Page 1
°
°
Product
Data
38BYC (60 Hz)
Heat Pump
Sizes 018 thru 060
The 38BYC Outdoor Sections
of Split-System Heat Pumps are
designed for quiet, reliable heating
during the winter and cooling during
the summer. With a SEER of up to
14.0 and HSPF of up to 8.3, these
heat pump systems provide economy
of operation through energy
conservation. They recover heat for
indoor comfort from outdoor air
during the heating season and, by
automatically reversing the
refrigerant system, remove indoor
heat and excess humidity during the
cooling season. All models are listed
with UL (U.S. and Canada), CEC,
and ARI.
FEATURES/BENEFITS
Electrical Range
offered in single phase 208–230v.
Size Range
7 nominal sizes from 018 through
060 to meet the needs of residential
and light commercial applications.
Compressor
scroll compressor which is
significantly more efficient than
conventional compressors. Its simple
design offers improved reliability.
Each compressor is mounted on
rubber isolators for additional sound
reduction. For improved
serviceability, all models are
equipped with a compressor terminal
plug. Continuous operation is
approved down to –30
in the heating mode and down to
55
F (12.8 ° C) in the cooling mode.
(See heating and cooling
performance tables.)
— All units are
— 38BYC is available in
— This unit features a
F (–34.4 ° C)
Copyright 2003 Carrier Corporation Form 38BYC-6PD
Page 2
Built-in-Reliable Components
—
Includes a suction-tube accumulator
that reduces the amount of liquid
refrigerant reaching the compressor,
a loss of charge switch, and an
internal pressure relief valve for highpressure protection.
Defrost Control Board
— Incorporates
a defrost relay, defrost timer, and lowvoltage terminations. The defrost
control is a time/temperature
initiation/termination control which
includes 3 field-selectable time
periods of 30, 50, and 90 minutes.
Thermostatic Expansion
Valve (TXV)
— This unit must be
installed with a TXV on the indoor
coil. The FC4 and FK4 indoor fan
coils come factory equipped with a
bi-flow TXV. When installed in this
application, no further change is
required. If any other indoor fan coil
or furnace coil is used, an accessory
bi-flow TXV must be installed. See
accessory list in this publication for
correct part number.
Discharge Muffler
— Incorporated
to minimize low frequency sound and
pressure pulsation generated by
compressor discharge gas.
Weather-Protective Cabinet
—
Steel is protected with a galvanized
coating and treated with a layer of
zinc phosphate. A coat of modified
polyester powder is then applied and
baked on, providing each unit with a
hard, smooth finish that will last for
many years.
All screws on cabinet exterior are
coated for a long-lasting, rustresistant, quality appearance.
Unit Design
— All units are equipped
with totally enclosed fan motors for
greater reliability under rain and snow
conditions. The large, wraparound
coil uses copper tube and enhanced
aluminum fin and is designed for
optimum heat transfer during heating
and cooling. The vertical air
discharge carries the sound and
air up and away from adjacent
patio areas and foliage. The
condenser coil can be cleaned with a
common garden hose.
External Service Valves
— Both
service valves are brass, front seating
type. Valves are externally located so
refrigerant tube connections can
be made quickly and easily with sweat
field connections. Each
valve has a service port for ease of
checking operating refrigerant
pressures.
Limited Warranty
— Standard 5-year
limited warranty on parts, 5-year
limited warranty on compressor.
Model number nomenclature
38BYC 018
Electric Heat Pump
Nominal Capacity
018 — 18,000 Btuh 042 — 42,000 Btuh
024 — 24,000 Btuh 048 — 48,000 Btuh
030 — 30,000 Btuh 060 — 60,000 Btuh
036 — 36,000 Btuh
331
3 — 208-230-1
Packaging
Series
Electrical
2
Page 3
*
T
O
D
E
A
I
R
F
I
I
T
A
R
S
E
C
R
E
R
U
T
C
A
U
F
U
N
A
M
A
R
C
O
M
H
P
E
A
Y
R
A
T
I
N
I
S
T
L
T
Y
P
I
U
N
M
G
P
W
I
T
H
®
E
T
Q
N
U
E
I
P
M
0
4
2
D
A
R
N
A
D
CERTIFICATION APPLIES ONLY WHEN THE
REGISTERED QUALITY SYSTEM
COMPLETE SYSTEM IS LISTED WITH ARI.
As an ENERGY STAR®
Partner, Carrier
*
Corporation has
determined that this
product meets the
ENERGY STAR® guidelines for energy
efficiency.
Refer to the combination ratings in the Product Data Digest for system combinations meeting ENERGY STAR® efficiency standards.
Physical data
UNIT SIZE 018 024 030 036 042 048 060
OPERATING WT (Lb)
COMPRESSOR
Manufacturer
Type
REFRIGERANT
Control
Charge (Lb) @ 15 Ft
CONDENSER FAN
Air Discharge
Air Qty (CFM)
Motor RPM (60 Hz)
CONDENSER COIL
Face Area (Sq ft)
CONNECTION VALVE (In. ID)
Liquid
Vapor
REFRIGERANT TUBES
(In. OD)
Vapor
Liquid
NOTE: See unit Installation Instructions for proper installation.
115 166 182 182 209 250 278
Copeland
Scroll
R-22
TXV
5.5 6.25 6.88 8.00 10.38 11.13 14.00
Propeller Type, Direct Drive
1800
1100
2800
825
2800
825
Vertical
2800
825
2800
825
12.4 14.93 18.5 18.5 16.18 18.5 22.40
5/8 3/4 3/4 3/4 7/8 7/8 7/8
3/8 3/8 3/8 3/8 3/8 3/8 3/8
5/8 3/4 3/4 3/4 7/8 1-1/8 1-1/8
3/8 3/8 3/8 3/8 3/8 3/8 3/8
Sweat
2800
825
3400
1125
UNIT
SIZE SERIES
018
024
030
036
042
048
060
* TXV must be ordered separately when indoor coil is not equipped with a TXV. TXV is listed
for any approved coil combination. All TXVs are bi-flow, hard shutoff.
METERING DEVICE
OUTDOOR
PISTON
33, 34 42 KSATX0601HSO
35, 36 52 KSATX0601HSO
34, 35 55 KSATX0601HSO
34, 35 63 KSATX0601HSO
33, 34 65 KSATX0601HSO
33, 34 73 KSATX0701HSO
33, 34 78 KSATX0701HSO
INDOOR
TXV*
3
Page 4
Accessories
ORDERING NUMBER DESCRIPTION
KAATD0101TDR
32LT660004† (RCD)
HC34GE232 (RCD)
HC38GE231 (RCD)
HC40GE232 (RCD)
KAAFT0101AAA*
KHAIR0101AAA*
KSAHS1501AAA
KSAHS1701AAA
KSAHS1601AAA
KAACS0201PTC
KAACH1401AAA
KAACH1201AAA
KSASH1801COP
KSASH0601COP
KSASH2101COP
KHAOT0301FST
KHAOT0201SEC
KHAIC0101AAA‡
KSALA0201R22
KSATX0601HSO
KSATX0701HSO
Standard
KHAHI0101HPS
P504-8083S (RCD)
P504-8163S (RCD)
KHALS0401LLS
KSACG1204CSM
KSACG1704CMD
KSACG1804CMD
KSACG2004CMD
KSACG2304CMD
KAACF1001MED
KAACF1101LRG
* Use with low-ambient controller.
† Fan motor with ball bearings required.
‡ Requires outdoor thermostat.
Time-Delay Relay — All Sizes
MotorMaster® Control — Sizes 018, 024, 042-060
Ball Bearing Fan Motor — Size 018
Ball Bearing Fan Motor — Size 024–048
Ball Bearing Fan Motor — Size 060
Evaporator Freeze Thermostat — All Sizes
Isolation Relay — All Sizes
Compressor Start Assist — Capacitor/Relay — Sizes 018–042
Compressor Start Assist — Capacitor/Relay — Size 048
Compressor Start Assist — Capacitor/Relay — Size 060
Compressor Start Assist — PTC — All Sizes
Crankcase Heater — Size 018
Crankcase Heater — Sizes 024–048
Sound Hood — Sizes 018–030
Sound Hood — Sizes 036, 042
Sound Hood — Sizes 048, 060
Outdoor Thermostat — All Sizes
Secondary Outdoor Thermostat — All Sizes
Interface Control (Optimizer II) — All Sizes
Low Ambient Kit — All Sizes
Thermostatic Expansion Valve (Hard Shutoff) — Sizes 018–042
Thermostatic Expansion Valve (Hard Shutoff) — Sizes 048–060
Low-Pressure Switch — All Sizes
High-Pressure Switch — All Sizes
Filter Drier (Bi-flow) — Sizes 018–036
Filter Drier (Bi-flow) — Sizes 042–060
Liquid Solenoid Valve (LSV) — All Sizes
Inlet Grille Kit (4 Pack) — Size 018
Inlet Grille Kit (4 Pack) — Size 024
Inlet Grille Kit (4 Pack) — Size 042
Inlet Grille Kit (4 Pack) — Sizes 030, 036, 048
Inlet Grille Kit (4 Pack) — Size 060
Coastal Filter Kit — Size 018
Coastal Filter Kit — Sizes 024–060
THERMOSTAT PKG DESCRIPTION
TSTATCCNHP01-B
TSTATCCPHP01-B
TSTATCCPDF01-B*
TSTATCCBHP01-B
TSTATCCSHP01
TSTATCCPRH01-B†
TSTATXXSEN01-B
TSTATXXNBP01
TSTATXXPBP01
TSTATXXBBP01
TSTATXXSBP01
TSTATXXCNV01
* High-pressure switch must be added if not supplied with the system.
† Do not use in zoning heat pump applications.
Thermostat, Auto Changeover, Non-Programmable, ° F /° C, 2-Stage Heat, 1-Stage Cool
Thermostat, Auto Changeover, 7-Day Programmable, ° F /° C, 2-Stage Heat, 1-Stage Cool
Thermostat, Auto Changeover, 7-Day Programmable, ° F/° C, Dual Fuel Thermostat,
Must be used with Outdoor Sensor (TSTATXXSEN01-B) Included
Builder’ s Thermostat, Manual Changeover, Non-Programmable, ° F, 2-Stage Heat, 1-Stage Cool
Standard Programmable Thermostat — Manual Changeover, 5-2 Day Programmable, °F/° C, 1-Stage
Heat, 1-Stage Cool
Thermidistat™ Control — Non-Programmable/Programmable Thermostat with Humidity Control (For
use in Dual Fuel, AC, HP, and 2S applications. Includes Outdoor Air Temperature Sensor.)
Outdoor Air Temperature Sensor
Backplate for Non-Programmable Thermostat
Backplate for Programmable Thermostat and Thermidistat Control
Backplate for Builder’ s Thermostat
Backplate for Standard Programmable Thermostat
Thermostat Conversion Kit (4 to 5 Wire) — 10 Pack
4
Page 5
Accessory usage guideline
*
REQUIRED FOR
LOW-AMBIENT
ACCESSORY
Crankcase Heater
Evaporator Freeze Thermostat
Accumulator
Compressor Start Assist
Capacitor and Relay
MotorMaster® Control
Wind Baffle
Coastal Filter
Support Feet Recommended No
Liquid-Line Solenoid Valve
or
Hard Shutoff TXV
Ball Bearing Fan Motor Ye s N o
For tubing line sets between 50 and 175 ft horizontal or 20 ft vertical differential, refer to Long-Line section of Application Guideline and Service Manual—
Air Conditioners and Heat Pumps Using R-22 Refrigerant.
APPLICATIONS
(Below 55°F)
Ye s Ye s
Ye s N o
No No
Ye s Ye s
Ye s N o
See Low-Ambient Instructions No
No No
No
REQUIRED FOR
LONG-LINE
APPLICATIONS*
(Over 50 Ft)
See Long-Line
Application
Guideline
Accessory description and usage (Listed alphabetically)
1. Ball Bearing Fan Motor
A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.
SUGGESTED USE: Required on all units where Low-Ambient kit (full modulation feature) or MotorMaster® Control has been added.
2. Crankcase Heater
An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart
and minimizes chance of refrigerant slugging. May or may not include a thermostat control.
SUGGESTED USE: When interconnecting tube length exceeds 50 ft.
3. Compressor Start Assist — Capacitor and Relay
Start capacitor and start relay which gives hard boost to compressor motor at each start-up.
SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft.
4. Compressor Start Assist — PTC
Solid-state electrical device which gives a soft boost to compressor motor at each start-up.
SUGGESTED USE: Installation with marginal power supply.
5. Evaporator Freeze Thermostat
An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions.
SUGGESTED USE: All units where low-ambient controller has been added.
6. Filter Drier — Bi-flow
A device for removing contaminants from refrigerant circulating in a heat pump system:2–direction flow.
SUGGESTED USE: Split-system heat pumps.
7. High-Pressure Switch
Auto reset SPST switch activated by refrigerant pressure on high side of refrigerant circuit. Cycles compressor off if refrigerant pressure rises to about 425 psig.
Provides additional protection against compressor damage due to loss of outdoor airflow.
SUGGESTED USE: Installations exposed to very dirty outdoor air.
8. Inlet Grille Kit
A field-installed enhanced inlet grille to replace the standard inlet grille on residential air conditioners and heat pumps.
SUGGESTED USE: For greater protection against inclement weather, incidental damage, and vandalism.
9. Interface Control
An electric control for controlling a heat pump and gas or oil furnace system for maximum energy savings. It allows heat pump to operate down to a predetermined economic balance point temperature, then switches to allow furnace operation only below that temperature. KHAIC0101AAA requires outdoor
thermostat to be adjusted for economic balance point temperature.
SUGGESTED USE: For heat pump and gas- or oil-fired furnace combination systems.
10. Isolation Relay
An SPDT relay which switches the low-ambient controller out of the outdoor fan motor circuit when the heat pump switches to heating mode.
SUGGESTED USE: All heat pumps where low-ambient controller has been added.
When unit will be operated below 55 ° F (12.8 ° C) outdoor air temperature. (Use with low-ambient controller).
All commercial installations.
Installations where outdoor design temperature exceeds 105 ° F (40.6 ° C).
Replacement installations with hard shutoff expansion valve on indoor coil.
Replacement installations with rapid pressure balance (RPB) expansion valve on indoor coil.
Installations where condenser inlet air temperature exceeds 125 ° F (51.7 ° C).
5
Page 6
Accessory description and usage (continued)
11. Liquid Solenoid Valve (LSV)
An electrically operated shutoff valve installed at the outdoor unit which stops and starts refrigerant liquid flow in response to compressor operation. Maintains a
column of refrigerant liquid ready for action at next compressor operation cycle.
NOTE:Compressor Start Assist — Capacitor and Relay must also be used.
SUGGESTED USE: For improved system performance in air conditioners for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.
12. MotorMaster® Control
A fan speed control device activated by a temperature sensor. Designed to control condenser fan motor speed in response to the saturated, condensing temperature
during operation in cooling mode only. For outdoor temperatures down to –20°F, it maintains condensing temperature at 100°F ± 10°F.
SUGGESTED USE: Cooling operation at outdoor temperatures below 55° F.
13. Outdoor Thermostat
An SPDT temperature actuated switch which turns on supplemental electric heaters when outdoor air temperature drops below set point.
SUGGESTED USE: Heat pump installations with multiple-stage supplemental heaters.
14. Secondary Outdoor Thermostat
An SPDT temperature actuated switch which turns on a third stage of supplemental electric heaters when outdoor air temperature drops below the second-stage
set point.
SUGGESTED USE: Heat pump installations where 3-stage operation of supplemental heaters is desired.
15. Sound Hood
Wraparound sound attenuation cover for the compressor. Reduces the sound level by about 2 dBA.
SUGGESTED USE: Unit installed closer than 15 ft to quiet areas — bedrooms, etc.
16. Thermostatic Expansion Valve (TXV)
A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator. Kit includes valve, adapter tubes, and external equalizer tube. Both hard shutoff and RPB valves are available.
SUGGESTED USE: For improved system performance in cooling mode for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.
17. Time-Delay Relay
An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off.
SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.
In certain long-line applications. Refer to Long-Line Application Guideline.
All commercial installations.
Used with KHAIC0101AAA (Interface Control).
Unit installed between 2 houses less than 10 ft apart.
Required for use on all zoning systems.
