Carrier 38EC User Manual

Page 1
Number One Air Conditbninq Maker
Installation, Start-Up ^ ^ 3
Division of
and Service Instructions
Carrier Corporation Carrier Parkway • Syracuse
SAFETY CONSIDERATIONS INSTALLATION
Step 1 — Check Equipment and
Jobsite.................................................................1
• UNPACK UNIT
• INSPECT EQUIPMENT
• COMPLETE OR CONSIDER
Step 2 — Make Piping Connections .... 2
• REPLACE THE ACCURATER™
• CONNECT REFRIGERANT LINES
Step 3 — Make Electrical
Connections........................................................5
• INSTALL A BRANCH CIRCUIT
• ROUTE LINE POWER LEADS INTO
• CONNECT GROUND LEAD AND
• CONNECT CONTROL POWER
START-UP
SERVICE.................................................................. 8-10
MAINTENANCE
Installation and servicing of air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and quali fied service personnel should install, repair or service air conditioning equipment.
Untrained personnel can perform basic mainten ance functions of cleaning coils and filters and re
placing filters. All other operations should be performed by trained service personnel. When working on air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may
apply.
Follow all safety codes. Wear safety glasses and
work gloves. Use quenching cloth for brazing opera-
Air-Cooled Condensing Units
INDEX
..................................
.......................................................
SYSTEM REQUIREMENTS
REFRIGERANT CONTROL PISTON IN THE INDOOR COIL IF REQUIRED
DISCONNECT PER NEC
UNIT
POWER WIRING
WIRING
...............................................................
......................................................
SAFETY CONSIDERATIONS
Page
1
1-5
6-8
10-12
tions. Have fire extinguisher available for all brazing
operations.
WARJ^iKG; Before performitsg $ervice or maiatesjaBce operatjojjs vam off
nsBiirt po’»er swiich. to indoor »nfi and outdoor
unit. Turn, off accessory heater poTser switch if applicable- Electrical siioolc could cause per­sortal irgnry.
Table 1 — Physical Data (Refer to Fig. 1.)
MODEL 38EC OPER WT (lb) DIMENSlbNS (ft-in.)
Diameter A
Height B
CONNECTIONS (in.)
Suction (DDF)
Liquid (DDF)
REFRIG LINES
Suction (in DDF)
Liquid (in DDF)
*Fora1-1/8in suction line on 38EC048,060, a 3/4-in x 1-1/8 in suction
valve connection adapter is available as an accessory See Table 3
018 024
116 130 137 165
2-2-3/8 1 2-8
INSTALLATION
Step 1 — Check Equipment and Jobsite
UNPACK UNIT — Move to final location. Slide
from carton taking special care not to damage serv
ice valves or grilles.
INSPECT EQUIPMENT — File claim with ship
ping company if damaged or incomplete. COMPLETE OR CONSIDER SYSTEM RE
QUIREMENTS before installation:
Consult local building codes and National Elec
trical Code (NEC) for special installation
requirements.
When installing, allow sufficient space for airflow
clearance, wiring, refrigerant piping and service.
Maintain a minimum of 4 ft clearance from obstruc tions above and 18 in. on sides of unit. Maintain a distance of 24 in. between condensing units. Posi tion so water from roof or eaves does not flow
directly on unit.
Install on a solid, level mounting pad. It is not
necessary to attach unit to pad but if desired or
required by local code, position tiedown bolts in pad. Fasten unit to pad using 2 holes provided in unit base. See Fig. 1.
030 036 042 048* 060*
212 230
18|
1-9-3/4
5/8 3/4*
Recommended Field-Supplied Sizes
5/8 1 3/4 I 7/8 I 1-1/8
2-5-1/4
2-2-3/8 1 2-8 1 3-2
3/8
3/S
© Carrier Corporation 1982
Form 38EC-2SI
Page 2
4-0 OVERHEAD SPACE REQUIRED FOR SERVICE AND AIRFLOW
LIQUID VALVE SERVICE PORT
CONDENSER AIRFLOW
liDIAM HOLE
FOR POWER WIRING
r-6 AIRFLOW AND SERVICE
CLEARANCE
SUCTION VALVE SERVICE PORT
orator i^^if^field replacement of piston. Refer to Table 2. Replace piston, if required, before connect ing refrigerant lines. Piston replacement instructions are ineluded in evaporator installation book. After system installation is complete, use Charging Chart to check and/or adjust refrigerant charge.
Condensing Units Connected to Carrier-Approved
Evaporators — Condensing units contain correct
system refrigerant charge for operation with evap
orator of the same size when connected by 25 ft of field-supplied or Carrier accessory tubing. Check refrigerant charge for maximum efficiency (see Refrigerant Charging, page 6).
Table 2 — Optimization Chart
(Outdoor air design temperature. db-F.
100 F and below)
COND
UNIT
38EC
018 024 030 036 042 048 060
014 018
— — —
— —
Factory-installed piston Obtain replacement pistons thru local Carrier distributor
ACCURATER™ piSTON NO.
Evap Size (Coil or Fan Coil)
024 030
46
TXV
52 SS
— —
57 63
— ■■■■ —
036
TXV
65
67
- -
042
048 060
_
TXV
70
TXV
76 78
S3 82
— ■ ; 64
TXV
*CONCRETE PAD SHOULD WEIGH I5 TO 2 TIMES WEIGHT OF UNIT
Certified dimension drawings available on request
Fig. 1 — Dimensions. Connections and
Mounting Pad (Refer to Table 1.)
Carrier Cooling System Capacity Optimization — AccuRater™ (bypass type) refrigerant control, with
field-replaceable piston (see Fig. 2), is supplied on evaporator. Use Optimization Chart, Table 2, to find AecuRater piston size required for eondenser/ evaporator system being installed. Pistons are cor­reetly sized for an evaporator of the same capacity as the condensing unit, so piston change is not neces sary. Mix-matching of condensing unit with evap-
Fig. 2 — AccuRater (Bypass Type)
Components
■Step 2 — Make Piping Connections — Con
densing units may be conneeted to evaporator sec tions using Carrier accessory tubing package (Table
3) or field-supplied tubing of refrigerant grade, correct size and condition (Table 1). For tubing requirements beyond 50 ft, obtain information from local Carrier distributor.
WARNING if
ùt
If 1-1/8 in. tubing is used (38EC048,060), braze it to theaecessory 1-1 / 8 x 3/4-in. suction eonnection adapter (Carrier Part No. 28VQ900011) or to eor-
rectly sized field-supplied adapter, then make Com patible Fitting connections.
Page 3

