Carrier 40QNB018, 40QNE018, 40QNB024, 53QNB018, 53QNB024 Installation, Start-up And Service Instructions Manual

...
Page 1
Installation, Start-Up
and Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ....................1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Step 1 − Complete Pre-Installation Checks ....2
• INSPECT SHIPMENT
Step 2 − Select Location .....................2
Step 3 − Mount Mounting Bracket on Wall ....4
Step 4 − Connect Refrigerant Piping .........5
Step 5 − Connect Condensate Drain Line .....7
Step 6 − Make Electrical Connections ........7
Step 7 − Make Connections to Outdoor Unit ..9
• COOLING-ONLY SYSTEMS
• HEAT PUMP SYSTEMS
Step 8 − Install Fan Coil Unit Onto Mounting
Bracket .....................................9
START-UP .................................9-12
40QN Control System . . . . . . . . . . . . . . . . . . . . . . . 10
After Extended Shutdowns . . . . . . . . . . . . . . . . . . 10
Seasonal Changeovers . . . . . . . . . . . . . . . . . . . . . . 10
To Turn The Unit On and Off . . . . . . . . . . . . . . . . . 10
Adjusting Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Operating Mode Memory . . . . . . . . . . . . . . . . . . . . 10
Automatic Operation (Auto) Mode ............11
Operating Fault Diagnosis ...................11
Microprocessor Control Operation ...........11
CLEANING AND MAINTENANCE ............12-14
Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
To Install or Replace Remote Controller
Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
To Set the Current Time . . . . . . . . . . . . . . . . . . . . . 13
To Remove and Clean or Replace Air Filters . . 13
• TO REMOVE AIR FILTERS
• TO CLEAN OR REPLACE FILTERS
To Clean Indoor Unit Front Panel . . . . . . . . . . . . 13
To Clean Indoor Coil . . . . . . . . . . . . . . . . . . . . . . . . 13
To Clean Outdoor Coil (Outdoor Unit) . . . . . . . . 14
To Clean Condensate Drains . . . . . . . . . . . . . . . . . 14
SERVICE ..................................14,15
Diagnostic Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
System Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
• THERMISTOR TESTS
• COMPRESSOR FAILURE
• REVERSING VALVE FAILURE (38BK Only)
System Safeties and Interlocks . . . . . . . . . . . . . . 15
• INDOOR FAN FAILURE
• COMPRESSOR SHORT-CYCLING PROTECTION
• INDOOR COIL FREEZE PROTECTION (Cooling or
Dehumidification Mode Only)
• INDOOR COIL HIGH-TEMPERATURE
PROTECTION (Heat Pump Systems Only)
TROUBLESHOOTING ......................15-18
START-UP CHECKLIST ....................CL-1
SAFETY CONSIDERATIONS
Installing and servicing air-conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install or service air-conditioning equipment.
Untrained personnel can perform basic maintenance, such as cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on air conditioning equipment, observe precautions in lit­erature and on tags and labels attached to unit.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire ex­tinguisher available. Read these instructions thoroughly. Con- sult local building codes and National Electrical Code (NEC) for special installation requirements.
Before installing or servicing system, always turn off main power to system. There may be more than one dis­connect switch. Turn off indoor fan coil power if ap­plicable. Electrical shock can cause personal injury.
GENERAL
The new Carrier 40QNE heat pump high wall fan coil units (Fig. 1) DO NOT have electric heaters. These new heat pump fan coil units have been specifically designed to improve sys­tem efficiency in both heating and cooling modes when matched with a 38BK outdoor heat pump unit. If your application requires heating, heat pump units must be used, both out­doors and indoors. See Table 1 for recommended system combinations.
Fig. 1 — 40QN High Wall Fan Coil Unit
40QNB/QNE
018,024
High Wall Fan Coil Units
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 3e 2f
PC 111 Catalog No. 534-078 Printed in U.S.A. Form 40QN-1SI Pg 1 4-96 Replaces: New
Page 2
Table 1 — System Combinations for Indoor
and Outdoor Units
SYSTEM INDOOR UNIT OUTDOOR UNIT
High Wall Cooling Only Systems
53QNB018 40QNB018 38HDC018 53QNB024 40QNB024 38HDC024
— (2) 40QNB018 38HDS024* — (4) 40QNB018 38HDS048* — 40QNB024, (2) 40QNB018 38HDS048* — (2) 40QNB024 38HDS048*
High Wall Heat Pump Systems
53QNE018 40QNE018 38BK018 53QNE024 40QNE024 38BK024
*Multi-split systems can accommodate up to 4 fan coil units of vari-
ous types with one condensing unit. The combinations listed in this table are those which use only high-wall units (not in combina­tion with any other type of fan coil unit). Refer to system presale literature or Price Pages for more details.
NOTE: Numbers in ( ) indicate quantities of more than 1. See Fig. 1 for 40QN high wall fan coil unit.
INSTALLATION
The 40QNB high wall fan coil unit is installed with either the 38HDC condensing or 38HDS multi-split condensing out­door unit, and the 40QNE unit is installed with the 38BK heat pump outdoor unit. Refer to Table 1 to make sure the correct indoor unit(s) is installed with the correct outdoor unit.
Installation instructions for the 40QN fan coil units are contained in this manual. Refer to this manual for proper installation of the complete system. Note that the 38HDC, HDS, and BK outdoor units are shipped with installation and service instructions for basic installation of the outdoor sec­tion. Be sure to make the modifications in Make Connec­tions to Outdoor Unit section on page 9 of this literature, so that the outdoor unit will operate properly with the 40QN control system. Be sure the unit will be operated within the application guidelines shown in Table 2. When installing the 38HDC, HDS, or BK unit, note that for cooling operation below 55 F (38HDC, QK) or 0°F (38HDS), it is necessary to equip the outdoor unit with the head pressure control ac­cessory.
To install this system, you will need:
• 40QNB or QNE fan coil unit(s)* with standard wireless
remote controller
• 38HDC, HDS, or BK outdoor unit
• low-ambient (HDC, BK) or winter start (HDS) kit (if
required for your application)
* More than one fan coil unit may be used with the 38HDS
multi-split units. Refer to 38HDS system Price Pages for
full details. NOTE: Refrigerant pipe, drain pipe, wire, etc., are also re-
quired to install unit and are field supplied.
Be sure you have the required parts before beginning in­stallation. The 40QN unit utilizes a microprocessor control system to deliver optimum levels of comfort and efficiency. Be sure to follow these instructions carefully to obtain proper functioning of the unit.
Step 1 — Complete Pre-Installation Checks
UNPACK UNIT — Store unit in the original packaging until it is moved to the final site for installation. When re­moving unit from carton, lift by its 4 corners. Also, note that there is a plastic bag containing mounting screws taped to the mounting bracket.
INSPECT SHIPMENT — Upon receipt of shipment check unit (Fig. 1) for damage. Forward claim papers directly to the transportation company. Manufacturer is not responsible for damage incurred in transit.
