Carrier 30RAP010-060 User Manual 2

30RAP010-060
AQUASNAP® Air-Cooled Chillers
with COMFORTLINK™ Controls
Controls, Start-Up, Operation,
Service, and Troubleshooting
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . .2
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Basic Controls Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
CONTROLS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-44
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Main Base Board (MBB) . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Current Sensor Board (CSB) . . . . . . . . . . . . . . . . . . . . . . .19
AUX Board (AUX) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Expansion Valve Board (EXV) . . . . . . . . . . . . . . . . . . . . . .19
Emergency On/Off Switch . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Board Addresses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Control Module Communication . . . . . . . . . . . . . . . . . . . . 19
Carrier Comfort Network
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
• COOLER LEAVING FLUID SENSOR
• COOLER ENTERING FLUID SENSOR
• COMPRESSOR RETURN GAS TEMPERATURE SENSOR
• OUTDOOR-AIR TEMPERATURE SENSOR (OAT)
• DISCHARGE TEMPERATURE THERMISTOR (DTT)
• REMOTE SPACE TEMPERATURE SENSOR OR DUAL LEAVING WATER TEMPERATURE SENSOR
Energy Management Module . . . . . . . . . . . . . . . . . . . . . . .29
Loss-of-Cooler Flow Protection. . . . . . . . . . . . . . . . . . . . .29
Capacity Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
• MINUTES LEFT FOR START
• MINUTES OFF TIME
• LEAD/LAG DETERMINATION
• CAPACITY CONTROL OVERRIDES
Head Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Operation of Machine Based on Control Method
and Cooling Set Point Selection Settings. . . . . . . . .32
Cooling Set Point Select. . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Low Sound Mode Operation . . . . . . . . . . . . . . . . . . . . . . . .34
Heating Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Service Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Optional Factory-Installed Hydronic Package. . . . . . .34
Cooler Pump Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Cooler Pump Sequence of Operation . . . . . . . . . . . . . . .35
Configuring and Operating Dual Chiller Control . . . . 36
Temperature Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Demand Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
• DEMAND LIMIT (2-Stage Switch Controlled)
• EXTERNALLY POWERED DEMAND LIMIT
(4 to 20 mA Controlled)
• DEMAND LIMIT (CCN Loadshed Controlled)
Cooling Set Point (4 to 20 mA). . . . . . . . . . . . . . . . . . . . . .43
Digital Scroll Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
• DIGITAL SCROLL OPERATION
• DIGITAL COMPRESSOR CONFIGURATION
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44,45
®
(CCN) Interface . . . . . . . . . . 19
System Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Actual Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Check Refrigerant Charge. . . . . . . . . . . . . . . . . . . . . . . . . 45
Operating Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
• TEMPERATURES
• LOW AMBIENT OPERATION
• VOLTAGE — ALL UNITS
OPERATION SEQUENCE . . . . . . . . . . . . . . . . . . . . . .46,47
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47-63
Page
Electronic Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
• CONTROL COMPONENTS
Electronic Expansion Valve (EXV) . . . . . . . . . . . . . . . 47
EXV Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . 47
• FIELD SERVICING INSTRUCTIONS
• VALVE REPLACEMENT
• VALVE REASSEMBLY
Compressor Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . 49
Cooler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
• BRAZED-PLATE COOLER HEAT EXCHANGER REPLACEMENT
• BRAZED-PLATE COOLER HEAT EXCHANGER CLEANING
Oil Charge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Microchannel Heat Exchanger (MCHX) Condenser Coil Maintenance and Cleaning
Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Check Refrigerant Feed Components . . . . . . . . . . . . . . 50
•FILTER DRIER
• MOISTURE-LIQUID INDICATOR
• MINIMUM LOAD VALVE
• PRESSURE RELIEF DEVICES
Check Unit Safeties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
• HIGH-PRESSURE SWITCH
• PRESSURE TRANSDUCERS
• COOLER FREEZE-UP PROTECTION
• HEATER CABLE
• WINTER SHUTDOWN
Thermistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Pressure Transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Chilled Water Flow Switch. . . . . . . . . . . . . . . . . . . . . . . . . . 53
Strainer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Condenser Fans. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Motormaster
• GENERAL OPERATION
• CONFIGURATION
• DRIVE PROGRAMMING
•EPM CHIP
• LOSS OF CCN COMMUNICATIONS
• REPLACING DEFECTIVE MODULES
Hydronic Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63,64
Recommended Maintenance Schedule . . . . . . . . . . . . . 63
Microchannel Heat Exchanger (MCHX) Condenser Coil Maintenance and Cleaning
Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . 64-73
®
V Controller . . . . . . . . . . . . . . . . . . . . . . . . . 58
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300067-01 Printed in U.S.A. Form 30RAP-2T Pg 1 12-10 Replaces: 30RAP-1T
CONTENTS (cont)
Complete Unit Stoppage and Restart . . . . . . . . . . . . . . 64
• GENERAL POWER FAILURE
• UNIT ENABLE-OFF-REMOTE CONTACT SWITCH IS OFF
• CHILLED FLUID PROOF-OF-FLOW SWITCH OPEN
• OPEN 24-V CONTROL CIRCUIT BREAKERS
• COOLING LOAD SATISFIED
• THERMISTOR FAILURE
• LOW SATURATED SUCTION
• COMPRESSOR SAFETIES
Alarms and Alerts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
APPENDIX A — DISPLAY TABLES . . . . . . . . . . . . . . 74-89
APPENDIX B — CCN TABLES . . . . . . . . . . . . . . . . . . 90-100
APPENDIX C — FACTORY SETTINGS FOR
PUMP AND MANUAL STARTERS. . . . . . . . . . . . . . . . 101
APPENDIX D — OPTIONAL BACNET
COMMUNICATONS WIRING . . . . . . . . . . . . . . . . . 102-109
APPENDIX E — MAINTENANCE SUMMARY
AND LOG SHEETS . . . . . . . . . . . . . . . . . . . . . . . . . . 110-113
START-UP CHECKLIST FOR 30RAP LIQUID
CHILLER
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1 to CL-10
Page
WARNING
DO NOT attempt to unbraze factory joints when servicing this equipment. Compressor oil is flammable and there is no way to detect how much oil may be in any of the refrigerant lines. Cut lines with a tubing cutter as required when performing service. Use a pan to catch any oil that may come out of the lines and as a gage for how much oil to add to system. DO NOT re-use compressor oil.
CAUTION
This unit uses a microprocessor-based electronic control system. Do not use jumpers or other tools to short out components, or to bypass or otherwise depart from recom­mended procedures. Any short-to-ground of the control board or accompanying wiring may destroy the electronic modules or electrical components.
CAUTION
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be
hazardous due to system pressures, electrical components, and equipment location (roof, elevated structures, mechanical rooms, etc.). Only trained, qualified installers and service mechanics should install, start up, and service this equipment.
When working on this equipment, observe precautions in
the literature, and on tags, stickers, and labels attached to the equipment, and any other safety precautions that apply. Follow all safety codes. Wear safety glasses and work gloves. Use care in handling, rigging, and setting this equipment, and in handling all electrical components.
WARNING
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation. There may be more than one disconnect switch. Tag all discon­nect locations to alert others not to restore power until work is completed.
WARNING
DO NOT VENT refrigerant relief valves within a building. Outlet from relief valves must be vented outdoors in accordance with the latest edition of ANSI/ASHRAE (American National Standards Institute/American Society of Heating, Refrigeration and Air Conditioning Engineers) 15 (Safety Code for Mechanical Refrigeration). The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation. Provide adequate ventilation in enclosed or low overhead areas. Inhalation of high concentrations of vapor is harmful and may cause heart irregularities, unconsciousness or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products are hazardous.
To prevent potential damage to heat exchanger, always run fluid through heat exchanger when adding or removing refrigerant charge. Use appropriate brine solutions in cooler fluid loop to prevent the freezing of brazed plate heat exchanger, optional hydronic section and/or interconnecting piping when the equipment is exposed to temperatures below 32 F (0 °C). Proof of flow switch and strainer are factory installed on all models. Do NOT remove power from this chiller during winter shutdown periods without taking precaution to remove all water from heat exchanger and optional hydronic system. Failure to properly protect the system from freezing may constitute abuse and may void warranty.
CAUTION
Compressors and optional hydronic system pumps require specific rotation. Test condenser fan(s) first to ensure proper phasing. Swap any two incoming power leads to correct condenser fan rotation before starting any other motors.
CAUTION
Refrigerant charge must be removed slowly to prevent loss of compressor oil that could result in compressor failure.
CAUTION
Puron® refrigerant (R-410A) systems operate at higher pressures than standard R-22 systems. Do not use R-22 ser­vice equipment or components on Puron refrigerant equip­ment. If service equipment is not rated for Puron refrigerant, equipment damage or personal injury may result.
2
ENTER
ESCAPE
ENTER
ENTER
ESCAPE
ESCAPE
ENTER
ESCAPE
ENTER
ESCAPE
ESCAPE
ENTER
ENTER
ENTER
Run Status
Service Test
Temperature
Pressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
Operating Modes
Alarms
Alarm Status
ENTER
MODE
ESCAPE
Fig. 1 — Scrolling Marquee Display
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
GENERAL
This publication contains Controls, Start-Up, Operation, Service, and Troubleshooting information for the 30RAP AquaSnap
®
air-cooled chillers. See Table 1. These chillers are equipped with ComfortLink™ controls and electronic expan­sion valves (EXVs).
WARNING
This unit uses a microprocessor-based electronic control system. Do not use jumpers or other tools to short out or bypass components or otherwise depart from recom­mended procedures. Any short-to-ground of the control board or accompanying wiring may destroy the board or electrical component.
Table 1 — Unit Sizes
UNIT NOMINAL CAPACITY (TONS) 30RAP010 10 30RAP015 14 30RAP018 16 30RAP020 19 30RAP025 24 30RAP030 28 30RAP035 34 30RAP040 39 30RAP045 43 30RAP050 48 30RAP055 53 30RAP060 56
Conventions Used in This Manual — The follow-
ing conventions for discussing configuration points for the local display (scrolling marquee or Navigator™ accessory) will be used in this manual.
Point names will be written with the mode name first, then any sub-modes, then the point name, each separated by an arrow symbol (. Names will also be shown in bold and italics. As an example, the Lead/Lag Circuit Select Point, which is located in the Configuration mode, Option sub-mode, would be written as Configuration OPTNLLCS.
This path name will show the user how to navigate through the local display to reach the desired configuration. The user would scroll through the modes and sub-modes using the
and keys. The arrow symbol in the path name repre­sents pressing to move into the next level of the menu structure.
When a value is included as part of the path name, it will be shown at the end of the path name after an equals sign. If the value represents a configuration setting, an explanation will be shown in parenthesis after the value. As an example, ConfigurationOPTNLLCS = 1 (Circuit A leads).
Pressing the and keys simultaneously will scroll an expanded text description of the point name or value across the display. The expanded description is shown in the local display tables but will not be shown with the path names in text.
®
The CCN (Carrier Comfort Network
) point names are also referenced in the local display tables for users configuring the unit with CCN software instead of the local display. The CCN tables are located in Appendix B of the manual.
Basic Controls Usage
SCROLLING MARQUEE DISPLAY — The scrolling mar­quee display is the standard interface display to the ComfortLink
Control System for 30RAP units. The display has up and down arrow keys, an key, and an key. These keys are used to navigate through the different levels of the display structure. Press the key until the highest operating level is displayed to move through the top 11 mode levels indicated by LEDs on the left side of the display. See Fig. 1 and Tables 2-14.
Once within a mode or sub-mode, pressing the and keys simultaneously will put the scrolling marquee display into expanded text mode where the full mean­ing of all sub-modes, items and their values can be displayed for the current selection. Press the and keys to return the scrolling marquee display to its default menu of rotating display items (those items in Run Status In addition, the password will be disabled, requiring that it be entered again before changes can be made to password protect­ed items. Press the key to exit out of the expanded text mode.
NOTE: When the Language Selection (Configuration DISPLANG), variable is changed, all appropriate display expansions will immediately change to the new language. No power-off or control reset is required when reconfiguring languages.
When a specific item is located, the item name alternates with the value. Press the key at a changeable item and the value will be displayed. Press again and the value will begin to flash indicating that the value can be changed. Use the up and down arrow keys to change the value, and confirm the value by pressing the key.
Changing item values or testing outputs is accomplished in the same manner. Locate and display the desired item. Press
so that the item value flashes. Use the arrow keys to change the value or state and press the key to accept it. Press the key to return to the next higher level of structure. Repeat the process as required for other items.
Items in the Configuration and Service Test modes are pass­word protected. The words ‘PASS’ and ‘WORD’ will alternate on the display when required. The default password is 0111. Press and the 1111 password will be displayed. Press
again and the first digit will begin to flash. Use the arrow keys to change the number and press to accept the digit. Continue with the remaining digits of the password. The password can only be changed through CCN operator in-
®
terface software such as ComfortWORKS
, ComfortVIEW™
and Service Tool.
See Tables 2-14 and Appendix A for further details.
3
VIEW).
ACCESSORY NAVIGATOR™ DISPLAY MODULE —
ENTER
ESCAPE
ESCAPE
ENTER
ESCAPE
ENTER
ESCAPE
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
Fig. 2 — Accessory Navigator™ Display Module
The Navigator module provides a mobile user interface to the ComfortLink™ control system, which is only available as a field-installed accessory. The display has up and down arrow keys, an key, and an key. These keys are used to navigate through the different levels of the display structure. Press the key until ‘Select a Menu Item’ is displayed to move through the top 11 mode levels indicated by LEDs on the left side of the display. See Fig. 2.
Once within a Mode or sub-mode, a “>” indicates the cur-
rently selected item on the display screen. Pressing the
and keys simultaneously will put the Nav­igator module into expanded text mode where the full meaning of all sub-modes, items and their values can be displayed. Press­ing the and keys when the display says ‘Select Menu Item’ (Mode LED level) will return the Navigator module to its default menu of rotating display items (those items
in Run Status
VIEW). In addition, the password will be dis-
abled, requiring that it be entered again before changes can be made to password protected items. Press the key to exit out of the expanded text mode.
NOTE: When the Language Selection (Configuration
DISPLANG), variable is changed, all appropriate display expansions will immediately change to the new language. No power-off or control reset is required when reconfiguring languages.
When a specific item is located, the item name appears on the left of the display, the value will appear near the middle of the display and the units (if any) will appear on the far right of the display. Press the key at a changeable item and the val­ue will begin to flash. Use the up and down arrow keys to change the value, and confirm the value by pressing the key.
Changing item values or testing outputs is accomplished in the same manner. Locate and display the desired item. Press
so that the item value flashes. Use the arrow keys to change the value or state and press the key to accept it. Press the key to return to the next higher level of structure. Repeat the process as required for other items.
Items in the Configuration and Service Test modes are pass­word protected. The words Enter Password will be displayed when required, with 1111 also being displayed. The default password is 1111. Use the arrow keys to change the number and press to enter the digit. Continue with the re­maining digits of the password. The password can only be changed through CCN operator interface software such as ComfortWORKS, ComfortVIEW and Service Tool.
