DO NOT attempt to unbraze factory joints when servicing
this equipment. Compressor oil is flammable and there is
no way to detect how much oil may be in any of the
refrigerant lines. Cut lines with a tubing cutter as required
when performing service. Use a pan to catch any oil that
may come out of the lines and as a gage for how much oil
to add to system. DO NOT re-use compressor oil.
CAUTION
This unit uses a microprocessor-based electronic control
system. Do not use jumpers or other tools to short out
components, or to bypass or otherwise depart from recommended procedures. Any short-to-ground of the control
board or accompanying wiring may destroy the electronic
modules or electrical components.
CAUTION
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be
hazardous due to system pressures, electrical components, and
equipment location (roof, elevated structures, mechanical
rooms, etc.). Only trained, qualified installers and service
mechanics should install, start up, and service this equipment.
When working on this equipment, observe precautions in
the literature, and on tags, stickers, and labels attached to the
equipment, and any other safety precautions that apply. Follow
all safety codes. Wear safety glasses and work gloves. Use
care in handling, rigging, and setting this equipment, and in
handling all electrical components.
WARNING
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work
is completed.
WARNING
DO NOT VENT refrigerant relief valves within a building.
Outlet from relief valves must be vented outdoors in
accordance with the latest edition of ANSI/ASHRAE
(American National Standards Institute/American Society
of Heating, Refrigeration and Air Conditioning Engineers)
15 (Safety Code for Mechanical Refrigeration). The
accumulation of refrigerant in an enclosed space can
displace oxygen and cause asphyxiation. Provide adequate
ventilation in enclosed or low overhead areas. Inhalation of
high concentrations of vapor is harmful and may cause
heart irregularities, unconsciousness or death. Misuse can
be fatal. Vapor is heavier than air and reduces the amount
of oxygen available for breathing. Product causes eye and
skin irritation. Decomposition products are hazardous.
To prevent potential damage to heat exchanger, always run
fluid through heat exchanger when adding or removing
refrigerant charge. Use appropriate brine solutions in cooler
fluid loop to prevent the freezing of brazed plate heat
exchanger, optional hydronic section and/or interconnecting
piping when the equipment is exposed to temperatures
below 32 F (0 °C). Proof of flow switch and strainer are
factory installed on all models. Do NOT remove power
from this chiller during winter shutdown periods without
taking precaution to remove all water from heat exchanger
and optional hydronic system. Failure to properly protect
the system from freezing may constitute abuse and may
void warranty.
CAUTION
Compressors and optional hydronic system pumps require
specific rotation. Test condenser fan(s) first to ensure
proper phasing. Swap any two incoming power leads to
correct condenser fan rotation before starting any other
motors.
CAUTION
Refrigerant charge must be removed slowly to prevent loss
of compressor oil that could result in compressor failure.
CAUTION
Puron® refrigerant (R-410A) systems operate at higher
pressures than standard R-22 systems. Do not use R-22 service equipment or components on Puron refrigerant equipment. If service equipment is not rated for Puron
refrigerant, equipment damage or personal injury may
result.
2
ENTER
ESCAPE
ENTER
ENTER
ESCAPE
ESCAPE
ENTER
ESCAPE
ENTER
ESCAPE
ESCAPE
ENTER
ENTER
ENTER
Run Status
Service Test
Temperature
Pressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
Operating Modes
Alarms
Alarm Status
ENTER
MODE
ESCAPE
Fig. 1 — Scrolling Marquee Display
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
GENERAL
This publication contains Controls, Start-Up, Operation,
Service, and Troubleshooting information for the 30RAP
AquaSnap
®
air-cooled chillers. See Table 1. These chillers are
equipped with ComfortLink™ controls and electronic expansion valves (EXVs).
WARNING
This unit uses a microprocessor-based electronic control
system. Do not use jumpers or other tools to short out or
bypass components or otherwise depart from recommended procedures. Any short-to-ground of the control
board or accompanying wiring may destroy the board or
electrical component.
ing conventions for discussing configuration points for the
local display (scrolling marquee or Navigator™ accessory)
will be used in this manual.
Point names will be written with the mode name first, then
any sub-modes, then the point name, each separated by an
arrow symbol (. Names will also be shown in bold
and italics. As an example, the Lead/Lag Circuit Select Point,
which is located in the Configuration mode, Option sub-mode,
would be written as Configuration OPTNLLCS.
This path name will show the user how to navigate through
the local display to reach the desired configuration. The user
would scroll through the modes and sub-modes using the
and keys. The arrow symbol in the path name represents pressing to move into the next level of the
menu structure.
When a value is included as part of the path name, it will be
shown at the end of the path name after an equals sign. If the
value represents a configuration setting, an explanation will
be shown in parenthesis after the value. As an example,
ConfigurationOPTNLLCS= 1 (Circuit A leads).
Pressing the and keys simultaneously
will scroll an expanded text description of the point name or
value across the display. The expanded description is shown in
the local display tables but will not be shown with the path
names in text.
®
The CCN (Carrier Comfort Network
) point names are also
referenced in the local display tables for users configuring the
unit with CCN software instead of the local display. The CCN
tables are located in Appendix B of the manual.
Basic Controls Usage
SCROLLING MARQUEE DISPLAY — The scrolling marquee display is the standard interface display to the ComfortLink
Control System for 30RAP units. The display has up and down
arrow keys, an key, and an key. These
keys are used to navigate through the different levels of the
display structure. Press the key until the highest
operating level is displayed to move through the top 11 mode
levels indicated by LEDs on the left side of the display. See
Fig. 1 and Tables 2-14.
Once within a mode or sub-mode, pressing the
and keys simultaneously will put the scrolling
marquee display into expanded text mode where the full meaning of all sub-modes, items and their values can be displayed
for the current selection. Press the and
keys to return the scrolling marquee display to its default menu
of rotating display items (those items in Run Status
In addition, the password will be disabled, requiring that it be
entered again before changes can be made to password protected items. Press the key to exit out of the expanded
text mode.
NOTE: When the Language Selection (ConfigurationDISPLANG), variable is changed, all appropriate display
expansions will immediately change to the new language. No
power-off or control reset is required when reconfiguring
languages.
When a specific item is located, the item name alternates
with the value. Press the key at a changeable item
and the value will be displayed. Press again and the
value will begin to flash indicating that the value can be
changed. Use the up and down arrow keys to change the value,
and confirm the value by pressing the key.
Changing item values or testing outputs is accomplished in
the same manner. Locate and display the desired item. Press
so that the item value flashes. Use the arrow keys to
change the value or state and press the key to accept
it. Press the key to return to the next higher level of
structure. Repeat the process as required for other items.
Items in the Configuration and Service Test modes are password protected. The words ‘PASS’ and ‘WORD’ will alternate
on the display when required. The default password is 0111.
Press and the 1111 password will be displayed. Press
again and the first digit will begin to flash. Use the
arrow keys to change the number and press to accept
the digit. Continue with the remaining digits of the password.
The password can only be changed through CCN operator in-
®
terface software such as ComfortWORKS
, ComfortVIEW™
and Service Tool.
See Tables 2-14 and Appendix A for further details.
3
VIEW).
ACCESSORY NAVIGATOR™ DISPLAY MODULE —
ENTER
ESCAPE
ESCAPE
ENTER
ESCAPE
ENTER
ESCAPE
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
Fig. 2 — Accessory Navigator™ Display Module
The Navigator module provides a mobile user interface to the
ComfortLink™ control system, which is only available as a
field-installed accessory. The display has up and down arrow
keys, an key, and an key. These keys are
used to navigate through the different levels of the display
structure. Press the key until ‘Select a Menu Item’
is displayed to move through the top 11 mode levels indicated
by LEDs on the left side of the display. See Fig. 2.
Once within a Mode or sub-mode, a “>” indicates the cur-
rently selected item on the display screen. Pressing the
and keys simultaneously will put the Navigator module into expanded text mode where the full meaning
of all sub-modes, items and their values can be displayed. Pressing the and keys when the display says
‘Select Menu Item’ (Mode LED level) will return the Navigator
module to its default menu of rotating display items (those items
in Run Status
VIEW). In addition, the password will be dis-
abled, requiring that it be entered again before changes can be
made to password protected items. Press the key to
exit out of the expanded text mode.
NOTE: When the Language Selection (Configuration
DISPLANG), variable is changed, all appropriate display
expansions will immediately change to the new language. No
power-off or control reset is required when reconfiguring
languages.
When a specific item is located, the item name appears on the
left of the display, the value will appear near the middle of the
display and the units (if any) will appear on the far right of the
display. Press the key at a changeable item and the value will begin to flash. Use the up and down arrow keys to change
the value, and confirm the value by pressing the key.
Changing item values or testing outputs is accomplished in
the same manner. Locate and display the desired item. Press
so that the item value flashes. Use the arrow keys to
change the value or state and press the key to accept
it. Press the key to return to the next higher level of
structure. Repeat the process as required for other items.
Items in the Configuration and Service Test modes are password protected. The words Enter Password will be displayed
when required, with 1111 also being displayed. The default
password is 1111. Use the arrow keys to change the number
and press to enter the digit. Continue with the remaining digits of the password. The password can only be
changed through CCN operator interface software such as
ComfortWORKS, ComfortVIEW and Service Tool.
Adjusting the Contrast
— The contrast of the display can be
adjusted to suit ambient conditions. To adjust the contrast of
the Navigator module, press the key until the display reads, “Select a menu item.” Using the arrow keys move
to the Configuration mode. Press to obtain access to
this mode. The display will read:
> TEST OFF
METR OFF
LANG ENGLISH
Pressing will cause the “OFF” to flash. Use the up
or down arrow to change “OFF” to “ON”. Pressing
will illuminate all LEDs and display all pixels in the view
screen. Pressing and simultaneously
allows the user to adjust the display contrast. Use the up or
down arrows to adjust the contrast. The screen’s contrast will
change with the adjustment. Press to accept the
change. The Navigator module will keep this setting as long as
it is plugged in to the LEN bus.
Adjusting the Backlight Brightness
— The backlight of the
display can be adjusted to suit ambient conditions. The factory
default is set to the highest level. To adjust the backlight of the
Navigator module, press the key until the display
reads, “Select a menu item.” Using the arrow keys move to the
Configuration mode. Press to obtain access to this
mode. The display will read:
> TEST OFF
METR OFF
LANG ENGLISH
Pressing will cause the “OFF” to flash. Use the up
or down arrow keys to change “OFF” to “ON”. Pressing
will illuminate all LEDs and display all pixels in the
view screen. Pressing the up and down arrow keys simultaneously allows the user to adjust the display brightness. Use the
up or down arrow keys to adjust screen brightness. Press
to accept the change. The Navigator module will
keep this setting as long as it is plugged in to the LEN bus.
