Certified dimension drawings are available on request
i'-0"(B0TH SIDES)
ra SPACE REQ'D FOR SERVICE
^ AIRFLOW
(BOTH SIDES)
Fig. 1 — Dimensions and Connections (Table 1)
Table 1 — Installation Data (Fig. 1)
UNIT 38CQ
OPER WT (lb)
UNIT DIM. (ft-in.)
Length A
Width B
Height C
REFRIG CONN (in.)
Suction* (ODF)
Liquid* (ODF)
‘Recommended field supplied refrigerant line sizes
UNIT 38CQ015
SUCTION (in. ODF)
LIQUID (in. ODF)
tMay use 7/8-in accy tubing package (slight capacity loss) See p 3
NOTES:
1 Maximum length of interconnecting tubing is 50 feet
2 Units 38CQ044, 048 factory supplied with 3/4 to 1-1/8 in suc
tion valve adapter (field installed) for field-supplied 1-1/8 in
suction line
; 015 1 Ò20
TÌ45 j_160
I -4^1 -4% 11 -4Vs[ 2-0)41 2-0yB|2-0VB 12-6Vs
Compatible Fitting (Suet) & Flare (Liq)
027
033
166 180
2-10V4
1-10
039
210
048
044
212 220
Ys I % I %
%
020 [027033
5/
Vs 1 ^4
78
039
044t 048t
V
78
%
%
fZ 1
IVb
INSTALLER'S PRELIMINARY SURVEY
Step 1 — Unpackage Unit — Move heat pump to
final location. Open carton at end marked
“compressor end.” Slide unit from carton taking
special care to not damage service valves or grilles.
Step 2 — Inspect Equipment — File claim with
shipping company if shipment is damaged or
incomplete.
Step 3 — Complete or Consider the Following
before installing the 38CQ unit.
Consult local building codes and National
Electrical Code (NEC) for special installation
requirements.
When installing unit, allow sufficient space for
airflow clearance, wiring, refrigerant piping and
servicing unit. Position unit so water or ice from
roof will not drop directly on top of unit.
Make provisions for condensate drainage and
defrost water disposal whether unit is installed on
ground or roof. (Make sure unit base pan drainage
holes are not blocked.) See Mounting Pad for
details. Roof installation method for 38CQ
depends on building construction and special re
quirements of local codes. Roof must be capable of
supporting unit weight. Maximum allowable ver
tical distance between indoor and outdoor sections
is 50 feet. See Table 2.
Use an indoor coil with a bleed-type expansion
device. (See Table 2 for Carrier approved indoor
sections.) If coil does not have a bleed-type
expansion device, it may be necessary to add an
accessory start capacitor and relay to heat pump.
This would require removing compressor start
thermistor (PTC device) on units so equipped. It is
recommended that 38CQ units be used with
Carrier approved indoor sections, all of which are
equipped with a bypass type AccuRater'^^ (bleed-
type expansion device).
Table 2 — Carrier Approved 38CQ System Data
INDOOR UNIT
OUT
DOOR
UNIT
^ .38CQQ15
38CQ020
38CQ027
38CQ033
38CQ039
38CQ044
38CQ048
‘Indoor units that require replacement of AccuRater refrigerant
control piston for optimum performance when used with specified
outdoor unit The 38CQ048 is factory supplied with no 8 piston for
indoor unit (28MQ048)
REFRIG
ERANT
22
Fan
Coi
4gAQpi8
^^^40AQ024
40AQ024*
40AQ030
40AQ030*
40AQ036^_
40FSJI60|28MQ036
40AQ036*
40FS160
4ÒFSÌ60
40FS160
40FS200
40FS200
28MQ036'
'28MQ042
28MQ042*
28MQg48^
28MQ048''
AccuRafer
Piston
.
.. 6
. 6
.. .Tt...
j HEIGHT (ft)
; Above 1 Be low
II
2
4*
4 .
6*
. If .
7
8*
I
Indoor Unit
Outdoor Unit
5050
(g) Carrier Corporation 1977
38CQ400105 B
Form 38CQ-6SI
MOUIMTirJtTP^
Step 4 — On the Ground: Mount Unit on a Solid,
Level Concrete Pad. See Fig. 2 for pad dimensions.
