Visit www.carrier.com
38BRC, 38CKC, 38CKG
38CKS, 38CKW, 38CMC
Split System Air Conditioners
Installation and Start-Up Instructions
NOTE: Read the entire instruction manual before starting the
installation.
This symbol → indicates a change since the last issue.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory-authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature
and attached to the unit. Consult local building codes and National
Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety-alert symbol
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
Before installing or servicing system, always turn off main
power to system. There may be more than 1 disconnect
switch. Turn off accessory heater power if applicable. Electrical shock can cause personal injury or death.
INSTALLATION RECOMMENDATIONS
NOTE: In some cases noise in the living area has been traced to
gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, and so forth,
where unit-operation sound may disturb customer.
2. Ensure that vapor- and liquid-tubediametersare appropriate to
capacity of unit.
3. Run refrigerant tubes as directly as possible by avoiding
unnecessary turns and bends.
4. Leave some slack between structure and unit to absorb
vibration.
5. When passing refrigerant tubes through the wall, seal opening
with RTV or other pliable silicon-based caulk. (See Fig. 1.)
6. Avoid direct tubing contact with water pipes, duct work, floor
joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with a
rigid wire or strap that comes in direct contact with tubing.
(See Fig. 1.)
8. Ensure that tubing insulation is pliable and completely surrounds vapor tube.
9. When necessary, use hanger straps which are 1 in. wide and
conform to shape of tubing insulation. (See Fig. 1.)
10. Isolate hanger straps from insulation by using metal sleeves
bent to conform to shape of insulation.
DO NOT BURY MORE THAN 36 IN. OF REFRIGERANT
TUBING IN GROUND. If any section of tubing is buried,
there must be a 6-in. vertical rise to valve connections on
outdoor unit. If more than recommended length is buried,
refrigerant may migrate to cooler buried section during
.
extended periods of unit shutdown, causing refrigerant slugging and possible compressor damage at start-up.
INSTALLATION
Step 1—Check Equipment and Job Site
UNPACK UNIT
Move to final location. Remove carton taking care not to damage
unit.
INSPECT EQUIPMENT
File claim with shipping company prior to installation if shipment
is damaged or incomplete. Locate unit rating plate on unit control
box access panel. It contains information needed to properly install
unit. Check rating plate to be sure unit matches job specifications.
Step 2—Install on a Solid, Level Mounting Pad
If conditions or local codes require the unit be attached to pad, tie
down bolts should be used and fastened through knockouts
provided in unit base pan. Refer to unit mounting pattern in Fig. 2
to determine base pan size and knockout hole location.
Arrange supporting members to adequately support unit and
minimize transmission of vibration to building. Consult local
codes governing rooftop applications.
Step 3—Clearance Requirements
When installing, allow sufficient space for airflow clearance,
wiring, refrigerant piping, and service. Allow 30-in. clearance to
service end of unit and 48 in. above unit. For proper airflow, a 6-in.
clearance on 1 side of unit and 12 in. on all remaining sides must
be maintained. Maintain a distance of 24 in. between units.
Position so water, snow, or ice from roof or eaves cannot fall
directly on unit.
On rooftop applications, locate unit at least 6 in. above roof
surface. Place unit above a load-bearing wall and isolate unit and
tubing set from structure.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 3a 2a
PC 101 Catalog No. 533-80015 Printed in U.S.A. Form 38CKC-4SI Pg 1 6-01 Replaces: 38CKC-3SI
Avoid contact between tubing and structureNOTE:
OUTDOOR WALL INDOOR WALL
CAULK
INSULATION
THROUGH THE WALL
HANGER STRAP
(AROUND VAPOR
TUBE ONLY)
1″ MIN.
SUSPENSION
Fig. 1—Connecting Tubing Installation
C
3
⁄8″D. (9.53) TIEDOWN
A
B
KNOCKOUTS (2) PLACES
A94199
Dimensions (In.)
UNIT BASE
DIMENSIONS
18X18 3 15 10-3/16
22-1/2 X 22-1/2 3-11/16 18-1/8 14-3/8
30X30 6-1/2 23-1/2 20
TIEDOWN KNOCKOUT LOCATIONS
ABC
Fig. 2—Mounting Unit to Pad
Step 4—Operating Ambients (Outdoor Temperatures)
The minimum outdoor operating ambient in cooling mode is 55°F,
and the maximum outdoor operating ambient in cooling mode is
125°F.
LIQUID TUBE
VAPOR TUBE
JOIST
INSULATION
VAPOR TUBE
LIQUID TUBE
A94028
Step 5—Replace Indoor AccuRater® Piston, If Required
Check indoor coil piston to see if it matches the required piston
shown on outdoor unit rating plate. If it does not match, replace
indoor coil piston with piston shipped with outdoor unit. The
piston shipped with outdoor unit is correct for any approved indoor
coil combination.
Step 6—Make Refrigerant Tubing Connections
Outdoor units may be connected to indoor sections using accessory
tubing package or field-supplied refrigerant grade tubing of correct
size and condition. For tubing requirements beyond 50 ft, consult
Application Guideline and Service Manual—Air Conditioners and
Heat Pumps Using R-22 Refrigerant. Connect tubing to fittings on
outdoor unit vapor and liquid service lines. (See Table 1.)