Adjusting the Contrast
— The contrast of the display can be
adjusted to suit ambient conditions. To adjust the contrast of
the Navigator module, press the key until the dis­play reads, “Select a menu item.” Using the arrow keys move to the Configuration mode. Press to obtain access to this mode. The display will read:
> TEST OFF METR OFF LANG ENGLISH
Pressing will cause the “OFF” to flash. Use the up or down arrow to change “OFF” to “ON”. Pressing will illuminate all LEDs and display all pixels in the view screen. Pressing and simultaneously allows the user to adjust the display contrast. Use the up or down arrows to adjust the contrast. The screen’s contrast will change with the adjustment. Press to accept the change. The Navigator module will keep this setting as long as it is plugged in to the LEN bus.
Adjusting the Backlight Brightness
— The backlight of the display can be adjusted to suit ambient conditions. The factory default is set to the highest level. To adjust the backlight of the Navigator module, press the key until the display reads, “Select a menu item.” Using the arrow keys move to the Configuration mode. Press to obtain access to this mode. The display will read:
> TEST OFF METR OFF LANG ENGLISH
Pressing will cause the “OFF” to flash. Use the up
or down arrow keys to change “OFF” to “ON”. Pressing
will illuminate all LEDs and display all pixels in the view screen. Pressing the up and down arrow keys simultane­ously allows the user to adjust the display brightness. Use the up or down arrow keys to adjust screen brightness. Press
to accept the change. The Navigator module will keep this setting as long as it is plugged in to the LEN bus.
ComfortLink
MODE
Alarm Status
Run Status
Service Test
Temperatures
Pressure
s
Setpoints
Inputs
Outputs
Configuration
Time Clock
ESC
Operating Modes
Alarms
ENTER
4
Table 2 — Scrolling Marquee Display Menu Structure*
MODE
SUB-MODE
RUN
STATUS
Auto
View of
Run Status
(VIEW)
Unit Run
Hour and
Start
(RUN)
Compressor
Run Hours
(HOUR)
Compressor
Starts
(STRT)
Preventive
Maintenance
(PM)
Software
Ver si on (VERS)
LEGEND Ckt — Circuit *Throughout this text, the location of items in the menu structure will be
described in the following format: Item Expansion (Mode Name For example, using the language selection item: Language Selection (Configuration
SERVICE
TEST
Service
Te s t M o d e
(TEST)
Outputs
and Pumps
(OUTS)
Ciruit A Comp
Te st
(CMPA)
Ciruit B Comp
Test
(CMPB)
TEMPERATURES PRESSURES
Ent and Leave Unit
Temperatures
Temperatures
Sub-mode NameITEM)
DISPLANG)
Te mp s (UNIT)
Ckt A
(CIR.A)
Ckt B
(CIR.B)
Pressures
Ckt A
(PRC.A)
Pressures
Ckt B
(PRC.B)
SET
POINTS
Cooling
Setpoints
(COOL)
Head
Pressure
Setpoint
(HEAD)
Brine
Freeze
Setpoint
(FRZ)
INPUTS OUTPUTS CONFIGURATION
General
Inputs
(GEN.I)
Circuit Inputs
(CRCT)
4-20mA
Inputs (4-20)
General Outputs
(GEN.O)
Outputs
Circuit A
EXV
(A.EXV) Outputs
Circuit B
EXV
(B.EXV)
Outputs
Circuit A
(CIR.A)
Outputs
Circuit B
(CIR.B)
Display
Configuration
(DISP)
Unit
Configuration
(UNIT)
Unit Options 1
Hardware
(OPT1)
Unit Options 2
Controls
(OPT2)
CCN Network Configuration
(CCN)
Head Pressure
Comp. Delta
(HP.A)
Head Pressure
Comp. Delta
(HP.B)
Cir. A EXV
Configuration
(EXV.A)
Cir. B EXV
Configuration
(EXV.B)
Motormaster
Configuration
(MM)
Reset Cool Temp
(RSET)
Set Point and
Ramp Load
(SLCT) Service
Configuration
(SERV)
Broadcast
Configuration
(BCST)
TIME
CLOCK
Time of
Day
(TIME)
Month,
Date, Day,
and Year
(DATE)
Daylight Savings
Time
(DST)
Local
Holiday
Schedules
(HOL.L)
Local Occu­pancy
Schedule
(SCH.L)
Schedule
Override
(OVR)
OPERATING
MODES
Modes
(MODE)
ALARMS
Current (CRNT)
Reset
Alarms
(RCRN)
Alarm
History
(HIST)
5
Table 3 — Run Status Mode and Sub-Mode Directory
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY SUB-ITEM DISPLAY SUB-ITEM DISPLAY
VIEW EWT XXX.X F ENTERING FLUID TEMP
LWT XXX.X F LEAVING FLUID TEMP
SETP XXX.X F ACTIVE SETPOINT
CTPT XXX.X F CONTROL POINT
LOD.F XXX LOAD/UNLOAD FACTOR
STAT X CONTROL MODE 0 = Service Test
LD.PM LEAD PUMP
OCC YES/NO OCCUPIED
LS.AC YES/NO LOW SOUND ACTIVE
MODE YES/NO OVERRIDE MODES IN EFFECT
CAP XXX % PERCENT TOTAL CAPACITY
STGE X REQUESTED STAGE
ALRM XXX CURRENT ALARMS & ALERTS
TIME XX.XX TIME OF DAY 00.00-23.59
ITEM
EXPANSION
COMMENT
1 = Off Local
2 = Off CCN
3 = Off Time
4 = Off Emrgcy
5 = On Local
6 = On CCN
7 = On Time
8 = Ht Enabled
9 = Pump Delay
MNTH XX MONTH OF YEAR 1 = January, 2 = February, etc.
DATE XX DAY OF MONTH 01-31
YEAR XX YEAR OF CENTURY
RUN HRS.U XXXX HRS MACHINE OPERATING HOURS
STR.U XXXX MACHINE STARTS
HR.P1 XXXX.X PUMP 1 RUN HOURS
HR.P2 XXXX.X PUMP 2 RUN HOURS
HOUR HRS.A XXXX HRS CIRCUIT A RUN HOURS
HRS.B XXXX HRS CIRCUIT B RUN HOURS See Note
HR.A1 XXXX HRS COMPRESSOR A1 RUN HOURS
HR.A2 XXXX HRS COMPRESSOR A2 RUN HOURS
HR.B1 XXXX HRS COMPRESSOR B1 RUN HOURS See Note
HR.B2 XXXX HRS COMPRESSOR B2 RUN HOURS See Note
STRT ST.A1 XXXX COMPRESSOR A1 STARTS
ST.A2 XXXX COMPRESSOR A2 STARTS
ST.B1 XXXX COMPRESSOR B1 STARTS See Note
ST.B2 XXXX COMPRESSOR B2 STARTS See Note
PM PUMP PUMP MAINTENANCE
SI.PM XXXX HRS PUMP SERVICE INTERVAL Default: 8760
P.1.DN XXXX HRS PUMP 1 SERVICE COUNTDOWN
P.2.DN XXXX HRS PUMP 2 SERVICE COUNTDOWN
P.1.MN YES/NO PUMP 1 MAINTENANCE DONE User Entry
P.2.MN YES/NO PUMP 2 MAINTENANCE DONE User Entry
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
6
Table 3 — Run Status Mode and Sub-Mode Directory (cont)
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ESCAPE
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY SUB-ITEM DISPLAY SUB-ITEM DISPLAY
PM (cont) PMDT PUMP MAINTENANCE DATES
P.1.M0 MM/DD/YY HH:MM
P.1.M1 MM/DD/YY HH:MM
P.1.M2 MM/DD/YY HH:MM
P.1.M3 MM/DD/YY HH:MM
P.1.M4 MM/DD/YY HH:MM
P.2.M0 MM/DD/YY HH:MM
P.2.M1 MM/DD/YY HH:MM
P.2.M2 MM/DD/YY HH:MM
P.2.M3 MM/DD/YY HH:MM
P.2.M4 MM/DD/YY HH:MM
STRN STRAINER MAINTENANCE
SI.ST XXXX HRS STRAINER SRVC INTERVAL Default: 8760
S.T.DN XXXX HRS STRAINER SRVC COUNTDOWN
S.T.MN YES/NO STRAINER MAINT. DONE User Entry
ST.DT STRAINER MAINT. DATES
S.T.M0 MM/DD/YY HH:MM
ITEM
EXPANSION
COMMENT
S.T.M1 MM/DD/YY HH:MM
S.T.M2 MM/DD/YY HH:MM
S.T.M3 MM/DD/YY HH:MM
S.T.M4 MM/DD/YY HH:MM
COIL COIL MAINTENANCE
SI.CL XXXX HRS COIL SRVC INTER Default: 8760
C.L.DN XXXX HRS COIL SERVICE COUNTDOWN
C.L.MN YES/NO COIL MAINT. DONE User Entry
CL.DT COIL MAINTENANCE DATES
C.L.M0 MM/DD/YY HH:MM
C.L.M1 MM/DD/YY HH:MM
C.L.M2 MM/DD/YY HH:MM
C.L.M3 MM/DD/YY HH:MM
C.L.M4 MM/DD/YY HH:MM
VERS MBB CESR131460-xx-xx xx-xx is Version number*
EXV CESR131172-xx-xx xx-xx is Version number*
AUX1 CESR131333-xx-xx xx-xx is Version number*
EMM CESR131174-xx-xx xx-xx is Version number*
MARQ CESR131171-xx-xx xx-xx is Version number*
NAVI CESR130227-xx-xx xx-xx is Version number*
*Press and simultaneously to obtain version number.
7
Table 4 — Service Test Mode and Sub-Mode Directory
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
TEST ON/OFF SERVICE TEST MODE To Enable Service Test Mode,
OUTS OUTPUTS AND PUMPS
EXV.A 0 to 100% EXV A % OPEN
EXV.B 0 to 100% EXV B % OPEN
FAN 1 ON / OFF FAN 1 REL AY
FAN 2 ON / OFF FAN 2 REL AY
FAN 3 ON / OFF FAN 3 REL AY
FAN 4 ON / OFF FAN 4 REL AY
FAN 5 ON / OFF FAN 5 REL AY
FAN 6 ON / OFF FAN 6 REL AY
V.HPA 0 to 100% VAR HEAD PRESS %
V.HPB 0 to 100% VAR HEAD PRESS %
CLP.1 ON/OFF COOLER PUMP 1 RELAY
CLP.2 ON/OFF COOLER PUMP 2 RELAY
UL.TM 0 to 15 COMP A1 UNLOAD TIME
CL.HT ON/OFF COOLER/PUMP HEATER
ITEM
EXPANSION
COMMENT
move Enable/Off/Remote Contact switch to OFF. Change TEST to ON. Move switch to ENABLE.
RMT.A ON/OFF REMOTE ALARM RELAY
CMPA CIRCUIT A COMPRESSOR TEST
CC.A1 ON/OFF COMPRESSOR A1 RELAY
UL.TM 0 to 15 COMP A1 UNLOAD TIME
CC.A2 ON/OFF COMPRESSOR A2 RELAY
CC.A3 ON/OFF COMPRESSOR A3 RELAY
CC.A4 ON/OFF COMPRESSOR A4 RELAY
MLV ON/OFF MINIMUM LOAD VALVE RELAY
CMPB CIRCUIT B COMPRESSOR TEST See Note
CC.B1 ON/OFF COMPRESSOR B1 RELAY
CC.B2 ON/OFF COMPRESSOR B2 RELAY
CC.B3 ON/OFF COMPRESSOR B3 RELAY
CC.B4 ON/OFF COMPRESSOR B4 RELAY
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
8
Table 5 — Temperature Mode and Sub-Mode Directory
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
UNIT ENT AND LEAVE UNIT TEMPS
CEWT XXX.X F COOLER ENTERING FLUID
CLWT XXX.X F COOLER LEAVING FLUID
OAT XXX.X F OUTSIDE AIR TEMPERATURE
SPT XXX.X F SPACE TEMPERATURE
DLWT XXX.X F LEAD/LAG LEAVING FLUID
CIR.A TEMPERATURES CIRCUIT A
SCT.A XXX.X F SATURATED CONDENSING TMP
SST.A XXX.X F SATURATED SUCTION TEMP
RGT.A XXX.X F COMPR RETURN GAS TEMP
D.G AS XXX.X F DISCHARGE GAS TEMP
SH.A XXX.X ^F SUCTION SUPERHEAT TEMP
CIR.B TEMPERATURES CIRCUIT B See Note
SCT.B XXX.X F SATURATED CONDENSING TMP See Note
SST.B XXX.X F SATURATED SUCTION TEMP See Note
RGT.B XXX.X F COMPR RETURN GAS TEMP See Note
SH.B XXX.X ^F SUCTION SUPERHEAT TEMP See Note
ITEM
EXPANSION
COMMENT
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
Table 6 — Pressure Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
PRC.A PRESSURES CIRCUIT A
DP.A XXX.X PSIG DISCHARGE PRESSURE
SP.A XXX.X PSIG SUCTION PRESSURE
PRC.B PRESSURES CIRCUIT B See Note