Position unit so that coil drainage holes in base pan
overhang the pad. Make sure pad does not obstruct
drainage holes (holes drain water during heating
and defrost cycles). Unit can be attached to pad
with mastic adhesive or by drilling holes in base
pan for 1/4-in. mounting bolts.
Construct pad a minimum of 6-in. thick to
provide clearance under holes for drainage and ice
buildup. In areas where prolonged subfreezing
temperature or heavy snows occur; increase clear
ance to 12 to 18 in. by constructing an angle iron
frame to support unit 12 to 18 in. off concrete
base. Cross angle of frame must not obstruct coil
drainage holes. See Fig. 3 for recommended frame
construction. Extend a 12-in. gravel apron around
pad for condensate and defrost water drainage
field.
Step 5 — On the Roof: Mount Unit on a Level
Platform or Frame: Unit must be elevated for
proper clearance as described under ground in
stallation above. Roof design and water drainage
must be planned to prevent unit from setting in
water. Flash all roof openings to prevent leaks.
«AtMtAK'tMV.VA'Kry.-
mtm
Fig. 3 — Heat Pump Mounting Frame
PART NO.
38CQ900081
38C 0900111
38CQ900182
38GS900381
38CQ900061
38CQ900091
38RQ900001
38RQ900021
1hH22AG110
Low-Voltage Control — Honeywell Thermostat HH07AT071 and
Thermostat Subbase HH93AZ073 — (Automatic Changeover)
Low-Voltage Control — Honeywell Thermostat HH07AT071 and
Thermostat Subbase HH93AZ075 — (Manual Changeover)
Service Sentry (Six HN65CT002)
Start Capacitor and Relay Package
Flare (3/8-in.) to Compatible (3/8-in.) Couplings (Two-Pack)
Liquid Line Filter-Drier
Emergency Heat Relay (Required with 2 outdoor thermostats.)
(Service Parts)
Outdoor Thermostat (Six 38RQ900032)
Optimizer Control
38CQ900141Solid State Time Guard (24 volt)
TUBING
PACKAGE
Length
(ft)OD1 ube End
Liquid
(in.)OD (in.)
38GC900031
38GC900041
38GS900221
38GC90006135
38GC900191
38GC90007110
38GC900081
38GC90009125
38GC90010135
38GC900m
38CQ900001
38CQ9000n25
38CQ90002135
38CQ900031
*Suction line is insulated and has a 90 bend at one end
fFor 5/8-in evaporator connection, cut off 3/4-in end
10
18
25
%%
%
%
Ha
50
18
50
18
50
V4
V
V
4
V
4
V
4
V
4
4
V
4
V
4
___
Table 3 — Accessories
DESCRIPTION
TUBING
Va
Va
Va
Va
Va4
4
V
4
Va
Va
V
4
Va
Va
Va
ICapacity reduction may occur when 7/8-in accessory tubing is used
on 38CQ044.048
____
Suction*
OD
(in.)
VaV4tVa
Va
VaV4tVa
VaV4ÎVa
VaV4t
1 ube bnd
OD (in.)
Evap
V4t
V4
V4V4
V4
V
4
V4
V
4
V4V4
Vat
Vai
V
4
4
V4
Vai
V4
Cond
Va
V
4
y
4
y
4
y
4
y
4
y
4
y
4
4
V4
4
UNIT
38CQ015,020
38CQ027,033
38CQ039,044,048
PIPING CONNECTIONS
The 38CQ units can be connected to indoor
units using Carrier accessory tubing package or
field-supplied tubing of refrigerant grade. See
Table 1 (with notes) for unit piping connection
type, size and line size recommendations and
Table 3 for accessory tubing sizes. Maximum
length of refrigerant piping allowed is 50 feet
A capacity reduction will result if accessory
tubing is used in 38CQ044,048 systems. For
example, when a 25-ft, 7/8-in. accessory tubing
package is used, there will be a capacity reduction
of 1-1/2%. For maximum capacity, use 1-1/8 in.
suction line as recommended in Table 1.
When other than 25 ft of interconnecting
piping is used, follow special requirements de
scribed in Refrigerant Charging. Do not use less
than 10 ft of accessory liquid line. Do not cut
5/16-in. or 1/4-in. liquid line. Do not cut 7/8-in.
suction line. Bend or coil to fit.
Do not use damaged or contaminated tubing.
Always evacuate or purge evaporator coil and
tubing system (use field-supplied refrigerant, not
unit refrigerant).
