Carrier 38E User Manual

38E,Q

HEATING & COOLING

Condensing Units and Heat Pumps

Service Manual
38EH,EN,ES,QH,QN,QS
TABLE OF CONTENTS
Page
INTRODUCTION
Models and SEER Ranges...................................... 1
Factory-Installed Options
SAFETY CONSIDERATIONS
SERVICE.................................................................... 3
Cabinet...................................................................... 3
• REMOVING LOUVERED CASING
• REMOVING FAN ORIFICE
• ELECTRICAL BOX ACCESS
Electrical
.................................................................
• CONTACTORS
• CAPACITORS
• TIME GUARD II
• CRANKCASE HEATER
• PRESSURE SWITCHES
• DEFROST THERMOSTATS ,
• PRINTED-CIRCUIT CONTROL BOARD
• FAN MOTORS
• SERVICE SENTRY CONTROL BOARD
• OUTDOOR THERMOSTATS
.......................................
.......
............................
1,2
2
3
5-11
Compressor
......................... ..................................
• MECHANICAL FAILURES
• ELECTRICAL FAILURES
• SYSTEM CLEAN-UP AFTER BURN-OUT
• COMPRESSOR REMOVAL AND REPLACEMENT
Refrigeration System
..........................................
15-20
• REFRIGERATION CYCLE
• LEAK DETECTING
• SERVICE VALVES
• CARRIER COMPATIBLE FITTING
• ACCURATER™ (Bypass type) COMPONENTS
• REVERSING VALVE
• COIL REMOVAL
• COIL CLEANING
• LIQUID LINE STRAINER
• ACCUMULATOR
• SYSTEM CHARGING (for all approved combinations)
Page
12-15
INTRODUCTION
This Service Manual enables a service technician to .service and repair a family of similar condensing units and heat pumps. Outwardly, many models appear
Models and SEER Ranges
Table 1 — Condensing Units
MODEL
38EH015 22 38EH018 22 38EH024 22 38EH030 30 38EH036 30 9.0 38EH042 30 9,0 38EH048 30 9.0 38EH060
38EN015 38EN018 38EN024 38EN030 22 38EN036
38EN042 30 8.0 38EN048 30 8.0 38EN060
38ES018 30 38ES024 38ES030 30 38ES036 38ES042 30 38ES048 30 38ES060 39
’SEER — Seasonal Energy Efficiency Ratio. The higher the number, the
less electrical power required to reach a given capacity. SEER is derived by dividing output energy by input energy.
DIAMETERS SEER*
(in.)
30 17
17 17
22
30 8.0
30 10.0 30
(Nominal)
9.0
9.0
9.0
9.0
9.0
8.0
8.0
8.0
8.0
8.0
10.0
10.0
10.0
10.0
10.0
10.0
similar, however, there are distinct differences. Tables 1 and 2 help to differentiate these differences.
Table 2 — Heat Pumps
MODEL
38QH015 38QH018 38QH024 30 38QH030 30 38QH036 38QH042 30 38QH048 38QH060 39
38QN015 38QN018 38QN024 22 38QN030 38QN036 30 38QN042 30 38QN048 30 38QN060 30
38QS018 30 38QS024 38QS030 30 38QS036 30 38QS042 30 38QS048 38QS060 39
tC.O.P. — Coefficient of Performance (heating), determined by dividing
DIAMETERS
(in.)
22 22
30 30
17 17
22
30
30
Btu output by power input required to producethis Btu output.
SEER*
(Nominal)
■ 9.0
9.0
9.0
9.0 2.85
9.0
9.0
9.0
9.0 2.85
8.0
8.0
8.0
8.0 2.55
8.0
8.0
8.0
8.0
10.0
10.0
10.0
10.0
10.0 2.85
10.0
10.0 2.85
CiO.P.t
(Minimum)
2.85
2.85
2.85
2.85
2.85
2.85
2.55
2.55
2.55
2.55
2.55
2.55
2.55
2.85
2.85
2.85
2.85
2.85
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book |l 1 |4 |4
Tab jsa
5a|2a|5a
PC 101
Catalog No. 563-857 Printed in U.S.A. Form 38E.Q-1SM
For replacement items use Carrier Specified Parts.
Pgi
11-85
Replaces; New
Factory-Installed Options — Any condensing unit
or heat pump listed in Tables 1 and 2 may be ordered as Basic or in one of 3 factory-option packages. Package
designations are included in model number (excluding

