Carrier 30RB080-390, 30RB060-390 User Manual

30RB060-390 Air-Cooled Chillers and
30RB080-390 Air-Cooled Chillers with
Greenspeed® Technology
Installation Instructions
AquaSnap
®

CONTENTS

Page
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . .1,2
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-73
Step 1 — Place, Rig and Mount Unit. . . . . . . . . . . . . 2
•PLACING UNIT
• MOUNTING UNIT
• RIGGING UNIT
Step 2 — Remove Compressor Rack
Holddown Bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Step 3 — Remove Compressor Shipping
Braces. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
• FOR UNITS WITH COMPRESSOR SOUND BLANKETS
Step 4 — Make Cooler Fluid, Heat Reclaim and
Drain Piping Connections . . . . . . . . . . . . . . . . . . . . 38
• FREEZE PROTECTION
• UNITS WITH HYDRONIC PUMP PACKAGE
• UNITS WITHOUT HYDRONIC PUMP PACKAGE
• UNITS WITH OPTIONAL HEAT RECLAIM
• HEAD PRESSURE CONTROL
• FOR ALL UNITS
Step 5 — Fill the Chilled Water and Heat Reclaim
Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
• WATER SYSTEM CLEANING
• WATER TREATMENT
• SYSTEM PRESSURIZATION
• FILLING THE SYSTEM(S)
• SET WATER FLOW RATE
• PUMP MODIFICATION/TRIMMING
•PUMP VFD
• SENSORLESS CONTROL (CLOSED LOOP)
• REMOTE SENSOR (CLOSED LOOP)
• REMOTE CONTROLLER (OPEN LOOP)
• PREPARATION FOR YEAR-ROUND OPERATION
• FREEZE PROTECTION
• PREPARATION FOR WINTER SHUTDOWN
• CHILLED WATER SYSTEM
• HEAT RECLAIM SYSTEM
Step 6 — Make Electrical Connections . . . . . . . . . . 57
• POWER SUPPLY
•POWER WIRING
• CONTROL POWER
• FIELD CONTROL OPTION WIRING
• DUAL CHILLER CONTROL OPTION
• CARRIER COMFORT NETWORK COMMUNICATION BUS WIRING
• NON-CCN COMMUNICATION WIRING
Step 7 — Install Accessories . . . . . . . . . . . . . . . . . . . . 70
• NAVIGATOR™ DISPLAY
• REMOTE ENHANCED DISPLAY
• LOW AMBIENT TEMPERATURE OPERATION
• MINIMUM LOAD ACCESSORY
• UNIT SECURITY/PROTECTION ACCESSORIES
• COMMUNICATION ACCESSORIES
• SERVICE OPTIONS
®
Refrigerant Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
• LEAK TESTING
• DEHYDRATION
• REFRIGERANT CHARGE
BACnet Communication Option Wiring . . . . . . . . . 71
Page

SAFETY CONSIDERATIONS

Installing, starting up, and servicing air-conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location.
Only trained, qualified installers and service mechanics should install, start up, and service this equipment.
Untrained personnel can perform basic maintenance func­tions such as cleaning coils. All other operations should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
Follow all safety codes.
Keep quenching cloth and fire extinguisher nearby when
brazing.
Wear safety glasses and work gloves.
Use care in handling, rigging, and setting bulky
equipment.
WARNING
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation. There may be more than one disconnect switch. Tag all discon­nect locations to alert others not to restore power until work is completed.
IMPORTANT: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with these instructions may cause radio interference. It has been tested and found to comply with the limits of a Class A computing device pursuant to International Standard in North America EN 61000-2/3, which are designed to provide reasonable protection against such interference when operated in a commercial environment.
CAUTION
This system uses Puron® refrigerant (R-410A), which has higher pressures than R-22 and other refrigerants. No other refrigerant can be used in this system. Failure to use gage set, hoses, and recovery systems designed to handle Puron refrigerant (R-410A) may result in equipment damage or personal injury. If unsure about equipment, consult the equipment manufacturer.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300124-01 Printed in U.S.A. Form 30RB-21SI Pg 1 1218 12-13 Replaces: 30RB-20SI
WARNING
DO NOT USE TORCH to remove any component. System contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and gog­gles and proceed as follows:
a. Shut off electrical power to unit. b. Recover refrigerant to relieve all pressure from sys-
tem using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen
and the work area should be well ventilated. Refrig­erant in contact with an open flame produces toxic gases.
d. Cut component connection tubing with tubing cutter
and remove component from unit. Use a pan to catch any oil that may come out of the lines and as a gage for how much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when nec-
essary. Oil can ignite when exposed to torch flame.
Failure to follow these procedures may result in personal injury or death.
CAUTION
DO NOT re-use compressor oil or any oil that has been exposed to the atmosphere. Dispose of oil per local codes and regulations. DO NOT leave refrigerant system open to air any longer than the actual time required to service the equipment. Seal circuits being serviced and charge with dry nitrogen to prevent oil contamination when timely repairs cannot be completed. Failure to follow these proce­dures may result in damage to equipment.

INTRODUCTION

These instructions cover installation of 30RB060-390 air­cooled liquid chillers with electronic controls and units with factory-installed options (FIOPs). See Fig. 1.
NOTE: The 30RB080-390 air-cooled chillers with Green-
®
speed
technology include high-efficiency variable condenser
fans. See Fig. 1. NOTE: Unit sizes 315-390 are modular units that are shipped
in separate sections as modules A or B as noted in position 8 of the unit model nomenclature. Installation directions specific to these units are noted in these instructions. For modules 315A, 315B, 330A, 330B, 345A, 345B, and 360B, follow all general instructions as noted for unit sizes 30RB160-170. For modules, 360A, 390A, and 390B follow instructions for 30RB190. See Table 1 for a listing of unit sizes and modular combinations.
NOTE: The nameplate for modular units contains only the first two digits in the model number. For example, 315A and 315B nameplates read 31A and 31B.
Table 1 — Modular Combinations
MODULE UNITS MODULE A MODULE B
30RBF315 30RBF160 30RBF160 30RBF330 30RBF170 30RBF160 30RBF345 30RBF170 30RBF170 30RBF360 30RBF190 30RBF170 30RBF390 30RBF190 30RBF190
NOTE: An “F” in the model number indicates the design series.

INSTALLATION

Storage —
before installation or start-up, be sure to protect the machine from construction dirt and moisture. Keep protective shipping covers in place until machine is ready for installation.
If the unit is to be stored for a period of time

Step 1 — Place, Rig and Mount the Unit

NOTE: Inspect the unit upon arrival for damage. If damage is found, file a claim right away with the shipping company.
PLACING UNIT — When considering location for the unit, be sure to consult National Electrical Code (NEC, U.S.A.) and local code requirements. Allow sufficient space for airflow, wiring, piping, and service. See Fig. 2-20. Be sure surface be­neath the unit is level, and is capable of supporting the operat­ing weight of the unit. See Fig. 21 and Tables 2-4B for unit lift­ing points, mounting and operating weights.
Locate the unit so that the condenser airflow is unrestricted both above and on the sides of the unit. Airflow and service clearances are 6 ft (1.8 m) around the unit. Acceptable clear­ance on the cooler connection side or end opposite the control box unit can be reduced to 3 ft (1 m) without sacrificing perfor­mance as long as the remaining three sides are unrestricted. Ac­ceptable clearance on the side with a control box can be re­duced to 4 ft (1.3 m) due to NEC regulations, without sacrific­ing performance as long as the remaining three sides are unrestricted. Provide ample room for servicing and removing cooler. See Fig. 2-20 for required clearances. Local codes for clearances take precedence over the manufacturer’s recom­mendations when local codes call for greater clearances.
Modular units (30RB315-390) must be installed with a min­imum separation end to end of 4 ft (1.3 m) for airflow and ser­vice clearance along with NEC regulations.
If multiple units are installed at the same site, a separation of 10 ft (3 m) between the sides of the machines is required to maintain proper airflow and minimize the chances of condens­er air recirculation.
MOUNTING UNIT — The unit may be mounted on a level pad directly on the base rails, on rails along the long axis of the machine, or on vibration isolation springs. For all units, ensure placement area is strong enough to support unit operating weight. Mounting holes are provided for securing the unit to the pad or vibration isolation springs. The base rail can be point loaded at the mounting points. The base rail is made from steel, which is formed into what is shown in Fig. 22. See Fig. 2-20 for locations of mounting points. At the mounting points, a U­shaped channel is welded into the base rail to provide a flat plate for mounting. See Fig. 23 for mounting plate dimensions.
9
The 1
/16 in. (40 mm) dimension shown is to the mounting hole
from the outside edge of the rail. NOTE: The 1
same dimension as the 1.42 in. (36 mm) flange that is turned under the base rail in Fig. 22.