Table 2 — Application Ranges
COOLING MODE
Maximum Minimum
Indoor
Unit
Outdoor
Unit
Indoor
Unit
Outdoor
Unit
95 F DB
115 F DB
67 F DB 55 F DB*
71 F WB 57 F WB 0° F DB†
HEATING MODE (38BK Systems Only)
Maximum Minimum
Indoor
Unit
Outdoor
Unit
Indoor
Unit
Outdoor
Unit
80 F DB 75 F DB
55 F DB 0° F DB
71 F WB 65 F WB
DB — Dry Bulb WB — Wet Bulb
*38HDC and BK systems only. †38HDS systems only.
NOTE: Unit may be equipped with a low-ambient control (HDC, BK) or winter start kit (HDS) that will allow operation down to −20 F.
Check all items. If any item is missing notify your Carrier distributor. To prevent loss or damage, leave all parts in origi­nal packages until installation.
Step 2 — Select Location — Consult local building
codes and NEC for special installation requirements.
There are several ways the unit may be installed to dif­ferent types of wall construction. These instructions do not cover all installation methods. As a typical installation, these instructions focus primarily on mounting the unit to wall studs in new construction. See Fig. 2 for unit dimensions and Fig. 3 for required clearances. Plan your installation care­fully before you begin. Listed below are some guidelines that should be followed when determining location for the unit.
1. Center unit (horizontally) on the wall selected.
2. Place the unit so it faces normal location of room
occupants.
3. Allow sufficient space for airflow clearance, wiring, re-
frigerant piping, and servicing unit. See Fig. 2 and 3.
4. Select walls that are:
a. Strong enough to support weight of the unit. b. Accessible to convenient condensate drainage. c. Free of obstacles that may block air circulation to the
fan coils.
d. Outside walls (if possible) to make piping easier.
5. Place top of fan coil unit as high on the wall as possible
making sure the unit is at least 10 in. down from ceiling to permit proper air intake. Also, make sure that the unit is not placed directly over anything to prevent filter re­moval or block airflow.
6. Make sure units are easily accessible to electrical power.
7. Refrigerant piping can enter the unit through the prepunched
holes. Refrigerant piping can run up or down along the wall, to the right or left along the wall, straight through the wall, or into the wall (Fig. 4). Once the piping is through the wall, it can run inside walls, in ceilings, between floors, or straight to the outside. See Fig. 5 for maximum line lengths.
NOTE: Run refrigerant piping as directly as possible, and avoid any unnecessary turns or bends.
8. Condensate piping can be directed through the inside wall
to an approved drain, or directed straight outside.
NOTE: The piping hole for condensate line must be made at a downward slope to ensure proper drainage. See Mount Mounting Bracket on Wall Section on page 4 for details.
2
Page 3
1. Dimensions in ( ) are in millimeters.
2. Direction of airflow.
3. Refrigerant, drain, and power connections may be made in unit rear, bot­tom, left side, or right side.
4. Refrigerant is metered by AccuRater™ device in the fan coil unit on 38HDC and BK applications. A thermostatic expansion valve is used in the outdoor unit on 38HDS applications. Insulate both refrigerant lines on 38HDS and BK applications.
5. The 49 top and left side clearances are absolute minimums. Clearances of 109 are recommended.
Fig. 2 — 40QN Dimensional Drawing
UNIT WEIGHT 40QN018 39 Lb (17.5 Kg) 40QN024 43 Lb (19.5 Kg)
3
Page 4
Step 3 − Mount Mounting Bracket on Wall
1. Decide how refrigerant will be piped. If necessary, knock out the appropriate pre-punched holes (Fig. 4) on unit for piping and electrical connections.
2. Remove bracket from fan coil unit by pulling it down from fan coil unit bottom as shown in Fig. 6.
3. Using a carpenter’s level, fasten mounting brackets into the studs in the wall at least 10 in. away from the ceiling with the 8 screws provided. Always be sure to insert screws into the top 2 holes indicated in Fig. 6. Make sure the attached bracket will support a 200 lb vertical load. For amasonrywall,anchorshieldscanbeusedtoattachbracket to the wall.
4. Temporarily hang unit on bracket to check location and level.
*A clearance of 49 is the absolute minimum. A clearance of 109 is
recommended.
NOTE: Remove unit front cover for control box access.
Fig. 3 — Minimum Required Clearances
Fig. 4 — Refrigerant Piping
*38HDC, 38BK/38HDS systems.
Fig. 5 — Maximum Line Lengths
4
Page 5
If mounting bracket is not mounted level, the indoor sec­tion will be mounted unevenly, and condensate drain­age water may drip onto the floor. Also, a gap between the bracket and the wall may result in vibration and noise from the indoor section.
5. Mark and cut condensate and piping holes. a. For piping through the wall, mark the wall below the
condensate connection and cut a 2
1
⁄2-in. hole into the
wall at either point ‘‘A’’ or point ‘‘B’’ in Fig. 7.
NOTE: The 2
1
⁄2-in hole must be made at a downward slope to ensure proper condensate drainage. See Fig. 8. Slope condensate line at a minimum pitch of1⁄4in. per foot of line. The condensate line cannot be run up for upper pip­ing connections − only refrigerant lines may be run up.
b. Push the wall sleeve (factory supplied with the unit)
through the 2
1
⁄2-in. wall opening.
Step 4 — Connect Refrigerant Piping — Fan coil
units may be connected to the outdoor units using field­supplied refrigerant grade piping. Refer to Table 3 for the correct size piping. The length of refrigerant pipe depends on the unit placement and building structure; run pipes as directly as possible. For piping requirements over 50 ft of total run, or more than 25 ft of lift, consult the long line application guidelines available in the product presale lit­erature, or contact your local representative.
DO NOT BURY MORE THAN 36 IN. OF REFRIG­ERANT PIPE IN THE GROUND. If any section of pipe is buried, there must be a 6-in. vertical rise to the valve connections on the outdoor unit. If more than the rec­ommended length is buried, refrigerant may migrate to the cooler, buried section during extended periods of unit shutdown, causing refrigerant slugging and possible com­pressor damage at start-up.
Use the following instructions to connect piping.
1. Install insulation. Insulate all refrigerant lines on heat pumps
and 38HDS systems to prevent condensation. It is ex­tremely important that all refrigerant lines and the AccuRatert metering device be insulated on heat pumps. On 38HDC cooling only units, the liquid line may be left
uninsulated. Use any acceptable heat resistant closed-cell foam insulation (minimum
3
⁄8-in. wall thickness). When insulating piping, cap ends and slide insulation over the piping. Insulation can also be cut and placed over piping.