6
Page 7
Electrical data
MAX
LENGTH
(Ft)
60° C/75° C‡
71/67
60/57
71/67
66/63
104/63
124/76
156/88
MAX FUSE†
OR CKT
BKR AMPS Max Min LRA RLA
20
25
30
35
50
45
60
UNIT
SIZE-SERIES
018-33, 34
024-35, 36
030-34, 35
036-34, 35
042-33, 34
048-33, 34
060-33, 34
V/PH
60 Hz
208-230/1 253 197
OPER VOLTS* COMPRESSOR
45.0
54.0
72.5
88.0
104.0
137.0
148.0
10.6
12.0
16.7
17.8
23.2
23.9
32.1
FAN
FLA MCA
0.5
1.1
1.1
1.1
1.1
1.1
1.4
13.8
16.1
22.0
23.4
30.1
31.0
41.5
MIN WIRE
SIZE**
60° C/75° C
14/14
14/14
12/12
12/12
8/10
8/10
6/8
* Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit failure.
† Time-delay fuse.
‡ Length shown is as measured 1 way along the wire path between the unit and the service panel for voltage drop not to exceed 2%.
** If wire is applied at ambient greater than 30°C (86° F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathed cable (NM),
trade name ROMEX, shall be that of 60° C (140° F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26. If other than uncoated (non-plated), 60° or 75°C
(140° or 167° F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the
NEC (ANSI/NFPA 70).
FLA — Full Load Amps
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
RLA — Rated Load Amps
NOTE: Control circuit is 24v on all units and requires external power source. Copper wire must be used from service disconnect to unit. All motors/compressors
contain internal overload protection.
Sound power
UNIT
SIZE-SERIES
SOUND LEVEL
(dBA)
125 250 500 1000 2000 4000 8000
018-33, 34 78 69.5 68.0 68.0 69.5 61.0 58.0 57.0
024-35, 36 78 70.5 69.5 69.5 73.0 65.0 63.5 58.0
030-34, 35 78 71.5 71.5 70.5 72.0 65.0 62.0 59.0
036-34, 35 78 68.5 69.0 69.0 71.0 66.0 61.5 61.0
042-33, 34 78 69.0 72.5 71.5 73.0 68.0 66.5 63.0
048-33, 34 78 77.5 68.0 70.0 71.5 68.5 64.5 60.5
060-33, 34 80 74.5 73.5 74.5 74.0 72.0 69.0 65.0
NOTE: Tested in accordance with ARI Standard 270-95. (Not listed with ARI).
A - WEIGHTED SOUND POWER LEVELS (dBA) WITHIN OCTAVE BAND SHOWN
7
Page 8
Dimensions
-IN. DIA
8
/
3
-IN. DIA KNOCKOUT
8
-IN. DIA HOLE WITH
/
1
8
/
FIELD POWER SUPPLY CONN
7
AND 1
1
A SQ
AIR DISCHARGE
-IN. DIA
8
/
7
FIELD CONTROL SUPPLY
CONN
HOLE
KNOCKOUT
-IN. DIA LIQUID
8
/
LINE CONN
3
MINIMUM
DIMENSIONS
MOUNTING PAD
A97045
C
/8 ″
7
2
/4 ″
1
1
AIR DISCHARGE
AIR IN
M
D DIA VAPOR LINE CONN
P
B
AIR IN
L
K
NOTES:
1. Allow 30 in. clearance to service side of
unit, 48 in. above unit, 6 in. on one side, 12 in.
3. Maximum outdoor operating ambient in heating mode
is 66° F.
4. Series designation is the 13th position of the unit
model number.
on remaining side, and 24 in. between units for proper airflow.
2. Minimum outdoor operating ambient in cooling mode is
55° F (unless low ambient control is used) max. 125° F.
5. Center of gravity .
DIMENSIONS (IN.)
J
AIR IN
H
G
F
E
N
AIR IN
TIEDOWN
/8 -IN. DIA
3
(2) PLACES
KNOCKOUTS
AIR DISCHARGE
8
018 33, 34 22-1/2 33-15/16 3-3/16 5/8 3-11/16 18-1/8 19-3/4 21-5/8 14-3/8 18-7/8 22-1/16 10-3/4 11 14-1/4 22-1/2 x 22-1/2
SIZE SERIES ABCDEFGHJKLMNP
UNIT
024 35, 36 30 27-15/16 3-3/16 3/4 6-1/2 23-1/2 27-1/4 29-1/8 20 26-3/8 29-9/16 15-1/2 15 11-3/4 30 x 30
030 34, 35 30 33-15/16 3-3/16 3/4 6-1/2 23-1/2 27-1/4 29-1/8 20 26-3/8 29-9/16 15-1/2 15 14-1/2 30 x 30
036 34, 35 30 33-15/16 3-3/16 3/4 6-1/2 23-1/2 27-1/4 29-1/8 20 26-3/8 29-9/16 15-1/2 15 14-1/2 30 x 30
042 33, 34 30 29-15/16 3-1/4 7/8 6-1/2 23-1/2 27-1/4 29-1/8 20 26-3/8 29-9/16 15-1/2 14-3/4 14-1/4 30 x 30
048 33, 34 30 33-15/16 3-1/4 7/8 6-1/2 23-1/2 27-1/4 29-1/8 20 26-3/8 29-9/16 15-1/2 14-1/4 14-1/2 30 x 30
060 33, 34 30 39-15/16 3-1/4 7/8 6-1/2 23-1/2 27-1/4 29-1/8 20 26-3/8 29-9/16 14-3/4 13-1/2 15-1/2 30 x 30
Page 9
Printed in U.S.A.
BUILDING HEAT LOSS, 1000 BTU/HR
OUTDOOR TEMPERATURE, °F
UNIT INTEGRATED HEATING CAPACITY, 1000 BTU/HR
60
-10
01 0
20 30
10
20
30
40
50
70
80
38BYC BALANCE POINT WORKSHEET
40 50
60 70
80
AND AT RATED CFM
BASED ON INDOOR ENT. AIR AT 70°F
38BYC036-35
38BYC024-36
38BYC018-34
F(A,B)4ANF024
2.9
5.9
F(A,B)4ANF030
8.8
KW
38BYC030-35
F(A,B)4ANF036
11.7
F(A,B)4AN(F,B)042
14.7
F(A,B)4AN(F,B)048
38BYC042-34
17.6
FK4CNF005
38BYC048-34
38BYC060-34
FK4CNB006
20.5
23.4
A02078
9
Page 10
Combination ratings
Seasonal Efficiency SEER
TC
Factory-
Supplied
Enhance-
ment
UNIT
SIZE-
SERIES
018-33,
34
024-35,
36
030-34,
35
INDOOR
UNIT
F(A,B)4(A,B)N(F,C)024† 18,700 TDR — 12.00 — 10.80 17,800 3.30 11,200 2.28 7.50
CC5A/CD5AA018 17,800 NONE ——11.50 10.25 17,500 2.98 11,100 2.14 7.00
CC5A/CD5AA024 18,500 NONE ——11.50 10.60 17,700 3.16 11,200 2.22 7.20
CC5A/CD5AW024 18,500 NONE ——11.50 10.60 17,700 3.16 11,200 2.22 7.20
CE3AA024 18,500 NONE ——12.00 10.65 17,700 3.20 11,200 2.24 7.20
CF5AA024 18,500 NONE ——12.00 10.65 17,800 3.20 11,200 2.24 7.20
CK3BA024 18,500 NONE ——11.50 10.40 17,900 3.34 11,300 2.30 7.20
CK5A/CK5BA018 17,800 NONE ——11.50 10.75 17,700 3.18 11,200 2.24 7.00
CK5A/CK5BA024 18,500 NONE ——11.50 10.75 17,900 3.34 11,300 2.30 7.20
CK5A/CK5BW024 18,500 NONE ——11.50 10.75 17,900 3.34 11,300 2.30 7.20
F(A,B)4(A,B)N(F,C)018 17,400 TDR — 11.30 — 10.30 17,500 3.10 11,100 2.20 7.00
FC4(B,C)NF024 18,800 TDR&TXV 12.00 ——10.80 17,800 3.30 11,200 2.28 7.50
FF1DNA018 17,600 TDR — 11.50 — 10.70 17,400 3.16 10,900 2.24 7.00
FF1DNA024 18,800 TDR — 12.00 — 10.75 17,800 3.30 11,200 2.28 7.50
FG3AAA024 18,400 NONE ——11.50 10.45 17,700 3.12 11,200 2.22 7.35
FK4(C,D)NF001 18,800 TDR&TXV 13.20 ——12.20 17,200 3.46 10,600 2.42 8.00
40FK(A,B)/FK4(C,D)NF002
CC5A/CD5AA024 18,500 TDR — 13.00 — 11.70 17,000 3.18 10,500 2.30 7.50
CC5A/CD5AW024 18,500 TDR — 13.00 — 11.70 17,000 3.18 10,500 2.30 7.50
CE3AA024 18,500 TDR — 13.00 — 11.75 17,000 3.20 10,500 2.34 7.50
CK3BA024 18,500 TDR — 13.00 — 12.00 17,000 3.42 10,600 2.40 7.50
CK5A/CK5BA024 18,500 TDR — 13.00 — 12.00 17,000 3.42 10,600 2.40 7.50
CK5A/CK5BW024 18,500 TDR — 13.00 — 12.00 17,000 3.42 10,600 2.40 7.50
F(A,B)4(A,B)N(F,C)030† 23,000 TDR — 12.00 — 11.00 23,600 3.38 14,100 2.26 7.50
CC5A/CD5AA024 22,400 NONE ——11.70 10.60 23,600 3.18 14,100 2.18 7.30
CC5A/CD5AA030 22,600 NONE ——12.00 10.60 23,600 3.16 14,100 2.18 7.30
CC5A/CD5AW024 22,400 NONE ——11.70 10.60 23,600 3.18 14,100 2.18 7.30
CC5A/CD5AW030 22,600 NONE ——12.00 10.60 23,600 3.16 14,100 2.18 7.30
CE3AA024 22,600 NONE ——11.80 10.65 23,600 3.24 14,100 2.20 7.30
CE3AA030 23,000 NONE ——12.00 10.80 23,600 3.32 14,200 2.24 7.50
CF5AA024 22,600 NONE ——11.80 10.60 23,600 3.18 14,100 2.18 7.30
CK3BA024 22,400 NONE ——11.70 10.75 23,600 3.40 14,200 2.26 7.30
CK3BA030 22,600 NONE ——12.00 10.65 23,600 3.28 14,200 2.24 7.30
CK5A/CK5BA024 22,400 NONE ——11.70 10.75 23,600 3.40 14,200 2.26 7.30
CK5A/CK5BA030 22,600 NONE ——12.00 10.65 23,600 3.30 14,200 2.24 7.30
CK5A/CK5BW024 22,400 NONE ——11.70 10.75 23,600 3.40 14,200 2.26 7.30
CK5A/CK5BW030 22,600 NONE ——12.00 10.65 23,600 3.30 14,200 2.24 7.30
F(A,B)4(A,B)N(F,C)024 22,600 TDR — 11.70 — 10.85 23,600 3.36 14,100 2.24 7.50
FC4(B,C)NF024 22,600 TDR&TXV 11.70 ——10.85 23,600 3.36 14,100 2.24 7.50
FC4(B,C)NF030 23,000 TDR&TXV 12.00 ——11.00 23,600 3.38 14,100 2.26 7.50
FF1DNA024 22,600 TDR — 11.70 — 10.65 23,600 3.32 14,200 2.22 7.50
FF1DNA030 23,200 TDR — 12.00 — 10.80 23,600 3.36 14,200 2.24 7.50
FF1DNE024 22,600 TDR&TXV 11.70 —— 10.65 23,600 3.32 14,200 2.22 7.50
FF1DNE030 23,200 TDR&TXV 12.00 —— 10.80 23,600 3.36 14,200 2.24 7.50
FG3AAA024 22,200 NONE ——11.60 10.40 23,600 3.20 14,100 2.18 7.40
FK4(C,D)NF001 23,200 TDR&TXV 13.00 ——12.15 23,200 3.50 13,500 2.38 7.80
40FK(A,B)/FK4(C,D)NF002
40FK(A,B)/FK4(C,D)NF003
CC5A/CD5AA030 22,600 TDR ——13.00 11.70 22,800 3.20 13,300 2.26 7.40
CC5A/CD5AW030 22,600 TDR ——13.00 11.70 22,800 3.20 13,300 2.26 7.40
CE3AA030 22,600 TDR ——13.30 11.90 23,000 3.36 13,400 2.32 7.50
CK3BA030 22,600 TDR ——13.00 11.85 23,000 3.36 13,400 2.34 7.40
CK5A/CK5BA030 22,600 TDR ——13.00 11.75 23,000 3.36 13,400 2.32 7.40
CK5A/CK5BW030 22,600 TDR ——13.00 11.80 23,000 3.36 13,400 2.34 7.40
F(A,B)4(A,B)N(F,C)036† 28,400 TDR — 12.10 — 10.45 29,600 3.28 18,500 2.28 7.60
CC5A/CD5AA030 27,800 NONE ——12.00 10.35 29,000 3.08 18,200 2.24 7.30
CC5A/CD5AA036 28,800 NONE ——12.50 10.70 29,400 3.32 18,300 2.30 7.50
CC5A/CD5AW030 27,800 NONE ——12.00 10.35 29,000 3.08 18,200 2.24 7.30
CC5A/CD5AW036 28,800 NONE ——12.50 10.70 29,400 3.32 18,300 2.30 7.50
CE3AA030 28,000 NONE ——12.10 10.50 29,400 3.28 18,300 2.28 7.50
CE3AA036 28,400 NONE ——12.30 10.55 29,400 3.22 18,300 2.30 7.50
CF5AA036 28,400 NONE ——12.40 10.65 29,400 3.28 18,200 2.28 7.50
CK3BA030 27,800 NONE ——12.10 10.40 29,000 3.20 18,300 2.30 7.30
CK3BA036 28,800 NONE ——12.50 10.75 29,400 3.36 18,400 2.34 7.50
CK5A/CK5BA036 28,800 NONE ——12.50 10.75 29,400 3.34 18,400 2.34 7.50
CK5A/CK5BT036 28,800 NONE ——12.50 10.75 29,400 3.36 18,400 2.34 7.50
CK5A/CK5BW030 27,800 NONE ——12.10 10.40 29,000 3.20 18,300 2.30 7.30
CK5A/CK5BW036 28,800 NONE ——12.50 10.75 29,400 3.36 18,400 2.34 7.50
F(A,B)4(A,B)N(F,C)030 28,000 TDR — 12.20 — 10.60 29,200 3.30 18,300 2.30 7.50
19,000 TDR&TXV 13.50 ——12.30 17,300 3.58 10,700 2.46 8.00
23,600 TDR&TXV 13.20 ——12.35 23,200 3.62 13,500 2.40 8.00
23,800 TDR&TXV 14.00 ——12.50 23,000 3.58 13,400 2.42 8.00
ARI STANDARD RATINGS*
Cooling Heating
Field-Supplied
Standard
Rating
COILS + 58CV(A,X)070-12 FURNACE
COILS + 58CV(A,X)070-12 FURNACE
Accessory
TXV‡
TXV & TDR**
EER
High-Temp Low-Temp
TC COP TC COP
Seasonal
Efficiency
HSPF
See notes on pg. 14.