When making tubing connections, be sure to
provide clearance at unit for electrical connections.
To assure noise-free installation, isolate refrig
erant lines from ductwork and framing or where
they run thru stud spaces, enclosed ceilings or pipe
chases. Use isolation hangers (Fig. 4), as rigid
fastening may transmit pulsations to structure,
creating an objectionable rumble. Do not attach
liquid line to uninsulated suction line. When
running thru structure, surround all lines with 1-in.
insulation to prevent transmission of vibration.
Before Connecting Refrigerant Lines, replace the
AccuRater'^'''^ refrigerant control piston in the
indoor coil as required. See Table 2. The 38CQ048 is
factory supplied with a No. 8 AccuRater piston for
installation in 28MQ048. For piston replacement
instructions, see AccuRater’’"''^ Servicing on page 15.
Step 6 — Connect Refrigerant Lines to fittings on
unit suction and liquid service valves (Fig. 1).
Liquid service valve has flare fitting; suction service
valve has Compatible Fitting. Make suction line
connection first. Slide flare nut on liquid line, then
flare and connect liquid line. (Do not disassemble
AccuRater.) Unit Compatible Fitting permits
mechanical (quick-connect) or sweat connection as
described below. It is not necessary to flare system
liquid line if an accessory flare to Compatible
Fitting coupler is used for liquid line connection.
See Accessory Coupler (Fig. 5).
38CQ044,048 UNITS - When using 1-1/8 in.
field-supplied suction line, remove suction line
adapter taped to compressor suction line. Sweat
connect refrigerant suction line to 1-1/8 in. end of
adapter. Connect 3/4-in. end of adapter to unit
suction line Compatible Fitting.
When a 7/8-in. field-supplied suction line is
used on 38CQ039, a field-supplied 3/4-in. to
7/8-in. suction line adapter must be provided (not
required if 38CQ accessory tubing is used).
MECHANICAL CONNECTION TO COMPATIBLE
FITTING (Mate one set of connections at a time.)
1. Loosen nut on Compatible Fitting one turn. Do
not remove.
2. Remove plug and be sure 0-ring is in the groove
inside the Compatible Fitting.
3. Cut tubing to correct length.
4. Insert tube into Compatible Fitting until it
bottoms.
5. Tighten nut until it bottoms on back coupler
flange. Keep tube bottomed in Compatible
Fitting while tightening nut.
SWEAT CONNECTION TO
COMPATIBLE
FITTING (Use refrigerant tubing.)
Remove locking nut,
1.
rubber 0-ring and
Schrader core from valve.
2.
Cut tubing to correct length.
3.
Insert tube in Compatible Fitting. Wrap top and
bottom of service valves in wet cloth to prevent
damage by heat. Solder with low temperature
(450 F) silver alloy solder.
4.
Replace Schrader core.
5.
Evacuate or purge system with field-supplied
refrigerant.
ACCESSORY FLARE TO COMPATIBLE COU
PLER is shown in Fig. 5. Attach flare nut on
coupler to flare fitting on unit liquid service valve.
Connect liquid line to Compatible Fitting using
mechanical or sweat connection. When mechanical
connection is made, use 2 wrenches when tighten
ing Compatible Fitting nut — one to hold coupler
and one to tighten nut. Liquid line must be flared
if coupler is not used.