Table 3 — Accessories

PART NO
HH01AD040 HH93AZ040
HH07AT170
Low-Voltage Control Honeywell Deluxe Thermostat Thermostat Subbase
Low-Voltage Control
DESCRIPTION
&
HH07AT174 HH93AZ176
HH01AD042 HH93AZ042
HH01YA192 HH93YZ194
38GS900102 Indoor Fan Relay (Six HN61KJ210) 38GS900212 28VQ900011 09WQ036.060 Refrigerant-to-Water Heat Exchanger for Chilled Water Systems All
TUBING
PACKAGES
38LS958151 38LS958201 38LS958251 38LS958301 38LS958351 38LS958401 38LS958501
38LS934151 38LS934201 38LS934251 38LS934301 38LS934351 35 3/8 38LS934401
38LS934501 38LS978151
38LS978201
38LS978251 38LS978301 38LS978351 38LS978401 38LS978501
‘For maximum capacities, use suction line sizes recommended in
Table 1 Use of accessory tubing packages smaller than recom
mended may result in slight capacity loss (see Note 2) tSuction line is insulated and has a 90 degree bend at one end JFor 5/8-in evaporator connection, cut off 3/4-in end
Length
Honeywell Thermostat
Thermostat Subbase Low-Voltage Control Honeywell Thermostat
Thermostat Subbase
Low-Voltage Control Grayson Thermostat
Thermostat Subbase
Low-Voltage Transformer (Six 38GS900091)
Twelve 3/4- x 1-1/8 in Connection Adapters
TUBING
Liquid
(ft)
15 3/8 3/8 20 3/8 3/8 25 3/8 30 5/16 35 5/16 40 5/16 50
15 3/8 20 3/8 25 3/8 30
40 3/8 3/8 3/4 3/4 3/4 50 3/8
15 3/8 3/8 20 25 3/8
30 3/8
35 3/8
40 3/8
50 3/8
OD
(in.)
1/4
3/8 3/8 3/4 3/4 3/4 030, 036
3/8 3/8 7/8 3/4
Tube End
OD (in.)
3/8 3/8 5/8 3/8 5/8 3/8 5/8 3/4t 3/8 5/8
3/8 3/4 3/4 3/4 3/8 3/8 3/4 3/4 3/4
3/8
3/8
3/8 7/8 3/4 3/8 7/8 3/4 3/8 7/8 3/8 7/8 3/4 3/8 7/8 3/4
*
Suctionf
OD
(in )
5/8 5/8 3/4t 5/8 5/8 3/4t 5/8
3/4
3/4 3/4 3/4
3/4 7/8
NOTES 1 Do not cut 3/8-in OD liquid lines to a length shorter than 10
feet Do not cut 5/1 6-or 1/4-in liquid line Do not cut 7/8-in OD suction lines
2 Field-supplied 1-1/8 in suction line is recommended on
38EC048 and 060 If accessory tubing package is used, a
capacity reduction can result
Tube End
OD (in.)
Evap Cond
3/4t
3/4t 5/8 3/4t 5/8
3/4t
3/4 3/4
3/4
3/4
3/4 3/4
MODEL
38EC
All
048, 060
MODEL
38EC
5/8
018, 024
5/8 5/8
3/4 3/4
3/4 3/4 3/4
3/4 3/4
■ WAHNiKO' IK> HOI Et'RY LiNESETS. if is for exsojaSod peraaisi. dint
ing vmtn westiher. rdVigoraoi may to the cookr boiieii ssetioo catismg sltsggisig m A sksn ruo of kss 3 Ci of Uoesei may in pousni but ihore mmi fee a 6 m vetiicai rise lo ifee valve cotmociiona oo tire condeosiog sale.
Isolate interconnecting tubing from framing and ductwork or where tubing runs thru stud spaces, en closed ceilings or pipe chases. Use isolation type
hanger (Fig. 3) since rigid fastening transmits pulsa
tions to structure, creating objectionable sound.
For maximum capacity on 38EC048 and 060 sys
tems use 1-1/8 in. suction line. A capacity reduction results if Carrier accessory tubing is used on these
systems. (Example: When a 25-ft accessory tubing package is used on a 38EC048 system, the smaller suction line results in a 3% capacity reduction.)
Length of interconnecting tubing may necessitate
refrigerant charge adjustment. Follow special re
quirements described in Start-Up, Refrigerant
Charging, page 6. Do not use less than 10 ft of inter
connecting tubing. On Carrier accessory tubing
packages, do not cut 5/ 16-in. or 1/4-in. liquid line or 7/8-in. suction line. These tubing packages have swaged ends that, if cut, will not fit into refrigerant line fittings. Bend or coil excess tubing to fit.
Do not use damaged, undersized or contaminated tubing. Always evacuate or purge evaporator coil and tubing system. When purging, use field-supplied refrigerant, not unit holding charge refrigerant.
