Carrier 38CQ User Manual

Page 1
Carrier Parkway • Syracuse, N Y 13221
Heat Pump - Outdoor Section
4'0" OVERHEAD SPACE REQ'D FOR SERVICE AND AIRFLOW
0 AIRFLOW
CLEARANCE
LIQUID LINE CONN
LIQUID LINE VALVE
Certified dimension drawings are available on request
i'-0"(B0TH SIDES)
ra SPACE REQ'D FOR SERVICE
^ AIRFLOW
Fig. 1 — Dimensions and Connections (Table 1)
Table 1 — Installation Data (Fig. 1)
UNIT 38CQ OPER WT (lb) UNIT DIM. (ft-in.)
Length A Width B Height C
REFRIG CONN (in.)
Suction* (ODF)
Liquid* (ODF)
‘Recommended field supplied refrigerant line sizes
UNIT 38CQ 015 SUCTION (in. ODF) LIQUID (in. ODF)
tMay use 7/8-in accy tubing package (slight capacity loss) See p 3 NOTES: 1 Maximum length of interconnecting tubing is 50 feet
2 Units 38CQ044, 048 factory supplied with 3/4 to 1-1/8 in suc
tion valve adapter (field installed) for field-supplied 1-1/8 in suction line
; 015 1 Ò20
TÌ45 j_160
I -4^1 -4% 11 -4Vs[ 2-0)41 2-0yB|2-0VB 12-6Vs
Compatible Fitting (Suet) & Flare (Liq)
027
033
166 180
2-10V4
1-10
039
210
048
044
212 220
Ys I % I %
%
020 [027 033
5/
Vs 1 ^4
78
039
044t 048t
V
78
%
%
fZ 1
IVb
INSTALLER'S PRELIMINARY SURVEY
Step 1 — Unpackage Unit — Move heat pump to
final location. Open carton at end marked “compressor end.” Slide unit from carton taking special care to not damage service valves or grilles.
Step 2 Inspect Equipment — File claim with
shipping company if shipment is damaged or incomplete.
Step 3 — Complete or Consider the Following
before installing the 38CQ unit.
Consult local building codes and National Electrical Code (NEC) for special installation requirements.
When installing unit, allow sufficient space for airflow clearance, wiring, refrigerant piping and servicing unit. Position unit so water or ice from roof will not drop directly on top of unit.
Make provisions for condensate drainage and defrost water disposal whether unit is installed on ground or roof. (Make sure unit base pan drainage holes are not blocked.) See Mounting Pad for details. Roof installation method for 38CQ depends on building construction and special re quirements of local codes. Roof must be capable of supporting unit weight. Maximum allowable ver tical distance between indoor and outdoor sections is 50 feet. See Table 2.
Use an indoor coil with a bleed-type expansion device. (See Table 2 for Carrier approved indoor sections.) If coil does not have a bleed-type expansion device, it may be necessary to add an accessory start capacitor and relay to heat pump. This would require removing compressor start thermistor (PTC device) on units so equipped. It is
recommended that 38CQ units be used with Carrier approved indoor sections, all of which are equipped with a bypass type AccuRater'^^ (bleed-
type expansion device).

Table 2 — Carrier Approved 38CQ System Data

INDOOR UNIT OUT DOOR
UNIT
^ .38CQQ15
38CQ020
38CQ027
38CQ033
38CQ039
38CQ044
38CQ048
‘Indoor units that require replacement of AccuRater refrigerant
control piston for optimum performance when used with specified outdoor unit The 38CQ048 is factory supplied with no 8 piston for indoor unit (28MQ048)
REFRIG
ERANT
22
Fan
Coi
4gAQpi8
^^^40AQ024
40AQ024* 40AQ030 40AQ030*
40AQ036^_
40FSJI60|28MQ036
40AQ036* 40FS160 4ÒFSÌ60 40FS160 40FS200
40FS200
28MQ036'
'28MQ042
28MQ042*
28MQg48^
28MQ048''
Accu­Rafer Piston
.
.. 6
. 6 .. .Tt...
j HEIGHT (ft)
; Above 1 Be low
II
2
4*
4 .
6*
. If .
7
8*
I
Indoor Unit
Outdoor Unit
50 50
(g) Carrier Corporation 1977
38CQ400105 B
Form 38CQ-6SI
Page 2