Table 3 — Option Packages

Basic). Example: 38EN0243015A/. SM designates this unit as sheet metal option package. Option package
designations are shown in Table 3.
Basic Sheet Metal Option (SM)
Deluxe Option (DL)
Custom Deluxe Option (CD) Same unit as (DL) except for addition of
Basic Sheet Metal Option (SM)
38EH,ES
Standard unit with no added options. Same unit as Basic except with addition
of louvered inlet casing.
Same unit as (SM) except for addition ■ of start assist components on single phase units, crankcase heater, high­and low-pressure switches, and accumulator.
sound shield around compressor, and Time Guard II device.
38EN
Standard unit with no added options. Same unit as Basic except for addition
of louvered inlet casing.
Table 4 — Condensing Unit Specifications
OUTDOOR
UNIT
MODEL NO.
38-
EH-
015301 018301 024301 030301 036301 AV5535E 042301 AV5542E 048321 AV5546H 060301
EN-
015310 AK8515E 018310 024310 030300
D30320
036320
042300 048300 060300 060310 030500 036500 042500 048500 060500 PY6716AF 060510 PY6716AF 036600 042600 048600 PH5316AD 060600 060610
ES­018
024 030 036 042 048 060
ORIGINAL
COMPRESSOR
MODEL
REZ3-0125 AB5515H MD2315GG MD3215GG
PC6016BD
RES3-0175-PFV H21B243ABC H21A313ABCA MD3215GG H21A363ABCA H21A463ABCA
PC5316BD PC6716AG PC6716AG H21A313DBD H21A373DBD H21A463DBD PY5316AD
H21A373DBE
A21A463DBE
PH6716AF
PH6716AF
AB5515H
CRC1-0175-PFV H23A263ABCA CRH3-0275-PFV CRK3-0325-PFV
AV5546H
REPLACEMENT
COMPRESSOR
■ 38EN663304
38EN663601
PH6766HF
50SR661301 32 38VH660303 50SR661333 50 51HK660304 48GH 662302 50SR661331 54
Basic Sheet Metal Option (SM) Same unit as Basic except for addition
Deluxe Option (DL)
Custom Deluxe Option (CD)
Basic Sheet Metal Option (SM)
OIL CHARGE
MODEL
50QT662300 50SR661301 32 MD2364GE 46 44 5.6 MD3264GE 46 44 50SR661336 50SR661300 50SR661331 54 PC6066ED
51D2661300 17 38EA662301 24 38EN663307 40 38EN663302 MD3264GE 38EN663303 50
PC5366HD PC6766HG 76
PC6766HG 38EN663501 38EN663502 38EN663500 See Note t See Note t See Note $ 38 EN 663600
PH5366HD PH6766HF
Initial Recharge
24
54 54
76 72 '12.7
40 37 46
50
76 .
76 40
50 50 76 76 76 50 50 76 76 76
55 55
55
38QH,QS
Standard unit with no added options.
of louvered inlet casing.
Same unit as (SM) except for addition of start assist components on single phase units, high-pressu.re switch, and Service Sentry device.
Same unit as (DL) except for addition of sound shield around compressor and Time Guard II device.
38QN
Standard unit with no added options. Same unit as Basic, except for addition
of louvered inlet casing.
REFRIG
CHARGE*
(R-22)
20 ■ ■ 6.2