Page 4
When making tubing connections, be sure to pro
vide clearance at unit for electrical connections.
REPLACE THE ACCURATER™ REFRIG ERANT CONTROL PISTON IN THE INDOOR
COIL, if required, before connecting refrigerant lines. See Carrier Cooling System Capacity Optimi zation, page 2.
CONNECT REFRIGERANT LINES to fittings on
eondensing unit suction and liquid service valves
(Fig. 1). Unit Compatible Fittings permit mechanical
(quick connect) or sweat connections.
Model 38EC048,060 — When using 1 -1 / 8 in. field­supplied suction line, use accessory suction line adapter. Braze refrigerant suction line to 1-1/8 in. end of adapter. Allow adapter to cool before insert ing into valve. Do not allow heat to reach valve as
O-ring damage may result. Connect 3/4-in. end of adapter to unit suetion line Compatible Fitting.
Connect liquid refrigerant line to unit. If a 7/8-in. field-supplied suction line is used, provide a field­supplied 3/ 4-in. to 7/ 8-in. suction line adapter. (Not
necessary if 38LS accessory tubing is used.)
Mechanical Connection — (Mate one set of connec
tions at a time.)
1. Loosen nut on Compatible Fitting one turn. Do not remove.
2. Remove plug and be sure O-ring is in the groove inside the Compatible Fitting.
3. Cut tubing to correct length. Deburr tubing.
4. Insert tube into Compatible Fitting until it bottoms. Keep tube bottomed in Compatible
Fitting while tightening nut. Tighten nut until it
bottoms on shoulder of fitting or valve.
Sweat Connection or Repair — (Use refrigerant
grade tubing.)
1. Remove locking nut, rubber O-ring and Schrader core and cap from valve service port.
2. Cut tubing to correct length. Deburr tubing.
3. Insert tube in Compatible Fitting until it bottoms.
Wrap top and bottom of service valves in wet cloth to prevent damage by heat. Solder with low­temperature (430 F) solder.
4. Replace Schrader core and cap.
5. Evacuate or purge system using field-supplied
refrigerant.
f
Table 4 — Electrical Data (60 Hz)
COND
UNIT
38EC
018300 41 9 1 14 024300 59 13 3 030300
036300 042310 108 048300
048310 060300
030500 60 036500 74 11 7 12
042510 048500 048510 80 163
060500 136 036600
042610 048600 048610 40 8 1 060600 49
AWG — American \A/ire Gage
FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration LRA — Locked Rotor Amps MCA — Minimum Circuit Amps RLA — Rated Load Amps
‘Permissible limits of the voltage range at which the unit will
operate satisfactorily
fCopper wire sizes based on 60C Use copper or copper-clad
aluminum wire only Use latest NEC for copper-clad aluminum conductor sizing
V/PH
208-230/1
230/1
208-230/3
460/3
OPER
VOLTAGE* Max
Min
254
197
254 207
254
197
506 414
Compressor Fan Min Wire
LRA RLA
69 16.2 10 93
145 105
22 9 35 3
150
74
120
41 5 9
38 6 5 60 74 1 2
FLA
Size (AWG)t
1 2 12
20 2 21 7 25 7
20 8
20
94 1 2
120
20
148
20 4
102 12
BRANCH CIRCUIT
Max Wire
(ft)
31 5 14 20 32 7 12 30
46.0 10 35
10
8 8
6
14
12 10 10 10
14 106 9 14 15 14 98 9 14 15 14 87 6 14 15 12
^Required when using nonmetallic conduit
“Maximum dual element size
NOTES
1 Fan motors are 230 v, single phase 2 All units have 24-v control circuit which requires external
power source
35 7 49 9
44.8 8 60 34.5
41 0 51 3
35 3 14 20
40 7 42 9 55 0
50 4 41 2
129 2 12 20 11 3
97 9
Min Gnd
Wire Size}
10
8
10
6
12 12 10 10 35
10
12
Max Fuse or
HACR Type
Ckt Bkr Amps“
45 50 29 5
50 60
25 25 30
45
25 14 9
MCA
12 6 17 8
21.5 27 7
31 0 46 5
13 0 16 6
17 0
20 9
22 8 27 9
8 6 9 3
105
Page 5