ComfortLink
MODE
Alarm Status
Run Status
Service Test
Temperatures
Pressure
s
Setpoints
Inputs
Outputs
Configuration
Time Clock
ESC
Operating Modes
Alarms
ENTER
4
Table 2 — Scrolling Marquee Display Menu Structure*
MODE
SUB-MODE
RUN
STATUS
Auto
View of
Run Status
(VIEW)
Unit Run
Hour and
Start
(RUN)
Compressor
Run Hours
(HOUR)
Compressor
Starts
(STRT)
Preventive
Maintenance
(PM)
Software
Ver si on
(VERS)
LEGEND
Ckt — Circuit
*Throughout this text, the location of items in the menu structure will be
described in the following format:
Item Expansion (Mode Name
For example, using the language selection item:
Language Selection (Configuration
SERVICE
TEST
Service
Te s t M o d e
(TEST)
Outputs
and Pumps
(OUTS)
Ciruit A Comp
Te st
(CMPA)
Ciruit B Comp
Test
(CMPB)
TEMPERATURES PRESSURES
Ent and Leave Unit
Temperatures
Temperatures
Sub-mode NameITEM)
DISPLANG)
Te mp s
(UNIT)
Ckt A
(CIR.A)
Ckt B
(CIR.B)
Pressures
Ckt A
(PRC.A)
Pressures
Ckt B
(PRC.B)
SET
POINTS
Cooling
Setpoints
(COOL)
Head
Pressure
Setpoint
(HEAD)
Brine
Freeze
Setpoint
(FRZ)
INPUTS OUTPUTS CONFIGURATION
General
Inputs
(GEN.I)
Circuit
Inputs
(CRCT)
4-20mA
Inputs
(4-20)
General
Outputs
(GEN.O)
Outputs
Circuit A
EXV
(A.EXV)
Outputs
Circuit B
EXV
(B.EXV)
Outputs
Circuit A
(CIR.A)
Outputs
Circuit B
(CIR.B)
Display
Configuration
(DISP)
Unit
Configuration
(UNIT)
Unit Options 1
Hardware
(OPT1)
Unit Options 2
Controls
(OPT2)
CCN Network
Configuration
(CCN)
Head Pressure
Comp. Delta
(HP.A)
Head Pressure
Comp. Delta
(HP.B)
Cir. A EXV
Configuration
(EXV.A)
Cir. B EXV
Configuration
(EXV.B)
Motormaster
Configuration
(MM)
Reset Cool Temp
(RSET)
Set Point and
Ramp Load
(SLCT)
Service
Configuration
(SERV)
Broadcast
Configuration
(BCST)
TIME
CLOCK
Time of
Day
(TIME)
Month,
Date, Day,
and Year
(DATE)
Daylight
Savings
Time
(DST)
Local
Holiday
Schedules
(HOL.L)
Local
Occupancy
Schedule
(SCH.L)
Schedule
Override
(OVR)
OPERATING
MODES
Modes
(MODE)
ALARMS
Current
(CRNT)
Reset
Alarms
(RCRN)
Alarm
History
(HIST)
5
Table 3 — Run Status Mode and Sub-Mode Directory
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY SUB-ITEM DISPLAY SUB-ITEM DISPLAY
VIEWEWTXXX.X FENTERING FLUID TEMP
LWTXXX.X FLEAVING FLUID TEMP
SETPXXX.X FACTIVE SETPOINT
CTPTXXX.X FCONTROL POINT
LOD.FXXXLOAD/UNLOAD FACTOR
STATXCONTROL MODE0 = Service Test
LD.PMLEAD PUMP
OCCYES/NOOCCUPIED
LS.ACYES/NOLOW SOUND ACTIVE
MODEYES/NOOVERRIDE MODES IN EFFECT
CAPXXX %PERCENT TOTAL CAPACITY
STGEXREQUESTED STAGE
ALRMXXXCURRENT ALARMS & ALERTS
TIMEXX.XXTIME OF DAY00.00-23.59
ITEM
EXPANSION
COMMENT
1 = Off Local
2 = Off CCN
3 = Off Time
4 = Off Emrgcy
5 = On Local
6 = On CCN
7 = On Time
8 = Ht Enabled
9 = Pump Delay
MNTHXXMONTH OF YEAR1 = January, 2 = February, etc.
DATEXXDAY OF MONTH01-31
YEARXXYEAR OF CENTURY
RUNHRS.U XXXX HRSMACHINE OPERATING HOURS
STR.UXXXXMACHINE STARTS
HR.P1XXXX.XPUMP 1 RUN HOURS
HR.P2XXXX.XPUMP 2 RUN HOURS
HOURHRS.A XXXX HRSCIRCUIT A RUN HOURS
HRS.B XXXX HRSCIRCUIT B RUN HOURSSee Note
HR.A1 XXXX HRSCOMPRESSOR A1 RUN HOURS
HR.A2 XXXX HRSCOMPRESSOR A2 RUN HOURS
HR.B1 XXXX HRSCOMPRESSOR B1 RUN HOURSSee Note
HR.B2 XXXX HRSCOMPRESSOR B2 RUN HOURSSee Note
STRTST.A1XXXXCOMPRESSOR A1 STARTS
ST.A2XXXXCOMPRESSOR A2 STARTS
ST.B1XXXXCOMPRESSOR B1 STARTSSee Note
ST.B2XXXXCOMPRESSOR B2 STARTSSee Note
PMPUMPPUMP MAINTENANCE
SI.PMXXXX HRSPUMP SERVICE INTERVALDefault: 8760
P.1.DNXXXX HRSPUMP 1 SERVICE COUNTDOWN
P.2.DNXXXX HRSPUMP 2 SERVICE COUNTDOWN
P.1.MNYES/NOPUMP 1 MAINTENANCE DONEUser Entry
P.2.MNYES/NOPUMP 2 MAINTENANCE DONEUser Entry
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
6
Table 3 — Run Status Mode and Sub-Mode Directory (cont)
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ESCAPE
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY SUB-ITEM DISPLAY SUB-ITEM DISPLAY
PM (cont)PMDTPUMP MAINTENANCE DATES
P.1.M0MM/DD/YY HH:MM
P.1.M1MM/DD/YY HH:MM
P.1.M2MM/DD/YY HH:MM
P.1.M3MM/DD/YY HH:MM
P.1.M4MM/DD/YY HH:MM
P.2.M0MM/DD/YY HH:MM
P.2.M1MM/DD/YY HH:MM
P.2.M2MM/DD/YY HH:MM
P.2.M3MM/DD/YY HH:MM
P.2.M4MM/DD/YY HH:MM
STRNSTRAINER MAINTENANCE
SI.STXXXX HRSSTRAINER SRVC INTERVALDefault: 8760
S.T.DNXXXX HRSSTRAINER SRVC COUNTDOWN
S.T.MNYES/NOSTRAINER MAINT. DONEUser Entry
ST.DTSTRAINER MAINT. DATES
S.T.M0MM/DD/YY HH:MM
ITEM
EXPANSION
COMMENT
S.T.M1MM/DD/YY HH:MM
S.T.M2MM/DD/YY HH:MM
S.T.M3MM/DD/YY HH:MM
S.T.M4MM/DD/YY HH:MM
COILCOIL MAINTENANCE
SI.CLXXXX HRSCOIL SRVC INTERDefault: 8760
C.L.DNXXXX HRSCOIL SERVICE COUNTDOWN
C.L.MNYES/NOCOIL MAINT. DONEUser Entry
CL.DTCOIL MAINTENANCE DATES
C.L.M0MM/DD/YY HH:MM
C.L.M1MM/DD/YY HH:MM
C.L.M2MM/DD/YY HH:MM
C.L.M3MM/DD/YY HH:MM
C.L.M4MM/DD/YY HH:MM
VERSMBBCESR131460-xx-xxxx-xx is Version number*
EXVCESR131172-xx-xxxx-xx is Version number*
AUX1CESR131333-xx-xxxx-xx is Version number*
EMMCESR131174-xx-xxxx-xx is Version number*
MARQCESR131171-xx-xxxx-xx is Version number*
NAVICESR130227-xx-xxxx-xx is Version number*
*Pressandsimultaneously to obtain version number.
7
Table 4 — Service Test Mode and Sub-Mode Directory
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
TESTON/OFFSERVICE TEST MODETo Enable Service Test Mode,
OUTSOUTPUTS AND PUMPS
EXV.A0 to 100%EXV A % OPEN
EXV.B0 to 100%EXV B % OPEN
FAN 1ON / OFFFAN 1 REL AY
FAN 2ON / OFFFAN 2 REL AY
FAN 3ON / OFFFAN 3 REL AY
FAN 4ON / OFFFAN 4 REL AY
FAN 5ON / OFFFAN 5 REL AY
FAN 6ON / OFFFAN 6 REL AY
V.HPA0 to 100%VAR HEAD PRESS %
V.HPB0 to 100%VAR HEAD PRESS %
CLP.1ON/OFFCOOLER PUMP 1 RELAY
CLP.2ON/OFFCOOLER PUMP 2 RELAY
UL.TM0 to 15COMP A1 UNLOAD TIME
CL.HTON/OFFCOOLER/PUMP HEATER
ITEM
EXPANSION
COMMENT
move Enable/Off/Remote
Contact switch to OFF. Change
TEST to ON. Move switch to
ENABLE.
