Carrier 38EC User Manual

Number One Air Conditbninq Maker
Installation, Start-Up ^ ^ 3
Division of
and Service Instructions
Carrier Corporation Carrier Parkway • Syracuse
SAFETY CONSIDERATIONS INSTALLATION
Step 1 — Check Equipment and
Jobsite.................................................................1
• UNPACK UNIT
• INSPECT EQUIPMENT
• COMPLETE OR CONSIDER
Step 2 — Make Piping Connections .... 2
• REPLACE THE ACCURATER™
• CONNECT REFRIGERANT LINES
Step 3 — Make Electrical
Connections........................................................5
• INSTALL A BRANCH CIRCUIT
• ROUTE LINE POWER LEADS INTO
• CONNECT GROUND LEAD AND
• CONNECT CONTROL POWER
START-UP
SERVICE.................................................................. 8-10
MAINTENANCE
Installation and servicing of air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and quali fied service personnel should install, repair or service air conditioning equipment.
Untrained personnel can perform basic mainten ance functions of cleaning coils and filters and re
placing filters. All other operations should be performed by trained service personnel. When working on air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may
apply.
Follow all safety codes. Wear safety glasses and
work gloves. Use quenching cloth for brazing opera-
Air-Cooled Condensing Units
INDEX
..................................
.......................................................
SYSTEM REQUIREMENTS
REFRIGERANT CONTROL PISTON IN THE INDOOR COIL IF REQUIRED
DISCONNECT PER NEC
UNIT
POWER WIRING
WIRING
...............................................................
......................................................
SAFETY CONSIDERATIONS
Page
1
1-5
6-8
10-12
tions. Have fire extinguisher available for all brazing
operations.
WARJ^iKG; Before performitsg $ervice or maiatesjaBce operatjojjs vam off
nsBiirt po’»er swiich. to indoor »nfi and outdoor
unit. Turn, off accessory heater poTser switch if applicable- Electrical siioolc could cause per­sortal irgnry.
Table 1 — Physical Data (Refer to Fig. 1.)
MODEL 38EC OPER WT (lb) DIMENSlbNS (ft-in.)
Diameter A
Height B
CONNECTIONS (in.)
Suction (DDF)
Liquid (DDF)
REFRIG LINES
Suction (in DDF)
Liquid (in DDF)
*Fora1-1/8in suction line on 38EC048,060, a 3/4-in x 1-1/8 in suction
valve connection adapter is available as an accessory See Table 3
018 024
116 130 137 165
2-2-3/8 1 2-8
INSTALLATION
Step 1 — Check Equipment and Jobsite
UNPACK UNIT — Move to final location. Slide
from carton taking special care not to damage serv
ice valves or grilles.
INSPECT EQUIPMENT — File claim with ship
ping company if damaged or incomplete. COMPLETE OR CONSIDER SYSTEM RE
QUIREMENTS before installation:
Consult local building codes and National Elec
trical Code (NEC) for special installation
requirements.
When installing, allow sufficient space for airflow
clearance, wiring, refrigerant piping and service.
Maintain a minimum of 4 ft clearance from obstruc tions above and 18 in. on sides of unit. Maintain a distance of 24 in. between condensing units. Posi tion so water from roof or eaves does not flow
directly on unit.
Install on a solid, level mounting pad. It is not
necessary to attach unit to pad but if desired or
required by local code, position tiedown bolts in pad. Fasten unit to pad using 2 holes provided in unit base. See Fig. 1.