Bolt the unit securely to pad or rails. If vibration isolators (field-supplied) are required for a particular installation, refer to unit weight distribution in Fig. 21 to aid in the proper selection of isolators. The 30RB units can be mounted directly on spring isolators. For each unit or module, the final unit location must be level so that oil will equalize properly.
RIGGING UNIT — The 30RB060-390 units are designed for overhead rigging and it is important that this method be used. Holes are provided in frame base channels, marked for rigging (see rigging label on unit). It is recommended that field-supplied shackles be used to facilitate lifting. Secure the shackles to the base rails at the points noted on the rigging label. See Table 2 for the number of lifting points for each unit.
Do not use a forklift truck to move the units.
9
/16 in. (40 mm) dimension in Fig. 23 is not the
2
Table 2 — Number of Lifting Points
30RB NUMBER OF LIFTING POINTS 060-110 4 120-150 6 160-300 8
315A, 315B, 330A, 330B,
345A, 345B, 360A 360B, 390A, 390B 8
6
Use spreader bars to keep cables or chains clear of unit sides. As further protection plywood sheets may be placed against sides of unit, behind cables or chains. Run cables or chains to a central suspension point so that angle from horizon­tal is not less than 45 degrees. Raise and set unit down careful­ly. See Fig. 24 and 25 for rigging centers of gravity.
Each module of the 30RB315-390 units must be rigged sep­arately. When placing unit modules for unit sizes 315-390, make sure modules are placed to permit access to the control boxes for each module.
For shipping, some domestic units and all export units are mounted on a wooden skid under entire base of unit. Skid can be removed before unit is moved to installation site. Lift the
unit from above to remove skid. See Fig. 24 and 25 for rigging center of gravity. On export units, the top skid can be used as the spreader bars. If the unit was shipped with a shipping bag, the bag must be removed to gain access to the rigging holes in the base rail. On export units with a full crate, the crate sides must be removed to aid in rigging.
If overhead rigging is not available, the unit can be moved on rollers or dragged. When unit is moved on rollers, the unit skid, if equipped, must be removed. To lift the unit, use jacks at the rigging points. Use a minimum number of rollers to distrib­ute the load such that the rollers are no more than 6 feet (1.8 m) apart. If the unit is to be dragged, lift the unit as described above, and place unit on a pad. Apply moving force to the pad, and not the unit. When in its final location, raise the unit and remove the pad.
If the unit was shipped with coil protection, it must be removed before start-up. The shipping bag for export units must be removed before start-up.
NOTE: If the application includes a remote-mounted cooler option, follow the instructions included with the accessory for cooler placement and refrigerant piping.
3
Fig. 1 — AquaSnap® Chiller Model Number Designation
LEGEND
*Refer to Table 1 on page 2 for modular unit combinations. †Sponsored by ASHRAE (American Society of Heating, Refrigerating and Air­Conditioning Engineers).
NOTE: A “Z” in position 11 indicates a special order machine. Digits following do not correspond to tables.
CRN Canadian Registration Number EMM Energy Management Module GFI-CO — Ground Fault Interrupting Convenience Outlet LON Local Operating Network SCCR Short Circuit Curr ent Rating VFD Variable Frequency Device XL Across-the-Line Start
a30-5694
30RB – Air-Cooled AquaSnap® Chiller
Design Series
Nominal Sizes
060 110 170 275 360* 070 120 190 300 390* 080 130 210 315* 090 150 225 330* 100 160 250 345*
Voltage 1 – 575-3-60 2 – 380-3-60
Condenser Coil Options
- – Aluminum Fin/Copper Tube 0 – Copper Fin/Copper Tube 1 – Aluminum Pre-Coat Fin/Copper Tube 2 – Aluminum E-Coat Fin/Copper Tube
3 – Copper E-Coat Fin/Copper Tube
4 – Microchannel (MCHX) 5 – E-Coat, Microchannel (MCHX)
Cooler Options
- – Integral Cooler, CRN (Canada) 0 – Integral Cooler, Cooler Heater, CRN (Canada) 4 – Integral Cooler, Microchannel (MCHX), CRN (Canada) 5 – Integral Cooler, Cooler Heater, Microchannel (MCHX), CRN (Canada) G – Integral Cooler, no CRN H – Integral Cooler, Cooler Heater, no CRN K – Integral Cooler, Microchannel (MCHX), no CRN L – Integral Cooler, Cooler Heater, Microchannel (MCHX), no CRN R – Integral Cooler, Microchannel (MCHX), Heat Recovery, no CRN
S – Integral Cooler, Cooler Heater, Microchannel (MCHX), Heat Recovery, no CRN
T – Integral Cooler, Microchannel (MCHX), Heat Recovery, CRN (Canada) V – Integral Cooler, Cooler Heater, Microchannel (MCHX), Heat Recovery,
CRN (Canada)
Hydronics Option†
- – No Pump Installed 0 – Single Pump, 3 HP 1 – Single Pump, 5 HP 2 – Single Pump, 7.5 HP
3 – Single Pump, 10 HP
4 – Single Pump, 15 HP 6 – Dual Pump, 3 HP 7 – Dual Pump, 5 HP
8 – Dual Pump, 7.5 HP, Low Head
9 – Dual Pump, 7.5 HP, High Head B – Dual Pump, 10 HP C – Dual Pump, 15 HP F – Single Pump, 3 HP with VFD G – Single Pump, 5 HP with VFD H – Single Pump, 7.5 HP with VFD J – Single Pump, 10 HP with VFD K – Single Pump, 15 HP with VFD M – Dual Pump, 3 HP with VFD N – Dual Pump, 5 HP with VFD P – Dual Pump, 7.5 HP, Low Head with VFD T – Dual Pump, 7.5 HP, High Head with VFD Q – Dual Pump, 10 HP with VFD R – Dual Pump, 15 HP with VFD Z – Special order designation
5 – 208/230-3-60 6 – 460-3-60
SEE NEXT PAGE
FOR REMAINDER
OF MODEL NUMBER
NOMENCLATURE
RB
190
318
4
Packaging/Security Options L – No Packaging 0 – Skid 1 – Skid, Top Crate, Bag
3 – Coil Trim Panels
4 – Skid, Coil Trim Panels 5 – Skid, Top Crate, Bag, Coil Trim Panels 7 – Coil Trim Panels, Upper and Lower Grilles
8 – Skid, Coil Trim Panels, Upper and Lower Grilles
9 – Skid, Top Crate, Bag, Coil Trim Panels, Upper and Lower Grilles C – Trim Panels, Upper and Lower Grilles, Upper Hail Guards D –
Skid, Trim Panels, Upper and Lower Grilles, Upper Hail Guards
FSkid, Top Crate, Bag, Trim Panels, Upper and Lower Grilles, Upper Hail Guards
H – Skid, Full End Covers J – Skid, Top Crate, Bag, Full End Covers K – Full End Covers
Controls/Communication Options
- – None 0 – EMM 1 – Remote Service Port, GFI-CO 2 – EMM, Remote Service Port, GFI-CO
3 – BACnet† Communication
4 – BACnet Communication, EMM 5 – BACnet Communication, Remote Service Port, GFI-CO 6 – BACnet Communic
ation, EMM, Remote Service Port, GFI-CO 7 – BACnet Translator 8 – BACnet Translator, EMM
9 – BACnet Translator, Remote Service Port, GFI-CO B – BACnet Translator, EMM, Remote Service Port, GFI-CO H – LON Translator J – LON Translator, EMM K – LON Translator, Remote Service Port, GFI-CO L – LON Translator, EMM, Remote Service Port, GFI-CO
Electrical/Low Sound Options
- – Single Point Power Connections, XL, Terminal Block 0 – Single Point Power Connections, XL, Terminal Block, High SCCR
3 – Dua
