9
Min Gnd
Wire Size}
10
8
10
6
12
12
10
1035
10
12
Max Fuse or
HACR Type
Ckt Bkr Amps“
45
5029 5
50
60
25
25
30
45
2514 9
MCA
12 6
17 8
21.5
27 7
31 0
46 5
13 0
16 6
17 0
20 9
22 8
27 9
8 6
9 3
105
Page 5
Step 3 — Make Electrical Connections — Be
sure field wiring complies with local and national
fire, safety and electrical codes, and that voltage to
unit is within limits shown in Table 4. Contact local
power company for correction of improper line
voltage.
See Tafek 4 ««t »pply i
See Table 4 for recommended wire and fuse sizes.
When making electric connections, provide clear
ance at unit for refrigerant piping connections.
INSTALL A BRANCH CIRCUIT DISCONNECT
PER NEC of adequate size to handle unit starting
current. Locate disconnect within sight from and
readily accessible from the unit, per section 440-14
of National Electrical Code (NEC).
ROUTE LINE POWER LEADS INTO UNIT —
Extend leads from disconnect thru power wiring
hole provided (see Fig. 1) and into unit splice area.
Remove top cover to gain access to unit wiring.
CONNECT GROUND LEAD AND POWER
WIRING — Connect ground lead to a ground lug
in control box for safety. Then connect power wiring.
See Fig. 4. Splice line power leads to yellow and
black pigtails. Use wire nuts and tape at each con
nection. Connect unit wiring to copper or copperclad aluminum power wiring. Do not connect to
aluminum wiring.
CONNECT CONTROE POWER WIRING —
Route 24-v control wires thru control wiring hole
and connect to pigtails supplied with unit (Fig. 1).
Use furnace or fan coil transformer as 24-v (40-va
minimum) supply for system as shown in Fig. 5, or
use accessory transformer shown in Table 3.
THERMOSTAT SUBBASE
HH93AZ042 OR
THERMOSTAT SUBBASE
HH93AZ042 OR
ARRANGEMENT B-ONE TRANSFORMER
(COOLING AND ONE-STAGE HEATING)
THERMOSTAT SUBBASE
HH93AZI76
_LEAVE JUMPER ON
SUBBASE (RH TORO
38EC
5»^ « £ K
MWk MW Mb •! t MV< VWWWM
iifscomiz^
PER
~ -«ROtiRtS V.E&0 ' UJS
MVWT
--
------
ftmwifvni
Fig. 4 — Line Power Connections
__
o
Eili&SS
tsam UNIT
CiMi ìmr
____
^
1
r
_L_
TO IFM LINE
VOLTAGE
POWER
SUPPLY
ARRANGEMENT C-ONE TRANSFORMER
(COOLING AND TWO-STAGE HEATING)
IFR, FS and IFM are located in furnace on heating-cooling
applications If accessory IFR is required for cooling-only
applications, locate IFR in fan coil
c
— Contactor (12-va) Trans — Transformer
— Fan Switch __
FS
HC
— Heating Control v-V Field Splice
IFM — Indoor Fan Motor
IFR
"Connect FS to low-speed indoor fan terminal when 2-speed fan
NOTE Refer to unit wiring label for wire colors C to G and C to Y
connections
Indoor Fan Relay
is used
1 1
1 !
1
1
L
1
ITRWS
HC|
-HC2
FURNACE
________
_________ Factory Wiring
Field Wiring
^ Fig. 5 — Control Circuit Connections
Page 6
START-UP
1. Backseat (open) liquid and suction line service
valves. Open liquid line first to equalize pres
sure and reduce oil flow to suction line.
2. Set thermostat selector switch at OFF.
3. Set room thermostat at desired temperature.
Be sure this temperature is below indoor ambient.
4. Close electrical disconnects energizing entire
system.
5. Set room thermostat at COOL and fan switch at
FAN or AUTO, as desired. Operate unit for 15
minutes; then check system refrigerant charge.