2. Run liquid and gas refrigerant piping. a. Run pipes as directly as possible, and avoid any un-
necessary turns and bends.
b. Suspend refrigerant pipes so that the insulation is not
damaged and vibrations are not transmitted to the structure.
c. Leave slack in the refrigerant pipe between the struc-
ture and the unit to absorb vibrations.
d. Install factory-supplied flare connection and Accu-
Rater metering device in liquid line at the fan coil unit on 38HDC and 38BK systems (Fig. 9). Make sure the arrow on the metering device body points AWAY F R OM the fan coil unit. Use Table 4 to verify that the correct piston for your system has been shipped with the unit.
Fig. 6 — Bracket Mounting
NOTE: Use either point ‘‘A’’ or point ‘‘B.’’
Fig. 7 — Wall Hole Location for Rear Piping
Fig. 8 — Piping Hole
5
Page 6
NOTE: No AccuRatert is required on 38HDS sys­tems. The 38HDS systems have a TXV (thermostatic expansion valve) in the condensing unit for refriger­ant metering and control.
e. On heat pump installations, install factory-supplied pis-
ton in the AccuRater metering device located in the service valve on the outdoor unit (Fig. 10). Make sure Teflon seal on the piston faces toward the outdoor unit. Use Table 4 to verify the correct piston for your sys­tem has been shipped with the unit. Refer to 38BK installation instructions for more details.
f. Install a liquid line filter drier near the outdoor unit
(38HDC and 38BK). On heat pump systems, a bi-flow filter drier must be used. DO NOT install a filter drier in 38HDS systems.
3. Insulate and caulk wall openings to reduce air infiltration and refrigerant pipe vibrations on structure.
4. Evacuate piping, if necessary. If either refrigerant piping or the indoor coil is exposed to atmospheric conditions, it must be evacuated to 1000 microns to eliminate con­tamination and moisture in the system.
Table 3 — Physical Data
UNIT 40QN 018 024 OPERATING WEIGHT
(lb)
39 43
REFRIGERANT R-22 with AccuRaterT Control or TXV FAN
Rpm 1120 1470 Nominal Cfm (High Speed)
540 550
COIL
Rows 23 Face Area (sq ft) 2.56 2.56 Fins/in. 15.9 18.1 Number of Circuits 23
CONNECTIONS (MPT)
Suction (in.) Flare
5
⁄
8
Liquid (in.) Flare
3
⁄
8
Condensate Drain
5
⁄
8
LINE SIZES
Suction (in.)
5
⁄
8
Liquid (in.)
3
⁄
8
Condensate Drain
5
⁄
8
TXV — Thermostatic Expansion Valve
(38HDS only)
Table 4 — Required Piston Sizes for AccuRater Metering Device
OUTDOOR
UNIT 38
INDOOR
UNIT 40QN
INDOOR
PISTON
INDOOR
PISTON TYPE
OUTDOOR
PISTON
OUTDOOR
PISTON TYPE
REQUIRED SYSTEM
CHARGE (lb)*
HDC018 B018 49 B N/A N/A 4.6 HDC024 B024 57 B N/A N/A 5.3
BK018 E018 51 B 47 B 5.0 BK024 E024 59 B 52 B 5.1
LEGEND
N/A — Not Applicable TXV — Thermostatic Expansion Valve
*Charge amount determined based on 25 ft of line. Check charge for longer lines using superheat method. See 38HDC and BK installation, start-up,
and service instructions for system charging procedures.
NOTE: The 38HDS systems do not use the AccuRater device. The 38HDS systems have a TXV in the condensing unit for refrigerant metering and control.
NOTE: Arrow on AccuRater body points in
free flow
direction away
from the coil.
Fig. 9 — AccuRater Metering Device in Liquid
Line (Bypass Type Components)
Fig. 10 — AccuRater Metering Device at Service
Valve (Bypass Type Components)
6
Page 7
Step 5 — Connect Condensate Drain Line —
Observe all local sanitary codes when installing condensate drains.
1. Connect drain line by inserting a
5
⁄8-in. rigid PVC pipe
over the drain connection. Refer to Fig. 11.
The drain tube extension must be securely fastened to the condensate drain. Failure to do so can result in condensate water dripping onto the floor.
2. To ensure regular flow of condensate water, the drain pipe should be pitched toward an open drain or sump at a down­ward slope of at least1⁄4-in. per foot. Refer to Fig. 12.
IMPORTANT: Be sure the drain piping has no slack which might form a trap. Do not insert a trap in the drain line; the drain is internally trapped.
3. Insulate condensate drain line(s). Insulate the condensate drain lines that are located in or above an occupied area with a condensate proof material such as polyurethane or neoprene.
Step 6 — Make Electrical Connections — Be sure
field wiring complies with local building codes and NEC, and unit voltage is within limits shown in Table 5.
Contact local power company for correction of improper
line voltage.
To avoid personal injury or damage to unit, do not make electrical connections until all power sources are shut down, locked out, and tagged off. Failure to do so could result in personal injury or unit damage.
Operation of unit on improper line voltage constitutes abuse and could affect warranty. Refer to Table 5 for permissible operating limits. Do not install unit in sys­tem where voltage may fluctuate above or below per­missible limits.
NOTE: Use type NM power cable only (per NEC; provided for fan coil units only) between disconnect switch and unit.
NOTE: Install branch circuit disconnect per NEC of ad­equate size to handle unit starting current. Locate disconnect within sight from and readily accessible from unit, per Section 440-14 of NEC. Some codes allow indoor unit to share disconnect with outdoor unit if disconnect can be locked; check local code before installing in this manner. To make electrical connections:
1. Remove the screws holding the front cover of the fan coil unit, and remove front cover. Save screws and screw covers for reinstallation.
2. Remove control box strain relief clamp (see Fig. 13).
3. Remove any factory test leads still connected to the power terminal box. These leads (if applicable) are for factory testing only and cannot be used for power connections.
4. Route the factory-supplied ground and power wires from terminal block 1 (TB1) to the field-supplied disconnect switch.
According to NEC and most local codes, the unit must have an uninterrupted, unbroken ground to mini­mize personal injury if an electrical fault should oc­cur. The ground may consist of electrical wire or metal conduit when installed in accordance with ex­isting electrical codes. Failure to follow this warn­ing could result in an electric shock, fire, or death.
5. Route factory-supplied line power leads (see Fig. 14) from field-supplied, indoor unit disconnect to the fan coil unit TB1 (see Fig. 14 and 15). Run wire through the strain relief on the control box (see Fig. 13). When routing wire in the fan coil unit, keep the wire away from refrigerant and condensate piping and any sharp edges on the unit.
Do not short circuit the 40QN transformer − it is fused. The transformer can be short circuited by con­necting the wrong wires or by touching a live wire to the side of a grounded control box.