Step 3 — Make Electrical Connections — Be

sure field wiring complies with local and national fire, safety and electrical codes, and that voltage to unit is within limits shown in Table 4. Contact local power company for correction of improper line voltage.
See Tafek 4 ««t »pply i
See Table 4 for recommended wire and fuse sizes. When making electric connections, provide clear ance at unit for refrigerant piping connections.
INSTALL A BRANCH CIRCUIT DISCONNECT PER NEC of adequate size to handle unit starting
current. Locate disconnect within sight from and
readily accessible from the unit, per section 440-14 of National Electrical Code (NEC).
ROUTE LINE POWER LEADS INTO UNIT — Extend leads from disconnect thru power wiring hole provided (see Fig. 1) and into unit splice area. Remove top cover to gain access to unit wiring.
CONNECT GROUND LEAD AND POWER WIRING — Connect ground lead to a ground lug in control box for safety. Then connect power wiring. See Fig. 4. Splice line power leads to yellow and black pigtails. Use wire nuts and tape at each con nection. Connect unit wiring to copper or copper­clad aluminum power wiring. Do not connect to aluminum wiring.
CONNECT CONTROE POWER WIRING
Route 24-v control wires thru control wiring hole
and connect to pigtails supplied with unit (Fig. 1).
Use furnace or fan coil transformer as 24-v (40-va minimum) supply for system as shown in Fig. 5, or use accessory transformer shown in Table 3.
THERMOSTAT SUBBASE HH93AZ042 OR
THERMOSTAT SUBBASE
HH93AZ042 OR
ARRANGEMENT B-ONE TRANSFORMER (COOLING AND ONE-STAGE HEATING)
THERMOSTAT SUBBASE
HH93AZI76
_LEAVE JUMPER ON
SUBBASE (RH TORO
38EC
5»^ « £ K
MWk MW Mb •! t MV< VWWWM
iifscomiz^
PER
~ -«ROtiRtS V.E&0 ' UJS
MVWT
--
------
ftmwifvni
Fig. 4 — Line Power Connections
__
o
Eili&SS
tsam UNIT
CiMi ìmr
____
^
1
r
_L_
TO IFM LINE
VOLTAGE POWER SUPPLY
ARRANGEMENT C-ONE TRANSFORMER (COOLING AND TWO-STAGE HEATING)
IFR, FS and IFM are located in furnace on heating-cooling applications If accessory IFR is required for cooling-only applications, locate IFR in fan coil
c
— Contactor (12-va) Trans — Transformer — Fan Switch __
FS HC
— Heating Control v-V Field Splice
IFM — Indoor Fan Motor IFR
"Connect FS to low-speed indoor fan terminal when 2-speed fan
NOTE Refer to unit wiring label for wire colors C to G and C to Y connections
Indoor Fan Relay
is used
1 1 1 !
1 1
L
1
ITRWS
HC|
-HC2 FURNACE
________ _________ Factory Wiring
Field Wiring
^ Fig. 5 — Control Circuit Connections
Page 6

START-UP

1. Backseat (open) liquid and suction line service valves. Open liquid line first to equalize pres sure and reduce oil flow to suction line.
2. Set thermostat selector switch at OFF.
3. Set room thermostat at desired temperature.
Be sure this temperature is below indoor ambient.
4. Close electrical disconnects energizing entire system.
5. Set room thermostat at COOL and fan switch at FAN or AUTO, as desired. Operate unit for 15
minutes; then check system refrigerant charge.
See Refrigerant Charging, discussed later.
Motors and controls are designed to operate satis
factorily in the voltage range shown in Table 4. If
necessary to use manifold gages for servicing, refer
to Carrier Standard Service Techniques Manual,
Chapter 1, Refrigerants, page 1-5, Fig. 8 for bypass method of returning charge to system. Removal of liquid line charging hose without following these precautions could result in some loss of charge.