l Point Power Connections, XL, Terminal Block
4 – Dual Point Power Connections, XL, Terminal Block, High SCCR 7 – Single Point Power Connections, XL, Non-Fused Disconnect
8 – Single Point Power Connections, XL, Non-Fused Disconnect, High SCCR
C – Dual Point Power Connections, XL, Non-Fused Disconnect D – Dual Point Power Connections, XL, Non-Fused Disconnect, High SCCR G – Single Point Power Connections, XL, Terminal Block, Cmpr Blankets H – Single Point Power Connections, XL, Terminal Block, Cmpr Blankets, High SCCR J – Dual Point Power Connections, XL, Terminal Block, Cmpr Blankets K – Dual Point Power Connections, XL, Termin
al Block, Cmpr Blankets, High SCCR
L – Single Point Power Connections, XL, Non-Fused Disconnect, Cmpr Blankets M – Single Point Power Connections, XL, Non-Fused Disconnect, Cmpr Blankets,
High SCCR
N – Dual Point Power Connections, XL, Non-Fused Disconnect, Cmpr Blankets P – Dual Point Power Connections, XL, Non-Fused Disconnect, Cmpr Blankets,
High SCCR QSingle Point Power Connections, XL, Terminal Block, Cmpr Blankets, Cmpr Enclosures RSingle Point Power Connections, XL, Terminal Block, Cmpr Blankets, Cmpr Enclosures, High
SCCR S – Dual Point Power Connections, XL, Terminal Block, Cmpr Blankets, Cmpr Enclosures T – Dual Point Power Connections, XL, Terminal Block, Cmpr Blankets, Cmpr Enclosures, High SCCR VSingle Point Power Connections, XL, Non-Fused Disconnect, Cmpr Blankets, Cmpr Enclosures WSingle Point Power Connections, XL, Non-Fused Disconnect, Cmpr Blankets, Cmpr Enclosures, High SCCR X – Dual Point Power Connections, XL, Non-Fused Disconnect, Cmpr Blankets, Cmpr Enclosures W – Dual Point Power Connections, XL, Non-Fus
ed Disconnect, Cmpr Blankets,
Cmpr Enclosures, High SCCR
Refrigeration Circuit Options
- – No Suction Line Insulation 0 – Suction Insulation 1 – Suction Service Valves 2 – Low Ambient Head Pressure Control Operation 3Suction Insulation, Suction Service Valves 4 – Suction Insulation, Low Ambient Head Pressure Control Operation 5 – Suction Service Valves, Low Ambient Head Pressure Control Oper
ation
6 Suction Insulation, Service Valves, Low Ambient Head Pressure Control Operation 7 – Minimum Load Control
8Suction Insulation, Minimum Load Control Operation 9 – Suction Service Valves, Minimum Load Control Operation B – Low Ambient Operation, Minimum Load Control Operation C – Suction Insulation, Suction Service Valves, Minimum Load
Control Operation
D – Suction In
sulation, Low Ambient Head Pressure Control Operation,
Minimum Load Control Operation
F Suction Service Valves, Low Ambient Head Pressure Control Operation, Minimum Load Control Operation G Suction Insulation, Suction Service Valves, Low Ambient Head Pressure Control, Operation, Minimum Load Control Operation
H – Suction Service Valves, High-Efficiency Variable Condenser Fans J – Suction Insula
tion, Suction Service Valve, High-Efficiency Variable
Condenser Fans
K – High-Efficiency Variable Condenser Fans L – Suction Insulation, High-Efficiency Variable Condenser Fans M – Suction Service Valves, High-Efficiency Variable Condenser Fans,
Minimum Load Control Operation NSuction Insulation, Suction Service Valve, High-Efficiency Variable Condenser Fans, Minimum Load Control Oper
ation
P – High-Efficiency Variable Condenser Fans, Minimum Load Control Operation Q – Suction Insulation, High-Efficiency Variable Condenser Fans,
Minimum Load Control Operation
F
SEE PREVIOUS PAGE
FOR REMAINDER
OF MODEL NUMBER
NOMENCLATURE
RB 190
8
6
Fig. 1 — AquaSnap® Chiller Model Number Designation (cont)
a30-5704
LEGEND
*Refer to Table 1 on page 2 for modular unit combinations. †Sponsored by ASHRAE (American Society of Heating, Refrigerating and Air­Conditioning Engineers).
NOTE: A “Z” in position 11 indicates a special order machine. Digits following do not correspond to tables.
CRN Canadian Registration Number EMM Energy Management Module GFI-CO — Ground Fault Interrupting Convenience Outlet LON Local Operating Network SCCR Short Circuit Current Rating VFD Variable Frequency Device XL Across-the-Line Start
5
2281.37
89.82[]
UNIT MOUNTING1575.30
62.02[]
298.45
11.75[]
PS
y
376.01
14.80[]
2236.08
88.03[]
1447.8[57.0]
PIPING ENTRANCE AREA1697.58
66.83[]
281.03
11.06[]
414.47
16.32[]
PD
Z
PS
Z
200.00
7.87[]
40.00
1.57[]
100.00
3.94[]
CG
x
CG
y
246.36
9.70[]
190.00
7.48[]
336.50
13.25[]
804.35
31.67[]
2393.08
94.22[]
PS
x
1714.90
67.52[]
408.89
16.10[]
408.89
16.10[]
PD
x
518.30
20.41[]
PD
y
860.93
33.89[]
2159.89
85.04[]
38.09
1.50[]
2438.40
[96.00]
RIGGING HOLE
38.00
1.50[]
949.14
37.37[]
215.73
8.49[]
WEIGHT
CU/AL
lb/kg
MAX WEIGHT
CU/AL PUMP
lb/kg
WEIGHT
CU/CU
lb/kg
MAX WEIGHT
CU/CU PUMP
lb/kg
WEIGHT
MCHX
lb/kg
MAX WEIGHT
MCHX PUMP
lb/kg
CENTER OF GRAVITY PUMP SUCTION (PS) PUMP DISCHARGE (PD)
CGx
MM [INCH]
CGy
MM [INCH]
X
.25
Y
.25
Z
.25
X
.25
Y
.25
Z
.25
30RB-060
4111
1869
4944
2247
4593
2088
5426
2466
3783
1716
4616
2094
1164
[45.82]
1038
[40.86]
675.6
[26.6]
309.9
[12.2]
353.1
[13.9]
381.0
[15.0]
482.6
[19.0]
188.0
[7.4]
30RB-070
4317
1932
5150
2641
4799
2181
5632
2560
3978
1804
4811
2182
1165
[45.86]
1013
[39.88]
675.6
[26.6]
309.9
[12.2]
353.1
[13.9]
381.0
[15.0]
482.6
[19.0]
188.0
[7.4]
COIL SERVICE AREA
NO PUMP PACKAGE
ENTERING WATER
4" VICTAULIC
(SEE NOTE 4)
COOLER VENT 1/4"
PUMP PACKAGE
LEAVING WATER
4" VICTAULIC
COOLER DRAIN
3/4" NPT
PUMP PACKAGE ENTERING
WATER 4" VICTAULIC
SEE DETAIL
A
CONTROL/POWER BOX
ALL VOLTAGES
AIR FLOW
7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD POWER WIRING
BACnet COMMUNICATION
OPTION KNOCKOUT
FOR 1/2" CONDUIT
COOLER TUBE
SERVICE AREA
SERVICE AREA 1219.2[48.0] FROM EACH SIDE OF THE UNIT
CIRCUIT
A
COMPRESSOR
CIRCUIT
B
COMPRESSORS
COIL SERVICE AREA
DETAIL
A
SCALE 1:2
22.2[.87] MOUNTING HOLE
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6 (1.8 m) from solid surface.
2. All pumps have drains located at the bottom of volute
for draining.
3. Temperature relief devices located on suction line,
liquid line and filter drier of each circuit and have
1
/
4
flare connection.
4. Units without a pump package have the same leaving
water connection, Y and Z dimensions (entering
water), and Pump Discharge X dimensions as units
with a pump package.
5. Dimensions are in mm [inches].
6. Allow 8 ft (2.4 m) of service access on either side of
unit for condenser coil removal.
a30-4732
MCHX — Microchannel Condenser Coil
Fig. 2 — 30RB060, 070 Air-Cooled Chiller Dimensions
6
0.75[]
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6 (1.8 m) from
solid surface.
2. All pumps have drains located at the
bottom of volute for draining.
3. Temperature relief devices located on
suction line, liquid line and filter drier
of each circuit and have
1
/
4
flare con-
nection.
4. Units without a pump package have
the same leaving water connection, Y
and Z dimensions (entering water),
and Pump Discharge X dimensions
as units with a pump package.