See Refrigerant Charging, discussed later.
Motors and controls are designed to operate satis
factorily in the voltage range shown in Table 4. If
necessary to use manifold gages for servicing, refer
to Carrier Standard Service Techniques Manual,
Chapter 1, Refrigerants, page 1-5, Fig. 8 for bypass
method of returning charge to system. Removal of
liquid line charging hose without following these
precautions could result in some loss of charge.
Refrigerant Charging
ca» саяш flooding.
Table 5 — Service Data
UNIT
38EC
0183 3
024
0305 3
0367.5
04263
0483006 1
048310
060
‘Factory refrigerant charge is adequate when evaporator and con
densing unit are the same size and are connected with 25 ft or less
of field-supplied tubing of recommended size or Carrier accessory
tubing
R-22 CHG*
(lb)
3 31110/950
72
9 6
CONDENSER
FAN RPM (Hi/Lo)
1075/950
Condensing units contain correct operating
charge for complete system when connected to
Carrier-approved evaporators of same capacity as
condensing unit with 25 ft or less of Carrier accessory
tubing or field-supplied tubing of recommended
size. For every 10 ft of liquid line of recommended
size over 25 ft, add refrigerant charge as follows: .41b
for 3/8-in. line; .28 lb for 5/ 16-in. line. On all other
systems, adjust eharge for correct operation as
applicable.
Service port eonnections are provided on liquid
and suction line service valves for evacuation and
charging. See Fig. 1.
TO CHECK, ADJUST OR REPLACE REFRIG
ERANT CHARGE use method recommended in
Table 6. Details of charging methods are listed
below.
Before recharging system, thoroughly evacuate
system and then weigh in refrigerant charge speci
fied in Table 5. Check or adjust charge as required.
Refer to Carrier Standard Service Techniques
Manual, Chapter 1, Refrigerants, for additional sys
tem evacuation and dehydration instructions.
WEIGHT METHOD — Refer to Table 5 or unit
nameplate for correct system refrigerant charge.
Remove any refrigerant remaining in system before
recharging.
When system is not evacuated, subtract the
following amount from total charge.
The Dial-a-charge charging cylinder is an accu
rate device used to recharge system by weight. These
cylinders are available at refrigeration supply firms.
CHARGING CHART METHOD — Use Charging
Chart, Fig. 6, and the following procedure.
1. Operate unit a minimum of 10 minutes before
checking charge.
Measure suction pressure by attaching a gage to
2.
suction valve service port.
Measure suction line temperature by attaching a
3.
service thermometer to unit suction line near suc
tion valve. Insulate bulb, thermocouple or
thermistor for accurate reading.
f:
Table 6 — Refrigerant Charging Methods
roNniilMlT ADJUSTING CHARGE
ALL 1 or
‘Sight glass field supplied and installed in liquid refrigerant line
I METHODS OF CHECKING OR
38EC 1 System Refrigerant Control
1 Non TXVTXV
1 Chargemaster®
1 Charging Chart
Sight
Glass*
METHODS FOR COMPLETE
System Refrigerant Control
Non TXV
Weight Method
plus
Chargemaster or
Charging Chart
RECHARGING
TXV
Weight Method
plus
Sight Glass*
Page 7
(AccuRater™ System)
4. Measure outdoor (condenser inlet) air dry-bulb
temperature with a second thermometer.
5. Refer to Charging Chart (Fig. 6). Find air tem
perature entering condenser and project hori
zontally to curve showing suction pressure (psig
at suction valve).
6. From this intersection, project vertically down
ward to suction line temperature.
7. If unit has a higher suction line temperature than
charted temperature, add refrigerant until
charted temperature is reached.
If unit has a lower suction line temperature than
8.
charted temperature, bleed refrigerant until
charted temperature is reached.