RMT.AON/OFFREMOTE ALARM RELAY
CMPACIRCUIT A COMPRESSOR TEST
CC.A1ON/OFFCOMPRESSOR A1 RELAY
UL.TM0 to 15COMP A1 UNLOAD TIME
CC.A2ON/OFFCOMPRESSOR A2 RELAY
CC.A3ON/OFFCOMPRESSOR A3 RELAY
CC.A4ON/OFFCOMPRESSOR A4 RELAY
MLVON/OFFMINIMUM LOAD VALVE RELAY
CMPBCIRCUIT B COMPRESSOR TESTSee Note
CC.B1ON/OFFCOMPRESSOR B1 RELAY
CC.B2ON/OFFCOMPRESSOR B2 RELAY
CC.B3ON/OFFCOMPRESSOR B3 RELAY
CC.B4ON/OFFCOMPRESSOR B4 RELAY
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
8
Table 5 — Temperature Mode and Sub-Mode Directory
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
UNITENT AND LEAVE UNIT TEMPS
CEWTXXX.X FCOOLER ENTERING FLUID
CLWTXXX.X FCOOLER LEAVING FLUID
OATXXX.X FOUTSIDE AIR TEMPERATURE
SPTXXX.X FSPACE TEMPERATURE
DLWTXXX.X FLEAD/LAG LEAVING FLUID
CIR.ATEMPERATURES CIRCUIT A
SCT.AXXX.X FSATURATED CONDENSING TMP
SST.AXXX.X FSATURATED SUCTION TEMP
RGT.AXXX.X FCOMPR RETURN GAS TEMP
D.G ASXXX.X FDISCHARGE GAS TEMP
SH.AXXX.X ^F SUCTION SUPERHEAT TEMP
CIR.BTEMPERATURES CIRCUIT BSee Note
SCT.BXXX.X FSATURATED CONDENSING TMPSee Note
SST.BXXX.X FSATURATED SUCTION TEMPSee Note
RGT.BXXX.X FCOMPR RETURN GAS TEMPSee Note
SH.BXXX.X ^FSUCTION SUPERHEAT TEMPSee Note
ITEM
EXPANSION
COMMENT
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
Table 6 — Pressure Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
PRC.APRESSURES CIRCUIT A
DP.AXXX.X PSIGDISCHARGE PRESSURE
SP.AXXX.X PSIGSUCTION PRESSURE
PRC.BPRESSURES CIRCUIT BSee Note
DP.BXXX.X PSIGDISCHARGE PRESSURESee Note
SP.BXXX.X PSIGSUCTION PRESSURESee Note
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
ITEM
EXPANSION
Table 7 — Set Points Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
COOLCOOLING SETPOINTS
CSP.1XXX.X
FCOOLING SETPOINT 1Default: 44 F
CSP.2XXX.X FCOOLING SETPOINT 2Default: 44 F
CSP.3XXX.X FICE SETPOINTDefault: 32 F
HEADHEAD PRESSURE SETPOINTS
H.DPXXX.X FHEAD SETPOINTDefault: 95 F
F. O NXXX.X FFAN ON SETPOINTDefault: 95 F
F. O F FXXX.X FFAN OFF SETPOINTDefault: 72 F
ITEM
EXPANSION
COMMENT
COMMENT
B.OFFXXX.X FBASE FAN OFF DELTA TEMPDefault: 23 F
F. D LTXXX.X FFAN STAGE DELTADefault: 15 F
FRZBRINE FREEZE SETPOINT
BR.FZXXX.X FBRINE FREEZE POINTDefault: 34 F
9
Table 8 — Inputs Mode and Sub-Mode Directory
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
GEN.IGENERAL INPUTS
STST STRT/STOPSTART/STOP SWITCH
FLOWON/OFFCOOLER FLOW SWITCH
PM.F.1OPEN/CLSECOOLER PUMP 1 INTERLOCK
PM.F.2OPEN/CLSECOOLER PUMP 2 INTERLOCK
HT.RQON/OFFHEAT REQUEST
DLS1ON/OFFDEMAND LIMIT SWITCH 1
DLS2ON/OFFDEMAND LIMIT SWITCH 2
ICEDON/OFFICE DONE
DUALON/OFFDUAL SETPOINT SWITCH
CRCTCIRCUITS INPUTS
FKA1 ON/OFFCOMPRESSOR A1 FEEDBACK
FKA2 ON/OFFCOMPRESSOR A2 FEEDBACK
FKA3 ON/OFFCOMPRESSOR A3 FEEDBACK
FKA4 ON/OFFCOMPRESSOR A4 FEEDBACK
FKB1 ON/OFFCOMPRESSOR B1 FEEDBACKSee Note
FKB2 ON/OFFCOMPRESSOR B2 FEEDBACKSee Note
FKB3 ON/OFFCOMPRESSOR B3 FEEDBACKSee Note
ITEM
EXPANSION
COMMENT
FKB4 ON/OFFCOMPRESSOR B4 FEEDBACKSee Note
4-204-20 MA INPUTS
DMNDXX.X MA4-20 MA DEMAND SIGNAL
RSETXX.X MA4-20 MA RESET SIGNAL
CSPXX.X MA4-20 MA COOLING SETPOINT
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
Table 9 — Outputs Mode and Sub-Mode Directory
SUB-MODE
GEN.OGENERAL OUTPUTS
KEYPAD
ENTRY
ITEM DISPLAY
FAN1ON/OFFFAN 1 RELAY
FAN2ON/OFFFAN 2 RELAY
FAN3ON/OFFFAN 3 RELAY
FAN4ON/OFFFAN 4 RELAY
FAN5ON/OFFFAN 5 RELAY
FAN6ON/OFFFAN 6 RELAY
V.HPAON/OFFFAN SPEED CIRCUIT A
V.HPBON/OFFFAN SPEED CIRCUIT B
C.WP1ON/OFFCOOLER PUMP RELAY 1
C.WP2ON/OFFCOOLER PUMP RELAY 2
CLHTON/OFFCOOLER/PUMP HEATER
MLV.RON/OFFMINIMUM LOAD VALVE RELAY
ITEM
EXPANSION
COMMENT
10
Table 9 — Outputs Mode and Sub-Mode Directory (cont)
ENTER
ENTER
ENTER
ENTER
ENTER
SUB-MODE
A.EXVOUTPUTS CIRCUIT A EXV
B.EXVOUTPUTS CIRCUIT B EXV
CIR.AOUTPUTS CIRCUIT A
CIR.BOUTPUTS CIRCUIT B (See Note)
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
KEYPAD
ENTRY
ITEM DISPLAY
EXV.A0 to 100%EXV % OPEN
APPRON/OFFCIRCUIT A APPROACH
AP.SPAPPROACH SETPOINT
X.SH.RSH RESET AT MAX UNL-DIG
S.SH.RDIGLOAD TO START SH RST
SH_RAMOUNT OF SH RESET
OVR.AEXVA OVERRIDE
SPH.ASUCTION SUPERHEAT TEMP
ASH.SACTIVE SUPERHEAT SETPT
AMP.SACTIVE MOP SETPT
PLM.ACIR A EXV POSITION LIMIT
SPR.1SPARE 1 TEMPERATURE
EXV.B0 to 100%EXV % OPEN
APPRON/OFFCIRCUIT B APPROACH
AP.SPAPPROACH SETPOINT
OVR.BEXVB OVERRIDE
SPH.BSUCTION SUPERHEAT TEMP
ASH.SACTIVE SUPERHEAT SETPT
AMP.SACTIVE MOP SETPT
PLM.BCIR B EXV POSITION LIMIT
SPR.2SPARE 2 TEMPERATURE
CC.A1ON/OFFCOMPRESSOR A1 RELAY
DPE.RON/OFFCOMP A1 LOAD PERCENT
CC.A2ON/OFFCOMPRESSOR A2 RELAY
CC.A3ON/OFFCOMPRESSOR A3 RELAY
CC.A4ON/OFFCOMPRESSOR A4 RELAY
CC.B1ON/OFFCOMPRESSOR B1 RELAY
CC.B2ON/OFFCOMPRESSOR B2 RELAY
CC.B3ON/OFFCOMPRESSOR B3 RELAY
CC.B4ON/OFFCOMPRESSOR B4 RELAY
ITEM
EXPANSION
COMMENT
Table 10 — Configuration Mode and Sub-Mode Directory
SUB-MODE
DISPDISPLAY CONFIGURATION
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
KEYPAD
ENTRY
ITEM DISPLAY
TESTON/OFFTEST DISPLAY LEDS
METRON/OFFMETRIC DISPLAYOff = English; On = Metric
LANG XLANGUAGE SELECTION
PAS.EENBL/DSBLPASSWORD ENABLEDefault: Enable
PASSxxxxSERVICE PASSWORDDefault: 1111
ITEM
EXPANSION
11
COMMENT
Default: 0
0 = English
1 = Espanol
2 = Francais
3 = Portuguese
Table 10 — Configuration Mode and Sub-Mode Directory
Table 11 — Time Clock Mode and Sub-Mode Directory (cont)
ENTER
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAYSUB-ITEMDISPLAY
OVRSCHEDULE OVERRIDE
OVR.TXTIMED OVERRIDE HOURSDefault: 0, Range 0-4 hours
OVR.LXOVERRIDE TIME LIMITDefault: 0, Range 0-4 hours
T.OVRYES/NOTIMED OVERRIDEUser Entry
ITEM
EXPANSION
Table 12 — Operating Mode and Sub-Mode Directory
COMMENT
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
MODEMODES CONTROLLING UNIT
MD01ON/OFFCSM CONTROLLING CHILLER
MD02ON/OFFWSM CONTROLLING CHILLER
MD03ON/OFFMASTER/SLAVE CONTROL
MD05ON/OFFRAMP LOAD LIMITED
MD06ON/OFFTIMED OVERRIDE IN EFFECT
MD07ON/OFFLOW COOLER SUCTION TEMPA
MD08ON/OFFLOW COOLER SUCTION TEMPB
MD09ON/OFFSLOW CHANGE OVERRIDE
MD10ON/OFFMINIMUM OFF TIME ACTIVE
MD13ON/OFFDUAL SETPOINT
MD14ON/OFFTEMPERATURE RESET
MD15ON/OFFDEMAND/SOUND LIMITED
MD16ON/OFFCOOLER FREEZE PROTECTION
MD17ON/OFFLOW TEMPERATURE COOLING
MD18ON/OFFHIGH TEMPERATURE COOLING
MD19ON/OFFMAKING ICE
MD20ON/OFFSTORING ICE
COMMENT
MD21ON/OFFHIGH SCT CIRCUIT A
MD22ON/OFFHIGH SCT CIRCUIT B
MD23ON/OFFMINIMUM COMP ON TIME
MD24ON/OFFPUMP OFF DELAY TIME
MD25ON/OFFLOW SOUND MODE
LEGEND
CSM— Chillervisor System Manager
SCT— Saturated Condensing Temperature
WSM — Water System Manager
Table 13 — Alarms Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM
CRNTAXXX OR TXXXCURRENTLY ACTIVE ALARMS
RCRNYES/NORESET ALL CURRENT ALARMS
HISTAXXX OR TXXXALARM HISTORY
ITEM
EXPANSION
17
COMMENT
Alarms are shown as AXXX.
Alerts are shown as TXXX.
Alarms are shown as AXXX.
Alerts are shown as TXXX.
Table 14 — Operating Modes
MODE
NO.
01CSM CONTROLLING CHILLERChillervisor System Manager (CSM) is controlling the chiller.
02WSM CONTROLLING CHILLERWater System Manager (WSM) is controlling the chiller.
03MASTER/SLAVE CONTROLDual Chiller control is enabled.
05
06
07
08
09
10MINIMUM OFF TIME ACTIVEChiller is being held off by Minutes Off Time (Configuration
13
14
15
16
17
18
19
20
21
22
23
24
25
ITEM EXPANSION DESCRIPTION
RAMP LOAD LIMITEDRamp load (pull-down) limiting in effect. In this mode, the rate at which leaving fluid temperature
TIMED OVERRIDE IN EFFECTTimed override is in effect. This is a 1 to 4 hour temporary override of the programmed
LOW COOLER SUCTION TEMPACircuit A cooler Freeze Protection mode. At least one compressor must be on, and the Sat-
LOW COOLER SUCTION TEMPBCircuit B cooler Freeze Protection mode. At least one compressor must be on, and the Sat-
SLOW CHANGE OVERRIDESlow change override is in effect. The leaving fluid temperature is close to and moving
DUAL SETPOINTDual Set Point mode is in effect. Chiller controls to Cooling Set Point 1 (Set Points
TEMPERATURE RESETTemperature reset is in effect. In this mode, chiller is using temperature reset to adjust leav-
DEMAND/SOUND LIMITEDDemand limit is in effect. This indicates that the capacity of the chiller is being limited by
COOLER FREEZE PROTECTIONCooler fluid temperatures are approaching the Freeze point (see Alarms and Alerts section
LOW TEMPERATURE COOLINGChiller is in Cooling mode and the rate of change of the leaving fluid is negative and
HIGH TEMPERATURE COOLINGChiller is in Cooling mode and the rate of change of the leaving fluid is positive and increasing.
MAKING ICEChiller is in an unoccupied mode and is using Cooling Set Point 3 (Set Points
STORING ICEChiller is in an unoccupied mode and is controlling to Cooling Set Point 2 (Set Points
HIGH SCT CIRCUIT AChiller is in a Cooling mode and the Saturated Condensing Temperature (SCT) is greater than
HIGH SCT CIRCUIT BChiller is in a Cooling mode and the Saturated Condensing Temperature (SCT) is greater than
MINIMUM COMP ON TIMECooling load may be satisfied, however control continues to operate compressor to ensure
PUMP OFF DELAY TIMECooling load is satisfied, however cooler pump continues to run for the number of minutes set
LOW SOUND MODEChiller operates at higher condensing temperature and/or reduced capacity to minimize
is dropped is limited to a predetermined value to prevent compressor overloading. See Cooling
Ramp Loading (Configuration
desired, to any rate from 0.2° F to 2° F (0.1° to 1° C)/minute.
schedule, forcing unit to Occupied mode. Override can be implemented with unit under
Local (Enable) or CCN (Carrier Comfort Network
urated Suction Temperature is not increasing greater than 1.1° F (0.6° C) in 10 seconds. If
the saturated suction temperature is less than the Brine Freeze Point (Set Points
BR.FZ) minus 6° F (3.4° C) and less than the leaving fluid temperature minus 14° F
(7.8° C) for 2 minutes, a stage of capacity will be removed from the circuit. Or, If the saturated suction temperature is less than the Brine Freeze Point minus 14° F (7.8° C), for
90 seconds, a stage of capacity will be removed from the circuit. The control will continue to
decrease capacity as long as either condition exists.
urated Suction Temperature is not increasing greater than 1.1° F (0.6° C) in 10 seconds. If
the saturated suction temperature is less than the Brine Freeze Point (Set Points
BR.FZ) minus 6° F (3.4° C) and less than the leaving fluid temperature minus 14° F
(7.8° C) for 2 minutes, a stage of capacity will be removed from the circuit. Or, If the saturated suction temperature is less than the Brine Freeze Point minus 14° F (7.8° C), for
90 seconds, a stage of capacity will be removed from the circuit. The control will continue to
decrease capacity as long as either condition exists.
towards the control point.
