Carrier 30RAP010-060 User Manual 2

Page 1
30RAP010-060
AQUASNAP® Air-Cooled Chillers
with COMFORTLINK™ Controls
Controls, Start-Up, Operation,
Service, and Troubleshooting
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . .2
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Basic Controls Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
CONTROLS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-44
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Main Base Board (MBB) . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Current Sensor Board (CSB) . . . . . . . . . . . . . . . . . . . . . . .19
AUX Board (AUX) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Expansion Valve Board (EXV) . . . . . . . . . . . . . . . . . . . . . .19
Emergency On/Off Switch . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Board Addresses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Control Module Communication . . . . . . . . . . . . . . . . . . . . 19
Carrier Comfort Network
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
• COOLER LEAVING FLUID SENSOR
• COOLER ENTERING FLUID SENSOR
• COMPRESSOR RETURN GAS TEMPERATURE SENSOR
• OUTDOOR-AIR TEMPERATURE SENSOR (OAT)
• DISCHARGE TEMPERATURE THERMISTOR (DTT)
• REMOTE SPACE TEMPERATURE SENSOR OR DUAL LEAVING WATER TEMPERATURE SENSOR
Energy Management Module . . . . . . . . . . . . . . . . . . . . . . .29
Loss-of-Cooler Flow Protection. . . . . . . . . . . . . . . . . . . . .29
Capacity Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
• MINUTES LEFT FOR START
• MINUTES OFF TIME
• LEAD/LAG DETERMINATION
• CAPACITY CONTROL OVERRIDES
Head Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Operation of Machine Based on Control Method
and Cooling Set Point Selection Settings. . . . . . . . .32
Cooling Set Point Select. . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Low Sound Mode Operation . . . . . . . . . . . . . . . . . . . . . . . .34
Heating Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Service Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Optional Factory-Installed Hydronic Package. . . . . . .34
Cooler Pump Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Cooler Pump Sequence of Operation . . . . . . . . . . . . . . .35
Configuring and Operating Dual Chiller Control . . . . 36
Temperature Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Demand Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
• DEMAND LIMIT (2-Stage Switch Controlled)
• EXTERNALLY POWERED DEMAND LIMIT
(4 to 20 mA Controlled)
• DEMAND LIMIT (CCN Loadshed Controlled)
Cooling Set Point (4 to 20 mA). . . . . . . . . . . . . . . . . . . . . .43
Digital Scroll Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
• DIGITAL SCROLL OPERATION
• DIGITAL COMPRESSOR CONFIGURATION
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44,45
®
(CCN) Interface . . . . . . . . . . 19
System Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Actual Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Check Refrigerant Charge. . . . . . . . . . . . . . . . . . . . . . . . . 45
Operating Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
• TEMPERATURES
• LOW AMBIENT OPERATION
• VOLTAGE — ALL UNITS
OPERATION SEQUENCE . . . . . . . . . . . . . . . . . . . . . .46,47
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47-63
Page
Electronic Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
• CONTROL COMPONENTS
Electronic Expansion Valve (EXV) . . . . . . . . . . . . . . . 47
EXV Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . 47
• FIELD SERVICING INSTRUCTIONS
• VALVE REPLACEMENT
• VALVE REASSEMBLY
Compressor Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . 49
Cooler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
• BRAZED-PLATE COOLER HEAT EXCHANGER REPLACEMENT
• BRAZED-PLATE COOLER HEAT EXCHANGER CLEANING
Oil Charge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Microchannel Heat Exchanger (MCHX) Condenser Coil Maintenance and Cleaning
Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Check Refrigerant Feed Components . . . . . . . . . . . . . . 50
•FILTER DRIER
• MOISTURE-LIQUID INDICATOR
• MINIMUM LOAD VALVE
• PRESSURE RELIEF DEVICES
Check Unit Safeties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
• HIGH-PRESSURE SWITCH
• PRESSURE TRANSDUCERS
• COOLER FREEZE-UP PROTECTION
• HEATER CABLE
• WINTER SHUTDOWN
Thermistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Pressure Transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Chilled Water Flow Switch. . . . . . . . . . . . . . . . . . . . . . . . . . 53
Strainer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Condenser Fans. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Motormaster
• GENERAL OPERATION
• CONFIGURATION
• DRIVE PROGRAMMING
•EPM CHIP
• LOSS OF CCN COMMUNICATIONS
• REPLACING DEFECTIVE MODULES
Hydronic Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63,64
Recommended Maintenance Schedule . . . . . . . . . . . . . 63
Microchannel Heat Exchanger (MCHX) Condenser Coil Maintenance and Cleaning
Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . 64-73
®
V Controller . . . . . . . . . . . . . . . . . . . . . . . . . 58
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300067-01 Printed in U.S.A. Form 30RAP-2T Pg 1 12-10 Replaces: 30RAP-1T
Page 2
CONTENTS (cont)
Complete Unit Stoppage and Restart . . . . . . . . . . . . . . 64
• GENERAL POWER FAILURE
• UNIT ENABLE-OFF-REMOTE CONTACT SWITCH IS OFF
• CHILLED FLUID PROOF-OF-FLOW SWITCH OPEN
• OPEN 24-V CONTROL CIRCUIT BREAKERS
• COOLING LOAD SATISFIED
• THERMISTOR FAILURE
• LOW SATURATED SUCTION
• COMPRESSOR SAFETIES
Alarms and Alerts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
APPENDIX A — DISPLAY TABLES . . . . . . . . . . . . . . 74-89
APPENDIX B — CCN TABLES . . . . . . . . . . . . . . . . . . 90-100
APPENDIX C — FACTORY SETTINGS FOR
PUMP AND MANUAL STARTERS. . . . . . . . . . . . . . . . 101
APPENDIX D — OPTIONAL BACNET
COMMUNICATONS WIRING . . . . . . . . . . . . . . . . . 102-109
APPENDIX E — MAINTENANCE SUMMARY
AND LOG SHEETS . . . . . . . . . . . . . . . . . . . . . . . . . . 110-113
START-UP CHECKLIST FOR 30RAP LIQUID
CHILLER
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1 to CL-10
Page
WARNING
DO NOT attempt to unbraze factory joints when servicing this equipment. Compressor oil is flammable and there is no way to detect how much oil may be in any of the refrigerant lines. Cut lines with a tubing cutter as required when performing service. Use a pan to catch any oil that may come out of the lines and as a gage for how much oil to add to system. DO NOT re-use compressor oil.
CAUTION
This unit uses a microprocessor-based electronic control system. Do not use jumpers or other tools to short out components, or to bypass or otherwise depart from recom­mended procedures. Any short-to-ground of the control board or accompanying wiring may destroy the electronic modules or electrical components.
CAUTION
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be
hazardous due to system pressures, electrical components, and equipment location (roof, elevated structures, mechanical rooms, etc.). Only trained, qualified installers and service mechanics should install, start up, and service this equipment.
When working on this equipment, observe precautions in
the literature, and on tags, stickers, and labels attached to the equipment, and any other safety precautions that apply. Follow all safety codes. Wear safety glasses and work gloves. Use care in handling, rigging, and setting this equipment, and in handling all electrical components.
WARNING
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation. There may be more than one disconnect switch. Tag all discon­nect locations to alert others not to restore power until work is completed.
WARNING
DO NOT VENT refrigerant relief valves within a building. Outlet from relief valves must be vented outdoors in accordance with the latest edition of ANSI/ASHRAE (American National Standards Institute/American Society of Heating, Refrigeration and Air Conditioning Engineers) 15 (Safety Code for Mechanical Refrigeration). The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation. Provide adequate ventilation in enclosed or low overhead areas. Inhalation of high concentrations of vapor is harmful and may cause heart irregularities, unconsciousness or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products are hazardous.
To prevent potential damage to heat exchanger, always run fluid through heat exchanger when adding or removing refrigerant charge. Use appropriate brine solutions in cooler fluid loop to prevent the freezing of brazed plate heat exchanger, optional hydronic section and/or interconnecting piping when the equipment is exposed to temperatures below 32 F (0 °C). Proof of flow switch and strainer are factory installed on all models. Do NOT remove power from this chiller during winter shutdown periods without taking precaution to remove all water from heat exchanger and optional hydronic system. Failure to properly protect the system from freezing may constitute abuse and may void warranty.
CAUTION
Compressors and optional hydronic system pumps require specific rotation. Test condenser fan(s) first to ensure proper phasing. Swap any two incoming power leads to correct condenser fan rotation before starting any other motors.
CAUTION
Refrigerant charge must be removed slowly to prevent loss of compressor oil that could result in compressor failure.
CAUTION
Puron® refrigerant (R-410A) systems operate at higher pressures than standard R-22 systems. Do not use R-22 ser­vice equipment or components on Puron refrigerant equip­ment. If service equipment is not rated for Puron refrigerant, equipment damage or personal injury may result.
2
Page 3
ENTER
ESCAPE
ENTER
ENTER
ESCAPE
ESCAPE
ENTER
ESCAPE
ENTER
ESCAPE
ESCAPE
ENTER
ENTER
ENTER
Run Status
Service Test
Temperature
Pressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
Operating Modes
Alarms
Alarm Status
ENTER
MODE
ESCAPE
Fig. 1 — Scrolling Marquee Display
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
GENERAL
This publication contains Controls, Start-Up, Operation, Service, and Troubleshooting information for the 30RAP AquaSnap
®
air-cooled chillers. See Table 1. These chillers are equipped with ComfortLink™ controls and electronic expan­sion valves (EXVs).
WARNING
This unit uses a microprocessor-based electronic control system. Do not use jumpers or other tools to short out or bypass components or otherwise depart from recom­mended procedures. Any short-to-ground of the control board or accompanying wiring may destroy the board or electrical component.
Table 1 — Unit Sizes
UNIT NOMINAL CAPACITY (TONS) 30RAP010 10 30RAP015 14 30RAP018 16 30RAP020 19 30RAP025 24 30RAP030 28 30RAP035 34 30RAP040 39 30RAP045 43 30RAP050 48 30RAP055 53 30RAP060 56
Conventions Used in This Manual — The follow-
ing conventions for discussing configuration points for the local display (scrolling marquee or Navigator™ accessory) will be used in this manual.
Point names will be written with the mode name first, then any sub-modes, then the point name, each separated by an arrow symbol (. Names will also be shown in bold and italics. As an example, the Lead/Lag Circuit Select Point, which is located in the Configuration mode, Option sub-mode, would be written as Configuration OPTNLLCS.
This path name will show the user how to navigate through the local display to reach the desired configuration. The user would scroll through the modes and sub-modes using the
and keys. The arrow symbol in the path name repre­sents pressing to move into the next level of the menu structure.
When a value is included as part of the path name, it will be shown at the end of the path name after an equals sign. If the value represents a configuration setting, an explanation will be shown in parenthesis after the value. As an example, ConfigurationOPTNLLCS = 1 (Circuit A leads).
Pressing the and keys simultaneously will scroll an expanded text description of the point name or value across the display. The expanded description is shown in the local display tables but will not be shown with the path names in text.
®
The CCN (Carrier Comfort Network
) point names are also referenced in the local display tables for users configuring the unit with CCN software instead of the local display. The CCN tables are located in Appendix B of the manual.
Basic Controls Usage
SCROLLING MARQUEE DISPLAY — The scrolling mar­quee display is the standard interface display to the ComfortLink
Control System for 30RAP units. The display has up and down arrow keys, an key, and an key. These keys are used to navigate through the different levels of the display structure. Press the key until the highest operating level is displayed to move through the top 11 mode levels indicated by LEDs on the left side of the display. See Fig. 1 and Tables 2-14.
Once within a mode or sub-mode, pressing the and keys simultaneously will put the scrolling marquee display into expanded text mode where the full mean­ing of all sub-modes, items and their values can be displayed for the current selection. Press the and keys to return the scrolling marquee display to its default menu of rotating display items (those items in Run Status In addition, the password will be disabled, requiring that it be entered again before changes can be made to password protect­ed items. Press the key to exit out of the expanded text mode.
NOTE: When the Language Selection (Configuration DISPLANG), variable is changed, all appropriate display expansions will immediately change to the new language. No power-off or control reset is required when reconfiguring languages.
When a specific item is located, the item name alternates with the value. Press the key at a changeable item and the value will be displayed. Press again and the value will begin to flash indicating that the value can be changed. Use the up and down arrow keys to change the value, and confirm the value by pressing the key.
Changing item values or testing outputs is accomplished in the same manner. Locate and display the desired item. Press
so that the item value flashes. Use the arrow keys to change the value or state and press the key to accept it. Press the key to return to the next higher level of structure. Repeat the process as required for other items.
Items in the Configuration and Service Test modes are pass­word protected. The words ‘PASS’ and ‘WORD’ will alternate on the display when required. The default password is 0111. Press and the 1111 password will be displayed. Press
again and the first digit will begin to flash. Use the arrow keys to change the number and press to accept the digit. Continue with the remaining digits of the password. The password can only be changed through CCN operator in-
®
terface software such as ComfortWORKS
, ComfortVIEW™
and Service Tool.
See Tables 2-14 and Appendix A for further details.
3
VIEW).
Page 4
ACCESSORY NAVIGATOR™ DISPLAY MODULE —
ENTER
ESCAPE
ESCAPE
ENTER
ESCAPE
ENTER
ESCAPE
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
Fig. 2 — Accessory Navigator™ Display Module
The Navigator module provides a mobile user interface to the ComfortLink™ control system, which is only available as a field-installed accessory. The display has up and down arrow keys, an key, and an key. These keys are used to navigate through the different levels of the display structure. Press the key until ‘Select a Menu Item’ is displayed to move through the top 11 mode levels indicated by LEDs on the left side of the display. See Fig. 2.
Once within a Mode or sub-mode, a “>” indicates the cur-
rently selected item on the display screen. Pressing the
and keys simultaneously will put the Nav­igator module into expanded text mode where the full meaning of all sub-modes, items and their values can be displayed. Press­ing the and keys when the display says ‘Select Menu Item’ (Mode LED level) will return the Navigator module to its default menu of rotating display items (those items
in Run Status
VIEW). In addition, the password will be dis-
abled, requiring that it be entered again before changes can be made to password protected items. Press the key to exit out of the expanded text mode.
NOTE: When the Language Selection (Configuration
DISPLANG), variable is changed, all appropriate display expansions will immediately change to the new language. No power-off or control reset is required when reconfiguring languages.
When a specific item is located, the item name appears on the left of the display, the value will appear near the middle of the display and the units (if any) will appear on the far right of the display. Press the key at a changeable item and the val­ue will begin to flash. Use the up and down arrow keys to change the value, and confirm the value by pressing the key.
Changing item values or testing outputs is accomplished in the same manner. Locate and display the desired item. Press
so that the item value flashes. Use the arrow keys to change the value or state and press the key to accept it. Press the key to return to the next higher level of structure. Repeat the process as required for other items.
Items in the Configuration and Service Test modes are pass­word protected. The words Enter Password will be displayed when required, with 1111 also being displayed. The default password is 1111. Use the arrow keys to change the number and press to enter the digit. Continue with the re­maining digits of the password. The password can only be changed through CCN operator interface software such as ComfortWORKS, ComfortVIEW and Service Tool.
Adjusting the Contrast
— The contrast of the display can be
adjusted to suit ambient conditions. To adjust the contrast of
the Navigator module, press the key until the dis­play reads, “Select a menu item.” Using the arrow keys move to the Configuration mode. Press to obtain access to this mode. The display will read:
> TEST OFF METR OFF LANG ENGLISH
Pressing will cause the “OFF” to flash. Use the up or down arrow to change “OFF” to “ON”. Pressing will illuminate all LEDs and display all pixels in the view screen. Pressing and simultaneously allows the user to adjust the display contrast. Use the up or down arrows to adjust the contrast. The screen’s contrast will change with the adjustment. Press to accept the change. The Navigator module will keep this setting as long as it is plugged in to the LEN bus.
Adjusting the Backlight Brightness
— The backlight of the display can be adjusted to suit ambient conditions. The factory default is set to the highest level. To adjust the backlight of the Navigator module, press the key until the display reads, “Select a menu item.” Using the arrow keys move to the Configuration mode. Press to obtain access to this mode. The display will read:
> TEST OFF METR OFF LANG ENGLISH
Pressing will cause the “OFF” to flash. Use the up
or down arrow keys to change “OFF” to “ON”. Pressing
will illuminate all LEDs and display all pixels in the view screen. Pressing the up and down arrow keys simultane­ously allows the user to adjust the display brightness. Use the up or down arrow keys to adjust screen brightness. Press
to accept the change. The Navigator module will keep this setting as long as it is plugged in to the LEN bus.
ComfortLink
MODE
Alarm Status
Run Status
Service Test
Temperatures
Pressure
s
Setpoints
Inputs
Outputs
Configuration
Time Clock
ESC
Operating Modes
Alarms
ENTER
4
Page 5
Table 2 — Scrolling Marquee Display Menu Structure*
MODE
SUB-MODE
RUN
STATUS
Auto
View of
Run Status
(VIEW)
Unit Run
Hour and
Start
(RUN)
Compressor
Run Hours
(HOUR)
Compressor
Starts
(STRT)
Preventive
Maintenance
(PM)
Software
Ver si on (VERS)
LEGEND Ckt — Circuit *Throughout this text, the location of items in the menu structure will be
described in the following format: Item Expansion (Mode Name For example, using the language selection item: Language Selection (Configuration
SERVICE
TEST
Service
Te s t M o d e
(TEST)
Outputs
and Pumps
(OUTS)
Ciruit A Comp
Te st
(CMPA)
Ciruit B Comp
Test
(CMPB)
TEMPERATURES PRESSURES
Ent and Leave Unit
Temperatures
Temperatures
Sub-mode NameITEM)
DISPLANG)
Te mp s (UNIT)
Ckt A
(CIR.A)
Ckt B
(CIR.B)
Pressures
Ckt A
(PRC.A)
Pressures
Ckt B
(PRC.B)
SET
POINTS
Cooling
Setpoints
(COOL)
Head
Pressure
Setpoint
(HEAD)
Brine
Freeze
Setpoint
(FRZ)
INPUTS OUTPUTS CONFIGURATION
General
Inputs
(GEN.I)
Circuit Inputs
(CRCT)
4-20mA
Inputs (4-20)
General Outputs
(GEN.O)
Outputs
Circuit A
EXV
(A.EXV) Outputs
Circuit B
EXV
(B.EXV)
Outputs
Circuit A
(CIR.A)
Outputs
Circuit B
(CIR.B)
Display
Configuration
(DISP)
Unit
Configuration
(UNIT)
Unit Options 1
Hardware
(OPT1)
Unit Options 2
Controls
(OPT2)
CCN Network Configuration
(CCN)
Head Pressure
Comp. Delta
(HP.A)
Head Pressure
Comp. Delta
(HP.B)
Cir. A EXV
Configuration
(EXV.A)
Cir. B EXV
Configuration
(EXV.B)
Motormaster
Configuration
(MM)
Reset Cool Temp
(RSET)
Set Point and
Ramp Load
(SLCT) Service
Configuration
(SERV)
Broadcast
Configuration
(BCST)
TIME
CLOCK
Time of
Day
(TIME)
Month,
Date, Day,
and Year
(DATE)
Daylight Savings
Time
(DST)
Local
Holiday
Schedules
(HOL.L)
Local Occu­pancy
Schedule
(SCH.L)
Schedule
Override
(OVR)
OPERATING
MODES
Modes
(MODE)
ALARMS
Current (CRNT)
Reset
Alarms
(RCRN)
Alarm
History
(HIST)
5
Page 6
Table 3 — Run Status Mode and Sub-Mode Directory
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY SUB-ITEM DISPLAY SUB-ITEM DISPLAY
VIEW EWT XXX.X F ENTERING FLUID TEMP
LWT XXX.X F LEAVING FLUID TEMP
SETP XXX.X F ACTIVE SETPOINT
CTPT XXX.X F CONTROL POINT
LOD.F XXX LOAD/UNLOAD FACTOR
STAT X CONTROL MODE 0 = Service Test
LD.PM LEAD PUMP
OCC YES/NO OCCUPIED
LS.AC YES/NO LOW SOUND ACTIVE
MODE YES/NO OVERRIDE MODES IN EFFECT
CAP XXX % PERCENT TOTAL CAPACITY
STGE X REQUESTED STAGE
ALRM XXX CURRENT ALARMS & ALERTS
TIME XX.XX TIME OF DAY 00.00-23.59
ITEM
EXPANSION
COMMENT
1 = Off Local
2 = Off CCN
3 = Off Time
4 = Off Emrgcy
5 = On Local
6 = On CCN
7 = On Time
8 = Ht Enabled
9 = Pump Delay
MNTH XX MONTH OF YEAR 1 = January, 2 = February, etc.
DATE XX DAY OF MONTH 01-31
YEAR XX YEAR OF CENTURY
RUN HRS.U XXXX HRS MACHINE OPERATING HOURS
STR.U XXXX MACHINE STARTS
HR.P1 XXXX.X PUMP 1 RUN HOURS
HR.P2 XXXX.X PUMP 2 RUN HOURS
HOUR HRS.A XXXX HRS CIRCUIT A RUN HOURS
HRS.B XXXX HRS CIRCUIT B RUN HOURS See Note
HR.A1 XXXX HRS COMPRESSOR A1 RUN HOURS
HR.A2 XXXX HRS COMPRESSOR A2 RUN HOURS
HR.B1 XXXX HRS COMPRESSOR B1 RUN HOURS See Note
HR.B2 XXXX HRS COMPRESSOR B2 RUN HOURS See Note
STRT ST.A1 XXXX COMPRESSOR A1 STARTS
ST.A2 XXXX COMPRESSOR A2 STARTS
ST.B1 XXXX COMPRESSOR B1 STARTS See Note
ST.B2 XXXX COMPRESSOR B2 STARTS See Note
PM PUMP PUMP MAINTENANCE
SI.PM XXXX HRS PUMP SERVICE INTERVAL Default: 8760
P.1.DN XXXX HRS PUMP 1 SERVICE COUNTDOWN
P.2.DN XXXX HRS PUMP 2 SERVICE COUNTDOWN
P.1.MN YES/NO PUMP 1 MAINTENANCE DONE User Entry
P.2.MN YES/NO PUMP 2 MAINTENANCE DONE User Entry
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
6
Page 7
Table 3 — Run Status Mode and Sub-Mode Directory (cont)
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ESCAPE
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY SUB-ITEM DISPLAY SUB-ITEM DISPLAY
PM (cont) PMDT PUMP MAINTENANCE DATES
P.1.M0 MM/DD/YY HH:MM
P.1.M1 MM/DD/YY HH:MM
P.1.M2 MM/DD/YY HH:MM
P.1.M3 MM/DD/YY HH:MM
P.1.M4 MM/DD/YY HH:MM
P.2.M0 MM/DD/YY HH:MM
P.2.M1 MM/DD/YY HH:MM
P.2.M2 MM/DD/YY HH:MM
P.2.M3 MM/DD/YY HH:MM
P.2.M4 MM/DD/YY HH:MM
STRN STRAINER MAINTENANCE
SI.ST XXXX HRS STRAINER SRVC INTERVAL Default: 8760
S.T.DN XXXX HRS STRAINER SRVC COUNTDOWN
S.T.MN YES/NO STRAINER MAINT. DONE User Entry
ST.DT STRAINER MAINT. DATES
S.T.M0 MM/DD/YY HH:MM
ITEM
EXPANSION
COMMENT
S.T.M1 MM/DD/YY HH:MM
S.T.M2 MM/DD/YY HH:MM
S.T.M3 MM/DD/YY HH:MM
S.T.M4 MM/DD/YY HH:MM
COIL COIL MAINTENANCE
SI.CL XXXX HRS COIL SRVC INTER Default: 8760
C.L.DN XXXX HRS COIL SERVICE COUNTDOWN
C.L.MN YES/NO COIL MAINT. DONE User Entry
CL.DT COIL MAINTENANCE DATES
C.L.M0 MM/DD/YY HH:MM
C.L.M1 MM/DD/YY HH:MM
C.L.M2 MM/DD/YY HH:MM
C.L.M3 MM/DD/YY HH:MM
C.L.M4 MM/DD/YY HH:MM
VERS MBB CESR131460-xx-xx xx-xx is Version number*
EXV CESR131172-xx-xx xx-xx is Version number*
AUX1 CESR131333-xx-xx xx-xx is Version number*
EMM CESR131174-xx-xx xx-xx is Version number*
MARQ CESR131171-xx-xx xx-xx is Version number*
NAVI CESR130227-xx-xx xx-xx is Version number*
*Press and simultaneously to obtain version number.
7
Page 8
Table 4 — Service Test Mode and Sub-Mode Directory
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
TEST ON/OFF SERVICE TEST MODE To Enable Service Test Mode,
OUTS OUTPUTS AND PUMPS
EXV.A 0 to 100% EXV A % OPEN
EXV.B 0 to 100% EXV B % OPEN
FAN 1 ON / OFF FAN 1 REL AY
FAN 2 ON / OFF FAN 2 REL AY
FAN 3 ON / OFF FAN 3 REL AY
FAN 4 ON / OFF FAN 4 REL AY
FAN 5 ON / OFF FAN 5 REL AY
FAN 6 ON / OFF FAN 6 REL AY
V.HPA 0 to 100% VAR HEAD PRESS %
V.HPB 0 to 100% VAR HEAD PRESS %
CLP.1 ON/OFF COOLER PUMP 1 RELAY
CLP.2 ON/OFF COOLER PUMP 2 RELAY
UL.TM 0 to 15 COMP A1 UNLOAD TIME
CL.HT ON/OFF COOLER/PUMP HEATER
ITEM
EXPANSION
COMMENT
move Enable/Off/Remote Contact switch to OFF. Change TEST to ON. Move switch to ENABLE.
RMT.A ON/OFF REMOTE ALARM RELAY
CMPA CIRCUIT A COMPRESSOR TEST
CC.A1 ON/OFF COMPRESSOR A1 RELAY
UL.TM 0 to 15 COMP A1 UNLOAD TIME
CC.A2 ON/OFF COMPRESSOR A2 RELAY
CC.A3 ON/OFF COMPRESSOR A3 RELAY
CC.A4 ON/OFF COMPRESSOR A4 RELAY
MLV ON/OFF MINIMUM LOAD VALVE RELAY
CMPB CIRCUIT B COMPRESSOR TEST See Note
CC.B1 ON/OFF COMPRESSOR B1 RELAY
CC.B2 ON/OFF COMPRESSOR B2 RELAY
CC.B3 ON/OFF COMPRESSOR B3 RELAY
CC.B4 ON/OFF COMPRESSOR B4 RELAY
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
8
Page 9
Table 5 — Temperature Mode and Sub-Mode Directory
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
UNIT ENT AND LEAVE UNIT TEMPS
CEWT XXX.X F COOLER ENTERING FLUID
CLWT XXX.X F COOLER LEAVING FLUID
OAT XXX.X F OUTSIDE AIR TEMPERATURE
SPT XXX.X F SPACE TEMPERATURE
DLWT XXX.X F LEAD/LAG LEAVING FLUID
CIR.A TEMPERATURES CIRCUIT A
SCT.A XXX.X F SATURATED CONDENSING TMP
SST.A XXX.X F SATURATED SUCTION TEMP
RGT.A XXX.X F COMPR RETURN GAS TEMP
D.G AS XXX.X F DISCHARGE GAS TEMP
SH.A XXX.X ^F SUCTION SUPERHEAT TEMP
CIR.B TEMPERATURES CIRCUIT B See Note
SCT.B XXX.X F SATURATED CONDENSING TMP See Note
SST.B XXX.X F SATURATED SUCTION TEMP See Note
RGT.B XXX.X F COMPR RETURN GAS TEMP See Note
SH.B XXX.X ^F SUCTION SUPERHEAT TEMP See Note
ITEM
EXPANSION
COMMENT
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
Table 6 — Pressure Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
PRC.A PRESSURES CIRCUIT A
DP.A XXX.X PSIG DISCHARGE PRESSURE
SP.A XXX.X PSIG SUCTION PRESSURE
PRC.B PRESSURES CIRCUIT B See Note
DP.B XXX.X PSIG DISCHARGE PRESSURE See Note
SP.B XXX.X PSIG SUCTION PRESSURE See Note
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
ITEM
EXPANSION
Table 7 — Set Points Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
COOL COOLING SETPOINTS
CSP.1 XXX.X
F COOLING SETPOINT 1 Default: 44 F
CSP.2 XXX.X F COOLING SETPOINT 2 Default: 44 F
CSP.3 XXX.X F ICE SETPOINT Default: 32 F
HEAD HEAD PRESSURE SETPOINTS
H.DP XXX.X F HEAD SETPOINT Default: 95 F
F. O N XXX.X F FAN ON SETPOINT Default: 95 F
F. O F F XXX.X F FAN OFF SETPOINT Default: 72 F
ITEM
EXPANSION
COMMENT
COMMENT
B.OFF XXX.X F BASE FAN OFF DELTA TEMP Default: 23 F
F. D LT XXX.X F FAN STAGE DELTA Default: 15 F
FRZ BRINE FREEZE SETPOINT
BR.FZ XXX.X F BRINE FREEZE POINT Default: 34 F
9
Page 10
Table 8 — Inputs Mode and Sub-Mode Directory
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
GEN.I GENERAL INPUTS
STST STRT/STOP START/STOP SWITCH
FLOW ON/OFF COOLER FLOW SWITCH
PM.F.1 OPEN/CLSE COOLER PUMP 1 INTERLOCK
PM.F.2 OPEN/CLSE COOLER PUMP 2 INTERLOCK
HT.RQ ON/OFF HEAT REQUEST
DLS1 ON/OFF DEMAND LIMIT SWITCH 1
DLS2 ON/OFF DEMAND LIMIT SWITCH 2
ICED ON/OFF ICE DONE
DUAL ON/OFF DUAL SETPOINT SWITCH
CRCT CIRCUITS INPUTS
FKA1 ON/OFF COMPRESSOR A1 FEEDBACK
FKA2 ON/OFF COMPRESSOR A2 FEEDBACK
FKA3 ON/OFF COMPRESSOR A3 FEEDBACK
FKA4 ON/OFF COMPRESSOR A4 FEEDBACK
FKB1 ON/OFF COMPRESSOR B1 FEEDBACK See Note
FKB2 ON/OFF COMPRESSOR B2 FEEDBACK See Note
FKB3 ON/OFF COMPRESSOR B3 FEEDBACK See Note
ITEM
EXPANSION
COMMENT
FKB4 ON/OFF COMPRESSOR B4 FEEDBACK See Note
4-20 4-20 MA INPUTS
DMND XX.X MA 4-20 MA DEMAND SIGNAL
RSET XX.X MA 4-20 MA RESET SIGNAL
CSP XX.X MA 4-20 MA COOLING SETPOINT
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
Table 9 — Outputs Mode and Sub-Mode Directory
SUB-MODE
GEN.O GENERAL OUTPUTS
KEYPAD
ENTRY
ITEM DISPLAY
FAN1 ON/OFF FAN 1 RELAY
FAN2 ON/OFF FAN 2 RELAY
FAN3 ON/OFF FAN 3 RELAY
FAN4 ON/OFF FAN 4 RELAY
FAN5 ON/OFF FAN 5 RELAY
FAN6 ON/OFF FAN 6 RELAY
V.HPA ON/OFF FAN SPEED CIRCUIT A
V.HPB ON/OFF FAN SPEED CIRCUIT B
C.WP1 ON/OFF COOLER PUMP RELAY 1
C.WP2 ON/OFF COOLER PUMP RELAY 2
CLHT ON/OFF COOLER/PUMP HEATER
MLV.R ON/OFF MINIMUM LOAD VALVE RELAY
ITEM
EXPANSION
COMMENT
10
Page 11
Table 9 — Outputs Mode and Sub-Mode Directory (cont)
ENTER
ENTER
ENTER
ENTER
ENTER
SUB-MODE
A.EXV OUTPUTS CIRCUIT A EXV
B.EXV OUTPUTS CIRCUIT B EXV
CIR.A OUTPUTS CIRCUIT A
CIR.B OUTPUTS CIRCUIT B (See Note)
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
KEYPAD
ENTRY
ITEM DISPLAY
EXV.A 0 to 100% EXV % OPEN
APPR ON/OFF CIRCUIT A APPROACH
AP.SP APPROACH SETPOINT
X.SH.R SH RESET AT MAX UNL-DIG
S.SH.R DIGLOAD TO START SH RST
SH_R AMOUNT OF SH RESET
OVR.A EXVA OVERRIDE
SPH.A SUCTION SUPERHEAT TEMP
ASH.S ACTIVE SUPERHEAT SETPT
AMP.S ACTIVE MOP SETPT
PLM.A CIR A EXV POSITION LIMIT
SPR.1 SPARE 1 TEMPERATURE
EXV.B 0 to 100% EXV % OPEN
APPR ON/OFF CIRCUIT B APPROACH
AP.SP APPROACH SETPOINT
OVR.B EXVB OVERRIDE
SPH.B SUCTION SUPERHEAT TEMP
ASH.S ACTIVE SUPERHEAT SETPT
AMP.S ACTIVE MOP SETPT
PLM.B CIR B EXV POSITION LIMIT
SPR.2 SPARE 2 TEMPERATURE
CC.A1 ON/OFF COMPRESSOR A1 RELAY
DPE.R ON/OFF COMP A1 LOAD PERCENT
CC.A2 ON/OFF COMPRESSOR A2 RELAY
CC.A3 ON/OFF COMPRESSOR A3 RELAY
CC.A4 ON/OFF COMPRESSOR A4 RELAY
CC.B1 ON/OFF COMPRESSOR B1 RELAY
CC.B2 ON/OFF COMPRESSOR B2 RELAY
CC.B3 ON/OFF COMPRESSOR B3 RELAY
CC.B4 ON/OFF COMPRESSOR B4 RELAY
ITEM
EXPANSION
COMMENT
Table 10 — Configuration Mode and Sub-Mode Directory
SUB-MODE
DISP DISPLAY CONFIGURATION
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
KEYPAD
ENTRY
ITEM DISPLAY
TEST ON/OFF TEST DISPLAY LEDS
METR ON/OFF METRIC DISPLAY Off = English; On = Metric
LANG X LANGUAGE SELECTION
PAS.E ENBL/DSBL PASSWORD ENABLE Default: Enable
PASS xxxx SERVICE PASSWORD Default: 1111
ITEM
EXPANSION
11
COMMENT
Default: 0 0 = English
1 = Espanol 2 = Francais 3 = Portuguese
Page 12
Table 10 — Configuration Mode and Sub-Mode Directory
ENTER
ENTER
SUB-MODE
UNIT UNIT CONFIGURATION
KEYPAD
ENTRY
ITEM DISPLAY
SIZE XX UNIT SIZE
SZA.1 XX COMPRESSOR A1 SIZE Unit Dependent
SZA.2 XX COMPRESSOR A2 SIZE Unit Dependent
SZA.3 XX COMPRESSOR A3 SIZE Unit Dependent
SZA.4 XX COMPRESSOR A4 SIZE Unit Dependent
SZB.1 XX COMPRESSOR B1 SIZE Unit Dependent
SZB.2 XX COMPRESSOR B2 SIZE Unit Dependent
SZB.3 XX COMPRESSOR B3 SIZE Unit Dependent
SZB.4 XX COMPRESSOR B4 SIZE Unit Dependent
SH.SP XX.X F SUPERHEAT SETPOINT Default: 9 F
FAN.S NUMBER OF FANS 1 = One Fan
ITEM
EXPANSION
COMMENT
2 = Two Fans 3 = Three Fans 4 = Four Fans
EXV YES/NO EXV MODULE INSTALLED?
A1.TY YES/NO COMPRESSOR A1 DIGITAL?
MAX.T 0 to 12 MAXIMUM A1 UNLOAD TIME
OPT1 UNIT OPTIONS 1 HARDWARE
FLUD X COOLER FLUID
MLV.S YES/NO MINIMUM LOAD VALVE SELECT Default: No
D.G.EN ENBL/DSBL DISCHARGE GAS TEMP ENABLE
CSB.E ENBL/DSBL CSB BOARDS ENABLE
CPC ON/OFF COOLER PUMP CONTROL Default: Off
PM1E YES/NO COOLER PUMP 1 ENABLE
PM2E YES/NO COOLER PUMP 2 ENABLE
PM.P.S YES/NO COOLER PMP PERIODIC STRT Default: No
PM.SL X COOLER PUMP SELECT Default: Automatic
PM.DY XX MIN COOLER PUMP SHUTDOWN DLY
PM.DT XXXX HRS PUMP CHANGEOVER HOURS Default: 500 hours
ROT.P YES/NO ROTATE COOLER PUMPS NOW User Entr y
EMM YES/NO EMM MODULE INSTALLED
CND.T 0,1 COND HX
MOPS XX EXV MOP SET POINT Range: 40 - 80 Default: 50
APPR XX CONFIG APPROACH SETPOINT Range: 5 - 40 Default: 9.0
Default: Yes
Default: No
Yes = A1 Compressor is Digital
Scroll
Default: 7
Max 12 010,015 Max 10 018-060
Default: Water 1 = Water 2 = Medium Temperature Brine
0 = Automatic 1 = Pump 1 Starts first 2 = Pump 2 Starts first
0 to 10 minutes, Default: 1 min.
