Carrier 38E User Manual

Page 1

38E,Q

HEATING & COOLING

Condensing Units and Heat Pumps

Service Manual
38EH,EN,ES,QH,QN,QS
TABLE OF CONTENTS
Page
INTRODUCTION
Models and SEER Ranges...................................... 1
Factory-Installed Options
SAFETY CONSIDERATIONS
SERVICE.................................................................... 3
Cabinet...................................................................... 3
• REMOVING LOUVERED CASING
• REMOVING FAN ORIFICE
• ELECTRICAL BOX ACCESS
Electrical
.................................................................
• CONTACTORS
• CAPACITORS
• TIME GUARD II
• CRANKCASE HEATER
• PRESSURE SWITCHES
• DEFROST THERMOSTATS ,
• PRINTED-CIRCUIT CONTROL BOARD
• FAN MOTORS
• SERVICE SENTRY CONTROL BOARD
• OUTDOOR THERMOSTATS
.......................................
.......
............................
1,2
2
3
5-11
Compressor
......................... ..................................
• MECHANICAL FAILURES
• ELECTRICAL FAILURES
• SYSTEM CLEAN-UP AFTER BURN-OUT
• COMPRESSOR REMOVAL AND REPLACEMENT
Refrigeration System
..........................................
15-20
• REFRIGERATION CYCLE
• LEAK DETECTING
• SERVICE VALVES
• CARRIER COMPATIBLE FITTING
• ACCURATER™ (Bypass type) COMPONENTS
• REVERSING VALVE
• COIL REMOVAL
• COIL CLEANING
• LIQUID LINE STRAINER
• ACCUMULATOR
• SYSTEM CHARGING (for all approved combinations)
Page
12-15
INTRODUCTION
This Service Manual enables a service technician to .service and repair a family of similar condensing units and heat pumps. Outwardly, many models appear
Models and SEER Ranges
Table 1 — Condensing Units
MODEL
38EH015 22 38EH018 22 38EH024 22 38EH030 30 38EH036 30 9.0 38EH042 30 9,0 38EH048 30 9.0 38EH060
38EN015 38EN018 38EN024 38EN030 22 38EN036
38EN042 30 8.0 38EN048 30 8.0 38EN060
38ES018 30 38ES024 38ES030 30 38ES036 38ES042 30 38ES048 30 38ES060 39
’SEER — Seasonal Energy Efficiency Ratio. The higher the number, the
less electrical power required to reach a given capacity. SEER is derived by dividing output energy by input energy.
DIAMETERS SEER*
(in.)
30 17
17 17
22
30 8.0
30 10.0 30
(Nominal)
9.0
9.0
9.0
9.0
9.0
8.0
8.0
8.0
8.0
8.0
10.0
10.0
10.0
10.0
10.0
10.0
similar, however, there are distinct differences. Tables 1 and 2 help to differentiate these differences.
Table 2 — Heat Pumps
MODEL
38QH015 38QH018 38QH024 30 38QH030 30 38QH036 38QH042 30 38QH048 38QH060 39
38QN015 38QN018 38QN024 22 38QN030 38QN036 30 38QN042 30 38QN048 30 38QN060 30
38QS018 30 38QS024 38QS030 30 38QS036 30 38QS042 30 38QS048 38QS060 39
tC.O.P. — Coefficient of Performance (heating), determined by dividing
DIAMETERS
(in.)
22 22
30 30
17 17
22
30
30
Btu output by power input required to producethis Btu output.
SEER*
(Nominal)
■ 9.0
9.0
9.0
9.0 2.85
9.0
9.0
9.0
9.0 2.85
8.0
8.0
8.0
8.0 2.55
8.0
8.0
8.0
8.0
10.0
10.0
10.0
10.0
10.0 2.85
10.0
10.0 2.85
CiO.P.t
(Minimum)
2.85
2.85
2.85
2.85
2.85
2.85
2.55
2.55
2.55
2.55
2.55
2.55
2.55
2.85
2.85
2.85
2.85
2.85
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book |l 1 |4 |4
Tab jsa
5a|2a|5a
PC 101
Catalog No. 563-857 Printed in U.S.A. Form 38E.Q-1SM
For replacement items use Carrier Specified Parts.
Pgi
11-85
Replaces; New
Page 2
Factory-Installed Options — Any condensing unit
or heat pump listed in Tables 1 and 2 may be ordered as Basic or in one of 3 factory-option packages. Package
designations are included in model number (excluding

Table 3 — Option Packages

Basic). Example: 38EN0243015A/. SM designates this unit as sheet metal option package. Option package
designations are shown in Table 3.
Basic Sheet Metal Option (SM)
Deluxe Option (DL)
Custom Deluxe Option (CD) Same unit as (DL) except for addition of
Basic Sheet Metal Option (SM)
38EH,ES
Standard unit with no added options. Same unit as Basic except with addition
of louvered inlet casing.
Same unit as (SM) except for addition ■ of start assist components on single phase units, crankcase heater, high­and low-pressure switches, and accumulator.
sound shield around compressor, and Time Guard II device.
38EN
Standard unit with no added options. Same unit as Basic except for addition
of louvered inlet casing.
Table 4 — Condensing Unit Specifications
OUTDOOR
UNIT
MODEL NO.
38-
EH-
015301 018301 024301 030301 036301 AV5535E 042301 AV5542E 048321 AV5546H 060301
EN-
015310 AK8515E 018310 024310 030300
D30320
036320
042300 048300 060300 060310 030500 036500 042500 048500 060500 PY6716AF 060510 PY6716AF 036600 042600 048600 PH5316AD 060600 060610
ES­018
024 030 036 042 048 060
ORIGINAL
COMPRESSOR
MODEL
REZ3-0125 AB5515H MD2315GG MD3215GG
PC6016BD
RES3-0175-PFV H21B243ABC H21A313ABCA MD3215GG H21A363ABCA H21A463ABCA
PC5316BD PC6716AG PC6716AG H21A313DBD H21A373DBD H21A463DBD PY5316AD
H21A373DBE
A21A463DBE
PH6716AF
PH6716AF
AB5515H
CRC1-0175-PFV H23A263ABCA CRH3-0275-PFV CRK3-0325-PFV
AV5546H
REPLACEMENT
COMPRESSOR
■ 38EN663304
38EN663601
PH6766HF
50SR661301 32 38VH660303 50SR661333 50 51HK660304 48GH 662302 50SR661331 54
Basic Sheet Metal Option (SM) Same unit as Basic except for addition
Deluxe Option (DL)
Custom Deluxe Option (CD)
Basic Sheet Metal Option (SM)
OIL CHARGE
MODEL
50QT662300 50SR661301 32 MD2364GE 46 44 5.6 MD3264GE 46 44 50SR661336 50SR661300 50SR661331 54 PC6066ED
51D2661300 17 38EA662301 24 38EN663307 40 38EN663302 MD3264GE 38EN663303 50
PC5366HD PC6766HG 76
PC6766HG 38EN663501 38EN663502 38EN663500 See Note t See Note t See Note $ 38 EN 663600
PH5366HD PH6766HF
Initial Recharge
24
54 54
76 72 '12.7
40 37 46
50
76 .
76 40
50 50 76 76 76 50 50 76 76 76
55 55
55
38QH,QS
Standard unit with no added options.
of louvered inlet casing.
Same unit as (SM) except for addition of start assist components on single phase units, high-pressu.re switch, and Service Sentry device.
Same unit as (DL) except for addition of sound shield around compressor and Time Guard II device.
38QN
Standard unit with no added options. Same unit as Basic, except for addition
of louvered inlet casing.
REFRIG
CHARGE*
(R-22)
20 ■ ■ 6.2
30
50 50 50
15 ,3.2 20 3.7 37 3.8
44
47 47 7.2 72 72 9.5 72 37 47 47 7.2 72 72 9.6 72 47 . 47 7.2
72 7.6 72 9.6 72 12.5
28 7.20 51 7.40
46 6.50 51 7.50 51 7.80 50 12.50
. 6.7
12.5
12.5
7.1
5.6
5.8'
7.6
5.5
5.8
7.6
5.8
6.3
7.3
7.4
8.9
’Factory refrigerant charge is adequate when indoor unit and outdoor unit are the same size
and are connected with 25 ft or less of field tubing of recommended size or Carrier accessory tubing. For tubing requirements beyond 50ft, consult Carrier distributor.
H-R
NOTE: Originally an extended voltage compressor. Select replacement compressor for voltage required: tPF5366HD (200-3-60), PG5366HD (230-3-60). tPF6766HF (200-3-60), PG6766HF (230-3-60).
Page 3
Table 5 — Heat Pump Specifications
OUTDOOR
UNIT
MODEL NO.
38­QH
015 018 024 030 036
042 .
048 060
060341
030 036 042 048 060
036 042 048 060
ON 015
018 024 030 036 042
048 060
036 042 048 060
036 042 048 060
QS 018
024 030 036 042
'Factory refrigerant charge is adequate when indoor unit and outdoor unit are the same
size and are connected with 25ft or less of field tubing of recommended size orCarrier accessory tubing. For tubing requirements beyond 50ft, consult Carrier distributor.
ORIGINAL
COMPRESSOR
MODEL
REZ3-0125-PFV H22B173ABCA
CRC2-0175-PFV AV5532E 50SR661333 AV5535H 50SR661336 AV5542H 50SR661330 AV5546H
WD60000AA WD6051AA 76
H23A563ABCA AV5532E 50SR661415
AV5535E 50SR661413 AV5542E AV5546E 50SR661500 WY6000AA WY6051AA 76
AV5535E 50SR661623 AV5542E AV5546E WH6000AA WH6051AA 76
REZ3-0125-PFV AB5519H MD2315GG MD2364GE MD3215GG MD3515GG AV5542E 50SR661330
PC5316BD PC5366HD PC6016BD
MF3513GB AV5542E PY5316AD See Note t PY6016BD
MH3513GB PH4616AD PH5316AD PH5366HD PH6016BD
AB5515H 50SR661301 32 JD2200AA JD2251AA 50 JD2800AA JD3300AA JD3300AA 50 CRJ3-0300-PFV 38EB660301 55
REPLACEMENT
COMPRESSOR
MODEL
50QT662300 38QF663300 38VH 660303
50SR661331
50SR661414 54
50SR661624 54 50SR661622
38QB662301 50SR661311
MD3264GE 46 MD3564GE 46
PC6066ED 76 MF3563GE 46
50SR661330 PY6066EF 76
MH3563GE 46 PH4666HD 76
PH6066EF 76
JD2851AA
OIL CHARGE
Initial
24 20 40 55 54 50 54 50 54 50 54 50
55 54 50
54
54 50
54 54 50
24 32 46
54 76
54 76
76
50
NOTE: Originally an extended voltage compressor. Select replacement compressor forvoltage-required:
tPF5366HD (200-3-60), PG5366HD (230-3-60).
Recharge
37 52
74 50
50 7.9 50
74 14.1 50
50 74
20 28 44 5.6 44 6.1 . , 44 8.9 50 9.5
72 72
44 8.9 50 72 72
44 8.9
72 72 72
28 46 46 46 51
REFRIG
CHARGE*
(R-22)
5.3
5.5
7.8
7.8
7.9
11.0
12.5
14.1
14.0
7.8
11.0
12.5
7.9
11.0
12.5
14.1
3.6
4.1
9.7
10.8
9.5
9.7
10.8
9.5
9.7
10.8
6.8
7.5
8.5
10.6
11.5