MOUIMTirJtTP^

Step 4 — On the Ground: Mount Unit on a Solid,
Level Concrete Pad. See Fig. 2 for pad dimensions.
Position unit so that coil drainage holes in base pan overhang the pad. Make sure pad does not obstruct drainage holes (holes drain water during heating and defrost cycles). Unit can be attached to pad
with mastic adhesive or by drilling holes in base
pan for 1/4-in. mounting bolts.
Construct pad a minimum of 6-in. thick to provide clearance under holes for drainage and ice buildup. In areas where prolonged subfreezing temperature or heavy snows occur; increase clear ance to 12 to 18 in. by constructing an angle iron frame to support unit 12 to 18 in. off concrete base. Cross angle of frame must not obstruct coil drainage holes. See Fig. 3 for recommended frame construction. Extend a 12-in. gravel apron around pad for condensate and defrost water drainage field.
Step 5 — On the Roof: Mount Unit on a Level Platform or Frame: Unit must be elevated for
proper clearance as described under ground in stallation above. Roof design and water drainage must be planned to prevent unit from setting in water. Flash all roof openings to prevent leaks.
«AtMtAK'tMV.VA'Kry.-
mtm
Fig. 3 — Heat Pump Mounting Frame
Page 3
PART NO.
38CQ900081
38C 0900111 38CQ900182
38GS900381 38CQ900061 38CQ900091
38RQ900001
38RQ900021
1hH22AG110
Low-Voltage Control — Honeywell Thermostat HH07AT071 and Thermostat Subbase HH93AZ073 — (Automatic Changeover)
Low-Voltage Control — Honeywell Thermostat HH07AT071 and
Thermostat Subbase HH93AZ075 — (Manual Changeover) Service Sentry (Six HN65CT002) Start Capacitor and Relay Package
Flare (3/8-in.) to Compatible (3/8-in.) Couplings (Two-Pack)
Liquid Line Filter-Drier
Emergency Heat Relay (Required with 2 outdoor thermostats.) (Service Parts)
Outdoor Thermostat (Six 38RQ900032)
Optimizer Control
38CQ900141 Solid State Time Guard (24 volt)
TUBING
PACKAGE
Length
(ft) OD 1 ube End
Liquid
(in.) OD (in.)
38GC900031 38GC900041 38GS900221
38GC900061 35
38GC900191
38GC900071 10
38GC900081
38GC900091 25
38GC900101 35
38GC900m
38CQ900001
38CQ9000n 25 38CQ900021 35 38CQ900031
*Suction line is insulated and has a 90 bend at one end fFor 5/8-in evaporator connection, cut off 3/4-in end
10 18
25
% % % %
Ha
50
18
50 18
50
V4
V V
4
V
4
V
4
V
4 4
V
4
V
4
___

Table 3 — Accessories

DESCRIPTION
TUBING
Va Va
Va Va
Va 4
4
V
4
Va Va
V
4
Va Va Va
ICapacity reduction may occur when 7/8-in accessory tubing is used
on 38CQ044.048
____
Suction*
OD
(in.)
Va V4t Va Va
Va V4t Va Va V4Î Va Va V4t
1 ube bnd
OD (in.)
Evap
V4t
V4
V4 V4
V4
V
4
V4
V
4
V4 V4
Vat Vai
V
4 4
V4
Vai
V4
Cond
Va
V
4
y
4
y
4
y
4
y
4
y
4
y
4
4
V4
4
UNIT
38CQ015,020
38CQ027,033
38CQ039,044,048

PIPING CONNECTIONS

The 38CQ units can be connected to indoor units using Carrier accessory tubing package or field-supplied tubing of refrigerant grade. See Table 1 (with notes) for unit piping connection type, size and line size recommendations and Table 3 for accessory tubing sizes. Maximum
length of refrigerant piping allowed is 50 feet
A capacity reduction will result if accessory tubing is used in 38CQ044,048 systems. For example, when a 25-ft, 7/8-in. accessory tubing package is used, there will be a capacity reduction
of 1-1/2%. For maximum capacity, use 1-1/8 in. suction line as recommended in Table 1.
When other than 25 ft of interconnecting
piping is used, follow special requirements de scribed in Refrigerant Charging. Do not use less than 10 ft of accessory liquid line. Do not cut
5/16-in. or 1/4-in. liquid line. Do not cut 7/8-in.
suction line. Bend or coil to fit.
Do not use damaged or contaminated tubing. Always evacuate or purge evaporator coil and tubing system (use field-supplied refrigerant, not unit refrigerant).
When making tubing connections, be sure to provide clearance at unit for electrical connections.
To assure noise-free installation, isolate refrig erant lines from ductwork and framing or where they run thru stud spaces, enclosed ceilings or pipe chases. Use isolation hangers (Fig. 4), as rigid fastening may transmit pulsations to structure,
creating an objectionable rumble. Do not attach
liquid line to uninsulated suction line. When
running thru structure, surround all lines with 1-in. insulation to prevent transmission of vibration.
Before Connecting Refrigerant Lines, replace the
AccuRater'^'''^ refrigerant control piston in the indoor coil as required. See Table 2. The 38CQ048 is
Page 4
factory supplied with a No. 8 AccuRater piston for installation in 28MQ048. For piston replacement instructions, see AccuRater’’"''^ Servicing on page 15.
Step 6 — Connect Refrigerant Lines to fittings on
unit suction and liquid service valves (Fig. 1).
Liquid service valve has flare fitting; suction service valve has Compatible Fitting. Make suction line
connection first. Slide flare nut on liquid line, then flare and connect liquid line. (Do not disassemble AccuRater.) Unit Compatible Fitting permits mechanical (quick-connect) or sweat connection as described below. It is not necessary to flare system liquid line if an accessory flare to Compatible Fitting coupler is used for liquid line connection. See Accessory Coupler (Fig. 5).
38CQ044,048 UNITS - When using 1-1/8 in. field-supplied suction line, remove suction line adapter taped to compressor suction line. Sweat connect refrigerant suction line to 1-1/8 in. end of
adapter. Connect 3/4-in. end of adapter to unit suction line Compatible Fitting.
When a 7/8-in. field-supplied suction line is
used on 38CQ039, a field-supplied 3/4-in. to
7/8-in. suction line adapter must be provided (not required if 38CQ accessory tubing is used). MECHANICAL CONNECTION TO COMPATIBLE FITTING (Mate one set of connections at a time.)
1. Loosen nut on Compatible Fitting one turn. Do not remove.
2. Remove plug and be sure 0-ring is in the groove inside the Compatible Fitting.
3. Cut tubing to correct length.
4. Insert tube into Compatible Fitting until it bottoms.
5. Tighten nut until it bottoms on back coupler flange. Keep tube bottomed in Compatible Fitting while tightening nut.
SWEAT CONNECTION TO
COMPATIBLE
FITTING (Use refrigerant tubing.)
Remove locking nut,
1.
rubber 0-ring and
Schrader core from valve.
2.
Cut tubing to correct length.
3.
Insert tube in Compatible Fitting. Wrap top and bottom of service valves in wet cloth to prevent damage by heat. Solder with low temperature (450 F) silver alloy solder.
4.
Replace Schrader core.
5.
Evacuate or purge system with field-supplied refrigerant.
ACCESSORY FLARE TO COMPATIBLE COU PLER is shown in Fig. 5. Attach flare nut on coupler to flare fitting on unit liquid service valve. Connect liquid line to Compatible Fitting using mechanical or sweat connection. When mechanical connection is made, use 2 wrenches when tighten ing Compatible Fitting nut — one to hold coupler and one to tighten nut. Liquid line must be flared if coupler is not used.
Fig. 5 — Accessory Coupler