5. Dimensions are in mm [inches].
6. Allow 8 ft (2.4 m) of service access on
either side of unit for condenser coil
removal.
a30-4733
MCHX — Microchannel Condenser Coil
Fig. 3 — 30RB080 Air-Cooled Chiller Dimensions
19.00
RIGGING HOLE
1.77[]
45.00
22.2[.87]
200.00
3.94[]
100.00
A
SCALE 11:32
DETAIL
MOUNTING HOLE
7.87[]
AIR FLOW
2438.40
[96.00]
DISPLAY
SCROLLING MARQUEE
COIL SERVICE AREA
POWER BOX 230V
CONTROL/POWER BOX
380V,460V,575V
7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD POWER WIRING
(FEB)
(230V ONLY)
FAN ELECTRICAL BOX
FIELD CONTROL WIRING
A
7.48[]
190.00
34.02[]
864.00
13.25[]
336.50
1.50[]
38.09
949.14
9.70[]
246.36
BACnet COMMUNICATION
OPTION KNOCKOUT
FOR 1/2" CONDUIT
8.49[]
215.73
37.37[]
85.035[]
2159.89
UNIT MOUNTING
CG
A
CIRCUIT
COMPRESSORS
B
CIRCUIT
COMPRESSORS
SERVICE AREA 1219.2[48.0] FROM EACH SIDE OF THE UNIT
COOLER TUBE
SERVICE AREA
1447.8 [57.00]
31.04[]
788.34
z
PD
88.03[]
2236.08
y
15.90[]
403.76
x
CG
66.64[]
1692.75
PIPING ENTRANCE AREA
z
11.67[]
PS
296.47
COIL SERVICE AREA
NO PUMP PACKAGE
ENTERING WATER
4" VICTAULIC
1/4" NTP
PUMP PACKAGE
COOLER VENT
89.82[]
2281.37
SEE DETAIL
(SEE NOTE 4)
3/4" NPT
COOLER DRAIN
4" VICTAULIC
LEAVING WATER
y
PS
15.23[]
386.88
PUMP PACKAGE
x
PD
y
PD
16.10[]
408.90
20.52[]
521.16
UNIT MOUNTING1575.30
ENTERING WATER
4" VICTAULIC
62.02[]
x
PS
16.10[]
408.89
Z
Y
94.22[]
X
2393.08
Z
Y
X
CGy
CGx
CENTER OF GRAVITY PUMP SUCTION (PS) PUMP DISCHARGE (PD)
MCHX PUMP
MAX WEIGHT
MCHX
WEIGHT
MAX WEIGHT
CU/CU PUMP
CU/CU
WEIGHT
.25
170.2
.25
497.8
.25
381.0
.25
353.1
.25
309.9
.25
675.6
1012
MM [INCH]
1206
MM [INCH]
5190
lb/kg
4267
lb/kg
6005
lb/kg
5082
lb/kg
[6.7]
[19.6]
[15.0]
[13.9]
[12.2]
[26.6]
[39.84]
[47.48]
2355
1934
2730
2310
7
lb/kg
MAX WEIGHT
CU/AL PUMP
CU/AL
lb/kg
WEIGHT
5523
2511
4600
2091
30RB-080
2281.37
89.82[]
UNIT MOUNTING1479.82
58.26[]
376.01
14.80[]
2236.08
88.03[]
1447.8[57.0]
200.00
7.87[]
45.00
1.77[]
100.00
3.94[]
CG
x
CG
y
246.36
9.70[]
190.00
7.48[]
336.50
13.25[]
804.35
31.67[]
2393.08
94.22[]
456.63
17.98[]
456.63
17.98[]
516.04
20.32[]
40.91
1.61[]
2154.26
84.81[]
126.80
4.99[]
PIPING ENTRANCE AREA
612.76 24.12[]
473.75
18.65[]
315.25
12.41[]
2X 344.79
13.57[]
2312.82
91.06[]
591.91
23.30[]
2X 674.81
26.57[]
376.01
14.80[]
1447.77
57.00[]
1387.21
54.61[]
1891.29
74.46[]
85.33
3.36[]
2052.75
80.82[]
215.73
8.49[]
949.14
37.37[]
38.00
1.496[]
WEIGHT
MCHX
lb/kg
CENTER OF GRAVITY
CGx
MM [INCH]
CGy
MM [INCH]
30RB-060
4703
2133
1235
[48.62]
1082
[42.60]
30RB-070
4898
2222
1198
[47.17]
1093
[43.03]
30RB-080
5187
2353
1199
[47.20]
1120
[44.10]
HR CONDENSER TUBE
SERVICE AREA
COOLER DRAIN
3/4" NPT
SEE DETAIL
A
1/4" NPT PRV
CONTROL/POWER BOX
ALL VOLTAGES
AIR FLOW
7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD POWER WIRING
BACnet COMMUNICATION
OPTION KNOCKOUT
FOR 1/2" CONDUIT
COOLER VENT 1/4" NPT
COOLER TUBE
SERVICE AREA
SERVICE AREA 1219.2[48.0] FROM EACH SIDE OF THE UNIT
CIRCUIT
A
COMPRESSOR
CIRCUIT
B
COMPRESSORS
DETAIL A
SCALE 1:2
RIGGING HOLE
22.2[.87] MOUNTING HOLE
COOLER LEAVING
WATER 4" VICTAULIC
CONDENSER ENTERING
WATER 3.0" VICTAULIC
CONDENSER LEAVING
WATER 3.0" VICTAULIC
COOLER ENTERING
WATER 4" VICTAULIC
CONDENSER DRAIN 3/8" NPT
CONDENSER VENT 1/4" NPT
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6 (1.8 m) from solid surface.
2. Temperature relief devices located on suction line,
liquid line and filter drier of each circuit and have
1
/
4
flare connection.
3. Dimensions are in mm [inches].
4. Allow 8 ft (2.4 m) of service access on either side of
unit for condenser coil removal.
a30-4734
LEGEND
HR Heat Reclaim
MCHX — Microchannel Condenser Coil
PRV Pressure Relief Valve
Fig. 4 — 30RB060-080 Air-Cooled Chiller with Heat Reclaim Option Dimensions
8
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6(1.8 m) from solid surface.
2. All pumps have drains located at the bottom of
volute for draining.
3. Temperature relief devices located on suction
line, liquid line and filter drier of each circuit and
have
1
/
4
flare connection.
4. Units without a pump package have the same
leaving water connection, Y and Z dimensions
(entering water), and Pump Discharge X dimen-
sions as units with a pump package.
5. Dimensions are in mm [inches].
6. Allow 8 ft (2.4 m) of service access on either
side of unit for condenser coil removal.
a30-4711
MCHX — Microchannel Condenser Coil
Fig. 5 — 30RB090, 100 Air-Cooled Chiller Dimensions
9
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6 (1.8 m) from solid surface.
Airflow Side — 8 (2.4 m) required for coil service
area.
2. All pumps have drains located at the bottom of
volute for draining.
3. Temperature relief devices ocated on suction line,
liquid line and filter drier of each circuit and have
1
/
4
flare connection.
4. No pump package leaving water connection is
same size and has same Y and Z dimensions as
entering water. Also has same PDx dimension as
pump package.
5. Dimensions are in mm [inches]. MCHX — Microchannel Condenser Coil
Fig. 6 — 30RB110 Air-Cooled Chiller Dimensions
7.48[]
190.00
1.57[]
POWER BOX 230V
CONTROL/POWER BOX
x
CG
CIRCUIT A
CIRCUIT B
1.50[]
38.00
RIGGING HOLE
y
CG
COMPRESSORS
COMPRESSORS
45.00
1.77[]
88.03[]
2236.08
22.2[.87]
200.00
3.94[]
100.00
761.94
MOUNTING HOLE
7.87[]
DETAIL B
SCALE 3:16
30.00[]
AIR FLOW
36.07[]
916.15
96.30[]
2446.09
PIPING ENTRANCE AREA
2438.40
[96.00]
COIL SERVICE AREA
COIL SERVICE AREA
380V,460V,575V
7/8" KNOCKOUT TO BE
USED FOR LOCATING
(FEB)
(230V ONLY)
FAN ELECTRICAL BOX
DISPLAY
SCROLLING MARQUEE
FIELD CONTROL WIRING
39.07[]
992.44 NO PUMP PACKAGE
FIELD POWER WIRING
33.89[]
860.81
ENTERING WATER
6" VICTAULIC
(SEE NOTE 4)
39.89
13.25[]
336.50
36.94[]
938.35
9.70[]
246.36
84.89[]
2156.30
UNIT MOUNTING
BACnet COMMUNICATION
OPTION KNOCKOUT
FOR 1/2" CONDUIT
8.49[]
215.73
15.43[]
391.88
16.10[]
408.89
B
SEE DETAIL
UNIT MOUNTING2769.30
107.42[]
2728.56
6" VICTAULIC
20.31[]
515.82
109.03[]
PUMP PACKAGE ENTERING WATER
141.22[]
3587.08
Z
.25
233.7
[9.2]
Y
.25
391.2
[15.4]
X
.25
340.4
[13.4]
Z
.25
60.9
[2.4]
Y
.25
281.9
[11.1]
X
.25
856.0
[33.7]
CGy
997
[39.25]
MM [INCH]
CGx
1713
CENTER OF GRAVITY PUMP SUCTION (PS) PUMP DISCHARGE (PD)
[67.44]
MM [INCH]
6950
3152
lb/kg
MCHX PUMP
MAX WEIGHT
MCHX
6027
2734
lb/kg
WEIGHT
PS
PD
SERVICE AREA 1219.2[48.0] FROM EACH SIDE OF THE UNIT
1447.8[57.0]
COOLER TUBE
SERVICE AREA
8166
3712
x
PS
z
z
8.85[]
224.84 1/4" NTP
COOLER VENT
PUMP PACKAGE
89.82[]
2281.37
6" VICTAULIC
LEAVING WATER
y
PS
y
PD
x
PD
16.10[]
408.89
3/4" NPT
COOLER DRAIN
lb/kg
MAX WEIGHT
CU/CU PUMP
CU/CU
lb/kg
WEIGHT
lb/kg
MAX WEIGHT
CU/AL PUMP
CU/AL
lb/kg
WEIGHT
7243
3292
7442
3383
6519
2963
30RB-110
10
7.48[]
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6 (1.8 m) from solid surface.