SAFETY CONSIDERATIONS

Service and repair of these units should be attempted only by trained service technicians familiar with Carrier Standard Service Instructions.
All equipment should be installed in accordance with accepted practices and in compliance with all national and local codes.
Power should be turned off when servicing or repair ing electrical components. Extreme caution should be observed when troubleshooting electrical components with power on. Observe all warning notices posted on
equipment.
Refrigeration system contains refrigerant under pressure. Extreme caution should be observed when handling refrigerants. Wear safety glasses and gloves to prevent personal injury. During normal system opera tion, some components are hot and can cause burns. Rotating fan blades can cause personal injury. Appro priate safety considerations are posted throughout this manual where potentially dangerous techniques are addressed.

SERVICE

Cabinet — Certain maintenance routines and repairs
require removal of cabinet panels. All condensing units
and heat pump models of this series have same basic
design with only minor differences. See Fig. 1.
REMOVING LOUVERED CASING — (See Fig. 2.)
1. Turn off all power to unit.
2. Loosen screws around circumference of fan orifice.
3. Remove screws around circumference of basepan.
4. Remove screws along control box support brackets.
5. Carefully remove louvered casing.

A CAUTION

Do not attempt to remove wire grille around coil. Grille is integral part of coil structure and sup ports coil.
REMOVING FAN ORIFICE — (See Fig. 3.)
1. Turn off all power to unit.
2. Remove screws holding grille on top of fan orifice.
3. Unplug wires from fan motor. Fan blades on certain models may have to be removed. Refer to Service — Electrical.
4. Remove screws holding fan orifice to wire grille and control box.
5. Remove fan orifice.
ELECTRICAL BOX ACCESS — (See Fig. 1.)
1. Turn off all power to unit.
2. Remove screws holding box cover.
Page 4
DISCHARGE GRILLE
BASIC CONDENSING UNIT
r-6" AIRFLOW AND SERVICE CLEARANCE ON 3 SIDES — 12" ON REMAINING SIDE
ON 3 SIDES — 12" ON REMAINING SIDE

LOUVERED CONDENSING UNIT

DISCHARGE GRILLE
IVb" DIAM
HOLE WITH 1%" CONCENTRIC KNOCKOUT FOR POWER WIRING (OPP. SIDE)
ELEC. WIRING RACEWAY
LIQUID LINE SERVICE PORT ATSERVlOE VALVE(CLG CYCLE)
SUCTION SERVICE PORT AT SERVICE VALVE(CLG CYCLE)
SUCTION SERVICE PORT (HIDDEN)
COIL SUPPORT
r-6" AIRFLOW AND SERVICE CLEARANCE ON 3 SIDES — 12" ON REMAINING SIDE
DISCHARGE GRILLE
LIQUID LINE SERVICE PORT AT SERVICE­VALVE (CLG
CYCLE) SUCTION
SERVICE POR AT SERVICE VALVE(CLG CYCLE)
SUCTION
SERVICE PORT
(HIDDEN)
4'-0” OVERHEAD SPACE REQUIRED
FOR SERVICE AND AIRFLOW
r-6" AIRFLOW AND SERVICE CLEARANCE ON 3 SIDES —12" ON REMAINING SIDE
BASIC HEAT PUMP UNIT

Fig. 1 — Condensing and Heat Pump Units

LOUVERED HEAT PUMP UNIT

Page 5
SCREWS
TOP COVER
BASEPAN FLANGE
C

Fig. 2 — Louvered Casing Assembly

Fig. 3 — Removing Orifice Fan
Electrical — Exercise extreme caution when work
ing on any electrical components. Shut off all power
to system prior to troubleshooting. Some trouble
shooting techniques require power to remain on. In these instances, exercise extreme caution to avoid danger of electrical shock. ONLY TRAINED SERVICE
PERSONNEL SHOULD PERFORM ELECTRICAL TROUBLESHOOTING.
CONTACTORS — (See Fig. 4.) Contactor provides means of applying power to unit using lower power (24 v) from transformer in order to power the contactor
coil. Depending on unit model, you may encounter
single-, double- or triple-pole contactors to break power.
One side of the line may be electrically hot, so extreme caution must be exercised when troubleshooting.
The contactor coil for these and most residential models of condensing units and heat pumps is powered by 24 vac. If contactor does not operate:
1. With power off, check whether contacts are free to move. Check for severe burning or arcing on contact points.
ATTACHING CASING TO TOP COVER
AND BASEPAN
2. With power off, use ohmmeter to check for continuity of coil. Disconnect leads before checking. A low­resistance reading is normal. Do not look for a specific value as different part numbers used will have different resistance values.
3. Reconnect leads and apply low-voltage power to contactor coil. This may be done by leaving high­voltage power to outdoor unit off, and by turning
thermostat to heat or cool. Check voltage at coil with voltmeter. Reading should be between 20 - 30 volts. Contactor should pull in if voltage is correct and coil is good. If contactor does not pull in, change contactor.
4. With high-voltage power off and contacts pulled in,
check for continuity across contacts with ohmmeter. A very low or zero resistance should be read. Higher readings could indicate burned or pitted contacts which may cause future failures.
Fig. 4 — Contactor
Page 6
CAPACITORS — (See Fig. 5.)