ELECTRICAL DATA AND WIRING

Field wiring must comply with local and national fire, safety and electrical codes. Voltage to unit must be within ± 10% of voltage indicated on
Table 4 — Electrical Data (60-Hz)
OPER
UNIT V/PH
38CQ015 41 38CQ020 65 10.3
38CQ027 82 38CQ033 38CQ039
38CQ044
38CQ048 106
38CQ033 38CQ039
38CQ044 38CQ048
38CQ039 38CQ044 38CQ048
FLA — Full Load Amps LRA — Locked Rotor Amps RLA — Rated Load Amps
*Permissible limits of the voltage range at which the units will
operate satisfactorily
fRequired when using nonmetallic conduit
^Maximum dual element fuse size
230/1 254 207
200/ 230/3
200/3
230/3
VOLTAGE*
Max Min
254 180 87
229 180 87 18.6
254
207 70
COMPR
LRA
88 19.8 2.4 10 36 94
106
79 17.4
87 18.6 67
70
BRANCH CIRCUIT
FAN FLA
RLA
9.0
17.7 2.4 10 42
22.2
25.0
25.0
13.0/
11.5
15.0
16.7
16.7
.9 14 31
.9 12 40 12
2.4 10 33
2.4
3.0
2.0/
2.0
2.4 12 31
2.4 10 35
3.0 10 35
2.4 12
2.4 12
3.0 12
NOTES: 1 Fan motors are 200-v or 230-v, single phase 2 All units have 24-v control circuit which requires external
power source
3 Copper wire sizes based on 60 C Use copper or copper-clad
aluminum wire only Use latest National Electrical Code for
wire sizing
Power
Wire
Size
(AWG)
8 46 8
12
Max
Ft
Wire
46 8
40 12
41 12
36
36 12 35
Gnd Wire Sizef
(AWG)
14 20
10 10 10 50
8 50
12 40 10 40 10 40
12
Max
Fuse
Ampsi
20 40 45
50
30/
25
35 35
V
Page 5
f
THERMOSTAT
SUBBASE
HH93AZ073 OR
HH93AZ075
40AQ FAN COIL
COOLING CONTROL KIT
TERMINAL BOARD
38CQ
TERMINAL
BOARD
THERMOSTAT
SUBBASE
HH93AZ0730R
HH93AZ075
(38CX) WITH 40AQ OR 40FS/28MQ
EQUIPPED WITH ELECTRIC HEATER;
EMERGENCY HEAT, ONE OUTDOOR THERMOSTAT)
40AQ OR 40FQ
ELECTRIC HEATER
TERMINAL BOARD
38CQ
TERMINAL
BOARD
THERMOSTAT
SUBBASE
HH93AZ073 OR
HH93AZ075
COOLING AND TWO-STAGE HEATING
(38CQ WITH 40AQ OR 40FS/28MQ
EMERGENCY HEAT, NO OUTDOOR THERMOSTATS)
EQUIPPED WITH ELECTRIC HEATER;
40AQ OR 40FQ
ELECTRIC HEATER
TERMINAL BOARD
B
EHR — Emergency Heat Relay ODT — Outdoor Thermostat
_______
Factory Wiring
_______
Field Wiring
38CQ
TERMINAL
BOARD
THERMOSTAT
SUBBASE
HH93AZ073 OR
HH93AZ075
COOLING AND TWO-STAGE HEATING EQUIPPED WITH ELECTRIC HEATER;
EMERGENCY HEAT, TWO OUTDOOR THERMOSTATS)
*Transformer (60 va) located in cooling control kit or electric heater
fTerminal L is identified as terminal X on some former thermostats
(Required for accessory Service Sentry)
:|;Remove factory-installed jumpers (connection B) when installing
outdoor thermostats (ODT)
Fig. 6 — Control Circuit Connections
40AQ OR 40FQ
ELECTRIC HEATER
TERMINAL BOARD
(38CQ WITH 40FS/28MQ
38CQ
TERMINAL
BOARD
nameplate. On 3'-phase units, phases must be balanced within 2%. Contact local power company for correction of improper line voltage.
When making electrical connections, provide
clearance at unit for refrigerant piping connections.
See Table 4 for recommended wire and fuse sizes.
Step 7 — Install a Branch Circuit Fused Disconnect
of adequate size to handle unit starting current. Provide a separate fused disconnect for outdoor unit, indoor unit and for each accessory electric heater circuit as required. (See Indoor Unit and Electric Heater Installation, Start-Up and Service
Instructions.) Locate disconnect(s) within sight of
and readily accessible from the unit, per section
440-14 of National Electrical Code (NEC).