10
Page 11
Combination ratings continued
Cooling Heating
Seasonal Efficiency SEER
UNIT
SIZE-
SERIES
030-34,
35
036-34,
35
Factory-
INDOOR
UNIT
FC4(B,C)NF030 28,000 TDR&TXV 12.20 ——10.60 29,200 3.30 18,300 2.30 7.50
FC4(B,C)NF036 28,400 TDR&TXV 12.10 ——10.45 29,600 3.26 18,500 2.28 7.60
FF1DNA030 28,200 TDR ——12.20 10.50 29,400 3.32 18,400 2.30 7.50
FG3AAA036 28,400 NONE ——12.20 10.50 29,400 3.26 18,300 2.30 7.50
FK4(C,D)NF001 28,600 TDR&TXV 13.50 ——11.50 29,000 3.38 17,600 2.38 7.90
FK4(C,D)NF002 28,600 TDR&TXV 13.50 ——11.55 29,000 3.50 17,700 2.42 8.00
FK4(C,D)NF003 29,200 TDR&TXV 14.00 ——11.90 28,800 3.46 17,500 2.44 8.10
CC5A/CD5AA036 28,800 TDR — 13.50 — 11.60 29,000 3.36 17,600 2.38 7.80
CE3AA036 28,400 TDR — 13.20 — 11.35 29,000 3.28 17,600 2.36 7.80
CK3BA036 28,800 TDR — 13.50 — 11.60 29,000 3.44 17,600 2.42 7.80
CK5A/CK5BA036 28,800 TDR — 13.50 — 11.60 29,000 3.44 17,600 2.42 7.80
CK5A/CK5BT036 28,800 TDR — 13.50 — 11.60 29,000 3.44 17,600 2.42 7.80
CC5A/CD5AA036 28,800 TDR — 13.50 — 11.75 29,000 3.38 17,500 2.40 7.80
CC5A/CD5AW036 28,800 TDR — 13.50 — 11.75 29,000 3.38 17,500 2.40 7.80
CE3AA036 28,800 TDR — 13.50 — 11.60 29,000 3.32 17,400 2.38 7.80
CK3BA036 28,800 TDR — 13.50 — 11.80 29,000 3.46 17,500 2.44 7.80
CK5A/CK5BA036 28,800 TDR — 13.50 — 11.80 29,000 3.46 17,600 2.44 7.80
CK5A/CK5BW036 28,800 TDR — 13.50 — 11.80 29,000 3.46 17,500 2.44 7.80
F(A,B)4(A,B)N(F,B,C)042† 33,800 TDR — 12.10 — 10.45 35,800 3.46 23,000 2.44 8.00
CC5A/CD5AA036 33,600 NONE ——12.10 10.50 35,800 3.42 22,800 2.42 7.70
CC5A/CD5AA042 33,600 NONE ——12.10 10.50 35,800 3.42 22,800 2.42 7.70
CC5A/CD5AW036 33,600 NONE ——12.10 11.25 35,400 3.46 22,000 2.48 7.70
CC5A/CD5AW042 33,400 NONE ——12.10 10.45 35,800 3.38 22,800 2.40 7.60
CE3AA036 33,200 NONE ——12.00 10.40 35,600 3.38 22,800 2.40 7.60
CE3AA042 33,800 NONE ——12.10 10.60 36,000 3.48 22,800 2.44 7.70
CF5AA036 33,400 NONE ——12.10 10.50 35,800 3.40 22,800 2.42 7.70
CK3BA036 33,600 NONE ——12.10 10.50 35,800 3.50 22,800 2.46 7.70
CK3BA042 33,600 NONE ——12.10 10.50 35,800 3.50 22,800 2.46 7.70
CK5A/CK5BA036 33,600 NONE ——12.10 10.55 35,800 3.50 22,800 2.46 7.70
CK5A/CK5BA042 33,600 NONE ——12.10 10.50 35,800 3.50 22,800 2.46 7.70
CK5A/CK5BE042 33,600 NONE ——12.10 10.60 35,800 3.54 23,000 2.48 7.70
CK5A/CK5BT036 33,600 NONE ——12.10 10.50 35,800 3.50 22,800 2.46 7.70
CK5A/CK5BT042 33,600 NONE ——12.10 10.50 35,800 3.50 22,800 2.46 7.70
CK5A/CK5BW036 33,600 NONE ——12.10 10.50 35,800 3.50 22,800 2.46 7.70
F(A,B)4(A,B)N(F,C)036 33,000 TDR — 11.70 — 10.20 36,000 3.38 23,000 2.38 7.60
FC4(B,C)NF036 33,000 TDR&TXV 11.70 ——10.20 36,000 3.38 23,000 2.38 7.60
FC4(B,C)N(F,B)042 33,800 TDR&TXV 12.10 ——10.45 35,800 3.46 23,000 2.44 8.00
FG3AAA036 33,000 None ——12.00 10.30 35,800 3.38 22,800 2.40 7.70
FK4(C,D)NF001 33,200 TDR&TXV 12.20 ——11.00 35,000 3.46 22,200 2.46 7.80
40FK(A,B)/FK4(C,D)NF002
40FK(A,B)/FK4(C,D)NF003
40FK(A,B)/FK4(C,D)NF005
CE3AA042 33,800 TDR — 13.00 — 11.30 35,200 3.52 22,000 2.50 8.00
CK5A/CK5BE042 33,800 TDR — 13.00 — 11.35 35,200 3.60 22,200 2.54 8.00
CC5A/CD5AA042 33,800 TDR — 13.00 — 11.50 35,200 3.50 21,800 2.52 8.00
CE3AA042 33,800 TDR — 13.00 — 11.50 35,200 3.56 22,000 2.54 8.00
CK3BA042 33,800 TDR — 13.00 — 11.45 35,200 3.58 22,000 2.56 8.00
CK5A/CK5BA042 33,800 TDR — 13.00 — 11.45 35,200 3.58 22,000 2.56 8.00
CK5A/CK5BE042 33,800 TDR — 13.00 — 11.50 35,200 3.64 22,000 2.56 8.00
CK5A/CK5BT042 33,800 TDR — 13.00 — 11.45 35,200 3.58 22,000 2.56 8.00
CC5A/CD5AA042 33,800 TDR — 13.50 — 11.60 35,200 3.52 21,800 2.52 8.00
CC5A/CD5AW042 33,800 TDR — 13.50 — 11.55 35,200 3.48 21,600 2.50 8.00
CE3AA042 33,800 TDR — 13.50 — 11.60 35,200 3.58 21,800 2.56 8.00
CK3BA042 33,800 TDR — 13.50 — 11.55 35,200 3.60 21,800 2.56 8.00
CK5A/CK5BA042 33,800 TDR — 13.50 — 11.55 35,200 3.60 21,800 2.56 8.00
CK5A/CK5BT042 33,800 TDR — 13.50 — 11.55 35,200 3.60 21,800 2.56 8.00
CC5A/CD5AA042 33,800 TDR — 13.50 — 11.55 35,200 3.52 21,800 2.52 8.00
CC5A/CD5AW042 33,800 TDR — 13.50 — 11.50 35,200 3.46 21,800 2.50 8.00
CE3AA042 33,800 TDR — 13.50 — 11.55 35,200 3.58 21,800 2.54 8.00
CK3BA042 33,800 TDR — 13.50 — 11.50 35,200 3.60 22,000 2.56 8.00
CK5A/CK5BA042 33,800 TDR — 13.50 — 11.50 35,200 3.60 22,000 2.56 8.00
CK5A/CK5BT042 33,800 TDR — 13.50 — 11.50 35,200 3.60 22,000 2.56 8.00
CC5A/CD5AA042 33,800 TDR — 13.50 — 11.65 35,200 3.54 21,600 2.54 8.00
CC5A/CD5AW042 33,800 TDR — 13.50 — 11.60 35,200 3.48 21,600 2.52 8.00
CE3AA042 33,800 TDR — 13.50 — 11.65 35,200 3.58 21,800 2.56 8.00
CK3BA042 33,800 TDR — 13.50 — 11.60 35,200 3.62 21,800 2.58 8.00
CK5A/CK5BA042 33,800 TDR — 13.50 — 11.60 35,200 3.62 21,800 2.58 8.00
CK5A/CK5BT042 33,800 TDR — 13.50 — 11.60 35,200 3.62 21,800 2.58 8.00
33,400 TDR&TXV 12.30 ——11.00 35,000 3.58 22,200 2.50 8.00
33,600 TDR&TXV 13.00 ——11.55 35,000 3.58 21,800 2.56 8.00
35,000 TDR&TXV 14.00 ——12.00 33,400 3.72 22,000 2.64 8.00
TC
Supplied
Enhance-
ment
Standard
Rating
COILS + 58CV(A,X)070-12 FURNACE
COILS + 58CV(A,X)090-16 FURNACE
COILS + 58CV(A,X)070-12 FURNACE
COILS + 58CV(A,X)090-16 FURNACE
COILS + 58CV(A,X)110-22 FURNACE
COILS + 58CV(A,X)135-22 FURNACE
COILS + 58CV(A,X)155-22 FURNACE
Field-Supplied
Accessory
TXV‡
TXV & TDR**
ARI STANDARD RATINGS*
High-Temp Low-Temp
EER
TC COP TC COP
Seasonal
Efficiency
HSPF
See notes on pg. 14.
11
Page 12
Combination ratings continued
ARI STANDARD RATINGS*
Cooling Heating
Seasonal Efficiency SEER
UNIT
SIZE-
SERIES
042-33,
34
048-33,
34
Factory-
INDOOR
UNIT
F(A,B)4(A,B)N(F,B)048†
CC5A/CD5AA042
CC5A/CD5AC048
CC5A/CD5AW042
CC5A/CD5AW048
CD5AA048
CE3AA042
CE3AA048
CF5AA048
CK3BA042 39,000 NONE ——12.00 10.70 42,000 3.38 27,200 2.52 7.50
CK3BA048 40,000 NONE ——12.00 10.85 42,500 3.42 27,200 2.54 7.60
CK5A/CK5BA042 39,000 NONE ——12.00 10.70 42,000 3.38 27,200 2.52 7.50
CK5A/CK5BA048 40,000 NONE ——12.00 10.85 42,500 3.46 27,400 2.56 7.60
CK5A/CK5BE042 39,000 NONE ——12.00 10.85 41,000 3.42 27,200 2.54 7.50
CK5A/CK5BN042 38,000 NONE ——12.00 10.70 41,000 3.38 27,200 2.52 7.40
CK5A/CK5BN048 39,000 NONE ——12.00 10.85 41,000 3.42 27,200 2.54 7.50
CK5A/CK5BW048 40,000 NONE ——12.00 10.85 42,500 3.42 27,200 2.54 7.60
F(A,B)4(A,B)N(F,B)042
FC4(B,C)N(F,B)042
FC4(B,C)N(F,B)048
FG3AAA048
40FK(A,B)/FK4(C,D)NB006
40FK(A,B)/FK4(C,D)NF003
40FK(A,B)/FK4(C,D)NF005
CC5A/CD5AC048 39,000 TDR — 13.00 — 11.35 42,000 3.26 26,200 2.56 7.80
CD5AA048 39,000 TDR — 13.00 — 11.55 42,000 3.44 26,400 2.60 8.00
CE3AA048 39,000 TDR — 13.00 — 11.50 42,000 3.48 26,600 2.62 8.00
CK3BA048 39,000 TDR — 13.00 — 11.50 42,000 3.52 26,600 2.64 8.00
CK5A/CK5BA048 39,000 TDR — 13.00 — 11.50 42,000 3.52 26,600 2.64 8.00
CK5A/CK5BT048 39,000 TDR — 13.00 — 11.50 42,000 3.52 26,600 2.64 8.00
CC5A/CD5AC048 39,000 TDR — 13.00 — 11.50 42,000 3.28 26,200 2.56 7.80
CC5A/CD5AW048 39,000 TDR — 13.00 — 11.65 42,000 3.44 26,200 2.62 8.00
CD5AA048 39,000 TDR — 13.00 — 11.65 42,000 3.46 26,200 2.62 8.00
CE3AA048 39,000 TDR — 13.00 — 11.60 42,000 3.50 26,400 2.64 8.00
CK3BA048 39,000 TDR — 13.00 — 11.65 42,000 3.54 26,400 2.66 8.00
CK5A/CK5BA048 39,000 TDR — 13.00 — 11.65 42,000 3.54 26,400 2.66 8.00
CK5A/CK5BT048 39,000 TDR — 13.00 — 11.65 42,000 3.54 26,400 2.66 8.00
CK5A/CK5BW048 39,000 TDR — 13.00 — 11.65 42,000 3.54 26,400 2.66 8.00
CC5A/CD5AC048 39,000 TDR — 13.00 — 11.50 42,000 3.28 26,000 2.58 7.80
CC5A/CD5AW048 39,000 TDR — 13.00 — 11.70 42,000 3.46 26,200 2.62 8.00
CD5AA048 39,000 TDR — 13.00 — 11.70 42,000 3.46 26,200 2.62 8.00
CE3AA048 39,000 TDR — 13.00 — 11.60 42,000 3.50 26,400 2.64 8.00
CK3BA048 39,000 TDR — 13.00 — 11.65 42,000 3.54 26,400 2.66 8.00
CK5A/CK5BA048 39,000 TDR — 13.00 — 11.65 42,000 3.54 26,400 2.66 8.00
CK5A/CK5BT048 39,000 TDR — 13.00 — 11.65 42,000 3.54 26,400 2.66 8.00
CK5A/CK5BW048 39,000 TDR — 13.00 — 11.65 42,000 3.54 26,400 2.66 8.00
CC5A/CD5AC048 39,000 TDR — 13.00 — 11.55 42,000 3.28 26,000 2.58 7.80
CC5A/CD5AW048 39,000 TDR — 13.00 — 11.75 42,000 3.46 26,200 2.64 8.00
CD5AA048 39,000 TDR — 13.00 — 11.75 42,000 3.46 26,200 2.64 8.00
CE3AA048 39,000 TDR — 13.00 — 11.65 42,000 3.50 26,400 2.64 8.00
CK3BA048 39,000 TDR — 13.00 — 11.70 42,000 3.56 26,400 2.68 8.00
CK5A/CK5BA048 39,000 TDR — 13.00 — 11.70 42,000 3.56 26,400 2.68 8.00
CK5A/CK5BT048 39,000 TDR — 13.00 — 11.70 42,000 3.56 26,400 2.68 8.00
CK5A/CK5BW048 39,000 TDR — 13.00 — 11.70 42,000 3.56 26,400 2.68 8.00
40FK(A,B)/FK4(C,D)NF005†
CC5A/CD5AA060 46,000 NONE — — 11.50 9.95 48,000 3.24 32,200 2.44 7.40
CC5A/CD5AC048 44,500 NONE — — 11.50 9.80 48,000 3.10 31,800 2.38 7.00
CC5A/CD5AW048 45,500 NONE — — 11.50 9.90 48,000 3.28 32,200 2.46 7.50
CC5A/CD5AW060 47,000 NONE — — 12.00 10.20 48,000 3.42 32,400 2.52 7.80
CD5AA048 45,500 NONE — — 11.50 9.90 48,000 3.28 32,200 2.46 7.50
CE3AA048 46,000 NONE — ---- 11.50 10.00 48,000 3.36 32,200 2.50 7.60
CE3AA060 47,500 NONE — — 12.00 10.25 48,000 3.44 32,400 2.54 7.80
CF5AA048 45,000 NONE — — 11.50 10.00 48,000 3.22 32,000 2.44 7.30
CK3BA048 45,500 NONE — — 11.50 9.90 48,000 3.36 32,200 2.50 7.50
CK3BA060 46,000 NONE — — 11.50 10.20 48,000 3.52 32,400 2.56 7.40
CK5A/CK5BA048 45,500 NONE — — 11.50 9.90 48,000 3.36 32,200 2.50 7.50
CK5A/CK5BA060 46,000 NONE — — 11.50 10.20 48,000 3.52 32,400 2.56 7.40
CK5A/CK5BN048 44,500 NONE — — 11.50 9.95 48,000 3.28 32,000 2.46 7.00
CK5A/CK5BN060 46,000 NONE — — 11.50 10.35 48,000 3.56 32,400 2.58 7.40
CK5A/CK5BT048 45,500 NONE — — 11.50 9.90 48,000 3.36 32,200 2.50 7.50
CK5A/CK5BT060 46,000 NONE — — 11.50 10.20 48,000 3.52 32,400 2.56 7.40
CK5A/CK5BW048 45,500 NONE — — 11.50 9.90 48,000 3.36 32,200 2.50 7.50
CK5A/CK5BX060 47,000 NONE — — 12.00 10.35 48,000 3.56 32,400 2.58 7.80
40,000
39,000
39,000
39,000
40,000
40,000
39,500
40,000
40,000
39,500
39,500
40,000
39,500
42,000
39,500
41,500
48,000 TDR&TXV 13.00 ——10.95 48,000 3.58 31,600 2.64 8.00
TC
,
Supplied
Enhance-
ment
TDR
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
TDR
TDR & TXV
TDR & TXV
NONE
TDR & TXV
TDR & TXV
TDR & TXV
Standard
Rating
11.70
12.00
14.00
13.00
13.50
COILS + 58CV(A,X)090-16 FURNACE
COILS + 58CV(A,X)110-22 FURNACE
COILS + 58CV(A,X)135-22 FURNACE
COILS + 58CV(A,X)155-22 FURNACE
—
—
—
—
—
—
—
—
—
—
—
Field-Supplied
Accessory
TXV‡
TXV & TDR**
12.00
—
—
—
—
—
—
—
—
11.70
—
—
—
—
—
—
—
12.00
11.80
11.80
12.00
12.00
12.00
12.00
12.00
—
—
—
—
—
—
—
EER
10.65
10.70
10.70
10.55
10.70
10.75
10.70
10.75
10.75
10.45
10.45
10.65
10.70
12.10
12.50
11.55
High-Temp Low-Temp
TC COP TC COP
43,000
42,000
42,000
43,500
42,500
42,500
42,500
42,500
42,000
42,500
42,500
43,000
42,500
42,000
41,500
42,000
3.46
3.32
3.24
3.28
3.38
3.38
3.38
3.42
3.36
3.32
3.32
3.46
3.46
3.86
3.40
3.70
27,800
27,200
27,200
27,200
27,400
27,400
27,400
27,400
27,400
27,600
27,600
27,800
27,400
26,600
26,400
26,600
2.54
2.50
2.46
2.48
2.52
2.52
2.52
2.54
2.52
2.48
2.48
2.54
2.56
2.82
2.60
2.74
Seasonal
Efficiency
HSPF
8.00
7.50
7.50
7.50
7.60
7.60
7.60
7.70
7.60
7.60
7.60
8.00
7.70
8.30
7.80
8.00
See notes on pg. 14.