If air temperature entering condenser or pressure
9.
at suction valve changes, charge to new suction
line temperature indicated on chart.
CHARGEMASTER® METHOD — Operate unit
for 10 minutes before using Chargemaster (Carrier
Part No. 38GC680004).
1. Tape Chargemaster feeler bulb to suction line
close to condensing unit. Insulate bulb. Ensure
suction line is clean for good contact with bulb.
(Uninsulated bulb or dirty suction line will seri
ously affect accuracy of temperature readings.)
2. Connect refrigerant drum to Chargemaster inlet
port keeping drum in position for vapor charging.
3. Connect Chargemaster outlet port to unit suction
valve service port.
4. Crack valves on refrigerant drum and Chargemaster to purge lines from drum to suction valve.
After purging lines, close valve on Chargemaster
only.
5. Measure outdoor air dry-bulb temperature.
6. Crack unit suction valve and read evaporator
temperature at red needle position on Chargemaster temperature gage and suction line tem
perature at black needle position.
Enter Chargemaster Charging Chart, Table 7, at
7.
outdoor air temperature (step 5) and evaporator
temperature (step 6). Find the suction line tem
perature required for correct system charge. If
actual suction line temperature (step 6) is higher
than table value, the system is undercharged. If
suction line temperature is lower than table
value, system is overcharged.
EXAMPLE: At outdoor air temperature of 84 F
and evaporator temperature of 43 F, the system
will be correctly charged at 76 F ± 2 F suction
line temperature. See Table 7.
Add charge by slowly opening Chargemaster
valve. If necessary, reduce charge by bleeding at
liquid line service valve. Check outdoor air and
evaporator temperature during procedure. If they
change, refer back to Chargemaster Charging
Chart.
Table 7 — 38EC Chargemaster Charging
Chart (AccuRater System)
OUTDOOR
TEMP
(F)
60
6230
6428
66
683443
70324152
72
74
76
78
8026
82
m3Î
86
8835
9034
92
94
9638
9836
too42495765 75
102
104
106
1084349
110414755 63
112
114
Example
EVAPORATOR TEMPERATURE (F)
21
32
27
25 2831
Suction Line Temperature (F)
4051
3839
3747;
3545 : 57
313950
37 : 48
30
3646
29
2735
33 42
32
2937
34
60
5467
44
40
mr
imm
33
37 4045 48
64
6172
58
69
56
66
54
63
52
6172
50
5968
46
5563 7385
44
5361 70
42
5159
41
495765
394755
4553
445159 67
41
39
75
X4£^:«:
48
46
4551
; ^
81
7890
68
75
63
72
61
70
5563 73
61
53
59
57
4653
50
86
83
80
77
70
68
65
61
59
Page 8
Correct use of Chargemaster ensures that an opti
mum refrigerant charge will be in system when con
ditions and system components are normal.
However, the Chargemaster does not solve or fix
system abnormalities. It indicates correct charge for
condition of the system. It will not make corrections
for dirty filters, slow fans, excessively long or short
suction lines or other abnormal conditions. This
charging device ensures that a correct relationship
exists between outdoor temperature, evaporator
temperature, and suction line temperature on a spe
cific system.
SIGHT GLASS METHOD — (Field-supplied sight
glass installed in liquid line.) A satisfactory oper
ating charge can be obtained on thermal expansion
valve systems only by charging to a clear sight glass.
For optimum charge, increase high-side pressure to
380 ± 10 psig by blocking condenser fan discharge
or air entering condenser. Charge to a clear sight
glass while holding constant high-side pressure. For
peak efficiency, adjust charge to yield a liquid refrig
erant temperature at the evaporator that is approxi
mately the same as outdoor dry-bulb temperature.