2. Temperature relief devices located on suction line,
liquid line and filter drier of each circuit and have
1
/
4
flare connection.
3. Dimensions are in mm [inches].
4. Allow 8 ft (2.4 m) of service access on either side of
unit for condenser coil removal.
a30-4735
LEGEND
HR Heat Reclaim
MCHX — Microchannel Condenser Coil
Fig. 7 — 30RB090-110 Air-Cooled Chiller with Heat Reclaim Option Dimensions
190.00
POWER BOX 230V
CONTROL/POWER BOX
380V,460V,575V
1.77[]
45.00
1.50[]
38.00
RIGGING HOLE
74.45[]
1891.00
88.03[]
2236.08
x
CG
CIRCUIT A
COMPRESSORS
y
CG
22.2[.87] MOUNTING HOLE
7.87[]
200.00
3.94[]
100.00
HR CONDENSER TUBE
DETAIL B
SCALE 3:16
SERVICE AREA
1447.80
30.00[]
761.94
2123.60
57.00[]
83.61[]
AIR FLOW
(FEB)
(230V ONLY)
FAN ELECTRICAL BOX
DISPLAY
SCROLLING MARQUEE
FIELD CONTROL WIRING
8.49[]
215.73
7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD POWER WIRING
13.25[]
336.50
36.94[]
938.35
9.70[]
246.36
BACnet COMMUNICATION
OPTION KNOCKOUT
FOR 1/2" CONDUIT
16.10[]
408.89
128.24[]
UNIT MOUNTING2769.30
3257.41
109.03[]
39.89
B
SEE DETAIL
84.894[]
2156.30
UNIT MOUNTING
1.570[]
141.22[]
3587.08
CIRCUIT B
COMPRESSORS
CONDENSER DRAIN
3/8" NPT
55.30[]
1404.67
SERVICE AREA 1219.2[48.0] FROM EACH SIDE OF THE UNIT
1447.8[57.0]
COOLER TUBE
SERVICE AREA
24.12[]
612.76
PIPING ENTRANCE AREA
8.61[]
218.65
2281.37
COOLER LEAVING
WATER 6" VICTAULIC
CONDENSER LEAVING
1/4" NPT
COOLER VENT
89.82[]
725.63
WATER 3.0" VICTAULIC
28.57[]
COOLER ENTERING
16.10[]
408.89
3/4" NPT
COOLER DRAIN
18.65[]
473.75
15.43[]
391.88
24.98[]
2X 634.55
13.59[]
2X 345.08
1/4" NPT
CONDENSER VENT
WATER 6" VICTAULIC
CONDENSER ENTERING
WATER 3.0" VICTAULIC
12.41[]
315.25
CGy
MM [INCH]
CGx
CENTER OF GRAVITY
MM [INCH]
MCHX
lb/kg
WEIGHT
1064
[41.89]
1759
[69.25]
7133
3236
30RB-110
1067
[42.00]
1676
[65.98]
6769
3071
30RB-100
1088
[42.84]
1689
[66.50]
6555
2974
30RB-090
11
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6 (1.8 m) from solid surface.
Airflow side — 82.4 mrequired for coil service area.
2. All pumps have drains located at the bottom of volute for draining.
3. Temperature relief devices located on suction line, liquid line and filter drier
of each circuit and have
1
/
4
flare connection.
4. No pump package leaving water connection is same size and has same Y
and Z dimensions as entering water. Also has same PDx dimension as
pump package.
5. Dimensions are in mm [inches].
a30-5333
MCHX — Microchannel Condenser Coil
Fig. 8 — 30RB120, 130 Air-Cooled Chiller Dimensions
12
2236.08
88.03[]
761.94
30.00[]
859.04
33.82[]
CG
y
x
CG
2281.37
89.82[]
4781.08
188.23[]
1159.04
45.63[]
391.88
15.43[]
408.89
16.10[]
408.89
16.10[]
246.36
9.70[]
336.50
13.25[]
190.00
7.48[]
200.00
7.87[]
100.00
3.94[]
45.00
1.77[]
RIGGING HOLE
38.00
1.50[]
1447.8[57.0]
UNIT MOUNTING
1981.65
78.02[]
UNIT MOUNTING
1981.65
78.02[]
864.00
34.02[]
39.89
1.57[]
UNIT MOUNTING
2156.30
84.89[]
PIPING ENTRANCE AREA
600.00
23.62[]
1070.10
42.13[]
171.47
6.75[]
PIPING ENTRANCE AREA
507.14
19.97[]
2X 343.33
13.52[]
342.96
13.50[]
553.77
21.80[]
3410.98 134.29[]
1892.75
74.52[]
2659.08
104.69[]
1000.00
[39.37]
3773.58
148.57[]
PIPING ENTRANCE AREA
600.00
23.62[]
507.19
19.97[]
739.49
29.11[]
739.49
29.11[]
507.19
19.97[]
215.73
8.49[]
938.35
36.94[]
WEIGHT
MCHX
lb/kg
CENTER OF GRAVITY
CGx
MM [INCH]
CGy
MM [INCH]
30RB-120
8405
3813
2413
[95.00]
1089
[42.87]
HR CONDENSER TUBE
SERVICE AREA
CIRCUIT B
COMPRESSORS
COOLER DRAIN
3/4" NPT
COOLER
ENTERING WATER
6" VICTAULIC
SEE DETAIL
B
CONDENSER DRAIN
3/8" NPT
AIR FLOW
7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD POWER WIRING
SCROLLING MARQUEE
DISPLAY
FIELD CONTROL WIRING
FAN ELECTRICAL BOX
(230V ONLY)
(FEB)
POWER BOX 230V
CONTROL/POWER BOX
380V,460V,575V
BACnet COMMUNICATION
OPTION KNOCKOUT
FOR 1/2" CONDUIT
COOLER TUBE
SERVICE AREA
SERVICE AREA 1219.2[48.0] FROM EACH SIDE OF THE UNIT
CIRCUIT A
COMPRESSORS
COOLER VENT
1/4" NPT
DETAIL
B
SCALE 3:16
22.2[.87] MOUNTING HOLE
CONDENSER VENT
1/4" NPT
COOLER
LEAVING WATER
6" VICTAULIC
CONDENSER
LEAVING WATER
5.0" VICTAULIC
CONDENSER
ENTERING WATER
5.0" VICTAULIC
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6 (1.8 m) from solid sur-
face.
2. Temperature relief devices located on suc-
tion line, liquid line and filter drier of each
circuit and have
1
/
4
flare connection.
3. Dimensions are in mm [inches].
4. Allow 8 ft (2.4 m) of service access on
either side of unit for condenser coil
removal.
a30-4736
LEGEND
HR Heat Reclaim
MCHX — Microchannel Condenser Coil
Fig. 9 — 30RB120 Air-Cooled Chiller with Heat Reclaim Option Dimensions
13
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6 (1.8 m) from solid surface.
2. Temperature relief devices located on suction line, liquid line and fil-
ter drier of each circuit and have
1
/
4
flare connection.
3. Dimensions are in mm [inches].
4. Allow 8 ft (2.4 m) of service access on either side of unit for con-
denser coil removal.
LEGEND
HR Heat Reclaim
MCHX — Microchannel Condenser Coil
Fig. 10 — 30RB130 Air-Cooled Chiller with Heat Reclaim Option Dimensions
a30-4737
14
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6 (1.8 m) from solid surface.
2. All pumps have drains located at the bottom of volute for draining.
3. Temperature relief devices located on suction line, liquid line and filter drier of
each circuit and have
1
/
4
flare connection.
4. Units without a pump package have the same leaving water connection, Y and Z
dimensions (entering water), and Pump Discharge X dimensions as units with a
pump package.
5. Dimensions are in mm [inches].
6. Allow 8 ft (2.4 m) of service access on either side of unit for condenser coil
removal.
Fig. 11 — 30RB150 Air-Cooled Chiller Dimensions
MCHX — Microchannel Condenser Coil
15
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6 (1.8 m) from solid surface.
2. Temperature relief devices located on suction line, liquid line and filter drier
of each circuit and have
1
/
4
flare connection.