A CAUTION

Capacitors can store electrical energy when power is off. Electrical shock can result if you touch the
capacitor terminals and discharge this stored energy.
Exercise extreme caution when working near capacitors. With power off, discharge stored energy by shorting across the capacitor terminals with a
15,000-ohm, 2-watt resistor, or a screwdriver blade with insulated handle.
Hard-Start Capacitors and PTC Devices — Sometimes, under adverse conditions, a standard run capacitor in a system is inadequate to start compressor. In these instances, a start-assist device is used to provide an extra starting boost to compressor motor. The first device is called a PTC (positive temperature coefficient) or ther
mistor (see Fig. 6). It is a resistor wired in parallel with run capacitor. As current flows through it at start-up, it heats up. As it heats up, its resistance increases greatly, until it effectively lowers current through it to an extremely
low value. This, in effect, removes it from the circuit.
After system shuts down, resistor cools and resistance
value returns to normal, until next time system starts.
Thermistor device is adequate for most conditions,
however, in systems where off cycle is short, device cannot cool fully and becomes less effective as a start device. It is an easy device to troubleshoot. Turn off all power to system.
Check thermistor with ohmmeter as described below.
If indoor coil does not have a bleed-type expansion device, it may be necessary to remove start thermistor and replace with accessory start capacitor and relay.
Shut off all power to unit. Remove PTC from unit.
Wait at least 10 minutes for PTC to cool to ambient
temperature.

RUN CAPACITOR START CAPACITOR

Fig. 5 — Capacitors
Capacitors are used as a phase shifting device to aid in starting certain single-phase motors. Check capacitors as follows:
1. Always check capacitors with power off. Attempting to troubleshoot a capacitor with power on can be dangerous. Defective capacitors may explode when power is applied. Insulating fluid inside is combustible
and may ignite, causing burns. After power is off, discharge capacitors as outlined above. Disconnect capacitor from circuit. Use ohmmeter, check each terminal to ground (use capacitor case). Discard any capacitor that shows resistance. Place ohmmeter leads
across capacitor and place on R x 10k scale. Meter
should jump to a low resistance value and slowly climb to higher value. Eailure of meter to do this indicates an open capacitor. If resistance stays at zero or a low value, capacitor is shorted.
2. Capacitance testers are available which will read value of capacitor. If value is not within ± 10% value stated on capacitor, it should be changed. If capacitor is not open or shorted, its capacitance value is calcu lated by measuring voltage across capacitor and current it draws.

A WARNING

Exercise extreme caution when taking readings while power is on. Use following formula to calculate capacitance:
^ . , r,. 2650 X amps Capacitance (mfd) =
3. Remove any capacitor that shows signs of bulging, dents or leaking. Do not apply power to a defective capacitor as it may explode.
volts
Measure resistance of PTC with ohmmeter. Resistance of 25-ohm PTC is measured between center tab and end tab with jumper across 2 end terminals.
Fig. 6 — PTC Devices
The cold resistance (Rj) of any PTC device should be
approximately 100 - 180% of device ohm rating.
50-ohm PTC = 50 - 90 ohm resistance 25-ohm PTC = 25 - 45 ohm resistance
If PTC resistance is appreciably lower or more than
200% higher than rating, device is defective.
If thermistor is good and compressor does not start, disconnect thermistor from starting circuit. Give com pressor a temporary capacitance boost. Run compressor for 10 minutes, shut off, allow system pressure to equal ize. Reconnect start thermistor. Try restarting com pressor without boost capacitor. If after 2 attempts, compressor does not start, remove thermistor. Add an
accessory start capacitor relay package.
Temporary Capacitance Boost — (See Fig. 7.) There are
times when a temporary capacitance boost is needed to get compressor started. Do not under any circumstances attach temporary boost capacitor directly across com pressor terminals. Serious personal injury can result.
Exercise extreme caution with this procedure when high­voltage power is on. If compressor motor does not start, it may be due to low-line voltage, improper pressure equalization or weak run capacitor. Check each possi bility, attempt capacitance boosting before adding auxiliary start capacitor and relay.
Page 7
220-V FROM UNIT
Fig. 7 — Capacitance Boosting
Turn off power. Check compressor for ground or open.
If there is none, proceed. Obtain a start capacitor approved by compressor manufacturer. Connect wires with insulated probes to each terminal. Touch probes to each side of run capacitor. Energize and start compressor,
pull probes away after about 3 seconds. Discharge start
capacitor. Run compressor about 10 minutes. Stop and
allow to sit idle about 5 minutes. Check system pressure equalization. Attempt to restart without capacitance boost. If compressor does not start after several attempts, add proper auxiliary start capacitor and relay.
If PTC thermistor device is inadequate as start device, a start capacitor and relay may be added to system to insure positive start. Capacitor is wired in parallel with run capacitor through normally closed set of contacts on
a device called start relay. The relay coil is wired across
start and common terminals of cornpressor. The added
capacitance gets compressor started. As compressor comes up to speed, voltage across start and common terminals increases to a value high enough to cause start relay to energize. This opens normally closed contacts and removes start capacitor from circuit. In actual practice, this occurs in a fraction of a second.
To check start relay and capacitor, first turn off all power to unit. Discharge start and run capacitors as outlined earlier. Most start capacitors will have a 15,000­ohm, 2-watt bleed resistor. Disconnect these devices from system. Start capacitor can be inspected visually. It is
designed for short duration or intermittent duty. If left in circuit for prolonged period it blows through a specially designed orifice. If it appears blown, check for stuck contacts in start relay. Start capacitor can be checked by ohmmeter method discussed earlier.

A CAUTION

If bleed resistor is wired across start capacitor, it
must be disconnected to avoid erroneous readings
when ohmmeter is applied across capacitor.
Start relay is checked with ohmmeter. Check for
continuity across coil of relay. You should encounter a high resistance. Since relay contacts are normally closed, you should read low resistance across them.
Both PTC device and capacitor relay start system are
standard equipment on some of these units. They are also available as accessories and may be field installed.
TIME GUARD II — (See Fig. 8.)
Description — Solid-state Time Guard device protects
unit compressor by preventing short cycling. After a
system shutdown. Time Guard provides for a 5 ± 2­minute delay before compressor restarts. On normal start-up, 5-minute delay occurs before thermostat closes. After thermostat closes. Time Guard device provides a 3-second delay to prevent contactor chattering.
Time Guard 11 device is simple to troubleshoot. Only a voltmeter capable of reading 24 v is needed. Device is in control circuit, therefore, troubleshooting is safe with control power (24 v) on and high-voltage power off.
With high-voltage power off, attach voltmeter leads across T1 and T3, set thermostat so that Y terminal is energized. Make sure all protective devices in series with Y terminal are closed. Voltmeter should read 24 v across T1 and T3. With 24 v still applied, move voltmeter lead from T1 terminal to T2 terminal. After 5 ± 2 minutes, voltmeter should read 24 v, indicating control is functioning normally. If no time delay is encountered, or device never times out, change control. A schematic diagram printed on device enables you to troubleshoot this device.
CRANKCASE HEATER — Crankcase heater is a device for keeping compressor oil warm. By keeping oil warm,
refrigerant does not migrate to and condense in com pressor shell. This prevents flooded starts which can severely damage compressor.
Crankcase heaters come in 2 basic types, wraparound
(belly-band) type that is wrapped externally around
compressor shell, and insertion type that is inserted into compressor oil well in shell of compressor. Both types are in this family of units.
Crankcase heater is powered by high-vo\tagt power of unit. Use extreme caution troubleshooting this device with power on. Easiest method of troubleshooting is to apply voltmeter across crankcase heater leads to see if heater voltage is on. Carefully feel area around crankcase heater. If warm, crankcase heater is probably function ing. Do not rely on this method as absolute evidence heater is functioning. If compressor has been running, area will still be warm.
With power off, and heater leads disconnected, check across leads with ohmmeter. Do not look for a specific resistance reading. Check for resistance or an open circuit. Change heater if an open circuit is detected. Some crankcase heaters in this series of units are
equipped with crankcase heater switch installed in series with heater. This energy-saving device shuts off power to heater when temperatures are high enough that heater is not needed. Be sure this switch is functioning normally before condemning crankcase heater.
PRESSURE SWITCHES — Pressure switches are pro tective devices wired into control circuit (low voltage). They shut compressor off if abnormally high or low pressures are present in refrigeration circuit. Depending on unit model, you may find a low- or high-pressure switch, or both, in system.
Low-Pressure Switch — Located on suction line, protects against low suction pressures caused by such events as loss of charge, low airflow across indoor coil, dirty filters, etc. It opens on a pressure drop at about 30 psi. If system pressure is above this, switch should be closed. To check switch, turn off all power to unit, disconnect leads on switch, apply ohmmeter leads across switch.
You should have continuity on a good switch. Because these switches are attached to refrigeration system under pressure, it is not advisable to remove this device for troubleshooting unless you are reasonably certain that a problem exists. If switch must be removed, bleed all system charge so that pressure gage reads 0 psi.
Page 8
ACCESSORY TIME GUARD II DEVICE
-CONTROL BOX
3
Tl
Т2
SEC
BLK DENOTES CLOSED CONTACTS
TIME GUARD II SEQUENCE CHART
OPERATING
TIME
CUT YELLOW WIRE
5MIN-
NOTE: When accessory Time Guard II is used with accessory Service Sentry control on 38QH,QN,QS units, refer to wiring instructions packed with Service Sentry control.
MOUNTING ACCESSORY TIME GUARD II
ON MODEL 38QH,QS,QN
Fig. 8 — Solid-State Time Guard II Description