Step 8 — Bring Line Power Leads Into Unit —

Extend leads from fused disconnect thru hole provided in service embossment (Fig. 1) and thru
7/8-in. hole into control box.
Step 9 — Connect Ground Lead to a Ground Lug in Control Box for safety. Connect power wiring.
See Fig. 7. Splice line power leads to yellow and black pigtails on single-phase units or to black pigtails (3) on 3-phase unit. Use wire nuts supplied with unit. Tape each connection.
Step 10 — See Indoor Unit and Electric Heater
Installation, Start-Up and Service Instructions for line power wiring details. All control wiring is
shown in this booklet.
Step 11 — Control Power Wiring (24 v) is brought
thru hole in unit service embossment. Fig. 1. Connect leads to control wiring terminal board (located on outside of control box) as shown in Fig. 6.
Page 6
3-PHASE CONN. TO FUSED DISCONNECT
I-PHASE
CONN. TO FUSED DISCONNECT
_________
L
------------
BLK-
GROUND LUG
38CQ HEAT PUMP
CONTROL BOX

Fig. 7 — Line Power Connections

BLK-
YEL OR BLK
------
emergency heat switch in the indoor thermostat subbase. The thermostat locks out compressor and the relay bypasses the outdoor thermostats for electric heater operation during heat pump shut down. When one outdoor thermostat is used, an emergency heat relay is not required. The emer gency heat switch in the indoor thermostat subbase bypasses outdoor thermostat, locks out compressor and activates electric heater. See 40FS Indoor Unit and Electric Heater Installation, Start-Up and
Service Instructions for installation of emergency
heat relay.
Use indoor unit transformer as 24-v supply for system. At least a 60-va transformer is recom mended. Carrier approved indoor units are equipped with 60-va transformer. See indoor unit data.
Use Carrier accessory indoor thermostat HH07AT071 with HH93AZ073 or HH93AZ075 subbase.

IWITIAL START-UP

The 38CQ unit is equipped with a crankcase heater. It is recommended that heater be energized a minimum of 24 hours before starting unit. To energize heater only, turn the thermostat to OFF position and close electrical disconnect to heat pump.
Heat Anticipator Settings for Room Thermostat
(HH07AT071) — Set anticipator settings for room thermostat according to Table 5. These settings may be changed slightly to provide a greater degree of comfort for a particular installation.
Table 5 — Thermostat Anticipator Settings
UNIT 38CQ
015 020 027 033 039 044
048
FIRST-
STAGE
ANTICIPATOR
SETTING
Fixed
INDOOR
UNIT WITH
ELECTRIC
HEATER
40AQ Fan-Coil with 40AQ Htrs
40FS/28MQ
with 40FQ
Htrs
HTR
KW
5 0 7 5
10 0
15 0
20 0 25 0
30 0 34 0
second-
stage
ANTICIPATOR
SETTINGS
16
33
49
Accessory Outdoor Thermostat provides adjustable
outdoor control of accessory electric heater. This thermostat makes contact when a drop in outdoor temperature occurs. It energizes a stage of electric
heat when the outdoor temperature setting is
reached, provided the room thermostat is on the second stage of heating. One outdoor thermostat is recommended for each stage of electric heat after the first stage. Set the outdoor thermostat(s) progressively lower for each stage. Refer to heat load of building and unit capacity to determine the correct outdoor thermostat settings.
The accessory emergency heat relay is required
when 2 outdoor thermostats are used. It is auto
matically energized by the manually operated

Accessory Outdoor Thermostat(s) Installation —

Install outdoor thermostat at a suitable location on the outside of the control box. Use any free hole to fasten thermostat bracket. Be sure that engage
ment screw does not interfere with wiring or components inside of control box Thermostat
bracket may be secured with only one screw; however, make sure that bracket is firmly attached to resist vibration forces. If a free hole is not available, drill hole in control box after assuring
that drilling will not damage any components inside of box If a second thermostat is used,
follow the procedure outlined above. If there is no available space on the control box for a second thermostat, mount the 2 thermostats together. Connect the 2 thermostats with a machine screw, lock washer and nut, and then mount assembled thermostats to the control box (See Fig. 8a).
Route the capillary and attached bulb below the control box to the upper portion of the outdoor coil grille. Carefully insert the bulb between the tube sheet and nearest vertical grille wire. Place the bulb across the grille and fasten with wire, wire ties or other suitable fastener (See Fig. 8b). Never expose bulb to direct sunlight. If necessary, shield bulb with appropriate material.
Replace access wrapper on unit. Check that
capillary is not pinched by wrapper
To Start Unit — (Make sure crankcase heater has
been energized for 24 hours.) Adjust the thermo
stat as follows:
1. Set selector switch at OFF.
2. Turn on main disconnect switch(es) to indoor and outdoor units.
3. Set fan switch as desired (ON or AUTO.).
4. Set thermostat dial at desired temperature.
5. Set selector switch at HEAT or COOL.
Check system refrigerant charge. See Refrig
erant Charging.