0 = RTPF 1 = MCHX Default MCHX
12
Page 13
Table 10 — Configuration Mode and Sub-Mode Directory (cont)
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
OPT2 UNIT OPTIONS 2 CONTROLS
CTRL X CONTROL METHOD Default: Switch
LOAD X LOADING SEQUENCE SELECT Default: Equal
LLCS X LEAD/LAG CIRCUIT SELECT Default: Automatic
LCWT XX.X F HIGH LCW ALERT LIMIT
DELY XX MINUTES OFF TIME
ICE.M ENBL/DSBL ICE MODE ENABLE Default: Disable
LS.MD X LOW SOUND MODE SELECT Default: 0
LS.ST 00:00 LOW SOUND START TIME Default: 00:00
LS.ND 00:00 LOW SOUND END TIME Default: 00:00
LS.LT XXX % LOW SOUND CAPACITY LIMIT
CCN CCN NETWORK CONFIGURATION
CCNA XXX CCN ADDRESS
CCNB XXX CCN BUS NUMBER
BAUD X CCN BAUD RATE Default: 9600
HP.A HEAD PRESSURE CMP DELTA
A1.DT XX SCT DELTA FOR COMP A1 Range: 0 - 50 Default: 12
A2.DT XX
SCT DELTA FOR COMP A2 Range: 0 - 50 Default: 12
HP.B HEAD PRESSURE CMP DELTA
B1.DT XX SCT DELTA FOR COMP B1 Range: 0 - 50 Default: 12
B2.DT XX
SCT DELTA FOR COMP B2 Range: 0 - 50 Default: 12
ITEM
EXPANSION
COMMENT
0 = Enable/Off/Remote Switch 2 = Occupancy 3 = CCN Control
1 = Equal 2 = Staged
1 = Automatic 2 = Circuit A Leads 3 = Circuit B Leads
Default: 60
Range: 2 to 60 F
Default: 0 Minutes Range: 0 to 15 Minutes
0 = Mode Disable 1 = Fan Noise Only 2 = Fan/Compressor Noise
Default: 100% Range: 0 to 100%
Default: 1 Range: 1 to 239
Default: 0 Range: 0 to 239
1 = 2400 2 = 4800 3 = 9600 4 = 19,200 5 = 38,400
13
Page 14
Table 10 — Configuration Mode and Sub-Mode Directory (cont)
ENTER
ENTER
ENTER
SUB-MODE
EXV.A CIR A EXV CONFIGURATION
EXV.B CIR B EXV CONFIGURATION
MM MOTORMASTER CONFIGURATION
KEYPAD
ENTRY
ITEM DISPLAY
STR.A XXX EXV CIRC.A START POS Range: 0 - 100 Default: 30
MIN.A XXX EXV CIRC.A MIN POSITION Range: 0 - 100 Default: 8
RNG.A XXXXX EXVA STEPS IN RANGE Range: 0 - 65535 Default: *
SPD.A XXXXX EXVA STEPS PER SECOND Range: 0 - 65535 Default: 200
POF.A XXX EXVA FAIL POSITION IN % Range: 0 - 100 Default: 0
MIN.A XXXXX EXVA MINIMUM STEPS Range: 0 - 65535 Default: 0
MAX.A XXXXX EXVA MAXIMUM STEPS Range: 0 - 65535 Default: *
OVR. A XXX EXVA OVERRUN STEPS Range: 0 - 65535 Default: 167
TYP.A 0,1 EXVA STEPPER TYPE
H.SCT XXX HIGH SCT THRESHOLD Range: 50 - 140 Default: 115
X.PCT XX OPEN EXV X% ON 2ND COMP Range: 0 - 30 Default: 10
X.PER XX MOVE EXV X% ON DISCRSOL Range: 0 - 30 Default: 5
A.PCT XXX PRE-OPEN EXV - FAN ADDING Range: 0 - 100 Default: 10
M.PCT XXX PRE-CLOSE EXV - FAN SUB Range: 0 - 100 Default: 10
S.PCT XXX PRE-CLOSE EXV - LAG SHUT Range: 0 - 100 Default: 10
DELY XXX LAG START DELAY Range: 0 - 100 Default: 10
STR.B XXX EXV CIRC.B START POS Range: 0 - 100 Default: 50
MIN.B XXX EXV CIRC.B MIN POSITION Range: 0 - 100 Default: 8
RNG.B XXXXX EXVB STEPS IN RANGE Range: 0 - 65535 Default: *
SPD.B XXXXX EXVB STEPS PER SECOND Range:
POF.B XXX EXVB FAIL POSITION IN % Range: 0 - 100 Default: 0
MIN.B XXXXX EXVB MINIMUM STEPS Range: 0 - 65535 Default: 0
MAX.B XXXXX EXVB MAXIMUM STEPS Range: 0 - 65535 Default: *
OVR. B XXX EXVB OVERRUN STEPS Range: 0 - 65535 Default: 167
TYP.B 0,1 EXVB STEPPER TYPE
MMR.S YES/NO MOTORMASTER SELECT
P.GAN XX HEAD PRESSURE P GAIN Range: -20 - 20 Default: 1.0
I.GAN XX HEAD PRESSURE I GAIN Range: -20 - 20 Default: 0.1
D.GAN XX HEAD PRESSURE D GAIN Range: -20 - 20 Default: 0.0
MIN.S XXX MINIMUM FAN SPEED Range: 0 - 100 Default: 5.0
ITEM
EXPANSION
COMMENT
0 = UNIPOLAR
1 = BIPOLAR Default: 1
0 - 65535 Default: 200
0 = UNIPOLAR
1 = BIPOLAR Default: 1
* Sizes 010-020 and 035-045, default is 1596. Sizes 025,030, and 050-060, default is 2500.
14
Page 15
Table 10 — Configuration Mode and Sub-Mode Directory (cont)
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
RSET RESET COOL TEMP
CRST X COOLING RESET TYPE Default: No Reset
MA.DG XX.X F 4-20 - DEGREES RESET
RM.NO XXX.X F REMOTE - NO RESET TEMP
RM.F XXX.X F REMOTE - FULL RESET TEMP
RM.DG XX.X F REMOTE - DEGREES RESET
RT.NO XXX.X F RETURN - NO RESET TEMP
RT.F XXX.X F RETURN - FULL RESET TEMP
RT.DG XX.X F
RETURN - DEGREES RESET
DMDC X DEMAND LIMIT SELECT Default: None
DM20 XXX % DEMAND LIMIT AT 20 MA
SHNM XXX LOADSHED GROUP NUMBER
SHDL XXX % LOADSHED DEMAND DELTA
SHTM XXX MAXIMUM LOADSHED TIME
DLS1 XXX % DEMAND LIMIT SWITCH 1
DLS2 XXX % DEMAND LIMIT SWITCH 2
LLEN ENBL/DSBL LEAD/LAG CHILLER ENABLE Default: Disable
MSSL SLVE/MAST MASTER/SLAVE SELECT Default: Master
SLVA XXX SLAVE ADDRESS
LLBL X LEAD/LAG BALANCE SELECT
LLBD XXX LEAD/LAG BALANCE DELTA
LLDY XXX LAG START DELAY
PARA YES PARALLEL CONFIGURATION Default: YES (CANNOT BE CHANGED)
SLCT SETPOINT AND RAMP LOAD
CLSP X COOLING SETPOINT SELECT Default: Single
RL.S ENBL/DSBL RAMP LOAD SELECT Default: Enable
CRMP X.X COOLING RAMP LOADING
SCHD XX SCHEDULE NUMBER
Z.GN X.X DEADBAND MULTIPLIER
SERV SERVICE CONFIGURATION
EN.A1 ENBL/DSBL ENABLE COMPRESSOR A1 Unit dependent
EN.A2 ENBL/DSBL ENABLE COMPRESSOR A2 Unit dependent
EN.B1 ENBL/DSBL ENABLE COMPRESSOR B1 Unit dependent
EN.B2 ENBL/DSBL ENABLE COMPRESSOR B2 Unit dependent
ITEM
EXPANSION
COMMENT
0 = No Reset 1 = 4 to 20 mA Input 2 = Outdoor Air Temperature 3 = Return Fluid 4 = Space Temperature
Default: 0.0F Range: –30 to 30F
Default: 125F (51.7C) Range: 0° to 125F
Default: 0.0F (-17.8C) Range: 0 to 125F
Default: 0.0F Range: –30 to 30F
Default: 10.0F (5.6C) Range: 0 to 125F COOLER T
Default: 0.0F (0.0C) Range: 0 to 125F COOLER T
Default: 0.0F Range: –30 to 30F (–34.4 to -1.1 C)
0 = None 1 = Switch 2 = 4 to 20 mA Input 3 = CCN Loadshed
Default: 100% Range: 0 to 100%
Default: 0 Range: 0 to 99
Default: 0% Range: 0 to 60%
Default: 60 minutes Range: 0 to 120 minutes
Default: 80% Range: 0 to 100%
Default: 50% Range: 0 to 100%
Default: 0 Range: 0 to 239
Default: Master Leads 0 = Master Leads 1 = Slave Leads 2 = Automatic
Default: 168 hours Range: 40 to 400 hours
Default: 5 minutes Range: 0 to 30 minutes
0 = Single 1 = Dual Switch 2 = Dual CCN Occupied 3 = 4 to 20 mA Input (requires
EMM)
Default: 1.0 Range: 0.2 to 2.0
Default: 1 Range: 1 to 99
Default: 1.0 Range: 1.0 to 4.0
15
Page 16
Table 10 — Configuration Mode and Sub-Mode Directory (cont)
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
SUB-MODE
BCST BROADCAST CONFIGURATION
KEYPAD
ENTRY
ITEM DISPLAY
T.D.BC ON/OFF CCN TIME/DATE BROADCAST
OAT.B ON/OFF CCN OAT BROADCAST
G.S.BC ON/OFF GLOBAL SCHEDULE BROADCAST
BC.AK ON/OFF CCN BROADCAST ACK’ER
ITEM
EXPANSION
Table 11 — Time Clock Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY SUB-ITEM DISPLAY
TIME TIME OF DAY
HH.MM XX.XX HOUR AND MINUTE Military (00:00 – 23:59)
DATE MONTH,DATE,DAY AND YEAR
MNTH XX MONTH OF YEAR 1-12 (1 = January, 2 = February, etc)
DOM XX DAY OF MONTH Range: 01-31
DAY X DAY OF WEEK 1-7 (1 = Sunday, 2 = Monday, etc)
YEAR XXXX YEAR OF CENTURY
DST DAYLIGHT SAVINGS TIME
STR.M XX MONTH Default: 4, Range 1 – 12
ITEM
EXPANSION
COMMENT
COMMENT
STR.W X WEEK Default: 1, Range 1 – 5
STR.D X DAY Default: 7, Range 1 – 7
MIN.A XX MINUTES TO ADD Default: 60, Range 0 – 99
STP.M XX MONTH Default: 10, Range 1 – 12
STP.W XX WEEK Default: 5, Range 1 – 5
STP.D XX DAY Default: 7, Range 1 – 7
MIN.S XX MINUTES TO SUBTRACT Default: 60, Range 0 – 99
HOL.L LOCAL HOLIDAY SCHEDULES HD.01 through HD.30
MON XX HOLIDAY START MONTH Range 0 – 12
DAY XX START DAY Range 0 – 31
LEN XX DURATION (DAYS) Range 0 - 99
SCH.N XX SCHEDULE NUMBER Default: 1, Range 1 – 99
SCH.L LOCAL OCCUPANCY SCHEDULE
PER.1 OCCUPANCY PERIOD 1*
OCC.1 XX:XX PERIOD OCCUPIED TIME Military (00:00 – 23:59)
UNC.1 XX.XX PERIOD UNOCCUPIED TIME Military (00:00 – 23:59)
MON.1 YES/NO MONDAY IN PERIOD
TUE.1 YES/NO TUESDAY IN PERIOD
WED.1 YES/NO WEDNESDAY IN PERIOD
THU.1 YES/NO THURSDAY IN PERIOD
FRI.1 YES/NO FRIDAY IN PERIOD
SAT.1 YES/NO SATURDAY IN PERIOD
SUN.1 YES/NO SUNDAY IN PERIOD
HOL.1 YES/NO HOLIDAY IN PERIOD
* Repeats for Occupancy Periods 2 through 8.
16
Page 17
Table 11 — Time Clock Mode and Sub-Mode Directory (cont)
ENTER
ENTER
ENTER
ENTER
ENTER
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY SUB-ITEM DISPLAY
OVR SCHEDULE OVERRIDE
OVR.T X TIMED OVERRIDE HOURS Default: 0, Range 0-4 hours
OVR.L X OVERRIDE TIME LIMIT Default: 0, Range 0-4 hours
T.OVR YES/NO TIMED OVERRIDE User Entry
ITEM
EXPANSION
Table 12 — Operating Mode and Sub-Mode Directory
COMMENT
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
MODE MODES CONTROLLING UNIT
MD01 ON/OFF CSM CONTROLLING CHILLER
MD02 ON/OFF WSM CONTROLLING CHILLER
MD03 ON/OFF MASTER/SLAVE CONTROL
MD05 ON/OFF RAMP LOAD LIMITED
MD06 ON/OFF TIMED OVERRIDE IN EFFECT
MD07 ON/OFF LOW COOLER SUCTION TEMPA
MD08 ON/OFF LOW COOLER SUCTION TEMPB
MD09 ON/OFF SLOW CHANGE OVERRIDE
MD10 ON/OFF MINIMUM OFF TIME ACTIVE
MD13 ON/OFF DUAL SETPOINT
MD14 ON/OFF TEMPERATURE RESET
MD15 ON/OFF DEMAND/SOUND LIMITED
MD16 ON/OFF COOLER FREEZE PROTECTION
MD17 ON/OFF LOW TEMPERATURE COOLING
MD18 ON/OFF HIGH TEMPERATURE COOLING
MD19 ON/OFF MAKING ICE
MD20 ON/OFF STORING ICE
COMMENT
MD21 ON/OFF HIGH SCT CIRCUIT A
MD22 ON/OFF HIGH SCT CIRCUIT B
MD23 ON/OFF MINIMUM COMP ON TIME
MD24 ON/OFF PUMP OFF DELAY TIME
MD25 ON/OFF LOW SOUND MODE
LEGEND
CSM Chillervisor System Manager SCT Saturated Condensing Temperature WSM — Water System Manager
Table 13 — Alarms Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM
CRNT AXXX OR TXXX CURRENTLY ACTIVE ALARMS
RCRN YES/NO RESET ALL CURRENT ALARMS
HIST AXXX OR TXXX ALARM HISTORY
ITEM
EXPANSION
17
COMMENT
Alarms are shown as AXXX. Alerts are shown as TXXX.
Alarms are shown as AXXX. Alerts are shown as TXXX.
Page 18
Table 14 — Operating Modes
MODE
NO.
01 CSM CONTROLLING CHILLER Chillervisor System Manager (CSM) is controlling the chiller.
02 WSM CONTROLLING CHILLER Water System Manager (WSM) is controlling the chiller.
03 MASTER/SLAVE CONTROL Dual Chiller control is enabled.
05
06
07
08
09
10 MINIMUM OFF TIME ACTIVE Chiller is being held off by Minutes Off Time (Configuration
13
14
15
16
17
18
19
20
21
22
23
24
25
ITEM EXPANSION DESCRIPTION
RAMP LOAD LIMITED Ramp load (pull-down) limiting in effect. In this mode, the rate at which leaving fluid temperature
TIMED OVERRIDE IN EFFECT Timed override is in effect. This is a 1 to 4 hour temporary override of the programmed
LOW COOLER SUCTION TEMPA Circuit A cooler Freeze Protection mode. At least one compressor must be on, and the Sat-
LOW COOLER SUCTION TEMPB Circuit B cooler Freeze Protection mode. At least one compressor must be on, and the Sat-
SLOW CHANGE OVERRIDE Slow change override is in effect. The leaving fluid temperature is close to and moving
DUAL SETPOINT Dual Set Point mode is in effect. Chiller controls to Cooling Set Point 1 (Set Points
TEMPERATURE RESET Temperature reset is in effect. In this mode, chiller is using temperature reset to adjust leav-
DEMAND/SOUND LIMITED Demand limit is in effect. This indicates that the capacity of the chiller is being limited by
COOLER FREEZE PROTECTION Cooler fluid temperatures are approaching the Freeze point (see Alarms and Alerts section
LOW TEMPERATURE COOLING Chiller is in Cooling mode and the rate of change of the leaving fluid is negative and
HIGH TEMPERATURE COOLING Chiller is in Cooling mode and the rate of change of the leaving fluid is positive and increasing.
MAKING ICE Chiller is in an unoccupied mode and is using Cooling Set Point 3 (Set Points
STORING ICE Chiller is in an unoccupied mode and is controlling to Cooling Set Point 2 (Set Points
HIGH SCT CIRCUIT A Chiller is in a Cooling mode and the Saturated Condensing Temperature (SCT) is greater than
HIGH SCT CIRCUIT B Chiller is in a Cooling mode and the Saturated Condensing Temperature (SCT) is greater than
MINIMUM COMP ON TIME Cooling load may be satisfied, however control continues to operate compressor to ensure
PUMP OFF DELAY TIME Cooling load is satisfied, however cooler pump continues to run for the number of minutes set
LOW SOUND MODE Chiller operates at higher condensing temperature and/or reduced capacity to minimize
is dropped is limited to a predetermined value to prevent compressor overloading. See Cooling Ramp Loading (Configuration desired, to any rate from 0.2° F to 2° F (0.1° to 1° C)/minute.
schedule, forcing unit to Occupied mode. Override can be implemented with unit under Local (Enable) or CCN (Carrier Comfort Network
urated Suction Temperature is not increasing greater than 1.1° F (0.6° C) in 10 seconds. If the saturated suction temperature is less than the Brine Freeze Point (Set Points
BR.FZ) minus 6° F (3.4° C) and less than the leaving fluid temperature minus 14° F (7.8° C) for 2 minutes, a stage of capacity will be removed from the circuit. Or, If the satu­rated suction temperature is less than the Brine Freeze Point minus 14° F (7.8° C), for 90 seconds, a stage of capacity will be removed from the circuit. The control will continue to decrease capacity as long as either condition exists.
urated Suction Temperature is not increasing greater than 1.1° F (0.6° C) in 10 seconds. If the saturated suction temperature is less than the Brine Freeze Point (Set Points
BR.FZ) minus 6° F (3.4° C) and less than the leaving fluid temperature minus 14° F (7.8° C) for 2 minutes, a stage of capacity will be removed from the circuit. Or, If the satu­rated suction temperature is less than the Brine Freeze Point minus 14° F (7.8° C), for 90 seconds, a stage of capacity will be removed from the circuit. The control will continue to decrease capacity as long as either condition exists.
towards the control point.
CSP.1) during occupied periods and Cooling Set Point 2 (Set PointsCOOLCSP.2) during unoccupied periods.
ing fluid set point upward and is currently controlling to the modified set point. The set point can be modified based on return fluid, outdoor-air-temperature, space temperature, or 4 to 20 mA signal.
demand limit control option. Because of this limitation, the chiller may not be able to pro­duce the desired leaving fluid temperature. Demand limit can be controlled by switch inputs or a 4 to 20 mA signal.
for definition). The chiller will be shut down when either fluid temperature falls below the Freeze point.
decreasing faster than -0.5° F per minute. Error between leaving fluid and control point exceeds fixed amount. Control will automatically unload the chiller if necessary.
Error between leaving fluid and control point exceeds fixed amount. Control will automatically load the chiller if necessary to better match the increasing load.
CSP.3) to make ice. The ice done input to the Energy Management Module (EMM) is open.
CSP.2). The ice done input to the Energy Management Module (EMM) is closed.
the calculated maximum limit. No additional stages of capacity will be added. Chiller capacity may be reduced if SCT continues to rise to avoid high-pressure switch trips by reducing con­densing temperature.
the calculated maximum limit. No additional stages of capacity will be added. Chiller capacity may be reduced if SCT continues to rise to avoid high-pressure switch trips by reducing con­densing temperature.
proper oil return. May be an indication of oversized application, low fluid flow rate or low loop volume.
by the configuration variable Cooler Pump Shutdown Delay (Configuration
PM.DY).
overall unit noise during evening/night hours (Configuration
SLCTCRMP). The pull-down limit can be modified, if
®
) control. Override expires after each use.
OPT2DELY).
OPT2LS.MD).

OPT1
FRZ
FRZ
COOL
COOL

COOL
18
Page 19
CONTROLS
General —
the ComfortLink™ electronic control system that controls and monitors all operations of the chiller.
The control system is composed of several components as listed in the sections below. See Fig. 3-5 for typical control box drawings. See Fig. 6 and 7 for control schematics.
The 30RAP air-cooled scroll chillers contain
Main Base Board (MBB) — See Fig. 8. The MBB is
the heart of the ComfortLink control system. It contains the major portion of operating software and controls the operation of the machine. The MBB continuously monitors input/output channel information received from its inputs and from all other modules. The MBB receives inputs from the discharge and suction pressure transducers and thermistors. See Table 15. The MBB also receives the feedback inputs from each compressor current sensor board and other status switches. See Table 16. The MBB also controls several outputs. Relay outputs con­trolled by the MBB are shown in Table 17. Information is transmitted between modules via a 3-wire communication bus or LEN (Local Equipment Network). The CCN (Carrier Com­fort Network) bus is also supported. Connections to both LEN and CCN buses are made at the LVT (low voltage terminal). See Fig. 8.
Energy Management Module (EMM) — The EMM
module is available as a factory-installed option or as a field­installed accessory. The EMM module receives 4 to 20 mA inputs for the leaving fluid temperature reset, cooling set point and demand limit functions. The EMM module also receives the switch inputs for the field-installed 2-stage demand limit and ice done functions. The EMM module communicates the status of all inputs with the MBB, and the MBB adjusts the control point, capacity limit, and other functions according to the inputs received.
Current Sensor Board (CSB) — The CSB is used to
monitor the status of the compressors by measuring current and providing an analog input to the main base board (MBB) or compressor expansion module (CXB).
AUX Board (AUX) — The AUX is used with the digital
scroll option and the low ambient head pressure option. It pro­vides additional inputs and outputs for digital scroll control along with analog outputs to control head pressure control fan speeds.
Expansion Valve Board (EXV) — The EXV board
communicates with the MBB and directly controls the expan­sion valves to maintain the correct compressor superheat.
Enable/Off/Remote Contact Switch — The Enable/
Off/Remote Contact switch is a 3-position switch used to control the chiller. When switched to the Enable position the chiller is under its own control. Move the switch to the Off position to shut the chiller down. Move the switch to the Remote Contact position and a field-installed dry contact can be used to start the chiller. The contacts must be capable of handling a 24 vac, 50-mA load. In the Enable and Remote Contact (dry contacts closed) positions, the chiller is allowed to operate and respond to the scheduling configuration, CCN configuration and set point data. See Fig. 9.
Emergency On/Off Switch — The Emergency On/Off
switch should only be used when it is required to shut the chiller off immediately. Power to the MBB, EMM, and marquee display is interrupted when this switch is off and all outputs from these modules will be turned off.
Board Addresses — The main base board (MBB) has a
3-position instance jumper that must be set to ‘1.’ The elec­tronic expansion valve board (EXV) and energy management board (EMM) have 4-position DIP switches. All switches are
set to ‘On’ for these boards. The auxiliary board (AUX) has an 8-position DIP switch. Switches 2, 5, and 7 are set to ‘On.’
Control Module Communication
RED LED — Proper operation of the control boards can be visually checked by looking at the red status LEDs (light-emitting diodes). When operating correctly, the red status LEDs should be blinking in unison at a rate of once every 2 seconds. If the red LEDs are not blinking in unison, verify that correct power is being supplied to all modules. Be sure that the main base board (MBB) is supplied with the current soft­ware. If necessary, reload current software. If the problem still persists, replace the MBB. A red LED that is lit continuously or blinking at a rate of once per second or faster indicates that the board should be replaced.
GREEN LED — The MBB has one green LED. The Local Equipment Network (LEN) LED should always be blinking whenever power is on. All other boards have a LEN LED which should be blinking whenever power is on. Check LEN connections for potential communication errors at the board J3 and/or J4 connectors. Communication between modules is accomplished by a 3-wire sensor bus. These 3 wires run in parallel from module to module. The J4 connector on the MBB provides both power and communication directly to the marquee display only.
YELLOW LED — The MBB has one yellow LED. The Carrier Comfort Network (CCN) LED will blink during times of network communication.
Carrier Comfort Network® (CCN) Interface —
The 30RAP chiller units can be connected to the CCN if desired. The communication bus wiring is a shielded, 3-conductor cable with drain wire and is supplied and installed in the field. See Table 18. The system elements are connected to the communication bus in a daisy chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system elements on either side of it. This is also required for the negative and signal ground pins of each system element. Wiring connections for CCN should be made at LVT. Consult the CCN Contrac­tor’s Manual for further information.
NOTE: Conductors and drain wire must be 20 AWG (Ameri­can Wire Gage) minimum stranded, tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of –20 C to 60 C is required. Wire manufactured by Alpha (2413 or 5463), American (A22503), Belden (8772), or Columbia (02525) meets the above mentioned requirements.
It is important when connecting to a CCN communication bus that a color coding scheme be used for the entire network to simplify the installation. It is recommended that red be used for the signal positive, black for the signal negative, and white for the signal ground. Use a similar scheme for cables contain­ing different colored wires.
At each system element, the shields of its communication bus cables must be tied together. If the communication bus is entirely within one building, the resulting continuous shield must be connected to a ground at one point only. If the commu­nication bus cable exits from one building and enters another, the shields must be connected to grounds at the lightning suppressor in each building where the cable enters or exits the building (one point per building only). To connect the unit to the network:
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white (ground), and black (–) conductors. (Substitute appropri­ate colors for different colored cables.)
19
Page 20
3. Connect the red wire to (+) terminal on LVT of the plug, the white wire to COM terminal, and the black wire to the (–) terminal.
4. The RJ14 CCN connector on LVT can also be used, but is only intended for temporary connection (for example, a laptop computer running Service Tool).
IMPORTANT: A shorted CCN bus cable will prevent some routines from running and may prevent the unit from start­ing. If abnormal conditions occur, unplug the connector. If conditions return to normal, check the CCN connector and cable. Run new cable if necessary. A short in one section of the bus can cause problems with all system elements on the bus.
Table 15 — Thermistor Designations
THERMISTOR
LWT J8-13,14 (MBB) Cooler Leaving Fluid
EWT J8-11,12 (MBB) Cooler Entering Fluid
RGTA
RGTB
OAT
SPT
DTT
LEGEND
LWT — Leaving Water Temperature MBB — Main Base Board
PIN
CONNECTION
POINT
J8-1,2 (MBB) Circuit A Return Gas
J8-3,4 (MBB) Circuit B (035-060 only)
J8-7,8 (MBB) Outdoor-Air Temperature
J8-5,6 (MBB) TB5-5,6
J6-1,2 (AUX) Discharge Temperature
THERMISTOR INPUT
Temperature
Return Gas Temperature
Sensor Accessory Remote Space
Temperature Sensor or Dual LWT Sensor
Thermistor
Table 16 — Status Inputs
STATUS SWITCH PIN CONNECTION POINT Chilled Water Pump 1 J7-1,2 Chilled Water Pump 2 J7-3,4
Remote On/Off LVT-13,14
Cooler Flow Switch J7-9,10 Compressor Fault Signal, A1 J9-11,12 Compressor Fault Signal, A2 J9-5,6 Compressor Fault Signal, B1 J9-8,9 Compressor Fault Signal, B2 J9-2,3
Table 17 — Output Relays
RELAY
NO.
Energize Compressor A1 (010-030)
K1
Energize Compressor A1 and Condenser Fan Contac­tor 3 (055,060)
K2 Energize Compressor A2 (all but 010, 015 60 Hz) K3 Energize Chilled Water Pump 1 Output K4 Energize Chilled Water Pump 2 Output
Energize Compressor B1 (035-050)
K5
Energize Compressor B1 and Condenser Fan Contac­tor 3 (055,060)
K6 Energize Compressor B2 (035-060) K7 Alarm Relay K8 Cooler/Pump Heater
K9 Energize Condenser Fan Contactor 1 (018-060) K10 Energize Condenser Fan Contactor 2 (018-060) K11 Minimum Load Valve
DESCRIPTION
Table 18 — CCN Communication Bus Wiring
MANUFACTURER
Alpha 1895 American A21451 A48301 Belden 8205 884421 Columbia D6451 Manhattan M13402 M64430 Quabik 6130
Regular Wiring Plenum Wiring
PART N O .
Sensors — The electronic control uses 4 to 7 thermistors to
sense temperatures for controlling chiller operation. See Table 15. These sensors are outlined below. Thermistors RG­TA, RGTB, EWT, LWT, and OAT are identical in temperature versus resistance and voltage drop performance. The dual chill­er thermistor is 5 kat 77 F (25 C)thermistor. Space tempera­ture thermistor is a 10 kat 77 F (25 C). The DTT thermistor is an 86 kat 77 F (25 C)thermistor. See Thermistors section for temperature-resistance-voltage drop characteristics.
COOLER LEAVING FLUID SENSOR — The thermistor is installed in a well in the factory-installed leaving fluid piping coming from the bottom of the brazed-plate heat exchanger.
COOLER ENTERING FLUID SENSOR — The thermistor is installed in a well in the factory-installed entering fluid piping coming from the top of the brazed-plate heat exchanger.
COMPRESSOR RETURN GAS TEMPERATURE SEN­SOR — These thermistors are installed in a well located in the suction line of each circuit.
OUTDOOR-AIR TEMPERATURE SENSOR (OAT) — This sensor is factory installed on a bracket which is inserted through the base pan of the unit.
DISCHARGE TEMPERATURE THERMISTOR (DTT) — This sensor is only used on units with a digital compressor. The sensor is mounted on the discharge line close to the discharge of the digital compressor. It attaches to the dis­charge line using a spring clip and protects the system from high discharge gas temperature when the digital compressor is used. This sensor is a connected to the AUX board.
REMOTE SPACE TEMPERATURE SENSOR OR DUAL LEAVING WATER TEMPERATURE SENSOR — One of two inputs can be connected to the LVT. See appropriate sen­sor below.
Remote Space Temperature Sensor 33ZCT55SPT) is an accessory sensor that is remotely mounted in the controlled space and used for space temperature reset. The sensor should be installed as a wall-mounted thermostat would be (in the conditioned space where it will not be sub­jected to either a cooling or heating source or direct exposure to sunlight, and 4 to 5 ft above the floor).
Space temperature sensor wires are to be connected to terminals in the unit main control box. The space temperature sensor includes a terminal block (SEN) and a RJ11 female connector. The RJ11 connector is used access into the Carrier Comfort Network
®
(CCN) at the sensor.
To connect the space temperature sensor (Fig. 10):
1. Using a 20 AWG twisted pair conductor cable rated for the application, connect 1 wire of the twisted pair to one SEN terminal and connect the other wire to the other SEN terminal located under the cover of the space temperature sensor.
2. Connect the other ends of the wires to terminals 5 and 6 on TB5 located in the unit control box.
— Sensor (part no.
20
Page 21
Units on the CCN can be monitored from the space at the sensor through the RJ11 connector, if desired. To wire the RJ11 connector into the CCN (Fig. 11):
IMPORTANT: The cable selected for the RJ11 connector wiring MUST be identical to the CCN communication bus wire used for the entire network. Refer to Table 18 for acceptable wiring.
1. Cut the CCN wire and strip ends of the red (+), white (ground), and black (–) conductors. (If another wire color scheme is used, strip ends of appropriate wires.)
2. Insert and secure the red (+) wire to terminal 5 of the space temperature sensor terminal block.
LEGEND FOR FIG. 3-7
ALMR Alarm Relay AUX Auxilliary BR Boiler Relay C—Contactor, Compressor CB Circuit Breaker CCB Compressor Circuit Breaker CH Crankcase Heater CHC Cooler/Pump Heater Contactor COMP Compressor CSB Current Sensor Board CWFS Chilled Water Flow Switch CWP Chilled Water Pump DGS Digital Scroll Compressor DPT Discharge Pressure Transducer DTT Discharge Temperature Thermistor DUS Digital Unloader Solenoid EMM Energy Management EXV Electronic Expansion Valve FB Fuse Block FC Fan Contactor FCB Fan Circuit Breaker FIOP factory Installed Option FR Fan Relay GND Ground HPS High-Pressure Switch LON Local Operating Network LV T Low Voltage Terminal Block MBB Main Base Board MLV Minimum Load Valve MM Motormaster MP Motor Protector MS Manual Starter NEC National Electrical Code OAT Outdoor-Air Thermistor OFM Outdoor Fan Motor RGT Return Gas Thermistor SCCR Short Circuit Current Rating SPT Suction Pressure Transducer SW Switch TB Terminal Block TNKR Storage Tank Heater Relay TRAN Transformer UPC Unitary Protocol Converter
Terminal Block
Terminal (Unmarked)
Terminal (Marked)
Splice
Factory Wiring
Field Wiring
Accessory or Option Wiring
To indicate common potential only; not to represent wiring.
3. Insert and secure the white (ground) wire to terminal 4 of the space temperature sensor.
4. Insert and secure the black (–) wire to terminal 2 of the space temperature sensor.
5. Connect the other end of the communication bus cable to the remainder of the CCN communication bus.
Dual Leaving Water Temperature Sensor
— For dual chiller applications (parallel only are supported), connect the dual chiller leaving fluid temperature sensor (refer to Configuring and Operating Dual Chiller Control section on page 36) to the space temperature input of the Master chiller. If space tempera­ture is required for reset applications, connect the sensor to the Slave chiller and configure the slave chiller to broadcast the value to the Master chiller.