DP.B XXX.X PSIG DISCHARGE PRESSURE See Note
SP.B XXX.X PSIG SUCTION PRESSURE See Note
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
ITEM
EXPANSION
Table 7 — Set Points Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
COOL COOLING SETPOINTS
CSP.1 XXX.X
F COOLING SETPOINT 1 Default: 44 F
CSP.2 XXX.X F COOLING SETPOINT 2 Default: 44 F
CSP.3 XXX.X F ICE SETPOINT Default: 32 F
HEAD HEAD PRESSURE SETPOINTS
H.DP XXX.X F HEAD SETPOINT Default: 95 F
F. O N XXX.X F FAN ON SETPOINT Default: 95 F
F. O F F XXX.X F FAN OFF SETPOINT Default: 72 F
ITEM
EXPANSION
COMMENT
COMMENT
B.OFF XXX.X F BASE FAN OFF DELTA TEMP Default: 23 F
F. D LT XXX.X F FAN STAGE DELTA Default: 15 F
FRZ BRINE FREEZE SETPOINT
BR.FZ XXX.X F BRINE FREEZE POINT Default: 34 F
9
Table 8 — Inputs Mode and Sub-Mode Directory
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
GEN.I GENERAL INPUTS
STST STRT/STOP START/STOP SWITCH
FLOW ON/OFF COOLER FLOW SWITCH
PM.F.1 OPEN/CLSE COOLER PUMP 1 INTERLOCK
PM.F.2 OPEN/CLSE COOLER PUMP 2 INTERLOCK
HT.RQ ON/OFF HEAT REQUEST
DLS1 ON/OFF DEMAND LIMIT SWITCH 1
DLS2 ON/OFF DEMAND LIMIT SWITCH 2
ICED ON/OFF ICE DONE
DUAL ON/OFF DUAL SETPOINT SWITCH
CRCT CIRCUITS INPUTS
FKA1 ON/OFF COMPRESSOR A1 FEEDBACK
FKA2 ON/OFF COMPRESSOR A2 FEEDBACK
FKA3 ON/OFF COMPRESSOR A3 FEEDBACK
FKA4 ON/OFF COMPRESSOR A4 FEEDBACK
FKB1 ON/OFF COMPRESSOR B1 FEEDBACK See Note
FKB2 ON/OFF COMPRESSOR B2 FEEDBACK See Note
FKB3 ON/OFF COMPRESSOR B3 FEEDBACK See Note
ITEM
EXPANSION
COMMENT
FKB4 ON/OFF COMPRESSOR B4 FEEDBACK See Note
4-20 4-20 MA INPUTS
DMND XX.X MA 4-20 MA DEMAND SIGNAL
RSET XX.X MA 4-20 MA RESET SIGNAL
CSP XX.X MA 4-20 MA COOLING SETPOINT
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
Table 9 — Outputs Mode and Sub-Mode Directory
SUB-MODE
GEN.O GENERAL OUTPUTS
KEYPAD
ENTRY
ITEM DISPLAY
FAN1 ON/OFF FAN 1 RELAY
FAN2 ON/OFF FAN 2 RELAY
FAN3 ON/OFF FAN 3 RELAY
FAN4 ON/OFF FAN 4 RELAY
FAN5 ON/OFF FAN 5 RELAY
FAN6 ON/OFF FAN 6 RELAY
V.HPA ON/OFF FAN SPEED CIRCUIT A
V.HPB ON/OFF FAN SPEED CIRCUIT B
C.WP1 ON/OFF COOLER PUMP RELAY 1
C.WP2 ON/OFF COOLER PUMP RELAY 2
CLHT ON/OFF COOLER/PUMP HEATER
MLV.R ON/OFF MINIMUM LOAD VALVE RELAY
ITEM
EXPANSION
COMMENT
10
Table 9 — Outputs Mode and Sub-Mode Directory (cont)
ENTER
ENTER
ENTER
ENTER
ENTER
SUB-MODE
A.EXV OUTPUTS CIRCUIT A EXV
B.EXV OUTPUTS CIRCUIT B EXV
CIR.A OUTPUTS CIRCUIT A
CIR.B OUTPUTS CIRCUIT B (See Note)
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
KEYPAD
ENTRY
ITEM DISPLAY
EXV.A 0 to 100% EXV % OPEN
APPR ON/OFF CIRCUIT A APPROACH
AP.SP APPROACH SETPOINT
X.SH.R SH RESET AT MAX UNL-DIG
S.SH.R DIGLOAD TO START SH RST
SH_R AMOUNT OF SH RESET
OVR.A EXVA OVERRIDE
SPH.A SUCTION SUPERHEAT TEMP
ASH.S ACTIVE SUPERHEAT SETPT
AMP.S ACTIVE MOP SETPT
PLM.A CIR A EXV POSITION LIMIT
SPR.1 SPARE 1 TEMPERATURE
EXV.B 0 to 100% EXV % OPEN
APPR ON/OFF CIRCUIT B APPROACH
AP.SP APPROACH SETPOINT
OVR.B EXVB OVERRIDE
SPH.B SUCTION SUPERHEAT TEMP
ASH.S ACTIVE SUPERHEAT SETPT
AMP.S ACTIVE MOP SETPT
PLM.B CIR B EXV POSITION LIMIT
SPR.2 SPARE 2 TEMPERATURE
CC.A1 ON/OFF COMPRESSOR A1 RELAY
DPE.R ON/OFF COMP A1 LOAD PERCENT
CC.A2 ON/OFF COMPRESSOR A2 RELAY
CC.A3 ON/OFF COMPRESSOR A3 RELAY
CC.A4 ON/OFF COMPRESSOR A4 RELAY
CC.B1 ON/OFF COMPRESSOR B1 RELAY
CC.B2 ON/OFF COMPRESSOR B2 RELAY
CC.B3 ON/OFF COMPRESSOR B3 RELAY
CC.B4 ON/OFF COMPRESSOR B4 RELAY
ITEM
EXPANSION
COMMENT
Table 10 — Configuration Mode and Sub-Mode Directory
SUB-MODE
DISP DISPLAY CONFIGURATION
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
KEYPAD
ENTRY
ITEM DISPLAY
TEST ON/OFF TEST DISPLAY LEDS
METR ON/OFF METRIC DISPLAY Off = English; On = Metric
LANG X LANGUAGE SELECTION
PAS.E ENBL/DSBL PASSWORD ENABLE Default: Enable
PASS xxxx SERVICE PASSWORD Default: 1111
ITEM
EXPANSION
11
COMMENT
Default: 0 0 = English
1 = Espanol 2 = Francais 3 = Portuguese
Table 10 — Configuration Mode and Sub-Mode Directory
ENTER
ENTER
SUB-MODE
UNIT UNIT CONFIGURATION
KEYPAD
ENTRY
ITEM DISPLAY
SIZE XX UNIT SIZE
SZA.1 XX COMPRESSOR A1 SIZE Unit Dependent
SZA.2 XX COMPRESSOR A2 SIZE Unit Dependent
SZA.3 XX COMPRESSOR A3 SIZE Unit Dependent
SZA.4 XX COMPRESSOR A4 SIZE Unit Dependent
SZB.1 XX COMPRESSOR B1 SIZE Unit Dependent
SZB.2 XX COMPRESSOR B2 SIZE Unit Dependent
SZB.3 XX COMPRESSOR B3 SIZE Unit Dependent
SZB.4 XX COMPRESSOR B4 SIZE Unit Dependent
SH.SP XX.X F SUPERHEAT SETPOINT Default: 9 F
FAN.S NUMBER OF FANS 1 = One Fan
ITEM
EXPANSION
COMMENT
2 = Two Fans 3 = Three Fans 4 = Four Fans
EXV YES/NO EXV MODULE INSTALLED?
A1.TY YES/NO COMPRESSOR A1 DIGITAL?
MAX.T 0 to 12 MAXIMUM A1 UNLOAD TIME
OPT1 UNIT OPTIONS 1 HARDWARE
FLUD X COOLER FLUID
MLV.S YES/NO MINIMUM LOAD VALVE SELECT Default: No
D.G.EN ENBL/DSBL DISCHARGE GAS TEMP ENABLE
CSB.E ENBL/DSBL CSB BOARDS ENABLE
CPC ON/OFF COOLER PUMP CONTROL Default: Off
PM1E YES/NO COOLER PUMP 1 ENABLE
PM2E YES/NO COOLER PUMP 2 ENABLE
PM.P.S YES/NO COOLER PMP PERIODIC STRT Default: No
PM.SL X COOLER PUMP SELECT Default: Automatic
PM.DY XX MIN COOLER PUMP SHUTDOWN DLY
PM.DT XXXX HRS PUMP CHANGEOVER HOURS Default: 500 hours
ROT.P YES/NO ROTATE COOLER PUMPS NOW User Entr y
EMM YES/NO EMM MODULE INSTALLED
CND.T 0,1 COND HX
MOPS XX EXV MOP SET POINT Range: 40 - 80 Default: 50
APPR XX CONFIG APPROACH SETPOINT Range: 5 - 40 Default: 9.0
Default: Yes
Default: No
Yes = A1 Compressor is Digital
Scroll
Default: 7
Max 12 010,015 Max 10 018-060
Default: Water 1 = Water 2 = Medium Temperature Brine
0 = Automatic 1 = Pump 1 Starts first 2 = Pump 2 Starts first
0 to 10 minutes, Default: 1 min.
0 = RTPF 1 = MCHX Default MCHX
12
Table 10 — Configuration Mode and Sub-Mode Directory (cont)
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
OPT2 UNIT OPTIONS 2 CONTROLS
CTRL X CONTROL METHOD Default: Switch
LOAD X LOADING SEQUENCE SELECT Default: Equal
LLCS X LEAD/LAG CIRCUIT SELECT Default: Automatic
LCWT XX.X F HIGH LCW ALERT LIMIT
DELY XX MINUTES OFF TIME
ICE.M ENBL/DSBL ICE MODE ENABLE Default: Disable
LS.MD X LOW SOUND MODE SELECT Default: 0
LS.ST 00:00 LOW SOUND START TIME Default: 00:00
LS.ND 00:00 LOW SOUND END TIME Default: 00:00
LS.LT XXX % LOW SOUND CAPACITY LIMIT
CCN CCN NETWORK CONFIGURATION
CCNA XXX CCN ADDRESS
CCNB XXX CCN BUS NUMBER
BAUD X CCN BAUD RATE Default: 9600
HP.A HEAD PRESSURE CMP DELTA
A1.DT XX SCT DELTA FOR COMP A1 Range: 0 - 50 Default: 12
A2.DT XX
SCT DELTA FOR COMP A2 Range: 0 - 50 Default: 12
HP.B HEAD PRESSURE CMP DELTA
B1.DT XX SCT DELTA FOR COMP B1 Range: 0 - 50 Default: 12
B2.DT XX
SCT DELTA FOR COMP B2 Range: 0 - 50 Default: 12
ITEM
EXPANSION
COMMENT
0 = Enable/Off/Remote Switch 2 = Occupancy 3 = CCN Control
1 = Equal 2 = Staged
1 = Automatic 2 = Circuit A Leads 3 = Circuit B Leads
Default: 60
Range: 2 to 60 F
Default: 0 Minutes Range: 0 to 15 Minutes
0 = Mode Disable 1 = Fan Noise Only 2 = Fan/Compressor Noise
Default: 100% Range: 0 to 100%
Default: 1 Range: 1 to 239
Default: 0 Range: 0 to 239
1 = 2400 2 = 4800 3 = 9600 4 = 19,200 5 = 38,400
13
Table 10 — Configuration Mode and Sub-Mode Directory (cont)
ENTER
ENTER
ENTER
SUB-MODE
EXV.A CIR A EXV CONFIGURATION
EXV.B CIR B EXV CONFIGURATION
MM MOTORMASTER CONFIGURATION
KEYPAD
ENTRY
ITEM DISPLAY
STR.A XXX EXV CIRC.A START POS Range: 0 - 100 Default: 30
MIN.A XXX EXV CIRC.A MIN POSITION Range: 0 - 100 Default: 8
RNG.A XXXXX EXVA STEPS IN RANGE Range: 0 - 65535 Default: *
SPD.A XXXXX EXVA STEPS PER SECOND Range: 0 - 65535 Default: 200
POF.A XXX EXVA FAIL POSITION IN % Range: 0 - 100 Default: 0
MIN.A XXXXX EXVA MINIMUM STEPS Range: 0 - 65535 Default: 0
MAX.A XXXXX EXVA MAXIMUM STEPS Range: 0 - 65535 Default: *
OVR. A XXX EXVA OVERRUN STEPS Range: 0 - 65535 Default: 167
TYP.A 0,1 EXVA STEPPER TYPE
H.SCT XXX HIGH SCT THRESHOLD Range: 50 - 140 Default: 115
X.PCT XX OPEN EXV X% ON 2ND COMP Range: 0 - 30 Default: 10
X.PER XX MOVE EXV X% ON DISCRSOL Range: 0 - 30 Default: 5
A.PCT XXX PRE-OPEN EXV - FAN ADDING Range: 0 - 100 Default: 10
M.PCT XXX PRE-CLOSE EXV - FAN SUB Range: 0 - 100 Default: 10
S.PCT XXX PRE-CLOSE EXV - LAG SHUT Range: 0 - 100 Default: 10
DELY XXX LAG START DELAY Range: 0 - 100 Default: 10
STR.B XXX EXV CIRC.B START POS Range: 0 - 100 Default: 50
MIN.B XXX EXV CIRC.B MIN POSITION Range: 0 - 100 Default: 8
RNG.B XXXXX EXVB STEPS IN RANGE Range: 0 - 65535 Default: *
SPD.B XXXXX EXVB STEPS PER SECOND Range:
POF.B XXX EXVB FAIL POSITION IN % Range: 0 - 100 Default: 0
MIN.B XXXXX EXVB MINIMUM STEPS Range: 0 - 65535 Default: 0
MAX.B XXXXX EXVB MAXIMUM STEPS Range: 0 - 65535 Default: *
OVR. B XXX EXVB OVERRUN STEPS Range: 0 - 65535 Default: 167
TYP.B 0,1 EXVB STEPPER TYPE
MMR.S YES/NO MOTORMASTER SELECT
P.GAN XX HEAD PRESSURE P GAIN Range: -20 - 20 Default: 1.0
I.GAN XX HEAD PRESSURE I GAIN Range: -20 - 20 Default: 0.1
D.GAN XX HEAD PRESSURE D GAIN Range: -20 - 20 Default: 0.0
MIN.S XXX MINIMUM FAN SPEED Range: 0 - 100 Default: 5.0
ITEM
EXPANSION
COMMENT
0 = UNIPOLAR
1 = BIPOLAR Default: 1
0 - 65535 Default: 200
0 = UNIPOLAR
1 = BIPOLAR Default: 1
* Sizes 010-020 and 035-045, default is 1596. Sizes 025,030, and 050-060, default is 2500.