SERVICE

Refrigerant Charging — The 38CQ units contain
correct operating charge for complete system when connected to 40FS/28MQ or 40AQ indoor units with 25 ft of tubing of recommended diameter. Charge adjustment is required on other systems. Adjust system charge for refrigerant line lengths and diameters that differ from 25 ft and 3/8-in.
V
Page 7
OD (liquid line), respectively, using refrigerant weights shown in table below. (Twenty-five feet of 3/8-in. OD tubing contains 14.4 oz of R-22.) Add R-22 charge to system if liquid line is over 25 ft; remove charge if liquid line is shorter than 25 feet.
(
LIQUID LINE 1 OUNCES OF ^22/FT LENGTH
DIAM (in.) OF LIQUID LINE
3/8 5/16 1/4
58 36
21
Table 6 — Service Data
UNIT 38CQ R-22 CHG
(Ib-oz) 1 4-10 4-1 1 6-5 7-11 7-13 7-10 REFRIG CONTROL A ccuRater*^^ FAN 1 Prope
Cfm
Rpm
Diam (in.) 1 17
Motor Hp
1 015, 1 020
]
1
2600
1/8
2600
027 033 039
(Bypass Type
Her - Direct Drive
2800
1075
17 18 18 16 18
1/4 1/4 1/4
1/4
044
2800 1 2600 3400
048
)
1/2
system before recharging. If system has lost com plete charge, evacuate system to 500 microns (29.7 in. vacuum) before recharging. Service port connec
tions are provided on liquid and suction line service valves for evacuation and charging. (See Fig. 32 for
correct service port location on cooling and heating
cycles.) DiaTa-charge charging cylinder is an
accurate device used to recharge systems by
weight. These cylinders are available at refrig
eration supply firms.
To check and/or adjust charge during cooling season, use correct Cooling Cycle Charging Chart (Fig. 9, 11, 13, 15, 17, 19, 21,23, 25, 27, 29) and follow Charging Chart Method below. The charging chart may also be used as an alternate method of recharging system.
To check system operation during heating cycle, use correct Heating Cycle Operation Check Chart (Fig. 10, 12, 14, 16, 18, 20, 22, 24, 26,28,
30). These charts indicate whether a correct relationship exists between system operating pres sures and air temperatures entering indoor and outdoor units. If pressure and temperature lines do not intersect on chart, the system refrigerant
When recharging is necessary during heating or cooling season, weigh in total charge indicated in Table 6. (Charge must be weighed in during heating season.) Remove any refrigerant remaining in
charge may not be correct or other system abnor malities may exist. Do not use Operation Check Charts to adjust refrigerant charge. Weigh charge into system.

a. 2 — Thermostat Assembly b. Capillary Tube Routing

^ Fig. 8 — Outdoor Thermostat Installation Details
7
Page 8
COOLING CYCLE CHARGING CHART METHOD
1. Operate unit a minimum of 10 minutes before checking charge, and after each charge adjustment.
2. Measure suction pressure by attaching a gage to outdoor unit suction valve service port. (See Fig. 32 for correct service port location on cooling cycle.)
3. Measure outdoor (coil inlet) air dry-bulb tem perature with service thermometer.
4. Using a sling psychrometer, measure wet-bulb
temperature of air entering indoor unit.
5. Refer to correct Charging Chart. Locate on curves where outdoor air dry-bulb and indoor air wet-bulb temperature lines intersect.
6. From intersect point, project vertically down ward to chart suction pressure line. Compare
chart suction pressure to unit suction pressure (Step 2).
7. If unit suction pressure is lower than chart pressure, add refrigerant to system until chart pressure is reached. If unit suction pressure is higher than chart pressure, remove refrigerant until chart pressure is reached.
340
320
300
3 5 ui
£ 280
o 260
PRESSURE AT SUCTION SERVICE VALVE (PSIG)
Fig. 9 — 38CQ015 with 40AQ018 Cooling Cycle
Charging Chart (R-22)
cr 240
220
20 O'
66 68 70 72 74 76 78 80 82 84 86 88 90
PRESSURE AT SUCTION SERVICE VALVE (PSIG)
Fig. 11 — 38CQ020 with 40AQ024 Cooling Cycle
Charging Chart (R-22)
Fig. 10 — 38CQ015 with 40AQ018 Heating Cycle
Operation Check Chart (R-22)
Fig. 12 — 38CQ020 with 40AQ024 Heating Cycle
Operation Check Chart (R-22)
Page 9
PRESSURE AT SUCTION SERVICE VALVE (PSI6)
Fig. 13 — 38CQ027 with 40AQ024 Cooling Cycle
Charging Chart (R-22)
Fig. 15 — 38CCX)27 with 40AQ030 Cooling Cycle
Charging Chart (R-22)
Fig. 14 — 38CQ027 with 40AQ024 Heating Cycle
Operation Check Chart (R-22)
Fig. 16 — 38CQ027 with 40AQ030 Heating Cycle
Operation Check Chart (R-22)
Page 10
360
Fig. 17 — 38CQ033 with 40AQ030 Cooling Cycle
Charging Chart (R-22)
260-
240-
DRY-BULB TEMP AIR ENT OUTDOOR UNIT
(F)
WET-BULB TEMP AIR ENT INDOORUNIT(f:
i8^
340
S» 320 £
^ 300-
o
280
o
220
200
66 68 70 72 74 76 78 80 82 84 86 88 90
PRESSURE AT SUCTION SERVICE VALVE (PSIG)
Fig. 19 - 38CQ033 with 40FS160/28MQ036 or
40AQ036 Cooling Cycle Charging Chart (R-22)
Fig. 18 — 38CQ033 with 40AQ030 Heating Cycle
Operation Check Chart (R-22)
Fig. 20 - 38CQ033 with
40FS160/28MQ036 or 40AQ036
Heating Cycle Operation Check Chart (R-22)
10
Page 11
PRESSURE AT SUCTION SERVICE VALVE (PSIG)
Fig. 21 - 38CQ039 with 40AQ036 or 40FS160/
28MQ036 Cooling Cycle Charging Chart (R-22)
Fig. 23 - 38CQ039 with 40FS160/28MQ042
Cooling Cycle Charging Chart (R-22)
SUCTION PRESSURE AT SERVICE PORT(PSIG)
Fig. 22 - 38CQ039 with 40AQ036 or 40FS160/ 28MQ036 Heating Cycle Operation Check Chart
Fig. 24 - 38CQ039 with 40FS160/28MQ042
Heating Cycle Operation Check Chart (R-22)
11
Page 12
PRESSURE AT SUCTION SERVICE VALVE (PSI6)
Fig. 25 - 38CQ044 with 40FS160/28MQ042
Cooling Cycle Charging Chart (R-22)
PRESSURE AT SUCTION SERVICE VALVE (PSIG)
Fig. 27 - 38CQ044 with 40FS200/28MQ048
Cooling Cycle Charging Chart (R-22)
SUCTION PRESSURE AT SERVICE PORT(PSIG)
Fig. 26 - 38CQ044 with 40FS160/28MQ042 Heating Cycle Operation Check Chart (R-22)
Fig. 28 - 38CQ044 with 40FS200/28MQ048 Heating Cycle Operation Check Chart (R-22)
12
Page 13
300
Fig. 29 - 38CQ048 with 40FS200/28MQ048
Cooling Cycle Charging Chart (R-22)
280
260
>240
fE 220
£ 180
140
120
WET-BULB TEMP AIR ENT OUTDOOR UNIT{F)
23.5F
15 F
9F
M
-I0.5F
20 30 40 50 60
SUCTION PRESSURE AT SUCTION SERVICE PORT
43F
I
33F
Fig. 30 - 38CQ048 with 40FS200/28MQ048 Heating Cycle Operation Check Chart (R-22)
DRY-BULB TEMP AIR ENT
INDOOR UNIT (F)
70