21
Page 22
CONTROL BOX
FAN
1
A1
COMPRESSOR
LOCATED OVER EMM AND EXV
EMM
EXV
LON
AUX
UPC
TB1
TB4
CSB-A1
MBB
CHC
CCB
FB-1
TRAN
DISCONNECT
OPTION/TB
C-A1
MM
MS-
CWP1
CWP1
MS-
CWP2
CWP2
Fig. 3 — Typical Control Box for 30RAP010,015
Fig. 4 — Typical Control Box for 30RAP018-030
a30-4962
a30-4963
FB-1
AUX
LON
EMM
EXV
CHC
CCB-1
CSB-A1
TB1
UPC
TB4
C-A1
FC1/MM
MBB
FB-3
MS-
CWP1
CWP1 CWP2
TRAN
MS-
CWP2
CSB-A2
FC2 C-A2
CCB-2
DISCONNECT
OPTION/TB
22
Page 23
Fig. 5 — Typical Control Box for 30RAP035-060
a30-4964
OPTION/TB
DISCONNECT
CHC
EXV
EMM
CB-4
CB-3
TB1
CSB-B2
CSB-B1
UPC
LON
AUX
TB4
MS-
MS-
CWP2
CWP1
FR-4
FR-3
C-B2
CWP2
CWP1
C-B1
MBB
055,060 UNIT ONLY
B2
2
4
FAN
FAN
FAN3FAN
LOCATED OVER EMM AND EXV
1
B1
A2
COMPRESSORS
A1
CONTROL BOX END
FCB-1/2/3
CB-2
CB-1
TRAN-1
CSB-A2
CSB-A1
TRAN-2
23
FC-3
FC-2
MM
FC-1
FR-2
FR-1
C-A2
C-A1
Page 24
OPTIONAL
Fig. 6A — Typical Wiring Schematic, 30RAP018-030 Units — Power Wiring
a30-4965
DISCONNECT
DISCONNECT
TO FUSED
PER NEC
EQUIP GND
~
FU5
RED
1
H3
H4
TRAN3
X3
WHT
WHT
GRN/YEL
2
GFI-CO
FIOP/ACCESSORY
SILVER SCREW
SILVER SCREW
GRN-YEL
FUSE
NUMBER
FU1 & FU2
380-3-60,460-3-60,575-3-60
FU3 (24V)
208/230-3-60,230-3-60
380-3-60,460-3-60,575-3-60
FU4 (115V)
380-3-60,460-3-60,575-3-60
FB1
(NO MM)
380-3-60,460-3-60,575-3-60
FB1
(WITH MM)
380-3-60,460-3-60,575-3-60
FB2
380-3-60,460-3-60,575-3-60
FB3
VOLTAGE SERIES
575-3-60 100 H1 & H2
380-3-60 200 H1 & H2
230-3-60 500 H2 & H4
208-3-60 500 H3 & H4
460-3-60 600 H1 & H4
CONNECT FOR APPROPRIATE PRIMARY VOLTAGE SEE TABLE 1
TB4
XF
RED
7
FU3
RED
A1
SW2
C1
B1
VIO
CB3
3.2 AMPS
TB4
VIO
6
VIO
CB1A
1
2
3
H2
~
SECONDARY
115V
LINE
RESET
TEST
LOAD
UNIT VOLTAGE
208/230-3-60
380-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60,575-3-60
208/230-3-60
208/230-3-60
208/230-3-60
208/230-3-60
TABLE 1
TRAN1
PRIMARY
H2
H1
SECONDARY 24V
X1
BRN
VIO
3
2
BRN
1
VIO
BRN
VIO
BRN
STANDARD
TERMINAL
BLOCK
TB1A
TO FUSED DISCONNECT
11
PER NEC
12
13
~
FU6
BLK
1
HF
H1
X1
FU4
XF
BLK
2
BRASS SCREW
BRASS SCREW
VOLTAGE SERIES
575-3-60 100 H1-H2 XF-X2
230-3-60 400,500 H2-H4 XF-X2
208-3-60 500 H3-H4 XF-X2
460-3-60 600 H1-H4 XF-X2
REPLACE
TRAN
WITH
SIZE
FNQ-R-3.5
FNQ-R-2.5
200VA
FNQ-R-2
FNQ-R-1.5
FNM-10
200VA
FNQ-R-2.5
AV0056UF & 5UF
FNQ-R-3.5
FNM-6
500VA
LP-CC-20
NONE
KTK-R-15
NONE
KTK-R-20208/230-3-60
LP-CC-20
NONE
LP-CC-20
NONE
TERMINAL
CONNECTIONS
FOR PRIMARY SIDE
FU1
BLK
FU2
YEL
H3
H4
X2
GRN/YEL
BRN
BRN
C
TB1
UPC FIOP
24VAC
2
GND
UPC
HOT
1
3
J1
3
3
2
1
CWFS
MBB
2
2
BRN
1
1
RED
J2
31
BRN
BLU
21
22
23
CONNECTIONS
FOR PRIMARY SIDE
TERMINAL
3
2
1
BLK BLK BLK
YEL YEL YEL
BLU BLU BLU
CONNECTIONS FOR SECONDARY SIDE
TB4CTB1
5
RED BRN
FIOP/ACCESSORY
J1
3
2
EMM
1
J2
TERMINAL
CH-A1
BLU
T2
T3
T2
T3
FC1
11 21
12
13 23
FC2
11 21
12
13 23
CA1
11 21
12 22
13 23
CA2
11 21
12 22
13 23
22
22
CHC
42
CHC
86
BLK
BLK
YEL
BLU
BLU BLK
BLK
YEL
BLU
BLK
BLK
BLK
BLK
BLK
BLK
BLK-1
BLK-2
BLK-3
BLK-1
BLK-2
BLK-3
~
COOLER/PUMP HEATERS (380,460,575V)
~~
~
CH-A2
BLK
WHT
BLK
1
T1
2
T2
3
1
2
3
COMP A1
T3
GRN/YEL
T1
COMP A2
T2
T3
GRN/YEL
L1
CWP1 WATER
L2
PUMP
L3
GRN/YEL
L1
CWP2 WATER
L2
PUMP
L3
GRN/YEL
1
2
3
1
2
3
1
3
2
BLK
BLK
COOLER/PUMP HEATERS (208/230,230V)
~
WHT
OFM1
GRN/YEL
OFM2
GRN/YEL
1
2
3
380V,460V,575V
CCB-1
ONLY
11
BLK
12
YEL
13
FB3
11
12
13
HIGH SCCR ONLY
BLU
BLK
YEL
BLU
208/230V ONLY
21
11
BLK
22
12
YEL
23
13
BLU
CCB-2
11
12
13
MS-CWP1
L1
BLK
YEL
L2
BLU
L3
MS-CWP2
L1
BLK
YEL
L2
BLU
L3
FB1
21
22
23
YEL
BLUBLK
BLK
YEL
BLU
CSB-A1
21
BLK
22
YEL
BLU
23
YEL
BLU BLK
CSB-A2
21
BLK
22
YEL
23
BLU
CHILLED WATER PUMP FIOP
CWP1
L1 T1
T1
L2
T2
T3
L3
CWP2
L1 T1
T1
L2
T2
T3
L3
BLK
YEL
BLU
BLK
YEL
BLU
YEL
BLUBLK
BLK
YEL
LOW AMBIENT OPERATION (MOTORMASTER V) FIOP/ACCESSORY
FB3
11
21
BLK
22
12
YEL
13
23
BLU
HIGH SCCR ONLY
NOTES:
1. FACTORY WIRING IS IN ACCORDANCE WITH UL 1995 STANDARDS. ANY FIELD MODIFICATIONS OR ADDITIONS MUST BE IN COMPLIANCE WITH ALL APPLICABLE CODES.
C MIN WIRE FOR FIELD POWER SUPPLY.
3. ALL FIELD INTERLOCK CONTACTS MUST HAVE A MIN RATING OF 2 AMPS @ 24VAC SEALED. SEE FIELD INTERLOCK WIRING.
4. COMPRESSOR AND FAN MOTORS ARE THERMALLY PROTECTED-­ THREE PHASE MOTORS PROTECTED AGAINST PRIMARY SINGLE PHASE CONDITIONS.
5. TERMINALS 13 & 14 OF LVT ARE FOR FIELD CONNECTION OF REMOTE ON-OFF. THE CONTACT MUST BE RATED FOR DRY CIRCUIT APPLICATION CAPABLE OF HANDLING A 5VDC 1 MA TO 20 MA LOAD.
6. FOR 500 SERIES UNIT OPERATION AT 208-3-60V LINE VOLTAGE, TRAN1 PRIMARY CONNECTIONS MUST BE MOVED TO TERMINALS H3 & H4.
7. FOR UNITS WITH LOW AMBIENT MOTOR MASTER V FIOP/ACCESSORY, FAN CONTACTOR FC1 IS REPLACED WITH MOTORMASTER RELAY MMR.
J1
EXV
J2
DGS FIOP
12
11
J1
AUX
3
3
2
2
1
1
3
3
2
2
BRN
1
1
RED
3
3
2
2
2
BRN
1
1
1
RED
FB1
11
21
BLK
22
12
YEL
13
23
BLU
FB2
11
21
BLK
22
12
YEL
13
23
BLU
MM-A
L1 T1
BLK
L2 T2
YEL
L3 T3
BLU
2
*1
25
2
FC2
11 21
BLK
YEL
22
12
13 23
BLU
BLK
YEL
CHC
42
CHC
86
1
BLK-1
2
BLK-2
3
BLK-3
YEL
MMR
VIO
11 14
240 1/4W
RED
FROM AUX-J4
BLK
BLK-1
BLK-2
BLK-3
~
BLK
WHT
COOLER/PUMP HEATERS (380,460,575V)
~~
~
BLK
8. IF CHILLED WATER PUMP INTERLOCK IS USED, REMOVE JUMPER FROM TERMINAL 11 TO 17 AND WIRE INTERLOCK CONTACT ACROSS TERMINALS 11 & 17.
9. MP-A1 NOT USED IN THE FOLLOWING UNITS:
018,020: ALL UNITS 025,030: 460V UNITS WITHOUT DIGITAL SCROLL
10. MP-A2 NOT USED IN THE FOLLOWING UNITS:
018-020: ALL UNITS 025,030: 460V UNITS
11. JUMPER PLUG REQUIRED WHEN MP NOT USED
* MM SIGNAL CONNECTION
1
2
3
~
1
3
2
OFM1
GRN/YEL
VOLTAGE
208/230/460/575
380
BLK
BLK
COOLER/PUMP HEATERS (208/230,230V)
~
WHT
OFM2
GRN/YEL
ZHBT
061
06A31
1
2
3
24
Page 25
HEAT
Fig. 6B — Typical Wiring Schematic, 30RAP018-030 Units — Control Wiring
a30-4966
SEE NOTES ON PAGE 24.
CWPI
SEE
NOTE 8
REMOTE
ON-OFF
SWITCH
(SEE NOTE
5)
DUAL
SETPOINT
J10A
J10B
RLY 11
RLY 9
RLY 10
RLY 5
RLY 6
RLY 7
RLY 8
RLY 1
RLY 2
RLY 3
RLY 4
RED
WHT
BLK
RED
BLK
WHT
MBB
LVT
20
19
LVT
17
11
13
14
15
16
LEN CCN
J1
PORT 2
PORT 1A
J12
6
7
J11
2
3
4
11
12
13
14
9
7
8
6
5
LVT
(+)
(COM)
(-)
SHIELD
UPC
NET +
1
NET -
2
N/C
3
N/C
4
SIGNAL
5
NET +
1
NET 2
2
SHIELD
3
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
1
10
2
11
3
12
4
13
5
14
6
15
7
16
8
17
9
18
10
19
11
20
12
21
13
22
14
23
15
24
16
25
17
26
18
27
BR
HEAT/BOILER FIELD
INSTALLED WIRING
BLK
RED
OFF
RED
RED
VIO
J13
BLK
1
WHT
2
RED
3
BRN
4
RED
5
BLK
6
WHT
7
RED
8
OPTION
J3
UPC OPT
CB1
3.2 AMPS
CB2
5.2 AMPS
TB4
ORN
5
RED
RED
RED
GRA
PNK
A2
SW2
RED
ORN
C2
ORN
B2
RED
TB4
7
XF
RED
BLK
TRAN1
SECONDARY 24V
X1
FU3
GRA
GRA
MLV-A
MLV ACCSY
FC1
PNK
SEE NOTE 7
ORN
TB4
RED
4
RED
RED
BLK
RED
ORN
HPS-A
BLK
BLK
BLK
ORN
GRA
SEE NOTE 11
SEE NOTE 11
VIO
RED
6
6
GRA
5
5
GRA
4
4
3
J6
HR
ALMR
3
2
2
VIO
1
1
BRN
LVT
J11
18
1
STORAGE TANK HEATER RELAY
ORN
PL1-2PL1-1
MP-A1
VIO
VIO
VIO
M1
M2
VIO
PL1-6PL1-5
MP-A2
VIO
M1
M2
VIO
LVT
J12
25
1
2
24
ORN
MAX LOAD-5VA SEALED
10VA INRUSH
ACCESSORY
RED
ORN
ORN
GRA
VIO
RED
FIOP OR
FIELD INSTALLED
OPTION
FIELD INSTALLED
MAX LOAD-5VA SEALED
10VA INRUSH
FC2
ALM
R
TNK
R
CHC
CA1
CA2
CWP
1
CWP
2
RED
TB1
X2
GRN/YEL
BRN
A2A1
A2A1
A2A1
A2A1
BRN
BRN
BRN
BRN
BRN
BRN
BRN
C
BRN
BRN
BRN
BRN
BRN
BRN
BRN
LVT
J12
5
21
BRN
BRN
BRN
BRN
A2A1
A2A1
A2A1
BRN
BRN
BRN
BRN
A2
A2
A2
A2
A2
A2
A2
C
C
C
A2
A2
C
A2
A2
MBB J1-2
UPC GND
CWFS 3
EXV J1-2
LVT J12-5
CHC
CA1
CWP1
CA2
FC2
FC1
FC3
TB1
TB1
TB1
CA2
CA1
TB1
CWP2
CWP1
TB4
4
RED
SEE NOTE 9
T2T1MP-A1
SEE NOTE 10
T2T1MP-A2
PL1-4
BRN
BRN
PL1-8
BRN
BRN
PL1-3
RED
RED
PL1-7
RED
RED
BRN
CWFS
4
2
10
10
WHT
1
RED
1
2
WHT
2
3
J3
9
ORN
9
J4
MAIN BASE
8
8
SW1
A1
ENABLE
RED
C1
B1
RED
GRA
GRA
13
RED
14
CWP2
13
VIO
14
CWP1
BRN
RED
BLK
WHT
RED
BLK
WHT
RED
LON
GND
NET
J4
1
2
BOARD
7
7
6
6
5
5
4
4
3
3
2
2
1
1
10
10
9
9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1
1
J9
J7
J8
J5
BLK
3
4
4
1
RED
1
2
WHT
2
3
BLK
3
4
4
5
BRN
5
6
RED
6
1
1
RED
2
2
ORN
3
3
BRN
4
4
RED
5
5
ORN
6
6
BRN
7
7
RED
8
8
ORN
9
9
BRN
10
10
RED
11
11
ORN
12
12
BRN
1
1
2
2
3
3
4
4
5
5
6
6
1
7
2
8
3
9
4
10
1
11
2
12
3
13
4
14
1
15
2
16
3
17
4
18
5
19
6
20
7
21
8
22
9
23
10
24
11
25
12
26
1
MARQUEE
RED
1
DISPLAY
2
WHT
2
3
BLK
3
4
4
5
RED
5
6
BRN
6
2
CSB
3
B2
1
2
CSB
3
A2
1
2
CSB
3
B1
1
2
CSB
3
A1
1
B
C
A
B
C
A
RGTA
OAT
EVAPORATOR ENTERING FLUID TEMP
EVAPORATOR LEAVING FLUID TEMP
+
DPTA
-
+
SPTA
-
LVT
J12 T55
3
4
23
22
T-55
SEN
ACCSY
SPACE TEMPERATURE ACCESSORY OR DUAL CHILLER LWT
RED
BLK
BLU
BLU
RED
BLK
RED
BLK
RED
BLK
RED
GRN
BLK
RED
GRN
BLK
BLK
WHT
RED
BLK
WHT
RED
BLK
WHT
RED
BLK
WHT
RED
BLK
WHT
RED
4
4
3
3
2
2
1
1
4
4
3
3
2
2
1
1
6
-
3
5
G
2
4
+
1
3
-
3
2
G
2
1
+
1
12345678
DARK = SWITCH LOCATION
4
4
3
3
2
2
1
1
4
4
3
3
2
2
1
1
ACCESSORY
J3
J4
J9
DGS OR
FIOP
J3
J4
FIOP/
MM
EXV
AUX
EMM
1
1
2
2
3
3
J7
4
4
5
5
PL-EXVA
BLK
1
1
BLK
YEL
2
2
WHT
3
3
J6
4
GRN
4
5
5
RED
7
-
VIO RED
7
8
J2
CH1
BRN BLK
8
1
CH11
RED RED
1
2
J6
-
BLK BLK
2
1
CH9
RED
1
2
J4
-
BLK
2
ON
OFF
J5
J7
J6
1
CH10
1
2
-
2
1
1
GRA
2
2
GRA
3
3
RED
4
4
RED
5
5
BLU
6
6
BLU
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
1
1
2
2
VIO
3
3
BRN
4
4
5
5
ORN
6
6
7
7
8
8
PNK
9
9
10
10
11
11
12
12
PL50-1
PL50-2
PL50-3
PL50-4
TO MM-A
J10
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
EXV-A
GRY
RED
DUS
DTT
LVT
1
2
ICE DONE
3
4
DLS STEP 1
5
6
DLS STEP 2
DEMAND
+
7
LIMIT
-
8
4-20mA
TEMP
9
+
RESET
-
4-20mA
COOLING
+
10
SETPOINT
-
4-20mA
25
Page 26
COMP A2
GRN/YEL
TRAN1
H2
H3
H4
SECONDARY 24V
RED
FC2
BLK-1
BLK-2
BLK-3
FU3
SW2
C1
A1
B1
1
2
3
H1
X1
CONNECT FOR APPROPRIATE PRIMARY VOLTAGE SEE TABLE 1
1
2
3
CB1A
11
12
13
TO FUSED
DISCONNECT
PER NEC
OPTIONAL
DISCONNECT
3.2 AMPS
CB3
1
2
3
T3
T1
T2
T3
T1
T2
3
2
1
LOW AMBIENT OPERATION (MOTORMASTER V) FIOP/ACCESSORY
GRN/YEL
GRN/YEL
XF
VIO
11 21
12
22
13 23
11 21
12 22
13 23
CA1
BLK
YEL
BLU
11 21
12 22
13 23
CA2
11
12
13
21
22
23
CCB-1
BLK
YEL
BLU
BLK
YEL
BLU
YEL
BLU BLK
YEL
BLU
BLK
11
12
13
21
22
23
CCB-2
BLK
YEL
BLK
380V,460V,575V
ONLY
BLU
YEL
BLU
GRN/YEL
OFM1
FC3
1
2
3
11 21
12
22
13 23
COMP B2
1
2
3
T3
T1
T2
T3
T1
T2
3
2
1
GRN/YEL
GRN/YEL
11 21
12 22
13 23
CB1
BLK
YEL
BLU
11 21
12 22
13 23
CB2
11
12
13
21
22
23
CCB-3
BLK
YEL
BLU
BLK
YEL
BLU
YEL
BLU BLK
YEL
BLU
BLK
11
12
13
21
22
23
CCB-4
BLK
YEL
380V,460V,575V
ONLY
208/230V ONLY
BLU
BLU
BLU
BLU BLU
YEL
YEL
YEL YEL
BLK
BLK
BLK BLK
BLK-1
BLK-2
BLK-3
BLK
YEL
BLU
BLK
YEL
BLU
YEL
BLUBLK
BRN
FU1
BLK
FU2
YEL
GRN/YEL
TRAN2
COM
RED
7
TB4
VIO
6
TB4
VIO
C
TB1
BLK
YEL
BRN
BRN
PRIMARY
PRIMARY
CONNECT FOR APPROPRIATE PRIMARY VOLTAGE SEE TABLE 2
X2
* MM SIGNAL CONNECTION
VOLTAGE
TB HZ
208/230/460/575
160
380
13A 60
FCB2/FB2
NOTES:
1. FACTORY WIRING IS IN ACCORDANCE WITH UL 1995 STANDARDS. ANY FIELD MODIFICATIONS OR ADDITIONS MUST BE IN COMPLIANCE WITH ALL APPLICABLE CODES.
2. USE 75
C MIN WIRE FOR FIELD POWER SUPPLY.
3. ALL FIELD INTERLOCK CONTACTS MUST HAVE A MIN RATING OF 2 AMPS @ 24VAC SEALED. SEE FIELD INTERLOCK WIRING.
4. COMPRESSOR AND FAN MOTORS ARE THERMALLY PROTECTED-­ THREE PHASE MOTORS PROTECTED AGAINST PRIMARY SINGLE PHASE CONDITIONS.
5. TERMINALS 13 & 14 OF LVT ARE FOR FIELD CONNECTION OF REMOTE ON-OFF. THE CONTACT MUST BE RATED FOR DRY CIRCUIT APPLICATION CAPABLE OF HANDLING A 5VDC 1 MA TO 20 MA LOAD.
6. FOR 500 SERIES UNIT OPERATION AT 208-3-60V LINE VOLTAGE, TRAN1 PRIMARY CONNECTIONS MUST BE MOVED TO TERMINALS H3 & H4.
10. MP-A1 NOT USED IN THE FOLLOWING UNITS: 035-045: ALL UNITS
11. MP-A2 NOT USED IN THE FOLLOWING UNITS: 035-045: ALL UNITS
12. MP-B1 NOT USED IN THE FOLLOWING UNITS: 035,040: ALL UNITS 045-060: 460V UNITS
13. MP-B2 NOT USED IN THE FOLLOWING UNITS: 035,040: ALL UNITS 045-060: 460V UNITS
14. JUMPER PLUG REQUIRED WHEN MP NOT USED
7. FOR 575-3-60V UNITS, FAN CIRCUIT BREAKER FCB2 IS REPLACED WITH FUSE BLOCK FB2.
SEE NOTE 7
BLK
BLU
YEL
VOLTAGE SERIES
TERMINAL
CONNECTIONS
FOR PRIMARY SIDE
575-3-60 100 H1 & H2
380-3-60 200 H1 & H2
230-3-60 500 H2 & H4
208-3-60 500 H3 & H4
460-3-60 600 H1 & H4
TABLE 1
UNIT VOLTAGE
REPLACE
WITH
FNQ-R-3.5
FU1 & FU2
FUSE
NUMBER
380-3-60
TRAN SIZE
200VA
FNQ-R-2.5
208/230-3-60
FNM-10
FU3 (24V)
380-3-60,460-3-60,575-3-60
200VA
208/230-3-60
VOLTAGE SERIES
TERMINAL
CONNECTIONS
FOR PRIMARY SIDE
575-3-60 100 COM & 575
380-3-60 200
230-3-60 500
208-3-60 500
460-3-60 600
TABLE 2
460-3-60
575-3-60
FNQ-R-2
FNQ-R-1.5
COM & 380
COM & 230
COM & 208
COM & 460
208
230
380
400
575 460
8. FOR UNITS WITH LOW AMBIENT MOTOR MASTER V FIOP/ACCESSORY, 030-050: FAN CONTACTOR FC1 IS REPLACED WITH MOTORMASTER RELAY MMR.
SECONDARY 24V
3.2 AMPS
CB4
RED
3
3
2
2
1
1
J2
BRN
RED
2
2
1
J1
1
3
3
EXV
BRN
RED
CWFS
CH-A2
BLU BLK
CH-B1
BLU BLK
CH-A1
BLU BLK
CH-B2
BLU BLK
GRN/YEL
OFM2
1
2
3
BLK-1
BLK-2
BLK-3
GRN/YEL
FC1
1
2
3
11 21
12
22
13 23
BLK-1
BLK-2
BLK-3
BLU
YEL
BLK
CWP1
CWP2
MS-CWP2
MS-CWP1
BLK
BLK
BLK
BLK
BLK
BLK
L3
L1
L2
CWP1 WATER PUMP
L3
L1
L2
CWP2 WATER PUMP
L1 T1
L2
T2
L3
T3
L1
L2
L3
T1
T2
T3
L1 T1
L2
T2
L3
T3
L1
L2
L3
T1
T2
T3
BLK
YEL
BLU
BLK
YEL
BLU
GRN/YEL
GRN/YEL
VOLTAGE SERIES
TERMINAL
CONNECTIONS
FOR PRIMARY SIDE
TERMINAL
CONNECTIONS FOR
SECONDARY SIDE
575-3-60 100 H1-H2 XF-X2
230-3-60 400,500 H2-H4 XF-X2
208-3-60 500 H3-H4 XF-X2
460-3-60 600 H1-H4 XF-X2
TRAN3
SECONDARY
115V
WHT
RESET
TEST
GRN-YEL
GFI-CO
FIOP/ACCESSORY
BRASS SCREW
SILVER SCREW
WHT
FU4
X3
X1
LOAD
LINE
BRASS SCREW
SILVER SCREW
BLK
2
2
XF
H4
H1
HF
H2
H3
BLK
1
FU6
RED
1
FU5
~
~
~
FU5 & FU6
500VA
FNM-6
FU4 (115V)
380-3-60,460-3-60,575-3-60
500VA
208/230-3-60
460-3-60,575-3-60
208/230-3-60,230-3-60
FNQ-R-2.5
FNQ-R-3.5
9. IF CHILLED WATER PUMP INTERLOCK IS USED,
REMOVE JUMPER FROM TERMINAL 11 TO 17 AND
CHILLED WATER PUMP FIOP
WIRE INTERLOCK CONTACT ACROSS TERMINALS 11 & 17.
050-060: 460V UNITS WITHOUT DIGITAL SCROLL
050-060: 460V UNITS
GRN/YEL
OFM3
OFM4
(055,060 ONLY)
(055,060 ONLY)
GRN/YEL
1
2
3
BLK-1
BLK-2
BLK-3
OFM4 (055,060)
OFM3 (035-050)
L1 T1
L2 T2
L3 T3
MMR
11 14
*1
2
YEL
VIO
MM-A
GRN/YEL
FC2
BLK-1
BLK-2
BLK-3
1
2
3
11 21
12
22
13 23
GRN/YEL
OFM1
FC1
1
2
3
11 21
12
22
13 23
BLK-1
BLK-2
BLK-3
BLK
YEL
BLU
BLK
YEL
BLU
FCB2/FB2
SEE NOTE 7
GRN/YEL
OFM2
1
2
3
BLK-1
BLK-2
BLK-3
OFM3
(055,060 ONLY)
(055,060 ONLY)
GRN/YEL
BLK
YEL
055,060: FAN CONTACTOR FC3 IS REPLACED WITH MOTORMASTER RELAY MMR..
208/230V ONLY
BLK
YEL
BLU
11
12
13
21
22
23
BLK
YEL
BLU
11
12
13
21
22
23
FB1
BLK
YEL
BLU
FB3
BLK
YEL
BLU
11
12
13
21
22
23
11
12
13
21
22
23
BLK
YEL
BLU
HIGH SCCR ONLY
FB1
BLK
YEL
BLU
FB3
BLK
YEL
BLU
11
12
13
21
22
23
11
12
13
21
22
23
BLK
YEL
BLU
HIGH SCCR ONLY
BLK
25
2
RED
FROM AUX-J4
YEL
BLUBLK
FB2 NONE
LP-CC-20575-3-60
LP-CC-20
380-3-60,460-3-60,575-3-60
NONE
208/230-3-60
KTK-R-15
380-3-60,460-3-60,575-3-60
NONE
KTK-R-20208/230-3-60
FB1
(NO MM)
FB1
(WITH MM)
LP-CC-20
380-3-60,460-3-60,575-3-60
NONE
208/230-3-60
FB3
3
3
2
2
1
1
J2
BRN
VIO
2
2
1
J1
1
3
3
MBB
BRN
RED
3
3
2
2
1
1
J2
2
J1
1
3
FIOP/ACCESSORY
EMM
BRN
RED
12
2
11
1
J1
DGS FIOP
AUX
2
1
3
2
1
UPC FIOP
UPC
GND
HOT
24VAC
BRN
VIO
42
86
BLK
YEL
COOLER/PUMP HEATERS (208/230,230V)
1
2
3
BLK
BLK
WHT
COOLER/PUMP HEATERS (380,460,575V)
3
2
BLK
BLK
~
~
~
~
WHT
~~
42
86
BLK
YEL
COOLER/PUMP HEATERS (208/230,230V)
1
2
3
BLK
BLK
WHT
COOLER/PUMP HEATERS (380,460,575V)
3
2
BLK
BLK
~
~
~
~
WHT
~~
VIO
BRN
BRN
BLU
31
240 1/4W
CHC
CHC
CHC
CHC
STANDARD
TERMINAL
BLOCK
PER NEC
TO FUSED DISCONNECT
21
22
23
TB1A
EQUIP GND
COMP A1
COMP B1
CSB-A1
CSB-A2
CSB-B1
CSB-B2
Fig. 7A — Typical Wiring Schematic, 30RAP035-060 Units — Power Wiring
a30-
5283
26
Page 27
LEGEND
TERMINAL BLOCK
X
TERMINAL (UNMARKED) TERMINAL (MARKED) SPLICE FACTORY WIRING FIELD WIRING ACCESSORY OR OPTION WIRING TO INDICATE COMMON POTENTIAL ONLY,NOT TO REPRESENT WIRING
X
9
9
7
7
8
8
4
6
4
6
RLY 9
5
5
1
3
1
3
RLY 11
2
2
A2A1
A2A1
ORN
3
12
1
10
2
11
4
13
MAX LOAD-5VA SEALED
10VA INRUSH
C
TB1
SW2
C2
A2
B2
9
18
10
19
8
17
11
12
13
14
20
21
22
23
6
15
7
16
5
14
15
16
17
18
24
25
26
27
5.2 AMPS
CB2
A2A1
PNK
A2A1
ACCSY ACCESSORY ALMR ALARM RELAY AUX AUXILIARY BR BOILER RELAY C CONTACTOR, COMPRESSOR CB CIRCUIT BREAKER CCB COMPRESSOR CIRCUIT BREAKER CH CRANKCASE HEATER CHC COOLER/PUMP HEATER CONTACTOR CO CONVENIENCE OUTLET COMP COMPRESSOR CSB CURRENT SENSOR BOARD CWFS CHILLED WATER FLOW SWITCH CWP CHILLED WATER PUMP CWPI CHILLED WATER PUMP INTERLOCK DGS DIGITAL SCROLL DLS DEMAND LIMIT SWITCH DPT DISCHARGE PRESSURE TRANSDUCER DTT DISCHARGE TEMPERATURE THERMISTOR DUS DIGITAL UNLOADER SOLENOID EMM ENERGY MANAGEMENT EWT ENTERING WATER TEMPERATURE EXV EXPANSION VALVE CONTROL BOARD FB FUSE BLOCK FC FAN CONTACTOR FCB FAN CIRCUIT BREAKER FIOP FACTORY INSTALLED OPTION FR FAN RELAY FU FUSE GND GROUND HPS HIGH PRESSURE SWITCH HR HEAT RELAY LVT LOW VOLTAGE TERMINAL LWT LEAVING WATER TEMPERATURE MBB MAIN BASE BOARD MLV MINIMUM LOAD VALVE MM MOTORMASTER MMR MOTORMASTER RELAY MP MODULAR MOTOR PROTECTOR MS MANUAL STARTER OAT OUTDOOR AIR THERMISTOR OFM OUTDOOR FAN MOTOR PL PLUG R RELAY RGT RETURN GAS TEMPERATURE RLY RELAY SAT SUPPLY AIR TEMPERATURE SCCR SHORT CIRCUIT CURRENT RATING SPT SUCTION PRESSURE TRANSDUCER SW SWITCH TB TERMINAL BLOCK TNKR STORAGE TANK HEATER RELAY TRAN TRANSFORMER UPC UNITARY PROTOCOL CONVERTER
RLY 10
J10A
J10B
RLY 5
RLY 6
RLY 7
RLY 8
RLY 1
RLY 2
RLY 3
RLY 4
12
11
10
9
8
7
6
5
4
3
2
1
26
25
24
23
22
17
16
15
14
13
12
11
10
9
8
7
6
10
9
8
7
6
5
4
3
2
1
8
8
3
1
3
1
3
1
6
2
4
2
4
2
12
1
2
3
4
5
6
7
8
9
10
11
1
2
3
4
5
6
12
11
10
9
8
7
3
4
4
3
2
2
1
1
BLK
WHT
RED
J9
21
20
19
18
10
9
8
7
6
5
4
5
4
3
2
1
4
2
1
3
5
RED
BRN
RED
WHT
BLK
RED
WHT
BLK
6
6
5
5
3
3
2
1
1
2
7
7
4
4
J7
MARQUEE DISPLAY
MAIN BASE
BOARD
J8
9
9
10
10
6
5
4
3
2
1
6
5
4
3
2
1
J6
FIOP/
M1
M2
SEE NOTE 14
M1
M2
M1
M2
M1
M2
ORN
GRA
A2A1
ORN
A2A1
VIO
A2A1
PNK
FC2
FC1
CB1
CB2
CHC
CA1
CA2
ORN
ORN
7
TB4
RED
SEE NOTE 14
SEE NOTE 14
SEE NOTE 14
RED
RED
RED
RED
BLU
PNK
ORN
VIO
PNK
RED
ORN
ORN
GRA
VIO
J5
GRA
6
6
5
5
RED
BRN
J4
1
2
3
4
5
6
1
2
3
4
5
6
BLK
WHT
RED
BRN
RED
CSB
B2
2
3
1
RED
ORN
BRN
CSB
A2
2
3
1
RED
ORN
BRN
CSB
B1
2
3
1
RED
ORN
BRN
CSB
A1
2
3
1
RED
ORN
BRN
EXV
4
3
2
1
4
3
2
1
J3
4
3
2
1
4
3
2
1
J4
RED
WHT
BLK
RED
WHT
BLK
ON
OFF
12345678
DARK = SWITCH LOCATION
DUS
3
2
1
3
2
1
6
5
4
3
2
1
J9
2
1
8
7
2
1
8
7
J2
J6
DTT
RED
WHT
BLK
DGS OR
MM
FIOP
MBB
BLK
RED
LVT
4
3
22
23
T-55 ACCSY
SEN
12
11
10
9
8
7
6
5
4
3
2
1
12
11
10
9
8
7
J7
EMM
4
3
2
1
4
3
2
1
J3
4
3
2
1
4
3
2
1
J4
RED
WHT
BLK
RED
WHT
BLK
12
11
10
9
8
7
6
5
4
3
2
1
12
11
10
9
8
7
J6
14
13
14
13
ACCESSORY
1
1
2
3
4
5
6
1
2
3
4
5
6
10
7
8
9
8
6
7
4
5
9
2
3
10
+
-
COOLING SETPOINT 4-20mA
LVT
8
1
3
2
5
4
7
6
(+)
(-)
(COM)
SHIELD
LEN CCN
1
2
3
1
2
3
4
5
NET +
NET 2
SHIELD
NET +
NET -
N/C
N/C
SIGNAL
PORT 1A
UPC
PORT 2
J3
1
2
LON
OPTION
GND
J4
NET
UPC OPT
BLK
WHT
RED
RED
BLK
WHT
RED
WHT
BLK
RED
BRN
RED
WHT
BLK
OAT
BLU
BLU
PNK
ORN
BRN
VIO
+
-
TEMP RESET 4-20mA
+
-
DEMAND LIMIT 4-20mA
LVT
2
1
24
25
ALM
R
LVT
1
18
C
TB1
BRN
MBB J1-2
T2T1MP-A1
T2T1MP-A2
T2T1MP-B1
T2T1MP-B2
SEE NOTE 10
SEE NOTE 11
SEE NOTE 12
SEE NOTE 13
3.2 AMPS
CB1
4
TB4
RED
RED
RED
BRN
UPC GND
BRN
CWFS 3
BRN
CB1
A2
BRN
LVT J12-5
BRN
CHC
A2
BRN
CA1
A2
BRN
TRAN1
SECONDARY 24V
RED
FU3
X1
XF
BRN
X2
GRN/YEL
5
TB4
RED
VIO RED
PL50-1
BRN BLK
PL50-2
RED RED
PL50-3
BLK BLK
PL50-4
BLK
RED
RGTB
BLK
RED
RGTA
2
1
2
1
RED
BLK
J4
CH1
-
CH11
-
CH9
-
-
+
G
-
+
G
2
1
2
1
J5
CH10
-
TO MM-A
SEE NOTE 8
BLK
BLU
EXV-B
5
4
3
2
1
5
4
3
2
1
WHT
BLK
RED
GRN
PL-EXVB
EXV-A
5
4
3
2
1
5
4
3
2
1
WHT
BLK
RED
GRN
PL-EXVA
J7
J6
RED
RED
BLK
GRY
YEL
BLK
YEL
GRY
FIOP OR
FIELD INSTALLED
OPTION
VIO
RED
FIELD INSTALLED
MAX LOAD-5VA SEALED
10VA INRUSH
A2A1
CWP
1
A2A1
CWP
2
BRN
CWP1
A2
MLV-A
GRA
BRN
MLV ACCSY
FR4
2
4
FR3
2
4
FR2
2
4
TAN
TAN
PNK
FR1
2
4
TAN
PNK
PNK
A2A1
BRN
PNK
FC2
A2
FC3
(055,060 ONLY)
RED
RED
4
TB4
ORN
RED
ACCESSORY STORAGE TANK HEATER RELAY
TNK
R
BLK
ORN
BRN
C
TB1
BRN
CWP2
A2
BRN
C
TB1
BRN
CA1
A2
BRN
CA2
A2
BRN
C
TB1
BRN
CB1
A2
BRN
CB2
A2
BRN
C
TB1
BRN
CWP1
A2
BRN
FC2
A2
BRN
CA2
A2
BRN
FC1
A2
BRN
FC3
A2
14
15
4
3
12
13
6
5
11
RED
RED
BLU
BLU
DLS STEP 2
DLS STEP 1
LVT
16
17
2
1
GRA
GRA
ICE DONE
SPTB
-
+
DPTB
-
+
A
C
B
A
C
B
GRN
RED
BLK
GRN
RED
BLK
SPTA
-
+
DPTA
-
+
A
C
B
A
C
B
GRN
RED
BLK
GRN
RED
BLK
BLK
RED
EVAPORATOR ENTERING FLUID TEMP
BLK
RED
EVAPORATOR LEAVING FLUID TEMP
SPACE TEMPERATURE ACCESSORY OR DUAL CHILLER LWT
3
4
4
3
2
2
1
1
BLK
WHT
RED
J3
14
13
RED
CWP2
RED
14
13
VIO
CWP1
VIO
BRN
VIO
BR
HR
ALMR
HEAT/BOILER FIELD
INSTALLED WIRING
RED
C1
A1
B1
OFF
3
2
16
13
6
4
15
7
5
17
9
8
14
REMOTE ON-OFF SWITCH
(SEE NOTE
5)
ENABLE
SW1
LVT
ORN
12
11
13
11
14
CWFS
DUAL
SETPOINT
LVT
7
6
19
20
GRA
TAN
RED
RED
RED
GRA
GRA
SEE
NOTE 9
(055,060 ONLY)
(055,060 ONLY)
(055,060 ONLY)
(055,060 ONLY)
SEE NOTE 8
LVT
5
21
BRN
FR110
ORN BRN
(055,060 ONLY)
FR210
GRA BRN
(055,060 ONLY)
FR310
VIO BRN
(055,060 ONLY)
FR410
PNK BRN
(055,060 ONLY)
MP-B1
VIO
VIO
PL2-2PL2-1
VIO
MP-A1
VIO
VIO
PL1-2PL1-1
VIO
MP-B2
VIO
VIO
PL2-6PL2-5
VIO
MP-A2
VIO
VIO
PL1-6PL1-5
VIO
BLU
BLK
BLK
HPS-B
J12 T55
J13
J1
J12
J11
PL1-3
RED
RED
PL1-4
BRN
BRN
PL1-7
RED
RED
PL2-3
RED
RED
PL2-7
RED
RED
PL1-8
BRN
BRN
PL2-4
BRN
BRN
PL2-8
BRN
BRN
BRN
GRA
GRA
BLK
BLK
BLK
HPS-A
J10
J11
BLK
4
WHT
2
J12
CWPI
HEAT
J12
AUX
Fig. 7B — Typical Wiring Schematic, 30RAP035-060 Units — Control Wiring
a30-5284
27
Page 28
CEPL130346-01
STATUS
LEN
J1
J2
J4
J3
J5
J6
J7
J8
J9
J10
CCN
RED LED - STATUS GREEN LED -
LEN (LOCAL EQUIPMENT NETWORK)
YELLOW LED ­CCN (CARRIER COMFORT NETWORK)
INSTANCE JUMPER
K11
K10 K9
K8
K7
K6
K5
K4
K3 K2
K1
Fig. 8 — Main Base Board
Fig. 9 — Enable/Off/Remote Contact Switch, and Emergency On/Off Switch Locations
SPT (T10) PART NO. 33ZCT55SPT
SENSOR
SEN
SEN
LVT
3
4
Fig. 10 — Typical Space Temperature
Sensor Wiring
T-55 SPACE SENSOR
CCN+
CCN GND
CCN-
TO CCN COMM 1 BUS (PLUG) AT UNIT
1
2
3
4
5
6
Fig. 11 — CCN Communications Bus Wiring
to Optional Space Sensor RJ11 Connector
a30-4967
a30-4968
28
Page 29
Energy Management Module (Fig. 12) — This
factory-installed option (FIOP) or field-installed accessory is used for the following types of temperature reset, demand limit, and/or ice features:
4 to 20 mA leaving fluid temperature reset (requires field-supplied 4 to 20 mA generator)
4 to 20 mA cooling set point reset (requires field­supplied 4 to 20 mA generator)
Discrete inputs for 2-step demand limit (requires field­supplied dry contacts capable of handling a 24 vac, 50 mA load)
4 to 20 mA demand limit (requires field-supplied 4 to 20 mA generator)
Discrete input for Ice Done switch (requires field­supplied dry contacts capable of handling a 24 vac, 50 mA load)
See Demand Limit and Temperature Reset sections on
pages 41 and 37 for further details.