A CAUTION

Wear safety glasses and gloves when working with
refrigerants. Apply heat with a torch to solder joint and remove switch. Wear safety glasses when using torch. Have quenching cloth available. Oil vapor in
line may ignite when switch is removed.
Braze in 1 / 4-in. flare fitting and screw on replacement pressure switch. Wear safety glasses, observe all safety precautions.
High-Pressure Switch — Located on discharge line, protects against high discharge pressures caused by such events as overcharge, condenser fan motor failure, system restriction, etc. It opens on pressure rise at about 425 psi.
If system pressures go above this setting during abnormal condition, switch opens. Do not attempt to simulate these system abnormalities, as high pressures pose a serious safety hazard. High-pressure switch is also checked with an ohmmeter similar to checking low-
pressure switch. If system pressure is below 425 psi, switch shows continuity. It is replaced in same manner as low­pressure switch. Observe all safety precautions.
TIME GUARD II CONTROL WIRING
CONNECTIONS FOR 38QH,QN,QS UNITS
Liquid Line Pressure Switch — Located on liquid line, used in heat pump only. Function is similar to con ventional low-pressure switch. Because heat pumps experience very low suction pressures during normal system operation, a conventional low-pressure switch
cannot be installed on suction line. Switch is installed in liquid line instead and acts as loss-of-charge protector.
It operates identically to low-pressure switch except it
opens at 5 psi. Troubleshooting and removing this switch is identical to procedures used on other switches. Observe same safety precautions.
DEFROST THERMOSTATS — Defrost thermostat signals heat pump that conditions are right for defrost or that conditions have changed to terminate defrost. It is a thermally actuated switch clamped to liquid line to sense its temperature. Normal temperature range is: closed at 27 - 5 F, open at 80 ± 5 F.
Since defrost thermostat is the heart of the defrost
system, its troubleshooting procedure is described below.
PRINTED-CIRCUIT CONTROL BOARD — Solid­state defrost control used on 38QH,QN,QS heat pumps replaces electro-mechanical timer and defrost relay found on previous Carrier Chronotemp^“ defrost systems. De frost control board can be set to check need for defrost
Page 9
every 30, 50 or 90 minutes of operating time. Control board has additional feature that allows unit to restart in defrost cycle if room thermostat is satisfied during defrost.
Troubleshooting defrost control involves a series of
simple steps that indicate whether board is defective.
NOTE: Procedure allows mechanic to check control board and defrost thermostat for defects. First, trouble shoot to make sure unit operates properly in heating and cooling modes. This ensures problems are not attributed
to the defrost control board. Additional steps follow:
1. Turn thermostat to OFF. Disconnect all power to outdoor unit.
2. Remove control box cover for access to electrical components and defrost control board.
3. Disconnect defrost thermostat leads from control board, connect to ohmmeter. Thermostat leads are the heavy-gage black insulated wires connected to DFT and C terminals on control board. Resistance reading may be 0 (indicating closed defrost thermo stat) or infinity ( oo for open thermostat) depending on outdoor temperature.
4. Jumper between DFT and C terminals on control board as shown in Fig. 9.
Fig. 10 — Inserting Jumper Wire
into Protective Cover
5. Disconnect outdoor fan motor lead. Tape lead to
prevent grounding.
6. Restart unit in heating, allowing frost to accumulate
on outdoor coil.
7. After a few minutes in heating, liquid line tempera
ture should drop below closing set point of defrost thermostat. Using ohmmeter, check resistance across defrost thermostat leads. Resistance of 0 indicates defrost thermostat is closed and operating properly.
8. Remove protective cover from TPl and TP2 speed up terminals. Insert jumper wire into protective cover, reinsert protective cover on speed-up termi nals. This reduces by 1 / 4 timing sequence of original time (see Fig. 10). Since Fig. 10 shows timing cycle set at 30 minutes, unit initiates defrost within approxi mately 30 seconds; if setting is at 50 minutes, within
50 seconds; 90 minutes, within 90 seconds. When you hear reversing valve change position, remove protec
tive cover/jumper, otherwise control will terminate
normal 10-minute defrost cycle in approximately
10 seconds.

A CAUTION

Do not use screwdriver or other means to short speed-up pins. If pins are accidentally grounded, control board is destroyed.
9. Unit is now operating in defrost mode. Using volt meter, check between R and W2 as shown in Fig. 11.
Fig. 11 — Checking Between R and W2
Page 10
Reading on voltmeter should indicate zero volts.
This step ensures defrost relay contacts have closed, energizing supplemental heat and reversing valve solenoid.
10. Unit should remain in defrost no longer than 10 minutes. Actual time in defrost depends on how quickly speed-up jumper is removed. If it takes 3 seconds to remove speed-up jumper after unit has switched to defrost, only 7 minutes of defrost cycle remains.
11. After a few minutes in defrost (cooling) operation, liquid line should be warm enough to have caused defrost thermostat contacts to open. Check resistance across defrost thermostat. Ohmmeter should read infinite resistance, indicating defrost thermostat has opened.
12. Shut off unit power and reconnect fan lead.
13. Remove jumper wire from speed-up terminal pro
tective cover and reinsert cover on speed-up termi nals. Failure to remove jumper causes unit to speed
up operating cycles continuously.
14. Remove jumper between DFT and C terminals.
Reconnect defrost thermostat leads.
15. Replace control box cover. Restore power to unit.
If defrost thermostat does not check out following above steps or incorrect calibration is suspected, check for a defective thermostat as follows:
1. Follow steps 1 - 5 above.
2. Using thermocouple temperature measuring device, route sensor or probe underneath coil (or other
convenient location). Attach to liquid line near defrost thermostat. Insulate for more accurate reading.
3. Restart unit in heating.
4. Within a few minutes, liquid line temperature drops
within a range causing defrost thermostat contacts to close. Temperature range is from 32 F to 22 F. Notice temperature at which ohmmeter reading goes from oc to 0 ohms. Thermostat contacts close at this point.
5. Remove protective cover from TP 1 and TP2 speed-up
terminals, insert jumper wire into protective cover,
reinsert protective cover on the speed-up terminals.
6. Unit changes over to defrost within 90 seconds
' (depending on timing cycle setting). Liquid line tem
perature rises to range where defrost thermostat contacts open. Temperature range is from 75 F to
85 F. Resistance goes from 0 to oc when contacts open.
7. If either opening or closing temperature does not fall
within above ranges, or thermostat sticks in one position, replace thermostat to ensure proper defrost operation.
COLOR-CODED TERMINAL BLOCK
Fig. 12 — Removing Outdoor Fan Motor
motor with 32 drops (16 drops per hole) of SAE 10 non
detergent oil at intervals described below:
a. Annually, when environment is very dirty, ambient
temperature is higher than 105 F (40 C), and average unit operating time exceeds 15 hours a day.
b. Every 3 years, when environment is reasonably clean,
ambient temperature is less than 105 F (40 C) and unit operating time averages 8 to 15 hours a day.
c. Every 5 years, when environment is clean, ambient
temperature is less than 105 F (40 C) and unit oper ating time averages less than 8 hours a day.
After motor is lubricated, be sure fan prop is positioned
correctly on motor shaft. See Fig. 13.
DISCHARGE GRILLE
Fig. 13 — Condenser Fan Position
FAN MOTORS (See Fig. 12.) Fan motor powers fan that draws air through outdoor coil to perform heat exchange. Motors are totally enclosed to increase reli ability. This also eliminates need for rain shield. Motors are provided with color-coded terminal block to facilitate removal. Oilers are provided on motor bearings. Adhere to following schedule for fan motor lubrication.