Unit Single-Phase Compressors

COMPRESSORS OF THE SPLIT CAPACITOR (PSC) TYPE require an equalized system pressure to start. When supply voltage is within 10% limit and compressor does not start, give compressor a temporary capacitance boost. See Carrier Standard
Service Techniques Manual, Chapter 2, for details. Use a 130-mfd start capacitor. Connect wires with insulated probes to each capacitor terminal. Touch probes to each side of run capacitor or to compressor motor terminals R and S. Start com pressor; pull probes away after 3 seconds Dis charge start capacitor. Run compressor for 10 minutes, then shut off and allow system pressure to equalize. Try restarting without boost capacitor. If after 2 attempts (without boost capacitor) the compressor does not start, add an accessory start thermistor (PTC device). If after 2 more attempts the compressor does not start, remove thermistor and add an accessory start capacitor relay package.
COMPRESSORS THAT ARE EQUIPPED WITH A COMPRESSOR START THERMISTOR (PTC device): if compressor does not start, check the thermistor with an ohmmeter as described below. Earlier unit models have a 50-ohm thermistor (with 2-prong connections), later models have a 25-ohm
thermistor (with 3-prong connections). If indoor
coil does not have a bleed-type expansion device, it may be necessary to remove start thermistor and replace with accessory start capacitor and relay.
Checking Start Thermistor
1. Shut off all power to unit and wait 5 minutes for thermistor to cool to outdoor temperature.
2. Measure resistance of thermistor with ohm­meter. Normal resistance readings at 75 F out door temperature are: 50 to 90 ohms for 50 ohm thermistor; 25 to 50 ohms for 25 ohm thermistor.
3. If ohmmeter resistance reading is 0 or much higher than 50 or 90 ohms, the thermistor is defective and must be replaced. If start thermistor is good and compressor does
not start, disconnect the thermistor from starting circuit and give compressor a temporary capaci tance boost as described above. Run compressor for 10 minutes, then shut off and allow system pressure to equalize. Reconnect start thermistor and try restarting compressor without boost capa citor. If aher 2 attempts the compressor does not start, remove thermistor and add an accessory start
capacitor relay package.
13
Page 14
Compressor Removal — See Table 7 for compressor
information and Fig. 31 for component location. Follow safety codes, and wear safety glasses and work gloves. Have quenching cloth available (Step 7).
pressor hold-down bolts are in place. Connect
wiring.
11. Evacuate and recharge unit. FILTER-DRIER — Install accessory heat pump filter-drier (Table 3) in system liquid line when refrigerant system is opened for service as de scribed under Compressor Removal. Position drier
in liquid line at convenient location. Do not use a standard single-pass filter-drier.
1. Shut off power to unit. Remove unit top access cover and rear access wrapper.
2. Remove refrigerant from unit using refrigerant removal methods described in Carrier Standard Service Techniques Manual, Chapter 1.
3. Disconnect compressor wiring at compressor terminal box.
4. Using a tubing cutter, cut suction and dis charge lines at convenient place near com pressor for easy reassembly to new compressor with copper slip couplings.
5. Remove crankcase heater from compressor base.
6. Remove compressor hold-down bolts and lift compressor out.
7. Carefully unbraze suction and discharge line piping stubs from compressor. If oil vapor in piping stubs ignites, use quenching cloth.
8. Braze piping stubs (removed in step 7) on new compressor.
9. Clean system. Add new liquid line heat pump
filter-drier as described below.
10. Install new compressor in unit. Braze suction and discharge lines to compressor piping stubs (at points where cut, step 4) using field-
supplied copper couplings. Make sure com
Table 7 — Compressor Data
UNIT
38CQ015
38CQ020 38CQ027 38CQ033 38CQ039 38CQ044 38CQ048
38CQ039
38CQ044
38CQ048
38CQ039
38CQ044
38CQ048
‘Refer to Service Parts catalog for replacement compressor
model numbers
V/PH
230/1
200/3
230/3 PG5316HD
PRODUCTION —
Model*
38CQ400994
MD2023HB MD3023HB MC3423HB PC4Ó16HD
PC5316HD PC5316HD
PF4616HD PF5316HD PF5316HD
.
PG4616HD
PG5316HD
Oil Recharge (oz)
20 44
44 44 64 64 64
64 64 64
64
64
64
Pumpdown Procedure (Cooling Cycle) — The
38CQ units may be pumped down in order to make repairs on low side of system without losing complete refrigerant charge. Ensure unit is in cooling mode.
1. Attach pressure gage to suction service valve service port.
2. Frontseat the liquid line valve.
3. Start unit and run until suction pressure reaches 5 psig (see Caution).
4. Shut unit off and frontseat suction valve.
5. Vent remaining pressure to atmosphere.
FAN COMPARTMENT
-WAY VALVE
CONTROL BOX
DISCHARGE LINE MUFFLER
(039,044,048)
COMPRESSOR