CAUTION
Care should be taken when interfacing with other manufac­turer’s control systems due to possible power supply differences, full wave bridge versus half wave rectification. The two different power supplies cannot be mixed. ComfortLink™ controls use half wave rectification. A signal isolation device should be utilized if a full wave bridge signal generating device is used.
Loss-of-Cooler Flow Protection — A proof-of-
cooler flow device is factory installed in all chillers. It is recom­mended that proper operation of the switch be verified on a reg­ular basis.
Electronic Expansion Valves (EXV) — All units are
equipped from the factory with EXVs. Each refrigeration cir­cuit is also supplied with a factory-installed liquid line filter drier and sight glass.
The EXV is set at the factory to maintain 9° F (5.0° C) suc­tion superheat leaving the cooler by metering the proper amount of refrigerant into the cooler. The superheat set point is adjustable, but should not be adjusted unless absolutely necessary.
The EXV is designed to limit the cooler saturated suction temperature to 50 F (12.8 C). This makes it possible for unit to start at high cooler fluid temperatures without overloading the compressor.
Capacity Control — The control system cycles com-
pressors, digital scroll modulting solenoid (if equipped), and minimum load valve solenoids (if equipped) to maintain the user-configured leaving chilled fluid temperature set point. En­tering fluid temperature is used by the main base board (MBB) to determine the temperature drop across the cooler and is used in determining the optimum time to add or subtract capacity stages. The chilled fluid temperature set point can be automati­cally reset by the return fluid temperature, space, or outdoor-air temperature reset features. It can also be reset from an external 4 to 20-mA signal (requires energy management module FIOP or accessory).
The standard control has an automatic lead-lag feature built in which determines the wear factor (combination of starts and run hours) for each compressor. If all compressors are off and less than 30 minutes has elapsed since the last compressor was turned off, the wear factor is used to determine which
compressor to start next. If no compressors have been running for more than 30 minutes and the leaving fluid temperature is greater than the saturated condensing temperature, the wear factor is still used to determine which compressor to start next. If the leaving fluid temperature is less than the saturated con­densing temperature, then the control will start either compres­sor A1 or compressor B1 first, depending on the user-configu­rable circuit lead-lag value. For units with the minimum load control valve, the A circuit with the minimum load valve is al­ways the lead circuit. The A circuit is also always the lead for units with the digital compressor option. On units with the dig­ital scroll option, the A1 compressor operates continuously, providing close leaving chilled water control. For this reason, on/off cycling of the unit’s compressors is dramatically re­duced, which in turn reduces wear associated with compressor start/stop cycles.
The EXVs will provide a controlled start-up. During start­up, the low pressure logic will be bypassed for 2 allow for the transient changes during start-up. As additional stages of compression are required, the processor control will add them. See Table 19.
If a circuit is to be stopped, the compressor with the lowest wear factor will be shut off first except when a digital compres­sor is used. The digital compressor is always the last compres­sor to shut off.
The capacity control algorithm runs every 30 seconds. The algorithm attempts to maintain the Control Point at the desired set point. Each time it runs, the control reads the entering and leaving fluid temperatures. The control determines the rate at which conditions are changing and calculates 2 variables based on these conditions. Next, a capacity ratio is calculated using the 2 variables to determine whether or not to make any changes to the current stages of capacity. This ratio value ranges from –100 to +100%. If the next stage of capacity is a compressor, the control starts (stops) a compressor when the ratio reaches +100% (–100%). If installed, the minimum load valve solenoid will be energized with the first stage of capacity. Minimum load valve value is a fixed 30% in the total capacity calculation. The control will also use the minimum load valve solenoid as the last stage of capacity before turning off the last compressor. A delay of 90 seconds occurs after each capacity step change. Refer to Table 19.
MINUTES LEFT FOR START — This value is displayed only in the network display tables (using Service Tool, ComfortVIEW™ or ComfortWORKS represents the amount of time to elapse before the unit will start its initialization routine. This value can be zero without the machine running in many situations. This can include being unoccupied, ENABLE/OFF/REMOTE CONTACT switch in the OFF position, CCN not allowing unit to start, Demand Limit in effect, no call for cooling due to no load, and alarm or alert conditions present. If the machine should be running and none of the above are true, a minimum off time (DELY, see below) may be in effect. The machine should start normally once the time limit has expired.
MINUTES OFF TIME (Configuration DELY) — This user-configurable time period is used by the control to determine how long unit operation is delayed after power is applied/restored to the unit. Typically, this time period is configured when multiple machines are located on a single site. For example, this gives the user the ability to prevent all the units from restarting at once after a power failure. A value of zero for this variable does not mean that the unit should be running.
1
/2 minutes to
®
software) and
OPT2
29
Page 30
CEBD430351-0396-01C
TEST 1
CEPL130351-01
PWR
TEST 2
J1
J2
J4 J3
J5
J6
J7
LEN
STATUS
RED LED - STATUS
GREEN LED ­LEN (LOCAL EQUIPMENT NETWORK)
ADDRESS DIP SWITCH
Fig. 12 — Energy Management Module
LEAD/LAG DETERMINATION — This is a configurable choice and is factory set to be automatic for all units unless the unit is equipped with a digital scroll compressor or minimum
load, then circuit A is lead (Configuration The value can be changed to Circuit A or Circuit B leading as desired. Set at automatic, the control will sum the current num­ber of logged circuit starts and one-quarter of the current oper-
OPT2 LLCS).
ating hours for each circuit. The circuit with the lowest sum is started first. Changes to which circuit is the lead circuit and which is the lag are also made when total machine capacity is at 100% or when there is a change in the direction of capacity (increase or decrease) and each circuit’s capacity is equal.
CAPACITY CONTROL OVERRIDES — The following over­rides will modify the normal operation of the routine.
Deadband Multiplier Multiplier (Configuration
— The user configurable Deadband
SLCTZ.GN) has a default val-
ue of 1.0. The range is from 1.0 to 4.0. When set to other than
1.0, this factor is applied to the capacity Load/Unload Factor. The larger this value is set, the longer the control will delay be­tween adding or removing stages of capacity. Figure 13 shows how compressor starts can be reduced over time if the leaving water temperature is allowed to drift a larger amount above and below the set point. This value should be set in the range of 3.0 to 4.0 for systems with small loop volumes.
First Stage Override the control will modify the routine with a 1.2 factor on adding
— If the current capacity stage is zero,
the first stage to reduce cycling. This factor is also applied
when the control is attempting to remove the last stage of capacity.
Slow Change Override
— The control prevents the capacity stages from being changed when the leaving fluid temperature is close to the set point (within an adjustable deadband) and moving towards the set point.
Ramp Loading
tion
SLCTCRMP) limits the rate of change of leaving
fluid temperature. If the unit is in a Cooling mode and config-
— Ramp loading (Configura-
ured for Ramp Loading, the control makes 2 comparisons be­fore deciding to change stages of capacity. The control calcu­lates a temperature difference between the control point and leaving fluid temperature. If the difference is greater than 4° F (2.2° C) and the rate of change (°F or °C per minute) is more than the configured Cooling Ramp Loading value (CRMP), the control does not allow any changes to the current stage of capacity.
Low Entering Fluid Temperature Unloading
— When the entering fluid temperature is below the control point, the control will attempt to remove 25% of the current stages being used. If exactly 25% cannot be removed, the control removes an amount greater than 25% but no more than necessary. The lowest stage will not be removed.
Minimum Load Control control valve is energized only when one compressor is run­ning on circuit A. If the close control feature is enabled the
— If equipped, the minimum load
minimum load control valve may be used as needed to obtain leaving fluid temperature close to set point.
30
Page 31
Table 19 — Part Load Data Percent Displacement, Standard Units with Minimum Load Valve
47
46
45
44
43
42
41
0 200 400 600 800 1000
TIME (SECONDS)
2 STARTS
3 STARTS
DEADBAND EXAMPLE
LWT (F)
MODIFIED DEADBAND
STANDARD DEADBAND
8
7
6
5
LWT (C)
LEGEND
LWT — Leaving Water Temperature
Fig. 13 — Deadband Multiplier
30RAP UNIT SIZE
CONTROL
STEPS
CAPACITY STEPS CAPACITY %
% Displacement Circuit A Circuit B 010 1 100100 015 1 100100
018
020
025
030
035
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3 4 5
1
040
2 3 4 5
1
045
050
055
2 3 4 5
1 2 3 4 5
1 2 3 4 5
1
060
2 3 4 5
*Minimum Load Valve energized. NOTE: These capacity steps may vary due to different capacity
100 50
20*
100 50
24*
100 50
29*
100 50
32*
100 77 50 23
9*
100 73 50 23
11*
100 74 50 24
12*
100 75 50 25
14*
100 73 50 23
13*
100 75 50 25
16*
staging sequences.
100
100
100
100
54 46
47 53
47 53
50 50
46 54
50 50
31
Page 32
Cooler Freeze Protection
60
160
130
LEGEND
Fig. 14 — Operating Envelope for R-410A Compressor
SCT —
Saturated Condensing Temperature
SST —
Saturated Suction Temperature
a30-4969
— The control will try to prevent shutting the chiller down on a Cooler Freeze Protection alarm by removing stages of capacity. If the cooler fluid selected is Water, the freeze point is 34 F (1.1 C). If the cooler fluid selected is Brine, the freeze point is the Brine Freeze Point (Set
Points
FRZBR.FZ). This alarm condition (A207) only
references leaving fluid temperature and NOT Brine Freeze point. If the cooler leaving fluid temperature is less than the freeze point plus 2.0° F (1.1° C), the control will immediately remove one stage of capacity. This can be repeated once every 30 seconds.
Low Saturated Suction Protection
— The control will try to prevent shutting a circuit down due to low saturated suction conditions by removing stages of capacity. These circuit alert conditions (T116, T117) compare saturated suction tempera­ture to the configured Brine Freeze Point (Set
Points
FRZBR.FZ). The Brine Freeze point is a user-
configurable value that must be left at 34 F (1.1 C) for 100% water systems. A lower value may be entered for systems with brine solutions, but this value should be set according to the freeze protection level of the brine mixture. Failure to properly set this brine freeze point value may permanently damage the brazed plate heat exchanger. The control will initiate Mode 7 (Circuit A) or Mode 8 (Circuit B) to indicate a circuit’s capaci­ty is limited and that eventually the circuit may shut down.
Head Pressure Control — The main base board
(MBB) controls the condenser fans to maintain the lowest condensing temperature possible, and thus the highest unit efficiency. The MBB uses the saturated condensing tempera­ture input from the discharge pressure transducer and outside air temperature sensor to control the fans. If OAT is greater than 70 F before a circuit is starting, then all condenser fan stages will be energized. A fan stage is increased based on SCT (saturated condensing temperature). When the highest SCT is greater than the Fan On Set Point (Set
Points
HEADF. O N ), then an additional stage of fan will
170
be added to the current fan stage. Fan On Set Point (F. O N ) equals Head Set Point (Set Points
HEADH.DP) except
after a fan stage increase when the Head Set Point is increased by Fan Stage Delta (Set Points
HEADF. D L T ). A fan
stage is decreased when the SCTs of both circuits are less than the Fan Off Set Point (Set Points
HEAD F. O F F ) for
two minutes. Table 20 shows the number of fan stages, contac­tors energized and the fans that are on during the fan stage. Unit sizes 035 to 060 have common fan control. Figure 14 shows the location of each fan and compressor within the unit.
MOTORMASTER
®
V OPTION — Motormaster V is stan­dard on 30RAP010 and 015 size units. For all other units that need low-ambient operation, the lead fan on a circuit can be equipped with the Motormaster V head pressure controller op­tion or accessory. The controller is energized with the first fan stage and adjusts fan speed to maintain a SCT of 72 F (22.2 C). The first stage of fan operation is controlled by the Motormas­ter V controller. Refer to Fig. 15 for condenser fan layout infor­mation. The Motormaster is configured in the Motormaster Se­lect (Configuration
MM
MMR.S)
Operation of Machine Based on Control Method and Cooling Set Point Selection Set­tings —
configuration of the Control Method (Configura­tion uration
configured with Cooling Set Point Select set to 0 (single set point). With the control method set to 0, simply switching the Enable/Off/Remote Contact switch to the Enable or Remote Contact position (external contacts closed) will put the chiller in an occupied state. The control mode (Operating
Modes
Off and will be 5 (ON LOCAL) when in the Enable position or Remote Contact position with external contacts closed.
Machine On/Off control is determined by the
OPT2CTRL) and Cooling Set Point Select (Config-
SLCTCLSP) variables. All units are factory
MODE) will be 1 (OFF LOCAL) when the switch is
1
150
140
120
110
SCT (F)
100
90
80
70
60
50
40
30
-30 -20 -10 0 10 20 304050607080
SST (F)
32
Page 33
Table 20 — Fan Stages
Top View
Top View Top View
Sizes 010,015
Sizes 035-050 Sizes 055,060
CONTROL BOX
CONTROL BOX
CONTROL BOX
OFM1
OFM2
OFM3
OFM3
OFM4
OFM2
OFM1
OFM1
Top View Sizes 018-030
CONTROL BOX
OFM1
OFM2
Fig. 15 — 30RAP Condenser Fan Layout
a30-4970
30RAP UNIT SIZE
010,015 Stage 1 OFM1
018-030
035-050
055,060
Fan Stage Contactor Energized Fans Operating
Stage 1 Stage 2
Stage 1 Stage 2 Stage 3
Stage 1 Stage 2 Stage 3 Stage 4
Two other control methods are available for Machine On/
Off control: OCCUPANCY SCHEDULE (Configuration
CTRL = 2) — The main base board will use the operating schedules as defined under the Time Clock mode in the scroll­ing marquee display. These schedules are identical. The sched­ule number must be set to 1 for local schedule.
The schedule number can be set anywhere from 65 to 99 for operation under a CCN global schedule. The Enable/Off/ Remote Contact must be in the Enable or Remote Contact posi­tion. The control mode (Operating Modes 1 when the switch is Off. The control mode will be 3 when the Enable/Off/Remote Contact switch input is On and the time of day is during an unoccupied period. Similarly, the control
MODE) will be
mode will be 7 when the time of day is during an occupied period.
CCN CONTROL (Configuration An external CCN device such as Chillervisor System Manager controls the On/Off state of the machine. This CCN device
OPT2CTRL = 3) —
forces the variable ‘CHIL_S_S’ between Start/Stop to control the chiller. The control mode (Operating Modes
will be 1 when the switch is Off. The control mode will be 2 when the Enable/Off/Remote Contact switch input is On and
OPT2
MODE)
FAN STAGES
FC1
FC1,2
FC1 FC2
FC1,2
FC3 FC1,3 FC3,2
FC1,2,3
OFM1
OFM1,2
OFM3
OFM1,2
OFM1,2,3
OFM4
OFM4,3
OFM4,1,2
OFM1,2,3,4
the CHIL_S_S variable is ‘Stop.’ Similarly, the control mode will be 6 when the CHIL_S_S variable is ‘Start.’
Table 20 illustrates how the control method and cooling set point select variables direct the operation of the chiller and the set point to which it controls. The illustration also shows the ON/OFF state of the machine for the given combinations.
Cooling Set Point Select
SINGLE — Unit operation is based on Cooling Set Point 1 (Set Points
DUAL SWITCH — Unit operation is based on Cooling Set Point 1 (Set Points Point switch contacts are open and Cooling Set Point 2 (Set
Points
DUAL CCN OCCUPIED — Unit operation is based on Cooling Set Point 1 (Set Points Occupied mode and Cooling Set Point 2 (Set
Points
configured under the local occupancy schedule accessible only from CCN. Schedule Number in Table SCHEDOVR (See Ap­pendix B) must be configured to 1. If the Schedule Number is set to 0, the unit will operate in a continuous 24-hr Occupied mode. Control method must be configured to 0 (switch). See Table 21.
COOLCSP.1).
COOLCSP.1) when the Dual Set
COOLCSP.2) when they are closed.
COOLCSP.1) during the
COOLCSP.2) during the Unoccupied mode as
33
Page 34
Table 21 — Control Methods and Cooling Set Points
ENTER
ENTER
ESCAPE
CONTROL
TYPE
(CTRL)
0 (switch)
2 (Occupancy)
3 (CCN)
*Dual set point switch input used. CSP1 used when switch input is open. CSP2 used when switch input is closed.
†Cooling set point determined from 4 to 20 mA input to energy management module (EMM) to terminals TB6-3,5.
OCCUPANCY
STATE
Occupied ON,CSP1 ON* ON,CSP1 ON† Unoccupied ON,CSP1 ON* ON,CSP2 ON Occupied ON,CSP1 ON* Illegal ON† Unoccupied OFF OFF Illegal OFF Occupied ON,CSP1 ON* ON,CSP1 ON† Unoccupied ON,CSP1 ON* ON,CSP2 ON†
0
(single)
4 TO 20 mA INPUT — Unit operation is based on an external 4 to 20 mA signal input to the Energy Management Module (EMM).
Low Sound Mode Operation — All models are fac-
tory configured with the Low Sound Mode disabled. In the Configuration mode under sub-mode OPT2, items for Low Sound Mode Select (Configuration Sound Start Time (Configuration
OPT2LS.MD), Low
OPT2LS.ST), Low
Sound End Time (ConfigurationOPT2LS.ND) and Low Sound Capacity Limit (Configuration
OPT2LS.LT) are
factory configured so that the chiller always runs as quietly as possible. This results in operation at increased saturated con­densing temperature. As a result, some models may not be able to achieve rated efficiency. For chiller operation at rated effi­ciency, disable the low sound mode or adjust the low sound mode start and stop times accordingly or set both times to 00:00 for rated efficiency operation 24 hours per day. In addi­tion, the low sound capacity limit can be used to reduce overall chiller capacity, if required, by limiting the maximum to a user­configured percentage.
Heating Operation — The chiller can be used for pump
outputs or optional factory-installed hydronic system operation
COOLING SET POINT SELECT (CLSP)
1
(dual, switch)
(dual, occ)
under the COMP mode will stay on for 10 minutes if there is no keypad activity. Compressors will stay on until they are turned off by the operator. The Service Test mode will remain enabled for as long as there is one or more compressors run­ning. All safeties are monitored during this test and will turn a compressor, circuit or the machine off if required. Any other mode or sub-mode can be accessed, viewed, or changed during the TEST mode. The MODE item (Run Status display “0” as long as the Service mode is enabled. The TEST sub-mode value must be changed back to OFF before the chill­er can be switched to Enable or Remote contact for normal operation.
Optional Factory-Installed Hydronic Pack­age —
specific steps should be followed for proper operation.
pre-wired into the main unit power supply/starter. In order to check proper pump rotation, use the Service Test function to test the condenser fans and observe them for proper rotation. If fans turn correctly, the pumps will rotate correctly. Clockwise rotation of the pump motor cooling fans can also be used to de­termine that pumps are rotating correctly.
If the chiller has factory-installed chilled fluid pumps,
The pump(s) in the hydronic package come factory
can be utilized for heating applications. The heating mode is activated when the control sees a field-supplied closed switch
CAUTION
input to terminal block LVT-19,20. The control locks out cool­ing when the heat relay input is seen. A field-supplied boiler re­lay connection is made using heat relay and alarm relay con­tacts. Factory-installed ‘BOILER’ connections exist in the con­trol panel near LVT for these applications. Alarms and alerts A189 through A202 are active during heating operation.
Service Test (See Table 4) — Both main power and
control circuit power must be on.
The Service Test function should be used to verify proper operation of condenser fan(s), compressors, minimum load valve solenoid (if installed), cooler pump(s), EXVs, and re­mote alarm relay. To use the Service Test mode, the Enable/ Off/Remote Contact switch must be in the OFF position. Use the display keys and Table 4 to enter the mode and display TEST. Press twice so that OFF flashes. Enter the password if required. Use either arrow key to change the TEST value to the ON position and press . Press and the button to enter the OUTS or COMP sub-mode.
Test the condenser fans, cooler pump(s) and alarm relay by changing the item values from OFF to ON. These discrete outputs are then turned off if there is no keypad activity for 10 minutes. Use the arrow keys to select the desired percentage when testing expansion valves and Motormaster When testing compressors, lead compressor must be started first. All compressor outputs can be turned on, but the control will limit the rate by staging one compressor per minute. Com­pressor unloaders and hot gas bypass relays/solenoids (if in-
®
V controller.
Operation of pump in wrong direction, even for a few seconds, can cause irreversible damage to pump impeller and housing. Always verify correct wiring/pump rotation before operation.
Use Service Test function to test operation of pumps. Verify that the flow switch input is made when the pump is running. For dual pump hydronic systems, the control only uses one pump at a time. Consult the Installation Instructions supplied with this chiller and use the circuit setter balancing valve installed in hydronic package to adjust fluid flow rate.
Cooler Pump Control — The AquaSnap® 30RAP ma-
chines equipped with a factory-installed pump package are configured with the Cooler Pump Control (Configura-
tion
OPT1CPC) = ON.
Machines not equipped with a pump package are config­ured with the cooler pump control OFF. It is recommended that the machine control the chilled water pump. If not, a 5-minute time delay is required after the command to shut the machine down is sent before the chilled water pump is turned off. This is required to maintain water flow during the shutdown period of the machine.
With or without this option enabled, the cooler pump relay will be energized when the machine enters an ON status (i.e., On Local, On CCN, On Time). An A207 - Cooler Freeze Protection Alarm, will energize the cooler pump relay also, as an override. The cooler pump relay will remain energized if the machine is in MODE 10 – Minimum Off Time.
stalled) can be tested with the compressors on or off. The relays
2
3
(4 to 20 mA)
VIEW) will
34
Page 35
Cooler Pump Sequence of Operation — At any-
time the unit is in an ON status, as defined by the one of the following conditions, the cooler pump relay will be enabled.
1. The Enable-Off-Remote Switch in ENABLE, (CTRL=0).
2. Enable-Off-Remote Switch in REMOTE with a Start-Stop remote contact closure (CTRL=0).
3. An Occupied Time Period from an Occupancy Schedule in combination with items 1 or 2 (CTRL=2).
4. A CCN Start-Stop Command to Start in combination with items 1 or 2 (CTRL=3).
As stated before, there are certain alarm conditions and Operating Modes that will turn the cooler pump relay ON. This sequence will describe the normal operation of the pump control algorithm.
When the unit cycles from an “On” state to an “Off” state, the cooler pump output will remain energized for the Cooler Pump Shutdown Delay (Configuration This is configurable from 0 to 10 minutes. The factory default is 1 minute.
NO INTEGRAL PUMP — SINGLE EXTERNAL PUMP CONTROL — With a single external pump, the following options must be configured:
• Cooler Pump Control (Configuration
OFF.
• Cooler Pump 1 Enable (Configuration
PM1E) = NO.
• Cooler Pump 2 Enable (Configuration
PM2E) = NO.
The maximum load allowed for the Chilled Water Pump Starter is 5 VA sealed, 10 VA inrush at 24 volts. The starter coil is powered from the chiller control system. The starter should be wired between LVT-25 and LVT-21. If equipped, the field­installed chilled water pump starter auxiliary contacts should be connected in series with the chilled water flow switch.
The Cooler Pump Relay will be energized when the machine is “On.” The chilled water pump interlock circuit consists of a chilled water flow switch and a field-installed chilled water pump interlock. If the chilled water pump inter­lock circuit does not close within five (5) minutes of starting, an A200 — Cooler Flow/Interlock Failed to Close at Start-Up Alarm will be generated and chiller will not be allowed to start.
If the chilled water pump interlock or chilled water flow switch opens for at least three (3) seconds after initially being closed, an A201 — Cooler Flow/Interlock Contacts Opened During Normal Operation Alarm will be generated and the ma­chine will stop.
NO INTEGRAL PUMP — DUAL EXTERNAL PUMP CONTROL — With two external pumps, the following options must be configured:
• Cooler Pump Control (Configuration
ON.
• Cooler Pump 1 Enable (Configuration
PM1E) = YES.
• Cooler Pump 2 Enable (Configuration
PM2E) = YES.
The maximum load allowed for the Chilled Water Pump Starters is 5 VA sealed, 10 VA inrush at 24 volts. The starter coil is powered from the chiller control system. The starter for Chilled Water Pump 1 should be wired between LVT-25 and LVT-21. The starter for Chilled Water Pump 2 should be wired between LVT-24 and LVT-21. A field-installed chilled water pump interlock for each pump must be connected to each pump’s interlock points on the main base board. The chilled water pump 1 interlock, CWP1, must be connected to MBB­J7-1 and –2. The chilled water pump 2 interlock, CWP2, must be connected to MBB-J7-3 and –4. The chilled water pump
OPT1PM.DY).
OPT1CPC) =
OPT1CPC) =
OPT1
OPT1
OPT1
OPT1
interlock contacts should be rated for dry circuit application capable of handling 5 vdc at 2 mA.
SINGLE INTEGRAL PUMP CONTROL — With a single pump, the following options must be configured:
• Cooler Pump Control (Configuration ON.
• Cooler Pump 1 Enable (Configuration
PM1E) = YES.
• Cooler Pump 2 Enable (ConfigurationOPT1
PM2E) = NO.
With a single integral pump, the Cooler Pump Starter will
be energized when the machine is occupied. As part of the factory-installed package, an auxiliary set of contacts is wired to the MBB to serve as Chilled Water Pump Interlock. When the mechanical cooling is called for, the pump interlock and flow switch is checked. If the circuits are closed, the machine starts its capacity routine. If the auxiliary contact interlock does not close within 25 seconds of the ON command, a T190 — Cooler Pump 1 Aux Contacts Failed to Close at Start-Up Alert will be generated and the pump shut down. The unit will not be allowed to start. If the chilled water flow switch does not close within one (1) minute, two alarms will be generated. A T192 — Cooler Pump 1 Failed to Provide Flow at Start-Up Alert and an A200 — Cooler Flow/Interlock Failed to Close at Start-Up Alarm will be generated and chiller will not be al­lowed to start.
If the chilled water flow switch opens for at least 3 seconds
after initially being closed, a T196 — Flow Lost While Pump 1 Running Alert and an A201 — Cooler Flow/Interlock Contacts Opened During Normal Operation Alarm will be generated and the machine will stop.
If the control detects the chilled water pump interlock open
for 25 seconds after initially being closed, a T194 — Cooler Pump 1 Contacts Opened During Normal Operation Alert is generated and the unit is shut down.
If the control detects the chilled water flow switch circuit
closed for at least 5 minutes with the pump output OFF, an A202 — Cooler Pump Interlock Closed When Pump is Off Alarm will be generated and the unit will not be allowed to start.
If the control detects that the chilled water pump auxiliary
contacts are closed for at least 25 seconds while the pump is OFF, a T198 — Cooler Pump 1 Aux Contacts Closed While Pump Off Alert is generated. The chiller will not be allowed to start.
If the control starts a pump and the wrong interlock circuit
closes for at least 20 seconds, an A189 — Cooler Pump and Aux Contact Input Miswire Alarm will be generated. The unit will be prevented from starting.
As part of a pump maintenance routine, the pump can be
started to maintain lubrication of the pump seal. To utilize this function, Cooler Pmp Periodic Start (Configuration
PM.P.S) must be set to YES. This option is set to NO as the factory default. With this feature enabled, if the pump is not op­erating, it will be started and operated for 2 seconds starting at 14:00 hours. If the pump is operating, this routine is skipped. If the pump has failed and an Alarm/Alert condition is active, the pump will not start that day.
DUAL INTEGRAL PUMP CONTROL — With a dual inte­gral pump package, the following options must be configured:
• Cooler Pump Control (Configuration
ON.
• Cooler Pump 1 Enable (Configuration
PM1E) = YES.
• Cooler Pump 2 Enable (Configuration
PM2E) = YES.
Pump Start Selection is a field-configurable choice. Cooler Pump Select (Configuration defaulted to 0 (Automatic). This value can be changed to 1
35
a30-4979
OPT1PM.SL) is factory
OPT1CPC) =
OPT1CPC) =
OPT1
OPT1
OPT1
OPT1
Page 36
(Pump 1 Starts First) or 2 (Pump 2 Starts First). If PM.SL is 0 (Automatic), the pump selection is based on two criteria: the alert status of a pump and the operational hours on the pump. If a pump has an active Alert condition, it will not be considered for the lead pump. The pump with the lowest operational hours will be the lead pump. A pump is selected by the control to start and continues to be the lead pump until the Pump Changeover Hours (Configuration Lead Pump (Run StatusVIEWLD.PM) indicates the pump that has been selected as the lead pump: 1 (Pump 1), 2 (Pump 2), 3 (No Pump). The Pump Changeover Hours is facto­ry defaulted to 500 hours. Regardless of the Cooler Pump Se­lection, any pump that has an active alert will not be allowed to start.
With the dual integral pump package, the Cooler Pump Starter will be energized when the machine is in an occupied period. As part of the factory-installed package, an auxiliary set of contacts is wired to the MBB to serve as Chilled Water Pump Interlock, one set for each pump to individual channels on the MBB. With a call for mechanical cooling, the specific pump interlock and flow switch are checked. If the circuits are closed, the machine starts its capacity routine. If Pump 1 starts and the auxiliary contact interlock does not close within 25 seconds of the ON command, a T190 — Cooler Pump 1 Aux Contacts Failed to Close at Start-Up Alert will be generated and the pump shut down. The unit will not be allowed to start. If the chilled water flow switch does not close within 1 minute, two alarms will be generated. A T192 — Cooler Pump 1 Failed to Provide Flow at Start-Up Alert and an A200 — Cooler Flow/ Interlock Failed to Close at Start-Up Alarm will be generated and chiller will not be allowed to start. In either fault case listed above, Pump 2 will be commanded to start once Pump 1 has failed.
If Pump 2 starts and the auxiliary contact interlock does not close within 25 seconds of the ON command, a T191 — Cooler Pump 2 Aux Contacts Failed to Close at Start-Up Alert will be generated and the pump shut down. The unit will not be allowed to start. If the chilled water flow switch does not close within one (1) minute, two alarms will be generated. A T193 — Cooler Pump 2 Failed to Provide Flow at Start-Up Alert and an A200 — Cooler Flow/Interlock Failed to Close at Start-Up Alarm will be generated and chiller will not be allowed to start. In either fault case listed above, Pump 1 will be commanded to start once Pump 2 has failed.
If the chilled water flow switch opens for at least 3 seconds after initially being closed, a T196 — Flow Lost While Pump 1 Running Alert or T197 — Flow Lost While Pump 2 Running Alert for the appropriate pump and an A201 — Cooler Flow/ Interlock Contacts Opened During Normal Operation Alarm will be generated and the machine will stop. If available, the other pump will be started. If flow is proven, the machine will be allowed to restart.
If the chilled water pump interlock opens for 25 seconds after initially being closed is detected by the control, the appro­priate T194 — Cooler Pump 1 Contacts Opened During Nor­mal Operation Alert or T195 — Cooler Pump 2 Contacts Opened During Normal Operation Alert is generated and the unit is shut down. If available, the other pump will be started. If flow is proven, the machine will be allowed to restart.
If the control detects that the chilled water flow switch circuit is closed for at least 5 minutes with the pump output OFF, an A202 — Cooler Pump Interlock Closed When Pump is Off Alarm will be generated and the unit will not be allowed to start.
If the control detects that the chilled water pump auxiliary contacts are closed for at least 25 seconds while the pump is OFF, the appropriate T198 — Cooler Pump 1 Aux Contacts Closed While Pump Off or Alert T199 — Cooler Pump 2 Aux Contacts Closed While Pump Off Alert is generated. The chiller will not be allowed to start.
OPT1PM.DT) is reached. The
If the control starts a pump and the wrong interlock circuit closes for at least 20 seconds, an A189 – Cooler Pump and Aux Contact Input Miswire Alarm will be generated. The unit will be prevented from starting.
The control will allow for pump changeover. Two methods will change the pump sequence. Before the changeover can occur, the unit must be at Capacity Stage 0. During changeover the chilled water flow switch input is ignored for 10 seconds to avoid a nuisance alarm.
With Cooler Pump Select (Configuration PM.SL) set to 0 (Automatic) and when the differential time limit Pump Changeover Hours (Configuration
PM.DT) is reached, the lead pump will be turned OFF. Ap­proximately one (1) second later, the lag pump will start. Manu­al changeover can be accomplished by changing Rotate Cooler Pump Now (Configuration the machine is at Capacity Stage 0 and the differential time limit Pump Changeover Hours (PM.DT) is reached. If the PM.DT is not satisfied, the changeover will not occur. With the machine at Capacity Stage 0, the pumps would rotate automatically as part of the normal routine.
With Cooler Pump Select (PM.SL) set to 1 (Pump 1 Starts First) or 2 (Pump 2 Starts First), a manual changeover can be ac­complished by changing PM.SL only. The machine Remote­Off-Enable Switch must be in the OFF position to change this variable. The Rotate Cooler Pump Now (ROT.P) feature does not work for these configuration options.
As part of a pump maintenance routine, the pumps can be started to maintain lubrication to the pump seal. To utilize this function, Cooler Pmp Periodic Start (Configuration
PM.PS) must be set to YES. This option is set to NO as the factory default. If feature is enabled and the pump(s) are not operating, then the pumps will be operated every other day for 2 seconds starting at 14:00 hours. If a pump has failed and has an active Alert condition, it will not be started that day.
OPT1ROT.P) to YES only if
OPT1
OPT1
OPT1
Configuring and Operating Dual Chiller Con­trol — The dual chiller routine is available for the control of
two units supplying chilled fluid on a common loop. This control algorithm is designed for parallel fluid flow arrangement only. One chiller must be configured as the master chiller, the other as the slave. An additional leaving fluid temperature thermistor (Dual Chiller LWT) must be installed as shown in Fig. 16 and 17 and connected to the master chiller. Refer to Sen­sors section, page 20, for wiring. The CCN communication bus must be connected between the two chillers. Connections can be made to the CCN screw terminals on LVT. Refer to Carrier Comfort Network mation. Configuration examples are shown in Tables 22 and 23.