Refrigerant Charging

ca» саяш flooding.
Table 5 — Service Data
UNIT
38EC
018 3 3 024 030 5 3 036 7.5
042 63 048300 6 1 048310
060
‘Factory refrigerant charge is adequate when evaporator and con
densing unit are the same size and are connected with 25 ft or less of field-supplied tubing of recommended size or Carrier accessory tubing
R-22 CHG*
(lb)
3 3 1110/950
72
9 6
CONDENSER
FAN RPM (Hi/Lo)
1075/950
Condensing units contain correct operating
charge for complete system when connected to
Carrier-approved evaporators of same capacity as condensing unit with 25 ft or less of Carrier accessory tubing or field-supplied tubing of recommended
size. For every 10 ft of liquid line of recommended
size over 25 ft, add refrigerant charge as follows: .41b
for 3/8-in. line; .28 lb for 5/ 16-in. line. On all other
systems, adjust eharge for correct operation as
applicable.
Service port eonnections are provided on liquid and suction line service valves for evacuation and charging. See Fig. 1.
TO CHECK, ADJUST OR REPLACE REFRIG ERANT CHARGE use method recommended in Table 6. Details of charging methods are listed below.
Before recharging system, thoroughly evacuate system and then weigh in refrigerant charge speci fied in Table 5. Check or adjust charge as required.
Refer to Carrier Standard Service Techniques Manual, Chapter 1, Refrigerants, for additional sys
tem evacuation and dehydration instructions.
WEIGHT METHOD — Refer to Table 5 or unit nameplate for correct system refrigerant charge.
Remove any refrigerant remaining in system before
recharging.
When system is not evacuated, subtract the following amount from total charge.
38EC018 thru 030 — .10 lb (1.6 oz) 38EC036 thru 060 — .20 lb (3.2 oz)
The Dial-a-charge charging cylinder is an accu rate device used to recharge system by weight. These cylinders are available at refrigeration supply firms.
CHARGING CHART METHOD — Use Charging Chart, Fig. 6, and the following procedure.
1. Operate unit a minimum of 10 minutes before checking charge.
Measure suction pressure by attaching a gage to
2.
suction valve service port.
Measure suction line temperature by attaching a
3. service thermometer to unit suction line near suc tion valve. Insulate bulb, thermocouple or thermistor for accurate reading.
f:
Table 6 — Refrigerant Charging Methods
roNniilMlT ADJUSTING CHARGE
ALL 1 or
‘Sight glass field supplied and installed in liquid refrigerant line
I METHODS OF CHECKING OR
38EC 1 System Refrigerant Control
1 Non TXV TXV 1 Chargemaster®
1 Charging Chart
Sight
Glass*
METHODS FOR COMPLETE
System Refrigerant Control
Non TXV
Weight Method
plus
Chargemaster or
Charging Chart
RECHARGING
TXV
Weight Method
plus
Sight Glass*
Page 7
(AccuRater™ System)
4. Measure outdoor (condenser inlet) air dry-bulb temperature with a second thermometer.
5. Refer to Charging Chart (Fig. 6). Find air tem perature entering condenser and project hori zontally to curve showing suction pressure (psig at suction valve).
6. From this intersection, project vertically down ward to suction line temperature.
7. If unit has a higher suction line temperature than charted temperature, add refrigerant until charted temperature is reached.
If unit has a lower suction line temperature than
8.
charted temperature, bleed refrigerant until charted temperature is reached.
If air temperature entering condenser or pressure
9.
at suction valve changes, charge to new suction line temperature indicated on chart.
CHARGEMASTER® METHOD — Operate unit
for 10 minutes before using Chargemaster (Carrier
Part No. 38GC680004).
1. Tape Chargemaster feeler bulb to suction line close to condensing unit. Insulate bulb. Ensure suction line is clean for good contact with bulb. (Uninsulated bulb or dirty suction line will seri ously affect accuracy of temperature readings.)
2. Connect refrigerant drum to Chargemaster inlet port keeping drum in position for vapor charging.
3. Connect Chargemaster outlet port to unit suction valve service port.
4. Crack valves on refrigerant drum and Charge­master to purge lines from drum to suction valve.
After purging lines, close valve on Chargemaster only.
5. Measure outdoor air dry-bulb temperature.
6. Crack unit suction valve and read evaporator
temperature at red needle position on Charge­master temperature gage and suction line tem perature at black needle position.
Enter Chargemaster Charging Chart, Table 7, at
7. outdoor air temperature (step 5) and evaporator temperature (step 6). Find the suction line tem perature required for correct system charge. If actual suction line temperature (step 6) is higher than table value, the system is undercharged. If suction line temperature is lower than table
value, system is overcharged.
EXAMPLE: At outdoor air temperature of 84 F and evaporator temperature of 43 F, the system will be correctly charged at 76 F ± 2 F suction
line temperature. See Table 7.
Add charge by slowly opening Chargemaster
valve. If necessary, reduce charge by bleeding at
liquid line service valve. Check outdoor air and
evaporator temperature during procedure. If they
change, refer back to Chargemaster Charging
Chart.
Table 7 — 38EC Chargemaster Charging
Chart (AccuRater System)
OUTDOOR
TEMP
(F)
60 62 30 64 28 66 68 34 43 70 32 41 52 72 74 76 78
80 26 82
m
86 88 35 90 34 92 94 96 38 98 36
too 42 49 57 65 75
102 104 106 108 43 49 110 41 47 55 63 112 114
Example
EVAPORATOR TEMPERATURE (F)
21
32
27
25 28 31
Suction Line Temperature (F)
40 51 38 39 37 47; 35 45 : 57
31 39 50
37 : 48
30
36 46
29 27 35
33 42 32
29 37
34
60
54 67
44
40
mr
im m
33
37 40 45 48
64 61 72 58
69
56
66
54
63
52
61 72
50
59 68
46
55 63 73 85
44
53 61 70
42
51 59
41
49 57 65
39 47 55
45 53 44 51 59 67
41 39
75
X4£^:«:
48 46 45 51
; ^
81 78 90
68
75
63
72
61
70
55 63 73
61
53
59 57
46 53
50
86 83 80 77
70 68 65
61 59
Page 8
Correct use of Chargemaster ensures that an opti mum refrigerant charge will be in system when con ditions and system components are normal. However, the Chargemaster does not solve or fix system abnormalities. It indicates correct charge for condition of the system. It will not make corrections for dirty filters, slow fans, excessively long or short suction lines or other abnormal conditions. This charging device ensures that a correct relationship exists between outdoor temperature, evaporator
temperature, and suction line temperature on a spe
cific system.
SIGHT GLASS METHOD — (Field-supplied sight glass installed in liquid line.) A satisfactory oper ating charge can be obtained on thermal expansion
valve systems only by charging to a clear sight glass. For optimum charge, increase high-side pressure to
380 ± 10 psig by blocking condenser fan discharge
or air entering condenser. Charge to a clear sight
glass while holding constant high-side pressure. For
peak efficiency, adjust charge to yield a liquid refrig erant temperature at the evaporator that is approxi mately the same as outdoor dry-bulb temperature.
CRANKCASE HEATER SWITCH
SUCTION LINE
LOW PRESSURE SWITCH
DISCHARGE GRILLE (FAN MOTOR UNDERNEATH) ^
WIRE ACCESS OPENING TOP COVER-
HOT GAS DISCHARGE LINE
CONDENSER COIL
COMPRESSOR
HIGH-
'/ PRESSURE
SWITCH
FAN MOTOR AND COMPRESSOR LEADS
PLASTIC PIN OF TUBE
lì SUPPORT