30
50 50 50
15 ,3.2 20 3.7 37 3.8
44
47 47 7.2 72 72 9.5 72 37 47 47 7.2 72 72 9.6 72 47 . 47 7.2
72 7.6 72 9.6 72 12.5
28 7.20 51 7.40
46 6.50 51 7.50 51 7.80 50 12.50
. 6.7
12.5
12.5
7.1
5.6
5.8'
7.6
5.5
5.8
7.6
5.8
6.3
7.3
7.4
8.9
’Factory refrigerant charge is adequate when indoor unit and outdoor unit are the same size
and are connected with 25 ft or less of field tubing of recommended size or Carrier accessory tubing. For tubing requirements beyond 50ft, consult Carrier distributor.
H-R
NOTE: Originally an extended voltage compressor. Select replacement compressor for voltage required: tPF5366HD (200-3-60), PG5366HD (230-3-60). tPF6766HF (200-3-60), PG6766HF (230-3-60).
Table 5 — Heat Pump Specifications
OUTDOOR
UNIT
MODEL NO.
38­QH
015 018 024 030 036
042 .
048 060
060341
030 036 042 048 060
036 042 048 060
ON 015
018 024 030 036 042
048 060
036 042 048 060
036 042 048 060
QS 018
024 030 036 042
'Factory refrigerant charge is adequate when indoor unit and outdoor unit are the same
size and are connected with 25ft or less of field tubing of recommended size orCarrier accessory tubing. For tubing requirements beyond 50ft, consult Carrier distributor.
ORIGINAL
COMPRESSOR
MODEL
REZ3-0125-PFV H22B173ABCA
CRC2-0175-PFV AV5532E 50SR661333 AV5535H 50SR661336 AV5542H 50SR661330 AV5546H
WD60000AA WD6051AA 76
H23A563ABCA AV5532E 50SR661415
AV5535E 50SR661413 AV5542E AV5546E 50SR661500 WY6000AA WY6051AA 76
AV5535E 50SR661623 AV5542E AV5546E WH6000AA WH6051AA 76
REZ3-0125-PFV AB5519H MD2315GG MD2364GE MD3215GG MD3515GG AV5542E 50SR661330
PC5316BD PC5366HD PC6016BD
MF3513GB AV5542E PY5316AD See Note t PY6016BD
MH3513GB PH4616AD PH5316AD PH5366HD PH6016BD
AB5515H 50SR661301 32 JD2200AA JD2251AA 50 JD2800AA JD3300AA JD3300AA 50 CRJ3-0300-PFV 38EB660301 55
REPLACEMENT
COMPRESSOR
MODEL
50QT662300 38QF663300 38VH 660303
50SR661331
50SR661414 54
50SR661624 54 50SR661622
38QB662301 50SR661311
MD3264GE 46 MD3564GE 46
PC6066ED 76 MF3563GE 46
50SR661330 PY6066EF 76
MH3563GE 46 PH4666HD 76
PH6066EF 76
JD2851AA
OIL CHARGE
Initial
24 20 40 55 54 50 54 50 54 50 54 50
55 54 50
54
54 50
54 54 50
24 32 46
54 76
54 76
76
50
NOTE: Originally an extended voltage compressor. Select replacement compressor forvoltage-required:
tPF5366HD (200-3-60), PG5366HD (230-3-60).
Recharge
37 52
74 50
50 7.9 50
74 14.1 50
50 74
20 28 44 5.6 44 6.1 . , 44 8.9 50 9.5
72 72
44 8.9 50 72 72
44 8.9
72 72 72
28 46 46 46 51
REFRIG
CHARGE*
(R-22)
5.3
5.5
7.8
7.8
7.9
11.0
12.5
14.1
14.0
7.8
11.0
12.5
7.9
11.0
12.5
14.1
3.6
4.1
9.7
10.8
9.5
9.7
10.8
9.5
9.7
10.8
6.8
7.5
8.5
10.6
11.5