Refer to Table 22 for dual chiller configuration. In this example the master chiller will be configured at address 1 and the slave chiller at address 2. The master and slave chillers must reside on the same CCN bus (Configuration
CCNB) but cannot have the same CCN address (Configu-
ration have Lead/Lag Chiller Enable (Configuration
uration
the master chiller and SLVE for the slave. Also in this example, the master chiller will be configured to use Lead/Lag Balance Select (Configuration ance Delta (Configuration chiller run-times weekly. The Lag Start Delay (Configura-
tion
will prevent the lag chiller from starting until the lead chiller has been at 100% capacity for the length of the delay time. Par­allel configuration (Configuration only be configured to YES. The variables LLBL, LLBD and
LLDY are not used by the slave chiller.
CCNCCNA). Both master and slave chillers must
LLEN) configured to ENBL. Master/Slave Select (Config-
RSETLLDY) feature will be set to 10 minutes. This
®
Interface section, page 19, for wiring infor-
CCN
RSET
RSET MSSL) must be configured to MAST for
RSETLLBL) and Lead/Lag Bal-
RSETLLBD) to even out the
RSETPARA) can
36
Page 37
Table 22 — Dual Chiller Configuration (Master Chiller Example)
ENTER
ENTER
ESCAPE
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
SUB-MODE ITEM KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENTS
DISP
UNIT
OPT1
CTRL CONTROL METHOD
OPT2
CCN
CTRL 0 SWITCH DEFAULT 0
OPT2
CCN
CCNA 1 CCN ADDRESS DEFAULT 1
CCNB
CCNB 0 CCN BUS NUMBER DEFAULT 0
CCN
RSET
PROCEED TO
SUBMODE RESET
CRST COOLING RESET TYPE
LLEN LEAD/LAG CHILLER ENABLE 15 ITEMS
LLEN DSBL SCROLLING STOPS
DSBL VALUE FLASHES
ENBL SELECT ENBL
LLEN ENBL LEAD/LAG CHILLER ENABLE CHANGE ACCEPTED
LLEN
RSET
MSSL MASTER /SLAVE SELECT
MSSL MAST MASTER /SLAVE SELECT DEFAULT MAST
MSSL
SLVA SLAVE ADDRESS
SLVA 0 SCROLLING STOPS
0 VALUE FLASHES
2 SELECT 2
SLVA 2 SLAVE ADDRESS CHANGE ACCEPTED
SLVA
LLBL LEAD/LAG BALANCE SELECT
LLBL 0 SCROLLING STOPS
0 VALUE FLASHES
2 SELECT 2 - Automatic
37
Page 38
Table 22 — Dual Chiller Configuration (Master Chiller Example) (cont)
ENTER
ESCAPE
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
ESCAPE
ENTER
MASTER CHILLER
SLAVE
CHILLER
LEAVING FLUID
RETURN FLUID
THERMISTOR WIRING*
INSTALL DUAL CHILLER LWT LEAVING FLUID TEMPERATURE THERMISTOR (T10) HERE
*Depending on piping sizes, use either:
• HH79NZ014 sensor/10HB50106801 well (3-in. sensor/well)
• HH79NZ029 sensor/10HB50106802 well (4-in. sensor/well)
Fig. 16 — Dual Chiller Thermistor Location
A
B
1/4 N.P.T.
0.505/0.495
0.61 DIA
6” MINIMUM
CLEARANCE FOR
THERMISTOR
REMOVAL
Fig. 17 — Dual Leaving Water Thermistor Well
PA RT
NUMBER
DIMENSIONS in. (mm)
A B 10HB50106801 3.10 (78.7) 1.55 (39.4) 10HB50106802 4.10 (104.1) 1.28 (32.5)
SUB-MODE ITEM KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENTS
LLBL 2 LEAD/LAG BALANCE SELECT CHANGE ACCEPTED
LLBL
LLBD LEAD/LAG BALANCE DELTA
LLBD 168 LEAD/LAG BALANCE DELTA DEFAULT 168
LLBD
LLDY LAG START DELAY
RSET
NOTES:
1. Master Control Method (CTRL) can be configured as 0-Switch, 2-Occupancy or 3-CCN.
2. Parallel Configuration (PARA) cannot be changed.
LLDY 5 SCROLLING STOPS
5 VALUE FLASHES
10 SELECT 10
LLDY 10 LAG START DELAY CHANGE ACCEPTED
LLDY
RSET
PARA YES MASTER COMPLETE
Dual chiller start/stop control is determined by configura-
tion of Control Method (Configuration
OPT1CTRL) of
the Master chiller. The Slave chiller should always be config­ured for CTRL=0 (Switch). If the chillers are to be controlled by Remote Contacts, both Master and Slave chillers should be enabled together. Two separate relays or one relay with two sets of contacts may control the chillers. The Enable/Off/ Remote Contact switch should be in the Remote Contact position on both the Master and Slave chillers. The Enable/Off/ Remote Contact switch should be in the Enable position for CTRL=2 (Occupancy) or CTRL=3 (CCN Control).
Both chillers will stop if the Master chiller Enable/Off/ Remote Contact switch is in the Off position. If the Emergency Stop switch is turned off or an alarm is generated on the Master chiller the Slave chiller will operate in a Stand-Alone mode. If the Emergency Stop switch is turned off or an alarm is generated on the Slave chiller the Master chiller will operate in a Stand-Alone mode.
The master chiller controls the slave chiller by changing its Control Mode (Run Status ing setpoint or Control Point (Run Status
VIEWSTAT) and its operat-
VIEWCT.PT).
Temperature Reset — The control system is capable of
handling leaving-fluid temperature reset based on return cooler fluid temperature. Because the change in temperature through the cooler is a measure of the building load, the return tempera­ture reset is in effect an average building load reset method. The control system is also capable of temperature reset based on outdoor-air temperature (OAT), space temperature (SPT), or from an externally powered 4 to 20 mA signal. Accessory sen­sors must be used for SPT reset (33ZCT55SPT). The energy management module (EMM) must be used for temperature reset using a 4 to 20 mA signal. See Tables 24 and 25.
38
Page 39
Table 23 — Dual Chiller Configuration (Slave Chiller Example)
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
ESCAPE
SUB-MODE ITEM KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENTS
DISP
UNIT
OPT1
CTRL CONTROL METHOD
OPT2
CCN
CTRL 0 SWITCH DEFAULT 0
OPT2
CCN
CCNA
CCNA 1 CCN ADDRESS SCROLLING STOPS
1 VALUE FLASHES
2
SELECT 2
(SEE NOTE 1)
CCNA 2 CCN ADDRESS CHANGE ACCEPTED
CCN
CCNB 0 CCN BUS NUMBER
DEFAULT 0
(SEE NOTE 2)
CCN
RSET
PROCEED TO
SUBMODE RSET
CRST COOLING RESET TYPE
LLEN LEAD/LAG CHILLER ENABLE 15 ITEMS
LLEN DSBL SCROLLING STOPS
DSBL VALUE FLASHES
ENBL SELECT ENBL
LLEN ENBL LEAD/LAG CHILLER ENABLE CHANGE ACCEPTED
LLEN
RSET
MSSL MASTER /SLAVE SELECT
MSSL MAST SCROLLING STOPS
MAST VALUE FLASHES
SLVE SELECT SLVE
MSSL SLVE MASTER /SLAVE SELECT CHANGE ACCEPTED
MSSL
RSET SLAVE COMPLETE
NOTES:
1. Slave Control Method (CTRL) must be configured for 0.
2. Slave CCN Address (CCNA) must be different than Master.
3. Slave CCN Bus Number (CCNB) must be the same as Master
4. Slave does not require SLVA, LLBL, LLBD, or LLDY to be configured.
39
Page 40
Table 24 — 4 to 20 mA Reset
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
SUB-MODE
RSET
NOTE: The example above shows how to configure the chiller for 4 to 20 mA reset. No reset will occur at 4.0 mA input, and a 5.0 F reset will occur at 20.0 mA. An EMM is required.
KEYPAD
ENTRY
ITEM DISPLAY
CRST 1
MA.DG
5.0 F
(2.8 C)
ITEM
EXPANSION
COOLING RESET
TYPE
DEGREES COOL
RESET
Table 25 — Menu Configuration of 4 to 20 mA Cooling Set Point Control
MODE
(RED LED)
KEYPAD
ENTRY
SUB-MODE
DISP
UNIT
OPT1
OPT2
HP.A
HP.B
EXV.A
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
0 = no reset 1 = 4 to 20 mA input 2 = Outdoor air temp 3 = Return Fluid 4 = Space Temperature
Default: 0° F (0° C) Reset at 20 mA Range: –30 to 30 F (–16.7 to 16.7 C)
COMMENT
CONFIGURATION
EXV.B
M.MST
RSET
DMDC
SLCT CLSP 0 COOLING SETPOINT SELECT
IMPORTANT: Care should be taken when interfacing with other control systems due to possible power supply differ­ences: full wave bridge versus half wave rectification. Con­nection of control devices with different power supplies may result in permanent damage. ComfortLink™ controls incorporate power supplies with half wave rectification. A signal isolation device should be utilized if the signal gen­erator incorporates a full wave bridge rectifier.
To use outdoor air or space temperature reset, four variables must be configured. In the Configuration mode under the sub­mode RSET, items (Configuration
figuration
RM.F), and (ConfigurationOPT1RT.DG) must be
OPT1RM.NO), (ConfigurationOPT1
OPT1CRST), (Con-
properly set. See Table 26A — Configuring Outdoor Air and Space Temperature Reset. The outdoor air reset example pro­vides 0° F (0° C) chilled water set point reset at 85.0 F (29.4 C) outdoor-air temperature and 15.0 F (8.3 C) reset at 55.0 F (12.8 C) outdoor-air temperature. The space temperature reset example provides 0° F (0° C) chilled water set point reset at
72.0 F (22.2 C) space temperature and 6.0 F (3.3 C) reset at
68.0 F (20.0 C) space temperature. The variable CRST should
0 Scrolling Stops
0 Flashing ‘0’
4Select4
4 Change Accepted
be configured for the type of reset desired. The variable RM.NO should be set to the temperature that no reset should occur. The variable RM.F should be set to the temperature that maximum reset is to occur. The variable RM.DG should be set to the maximum amount of reset desired. Figures 18 and 19 are examples of outdoor air and space temperature resets.
To use return reset, four variables must be configured. In the Configuration mode under the sub-mode RSET, items CRST, RT.NO, RT.F and RT.DG must be properly set. See Table 26B — Configuring Return Temperature Reset. This example pro­vides 5.0 F (2.8 C) chilled water set point reset at 2.0 F (1.1 C) cooler T and 0° F (0° C) reset at 10.0 F (5.6 C) cooler T. The variable RT.NO should be set to the cooler temperature differ­ence (T) where no chilled water temperature reset should oc­cur. The variable RT.F should be set to the cooler temperature difference where the maximum chilled water temperature reset should occur. The variable RM.DG should be set to the maxi­mum amount of reset desired.
To verify that reset is functioning correctly proceed to Run Status mode, sub-mode VIEW, and subtract the active set point (Run Status
Status
VIEWSETP) from the control point (Run
VIEWCTPT) to determine the degrees reset.
40
Page 41
Table 26A — Configuring Outdoor Air and Space Temperature Reset
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
MODE
(RED LED)
KEYPAD
ENTRY
CONFIGURATION
*4 items skipped in this example.
SUB-
MODE
KEYPAD
ENTRY
ITEM
DISPLAY
Outdoor
Air
Space
DISP
UNIT
OPT1
OPT2
HP.A
HP.B
EXV.A
EXV.B
M.MST
RSET CRST 2 4
RM.NO* 85 °F 72 °F
RM.F 55 °F 68 °F
RM.DG 15 °F 6 °F
ITEM
EXPANSION
COOLING RESET
TYPE
REMOTE - NO
RESET TEMP
REMOTE - FULL
RESET TEMP
REMOTE - DEGREES
RESET
COMMENT
2 = Outdoor-Air Temperature 4 = Space Temperature (Connect to TB5-5,6)
Default: 125.0 F (51.7 C) Range: 0° to125 F
Default: 0.0° F (-17.7 C) Range: 0° to 125 F
Default: 0° F (0° C) Range: –30 to 30 F (–34.4 to -1.1 °C)
MODE
(RED LED)
KEYPAD
ENTRY
CONFIGURATION
*4 items skipped in this example.
Table 26B — Configuring Return Temperature Reset
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
DISP TEST ON/OFF TEST DISPLAY LEDs
UNIT TYPE X UNIT TYPE
OPT1 FLUD X COOLER FLUID
OPT2 CTRL X CONTROL METHOD
HP.A
HP.B
EXV.A
EXV.B
M.MST
RSET CRST 3 COOLING RESET TYPE
RT.NO* 10.0
RT.F 0.0
RT.DG 10.0 F
F
RETURN FLUID - FULL
F
RETURN - DEGREES
ITEM
EXPANSION
RETURN FLUID - NO
RESET TEMP
RESET TEMP
RESET
COMMENT
0 = No Reset 1 = 4 to 20 mA Input (EMM required)
(Connect to EMM TB6-2,3) 2 = Outdoor-Air Temperature 3 = Return Fluid 4 = Space Temperature (Connect to TB5-5,6)
Default: 10.0 Range: 0° to10 F COOLER T
Default: 0 Range: 0° to 30 F COOLER
Default: 0
F (5.6 C)
F (–17.8 C)
F (0 C)
T
Range: –30 to 30°F (–16.7 to 16.7 C)
41
Page 42
Under normal operation, the chiller will maintain a constant
LEGEND
LWT — Leaving Water (Fluid) Temperature
Fig. 18 — Outdoor-Air Temperature Reset
LEGEND
LWT — Leaving Water (Fluid) Temperature
Fig. 19 — Space Temperature Reset
LEGEND
Fig. 20 — Standard Chilled Fluid
Temperature Control — No Reset
EWT —
Entering Water (Fluid) Temperature
LWT
Leaving Water (Fluid) Temperature
leaving fluid temperature approximately equal to the chilled fluid set point. As the cooler load varies, the entering cooler fluid will change in proportion to the load as shown in Fig. 20. Usually the chiller size and leaving-fluid temperature set point are selected based on a full-load condition. At part load, the flu­id temperature set point may be colder than required. If the leaving fluid temperature was allowed to increase at part load, the efficiency of the machine would increase.
Return temperature reset allows for the leaving temperature set point to be reset upward as a function of the return fluid temperature or, in effect, the building load.
Demand Limit — Demand limit is a feature that allows
the unit capacity to be limited during periods of peak energy us­age. There are 3 types of demand limiting that can be config­ured. The first type is through 2-stage switch control, which will reduce the maximum capacity to 2 user-configurable percentag­es. The second type is by 4 to 20 mA signal input which will re­duce the maximum capacity linearly between 100% at a 4 mA input signal (no reduction) down to the user-configurable level at a 20 mA input signal. The third type uses the CCN Loadshed module and has the ability to limit the current operating capaci­ty to maximum and further reduce the capacity if required.
NOTE: The 2-stage switch control and 4 to 20-mA input sig­nal types of demand limiting require the energy management module (EMM).
To use demand limit, select the type of demand limiting to use. Then configure the demand limit set points based on the type selected.
DEMAND LIMIT (2-Stage Switch Controlled) — To con­figure demand limit for 2-stage switch control set the Demand Limit Select (Configuration
RSETDMDC) to 1. Then
configure the 2 Demand Limit Switch points (Configura-
tion
RSETDLS1) and (ConfigurationRSETDLS2)
to the desired capacity limit. See Table 27. Capacity steps are controlled by 2 relay switch inputs field wired to TB6 as shown in Fig. 6 and 7.
For demand limit by 2-stage switch control, closing the first stage demand limit contact will put the unit on the first demand limit level. The unit will not exceed the percentage of capacity entered as Demand Limit Switch 1 set point (DLS1). Closing contacts on the second demand limit switch prevents the unit from exceeding the capacity entered as Demand Limit Switch 2 set point. The demand limit stage that is set to the lowest de­mand takes priority if both demand limit inputs are closed. If the demand limit percentage does not match unit staging, the unit will limit capacity to the closest capacity stage.
To disable demand limit configure DMDC to 0. See Table 27.
EXTERNALLY POWERED DEMAND LIMIT (4 to 20 mA Controlled) — To configure demand limit for 4 to 20 mA control set the Demand Limit Select (Configura-
tion
RSETDMDC) to 2. Then configure the Demand
Limit at 20 mA (Configuration
RSETDM20) to the
maximum loadshed value desired. Connect the output from an externally powered 4 to 20 mA signal to terminal block TB6, terminals 1 and 5. Refer to the unit wiring diagram for these connections to the optional/accessory energy management module and terminal block. The control will reduce allowable capacity to this level for the 20 mA signal. See Table 27 and Fig. 21.
CAUTION
Care should be taken when interfacing with other manufac­turer’s control systems, due to possible power supply differences, full wave bridge versus half wave rectification. The two different power supplies cannot be mixed. ComfortLink™ controls use half wave rectification. A sig­nal isolation device should be utilized if a full wave bridge signal generating device is used.
42
Page 43
DEMAND LIMIT (CCN Loadshed Controlled) — To con-
50% CAPACITY AT 20 mA
75% CAPACITY AT 12 mA
100% CAPACITY AT 4 mA
0
2
4
6
8
10
12
14
16 18
20
DEMAND LIMIT SIGNAL – 4 - 20 mA INPUT
100
80
60
40
20
0
MAX. ALLOWABLE LOAD (%)
Fig. 21 — 4 to 20-mA Demand Limiting
100 (38)
80
(27)
60
(15)
40
(4.4)
20
(-7)
0
(-17)
4 6.3 8.6 10.9 13.1 15.4 17.7 20
4 TO 20 mA SIGNAL TO EMM
SET POINT, F (C)
90
(32)
70
(21)
50
(10)
30
(-1)
10
(-12)
(FLUD = 2) MINIMUM SET POINT 14 F (-10 C)
(FLUD = 1) MINIMUM SET POINT 38 F (3.3 C)
MAXIMUM SET POINT 70 F (21.1 C)
Fig. 22 — Cooling Set Point (4 to 20 mA)
EMM — Energy Management Module
figure Demand Limit for CCN Loadshed control set the De­mand Limit Select (Configuration
RSETDMDC) to 3.
Then configure the Loadshed Group Number (Configura-
tion
RSETSHNM), Loadshed Demand Delta (Configu-
rationRSETSHDL), and Maximum Loadshed Time (Configuration
RSETSHTM). See Table 27.
The Loadshed Group number is established by the CCN system designer. The ComfortLink controls will respond to a Redline command from the Loadshed control. When the Redline command is received, the current stage of capacity is set to the maximum stages available. Should the loadshed con­trol send a Loadshed command, the ComfortLink controls will reduce the current stages by the value entered for Loadshed Demand delta. The Maximum Loadshed Time is the maximum
length of time that a loadshed condition is allowed to exist. The control will disable the Redline/Loadshed command if no Cancel command has been received within the configured maximum loadshed time limit.
Cooling Set Point (4 to 20 mA) — A field supplied
and generated, externally powered 4 to 20 mA signal can be used to provide the leaving fluid temperature set point. Connect the signal to LVT7,8 (+,–). See Table 27 for instructions to enable the function. Figure 22 shows how the 4 to 20 mA sig­nal is linearly calculated on an overall 10 F to 80 F range for fluid types (Configuration point will be limited by the fluid (FLUD) type. Be sure that the chilled water loop is protected at the lowest temperature.
OPT1FLUD) 1 or 2. The set
43
Page 44
Table 27 — Configuring Demand Limit
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
MODE
CONFIGURATION
*Seven items skipped in this example.
KEYPAD
ENTRY
SUB-MODE
KEYPAD
ENTRY
DISP TEST ON/OFF Test Display LEDs
UNIT TYPE X Unit Type
OPT1 FLUD X Cooler Fluid
OPT2 CTRL X Control Method
HP.A
HP.B
EXV.A
EXV.B
M.MST
RSET CRST X Cooling Reset Type
ITEM DISPLAY ITEM EXPANSION COMMENT
DMDC* X Demand Limit Select
DM20 XXX % Demand Limit at 20 mA
SHNM XXX
SHDL XXX%
SHTM XXX MIN
DLS1 XXX %
DLS2 XXX %
Loadshed Group
Number
Loadshed Demand
Delta
Maximum Loadshed
Time
Demand Limit
Switch 1
Demand Limit
Switch 2
Default: 0 0 = None 1 = Switch 2 = 4 to 20 mA Input 3 = CCN Loadshed
Default: 100% Range: 0 to 100
Default: 0 Range: 0 to 99
Default: 0% Range: 0 to 60%
Default: 60 min. Range: 0 to 120 min.
Default: 80% Range: 0 to 100%
Default: 50% Range: 0 to 100%
Digital Scroll Option — The 30RAP units have a
factory-installed option for a digital scroll compressor which provides additional stages of unloading for the unit. The digital compressor is always installed in the A1 compressor location. When a digital compressor is installed, a digital unloader sole­noid (DUS) is used on the digital compressor.
DIGITAL SCROLL OPERATION — A digital scroll oper­ates in two stages - the "loaded state" when the solenoid valve is normally closed and the "unloaded state" when the solenoid valve is open. During the loaded state, the compressor operates like a standard scroll and delivers full capacity and mass flow.
However, during the unloaded state, there is no capacity and no mass flow through the compressor. The capacity of the system is varied by varying the time the compressor operates in an unloaded and loaded state during a 15-second period. If the DUS is energized for 7 seconds, the compressor will be operating at 47% capacity. If the DUS is energized for 10 sec­onds, the compressor will be operating at approximately 33% of its capacity. Capacity is the time averaged summation of loaded and unloaded states, and its range is continuous from the minimum configured capacity to 100%. Regardless of capacity, the compressor always rotates with constant speed. As the compressor transitions from a loaded to unloaded state, the discharge and suction pressures will fluctuate and the com­pressor sound will change.
The ComfortLink controller controls and integrates the op­eration of the DUS into the compressor staging routine to maintain temperature control. When a digital compressor is in­stalled, an additional discharge gas temperature thermistor
(DTT) is installed along with the AUX board for control of the DUS.
DIGITAL COMPRESSOR CONFIGURATION — When a digital compressor is installed, the configuration parameter (Configuration
UNITA1TY) is configured to YES.
There is also a maximum unload time configuration, (Config-
uration
UNITMAX.T) that is set to 7 seconds, which in-
dicates the maximum unloading for the digital compressor is 47%. This is done to optimize efficiency of the system.
PRE-START-UP
IMPORTANT: Before beginning Pre-Start-Up or Start-Up, complete Start-Up Checklist for 30RAP Liquid Chiller at end of this publication (pages CL-1 to CL-10). The check­list assures proper start-up of a unit, and provides a record of unit condition, application requirements, system infor­mation, and operation at initial start-up.
Do not attempt to start the chiller until following checks
have been completed.
System Check
1. Check all auxiliary components, such as chilled fluid pumps, air-handling equipment, or other equipment to which the chiller supplies liquid. Consult manufacturer's instructions. Verify that any pump interlock contacts have been properly installed. If the unit If the unit has field-installed accessories, be sure all are properly in­stalled and wired correctly. Refer to unit wiring diagrams.
44
Page 45
2. Use the scrolling marquee display to adjust the Cooling
OIL SIGHTGLASS
Fig. 23 — Sight Glass Location
a30-4978
Set Point.
3. Fill chilled fluid circuit with clean water (with recom­mended inhibitor added) or other non-corrosive fluid to be cooled. Bleed all air out of the high points of the sys­tem. If chilled water is to be maintained at a temperature below 40 F (4.4 C) or outdoor temperatures are expected to be below 32 F (0° C), a brine of sufficient concentra­tion must be used to prevent freeze-up at anticipated suction temperatures. See Table 28.
4. Check tightness of all electrical connections.
5. Oil should be visible in the compressor sightglass(es). See Fig. 23. An acceptable oil level in the compressors is
1
from
/8 to 3/8 of sight glass. Adjust the oil level as re­quired. See Oil Charge section on page 50 for Carrier ap­proved oils.
6. Electrical power source must agree with unit nameplate.
7. All condenser fan and factory installed hydronic package pump motors are three phase. Check for proper rotation of condenser fans first BEFORE attempting to start pumps or compressors. To reverse rotation, interchange any two of the main incoming power leads.
8. Be sure system is fully charged with refrigerant (see Check Refrigerant Charge section on this page).
9. If unit is a brine unit, check to ensure proper brine con­centration is used to prevent freezing.
10. Verify proper operation of cooler and hydronic package heaters (if installed). Heaters operate at the same voltage as the main incoming power supply and are single phase. Heater current is approximately 0.4 amps for 460 and 575 v units. Heater current is approximately 0.8 amps for 230 v units.
START-UP AND OPERATION
NOTE: Refer to Start-Up Checklist on pages CL-1 to CL-10.
Actual Start-Up — Actual start-up should be done only
under supervision of a qualified refrigeration mechanic.
1. Be sure all service valves are open.
2. Using the scrolling marquee display, set leaving-fluid set point (Set Points
COOLCSP.1). No cooling range
adjustment is necessary.
3. Start chilled fluid pump (if not configured for cooler pump control).
4. Turn ENABLE/OFF/REMOTE CONTACT switch to ENABLE position.
5. Allow unit to operate and confirm that everything is func­tioning properly. Check to see that leaving fluid tempera­ture agrees with leaving set point (Set Points
CSP.1) or (Set PointsCOOLCSP.2), or if reset is
COOL
used, with the control point (Run StatusVIEW
CTPT).
6. Check the cooler leaving chilled water temperature to see that it remains well above 32 F (0° C), or the brine freez­ing point if the unit is a medium temperature brine unit.
7. Recheck compressor oil level (see Oil Charge section).
Check Refrigerant Charge — All 30RAP units are
shipped with a complete operating charge of R-410A and should be under sufficient pressure to conduct a leak test after installation. If there is no system pressure, admit nitrogen until a pressure is observed and then proceed to test for leaks. After leaks are repaired, the system must be dehydrated.
All refrigerant charging should be done through the ¼-in. Schraeder connection on the liquid line. Do NOT add refriger­ant charge through the low-pressure side of the system. If com­plete charging is required, weigh in the appropriate charge for the circuit as shown on the unit nameplate. If partial charging is required, operate circuit at full load and use an accurate tem­perature sensor on the liquid line as it enters the EXV. Use the Temperatures mode on the scrolling marquee display to show the circuit saturated condensing temperature (Tem pe ra -
tures
temperatures of 120 to 125 F (49 to 52 C). Block condenser air­flow as required to reach this temperature range. Add refriger­ant until the system subcooling (SCT.A or SCT.B minus liquid line temperature entering EXV) is approximately 15 to 17 F (–9.4 to –8.3 C). Refrigerant VAPOR only may be added to a circuit through the suction line.
CIR.ASCT.A) or (Temp er at ur esCIR.B
SCT.B). Charging is most accurate at saturated discharge
1
/4-in. suction Schraeder connection on the
Table 28 — Minimum Cooler Flow Rates and Minimum Loop Volume
30RAP
SIZE
010 13 50 0.8 3.2 015 17 66 1.1 4.2 018 20 78 1.3 4.9 020 23 91 1.5 5.7 025 28 112 1.8 7.1 030 33 133 2.1 8.4 035 41 164 2.6 10.3 040 47 186 3.0 11.7 045 53 209 3.3 13.2 050 57 228 3.6 14.4 055 63 251 4.0 15.8 060 68 270 4.3 17.0
MINIMUM COOLER FLOW
RATE (gpm)
MAXIMUM COOLER FLOW
RATE (gpm)
MINIMUM COOLER FLOW
RATE (l/s)
MAXIMUM COOLER FLOW
RATE (l/s)
45
Page 46
CAUTION
Never charge liquid into low-pressure side of system. Do not overcharge. Overcharging results in higher discharge pressure, possible compressor damage, and higher power consumption. During charging or removal of refrigerant, be sure water is continuously circulating through the cooler to prevent freezing.
Operating Limitations
TEMPERATURES (See Table 29 for 30RAP standard tem­perature limits).
CAUTION
Do not operate with cooler leaving chiller water (fluid) temperature (LCWT) below 40 F (4.4 C) for the standard units, or below 15 F (–9.4 C) for units factory built for medium temperature brine.
High Cooler Leaving Chilled Water (Fluid) Temperatures (LCWT) — During start-up with cooler LCWT above approx­imately 60 F (16 C), the unit expansion valve will limit suction pressure to approximately 90 psig (620 kPa) to avoid overload­ing the compressor.
Low Cooler LCWT no lower than 40 F (4.4 C). If the unit is the factory-installed optional medium temperature brine unit, the cooler LCWT can go down to 15 F (–9.4 C).
Table 29 — Temperature Limits for
UNIT SIZE 30RA 010-030 035-060 Temperature F C F C Maximum Ambient
Temperature Minimum Ambient
Temperature Maximum Cooler EWT* 95 35 95 35 Maximum Cooler LWT 70 21 70 21 Minimum Cooler LWT† 40 4.4 40 4.4
EWT — LWT —
*For sustained operation, EWT should not exceed 85 F (29.4 C). †Unit requires modification below this temperature.
Entering Fluid (Water) Temperature Leaving Fluid (Water) Temperature
— For standard units, the LCWT must be
Standard 30RAP Units
120 49 120 49
457 320
LEGEND
Unbalanced 3-Phase Supply Voltage — Never operate a motor where a phase imbalance between phases is greater than 2%.
To determine percent voltage imbalance:
max voltage deviation
% Voltage Imbalance = 100 x
from avg voltage
average voltage
The maximum voltage deviation is the largest difference between a voltage measurement across 2 legs and the average across all 3 legs.
Example: Supply voltage is 240-3-60.
AB = 243 v
BC = 236 v AC = 238 v
1. Determine average voltage:
Average voltage =
243 + 236 + 238
3
717
=
3
= 239
2. Determine maximum deviation from average voltage: (AB) 243 – 239 = 4 v
(BC) 239 – 236 = 3 v (AC) 239 – 238 = 1 v
Maximum deviation is 4 v.
3. Determine percent voltage imbalance:
% Voltage Imbalance = 100 x
4
239
= 1.7%
This voltage imbalance is satisfactory as it is below the
maximum allowable of 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. Do not operate unit until imbalance condition is corrected.
Control Circuit Power
— Power for the control circuit is supplied from the main incoming power through a factory­installed control power transformer (TRAN1) for all models. Field wiring connections are made to the LVT.
LOW-AMBIENT OPERATION — If operating temperatures below 45 F (7 C) on size 018-030 units, and 32 F (0° C) on size 035-060 units are expected, accessory Motormaster® V con­trol must be installed. Operating temperatures can go as low as –20 F (–29 C) on size 010 and 015 units, as standard. Installa­tion of wind baffles is also required. Refer to separate installa­tion instructions for operation using this accessory. Contact your Carrier representative for details.
CAUTION
Brine duty application (below 40 F [4.4 C] LCWT) for chiller normally requires factory modification. Contact your Carrier representative for applicable LCWT range for standard water-cooled chiller in a specific application.
VOLTAGE — ALL UNITS Main Power Supply
supply voltages are listed in the Installation Instructions.
— Minimum and maximum acceptable
OPERATION SEQUENCE
During unit off cycle, the control monitors the outdoor air temperature. If the ambient temperature drops below 40 F (4.4 C), cooler and hydronic system heaters (if either are facto­ry installed) are energized. If power is maintained to the chiller and the EMERGENCY ON/OFF switch is left in the OFF po­sition, these heaters are also energized.
The unit is started by putting the ENABLE/OFF/REMOTE CONTACT switch in the ENABLE or REMOTE CONTACT position. When the unit receives a call for cooling (either from the internal control or CCN network command or remote con­tact closure), the unit stages up in capacity to maintain the leav­ing fluid set point. The first compressor starts 1 after the call for cooling.
The lead circuit can be specifically designated on all models or selected based on compressor run hours and starts depend­ing on field configuration. The unit control will override this selection under certain starting conditions to properly maintain oil return to the compressors. In general, on dual compressor
46
1
/2 to 3 minutes
Page 47
circuits, the control will most often start the A1 or B1 compres-
ESCAPE
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
sor first, especially after long off periods. The MBB controls fan stages to maintain the head pressure set point and will auto­matically adjust unit capacity as required to keep compressors from operating outside of the specified envelope. There are no pumpout or pumpdown sequences on these chillers.
For all units, if temperature reset is being used, the unit con­trols to a higher leaving-fluid temperature as the building load reduces. If demand limit is used, the unit may temporarily be unable to maintain the desired leaving-fluid temperature be­cause of imposed power limitations.
SERVICE
WARNING
Electrical shock can cause personal injury and death. Shut off all power to this equipment during service. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
Electronic Components
CONTROL COMPONENTS — Unit uses an advanced elec­tronic control system that normally does not require service. For details on controls refer to Operating Data section.
Access to the compressors is through latched panels from beneath the control box on all models or from opposite the coil side (sizes 010-030 only). The front door(s) provide access to the compressor(s) and all components of the refrigeration sys­tem. For size 010-030 units, access to the controls is through the upper latched outer door above the compressor access door. Similarly, the upper center latched door on sizes 035-060 gives access to the controls. Inner panels are secured in place and should not be removed unless all power to the chiller is off.
Electronic Expansion Valve (EXV) — See Fig. 24
for a cutaway view of the EXV. High-pressure liquid refriger­ant enters valve through the top. As refrigerant passes through the orifice, pressure drops and refrigerant changes to a 2-phase condition (liquid and vapor). The electronic expansion valve operates through an electronically controlled activation of a stepper motor. The stepper motor stays in position, unless power pulses initiate the two discrete sets of motor stator wind­ings for rotation in either direction. The direction depends on the phase relationship of the power pulses.
The motor directly operates the spindle, which has rotating movements that are transformed into linear motion by the transmission in the cage assembly. The valve includes a posi­tive shut-off when closed.
There are two different EXVs. See Table 30 for number of steps. The EXV motor moves at 200 steps per second. Com­manding the valve to either 0% or 100% will add extra steps to the move, to ensure the value is open or closed completely.
Table 30 — EXV Steps
UNIT SIZE 30RAP EXV STEPS
010-020 1596 025,030 2500 035-045 1596 050-060 2500
The EXV board controls the valve. Each circuit has a thermistor located in a well in the suction manifold before the compressor. Suction pressure as measured by the suction pres­sure transducer is converted to a saturated suction temperature. The thermistor measures the temperature of the superheated gas entering the compressor and the pressure transducer
determines the saturated temperature of suction gas. The differ­ence between the temperature of the superheated gas and the saturated suction temperature is the superheat. The EXV board controls the position of the electronic expansion valve stepper motor to maintain superheat set point.
The MBB controls the superheat leaving cooler to approxi­mately 9° F (5° C). Because EXV status is communicated to the main base board (MBB) and is controlled by the EXV boards, it is possible to track the valve position. The unit is then protected against loss of charge and a faulty valve. Just prior to compressor start, the EXV will open. At low ambient tempera­tures the EXV is closed at start up. After initialization period, valve position is tracked by the EXV board by constantly mon­itoring the amount of valve movement.
The EXV is also used to limit cooler saturated suction tem­perature to 50 F (10 C). This makes it possible for the chiller to start at higher cooler fluid temperatures without overloading the compressor. This is commonly referred to as MOP (maxi­mum operating pressure). At ambient temperatures above 110 F, MOP is bypassed at start-up to prevent charge backup in the condenser.
If it appears that the EXV module is not properly control­ling circuit operation to maintain correct superheat, there are a number of checks that can be made using test functions and initialization features built into the microprocessor control. See the EXV Troubleshooting Procedure section to test EXVs.
EXV Troubleshooting Procedure — Follow steps
below to diagnose and correct EXV/economizer problems.
Check EXV motor operation first. Switch the Enable/Off/ Remote Contact (EOR) switch to the Off position. Press on the Navigator™ display until ‘Select a menu item’ appears on the display. Use the arrow keys to select the Service Test mode. Press . The display will be:
> TEST OFF OUTS COMP
Press (password entry may be required) and use
to change ‘OFF’ to ‘ON’. Switch the EOR switch to Enable. The Service Test mode is now enabled. Move the pointer down to the OUTS sub-mode and press . Move the pointer to item EXV.A or EXV.B as needed. Press and the valve position will flash. Use to select 100% valve position (hold for quick movement) and press .
The technician should be able to feel the actuator moving by placing a hand on the EXV. A sight glass is located on the valve body to verify that the sleeve is moving to expose/cover slots in the orifice. A hard knocking should be felt from the actuator when it reaches the top of its stroke (can be heard if surround­ings are relatively quiet). Press again twice if necessary to confirm this. To close the valve, press , select 0% with
and press . The actuator should knock when it reaches the bottom of its stroke. If it is believed that the valve is not working properly, continue with the checkout procedure below:
Check the EXV output signals at appropriate terminals on the EXV module (see Fig. 25). Connect positive test lead to red wire (EXV-J6 terminal 3 for Circuit A, EXV-J7 terminal 3 for Circuit B). Set meter to approximately 20 vdc. Using the Service Test procedure above, move the valve output under test to 100%. DO NOT short meter leads together or pin 3 to any other pin as board damage will occur.