12
Page 13
Combination ratings continued
ARI STANDARD RATINGS*
Cooling Heating
Seasonal Efficiency SEER
UNIT
SIZE-
SERIES
048-33,
34
060-33,
34
Factory-
INDOOR
UNIT
F(A,B)4(A,B)N(F,B,C)048 46,000 TDR — 11.50 — 9.90 48,000 3.40 32,600 2.50 7.60
F(A,B)4(A,B)N(F,B,C)060 47,500 TDR — 11.70 — 10.00 48,000 3.48 33,000 2.52 7.80
FB4(A,B)NB070 48,000 TDR — 12.00 — 10.40 48,000 3.62 32,800 2.60 8.00
FC4(B,C)N(F,B)048 46,000 TDR&TXV 11.50 —— 9.90 48,000 3.40 32,600 2.50 7.60
FC4(B,C)N(F,B)060 47,500 TDR&TXV 11.70 ——10.00 48,000 3.48 33,000 2.52 7.80
FC4(B,C)NB054 48,000 TDR&TXV 12.10 —— 10.45 48,000 3.64 32,600 2.60 8.00
FC4(B,C)NB070 48,000 TDR&TXV 12.00 —— 10.40 48,000 3.62 32,800 2.60 8.00
FG3AAA048 45,000 NONE — — 11.40 9.90 48,000 3.34 32,200 2.48 7.50
FG3AAA060 46,000 NONE — — 11.80 10.10 48,000 3.38 32,400 2.50 7.60
40FK(A,B)/FK4(C,D)NB006
CE3AA060 45,500 TDR — 12.50 — 10.70 48,000 3.42 31,600 2.58 7.80
CC5A/CD5AA060 45,000 TDR — 12.00 — 10.60 48,000 3.24 31,000 2.50 7.80
CE3AA060 45,500 TDR — 12.50 — 10.90 48,000 3.46 31,400 2.60 7.80
CK3BA060 45,500 TDR — 12.50 — 10.85 48,000 3.58 31,400 2.64 7.80
CK5A/CK5BA060 45,500 TDR — 12.50 — 10.85 48,000 3.58 31,400 2.64 7.80
CK5A/CK5BT060 45,500 TDR — 12.50 — 10.85 48,000 3.58 31,400 2.64 7.80
CK5A/CK5BX060 47,000 TDR — 13.00 — 11.15 48,000 3.62 31,400 2.66 7.80
CC5A/CD5AA060 45,000 TDR — 12.00 — 10.55 48,000 3.24 31,200 2.50 7.80
CC5A/CD5AW060 47,000 TDR — 13.00 — 10.85 48,000 3.44 31,200 2.58 7.80
CE3AA060 45,500 TDR — 12.50 — 10.85 48,000 3.44 31,400 2.60 7.80
CK3BA060 45,500 TDR — 12.50 — 10.85 48,000 3.58 31,400 2.64 7.80
CK5A/CK5BA060 45,500 TDR — 12.50 — 10.85 48,000 3.58 31,400 2.64 7.80
CK5A/CK5BT060 45,500 TDR — 12.50 — 10.85 48,000 3.58 31,400 2.64 7.80
CK5A/CK5BX060 47,000 TDR — 13.00 — 11.05 48,000 3.60 31,400 2.66 7.80
CC5A/CD5AA060 45,000 TDR — 12.00 — 10.65 48,000 3.26 30,200 2.46 7.80
CC5A/CD5AW060 47,000 TDR — 13.00 — 10.95 48,000 3.46 31,200 2.60 7.80
CE3AA060 45,500 TDR — 12.50 — 10.95 48,000 3.46 31,200 2.60 7.80
CK3BA060 45,500 TDR — 12.50 — 10.95 48,000 3.60 31,400 2.64 7.80
CK5A/CK5BA060 45,500 TDR — 12.50 — 10.95 48,000 3.60 31,400 2.64 7.80
CK5A/CK5BT060 45,500 TDR — 12.50 — 10.95 48,000 3.60 31,400 2.66 7.80
CK5A/CK5BX060 47,000 TDR — 13.00 — 11.15 48,000 3.62 31,400 2.68 7.80
40FK(A,B)/FK4(C,D)NB006†
CC5A/CD5AA060 55,000 NONE ——11.00 9.45 60,000 2.94 39,000 2.24 7.00
CC5A/CD5AW060 57,000 NONE ——11.40 9.75 60,000 3.08 38,500 2.30 7.40
CE3AA060 57,000 NONE ——11.50 9.75 60,000 3.12 39,000 2.32 7.40
CK3BA060 55,000 NONE ——11.00 9.65 60,000 3.06 39,000 2.30 7.00
CK5A/CK5BA060 55,000 NONE ——11.00 9.85 60,000 3.06 39,000 2.30 7.00
CK5A/CK5BN060 55,000 NONE ——11.00 9.65 60,000 3.18 39,000 2.36 7.00
CK5A/CK5BT060 55,000 NONE ——11.00 9.85 60,000 3.06 39,000 2.30 7.00
CK5A/CK5BX060 57,000 NONE ——11.50 9.65 60,000 3.18 39,000 2.36 7.40
F(A,B)4(A,B)N(F,B,C)060 56,500 TDR — 11.20 — 9.50 60,000 3.16 40,000 2.32 7.50
FB4(A,B)NB070 58,000 TDR — 11.50 — 9.80 60,000 3.30 39,500 2.38 7.70
FC4(B,C)N(F,B)060 56,500 TDR&TXV 11.20 —— 9.50 60,000 3.16 40,000 2.32 7.50
FC4(B,C)NB070 58,000 TDR&TXV 11.50 —— 9.80 60,000 3.30 39,500 2.38 7.70
FG3AAA060 55,500 NONE ——— 9.60 60,000 3.04 39,000 2.30 7.30
CC5A/CD5AA060 54,500 TDR — 11.30 — 9.75 60,000 2.96 38,500 2.28 7.20
CE3AA060 56,500 TDR — 11.50 — 10.05 60,000 3.16 38,500 2.38 7.50
CK3BA060 54,500 TDR — 11.50 — 9.90 60,000 3.28 39,000 2.40 7.50
CK5A/CK5BA060 54,500 TDR — 11.50 — 9.90 60,000 3.28 39,000 2.40 7.50
CK5A/CK5BT060 54,500 TDR — 11.50 — 9.90 60,000 3.28 39,000 2.40 7.50
CK5A/CK5BX060 56,500 TDR — 12.00 — 10.20 60,000 3.30 38,500 2.44 7.50
CC5A/CD5AA060 54,500 TDR — 11.30 — 9.70 60,000 2.96 38,500 2.28 7.20
CC5A/CD5AW060 54,500 TDR — 11.50 — 10.00 60,000 3.14 38,500 2.36 7.50
CE3AA060 56,500 TDR — 11.50 — 10.05 60,000 3.16 38,500 2.38 7.50
CK3BA060 54,500 TDR — 11.50 — 9.85 60,000 3.28 39,000 2.40 7.50
CK5A/CK5BA060 54,500 TDR — 11.50 — 9.85 60,000 3.28 39,000 2.40 7.50
CK5A/CK5BT060 54,500 TDR — 11.50 — 9.85 60,000 3.28 39,000 2.40 7.50
CK5A/CK5BX060 56,500 TDR — 12.00 — 10.20 60,000 3.30 38,500 2.44 7.50
CC5A/CD5AA060 54,500 TDR — 11.50 — 9.80 60,000 2.98 38,500 2.28 7.20
CC5A/CD5AW060 54,500 TDR — 11.50 — 10.1 60,000 3.16 38,500 2.36 7.50
CE3AA060 56,500 TDR — 11.50 — 10.10 60,000 3.18 38,500 2.38 7.50
CK3BA060 54,500 TDR — 11.50 — 9.95 60,000 3.28 38,500 2.42 7.50
CK5A/CK5BA060 54,500 TDR — 11.50 — 9.95 60,000 3.28 38,500 2.42 7.50
CK5A/CK5BT060 54,500 TDR — 11.50 — 9.95 60,000 3.28 38,500 2.42 7.50
CK5A/CK5BX060 56,500 TDR — 12.00 — 10.25 60,000 3.30 38,500 2.44 7.50
48,000 TDR&TXV 13.50 ——11.35 48,000 3.74 31,400 2.72 8.20
59,000 TDR&TXV 12.00 ——10.30 60,000 3.40 39,000 2.46 8.00
TC
Supplied
Enhance-
ment
Standard
Rating
COILS + 58CV(A,X)090-16 FURNACE
COILS + 58CV(A,X)110-22 FURNACE
COILS + 58CV(A,X)135-22 FURNACE
COILS + 58CV(A,X)155-22 FURNACE
COILS + 58CV(A,X)110-22 FURNACE
COILS + 58CV(A,X)135-22 FURNACE
COILS + 58CV(A,X)155-22 FURNACE
Field-Supplied
Accessory
TXV‡
TXV & TDR**
EER
High-Temp Low-Temp
TC COP TC COP
Seasonal
Efficiency
HSPF
See notes on pg. 14.
13
Page 14
* Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on:
Cooling Standard:80° F (27° C) db 67° F (19° C) wb indoor entering air temperature and 95° F (35° C) db air entering outdoor unit.
High-Temperature Heating Standard:70° F (21° C) db indoor entering air temperature and 47° F (8° C) db 43° F (6° C) wb air entering outdoor unit.
Low-Temperature Heating Standard:70° F (21° C) db indoor entering air temperature and 17° F (–8° C) db 15° F (11° C) wb air entering outdoor
unit.
† Outdoor section/indoor section combination tested in accordance with DOE test procedures for heat pumps. Ratings for other combinations are
determined under DOE computer simulation procedures.
‡ Requires hard shutoff TXV; based on computer simulation.
** TDR is provided on most Carrier Furnaces.
COP — Coefficient of Performance
HSPF — Heating Seasonal Performance Factor
SEER — Seasonal Energy Efficiency Ratio
TC — Total Capacity (Btuh)
TDR — Time-Delay Relay
TXV — Thermostatic Expansion Valve
14
Page 15
Detailed cooling capacities*
EVAPORATOR
AIR
CFM EWB
85 95 105 115 125
Capacity
MBtuh†
Total
System
kW**
Capacity
CONDENSER ENTERING AIR TEMPERATURES ° F
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
System
38BYC018-33, 34 Outdoor Section with F(A,B)4(A,B)N(F,C)024 Indoor Section
72 21.0 10.5 1.51 20.1 10.2 1.69 19.2 9.86 1.91 18.2 9.52 2.12 17.2 9.17 2.36
550 63†† 17.8 13.0 1.49 17.0 12.6 1.68 16.2 12.3 1.88 15.3 11.9 2.10 14.4 11.5 2.34
650 63†† 18.2 14.0 1.53 17.4 13.7 1.72 16.5 13.3 1.93 15.6 12.9 2.13 14.7 12.5 2.38
750 63†† 18.4 15.0 1.58 17.6 14.6 1.75 16.7 14.2 1.95 15.8 13.9 2.17 14.9 13.5 2.41
CC5A/CD5AA 018 0.95 1.00 FF1DNA 018 0.94 0.96
CC5A/CD5AW 024 0.99 1.01 FG3AAA 024 0.98 1.00
CK5A/CK5BA 018
CK5A/CK5BW 024
F(A,B)4(A,B)N(F,C) 024
FC4(B,C)NF 024
See notes on pg. 21.
67 19.1 13.4 1.51 18.3 13.0 1.68 17.5 12.7 1.88 16.6 12.3 2.11 15.6 12.0 2.34
62 17.5 16.1 1.49 16.7 15.8 1.68 16.0 15.4 1.88 15.2 15.0 2.10 14.4 14.4 2.33
57 17.0 17.0 1.50 16.4 16.4 1.68 15.8 15.8 1.87 15.1 15.1 2.08 14.4 14.4 2.34
72 21.4 11.1 1.56 20.5 10.8 1.74 19.5 10.5 1.93 18.5 10.1 2.15 17.5 9.80 2.41
67 19.5 14.4 1.53 18.7 14.1 1.73 17.8 13.8 1.93 16.8 13.4 2.14 15.9 13.1 2.39
62 18.0 17.5 1.53 17.2 17.1 1.71 16.5 16.5 1.92 15.8 15.8 2.14 15.0 15.0 2.37
57 17.8 17.8 1.53 17.2 17.2 1.72 16.5 16.5 1.91 15.8 15.8 2.12 15.0 15.0 2.38
72 21.6 11.7 1.58 20.7 11.4 1.78 19.7 11.1 1.98 18.7 10.7 2.19 17.7 10.4 2.45
67 19.8 15.5 1.58 18.9 15.1 1.75 18.0 14.8 1.97 17.1 14.4 2.18 16.1 14.1 2.41
62 18.5 18.5 1.57 17.8 17.8 1.75 17.1 17.1 1.96 16.3 16.3 2.18 15.5 15.5 2.41
57 18.5 18.5 1.57 17.8 17.8 1.75 17.1 17.1 1.95 16.3 16.3 2.19 15.5 15.5 2.42
Multipliers for Determining the Performance With Other Indoor Sections
0.95
0.99
0.99
1.00
0.93
1.01
Cooling
1.01
1.01
1.01
1.00
0.99
1.00
Indoor
Section Size
40FK(A,B)/FK4(C,D)NF
COILS + 58CV(A,X)070-12 FURNACE
CC5A/CD5AA
CC5A/CD5AW
CE3AA
CK3BA
CK5A/CK5BA
CK5A/CK5BW
002 1.02 0.90
024 0.99
024 0.99
024 0.99
024 0.99
024 0.99
024 0.99
Indoor
Section Size
024 0.99 1.01 024 1.01 1.00
CE3AA 024 0.99 1.01 FK4(C,D)NF 001 1.01 0.90
CF5AA 024 0.99 1.01
CK3BA 024 0.99 1.01
024
018
Capacity Power Capacity Power
Cooling
0.91
0.91
0.91
0.89
0.89
0.89
Total
kW** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
15
Page 16
Detailed cooling capacities* continued
EVAPORATOR
AIR
CFM EWB
85 95 105 115 125
Capacity
MBtuh†
Total
System
kW**
Capacity
CONDENSER ENTERING AIR TEMPERATURES ° F
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
38BYC024-35, 36 Outdoor Section With F(A,B)4(A,B)N(F,C)030 Indoor Section
72
725
825
925
CC5A/CD5AA 024 0.97 1.01 FF1DNA 024 0.98 1.02
CC5A/CD5AW 024 0.97 1.01 FF1DNE 024 0.98 1.02
CK5A/CK5BA 024 0.97 0.99 CC5A/CD5AA 030 0.98 0.92
CK5A/CK5BW 024 0.97 0.99 CE3AA 030 0.98 0.91
F(A,B)4(A,B)N(F,C) 024 0.98 1.00 CK5A/CK5BA 030 0.98 0.92
FC4(B,C)NF 024 0.98 1.00 —— —
See notes on pg. 21.