SERVICE

Compressor Removal — See Table 8 for com
pressor information and Fig. 7 for component loca tion. Shut off power to unit. Remove refrigerant from unit using refrigerant removal methods de scribed in Carrier Standard Service Techniques
Manual, Chapter 1, Refrigerants. Be sure system pressure is 0 psig before attempting eompressor removal.
^ Table 8 — Compressor Data
UNIT PRODUCTION
38EC
018300 AJ8520G 024300 030300 CRF1-0250PFV Ì; 036300 CRJ1-0300PFV 55 042310 048300 048310 060300 PC6416AG 030500 036500 042510 048500 YRD6-0400-TFC 048510
060500 036600 042610 048600 048610 060600
'Refer to Carrier Service Parts Catalog for replacement model
numbers
tWhere piping exceeds 50ft, obtain information from local Carrier
distributor
COMPR*
CRD-0200PFV 55
AV5542E 54
YRD-0400-PFV 72
PC5016BD 66
CRF1-0250-TF5
CRJ1-0300-TF5 55
AV5542E
PY5016BD 66 PY6416AF 66 CRJ1-0300-TFD 55
AV5542E
YRD6-0400-FFD 72 68 PH5016BD PH6416AF 66 62
OIL CHARGE (oz)t
Initial Recharge
26
55
66 55
54 72
54
66 62
24 51 51 51 50 68 62 62 51 51
50 68 62 62
51
50
Fig. 7 — Condensing Unit 38EC
Component Locations
Follow safety codes. Wear safety glasses and
work gloves. Have quenching cloth available.
CAilTIOMi m iufeisjg or doroags tmy
1. Remove top cover: remove 3 screws holding top cover to connector plate; remove third screw clockwise from connector plate; loosen remain ing 5 screws; lift cover straight up.
2. Disconnect high- and low-voltage field wiring and fan motor leads from capacitor and contactor.
3. Remove 4 screws (38FC018 thru 030) or 8 screws (38FC036 thru 060) holding discharge grille in place. Lift grille from unit.
4. Disconnect compressor leads (crankcase heater, low-pressure switch, if so equipped) from elec trical components and pull them thru the wire access opening into the coil section. Lift fan
orifice/control ring after pinching and pressing
down on 3 plastic pins of tube supports.
5. Remove louvered casing by taking out 16 screws securing it to the cabinet and sliding it away from the coil.
Page 9
6. Using a midget tubing cutter, cut liquid and discharge lines on the coil and suction line at a convenient place for easy reassembly with copper slip couplings.
After plugging connections, remove condenser coil by pinching plastic pins of tube supports that extend into basepan and lift vertically. Set coil on a clean, flat surface.
Remove compressor holddown bolts and slide
8.
out compressor. Remove crankcase heater, if
so equipped.
9. Carefully unbraze suction and discharge line piping stubs from compressor after noting posi tion of stubs to assist when reinstalling.
10. Install new compressor, placing crankcase heater around compressor, if so equipped. Be sure compressor holddown bolts are in place.
11. Replace coil; braze suction and discharge lines to compressor piping stubs (at points where eut.
Step 6); rewire compressor and leak test.
12. Replace fan orifice/control ring; connect com pressor wires after feeding them thru eontrol ring; replace fan/grille assembly and rewire; connect high- and low-voltage power wiring; and replace louvered casing.
13. Replace top cover by running screws into orifice loosely and tighten when cover is in plaee.
14. Evacuate and reeharge system.
Filter Drier — Install field-supplied filter drier
(Table 3) in system liquid line when refrigerant
system is opened for serviee as described under Compressor Removal. Position drier in liquid line
at convenient loeation.
Pumpdown Procedure — The system may be
pumped down in order to make repairs on low side without losing eomplete refrigerant charge.
1. Attach pressure gage to suction service valve gage port.
2. Frontseat the liquid line service valve.
3. Start unit and run until suction pressure reaches 5 psig (see Caution).
4. Shut unit off and frontseat suction valve.
5. Vent remaining pressure to atmosphere.
1
Unit Controls and Safety Devices
HIGH-PRESSURE RELIEF VALVE is located in eompressor. Relief valve opens if system operating pressure differential between suction and discharge pressure reaches 400 to 500 psi on all models.
LOW-PRESSURE SWITCH is located on unit
suction line. Low-pressure switch settings are: cut
out, 31 ± 4 psig; cut-in, 60 (+15, -0) psig.
INTERNAL TEMPERATURE AND/OR CUR RENT SENSITIVE OVERLOADS reset automati
cally when motor internal temperatures drop to a
safe level (overload may require up to 30 minutes to reset). When internal overload is suspected of being open, check by using an ohmmeter or continuity tester. If neeessary, refer to Carrier Standard Serv ice Techniques Manual, Chapter 2, Eleetrical, for complete instructions.