030 036 042 048* 060*
212 230
18|
1-9-3/4
5/8 3/4*
Recommended Field-Supplied Sizes
5/8 1 3/4 I 7/8 I 1-1/8
2-5-1/4
2-2-3/8 1 2-8 1 3-2
3/8
3/S
© Carrier Corporation 1982
Form 38EC-2SI
4-0 OVERHEAD SPACE REQUIRED FOR SERVICE AND AIRFLOW
LIQUID VALVE SERVICE PORT
CONDENSER AIRFLOW
liDIAM HOLE
FOR POWER WIRING
r-6 AIRFLOW AND SERVICE
CLEARANCE
SUCTION VALVE SERVICE PORT
orator i^^if^field replacement of piston. Refer to Table 2. Replace piston, if required, before connect ing refrigerant lines. Piston replacement instructions are ineluded in evaporator installation book. After system installation is complete, use Charging Chart to check and/or adjust refrigerant charge.
Condensing Units Connected to Carrier-Approved
Evaporators — Condensing units contain correct
system refrigerant charge for operation with evap
orator of the same size when connected by 25 ft of field-supplied or Carrier accessory tubing. Check refrigerant charge for maximum efficiency (see Refrigerant Charging, page 6).
Table 2 — Optimization Chart
(Outdoor air design temperature. db-F.
100 F and below)
COND
UNIT
38EC
018 024 030 036 042 048 060
014 018
— — —
— —
Factory-installed piston Obtain replacement pistons thru local Carrier distributor
ACCURATER™ piSTON NO.
Evap Size (Coil or Fan Coil)
024 030
46
TXV
52 SS
— —
57 63
— ■■■■ —
036
TXV
65
67
- -
042
048 060
_
TXV
70
TXV
76 78
S3 82
— ■ ; 64
TXV
*CONCRETE PAD SHOULD WEIGH I5 TO 2 TIMES WEIGHT OF UNIT
Certified dimension drawings available on request
Fig. 1 — Dimensions. Connections and
Mounting Pad (Refer to Table 1.)
Carrier Cooling System Capacity Optimization — AccuRater™ (bypass type) refrigerant control, with
field-replaceable piston (see Fig. 2), is supplied on evaporator. Use Optimization Chart, Table 2, to find AecuRater piston size required for eondenser/ evaporator system being installed. Pistons are cor­reetly sized for an evaporator of the same capacity as the condensing unit, so piston change is not neces sary. Mix-matching of condensing unit with evap-
Fig. 2 — AccuRater (Bypass Type)
Components
■Step 2 — Make Piping Connections — Con
densing units may be conneeted to evaporator sec tions using Carrier accessory tubing package (Table
3) or field-supplied tubing of refrigerant grade, correct size and condition (Table 1). For tubing requirements beyond 50 ft, obtain information from local Carrier distributor.
WARNING if
ùt
If 1-1/8 in. tubing is used (38EC048,060), braze it to theaecessory 1-1 / 8 x 3/4-in. suction eonnection adapter (Carrier Part No. 28VQ900011) or to eor-
rectly sized field-supplied adapter, then make Com patible Fitting connections.

Table 3 — Accessories

PART NO
HH01AD040 HH93AZ040
HH07AT170
Low-Voltage Control Honeywell Deluxe Thermostat Thermostat Subbase
Low-Voltage Control
DESCRIPTION
&
HH07AT174 HH93AZ176
HH01AD042 HH93AZ042
HH01YA192 HH93YZ194
38GS900102 Indoor Fan Relay (Six HN61KJ210) 38GS900212 28VQ900011 09WQ036.060 Refrigerant-to-Water Heat Exchanger for Chilled Water Systems All
TUBING
PACKAGES
38LS958151 38LS958201 38LS958251 38LS958301 38LS958351 38LS958401 38LS958501
38LS934151 38LS934201 38LS934251 38LS934301 38LS934351 35 3/8 38LS934401
38LS934501 38LS978151
38LS978201
38LS978251 38LS978301 38LS978351 38LS978401 38LS978501
‘For maximum capacities, use suction line sizes recommended in
Table 1 Use of accessory tubing packages smaller than recom
mended may result in slight capacity loss (see Note 2) tSuction line is insulated and has a 90 degree bend at one end JFor 5/8-in evaporator connection, cut off 3/4-in end
Length
Honeywell Thermostat
Thermostat Subbase Low-Voltage Control Honeywell Thermostat
Thermostat Subbase
Low-Voltage Control Grayson Thermostat
Thermostat Subbase
Low-Voltage Transformer (Six 38GS900091)
Twelve 3/4- x 1-1/8 in Connection Adapters
TUBING
Liquid
(ft)
15 3/8 3/8 20 3/8 3/8 25 3/8 30 5/16 35 5/16 40 5/16 50
15 3/8 20 3/8 25 3/8 30
40 3/8 3/8 3/4 3/4 3/4 50 3/8
15 3/8 3/8 20 25 3/8
30 3/8
35 3/8
40 3/8
50 3/8
OD
(in.)