14
Table 10 — Configuration Mode and Sub-Mode Directory (cont)
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
RSET RESET COOL TEMP
CRST X COOLING RESET TYPE Default: No Reset
MA.DG XX.X F 4-20 - DEGREES RESET
RM.NO XXX.X F REMOTE - NO RESET TEMP
RM.F XXX.X F REMOTE - FULL RESET TEMP
RM.DG XX.X F REMOTE - DEGREES RESET
RT.NO XXX.X F RETURN - NO RESET TEMP
RT.F XXX.X F RETURN - FULL RESET TEMP
RT.DG XX.X F
RETURN - DEGREES RESET
DMDC X DEMAND LIMIT SELECT Default: None
DM20 XXX % DEMAND LIMIT AT 20 MA
SHNM XXX LOADSHED GROUP NUMBER
SHDL XXX % LOADSHED DEMAND DELTA
SHTM XXX MAXIMUM LOADSHED TIME
DLS1 XXX % DEMAND LIMIT SWITCH 1
DLS2 XXX % DEMAND LIMIT SWITCH 2
LLEN ENBL/DSBL LEAD/LAG CHILLER ENABLE Default: Disable
MSSL SLVE/MAST MASTER/SLAVE SELECT Default: Master
SLVA XXX SLAVE ADDRESS
LLBL X LEAD/LAG BALANCE SELECT
LLBD XXX LEAD/LAG BALANCE DELTA
LLDY XXX LAG START DELAY
PARA YES PARALLEL CONFIGURATION Default: YES (CANNOT BE CHANGED)
SLCT SETPOINT AND RAMP LOAD
CLSP X COOLING SETPOINT SELECT Default: Single
RL.S ENBL/DSBL RAMP LOAD SELECT Default: Enable
CRMP X.X COOLING RAMP LOADING
SCHD XX SCHEDULE NUMBER
Z.GN X.X DEADBAND MULTIPLIER
SERV SERVICE CONFIGURATION
EN.A1 ENBL/DSBL ENABLE COMPRESSOR A1 Unit dependent
EN.A2 ENBL/DSBL ENABLE COMPRESSOR A2 Unit dependent
EN.B1 ENBL/DSBL ENABLE COMPRESSOR B1 Unit dependent
EN.B2 ENBL/DSBL ENABLE COMPRESSOR B2 Unit dependent
ITEM
EXPANSION
COMMENT
0 = No Reset 1 = 4 to 20 mA Input 2 = Outdoor Air Temperature 3 = Return Fluid 4 = Space Temperature
Default: 0.0F Range: –30 to 30F
Default: 125F (51.7C) Range: 0° to 125F
Default: 0.0F (-17.8C) Range: 0 to 125F
Default: 0.0F Range: –30 to 30F
Default: 10.0F (5.6C) Range: 0 to 125F COOLER T
Default: 0.0F (0.0C) Range: 0 to 125F COOLER T
Default: 0.0F Range: –30 to 30F (–34.4 to -1.1 C)
0 = None 1 = Switch 2 = 4 to 20 mA Input 3 = CCN Loadshed
Default: 100% Range: 0 to 100%
Default: 0 Range: 0 to 99
Default: 0% Range: 0 to 60%
Default: 60 minutes Range: 0 to 120 minutes
Default: 80% Range: 0 to 100%
Default: 50% Range: 0 to 100%
Default: 0 Range: 0 to 239
Default: Master Leads 0 = Master Leads 1 = Slave Leads 2 = Automatic
Default: 168 hours Range: 40 to 400 hours
Default: 5 minutes Range: 0 to 30 minutes
0 = Single 1 = Dual Switch 2 = Dual CCN Occupied 3 = 4 to 20 mA Input (requires
EMM)
Default: 1.0 Range: 0.2 to 2.0
Default: 1 Range: 1 to 99
Default: 1.0 Range: 1.0 to 4.0
15
Table 10 — Configuration Mode and Sub-Mode Directory (cont)
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
SUB-MODE
BCST BROADCAST CONFIGURATION
KEYPAD
ENTRY
ITEM DISPLAY
T.D.BC ON/OFF CCN TIME/DATE BROADCAST
OAT.B ON/OFF CCN OAT BROADCAST
G.S.BC ON/OFF GLOBAL SCHEDULE BROADCAST
BC.AK ON/OFF CCN BROADCAST ACK’ER
ITEM
EXPANSION
Table 11 — Time Clock Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY SUB-ITEM DISPLAY
TIME TIME OF DAY
HH.MM XX.XX HOUR AND MINUTE Military (00:00 – 23:59)
DATE MONTH,DATE,DAY AND YEAR
MNTH XX MONTH OF YEAR 1-12 (1 = January, 2 = February, etc)
DOM XX DAY OF MONTH Range: 01-31
DAY X DAY OF WEEK 1-7 (1 = Sunday, 2 = Monday, etc)
YEAR XXXX YEAR OF CENTURY
DST DAYLIGHT SAVINGS TIME
STR.M XX MONTH Default: 4, Range 1 – 12
ITEM
EXPANSION
COMMENT
COMMENT
STR.W X WEEK Default: 1, Range 1 – 5
STR.D X DAY Default: 7, Range 1 – 7
MIN.A XX MINUTES TO ADD Default: 60, Range 0 – 99
STP.M XX MONTH Default: 10, Range 1 – 12
STP.W XX WEEK Default: 5, Range 1 – 5
STP.D XX DAY Default: 7, Range 1 – 7
MIN.S XX MINUTES TO SUBTRACT Default: 60, Range 0 – 99
HOL.L LOCAL HOLIDAY SCHEDULES HD.01 through HD.30
MON XX HOLIDAY START MONTH Range 0 – 12
DAY XX START DAY Range 0 – 31
LEN XX DURATION (DAYS) Range 0 - 99
SCH.N XX SCHEDULE NUMBER Default: 1, Range 1 – 99
SCH.L LOCAL OCCUPANCY SCHEDULE
PER.1 OCCUPANCY PERIOD 1*
OCC.1 XX:XX PERIOD OCCUPIED TIME Military (00:00 – 23:59)
UNC.1 XX.XX PERIOD UNOCCUPIED TIME Military (00:00 – 23:59)
MON.1 YES/NO MONDAY IN PERIOD
TUE.1 YES/NO TUESDAY IN PERIOD
WED.1 YES/NO WEDNESDAY IN PERIOD
THU.1 YES/NO THURSDAY IN PERIOD
FRI.1 YES/NO FRIDAY IN PERIOD
SAT.1 YES/NO SATURDAY IN PERIOD
SUN.1 YES/NO SUNDAY IN PERIOD
HOL.1 YES/NO HOLIDAY IN PERIOD
* Repeats for Occupancy Periods 2 through 8.
16
Table 11 — Time Clock Mode and Sub-Mode Directory (cont)
ENTER
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY SUB-ITEM DISPLAY
OVR SCHEDULE OVERRIDE
OVR.T X TIMED OVERRIDE HOURS Default: 0, Range 0-4 hours
OVR.L X OVERRIDE TIME LIMIT Default: 0, Range 0-4 hours
T.OVR YES/NO TIMED OVERRIDE User Entry
ITEM
EXPANSION
Table 12 — Operating Mode and Sub-Mode Directory
COMMENT
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
MODE MODES CONTROLLING UNIT
MD01 ON/OFF CSM CONTROLLING CHILLER
MD02 ON/OFF WSM CONTROLLING CHILLER
MD03 ON/OFF MASTER/SLAVE CONTROL
MD05 ON/OFF RAMP LOAD LIMITED
MD06 ON/OFF TIMED OVERRIDE IN EFFECT
MD07 ON/OFF LOW COOLER SUCTION TEMPA
MD08 ON/OFF LOW COOLER SUCTION TEMPB
MD09 ON/OFF SLOW CHANGE OVERRIDE
MD10 ON/OFF MINIMUM OFF TIME ACTIVE
MD13 ON/OFF DUAL SETPOINT
MD14 ON/OFF TEMPERATURE RESET
MD15 ON/OFF DEMAND/SOUND LIMITED
MD16 ON/OFF COOLER FREEZE PROTECTION
MD17 ON/OFF LOW TEMPERATURE COOLING
MD18 ON/OFF HIGH TEMPERATURE COOLING
MD19 ON/OFF MAKING ICE
MD20 ON/OFF STORING ICE
COMMENT
MD21 ON/OFF HIGH SCT CIRCUIT A
MD22 ON/OFF HIGH SCT CIRCUIT B
MD23 ON/OFF MINIMUM COMP ON TIME
MD24 ON/OFF PUMP OFF DELAY TIME
MD25 ON/OFF LOW SOUND MODE
LEGEND
CSM Chillervisor System Manager SCT Saturated Condensing Temperature WSM — Water System Manager
Table 13 — Alarms Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM
CRNT AXXX OR TXXX CURRENTLY ACTIVE ALARMS
RCRN YES/NO RESET ALL CURRENT ALARMS
HIST AXXX OR TXXX ALARM HISTORY
ITEM
EXPANSION
17
COMMENT
Alarms are shown as AXXX. Alerts are shown as TXXX.
Alarms are shown as AXXX. Alerts are shown as TXXX.
Table 14 — Operating Modes
MODE
NO.
01 CSM CONTROLLING CHILLER Chillervisor System Manager (CSM) is controlling the chiller.
02 WSM CONTROLLING CHILLER Water System Manager (WSM) is controlling the chiller.
03 MASTER/SLAVE CONTROL Dual Chiller control is enabled.
05
06
07
08
09
10 MINIMUM OFF TIME ACTIVE Chiller is being held off by Minutes Off Time (Configuration
13
14
15
16
17
18
19
20
21
22
23
24
25
ITEM EXPANSION DESCRIPTION
RAMP LOAD LIMITED Ramp load (pull-down) limiting in effect. In this mode, the rate at which leaving fluid temperature
TIMED OVERRIDE IN EFFECT Timed override is in effect. This is a 1 to 4 hour temporary override of the programmed
LOW COOLER SUCTION TEMPA Circuit A cooler Freeze Protection mode. At least one compressor must be on, and the Sat-
LOW COOLER SUCTION TEMPB Circuit B cooler Freeze Protection mode. At least one compressor must be on, and the Sat-
SLOW CHANGE OVERRIDE Slow change override is in effect. The leaving fluid temperature is close to and moving
DUAL SETPOINT Dual Set Point mode is in effect. Chiller controls to Cooling Set Point 1 (Set Points
TEMPERATURE RESET Temperature reset is in effect. In this mode, chiller is using temperature reset to adjust leav-
DEMAND/SOUND LIMITED Demand limit is in effect. This indicates that the capacity of the chiller is being limited by
COOLER FREEZE PROTECTION Cooler fluid temperatures are approaching the Freeze point (see Alarms and Alerts section
LOW TEMPERATURE COOLING Chiller is in Cooling mode and the rate of change of the leaving fluid is negative and
HIGH TEMPERATURE COOLING Chiller is in Cooling mode and the rate of change of the leaving fluid is positive and increasing.
MAKING ICE Chiller is in an unoccupied mode and is using Cooling Set Point 3 (Set Points
STORING ICE Chiller is in an unoccupied mode and is controlling to Cooling Set Point 2 (Set Points
HIGH SCT CIRCUIT A Chiller is in a Cooling mode and the Saturated Condensing Temperature (SCT) is greater than
HIGH SCT CIRCUIT B Chiller is in a Cooling mode and the Saturated Condensing Temperature (SCT) is greater than
MINIMUM COMP ON TIME Cooling load may be satisfied, however control continues to operate compressor to ensure
PUMP OFF DELAY TIME Cooling load is satisfied, however cooler pump continues to run for the number of minutes set
LOW SOUND MODE Chiller operates at higher condensing temperature and/or reduced capacity to minimize
is dropped is limited to a predetermined value to prevent compressor overloading. See Cooling Ramp Loading (Configuration desired, to any rate from 0.2° F to 2° F (0.1° to 1° C)/minute.
schedule, forcing unit to Occupied mode. Override can be implemented with unit under Local (Enable) or CCN (Carrier Comfort Network
urated Suction Temperature is not increasing greater than 1.1° F (0.6° C) in 10 seconds. If the saturated suction temperature is less than the Brine Freeze Point (Set Points
BR.FZ) minus 6° F (3.4° C) and less than the leaving fluid temperature minus 14° F (7.8° C) for 2 minutes, a stage of capacity will be removed from the circuit. Or, If the satu­rated suction temperature is less than the Brine Freeze Point minus 14° F (7.8° C), for 90 seconds, a stage of capacity will be removed from the circuit. The control will continue to decrease capacity as long as either condition exists.
urated Suction Temperature is not increasing greater than 1.1° F (0.6° C) in 10 seconds. If the saturated suction temperature is less than the Brine Freeze Point (Set Points
BR.FZ) minus 6° F (3.4° C) and less than the leaving fluid temperature minus 14° F (7.8° C) for 2 minutes, a stage of capacity will be removed from the circuit. Or, If the satu­rated suction temperature is less than the Brine Freeze Point minus 14° F (7.8° C), for 90 seconds, a stage of capacity will be removed from the circuit. The control will continue to decrease capacity as long as either condition exists.
towards the control point.
CSP.1) during occupied periods and Cooling Set Point 2 (Set PointsCOOLCSP.2) during unoccupied periods.
ing fluid set point upward and is currently controlling to the modified set point. The set point can be modified based on return fluid, outdoor-air-temperature, space temperature, or 4 to 20 mA signal.
demand limit control option. Because of this limitation, the chiller may not be able to pro­duce the desired leaving fluid temperature. Demand limit can be controlled by switch inputs or a 4 to 20 mA signal.
for definition). The chiller will be shut down when either fluid temperature falls below the Freeze point.
decreasing faster than -0.5° F per minute. Error between leaving fluid and control point exceeds fixed amount. Control will automatically unload the chiller if necessary.
Error between leaving fluid and control point exceeds fixed amount. Control will automatically load the chiller if necessary to better match the increasing load.
CSP.3) to make ice. The ice done input to the Energy Management Module (EMM) is open.
CSP.2). The ice done input to the Energy Management Module (EMM) is closed.
the calculated maximum limit. No additional stages of capacity will be added. Chiller capacity may be reduced if SCT continues to rise to avoid high-pressure switch trips by reducing con­densing temperature.
the calculated maximum limit. No additional stages of capacity will be added. Chiller capacity may be reduced if SCT continues to rise to avoid high-pressure switch trips by reducing con­densing temperature.
proper oil return. May be an indication of oversized application, low fluid flow rate or low loop volume.
by the configuration variable Cooler Pump Shutdown Delay (Configuration
PM.DY).
overall unit noise during evening/night hours (Configuration
SLCTCRMP). The pull-down limit can be modified, if
®
) control. Override expires after each use.
OPT2DELY).
OPT2LS.MD).

OPT1
FRZ
FRZ
COOL
COOL

COOL
18
CONTROLS
General —
the ComfortLink™ electronic control system that controls and monitors all operations of the chiller.
The control system is composed of several components as listed in the sections below. See Fig. 3-5 for typical control box drawings. See Fig. 6 and 7 for control schematics.
The 30RAP air-cooled scroll chillers contain
Main Base Board (MBB) — See Fig. 8. The MBB is
the heart of the ComfortLink control system. It contains the major portion of operating software and controls the operation of the machine. The MBB continuously monitors input/output channel information received from its inputs and from all other modules. The MBB receives inputs from the discharge and suction pressure transducers and thermistors. See Table 15. The MBB also receives the feedback inputs from each compressor current sensor board and other status switches. See Table 16. The MBB also controls several outputs. Relay outputs con­trolled by the MBB are shown in Table 17. Information is transmitted between modules via a 3-wire communication bus or LEN (Local Equipment Network). The CCN (Carrier Com­fort Network) bus is also supported. Connections to both LEN and CCN buses are made at the LVT (low voltage terminal). See Fig. 8.
Energy Management Module (EMM) — The EMM
module is available as a factory-installed option or as a field­installed accessory. The EMM module receives 4 to 20 mA inputs for the leaving fluid temperature reset, cooling set point and demand limit functions. The EMM module also receives the switch inputs for the field-installed 2-stage demand limit and ice done functions. The EMM module communicates the status of all inputs with the MBB, and the MBB adjusts the control point, capacity limit, and other functions according to the inputs received.
Current Sensor Board (CSB) — The CSB is used to
monitor the status of the compressors by measuring current and providing an analog input to the main base board (MBB) or compressor expansion module (CXB).
AUX Board (AUX) — The AUX is used with the digital
scroll option and the low ambient head pressure option. It pro­vides additional inputs and outputs for digital scroll control along with analog outputs to control head pressure control fan speeds.
Expansion Valve Board (EXV) — The EXV board
communicates with the MBB and directly controls the expan­sion valves to maintain the correct compressor superheat.
Enable/Off/Remote Contact Switch — The Enable/
Off/Remote Contact switch is a 3-position switch used to control the chiller. When switched to the Enable position the chiller is under its own control. Move the switch to the Off position to shut the chiller down. Move the switch to the Remote Contact position and a field-installed dry contact can be used to start the chiller. The contacts must be capable of handling a 24 vac, 50-mA load. In the Enable and Remote Contact (dry contacts closed) positions, the chiller is allowed to operate and respond to the scheduling configuration, CCN configuration and set point data. See Fig. 9.
Emergency On/Off Switch — The Emergency On/Off
switch should only be used when it is required to shut the chiller off immediately. Power to the MBB, EMM, and marquee display is interrupted when this switch is off and all outputs from these modules will be turned off.
Board Addresses — The main base board (MBB) has a
3-position instance jumper that must be set to ‘1.’ The elec­tronic expansion valve board (EXV) and energy management board (EMM) have 4-position DIP switches. All switches are
set to ‘On’ for these boards. The auxiliary board (AUX) has an 8-position DIP switch. Switches 2, 5, and 7 are set to ‘On.’