INHERENT FAN MOTOR PROTECTION pro
tects motor from abnormal current and temperature.
FAN SWITCH changes to high speed at 90 F ± 5;
changes to low speed at 75 F ± 5.
SOLID-STATE TIME GUARD II CIRCUIT, if so equipped, protects unit compressor by prevent ing short cycling. Time Guard II circuit provides a 5 ± 2-minute delay before restarting compressor after shutdown for any reason. On normal start-up, the 5-minute delay occurs before thermostat closes. After thermostat closes, the Time Guard 11 circuit then provides a 3-second delay to prevent contactor chattering.
CRANKCASE HEATER keeps the crankcase warm during the off cycle and thus prevents dilution of the oil with refrigerant. This assures good lubriea­tion and prevents loss of oil from crankcase during start-up.
CRANKCASE HEATER SWITCH (relay for 060,
3-ph, 460-v units only) deaetivates heater when compressor is operating for maximum energy efficiency.
START CAPACITOR AND RELAY assure
proper compressor start-up under adverse
conditions.
Page 10
Compatible Fitting Repair
MECHANICAL CONNECTION — Frontseat unit
service valves. Relieve refrigerant pressure from tubing. Back off locknut from Compatible Fitting onto tube. Cut fitting between threads and 0-ring as shown in Fig. 8. Remove tubing section
remaining in threaded portion of fitting. Discard
locknut.
Clean, flux, and insert new tube end into remain ing portion of Compatible Fitting. Wrap valve in wet rag. Heat and apply low-temperature (430 F) solder. Do not overheat valve.
Evacuate or purge evaporator coil and tubing system. Add refrigerant charge. See Refrigerant Charging instructions described previously.
Fig. 8 — Repair of Mechanical Connection
Lubrication
■COMPRESSOR contains factory oil charge. Re place oil when lost. See Table 8 for oil recharge and refer to Carrier Standard Service Techniques
Manual, Chapter 1, page 1-21, for oil recharg ing procedure. Use Carrier PP33-1, Texaco WFl-32 or Suniso 3GS oil.
FAN MOTOR BEARINGS are prelubricated for 3 years heavy duty or 5 years normal duty. When lubrication is necessary, send motor to authorized
motor repair shop.
^Coil Repair — A flare-union coupling repair kit
is available, with instructions, thru Carrier Service
Parts.
Coil Cleaning to be done at the beginning of
each cooling season or more often if required.
Condenser Fan Adjustment — Required fan
position is shown in Fig. 9. Adjust fan by loosening setscrew(s) and moving fan blade up or down.
Fig. 9 — Condenser Fan Position
Condenser Fan Motor Removal
1. Shut off power to unit. Failure to do so may result in electric shock or injury from rotating fan blade.
2. Remove top cover, referring to Compressor Removal, step 1.
3. Disconnect fan motor leads from control leads.
See Fig. 7.
4. Remove 4 screws (38EC018 thru 030) or 8 screws
(38EC036 thru 060) holding fan motor/discharge grille in place and lift assembly from unit.
5. Remove Carrier nameplate by straightening tabs.
6. Remove 4 nuts holding fan motor to discharge grille. Remove motor and leads.
7. Reassembly is reverse of above procedure. Make
sure fan is positioned correctly as in Fig. 9.
1. Shut off power to unit.
2. Remove louvered casing by taking out 16 screws securing it to the cabinet and sliding it away from the coil.
3. Clean coil using vacuum cleaner and its crevice tool (see Fig. 10). Work crevice tool vertically making sure tool only touches dirt on fins. To prevent fm removal, do not “scrub” fins with tool or move tool horizontally.
4. If oil deposits are present, spray coil with house hold detergent (Fantastic, Lestoil, 409, or any similar type). Wait 10 minutes then proceed to step 5.
Fig. 10 — Crevice Cleaning Tool
10
Page 11
5. Using garden hose, spray coil vertically down ward with a constant stream of water at moderate pressure (see Fig. 11). Keep nozzle at a 15 to 20 degree angle, about 3 in. from coil face and 18 in. from tube. Spray so debris is washed out and away from coil.
6. Reinstall louvered casing being careful not to damage coil.
7. Restore power to unit.
Page 12
TROUBLESHOOTING GUIDE
SYMPTOM AND
PROBABLE CAUSE
COMPRESSOR SHUTS OFF. FAN OVERLOAD OR HIGH-PRESSURE SWITCH CUT OUT, OR INTERNAL PRESSURE RELIEF OPENS
Condenser Fan On
1. Condenser air restricted or recirculating.
2. Refrigerant overcharge, noncondensables in
system; system restricted.
3. Improper line voltage, loose electrical connec tions, faulty run capacitor.
Condenser Fan Off
1. Fan slipping on shaft, fan motor bearing stuck,
fan motor defective.
2. Loose electrical connections. Fan motor over
load open.