A CAUTION

Turn off all power to unit before servicing or replac ing fan motor.
Fan Motor Bearings — Oiling holes are provided at each end of condenser fan motor. Remove fan motor, lubricate
Fan motors should present no problem in trouble shooting. A motor with seized or tight bearings can sometimes be saved or have its life extended by adding oil to the bearings.
A CAUTION
Be sure unit main power switch is turned off. Failure to do so may result in electric shock, or injury from rotating fan blade.
For suspected electrical failures, check for loose or
faulty electrical connections, or defective fan motor
10
Page 11
capacitor. Fan motor is equipped with thermal overload device in motor windings which may open under adverse operating conditions. Allow time for motor to cool so device can reset. Further checking of motor can be done with an ohmmeter. Set scale on R x 1 position, check for continuity between 3 leads. Replace motors that show an open circuit in any of the windings. Place one lead of ohmmeter on each motor lead. At same time, place other ohmmeter lead on motor case (ground). Replace any motor that shows resistance to ground. Obviously any motor that shows signs of arcing, burning or over heating should be suspect and replaced.
SERVICE SENTRY CONTROL BOARD — Service Sentry control provides immediate warning when out door heat pump requires servicing. It turns on indoor thermostat light if compressor doesn’t operate for either heating or cooling. This enables owner to obtain speedy heat pump service during heating season, reducing supplementary electric heat costs, and during cooling .season, reducing period of heat discomfort. Fig. 14.
Refer to Fig. 15 for wiring connections when Service
Sentry and solid-state Time Guard II accessories are used.
The Service Sentry is an accessory device. On heat pump DL and CD option packages, a slightly different version of Service Sentry is installed as standard equip ment. It functions almost identically to accessory Service Sentry except that it locks out compressor under certain
adverse operating conditions. System is manually reset by shutting it off at thermostat subbase, then turning it back on. If adverse condition is corrected, system restarts.
One example of an adverse condition would be if
system is located in a desert climate where high operating temperatures may cause system to shut down on the high­pressure switch, or on the compressor internal overload.
Service Sentry Requires 2 Inputs:
1. It must sense a 24-v input from thermostat. As thermo
stat calls for heating or cooling, it supplies 24 v to Service Sentry device.
2. A current transformer (or induction loop) similar to a clamp-on ammeter senses current draw in the com pressor lead. Induction loop must sense a minimum current draw when thermostat is calling for heating or cooling.
NOTES:
1. On a single-phase compressor, induction loop senses
current in common leg.
2. On a 3-phase compressor, induction loop senses current in one of the pha.ses.
Troubleshooting Service Sentry device is easy. With thermostat calling for heating or cooling and compressor running, indoor thermostat light should be off If on, check for wiring errors or replace the Service Sentry.
To check for correct operation, shut off circuit breaker or disconnect switch to outdoor unit while it is running. Signal light on thermostat should light. If this does not
occur, check for wiring errors or replace the Service Sentry.
Fig. 14 — Service Sentry Control
Use Service Sentry control with single-phase Carrier
heat pumps equipped with 24-v control circuit.
Connect black, orange and red pigtails (24 v) on Service Sentry to outdoor unit control circuit terminal board. See Fig. 15 and wiring diagram on unit. An extra control
wire is required between L terminals on outdoor unit, indoor unit and thermostat subbase (the L terminal is currently being added to outdoor and indoor unit termi nal blocks). If units do not already have L terminal, splice control wire between L terminals on Service Sentry and thermostat subbase. Terminal L is labeled terminal X on some thermostat subbases (all future subbases will read terminal L).
Connect all field line power wires to unit in usual
manner. However, route one field line power supply wire through metallic loop on bottom of Service Sentry, then to normal unit connection. On 015 (230-1-60) and 018 (230-1-60) units, pass supply wire through metallic loop twice, as shown in Fig. 14 and 15. On all other units, pass supply wire through loop only once.

A CAUTION

If Service Sentry needs replacing, shut off all power
to unit before attempting repairs.
OUTDOOR THERMOSTATS — (See Fig. 16.) Out door thermostat brings on stages of electric heat as out
door temperature and heat pump output drops. Setting at which thermostat closes is variable, depending on design of system. It is .set at time of installation and should
not be changed without good reason. Up to 2 outdoor thermostats may be installed. Some systems may not
have any thermostat.
Although these devices are installed in control circuit (24 v), turn off all power to unit before attempting to troubleshoot thermostat.
Use a standard ohmmeter to check for continuity through thermostat. If you suspect thermostat is out of calibration, use calibrated electronic thermometer to
determine correct outdoor temperature. Insert a screw driver blade in adjustment slot and turn thermostat switch until it closes. Observe this using ohmmeter across switch. Read temperature setting when switch clo.ses. It should be close to reading observed using electronic thermometer. Any setting within ± 5 degrees is acceptable.
11
Page 12
24-VOLT WIRING
LINE VOLTAGE
*
P
c
PASS SUPPLY WIRE THRU
METALLIC LOOP TWICE ON UNITS WITH NAMEPLATE RLA OF 14 AMPS OR LESS
SUPPLY WIRE
07
THERMOSTAT
SUBBASE
FIELD LINE VOLTAGE SUPPLY WIRE
INDOOR UNIT
TERMINAL
BOARD
OUTDOOR UNIT
TERMINAL
BOARD
C — Contactor LLPS — Liquid Line Low-Pressure Switch TB — Terminal Board
Common Potential Factory Wiring (field connected)
_____
Field-Supplied Wiring
Fig. 15 — Wiring Connections for Service Sentry and Solid-State Time Guard II
>TB
Compressor — The compressor is the heart of the
refrigeration system. It pumps refrigerant through the system. If it malfunctions, the whole system suffers.
The compressor is an electrical (as well as mechanical)
device. Extreme caution should be exercised when work
ing near compressors. Power should be shut off, if possible, for most troubleshooting techniques. Refrig erants in system present other safety hazards.
Always
wear safety glasses and gloves when handling refrigerants.
Compressor failures are classified in 2 broad failure categories, mechanical and electrical. Both types are discussed below and on page 13.
MECHANICAL FAILURES — Compressor is a
mechanical pump driven by an electric motor contained in a welded or hermetic shell. In a mechanical failure, motor or electrical circuit appears normal, but com pressor does not function normally.
12
Page 13
NOTES:
1. Affix capillary and bulb on outside of grille wire nearest control box.
2. Secure bulb to grille with wire ties or suitable fastener.
3. If necessary, shield bulb from direct sunlight using appropriate material.
Fig. 16 — Outdoor Thermostat Installation

A CAUTION

Exercise extreme caution when reading compressor currents, as high-voltage power is on. Correct any of the problems described below before installing and running a replacement compressor. Wear safety glasses and gloves when handling refrigerants.
Locked Rotor — In this type of failure, compressor motor and all starting components are normal. When compressor attempts to start, it draws locked rotor current and cycles off on the internal protection. Locked rotor current is measured by applying a clamp-on ammeter around common lead of the compressor on a single-phase compressor, or any one of the leads on a 3-phase compressor. Then measure current it draws when
it attempts to start. LRA (locked rotor amp value) is stamped on compressor nameplate.
If compressor draws locked rotor amps, and all other external sources of problems have been eliminated, compressor must be changed. Because compressor is a sealed unit, it is impossible to determine exact mechanical failure. However, complete system should be checked for abnormalities such as incorrect refrigerant charge, restrictions, insufficient airflow across indoor or outdoor
coil, etc., which could be contributing to the failure.
Runs, Doesn't Pump — In this type of failure, compres sor motor runs and turns compressor, but compressor
does not pump the refrigerant. A clamp-on ammeter on common leg of a single-phase compressor, or any one lead of a 3-phase compressor, shows a very low current draw, much lower than RLA (rated load amps) value
stamped on compressor nameplate. Because no refrig erant is being pumped, there is no return gas to cool compressor motor. It eventually overheats and shuts off on its internal protection.
Runs — Doesn’t Pump, High-To-Low Side Leak — This
failure is similar to previous one except compressor is
pumping. Usually, an internal problem such as blown head gasket or broken internal discharge line causes compressor to pump hot discharge gas back into its own shell rather than through system.
Using pressure gages on service valves shows high
suction and low discharge pressure readings. Motor currents are lower than normal. Because hot gas is being discharged into shell, the shell becomes hot. The hot gas causes compressor motor to cycle off on its internal protection.
Runs and Pumps, Low Capacity — This failure type is
difficult to pinpoint because extent of damage varies. Compressor is a pump with internal valves that enable compressor to pump properly. On multicylinder com pressors, each cylinder has a complete set of suction and discharge valves. Any of these parts may become damaged or broken causing loss in pumping capacity. Severity of damage determines amount of capacity loss. Use pressure gages to find any abnormal system pressures if system charge and other conditions are normal.
An owner may complain that a unit is not handling the building’s heating or cooling load. The compressor current draw may be abnormally low or high. Although this type of failure does occur, all other possible causes of capacity loss must be eliminated before condemning compressor.
Noisy Compressor— May be caused by variety of inter­nal problems such as loosened hardware, broken mounting springs, etc. May also be caused by system problems. Overcharging a compressor causes operating noise, particularly at start-up. Certain single-cylinder compressors are noisy at start-up and may operate noisily. Too much oil in compressor may cause noise. Normally this problem is encountered only after a replacement compressor has been added, without purging oil from previous compressor. As new compressor
pumps, excess oil in system returns and adds to volume already present, causing noise.
Compressor Leaks — Sometimes a leak is detected at weld seam around girth of compressor, or a fitting that
joins compressor shell. Many of these leaks can be re
paired and the compressor saved if correct procedure is followed. Turn off all power to unit. Remove all refrig erant from system so that gage pressure is 0 psi. Use safety glasses and gloves when handling refrigerants. Clean area around leak to bare metal. Apply flux and repair joint with silver solder.
Do not use low-temperature solder such as 50-50. Clean off excess flux, check for leaks, and apply paint over repaired area to prevent corrosion. Do not use this method to repair a compressor leak due to severe corrosion. Never attempt to repair a compressor leaking at electric terminals. This type of failure requires compressor replacement.
ELECTRICAL FAILURES — The compressor me chanical pump is driven by an electric motor within hermetic shell. In electrical failures, compressor does not run although external electrical and mechanical systems appear normal. Compressor must be checked electrically for abnormalities.
Before troubleshooting compressor motor, review this
description of compressor motor terminal identification.
Single-Phase Motors — See Fig. 17. To determine ter
minals C, S, and R: Turn off all unit power. Short the run
(and start) capacitor to prevent shock. Remove all
wires from motor terminals. Using an ohmmeter on 0-10 ohm scale, read resistance between all pairs of terminals. Determine 2 terminals that provide greatest
resistance reading. Through elimination, remaining
13
Page 14
(example)
TO DETERMINE INTERNAL CONNECTIONS OF SINGLE
PHASE MOTORS (C,S,R) except shaded-pole
Deduction:
©—(D
J OHM METER
0-10 ÍÍ SCALE
Ф
5.2 Í1
0.6 Í!
é