Control Module Communication
RED LED — Proper operation of the control boards can be visually checked by looking at the red status LEDs (light-emitting diodes). When operating correctly, the red status LEDs should be blinking in unison at a rate of once every 2 seconds. If the red LEDs are not blinking in unison, verify that correct power is being supplied to all modules. Be sure that the main base board (MBB) is supplied with the current soft­ware. If necessary, reload current software. If the problem still persists, replace the MBB. A red LED that is lit continuously or blinking at a rate of once per second or faster indicates that the board should be replaced.
GREEN LED — The MBB has one green LED. The Local Equipment Network (LEN) LED should always be blinking whenever power is on. All other boards have a LEN LED which should be blinking whenever power is on. Check LEN connections for potential communication errors at the board J3 and/or J4 connectors. Communication between modules is accomplished by a 3-wire sensor bus. These 3 wires run in parallel from module to module. The J4 connector on the MBB provides both power and communication directly to the marquee display only.
YELLOW LED — The MBB has one yellow LED. The Carrier Comfort Network (CCN) LED will blink during times of network communication.
Carrier Comfort Network® (CCN) Interface —
The 30RAP chiller units can be connected to the CCN if desired. The communication bus wiring is a shielded, 3-conductor cable with drain wire and is supplied and installed in the field. See Table 18. The system elements are connected to the communication bus in a daisy chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system elements on either side of it. This is also required for the negative and signal ground pins of each system element. Wiring connections for CCN should be made at LVT. Consult the CCN Contrac­tor’s Manual for further information.
NOTE: Conductors and drain wire must be 20 AWG (Ameri­can Wire Gage) minimum stranded, tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of –20 C to 60 C is required. Wire manufactured by Alpha (2413 or 5463), American (A22503), Belden (8772), or Columbia (02525) meets the above mentioned requirements.
It is important when connecting to a CCN communication bus that a color coding scheme be used for the entire network to simplify the installation. It is recommended that red be used for the signal positive, black for the signal negative, and white for the signal ground. Use a similar scheme for cables contain­ing different colored wires.
At each system element, the shields of its communication bus cables must be tied together. If the communication bus is entirely within one building, the resulting continuous shield must be connected to a ground at one point only. If the commu­nication bus cable exits from one building and enters another, the shields must be connected to grounds at the lightning suppressor in each building where the cable enters or exits the building (one point per building only). To connect the unit to the network:
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white (ground), and black (–) conductors. (Substitute appropri­ate colors for different colored cables.)
19
3. Connect the red wire to (+) terminal on LVT of the plug, the white wire to COM terminal, and the black wire to the (–) terminal.
4. The RJ14 CCN connector on LVT can also be used, but is only intended for temporary connection (for example, a laptop computer running Service Tool).
IMPORTANT: A shorted CCN bus cable will prevent some routines from running and may prevent the unit from start­ing. If abnormal conditions occur, unplug the connector. If conditions return to normal, check the CCN connector and cable. Run new cable if necessary. A short in one section of the bus can cause problems with all system elements on the bus.
Table 15 — Thermistor Designations
THERMISTOR
LWT J8-13,14 (MBB) Cooler Leaving Fluid
EWT J8-11,12 (MBB) Cooler Entering Fluid
RGTA
RGTB
OAT
SPT
DTT
LEGEND
LWT — Leaving Water Temperature MBB — Main Base Board
PIN
CONNECTION
POINT
J8-1,2 (MBB) Circuit A Return Gas
J8-3,4 (MBB) Circuit B (035-060 only)
J8-7,8 (MBB) Outdoor-Air Temperature
J8-5,6 (MBB) TB5-5,6
J6-1,2 (AUX) Discharge Temperature
THERMISTOR INPUT
Temperature
Return Gas Temperature
Sensor Accessory Remote Space
Temperature Sensor or Dual LWT Sensor
Thermistor
Table 16 — Status Inputs
STATUS SWITCH PIN CONNECTION POINT Chilled Water Pump 1 J7-1,2 Chilled Water Pump 2 J7-3,4
Remote On/Off LVT-13,14
Cooler Flow Switch J7-9,10 Compressor Fault Signal, A1 J9-11,12 Compressor Fault Signal, A2 J9-5,6 Compressor Fault Signal, B1 J9-8,9 Compressor Fault Signal, B2 J9-2,3
Table 17 — Output Relays
RELAY
NO.
Energize Compressor A1 (010-030)
K1
Energize Compressor A1 and Condenser Fan Contac­tor 3 (055,060)
K2 Energize Compressor A2 (all but 010, 015 60 Hz) K3 Energize Chilled Water Pump 1 Output K4 Energize Chilled Water Pump 2 Output
Energize Compressor B1 (035-050)
K5
Energize Compressor B1 and Condenser Fan Contac­tor 3 (055,060)
K6 Energize Compressor B2 (035-060) K7 Alarm Relay K8 Cooler/Pump Heater
K9 Energize Condenser Fan Contactor 1 (018-060) K10 Energize Condenser Fan Contactor 2 (018-060) K11 Minimum Load Valve
DESCRIPTION
Table 18 — CCN Communication Bus Wiring
MANUFACTURER
Alpha 1895 American A21451 A48301 Belden 8205 884421 Columbia D6451 Manhattan M13402 M64430 Quabik 6130
Regular Wiring Plenum Wiring
PART N O .
Sensors — The electronic control uses 4 to 7 thermistors to
sense temperatures for controlling chiller operation. See Table 15. These sensors are outlined below. Thermistors RG­TA, RGTB, EWT, LWT, and OAT are identical in temperature versus resistance and voltage drop performance. The dual chill­er thermistor is 5 kat 77 F (25 C)thermistor. Space tempera­ture thermistor is a 10 kat 77 F (25 C). The DTT thermistor is an 86 kat 77 F (25 C)thermistor. See Thermistors section for temperature-resistance-voltage drop characteristics.
COOLER LEAVING FLUID SENSOR — The thermistor is installed in a well in the factory-installed leaving fluid piping coming from the bottom of the brazed-plate heat exchanger.
COOLER ENTERING FLUID SENSOR — The thermistor is installed in a well in the factory-installed entering fluid piping coming from the top of the brazed-plate heat exchanger.
COMPRESSOR RETURN GAS TEMPERATURE SEN­SOR — These thermistors are installed in a well located in the suction line of each circuit.
OUTDOOR-AIR TEMPERATURE SENSOR (OAT) — This sensor is factory installed on a bracket which is inserted through the base pan of the unit.
DISCHARGE TEMPERATURE THERMISTOR (DTT) — This sensor is only used on units with a digital compressor. The sensor is mounted on the discharge line close to the discharge of the digital compressor. It attaches to the dis­charge line using a spring clip and protects the system from high discharge gas temperature when the digital compressor is used. This sensor is a connected to the AUX board.
REMOTE SPACE TEMPERATURE SENSOR OR DUAL LEAVING WATER TEMPERATURE SENSOR — One of two inputs can be connected to the LVT. See appropriate sen­sor below.
Remote Space Temperature Sensor 33ZCT55SPT) is an accessory sensor that is remotely mounted in the controlled space and used for space temperature reset. The sensor should be installed as a wall-mounted thermostat would be (in the conditioned space where it will not be sub­jected to either a cooling or heating source or direct exposure to sunlight, and 4 to 5 ft above the floor).
Space temperature sensor wires are to be connected to terminals in the unit main control box. The space temperature sensor includes a terminal block (SEN) and a RJ11 female connector. The RJ11 connector is used access into the Carrier Comfort Network
®
(CCN) at the sensor.
To connect the space temperature sensor (Fig. 10):
1. Using a 20 AWG twisted pair conductor cable rated for the application, connect 1 wire of the twisted pair to one SEN terminal and connect the other wire to the other SEN terminal located under the cover of the space temperature sensor.
2. Connect the other ends of the wires to terminals 5 and 6 on TB5 located in the unit control box.
— Sensor (part no.
20
Units on the CCN can be monitored from the space at the sensor through the RJ11 connector, if desired. To wire the RJ11 connector into the CCN (Fig. 11):
IMPORTANT: The cable selected for the RJ11 connector wiring MUST be identical to the CCN communication bus wire used for the entire network. Refer to Table 18 for acceptable wiring.
1. Cut the CCN wire and strip ends of the red (+), white (ground), and black (–) conductors. (If another wire color scheme is used, strip ends of appropriate wires.)
2. Insert and secure the red (+) wire to terminal 5 of the space temperature sensor terminal block.
LEGEND FOR FIG. 3-7
ALMR Alarm Relay AUX Auxilliary BR Boiler Relay C—Contactor, Compressor CB Circuit Breaker CCB Compressor Circuit Breaker CH Crankcase Heater CHC Cooler/Pump Heater Contactor COMP Compressor CSB Current Sensor Board CWFS Chilled Water Flow Switch CWP Chilled Water Pump DGS Digital Scroll Compressor DPT Discharge Pressure Transducer DTT Discharge Temperature Thermistor DUS Digital Unloader Solenoid EMM Energy Management EXV Electronic Expansion Valve FB Fuse Block FC Fan Contactor FCB Fan Circuit Breaker FIOP factory Installed Option FR Fan Relay GND Ground HPS High-Pressure Switch LON Local Operating Network LV T Low Voltage Terminal Block MBB Main Base Board MLV Minimum Load Valve MM Motormaster MP Motor Protector MS Manual Starter NEC National Electrical Code OAT Outdoor-Air Thermistor OFM Outdoor Fan Motor RGT Return Gas Thermistor SCCR Short Circuit Current Rating SPT Suction Pressure Transducer SW Switch TB Terminal Block TNKR Storage Tank Heater Relay TRAN Transformer UPC Unitary Protocol Converter
Terminal Block
Terminal (Unmarked)
Terminal (Marked)
Splice
Factory Wiring
Field Wiring
Accessory or Option Wiring
To indicate common potential only; not to represent wiring.
3. Insert and secure the white (ground) wire to terminal 4 of the space temperature sensor.
4. Insert and secure the black (–) wire to terminal 2 of the space temperature sensor.
5. Connect the other end of the communication bus cable to the remainder of the CCN communication bus.
Dual Leaving Water Temperature Sensor
— For dual chiller applications (parallel only are supported), connect the dual chiller leaving fluid temperature sensor (refer to Configuring and Operating Dual Chiller Control section on page 36) to the space temperature input of the Master chiller. If space tempera­ture is required for reset applications, connect the sensor to the Slave chiller and configure the slave chiller to broadcast the value to the Master chiller.
21
CONTROL BOX
FAN
1
A1
COMPRESSOR
LOCATED OVER EMM AND EXV
EMM
EXV
LON
AUX
UPC
TB1
TB4
CSB-A1
MBB
CHC
CCB
FB-1
TRAN
DISCONNECT
OPTION/TB
C-A1
MM
MS-
CWP1
CWP1
MS-
CWP2
CWP2
Fig. 3 — Typical Control Box for 30RAP010,015
Fig. 4 — Typical Control Box for 30RAP018-030
a30-4962
a30-4963
FB-1
AUX
LON
EMM
EXV
CHC
CCB-1
CSB-A1
TB1
UPC
TB4
C-A1
FC1/MM
MBB
FB-3
MS-
CWP1
CWP1 CWP2
TRAN
MS-
CWP2
CSB-A2
FC2 C-A2
CCB-2
DISCONNECT
OPTION/TB
22
Fig. 5 — Typical Control Box for 30RAP035-060
a30-4964
OPTION/TB
DISCONNECT
CHC
EXV
EMM
CB-4
CB-3
TB1
CSB-B2
CSB-B1
UPC
LON
AUX
TB4
MS-
MS-
CWP2
CWP1
FR-4
FR-3
C-B2
CWP2
CWP1
C-B1
MBB
055,060 UNIT ONLY
B2
2
4
FAN
FAN
FAN3FAN
LOCATED OVER EMM AND EXV
1
B1
A2
COMPRESSORS
A1
CONTROL BOX END
FCB-1/2/3
CB-2
CB-1
TRAN-1
CSB-A2
CSB-A1
TRAN-2
23
FC-3
FC-2
MM
FC-1
FR-2
FR-1
C-A2
C-A1
OPTIONAL
Fig. 6A — Typical Wiring Schematic, 30RAP018-030 Units — Power Wiring
a30-4965
DISCONNECT
DISCONNECT
TO FUSED
PER NEC
EQUIP GND
~
FU5
RED
1
H3
H4
TRAN3
X3
WHT
WHT
GRN/YEL
2
GFI-CO
FIOP/ACCESSORY
SILVER SCREW
SILVER SCREW
GRN-YEL
FUSE
NUMBER
FU1 & FU2
380-3-60,460-3-60,575-3-60
FU3 (24V)
208/230-3-60,230-3-60
380-3-60,460-3-60,575-3-60
FU4 (115V)
380-3-60,460-3-60,575-3-60
FB1
(NO MM)
380-3-60,460-3-60,575-3-60
FB1
(WITH MM)
380-3-60,460-3-60,575-3-60
FB2
380-3-60,460-3-60,575-3-60
FB3
VOLTAGE SERIES
575-3-60 100 H1 & H2
380-3-60 200 H1 & H2
230-3-60 500 H2 & H4
208-3-60 500 H3 & H4
460-3-60 600 H1 & H4
CONNECT FOR APPROPRIATE PRIMARY VOLTAGE SEE TABLE 1
TB4
XF
RED
7
FU3
RED
A1
SW2
C1
B1
VIO
CB3
3.2 AMPS
TB4
VIO
6
VIO
CB1A
1
2
3
H2
~
SECONDARY
115V
LINE
RESET
TEST
LOAD
UNIT VOLTAGE
208/230-3-60
380-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60,575-3-60
208/230-3-60
208/230-3-60
208/230-3-60
208/230-3-60
TABLE 1
TRAN1
PRIMARY
H2
H1
SECONDARY 24V
X1
BRN
VIO
3
2
BRN
1
VIO
BRN
VIO
BRN
STANDARD
TERMINAL
BLOCK
TB1A
TO FUSED DISCONNECT
11
PER NEC
12
13
~
FU6
BLK
1
HF
H1
X1
FU4
XF
BLK
2
BRASS SCREW
BRASS SCREW
VOLTAGE SERIES
575-3-60 100 H1-H2 XF-X2
230-3-60 400,500 H2-H4 XF-X2
208-3-60 500 H3-H4 XF-X2
460-3-60 600 H1-H4 XF-X2
REPLACE
TRAN
WITH
SIZE
FNQ-R-3.5
FNQ-R-2.5
200VA
FNQ-R-2
FNQ-R-1.5
FNM-10
200VA
FNQ-R-2.5
AV0056UF & 5UF
FNQ-R-3.5
FNM-6
500VA
LP-CC-20
NONE
KTK-R-15
NONE
KTK-R-20208/230-3-60
LP-CC-20
NONE
LP-CC-20
NONE
TERMINAL
CONNECTIONS
FOR PRIMARY SIDE
FU1
BLK
FU2
YEL
H3
H4
X2
GRN/YEL
BRN
BRN
C
TB1
UPC FIOP
24VAC
2
GND
UPC
HOT
1
3
J1
3
3
2
1
CWFS
MBB
2
2
BRN
1
1
RED
J2
31
BRN
BLU
21
22
23
CONNECTIONS
FOR PRIMARY SIDE
TERMINAL
3
2
1
BLK BLK BLK
YEL YEL YEL
BLU BLU BLU
CONNECTIONS FOR SECONDARY SIDE
TB4CTB1
5
RED BRN
FIOP/ACCESSORY
J1
3
2
EMM
1
J2
TERMINAL
CH-A1
BLU
T2
T3
T2
T3
FC1
11 21
12
13 23
FC2
11 21
12
13 23
CA1
11 21
12 22
13 23
CA2
11 21
12 22
13 23
22
22
CHC
42
CHC
86
BLK
BLK
YEL
BLU
BLU BLK
BLK
YEL
BLU
BLK
BLK
BLK
BLK
BLK
BLK
BLK-1
BLK-2
BLK-3
BLK-1
BLK-2
BLK-3
~
COOLER/PUMP HEATERS (380,460,575V)
~~
~
CH-A2
BLK
WHT
BLK
1
T1
2
T2
3
1
2
3
COMP A1
T3
GRN/YEL
T1
COMP A2
T2
T3
GRN/YEL
L1
CWP1 WATER
L2
PUMP
L3
GRN/YEL
L1
CWP2 WATER
L2
PUMP
L3
GRN/YEL
1
2
3
1
2
3
1
3
2
BLK
BLK
COOLER/PUMP HEATERS (208/230,230V)
~
WHT
OFM1
GRN/YEL
OFM2
GRN/YEL
1
2
3
380V,460V,575V
CCB-1
ONLY
11
BLK
12
YEL
13
FB3
11
12
13
HIGH SCCR ONLY
BLU
BLK
YEL
BLU
208/230V ONLY
21
11
BLK
22
12
YEL
23
13
BLU
CCB-2
11
12
13
MS-CWP1
L1
BLK
YEL
L2
BLU
L3
MS-CWP2
L1
BLK
YEL
L2
BLU
L3
FB1
21
22
23
YEL
BLUBLK
BLK
YEL
BLU
CSB-A1
21
BLK
22
YEL
BLU
23
YEL
BLU BLK
CSB-A2
21
BLK
22
YEL
23
BLU
CHILLED WATER PUMP FIOP
CWP1
L1 T1
T1
L2
T2
T3
L3
CWP2
L1 T1
T1
L2
T2
T3
L3
BLK
YEL
BLU
BLK
YEL
BLU
YEL
BLUBLK
BLK
YEL
LOW AMBIENT OPERATION (MOTORMASTER V) FIOP/ACCESSORY
FB3
11
21
BLK
22
12
YEL
13
23
BLU
HIGH SCCR ONLY
NOTES:
1. FACTORY WIRING IS IN ACCORDANCE WITH UL 1995 STANDARDS. ANY FIELD MODIFICATIONS OR ADDITIONS MUST BE IN COMPLIANCE WITH ALL APPLICABLE CODES.