COMPRESSOR RUNS BUT COOLING IS INSUFFICIENT

1. Low refrigerant charge.
2. Dirty filters, partially restricted airflow (evap orator coil may be partially iced).

High Suction Pressure

1. Defective compressor valves (accompanied by
low head pressure).

COMPRESSOR SHUTS OFF FROM LOW-PRESSURE SWITCH CUTOUT

Evaporator Fan Runs
1. Low refrigerant charge or restricted evaporator
air.
2. Restricted refrigerant flow.

Evaporator Fan Stopped

1. Evaporator fan-motor defective or inoperative

COMPRESSOR SHUTS OFF WILL NOT RESTART

Contactor Open
1. Burned out transformer, open thermostat circuit,
faulty control relay, open overload

Contactor Closed or Closes Then Opens

1. Compressor power is out, compressor motor is burned out or internal overloads are open. Time Guard II circuit faulty.
PROBABLE REMEDY
1. Condenser coil blocked. See Maintenance, Coil
Cleaning. Check airflow clearance (Fig.‘ 1)
2. Review Refrigerant Charging procedures; purge system, replace filter drier, check refrigerant control.
3. Review Installation, Step 3; replace capacitor.
1. Tighten fan hub setscrews, see Condenser Fan
Motor Removal.
2. Check unit wiring. Check motor bearings. Re
place motor.
1. Check Refrigerant Charging procedures.
2. Check evaporator air system for dirty filters, obstruction in ductwork, improper damper settings. Refer to coil, fan coil or furnace
instructions as applicable.
1. Perform Compressor Replacement procedure.
Recheck system charge.
1. See Compressor Runs But Cooling Is Insufficient
above regarding filters, ductwork, etc
2. Check refrigerant flow device, be sure correct
AccuRaterTf^ or TXV is used.
Check furnace or fan instructions regarding de fective fan relay, belt adjustment, condition of motor bearings and overloads, check and tighten electrical connections, check power supply.
Check control circuit components and wiring.
Refer to unit label diagram, check all conditions. Refer to Standard System Techniques Manual, Chapter 2, Electrical.
Check main power supply wiring. Refer to Elec
trical Data table and label diagram. Substitute Time Guard II with a replacement to verify its
operation. Refer to Standard Service Techniques Manual, Chapter 2, Electrical.
For replacement items use Carrier Specified Parts
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations
Book
Tab
1 4
3a 2a
Form 38EC-2SI Supersedes 38EC-1 SI
Printed in U S A 6-82
PC 101 Catalog No 533-848
Loading...