Fig. 11 — Drain Connection (Right Side Shown When
Facing Fan Coil Unit)
7
Page 8
Table 5 — Electrical Data
INDOOR
UNIT
40QN
V (Single-
Ph, 60 Hz)
OPERATING VOLTAGE* FAN
WATTS MCA
MAX FUSE OR HACR TYPE CKT BKR AMPS
Max Min LRA FLA
B018
208/230 253 187 3.2 0.53 94 0.66 15
B024 E018 E024
LEGEND
FLA — Full Load Amps HACR — Heating, Air Conditioning, and Refrigeration LRA — Locked Rotor Amps MCA — Minimum Circuit Amps per NEC Section 430-24 NEC — National Electrical Code
*Permissible limits of the voltage range at which unit will operate satisfactorily.
Fig. 12 — Drainage System (Rear Piping Shown)
NOTE: This shows item locations only. Front cover of fan coil unit must be removed to access terminal boards.
Fig. 13 — Fan Coil Unit Wiring Preparation
FAN COIL UNITS
LEGEND
CONN — Connection EQUIP GND — Equipment Ground TB — Terminal Block
Fig. 14 — Line Power Connections
8
Page 9
Step 7 − Make Connections to the Outdoor Unit
COOLING-ONLY SYSTEMS − To connect the 38HDC or HDS condensing unit to the fan coil unit(s) so that the sys­tem will operate correctly:
Route 2 field-supplied wires of 18-gage AWG (American Wire Gage) thermostat cable between the low-voltage ter­minal block of the fan coil unit (TB2) and the 38HDC or HDS unit low-voltage terminal block. Connect the wires be­tween terminals Y and Y and between terminals C and C.
HEAT PUMP SYSTEMS − To connect the 38BK heat pump unit to the fan coil unit so that the system will operate correctly:
IMPORTANT: DO NOT RUN THE THERMISTOR CABLE IN THE SAME CONDUIT AS THE POWER WIRING.
1. One thermistor connection cord with a lead length of
24 ft is shipped with the 40QNE fan coil unit. Run the connection cord from the low-voltage terminal board in the control box in the fan coil unit (TB3) to the heat pump unit. Route the wire carefully so that it will not be damaged.
2. For cooling operation, route 2 field-supplied wires of
18-gage AWG (American Wire Gage) thermostat cable between the low-voltage terminal block of the fan coil unit (TB2) and the 38BK unit low-voltage terminal block. Connect the wires between terminals Y and Y and be­tween terminals C and C.
3. For heating operation, route 3 additional wires of
18-gage AWG thermostat cable between the low-voltage terminal block of the fan coil unit (TB2) and the 38BK unit low-voltage terminal block. Connect the wires be­tween terminals R and R, O and O, and G and G.
Step 8 − Install Fan Coil Unit Onto Mounting Bracket
1. Hook the fan coil unit onto the top of the mounting bracket. See Fig. 16.
2. Snap the fan coil unit onto the mounting bracket as shown in Fig. 16.
IMPORTANT: An audible snapping sound will be heard as the hook on the unit is secured into the hole on the mounting bracket. Be sure unit is cor­rectly mounted.
START-UP
Complete the following checks and the Start-Up Check­list on page CL-1 before system start-up. Refer to outdoor unit installation, start-up and service instructions for system start-up procedures and refrigerant charging methods.
1. Check condensate drainage system. Add water to check the drainage flow. If water does not
flow regularly, check the pipe slope or see if there are any pipe restrictions.
2. Make sure that all wiring connections are correct and tight.
3. Make sure that all barriers, covers, and panels are in place.
4. Ensure that the filters have been installed and that the discharge louvers are correctly positioned.
Never operate unit without a filter. Damage to the unit or personal injury may result.
5. If the unit is equipped with a crankcase heater, energize a minimum of 24 hours before starting the unit. To en­ergize crankcase heater only, close indoor unit discon­nect, then with the remote controller, set unit in off mode and close the outdoor unit disconnect.
6. Fully backseat (open) the liquid and vapor tube service valves.
7. Unit is shipped with valve stems frontseated and caps factory installed. Replace stem caps after system is opened to refrigerant flow (backseated). Replace caps finger tight.
Fig. 15 — High Voltage Connections
Fig. 16 — Mounting Unit to Bracket
9
Page 10
8. With the remote controller, turn on the unit and operate in each mode (as applicable) for 15 minutes to test for proper operation. Do not operate in cooling mode if out­door temperature is below 55 F (HDC,BK) or 0° F (HDS) unless unit is equipped with low ambient control (HDC, BK) or winter start kit (HDS). Do not operate in heating mode (heat pump systems only) if the outdoor tempera­ture is above 75 F.
9. Test for proper refrigerant charge using the superheat method (HDC,BK) or subcooling method (HDS).
10. Explain basic system operation to the owner.
40QN Control System — The 40QN unit is equipped
with a microprocessor control which operates the system. This control is located in the control box of the fan coil unit, with thermistors located in the fan coil inlet and on the in­door coil. The 40QNE heat pump fan coil units also have thermistors located on the outdoor coil and in the outdoor air inlet. These thermistors monitor system operation and con­trol the operating mode. To change settings or modes of op­eration, use the factory-supplied infrared wireless remote controller. This controller allows the fan coil unit to be op­erated from within the same room without any wire connec­tions to the unit.
The remote controller includes a wall-mounted bracket. To install the bracket, attach bracket to the wall as shown in Fig. 17 using factory-supplied, double-sided tape. Install factory­supplied batteries into the remote controller per To Install or Replace Remote Controller Batteries section on page 12, and place the controller into the bracket so that it will be ready for use.
After Extended Shutdowns — If the system has been
turned off for more than 12 hours, turn on the indoor and outdoor unit disconnect switches to supply power to the sys­tem for 12 hours BEFORE starting the system.
Seasonal Changeovers — When changing heat pump
system from cooling to heating or heating to cooling, or be­fore starting cooling only system after it has been out of use for the winter season, perform the following steps BEFORE starting the system:
1. Inspect and clean the outdoor unit, particularly the coil.
2. Clean or replace the air filters in the indoor unit.
3. Clean the indoor unit drain pan and drain pipe, and re-
move any obstructions.
4. Turn on indoor and outdoor unit disconnect switches to
supply power to the system 12 hours before starting the system.
To Turn the Unit On and Off — To turn the unit on,
press the orange ON/OFF button (See Fig. 18). Unit will start. To stop unit operation, press the ON/OFF button again. Unit will stop. Refer to Owner’s Manual enclosed with the fan coil unit for full remote control operating details.
Adjusting Airflow — The airflow direction may be ad-
justed up and down using the remote controller, and from side to side by manually moving the vents. For cooling only units and heat pump units when in the cooling mode, set the louvers to discharge straight out (parallel to the floor) (see Fig. 19). For the heat pump units operating in heating mode, it is recommended that the air discharge louvers be set to discharge vertically (see Fig. 19).
The swing range shown in Fig. 19 is the range which will provide maximum occupant comfort in each mode. It is rec­ommended that the louvers be positioned within this range (using the remote controller).