C MIN WIRE FOR FIELD POWER SUPPLY.
3. ALL FIELD INTERLOCK CONTACTS MUST HAVE A MIN RATING OF 2 AMPS @ 24VAC SEALED. SEE FIELD INTERLOCK WIRING.
4. COMPRESSOR AND FAN MOTORS ARE THERMALLY PROTECTED-­ THREE PHASE MOTORS PROTECTED AGAINST PRIMARY SINGLE PHASE CONDITIONS.
5. TERMINALS 13 & 14 OF LVT ARE FOR FIELD CONNECTION OF REMOTE ON-OFF. THE CONTACT MUST BE RATED FOR DRY CIRCUIT APPLICATION CAPABLE OF HANDLING A 5VDC 1 MA TO 20 MA LOAD.
6. FOR 500 SERIES UNIT OPERATION AT 208-3-60V LINE VOLTAGE, TRAN1 PRIMARY CONNECTIONS MUST BE MOVED TO TERMINALS H3 & H4.
7. FOR UNITS WITH LOW AMBIENT MOTOR MASTER V FIOP/ACCESSORY, FAN CONTACTOR FC1 IS REPLACED WITH MOTORMASTER RELAY MMR.
J1
EXV
J2
DGS FIOP
12
11
J1
AUX
3
3
2
2
1
1
3
3
2
2
BRN
1
1
RED
3
3
2
2
2
BRN
1
1
1
RED
FB1
11
21
BLK
22
12
YEL
13
23
BLU
FB2
11
21
BLK
22
12
YEL
13
23
BLU
MM-A
L1 T1
BLK
L2 T2
YEL
L3 T3
BLU
2
*1
25
2
FC2
11 21
BLK
YEL
22
12
13 23
BLU
BLK
YEL
CHC
42
CHC
86
1
BLK-1
2
BLK-2
3
BLK-3
YEL
MMR
VIO
11 14
240 1/4W
RED
FROM AUX-J4
BLK
BLK-1
BLK-2
BLK-3
~
BLK
WHT
COOLER/PUMP HEATERS (380,460,575V)
~~
~
BLK
8. IF CHILLED WATER PUMP INTERLOCK IS USED, REMOVE JUMPER FROM TERMINAL 11 TO 17 AND WIRE INTERLOCK CONTACT ACROSS TERMINALS 11 & 17.
9. MP-A1 NOT USED IN THE FOLLOWING UNITS:
018,020: ALL UNITS 025,030: 460V UNITS WITHOUT DIGITAL SCROLL
10. MP-A2 NOT USED IN THE FOLLOWING UNITS:
018-020: ALL UNITS 025,030: 460V UNITS
11. JUMPER PLUG REQUIRED WHEN MP NOT USED
* MM SIGNAL CONNECTION
1
2
3
~
1
3
2
OFM1
GRN/YEL
VOLTAGE
208/230/460/575
380
BLK
BLK
COOLER/PUMP HEATERS (208/230,230V)
~
WHT
OFM2
GRN/YEL
ZHBT
061
06A31
1
2
3
24
HEAT
Fig. 6B — Typical Wiring Schematic, 30RAP018-030 Units — Control Wiring
a30-4966
SEE NOTES ON PAGE 24.
CWPI
SEE
NOTE 8
REMOTE
ON-OFF
SWITCH
(SEE NOTE
5)
DUAL
SETPOINT
J10A
J10B
RLY 11
RLY 9
RLY 10
RLY 5
RLY 6
RLY 7
RLY 8
RLY 1
RLY 2
RLY 3
RLY 4
RED
WHT
BLK
RED
BLK
WHT
MBB
LVT
20
19
LVT
17
11
13
14
15
16
LEN CCN
J1
PORT 2
PORT 1A
J12
6
7
J11
2
3
4
11
12
13
14
9
7
8
6
5
LVT
(+)
(COM)
(-)
SHIELD
UPC
NET +
1
NET -
2
N/C
3
N/C
4
SIGNAL
5
NET +
1
NET 2
2
SHIELD
3
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
1
10
2
11
3
12
4
13
5
14
6
15
7
16
8
17
9
18
10
19
11
20
12
21
13
22
14
23
15
24
16
25
17
26
18
27
BR
HEAT/BOILER FIELD
INSTALLED WIRING
BLK
RED
OFF
RED
RED
VIO
J13
BLK
1
WHT
2
RED
3
BRN
4
RED
5
BLK
6
WHT
7
RED
8
OPTION
J3
UPC OPT
CB1
3.2 AMPS
CB2
5.2 AMPS
TB4
ORN
5
RED
RED
RED
GRA
PNK
A2
SW2
RED
ORN
C2
ORN
B2
RED
TB4
7
XF
RED
BLK
TRAN1
SECONDARY 24V
X1
FU3
GRA
GRA
MLV-A
MLV ACCSY
FC1
PNK
SEE NOTE 7
ORN
TB4
RED
4
RED
RED
BLK
RED
ORN
HPS-A
BLK
BLK
BLK
ORN
GRA
SEE NOTE 11
SEE NOTE 11
VIO
RED
6
6
GRA
5
5
GRA
4
4
3
J6
HR
ALMR
3
2
2
VIO
1
1
BRN
LVT
J11
18
1
STORAGE TANK HEATER RELAY
ORN
PL1-2PL1-1
MP-A1
VIO
VIO
VIO
M1
M2
VIO
PL1-6PL1-5
MP-A2
VIO
M1
M2
VIO
LVT
J12
25
1
2
24
ORN
MAX LOAD-5VA SEALED
10VA INRUSH
ACCESSORY
RED
ORN
ORN
GRA
VIO
RED
FIOP OR
FIELD INSTALLED
OPTION
FIELD INSTALLED
MAX LOAD-5VA SEALED
10VA INRUSH
FC2
ALM
R
TNK
R
CHC
CA1
CA2
CWP
1
CWP
2
RED
TB1
X2
GRN/YEL
BRN
A2A1
A2A1
A2A1
A2A1
BRN
BRN
BRN
BRN
BRN
BRN
BRN
C
BRN
BRN
BRN
BRN
BRN
BRN
BRN
LVT
J12
5
21
BRN
BRN
BRN
BRN
A2A1
A2A1
A2A1
BRN
BRN
BRN
BRN
A2
A2
A2
A2
A2
A2
A2
C
C
C
A2
A2
C
A2
A2
MBB J1-2
UPC GND
CWFS 3
EXV J1-2
LVT J12-5
CHC
CA1
CWP1
CA2
FC2
FC1
FC3
TB1
TB1
TB1
CA2
CA1
TB1
CWP2
CWP1
TB4
4
RED
SEE NOTE 9
T2T1MP-A1
SEE NOTE 10
T2T1MP-A2
PL1-4
BRN
BRN
PL1-8
BRN
BRN
PL1-3
RED
RED
PL1-7
RED
RED
BRN
CWFS
4
2
10
10
WHT
1
RED
1
2
WHT
2
3
J3
9
ORN
9
J4
MAIN BASE
8
8
SW1
A1
ENABLE
RED
C1
B1
RED
GRA
GRA
13
RED
14
CWP2
13
VIO
14
CWP1
BRN
RED
BLK
WHT
RED
BLK
WHT
RED
LON
GND
NET
J4
1
2
BOARD
7
7
6
6
5
5
4
4
3
3
2
2
1
1
10
10
9
9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1
1
J9
J7
J8
J5
BLK
3
4
4
1
RED
1
2
WHT
2
3
BLK
3
4
4
5
BRN
5
6
RED
6
1
1
RED
2
2
ORN
3
3
BRN
4
4
RED
5
5
ORN
6
6
BRN
7
7
RED
8
8
ORN
9
9
BRN
10
10
RED
11
11
ORN
12
12
BRN
1
1
2
2
3
3
4
4
5
5
6
6
1
7
2
8
3
9
4
10
1
11
2
12
3
13
4
14
1
15
2
16
3
17
4
18
5
19
6
20
7
21
8
22
9
23
10
24
11
25
12
26
1
MARQUEE
RED
1
DISPLAY
2
WHT
2
3
BLK
3
4
4
5
RED
5
6
BRN
6
2
CSB
3
B2
1
2
CSB
3
A2
1
2
CSB
3
B1
1
2
CSB
3
A1
1
B
C
A
B
C
A
RGTA
OAT
EVAPORATOR ENTERING FLUID TEMP
EVAPORATOR LEAVING FLUID TEMP
+
DPTA
-
+
SPTA
-
LVT
J12 T55
3
4
23
22
T-55
SEN
ACCSY
SPACE TEMPERATURE ACCESSORY OR DUAL CHILLER LWT
RED
BLK
BLU
BLU
RED
BLK
RED
BLK
RED
BLK
RED
GRN
BLK
RED
GRN
BLK
BLK
WHT
RED
BLK
WHT
RED
BLK
WHT
RED
BLK
WHT
RED
BLK
WHT
RED
4
4
3
3
2
2
1
1
4
4
3
3
2
2
1
1
6
-
3
5
G
2
4
+
1
3
-
3
2
G
2
1
+
1
12345678
DARK = SWITCH LOCATION
4
4
3
3
2
2
1
1
4
4
3
3
2
2
1
1
ACCESSORY
J3
J4
J9
DGS OR
FIOP
J3
J4
FIOP/
MM
EXV
AUX
EMM
1
1
2
2
3
3
J7
4
4
5
5
PL-EXVA
BLK
1
1
BLK
YEL
2
2
WHT
3
3
J6
4
GRN
4
5
5
RED
7
-
VIO RED
7
8
J2
CH1
BRN BLK
8
1
CH11
RED RED
1
2
J6
-
BLK BLK
2
1
CH9
RED
1
2
J4
-
BLK
2
ON
OFF
J5
J7
J6
1
CH10
1
2
-
2
1
1
GRA
2
2
GRA
3
3
RED
4
4
RED
5
5
BLU
6
6
BLU
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
1
1
2
2
VIO
3
3
BRN
4
4
5
5
ORN
6
6
7
7
8
8
PNK
9
9
10
10
11
11
12
12
PL50-1
PL50-2
PL50-3
PL50-4
TO MM-A
J10
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
EXV-A
GRY
RED
DUS
DTT
LVT
1
2
ICE DONE
3
4
DLS STEP 1
5
6
DLS STEP 2
DEMAND
+
7
LIMIT
-
8
4-20mA
TEMP
9
+
RESET
-
4-20mA
COOLING
+
10
SETPOINT
-
4-20mA
25
COMP A2
GRN/YEL
TRAN1
H2
H3
H4
SECONDARY 24V
RED
FC2
BLK-1
BLK-2
BLK-3
FU3
SW2
C1
A1
B1
1
2
3
H1
X1
CONNECT FOR APPROPRIATE PRIMARY VOLTAGE SEE TABLE 1
1
2
3
CB1A
11
12
13
TO FUSED
DISCONNECT
PER NEC
OPTIONAL
DISCONNECT
3.2 AMPS
CB3
1
2
3
T3
T1
T2
T3
T1
T2
3
2
1
LOW AMBIENT OPERATION (MOTORMASTER V) FIOP/ACCESSORY
GRN/YEL
GRN/YEL
XF
VIO
11 21
12
22
13 23
11 21
12 22
13 23
CA1
BLK
YEL
BLU
11 21
12 22
13 23
CA2
11
12
13
21
22
23
CCB-1
BLK
YEL
BLU
BLK
YEL
BLU
YEL
BLU BLK
YEL
BLU
BLK
11
12
13
21
22
23
CCB-2
BLK
YEL
BLK
380V,460V,575V
ONLY
BLU
YEL
BLU
GRN/YEL
OFM1
FC3
1
2
3
11 21
12
22
13 23
COMP B2
1
2
3
T3
T1
T2
T3
T1
T2
3
2
1
GRN/YEL
GRN/YEL
11 21
12 22
13 23
CB1
BLK
YEL
BLU
11 21
12 22
13 23
CB2
11
12
13
21
22
23
CCB-3
BLK
YEL
BLU
BLK
YEL
BLU
YEL
BLU BLK
YEL
BLU
BLK
11
12
13
21
22
23
CCB-4
BLK
YEL
380V,460V,575V
ONLY
208/230V ONLY
BLU
BLU
BLU
BLU BLU
YEL
YEL
YEL YEL
BLK
BLK
BLK BLK
BLK-1
BLK-2
BLK-3
BLK
YEL
BLU
BLK
YEL
BLU
YEL
BLUBLK
BRN
FU1
BLK
FU2
YEL
GRN/YEL
TRAN2
COM
RED
7
TB4
VIO
6
TB4
VIO
C
TB1
BLK
YEL
BRN
BRN
PRIMARY
PRIMARY
CONNECT FOR APPROPRIATE PRIMARY VOLTAGE SEE TABLE 2
X2
* MM SIGNAL CONNECTION
VOLTAGE
TB HZ
208/230/460/575
160
380
13A 60
FCB2/FB2
NOTES:
1. FACTORY WIRING IS IN ACCORDANCE WITH UL 1995 STANDARDS. ANY FIELD MODIFICATIONS OR ADDITIONS MUST BE IN COMPLIANCE WITH ALL APPLICABLE CODES.