SAFETY CONSIDERATIONS

Service and repair of these units should be attempted only by trained service technicians familiar with Carrier Standard Service Instructions.
All equipment should be installed in accordance with accepted practices and in compliance with all national and local codes.
Power should be turned off when servicing or repair ing electrical components. Extreme caution should be observed when troubleshooting electrical components with power on. Observe all warning notices posted on
equipment.
Refrigeration system contains refrigerant under pressure. Extreme caution should be observed when handling refrigerants. Wear safety glasses and gloves to prevent personal injury. During normal system opera tion, some components are hot and can cause burns. Rotating fan blades can cause personal injury. Appro priate safety considerations are posted throughout this manual where potentially dangerous techniques are addressed.

SERVICE

Cabinet — Certain maintenance routines and repairs
require removal of cabinet panels. All condensing units
and heat pump models of this series have same basic
design with only minor differences. See Fig. 1.
REMOVING LOUVERED CASING — (See Fig. 2.)
1. Turn off all power to unit.
2. Loosen screws around circumference of fan orifice.
3. Remove screws around circumference of basepan.
4. Remove screws along control box support brackets.
5. Carefully remove louvered casing.

A CAUTION

Do not attempt to remove wire grille around coil. Grille is integral part of coil structure and sup ports coil.
REMOVING FAN ORIFICE — (See Fig. 3.)
1. Turn off all power to unit.
2. Remove screws holding grille on top of fan orifice.
3. Unplug wires from fan motor. Fan blades on certain models may have to be removed. Refer to Service — Electrical.
4. Remove screws holding fan orifice to wire grille and control box.
5. Remove fan orifice.
ELECTRICAL BOX ACCESS — (See Fig. 1.)
1. Turn off all power to unit.
2. Remove screws holding box cover.
DISCHARGE GRILLE
BASIC CONDENSING UNIT
r-6" AIRFLOW AND SERVICE CLEARANCE ON 3 SIDES — 12" ON REMAINING SIDE
ON 3 SIDES — 12" ON REMAINING SIDE

LOUVERED CONDENSING UNIT

DISCHARGE GRILLE
IVb" DIAM
HOLE WITH 1%" CONCENTRIC KNOCKOUT FOR POWER WIRING (OPP. SIDE)
ELEC. WIRING RACEWAY
LIQUID LINE SERVICE PORT ATSERVlOE VALVE(CLG CYCLE)
SUCTION SERVICE PORT AT SERVICE VALVE(CLG CYCLE)
SUCTION SERVICE PORT (HIDDEN)
COIL SUPPORT
r-6" AIRFLOW AND SERVICE CLEARANCE ON 3 SIDES — 12" ON REMAINING SIDE
DISCHARGE GRILLE
LIQUID LINE SERVICE PORT AT SERVICE­VALVE (CLG
CYCLE) SUCTION
SERVICE POR AT SERVICE VALVE(CLG CYCLE)
SUCTION
SERVICE PORT
(HIDDEN)
4'-0” OVERHEAD SPACE REQUIRED
FOR SERVICE AND AIRFLOW
r-6" AIRFLOW AND SERVICE CLEARANCE ON 3 SIDES —12" ON REMAINING SIDE
BASIC HEAT PUMP UNIT

Fig. 1 — Condensing and Heat Pump Units

LOUVERED HEAT PUMP UNIT

SCREWS
TOP COVER
BASEPAN FLANGE
C

Fig. 2 — Louvered Casing Assembly

Fig. 3 — Removing Orifice Fan
Electrical — Exercise extreme caution when work
ing on any electrical components. Shut off all power
to system prior to troubleshooting. Some trouble
shooting techniques require power to remain on. In these instances, exercise extreme caution to avoid danger of electrical shock. ONLY TRAINED SERVICE
PERSONNEL SHOULD PERFORM ELECTRICAL TROUBLESHOOTING.
CONTACTORS — (See Fig. 4.) Contactor provides means of applying power to unit using lower power (24 v) from transformer in order to power the contactor
coil. Depending on unit model, you may encounter
single-, double- or triple-pole contactors to break power.
One side of the line may be electrically hot, so extreme caution must be exercised when troubleshooting.
The contactor coil for these and most residential models of condensing units and heat pumps is powered by 24 vac. If contactor does not operate:
1. With power off, check whether contacts are free to move. Check for severe burning or arcing on contact points.
ATTACHING CASING TO TOP COVER
AND BASEPAN
2. With power off, use ohmmeter to check for continuity of coil. Disconnect leads before checking. A low­resistance reading is normal. Do not look for a specific value as different part numbers used will have different resistance values.
3. Reconnect leads and apply low-voltage power to contactor coil. This may be done by leaving high­voltage power to outdoor unit off, and by turning
thermostat to heat or cool. Check voltage at coil with voltmeter. Reading should be between 20 - 30 volts. Contactor should pull in if voltage is correct and coil is good. If contactor does not pull in, change contactor.
4. With high-voltage power off and contacts pulled in,
check for continuity across contacts with ohmmeter. A very low or zero resistance should be read. Higher readings could indicate burned or pitted contacts which may cause future failures.
Fig. 4 — Contactor
CAPACITORS — (See Fig. 5.)