NOTE: The full swing range for the mode selected will au­tomatically be used if auto. fan mode is selected.
Operating Mode Memory — After the system is turned
off or after a power failure, the system remains in the last operating mode selected. When the system is turned back on, or when power is automatically restored, operation con­tinues in the same operating mode as when power shut down.
Fig. 17 — Mounting Remote Controller Bracket
Fig. 18 — Remote Controller
*Potential range. †Desirable range.
NOTE: Unit is equipped with manual air vents which direct the air from side to side. Up and down louver motion can be selected using the remote controller. For maximum comfort, set louvers within the swing range. See Adjusting Airflow section on this page for more information.
Fig. 19 — Louver Adjustments
10
Page 11
Automatic Operation (Auto) Mode — If auto mode
is selected, the system automatically switches the operating mode from heating (heat pump system only) to cooling, or from cooling to heating (heat pump system only) depending on the selected temperature.
NOTE: Between the cooling cycle and the heating cycle there is a neutral zone of approximately 2° F above and 2° F be­low the selected temperature when only the fan is operating.
Operating Fault Diagnosis — The system includes
an automatic diagnosis feature which is activated under difficult or unacceptable operating conditions. If such con­ditions occur, the system stops automatically, the operating fault signal appears (green ‘‘UNIT ON’’ light on the front of the fan coil unit flashes), and an analysis of the system op­erating conditions is initiated. The system will then be re­started automatically, as soon as normal conditions have been restored, or it will remain off. If the system does not start again, the green ‘‘UNIT ON’’ light will flash an error code.
Microprocessor Control Operation — This sys-
tem is controlled by a microprocessor designed to give op­timum levels of comfort and operating efficiency. The con­trol is located in the 40QN unit. To operate the unit, the factory­supplied remote controller is required.
There are 9 (QNB systems) or 11 (QNE systems) oper­ating modes (including the off mode) for the unit. Each mode operates as follows:
• Off Mode — When the unit is in the off mode, all func-
tions (compressor, outdoor fan, indoor fan, and air sweep) are off, except the reversing valve (QNE only), which will stay energized if the unit was last operated in the cooling mode.
• Air Circulation Mode (Fan Operation Only) — When air
circulation mode is selected, the indoor fan will operate continuously in the selected speed (high, medium, low, or auto.). If the auto. mode is selected, the indoor fan will operate at low speed. The compressor and outdoor fan are off. The reversing valve (QNE only) will remain in the last operating mode.
• Cooling Mode — When the cooling mode is selected, the
indoor fan will operate continuously at the selected speed if the speed is high, medium, or low. If the indoor fan is in auto. mode, the fan will change operating speeds de­pending on the difference between the room temperature and the set point. The reversing valve (QNE only) will be on. The compressor cannot run for 3 minutes from the time the system starts up or for 3 minutes from the time the compressor last operated. When the temperature of the room is equal to or greater than the selected temperature, the compressor and outdoor fan will operate until the room temperature is 2° F below the set point, and then shut off. When the room temperature is less than the selected tem­perature, the compressor and outdoor fan remain off.
•MaximumDehumidificationMode—Whenthedehu-
midification mode is selected, the indoor fan will operate continuously at the selected speed if the speed is high, me­dium, or low. If the indoor fan is in auto. mode, the fan will change operating speeds depending on the room tem­perature. If the room temperature is below the set point, the indoor fan will run at ultra-low speed, and the com­pressor could run for up to 4 minutes. (Ultra-low speed is acontrol-drivenspeed[notuserconfigurable]usedtosample the space when the fan would normally be off.) The re­versing valve (QNE only) will be on. The compressor can­not run for 3 minutes from the time the system starts up or for 3 minutes from the time the compressor last operated.
Initial Operation — When the mode is first selected, one of the following occurs:
1. If the room temperature is above or equal to the selected temperature, the unit will operate for 16 minutes, and the compressor and outdoor fan will operate. The indoor fan will operate as in the cooling mode. After 16 minutes of operation (or when the room reaches 2° F below set point), the unit switches to normal dehumidification operation.
2. If the room temperature is below the selected tempera­ture, the unit will operate for 8 minutes as follows: the compressor and outdoor fan will operate for 3 minutes. The indoor fan will operate in low speed, and 30 seconds after the compressor stops, the indoor fan stops. The unit remains off for 1 minute, and then the indoor fan starts in ultra-low speed for 30 seconds. The unit then switches to normal dehumidification operation.
Normal Operation — One of the following will take place:
1. When the temperature of the room is equal to or greater than the selected temperature (by not more than 3° F), the unit will operate for 8 minutes as follows: the compres­sor and outdoor fan will operate for 3 minutes. The in­door fan will operate in low speed, and 30 seconds after the compressor stops, the indoor fan stops. The unit re­mains off for 1 minute, and then the indoor fan starts in ultra-low speed for 30 seconds. The normal dehumidifi­cation operation is repeated for the newly sensed room temperature.
2. If the room temperature is equal to or greater than the selected temperature, but not by more than between 4° F and 6° F, the compressor and outdoor fan operate for 4 minutes. The indoor fan will run at ultra-low speed and will stop 30 seconds after the compressor stops. After 3 minutes, the indoor fan runs at ultra-low speed for 30 seconds. The normal dehumidification operation is re­peated for the newly sensed room temperature.
3. When the room temperature is equal to or greater than 4° F below the selected temperature, the system operates as follows: The compressor and outdoor fan operate for 3 minutes. The indoor fan will operate at ultra-low speed and will stop 30 seconds after the compressor stops. Af­ter 4 or 5 minutes, the indoor fan starts in ultra-low speed for 30 seconds. The normal dehumidification operation is repeated for the newly sensed room temperature. If the room temperature is still 4° F below the selected tem­perature, the compressor, outdoor fan, and indoor fan re­main off. After 7
1
⁄2minutes, the indoor fan operates at ultra-low speed for 30 seconds. The normal dehumidifi­cation operation is repeated for the newly sensed room temperature.
• Heat Pump Heating Mode (Heat Pump Systems Only) — When the heat pump mode is selected, the indoor fan will operate at the selected speed if the speed is high, medium, or low, unless overridden by the coil temperature (to pre­vent cold drafts). If the indoor fan is in auto. mode, the fan will change operating speeds depending on the difference between the room temperature, the set point, and the coil temperature. The reversing valve will be off. The com­pressor cannot run for 3 minutes from the time the system starts up or for 3 minutes from the time it last operated. When the temperature of the room is 8° F below the se­lected temperature, the unit will operate in heat pump mode until the temperature is 6° F above the selected tempera­ture, or the compressor runs for 40 minutes (whichever comes first). If the temperature of the room is less than 7° F below or equal to the selected temperature, the unit operates in heat pump mode until the selected set point temperature plus 2° F is reached.
•DemandDefrostMode(HeatPumpSystemsOnly)—This unit uses a demand defrost system to remove frost from the outdoor coil during heating operation. The indoor and outdoor fans are shut off during defrost mode.