If refrigerant tubes or indoor coil is exposed to atmospheric
conditions for longer than 5 minutes, it must be evacuated to 500
microns to eliminate contamination and moisture in system.
OUTDOOR UNIT CONNECTED TO FACTORY-APPROVED
INDOOR UNIT
Outdoor unit contains correct system refrigerant charge for operation with indoor unit of same size when connected by 15 ft of
field-supplied or factory accessory tubing. Check refrigerant
charge for maximum efficiency. (See Procedure 11–Check
Charge.)
To avoid valve damage while brazing, service valves must be
wrapped with a heat-sinking material such as a wet cloth.
SWEAT CONNECTION
Use refrigerant grade tubing. Service valves are closed from
factory and ready for brazing. After wrapping service valve with a
2
wet cloth, braze sweat connections using industry accepted methods and materials. Consult local code requirements. Refrigerant
tubing and indoor coil are now ready for leak testing. This check
should include all field and factory joints.
Table 1—Refrigerant Connections
and Recommended
Liquid and Vapor Tube Diameters (In.)
LIQUID VAPOR
UNIT SIZE
018, 024 3/8 3/8 3/8 5/8
030, 036 3/8 3/8 3/8 3/4
042-048 3/8 3/8 7/8 7/8
060 3/8 3/8 7/8 1-1/8
Note: Tube diameters are for lengths up to 50 ft. For tubing lengths greater
than 50 ft, consult your local distributor or Long-Line Application Guideline.
DISCONNECT
PER N.E.C. AND/OR
LOCAL CODES
FIELD POWER
FIELD GROUND
WIRING
WIRING
Connect
Diameter
Tube
Diameter
Connect
Diameter
GROUND
LUG
Tube
Diameter
CONTACTOR
A88174
Fig. 3—Line Power Connections
Step 7—Make Electrical Connections
According to NEC, ANSI/NFPA 70, and local codes, cabinet
must have an uninterrupted or unbroken ground to minimize
personal injury if an electrical fault should occur. The ground
may consist of electrical wire or metal conduit when installed
in accordance with existing electrical codes. Failure to follow
this warning can result in an electric shock, fire, or death.
CONNECT GROUND AND POWER WIRES
Connect ground wire to ground connection in control box for
safety. Connect power wiring to contactor as shown in Fig. 3.
CONNECT CONTROL WIRING
Route 24v control wires through control wiring grommet and
connect leads to control wiring. (See Fig. 5.) Use No. 18 AWG
color-coded, insulated (35°C minimum) wire. If thermostat is
located more than 100 ft from unit, as measured along the control
voltage wires, use No. 16 AWG color-coded wire to avoid
excessive voltage drop.
Use furnace transformer, fan coil transformer, or accessory transformer for control power, 24v/40va minimum.
NOTE: Use of available 24v accessories may exceed the minimum 40va power requirement. Determine total transformer loading and increase the transformer capacity or split the load with an
accessory transformer as required.
Step 8—Compressor Crankcase Heater
A crankcase heater is required if refrigerant tubing is longer than
50 ft.
Step 9—Install Electrical Accessories
Refer to the individual instructions packaged with kits or accessories when installing.
Step 10—Start-Up
To avoid personal injury or death, do not supply power to unit
with compressor terminal box cover removed.
Be sure field wiring complies with local and national fire, safety,
and electrical codes, and voltage to system is within limits shown
on unit rating plate. Contact local power company for correction of
improper voltage. See unit rating plate for recommended circuit
protection device.
NOTE: Operation of unit on improper line voltage constitutes
abuse and could affect unit reliability. See unit rating plate. Do not
install unit in system where voltage or phase imbalance (3 phase)
may fluctuate above or below permissible limits.
NOTE: Use copper wire only between disconnect switch and
unit.
NOTE: Install branch circuit disconnect of adequate size per
NEC to handle unit starting current. Locate disconnect within sight
from and readily accessible from unit, per Section 440-14 of NEC.
ROUTE GROUND AND POWER WIRES
Remove access panel to gain access to unit wiring. Extend wires
from disconnect through power wiring hole provided and into unit
control box.
• 3-phase scroll compressors are rotation sensitive.
• A flashing LED on phase monitor indicates reverse rotation.
(See Fig. 4 and Table 2.)
• This will not allow contactor to be energized.
• Disconnect power to unit and interchange 2 field wiring
leads on unit contactor.
1. When equipped with a crankcase heater, energize heater a
minimum of 24 hr before starting unit. To energize heater
only, set thermostat to OFF mode and close electrical disconnect to outdoor unit.
Service valve gage ports are equipped with Schrader valves.
To prevent personal injury, wear safety glasses and gloves
when handling refrigerant.
2. Fully back seat (open) liquid and vapor service valves.
3. Unit is shipped with valve stem(s) front seated (closed), and
caps installed. Replace stem caps after system is opened to
refrigerant flow. Replace caps finger-tight and tighten additional 1/6 turn with wrench.
4. Close electrical disconnects to energize system.
5. Set room thermostat at desired temperature. Be sure set point
is below indoor ambient temperature.
6. Set room thermostat at COOL and fan ON or AUTO modes,
as desired. Operate unit for 15 minutes. Check system
refrigerant charge. See Check Charge section.
3