Fig. 5 — Accessory Coupler
ELECTRICAL DATA AND WIRING
Field wiring must comply with local and
national fire, safety and electrical codes. Voltage to
unit must be within ± 10% of voltage indicated on
*Permissible limits of the voltage range at which the units will
operate satisfactorily
fRequired when using nonmetallic conduit
^Maximum dual element fuse size
230/1254207
200/
230/3
200/3
230/3
VOLTAGE*
MaxMin
25418087
2291808718.6
254
20770
COMPR
LRA
8819.82.41036
94
106
7917.4
8718.6
67
70
BRANCH CIRCUIT
FAN
FLA
RLA
9.0
17.72.41042
22.2
25.0
25.0
13.0/
11.5
15.0
16.7
16.7
.91431
.9124012
2.41033
2.4
3.0
2.0/
2.0
2.41231
2.41035
3.01035
2.412
2.412
3.012
NOTES:
1 Fan motors are 200-v or 230-v, single phase
2 All units have 24-v control circuit which requires external
power source
3 Copper wire sizes based on 60 C Use copper or copper-clad
aluminum wire only Use latest National Electrical Code for
wire sizing
Power
Wire
Size
(AWG)
846
8
12
Max
Ft
Wire
468
4012
4112
36
361235
Gnd
Wire
Sizef
(AWG)
1420
10
10
1050
850
1240
1040
1040
12
Max
Fuse
Ampsi
20
40
45
50
30/
25
35
35
V
f
THERMOSTAT
SUBBASE
HH93AZ073 OR
HH93AZ075
40AQ FAN COIL
COOLING CONTROL KIT
TERMINAL BOARD
38CQ
TERMINAL
BOARD
THERMOSTAT
SUBBASE
HH93AZ0730R
HH93AZ075
(38CX) WITH 40AQ OR 40FS/28MQ
EQUIPPED WITH ELECTRIC HEATER;
EMERGENCY HEAT, ONE OUTDOOR THERMOSTAT)
40AQ OR 40FQ
ELECTRIC HEATER
TERMINAL BOARD
38CQ
TERMINAL
BOARD
THERMOSTAT
SUBBASE
HH93AZ073 OR
HH93AZ075
COOLING AND TWO-STAGE HEATING
(38CQ WITH 40AQ OR 40FS/28MQ
EMERGENCY HEAT, NO OUTDOOR THERMOSTATS)
EQUIPPED WITH ELECTRIC HEATER;
40AQ OR 40FQ
ELECTRIC HEATER
TERMINAL BOARD
B
EHR — Emergency Heat Relay
ODT — Outdoor Thermostat
_______
Factory Wiring
_______
Field Wiring
38CQ
TERMINAL
BOARD
THERMOSTAT
SUBBASE
HH93AZ073 OR
HH93AZ075
COOLING AND TWO-STAGE HEATING
EQUIPPED WITH ELECTRIC HEATER;
EMERGENCY HEAT, TWO OUTDOOR THERMOSTATS)
*Transformer (60 va) located in cooling control kit or electric heater
fTerminal L is identified as terminal X on some former thermostats
(Required for accessory Service Sentry)
:|;Remove factory-installed jumpers (connection B) when installing
outdoor thermostats (ODT)
Fig. 6 — Control Circuit Connections
40AQ OR 40FQ
ELECTRIC HEATER
TERMINAL BOARD
(38CQ WITH 40FS/28MQ
38CQ
TERMINAL
BOARD
nameplate. On 3'-phase units, phases must be
balanced within 2%. Contact local power company
for correction of improper line voltage.
When making electrical connections, provide
clearance at unit for refrigerant piping connections.
See Table 4 for recommended wire and fuse sizes.
Step 7 — Install a Branch Circuit Fused Disconnect
of adequate size to handle unit starting current.
Provide a separate fused disconnect for outdoor
unit, indoor unit and for each accessory electric
heater circuit as required. (See Indoor Unit and
Electric Heater Installation, Start-Up and Service
Instructions.) Locate disconnect(s) within sight of
and readily accessible from the unit, per section
440-14 of National Electrical Code (NEC).
Step 8 — Bring Line Power Leads Into Unit —
Extend leads from fused disconnect thru hole
provided in service embossment (Fig. 1) and thru
7/8-in. hole into control box.
Step 9 — Connect Ground Lead to a Ground Lug
in Control Box for safety. Connect power wiring.
See Fig. 7. Splice line power leads to yellow and
black pigtails on single-phase units or to black
pigtails (3) on 3-phase unit. Use wire nuts supplied
with unit. Tape each connection.
Step 10 — See Indoor Unit and Electric Heater
Installation, Start-Up and Service Instructions for
line power wiring details. All control wiring is
shown in this booklet.
Step 11 — Control Power Wiring (24 v) is brought
thru hole in unit service embossment. Fig. 1.
Connect leads to control wiring terminal board
(located on outside of control box) as shown in
Fig. 6.