47
Page 48
Fig. 24 — Electronic Expansion Valve Details
a30-4971
ENTER
INCLUDED IN CABLE KIT
CABLE
CABLE
CABLE RETAINER
MOTOR AND
MOTOR ADAPTER ASSEMBLY
ADAPTER ASSEMBLY
CABLE RETAINER
GASKET
SIGHTGLASS
SPORLAN
During the next several seconds, carefully connect the nega­tive test lead to pins 1,2,4 and 5 in succession (plug J6 for Cir­cuit A, plug J7 for Circuit B). Digital voltmeters will average this signal and display approximately 6 vdc. If it remains con­stant at a voltage other than 6 VDC or shows 0 volts, remove the connector to the valve and recheck.
Press and select 0% to close the valve. Check the 4 po­sition DIP switch on the board (all switches should be set to On). If a problem still exists, replace the EXV module. If the reading is correct, the expansion valve and EXV wiring should be checked. Check the EXV terminal strip and interconnecting wiring.
1. Check color coding and wire connections. Make sure they are connected to the correct terminals at the EXV driver and EXV plug and that the cables are not crossed.
2. Check for continuity and tight connection at all pin terminals.
3. Check the resistance of the EXV motor windings. Re­move the EXV module plug (J6 for Circuit A, J7 for Cir­cuit B) and check the resistance of the two windings be­tween pins 1 and 2 for one winding and pins 4 and 5 for the other winding (see Fig. 25). The resistance should be 100 ohms ± 10 ohms.
FLOW DIRECTION
MOTOR ADAPTER ASSEMBLY
NORMAL FLOW DIRECTION
FIELD SERVICING INSTRUCTIONS — The EXV valves on sizes 025, 030, 050-060 can be serviced. The EXV valves on all other sizes are hermetic and cannot be disassembled for installation or during service, however, the cable and retainer may be replaced if necessary. Motor kits for the EXV valve are available as replacement parts.
To remove the valve from the system, perform the follow-
ing procedure:
1. Be sure the refrigerant has been recovered from the circuit.
2. Disconnect the line voltage to the valve controller. Dis­connect the valve wires from the controller.
3. If the motor fails to operate properly, check the resistance of each motor phase. Resistance between black and white leads or between the red and green leads should be ap­proximately 100 ohms. Differences of more than 10% be­tween phases indicate a defective motor. Resistance be­tween black and red, or any lead and piping, should be in­finite or “open”. Any resistance reading will indicate a shorted winding and the valve will need to be replaced.
4. The output of the controller to the valve can be tested with the following procedure:
a. Disconnect supply voltage to the controller.
48
Page 49
b. Place a digital voltmeter, on 20-volt AC scale,
BLK
WHT
GRN
RED
BLK
WHT
GRN
RED
Fig. 25 — EXV Cable Connections to EXV Module
a30-4972
across the black and white terminals on the con­troller. Restore power to the controller. For at least 7 seconds, the voltmeter should read approxi­mately 12 to 14 volts. Significant differences mean the controller is defective or not properly config­ured for the EXV valve.
c. Repeat the procedure in Step b above using the red
and green terminals on the controller. If the con­troller responds properly, then the wiring may be damaged or the valve may be plugged with debris or otherwise obstructed.
d. The EXV valves on sizes 025, 030, 050-060 may
be disassembled for cleaning, inspection or motor assembly replacement.
VALVE REPLACEMENT — The valve may be replaced by unsoldering or cutting the piping. A tubing cutter must be used to prevent creating contaminants in the piping.
VALVE REASSEMBLY — Perform the following procedure to reassemble the EXV valve:
1. Use Service Test to open the EXV to 100%. This will re­tract the white polyester driver/piston fully into the driver guide. Remove power from the valve or controller.
2. Lightly oil the threads, and gasket or knife-edge on the new motor adaptor. Carefully seat the adaptor on the valve body or engage and tighten the lock nut if used. Lock nuts should be torqued to approximately 45 ft-lb. One eighth turn more than hand tight is sufficient to achieve a leak proof seal on knife-edge joints.
3. After the motor is tightened, the cable should be replaced on the valve. Care should be taken to ensure engagement of the alignment key. Snap on the cable retainer.
4. Pressurize the system and check for leaks.
5. Reapply power to the ComfortLink™ controller. Since, during service, valve position as calculated by the con­troller will be lost, the controller should be initialized at least twice. In some instances, cycling power to the con­troller will accomplish this.
CAUTION
If the existing motor has been removed for inspection or cleaning, be sure that the piston is fully retracted into the motor assembly before installation on the valve. Failure to do so will permanently damage the drive and motor. Replacement motor assemblies are shipped in the retracted position and may be installed as received.
Compressor Replacement (Refer to Fig. 26 and 27) —
from one to four compressors. The size 010-030 units are a sin­gle refrigeration circuit while sizes 035-060 are dual circuit. A compressor is most easily removed from the front of the unit, depending on where clearance space was allowed during unit installation.
Remove the junction box cover bolts and disconnect the compressor power and ground connections. Remove the cable from the compressor junction box. Remove the connections from the high-pressure switch. Knock the same holes out of the new compressor junction box and install the cable connectors from the old compressor.
The compressors are bolted to rails, which are in turn bolted to the unit basepan for all sizes except 010 and 015 which are directly bolted to the basepan. Remove the 4 bolts holding the compressor to the rail on the basepan. Save the mounting hard­ware for use with the new compressor. Carefully cut the com­pressor suction and discharge lines with a tubing cutter as close to the compressor as feasible. Remove high-pressure switch and pressure transducer(s) if required for compressor removal. Lift one corner of the compressor at a time and remove all the rubber mounting grommets (single compressor circuits) or steel spacers (dual compressor circuits). Remove the old com­pressor from the unit.
Slide the new compressor in place on the basepan. Lifting one side of the compressor at a time, replace all of the compres­sor mounting grommets. Using new tubing as required, recon­nect compressor suction and discharge lines. Using hardware saved, reinstall the mounting bolts and washers through the compressor feet. Using proper techniques, braze suction and discharge lines and check for leaks. Reconnect oil equalization line on dual compressor circuit models.
Reconnect the compressor power connections and high­pressure switch wiring as on the old compressor. Refer to Fig. 26 and 27. Following the installation of the new compres­sor, tighten all hardware to the following specifications. (See Table 31.)
Compressor Mounting Bolts
Compressor Power Connections
Compressor Ground Terminal Connections
All models contain scroll compressors and have
Table 31 — Unit Torque Specification
FASTENER RECOMMENDED TORQUE
7 to 10 ft-lb (9.5 to 13.5 N-m)
24 to 28 in.-lb (2.7- to 3.2 N-m)
14 to 18 in.-lb (1.6 to 2.0 N-m)
Cooler
BRAZED-PLATE COOLER HEAT EXCHANGER RE­PLACEMENT — Brazed-plate heat exchangers cannot be repaired if they develop a leak. If a leak (refrigerant or water) develops, the heat exchanger must be replaced. To replace a brazed-plate heat exchanger:
1. Check that the replacement heat exchanger is the same as the original heat exchanger. The unit insulation covers the manufacturer’s part number. Make sure the depths of the replacement and original cooler heat exchangers are the same.
49
Page 50
2. Disconnect the liquid-in and liquid-out connections at the heat exchanger.
3. Recover the refrigerant from the system, and unsolder the refrigerant-in and refrigerant-out connections.
4. Remove the old heat exchanger. The replacement heat ex­changer is supplied fully insulated. It also includes a cool­er heater. Use of the heater is not required unless the orig­inal cooler contained a factory installed heater.
5. Install the replacement heat exchanger in the unit and at­tach the mounting bracket hardware to the fan uprights (sizes 010-030) or to the bottom bracket (sizes 035-060) using the hardware removed in Step 4. Reconnect the cooler heater if required. For sizes 010-025, torque the bolts to 7-10 ft-lb. For sizes 030-060, torque the bolts to 30-50 ft-lb.
6. Carefully braze the refrigerant lines to the connections on the heat exchanger. Lines should be soldered using silver as the soldering material with a minimum of 45% silver. Keep the temperature below 1472 F (800 C) under nor­mal soldering conditions (no vacuum) to prevent the cop­per solder of the brazed plate heat exchanger from chang­ing its structure. Failure to do so can result in internal or external leakage at the connections which cannot be re­paired. Braze the liquid lines with a heat sink around the expansion valve to protect it from excess heat.
7. Reconnect the water/brine lines.
8. Dehydrate and recharge the unit. Check for leaks.
BRAZED-PLATE COOLER HEAT EXCHANGER CLEANING — Brazed-plate heat exchangers must be cleaned chemically. A professional cleaning service skilled in chemical cleaning should be used. Use a weak acid (5% phos­phoric acid, or if the heat exchanger is cleaned frequently, 5% oxalic acid). Pump the cleaning solution through the exchanger, preferably in a backflush mode. After cleaning, rinse with large amounts of fresh water to dispose of all the acid. Cleaning materials must be disposed of properly.
The factory-installed strainer screen in front of the water/ brine inlets of the heat exchangers should be cleaned periodi­cally, depending on condition of the chiller water/brine.
Oil Charge
Mobil . . . . . . . . . . . . . . . . . . . . . . . . . . .EAL Arctic 32-3MA
Uniqema . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RL32-3MAF
Do not reuse oil that has been drained out, or oil that has
been exposed to atmosphere.
Microchannel Heat Exchanger (MCHX) Con­denser Coil Maintenance and Cleaning Recommendations
CAUTION
Do not apply any chemical cleaners to MCHX condenser coils. These cleaners can accelerate corrosion and damage the coil.
Routine cleaning of coil surfaces is essential to maintain proper operation of the unit. Elimination of contamination and removal of harmful residues will greatly increase the life of the coil and extend the life of the unit. The following steps should be taken to clean MCHX condenser coils:
1. Remove any foreign objects or debris attached to the coreface or trapped within the mounting frame and brackets.
2. Put on personal protective equipment including safety­glasses and/or face shield, waterproof clothing and gloves. It is recommended to use full coverage clothing.
3. Start high pressure water sprayer and purge any soap or industrial cleaners from sprayer before cleaning condens­er coils. Only clean, potable water is authorized for clean­ing condenser coils.
4. Clean condenser face by spraying the core steady and uniformly from top to bottom while directing the spray straight toward the core. Do not exceed 900 psig or 30 de­gree angle. The nozzle must be at least 12 in. from the core face. Reduce pressure and use caution to prevent damage to air centers.
CAUTION
Excessive water pressure will fracture the braze between air centers and refrigerant tubes.
CAUTION
The compressor in a Puron® refigerant (R-410A) system uses a polyol ester (POE) oil. This is extremely hygro­scopic, meaning it absorbs water readily. POE oils can absorb 15 times as much water as other oils designed for HCFC and CFC refrigerants. Take all necessary precau­tions to avoid exposure of the oil to the atmosphere. Failure to do so could result in possible equipment damage.
Puron refrigerant systems use a polyol ester (POE) oil. Use only Carrier approved compressor oil. Oil should be visible in compressor oil sight glass. An acceptable oil level is from
3
/8 of sight glass. All compressors must be off when checking oil level. Recommended oil level adjustment method is as follows:
ADD OIL — Recover charge from the unit. Add oil to suction line Schrader valve on tandem compressors sets and the com­pressor Schrader on the trio's and single compressor circuits. (See Fig. 26 and 27.) When oil can be seen at the bottom of the sight glass, add oil in 5 oz increments which is approximately
1
/8 in oil level. Run all compressors for 20 minutes then shut off to check oil level. Repeat procedure until acceptable oil level is present.
NOTE: Use only Carrier approved compressor oil. Approved sources are:
Totaline . . . . . . . . . . . . . . . . . . . . . . 3MAF POE, P903-1601
1
/8 to
Check Refrigerant Feed Components
FILTER DRIER — The function of the filter drier is to main­tain a clean, dry system. The moisture indicator (described below) indicates any need to change the filter drier. The filter drier is a sealed-type drier. When the drier needs to be changed, the entire filter drier must be replaced.
NOTE: Dual circuit (035-060 sizes) units have 1 filter drier per circuit.
MOISTURE-LIQUID INDICATOR — The indicator is located immediately ahead of the TXV to provide an indication of the refrigerant moisture content. It also provides a sight glass for refrigerant liquid. Clear flow of liquid refrigerant (at full unit loading) indicates sufficient charge in the system. Bubbles in the sight glass (at full unit loading) indicate an undercharged system or the presence of noncondensables. Moisture in the system, measured in parts per million (ppm), changes the color of the indicator as follows:
Green (safe) —Moisture is below 75 ppm Yellow-Green (caution) — 75 to 150 ppm Yellow (wet) — above 150 ppm
The unit must be in operation at least 12 hours before the moisture indicator gives an accurate reading, and must be in contact with liquid refrigerant. At the first sign of moisture in the system, change the corresponding filter drier.
NOTE: Dual circuit (035-060 sizes) units have one indicator per circuit.
50
Page 51
A1
A2
B1
B2
OIL SIGHTGLASS
DISCHARGE ACCESS VALVE
FLOW SWITCH
LWT
DTT
DISCHARGE ACCESS VALVE
DPT
HPS
RGT
SPT
SUCTION
ACCESS VALVE
RGT
SPT
DPT
HPS
EWT
EWT
Fig. 26 — Compressor Location — 30RAP010-030
Fig. 27 — Compressor Location — 30RAP035-060
LEGEND FOR FIG. 26 AND 27
DPT Discharge Pressure Thermostat DTT Discharge Temperature Thermistor EWT Entering Water Thermistor HPS High Pressure Switch LWT Leaving Water Thermistor RGT Return Gas Thermistor SPT Suction Pressure Transducer
a30-4973
a30-4974
SUCTION ACCESS VALV E
HPSDPT
SPT
RGT
COMPRESSOR A2
LWT
FLOW SWITCH
DTT
COMPRESSOR A1
51
Page 52
MINIMUM LOAD VALVE — On units equipped with the factory-installed capacity reduction option, a solenoid valve and discharge bypass valve (minimum load valve) are located between the discharge line and the cooler entering-refrigerant line. The MBB cycles the solenoid to perform minimum load valve function and the discharge bypass valve modulates to the suction pressure set point and the valve.
The amount of capacity reduction achieved by the mini­mum load valve is not adjustable. The total unit capacity with the minimum load valve is shown in Table 19.
PRESSURE RELIEF DEVICES — All units have one pres­sure relief device per circuit located in the liquid line which re­lieves at 210 F (100 C).
Check Unit Safeties
HIGH-PRESSURE SWITCH — A high-pressure switch is provided to protect each compressor and refrigeration system from unsafe high pressure conditions. See Table 32 for high­pressure switch settings.
The high-pressure switch is mounted in the discharge line of each circuit. If an unsafe, high-pressure condition should exist, the switch opens and shuts off the affected circuit. The CSB senses the compressor feedback signal and generates an appro­priate alarm. The MBB prevents the circuit from restarting un­til the alert condition is reset. The switch should open at the pressure corresponding to the appropriate switch setting as shown in Table 32.
Table 32 — Factory Settings, High-Pressure
Switch (Fixed)
UNIT
30RA 650 4482 500 3447
CUTOUT CUT-IN
Psig kPa Psig kPa
Clear the alarm using the scrolling marquee display as de­scribed on page 63. The unit should restart after the compressor anti-short-cycle delay, built into the unit control module, expires.
PRESSURE TRANSDUCERS — Each refrigerant circuit is equipped with a suction and discharge pressure transducer. These inputs to the MBB are not only used to monitor the sta­tus of the unit, but to also maintain operation of the chiller within the compressor manufacturer's specified limits. The in­put to the MBB from the suction pressure transducer is also used to protect the compressor from operating at low pressure conditions and low superheat conditions. In some cases, the unit may not be able to run at full capacity. The control module will automatically reduce the capacity of a circuit as needed to maintain specified maximum/minimum operating pressures.
COOLER FREEZE-UP PROTECTION
WARNING
On medium temperature brine units, the anti-freeze solu­tion must be properly mixed to prevent freezing at a tem­perature of at least 15 F (8.3 C) below the leaving-fluid temperature set point. Failure to provide the proper anti­freeze solution mixture is considered abuse and may impair or otherwise negatively impact the Carrier warranty.
The main base board (MBB) monitors leaving fluid temper­ature at all times. The MBB will rapidly remove stages of ca­pacity as necessary to prevent freezing conditions due to the rapid loss of load or low cooler fluid flow.
When the cooler is exposed to lower ambient temperatures (34 F [1° C] or below), freeze-up protection is required using inhibited ethylene or propylene glycol.
HEATER CABLE — Optional factory-installed cooler and/or hydronic package heaters are cycled based on the input from the outside-air temperature sensor. These heaters, when in­stalled, are designed to protect the cooler and/or hydronic pack­age from freezing down to –20 F (–29 C). Power for these heat­ers is supplied from the main unit power.
The input from the low pressure transducer provides a back­up cooler freeze protection package. The MBB shuts down the unit when a low pressure condition exists that could cause the cooler to freeze up.
CAUTION
Do not disconnect main unit power when servicing com­pressor(s) if ambient temperature is below 40 F (4.4 C). The compressors have either a single circuit breaker or multiple circuit breakers which can be used to shut off power to the compressors. If power to the unit must be off for a prolonged period, drain the cooler, hydronic package (if installed) and internal piping. Add glycol according to Winter Shutdown Step 2 below.
WINTER SHUTDOWN — At the end of the cooling season:
1. Drain the fluid from the cooler, hydronic package (if in­stalled) and internal piping.
2. Fill the cooler and hydronic package with at least 2 gal­lons (7.6 L) of inhibited propylene glycol or other suit­able inhibited antifreeze solution to prevent any residual water in the cooler and hydronic package/piping from freezing.
3. At the beginning of the next cooling season, refill the cooler and add the recommended inhibitor.
Thermistors — Electronic control uses up to five 5 k
thermistors to sense temperatures used to control operation of the chiller. Thermistors EWT, LWT, RGTA, RGTB, and OAT are identical in their temperature and voltage drop perfor­mance. The SPT space temperature thermistor has a 10 k in­put channel and it has a different set of temperature vs. resis­tance and voltage drop performance. Resistance at various tem­peratures are listed in Tables 33-37. For dual chiller operation, a dual chiller sensor is required which is a 5 k thermistor. When a digital compressor is used, a DTT (digital temperature thermistor) is used. The DTT is an 86 k thermistor.
REPLACING THERMISTORS (EWT, LWT, RGT) — Add a small amount of thermal conductive grease to the thermistor well and end of probe. For all probes, tighten the retaining nut ¼ turn past finger tight. See Fig. 28.
THERMISTOR/TEMPERATURE SENSOR CHECK — A high quality digital volt-ohmmeter is required to perform this check.
1. Connect the digital voltmeter across the appropriate the­mistor terminals at the J8 terminal strip on the Main Base Board (see Fig. 29).
2. Using the voltage reading obtained, read the sensor tem­perature from Tables 33-37.
3. To check thermistor accuracy, measure temperature at probe location with an accurate thermocouple-type tem­perature measuring instrument. Insulate thermocouple to avoid ambient temperatures from influencing reading. Temperature measured by thermocouple and temperature determined from thermistor voltage reading should be close, ± 5° F (3° C) if care was taken in applying thermo­couple and taking readings.
If a more accurate check is required, unit must be shut down and thermistor removed and checked at a known temperature (freezing point or boiling point of water) using either voltage drop measured across thermistor at the J8 terminal, by deter­mining the resistance with chiller shut down and thermistor
52
Page 53
disconnected from J8. Compare the values determined with the
5/8 in. HEX
6" MINIMUM
CLEARANCE FOR
THERMISTOR
REMOVAL
1/4-18 NPT
Fig. 28 — Thermistor Well
value read by the control in the Temperatures mode using the scrolling marquee display.
Pressure Transducers — The suction and discharge
transducers are different part numbers and can be distinguished by the color of the transducer body, suction (yellow) and dis­charge (red). No pressure transducer calibration is required. The transducers operate on a 5 vdc supply, which is generated by the main base board (MBB). See Fig. 29 for transducer con­nections to the J8 connector on the MBB.
TROUBLESHOOTING — If a transducer is suspected of be­ing faulty, first check supply voltage to the transducer. Supply voltage should be 5 vdc ± 0.2 v. If supply voltage is correct, compare pressure reading displayed on the scrolling marquee display module against pressure shown on a calibrated pressure gauge. Pressure readings should be within ± 15 psig. If the two readings are not reasonably close, replace the pressure transducer.
Chilled Water Flow Switch — A factory-installed
flow switch is installed in the leaving fluid piping for all units without the factory-installed hydronic package. See Fig. 30. Units with the optional hydronic package have the flow switch installed in the entering fluid piping. This is a thermal-disper­sion flow switch with no field adjustments. The switch is set for approximately 0.5 ft/sec of flow. The sensor tip houses two thermistors and a heater element. One thermistor is located in the sensor tip, closest to the flowing fluid. This thermistor is used to detect changes in the flow velocity of the liquid. The second thermistor is bonded to the cylindrical wall and is af­fected only by changes in the temperature of the liquid. The thermistors are positioned to be in close contact with the wall of the sensor probe and, at the same time, to be kept separated from each other within the confines of the probe.
In order to sense flow, it is necessary to heat one of the thermistors in the probe. When power is applied, the tip of the probe is heated. As the fluid starts to flow, heat will be carried away from the sensor tip. Cooling of the first thermistor is a function of how fast heat is conducted away by the flowing liquid.
The difference in temperature between the two thermistors provides a measurement of fluid velocity past the sensor probe. When fluid velocity is high, more heat will be carried away from the heated thermistor and the temperature differential will be small. As fluid velocity decreases, less heat will be taken from the heated thermistor and there will be an increase in tem­perature differential.
When unit flow rate is above the minimum flow rate, then the output is switched on, sending 24 vac to the MBB to prove flow has been established.
For recommended maintenance, check the sensor tip for build-up every 6 months. Clean the tip with a soft cloth. If
necessary, build-up (e.g., lime) can be removed with a common vinegar cleansing agent.
The flow sensor cable is provided with (3) LEDs that indi­cate if 24 vac power is present and also status of the switch contacts. The LEDs are as follows:
• Green LED ON – 24 vac present
• One Yellow LED ON – Flow sensor switch OPEN
• Two Yellow LED ON – Flow sensor switch CLOSED
If nuisance trips of the sensor are occurring, follow the steps below to correct the situation:
1. Check to confirm that the factory installed strainer is clean. Use the blow-down valve provided or remove the screen and clean it. For the case of VFD controlled pumps, ensure that the minimum speed setting has not been changed.
2. Measure the pressure drop across the cooler or cooler/ pump system and compare this to the system requirements.
3. Verify that cable connections at the switch and at the ter­minal block are secure.
4. For factory-installed hydronic systems, verify that:
• All air has been purged from the system.
• Circuit setter balance valve has been correctly set.
5. Pump impeller has been improperly trimmed and is not providing sufficient flow.
6. Wrong pump motor rotation. Pump must rotate clockwise when viewed from motor end of pump.
Strainer — Periodic factory-installed strainer cleaning is
required. Pressure drop across strainer in excess of 3 psi (21 kPa) indicates the need for cleaning. Normal (clean) pres­sure drop is approximately 1 psi (6.9 kPa). Open the factory­installed blowdown valve to clean the strainer. If required, shut the chiller down and remove the strainer screen to clean. When strainer has been cleaned, enter ‘YES’ for Strainer Mainte­nance Done (Run Status
PM
S.T.MN).
Condenser Fans — Each fan is supported by a formed
wire mount bolted to a fan deck and covered with a wire guard. METAL FANS — The exposed end of fan motor shaft is pro-
tected from weather by grease and a rubber boot. If fan motor must be removed for service or replacement, be sure to re­grease fan shaft and reinstall fan guard. For proper perfor­mance with the value sound fan option, fan web should be
0.32 in. (8 mm) below top of orifice on the fan deck to top of the fan hub. (See Fig. 31.) Tighten set screws to 15 ± 1 ft-lb (20 ± 1.3 N-m).
IMPORTANT: Check for proper fan rotation (clockwise when viewed from above). If necessary, switch any 2 power leads to reverse fan rotation.
53
Page 54
Table 33 — 5K Thermistor Temperatures (°F) vs. Resistance/Voltage Drop
TEMP
(F)
VO LTAGE
DROP
(V)
RESISTANCE
(Ohms)
–25 3.699 98,010 –24 3.689 94,707 –23 3.679 91,522 –22 3.668 88,449 –21 3.658 85,486 –20 3.647 82,627 –19 3.636 79,871 –18 3.624 77,212 –17 3.613 74,648 –16 3.601 72,175 –15 3.588 69,790 –14 3.576 67,490 –13 3.563 65,272 –12 3.550 63,133 –11 3.536 61,070 –10 3.523 59,081
–9 3.509 57,162 –8 3.494 55,311 –7 3.480 53,526 –6 3.465 51,804 –5 3.450 50,143 –4 3.434 48,541 –3 3.418 46,996 –2 3.402 45,505 –1 3.386 44,066
0 3.369 42,679 1 3.352 41,339 2 3.335 40,047 3 3.317 38,800 4 3.299 37,596 5 3.281 36,435 6 3.262 35,313 7 3.243 34,231 8 3.224 33,185
9 3.205 32,176 10 3.185 31,202 11 3.165 30,260 12 3.145 29,351 13 3.124 28,473 14 3.103 27,624 15 3.082 26,804 16 3.060 26,011 17 3.038 25,245 18 3.016 24,505 19 2.994 23,789 20 2.972 23,096 21 2.949 22,427 22 2.926 21,779 23 2.903 21,153 24 2.879 20,547 25 2.856 19,960 26 2.832 19,393 27 2.808 18,843 28 2.784 18,311 29 2.759 17,796 30 2.735 17,297 31 2.710 16,814 32 2.685 16,346 33 2.660 15,892 34 2.634 15,453 35 2.609 15,027 36 2.583 14,614 37 2.558 14,214 38 2.532 13,826 39 2.506 13,449 40 2.480 13,084 41 2.454 12,730 42 2.428 12,387 43 2.402 12,053 44 2.376 11,730 45 2.349 11,416 46 2.323 11,112 47 2.296 10,816 48 2.270 10,529 49 2.244 10,250 50 2.217 9,979 51 2.191 9,717 52 2.165 9,461 53 2.138 9,213 54 2.112 8,973 55 2.086 8,739 56 2.060 8,511 57 2.034 8,291 58 2.008 8,076
TEMP
(F)
VOLTAGE
DROP
(V)
RESISTANCE
(Ohms)
59 1.982 7,686 60 1.956 7,665 61 1.930 7,468 62 1.905 7,277 63 1.879 7,091 64 1.854 6,911 65 1.829 6,735 66 1.804 6,564 67 1.779 6,399 68 1.754 6,238 69 1.729 6,081 70 1.705 5,929 71 1.681 5,781 72 1.656 5,637 73 1.632 5,497 74 1.609 5,361 75 1.585 5,229 76 1.562 5,101 77 1.538 4,976 78 1.516 4,855 79 1.493 4,737 80 1.470 4,622 81 1.448 4,511 82 1.426 4,403 83 1.404 4,298 84 1.382 4,196 85 1.361 4,096 86 1.340 4,000 87 1.319 3,906 88 1.298 3,814 89 1.278 3,726 90 1.257 3,640 91 1.237 3,556 92 1.217 3,474 93 1.198 3,395 94 1.179 3,318 95 1.160 3,243 96 1.141 3,170 97 1.122 3,099 98 1.104 3,031
99 1.086 2,964 100 1.068 2,898 101 1.051 2,835 102 1.033 2,773 103 1.016 2,713 104 0.999 2,655 105 0.983 2,597 106 0.966 2,542 107 0.950 2,488 108 0.934 2,436 109 0.918 2,385 110 0.903 2,335 111 0.888 2,286 112 0.873 2,239 113 0.858 2,192 114 0.843 2,147 115 0.829 2,103 116 0.815 2,060 117 0.801 2,018 118 0.787 1,977 119 0.774 1,937 120 0.761 1,898 121 0.748 1,860 122 0.735 1,822 123 0.723 1,786 124 0.710 1,750 125 0.698 1,715 126 0.686 1,680 127 0.674 1,647 128 0.663 1,614 129 0.651 1,582 130 0.640 1,550 131 0.629 1,519 132 0.618 1,489 133 0.608 1,459 134 0.597 1,430 135 0.587 1,401 136 0.577 1,373 137 0.567 1,345 138 0.557 1,318 139 0.548 1,291 140 0.538 1,265 141 0.529 1,240 142 0.520 1,214
TEMP
(F)
VO LTAGE
DROP
(V)
RESISTANCE
(Ohms)
143 0.511 1,190 144 0.502 1,165 145 0.494 1,141 146 0.485 1,118 147 0.477 1,095 148 0.469 1,072 149 0.461 1,050 150 0.453 1,029 151 0.445 1,007 152 0.438 986 153 0.430 965 154 0.423 945 155 0.416 925 156 0.408 906 157 0.402 887 158 0.395 868 159 0.388 850 160 0.381 832 161 0.375 815 162 0.369 798 163 0.362 782 164 0.356 765 165 0.350 750 166 0.344 734 167 0.339 719 168 0.333 705 169 0.327 690 170 0.322 677 171 0.317 663 172 0.311 650 173 0.306 638 174 0.301 626 175 0.296 614 176 0.291 602 177 0.286 591 178 0.282 581 179 0.277 570 180 0.272 561 181 0.268 551 182 0.264 542 183 0.259 533 184 0.255 524 185 0.251 516 186 0.247 508 187 0.243 501 188 0.239 494 189 0.235 487 190 0.231 480 191 0.228 473 192 0.224 467 193 0.220 461 194 0.217 456 195 0.213 450 196 0.210 445 197 0.206 439 198 0.203 434 199 0.200 429 200 0.197 424 201 0.194 419 202 0.191 415 203 0.188 410 204 0.185 405 205 0.182 401 206 0.179 396 207 0.176 391 208 0.173 386 209 0.171 382 210 0.168 377 211 0.165 372 212 0.163 367 213 0.160 361 214 0.158 356 215 0.155 350 216 0.153 344 217 0.151 338 218 0.148 332 219 0.146 325 220 0.144 318 221 0.142 311 222 0.140 304 223 0.138 297 224 0.135 289 225 0.133 282
(Voltage Drop for EWT, LWT, RGT, and OAT)
54
Page 55
Table 34 — 5K Thermistor Temperatures (°C) vs. Resistance/Voltage Drop
TEMP
(C)
VO LTAGE
DROP
(V)
RESISTANCE
(Ohms)
–32 3.705 100,260 –31 3.687 94,165 –30 3.668 88,480 –29 3.649 83,170 –28 3.629 78,125 –27 3.608 73,580 –26 3.586 69,250 –25 3.563 65,205 –24 3.539 61,420 –23 3.514 57,875 –22 3.489 54,555 –21 3.462 51,450 –20 3.434 48,536 –19 3.406 45,807 –18 3.376 43,247 –17 3.345 40,845 –16 3.313 38,592 –15 3.281 38,476 –14 3.247 34,489 –13 3.212 32,621 –12 3.177 30,866 –11 3.140 29,216 –10 3.103 27,633
–9 3.065 26,202 –8 3.025 24,827 –7 2.985 23,532 –6 2.945 22,313 –5 2.903 21,163 –4 2.860 20,079 –3 2.817 19,058 –2 2.774 18,094 –1 2.730 17,184
0 2.685 16,325 1 2.639 15,515 2 2.593 14,749 3 2.547 14,026 4 2.500 13,342 5 2.454 12,696 6 2.407 12,085 7 2.360 11,506 8 2.312 10,959
9 2.265 10,441 10 2.217 9,949 11 2.170 9,485 12 2.123 9,044 13 2.076 8,627 14 2.029 8,231
TEMP
(C)
VOLTAGE
DROP
(V)
RESISTANCE
(Ohms)
15 1.982 7,855 16 1.935 7,499 17 1.889 7,161 18 1.844 6,840 19 1.799 6,536 20 1.754 6,246 21 1.710 5,971 22 1.666 5,710 23 1.623 5,461 24 1.580 5,225 25 1.538 5,000 26 1.497 4,786 27 1.457 4,583 28 1.417 4,389 29 1.378 4,204 30 1.340 4,028 31 1.302 3,861 32 1.265 3,701 33 1.229 3,549 34 1.194 3,404 35 1.160 3,266 36 1.126 3,134 37 1.093 3,008 38 1.061 2,888 39 1.030 2,773 40 0.999 2,663 41 0.969 2,559 42 0.940 2,459 43 0.912 2,363 44 0.885 2,272 45 0.858 2,184 46 0.832 2,101 47 0.807 2,021 48 0.782 1,944 49 0.758 1,871 50 0.735 1,801 51 0.713 1,734 52 0.691 1,670 53 0.669 1,609 54 0.649 1,550 55 0.629 1,493 56 0.610 1,439 57 0.591 1,387 58 0.573 1,337 59 0.555 1,290 60 0.538 1,244 61 0.522 1,200
TEMP
(C)
VO LTAGE
DROP
(V)
RESISTANCE
(Ohms)
62 0.506 1,158 63 0.490 1,118 64 0.475 1,079 65 0.461 1,041 66 0.447 1,006 67 0.433 971 68 0.420 938 69 0.407 906 70 0.395 876 71 0.383 836 72 0.371 805 73 0.360 775 74 0.349 747 75 0.339 719 76 0.329 693 77 0.319 669 78 0.309 645 79 0.300 623 80 0.291 602 81 0.283 583 82 0.274 564 83 0.266 547 84 0.258 531 85 0.251 516 86 0.244 502 87 0.237 489 88 0.230 477 89 0.223 466 90 0.217 456 91 0.211 446 92 0.204 436 93 0.199 427 94 0.193 419 95 0.188 410 96 0.182 402 97 0.177 393 98 0.172 385
99 0.168 376 100 0.163 367 101 0.158 357 102 0.154 346 103 0.150 335 104 0.146 324 105 0.142 312 106 0.138 299 107 0.134 285
(Voltage Drop for EWT, LWT, RGT, and OAT)
55
Page 56
Table 35 — 10K Thermistor Temperature (°F) vs. Resistance/Voltage Drop
TEMP
(F)
VO LTAGE
DROP
(V)
RESISTANCE
(Ohms)
–25 4.758 196,453 –24 4.750 189,692 –23 4.741 183,300 –22 4.733 177,000 –21 4.724 171,079 –20 4.715 165,238 –19 4.705 159,717 –18 4.696 154,344 –17 4.686 149,194 –16 4.676 144,250 –15 4.665 139,443 –14 4.655 134,891 –13 4.644 130,402 –12 4.633 126,183 –11 4.621 122,018 –10 4.609 118,076
–9 4.597 114,236 –8 4.585 110,549 –7 4.572 107,006 –6 4.560 103,558 –5 4.546 100,287 –4 4.533 97,060 –3 4.519 94,020 –2 4.505 91,019 –1 4.490 88,171
0 4.476 85,396 1 4.461 82,729 2 4.445 80,162 3 4.429 77,662 4 4.413 75,286 5 4.397 72,940 6 4.380 70,727 7 4.363 68,542 8 4.346 66,465
9 4.328 64,439 10 4.310 62,491 11 4.292 60,612 12 4.273 58,781 13 4.254 57,039 14 4.235 55,319 15 4.215 53,693 16 4.195 52,086 17 4.174 50,557 18 4.153 49,065 19 4.132 47,627 20 4.111 46,240 21 4.089 44,888 22 4.067 43,598 23 4.044 42,324 24 4.021 41,118 25 3.998 39,926 26 3.975 38,790 27 3.951 37,681 28 3.927 36,610 29 3.903 35,577 30 3.878 34,569 31 3.853 33,606 32 3.828 32,654 33 3.802 31,752 34 3.776 30,860 35 3.750 30,009 36 3.723 29,177 37 3.697 28,373 38 3.670 27,597 39 3.654 26,838 40 3.615 26,113 41 3.587 25,396 42 3.559 24,715 43 3.531 24,042 44 3.503 23,399 45 3.474 22,770 46 3.445 22,161 47 3.416 21,573 48 3.387 20,998 49 3.357 20,447 50 3.328 19,903 51 3.298 19,386 52 3.268 18,874 53 3.238 18,384 54 3.208 17,904 55 3.178 17,441 56 3.147 16,991 57 3.117 16,552 58 3.086 16,131 59 3.056 15,714 60 3.025 15,317
TEMP
(F)
VO LTAGE
DROP
(V)
RESISTANCE
(Ohms)
61 2.994 14,925 62 2.963 14,549 63 2.932 14,180 64 2.901 13,824 65 2.870 13,478 66 2.839 13,139 67 2.808 12,814 68 2.777 12,493 69 2.746 12,187 70 2.715 11,884 71 2.684 11,593 72 2.653 11,308 73 2.622 11,031 74 2.592 10,764 75 2.561 10,501 76 2.530 10,249 77 2.500 10,000 78 2.470 9,762 79 2.439 9,526 80 2.409 9,300 81 2.379 9,078 82 2.349 8,862 83 2.319 8,653 84 2.290 8,448 85 2.260 8,251 86 2.231 8,056 87 2.202 7,869 88 2.173 7,685 89 2.144 7,507 90 2.115 7,333 91 2.087 7,165 92 2.059 6,999 93 2.030 6,838 94 2.003 6,683 95 1.975 6,530 96 1.948 6,383 97 1.921 6,238 98 1.894 6,098
99 1.867 5,961 100 1.841 5,827 101 1.815 5,698 102 1.789 5,571 103 1.763 5,449 104 1.738 5,327 105 1.713 5,210 106 1.688 5,095 107 1.663 4,984 108 1.639 4,876 109 1.615 4,769 110 1.591 4,666 111 1.567 4,564 112 1.544 4,467 113 1.521 4,370 114 1.498 4,277 115 1.475 4,185 116 1.453 4,096 117 1.431 4,008 118 1.409 3,923 119 1.387 3,840 120 1.366 3,759 121 1.345 3,681 122 1.324 3,603 123 1.304 3,529 124 1.284 3,455 125 1.264 3,383 126 1.244 3,313 127 1.225 3,244 128 1.206 3,178 129 1.187 3,112 130 1.168 3,049 131 1.150 2,986 132 1.132 2,926 133 1.114 2,866 134 1.096 2,809 135 1.079 2,752 136 1.062 2,697 137 1.045 2,643 138 1.028 2,590 139 1.012 2,539 140 0.996 2,488 141 0.980 2,439 142 0.965 2,391 143 0.949 2,343 144 0.934 2,297 145 0.919 2,253 146 0.905 2,209
TEMP
(F)
VO LTAGE
DROP
(V)
RESISTANCE
(Ohms)
147 0.890 2,166 148 0.876 2,124 149 0.862 2,083 150 0.848 2,043 151 0.835 2,003 152 0.821 1,966 153 0.808 1,928 154 0.795 1,891 155 0.782 1,855 156 0.770 1,820 157 0.758 1,786 158 0.745 1,752 159 0.733 1,719 160 0.722 1,687 161 0.710 1,656 162 0.699 1,625 163 0.687 1,594 164 0.676 1,565 165 0.666 1,536 166 0.655 1,508 167 0.645 1,480 168 0.634 1,453 169 0.624 1,426 170 0.614 1,400 171 0.604 1,375 172 0.595 1,350 173 0.585 1,326 174 0.576 1,302 175 0.567 1,278 176 0.558 1,255 177 0.549 1,233 178 0.540 1,211 179 0.532 1,190 180 0.523 1,169 181 0.515 1,148 182 0.507 1,128 183 0.499 1,108 184 0.491 1,089 185 0.483 1,070 186 0.476 1,052 187 0.468 1,033 188 0.461 1,016 189 0.454 998 190 0.447 981 191 0.440 964 192 0.433 947 193 0.426 931 194 0.419 915 195 0.413 900 196 0.407 885 197 0.400 870 198 0.394 855 199 0.388 841 200 0.382 827 201 0.376 814 202 0.370 800 203 0.365 787 204 0.359 774 205 0.354 762 206 0.349 749 207 0.343 737 208 0.338 725 209 0.333 714 210 0.328 702 211 0.323 691 212 0.318 680 213 0.314 670 214 0.309 659 215 0.305 649 216 0.300 639 217 0.296 629 218 0.292 620 219 0.288 610 220 0.284 601 221 0.279 592 222 0.275 583 223 0.272 574 224 0.268 566 225 0.264 557
(For SPT)
56
Page 57
Table 36 — 10K Thermistor Temperature (°C) vs. Resistance/Voltage Drop
TEMP
(C)
VO LTAGE
DROP
(V)
RESISTANCE
(Ohms)
–32 4.762 200,510 –31 4.748 188,340 –30 4.733 177,000 –29 4.716 166,342 –28 4.700 156,404 –27 4.682 147,134 –26 4.663 138,482 –25 4.644 130,402 –24 4.624 122,807 –23 4.602 115,710 –22 4.580 109,075 –21 4.557 102,868 –20 4.533 97,060 –19 4.508 91,588 –18 4.482 86,463 –17 4.455 81,662 –16 4.426 77,162 –15 4.397 72,940 –14 4.367 68,957 –13 4.335 65,219 –12 4.303 61,711 –11 4.269 58,415 –10 4.235 55,319
–9 4.199 52,392 –8 4.162 49,640 –7 4.124 47,052 –6 4.085 44,617 –5 4.044 42,324 –4 4.003 40,153 –3 3.961 38,109 –2 3.917 36,182 –1 3.873 34,367
0 3.828 32,654 1 3.781 31,030 2 3.734 29,498 3 3.686 28,052 4 3.637 26,686 5 3.587 25,396 6 3.537 24,171 7 3.485 23,013 8 3.433 21,918
9 3.381 20,883 10 3.328 19,903 11 3.274 18,972 12 3.220 18,090 13 3.165 17,255 14 3.111 16,464
TEMP
(C)
VO LTAGE
DROP
(V)
RESISTANCE
(Ohms)
15 3.056 15,714 16 3.000 15,000 17 2.944 14,323 18 2.889 13,681 19 2.833 13,071 20 2.777 12,493 21 2.721 11,942 22 2.666 11,418 23 2.610 10,921 24 2.555 10,449 25 2.500 10,000 26 2.445 9,571 27 2.391 9,164 28 2.337 8,776 29 2.284 8,407 30 2.231 8,056 31 2.178 7,720 32 2.127 7,401 33 2.075 7,096 34 2.025 6,806 35 1.975 6,530 36 1.926 6,266 37 1.878 6,014 38 1.830 5,774 39 1.784 5,546 40 1.738 5,327 41 1.692 5,117 42 1.648 4,918 43 1.605 4,727 44 1.562 4,544 45 1.521 4,370 46 1.480 4,203 47 1.439 4,042 48 1.400 3,889 49 1.362 3,743 50 1.324 3,603 51 1.288 3,469 52 1.252 3,340 53 1.217 3,217 54 1.183 3,099 55 1.150 2,986 56 1.117 2,878 57 1.086 2,774 58 1.055 2,675 59 1.025 2,579 60 0.996 2,488 61 0.968 2,400
TEMP
(C)
VO LTAGE
DROP
(V)
RESISTANCE
(Ohms)
62 0.940 2,315 63 0.913 2,235 64 0.887 2,157 65 0.862 2,083 66 0.837 2,011 67 0.813 1,943 68 0.790 1,876 69 0.767 1,813 70 0.745 1,752 71 0.724 1,693 72 0.703 1,637 73 0.683 1,582 74 0.663 1,530 75 0.645 1,480 76 0.626 1,431 77 0.608 1,385 78 0.591 1,340 79 0.574 1,297 80 0.558 1,255 81 0.542 1,215 82 0.527 1,177 83 0.512 1,140 84 0.497 1,104 85 0.483 1,070 86 0.470 1,037 87 0.457 1,005 88 0.444 974 89 0.431 944 90 0.419 915 91 0.408 889 92 0.396 861 93 0.386 836 94 0.375 811 95 0.365 787 96 0.355 764 97 0.345 742 98 0.336 721
99 0.327 700 100 0.318 680 101 0.310 661 102 0.302 643 103 0.294 626 104 0.287 609 105 0.279 592 106 0.272 576 107 0.265 561
(For SPT)
TEMP
(C)
-40 -40 2,889,600
-35 -31 2,087,220
-30 -22 1,522,200
-25 -13 1,121,440
-20 -4 834,720
-15 5 627,280
-10 14 475,740
-5 23 363,990 0 32 280,820 5 41 218,410
10 50 171,170 15 59 135,140 20 68 107,440 25 77 86,000 30 86 69,280 35 95 56,160 40 104 45,810 45 113 37,580 50 122 30,990 55 131 25,680 60 140 21,400 70 158 15,070
TEMP
(F)
Table 37 — 86K Thermistor vs Resistance (DTT)
RESISTANCE
(Ohms)
TEMP
(C)
75 167 12,730 80 176 10,790 85 185 9,200 90 194 7,870 95 203 6,770 100 212 5,850 105 221 5,090 110 230 4,450 115 239 3,870 120 248 3,350 125 257 2,920 130 266 2,580 135 275 2,280 140 284 2,020 145 293 1,800 150 302 1,590 155 311 1,390 160 320 1,250 165 329 1,120 170 338 1,010 175 347 920 180 356 830
57
TEMP
(F)
RESISTANCE
(Ohms)
Page 58
LOW SOUND FAN — A shroud and a wire guard provide
26
25
24
23
22
17
16
15
14
13
12
11
10
9
8
7
6
3
1
3
1
3
1
6
2
4
2
4
2
12
11
21
20
19
18
10
9
8
7
6
5
4
5
4
3
2
1
4
2
1
3
5
J8
BLK
RED
LVT
4
3
22
23
T-55 ACCSY
SEN
OAT
BLU
BLU
BLK
RED
RGTB
BLK
RED
RGTA
SPTB
-
+
DPTB
-
+
A
C
B
A
C
B
GRN
RED
BLK
GRN
RED
BLK
SPTA
-
+
DPTA
-
+
A
C
B
A
C
B
GRN
RED
BLK
GRN
RED
BLK
BLK
RED
EVAPORATOR ENTERING FLUID TEMP
BLK
RED
EVAPORATOR LEAVING FLUID TEMP
SPACE TEMPERATURE ACCESSORY OR DUAL CHILLER LWT
J12 T55
Fig. 29 — Thermistor Connections to
Main Base Board, J8 Connector
LEGEND
ACCSY — Accessory DPT Discharge Pressure Transducer LWT Leaving Water Temperature Sensor LV T Low Voltage Terminal OAT Outdoor Air Temperature Sensor RGT Return Gas Temperature Sensor SEN Sensor Terminal Block SPT Space Temperature Sensor
a30-4975
Fig. 30 — Chilled Water Flow Switch
a30-499
Fig. 31 — Mounted Fan Position
a30-4976
protection from the rotating fan. The exposed end of the fan motor shaft is protected from weather by grease. If fan motor must be removed for service or replacement, be sure to re­grease fan shaft and reinstall fan guard. The fan motor has a step in the motor shaft. For proper performance, fan should be positioned such that it is securely seated on this step. Tighten the bolt to 15 ± 1 ft-lb (20 ± 1.3 N·m).