3. Dimensions are in mm [inches].
4. Allow 8 ft (2.4 m) of service access on either side of unit for condenser coil
removal.
a30-4738
LEGEND
HR Heat Reclaim
MCHX — Microchannel Condenser Coil
Fig. 12 — 30RB150 Air-Cooled Chiller with Heat Reclaim Option Dimensions
16
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6 (1.8 m) from solid surface.
2. All pumps have drains located at the bottom of volute for draining.
3. Temperature relief devices located on suction line, liquid line and filter drier of each circuit and have
1
/
4
flare connection.
4. Units without a pump package have the same leaving water connection, Y and Z dimensions (entering
water), and Pump Discharge X dimensions as units with a pump package.
5. Dimensions are in mm [inches].
6. Allow 8 ft (2.4 m) of service access on either side of unit for condenser coil removal.
a30-4715
MCHX — Microchannel Condenser Coil
Fig. 13 — 30RB160, 170, 315A/B, 330A/B, 345A/B, 360B Air-Cooled Chiller Dimensions
5975.08
235.24[]
PS
x
4164.06
163.94[]
408.89
16.10[]
UNIT MOUNTING
2769.30
109.03[]
408.89
16.10[]
PD
x
923.39
36.35[]
PD
y
PS
y
422.24
16.62[]
2073.54
81.64[]
2281.37
89.82[]
864.00
34.02[]
2016.54
79.39[]
800.00
31.50[]
101.20
3.98[]
2236.08
88.03[]
PS
z
PD
z
CG
y
CG
x
1447.8
[57.00]
200.00
7.87[]
100.00
3.94[]
769.51
30.30[]
1483.83
58.42[]
1456.33
57.34[]
1993.25
78.47[]
PIPING ENTRANCE AREA3212.33
126.47[]
755.58
29.75[]
246.36
9.70[]
190.00
7.48[]
336.50
13.25[]
UNIT MOUNTING
2388.00
94.016[]
400.00
15.75[]
200.00
7.87[]
240.00
9.45[]
39.89
1.57[]
UNIT MOUNTING
2156.30
84.89[]
2438.40
[96.00]
RIGGING HOLE
38.00
1.50[]
938.35
36.94[]
215.73
8.49[]
WEIGHT
CU/AL
lb/kg
MAX WEIGHT
CU/AL PUMP
lb/kg
WEIGHT
CU/CU
lb/kg
MAX WEIGHT
CU/CU PUMP
lb/kg
WEIGHT
MCHX
lb/kg
MAX WEIGHT
MCHX PUMP
lb/kg
CENTER OF GRAVITY PUMP SUCTION (PS) PUMP DISCHARGE (PD)
CGx
MM [INCH]
CGy
MM [INCH]
X
.25
Y
.25
Z
.25
X
.25
Y
.25
Z
.25
30RB-160
315A/B,330B
10266
4666
11511
5232
11472
5215
12717
5781
9475
4297
10720
4860
3065
[120.66]
994
[39.13]
1808.48
[71.2]
381
[15.0]
297.2 [11.7]
883.92
[34.8]
421.64
[16.6]
231.14
[9.1]
30RB-170
330A,345A/B,360B
10601
4819
11846
5385
11807
5367
13052
5933
9799
4443
11044
5009
3114
[122.59]
978
[30.5]
1808.48
[71.2]
381
[15.0]
297.2 [11.7]
883.92
[34.8]
421.64
[16.6]
231.14
[9.1]
AIR FLOW
COOLER TUBE
SERVICE AREA
SERVICE AREA 1219.2[48.0] FROM EACH SIDE OF THE UNIT
A
A
FAN ELECTRICAL BOX
(FEB)
ALL VOLTAGES
VIEW-A-A
CIRCUIT A
COMPRESSORS
CIRCUIT B
COMPRESSORS
COOLER VENT 1/4" NPT
PUMP PACKAGE
LEAVING WATER
6" VICTAULIC
COOLER DRAIN
3/4" NPT}
NO PUMP PACKAGE
ENTERING WATER
6" VICTAULIC
(SEE NOTE 4)
PUMP PACKAGE
ENTERING WATER
6" VICTAULIC
SCROLLING MARQUEE
DISPLAY
FIELD CONTROL WIRING
POWER BOX 230V ONLY (CKT A)
7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD POWER WIRING
(DUAL POINT 230V ONLY)
(DUAL POWER NFD
CIRCUIT B 380,460,575V
ONLY)
BACnet COMMUNICATION
OPTION KNOCKOUT
FOR 1/2" CONDUIT
COIL SERVICE AREA
COIL SERVICE AREA
SEE DETAIL
B
7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD POWER WIRING
(DUAL AND SINGLE POINT)
POWER BOX 230V (CKT B)
POWER BOX
380V,460V,575V (CKT A,B)
DETAIL
B
SCALE 3:16
22.2 [.87] MOUNTING HOLE
17
5975.08
235.24[]
408.89
16.10[]
UNIT MOUNTING
2769.30
109.03[]
408.89
16.10[]
422.24
16.62[]
2073.54
81.64[]
2281.37
89.82[]
864.00
34.02[]
2016.54
79.39[]
800.00
31.50[]
101.20
3.98[]
2236.08
88.03[]
CG
y
CG
x
1447.80
[57.00]
200.00
7.87[]
100.00
3.94[]
1773.54
69.82[]
246.36
9.70[]
190.00
7.48[]
336.50
13.25[]
UNIT MOUNTING
2388.00
94.02[]
400.00
15.75[]
200.00
7.87[]
240.00
9.45[]
39.89
1.57[]
UNIT MOUNTING
2156.30
84.89[]
PIPING ENTRANCE AREA
600.00 23.62[]
191.86
7.55[]
PIPING ENTRANCE AREA
631.30
24.85[]
400.00
[15.75]
553.81
21.80[]
343.81
13.54[]
2X 343.33
13.52[]
3344.61
131.68[]
1892.75
74.52[]
4459.11
175.56[]
PIPING ENTRANCE AREA
600.00
23.62[]
587.63
23.14[]
2X 503.37
19.82[]
2X 769.85
30.31[]
5087.45
200.29[]
938.35
36.94[]
215.71
8.49[]
38.00
1.496[]
WEIGHT
MCHX
lb/kg
CENTER OF GRAVITY
CGx
MM [INCH]
CGy
MM [INCH]
30RB-160
315A/B,330B
10991
4986
3124
[122.99]
1001
[39.41]
30RB-170
330A,345A/B,360B
11315
5133
3168
[124.74]
986
[38.82]
AIR FLOW
COOLER TUBE
SERVICE AREA
SERVICE AREA 1219.2[48.0] FROM EACH SIDE OF THE UNIT
A
A
VIEW-A-A
COOLER VENT
1/4" NPT
COOLER DRAIN
3/4" NPT
COOLER
ENTERING WATER
6" VICTAULIC
COOLER
LEAVING WATER
6" VICTAULIC
CONDENSER DRAIN
3/8" NPT
SCROLLING MARQUEE
DISPLAY
FIELD CONTROL WIRING
FAN ELECTRICAL BOX
(FEB)
ALL VOLTAGES
BACnet COMMUNICATION
OPTION KNOCKOUT
FOR 1/2" CONDUIT
POWER BOX 230V ONLY (CKT A)
7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD POWER WIRING
(DUAL POINT 230V ONLY)
CIRCUIT A
COMPRESSORS
CIRCUIT B
COMPRESSORS
HR CONDENSER TUBE
SERVICE AREA
SEE DETAIL
B
7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD POWER WIRING
(DUAL AND SINGLE POINT)
POWER BOX 230V (CKT B)
POWER BOX
380V,460V,575V (CKT A,B)
DETAIL
B
SCALE 3:16
22.2 [.87] MOUNTING HOLE
CONDENSER
LEAVING WATER
5.0" VICTAULIC
CONDENSER
ENTERING WATER
5.0" VICTAULIC
CONDENSER VENT
1/4" NPT
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6 (1.8 m) from solid surface.
2. Temperature relief devices located on suction line, liquid line and filter drier
of each circuit and have
1
/
4
flare connection.
3. Dimensions are in mm [inches].
4. Allow 8 ft (2.4 m) of service access on either side of unit for condenser coil
removal.
a30-4739
LEGEND
HR Heat Reclaim
MCHX — Microchannel Condenser Coil
Fig. 14 — 30RB160,170 Air-Cooled Chiller with Heat Reclaim Option Dimensions
18
B
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6 (1.8 m) from solid surface.
2. All pumps have drains located at the bottom of volute for draining.
3. Temperature relief devices located on suction line, liquid line and
filter drier of each circuit and have
1
/
4
flare connection.