3-PHASE
CONN. TO
FUSED
DISCONNECT
I-PHASE
CONN. TO
FUSED
DISCONNECT
_________
L
------------
BLK-
GROUND LUG
38CQ HEAT PUMP
CONTROL BOX
Fig. 7 — Line Power Connections
BLK-
YEL OR BLK
------
emergency heat switch in the indoor thermostat
subbase. The thermostat locks out compressor and
the relay bypasses the outdoor thermostats for
electric heater operation during heat pump shut
down. When one outdoor thermostat is used, an
emergency heat relay is not required. The emer
gency heat switch in the indoor thermostat subbase
bypasses outdoor thermostat, locks out compressor
and activates electric heater. See 40FS Indoor Unit
and Electric Heater Installation, Start-Up and
Service Instructions for installation of emergency
heat relay.
Use indoor unit transformer as 24-v supply for
system. At least a 60-va transformer is recom
mended. Carrier approved indoor units are
equipped with 60-va transformer. See indoor unit
data.
Use Carrier accessory indoor thermostat
HH07AT071 with HH93AZ073 or HH93AZ075
subbase.
IWITIAL START-UP
The 38CQ unit is equipped with a crankcase
heater. It is recommended that heater be energized
a minimum of 24 hours before starting unit. To
energize heater only, turn the thermostat to OFF
position and close electrical disconnect to heat
pump.
Heat Anticipator Settings for Room Thermostat
(HH07AT071) — Set anticipator settings for room
thermostat according to Table 5. These settings
may be changed slightly to provide a greater degree
of comfort for a particular installation.
Table 5 — Thermostat Anticipator Settings
UNIT
38CQ
015
020
027
033
039
044
048
FIRST-
STAGE
ANTICIPATOR
SETTING
Fixed
INDOOR
UNIT WITH
ELECTRIC
HEATER
40AQ Fan-Coil
with 40AQ Htrs
40FS/28MQ
with 40FQ
Htrs
HTR
KW
5 0
7 5
10 0
15 0
20 0
25 0
30 0
34 0
second-
stage
ANTICIPATOR
SETTINGS
16
33
49
Accessory Outdoor Thermostat provides adjustable
outdoor control of accessory electric heater. This
thermostat makes contact when a drop in outdoor
temperature occurs. It energizes a stage of electric
heat when the outdoor temperature setting is
reached, provided the room thermostat is on the
second stage of heating. One outdoor thermostat is
recommended for each stage of electric heat after
the first stage. Set the outdoor thermostat(s)
progressively lower for each stage. Refer to heat
load of building and unit capacity to determine the
correct outdoor thermostat settings.
The accessory emergency heat relay is required
when 2 outdoor thermostats are used. It is auto
matically energized by the manually operated
Accessory Outdoor Thermostat(s) Installation —
Install outdoor thermostat at a suitable location on
the outside of the control box. Use any free hole
to fasten thermostat bracket. Be sure that engage
ment screw does not interfere with wiring or
components inside of control box Thermostat
bracket may be secured with only one screw;
however, make sure that bracket is firmly attached
to resist vibration forces. If a free hole is not
available, drill hole in control box after assuring
that drilling will not damage any components
inside of box If a second thermostat is used,
follow the procedure outlined above. If there is no
available space on the control box for a second
thermostat, mount the 2 thermostats together.
Connect the 2 thermostats with a machine screw,
lock washer and nut, and then mount assembled
thermostats to the control box (See Fig. 8a).
Route the capillary and attached bulb below the
control box to the upper portion of the outdoor
coil grille. Carefully insert the bulb between the
tube sheet and nearest vertical grille wire. Place the
bulb across the grille and fasten with wire, wire ties
or other suitable fastener (See Fig. 8b). Never
expose bulb to direct sunlight. If necessary, shield
bulb with appropriate material.
Replace access wrapper on unit. Check that
capillary is not pinched by wrapper
To Start Unit — (Make sure crankcase heater has
been energized for 24 hours.) Adjust the thermo
stat as follows:
1. Set selector switch at OFF.
2. Turn on main disconnect switch(es) to indoor
and outdoor units.
3. Set fan switch as desired (ON or AUTO.).
4. Set thermostat dial at desired temperature.
5. Set selector switch at HEAT or COOL.
Check system refrigerant charge. See Refrig
erant Charging.
SERVICE
Refrigerant Charging — The 38CQ units contain
correct operating charge for complete system when
connected to 40FS/28MQ or 40AQ indoor units
with 25 ft of tubing of recommended diameter.
Charge adjustment is required on other systems.
Adjust system charge for refrigerant line lengths
and diameters that differ from 25 ft and 3/8-in.
V
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.