IMPORTANT: Check for proper fan rotation (counter­clockwise when viewed from above). If necessary, switch any 2 power leads to reverse fan rotation.
Motormaster® V Controller — The Motormaster V
controller is standard on size 010 and 015 units. For other sizes, the optional or accessory Motormaster V controller uses an in­put signal from the AUX board. See Fig. 32. The controller is factory configured and requires no field programming. If a situ­ation arises where the drive does not function properly, the in­formation provided below and in Table 38 can be used to trou­bleshoot the drive.
WARNING
Hazard of electrical shock. Wait three minutes after discon­necting incoming power before servicing drive. Capacitors retain charge after power is removed. Drive assembly includes externally mounted current limiting resistors. Use extreme caution when servicing the drive. Failure to com­ply could result in possible personal injury.
WARNING
When configured as shown in this literature, this equip­ment is designed to start when it receives line power. Ensure that all personnel are clear of fans and guards are installed before applying power. Failure to comply could result in possible personal injury.
CAUTION
DO NOT connect incoming AC power to output terminals T1, T2, and T3. Severe damage to the drive will result. Do not continuously cycle input power to the drive more than once every two minutes. Damage to the drive will result.
CAUTION
If input power has not been applied to the drive for a period of time exceeding three years (due to storage, etc.), the electrolytic DC bus capacitors within the drive can change internally, resulting in excessive leakage current. This can result in premature failure of the capacitors if the drive is operated after such a long period of inactivity or storage. In order to reform the capacitors and prepare the drive for operation after a long period of inactivity, apply input power to the drive for 8 hours prior to actually operating the motor. Before attempting to operate the drive, motor, and driven equipment, be sure all procedures pertaining to installation and wiring have been properly followed. Fail­ure to comply could result in equipment damage.
GENERAL OPERATION — The speed varies in proportion to a 4 to 20 mA signal produced by the ComfortLink™ con­trols. The MMV output speed is displayed in Hz.
The ComfortLink controls must be configured for MMV operation in order for it to operate. This is configured under the Configuration menu (Configuration
58
MM
MMR.S) and
Page 59
selecting “YES”. This configuration menu also contains the gains and minimum speed for the Motormaster control logic.
CONFIGURATION — The MMV is configured for 1 of 12 operation modes based on the inputs to the control terminal block. The 30RAP units use operating modes 5-8. In these con­figurations, the MMV follows a 4 to 20 mA speed reference signal present on terminals 25 (+) and 2 (-). One additional jumper is required to configure the drive for 50/60 Hz opera­tion and input voltage. See Table 39 for proper inputs. Once the drive is powered, it will change to the mode selected according to the inputs. See Fig. 33.
DRIVE PROGRAMMING
CAUTION
It is strongly recommended that the user NOT change any programming without consulting Carrier service personnel. Unit damage may occur from improper programming.
To enter password and change program values:
1. Press Mode.
2. Upper right decimal point blinks.
3. Display reads “00”. To enter the PROGRAM mode to ac­cess the parameters, press the Mode button. This will ac- tivate the PASSWORD prompt (if the password has not been disabled). The display will read “00” and the upper right-hand decimal point will be blinking. (See Fig. 33.)
4. Use the and buttons to scroll to the password value (the factory default password is “1111”) and press the Mode button. Once the correct password value is entered, the display will read “P01”, which indicates that the PROGRAM mode has been accessed at the beginning of the parameter menu (P01 is the first parameter).
NOTE: If the display flashes “Er”, the password was incorrect, and the process to enter the password must be repeated.
5. Press Mode to display present parameter number. Upper right decimal point blinks.
Use the and buttons to scroll to the desired parameter number.
Once the desired parameter number is found, press the Mode button to display the present parameter setting. The up­per right-hand decimal point will begin blinking, indicating that the present parameter setting is being displayed, and that it can be changed by using the up and down buttons. Use and to change setting. Press Mode to store new setting.
Pressing the Mode will store the new setting and also exit the PROGRAM mode. To change another parameter, press the Mode key again to re-enter the PROGRAM mode (the param­eter menu will be accessed at the parameter that was last viewed or changed before exiting). If the Mode key is pressed within two minutes of exiting the PROGRAM mode, the pass­word is not required to access the parameters. After two min­utes, the password must be entered in order to access the pa­rameters again.
To change password: first enter the current password then change parameter P44 to the desired password.
To disable automatic control mode and enter manual speed control mode:
1. Change P05 to ‘01- keypad’.
2. Push UP and DOWN arrow key to set manual speed.
3. Set P05 to ‘04 - 4-20mA control’ to restore 4 to 20 mA control.
EPM CHIP — The drive uses a electronic programming mod­ule (EPM) chip to store the program parameters. This is an EEPROM memory chip and is accessible from the front of the
VFD. It should not be removed with power applied to the VFD.
LOSS OF CCN COMMUNICATIONS — Carrier Comfort Network
®
(CCN) communications with external control systems can be affected by high frequency electrical noise gen­erated by the Motormaster V control. Ensure unit is well grounded to eliminate ground currents along communication lines.
If communications are lost only while Motormaster V con­trol is in operation, order a signal isolator (CEAS420876-2) and power supplies (CEAS221045-01, 2 required) for the CCN communication line.
Fault Codes
— The drive is programmed to automatically re­start after a fault and will attempt to restart three times after a fault (the drive will not restart after CF, cF, GF, F1, F2-F9, or Fo faults). If all three restart attempts are unsuccessful, the drive will trip into FAULT LOCKOUT (LC), which requires a manual reset.
Manual Reset
— If fault condition has been removed, cycle
power to the chiller to reset the VFD. Troubleshooting
— Troubleshooting the Motormaster® V control requires a combination of observing system operation and VFD information. The drive provides 2 kinds of trouble­shooting modes: a status matrix using the 3-digit display (P57, P58) and real time monitoring of key inputs and outputs. The collective group is displayed through parameters 50-60 and all values are read-only.
P50: FAULT HISTORY — Last 8 faults
P51: SOFTWARE version
P52: DC BUS VOLTAGE — in percent of nominal.
Usually rated input voltage x 1.4
P53: MOTOR VOLAGE — in percent of rated output
voltage
P54: LOAD — in percent of drives rated output current
rating
P55: VDC INPUT — in percent of maximum input:
100 will indicate full scale which is 5 v
P56: 4-20 mA INPUT — in percent of maximum input.
20% = 4 mA, 100% = 20 mA
Manual Starter Trip
— If the VFD manual starter (MS-FC­HS, MS-FC-A1 or MS-FC-B1 depending on model) trips, locate the inrush current protectors (3 round black disks per motor) and verify their resistance. For units operating at 208 v or 230 v, these devices should measure approximately 7 ohms. For all other voltages, they should measure approximately 20 ohms. Check value with mating plug disconnected, power to chiller off and at ambient temperature (not hot immediately after stopping VFD). These are standard resistances at 77 F (25 C). Resistance values decrease at higher temperatures and increase at lower temperatures.
REPLACING DEFECTIVE MODULES — The Comfort-
Link
replacement modules are shown in Table 40. If the main base board (MBB) has been replaced, verify that all configura­tion data is correct. Follow the Configuration mode table and verify that all items under sub-modes UNIT, OPT1 and OPT2 are correct. Any additional field-installed accessories or op­tions (RSET, SLCT sub-modes) should also be verified as well as any specific time and maintenance schedules.
Refer to the Start-Up Checklist for 30RAP Liquid Chillers (completed at time of original start-up) found in the job folder. This information is needed later in this procedure. If the check­list does not exist, fill out the current information in the Config­uration mode on a new checklist. Tailor the various options and configurations as needed for this particular installation.
59
Page 60
Fig. 32 — Typical Motormaster Wiring
CONFIGURATION TABLE
*208-v can run in mode 5 or 6.
MODE NOMINAL VOLTAGE Hz
CONTROL INPUT
(PINS 25, 2)
START JUMPER
5 208/230/460/575* 60 External control 4-20 mA TB1-TB2 6 208/380 60 External control 4-20 mA TB13A-TB2
LEGEND
AUX — Auxiliary FB Fuse Block MM Motormaster OFM — Outdoor Fan Motor TB Terminal Block
a30-4977
L1
L2
L3
Mode
DANGER
T1
T2
T3
B+
B-
DISPLAY
BUTTONS
Mode
MMV TERMINAL BLOCK
EPM
Fig. 33 — Motormaster® V Mode Buttons and Mode Display
LOW AMBIENT OPERATION (MOTORMASTER V) FIOP/ACCESSORY
FC2
11 21
12
13 23
BLK
YEL
MM-A
L1 T1
L2 T2
L3 T3
BLK-1
BLK-2
BLK-3
YEL
2
*1
VIO
240 1/4W
25
2
22
CHC
42
COOLER/PUMP HEATERS (380,460,575V)
CHC
86
~~
MMR
11 14
RED
BLK
BLK-1
BLK-2
BLK-3
~
~
BLK
WHT
BLK
1
2
3
FROM AUX-J4
* MM SIGNAL CONNECTION
1
2
3
~
1
3
COOLER/PUMP HEATERS (208/230,230V)
2
OFM1
GRN/YEL
VOLTAGE
208/230/460/575
380
OFM2
GRN/YEL
BLK
BLK
~
WHT
ZHBT
061
06A31
1
2
3
BLK
YEL
BLU
FB3
11
12
13
HIGH SCCR ONLY
FB1
11
21
22
23
BLK
YEL
BLU
21
BLK
22
12
13
YEL
23
BLU
FB2
11
21
BLK
YEL
BLU
12
13
BLK
22
YEL
23
BLU
60
Page 61
Table 38 — Fault Codes
FAULT CODE DESCRIPTION SOLUTION
AF High Temperature Fault: Ambient temperature is too high;
CF Control Fault: A blank EPM, or an EPM with corrupted data
cF Incompatibility Fault: An EPM with an incompatible parame-
CL CURRENT LIMIT: The output current has exceeded the
GF Data Fault: User data and OEM defaults in the EPM are
HF High DC Bus Voltage Fault: Line voltage is too high; Decel-
JF Serial Fault: The watchdog timer has timed out, indicating
LF Low DC Bus Voltage Fault: Line voltage is too low. Check line voltage — set P01 appropriately OF Output Transistor Fault: Phase to phase or phase to ground
PF Current Overload Fault: VFD is undersized for the applica-
SF Single-phase Fault: Single-phase input power has been
F1 EPM Fault: The EPM is missing or damaged. F2-F9, Fo Internal Faults: The control board has sensed a problem Consult factory Drive display = 60.0 even though it
is cold outside and it should be run­ning slower
Drive display = ‘---’ even though drive should be running
Drive display = 8.0 even though fan should be running faster
VFD flashes 57 and LCS Feedback or speed signal lost. Drive will operate at 57 Hz
Cooling fan has failed (if equipped).
has been installed.
ter version has been installed.
CURRENT LIMIT setting (Parameter 25) and the drive is reducing the output frequency to reduce the output current. If the drive remains in CURRENT LIMIT too long, it can trip into a CURRENT OVERLOAD fault (PF).
corrupted.
eration rate is too fast; Overhauling load.
that the serial link has been lost.
short circuit on the output; Failed output transistor; Boost settings are too high; Acceleration rate is too fast.
tion; Mechanical problem with the driven equipment.
applied to a three-phase drive.
Feedback signal is above set point Check for proper set point
Start jumper is missing Replace start jumper. See section above
Feedback signal is below set point and fan is at minimum speed
until reset or loss of start command. Resetting requires cycling start command (or power).
Check cooling fan operation
Perform a factory reset using Parameter 48 — PROGRAM SELECTION.
Either remove the EPM or perform a factory reset (Parameter 48) to change the parameter version of the EPM to match the parameter version of the drive.
Check for loose electrical connections. Check for faulty condenser fan motor. Check Parameter P25 from Table 39 is set correctly.
Restore factory defaults P48, see section above. If that does not work, replace EPM.
Check line voltage — set P01 appropriately
Check serial connection (computer) Check settings for PXX. Check settings in communication software to match PXX.
Reduce boost or increase acceleration values. If unsuccessful, replace drive.
Check line voltage — set P01 appropriately Check for dirty coils Check for motor bearing failure
Check input power phasing
Check liquid line pressure
Check for proper set point Check liquid line pressure
In stand alone mode: Check transducer wiring and feedback voltage. Feedback voltage dis­played on P-69. Pin 6 should be 5 v output. Pin 5 (feedback) should be somewhere between 0 and 5 v.
LEGEND
EPM Electronic Programming Module LCS Lost Control Signal OEM Outside Equipment Manufacturer VFD Variable Frequency Drive
61
Page 62
Table 39 — Motormaster® V Program Parameters for Operating Modes
PARAMETERS DESCRIPTION
P01 Line Voltage: 01 = low line, 02 = high line 01 02 01 02 P02 Carrier Freq: 01 = 4 kHz, 02 = 6 kHz, 03 = 8 kHz 01 01 01 01 P03 Startup mode: flying restart 06 06 06 06 P04 Stop mode: coast to stop 01 01 01 01
P05
P06 TB-14 output: 01 = none 01 01 01 01 P08 TB-30 output: 01 = none 01 01 01 01 P09 TB-31 Output: 01 = none 01 01 01 01 P10 TB-13A function sel: 01 = none 01 01 01 01 P11 TB-13B function sel: 01 = none 01 01 01 01 P12 TB-13C function sel: 01 = none 01 01 01 01 P13 TB-15 output: 01 = none 01 01 01 01 P14 Control: 01 = Terminal strip 01 01 01 01 P15 Serial link: 02 = enabled 9600,8,N,2 with timer 02 02 02 02 P16 Units editing: 02 = whole units 02 02 02 02 P17 Rotation: 01 = forward only, 03 = reverse only 01 01 01 01 P19 Acceleration time: 10 sec 10 10 10 10 P20 Deceleration time: 10 sec 10 10 10 10 P21 DC brake time: 0 0 0 0 0 P22 DC BRAKE VOLTAGE 0% 0 0 0 0 P23 Min freq = 8 Hz ~ 100 – 160 rpm 8 8 8 8 P24 Max freq 60 60 50 50 P25 Current limit: (%) 125 110 125 110 P26 Motor overload: 100 100 100 100 100 P27 Base freq: 60 or 50 Hz 60 60 50 50 P28 Fixed boost: 0.5% at low frequencies 0.5 0.5 0.5 0.5 P29 Accel boost: 0% 0 0 0 0 P30 Slip compensation: 0% 0 0 0 0 P31 Preset spd #1: speed if loss of control signal 57 57 47 47 P32 Preset spd #2: 0 0 0 0 0 P33 Preset spd #3: 0 0 0 0 0
P34
P35
P36 Preset spd 6 default 0 0 0 0 P37 Preset spd 7 default 0 0 0 0 P38 Skip bandwidth 0 0 0 0 P39 Speed scaling 0 0 0 0 P40 Frequency scaling 50 or 60 Hz 60 60 50 50 P41 Load scaling: default (not used so NA) 200 200 200 200 P42 Accel/decel #2: default (not used so NA) 60 60 60 60 P43 Serial address 1 1 1 1 P44 Password:111 111 111 111 111
P45
P46
P47 Clear history? 01 = maintain. (set to 02 to clear) 01 01 01 01 P48 Program selection: Program 1 – 12 05 06 07 08 P61 PI Mode: 05= reverse, 0-5V, 01 = no PID 01 01 01 01 P62 Min feedback = 0 (0V *10) 0 0 0 0 P63 Max feedback = 50 (5V * 10) 50 50 50 50 P64 Proportional gain = 4% 4 4 4 4 P65 Integral gain = .2 .2 .2 .2 .2 P66 PI acell/decel (set point change filter) = 5 5 5 5 5 P67 Min alarm 0 0 0 0 P68 Max alarm 0 0 0 0
LEGEND
NA — Not Applicable PID — Proportional Integral Derivative TB — Terminal Block
Standard Speed source: 01= keypad, 04=4-20mA (NO PI), 05= R22, 06=R134a
Preset spd 4 default — R22 set point. TB12-2 open
Preset spd 5 default — R134a set point. TB12-2 closed
Speed at min signal: 8 Hz; used when PID mode is disabled and 4-20mA input is at 4 mA
Speed at max feedback: 60 or 50 Hz. Used when PID disabled and 4-20mA input is at 20 mA
MODE
5
04 04 04 04
18.0 18.0 18.0 18.0
12.6 12.6 12.6 12.6
8888
60 60 50 50
MODE
6
MODE
7
MODE
8
62
Page 63
WARNING
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation. There may be more than one disconnect switch. Tag all discon­nect locations to alert others not to restore power until work is completed.
1. Check that all power to unit is off. Carefully disconnect all wires from the defective module by unplugging its connectors.
2. Remove the defective module by removing its mounting screws with a Phillips screwdriver, and removing the module from the control box. Save the screws later use.
3. Verify that the instance jumper (MBB) or address switch­es (all other modules) exactly match the settings of the defective module.
NOTE: Handle boards by mounting standoffs only to avoid electrostatic discharge.
4. Package the defective module in the carton of the new module for return to Carrier.
5. Mount the new module in the unit’s control box using a Phillips screwdriver and the screws saved in Step 2.
6. Reinstall all module connectors. For accessory Navigator replacement, make sure the plug is installed at TB3 in the LEN connector.
7. Carefully check all wiring connections before restoring power.
8. Verify the ENABLE/OFF/REMOTE CONTACT switch is in the OFF position.
9. Restore control power. Verify that all module red LEDs blink in unison. Verify that all green LEDs are blinking and that the scrolling marquee or Navigator™ display is communicating correctly.
10. Verify all configuration information, settings, set points and schedules. Return the ENABLE/OFF/REMOTE CONTACT switch to its previous position.
Table 40 — Replacement Modules
MODULE
Main Base
Board (MBB)
Scrolling Marquee
Display Energy
Management
Module
(EMM)
Navigator
Display
EXV 30GT515217 HK50AA026 AUX 32GB500442E N/A
REPLACEMENT
PART NO. (with
Software)
30RA502134 HK50AA029
HK50AA031 HK50AA030
30GT515218 HK50AA028
HK50AA033 N/A
REPLACEMENT PART
NO. (without Software)
Hydronic Package — If the unit is equipped with a
factory-installed hydronic package, consult the information be­low for proper maintenance and service. In addition to this information, each factory-installed hydronic package is sup­plied with a packet of information supplied by the manufactur­er, Bell & Gossett. Carrier Corporation strongly recommends that this information be thoroughly reviewed prior to operation of the chiller.
PUMP PERFORMANCE CHECK — The factory-installed pumps in the 30RAP units are shipped with a single impeller size available for that pump. The pump was selected based on the flow and head requirements as provided to Carrier. It is not
uncommon for actual pump duty to be different than what was anticipated at time of selection. In many cases, it may be desir­able to make some field modifications to obtain optimum pump performance.
Before any pump modifications are made, it is recommend­ed that actual pump performance be verified and compared to the applicable pump curve. See base unit installation instruc­tions. This can be done in a variety of ways:
1. If pump impeller diameter is known: a. Connect a differential pressure gage across the
pump at the ports provided on the pump volutes.
b. Read GPM from applicable impeller curve.
2. If pump impeller diameter is not known:
If pump impeller diameter has been trimmed and the size is not known, it is necessary to determine which impeller curve to read.
The easiest way to confirm pump performance is to “dead-head” the pump and read the differential pressure across the pressure ports on the pump. “Dead-heading” can be done by shutting the circuit setter valve on the dis­charge side of the pump.
NOTE: Although not all pumps can be safely “dead­headed”, centrifugal pumps (such as on the 30RAP units) can be “dead-headed” for short amounts of time. It is rec­ommended to keep the time short due to excessive heat build-up in the pump.
Since the “dead-head” condition is a no-flow condition, the head will correspond to the intersection of an impel­ler curve with the vertical axis of the pump chart. The correct impeller diameter is that which corresponds to the measured head.
3. Once the impeller diameter is known, proceed as in
Step 1.
4. Water flow rate can be determined by using a differential
pressure gage with the Bell & Gossett circuit setter bal­ance valve calculator. (This information is also provided in the installation instructions.) This method will not di­rectly measure pressure differential seen by the pump, but can be used to “double-check” the pump measurement.
5. Verify that cable connections at the switch and at the ter-
minal block are secure.
6. For factory-installed hydronic system, verify that:
• All air has been purged from the system.
• Circuit setter balance valve has been correctly set.
7. Pump impeller has been improperly trimmed and is not
providing sufficient flow.
8. Wrong pump motor rotation. Pump must rotate clockwise
when viewed from motor end of pump.
PUMP MODIFICATIONS AND IMPELLER TRIMMING — See applicable section in the Installation instructions.
RESET OF CHILLER WATER FLOW — See applicable sec­tion in the Installation instructions.
CHANGING OF PUMP SEALS — See Bell & Gossett ser­vice instruction manual provided with the hydronic package.
MAINTENANCE
Recommended Maintenance Schedule —
lowing are only recommended guidelines. Jobsite conditions may dictate that maintenance schedule is performed more often than recommended.
Routine: For machines with e-coat condenser coils:
Periodic clean water rinse, especially in coastal and industrial applications.
The fol-
63
Page 64
Check condenser coils for debris, clean as necessary. Every month:
Check moisture indicating sight glass for possible refrig­erant loss and presence of moisture.
Every 3 months (for all machines):
Check refrigerant charge.
Check all refrigerant joints and valves for refrigerant leaks, repair as necessary.
Check chilled water flow switch operation.
Check all condenser fans for proper operation.
Check compressor oil level.
Every 12 months (for all machines):
Check all electrical connections, tighten as necessary.
Inspect all contactors and relays, replace as necessary.
Check accuracy of thermistors, replace if greater than ± 2° F (1.2° C) variance from calibrated thermometer.
Obtain and test an oil sample. Change oil only if necessary.
Check to be sure that the proper concentration of anti­freeze is present in the chilled water loop, if applicable.
Verify that the chilled water loop is properly treated.
Check refrigerant filter driers for excessive pressure drop, replace as necessary.
Check chilled water strainers, clean as necessary.
Check cooler heater operation, if equipped.
Check condition of condenser fan blades and that they are securely fastened to the motor shaft.
Perform Service Test to confirm operation of all components.
Check for excessive cooler approach (Leaving Chilled Water Temperature — Saturated Suction Temperature) which may indicate fouling. Clean cooler vessel if necessary.
Microchannel Heat Exchanger (MCHX) Con­denser Coil Maintenance and Cleaning Recommendations
CAUTION
Do not apply any chemical cleaners to MCHX condenser coils. These cleaners can accelerate corrosion and damage the coil.
Routine cleaning of coil surfaces is essential to maintain proper operation of the unit. Elimination of contamination and removal of harmful residues will greatly increase the life of the coil and extend the life of the unit. The following steps should be taken to clean MCHX condenser coils:
1. Remove any foreign objects or debris attached to the coreface or trapped within the mounting frame and brackets.
2. Put on personal protective equipment including safety glasses and/or face shield, waterproof clothing and gloves. It is recommended to use full coverage clothing.
3. Start high pressure water sprayer and purge any soap or industrial cleaners from sprayer before cleaning condens­er coils. Only clean, potable water is authorized for clean­ing condenser coils.
4. Clean condenser face by spraying the core steady and uniformly from top to bottom while directing the spray straight toward the core. Do not exceed 900 psig or 30 de­gree angle. The nozzle must be at least 12 in. from the
core face. Reduce pressure and use caution to prevent damage to air centers.
CAUTION
Excessive water pressure will fracture the braze between air centers and refrigerant tubes.
TROUBLESHOOTING
Complete Unit Stoppage and Restart —
ble causes for unit stoppage and reset methods are shown be­low and in Table 41. Refer to Fig. 3-7 for component arrange­ment and control wiring diagrams.
GENERAL POWER FAILURE — After power is restored, restart is automatic through normal MBB start-up.
UNIT ENABLE-OFF-REMOTE CONTACT SWITCH IS OFF — When the switch is OFF, the unit will stop immediate­ly. Place the switch in the ENABLE position for local switch control or in the REMOTE CONTACT position for control through remote contact closure.
CHILLED FLUID PROOF-OF-FLOW SWITCH OPEN — After the problem causing the loss of flow has been corrected, reset is manual by resetting the alarm with the scrolling mar­quee as shown in Table 42.
OPEN 24-V CONTROL CIRCUIT BREAKER(S) — De­termine the cause of the failure and correct. Reset circuit break­er(s). Restart is automatic after MBB start-up cycle is complete.
COOLING LOAD SATISFIED — Unit shuts down when cooling load has been satisfied. Unit restarts when required to satisfy leaving fluid temperature set point.
THERMISTOR FAILURE — If a thermistor fails in either an open or shorted condition, the unit will be shut down. Replace EWT, LWT, or OAT as required. Unit restarts automatically, but must be reset manually by resetting the alarm with the scrolling marquee as shown in Table 42.
Possi-
CAUTION
If unit stoppage occurs more than once as a result of any of the safety devices listed, determine and correct cause before attempting another restart.
LOW SATURATED SUCTION — Several conditions can lead to low saturated suction alarms and the chiller controls have several override modes built in which will attempt to keep the chiller from shutting down. Low fluid flow, low refrigerant charge and plugged filter driers are the main causes for this condition. To avoid permanent damage and potential freezing of the system, do NOT repeatedly reset these alert and/or alarm conditions without identifying and correcting the cause(s).
COMPRESSOR SAFETIES — The 30RAP units with Com- fortLink™ controls include a compressor protection board that protects the operation of each of the compressors. Each board senses the presence or absence of current to each compressor.
If there is a command for a compressor to run and there is no current, then one of the following safeties or conditions have turned the compressor off:
Compressor Overcurrent line breaks or a motor protection device located in the com­pressor electrical box.
Compressor Short Circuit compressor circuit breaker that provides short circuit protection has tripped.
Compressor Motor Over Temperature break or over temperature switch has opened.
— All compressors have internal
— There will not be current if the
— The internal line-
64
Page 65
High-Pressure Switch Trip
Fig. 34 — Advanced Scroll Temperature
Protection Label
ENTER
ENTER
ENTER
ENTER
ENTER
Fig. 35 — Recommended Minimum Cool Down Time After Compressor is Stopped*
0
10
20
30
40
50
60
70
80
90
100
110
120
0 102030405060708090
Compressor Unloaded Run Time (Minutes)
Recommended Cooling Time
(Mi
nut
es)
*Times are approximate. NOTE: Various factors, including high humidity, high ambient temperature, and the presence of a sound blanket will increase cool-down times.