Fig. 31 — Component Location

14
CONTROL WIRING TERMINAL BOARD
ACCUMULATOR'
SUCTION LINE SERVICE VALVE-
LIQUID LINE SERVICE VALVE
Page 15

Unit Controls and Safety Devices

HIGH-PRESSURE RELIEF VALVE is located in compressor. Relief valve opens at a pressure differ
ential of approximately 600 psi between suction (low side) and discharge (high side) to allow pressure equalization.
INTERNAL CURRENT AND TEMPERATURE SENSITIVE OVERLOAD resets automatically when internal compressor motor temperature drops to a safe level (overloads may require up to 45 minutes to reset). When an internal overload is suspected of being open, check by using an ohmmeter or continuity tester. If necessary, refer to Carrier Standard Service Techniques Manual, Chapter 2, for complete instructions.
LIQUID LINE LOW-PRESSURE SWITCH (LLPS) is connected in liquid line to work with compressor internal thermostat in providing loss-of-charge pro tection during the heating cycle. Control is mounted on liquid line.
With a high-side leak, pressure gradually de creases until low-pressure control stops the com pressor. (Low-pressure control settings are shown in Table 8.)
Table 8 — Pressure Switch Settings
UNIT 38CQ
015 020 027 033 20 + 5 5+3 039 044 048
Cut-in (psig) Cutout (psig)
LIQUID LINE
LOW-PRESSURE SWITCH
With a low-side leak there is always some
pressure in the liquid line. However, compressor
motor temperature increases because of in sufficient suction gas cooling. This causes internal thermostat to actuate and stop compressor. When compressor stops, system pressure equalizes and contacts on pressure control open. The compressor cannot restart until leak is repaired and system recharged.
CRANKCASE HEATER is connected across line side of contactor and operates continuously.
The purpose of the heater is to keep the
crankcase warm during the off cycle and thus
prevent dilution of the oil with refrigerant. This
assures good lubrication and prevents loss of oil
from crankcase during start-up.
If the electrical disconnect switch to the out
side unit has been off for an extended period of
time, the crankcase heater should be energized for 24 hours before starting the compressor
DEFROST CONTROL, consisting of a defrost timer, defrost thermostat and defrost relay, inter rupts normal system heating operation every 90 minutes to defrost outdoor coil, if the coil satu
rated suction temperature indicates freezing temperatures. Defrost control simultaneously stops
outdoor fan, energizes reversing valve solenoid to return system to cooling cycle (outdoor unit as condenser, indoor unit as evaporator), and acti vates accessory electric heater.
For the heat pump to defrost, 2 conditions are
necessary:
1. Defrost timer contacts must be closed.
2. Refrigerant temperature from outdoor unit must be cold enough to cause defrost ther mostat contacts to close. Contacts close at 31 (±4) F. Every 90 minutes of elapsed running time, the
defrost timer contacts close for 10 seconds. If the defrost thermostat contacts are closed, the unit defrosts. The defrost timer limits defrosting period to 10 minutes. Normally the frost is removed and the defrost thermostat contacts will open to terminate defrosting before 10 minutes have elapsed. Defrost thermostat contacts open at 80 (±6) F liquid refrigerant temperature. When de frosting is terminated, the outdoor fan motor is energized and reversing valve solenoid is de energized returning unit to heating cycle.
HEAT PUMP CIRCUITS shown in Fig. 32 are refrigerant flow diagrams for heating and cooling
cycles.
AccuRater^''^ (Bypass Type) Servicing — See Fig.
33 for bypass type AccuRater components. The piston has a refrigerant metering hole thru it. The retainer forms a stop for the piston in the
refrigerant bypass mode, and a sealing surface for liquid line flare connection. To check, clean or replace piston:
1. Shut off power to unit.
2. Pump unit down using Pumpdown Procedure described previously.
3. Remove liquid line flare connection from AccuRater.
4. Pull retainer out of body being careful not to scratch flare sealing surface. If retainer does not pull out easily, carefully use vise grips or pliers to remove retainer.
5. Slide piston out by inserting a small soft wire, with small kinks, thru metering hole. Ensure metering hole, sealing surface around piston cones and fluted portion of piston are not damaged.
15
Page 16
SUCTION SERVICE
PORTAT
SERVICE VALVE (HTG CYCLE)
OUTDOOR COIL
SUCTION SERVICE PORT
ACCESSORY FILTER DRIER
DISCHARGE SERVICE PORT AT SERVICE VALVE
(HTG CYCLE)
LIQUID LINE SERVICE PORT AT SERVICE VALVE (CL6 CYCLE)
ACCESSORY FILTER DRIER
BYPASS TYPE
ACCURATOR (PERMITS FLOW IN EITHER DIRECTION)
STRAINERS
ACCUMULATOR
-WAY valve
SUCTION SERV^ICE PORTAT SERVICE VALVE
(CLG CYCLE)
iUNIT PIPING
HEATING CYCLE