11
Page 12
• Sleep Mode — The sleep mode timer will turn the unit off when the timer reaches zero minutes. During the first 11⁄2hours from the time the sleep mode timer starts, the room temperature is set back from the selected tempera­ture a total of 4° F in cooling and 6° F in heating (BK only).
• Awake Mode — The awake timer will turn the unit on when the timer reaches zero minutes. The unit will start in the same mode and at the same selected temperature as when the system shut off.
•AutomaticOperationModeforCoolingOnlySystems (38HDC and HDS) — The unit samples the air in the room. Based on the room temperature, the unit selects one of the following modes:
1. Cooling Mode — If the room temperature is more than
82.4 F with a preset temperature of 78.8 F.
2. Dry Mode — If the room temperature is more than
75.2 F and less than 82.4 F with a preset temperature of 77 F.
3. Fan Only Mode — If the room temperature is less than
75.2 F.
The preset temperature can be changed by ±4° F using the remote control.
•AutomaticOperationModeforHeatPumpSystems(38BK) — The operation mode will be determined after 20 sec­onds of room monitoring (to determine the room tempera­ture and the outdoor air temperature).
• Test Mode — The test mode can be selected by setting the slide switch on the fan coil unit to TEST position. The slide switch is located on the front of the unit as shown in Fig. 20. The fan coil unit will start immediately (there is no compressor time delay when using test mode) in cool­ing mode with an infinitely low set point. The indoor fan speed will be at the high setting, and the swing louvers will be on (moving up and down).
NOTE: The unit cannot be controlled by the remote con­troller until the slide switch is returned to the REMOTE position.
• Emergency Mode — This mode is only to be used if the remote controller is lost, damaged, or the batteries are dis­charged. To initiate emergency mode, manually move the slide switch on the fan coil unit to the EMER position (Fig. 20). The unit is automatically operated in cooling or heating (BK units only) mode according to room tempera­ture. Emergency operation settings are as follows:
1. Operation mode: AUTO.
2. Fan Speed: AUTO.
3. Cooling set point: 77 F
4. Timer Mode: Continuous NOTE: The unit cannot be controlled by the remote con-
troller until the slide switch is returned to the REMOTE position.
CLEANING AND MAINTENANCE
To avoid the possibility of electric shock, before per­forming any cleaning and maintenance operations, al­ways turn off power to the system by pressing the orange ON/OFF button on the remote controller. Turn off the outdoor disconnect switch located near the out­door unit. If the indoor unit is on a separate switch, be sure it is also disconnected.
For proper system operation, perform the cleaning and main-
tenance operations in Table 6.
Lubrication — The indoor-fan automatic air sweep mo-
tor, and the outdoor fan motor are factory lubricated and re­quire no oiling.
To Install or Replace Remote Controller Batteries
Do not drop the remote controller — damage to the device may result. Avoid getting the controller wet.
NOTE: Before replacing the batteries, note that the remote controller signal can be affected if electronic fluorescent lights are installed nearby. The batteries may not need to be replaced. If you suspect this is the problem, consult your Carrier distributor.
Table 6 — Cleaning and Maintenance Schedule
TASK MONTHLY QUARTERLY YEARLY
INDOOR UNIT
Clean Air Filters X Clean Drain Pipe X Clean Condensate Drain Pan X Replace Batteries in the Remote Controller X Clean Indoor Unit Front Panel X
OUTDOOR UNIT
Clean the Fins From Outside X Open the Unit and Clean Fins Inside X Remove Dust From Electrical Parts X Check Electrical Connections are Tight X Clean Outdoor Fan X Check that Outdoor Fan Assembly is Tight X Clean Drain Pan X
NOTE: Maintenance procedures for the outdoor unit are in the 38HDC, HDS, and BK installation instructions.
EMER — Emergency Mode
Fig. 20 — Slide Switch
12
Page 13
Batteries should be replaced once a year. Use 2 batteries (1.5 v, dc-t ype, AAA alkalin e batte ries ). Neve r use o ld or r e­charged batteries together with new ones.
To replace batteries:
1. Slide the battery cover off from the back of the remote controller. See Fig. 21.
2. Insert the 2 batteries in accordance with the markings on the remote controller, so that the poles are correct (+ and −).
RST
3. Press the button using an instrument screwdriver or similar small, pointed tool.
4. Replace the cover securely.
It is time to replace the remote controller batteries when the remote controller function becomes irregular, or the sys­tem no longer responds to commands given close to the unit.
When shutting down the system for an extended period of time, it is advisable to remove the batteries.
Consult distributor if any other equipment is turned on or shows signs of disrupted operation if you use the wireless remote controller, or if the system is turned on or shows signs of disrupted operation when the remote controller of any other equipment is used.
To Set the Current Time
TA1. Press the button (located on the back of the remote
controller; see Fig. 22) with an instrument screwdriver or similar small, pointed tool, and the current time indica­tion symbol flashes.
Note that the controller comes preset from the factory set for 6:00 a.m.
2. Set the current time with the hour and minute buttons on
the front of the remote controller (see Fig. 21) while the current time indication is flashing. Note that a.m. and p.m. are also indicated as the times are scrolled through.
TA
3. Press again. The flashing will stop and the current
time will be reset to the new setting.
To Remove and Clean or Replace Air Filters
Operating your system with dirty air filters may damage the indoor unit and can also cause reduced cooling per­formance, intermittent system operation, frost build-up on the indoor coil, and blown fuses. Inspect and clean or replace the air filters monthly.
TO REMOVE AIR FILTERS
1. Open fan coil unit front panel (lift). See Fig. 23.
2. Pull the filters down to remove.
TO CLEAN OR REPLACE FILTERS — Filters should be vacuumed and washed with warm water (see Fig. 23). Shake filter to remove any excess water, dry thoroughly, and re­place by sliding filter behind front grille until filter snaps in place.
If the filter has begun to break down or is torn, it needs to be replaced. Replacement filters are available through your Carrier distributor.
To Clean Indoor Unit Front Panel — If the front
panel of the unit becomes dirty or smudged, wipe the out­side of the front panel with a soft dry cloth. If necessary, use amildliquiddetergentandwipeoffcarefullywithadrycloth.
When cleaning the front panel, NEVER use water hotter than 105 F, and DO NOT pour water onto the fan coil unit. Do not use abrasive or petroleum-based clean­ers — damage to unit appearance will result.
To Clean Indoor Coil — To clean the coil, remove in-
door unit front panel, and vacuum the coil fins. Use care not to bend or damage fins.
REMOVE COVER INSERT NEW BATTERIES PRESS RST
NOTE: Be sure to insert new batteries correctly (as shown).
Fig. 21 — Installing or Replacing Batteries
13
Page 14
To Clean Outdoor Coil (Outdoor Unit)
Some metal parts and sharp fins of outdoor unit coil can cause personal injury during cleaning. Clean coil carefully.