Fig. 17 — Determining Internal Connections

terminal must be common (C). Greatest resistance between common (C) and another terminal indicates start winding because it has more turns. This terminal is start (S). Remaining terminal will be run winding (R).
NOTE: If there is an internal line break protector, it must be closed.
Three-Phase Motors — See Fig. 18. Resistance readings between all 3 sets of windings should be the same.
All compressors are equipped with internal motor pro tection. If motor becomes hot for any reason, protector opens. Compressor should always be allowed to cool and protector to close before troubleshooting. Always turn off all power to unit and disconnect leads at com pressor terminals before taking readings.
Most common motor failures are due to either an open, grounded or short circuit. Directions below are specifi cally for single-phase units, however, they also apply to 3-phase compressors. When a single-phase compressor fails to start or run, 3 tests can help determine the problem. First, all possible external causes should be eliminated, such as overloads, improper voltage, pressure equalization, defective capacitor(s), relays, wiring, etc. If compressor has internal line break overload, be sure it is closed.
@@ (smallest resistance)
(3)—@ (remaining resistance)
5.8 Í1
(greatest resistance)
5.8il (ohm)
0.611
5.211
Run Winding (R) Start Winding (S)
(2) is common (C)
by elimination
(2) is common,
therefore (T) is Start Winding (S)
(J) is Run Winding (R)
Ground Circuit — To determine if a wire has broken or come in direct contact with shell, causing a direct short to ground: Be sure all power is off. Discharge all capaci tors. Remove wires from terminals C, S and R. On hermetic compressors, allow crankcase heaters to remain on for several hours before checking motor to ensure windings are not saturated with refrigerant. Use an ohmmeter on R x 10,000 ohm scale. A megohmmeter may be used in place of ohmmeter (follow manufacturer’s instructions). Place one meter probe on ground or on compressor shell. Make a good metal-to-metal contact.
Place other probe on terminals C, S and R in sequence. Note meter scale. If reading of zero or low resistance is obtained, motor is grounded. Replace compressor.
A compressor of one-ton capacity or less is probably grounded if resistance is below one million ohms. On larger size single-phase compressors, resistance to ground should not be less than 1000 ohms per volt of operating
voltage.
Example:
230-1-60 ... 230 X 1000 = 230,000 ohms minimum.
Open Circuit — To determine if any winding has a break in the internal wires and current is unable to pass through: Be sure all power is off. Discharge all capacitors. Remove
wires from terminals C, S and R. Use an ohmmeter on 0-1000 ohm scale to check resistance from C-R, C-S and R-S. Because winding resistances are usually less than 10 ohms, each reading appears to be approximately zero ohm. If resistance remains at 1000 ohms, an open or
break exists and compressor should be replaced.
Short Circuit — To determine if any wires within windings have broken through their insulation and made contact with other wires, thereby shorting all or part of the winding(s): First, be sure the following conditions are met:
1. Correct motor winding resistances must be known before testing, either from previous readings or from manufacturer’s specifications.
2. Temperature of windings must be as specified, usually about 70 F.
3. Resistance measuring instrument must have an accu racy within ± 5% - 10%. This requires accurate
ohmmeter (such as a Wheatstone bridge or null
balance-type instrument).
4. Motor must be dry or free from direct contact with liquid refrigerant.
Make This Critical Test — (Not advisable unless above conditions are met.) Be sure all power is off. Discharge all capacitors. Remove wires from terminals C, S and R.
Place instrument probes together, determine probe and lead wire resistance. Check resistance readings from C-R,
C-S and R-S. Subtract instrument probe and lead
14
Page 15
resistance from each reading. If any reading is within
± 20% of known resistance, motor is probably normal.
Usually a considerable difference in reading is noted if a
turn-to-turn short is present. SYSTEM CLEAN-UP AFTER BURN-OUT

A CAUTION

Turn off all power to unit before proceeding. Wear safety glasses and gloves when handling refrigerants. Acids formed as a result of motor burn-out can cause burns.
Some compressor electrical failures can cause motor to burn. When this occurs, byproducts of burn, which include sludge, carbon and acids contaminate system.
If burn-out is severe enough, system must be cleaned before replacement compressor is installed. The 2 types of motor burn-out can be classified as mild or severe.
In mild burn-out, there is little or no odor detectable.
Compressor oil is clear or slightly discolored. An acid
test of compressor oil will be negative. This type of failure is treated the same as mechanical failure. Liquid line strainer should be removed and liquid line filter drier installed.
In a severe burn-out, there is a strong, pungent, rotten
egg odor. Compressor oil is very dark. Evidence of burn
ing may be present in tubing connected to compressor. An acid test of compressor oil will be positive. Complete system must be reverse-flushed with refrigerant. Accu-
RateT“ or TXV must be cleaned or replaced. In a heat
pump, accumulator and reversing valve are replaced. These components are also removed and bypassed during
reverse-flushing procedure. Remove and discard liquid line strainer. After system is reassembled, install liquid and suction line filter driers, run system for 2 hours. Discard both driers, install new liquid line drier only.
line and enters metering device at indoor coil. As it passes through metering device, it becomes a gas-liquid mixture. As it passes through indoor coil, it absorbs heat and refrigerant is again changed to gas. The gas is returned to compressor, where it is compressed to a hot gas, and cycle repeats.
In a heat pump (see Fig. 19), the basic cycle is the same. Reversing valve in system decides which coil, indoor or outdoor, becomes evaporator or condenser. In heating mode, indoor coil is condenser. It rejects heat into the home after heat is absorbed by outdoor evaporator coil. Thus, home is heated.
In cooling cycle, indoor coil becomes evaporator. It absorbs heat from home and rejects it out-of-doors through outdoor condenser coil. Thus, home is cooled.
A unique feature of the heat pump is that metering
devices are designed to meter refrigerant in one direction
of flow, and allow refrigerant to pass unhindered in other
direction. If indoor metering device is metering refrig erant, outdoor device bypasses refrigerant and vice versa.
This allows both coils to serve a dual function.
HEATING CYCLE
INDOOR COIL
ACCUMULATOR
DISCHARGE SERVICE PORTAT SERVICE VALVE (HTG CYCLE)
HEAT PUMP
STRAINER
ACCURATER'™
(BYPASSING)
ACCESSORY FILTER DRIER (DUAL FLOW)
/SUCTION \ STRAINER
SERVICE \ OUTDOOR PORT LIQUID LINE COIL
COMPRESSOR REMOVAL AND REPLACEMENT — Once it is determined that compressor has failed and the reason established, compressor must be changed.
Shut off all power to unit. Remove all refrigerant
from system until pressure gage reads 0 psi.

A CAUTION

Wear safety glasses and gloves when handling refrig
erants. Disconnect electrical leads from compressor.
Disconnect or remove crankcase heater. Remove
compressor holddown bolts.
Cut compressor from system with tubing cutters. Do not use brazing torch for compressor removal. Oil vapor may ignite when compressor is disconnected. Scratch matching marks on stubs in old compressor. Make corresponding marks on replacement compressor. Use torch to remove stubs from old compressor and to re
install them in replacement compressor. Use copper couplings to tie compressor back into system. Wear safety glasses when using brazing torch. Evacuate system, recharge, check for normal system operation.