1/4
3/8 3/8 3/4 3/4 3/4 030, 036
3/8 3/8 7/8 3/4
Tube End
OD (in.)
3/8 3/8 5/8 3/8 5/8 3/8 5/8 3/4t 3/8 5/8
3/8 3/4 3/4 3/4 3/8 3/8 3/4 3/4 3/4
3/8
3/8
3/8 7/8 3/4 3/8 7/8 3/4 3/8 7/8 3/8 7/8 3/4 3/8 7/8 3/4
*
Suctionf
OD
(in )
5/8 5/8 3/4t 5/8 5/8 3/4t 5/8
3/4
3/4 3/4 3/4
3/4 7/8
NOTES 1 Do not cut 3/8-in OD liquid lines to a length shorter than 10
feet Do not cut 5/1 6-or 1/4-in liquid line Do not cut 7/8-in OD suction lines
2 Field-supplied 1-1/8 in suction line is recommended on
38EC048 and 060 If accessory tubing package is used, a
capacity reduction can result
Tube End
OD (in.)
Evap Cond
3/4t
3/4t 5/8 3/4t 5/8
3/4t
3/4 3/4
3/4
3/4
3/4 3/4
MODEL
38EC
All
048, 060
MODEL
38EC
5/8
018, 024
5/8 5/8
3/4 3/4
3/4 3/4 3/4
3/4 3/4
■ WAHNiKO' IK> HOI Et'RY LiNESETS. if is for exsojaSod peraaisi. dint
ing vmtn westiher. rdVigoraoi may to the cookr boiieii ssetioo catismg sltsggisig m A sksn ruo of kss 3 Ci of Uoesei may in pousni but ihore mmi fee a 6 m vetiicai rise lo ifee valve cotmociiona oo tire condeosiog sale.
Isolate interconnecting tubing from framing and ductwork or where tubing runs thru stud spaces, en closed ceilings or pipe chases. Use isolation type
hanger (Fig. 3) since rigid fastening transmits pulsa
tions to structure, creating objectionable sound.
For maximum capacity on 38EC048 and 060 sys
tems use 1-1/8 in. suction line. A capacity reduction results if Carrier accessory tubing is used on these
systems. (Example: When a 25-ft accessory tubing package is used on a 38EC048 system, the smaller suction line results in a 3% capacity reduction.)
Length of interconnecting tubing may necessitate
refrigerant charge adjustment. Follow special re
quirements described in Start-Up, Refrigerant
Charging, page 6. Do not use less than 10 ft of inter
connecting tubing. On Carrier accessory tubing
packages, do not cut 5/ 16-in. or 1/4-in. liquid line or 7/8-in. suction line. These tubing packages have swaged ends that, if cut, will not fit into refrigerant line fittings. Bend or coil excess tubing to fit.
Do not use damaged, undersized or contaminated tubing. Always evacuate or purge evaporator coil and tubing system. When purging, use field-supplied refrigerant, not unit holding charge refrigerant.
When making tubing connections, be sure to pro
vide clearance at unit for electrical connections.
REPLACE THE ACCURATER™ REFRIG ERANT CONTROL PISTON IN THE INDOOR
COIL, if required, before connecting refrigerant lines. See Carrier Cooling System Capacity Optimi zation, page 2.