Fig. 32 — 38CQ Refrigerant Flow Diagrams

Fig. 33 — AccuRater^'^ (Bypass Type) Components
6. Clean piston refrigerant metering hole.
7. Replace retainer 0-ring before reassembling bypass type AccuRater. Carrier O-ring part no. is99CC501052.
LIQUID LINE STRAINER (protects AccuRater) made of wire mesh is located in the liquid line inside 38CQ unit behind liquid line service valve. Liquid line is belled and sweat connected where strainer is located. If strainer is plugged, unsweat belled liquid line connection and replace strainer.
Compatible Fitting Repair
LEAKING MECHANICAL CONNECTION ­Frontseat outdoor section service valves and relieve refrigerant pressure in tubing. Back locknut off Carrier Compatible Fitting onto tube. Cut fitting between threads and seal ring bead shown in
Fig. 34. Remove tubing section remaining in
threaded portion of fitting. Discard locknut.
Clean, flux, and insert new tube end into remaining portion of Carrier Compatible Fitting. Wrap valve base in wet rag. Heat and apply
low-temperature solder (450 F).
COOLING CYCLE
LEAKING SWEAT CONNECTION - Frontseat service valves and relieve refrigerant pressure in tubing. Clean and flux area around leak and apply low-temperature solder (450 F).
Evacuate or purge indoor coil and tubing system. Add refrigerant charge (seb charging instructions).
Leaking Flare Connection — Cut and reflare 3/8-in.
system liquid line.
I,
Fig. 34 — Carrier Compatible Fitting
16
Page 17
Outdoor Fan Position — Required fan position is
shown in Fig. 35. Adjust fan by loosening setscrew
and moving fan blades up or down.
Fan Motor Removal
1. Shut off power to unit.
2. Remove unit top access cover and fan grille.
3. Disconnect fan motor wires from fan capacitor and control relay or contactor. Pull wires out of control box.
4. Remove fan from motor shaft by loosening setscrew and pulling upward on fan hub.
5. Remove rain shield from motor shaft by pulling upward.
6. Loosen bolt holding fan motor to motor mounting bracket. Remove motor thru top of unit. To replace motor, place motor on self positioning motor mounting flanges and re tighten bolt.
Before replacing fan, ensure rain protector is in
place on motor shaft.
FAN BLADE
MOTOR
setscrew""
Fig. 35 — Condenser Fan Position
MAINTENANCE
Outdoor Coil Cleaning — Inspect coil periodically.
Clean coil with water at the beginning of every cooling season or more often if required. Use ordinary garden hose at a pressure high enough to clean efficiently. For best results, unscrew and remove unit top cover (grille). Insert hose nozzle between fan blades and spray coil fins from
inside-to-outside the unit or top to bottom be tween rows of tubing. If unit has a double-row coil, loosen screws to separate coils. Pull outer row of coils away from inner row and flush dirt toward
outside of both coils. Flush dirt from base pan by
spraying water thru top of unit. Avoid splashing mud on coil or water on fan motor. Make sure water drainage holes under outdoor coil are not obstructed.

Lubrication

FAN MOTOR BEARINGS - Oiling holes are provided at each end of outdoor unit fan motor.
Remove fan motor and lubricate motor with 32 drops (16 drops per hole) of SAE-10 nondetergent oil at intervals described below: a. Annually, when environment is very dirty,
ambient temperature is higher than 105 E and average unit operating time exceeds 15 hours a day.
b. Every 3 years when environment is reasonably
clean, ambient temperature is less than 105 F and unit operating time averages 8 to 15 hours a day.
c. Every 5 years when environment is clean,
ambient temperature is less than 105 F and unit operating time averages less than 8 hours a day.
COMPRESSOR contains factory oil charge. When
oil is lost, see Table 7 for oil charge and Carrier
Standard Service Techniques Manual, Chapter 1,
page 1-21, for instructions. Use Carrier PP33-1,
Texaco Capella B or Suniso 3G oil.
17
Page 18
00
TROUBLESHOOTING CHART - COOLING CYCLE
Page 19
TROUBLESHOOTING CHART - HEATING CYCLE
Page 20
SI METRIC CONVERSIONS
(°F - 32) X 5/9
= °C BTU X 1.055 = kJ BTU/hr X Tons refrig x 3.517
0.2931 = W = kW
HP X 0.7457 = kW kcal/hr X
ft X
1.163
0.3048
ft^x 0.09290 fpm
in X
0.005080
25.4 = mm in wg 39.2° F x 0.2491 in Hg 32° F X 3.386 CFM X gpm (U.S.) X
0.0004719
0.06309 = l/s Ibx 0.4536 lb/in^ X 6.895
OZ. X 0.02835 fluid OZ. (U.S.) X 0.02957 = 1
kcal X kg f/cm^ X Metric HP X
4.1855
98.07 = kPa
735.5 = W
pints X 0.4732
= W = m = m2 = m/s
= kPa = kPa = m^/s
= kg
= kP
= kg
= kJ
= 1
For replacement items use Carrier Specified Parts.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Tab 12 Form 38CQ-6SI Supersedes 38CQ-4SI Printed in USA 1-77 PC 101 Catalog No 533-854
Book
1 4
Tab 5a
5a
Loading...