CRANKCASE HEATER SWITCH
SUCTION LINE
LOW
PRESSURE
SWITCH
DISCHARGE GRILLE (FAN
MOTOR UNDERNEATH) ^
WIRE ACCESS OPENING
TOP COVER-
HOT GAS
DISCHARGE LINE
CONDENSER COIL
COMPRESSOR
HIGH-
'/ PRESSURE
SWITCH
FAN MOTOR
AND
COMPRESSOR
LEADS
PLASTIC PIN
OF TUBE
lì SUPPORT
SERVICE
Compressor Removal — See Table 8 for com
pressor information and Fig. 7 for component loca
tion. Shut off power to unit. Remove refrigerant
from unit using refrigerant removal methods de
scribed in Carrier Standard Service Techniques
Manual, Chapter 1, Refrigerants. Be sure system
pressure is 0 psig before attempting eompressor
removal.
'Refer to Carrier Service Parts Catalog for replacement model
numbers
tWhere piping exceeds 50ft, obtain information from local Carrier
distributor
COMPR*
CRD-0200PFV55
AV5542E54
YRD-0400-PFV72
PC5016BD66
CRF1-0250-TF5
CRJ1-0300-TF555
AV5542E
PY5016BD66
PY6416AF66
CRJ1-0300-TFD55
AV5542E
YRD6-0400-FFD7268
PH5016BD
PH6416AF6662
OIL CHARGE (oz)t
InitialRecharge
26
55
66
55
54
72
54
6662
24
51
51
51
50
68
62
62
51
51
50
68
62
62
51
50
Fig. 7 — Condensing Unit 38EC
Component Locations
Follow safety codes. Wear safety glasses and
work gloves. Have quenching cloth available.
CAilTIOMi
m iufeisjg or doroags tmy
1. Remove top cover: remove 3 screws holding
top cover to connector plate; remove third screw
clockwise from connector plate; loosen remain
ing 5 screws; lift cover straight up.
2. Disconnect high- and low-voltage field wiring
and fan motor leads from capacitor and
contactor.
3. Remove 4 screws (38FC018 thru 030) or 8 screws
(38FC036 thru 060) holding discharge grille in
place. Lift grille from unit.
4. Disconnect compressor leads (crankcase heater,
low-pressure switch, if so equipped) from elec
trical components and pull them thru the wire
access opening into the coil section. Lift fan
orifice/control ring after pinching and pressing
down on 3 plastic pins of tube supports.
5. Remove louvered casing by taking out 16 screws
securing it to the cabinet and sliding it away
from the coil.
Page 9
6. Using a midget tubing cutter, cut liquid and
discharge lines on the coil and suction line at a
convenient place for easy reassembly with
copper slip couplings.
After plugging connections, remove condenser
coil by pinching plastic pins of tube supports
that extend into basepan and lift vertically. Set
coil on a clean, flat surface.
Remove compressor holddown bolts and slide
8.
out compressor. Remove crankcase heater, if
so equipped.
9. Carefully unbraze suction and discharge line
piping stubs from compressor after noting posi
tion of stubs to assist when reinstalling.
10. Install new compressor, placing crankcase
heater around compressor, if so equipped. Be
sure compressor holddown bolts are in place.
11. Replace coil; braze suction and discharge lines
to compressor piping stubs (at points where eut.
Step 6); rewire compressor and leak test.
12. Replace fan orifice/control ring; connect com
pressor wires after feeding them thru eontrol
ring; replace fan/grille assembly and rewire;
connect high- and low-voltage power wiring;
and replace louvered casing.
13. Replace top cover by running screws into orifice
loosely and tighten when cover is in plaee.
system is opened for serviee as described under
Compressor Removal. Position drier in liquid line
at convenient loeation.
Pumpdown Procedure — The system may be
pumped down in order to make repairs on low side
without losing eomplete refrigerant charge.
1. Attach pressure gage to suction service valve gage
port.
2. Frontseat the liquid line service valve.
3. Start unit and run until suction pressure reaches
5 psig (see Caution).