CSP.1) during occupied periods and Cooling Set Point 2 (Set PointsCOOLCSP.2)
during unoccupied periods.
ing fluid set point upward and is currently controlling to the modified set point. The set point
can be modified based on return fluid, outdoor-air-temperature, space temperature, or 4 to
20 mA signal.
demand limit control option. Because of this limitation, the chiller may not be able to produce the desired leaving fluid temperature. Demand limit can be controlled by switch inputs
or a 4 to 20 mA signal.
for definition). The chiller will be shut down when either fluid temperature falls below the
Freeze point.
decreasing faster than -0.5° F per minute. Error between leaving fluid and control point
exceeds fixed amount. Control will automatically unload the chiller if necessary.
Error between leaving fluid and control point exceeds fixed amount. Control will automatically
load the chiller if necessary to better match the increasing load.
CSP.3) to make ice. The ice done input to the Energy Management Module (EMM) is open.
CSP.2). The ice done input to the Energy Management Module (EMM) is closed.
the calculated maximum limit. No additional stages of capacity will be added. Chiller capacity
may be reduced if SCT continues to rise to avoid high-pressure switch trips by reducing condensing temperature.
the calculated maximum limit. No additional stages of capacity will be added. Chiller capacity
may be reduced if SCT continues to rise to avoid high-pressure switch trips by reducing condensing temperature.
proper oil return. May be an indication of oversized application, low fluid flow rate or low loop
volume.
by the configuration variable Cooler Pump Shutdown Delay (Configuration
PM.DY).
overall unit noise during evening/night hours (Configuration
SLCTCRMP). The pull-down limit can be modified, if
®
) control. Override expires after each use.
OPT2DELY).
OPT2LS.MD).
OPT1
FRZ
FRZ
COOL
COOL
COOL
18
CONTROLS
General —
the ComfortLink™ electronic control system that controls and
monitors all operations of the chiller.
The control system is composed of several components as
listed in the sections below. See Fig. 3-5 for typical control box
drawings. See Fig. 6 and 7 for control schematics.
The 30RAP air-cooled scroll chillers contain
Main Base Board (MBB) — See Fig. 8. The MBB is
the heart of the ComfortLink control system. It contains the
major portion of operating software and controls the operation
of the machine. The MBB continuously monitors input/output
channel information received from its inputs and from all other
modules. The MBB receives inputs from the discharge and
suction pressure transducers and thermistors. See Table 15. The
MBB also receives the feedback inputs from each compressor
current sensor board and other status switches. See Table 16.
The MBB also controls several outputs. Relay outputs controlled by the MBB are shown in Table 17. Information is
transmitted between modules via a 3-wire communication bus
or LEN (Local Equipment Network). The CCN (Carrier Comfort Network) bus is also supported. Connections to both LEN
and CCN buses are made at the LVT (low voltage terminal).
See Fig. 8.
Energy Management Module (EMM) — The EMM
module is available as a factory-installed option or as a fieldinstalled accessory. The EMM module receives 4 to 20 mA
inputs for the leaving fluid temperature reset, cooling set point
and demand limit functions. The EMM module also receives
the switch inputs for the field-installed 2-stage demand limit
and ice done functions. The EMM module communicates the
status of all inputs with the MBB, and the MBB adjusts the
control point, capacity limit, and other functions according to
the inputs received.
Current Sensor Board (CSB) — The CSB is used to
monitor the status of the compressors by measuring current and
providing an analog input to the main base board (MBB) or
compressor expansion module (CXB).
AUX Board (AUX) — The AUX is used with the digital
scroll option and the low ambient head pressure option. It provides additional inputs and outputs for digital scroll control
along with analog outputs to control head pressure control fan
speeds.
Expansion Valve Board (EXV) — The EXV board
communicates with the MBB and directly controls the expansion valves to maintain the correct compressor superheat.
Enable/Off/Remote Contact Switch — The Enable/
Off/Remote Contact switch is a 3-position switch used to
control the chiller. When switched to the Enable position the
chiller is under its own control. Move the switch to the Off
position to shut the chiller down. Move the switch to the
Remote Contact position and a field-installed dry contact can
be used to start the chiller. The contacts must be capable of
handling a 24 vac, 50-mA load. In the Enable and Remote
Contact (dry contacts closed) positions, the chiller is allowed to
operate and respond to the scheduling configuration, CCN
configuration and set point data. See Fig. 9.
Emergency On/Off Switch — The Emergency On/Off
switch should only be used when it is required to shut the
chiller off immediately. Power to the MBB, EMM, and
marquee display is interrupted when this switch is off and all
outputs from these modules will be turned off.
Board Addresses — The main base board (MBB) has a
3-position instance jumper that must be set to ‘1.’ The electronic expansion valve board (EXV) and energy management
board (EMM) have 4-position DIP switches. All switches are
set to ‘On’ for these boards. The auxiliary board (AUX) has an
8-position DIP switch. Switches 2, 5, and 7 are set to ‘On.’
Control Module Communication
RED LED — Proper operation of the control boards can be
visually checked by looking at the red status LEDs
(light-emitting diodes). When operating correctly, the red status
LEDs should be blinking in unison at a rate of once every
2 seconds. If the red LEDs are not blinking in unison, verify
that correct power is being supplied to all modules. Be sure that
the main base board (MBB) is supplied with the current software. If necessary, reload current software. If the problem still
persists, replace the MBB. A red LED that is lit continuously or
blinking at a rate of once per second or faster indicates that the
board should be replaced.
GREEN LED — The MBB has one green LED. The Local
Equipment Network (LEN) LED should always be blinking
whenever power is on. All other boards have a LEN LED
which should be blinking whenever power is on. Check LEN
connections for potential communication errors at the board J3
and/or J4 connectors. Communication between modules is
accomplished by a 3-wire sensor bus. These 3 wires run in
parallel from module to module. The J4 connector on the MBB
provides both power and communication directly to the
marquee display only.
YELLOW LED — The MBB has one yellow LED. The
Carrier Comfort Network (CCN) LED will blink during times
of network communication.
Carrier Comfort Network® (CCN) Interface —
The 30RAP chiller units can be connected to the CCN if
desired. The communication bus wiring is a shielded,
3-conductor cable with drain wire and is supplied and installed
in the field. See Table 18. The system elements are connected
to the communication bus in a daisy chain arrangement. The
positive pin of each system element communication connector
must be wired to the positive pins of the system elements on
either side of it. This is also required for the negative and
signal ground pins of each system element. Wiring connections
for CCN should be made at LVT. Consult the CCN Contractor’s Manual for further information.
NOTE: Conductors and drain wire must be 20 AWG (American Wire Gage) minimum stranded, tinned copper. Individual
conductors must be insulated with PVC, PVC/nylon, vinyl,
Teflon, or polyethylene. An aluminum/polyester 100% foil
shield and an outer jacket of PVC, PVC/nylon, chrome vinyl,
or Teflon with a minimum operating temperature range of
–20 C to 60 C is required. Wire manufactured by Alpha (2413
or 5463), American (A22503), Belden (8772), or Columbia
(02525) meets the above mentioned requirements.
It is important when connecting to a CCN communication
bus that a color coding scheme be used for the entire network
to simplify the installation. It is recommended that red be used
for the signal positive, black for the signal negative, and white
for the signal ground. Use a similar scheme for cables containing different colored wires.
At each system element, the shields of its communication
bus cables must be tied together. If the communication bus is
entirely within one building, the resulting continuous shield
must be connected to a ground at one point only. If the communication bus cable exits from one building and enters another,
the shields must be connected to grounds at the lightning
suppressor in each building where the cable enters or exits the
building (one point per building only). To connect the unit to
the network:
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white
(ground), and black (–) conductors. (Substitute appropriate colors for different colored cables.)
19
3. Connect the red wire to (+) terminal on LVT of the plug,
the white wire to COM terminal, and the black wire to the
(–) terminal.
4. The RJ14 CCN connector on LVT can also be used, but is
only intended for temporary connection (for example, a
laptop computer running Service Tool).
IMPORTANT: A shorted CCN bus cable will prevent some
routines from running and may prevent the unit from starting. If abnormal conditions occur, unplug the connector. If
conditions return to normal, check the CCN connector and
cable. Run new cable if necessary. A short in one section of
the bus can cause problems with all system elements on the
bus.
Table 15 — Thermistor Designations
THERMISTOR
LWTJ8-13,14 (MBB) Cooler Leaving Fluid
EWTJ8-11,12 (MBB) Cooler Entering Fluid
RGTA
RGTB
OAT
SPT
DTT
LEGEND
LWT — Leaving Water Temperature
MBB — Main Base Board
PIN
CONNECTION
POINT
J8-1,2 (MBB)Circuit A Return Gas
J8-3,4 (MBB)Circuit B (035-060 only)
J8-7,8 (MBB)Outdoor-Air Temperature
J8-5,6 (MBB)
TB5-5,6
J6-1,2 (AUX)Discharge Temperature
THERMISTOR INPUT
Temperature
Return Gas Temperature
Sensor
Accessory Remote Space
Temperature Sensor or
Dual LWT Sensor
Thermistor
Table 16 — Status Inputs
STATUS SWITCHPIN CONNECTION POINT
Chilled Water Pump 1J7-1,2
Chilled Water Pump 2J7-3,4
Sensors — The electronic control uses 4 to 7 thermistors to
sense temperatures for controlling chiller operation. See
Table 15. These sensors are outlined below. Thermistors RGTA, RGTB, EWT, LWT, and OAT are identical in temperature
versus resistance and voltage drop performance. The dual chiller thermistor is 5 kat 77 F (25 C)thermistor. Space temperature thermistor is a 10 kat 77 F (25 C). The DTT thermistor
is an 86 kat 77 F (25 C)thermistor. See Thermistors section
for temperature-resistance-voltage drop characteristics.
COOLER LEAVING FLUID SENSOR — The thermistor is
installed in a well in the factory-installed leaving fluid piping
coming from the bottom of the brazed-plate heat exchanger.
COOLER ENTERING FLUID SENSOR — The thermistor is
installed in a well in the factory-installed entering fluid piping
coming from the top of the brazed-plate heat exchanger.
COMPRESSOR RETURN GAS TEMPERATURE SENSOR — These thermistors are installed in a well located in the
suction line of each circuit.
OUTDOOR-AIR TEMPERATURE SENSOR (OAT) —
This sensor is factory installed on a bracket which is inserted
through the base pan of the unit.
DISCHARGE TEMPERATURE THERMISTOR
(DTT) — This sensor is only used on units with a digital
compressor. The sensor is mounted on the discharge line close
to the discharge of the digital compressor. It attaches to the discharge line using a spring clip and protects the system from
high discharge gas temperature when the digital compressor is
used. This sensor is a connected to the AUX board.
REMOTE SPACE TEMPERATURE SENSOR OR DUAL
LEAVING WATER TEMPERATURE SENSOR — One of
two inputs can be connected to the LVT. See appropriate sensor below.
Remote Space Temperature Sensor
33ZCT55SPT) is an accessory sensor that is remotely mounted
in the controlled space and used for space temperature reset.
The sensor should be installed as a wall-mounted thermostat
would be (in the conditioned space where it will not be subjected to either a cooling or heating source or direct exposure
to sunlight, and 4 to 5 ft above the floor).
Space temperature sensor wires are to be connected to
terminals in the unit main control box. The space temperature
sensor includes a terminal block (SEN) and a RJ11 female
connector. The RJ11 connector is used access into the Carrier
Comfort Network
®
(CCN) at the sensor.