A CAUTION

Capacitors can store electrical energy when power is off. Electrical shock can result if you touch the
capacitor terminals and discharge this stored energy.
Exercise extreme caution when working near capacitors. With power off, discharge stored energy by shorting across the capacitor terminals with a
15,000-ohm, 2-watt resistor, or a screwdriver blade with insulated handle.
Hard-Start Capacitors and PTC Devices — Sometimes, under adverse conditions, a standard run capacitor in a system is inadequate to start compressor. In these instances, a start-assist device is used to provide an extra starting boost to compressor motor. The first device is called a PTC (positive temperature coefficient) or ther
mistor (see Fig. 6). It is a resistor wired in parallel with run capacitor. As current flows through it at start-up, it heats up. As it heats up, its resistance increases greatly, until it effectively lowers current through it to an extremely
low value. This, in effect, removes it from the circuit.
After system shuts down, resistor cools and resistance
value returns to normal, until next time system starts.
Thermistor device is adequate for most conditions,
however, in systems where off cycle is short, device cannot cool fully and becomes less effective as a start device. It is an easy device to troubleshoot. Turn off all power to system.
Check thermistor with ohmmeter as described below.
If indoor coil does not have a bleed-type expansion device, it may be necessary to remove start thermistor and replace with accessory start capacitor and relay.
Shut off all power to unit. Remove PTC from unit.
Wait at least 10 minutes for PTC to cool to ambient
temperature.

RUN CAPACITOR START CAPACITOR

Fig. 5 — Capacitors
Capacitors are used as a phase shifting device to aid in starting certain single-phase motors. Check capacitors as follows:
1. Always check capacitors with power off. Attempting to troubleshoot a capacitor with power on can be dangerous. Defective capacitors may explode when power is applied. Insulating fluid inside is combustible
and may ignite, causing burns. After power is off, discharge capacitors as outlined above. Disconnect capacitor from circuit. Use ohmmeter, check each terminal to ground (use capacitor case). Discard any capacitor that shows resistance. Place ohmmeter leads
across capacitor and place on R x 10k scale. Meter
should jump to a low resistance value and slowly climb to higher value. Eailure of meter to do this indicates an open capacitor. If resistance stays at zero or a low value, capacitor is shorted.
2. Capacitance testers are available which will read value of capacitor. If value is not within ± 10% value stated on capacitor, it should be changed. If capacitor is not open or shorted, its capacitance value is calcu lated by measuring voltage across capacitor and current it draws.

A WARNING

Exercise extreme caution when taking readings while power is on. Use following formula to calculate capacitance:
^ . , r,. 2650 X amps Capacitance (mfd) =
3. Remove any capacitor that shows signs of bulging, dents or leaking. Do not apply power to a defective capacitor as it may explode.
volts
Measure resistance of PTC with ohmmeter. Resistance of 25-ohm PTC is measured between center tab and end tab with jumper across 2 end terminals.
Fig. 6 — PTC Devices
The cold resistance (Rj) of any PTC device should be
approximately 100 - 180% of device ohm rating.
50-ohm PTC = 50 - 90 ohm resistance 25-ohm PTC = 25 - 45 ohm resistance
If PTC resistance is appreciably lower or more than
200% higher than rating, device is defective.
If thermistor is good and compressor does not start, disconnect thermistor from starting circuit. Give com pressor a temporary capacitance boost. Run compressor for 10 minutes, shut off, allow system pressure to equal ize. Reconnect start thermistor. Try restarting com pressor without boost capacitor. If after 2 attempts, compressor does not start, remove thermistor. Add an
accessory start capacitor relay package.
Temporary Capacitance Boost — (See Fig. 7.) There are
times when a temporary capacitance boost is needed to get compressor started. Do not under any circumstances attach temporary boost capacitor directly across com pressor terminals. Serious personal injury can result.
Exercise extreme caution with this procedure when high­voltage power is on. If compressor motor does not start, it may be due to low-line voltage, improper pressure equalization or weak run capacitor. Check each possi bility, attempt capacitance boosting before adding auxiliary start capacitor and relay.
Loading...
+ 14 hidden pages