4. Shut unit off and frontseat suction valve.
5. Vent remaining pressure to atmosphere.
1
Unit Controls and Safety Devices
HIGH-PRESSURE RELIEF VALVE is located in
eompressor. Relief valve opens if system operating
pressure differential between suction and discharge
pressure reaches 400 to 500 psi on all models.
INTERNAL TEMPERATURE AND/OR CUR
RENT SENSITIVE OVERLOADS reset automati
cally when motor internal temperatures drop to a
safe level (overload may require up to 30 minutes to
reset). When internal overload is suspected of being
open, check by using an ohmmeter or continuity
tester. If neeessary, refer to Carrier Standard Serv
ice Techniques Manual, Chapter 2, Eleetrical, for
complete instructions.
INHERENT FAN MOTOR PROTECTION pro
tects motor from abnormal current and temperature.
FAN SWITCH changes to high speed at 90 F ± 5;
changes to low speed at 75 F ± 5.
SOLID-STATE TIME GUARD II CIRCUIT,
if so equipped, protects unit compressor by prevent
ing short cycling. Time Guard II circuit provides a
5 ± 2-minute delay before restarting compressor
after shutdown for any reason. On normal start-up,
the 5-minute delay occurs before thermostat closes.
After thermostat closes, the Time Guard 11 circuit
then provides a 3-second delay to prevent contactor
chattering.
CRANKCASE HEATER keeps the crankcase
warm during the off cycle and thus prevents dilution
of the oil with refrigerant. This assures good lubrieation and prevents loss of oil from crankcase during
start-up.
CRANKCASE HEATER SWITCH (relay for 060,
3-ph, 460-v units only) deaetivates heater when
compressor is operating for maximum energy
efficiency.
START CAPACITOR AND RELAY assure
proper compressor start-up under adverse
conditions.
Page 10
Compatible Fitting Repair
MECHANICAL CONNECTION — Frontseat unit
service valves. Relieve refrigerant pressure from
tubing. Back off locknut from Compatible Fitting
onto tube. Cut fitting between threads and 0-ring
as shown in Fig. 8. Remove tubing section
remaining in threaded portion of fitting. Discard
locknut.
Clean, flux, and insert new tube end into remain
ing portion of Compatible Fitting. Wrap valve in wet rag. Heat and apply low-temperature (430 F)
solder. Do not overheat valve.
Evacuate or purge evaporator coil and tubing
system. Add refrigerant charge. See Refrigerant
Charging instructions described previously.
Fig. 8 — Repair of Mechanical Connection
Lubrication
■COMPRESSOR contains factory oil charge. Re
place oil when lost. See Table 8 for oil recharge and
refer to Carrier Standard Service Techniques
Manual, Chapter 1, page 1-21, for oil recharg
ing procedure. Use Carrier PP33-1, Texaco WFl-32
or Suniso 3GS oil.
FAN MOTOR BEARINGS are prelubricated for 3
years heavy duty or 5 years normal duty. When
lubrication is necessary, send motor to authorized
motor repair shop.
^Coil Repair — A flare-union coupling repair kit
is available, with instructions, thru Carrier Service
Parts.
Coil Cleaning to be done at the beginning of
each cooling season or more often if required.
Condenser Fan Adjustment — Required fan
position is shown in Fig. 9. Adjust fan by loosening
setscrew(s) and moving fan blade up or down.
Fig. 9 — Condenser Fan Position
Condenser Fan Motor Removal
1. Shut off power to unit. Failure to do so may
result in electric shock or injury from rotating fan
blade.
2. Remove top cover, referring to Compressor
Removal, step 1.
3. Disconnect fan motor leads from control leads.
See Fig. 7.
4. Remove 4 screws (38EC018 thru 030) or 8 screws
(38EC036 thru 060) holding fan motor/discharge
grille in place and lift assembly from unit.
5. Remove Carrier nameplate by straightening
tabs.