To connect the space temperature sensor (Fig. 10):
1. Using a 20 AWG twisted pair conductor cable rated for
the application, connect 1 wire of the twisted pair to one
SEN terminal and connect the other wire to the other
SEN terminal located under the cover of the space
temperature sensor.
2. Connect the other ends of the wires to terminals 5 and 6
on TB5 located in the unit control box.
— Sensor (part no.
20
Units on the CCN can be monitored from the space at the
sensor through the RJ11 connector, if desired. To wire the RJ11
connector into the CCN (Fig. 11):
IMPORTANT: The cable selected for the RJ11 connector
wiring MUST be identical to the CCN communication bus
wire used for the entire network. Refer to Table 18 for
acceptable wiring.
1. Cut the CCN wire and strip ends of the red (+), white
(ground), and black (–) conductors. (If another wire color
scheme is used, strip ends of appropriate wires.)
2. Insert and secure the red (+) wire to terminal 5 of the
space temperature sensor terminal block.
LEGEND FOR FIG. 3-7
ALMR— Alarm Relay
AUX— Auxilliary
BR— Boiler Relay
C—Contactor, Compressor
CB— Circuit Breaker
CCB— Compressor Circuit Breaker
CH— Crankcase Heater
CHC— Cooler/Pump Heater Contactor
COMP— Compressor
CSB— Current Sensor Board
CWFS— Chilled Water Flow Switch
CWP— Chilled Water Pump
DGS— Digital Scroll Compressor
DPT— Discharge Pressure Transducer
DTT— Discharge Temperature Thermistor
DUS— Digital Unloader Solenoid
EMM— Energy Management
EXV— Electronic Expansion Valve
FB— Fuse Block
FC— Fan Contactor
FCB— Fan Circuit Breaker
FIOP— factory Installed Option
FR— Fan Relay
GND— Ground
HPS— High-Pressure Switch
LON— Local Operating Network
LV T— Low Voltage Terminal Block
MBB— Main Base Board
MLV— Minimum Load Valve
MM— Motormaster
MP— Motor Protector
MS— Manual Starter
NEC— National Electrical Code
OAT— Outdoor-Air Thermistor
OFM— Outdoor Fan Motor
RGT— Return Gas Thermistor
SCCR— Short Circuit Current Rating
SPT— Suction Pressure Transducer
SW— Switch
TB— Terminal Block
TNKR— Storage Tank Heater Relay
TRAN— Transformer
UPC— Unitary Protocol Converter
Terminal Block
Terminal (Unmarked)
Terminal (Marked)
Splice
Factory Wiring
Field Wiring
Accessory or Option Wiring
To indicate common potential only; not to represent wiring.
3. Insert and secure the white (ground) wire to terminal 4 of
the space temperature sensor.
4. Insert and secure the black (–) wire to terminal 2 of the
space temperature sensor.
5. Connect the other end of the communication bus cable to
the remainder of the CCN communication bus.
Dual Leaving Water Temperature Sensor
— For dual chiller
applications (parallel only are supported), connect the dual
chiller leaving fluid temperature sensor (refer to Configuring
and Operating Dual Chiller Control section on page 36) to the
space temperature input of the Master chiller. If space temperature is required for reset applications, connect the sensor to the
Slave chiller and configure the slave chiller to broadcast the
value to the Master chiller.
21
CONTROL BOX
FAN
1
A1
COMPRESSOR
LOCATED OVER EMM AND EXV
EMM
EXV
LON
AUX
UPC
TB1
TB4
CSB-A1
MBB
CHC
CCB
FB-1
TRAN
DISCONNECT
OPTION/TB
C-A1
MM
MS-
CWP1
CWP1
MS-
CWP2
CWP2
Fig. 3 — Typical Control Box for 30RAP010,015
Fig. 4 — Typical Control Box for 30RAP018-030
a30-4962
a30-4963
FB-1
AUX
LON
EMM
EXV
CHC
CCB-1
CSB-A1
TB1
UPC
TB4
C-A1
FC1/MM
MBB
FB-3
MS-
CWP1
CWP1 CWP2
TRAN
MS-
CWP2
CSB-A2
FC2C-A2
CCB-2
DISCONNECT
OPTION/TB
22
Fig. 5 — Typical Control Box for 30RAP035-060
a30-4964
OPTION/TB
DISCONNECT
CHC
EXV
EMM
CB-4
CB-3
TB1
CSB-B2
CSB-B1
UPC
LON
AUX
TB4
MS-
MS-
CWP2
CWP1
FR-4
FR-3
C-B2
CWP2
CWP1
C-B1
MBB
055,060 UNIT ONLY
B2
2
4
FAN
FAN
FAN3FAN
LOCATED OVER EMM AND EXV
1
B1
A2
COMPRESSORS
A1
CONTROL BOX END
FCB-1/2/3
CB-2
CB-1
TRAN-1
CSB-A2
CSB-A1
TRAN-2
23
FC-3
FC-2
MM
FC-1
FR-2
FR-1
C-A2
C-A1
OPTIONAL
Fig. 6A — Typical Wiring Schematic, 30RAP018-030 Units — Power Wiring
a30-4965
DISCONNECT
DISCONNECT
TO FUSED
PER NEC
EQUIP GND
~
FU5
RED
1
H3
H4
TRAN3
X3
WHT
WHT
GRN/YEL
2
GFI-CO
FIOP/ACCESSORY
SILVER SCREW
SILVER SCREW
GRN-YEL
FUSE
NUMBER
FU1 & FU2
380-3-60,460-3-60,575-3-60
FU3 (24V)
208/230-3-60,230-3-60
380-3-60,460-3-60,575-3-60
FU4 (115V)
380-3-60,460-3-60,575-3-60
FB1
(NO MM)
380-3-60,460-3-60,575-3-60
FB1
(WITH MM)
380-3-60,460-3-60,575-3-60
FB2
380-3-60,460-3-60,575-3-60
FB3
VOLTAGE SERIES
575-3-60 100H1 & H2
380-3-60 200H1 & H2
230-3-60 500H2 & H4
208-3-60 500H3 & H4
460-3-60 600H1 & H4
CONNECT FOR
APPROPRIATE
PRIMARY VOLTAGE
SEE TABLE 1
1. FACTORY WIRING IS IN ACCORDANCE WITH UL 1995 STANDARDS.
ANY FIELD MODIFICATIONS OR ADDITIONS MUST BE IN
COMPLIANCE WITH ALL APPLICABLE CODES.
C MIN WIRE FOR FIELD POWER SUPPLY.
3. ALL FIELD INTERLOCK CONTACTS MUST HAVE A MIN RATING OF
2 AMPS @ 24VAC SEALED. SEE FIELD INTERLOCK WIRING.
4. COMPRESSOR AND FAN MOTORS ARE THERMALLY PROTECTED- THREE PHASE MOTORS PROTECTED AGAINST PRIMARY SINGLE
PHASE CONDITIONS.
5. TERMINALS 13 & 14 OF LVT ARE FOR FIELD CONNECTION
OF REMOTE ON-OFF. THE CONTACT MUST BE RATED FOR DRY
CIRCUIT APPLICATION CAPABLE OF HANDLING A 5VDC
1 MA TO 20 MA LOAD.
6. FOR 500 SERIES UNIT OPERATION AT 208-3-60V LINE VOLTAGE,
TRAN1 PRIMARY CONNECTIONS MUST BE MOVED TO TERMINALS H3 & H4.
7. FOR UNITS WITH LOW AMBIENT MOTOR MASTER V FIOP/ACCESSORY,
FAN CONTACTOR FC1 IS REPLACED WITH MOTORMASTER RELAY MMR.
J1
EXV
J2
DGS FIOP
12
11
J1
AUX
3
3
2
2
1
1
3
3
2
2
BRN
1
1
RED
3
3
2
2
2
BRN
1
1
1
RED
FB1
11
21
BLK
22
12
YEL
13
23
BLU
FB2
11
21
BLK
22
12
YEL
13
23
BLU
MM-A
L1 T1
BLK
L2 T2
YEL
L3 T3
BLU
2
*1
25
2
FC2
11 21
BLK
YEL
22
12
13 23
BLU
BLK
YEL
CHC
42
CHC
86
1
BLK-1
2
BLK-2
3
BLK-3
YEL
MMR
VIO
11 14
240 1/4W
RED
FROM
AUX-J4
BLK
BLK-1
BLK-2
BLK-3
~
BLK
WHT
COOLER/PUMP
HEATERS
(380,460,575V)
~~
~
BLK
8. IF CHILLED WATER PUMP INTERLOCK IS USED,
REMOVE JUMPER FROM TERMINAL 11 TO 17 AND
WIRE INTERLOCK CONTACT ACROSS TERMINALS 11 & 17.
9. MP-A1 NOT USED IN THE FOLLOWING UNITS:
018,020: ALL UNITS
025,030: 460V UNITS WITHOUT DIGITAL SCROLL
10. MP-A2 NOT USED IN THE FOLLOWING UNITS:
018-020: ALL UNITS
025,030: 460V UNITS
11. JUMPER PLUG REQUIRED WHEN MP NOT USED
* MM SIGNAL CONNECTION
1
2
3
~
1
3
2
OFM1
GRN/YEL
VOLTAGE
208/230/460/575
380
BLK
BLK
COOLER/PUMP
HEATERS
(208/230,230V)
~
WHT
OFM2
GRN/YEL
ZHBT
061
06A31
1
2
3
24
HEAT
Fig. 6B — Typical Wiring Schematic, 30RAP018-030 Units — Control Wiring
a30-4966
SEE NOTES ON
PAGE 24.