67
63††
62
57
72
67
63††
62
57
72
67
63††
62
57
Indoor
Section Size
CE3AA 024 0.98 1.01 FG3AAA 024 0.97 1.02
CF5AA 024 0.98 1.02 40FK(A,B)/
CK3BA 024 0.97 1.00 003 1.03 0.91
25.7
23.6
21.9
21.7
21.1
26.0
24.0
22.3
22.1
21.9
26.3
24.2
22.5
22.5
22.5
13.0
1.95
16.6
16.1
20.1
21.1
13.5
17.6
17.0
21.4
21.9
14.0
18.5
17.9
22.4
22.5
Capacity Power Capacity Power
030 0.98 1.02 030 1.01 1.03
030 0.98 1.02 030 1.01 1.03
030 1.00 1.02 FK4(C,D)NF 001 1.01 0.91
030 0.98 1.01
030 0.98 1.01 CC5A/CD5AW 030 0.98 0.92
030 0.98 1.01 CK3BA 030 0.98 0.91
030 1.00 1.00 CK5A/CK5BW 030 0.98 0.92
030 1.00 1.00
24.7
1.95
22.7
1.95
21.1
1.94
20.8
1.94
20.4
1.98
25.0
1.98
23.0
1.98
21.4
1.98
21.2
1.98
21.1
2.01
25.2
2.01
23.2
2.01
21.6
2.01
21.7
2.01
21.7
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
12.6
16.3
15.8
19.7
20.4
13.1
17.2
16.7
20.9
21.1
13.6
18.2
17.5
21.7
21.7
2.15
2.14
2.14
2.14
2.14
2.18
2.18
2.18
2.18
2.18
2.22
2.21
2.21
2.21
2.21
23.7
21.7
20.1
19.9
19.7
12.2
15.9
15.4
19.3
19.7
24.0
12.8
22.0
16.9
20.4
16.3
20.4
20.3
20.4
20.4
24.2
13.3
22.2
17.8
20.6
17.1
20.9
20.9
20.9
20.9
Indoor
Section Size
FK4(C,D)NF
2.38
22.7
2.37
2.37
2.37
2.37
2.41
2.41
2.40
2.40
2.40
2.44
2.44
2.44
2.44
2.44
COILS + 58CV(A,X)070-12 FURNACE
11.9
20.7
15.5
19.2
15.0
19.1
18.8
19.0
19.0
22.9
12.4
21.0
16.5
19.5
15.9
19.6
19.6
19.6
19.6
23.1
12.9
21.2
17.4
19.7
16.7
20.1
20.1
20.1
20.1
002 1.03 0.91
2.63
2.63
2.62
2.62
2.62
2.67
2.66
2.66
2.66
2.66
2.70
2.70
2.69
2.69
2.69
Cooling
21.6
19.8
18.3
18.3
18.2
21.9
20.0
18.5
18.8
18.8
22.0
20.2
18.7
19.3
19.3
11.5
15.1
14.6
18.2
18.2
12.1
16.1
15.5
18.8
18.8
12.6
17.0
16.4
19.3
19.3
2.92
2.91
2.90
2.90
2.90
2.96
2.95
2.94
2.94
2.94
3.00
2.99
2.98
2.98
2.98
16
Page 17
Detailed cooling capacities* continued
EVAPORATOR
AIR
CFM EWB
85 95 105 115 125
Capacity
MBtuh†
Total
System
kW**
Capacity
CONDENSER ENTERING AIR TEMPERATURES ° F
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
38BYC030-34, 35 Outdoor Section With F(A,B)4(A,B)NF036 Indoor Section
72
900
950
1125
CC5A/CD5AA 030 0.98 0.98 FG3AAA 036 1.00 0.98
CC5A/CD5AW 030 0.98 0.98
CK5A/CK5BA 036 1.01 0.99
CK5A/CK5BT 036 1.01 0.99
CK5A/CK5BW 030 0.98 0.98
F(A,B)4(A,B)N(F,C) 030 0.99 0.98
FC4(B,C)NF 030 0.99 0.98
See notes on pg. 21.
67
63††
62
57
72
67
63††
62
57
72
67
63††
62
57
Indoor
Section Size
CE3AA 030 0.99 0.98
CF5AA 036 1.00 0.99
CK3BA 030 0.98 0.98
FF1DNA 030 0.99 0.99
32.1 16.6 2.38 30.8 16.1 2.67 29.3 15.6 2.99 27.9 15.0 3.32 26.3 14.5 3.68
29.2 20.7 2.39 28.0 20.2 2.67 26.7 19.6 2.98 25.3 19.1 3.31 23.8 18.5 3.67
27.1 20.0 2.39 25.9 19.5 2.67 24.7 18.9 2.98 23.4 18.3 3.30 22.0 17.7 3.65
26.7 24.8 2.39 25.5 24.2 2.67 24.4 23.6 2.97 23.2 22.9 3.30 21.9 21.9 3.65
26.0 26.0 2.39 25.1 25.1 2.67 24.1 24.1 2.97 23.1 23.1 3.30 21.9 21.9 3.65
32.6 17.3 2.43 31.2 16.8 2.72 29.8 16.3 3.03 28.3 15.7 3.37 26.6 15.1 3.73
29.7 22.0 2.43 28.4 21.4 2.72 27.1 20.9 3.03 25.6 20.3 3.36 24.1 19.7 3.72
27.6 21.2 2.44 26.3 20.6 2.72 25.0 20.1 3.02 23.7 19.5 3.35 22.3 18.8 3.70
27.2 26.4 2.44 26.1 25.7 2.72 24.9 24.9 3.02 23.8 23.8 3.35 22.7 22.7 3.71
26.9 26.9 2.44 26.0 26.0 2.72 24.9 24.9 3.02 23.8 23.8 3.35 22.7 22.7 3.71
33.0 18.0 2.47 31.6 17.5 2.76 30.1 17.0 3.08 28.5 16.4 3.41 26.8 15.8 3.78
30.1 23.2 2.48 28.8 22.6 2.77 27.3 22.1 3.08 25.9 21.5 3.40 24.3 20.8 3.77
27.9 22.3 2.48 26.6 21.7 2.77 25.3 21.2 3.07 23.9 20.6 3.40 22.5 19.9 3.75
27.8 27.8 2.48 26.7 26.7 2.77 25.6 25.6 3.07 24.5 24.5 3.40 23.2 23.2 3.76
27.7 27.7 2.48 26.7 26.7 2.77 25.6 25.6 3.07 24.5 24.5 3.40 23.3 23.3 3.76
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Capacity Power Capacity Power
036 1.01 0.99 FK4(C,D)NF 001 1.01 0.91
036 1.01 0.99 003 1.03 0.90
036 1.00 0.98
036 1.01 0.99
036 1.01 0.99
036 1.00 1.00
036 1.00 1.00
Indoor
Section Size
40FK(A,B)/FK4(C,D)NF
CC5A/CD5AA 036 1.01 0.91
CE3AA 036 1.00 0.92
CK3BA 036 1.01 0.91
CK5A/CK5BA 036 1.01 0.91
CK5A/CK5BT 036 1.01 0.91
CC5A/CD5AA 036 1.01 0.90
CC5A/CD5AW 036 1.01 0.90
CE3AA 036 1.01 0.91
CK3BA 036 1.01 0.90
CK5A/CK5BA 036 1.01 0.90
CK5A/CK5BW 036 1.01 0.90
002 1.01 0.92
COILS + 58CV(A,X)070-12 FURNACE
COILS + 58CV(A,X)090-16 FURNACE
—— —
Cooling
Total
System
kW** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
17
Page 18
Detailed cooling capacities* continued
EVAPORATOR
AIR
CFM EWB
85 95 105 115 125
Capacity
MBtuh†
Total
System
kW**
Capacity
CONDENSER ENTERING AIR TEMPERATURES ° F
MBtuh†
Total
System
kW**
Capacity
MBtuh†
38BYC036-34, 35 Outdoor Section With F(A,B)4(A,B)N(F,C)042 Indoor Section
72
1050
1200
1350
CC5A/CD5AA 036 0.99 0.99 CK3BA
CC5A/CD5AW 036 0.99 0.99 CK5A/CK5BE
CK5A/CK5BA 036 0.99 0.99 CK5A/CK5BA
CK5A/CK5BE 042 0.99 0.99
CK5A/CK5BT 036 0.99 0.99 CC5A/CD5AA
CK5A/CK5BW 036 0.99 0.99 CE3AA
F(A,B)4(A,B)N(F,B,C)
FC4(B,C)NF 036 0.98 1.01 CK5A/CK5BT
FC4(B,C)N(F,B) 042 1.00 1.00
CK5A/CK5BE
CC5A/CD5AA
See notes on pg. 21.
67
63††
62
57
72
67
63††
62
57
72
67
63††
62
57
Indoor
Section Size
CE3AA 036 0.98 0.99
CF5AA 036 0.99 0.99 CC5A/CD5AW
CK3BA 036 0.99 0.99 CE3AA
FG3AAA 036 0.98 0.99 CC5A/CD5AA
CE3AA
CE3AA
38.2 19.8 2.90 36.6 19.2 3.20 35.0 18.6 3.51 33.2 17.9 3.86 31.4 17.3 4.25
34.8 24.8 2.88 33.3 24.2 3.17 31.8 23.6 3.48 30.2 22.9 3.83 28.5 22.2 4.21
32.3 24.0 2.86 30.9 23.3 3.15 29.5 22.7 3.46 27.9 22.0 3.81 26.3 21.3 4.18
31.8 29.8 2.86 30.5 29.1 3.15 29.1 28.3 3.46 27.7 27.5 3.80 26.3 26.3 4.18
31.1 31.1 2.85 30.0 30.0 3.14 28.8 28.8 3.46 27.6 27.6 3.80 26.3 26.3 4.18
38.8 20.7 2.97 37.1 20.1 3.26 35.4 19.4 3.58 33.7 18.8 3.93 31.7 18.1 4.31
35.3 26.3 2.94 33.8 25.7 3.23 32.2 25.0 3.55 30.6 24.4 3.90 28.8 23.6 4.27
32.8 25.4 2.92 31.4 24.7 3.22 29.9 24.1 3.53 28.3 23.4 3.87 26.6 22.6 4.24
32.5 31.6 2.92 31.2 30.8 3.21 29.8 29.8 3.53 28.5 28.5 3.87 27.1 27.1 4.25
32.2 32.2 2.92 31.0 31.0 3.21 29.8 29.8 3.53 28.5 28.5 3.87 27.1 27.1 4.25
39.2 21.5 3.03 37.5 20.9 3.33 35.8 20.3 3.65 33.9 19.6 3.99 32.0 18.9 4.37
35.7 27.8 3.01 34.2 27.1 3.30 32.5 26.5 3.62 30.8 25.7 3.96 29.0 25.0 4.34
33.2 26.7 2.99 31.7 26.1 3.28 30.2 25.4 3.59 28.5 24.6 3.93 26.9 23.9 4.31
33.1 33.1 2.99 31.8 31.8 3.28 30.5 30.5 3.60 29.2 29.2 3.94 27.8 27.8 4.32
33.1 33.1 2.99 31.8 31.8 3.28 30.6 30.6 3.60 29.2 29.2 3.94 27.8 27.8 4.32
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Capacity Power Capacity Power
042 0.99 0.92 CK5A/CK5BA
042 0.99 0.99 CK5A/CK5BT
042 1.00 0.99 CC5A/CD5AA
042 0.99 0.99 CK3BA
042 0.99 0.99 CK5A/CK5BT
042 0.99 0.99 CC5A/CD5AW
036 0.98 1.01 CK3BA
042 1.00 1.00 CK5A/CK5BA
COILS + 58CV(A,X)070-12 FURNACE
042 1.00
042 1.00
COILS + 58CV(A,X)090-16 FURNACE
042 1.00
042 1.00
0.93 CE3AA
0.92 CK3BA
0.91
0.91
Indoor
Section Size
CC5A/CD5AW
CK5A/CK5BA
CK5A/CK5BT 042 1.00
Total
System
kW**
COILS + 58CV(A,X)110-22 FURNACE
COILS + 58CV(A,X)135-22 FURNACE
COILS + 58CV(A,X)155-22 FURNACE
Capacity
MBtuh†
042 1.00
042 1.00
042 1.00
042 1.00
042 1.00
042 1.00
042 1.00
042 1.00
042 1.00
042 1.00
042 1.00
042 1.00
042 1.00
042 1.00
042 1.00
042 1.00
042 1.00
042 1.00
042 1.00
042 1.00
042 1.00
——
Total
System
kW**
Capacity
MBtuh†
Cooling
0.91
0.91
0.91
0.91
0.90
0.91
0.90
0.90
0.90
0.90
0.90
0.91
0.91
0.91
0.91
0.91
0.90
0.90
0.90
0.90
0.90
0.90
—
Total
System
kW** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
18
Page 19
Detailed cooling capacities* continued
EVAPORATOR
AIR
CFM EWB
85 95 105 115 125
Capacity
MBtuh†
Total
System
kW**
Capacity
CONDENSER ENTERING AIR TEMPERATURES ° F
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
38BYC042-33, 34 Outdoor Section With F(A,B)4(A,B)N(F,C)048 Indoor Section
72
1275
1475
1675
CC5A/CD5AA 042 0.98 0.98 CK5A/CK5BT 048 0.98 0.91
CC5A/CD5AC 048 0.98 0.98
CC5A/CD5AW 042 0.98 0.98 CC5A/CD5AC 048 0.98 0.91
CK5A/CK5BA 042 0.98 0.97
CK5A/CK5BN 042 0.95 0.97 CC5A/CD5AW 048 0.98 0.89
CK5A/CK5BW 048 1.00 0.98 CE3AA 048 0.98 0.90
F(A,B)4(A,B)N(F,B) 042 0.99 1.00 CK3BA 048 0.98 0.89
FC4(B,C)N(F,B) 042 0.99 1.00 CK5A/CK5BT 048 0.98 0.89
40FK(A,B)/FK4(C,D)NF
CC5A/CD5AC 048 0.98 0.92 CK3BA 048 0.98 0.89
CK5A/CK5BA 048 0.98 0.91 —— —
See notes on pg. 21.