2. USE 75
C MIN WIRE FOR FIELD POWER SUPPLY.
3. ALL FIELD INTERLOCK CONTACTS MUST HAVE A MIN RATING OF 2 AMPS @ 24VAC SEALED. SEE FIELD INTERLOCK WIRING.
4. COMPRESSOR AND FAN MOTORS ARE THERMALLY PROTECTED-­ THREE PHASE MOTORS PROTECTED AGAINST PRIMARY SINGLE PHASE CONDITIONS.
5. TERMINALS 13 & 14 OF LVT ARE FOR FIELD CONNECTION OF REMOTE ON-OFF. THE CONTACT MUST BE RATED FOR DRY CIRCUIT APPLICATION CAPABLE OF HANDLING A 5VDC 1 MA TO 20 MA LOAD.
6. FOR 500 SERIES UNIT OPERATION AT 208-3-60V LINE VOLTAGE, TRAN1 PRIMARY CONNECTIONS MUST BE MOVED TO TERMINALS H3 & H4.
10. MP-A1 NOT USED IN THE FOLLOWING UNITS: 035-045: ALL UNITS
11. MP-A2 NOT USED IN THE FOLLOWING UNITS: 035-045: ALL UNITS
12. MP-B1 NOT USED IN THE FOLLOWING UNITS: 035,040: ALL UNITS 045-060: 460V UNITS
13. MP-B2 NOT USED IN THE FOLLOWING UNITS: 035,040: ALL UNITS 045-060: 460V UNITS
14. JUMPER PLUG REQUIRED WHEN MP NOT USED
7. FOR 575-3-60V UNITS, FAN CIRCUIT BREAKER FCB2 IS REPLACED WITH FUSE BLOCK FB2.
SEE NOTE 7
BLK
BLU
YEL
VOLTAGE SERIES
TERMINAL
CONNECTIONS
FOR PRIMARY SIDE
575-3-60 100 H1 & H2
380-3-60 200 H1 & H2
230-3-60 500 H2 & H4
208-3-60 500 H3 & H4
460-3-60 600 H1 & H4
TABLE 1
UNIT VOLTAGE
REPLACE
WITH
FNQ-R-3.5
FU1 & FU2
FUSE
NUMBER
380-3-60
TRAN SIZE
200VA
FNQ-R-2.5
208/230-3-60
FNM-10
FU3 (24V)
380-3-60,460-3-60,575-3-60
200VA
208/230-3-60
VOLTAGE SERIES
TERMINAL
CONNECTIONS
FOR PRIMARY SIDE
575-3-60 100 COM & 575
380-3-60 200
230-3-60 500
208-3-60 500
460-3-60 600
TABLE 2
460-3-60
575-3-60
FNQ-R-2
FNQ-R-1.5
COM & 380
COM & 230
COM & 208
COM & 460
208
230
380
400
575 460
8. FOR UNITS WITH LOW AMBIENT MOTOR MASTER V FIOP/ACCESSORY, 030-050: FAN CONTACTOR FC1 IS REPLACED WITH MOTORMASTER RELAY MMR.
SECONDARY 24V
3.2 AMPS
CB4
RED
3
3
2
2
1
1
J2
BRN
RED
2
2
1
J1
1
3
3
EXV
BRN
RED
CWFS
CH-A2
BLU BLK
CH-B1
BLU BLK
CH-A1
BLU BLK
CH-B2
BLU BLK
GRN/YEL
OFM2
1
2
3
BLK-1
BLK-2
BLK-3
GRN/YEL
FC1
1
2
3
11 21
12
22
13 23
BLK-1
BLK-2
BLK-3
BLU
YEL
BLK
CWP1
CWP2
MS-CWP2
MS-CWP1
BLK
BLK
BLK
BLK
BLK
BLK
L3
L1
L2
CWP1 WATER PUMP
L3
L1
L2
CWP2 WATER PUMP
L1 T1
L2
T2
L3
T3
L1
L2
L3
T1
T2
T3
L1 T1
L2
T2
L3
T3
L1
L2
L3
T1
T2
T3
BLK
YEL
BLU
BLK
YEL
BLU
GRN/YEL
GRN/YEL
VOLTAGE SERIES
TERMINAL
CONNECTIONS
FOR PRIMARY SIDE
TERMINAL
CONNECTIONS FOR
SECONDARY SIDE
575-3-60 100 H1-H2 XF-X2
230-3-60 400,500 H2-H4 XF-X2
208-3-60 500 H3-H4 XF-X2
460-3-60 600 H1-H4 XF-X2
TRAN3
SECONDARY
115V
WHT
RESET
TEST
GRN-YEL
GFI-CO
FIOP/ACCESSORY
BRASS SCREW
SILVER SCREW
WHT
FU4
X3
X1
LOAD
LINE
BRASS SCREW
SILVER SCREW
BLK
2
2
XF
H4
H1
HF
H2
H3
BLK
1
FU6
RED
1
FU5
~
~
~
FU5 & FU6
500VA
FNM-6
FU4 (115V)
380-3-60,460-3-60,575-3-60
500VA
208/230-3-60
460-3-60,575-3-60
208/230-3-60,230-3-60
FNQ-R-2.5
FNQ-R-3.5
9. IF CHILLED WATER PUMP INTERLOCK IS USED,
REMOVE JUMPER FROM TERMINAL 11 TO 17 AND
CHILLED WATER PUMP FIOP
WIRE INTERLOCK CONTACT ACROSS TERMINALS 11 & 17.
050-060: 460V UNITS WITHOUT DIGITAL SCROLL
050-060: 460V UNITS
GRN/YEL
OFM3
OFM4
(055,060 ONLY)
(055,060 ONLY)
GRN/YEL
1
2
3
BLK-1
BLK-2
BLK-3
OFM4 (055,060)
OFM3 (035-050)
L1 T1
L2 T2
L3 T3
MMR
11 14
*1
2
YEL
VIO
MM-A
GRN/YEL
FC2
BLK-1
BLK-2
BLK-3
1
2
3
11 21
12
22
13 23
GRN/YEL
OFM1
FC1
1
2
3
11 21
12
22
13 23
BLK-1
BLK-2
BLK-3
BLK
YEL
BLU
BLK
YEL
BLU
FCB2/FB2
SEE NOTE 7
GRN/YEL
OFM2
1
2
3
BLK-1
BLK-2
BLK-3
OFM3
(055,060 ONLY)
(055,060 ONLY)
GRN/YEL
BLK
YEL
055,060: FAN CONTACTOR FC3 IS REPLACED WITH MOTORMASTER RELAY MMR..
208/230V ONLY
BLK
YEL
BLU
11
12
13
21
22
23
BLK
YEL
BLU
11
12
13
21
22
23
FB1
BLK
YEL
BLU
FB3
BLK
YEL
BLU
11
12
13
21
22
23
11
12
13
21
22
23
BLK
YEL
BLU
HIGH SCCR ONLY
FB1
BLK
YEL
BLU
FB3
BLK
YEL
BLU
11
12
13
21
22
23
11
12
13
21
22
23
BLK
YEL
BLU
HIGH SCCR ONLY
BLK
25
2
RED
FROM AUX-J4
YEL
BLUBLK
FB2 NONE
LP-CC-20575-3-60
LP-CC-20
380-3-60,460-3-60,575-3-60
NONE
208/230-3-60
KTK-R-15
380-3-60,460-3-60,575-3-60
NONE
KTK-R-20208/230-3-60
FB1
(NO MM)
FB1
(WITH MM)
LP-CC-20
380-3-60,460-3-60,575-3-60
NONE
208/230-3-60
FB3
3
3
2
2
1
1
J2
BRN
VIO
2
2
1
J1
1
3
3
MBB
BRN
RED
3
3
2
2
1
1
J2
2
J1
1
3
FIOP/ACCESSORY
EMM
BRN
RED
12
2
11
1
J1
DGS FIOP
AUX
2
1
3
2
1
UPC FIOP
UPC
GND
HOT
24VAC
BRN
VIO
42
86
BLK
YEL
COOLER/PUMP HEATERS (208/230,230V)
1
2
3
BLK
BLK
WHT
COOLER/PUMP HEATERS (380,460,575V)
3
2
BLK
BLK
~
~
~
~
WHT
~~
42
86
BLK
YEL
COOLER/PUMP HEATERS (208/230,230V)
1
2
3
BLK
BLK
WHT
COOLER/PUMP HEATERS (380,460,575V)
3
2
BLK
BLK
~
~
~
~
WHT
~~
VIO
BRN
BRN
BLU
31
240 1/4W
CHC
CHC
CHC
CHC
STANDARD
TERMINAL
BLOCK
PER NEC
TO FUSED DISCONNECT
21
22
23
TB1A
EQUIP GND
COMP A1
COMP B1
CSB-A1
CSB-A2
CSB-B1
CSB-B2
Fig. 7A — Typical Wiring Schematic, 30RAP035-060 Units — Power Wiring
a30-
5283
26
LEGEND
TERMINAL BLOCK
X
TERMINAL (UNMARKED) TERMINAL (MARKED) SPLICE FACTORY WIRING FIELD WIRING ACCESSORY OR OPTION WIRING TO INDICATE COMMON POTENTIAL ONLY,NOT TO REPRESENT WIRING
X
9
9
7
7
8
8
4
6
4
6
RLY 9
5
5
1
3
1
3
RLY 11
2
2
A2A1
A2A1
ORN
3
12
1
10
2
11
4
13
MAX LOAD-5VA SEALED
10VA INRUSH
C
TB1
SW2
C2
A2
B2
9
18
10
19
8
17
11
12
13
14
20
21
22
23
6
15
7
16
5
14
15
16
17
18
24
25
26
27
5.2 AMPS
CB2
A2A1
PNK
A2A1
ACCSY ACCESSORY ALMR ALARM RELAY AUX AUXILIARY BR BOILER RELAY C CONTACTOR, COMPRESSOR CB CIRCUIT BREAKER CCB COMPRESSOR CIRCUIT BREAKER CH CRANKCASE HEATER CHC COOLER/PUMP HEATER CONTACTOR CO CONVENIENCE OUTLET COMP COMPRESSOR CSB CURRENT SENSOR BOARD CWFS CHILLED WATER FLOW SWITCH CWP CHILLED WATER PUMP CWPI CHILLED WATER PUMP INTERLOCK DGS DIGITAL SCROLL DLS DEMAND LIMIT SWITCH DPT DISCHARGE PRESSURE TRANSDUCER DTT DISCHARGE TEMPERATURE THERMISTOR DUS DIGITAL UNLOADER SOLENOID EMM ENERGY MANAGEMENT EWT ENTERING WATER TEMPERATURE EXV EXPANSION VALVE CONTROL BOARD FB FUSE BLOCK FC FAN CONTACTOR FCB FAN CIRCUIT BREAKER FIOP FACTORY INSTALLED OPTION FR FAN RELAY FU FUSE GND GROUND HPS HIGH PRESSURE SWITCH HR HEAT RELAY LVT LOW VOLTAGE TERMINAL LWT LEAVING WATER TEMPERATURE MBB MAIN BASE BOARD MLV MINIMUM LOAD VALVE MM MOTORMASTER MMR MOTORMASTER RELAY MP MODULAR MOTOR PROTECTOR MS MANUAL STARTER OAT OUTDOOR AIR THERMISTOR OFM OUTDOOR FAN MOTOR PL PLUG R RELAY RGT RETURN GAS TEMPERATURE RLY RELAY SAT SUPPLY AIR TEMPERATURE SCCR SHORT CIRCUIT CURRENT RATING SPT SUCTION PRESSURE TRANSDUCER SW SWITCH TB TERMINAL BLOCK TNKR STORAGE TANK HEATER RELAY TRAN TRANSFORMER UPC UNITARY PROTOCOL CONVERTER
RLY 10
J10A
J10B
RLY 5
RLY 6
RLY 7
RLY 8
RLY 1
RLY 2
RLY 3
RLY 4
12
11
10
9
8
7
6
5
4
3
2
1
26
25
24
23
22
17
16
15
14
13
12
11
10
9
8
7
6
10
9
8
7
6
5
4
3
2
1
8
8
3
1
3
1
3
1
6
2
4
2
4
2
12
1
2
3
4
5
6
7
8
9
10
11
1
2
3
4
5
6
12
11
10
9
8
7
3
4
4
3
2
2
1
1
BLK
WHT
RED
J9
21
20
19
18
10
9
8
7
6
5
4
5
4
3
2
1
4
2
1
3
5
RED
BRN
RED
WHT
BLK
RED
WHT
BLK
6
6
5
5
3
3
2
1
1
2
7
7
4
4
J7
MARQUEE DISPLAY
MAIN BASE
BOARD
J8
9
9
10
10
6
5
4
3
2
1
6
5
4
3
2
1
J6
FIOP/
M1
M2
SEE NOTE 14
M1
M2
M1
M2
M1
M2
ORN
GRA
A2A1
ORN
A2A1
VIO
A2A1
PNK
FC2
FC1
CB1
CB2
CHC
CA1
CA2
ORN
ORN
7
TB4
RED
SEE NOTE 14
SEE NOTE 14
SEE NOTE 14
RED
RED
RED
RED
BLU
PNK
ORN
VIO
PNK
RED
ORN
ORN
GRA
VIO
J5
GRA
6
6
5
5
RED
BRN
J4
1
2
3
4
5
6
1
2
3
4
5
6
BLK
WHT
RED
BRN
RED
CSB
B2
2
3
1
RED
ORN
BRN
CSB
A2
2
3
1
RED
ORN
BRN
CSB
B1
2
3
1
RED
ORN
BRN
CSB
A1
2
3
1
RED
ORN
BRN
EXV
4
3
2
1
4
3
2
1
J3
4
3
2
1
4
3
2
1
J4
RED
WHT
BLK
RED
WHT
BLK
ON
OFF
12345678
DARK = SWITCH LOCATION
DUS
3
2
1
3
2
1
6
5
4
3
2
1
J9
2
1
8
7
2
1
8
7
J2
J6
DTT
RED
WHT
BLK
DGS OR
MM
FIOP
MBB
BLK
RED
LVT
4
3
22
23
T-55 ACCSY
SEN
12
11
10
9
8
7
6
5
4
3
2
1
12
11
10
9
8
7
J7
EMM
4
3
2
1
4
3
2
1
J3
4
3
2
1
4
3
2
1
J4
RED
WHT
BLK
RED
WHT
BLK
12
11
10
9
8
7
6
5
4
3
2
1
12
11
10
9
8
7
J6
14
13
14
13
ACCESSORY
1
1
2
3
4
5
6
1
2
3
4
5
6
10
7
8
9
8
6
7
4
5
9
2
3
10
+
-
COOLING SETPOINT 4-20mA
LVT
8
1
3
2
5
4
7
6
(+)
(-)
(COM)
SHIELD
LEN CCN
1
2
3
1
2
3
4
5
NET +
NET 2
SHIELD
NET +
NET -
N/C
N/C
SIGNAL
PORT 1A
UPC
PORT 2
J3
1
2
LON
OPTION
GND
J4
NET
UPC OPT
BLK
WHT
RED
RED
BLK
WHT
RED
WHT
BLK
RED
BRN
RED
WHT
BLK
OAT
BLU
BLU
PNK
ORN
BRN
VIO
+
-
TEMP RESET 4-20mA
+
-
DEMAND LIMIT 4-20mA
LVT
2
1
24
25
ALM
R
LVT
1
18
C
TB1
BRN
MBB J1-2
T2T1MP-A1
T2T1MP-A2
T2T1MP-B1
T2T1MP-B2
SEE NOTE 10
SEE NOTE 11
SEE NOTE 12
SEE NOTE 13
3.2 AMPS
CB1
4
TB4
RED
RED
RED
BRN
UPC GND
BRN
CWFS 3
BRN
CB1
A2
BRN
LVT J12-5
BRN
CHC
A2
BRN
CA1
A2
BRN
TRAN1
SECONDARY 24V
RED
FU3
X1
XF
BRN
X2
GRN/YEL
5
TB4
RED
VIO RED
PL50-1
BRN BLK
PL50-2
RED RED
PL50-3
BLK BLK
PL50-4
BLK
RED
RGTB
BLK
RED
RGTA
2
1
2
1
RED
BLK
J4
CH1
-
CH11
-
CH9
-
-
+
G
-
+
G
2
1
2
1
J5
CH10
-
TO MM-A
SEE NOTE 8
BLK
BLU
EXV-B
5
4
3
2
1
5
4
3
2
1
WHT
BLK
RED
GRN
PL-EXVB
EXV-A
5
4
3
2
1
5
4
3
2
1
WHT
BLK
RED
GRN
PL-EXVA
J7
J6
RED
RED
BLK
GRY
YEL
BLK
YEL
GRY
FIOP OR
FIELD INSTALLED
OPTION
VIO
RED
FIELD INSTALLED
MAX LOAD-5VA SEALED
10VA INRUSH
A2A1
CWP
1
A2A1
CWP
2
BRN
CWP1
A2
MLV-A
GRA
BRN
MLV ACCSY
FR4
2
4
FR3
2
4
FR2
2
4
TAN
TAN
PNK
FR1
2
4
TAN
PNK
PNK
A2A1
BRN
PNK
FC2
A2
FC3
(055,060 ONLY)
RED
RED
4
TB4
ORN
RED
ACCESSORY STORAGE TANK HEATER RELAY
TNK
R
BLK
ORN
BRN
C
TB1
BRN
CWP2
A2
BRN
C
TB1
BRN
CA1
A2
BRN
CA2
A2
BRN
C
TB1
BRN
CB1
A2
BRN
CB2
A2
BRN
C
TB1
BRN
CWP1
A2
BRN
FC2
A2
BRN
CA2
A2
BRN
FC1
A2
BRN
FC3
A2
14
15
4
3
12
13
6
5
11
RED
RED
BLU
BLU
DLS STEP 2
DLS STEP 1
LVT
16
17
2
1
GRA
GRA
ICE DONE
SPTB
-
+
DPTB
-
+
A
C
B
A
C
B
GRN
RED
BLK
GRN
RED
BLK
SPTA
-
+
DPTA
-
+
A
C
B
A
C
B
GRN
RED
BLK
GRN
RED
BLK
BLK
RED
EVAPORATOR ENTERING FLUID TEMP
BLK
RED
EVAPORATOR LEAVING FLUID TEMP
SPACE TEMPERATURE ACCESSORY OR DUAL CHILLER LWT
3
4
4
3
2
2
1
1
BLK
WHT
RED
J3
14
13
RED
CWP2
RED
14
13
VIO
CWP1
VIO
BRN
VIO
BR
HR
ALMR
HEAT/BOILER FIELD
INSTALLED WIRING
RED
C1
A1
B1
OFF
3
2
16
13
6
4
15
7
5
17
9
8
14
REMOTE ON-OFF SWITCH
(SEE NOTE
5)
ENABLE
SW1
LVT
ORN
12
11
13
11
14
CWFS
DUAL
SETPOINT
LVT
7
6
19
20
GRA
TAN
RED
RED
RED
GRA
GRA
SEE
NOTE 9
(055,060 ONLY)
(055,060 ONLY)
(055,060 ONLY)
(055,060 ONLY)
SEE NOTE 8
LVT
5
21
BRN
FR110
ORN BRN
(055,060 ONLY)
FR210
GRA BRN
(055,060 ONLY)
FR310
VIO BRN
(055,060 ONLY)
FR410
PNK BRN
(055,060 ONLY)
MP-B1
VIO
VIO
PL2-2PL2-1
VIO
MP-A1
VIO
VIO
PL1-2PL1-1
VIO
MP-B2
VIO
VIO
PL2-6PL2-5
VIO
MP-A2
VIO
VIO
PL1-6PL1-5
VIO
BLU
BLK
BLK
HPS-B
J12 T55
J13
J1
J12
J11
PL1-3
RED
RED
PL1-4
BRN
BRN
PL1-7
RED
RED
PL2-3
RED
RED
PL2-7
RED
RED
PL1-8
BRN
BRN
PL2-4
BRN
BRN
PL2-8
BRN
BRN
BRN
GRA
GRA
BLK
BLK
BLK
HPS-A
J10
J11
BLK
4
WHT
2
J12
CWPI
HEAT
J12
AUX
Fig. 7B — Typical Wiring Schematic, 30RAP035-060 Units — Control Wiring
a30-5284
27
CEPL130346-01
STATUS
LEN
J1
J2
J4
J3
J5
J6
J7
J8
J9
J10
CCN
RED LED - STATUS GREEN LED -
LEN (LOCAL EQUIPMENT NETWORK)
YELLOW LED ­CCN (CARRIER COMFORT NETWORK)
INSTANCE JUMPER
K11
K10 K9
K8
K7
K6
K5
K4