Refrigeration System

REFRIGERATION CYCLE — In a refrigerant system, refrigerant moves heat from one place to another. It is
useful to understand flow of refrigerant in a system.
In a straight cooling system, compressed hot gas leaves compressor and enters condensing coil. As gas passes through condenser coil it rejects heat and condenses into liquid. The liquid leaves condensing unit through liquid
□ O OoQ
□ o Onn
o o
STRAINER
(METERING)
LIQUID LINE SERVICE PORT AT SERVICE VALVE (CLG CYCLE)
COOLING CYCLE
INDOOR COIL
ACCUMULATOR
SUCTION SERVICE
PORT AT SERVICE VALVE (CLG CYCLE)
HEAT PUMP ACCESSORY FILTER DRIEF
(DUAL FLOW)ACCU RATER
ACCURATER (BYPASSING)
OUTDOOR
LIQUID LINE PRESSURE SWITCH
COIL
Fig. 19 — 38QN Heat Pump
Refrigerant Flow Diagrams
LEAK DETECTING — (See Fig. 20.) New installations should be checked for leaks prior to complete charging.

A CAUTION

Always wear safety glasses and gloves when handling refrigerants.
15
Page 16
Fig. 20 — Leak Detector
If a system has lost all or most of its charge, system must be pressurized again, up to approximately 1501b minimum. This can be done by adding refrigerant, using normal charging procedures. Or, it may be pressurized with nitrogen (less expensive than refrigerant). Nitrogen also leaks faster than R-22 and is not absorbed by refrig eration oil. Nitrogen cannot, however, be detected by leak detector.
gage ports for measuring system pressures, and provide
shutoff convenience for certain types of repairs.
Vapor line on all units and liquid line on condensing units are connected to service valves by means of Compatible Fitting. This mechanical-type fitting is also
used as a sweat fitting. Connections are made as follows:
Fig. 21 — Service Valves
COMPATIBLE FITTING

A CAUTION

Due to explosive pressures of nitrogen, it should never be used without a pressure regulator on
the tank.
On the other hand, leaks in a system pressurized with
refrigerant can be spotted with a leak detector which detects extremely small refrigerant leaks. This discussion assumes that system is pressurized with either all refrig erant or a mixture of nitrogen and refrigerant.
If system has been operating for some time, make first check for a leak visually. Since refrigerant carries a small quantity of oil, traces of oil at any joint or connection is
an indication the refrigerant is leaking at that point.
A simple and inexpensive method of testing for leaks is to use soap bubbles. Any solution of water and soap may be used.
Soap solution is applied to all joints and connections in system. A small pinhole leak is located by tracing bubbles in soap solution around leak.
Electronic leak detectors are now available for check ing for leaks. These unquestionably represent the most efficient and easiest method for checking for leaks. There are various types of electronic leak detectors. Generally speaking, they are all portable, most are light weight, and consist of a box with several switches and a probe or sniffer. Detector is turned on and probe is passed around all fittings and connections in system. Leak is detected by either a movement of a pointer on detector dial, by a buzzing sound or a light.
In all instances, when a leak is found, system charge must be hied down and leak repaired before final charging and operation. After leak is repaired, evacuate system, and correct refrigerant charge.
SERVICE VALVES (See Fig. 21.) Service valves pro
vide means for holding original factory charge in outdoor unit prior to hookup to indoor coil. They also contain
Fig. 22 — Carrier Compatible Fitting
CARRIER COMPATIBLE FITTING — (See Fig. 22.) Mechanical Connection to Compatible Fitting — (Mate
one set of connections at a time.)
1. Loosen nut on Compatible Fitting one turn. Do not remove.
2. Remove plug, be sure 0-ring is in groove inside Compatible Fitting.
3. Cut tubing to correct length. Deburr and size properly,
4. Insert tube into Compatible Fitting until it bottoms.
5. Tighten nut until it bottoms on shoulder of fitting. Keep tube bottomed in Compatible Fitting while
tightening nut.
Sweat Connection to Compatible Fitting — (Use refrig­erant grade tubing.)
1. Remove locking nut, rubber 0-ring and Schrader core from valve.
2. Cut tubing to correct length. Deburr and size properly.
3. Insert tube into Compatible Fitting. NOTE: Wrap top and bottom of service valves in wet
cloth to prevent damage by heat. Solder with low­temperature 430 F (221 C) silver alloy solder.
4. Replace Schrader core.
5. Evacuate or purge system with field-supplied
refrigerant.
16
Page 17
This type of fitting is easily repaired if leaks develop.
2. Frontseat liquid line valve.
3. Start unit in cooling mode. Run until suction pressure reaches 5 psig (35 kPa).
4. Shut unit off. Frontseat suction valve.
5. Vent remaining pressure to atmosphere.
Frontseat outdoor section service valves after relieving
refrigerant pressure in system. Back locknut off Carrier Compatible Fitting onto tube. Cut fitting between threads and 0-ring. Remove tubing section remaining in threaded portion of fitting. Discard locknut.
Clean, flux and insert new tube end into remaining
portion of Carrier Compatible Fitting. Wrap valve in wet
cloth to prevent damaging valve. Heat and apply low­temperature solder (430 F [221 C]).
Leaking Sweat Connection — Frontseat service valves and relieve refrigerant pressure in tubing. Clean and flux area around leak and apply low-temperature solder (430 F [221 C]).
Liquid line service valves on all heat pump models
differ from condensing unit valves in that heat pump
connection has 3/8-in. male flare. When making connec
tion, remove flare nut, install it on liquid line prior to
flaring. Flare liquid line using standard flaring tech niques. Valve also contains piston and retainer. Service as follows:
ACCURATER"“ (Bypass Type) COMPONENTS — (See Fig. 23.) AccuRater piston has a refrigerant metering hole through it. Retainer forms a stop for piston in refrigerant bypass mode, and a sealing surface for liquid
line flare connection. To check, clean or replace piston:
1. Shut off power to unit.
2. Pump unit down using Pumpdown Procedure des cribed in this Service Manual.
3. Remove liquid line flare connection from AccuRater.
4. Pull retainer out of body, being careful not to scratch flare sealing surface. If retainer does not pull out easily, carefully use locking pliers to remove it.
5. Slide piston out by inserting a small soft wire, with small kinks, through metering hole. Do not damage
metering hole, sealing surface around piston cones or
fluted portion of piston.
6. Clean piston refrigerant metering hole.
7. Replace retainer 0-ring (Part No. 99CC501052) before reassembling bypass-type AccuRater.

A CAUTION

All outdoor unit coils will hold only factory-supplied amount of refrigerant. Excess refrigerant may cause unit to relieve pressure through internal pressure relief valve (indicated by sudden rise of suction pressure) before suction pressure reaches 5 psig (35 kPa), If this occurs, shut off unit immediately, frontseat suction valve, and vent remaining pressure to atmosphere.
REVERSING VALVE — (See Fig. 24.) In heat pumps, changeover between heating and cooling modes is accomplished with a valve that reverses flow of refrig
erant in system. This reversing valve device is easy to troubleshoot and replace. The reversing valve solenoid can be checked with power off with an ohmmeter. Check for continuity and shorting to ground. With control circuit (24 v) power on, check for correct voltage at solenoid coil. Check for burned or overheated solenoid.
FLARE NUT
Fig. 23 — AccuRater™ (Bypass Type) Components
Service valves provide a convenient shutoff valve useful for certain refrigeration system repairs. System may be pumped down to make repairs on low side without losing
complete refrigerant charge.
1. Attach pressure gage to suction service valve gage port.
Fig. 24 — Reversing Valve
With unit operating, other items can be checked, such
as frost or condensate water on refrigerant lines.
The sound made by a reversing valve, as it begins or
ends defrost, is a loud whooshing noise, as reversing
valve reverses, and pressures in system equalize. An experienced service person detects this sound and uses it as a valuable troubleshooting tool.
Using a remote measuring device, check inlet and outlet line temperatures. Do not touch lines. If reversing valve is operating normally, inlet and outlet temperatures on appropriate lines should be close. Any difference would be due to heat loss or gain across valve body. Tempera tures are best checked with a remote reading electronic­type thermometer with multiple probes. Route thermo couple leads to inside of coil area through service valve mounting plate area underneath coil. Figures 25 and 26 show test points on reversing valve for recording tempera tures. Insulate points for more accurate reading.
17
Page 18
TO OUTDOOR COIL
TP-4
FROM INDOOR COIL VIA SERVICE VALVE ON OUTDOOR COIL
TO ACCUMULATOR
TP-3 TP-2
Use slip couplings to install new valve with stubs back into system. Even if stubs are long, wrap valve with a wet rag to prevent overheating.
After valve is brazed in, check for leaks. Evacuate and
charge system. Operate system in both modes several
times to be sure valve functions properly.
J
TP-1
FROM
COMPRESSOR
DISCHARGE LINE
TP = Test Point TP-2 and TP-3 Cool or cold, may have condensation or frost on both lines
entering valve body, 5F to 10F maximum temperature difference across normally operating valve.
TP-1 and TP-4 Hot, 5 F to 10 F maximum temperature difference across normally operating valve.
Fig. 25 — Reversing Valve (Cooling Mode or
Defrost Mode, Solenoid Energized)
COIL REMOVAL — (See Fig. 27.) Coils on this family of units are ea.sy to remove if required for compressor removal, or to replace coil. Shut off all power to unit.
Remove refrigerant from system through service valves.
A CAUTION
Wear safety glasses and gloves when handling refrig erants. If unit is equipped with a louvered casing, refer to Cabinet Servicing for casing removal procedure.
1. Remove discharge grille by removing 3 (015-030) or
6 (036-060) screws.
2. Remove control box cover (3 screws).
3. Remove fan/motor/orifice assembly by removing, 4 screws (2 in top of control box). Prior to lifting out assembly, unplug motor wires from base of motor.