67
63††
62
57
72
67
63††
62
57
72
67
63††
62
57
Indoor
Section Size
CD5AA 048 1.00 0.99 CD5AA 048 0.98 0.89
CE3AA 042 0.99 0.99 CE3AA 048 0.98 0.90
CF5AA 048 1.00 0.99 CK5A/CK5BA 048 0.98 0.90
CK3BA 042 0.98 0.97 CK5A/CK5BT 048 0.98 0.90
FG3AAA 048 0.99 0.99
CD5AA 048 0.98 0.90 CK5A/CK5BA 048 0.98 0.89
CE3AA 048 0.98 0.91 CK5A/CK5BT 048 0.98 0.89
CK3BA 048 0.98 0.91 CK5A/CK5BW 048 0.98 0.89
44.7
41.2
38.4
38.0
37.5
45.3
41.8
39.0
38.9
38.8
45.8
42.1
39.4
39.8
39.8
COILS + 58CV(A,X)090-16 FURNACE CE3AA 048 0.98 0.90
22.9
3.39
29.7
28.9
36.2
37.5
24.1
31.8
30.8
38.6
38.8
25.2
33.8
32.6
39.8
39.8
Capacity Power Capacity Power
048 1.00 0.99 CC5A/CD5AW 048 0.98 0.89
048 1.00 0.99 CK3BA 048 0.98 0.90
048 1.00 0.98 CK5A/CK5BW 048 0.98 0.90
048 1.00 0.97 CC5A/CD5AC 048 0.98 0.91
048 0.98 0.98 CD5AA 048 0.98 0.89
048 1.00 1.00 CK5A/CK5BA 048 0.98 0.89
048 1.00 1.00 CK5A/CK5BW 048 0.98 0.89
003 0.99 0.91 CC5A/CD5AC 048 0.98 0.90
005 1.04 0.91 CC5A/CD5AW 048 0.98 0.89
006 1.05 0.90 CD5AA 048 0.98 0.89
42.9
3.34
39.5
3.31
36.8
3.30
36.5
3.30
36.2
3.47
43.4
3.43
40.0
3.40
37.4
3.39
37.4
3.39
37.4
3.56
43.7
3.52
40.3
3.48
37.7
3.49
38.4
3.49
38.4
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
22.3
29.1
28.2
35.4
36.2
23.4
31.1
30.1
37.4
37.4
24.5
33.1
31.9
38.4
38.4
3.72
3.67
3.63
3.63
3.62
3.80
3.76
3.72
3.72
3.72
3.89
3.84
3.81
3.82
3.82
41.0
21.6
37.7
28.4
35.2
27.5
34.9
34.5
34.8
34.8
41.6
22.8
38.2
30.4
35.6
29.4
36.0
36.0
35.9
35.9
41.8
23.9
38.5
32.3
35.9
31.1
36.9
36.9
36.9
36.9
Indoor
Section Size
4.08
39.0
4.03
35.8
3.99
33.4
3.98
33.3
3.98
33.3
4.17
39.4
4.11
36.2
4.07
33.7
4.08
34.4
4.08
34.4
4.25
39.6
4.20
36.5
4.16
34.0
4.18
35.2
4.18
35.2
COILS + 58CV(A,X)110-22 FURNACE
COILS + 58CV(A,X)135-22 FURNACE
COILS + 58CV(A,X)155-22 FURNACE
20.9
27.6
26.7
33.3
33.3
22.1
29.6
28.6
34.4
34.4
23.2
31.6
30.4
35.2
35.2
4.47
4.41
4.37
4.37
4.37
4.56
4.50
4.45
4.47
4.47
4.64
4.59
4.54
4.57
4.57
36.9
33.9
31.5
31.8
31.8
37.3
34.2
31.9
32.8
32.8
37.4
34.5
32.1
33.6
33.6
Cooling
20.2
26.9
25.9
31.8
31.8
21.3
28.9
27.8
32.8
32.8
22.5
30.8
29.5
33.6
33.6
4.89
4.83
4.78
4.78
4.78
4.98
4.92
4.87
4.89
4.89
5.07
5.01
4.96
4.99
4.99
19
Page 20
Detailed cooling capacities* continued
EVAPORATOR
AIR
CFM EWB
85 95 105 115 125
Capacity
MBtuh†
Total
System
kW**
Capacity
CONDENSER ENTERING AIR TEMPERATURES ° F
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
38BYC048-33, 34 Outdoor Section With 40FK(A,B)/FK4(C,D)NF005 Indoor Section
72 54.2 27.2 3.94 52.0 26.4 4.42 49.7 25.6 4.95 47.3 24.7 5.52 44.7 23.8 6.12
1400
1600
1800
CC5A/CD5AA 060 0.96 1.05
CC5A/CD5AC 048 0.93 1.04
CC5A/CD5AW 048 0.95 1.05
CK5A/CK5BA 048 0.95 1.05 CK5A/CK5BX 060 0.98 0.96
CK5A/CK5BN 048 0.93 1.03 CC5A/CD5AA 060 0.94 0.97
CK5A/CK5BT 048 0.95 1.05 CE3AA 060 0.95 0.96
CK5A/CK5BW 048 0.95 1.05 CK5A/CK5BA 060 0.95 0.96
CK5A/CK5BX 060 0.98 1.05 CK5A/CK5BT 060 0.95 0.96
F(A,B)4(A,B)N(F,B,C) 048 0.96 1.07 CK5A/CK5BX 060 0.98 0.97
FB4(A,B)NB 070 1.00 1.07 CC5A/CD5AA 060 0.94 0.96
FC4(B,C)N(F,B) 048 0.96 1.07 CC5A/CD5AW 060 0.98 0.98
FC4(B,C)NB 054 1.00 1.07 CK3BA 060 0.95 0.95
See notes on pg. 21.
67 50.1 34.7 3.91 48.0 33.8 4.39 45.8 33.0 4.90 43.5 32.0 5.46 41.2 31.1 6.05
63†† 46.7 33.8 3.88 44.8 32.9 4.35 42.7 32.0 4.86 40.6 31.1 5.41 38.3 30.1 6.00
62 46.1 41.9 3.88 44.2 41.0 4.35 42.3 40.0 4.86 40.2 38.9 5.41 38.0 37.8 5.99
57 44.7 44.7 3.87 43.2 43.2 4.34 41.5 41.5 4.85 39.6 39.6 5.39 37.9 37.9 5.99
72 55.1 28.5 4.00 52.8 27.7 4.49 50.4 26.9 5.01 47.9 26.0 5.58 45.3 25.1 6.19
67 51.0 36.9 3.97 48.8 36.0 4.45 46.6 35.1 4.97 44.2 34.2 5.53 41.7 33.3 6.12
63†† 47.6 35.8 3.94 45.6 35.0 4.41 43.4 34.1 4.93 41.2 33.1 5.48 38.9 32.1 6.07
62 47.1 44.8 3.94 45.2 43.8 4.41 43.2 42.7 4.92 41.2 41.2 5.48 39.3 39.3 6.07
57 46.4 46.4 3.93 44.7 44.7 4.41 43.0 43.0 4.92 41.1 41.1 5.47 39.2 39.2 6.07
72 55.7 29.7 4.06 53.4 28.9 4.55 51.0 28.0 5.07 48.4 27.1 5.64 45.7 26.2 6.25
67 51.6 39.0 4.03 49.4 38.1 4.51 47.1 37.2 5.03 44.7 36.3 5.59 42.2 35.3 6.19
63†† 48.3 37.8 4.00 46.2 36.9 4.48 44.0 36.0 4.99 41.7 35.0 5.54 39.3 34.0 6.13
62 48.1 47.4 4.00 46.2 46.1 4.47 44.3 44.3 4.99 42.4 42.4 5.55 40.4 40.4 6.15
57 47.8 47.8 4.00 46.0 46.0 4.47 44.3 44.3 4.99 42.2 42.2 5.54 40.3 40.3 6.15
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
060 0.98 1.05 CE3AA 060 0.95 0.97
CD5AA 048 0.95 1.05
CE3AA 048 0.96 1.05 CC5A/CD5AA 060 0.94 0.97
060 0.99 1.05 CE3AA 060 0.95 0.95
CF5AA 048 0.94 1.04 CK3BA 060 0.95 0.96
CK3BA 048 0.95 1.05 CK5A/CK5BA 060 0.95 0.95
060 0.96 1.05 CK5A/CK5BT 060 0.95 0.96
060 0.96 1.05
060 0.96 1.05 CC5A/CD5AW 060 0.98 0.99
060 0.96 1.05 CK3BA 060 0.95 0.96
060 0.99 1.09
060 0.99 1.09 CE3AA 060 0.95 0.95
070 1.00 1.07 CK5A/CK5BA 060 0.95 0.95
FG3AAA 048 0.94 1.05 CK5A/CK5BT 060 0.95 0.95
060 0.96 1.05 CK5A/CK5BX 060 0.98 0.96
Capacity Power Capacity Power
Cooling
Indoor
Section Size
40FK(A,B)/FK4(C,D)NB
40FK(A,B)/FK4(C,D)NF
COILS + 58CV(A,X)090-16 FURNACE
COILS + 58CV(A,X)110-22 FURNACE
COILS + 58CV(A,X)135-22 FURNACE
COILS + 58CV(A,X)155-22 FURNACE
006 1.00 0.98
005 1.00 1.00
Cooling
Total
System
kW** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
20
Page 21
Detailed cooling capacities* continued
EVAPORATOR
AIR
CFM EWB
85 95 105 115 125
Capacity
MBtuh†
Total
System
kW**
Capacity
CONDENSER ENTERING AIR TEMPERATURES ° F
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW**
Capacity
MBtuh†
Total
System
kW** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
38BYC060-33, 34 Outdoor Section With 40FK(A,B)/FK4(C,D)NF006 Indoor Section
72 66.7 33.9 5.29 63.7 32.8 5.86 60.5 31.7 6.48 57.2 30.5 7.16 53.6 29.3 7.88
1750
2000
2250
CC5A/CD5AA 060 0.93 1.02
CC5A/CD5AW 060 0.97 1.01
CK5A/CK5BA 060 0.93 1.02
CK5A/CK5BN 060 0.93 1.03
CK5A/CK5BX 060 0.97 1.03
F(A,B)4(A,B)N(F,B,C)
FB4(A,B)NB 070 0.98 1.04
FC4(B,C)N(F,B) 060 0.96 1.05
FC4(B,C)NB 070 0.98 1.04
40FK(A,B)/FK4(C,D)NF
CC5A/CD5AA 060 0.92 0.98 CK3BA 060 0.92 0.96
CK5A/CK5BA 060 0.92 0.96 CK5A/CK5BX 060 0.96 0.96
NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* Detailed cooling capacities are based on indoor and outdoor unit at same elevation per ARI standard 210/240-94. If additional tubing length and/or indoor
unit is located above outdoor unit, a slight variation in capacity may occur.
† Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
‡ Sensible capacities shown are based on 80 °F (27 °C) entering air at the indoor coil. For sensible capacities at other than 80 °F (27 °C), deduct 835 Btuh (245
kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80° F (27° C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per
degree above 80° F (27° C).
** System kW is total of indoor and outdoor unit kilowatts.
†† At TVA rating indoor condition (75° F edb/63° F ewb). All other indoor air temperatures are at 80° F edb.
EWB — Entering Wet-Bulb
67 61.8 43.6 5.22 59.0 42.4 5.78 56.0 41.3 6.40 52.9 40.1 7.07 49.7 38.8 7.78
63†† 57.9 42.5 5.16 55.3 41.4 5.72 52.5 40.1 6.33 49.5 38.9 6.99 46.5 37.6 7.69
62 57.2 53.0 5.15 54.6 51.7 5.71 52.0 50.4 6.32 49.2 48.8 6.98 46.5 46.5 7.70
57 55.9 55.9 5.13 53.8 53.8 5.70 51.6 51.6 6.32 49.2 49.2 6.98 46.6 46.6 7.70
72 67.8 35.6 5.39 64.7 34.5 5.96 61.5 33.4 6.59 58.1 32.2 7.26 54.4 31.0 7.99
67 62.6 46.3 5.31 59.7 45.2 5.87 56.6 44.0 6.49 53.4 42.7 7.15 50.0 41.4 7.87
63†† 59.0 45.2 5.26 56.3 44.1 5.82 53.4 42.8 6.44 50.4 41.6 7.09 47.3 40.2 7.80
62 58.2 56.6 5.24 55.7 55.1 5.80 53.1 53.1 6.42 50.5 50.5 7.09 47.9 47.9 7.81
57 57.8 57.8 5.24 55.5 55.5 5.80 53.2 53.2 6.42 50.6 50.6 7.10 47.9 47.9 7.82
72 68.3 37.0 5.47 65.5 36.1 6.06 62.2 35.0 6.68 58.7 33.8 7.36 54.6 32.4 8.06
67 63.5 49.1 5.40 60.6 48.0 5.97 57.4 46.7 6.59 53.8 45.3 7.24 50.4 44.0 7.95
63†† 59.6 47.6 5.34 57.1 46.6 5.92 54.2 45.4 6.53 51.1 44.1 7.19 47.5 42.5 7.88
62 59.6 59.5 5.34 57.2 57.2 5.91 54.7 54.7 6.53 51.7 51.7 7.20 48.9 48.9 7.92
57 59.3 59.3 5.34 57.0 57.0 5.90 54.5 54.5 6.53 51.8 51.8 7.20 49.0 49.0 7.92
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
CE3AA 060 0.97 1.02
CK3BA 060 0.93 1.02
060 0.96 1.05
FG3AAA 060 0.94 1.02
006 1.00 1.00
COILS + 58CV(A,X)110-22 FURNACE
CE3AA 060 0.96 0.98 CK5A/CK5BA 060 0.92 0.96
CK3BA 060 0.92 0.96 CK5A/CK5BT 060 0.92 0.96
Capacity Power Capacity Power
Cooling
Indoor
Section Size
CK5A/CK5BT 060 0.92 0.96
CK5A/CK5BX 060 0.96 0.97
COILS + 58CV(A,X)135-22 FURNACE
CC5A/CD5AA 060 0.92 0.98
CC5A/CD5AW 060 0.92 0.95
CE3AA 060 0.96 0.98
CK3BA 060 0.92 0.96
CK5A/CK5BA 060 0.92 0.96
CK5A/CK5BT 060 0.92 0.96
CK5A/CK5BX 060 0.96 0.97
COILS + 58CV(A,X)155-22 FURNACE
CC5A/CD5AA 060 0.92 0.97
CC5A/CD5AW 060 0.92 0.94
CE3AA 060 0.96 0.97
Cooling
21
Page 22
Heat pump heating performance
OUTDOOR COIL ENTERING AIR TEMPERATURES
–3 7 17 27 37 47 57 67
INDOOR
AIR
EDB CFM Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW†
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
38BYC018-33, 34 Outdoor Section With F(A,B)4(A,B)N(F,C)024 Indoor Section
550 7.82 7.20 1.19 9.40 8.63 1.24 11.2 10.2 1.29 13.1 11.6 1.34 15.3 13.9 1.42 17.8 17.8 1.52 20.5 20.5 1.64 23.6 23.6 1.82
65
650 7.97 7.33 1.21 9.55 8.78 1.25 11.3 10.3 1.29 13.2 11.8 1.34 15.5 14.1 1.41 18.0 18.0 1.51 20.8 20.8 1.63 23.9 23.9 1.80
550 8.10 7.45 1.23 9.69 8.91 1.27 11.5 10.5 1.31 13.4 11.9 1.35 15.7 14.3 1.42 18.2 18.2 1.52 20.9 20.9 1.64 24.1 24.1 1.82
650 7.73 7.11 1.25 9.29 8.54 1.30 11.0 10.1 1.36 12.9 11.5 1.42 15.1 13.7 1.49 17.6 17.6 1.59 20.3 20.3 1.72 23.3 23.3 1.90
70
750 7.87 7.24 1.27 9.44 8.68 1.31 11.2 10.2 1.36 13.1 11.6 1.41 15.3 13.9 1.49 17.8 17.8 1.58 20.5 20.5 1.71 23.6 23.6 1.88
550 8.01 7.37 1.29 9.58 8.81 1.33 11.4 10.4 1.37 13.3 11.8 1.42 15.5 14.1 1.49 18.0 18.0 1.59 20.7 20.7 1.71 23.9 23.9 1.89
550 7.61 7.00 1.31 9.19 8.45 1.37 10.9 9.95 1.42 12.8 11.3 1.49 14.9 13.6 1.57 17.4 17.4 1.67 20.0 20.0 1.81 23.1 23.1 1.98
75
650 7.76 7.14 1.33 9.34 8.59 1.38 11.1 10.1 1.43 13.0 11.5 1.49 15.2 13.8 1.56 17.6 17.6 1.66 20.3 20.3 1.79 23.4 23.4 1.96
750 7.90 7.27 1.35 9.48 8.71 1.39 11.2 10.2 1.44 13.1 11.6 1.49 15.3 13.9 1.56 17.8 17.8 1.66 20.5 20.5 1.79 23.6 23.6 1.96
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Capacity Power Capacity Power
CC5A/CD5AA 018 0.98 1.09 FF1DNA 018 0.98 1.02
024 0.99 1.04 024 1.00 1.00
CC5A/CD5AW 024 0.99 1.04 FG3AAA 024 0.99 1.05
CE3AA 024 0.99 1.03 FK4(C,D)NF 001 0.97 0.92
CF5AA 024 1.00 1.03
CK3BA 024 1.01 0.99
CK5A/CK5BA 018 0.99
024 1.01
CK5A/CK5BW 024 1.01
F(A,B)4(A,B)N(F,C)
024
1.00
018 0.98
FC4(B,C)NF 024 1.00
See notes on pg. 28.