To clean the outdoor coil:
1. Remove any dirt or obstruction from discharge opening.
2. Use a garden hose to spray water on the coil. Debris that collects between coil fins inhibits heat transfer — direct the water spray between coil fins to flush out debris.
Cleaning Condensate Drains — Clean all drains and
drain pans at the start of each cooling season. Check the flow by pouring water into the drain.
SERVICE
When servicing unit, turn off all electric power to unit to avoid shock hazard or injury from rotating parts.
Do not vent refrigerant to atmosphere when servicing unit. Reclaim refrigerant during system repair or unit removal.
Diagnostic Codes — This unit is equipped with a mi-
croprocessor control which continuously monitors the op­eration of the unit. If an operational fault is detected, a fault is indicated by the flashing of the green ‘‘UNIT ON’’ light on the front of the fan coil unit. A red LED (light-emitting diode) indicator light, located on the control board in the control box of the indoor unit, will emit a flash code which can be used to troubleshoot a system problem. The control will continue to monitor the unit and, if the conditions which cause the fault are cleared, the unit will return to normal operation. If the fault code is present for 5 cycles of the unit, the unit will be locked out and the alarm is indicated by the flashing of the green ‘‘UNIT ON’’ light on the front of the fan coil unit.
To access the LED indicator light, remove the front cover
of the unit by removing the 3 screws holding it in place.
If the LED indicator light continuously flashes on for one second, then off for one second, the control is functioning properly and no fault is present. A fast flashing LED indi­cates that a fault has been detected. Table 7 lists the number of quick flashes and the associated fault. If the system does not operate, and the LED indicator does not flash, either the power to the control board is off, or the control board has failed.
System Tests — System tests listed below are per-
formed continuously by the microprocessor. If a fault is indicated, then the system allows only limited operation un­til the problem is resolved. If the problem resolves itself, then the code is cleared and operation resumes.
THERMISTOR TESTS — Each thermistor is tested for high limit out of range (shorted condition) and low limit out of range (open condition). If the thermistor is out of range, the fault status indicator comes on and the LED flashes the ap­propriate fault code.
Table 7 — System Fault Codes
NO. OF QUICK LED FLASHES
SYSTEM FAULT
2 Room Air Thermistor 3 Indoor Coil Thermistor 4 Outdoor Coil Thermistor* 5 Compressor Malfunction 6 Reversing Valve Malfunction* 7 Outdoor Air Thermistor* 8 Indoor Fan Failure 9 Discharge Air Thermistor
LED — Light-Emitting Diode
*Heat pump systems only.
NOTE: If the LED light continuously flashes on for one second, then off for one second, the control is functioning properly and no fault is present.
PRESS SET TIME PRESSTA TA
Fig. 22 — Setting The Current Time
REMOVE FILTER VACUUM CLEAN RINSE WITH WATER
Fig. 23 — Air Filter Maintenance
14
Page 15
COMPRESSOR FAILURE
If the System is in Cooling or Dehumidification Mode — After 5 minutes of operation, if the temperature of the in­door coil is not 4° F less than at the time the call for cooling started, then a compressor failure is indicated on the remote controller LCD display.
If the System is in Heat Pump Heating Mode (38BK only) —After5minutesofoperation,ifthetemperatureindi­cated by the outdoor coil thermistor is not 4° F less than at the time the call for heating started, then a compressor fail­ure is indicated.
REVERSING VALVE FAILURE (38BK Only)
If the System is in Cooling or Dehumidification Mode — After 5 minutes of operation, if the temperature at the indoor coil is 4° F more than at the time the call for cooling started, then a reversing valve failure is indicated.
If the System is in Heat Pump Heating Mode — After 5 min­utes of operation, if the temperature indicated by the out­door coil is 4° F more than at the time the call for heating started, then a reversing valve failure is indicated.
System Safeties and Interlocks
INDOOR FAN FAILURE — If the indoor fan rpm shows greater than 800 rpm for 30 seconds with the fan in the off mode, then this test indicates an indoor fan failure. Also, if the indoor fan rpm is greater than 1700 rpm for 30 seconds, then this test indicates an indoor fan failure.
COMPRESSOR SHORT-CYCLING PROTECTION — There is a time delay of 3 minutes between compressor turning off and turning back on.
INDOOR COIL FREEZE PROTECTION (Cooling or De­humidification Mode Only) — If the indoor coil tempera­ture is less than or equal to 32 F for 10 minutes after the compressor has started, then the compressor and outdoor fan are turned off. The indoor fan continues to run at the user­selected speed until the indoor coil reaches 44 F.At that time, the compressor and outdoor fan will restart.
INDOOR COIL HIGH-TEMPERATURE PROTECTION (Heat Pump Systems Only) — If indoor coil temperature is greater than or equal to 135 F, the outdoor fan shuts down. The outdoor fan will restart automatically when the indoor coil temperature drops to 120 F.
TROUBLESHOOTING
See Table 8 and Fig. 24 and 25 to assist in troubleshooting
the 40QN fan coil units.
Table 8 — Troubleshooting
PROBLEM POTENTIAL SOURCE ACTION
Unit does not operate
Circuit breaker has tripped or fuse is blown Reset the circuit breaker or replace the fuse.
Power failure
Restart fan coil unit operation when power is restored.
Voltage is too low Confirm the available voltage.
Insufficient Cooling
Air filter is blocked with dust Clean the air filter. Temperature is not set properly Check and reset if necessary. Window(s) and/or door(s) are open Close window(s) and door(s). Outdoor unit is obstructed Remove the obstruction. Fan speed is too low Change the fan speed
Operation mode is set to fan or auto. mode
Change to cooling operation or reset temperature (using remote controller).
Insufficient Heating*
Air filter is blocked with dust Clean the air filter. Temperature is not set properly Check and reset if necessary. Window(s) and/or door(s) are open Close window(s) and door(s). Outdoor unit is obstructed Remove the obstruction.
Unit stops during operation
Off timer is operating Turn off the off timer function. Room temperature has reached the programmed
set point
Normal unit operation.
*Heat pump systems only.