K3 K2
K1
Fig. 8 — Main Base Board
Fig. 9 — Enable/Off/Remote Contact Switch, and Emergency On/Off Switch Locations
SPT (T10) PART NO. 33ZCT55SPT
SENSOR
SEN
SEN
LVT
3
4
Fig. 10 — Typical Space Temperature
Sensor Wiring
T-55 SPACE SENSOR
CCN+
CCN GND
CCN-
TO CCN COMM 1 BUS (PLUG) AT UNIT
1
2
3
4
5
6
Fig. 11 — CCN Communications Bus Wiring
to Optional Space Sensor RJ11 Connector
a30-4967
a30-4968
28
Energy Management Module (Fig. 12) — This
factory-installed option (FIOP) or field-installed accessory is used for the following types of temperature reset, demand limit, and/or ice features:
4 to 20 mA leaving fluid temperature reset (requires field-supplied 4 to 20 mA generator)
4 to 20 mA cooling set point reset (requires field­supplied 4 to 20 mA generator)
Discrete inputs for 2-step demand limit (requires field­supplied dry contacts capable of handling a 24 vac, 50 mA load)
4 to 20 mA demand limit (requires field-supplied 4 to 20 mA generator)
Discrete input for Ice Done switch (requires field­supplied dry contacts capable of handling a 24 vac, 50 mA load)
See Demand Limit and Temperature Reset sections on
pages 41 and 37 for further details.
CAUTION
Care should be taken when interfacing with other manufac­turer’s control systems due to possible power supply differences, full wave bridge versus half wave rectification. The two different power supplies cannot be mixed. ComfortLink™ controls use half wave rectification. A signal isolation device should be utilized if a full wave bridge signal generating device is used.
Loss-of-Cooler Flow Protection — A proof-of-
cooler flow device is factory installed in all chillers. It is recom­mended that proper operation of the switch be verified on a reg­ular basis.
Electronic Expansion Valves (EXV) — All units are
equipped from the factory with EXVs. Each refrigeration cir­cuit is also supplied with a factory-installed liquid line filter drier and sight glass.
The EXV is set at the factory to maintain 9° F (5.0° C) suc­tion superheat leaving the cooler by metering the proper amount of refrigerant into the cooler. The superheat set point is adjustable, but should not be adjusted unless absolutely necessary.
The EXV is designed to limit the cooler saturated suction temperature to 50 F (12.8 C). This makes it possible for unit to start at high cooler fluid temperatures without overloading the compressor.
Capacity Control — The control system cycles com-
pressors, digital scroll modulting solenoid (if equipped), and minimum load valve solenoids (if equipped) to maintain the user-configured leaving chilled fluid temperature set point. En­tering fluid temperature is used by the main base board (MBB) to determine the temperature drop across the cooler and is used in determining the optimum time to add or subtract capacity stages. The chilled fluid temperature set point can be automati­cally reset by the return fluid temperature, space, or outdoor-air temperature reset features. It can also be reset from an external 4 to 20-mA signal (requires energy management module FIOP or accessory).
The standard control has an automatic lead-lag feature built in which determines the wear factor (combination of starts and run hours) for each compressor. If all compressors are off and less than 30 minutes has elapsed since the last compressor was turned off, the wear factor is used to determine which
compressor to start next. If no compressors have been running for more than 30 minutes and the leaving fluid temperature is greater than the saturated condensing temperature, the wear factor is still used to determine which compressor to start next. If the leaving fluid temperature is less than the saturated con­densing temperature, then the control will start either compres­sor A1 or compressor B1 first, depending on the user-configu­rable circuit lead-lag value. For units with the minimum load control valve, the A circuit with the minimum load valve is al­ways the lead circuit. The A circuit is also always the lead for units with the digital compressor option. On units with the dig­ital scroll option, the A1 compressor operates continuously, providing close leaving chilled water control. For this reason, on/off cycling of the unit’s compressors is dramatically re­duced, which in turn reduces wear associated with compressor start/stop cycles.
The EXVs will provide a controlled start-up. During start­up, the low pressure logic will be bypassed for 2 allow for the transient changes during start-up. As additional stages of compression are required, the processor control will add them. See Table 19.
If a circuit is to be stopped, the compressor with the lowest wear factor will be shut off first except when a digital compres­sor is used. The digital compressor is always the last compres­sor to shut off.
The capacity control algorithm runs every 30 seconds. The algorithm attempts to maintain the Control Point at the desired set point. Each time it runs, the control reads the entering and leaving fluid temperatures. The control determines the rate at which conditions are changing and calculates 2 variables based on these conditions. Next, a capacity ratio is calculated using the 2 variables to determine whether or not to make any changes to the current stages of capacity. This ratio value ranges from –100 to +100%. If the next stage of capacity is a compressor, the control starts (stops) a compressor when the ratio reaches +100% (–100%). If installed, the minimum load valve solenoid will be energized with the first stage of capacity. Minimum load valve value is a fixed 30% in the total capacity calculation. The control will also use the minimum load valve solenoid as the last stage of capacity before turning off the last compressor. A delay of 90 seconds occurs after each capacity step change. Refer to Table 19.
MINUTES LEFT FOR START — This value is displayed only in the network display tables (using Service Tool, ComfortVIEW™ or ComfortWORKS represents the amount of time to elapse before the unit will start its initialization routine. This value can be zero without the machine running in many situations. This can include being unoccupied, ENABLE/OFF/REMOTE CONTACT switch in the OFF position, CCN not allowing unit to start, Demand Limit in effect, no call for cooling due to no load, and alarm or alert conditions present. If the machine should be running and none of the above are true, a minimum off time (DELY, see below) may be in effect. The machine should start normally once the time limit has expired.
MINUTES OFF TIME (Configuration DELY) — This user-configurable time period is used by the control to determine how long unit operation is delayed after power is applied/restored to the unit. Typically, this time period is configured when multiple machines are located on a single site. For example, this gives the user the ability to prevent all the units from restarting at once after a power failure. A value of zero for this variable does not mean that the unit should be running.
1
/2 minutes to
®
software) and
OPT2
29
CEBD430351-0396-01C
TEST 1
CEPL130351-01
PWR
TEST 2
J1
J2
J4 J3
J5
J6
J7
LEN
STATUS
RED LED - STATUS
GREEN LED ­LEN (LOCAL EQUIPMENT NETWORK)
ADDRESS DIP SWITCH
Fig. 12 — Energy Management Module
LEAD/LAG DETERMINATION — This is a configurable choice and is factory set to be automatic for all units unless the unit is equipped with a digital scroll compressor or minimum
load, then circuit A is lead (Configuration The value can be changed to Circuit A or Circuit B leading as desired. Set at automatic, the control will sum the current num­ber of logged circuit starts and one-quarter of the current oper-
OPT2 LLCS).
ating hours for each circuit. The circuit with the lowest sum is started first. Changes to which circuit is the lead circuit and which is the lag are also made when total machine capacity is at 100% or when there is a change in the direction of capacity (increase or decrease) and each circuit’s capacity is equal.
CAPACITY CONTROL OVERRIDES — The following over­rides will modify the normal operation of the routine.
Deadband Multiplier Multiplier (Configuration
— The user configurable Deadband
SLCTZ.GN) has a default val-
ue of 1.0. The range is from 1.0 to 4.0. When set to other than
1.0, this factor is applied to the capacity Load/Unload Factor. The larger this value is set, the longer the control will delay be­tween adding or removing stages of capacity. Figure 13 shows how compressor starts can be reduced over time if the leaving water temperature is allowed to drift a larger amount above and below the set point. This value should be set in the range of 3.0 to 4.0 for systems with small loop volumes.
First Stage Override the control will modify the routine with a 1.2 factor on adding
— If the current capacity stage is zero,
the first stage to reduce cycling. This factor is also applied
when the control is attempting to remove the last stage of capacity.
Slow Change Override
— The control prevents the capacity stages from being changed when the leaving fluid temperature is close to the set point (within an adjustable deadband) and moving towards the set point.
Ramp Loading
tion
SLCTCRMP) limits the rate of change of leaving
fluid temperature. If the unit is in a Cooling mode and config-
— Ramp loading (Configura-
ured for Ramp Loading, the control makes 2 comparisons be­fore deciding to change stages of capacity. The control calcu­lates a temperature difference between the control point and leaving fluid temperature. If the difference is greater than 4° F (2.2° C) and the rate of change (°F or °C per minute) is more than the configured Cooling Ramp Loading value (CRMP), the control does not allow any changes to the current stage of capacity.
Low Entering Fluid Temperature Unloading
— When the entering fluid temperature is below the control point, the control will attempt to remove 25% of the current stages being used. If exactly 25% cannot be removed, the control removes an amount greater than 25% but no more than necessary. The lowest stage will not be removed.
Minimum Load Control control valve is energized only when one compressor is run­ning on circuit A. If the close control feature is enabled the
— If equipped, the minimum load
minimum load control valve may be used as needed to obtain leaving fluid temperature close to set point.
30
Loading...
+ 94 hidden pages