4. Units without a pump package have the same leaving water con-
nection, Y and Z dimensions (entering water), and Pump Dis-
charge X dimensions as units with a pump package.
5. Allow 8 ft (2.4 m) of service access on either side of unit for con-
denser coil removal.
6. Dimensions are in mm [inches].
a30-4589
MCHX — Microchannel Condenser Coil
Fig. 15 — 30RB190, 360A, 390A/B Air-Cooled Chiller Dimensions
100.00
DETAIL
SCALE 1:4
78.63[]
1997.28
22.2 [.87] MOUNTING HOLE
7.87[]
200.00
3.94[]
AIR FLOW
2438.40
[96.00]
COIL SERVICE AREA
7/8" KNOCKOUT TO BE
(FEB)
ALL VOLTAGES
FAN ELECTRICAL BOX
DISPLAY
SCROLLING MARQUEE
FIELD CONTROL WIRING
USED FOR LOCATING
FIELD POWER WIRING
(DUAL POINT 230V ONLY)
(DUAL POWER NFD
CIRCUIT B 380,460,575V
ONLY)
215.71
36.69[]
931.93
NO PUMP PACKAGE
ENTERING WATER
6" VICTAULIC
(SEE NOTE 4)
336.50
84.89[]
2156.30
8.49[]
422.24
13.25[]
9.70[]
246.36
UNIT MOUNTING
OPTION KNOCKOUT
FOR 1/2" CONDUIT
BACnet COMMUNICATION
1.57[]
39.89
16.62[]
16.10[]
408.89
81.64[]
2073.54
36.94[]
938.35
POWER BOX 230V ONLY (CKT A)
1.50[]
38.00
200.00
200.00
29.75[]
755.58
RIGGING HOLE
7.87[]
VIEW A-A
15.75[]
400.00
7.87[]
SCALE 1:16
9.45[]
240.00
POWER BOX 230V (CKT B)
POWER BOX
380V,460V,575V (CKT A,B)
SEE DETAIL B
USED FOR LOCATING
FIELD POWER WIRING
7/8" KNOCKOUT TO BE
y
CG
(DUAL AND SINGLE POINT)
88.03[]
2236.08
x
CG
CIRCUIT A
COMPRESSORS
A
31.50[]
800.00
A
CIRCUIT B
COMPRESSORS
126.30[]
3208.00
37.81[]
SERVICE AREA 1219.2[48.0] FROM EACH SIDE OF THE UNIT
960.40 COOLER TUBE
SERVICE AREA
UNIT MOUNTING2769.30
163.95[]
4164.26
109.03[]
51.08[]
1297.44
32.00[]
126.30[]
3208.06
COIL SERVICE AREA
PIPING ENTRANCE AREA
52.98[]
1345.70
77.31[]
1963.74
y
6" VICTAULIC
LEAVING WATER
PS
y
PD
z
PS
z
PD
1/4" NTP
COOLER VENT
89.82[]
2281.37
PUMP PACKAGE
PUMP PACKAGE
ENTERING WATER
6" VICTAULIC
36.35[]
923.19
3/4" NPT
x
COOLER DRAIN
PD
812.70
UNIT MOUNTING2769.30
x
PS
109.03[]
16.10[]
408.89
282.25[]
7169.08
Z
.25
231.1
[9.1]
Y
.25
421.6 [16.6]
X
.25
2080.3
[81.9]
Z
.25
297.2 [11.7]
Y
.25
381
[15.0]
X
.25
3002
[118.2]
CGy
974
[38.35]
MM [INCH]
CGx
3578
CENTER OF GRAVITY PUMP SUCTION (PS) PUMP DISCHARGE (PD)
[140.87]
MM [INCH]
5582
lb/kg
12309
MCHX PUMP
MAX WEIGHT
MCHX
5019
lb/kg
11064
WEIGHT
lb/kg
14705
14705
MAX WEIGHT
CU/CU PUMP
6118
CU/CU
lb/kg
13460
WEIGHT
6014
lb/kg
13258
MAX WEIGHT
CU/AL PUMP
5461
CU/AL
lb/kg
12013
WEIGHT
30RB-190,
360A,390A/B
19
2281.37
89.82[]
408.89
16.10[]
UNIT MOUNTING2769.30
109.03[]
812.70
32.00[]
UNIT MOUNTING2769.30
109.03[]
408.89
16.10[]
2073.54
81.64[]
7169.08
282.25[]
3208.00
126.30[]
800.00
31.50[]
1781.62
70.14[]
1773.54
69.82[]
755.58
29.75[]
2236.08
88.03[]
934.00
36.77[]
200.00
7.87[]
100.00
3.94[]
y
CG
CG
x
960.40
37.81[]
400.00
15.75[]
240.00
9.45[]
246.36
9.70[]
336.50
13.25[]
39.89
1.57[]
UNIT MOUNTING
2156.30
84.89[]
200.00
7.87[]
200.00
7.87[]
2X 343.58
13.53[]
343.81
13.54[]
553.81
21.80[]
5087.45
200.29[]
3344.54
131.67[]
1892.50
74.51[]
4459.04
175.55[]
601.22
23.67[]
PIPING ENETRANCE AREA
600.00
23.62[]
PIPING ENETRANCE AREA
600.00
23.62[]
PIPING ENETRANCE AREA
600.00
23.62[]
162.77
6.41[]
2X
503.37
19.82[]
2X 769.85
30.31[]
938.35
36.94[]
215.55
8.49[]
WEIGHT
MCHX
lb/kg
CENTER OF GRAVITY
CGx
MM [INCH]
CGy
MM [INCH]
30RB-190,
360A,390A/B
12850
5706
3566
[140.39]
979
[38.54]
CIRCUIT B
COMPRESSORS
SCROLLING MARQUEE
DISPLAY
CIRCUIT A
COMPRESSORS
A
A
HR CONDENSER
TUBE SERVICE AREA
COOLER VENT
1/4" NPT
COOLER DRAIN
3/4" NPT
COOLER
LEAVING WATER
6" VICTAULIC
COOLER
ENTERING WATER
6" VICTAULIC
CONDENSER DRAIN
3/8" NPT
AIR FLOW
FIELD CONTROL WIRING
FAN ELECTRICAL BOX
(FEB)
ALL VOLTAGES
POWER BOX 230V ONLY (CKT A)
7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD POWER WIRING
(DUAL POINT 230V ONLY)
BACnet COMMUNICATION
OPTION KNOCKOUT
FOR 1/2" CONDUIT
COOLER TUBE
SERVICE AREA
SERVICE AREA 1219.2[48.0] FROM EACH SIDE OF THE UNIT
SEE DETAIL B
VIEW A-A
SCALE 1:32
7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD POWER WIRING
(DUAL AND SINGLE POINT)
POWER BOX 230V (CKT B)
POWER BOX
380V,460V,575V (CKT A,B)
DETAIL B
SCALE 1:4
22.2 [.87] MOUNTING HOLE
CONDENSER
ENTERING WATER
5.0" VICTAULIC
CONDENSER
LEAVING WATER
5.0" VICTAULIC
CONDENSER VENT
1/4" NPT
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6 (1.8 m) from solid surface.
2. Temperature relief devices located on suction line, liquid line and filter drier
of each circuit and have
1
/
4
flare connection.
3. Dimensions are in mm [inches].
4. Allow 8 ft (2.4 m) of service access on either side of unit for condenser coil
removal.