15
Page 16
LEGEND AND NOTES FOR FIG. 24 AND 25
AGING — For the Burn-In Test
(short terminals)
AS — Assembly C—Contactor CAP — Capacitor CH — Crankcase Heater CLO — Compressor Lockout CN — Connector COMP — Compressor CT — Current Transformer DFB — Defrost Board DFT — Defrost Thermostat EQUIP GND — Equipment Ground FMC — Fan Motor Capacitor GND — Ground HA — Home Automation HPS — High-Pressure Switch IDC TH — Indoor-Coil Thermistor IDFM — Indoor Fan Motor JEM-A — Japan Electric Manufacturing
Industry Association
LLPS — Liquid Low Pressure Switch LPS — Low-Pressure Switch OAC TH — Outdoor Coil Thermistor ODA TH — Outdoor-Air Thermistor ODC TH — Outdoor-Coil Thermistor
OFM — Outdoor Fan Motor OFR — Outdoor Fan Relay OL — Overload PCB — Printed Circuit Board RA TH — Return Air Thermistor RC — Resistor Capacitor RCV — Receiver RVS — Reversing Valve Solenoid SC — Start Capacitor SR — Start Relay STM — Step Motor TB — Terminal Block TRAN — Transformer U—Unloader
Terminal (Marked)
Terminal (Unmarked)
Splice
Terminal Block
Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring
1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
2. Wire in accordance with National Electrical Code (NEC) and local codes.
3. The CLO locks out the compressor to prevent short cycling on com­pressor overloads and safety devices. Before replacing CLO, check these other devices. A minimum 1 amp turn is required to hold contacts closed.
4. A 24-ft long thermistor wiring cable is provided with the fan coil unit.
5. Compressor and fan motors are protected by internal thermal over­loads.
6. Transformer has an internal 2 amp thermal fuse on the primary side.
16
Page 17
Fig. 24 — Cooling-Only System (38HDC Shown)
RELAY CHART
COMPRESSOR K13
THERMISTOR EQUIVALENCE
TEMPERATURE RESISTANCE
°F °C V
95 35 6,500 72 22 11,400 32 0 32,500
ALL THERMISTORS IN THE 40QN SYSTEMS ARE
IDENTICAL TO EACH OTHER
17
Page 18
Fig. 25 — Heat Pump System
RELAY CHART
COMPRESSOR K13
REV. VALVE K11
OUTDOOR FAN K12
THERMISTOR EQUIVALENCE
TEMPERATURE RESISTANCE
°F °C V
95 35 6,500
72 22 11,400
32 0 32,500
ALL THERMISTORS IN THE 40QN SYSTEMS ARE
IDENTICAL TO EACH OTHER
Copyright 1996 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 3e 2f
PC 111 Catalog No. 534-078 Printed in U.S.A. Form 40QN-1SI Pg 18 4-96 Replaces: New
Page 19
START-UP CHECKLIST
I. PRELIMINARY INFORMATION
OUTDOOR UNIT: MODEL NO.
OUTDOOR UNIT: MODEL NO.
SERIAL NO.
SERIAL NO.
ACCESSORIES: __________________________________________________________________________________
PISTONS (38HDC and 38BK SYSTEMS ONLY): INDOOR SIZE: OUTDOOR SIZE (38BK SYSTEMS ONLY):
REFRIGERANT PIPING: EQUIVALENT LINE LENGTH: (IF OVER 50 FT)*
LIFT: FAN COIL ABOVE OUTDOOR UNIT (IF OVER 25 FT)*?
FAN COIL BELOW OUTDOOR UNIT (IF OVER 25 FT)*?
*APPLIES ONLY TO 38HDC AND 38BK UNITS USING LONG-LINES APPLICATIONS. MAXIMUM EQUIVALENT
LINE LENGTH FOR 38HDS SYSTEMS IS 50 FT. MAXIMUM LIFT ON 38HDS APPLICATIONS IS 30 FT FROM LOWEST SYSTEM POINT TO HIGHEST SYSTEM POINT.
PRE-START-UP
INDOOR UNIT (REFER TO OUTDOOR UNIT INSTALLATION INSTRUCTIONS FOR OUTDOOR UNIT PRE-START-UP FUNCTIONS)
IS THERE ANY SHIPPING DAMAGE?
IF YES, WHERE?
WILL THIS DAMAGE PREVENT UNIT START-UP?
CHECK POWER SUPPLY. IS IT 208/230, SINGLE PHASE?
HAS GROUND WIRE BEEN CONNECTED?
HAS THE CORRECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED?
ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY?
IS THE DISCONNECT SWITCH INSTALLED IN SIGHT FROM THE UNIT?
IS THE LOW-VOLTAGE CABLE (INDOOR TO OUTDOOR UNIT) RUN AND CONNECTED PROPERLY?
HAS CONDENSATE DRAIN BEEN RUN AND SLOPED PROPERLY?
IS AIR FILTER(S) IN PLACE?
IS UNIT MOUNTED LEVEL?
IS COOLING PISTON INSTALLED, THE CORRECT SIZE, AND IN THE CORRECT DIRECTION (38HDC AND 38BK SYSTEMS ONLY)?
IS HEATING PISTON INSTALLED, THE CORRECT SIZE, AND IN THE CORRECT DIRECTION
(38BK SYSTEMS ONLY)?
PIPING
IS A LIQUID LINE SOLENOID INSTALLED IF REQUIRED BY LONG-LINE APPLICATIONS (38HDC AND 38BK SYSTEMS ONLY)?
IS FILTER DRIER INSTALLED AT THE OUTDOOR UNIT (38HDC AND 38BK SYSTEMS ONLY)?
HAVE LEAK CHECKS BEEN MADE AT THE COMPRESSOR, OUTDOOR UNIT, FLARE CONNECTIONS, FILTER DRIERS, AND FUSIBLE PLUGS WITH A LEAK DETECTOR?†
†FIELD PIPING AND ALL TUBING CONNECTIONS MUST BE LEAK TESTED BY THE PRESSURE METHOD DE-
SCRIBED IN CARRIER GENERAL TRAINING FOR AIR CONDITIONING MANUAL (GTAC2), MODULE 5. USE R-22 AT APPROXIMATELY 25 PSIG BACKED UP WITH AN INERT GAS TO REACH A TOTAL SYSTEM PRESSURE NOT TO EXCEED 245 PSIG.
CL-1
Page 20
START-UP CHECKLIST (cont)
HAS PIPING SYSTEM BEEN EVACUATED TO 1000 MICRONS (IF REQUIRED)?
HAS SYSTEM CHARGE BEEN WEIGHED IN (IF REQUIRED)?
HAVE SERVICE VALVES BEEN FULLY BACKSEATED?
CHECK VOLTAGE: IS VOLTAGE WITHIN RANGE SHOWN FOR UNIT (WITH UNIT OPERATING)?
OUTDOOR INDOOR
START-UP
IF UNIT HAS A CRANKCASE HEATER, HAS IT BEEN ON FOR 24 HOURS?
MEASURE AND RECORD THE:
AIR ENTERING OUTDOOR UNIT:
F
AIR ENTERING INDOOR UNIT:
F
DISCHARGE LINE TEMPERATURE:
F
VAPOR LINE TEMPERATURE:
F
MEASURE AND RECORD THE:
VAPOR LINE PRESSURE:
PSIG
DISCHARGE PRESSURE:
PSIG
----------------------------------------------------------------------------------------
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
Copyright 1996 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 3e 2f
PC 111 Catalog No. 534-078 Printed in U.S.A. Form 40QN-1SI Pg CL-2 4-96 Replaces: New
Loading...