Heating
1.03
0.99
0.99
1.00
1.05
1.00
Indoor
Section Size
40FK(A,B)/FK4(C,D)NF
CC5A/CD5AA 024 0.96 0.99
CC5A/CD5AW 024 0.96 0.99
CE3AA 024 0.96 0.98
CK3BA 024 0.96 0.92
CK5A/CK5BA 024 0.96 0.92
CK5A/CK5BW 024 0.96 0.92
°F
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Heating
002 0.97 0.90
COILS + 58CV(A,X)070-12 FURNACE
Capacity
MBtuh
Total
Power
22
Page 23
Heat pump heating performance continued
OUTDOOR COIL ENTERING AIR TEMPERATURES
–3 7 17 27 37 47 57 67
INDOOR
AIR
EDB CFM Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW†
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
38BYC024-35, 36 Outdoor Section With F(A,B)4(A,B)N(F,C)030 Indoor Section
1.93
18.5
20.4
1.88
15.5
17.5
1.84
13.5
14.8
1.80
11.4
12.4
1.75
9.09
9.88
65
70
75
725
825
925
725
825
925
725
825
925
10.1
10.2
9.56
9.76
9.93
9.25
9.44
9.61
9.26
9.41
8.80
8.98
9.14
8.51
8.68
8.84
1.77
1.79
1.80
7.83
1.85
1.86
1.88
1.91
12.5
12.7
12.1
12.3
12.5
11.9
12.1
12.2
11.5
11.7
11.1
11.3
11.5
10.9
11.1
11.2
1.81
1.83
1.86
1.88
1.90
1.93
1.94
1.96
15.0
15.2
14.6
14.8
15.0
14.4
14.6
14.8
13.7
13.8
13.3
13.5
13.6
13.2
13.3
13.5
1.84
1.86
1.91
1.92
1.93
1.99
2.00
2.01
17.6
17.8
17.3
17.4
17.6
17.1
17.2
17.4
15.7
15.8
15.3
15.5
15.6
15.2
15.3
15.5
1.88
1.89
1.96
1.96
1.97
2.04
2.04
2.05
20.6
20.8
20.2
20.4
20.6
19.9
20.1
20.3
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Capacity Power Capacity Power
Heating
Indoor
Section Size
CC5A/CD5AA 024 1.00 1.06 FF1DNA 024 1.00 1.02
030 1.00 1.07 030 1.00 1.00
CC5A/CD5AW 024 1.00 1.06 FF1DNE 024 1.00 1.02
030 1.00 1.07 030 1.00 1.00
CE3AA 024 1.00 1.04 FG3AAA 024 1.00 1.06
030 1.00 1.02 FK4(C,D)NF 001 0.98 0.95
CF5AA 024 1.00 1.06 40FK(A,B)/
CK3BA 024 1.00 0.99 003 0.97 0.92
FK4(C,D)NF
030 1.00 1.03
CK5A/CK5BA 024 1.00 0.99 CC5A/CD5AA 030 0.97 1.02
030 1.00 1.03 CC5A/CD5AW 030 0.97 1.02
CK5A/CK5BW 024 1.00 0.99 CE3AA 030 0.97 0.98
030 1.00 1.03 CK3BA 030 0.97 0.98
F(A,B)4(A,B)N(F,C) 024 1.00 1.01 CK5A/CK5BA 030 0.97 0.98
030 1.00 1.00 CK5A/CK5BW 030 0.97 0.98
FC4(B,C)NF 024 1.00 1.01 —— —
030 1.00 1.00
See notes on pg. 28.
18.8
18.9
18.3
18.5
18.7
18.1
18.3
18.5
1.92
1.92
2.01
2.00
2.00
2.10
2.09
2.09
°F
Capacity
MBtuh
23.6
23.8
24.1
23.4
23.6
23.8
23.1
23.4
23.6
23.6
23.8
24.1
23.4
23.6
23.8
23.1
23.4
23.6
Total
Power
1.99
1.97
1.96
2.08
2.06
2.05
2.18
2.15
2.14
Capacity
MBtuh
27.4
27.7
27.9
27.0
27.3
27.6
26.7
27.0
27.3
27.4
27.7
27.9
27.0
27.3
27.6
26.7
27.0
27.3
Total
Power
2.07
2.05
2.04
2.17
2.14
2.13
2.27
2.24
2.22
Heating
002 0.98 0.92
COILS + 58CV(A,X)070-12 FURNACE
Capacity
MBtuh
31.5
31.9
32.2
31.1
31.5
31.8
30.8
31.1
31.4
31.5
31.9
32.2
31.1
31.5
31.8
30.8
31.1
31.4
Total
Power
2.19
2.16
2.14
2.30
2.25
2.23
2.41
2.36
2.33
23
Page 24
Heat pump heating performance continued
OUTDOOR COIL ENTERING AIR TEMPERATURES
–3 7 17 27 37 47 57 67
INDOOR
AIR
EDB CFM Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW†
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
38BYC030-34, 35 Outdoor Section With F(A,B)4(A,B)N(F,C)036 Indoor Section
12.2 11.2 2.00 15.0 13.8 2.07 18.1 16.5 2.15 21.6 19.2 2.26 25.4 23.1 2.39 29.6 29.6 2.55 34.5 34.5 2.77 39.0 39.0 2.91
875
65
1000
12.4 11.4 2.02 15.2 14.0 2.09 18.4 16.8 2.16 21.9 19.4 2.26 25.7 23.4 2.38 30.0 30.0 2.54 34.6 34.6 2.69 38.4 38.4 2.83
1125
12.6 11.6 2.05 15.4 14.2 2.11 18.6 17.0 2.18 22.1 19.7 2.27 26.0 23.6 2.38 30.2 30.2 2.53 34.4 34.4 2.65 37.8 37.8 2.78
11.9 10.9 2.08 14.7 13.5 2.16 17.8 16.3 2.25 21.3 18.9 2.36 25.1 22.9 2.50 29.3 29.3 2.67 34.1 34.1 2.89 38.9 38.9 3.07
875
70
1000
12.1 11.1 2.11 15.0 13.8 2.18 18.1 16.5 2.25 21.6 19.2 2.36 25.4 23.1 2.48 29.6 29.6 2.65 34.4 34.4 2.83 38.6 38.6 2.97
1125
12.3 11.3 2.14 15.2 13.9 2.20 18.3 16.7 2.27 21.9 19.4 2.37 25.7 23.4 2.49 29.9 29.9 2.64 34.4 34.4 2.78 38.1 38.1 2.92
11.6 10.7 2.16 14.5 13.3 2.26 17.6 16.0 2.35 21.0 18.7 2.47 24.8 22.6 2.61 28.9 28.9 2.79 33.7 33.7 3.02 38.7 38.7 3.23
875
75
1000
11.8 10.9 2.19 14.7 13.5 2.27 17.8 16.2 2.35 21.3 18.9 2.46 25.1 22.9 2.59 29.3 29.3 2.76 34.1 34.1 2.98 38.6 38.6 3.12
1125
12.0 11.0 2.22 14.9 13.7 2.30 18.0 16.5 2.37 21.5 19.1 2.47 25.4 23.1 2.60 29.5 29.5 2.76 34.3 34.3 2.93 38.2 38.2 3.07
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Capacity Power Capacity Power
CC5A/CD5AA 030 0.98 1.04 FG3AAA 036 0.99 1.00
036 0.99 0.98 FK4(C,D)NF 001 0.98 0.94
CC5A/CD5AW 030 0.98 1.04
036 0.99 0.98 003 0.97 0.91
CE3AA 030 0.99 0.99
036 0.99 1.01 CC5A/CD5AA 036 0.98 0.96
CF5AA 036 0.99 0.99 CE3AA 036 0.98 0.98
CK3BA 030 0.98 1.01 CK3BA 036 0.98 0.93
036 0.99 0.97 CK5A/CK5BA 036 0.98 0.93
CK5A/CK5BA 036 0.99 0.98 CK5A/CK5BT 036 0.98 0.93
CK5A/CK5BT 036 0.99 0.97
CK5A/CK5BW 030 0.98 1.01 CC5A/CD5AA 036 0.98 0.95
036 0.99 0.97 CC5A/CD5AW 036 0.98 0.95
F(A,B)4(A,B)N(F,C) 030 0.99 0.98 CE3AA 036 0.98 0.97
036 1.00 1.00 CK3BA 036 0.98 0.92
FC4(B,C)NF 030 0.99 0.98 CK5A/CK5BA 036 0.98 0.92
036 1.00 1.00 CK5A/CK5BW 036 0.98 0.92
FF1DNA 030 0.99 0.99 —— —
See notes on pg. 28.
Heating
Indoor
Section Size
40FK(A,B)/FK4(C,D)NF
°F
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Heating
002 0.98 0.91
COILS + 58CV(A,X)070-12 FURNACE
COILS + 58CV(A,X)090-16 FURNACE
Capacity
MBtuh
Total
Power
24
Page 25
Heat pump heating performance continued
OUTDOOR COIL ENTERING AIR TEMPERATURES
–3 7 17 27 37 47 57 67
INDOOR
AIR
EDB CFM Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW†
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
38BYC036-34, 35 Outdoor Section With F(A,B)4(A,B)N(F,C)042 Indoor Section
15.0 13.8 2.27 18.4 16.9 2.36 22.1 20.2 2.46 26.2 23.2 2.58 30.7 27.9 2.73 35.8 35.8 2.92 41.2 41.2 3.09 45.6 45.6 3.26
1050
65
1200
15.3 14.0 2.30 18.7 17.2 2.38 22.4 20.5 2.47 26.5 23.5 2.59 31.1 28.3 2.73 36.2 36.2 2.91 40.8 40.8 3.03 43.0 43.0 3.09
1350
15.5 14.3 2.34 18.9 17.4 2.42 22.7 20.7 2.50 26.8 23.8 2.61 31.4 28.6 2.75 36.5 36.5 2.88 40.2 40.2 2.99 39.8 39.8 2.96
14.7 13.5 2.35 18.1 16.6 2.45 21.8 19.9 2.56 25.9 23.0 2.69 30.3 27.6 2.85 35.4 35.4 3.05 41.0 41.0 3.25 45.6 45.6 3.41
1050
70
1200
14.9 13.7 2.39 18.4 16.9 2.48 22.1 20.2 2.57 26.2 23.3 2.70 30.7 27.9 2.84 35.8 35.8 3.03 40.9 40.9 3.17 44.8 44.8 3.32
1350
15.2 14.0 2.43 18.7 17.1 2.51 22.4 20.4 2.60 26.5 23.5 2.72 31.0 28.2 2.86 36.1 36.1 3.03 40.5 40.5 3.14 41.6 41.6 3.16
14.3 13.2 2.44 17.8 16.3 2.55 21.5 19.6 2.67 25.6 22.7 2.81 30.0 27.3 2.97 34.9 34.9 3.18 40.6 40.6 3.42 45.6 45.6 3.58
1050
75
1200
14.6 13.4 2.48 18.1 16.6 2.58 21.8 19.9 2.68 25.9 23.0 2.81 30.4 27.6 2.97 35.4 35.4 3.16 40.8 40.8 3.32 45.1 45.1 3.48
1350
14.8 13.7 2.52 18.4 16.9 2.61 22.1 20.2 2.71 26.2 23.3 2.83 30.7 27.9 2.97 35.7 35.7 3.16 40.6 40.6 3.28 43.6 43.6 3.39
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Capacity Power Capacity Power
CC5A/CD5AA 036 1.00 1.00 COILS + 58CV(A,X)090-16 FURNACE
042 1.00 1.00 CC5A/CD5AA 042 0.98 0.97
CC5A/CD5AW 036 0.99 0.96 CE3AA 042 0.98 0.96
042 1.00 1.01 CK3BA 042 0.98 0.95
CE3AA 036 0.99 1.02 CK5A/CK5BA 042 0.98 0.95
042 1.01 0.99 CK5A/CK5BE 042 0.98 0.94
CF5AA 036 1.00 1.01 CK5A/CK5BT 042 0.98 0.95
CK3BA 036 1.00 0.99
042 1.00 0.99 CC5A/CD5AA 042 0.98 0.97
CK5A/CK5BA 036 1.00 0.99 CC5A/CD5AW 042 0.98 0.98
042 1.00 0.99 CE3AA 042 0.98 0.95
CK5A/CK5BE 042 1.00 0.98 CK3BA 042 0.98 0.94
CK5A/CK5BT 036 1.00 0.99 CK5A/CK5BA 042 0.98 0.94
042 1.00 0.99 CK5A/CK5BT 042 0.98 0.94
CK5A/CK5BW 036 1.00 0.99
F(A,B)4(A,B)N(F,B,C)
036 1.01 1.02 CC5A/CD5AA 042 0.98 0.97
042 1.00 1.00 CC5A/CD5AW 042 0.98 0.98
FC4(B,C)N(F,B) 036 1.01 1.02 CE3AA 042 0.98 0.95
042 1.00 1.00 CK3BA 042 0.98 0.95
FG3AAA 036 1.00 1.01 CK5A/CK5BA 042 0.98 0.95
FK4(C,D)NF 001 0.98 0.97 CK5A/CK5BT 042 0.98 0.95
40FK(A,B)/FK4(C,D)NF
002 0.98 0.95 COILS + 58CV(A,X)155-22 FURNACE
003 0.98 0.93 CC5A/CD5AA 042 0.98 0.96
005 0.93 0.85 CC5A/CD5AW 042 0.98 0.98
COILS + 58CV(A,X)070-12 FURNACE CE3AA 042 0.98 0.95
CE3AA 042 0.98 0.97 CK3BA 042 0.98 0.94
CK5A/CK5BE 042 0.98 0.95 CK5A/CK5BA 042 0.98 0.94
—— — CK5A/CK5BT 042 0.98 0.94
See notes on pg. 28.
Heating
Indoor
Section Size
°F
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Heating
COILS + 58CV(A,X)110-22 FURNACE
COILS + 58CV(A,X)135-22 FURNACE
Capacity
MBtuh
Power
Total
25
Page 26
Heat pump heating performance continued
OUTDOOR COIL ENTERING AIR TEMPERATURES
–3 7 17 27 37 47 57 67
INDOOR
AIR
EDB CFM Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW†
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
38BYC042-33, 34 Outdoor Section With F(A,B)4(A,B)N(F,C)048 Indoor Section
3.28
33.6
36.9
3.13
28.4
31.9
3.00
25.1
27.5
2.88
21.6
23.5
2.77
18.1
19.7
1275
1475
1675
1275
1475
1675
1275
1475
1675
20.0
20.4
19.2
19.6
20.0
18.7
19.1
19.5
65
70
75
18.4
18.7
17.7
18.1
18.4
17.2
17.6
18.0
2.82
2.88
2.87
2.92
2.98
2.97
3.03
3.09
23.8
24.1
23.2
23.5
23.9
22.9
23.2
23.6
21.9
22.2
21.3
21.6
21.9
21.0
21.4
21.7
2.92
2.98
3.00
3.04
3.10
3.12
3.17
3.22
27.9
28.3
27.2
27.6
28.0
26.9
27.3
27.6
25.4
25.8
24.8
25.2
25.5
24.5
24.9
25.2
3.03
3.07
3.13
3.16
3.20
3.26
3.29
3.33
32.4
32.7
31.6
32.0
32.4
31.3
31.7
32.1
28.7
29.1
28.1
28.4
28.8
27.8
28.1
28.5
3.15
3.18
3.27
3.28
3.32
3.41
3.42
3.46
37.4
37.8
36.5
37.0
37.4
36.1
36.6
37.0
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Capacity Power Capacity Power
Heating
Indoor
Section Size
CC5A/CD5AA 042 0.98 1.02 CK5A/CK5BT 048 0.98 0.97
CC5A/CD5AC 048 0.98 1.05
CC5A/CD5AW 042 1.01 1.07 CC5A/CD5AC 048 0.98 1.04
048 0.99 1.02 CC5A/CD5AW 048 0.98 0.98
CD5AA 048 0.99 1.02 CD5AA 048 0.98 0.98
CE3AA 042 0.99 1.02 CE3AA 048 0.98 0.97
048 0.99 1.01 CK3BA 048 0.98 0.96
CF5AA 048 0.98 1.01 CK5A/CK5BA 048 0.98 0.96
CK3BA 042 0.98 1.01 CK5A/CK5BT 048 0.98 0.96
048 0.99 1.01 CK5A/CK5BW 048 0.98 0.96
CK5A/CK5BA 042 0.98 1.01
048 0.99 0.99 CC5A/CD5AC 048 0.98 1.04
CK5A/CK5BN 042 0.95 0.98 CC5A/CD5AW 048 0.98 0.98
048 0.95 0.97 CD5AA 048 0.98 0.98
CK5A/CK5BW 048 0.99 1.01 CE3AA 048 0.98 0.97
F(A,B)4(A,B)N(F,B) 042 0.99 1.04 CK3BA 048 0.98 0.96
048 1.00 1.00 CK5A/CK5BA 048 0.98 0.96
FC4(B,C)N(F,B) 042 0.99 1.04 CK5A/CK5BT 048 0.98 0.96
048 1.00 1.01 CK5A/CK5BW 048 0.98 0.96
FG3AA 048 0.99 0.99
40FK(A,B)/FK4(C,D)NF
003 0.97 0.99 CC5A/CD5AC 048 0.98 1.03
005 0.98 0.92 CC5A/CD5AW 048 0.98 0.98
006 0.98 0.88 CD5AA 048 0.98 0.98
COILS + 58CV(A,X)090-16 FURNACE CE3AA 048 0.98 0.97
CC5A/CD5AC 048 0.98 1.04 CK3BA 048 0.98 0.96
CD5AA 048 0.98 0.99 CK5A/CK5BA 048 0.98 0.96
CE3AA 048 0.98 0.98 CK5A/CK5BT 048 0.98 0.96
CK3BA 048 0.98 0.97 CK5A/CK5BW 048 0.98 0.96
CK5A/CK5BA 048 0.98 0.96 —— —
See notes on pg. 28.