a30-4740
LEGEND
HR Heat Reclaim
MCHX — Microchannel Condenser Coil
Fig. 16 — 30RB190 Air-Cooled Chiller with Heat Reclaim Option Dimensions
20
7169.08
282.25[]
2806.54
110.49[]
800.00
31.50[]
CG
x
930.95
36.652[]
1885.22
74.221[]
PIPING ENTRANCE AREA3222.17
126.86[]
1348.58
53.09[]
1256.59
49.47[]
2690.32
105.92[]
2236.08
88.03[]
760.39
29.94[]
1447.8
[57.0]
400.00
15.75[]
240.00
9.45[]
CG
y
200.00
7.87[]
100.00
3.94[]
RIGGING HOLE
38.00
1.50[]
864.00
34.02[]
408.89
16.10[]
UNIT MOUNTING
1981.65
78.02[]
UNIT MOUNTING
2794.35
110.01[]
UNIT MOUNTING
1575.30
62.02[]
408.89
16.10[]
2281.37
89.82[]
437.86
17.24[]
437.86
17.24[]
200.00
7.87[]
200.00
7.87[]
1990.54
78.37[]
UNIT MOUNTING
2156.30
84.89[]
39.89
1.57 []
800.00
31.50[]
2016.54
79.39[]
759.89
29.92[]
2438.40
[96.00]
938.35
36.94[]
215.73
8.49[]
WEIGHT
CU/AL
lb/kg
WEIGHT
CU/CU
lb/kg
WEIGHT
MCHX
lb/kg
CENTER OF GRAVITY
CGx
MM [INCH]
CGy
MM [INCH]
30RB-210
13734
6243
15181
6901
12772
5793
3528
[138.90]
917
[36.10]
30RB-225
14067
6394
15514
7052
13093
5937
3588
[141.26]
906
[35.67]
CIRCUIT C
COMPRESSORS
POWER BOX 2
230V ONLY
CKT C
POWER BOX 1 & 2
(PEB)
ALL VOLTAGES
LEAVING WATER
6" VICTAULIC
ENTERING WATER
6" VICTAULIC
COOLER VENT
1/4" NPT
COOLER DRAIN
3/4" NPT
COOLER TUBE
SERVICE AREA
SERVICE AREA 1219.2[48.0] FROM EACH SIDE OF THE UNIT
A
A
CIRCUIT A
COMPRESSORS
CIRCUIT B
COMPRESSORS
POWER BOX 1
230V CKT B
380V,460V,575V
CKT A,B,C
COIL SERVICE AREA
7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD POWER WIRING
PEB1 230V DUAL POINT
380V,460V,575V DUAL & SINGLE POINT
PEB2 230V DUAL POINT
380V,460V,575V DUAL POINT
SEE DETAIL
B
VIEW-A-A
DETAIL B
SCALE 1:4
22.2[.87] MOUNTING HOLE
POWER BOX
230V ONLY (CKT A)
SCROLLING MARQUEE
DISPLAY
FIELD CONTROL WIRING
FAN ELECTRICAL BOX
(FEB)
ALL VOLTAGES
AIR FLOW
COIL SERVICE AREA
7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD POWER WIRING
(DUAL POINT 230V ONLY)
(DUAL POWER NFD
CIRCUIT B 380,460,
575V ONLY)
BACnet COMMUNICATION
OPTION KNOCKOUT
FOR 1/2" CONDUIT
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6 (1.8 m) from solid surface.
2. Temperature relief devices located on suction line, liquid line
and filter drier of each circuit and have
1
/
4
flare connection.
3. Dimensions are in mm [inches].
4. Allow 8 ft (2.4 m) of service access on either side of unit for
condenser coil removal.
a30-4716
MCHX — Microchannel Condenser Coil
Fig. 17 — 30RB210, 225 Air-Cooled Chiller Dimensions
21
2281.37
89.82[]
408.89
16.10[]
UNIT MOUNTING
2769.30
109.03[]
UNIT MOUNTING
1981.65
78.02[]
408.89
16.10[]
2806.54
110.49[]
8363.08
329.26[]
2236.08
88.03[]
200.00
7.87[]
100.00
3.94[]
RIGGING HOLE
38.00
1.50[]
3154.63
124.20[]
800.00
31.50[]
800.00
31.50[]
CGx
CGy
1020.13
40.16[]
1941.86
76.45[]
2416.18
95.13[]
PIPING ENTRANCE AREA3253.173
128.0777[]
2693.73
106.05[]
437.86
17.24[]
2542.58
100.10[]
1447.8 [57.00]
101.20
3.98[]
964.00
37.95[]
UNIT MOUNTING
2794.35
110.01[]
39.89
1.57[]
UNIT MOUNTING
2156.30
84.89[]
400.00
15.75[]
240.00
9.45[]
1990.54
78.37[]
200.00
7.874[]
761.93
30.00[]
761.93
30.00[]
437.86
17.24[]
2438.40
[96.00]
938.35
36.94[]
215.75
8.49[]
WEIGHT
CU/AL
lb/kg
WEIGHT
CU/CU
lb/kg
WEIGHT
MCHX
lb/kg
CENTER OF GRAVITY
CGx
MM [INCH]
CGy
MM [INCH]
30RB-250
15468
7031
17157
7799
14349
6509
4022
[158.35]
910
[35.86]
SCROLLING MARQUEE
DISPLAY
LEAVING WATER
6" VICTAULIC
ENTERING WATER
6" VICTAULIC
COOLER VENT
1/4 NPT
COOLER DRAIN 3/4" NPT
COOLER TUBE
SERVICE AREA
SERVICE AREA 1219.2[48.0] FROM EACH SIDE OF THE UNIT
A
A
CIRCUIT A
COMPRESSORS
CIRCUIT B
COMPRESSORS
CIRCUIT C
COMPRESSORS
POWER BOX 1
380V,460V,575V
CKT A,B
POWER BOX 2
380V,460V,575V
CKT C
COIL SERVICE AREA
SEE DETAIL
B
VIEW A - A
SCALE 1:16
7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD POWER WIRING
PEB1 230V DUAL POINT
380V,460V,575V DUAL & SINGLE POINT
PEB2 ALL VOLTAGES DUAL POINT
DETAIL
B
SCALE 3:16
22.2 [.87] MOUNTING HOLE
FIELD CONTROL WIRING
AIR FLOW
FAN ELECTRICAL BOX
(FEB)
ALL VOLTAGES
COIL SERVICE AREA
BACnet COMMUNICATION
OPTION KNOCKOUT
FOR 1/2" CONDUIT
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6 (1.8 m) from solid surface.
2. Temperature relief devices located on suction line, liquid line
and filter drier of each circuit and have
1
/
4
flare connection.
3. Dimensions are in mm [inches].
4. Allow 8 ft (2.4 m) of service access on either side of unit for
condenser coil removal.
a30-4717
MCHX — Microchannel Condenser Coil
Fig. 18 — 30RB250 Air-Cooled Chiller Dimensions
22
2281.37
89.82[]
4319.54
170.06[]
408.89
16.10[]
UNIT MOUNTING
1575.30
62.02[]
200.00
7.87[]
100.00
3.94[]
2236.08
88.03[]
2016.54
79.39[]
800.00
31.50[]
800.00
31.50[]
437.86
17.24[]
CGy
CGx
45.00
1.77[]
964.00
37.95[]
2097.41
82.58[]
PIPING ENTRANCE AREA3227.88
127.08[]
4231.79
166.61[]
101.20
3.98[]
2782.00
109.53[]
1447.8
[57.0]
9557.08
376.26[]
408.89
16.10[]
2223.58
87.54[]
UNIT MOUNTING
3582.00
141.02[]
UNIT MOUNTING
3582.00
141.02[]
400.00
15.75[]
200.00
7.87[]
39.89
1.57[]
UNIT MOUNTING
2156.30
84.89[]
759.39
29.90[]
759.39
29.90[]
437.86
17.24[]
2438.40
[96.00]
938.35
36.94[]
215.73
8.49[]
WEIGHT
CU/AL
lb/kg
WEIGHT
CU/CU
lb/kg
WEIGHT
MCHX
lb/kg
CENTER OF GRAVITY
CGx
MM [INCH]
CGy
MM [INCH]
30RB-275
16915
7689
18845
8566
15647
7096
4857
[191.22]
914
[35.98]
CIRCUIT A
COMPRESSORS
CIRCUIT B
COMPRESSORS
CIRCUIT C
COMPRESSORS
POWER BOX 1
380V,460V,575V
CKT A,B
POWER BOX 2
380V,460V,575V
CKT C
COIL SERVICE AREA
LEAVING WATER
6" VICTAULIC
ENTERING WATER
6" VICTAULIC
COOLER VENT
1/4" NPT
COOLER DRAIN 3/4" NPT
COOLER TUBE
SERVICE AREA
SERVICE AREA 1219.2[48.0] FROM EACH SIDE OF THE UNIT
A
A
SEE DETAIL
B
VIEW A - A
SCALE 9:160
POWER ELECTRICAL BOX (PEB)
7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD POWER WIRING
PEB1 230V DUAL POINT
380V,460V,575V DUAL & SINGLE POINT
PEB2 ALL VOLTAGES DUAL POINT
DETAIL
B
SCALE 9:40
22.2[.87] MOUNTING HOLE
RIGGING HOLE
38.00 [1.50]
FIELD CONTROL WIRING
SCROLLING MARQUEE
DISPLAY
FAN ELECTRICAL BOX
(FEB)
AIR FLOW
BACnet COMMUNICATION
OPTION KNOCKOUT
FOR 1/2" CONDUIT
a30-4718
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6 (1.8 m) from solid surface.
2. Temperature relief devices located on suction line, liquid line and fil-
ter drier of each circuit and have
1
/
4
flare connection.
3. Dimensions are in mm [inches].
4. Allow 8 ft (2.4 m) of service access on either side of unit for con-
denser coil removal.
a30-4718
MCHX — Microchannel Condenser Coil
Fig. 19 — 30RB275 Air-Cooled Chiller Dimensions
23
Loading...
+ 53 hidden pages