6. Remove 4 nuts holding fan motor to discharge
grille. Remove motor and leads.
7. Reassembly is reverse of above procedure. Make
sure fan is positioned correctly as in Fig. 9.
1. Shut off power to unit.
2. Remove louvered casing by taking out 16 screws
securing it to the cabinet and sliding it away from
the coil.
3. Clean coil using vacuum cleaner and its crevice
tool (see Fig. 10). Work crevice tool vertically
making sure tool only touches dirt on fins. To
prevent fm removal, do not “scrub” fins with tool
or move tool horizontally.
4. If oil deposits are present, spray coil with house
hold detergent (Fantastic, Lestoil, 409, or any
similar type). Wait 10 minutes then proceed to
step 5.
Fig. 10 — Crevice Cleaning Tool
10
Page 11
5. Using garden hose, spray coil vertically down
ward with a constant stream of water at moderate
pressure (see Fig. 11). Keep nozzle at a 15 to 20
degree angle, about 3 in. from coil face and 18 in.
from tube. Spray so debris is washed out and
away from coil.
6. Reinstall louvered casing being careful not to
damage coil.
7. Restore power to unit.
Page 12
TROUBLESHOOTING GUIDE
SYMPTOM AND
PROBABLE CAUSE
COMPRESSOR SHUTS OFF. FAN OVERLOAD
OR HIGH-PRESSURE SWITCH CUT OUT, OR
INTERNAL PRESSURE RELIEF OPENS
Condenser Fan On
1. Condenser air restricted or recirculating.
2. Refrigerant overcharge, noncondensables in
system; system restricted.
3. Improper line voltage, loose electrical connec
tions, faulty run capacitor.
Condenser Fan Off
1. Fan slipping on shaft, fan motor bearing stuck,
fan motor defective.
2. Loose electrical connections. Fan motor over
load open.
COMPRESSOR RUNS BUT COOLING
IS INSUFFICIENT
1. Low refrigerant charge.
2. Dirty filters, partially restricted airflow (evap
orator coil may be partially iced).
High Suction Pressure
1. Defective compressor valves (accompanied by
low head pressure).
COMPRESSOR SHUTS OFF FROM
LOW-PRESSURE SWITCH CUTOUT
Evaporator Fan Runs
1. Low refrigerant charge or restricted evaporator
air.
2. Restricted refrigerant flow.
Evaporator Fan Stopped
1. Evaporator fan-motor defective or inoperative
COMPRESSOR SHUTS OFF
WILL NOT RESTART
Contactor Open
1. Burned out transformer, open thermostat circuit,
faulty control relay, open overload
Contactor Closed or Closes Then Opens
1. Compressor power is out, compressor motor is
burned out or internal overloads are open. Time
Guard II circuit faulty.
2. Check evaporator air system for dirty filters,
obstruction in ductwork, improper damper
settings. Refer to coil, fan coil or furnace
instructions as applicable.
1. Perform Compressor Replacement procedure.
Recheck system charge.
1. See Compressor Runs But Cooling Is Insufficient
above regarding filters, ductwork, etc
2. Check refrigerant flow device, be sure correct
AccuRaterTf^ or TXV is used.
Check furnace or fan instructions regarding de
fective fan relay, belt adjustment, condition of
motor bearings and overloads, check and tighten
electrical connections, check power supply.
Check control circuit components and wiring.
Refer to unit label diagram, check all conditions.
Refer to Standard System Techniques Manual,
Chapter 2, Electrical.
Check main power supply wiring. Refer to Elec
trical Data table and label diagram. Substitute
Time Guard II with a replacement to verify its
operation. Refer to Standard Service Techniques
Manual, Chapter 2, Electrical.
For replacement items use Carrier Specified Parts
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations
Book
Tab
1 4
3a 2a
Form 38EC-2SI Supersedes 38EC-1 SI
Printed in U S A6-82
PC 101Catalog No 533-848
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.