CONNECT REFRIGERANT LINES to fittings on
eondensing unit suction and liquid service valves
(Fig. 1). Unit Compatible Fittings permit mechanical
(quick connect) or sweat connections.
Model 38EC048,060 — When using 1 -1 / 8 in. field­supplied suction line, use accessory suction line adapter. Braze refrigerant suction line to 1-1/8 in. end of adapter. Allow adapter to cool before insert ing into valve. Do not allow heat to reach valve as
O-ring damage may result. Connect 3/4-in. end of adapter to unit suetion line Compatible Fitting.
Connect liquid refrigerant line to unit. If a 7/8-in. field-supplied suction line is used, provide a field­supplied 3/ 4-in. to 7/ 8-in. suction line adapter. (Not
necessary if 38LS accessory tubing is used.)
Mechanical Connection — (Mate one set of connec
tions at a time.)
1. Loosen nut on Compatible Fitting one turn. Do not remove.
2. Remove plug and be sure O-ring is in the groove inside the Compatible Fitting.
3. Cut tubing to correct length. Deburr tubing.
4. Insert tube into Compatible Fitting until it bottoms. Keep tube bottomed in Compatible
Fitting while tightening nut. Tighten nut until it
bottoms on shoulder of fitting or valve.
Sweat Connection or Repair — (Use refrigerant
grade tubing.)
1. Remove locking nut, rubber O-ring and Schrader core and cap from valve service port.
2. Cut tubing to correct length. Deburr tubing.
3. Insert tube in Compatible Fitting until it bottoms.
Wrap top and bottom of service valves in wet cloth to prevent damage by heat. Solder with low­temperature (430 F) solder.
4. Replace Schrader core and cap.
5. Evacuate or purge system using field-supplied
refrigerant.
f
Table 4 — Electrical Data (60 Hz)
COND
UNIT
38EC
018300 41 9 1 14 024300 59 13 3 030300
036300 042310 108 048300
048310 060300
030500 60 036500 74 11 7 12
042510 048500 048510 80 163
060500 136 036600
042610 048600 048610 40 8 1 060600 49
AWG — American \A/ire Gage
FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration LRA — Locked Rotor Amps MCA — Minimum Circuit Amps RLA — Rated Load Amps
‘Permissible limits of the voltage range at which the unit will
operate satisfactorily
fCopper wire sizes based on 60C Use copper or copper-clad
aluminum wire only Use latest NEC for copper-clad aluminum conductor sizing
V/PH
208-230/1
230/1
208-230/3
460/3
OPER
VOLTAGE* Max
Min
254
197
254 207
254
197
506 414
Compressor Fan Min Wire
LRA RLA
69 16.2 10 93
145 105
22 9 35 3
150
74
120
41 5 9
38 6 5 60 74 1 2
FLA
Size (AWG)t
1 2 12
20 2 21 7 25 7
20 8
20
94 1 2
120
20
148
20 4
102 12
BRANCH CIRCUIT
Max Wire
(ft)
31 5 14 20 32 7 12 30
46.0 10 35
10
8 8
6
14
12 10 10 10
14 106 9 14 15 14 98 9 14 15 14 87 6 14 15 12
^Required when using nonmetallic conduit
“Maximum dual element size
NOTES
1 Fan motors are 230 v, single phase 2 All units have 24-v control circuit which requires external
power source
35 7 49 9
44.8 8 60 34.5
41 0 51 3
35 3 14 20
40 7 42 9 55 0
50 4 41 2
129 2 12 20 11 3
97 9
Min Gnd
Wire Size}
10
8
10
6
12 12 10 10 35
10
12
Max Fuse or
HACR Type
Ckt Bkr Amps“
45 50 29 5
50 60
25 25 30
45
25 14 9
MCA
12 6 17 8
21.5 27 7
31 0 46 5
13 0 16 6
17 0
20 9
22 8 27 9
8 6 9 3
105
Loading...
+ 8 hidden pages