CWPI
SEE
NOTE 8
REMOTE
ON-OFF
SWITCH
(SEE NOTE
5)
DUAL
SETPOINT
J10A
J10B
RLY 11
RLY 9
RLY 10
RLY 5
RLY 6
RLY 7
RLY 8
RLY 1
RLY 2
RLY 3
RLY 4
RED
WHT
BLK
RED
BLK
WHT
MBB
LVT
20
19
LVT
17
11
13
14
15
16
LEN CCN
J1
PORT 2
PORT 1A
J12
6
7
J11
2
3
4
11
12
13
14
9
7
8
6
5
LVT
(+)
(COM)
(-)
SHIELD
UPC
NET +
1
NET -
2
N/C
3
N/C
4
SIGNAL
5
NET +
1
NET 2
2
SHIELD
3
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
1
10
2
11
3
12
4
13
5
14
6
15
7
16
8
17
9
18
10
19
11
20
12
21
13
22
14
23
15
24
16
25
17
26
18
27
BR
HEAT/BOILER FIELD
INSTALLED WIRING
BLK
RED
OFF
RED
RED
VIO
J13
BLK
1
WHT
2
RED
3
BRN
4
RED
5
BLK
6
WHT
7
RED
8
OPTION
J3
UPC OPT
CB1
3.2 AMPS
CB2
5.2 AMPS
TB4
ORN
5
RED
RED
RED
GRA
PNK
A2
SW2
RED
ORN
C2
ORN
B2
RED
TB4
7
XF
RED
BLK
TRAN1
SECONDARY 24V
X1
FU3
GRA
GRA
MLV-A
MLV ACCSY
FC1
PNK
SEE NOTE 7
ORN
TB4
RED
4
RED
RED
BLK
RED
ORN
HPS-A
BLK
BLK
BLK
ORN
GRA
SEE NOTE 11
SEE NOTE 11
VIO
RED
6
6
GRA
5
5
GRA
4
4
3
J6
HR
ALMR
3
2
2
VIO
1
1
BRN
LVT
J11
18
1
STORAGE TANK
HEATER RELAY
ORN
PL1-2PL1-1
MP-A1
VIO
VIO
VIO
M1
M2
VIO
PL1-6PL1-5
MP-A2
VIO
M1
M2
VIO
LVT
J12
25
1
2
24
ORN
MAX LOAD-5VA SEALED
10VA INRUSH
ACCESSORY
RED
ORN
ORN
GRA
VIO
RED
FIOP OR
FIELD INSTALLED
OPTION
FIELD INSTALLED
MAX LOAD-5VA SEALED
10VA INRUSH
FC2
ALM
R
TNK
R
CHC
CA1
CA2
CWP
1
CWP
2
RED
TB1
X2
GRN/YEL
BRN
A2A1
A2A1
A2A1
A2A1
BRN
BRN
BRN
BRN
BRN
BRN
BRN
C
BRN
BRN
BRN
BRN
BRN
BRN
BRN
LVT
J12
5
21
BRN
BRN
BRN
BRN
A2A1
A2A1
A2A1
BRN
BRN
BRN
BRN
A2
A2
A2
A2
A2
A2
A2
C
C
C
A2
A2
C
A2
A2
MBB J1-2
UPC GND
CWFS 3
EXV J1-2
LVT J12-5
CHC
CA1
CWP1
CA2
FC2
FC1
FC3
TB1
TB1
TB1
CA2
CA1
TB1
CWP2
CWP1
TB4
4
RED
SEE NOTE 9
T2T1MP-A1
SEE NOTE 10
T2T1MP-A2
PL1-4
BRN
BRN
PL1-8
BRN
BRN
PL1-3
RED
RED
PL1-7
RED
RED
BRN
CWFS
4
2
10
10
WHT
1
RED
1
2
WHT
2
3
J3
9
ORN
9
J4
MAIN
BASE
8
8
SW1
A1
ENABLE
RED
C1
B1
RED
GRA
GRA
13
RED
14
CWP2
13
VIO
14
CWP1
BRN
RED
BLK
WHT
RED
BLK
WHT
RED
LON
GND
NET
J4
1
2
BOARD
7
7
6
6
5
5
4
4
3
3
2
2
1
1
10
10
9
9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1
1
J9
J7
J8
J5
BLK
3
4
4
1
RED
1
2
WHT
2
3
BLK
3
4
4
5
BRN
5
6
RED
6
1
1
RED
2
2
ORN
3
3
BRN
4
4
RED
5
5
ORN
6
6
BRN
7
7
RED
8
8
ORN
9
9
BRN
10
10
RED
11
11
ORN
12
12
BRN
1
1
2
2
3
3
4
4
5
5
6
6
1
7
2
8
3
9
4
10
1
11
2
12
3
13
4
14
1
15
2
16
3
17
4
18
5
19
6
20
7
21
8
22
9
23
10
24
11
25
12
26
1
MARQUEE
RED
1
DISPLAY
2
WHT
2
3
BLK
3
4
4
5
RED
5
6
BRN
6
2
CSB
3
B2
1
2
CSB
3
A2
1
2
CSB
3
B1
1
2
CSB
3
A1
1
B
C
A
B
C
A
RGTA
OAT
EVAPORATOR ENTERING
FLUID TEMP
EVAPORATOR LEAVING
FLUID TEMP
+
DPTA
-
+
SPTA
-
LVT
J12 T55
3
4
23
22
T-55
SEN
ACCSY
SPACE TEMPERATURE
ACCESSORY OR
DUAL CHILLER LWT
RED
BLK
BLU
BLU
RED
BLK
RED
BLK
RED
BLK
RED
GRN
BLK
RED
GRN
BLK
BLK
WHT
RED
BLK
WHT
RED
BLK
WHT
RED
BLK
WHT
RED
BLK
WHT
RED
4
4
3
3
2
2
1
1
4
4
3
3
2
2
1
1
6
-
3
5
G
2
4
+
1
3
-
3
2
G
2
1
+
1
12345678
DARK = SWITCH LOCATION
4
4
3
3
2
2
1
1
4
4
3
3
2
2
1
1
ACCESSORY
J3
J4
J9
DGS OR
FIOP
J3
J4
FIOP/
MM
EXV
AUX
EMM
1
1
2
2
3
3
J7
4
4
5
5
PL-EXVA
BLK
1
1
BLK
YEL
2
2
WHT
3
3
J6
4
GRN
4
5
5
RED
7
-
VIORED
7
8
J2
CH1
BRNBLK
8
1
CH11
REDRED
1
2
J6
-
BLKBLK
2
1
CH9
RED
1
2
J4
-
BLK
2
ON
OFF
J5
J7
J6
1
CH10
1
2
-
2
1
1
GRA
2
2
GRA
3
3
RED
4
4
RED
5
5
BLU
6
6
BLU
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
1
1
2
2
VIO
3
3
BRN
4
4
5
5
ORN
6
6
7
7
8
8
PNK
9
9
10
10
11
11
12
12
PL50-1
PL50-2
PL50-3
PL50-4
TO MM-A
J10
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
EXV-A
GRY
RED
DUS
DTT
LVT
1
2
ICE DONE
3
4
DLS STEP 1
5
6
DLS STEP 2
DEMAND
+
7
LIMIT
-
8
4-20mA
TEMP
9
+
RESET
-
4-20mA
COOLING
+
10
SETPOINT
-
4-20mA
25
COMP A2
GRN/YEL
TRAN1
H2
H3
H4
SECONDARY 24V
RED
FC2
BLK-1
BLK-2
BLK-3
FU3
SW2
C1
A1
B1
1
2
3
H1
X1
CONNECT FOR
APPROPRIATE
PRIMARY VOLTAGE
SEE TABLE 1
CONNECT FOR
APPROPRIATE
PRIMARY VOLTAGE
SEE TABLE 2
X2
* MM SIGNAL CONNECTION
VOLTAGE
TBHZ
208/230/460/575
160
380
13A60
FCB2/FB2
NOTES:
1. FACTORY WIRING IS IN ACCORDANCE WITH UL 1995 STANDARDS.
ANY FIELD MODIFICATIONS OR ADDITIONS MUST BE IN
COMPLIANCE WITH ALL APPLICABLE CODES.
2. USE 75
C MIN WIRE FOR FIELD POWER SUPPLY.
3. ALL FIELD INTERLOCK CONTACTS MUST HAVE A MIN RATING OF
2 AMPS @ 24VAC SEALED. SEE FIELD INTERLOCK WIRING.
4. COMPRESSOR AND FAN MOTORS ARE THERMALLY PROTECTED- THREE PHASE MOTORS PROTECTED AGAINST PRIMARY SINGLE
PHASE CONDITIONS.
5. TERMINALS 13 & 14 OF LVT ARE FOR FIELD CONNECTION
OF REMOTE ON-OFF. THE CONTACT MUST BE RATED FOR DRY
CIRCUIT APPLICATION CAPABLE OF HANDLING A 5VDC
1 MA TO 20 MA LOAD.
6. FOR 500 SERIES UNIT OPERATION AT 208-3-60V LINE VOLTAGE,
TRAN1 PRIMARY CONNECTIONS MUST BE MOVED TO TERMINALS H3 & H4.
10. MP-A1 NOT USED IN THE FOLLOWING UNITS:
035-045: ALL UNITS
11. MP-A2 NOT USED IN THE FOLLOWING UNITS:
035-045: ALL UNITS
12. MP-B1 NOT USED IN THE FOLLOWING UNITS:
035,040: ALL UNITS
045-060: 460V UNITS
13. MP-B2 NOT USED IN THE FOLLOWING UNITS:
035,040: ALL UNITS
045-060: 460V UNITS
14. JUMPER PLUG REQUIRED WHEN MP NOT USED
7. FOR 575-3-60V UNITS, FAN CIRCUIT BREAKER FCB2
IS REPLACED WITH FUSE BLOCK FB2.
SEE NOTE 7
BLK
BLU
YEL
VOLTAGE SERIES
TERMINAL
CONNECTIONS
FOR PRIMARY SIDE
575-3-60 100H1 & H2
380-3-60 200H1 & H2
230-3-60 500H2 & H4
208-3-60 500H3 & H4
460-3-60 600H1 & H4
TABLE 1
UNIT VOLTAGE
REPLACE
WITH
FNQ-R-3.5
FU1 & FU2
FUSE
NUMBER
380-3-60
TRAN
SIZE
200VA
FNQ-R-2.5
208/230-3-60
FNM-10
FU3 (24V)
380-3-60,460-3-60,575-3-60
200VA
208/230-3-60
VOLTAGE SERIES
TERMINAL
CONNECTIONS
FOR PRIMARY SIDE
575-3-60 100COM & 575
380-3-60 200
230-3-60 500
208-3-60 500
460-3-60 600
TABLE 2
460-3-60
575-3-60
FNQ-R-2
FNQ-R-1.5
COM & 380
COM & 230
COM & 208
COM & 460
208
230
380
400
575
460
8. FOR UNITS WITH LOW AMBIENT MOTOR MASTER V FIOP/ACCESSORY,
030-050: FAN CONTACTOR FC1 IS REPLACED WITH MOTORMASTER RELAY MMR.
SECONDARY 24V
3.2 AMPS
CB4
RED
3
3
2
2
1
1
J2
BRN
RED
2
2
1
J1
1
3
3
EXV
BRN
RED
CWFS
CH-A2
BLU
BLK
CH-B1
BLU
BLK
CH-A1
BLU
BLK
CH-B2
BLU
BLK
GRN/YEL
OFM2
1
2
3
BLK-1
BLK-2
BLK-3
GRN/YEL
FC1
1
2
3
11 21
12
22
13 23
BLK-1
BLK-2
BLK-3
BLU
YEL
BLK
CWP1
CWP2
MS-CWP2
MS-CWP1
BLK
BLK
BLK
BLK
BLK
BLK
L3
L1
L2
CWP1
WATER
PUMP
L3
L1
L2
CWP2
WATER
PUMP
L1 T1
L2
T2
L3
T3
L1
L2
L3
T1
T2
T3
L1 T1
L2
T2
L3
T3
L1
L2
L3
T1
T2
T3
BLK
YEL
BLU
BLK
YEL
BLU
GRN/YEL
GRN/YEL
VOLTAGE SERIES
TERMINAL
CONNECTIONS
FOR PRIMARY SIDE
TERMINAL
CONNECTIONS FOR
SECONDARY SIDE
575-3-60 100H1-H2XF-X2
230-3-60 400,500H2-H4XF-X2
208-3-60 500H3-H4XF-X2
460-3-60 600H1-H4XF-X2
TRAN3
SECONDARY
115V
WHT
RESET
TEST
GRN-YEL
GFI-CO
FIOP/ACCESSORY
BRASS SCREW
SILVER SCREW
WHT
FU4
X3
X1
LOAD
LINE
BRASS SCREW
SILVER SCREW
BLK
2
2
XF
H4
H1
HF
H2
H3
BLK
1
FU6
RED
1
FU5
~
~
~
FU5 & FU6
500VA
FNM-6
FU4 (115V)
380-3-60,460-3-60,575-3-60
500VA
208/230-3-60
460-3-60,575-3-60
208/230-3-60,230-3-60
FNQ-R-2.5
FNQ-R-3.5
9. IF CHILLED WATER PUMP INTERLOCK IS USED,
REMOVE JUMPER FROM TERMINAL 11 TO 17 AND
CHILLED WATER PUMP FIOP
WIRE INTERLOCK CONTACT ACROSS TERMINALS 11 & 17.