34.0
34.4
33.2
33.7
34.0
32.9
33.3
33.7
3.29
3.31
3.42
3.43
3.45
3.58
3.58
3.60
°F
Capacity
MBtuh
43.0
43.5
44.0
42.4
43.0
43.5
41.9
42.5
43.0
43.0
43.5
44.0
42.4
43.0
43.5
41.9
42.5
43.0
Total
Power
3.48
3.47
3.49
3.63
3.62
3.64
3.79
3.78
3.79
Capacity
MBtuh
50.4
51.1
51.6
49.7
50.4
51.0
49.0
49.7
50.3
50.4
51.1
51.6
49.7
50.4
51.0
49.0
49.7
50.3
Total
Power
3.75
3.73
3.75
3.91
3.89
3.89
4.08
4.05
4.05
Heating
COILS + 58CV(A,X)110-22 FURNACE
COILS + 58CV(A,X)135-22 FURNACE
COILS + 58CV(A,X)155-22 FURNACE
Capacity
MBtuh
58.0
58.8
59.2
57.3
58.1
58.7
56.5
57.3
57.9
58.0
58.8
59.2
57.3
58.1
58.7
56.5
57.3
57.9
Total
Power
4.08
4.05
4.01
4.25
4.21
4.22
4.42
4.38
4.38
26
Page 27
Heat pump heating performance continued
OUTDOOR COIL ENTERING AIR TEMPERATURES
–3 7 17 27 37 47 57 67
INDOOR
AIR
EDB CFM Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW†
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
38BYC048-33, 34 Outdoor Section With 40FK(A,B)/FK4(C,D)NF005 Indoor Section
1400 22.2 20.4 2.99 26.7 24.6 3.13 31.4 28.6 3.25 36.3 32.2 3.38 42.1 38.3 3.54 48.5 48.5 3.73 56.1 56.1 3.97 64.6 64.6 4.29
65
1600 22.5 20.7 3.00 27.0 24.8 3.13 31.7 28.9 3.23 36.6 32.5 3.35 42.5 38.6 3.48 49.1 49.1 3.66 56.7 56.7 3.88 65.4 65.4 4.18
1800 22.7 20.9 3.02 27.2 25.0 3.13 32.0 29.1 3.23 36.9 32.8 3.33 42.8 39.0 3.46 49.5 49.5 3.62 57.2 57.2 3.83 66.0 66.0 4.12
1400 21.7 19.9 3.13 26.4 24.3 3.28 31.1 28.4 3.42 35.9 31.9 3.56 41.6 37.9 3.73 48.0 48.0 3.93 55.4 55.4 4.19 63.7 63.7 4.51
70
1600 22.0 20.2 3.14 26.7 24.5 3.28 31.4 28.6 3.40 36.3 32.2 3.53 42.0 38.2 3.67 48.5 48.5 3.85 56.0 56.0 4.09 64.5 64.5 4.40
1800 22.3 20.5 3.16 27.0 24.8 3.29 31.7 28.9 3.40 36.6 32.5 3.51 42.4 38.6 3.65 48.9 48.9 3.81 56.5 56.5 4.03 65.1 65.1 4.33
1400 21.1 19.4 3.26 26.0 23.9 3.43 30.8 28.1 3.60 35.6 31.6 3.75 41.2 37.5 3.93 47.5 47.5 4.14 54.7 54.7 4.41 62.9 62.9 4.75
75
1600 21.4 19.7 3.28 26.3 24.2 3.43 31.1 28.4 3.58 35.9 31.9 3.71 41.6 37.8 3.87 48.0 48.0 4.06 55.3 55.3 4.31 63.7 63.7 4.62
1800 21.7 20.0 3.30 26.6 24.4 3.44 31.4 28.6 3.57 36.2 32.1 3.69 41.9 38.1 3.84 48.4 48.4 4.01 55.8 55.8 4.24 64.3 64.3 4.55
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Capacity Power Capacity Power
CC5A/CD5AA 060 1.00 1.10
CC5A/CD5AC 048 1.00 1.15
CC5A/CD5AW 048 1.00 1.09
060 1.00 1.05 CE3AA 060 1.00 1.05
CD5AA 048 1.00 1.09
CE3AA 048 1.00 1.07 CC5A/CD5AA 060 1.00 1.10
060 1.00 1.04 CE3AA 060 1.00 1.04
CF5AA 048 1.00 1.11 CK3BA 060 1.00 1.00
CK3BA 048 1.00 1.07 CK5A/CK5BA 060 1.00 1.00
060 1.00 1.02 CK5A/CK5BT 060 1.00 1.00
CK5A/CK5BA 048 1.00 1.07 CK5A/CK5BX 060 1.00 0.99
060 1.00 1.02
CK5A/CK5BN 048 1.00 1.09 CC5A/CD5AA 060 1.00 1.10
060 1.00 1.01 CC5A/CD5AW 060 1.00 1.04
CK5A/CK5BT 048 1.00 1.07 CE3AA 060 1.00 1.04
060 1.00 1.02 CK3BA 060 1.00 1.00
CK5A/CK5BW 048 1.00 1.07 CK5A/CK5BA 060 1.00 1.00
CK5A/CK5BX 060 1.00 1.01 CK5A/CK5BT 060 1.00 1.00
F(A,B)4(A,B)N(F,B,C)
048 1.00 1.05 CK5A/CK5BX 060 1.00 0.99
060 1.00 1.03
FB4(A,B)NB 070 1.00 0.99 CC5A/CD5AA 060 1.00 1.10
FC4(B,C)NB 054 1.00 0.98 CC5A/CD5AW 060 1.00 1.04
070 1.00 0.99 CE3AA 060 1.00 1.03
FC4(B,C)N(F,B) 048 1.00 1.05 CK3BA 060 1.00 0.99
060 1.00 1.03 CK5A/CK5BA 060 1.00 0.99
FG3AAA 048 1.00 1.07 CK5A/CK5BT 060 1.00 0.99
060 1.00 1.06 CK5A/CK5BX 060 1.00 0.99
See notes on pg. 28.
Heating
Indoor
Section Size
40FK(A,B)/FK4(C,D)NB
40FK(A,B)/FK4(C,D)NF
°F
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Heating
006 1.00 0.96
005 1.00 1.00
COILS + 58CV(A,X)090-16 FURNACE
COILS + 58CV(A,X)110-22 FURNACE
COILS + 58CV(A,X)135-22 FURNACE
COILS + 58CV(A,X)155-22 FURNACE
Capacity
MBtuh
Power
Total
27
Page 28
Heat pump heating performance continued
OUTDOOR COIL ENTERING AIR TEMPERATURES
–3 7 17 27 37 47 57 67
INDOOR
AIR
EDB CFM Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW† Total Integ* kW†
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
38BYC060-33, 34 Outdoor Section With 40FK(A,B)/FK4(C,D)NF006 Indoor Section
1750 28.2 26.0 4.20 33.5 30.8 4.37 39.1 35.7 4.55 45.3 40.2 4.75 52.5 47.8 5.00 60.7 60.7 5.30 70.1 70.1 5.69 79.6 79.6 6.03
65
2000 28.6 26.3 4.22 33.8 31.1 4.38 39.5 36.0 4.54 45.7 40.6 4.72 53.0 48.3 4.95 61.3 61.3 5.23 70.7 70.7 5.56 79.4 79.4 5.87
2250 28.9 26.6 4.26 34.1 31.3 4.40 39.9 36.3 4.55 46.1 41.0 4.72 53.5 48.7 4.93 61.8 61.8 5.20 70.8 70.8 5.48 78.5 78.5 5.75
1750 27.8 25.5 4.38 33.2 30.5 4.59 38.8 35.4 4.78 44.9 39.8 4.99 52.0 47.3 5.25 60.0 60.0 5.57 69.3 69.3 5.97 79.7 79.7 6.41
70
2000 28.1 25.9 4.41 33.5 30.8 4.59 39.2 35.7 4.77 45.3 40.2 4.96 52.5 47.8 5.20 60.6 60.6 5.49 70.1 70.1 5.87 79.2 79.2 6.18
2250 28.5 26.2 4.45 33.8 31.1 4.61 39.5 36.0 4.78 45.7 40.6 4.95 52.9 48.2 5.18 61.1 61.1 5.45 70.4 70.4 5.77 78.5 78.5 6.05
1750 27.2 25.0 4.57 32.9 30.2 4.80 38.5 35.1 5.02 44.4 39.5 5.24 51.4 46.8 5.52 59.3 59.3 5.84 68.5 68.5 6.26 79.0 79.0 6.80
75
2000 27.6 25.4 4.59 33.2 30.5 4.81 38.8 35.4 5.00 44.9 39.8 5.21 52.0 47.3 5.45 60.0 60.0 5.76 69.3 69.3 6.15 79.4 79.4 6.55
2250 28.0 25.7 4.63 33.5 30.8 4.83 39.2 35.7 5.01 45.2 40.2 5.20 52.4 47.7 5.43 60.4 60.4 5.71 69.9 69.9 6.09 78.8 78.8 6.39
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Capacity Power Capacity Power
CC5A/CD5AA 060 1.00 1.16 CK5A/CK5BT 060 1.00 1.04
CC5A/CD5AW 060 1.00 1.10 CK5A/CK5BX 060 1.00 1.03
CE3AA 060 1.00 1.09
CK3BA 060 1.00 1.11 CC5A/CD5AA 060 1.00 1.15
CK5A/CK5BA 060 1.00 1.11 CC5A/CD5AW 060 1.00 1.08
CK5A/CK5BN 060 1.00 1.07 CE3AA 060 1.00 1.08
CK5A/CK5BX 060 1.00 1.07 CK3BA 060 1.00 1.04
F(A,B)4(A,B)N(F,B,C)
060 1.00 1.08 CK5A/CK5BA 060 1.00 1.04
FB4(A,B)NB 070 1.00 1.03 CK5A/CK5BT 060 1.00 1.04
FC4(B,C)N(F,B) 060 1.00 1.08 CK5A/CK5BX 060 1.00 1.03
FC4(B,C)NB 070 1.00 1.03
FG3AAA 060 1.00 1.12 CC5A/CD5AA 060 1.00 1.14
40FK(A,B)/FK4(C,D)NB
006 1.00 1.00 CC5A/CD5AW 060 1.00 1.08
COILS + 58CV(A,X)110-22 FURNACE CE3AA 060 1.00 1.07
CC5A/CD5AA 060 1.00 1.15 CK3BA 060 1.00 1.03
CE3AA 060 1.00 1.07 CK5A/CK5BA 060 1.00 1.03
CK3BA 060 1.00 1.04 CK5A/CK5BT0 06 1.00 1.03
CK5A/CK5BA 060 1.00 1.04 CK5A/CK5BX 060 1.00 1.03
NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* The Btuh heating capacity values shown are net integrated values from which the defrost effect has been subtracted. The Btuh heating from supplement
heaters should be added to those values to obtain total system capacity.
† The kW values include the compressor, outdoor fan motor, and indoor blower motor. The kW from supplement heaters should be added to these values to
obtain total system kilowatts.
EDB — Entering Dry Bulb
Heating
Indoor
Section Size
°F
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Heating
COILS + 58CV(A,X)135-22 FURNACE
COILS + 58CV(A,X)155-22 FURNACE
Capacity
MBtuh
Total
Power
28
Page 29
System Design
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.
2. Minimum outdoor operating air temperature for cooling mode without low-ambient operation accessory is 55° F (12.8° C).
3. Maximum outdoor operating air temperature for cooling mode is 125° F (51.7° C).
4. Minimum outdoor operating air temperature for heating mode is –30° F (–34.4° C).
5. Maximum outdoor operating air temperature for heating mode is 66° F (18.9° C).
6. For reliable operation, unit should be level in all horizontal planes.
7. Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above = 50 ft, indoor coil below = 150 ft. (See items 8 and 9 following.)
8. For interconnecting refrigerant tube lengths greater than 50 ft, consult Application Guideline and Service Manual—Air Conditioners and Heat Pumps Using
R-22 Refrigerant.
9. For buried refrigerant tubing lengths greater than 36 in., consult your local distributor.
10. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
11. Mismatches of indoor coil capacity more than 1 size larger than outdoor unit capacity may result in inadequate indoor comfort.
29
Page 30
30
Page 31
31
Page 32
Guide specifications
GENERAL
System Description
Outdoor-mounted, air-cooled, split-system heat pump unit
suitable for ground or rooftop installation. Unit consists of a
hermetic compressor, an air-cooled coil, propeller-type
condenser fan, and a control box. Unit will discharge supply
air upward as shown on contract drawings. Unit will be used
in a refrigeration circuit to match up to a packaged fan coil or
coil unit.
Quality Assurance
Unit will be rated in accordance with the latest edition of
ARI Standard 240.
Unit will be certified for capacity and efficiency, and listed
in the latest ARI directory.
Unit construction will comply with latest edition of ANSI/
ASHRAE and with NEC.
Unit will be constructed in accordance with UL standards
and will carry the UL label of approval. Unit will have C-UL
approval.
Unit cabinet will be capable of withstanding Federal Test
Method Standard No. 141 (Method 6061) 500-hr salt spray
test.
Air-cooled condenser coils will be leak tested at 217 psig
and pressure tested at 450 psig.
Delivery, Storage, and Handling
Unit will be shipped as single package only and is stored
and handled per unit manufacturer’s recommendations.
Warranty (for inclusion by specifying engineer)
U.S. and Canada only.
PRODUCTS
Equipment
Factory assembled, single piece, air-cooled heat pump unit.
Contained within the unit enclosure will be all factory wiring,
piping, controls, compressor, refrigerant charge (Puron®), and
special features required prior to field start-up.
Unit Cabinet
Unit cabinet will be constructed of galvanized steel,
bonderized, and coated with a powder coat paint.
Fans
Condenser fan will be direct-drive propeller type,
discharging air upward.
Air-Cooled, Split-System
Heat Pump
38BYC
1-1/2 to 5 Tons Nominal
Condenser fan motors will be totally enclosed, 1-phase type
with class B insulation and permanently lubricated bearings.
Shafts will be corrosion resistant.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with steel wire
safety guards.
Compressor
Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration isolators.
Condenser Coil
Condenser coil will be air cooled.
Coil will be constructed of aluminum fins mechanically
bonded to copper tubes which are then cleaned, dehydrated,
and sealed.
Refrigeration Components
Refrigeration circuit components will include liquid tube
shutoff valve with sweat connections, suction tube shutoff
valves with sweat connections, system charge of Puron®
refrigerant, POE compressor oil, accumulator, and reversing
valve.
Operating Characteristics
The capacity of the unit will meet or exceed Btuh at a
suction temperature of °F. The power consumption at
full load will not exceed kW.
Combination of the unit and the evaporator or fan coil unit
will have a total net cooling capacity of Btuh or greater
at conditions of CFM entering air temperature at the
evaporator at °F wet bulb and °F dry bulb, and air
entering the unit at °F.
The system will have an SEER of Btuh/watt or greater
at DOE conditions.
Electrical Requirements
Nominal unit electrical characteristics will be v,
phase, 60 hz. The unit will be capable of satisfactory
operation within voltage limits of v to v.
Unit electrical power will be single point connection.
Control circuit will be 24v.
Special Features
Refer to section of this literature identifying accessories and
descriptions for specific features and available enhancements.
Carrier Corporation • Indianapolis, IN 46231 06-03
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Page 32 Catalog No. 523-80101 Printed in U.S.A. PC 101 Form 38BYC-6PD
Tab 5a 5a
Replaces: 38BYC-5PD