A WARNING

Avoid possibility of fire and personal injury by cutting tubing.
4. Use midget tubing cutter to cut liquid and vapor lines at both sides of coil. Cut in convenient location for easy reassembly with copper slip couplings.
TP = Test Point TP-1 and TP-2 Hot, 5F to 10F maximum temperature difference across
normally operating valve.
TP-3 and TP-4 Cool or cold, may have condensation or frost on both lines
into valve body, 5F to 10 F maximum temperature difference across normally operating valve.
Fig. 26 — Reversing Valve (Heating Mode
Solenoid De-Energized)
If valve is defective: Shut off all power to unit. Some smaller sizes may require coil to be removed to gain access to reversing valve. See appropriate coil removal section. Remove all charge from system.
Remove solenoid coil from valve body. Remove valve by cutting it from system with tubing cutter. Repair person should cut in such a way that stubs can be easily rebrazed back into system. Do not use hacksaw. This introduces chips into system that cause failure. After
defective valve is removed, wrap it in wet rag and care fully unbraze stubs. Save stubs for future use. Because defective valve is not overheated, it can be analyzed for cause of failure when it is returned.
Braze new valve onto used stubs. Keep stubs oriented correctly. Scratch corresponding matching marks on old valve and stubs, and new valve body, to aid in lining up new valve properly. When brazing stubs into valve, protect valve body with wet rag to prevent overheating.
Fig. 27 — Removing Outdoor Coil
18
Page 19
5. Remove 2 (015,018) or 4 (024,060) screws at base of coil (located at end of large vertical wires in coil support).
6. Lift coil vertically from basepan, place aside carefully. NOTE: When coil is removed, use opportunity to also
remove liquid line strainer. Strainer location is identified by label on liquid line.
7. Reverse procedure to reinstall coil.
COIL CLEANING — (See Fig. 28, 29.) For best unit
efficiency, clean outdoor coil prior to start of each heating
or cooling season. Shut off all power to unit if coil is equipped with louvered casing. Refer to Cabinet Servic ing for casing removal procedure. To clean coil:

A CAUTION

Coil fin damage can result in higher operating costs or compressor damage. Do not use ñame, high­pressure water, steam, volatile or corrosive cleaners on fins or tubing.
Clean coil using vacuum cleaner and its crevice tool. Move crevice tool vertically, close to area being cleaned, making sure tool touches only the dirt on the fins and not the fins. To prevent fin damage, do not scrub fins with tool or move tool horizontally against fins.
If oil deposits are present, spray coil with ordinary
household detergent. Wait 10 minutes, proceed to next step.
Using garden hose, spray coil vertically downward with
constant stream of water at moderate pressure. Keep nozzle at a 15 to 20 degree angle, about 3in. (76 mm) from coil face and 18 in. (457 mm) from tube. Spray so
debris is washed out of coil. Reinstall louvered casing
if necessary. ,
Restore power to unit. LIQUID LINE STRAINER — Heating and cooling
models are equipped with a strainer in liquid line. It is
marked with identifying sticker. Strainer picks up harm
ful debris that may be in system. If it becomes plugged,
system does not perform properly. System pressures become abnormal and compressor may become very hot and cycle off on its protection device. If strainer is plugged, it can be easily removed.
Shut off all power to unit. Bleed off all refrigerant
from system.
CREVICE TOOL
VACUUM CLEANER HOSE
TO 2^ X I OPENINGS ARE IDEAL
Fig. 28 — Crevice Cleaning Tool

A CAUTION

Wear safety glasses and gloves when handling refrig
erants. Remove fan blades and fan motor to gain access to liquid line. Cut tubing with midget tubing cutter near belled connection close to strainer. Peel
off identifying sticker. Unbraze stub.

A CAUTION

Wear safety glasses when brazing. Protect any alumi-
nuih tubing in vicinity ofjoint with wet rag to prevent
overheating. After stub is removed, pull strainer
from line with needle nose pliers. Discard strainer.
Do not install another strainer. Braze liquid line
together using copper coupling. Cut liquid line
between indoor and outdoor units. Install liquid line
filter drier (bifiow drier for heat pump). Evacuate and charge system. Add charge to compensate for volume needed by drier. Check for normal system
operation.
19
Page 20

38E,Q

HEATING a COOLING
New drier takes over function of strainer. If refrigera tion system in outdoor unit is opened for any reason, remove strainer and install a filter drier in liquid line between indoor and outdoor sections.
ACCUMULATOR — Accumulator is a device always found in heat pumps and in some condensing unit models. Under some light-load conditions on indoor coils (on out door coil with heat pump in heating mode), some liquid refrigerant is present in suction gas returning to com pressor. Accumulator stores liquid, allows it to boil off into a vapor so it can be safely returned to compressor. Since compressor is designed to pump refrigerant in its
gaseous state, introduction of liquid into it could cause
severe damage or total failure of compressor.
Accumulator is a passive device which seldom needs
replacing. Occasionally its internal oil return orifice or
bleed hole may become plugged. Some oil is contained in refrigerant returning to compressor. It cannot boil off in accumulator with liquid refrigerant. Bleed hole allows a small amount of oil and refrigerant to enter return line where velocity of refrigerant returns it to compressor. If bleed hole plugs, oil is trapped in accumulator, and compressor will eventually fail from lack of lubrication. If bleed hole is plugged, accumulator must be changed. Bleed hole is so tiny, cleaning efforts usually are not successful. The only other reason for changing accumu lator is if it leaks and is not repairable.
To Change Accumulator: Shut off all power to unit. Remove all refrigerant Ifom system.

Condensing Units and Heat Pumps

A CAUTION

Wear safety glasses and gloves when working on refrigerants. Remove discharge grille and remove fan orifice. Refer to Cabinet Servicing section. Some
models may require louvered casing and coil to be removed for access to accumulator. Refer to appro priate sections of Service Manual for instructions.
When accumulator is exposed, remove it from system
with tubing cutters. Scratch matching marks on tubing
stubs and old accumulator. Scratch matching marks on
new accumulator. Unbraze stubs from old accumulator and braze into new accumulator. Thoroughly rinse any flux residue from joints and paint with corrosion-
resistant coating such as zinc-rich paint. Reinstall accumulator into system with copper slip couplings.
Evacuate and charge system.
Pour and measure oil quantity (if any) from old accumulator. If more than 20% of oil charge is trapped in accumulator, add oil to compressor to make up for this loss.
SYSTEM CHARGING (for all approved combinations) — System must be charged correctly for normal system operation and reliable operation of components.

A CAUTION

Always wear safety glasses and gloves when hand ling refrigerants. If system has lost all charge, weigh
in charge. Use dial-a-charge or digital scale.
If system has some charge, charts are available to check
and add small amounts of refrigerant with system
running. Refer to individual unit installation instructions
for charge charts.

A CAUTION

Heat pump charts are for checking charge and per
formance and for adding a small amount of charge.
During heating mode, correct method of charging is
the weight method. In heating mode, check should
be made approximately 15 minutes after a defrost, with unit running with a clean coil. In cooling cycle, system should run at least 10 minutes for tempera tures and pressures to stabilize. All charts assume there are no system abnormalities and indoor coil airflows are correct. If system abnormalities exist, correct them before checking system charge.
' BookM |1 |4 |4 PC101 Catalog No. 563-857 Printed in U.S.A. Form 38E.Q-1SM Pg 20 11-85 Replaces: New
Tab |3a|5a|2a j5a For replacement Items use Carrier Specified Parts.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Loading...