050-060: 460V UNITS WITHOUT DIGITAL SCROLL
050-060: 460V UNITS
GRN/YEL
OFM3
OFM4
(055,060 ONLY)
(055,060 ONLY)
GRN/YEL
1
2
3
BLK-1
BLK-2
BLK-3
OFM4 (055,060)
OFM3 (035-050)
L1 T1
L2 T2
L3 T3
MMR
11 14
*1
2
YEL
VIO
MM-A
GRN/YEL
FC2
BLK-1
BLK-2
BLK-3
1
2
3
11 21
12
22
13 23
GRN/YEL
OFM1
FC1
1
2
3
11 21
12
22
13 23
BLK-1
BLK-2
BLK-3
BLK
YEL
BLU
BLK
YEL
BLU
FCB2/FB2
SEE NOTE 7
GRN/YEL
OFM2
1
2
3
BLK-1
BLK-2
BLK-3
OFM3
(055,060 ONLY)
(055,060 ONLY)
GRN/YEL
BLK
YEL
055,060: FAN CONTACTOR FC3 IS REPLACED WITH MOTORMASTER RELAY MMR..
208/230V ONLY
BLK
YEL
BLU
11
12
13
21
22
23
BLK
YEL
BLU
11
12
13
21
22
23
FB1
BLK
YEL
BLU
FB3
BLK
YEL
BLU
11
12
13
21
22
23
11
12
13
21
22
23
BLK
YEL
BLU
HIGH SCCR
ONLY
FB1
BLK
YEL
BLU
FB3
BLK
YEL
BLU
11
12
13
21
22
23
11
12
13
21
22
23
BLK
YEL
BLU
HIGH SCCR
ONLY
BLK
25
2
RED
FROM
AUX-J4
YEL
BLUBLK
FB2NONE
LP-CC-20575-3-60
LP-CC-20
380-3-60,460-3-60,575-3-60
NONE
208/230-3-60
KTK-R-15
380-3-60,460-3-60,575-3-60
NONE
KTK-R-20208/230-3-60
FB1
(NO MM)
FB1
(WITH MM)
LP-CC-20
380-3-60,460-3-60,575-3-60
NONE
208/230-3-60
FB3
3
3
2
2
1
1
J2
BRN
VIO
2
2
1
J1
1
3
3
MBB
BRN
RED
3
3
2
2
1
1
J2
2
J1
1
3
FIOP/ACCESSORY
EMM
BRN
RED
12
2
11
1
J1
DGS FIOP
AUX
2
1
3
2
1
UPC FIOP
UPC
GND
HOT
24VAC
BRN
VIO
42
86
BLK
YEL
COOLER/PUMP
HEATERS
(208/230,230V)
1
2
3
BLK
BLK
WHT
COOLER/PUMP
HEATERS
(380,460,575V)
3
2
BLK
BLK
~
~
~
~
WHT
~~
42
86
BLK
YEL
COOLER/PUMP
HEATERS
(208/230,230V)
1
2
3
BLK
BLK
WHT
COOLER/PUMP
HEATERS
(380,460,575V)
3
2
BLK
BLK
~
~
~
~
WHT
~~
VIO
BRN
BRN
BLU
31
240 1/4W
CHC
CHC
CHC
CHC
STANDARD
TERMINAL
BLOCK
PER NEC
TO FUSED DISCONNECT
21
22
23
TB1A
EQUIP GND
COMP A1
COMP B1
CSB-A1
CSB-A2
CSB-B1
CSB-B2
Fig. 7A — Typical Wiring Schematic, 30RAP035-060 Units — Power Wiring
a30-
5283
26
LEGEND
TERMINAL BLOCK
X
TERMINAL (UNMARKED)
TERMINAL (MARKED)
SPLICE
FACTORY WIRING
FIELD WIRING
ACCESSORY OR OPTION WIRING
TO INDICATE COMMON POTENTIAL
ONLY,NOT TO REPRESENT WIRING
X
9
9
7
7
8
8
4
6
4
6
RLY 9
5
5
1
3
1
3
RLY 11
2
2
A2A1
A2A1
ORN
3
12
1
10
2
11
4
13
MAX LOAD-5VA SEALED
10VA INRUSH
C
TB1
SW2
C2
A2
B2
9
18
10
19
8
17
11
12
13
14
20
21
22
23
6
15
7
16
5
14
15
16
17
18
24
25
26
27
5.2 AMPS
CB2
A2A1
PNK
A2A1
ACCSY ACCESSORY
ALMR ALARM RELAY
AUX AUXILIARY
BR BOILER RELAY
C CONTACTOR, COMPRESSOR
CB CIRCUIT BREAKER
CCB COMPRESSOR CIRCUIT BREAKER
CH CRANKCASE HEATER
CHC COOLER/PUMP HEATER CONTACTOR
CO CONVENIENCE OUTLET
COMP COMPRESSOR
CSB CURRENT SENSOR BOARD
CWFS CHILLED WATER FLOW SWITCH
CWP CHILLED WATER PUMP
CWPI CHILLED WATER PUMP INTERLOCK
DGS DIGITAL SCROLL
DLS DEMAND LIMIT SWITCH
DPT DISCHARGE PRESSURE TRANSDUCER
DTT DISCHARGE TEMPERATURE THERMISTOR
DUS DIGITAL UNLOADER SOLENOID
EMM ENERGY MANAGEMENT
EWT ENTERING WATER TEMPERATURE
EXV EXPANSION VALVE CONTROL BOARD
FB FUSE BLOCK
FC FAN CONTACTOR
FCB FAN CIRCUIT BREAKER
FIOP FACTORY INSTALLED OPTION
FR FAN RELAY
FU FUSE
GND GROUND
HPS HIGH PRESSURE SWITCH
HR HEAT RELAY
LVT LOW VOLTAGE TERMINAL
LWT LEAVING WATER TEMPERATURE
MBB MAIN BASE BOARD
MLV MINIMUM LOAD VALVE
MM MOTORMASTER
MMR MOTORMASTER RELAY
MP MODULAR MOTOR PROTECTOR
MS MANUAL STARTER
OAT OUTDOOR AIR THERMISTOR
OFM OUTDOOR FAN MOTOR
PL PLUG
R RELAY
RGT RETURN GAS TEMPERATURE
RLY RELAY
SAT SUPPLY AIR TEMPERATURE
SCCR SHORT CIRCUIT CURRENT RATING
SPT SUCTION PRESSURE TRANSDUCER
SW SWITCH
TB TERMINAL BLOCK
TNKR STORAGE TANK HEATER RELAY
TRAN TRANSFORMER
UPC UNITARY PROTOCOL CONVERTER
RLY 10
J10A
J10B
RLY 5
RLY 6
RLY 7
RLY 8
RLY 1
RLY 2
RLY 3
RLY 4
12
11
10
9
8
7
6
5
4
3
2
1
26
25
24
23
22
17
16
15
14
13
12
11
10
9
8
7
6
10
9
8
7
6
5
4
3
2
1
8
8
3
1
3
1
3
1
6
2
4
2
4
2
12
1
2
3
4
5
6
7
8
9
10
11
1
2
3
4
5
6
12
11
10
9
8
7
3
4
4
3
2
2
1
1
BLK
WHT
RED
J9
21
20
19
18
10
9
8
7
6
5
4
5
4
3
2
1
4
2
1
3
5
RED
BRN
RED
WHT
BLK
RED
WHT
BLK
6
6
5
5
3
3
2
1
1
2
7
7
4
4
J7
MARQUEE
DISPLAY
MAIN
BASE
BOARD
J8
9
9
10
10
6
5
4
3
2
1
6
5
4
3
2
1
J6
FIOP/
M1
M2
SEE NOTE 14
M1
M2
M1
M2
M1
M2
ORN
GRA
A2A1
ORN
A2A1
VIO
A2A1
PNK
FC2
FC1
CB1
CB2
CHC
CA1
CA2
ORN
ORN
7
TB4
RED
SEE NOTE 14
SEE NOTE 14
SEE NOTE 14
RED
RED
RED
RED
BLU
PNK
ORN
VIO
PNK
RED
ORN
ORN
GRA
VIO
J5
GRA
6
6
5
5
RED
BRN
J4
1
2
3
4
5
6
1
2
3
4
5
6
BLK
WHT
RED
BRN
RED
CSB
B2
2
3
1
RED
ORN
BRN
CSB
A2
2
3
1
RED
ORN
BRN
CSB
B1
2
3
1
RED
ORN
BRN
CSB
A1
2
3
1
RED
ORN
BRN
EXV
4
3
2
1
4
3
2
1
J3
4
3
2
1
4
3
2
1
J4
RED
WHT
BLK
RED
WHT
BLK
ON
OFF
12345678
DARK = SWITCH LOCATION
DUS
3
2
1
3
2
1
6
5
4
3
2
1
J9
2
1
8
7
2
1
8
7
J2
J6
DTT
RED
WHT
BLK
DGS OR
MM
FIOP
MBB
BLK
RED
LVT
4
3
22
23
T-55
ACCSY
SEN
12
11
10
9
8
7
6
5
4
3
2
1
12
11
10
9
8
7
J7
EMM
4
3
2
1
4
3
2
1
J3
4
3
2
1
4
3
2
1
J4
RED
WHT
BLK
RED
WHT
BLK
12
11
10
9
8
7
6
5
4
3
2
1
12
11
10
9
8
7
J6
14
13
14
13
ACCESSORY
1
1
2
3
4
5
6
1
2
3
4
5
6
10
7
8
9
8
6
7
4
5
9
2
3
10
+
-
COOLING
SETPOINT
4-20mA
LVT
8
1
3
2
5
4
7
6
(+)
(-)
(COM)
SHIELD
LEN CCN
1
2
3
1
2
3
4
5
NET +
NET 2
SHIELD
NET +
NET -
N/C
N/C
SIGNAL
PORT 1A
UPC
PORT 2
J3
1
2
LON
OPTION
GND
J4
NET
UPC OPT
BLK
WHT
RED
RED
BLK
WHT
RED
WHT
BLK
RED
BRN
RED
WHT
BLK
OAT
BLU
BLU
PNK
ORN
BRN
VIO
+
-
TEMP
RESET
4-20mA
+
-
DEMAND
LIMIT
4-20mA
LVT
2
1
24
25
ALM
R
LVT
1
18
C
TB1
BRN
MBB J1-2
T2T1MP-A1
T2T1MP-A2
T2T1MP-B1
T2T1MP-B2
SEE NOTE 10
SEE NOTE 11
SEE NOTE 12
SEE NOTE 13
3.2 AMPS
CB1
4
TB4
RED
RED
RED
BRN
UPC GND
BRN
CWFS 3
BRN
CB1
A2
BRN
LVT J12-5
BRN
CHC
A2
BRN
CA1
A2
BRN
TRAN1
SECONDARY 24V
RED
FU3
X1
XF
BRN
X2
GRN/YEL
5
TB4
RED
VIORED
PL50-1
BRNBLK
PL50-2
REDRED
PL50-3
BLKBLK
PL50-4
BLK
RED
RGTB
BLK
RED
RGTA
2
1
2
1
RED
BLK
J4
CH1
-
CH11
-
CH9
-
-
+
G
-
+
G
2
1
2
1
J5
CH10
-
TO MM-A
SEE NOTE 8
BLK
BLU
EXV-B
5
4
3
2
1
5
4
3
2
1
WHT
BLK
RED
GRN
PL-EXVB
EXV-A
5
4
3
2
1
5
4
3
2
1
WHT
BLK
RED
GRN
PL-EXVA
J7
J6
RED
RED
BLK
GRY
YEL
BLK
YEL
GRY
FIOP OR
FIELD INSTALLED
OPTION
VIO
RED
FIELD INSTALLED
MAX LOAD-5VA SEALED
10VA INRUSH
A2A1
CWP
1
A2A1
CWP
2
BRN
CWP1
A2
MLV-A
GRA
BRN
MLV ACCSY
FR4
2
4
FR3
2
4
FR2
2
4
TAN
TAN
PNK
FR1
2
4
TAN
PNK
PNK
A2A1
BRN
PNK
FC2
A2
FC3
(055,060 ONLY)
RED
RED
4
TB4
ORN
RED
ACCESSORY
STORAGE TANK
HEATER RELAY
TNK
R
BLK
ORN
BRN
C
TB1
BRN
CWP2
A2
BRN
C
TB1
BRN
CA1
A2
BRN
CA2
A2
BRN
C
TB1
BRN
CB1
A2
BRN
CB2
A2
BRN
C
TB1
BRN
CWP1
A2
BRN
FC2
A2
BRN
CA2
A2
BRN
FC1
A2
BRN
FC3
A2
14
15
4
3
12
13
6
5
11
RED
RED
BLU
BLU
DLS STEP 2
DLS STEP 1
LVT
16
17
2
1
GRA
GRA
ICE DONE
SPTB
-
+
DPTB
-
+
A
C
B
A
C
B
GRN
RED
BLK
GRN
RED
BLK
SPTA
-
+
DPTA
-
+
A
C
B
A
C
B
GRN
RED
BLK
GRN
RED
BLK
BLK
RED
EVAPORATOR ENTERING
FLUID TEMP
BLK
RED
EVAPORATOR LEAVING
FLUID TEMP
SPACE TEMPERATURE
ACCESSORY OR
DUAL CHILLER LWT
3
4
4
3
2
2
1
1
BLK
WHT
RED
J3
14
13
RED
CWP2
RED
14
13
VIO
CWP1
VIO
BRN
VIO
BR
HR
ALMR
HEAT/BOILER FIELD
INSTALLED WIRING
RED
C1
A1
B1
OFF
3
2
16
13
6
4
15
7
5
17
9
8
14
REMOTE
ON-OFF
SWITCH
(SEE NOTE
5)
ENABLE
SW1
LVT
ORN
12
11
13
11
14
CWFS
DUAL
SETPOINT
LVT
7
6
19
20
GRA
TAN
RED
RED
RED
GRA
GRA
SEE
NOTE 9
(055,060 ONLY)
(055,060 ONLY)
(055,060 ONLY)
(055,060 ONLY)
SEE NOTE 8
LVT
5
21
BRN
FR110
ORNBRN
(055,060 ONLY)
FR210
GRABRN
(055,060 ONLY)
FR310
VIOBRN
(055,060 ONLY)
FR410
PNKBRN
(055,060 ONLY)
MP-B1
VIO
VIO
PL2-2PL2-1
VIO
MP-A1
VIO
VIO
PL1-2PL1-1
VIO
MP-B2
VIO
VIO
PL2-6PL2-5
VIO
MP-A2
VIO
VIO
PL1-6PL1-5
VIO
BLU
BLK
BLK
HPS-B
J12 T55
J13
J1
J12
J11
PL1-3
RED
RED
PL1-4
BRN
BRN
PL1-7
RED
RED
PL2-3
RED
RED
PL2-7
RED
RED
PL1-8
BRN
BRN
PL2-4
BRN
BRN
PL2-8
BRN
BRN
BRN
GRA
GRA
BLK
BLK
BLK
HPS-A
J10
J11
BLK
4
WHT
2
J12
CWPI
HEAT
J12
AUX
Fig. 7B — Typical Wiring Schematic, 30RAP035-060 Units — Control Wiring
factory-installed option (FIOP) or field-installed accessory is
used for the following types of temperature reset, demand
limit, and/or ice features:
•4 to 20 mA leaving fluid temperature reset (requires
field-supplied 4 to 20 mA generator)
•4 to 20 mA cooling set point reset (requires fieldsupplied 4 to 20 mA generator)
•Discrete inputs for 2-step demand limit (requires fieldsupplied dry contacts capable of handling a 24 vac,
50 mA load)
•4 to 20 mA demand limit (requires field-supplied 4 to
20 mA generator)
•Discrete input for Ice Done switch (requires fieldsupplied dry contacts capable of handling a 24 vac,
50 mA load)
See Demand Limit and Temperature Reset sections on
pages 41 and 37 for further details.
CAUTION
Care should be taken when interfacing with other manufacturer’s control systems due to possible power supply
differences, full wave bridge versus half wave rectification.
The two different power supplies cannot be mixed.
ComfortLink™ controls use half wave rectification. A
signal isolation device should be utilized if a full wave
bridge signal generating device is used.
Loss-of-Cooler Flow Protection — A proof-of-
cooler flow device is factory installed in all chillers. It is recommended that proper operation of the switch be verified on a regular basis.
Electronic Expansion Valves (EXV) — All units are
equipped from the factory with EXVs. Each refrigeration circuit is also supplied with a factory-installed liquid line filter
drier and sight glass.
The EXV is set at the factory to maintain 9° F (5.0° C) suction superheat leaving the cooler by metering the proper
amount of refrigerant into the cooler. The superheat set point is
adjustable, but should not be adjusted unless absolutelynecessary.
The EXV is designed to limit the cooler saturated suction
temperature to 50 F (12.8 C). This makes it possible for unit to
start at high cooler fluid temperatures without overloading the
compressor.
Capacity Control — The control system cycles com-
pressors, digital scroll modulting solenoid (if equipped), and
minimum load valve solenoids (if equipped) to maintain the
user-configured leaving chilled fluid temperature set point. Entering fluid temperature is used by the main base board (MBB)
to determine the temperature drop across the cooler and is used
in determining the optimum time to add or subtract capacity
stages. The chilled fluid temperature set point can be automatically reset by the return fluid temperature, space, or outdoor-air
temperature reset features. It can also be reset from an external
4 to 20-mA signal (requires energy management module FIOP
or accessory).
The standard control has an automatic lead-lag feature built
in which determines the wear factor (combination of starts and
run hours) for each compressor. If all compressors are off and
less than 30 minutes has elapsed since the last compressor was
turned off, the wear factor is used to determine which
compressor to start next. If no compressors have been running
for more than 30 minutes and the leaving fluid temperature is
greater than the saturated condensing temperature, the wear
factor is still used to determine which compressor to start next.
If the leaving fluid temperature is less than the saturated condensing temperature, then the control will start either compressor A1 or compressor B1 first, depending on the user-configurable circuit lead-lag value. For units with the minimum load
control valve, the A circuit with the minimum load valve is always the lead circuit. The A circuit is also always the lead for
units with the digital compressor option. On units with the digital scroll option, the A1 compressor operates continuously,
providing close leaving chilled water control. For this reason,
on/off cycling of the unit’s compressors is dramatically reduced, which in turn reduces wear associated with compressor
start/stop cycles.
The EXVs will provide a controlled start-up. During startup, the low pressure logic will be bypassed for 2
allow for the transient changes during start-up. As additional
stages of compression are required, the processor control will
add them. See Table 19.
If a circuit is to be stopped, the compressor with the lowest
wear factor will be shut off first except when a digital compressor is used. The digital compressor is always the last compressor to shut off.
The capacity control algorithm runs every 30 seconds. The
algorithm attempts to maintain the Control Point at the desired
set point. Each time it runs, the control reads the entering and
leaving fluid temperatures. The control determines the rate at
which conditions are changing and calculates 2 variables based
on these conditions. Next, a capacity ratio is calculated using
the 2 variables to determine whether or not to make any
changes to the current stages of capacity. This ratio value
ranges from –100 to +100%. If the next stage of capacity is a
compressor, the control starts (stops) a compressor when the
ratio reaches +100% (–100%). If installed, the minimum load
valve solenoid will be energized with the first stage of capacity.
Minimum load valve value is a fixed 30% in the total capacity
calculation. The control will also use the minimum load valve
solenoid as the last stage of capacity before turning off the last
compressor. A delay of 90 seconds occurs after each capacity
step change. Refer to Table 19.
MINUTES LEFT FOR START — This value is displayed
only in the network display tables (using Service Tool,
ComfortVIEW™ or ComfortWORKS
represents the amount of time to elapse before the unit will start
its initialization routine. This value can be zero without the
machine running in many situations. This can include being
unoccupied, ENABLE/OFF/REMOTE CONTACT switch in
the OFF position, CCN not allowing unit to start, Demand
Limit in effect, no call for cooling due to no load, and alarm or
alert conditions present. If the machine should be running and
none of the above are true, a minimum off time (DELY, see
below) may be in effect. The machine should start normally
once the time limit has expired.
MINUTES OFF TIME (ConfigurationDELY) — This user-configurable time period is used by the
control to determine how long unit operation is delayed after
power is applied/restored to the unit. Typically, this time period
is configured when multiple machines are located on a single
site. For example, this gives the user the ability to prevent all
the units from restarting at once after a power failure. A value
of zero for this variable does not mean that the unit should be
running.
1
/2 minutes to
®
software) and
OPT2
29
CEBD430351-0396-01C
TEST 1
CEPL130351-01
PWR
TEST 2
J1
J2
J4J3
J5
J6
J7
LEN
STATUS
RED LED - STATUS
GREEN LED LEN (LOCAL EQUIPMENT NETWORK)
ADDRESS
DIP SWITCH
Fig. 12 — Energy Management Module
LEAD/LAG DETERMINATION — This is a configurable
choice and is factory set to be automatic for all units unless the
unit is equipped with a digital scroll compressor or minimum
load, then circuit A is lead (Configuration
The value can be changed to Circuit A or Circuit B leading as
desired. Set at automatic, the control will sum the current number of logged circuit starts and one-quarter of the current oper-
OPT2 LLCS).
ating hours for each circuit. The circuit with the lowest sum is
started first. Changes to which circuit is the lead circuit and
which is the lag are also made when total machine capacity is
at 100% or when there is a change in the direction of capacity
(increase or decrease) and each circuit’s capacity is equal.
CAPACITY CONTROL OVERRIDES — The following overrides will modify the normal operation of the routine.
Deadband Multiplier
Multiplier (Configuration
— The user configurable Deadband
SLCTZ.GN) has a default val-
ue of 1.0. The range is from 1.0 to 4.0. When set to other than
1.0, this factor is applied to the capacity Load/Unload Factor.
The larger this value is set, the longer the control will delay between adding or removing stages of capacity. Figure 13 shows
how compressor starts can be reduced over time if the leaving
water temperature is allowed to drift a larger amount above and
below the set point. This value should be set in the range of 3.0
to 4.0 for systems with small loop volumes.
First Stage Override
the control will modify the routine with a 1.2 factor on adding
— If the current capacity stage is zero,
the first stage to reduce cycling. This factor is also applied
when the control is attempting to remove the last stage of
capacity.
Slow Change Override
— The control prevents the capacity
stages from being changed when the leaving fluid temperature
is close to the set point (within an adjustable deadband) and
moving towards the set point.
Ramp Loading
tion
SLCTCRMP) limits the rate of change of leaving
fluid temperature. If the unit is in a Cooling mode and config-
— Ramp loading (Configura-
ured for Ramp Loading, the control makes 2 comparisons before deciding to change stages of capacity. The control calculates a temperature difference between the control point and
leaving fluid temperature. If the difference is greater than 4° F
(2.2° C) and the rate of change (°F or °C per minute) is more
than the configured Cooling Ramp Loading value (CRMP),
the control does not allow any changes to the current stage of
capacity.
Low Entering Fluid Temperature Unloading
— When the
entering fluid temperature is below the control point, the
control will attempt to remove 25% of the current stages being
used. If exactly 25% cannot be removed, the control removes
an amount greater than 25% but no more than necessary. The
lowest stage will not be removed.
Minimum Load Control
control valve is energized only when one compressor is running on circuit A. If the close control feature is enabled the
— If equipped, the minimum load
minimum load control valve may be used as needed to obtain
leaving fluid temperature close to set point.
30
Loading...
+ 94 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.