— The high pressure switch has opened. Below are the factory settings for the fixed high pres­sure switch.
30RAP UNIT
SIZE
010-060 650 4482 500 3447
ASTP Protection Trip
CUTOUT CUT-IN
psig kPa psig kPa
— All non-digital Copeland compres­sors are equipped with an advanced scroll temperature protec­tion (ASTP). A label located above the terminal box identifies models that contain this technology. See Fig. 34.
Advanced scroll temperature protection is a form of inter­nal discharge temperature protection that unloads the scroll compressor when the internal temperature reaches approxi­mately 300 F. At this temperature, an internal bi-metal disk valve opens and causes the scroll elements to separate, which stops compression. Suction and discharge pressures balance while the motor continues to run. The longer the compressor runs unloaded, the longer it must cool before the bi-metal disk resets. See Fig. 35 for approximate reset times.
To manually reset ASTP, the compressor should be stopped and allowed to cool. If the compressor is not stopped, the motor will run until the motor protector trips, which occurs up to 90 minutes later. Advanced scroll temperature protection will
reset automatically before the motor protector resets, which may take up to 2 hours.
High Discharge Gas Temperature Protection
— Units equipped with digital compressors have an additional thermis­tor located on the discharge line, If discharge temperature ex­ceeds 265 F (129.4 C), the digital compressor will be shut off.
Alarms will also occur if the current sensor board malfunc­tions or is not properly connected to its assigned digital input. If the compressor is commanded OFF and the current sensor reads ON, an alert is generated. This will indicate that a com­pressor contactor has failed closed. In this case, a special mode, Compressor Stuck on Control, will be enabled and all other compressors will be turned off. An alarm will then be enabled to indicate that service is required. Outdoor fans will continue to operate. The first outdoor fan stage is turned on immediately. The other stages of fan will be turned on as required by SCT.
Alarms and Alerts — These are warnings of abnormal
or fault conditions, and may cause either one circuit or the whole unit to shut down. They are assigned code numbers as described in Table 42.
Automatic alarms will reset without operator intervention if the condition corrects itself. The following method must be used to reset manual alarms:
Before resetting any alarm, first determine the cause of the alarm and correct it. Enter the Alarms mode indicated by the LED on the side of the scrolling marquee display. Press
and until the sub-menu item RCRN “RESET ALL CURRENT ALARMS” is displayed. Press . The control will prompt the user for a password, by displaying PASS and WORD. Press to display the default pass­word, 1111. Press for each character. If the password has been changed, use the arrow keys to change each individu­al character. Toggle the display to “YES” and press . The alarms will be reset.
65
Page 66
Table 41 — Troubleshooting
SYMPTOMS CAUSE REMEDY
Cooler Circulating Pump Does Not Run
Compressor Cycles Off on Loss of Charge
Compressor Cycles Off on Cooler Freeze Protection
Compressor Shuts Down on High-Pressure Control
Unit Operates Too Long or Continuously
Unusual or Loud System Noises
Compressor Loses Oil Leak in system Repair leak.
Hot Liquid Line Shortage of refrigerant due to leak Repair leak and recharge. Frosted Liquid Line Restricted filter drier Replace filter drier. Frosted Suction Line Expansion valve admitting excess refrigerant (note: this is a
Freeze-Up Improper charging Make sure a full quantity of fluid is flowing through the cooler
Power line open Reset circuit breaker. Control fuse or circuit breaker open Check control circuit for ground or short. Reset breaker and
Tripped power breaker Check the controls. Find the cause of trip and reset breaker. Loose terminal connection Check connections. Improperly wired controls Check wiring and rewire if necessary. Low line voltage Check line voltage — determine location of
Pump motor defective Check motor winding for open or short.
Pump seized Replace pump. Low refrigerant charge Repair leak and recharge.
Thermistor failure Replace thermistor. System load was reduced faster than controller could
remove stages High-pressure control acting erratically Replace control. Noncondensables in system Evacuate and recharge. Condenser dirty Clean condenser. Fans not operating Repair or replace if defective. System overcharged with refrigerant Reduce charge. Low refrigerant charge Add refrigerant. Control contacts fused Replace control. Partially plugged or plugged expansion valve or filter drier Clean or replace as needed. Defective insulation Replace or repair as needed. Damaged compressor Check compressor and replace if necessary. Piping vibration Support piping as required.
Compressor noisy Replace compressor (worn bearings).
Mechanical damage (Failed seals or broken scrolls) Replace compressor. Oil trapped in line Check piping for oil traps.
normal condition for brine applications) Stuck EXV Replace valve if defective.
System not drained for winter shutdown Recommended that system be filled with an appropriate gly-
Loose Thermistor Verify thermistors are fully inserted in wells.
replace fuse.
voltage drop and remedy deficiency.
Replace compressor if necessary.
Unit will restart after fluid temperature rises back into the control band. Avoid rapidly removing system load.
Check for loose pipe connections or damaged compressor
Check for loose compressor holddown bolts.
Replace valve if defective.
while charging, and suction pressure in cooler is equal to or greater than pressure corresponding to 32 F (0° C).
col mixture to prevent freezing of pumps and fluid tubing.
66
Page 67
Table 42 — Alarm and Alert Codes
ALARM/
ALERT
CODE
ALARM
OR
ALERT
T051 Alert
A051 Alarm
T052 Alert
A052 Alarm
T055 Alert
A055 Alarm
T056 Alert
A056 Alarm
A060 Alarm
A061 Alarm
T068 None Circuit A Return Gas Thermistor Failure
T069 None Circuit B Return Gas Thermistor Failure
T073 Alert
T074 Alert
T077 Alert
T078 Alert
T079 Alert
T090 Alert
T091 Alert
T092 Alert
T093 Alert
T094 Alert
Circuit A, Compressor 1 Fail ure
Circuit A, Compressor 1 Fail ure
Circuit A, Compressor 2 Fail ure
Circuit A, Compressor 2 Fail ure
Circuit B, Compressor 1 Fail ure
Circuit B, Compressor 1 Fail ure
Circuit B, Compressor 2 Fail ure
Circuit B, Compressor 2 Fail ure
Cooler Leaving Fluid Thermistor Failure
Cooler Entering Fluid Thermistor Failure
Outside Air Thermistor Fail ure
Space Temperature/Dual Chiller Thermistor Failure
Circuit A Saturated Suction Temperature exceeds Cooler Leaving Fluid Temperature
Circuit B Saturated Suction Temperature exceeds Cooler Leaving Fluid Temperature
Lead/Lag LWT Thermistor Failure
Circuit A Discharge Pressure Transducer Failure
Circuit B Discharge Pressure Transducer Failure
Circuit A Suction Pressure Transducer Failure
Circuit B Suction Pressure Transducer Fail ure
Discharge Gas Thermistor Failure
DESCRIPTION
WHY WAS THIS
ALARM
GENERATED?
Compressor feedback signal does not match relay state
Respective current sensor board (CSB) feedback signal is ON when the compressor should be off
Compressor feedback signal does not match relay state
Respective current sensor board (CSB) feedback signal is ON when the compressor should be off
Compressor feedback signal does not match relay state
Respective current sensor board (CSB) feedback signal is ON when the compressor should be off
Compressor feedback signal does not match relay state
Respective current sensor board (CSB) feedback signal is ON when the compressor should be off
Thermistor outside range of –40 to 245 F (–40 to 118 C)
Thermistor outside range of –40 to 245 F (–40 to 118 C)
If return gas sensors are enabled (RG.EN) and thermistor is outside range of –40 to 245 F (–40 to 118 C)
If return gas sensors are enabled (RG.EN) and thermistor is outside range of –40 to 245 F –40 to 118 C)
Thermistor outside range of –40 to 245 F (–40 to 118 C)
Thermistor outside range of –40 to 245 F (–40 to 118 C)
Faulty expansion valve, suction pressure transducer or leaving fluid thermistor.
Faulty expansion valve, suction pressure transducer or leaving fluid thermistor.
Thermistor outside range of –40 to 245 F (–40 to 118 C)
Outside of range (0 to 667 psig)
Outside of range (0 to 667 psig)
Outside of range (0 to 420 psig)
Outside of range (0 to 420 psig)
Discharge thermistor (DTT) is either open or shorted
ACTION TAKEN
BY CONTROL
Compressor A1 shut down.
Unit shut down Manual
Compressor A2 shut down.
Unit shut down Manual
Compressor B1 shut down.
Unit shut down Manual
Compressor B2 shut down.
Unit shut down Manual
Chiller shut down immediately
Chiller shut down immediately
Circuit A shut down Automatic
Circuit B shut down Automatic
Temperature reset disabled. Chiller runs under normal control/set points. When capacity reaches 0, cooler/pump heaters are energized.
Temperature reset disabled. Chiller runs under normal control/set points.
Circuit A shutdown after pumpdown complete.
Circuit B shutdown after pumpdown complete
Chiller runs as a stand alone machine
Circuit A shut down Automatic
Circuit B shut down Automatic
Circuit A shut down Automatic
Circuit B shut down Automatic
Digital compressor shut down.
RESET
METHOD
Manual
Manual
Manual
Manual
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
PROBABLE
CAUSE
High-pressure switch open, faulty CSB, loss of condenser air, filter drier plugged, non­condensables, operation beyond capability.
Welded compressor contac­tor, CSB wiring error.
High-pressure switch open, faulty CSB, loss of condenser air, filter drier plugged, non­condensables, operation beyond capability.
Welded compressor contac­tor, CSB wiring error.
High-pressure switch open, faulty CSB, loss of condenser air, filter drier plugged, non­condensables, operation beyond capability.
Welded compressor contac­tor, CSB wiring error.
High-pressure switch open, faulty CSB, loss of condenser air, filter drier plugged, non­condensables, operation beyond capability.
Welded compressor contac­tor, CSB wiring error.
Thermistor failure, damaged cable/wire or wiring error.
Thermistor failure, damaged cable/wire or wiring error.
Thermistor failure, damaged cable/wire or wiring error.
Thermistor failure, damaged cable/wire or wiring error.
Thermistor failure, damaged cable/wire or wiring error.
Thermistor failure, damaged cable/wire or wiring error.
Faulty expansion valve or suction pressure transducer or leaving fluid thermistor.
Faulty expansion valve or suction pressure transducer or leaving fluid thermistor.
Dual LWT thermistor failure, damaged cable/wire or wiring error.
Transducer failure, poor connection to MBB, or wiring damage/error.
Transducer failure, poor connection to MBB, or wiring damage/error.
Transducer failure, poor connection to MBB, or wiring damage/error.
Transducer failure, poor connection to MBB, or wiring damage/error.
Thermistor failure, damaged cable/wire or wiring error.
67
Page 68
Table 42 — Alarm and Alert Codes (cont)
ALARM/
ALERT
CODE
T110 Alert Circuit A Loss of Charge
T111 Alert Circuit B Loss of Charge
T112 Alert
T113 Alert
T114 Alert
T115 Alert
T116 Alert
T117 Alert
T118 Alert
A118 Alarm
T126 Alert
T127 Alert
T133 Alert
T134 Alert
A140 Alert
A150 Alarm Emergency Stop
A151 Alarm Illegal Configuration
A152 Alarm
ALARM
OR
ALERT
DESCRIPTION
Circuit A High Saturated Suction Temperature
Circuit B High Saturated Suction Temperature
Circuit A Low Suction Superheat
Circuit B Low Suction Superheat
Circuit A Low Cooler Suction Temperature
Circuit B Low Cooler Suction Temperature
High Discharge Gas Temperature Alert
High Discharge Gas Temperature
Circuit A High Discharge Pressure
Circuit B High Discharge Pressure
Circuit A Low Suction Pressure
Circuit B Low Suction Pressure
Reverse Rotation Detected
Unit Down Due to Failure
WHY WAS THIS
ALARM
GENERATED?
If the compressors are off and discharge pressure reading is < 26 psig for 30 sec.
If the compressors are off and discharge pressure reading is < 26 psig for 30 sec.
Circuit saturated suction temperature pressure transducer > 70 F (21.1 C) for 5 minutes
Circuit saturated suction temperature pressure transducer > 70 F (21.1 C) for 5 minutes
Suction superheat is less than 5° F (2.8 C) for 5 minutes.
Suction superheat is less than 5° F (2.8 C) for 5 minutes.
Mode 7 caused the com­pressor to unload 6 consecu­tive times with less than a 30-minute interval between each circuit shutdown.
Mode 8 caused the com­pressor to unload 6 consecu­tive times with less than a 30-minute interval between each circuit shutdown.
Discharge Thermistor (DTT) reading is greater than 250 F
3 Discharge Gas Tempera­ture alarms occur within a day
Compressor operation out­side of operating envelope.
Compressor operation out­side of operating envelope.
Suction pressure below 34 psig for 8 seconds or below 23 psig
Suction pressure below 34 psig for 8 seconds or below 23 psig
Incoming chiller power leads not phased correctly
CCN emergency stop command received
One or more illegal configurations exists.
Both circuits are down due to alarms/alerts.
ACTION TAKEN
BY CONTROL
Circuit not allowed to start.
Circuit not allowed to start.
Circuit shut down Manual
Circuit shut down Manual
Circuit A shut down.
Circuit B shut down.
Circuit shut down Manual
Circuit shut down Manual
Compressor A1 shut down
Compressor A1 shut down
Circuit shut down
Circuit shut down
Circuit shut down
Circuit shut down
Chiller not allowed to start.
Chiller shutdown without going through pumpdown.
Chiller is not allowed to start.
Chiller is unable to run.
RESET
METHOD
Manual
Manual
Automatic restart
after first daily
occurrence.
Manual restart
thereafter.
Automatic restart
after first daily
occurrence.
Manual restart
thereafter.
Autom atic
Manual
Automatic, only after first 3 daily occurrences. Manual reset thereafter. Read­ing from OAT sen­sor must drop 5 F (2.8 C) before restart
Automatic, only after first 3 daily occurrences. Man­ual reset thereafter. Reading from OAT sensor must drop 5 F (2.8 C) before restart
Automatic restart after first daily occurrence. Manual restart thereafter.
Automatic restart after first daily occurrence. Manual restart thereafter.
Manual
Automatic once CCN command for EMSTOP returns to normal
Manual once configuration errors are corrected
Automatic once alarms/alerts are cleared that pre­vent the chiller from starting.
PROBABLE
CAUSE
Refrigerant leak or transducer failure
Refrigerant leak or transducer failure
Faulty Expansion valve, faulty suction pressure transducer or high entering fluid temperature.
Faulty Expansion valve, faulty suction pressure transducer or high entering fluid temperature.
Faulty expansion valve, faulty suction pressure transducer, faulty suction gas thermistor, circuit overcharged
Faulty expansion valve, faulty suction pressure transducer, faulty suction gas thermistor, circuit overcharged
Faulty expansion valve, low refrigerant charge, plugged filter drier, faulty suction pressure transducer, low cooler fluid flow
Faulty expansion valve, low refrigerant charge, plugged filter drier, faulty suction pressure transducer, low cooler fluid flow
Refrigerant charge, plugged filter drier, head pressure control.
Refrigerant charge, plugged filter drier, head pressure control.
Faulty transducer/high pressure switch, low/ restricted condenser airflow
Faulty transducer/high pressure switch, low/ restricted condenser airflow
Faulty or sticking EXV, low refrigerant charge, plugged filter drier.
Faulty or sticking EXV, low refrigerant charge, plugged filter drier.
Reverse any two incoming power leads to correct. Check for correct fan rotation first.
CCN Network command.
Configuration error. Check unit settings.
Alarm notifies user that chiller is 100% down.
68
Page 69
Table 42 — Alarm and Alert Codes (cont)
ALARM/
ALERT
CODE
T153 Aler t
A154 Alarm
T155 Aler t
A156 Alarm
A157 Alarm A/D Hardware Failure
A172 Alarm
T173 Aler t
T174 Aler t
T175 Aler t
T176 Aler t
T177 Aler t
A189 Alarm
T190 Aler t
T191 Aler t
T192 Aler t
T193 Aler t
T194 Aler t
T195 Aler t
T196 Aler t
ALARM
OR
ALERT
DESCRIPTION
Real Time Clock Hardware Failure
Serial EEPROM Hardware Failure
Serial EEPROM Storage Failure
Critical Serial EEPROM Storage Failure
Loss of Communication with EXV Board
Loss of Communication with EMM
4 to 20 mA Cooling Set Point Input Failure
Loss of Communication with the AUX Board
4 to 20 mA Temperature Reset Input Failure
4 to 20 mA Demand Limit Input Failure
Cooler Pump Auxiliary Contact Inputs Miswired
Cooler Pump 1 Aux Contacts Failed to Close at Start-Up
Cooler Pump 2 Aux Contacts Failed to Close at Start-Up
Cooler Pump 1 Failed to Provide Flow at Start-Up
Cooler Pump 2 Failed to Provide Flow at Start-Up
Cooler Pump 1 Aux Contacts Opened During Normal Operation
Cooler Pump 2 Aux Contacts Opened During Normal Operation
Flow Lost While Pump 1 Running
WHY WAS THIS
ALARM
GENERATED?
Internal clock on MBB fails
Hardware failure with MBB
Configuration/storage failure with MBB
Configuration/storage failure with MBB
Hardware failure with peripheral device
MBB loses communication with EXV board
MBB loses communication with EMM
If configured with EMM and input less than 2 mA or greater than 22 mA
MBB loses communication with AUX Board.
If configured with EMM and input less than 2 mA or greater than 22 mA
If configured with EMM and input less than 2 mA or greater than 22 mA
Pump 1 Auxiliary Contacts are closed when Pump 2 output is energized or if Pump 2 Auxiliary Contacts are closed when Pump 1 output is energized.
Pump 1 Auxiliary Contacts did not close within 26 seconds after pump was started
Pump 2 Auxiliary Contacts did not close within 26 seconds after pump was started
Pump 1 did not provide flow to close flow switch within 60 seconds
Pump 2 did not provide flow to close flow switch within 60 seconds
Pump 1 Auxiliary Contacts open for 26 seconds after initially made. All compressors shut down. Pump 1 turned off.
Pump 2 Auxiliary Contacts open for 26 seconds after initially made. All compressors shut down. Pump 2 turned off.
Cooler flow switch contacts open for 3 seconds after initially made
ACTI ON TAKEN
BY CONTROL
Occupancy schedule will not be used. Chiller defaults to Local On mode.
Chiller is unable to run.
No Action Manual
Chiller is not allowed to run.
Chiller is not allowed to run.
Chiller is not allowed to run.
4 to 20 mA temperature reset disabled. Demand Limit set to 100%. 4 to 20 mA set point disabled.
Set point function disabled. Chiller controls to CSP1.
Reset function disabled. Chiller returns to normal set point control.
Demand limit function disabled. Chiller returns to 100% demand limit control.
Both pump outputs are turned off.
Pump 1 turned off. Pump 2 will be started if available.
Pump 2 turned off. Pump 1 will be started if available.
Pump 1 turned off. Pump 2 will be started if available.
Pump 1 turned off. Pump 2 will be started if available.
Pump 2 will be started if available. Chiller allowed to run if Pump 2 successfully starts.
Pump 1 will be started if available. Chiller allowed to run if Pump 1 successfully starts.
All compressors shut down. Pump 1 turned off. Pump 2 will be started if available. Chiller allowed to run if Pump 2 successfully starts and flow switch is closed.
RESET
METHOD
Automatic when correct clock control restarts.
Manual
Manual
Manual
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
PROBABLE
CAUSE
Time/Date/Month/ Day/Year not properly set.
Main Base Board failure.
Potential failure of MBB. Download current operating software. Replace MBB if error occurs again.
Main Base Board failure.
Main Base Board failure.
Wiring error, faulty wiring or failed EXV board.
Wiring error, faulty wiring or failed Energy Manage­ment Module (EMM).
Faulty signal generator, wiring error, or faulty EMM.
Wiring error, faulty wiring or failed AUX board.
Faulty signal generator, wiring error, or faulty EMM.
Faulty signal generator, wiring error, or faulty EMM.
Wiring error, faulty pump contactor auxiliary contacts.
Wiring error, faulty contacts on pump contactor
Wiring error, faulty contacts on pump contactor
Wiring error, pump circuit breaker tripped, contactor failure
Wiring error, pump circuit breaker tripped, contactor failure
Wiring error, faulty contacts on pump contactor
Wiring error, faulty contacts on pump contactor
Wiring error, pump circuit breaker tripped, contactor failure
69
Page 70
Table 42 — Alarm and Alert Codes (cont)
ALARM/
ALERT
CODE
T197 Aler t
T198 Aler t
T199 Aler t
T200 Aler t
A201 Alarm
A202 Alarm
T203 Aler t
T204 Aler t
T205 Aler t
T206 Aler t
A207 Alarm
A208 Alarm
T300 Aler t
T301 Aler t
ALARM
ALERT
OR
DESCRIPTION
Flow Lost While Pump 2 Running
Cooler Pump 1 Aux Contacts Closed While Pump Off
Cooler Pump 2 Aux Contacts Closed While Pump Off
Cooler Flow/Interlock Contacts Failed to Close at Start-Up
Cooler Flow/Interlock Contacts Opened During Normal Operation
Cooler Pump Interlock Closed When Pump is Off
Loss of Communication with Slave Chiller
Loss of Communication with Master Chiller
Master and Slave Chiller with Same Address
High Leaving Chilled Water Temperature
Cooler Freeze Protection
EWT or LWT Thermistor failure
Cooler Pump 1 Scheduled Maintenance Due
Cooler Pump 2 Scheduled Maintenance Due
WHY WAS THIS
ALARM
GENERATED?
Cooler flow switch contacts open for 3 seconds after initially made
Pump 1 Auxiliary Contacts closed for 26 seconds when pump state is off
Pump 2 Auxiliary Contacts closed for 26 seconds when pump state is off
Cooler flow switch contacts failed to close within 1 minute (if cooler pump control is enabled) or within 5 minutes (if cooler pump control is not enabled) after start-up
Flow switch opens for at least 3 seconds after being initially closed
If configured for cooler pump control and flow switch input is closed for 5 minutes while pump output(s) are off
Master chiller MBB loses communication with slave chiller MBB
Slave chiller MBB loses communication with master chiller MBB
Master and slave chiller have the same CCN address (CCN.A)
LWT read is greater than LCW Alert Limit, Total capacity is 100% and LWT is greater than LWT reading one minute ago
Cooler EWT or LWT is less than Brine Freeze (BR.FZ)
Cooler EWT is less than LWT by 3° F (1.7° C) for 1 minute after a circuit is started
Pump 1 Service Countdown (P.1.DN) expired. Complete pump 1 maintenance and enter 'YES' for Pump 1 Maintenance Done (P.1.MN) item.
Pump 2 Service Countdown (P.2.DN) expired. Complete pump 2 maintenance and enter 'YES' for Pump 1 Maintenance Done (P.2.MN) item.
ACTI ON TAKEN
BY CONTROL
All compressors shut down. Pump 2 turned off. Pump 1 will be started if available. Chiller allowed to run if Pump 1 successfully starts and flow switch is closed.
Chiller not allowed to start
Chiller not allowed to start
Chiller not allowed to start. For models with dual pumps, the second pump will be started if available
All compressors shut down. For models with dual pumps, the second pump will be started if available
Chiller shut down
Dual chiller control disabled. Chiller runs as a stand-alone machine.
Dual chiller control disabled. Chiller runs as a stand-alone machine
Dual chiller routine disabled. Master/slave run as stand-alone chillers.
Alert only. No action taken.
Chiller shutdown without going through pumpdown. Cooler pump continues to run a minimum of 5 minutes (if control enabled).
Chiller shutdown. Cooler pump shut off (if control enabled).
None Automatic
None Automatic
RESET
METHOD
Manual
Automatic when aux contacts open
Automatic when aux contacts open
Manual
Manual
Automatic when aux contacts open
Automatic
Automatic
Automatic
Automatic
Both EWT and LWT must be at least 6 F (3.3 C) above Brine Freeze point (BR.FZ). Automatic for first, Manual reset thereaf­ter.
Manual
PROBABLE
CAUSE
Wiring error, pump circuit breaker tripped, contactor failure
Wiring error, faulty pump contactor (welded contacts)
Wiring error, faulty pump contactor (welded contacts)
Wiring error, pump circuit breaker tripped, contactor failure, faulty flow switch or interlock
Cooler pump failure, faulty flow switch or interlock, pump circuit breaker tripped
Wiring error, faulty pump contactor (welded contacts)
Wiring error, faulty wiring, failed Slave chiller MBB module, power loss at slave chiller, wrong slave address.
Wiring error, faulty wiring, failed master chiller MBB module, power loss at Master chiller.
CCN Address for both chillers is the same. Must be different. Check CCN.A under the OPT2 sub-mode in Configuration at both chillers.
Building load greater than unit capacity, low water/brine flow or compressor fault. Check for other alarms/alerts.
Faulty thermistor, low water flow.
Faulty cooler pump, low water flow, plugged fluid strainer.
Routine pump maintenance required
Routine pump maintenance required
70
Page 71
Table 42 — Alarm and Alert Codes (cont)
ALARM/
ALERT
CODE
T302 Alert
T303 Alert
T500 Alert
T501 Alert
T502 Alert
T503 Alert
T504 Alert
T505 Alert
T950 Alert Loss of Communication
T951 Alert Loss of Communication
T952 Alert Loss of Communication
CCN Carrier Comfort Network CSB Current Sensor Board EEPROM — Electronic Eraseable Programmable Read Only Memory EMM Energy Management Module EWT Entering Fluid Temperature EXV Electronic Expansion Valve HSM Hydronic System Manager LCW Leaving Chilled Water LWT Leaving Fluid Temperature MBB Main Base Board OAT Outdoor-Air Temperature SCT Saturated Condensing Temperature WSM Water System Manager
ALARM
OR
ALERT
LEGEND FOR TABLE 42
DESCRIPTION
Strainer Blowdown Scheduled Maintenance Due
Condenser Coil Maintenance Due
Current Sensor Board A1 Failure
Current Sensor Board A2 Failure
Current Sensor Board A3 Failure
Current Sensor Board B1 Failure
Current Sensor Board B2 Failure
Current Sensor Board B3 Failure
with Water System Manager
with Chillervisor System Manager
with Hydronic System Manager
WHY WAS THIS
ALARM
GENERATED?
Strainer Service Countdown (S.T.DN) expired. Complete strainer blowdown and enter 'YES' for Strainer Maintenance Done (S.T.MN) item.
Coil Service Countdown (C.L.DN) expired. Complete condenser coil cleaning and enter 'YES' for Coil Maintenance Done (C.L.MN) item.
Alert occurs when CSB out­put is a constant high value
Alert occurs when CSB out­put is a constant high value
Alert occurs when CSB out­put is a constant high value
Alert occurs when CSB out­put is a constant high value
Alert occurs when CSB out­put is a constant high value
Alert occurs when CSB out­put is a constant high value
No communications have been received by the MBB within 5 minutes of last transmission
No communications have been received by the MBB within 5 minutes of last transmission
No communications have been received by the MBB within 5 minutes of last transmission
ACTION TAKEN
BY CONTROL
None Automatic
None Automatic
Compressor A1 shut down
Compressor A2 shut down
Compressor A3 shut down
Compressor B1 shut down
Compressor B2 shut down
Compressor B3 shut down
WSM forces removed. Chiller runs under own control
CSM forces removed. Chiller runs under own control
HSM forces removed. Chiller runs under own control
RESET
METHOD
Autom atic
Autom atic
Autom atic
Autom atic
Autom atic
Autom atic
Automatic Failed module, wiring
Automatic Failed module, wiring
Automatic Failed module, wiring
PROBABLE
CAUSE
Routine strainer maintenance required
Routine condenser coil maintenance required
CSB failure. Wiring error.
CSB failure. Wiring error.
CSB failure. Wiring error.
CSB failure. Wiring error.
CSB failure. Wiring error.
CSB failure. Wiring error.
error, failed transformer, loose connection plug, wrong address
error, failed transformer, loose connection plug, wrong address
error, failed transformer, loose connection plug, wrong address
COMPRESSOR FAILURE ALERTS T051, T052 (Circuit A Compresser Failures) T055, T056 (Circuit B Compressor Failures) — Alert codes
051, 052, 055, and 056 are for compressors A1, A2, B1, and B2 respectively. These alerts occur when the current sensor (CS) does not detect compressor current during compressor op­eration. When this occurs, the control turns off the compressor.
If the current sensor board reads OFF while the compressor
relay has been commanded ON, an alert is generated. POSSIBLE CAUSES Compressor Overload
— Either the compressor internal over­load protector is open or the external overload protector (Kri­wan module) has activated. The external overload protector modules are mounted in the compressor wiring junction box. Temperature sensors embedded in the compressor motor wind­ings are the inputs to the module. The module is powered with 24 vac from the units main control box. The module output is a normally closed contact that is wired in series with the com­pressor contactor coil. In a compressor motor overload condi­tion, contact opens, deenergizing the compressor contactor.
Low Refrigerant Charge
— If the compressor operates for an extended period of time with low refrigerant charge, the com­pressor ASTP device will open, which will cause the compres­sor to trip on its overload protection device.
Circuit Breaker Trip
— The compressors are protected from
short circuit by a breaker in the control box. Wiring Error
— A wiring error might not allow the compres-
sor to start.
To check out alerts T051-T056:
1. Turn on the compressor in question using Service Test mode. If the compressor does not start, then most likely the problem is one of the following: HPS open, open in­ternal protection, circuit breaker trip, incorrect safety wir­ing, or incorrect compressor wiring.
2. If the compressor does start, verify it is rotating in the cor­rect direction.
IMPORTANT: Prolonged operation in the wrong direction can damage the compressor. Correct rotation can be veri­fied by a gage set and looking for a differential pressure rise on start-up.
71
Page 72
IMPORTANT: If the CS is always detecting current, verify that the compressor is on. If the compressor is on, check the contactor and the relay on the MBB. If the compressor is off and there is no current, verify the CSB wiring and replace if necessary.
IMPORTANT: Return to Normal mode and observe com­pressor operation to verify that compressor current sensor is working and condenser fans are energized.
COMPRESSOR STUCK ON FAILURE ALARMS Circuit A A051, A052 Circuit B A055, A056 — Alarm codes 051, 052, 055, and
056 are for compressors A1, A2, B1, and B2. These alarms oc­cur when the CSB detects current when the compressor should be off. When this occurs, the control turns off the compressor.
If the current sensor board reads ON while the compressor relay has been commanded OFF for a period of 4 continuous seconds, an alarm is generated. These alarms are only moni­tored for a period of 10 seconds after the compressor relay has been commanded OFF. This is done to facilitate a service tech­nician forcing a relay to test a compressor.
In addition, if a compressor stuck failure occurs and the cur­rent sensor board reports the compressor and the request off, certain diagnostics will take place as follows:
1. If any of the compressors are diagnosed as stuck on and the current sensor board is on and the request is off, the control will command the condenser fans to maintain normal head pressure.
2. The control will shut-off all other compressors. The possible causes include welded contactor or frozen
compressor relay on the MBB.
To check out alarms A051-A056:
1. Place the unit in Service Test mode. All compressors should be off.
2. Verify that there is not 24-v at the contactor coil. If there is 24 v at the contactor, check relay on MBB and wiring.
3. Check for welded contactor.
4. Verify CSB wiring.
5. Return to Normal mode and observe compressor opera­tion to verify that compressor current sensor is working and condenser fans are energized.
A060 (Cooler Leaving Fluid Thermistor Failure) sensor reading is outside the range of –40 to 245 F (–40 to 118 C) then the alarm will occur. The cause of the alarm is usu­ally a faulty thermistor, a shorted or open thermistor caused by a wiring error, or a loose connection. Failure of this thermistor will shut down the entire unit.
A061 (Cooler Entering Thermistor Failure) reading is outside the range of –40 to 240 F (–40 to116 C) then the alarm will occur. The cause of the alarm is usually a faulty thermistor, a shorted or open thermistor caused by a wiring er­ror, or a loose connection. Failure of this thermistor will shut down the entire unit.
T068, T69 (Circuit A,B Compressor Return Gas Tempera­ture Thermistor Failure) — This alert occurs when the com­pressor return gas temperature sensor is outside the range of –40 to 240 F (–40 to 116 C). Failure of this thermistor will shut down the appropriate circuit.
T073 (Outside Air Temperature Thermistor Failure) alert occurs when the outside air temperature sensor is outside the range of –40 to 240 F (–40 to 116 C). Failure of this therm­istor will disable any elements of the control which requires its use.
T074 (Space Temperature Thermistor Failure) occurs when the space temperature sensor is outside the range
— The
— If the sensor
— This
— This alert
of –40 to 245 F (–40 to 118 C). Failure of this thermistor will disable any elements of the control which requires its use. The cause of the alert is usually a faulty thermistor in the T55, or T58 device, a shorted or open thermistor caused by a wiring er­ror, or a loose connection.
T090 (Circuit A Discharge Pressure Transducer Failure) T091 (Circuit B Discharge Pressure Transducer Failure) —
Alert codes 090 and 091 are for circuits A and B respectively. These alerts occur when the pressure is outside the range of 0.0 to 667.0 psig. A circuit cannot run when this alert is active. Use the scrolling marquee to reset the alert. The cause of the alert is usually a faulty transducer, faulty 5-v power supply, or a loose connection.
T092 (Circuit A Suction Pressure Transducer Failure) T093 (Circuit B Suction Pressure Transducer Failure) —
Alert codes 092 and 093 are for circuits A and B respectively. These alerts occur when the pressure is outside the range of 0.0 to 420.0 psig. A circuit cannot run when this alert is active. Use the scrolling marquee to reset the alert. The cause of the alert is usually a faulty transducer, faulty 5-v power supply, or a loose connection.
T094 (Discharge Gas Thermistor Failure) curs for units which have the digital compressor installed on circuit A. If discharge gas temperature is open or shorted, the circuit will be shutoff. The alert will reset itself when discharge temperature is less than 250 F (121.1 C). The cause of the alert is usually low refrigerant charge or a faulty thermistor.
T110 (Circuit A Loss of Charge) T111 (Circuit B Loss of Charge) — Alert codes 110 and 111
are for circuits A and B respectively. These alerts occur when the compressor is OFF and the discharge pressure is less than 26 psig.
T112 (Circuit A High Saturated Suction Temperature) T113 (Circuit B High Saturated Suction Temperature) —
Alert codes 112 and 113 occur when compressors in a circuit have been running for at least 5 minutes and the circuit saturat­ed suction temperature is greater than 70 F (21.1 C). The high saturated suction alert is generated and the circuit is shut down.
T114 (Circuit A Low Superheat) T115 (Circuit B Low Superheat) — Alert codes 114 and 115 occur when the superheat of a circuit is less than 5 F (2.8 C) for 5 continuous minutes. The low superheat alert is generated and the circuit is shut down.
T116 (Circuit A Low Cooler Suction Temperature) T117 (Circuit B Low Cooler Suction Temperature) — Alert
codes 116 and 117 are for circuits A and B respectively. These alerts are generated if the capacity stages are reduced three times without a 30 minute interval between capacity reductions due to operating mode 7 or mode 8.
T118 (High Discharge Gas Temperature Alert) A118 (High Discharge Gas Temperature Alarm) — This
alert or alarm occurs for units which have the digital compres­sor installed on circuit A. If discharge gas temperature is great­er than 268 F (131.1 C), the circuit will be shut off. The alert will reset itself when discharge temperature is less than 250 F (121.1 C). If this alert occurs 3 times within a day, the A118 alarm will be generated and the alarm must be reset manually. The cause of the alert is usually low refrigerant charge or a faulty thermistor.
T126 (Circuit A High Head Pressure) T127 (Circuit B High Head Pressure) — Alert codes 126 and
127 are for circuits A and B respectively. These alerts occur when the appropriate saturated condensing temperature is greater than the operating envelope shown in Fig 14. Prior to the alert, the control will shut down one compressor on a circuit if that circuit's saturated condensing temperature is greater than the maximum SCT minus 5° F (2.7° C). If SCT continues to
— This alert oc-
72
Page 73
rise to greater than the maximum SCT, the alert will occur and the circuit's remaining compressor will shut down. The cause of the alarm is usually an overcharged system, high outdoor ambient temperature coupled with dirty outdoor coil, plugged filter drier, or a faulty high-pressure switch.
T133 (Circuit A Low Suction Pressure) T134 (Circuit B Low Suction Pressure) — Alert codes 133
and 134 are for circuits A and B respectively. These alerts are generated if one of the two following conditions is satisfied: the circuit suction pressure is below 34 psig (234.4 kPa) for 8 seconds, or the suction pressure is below 23 psig (158.6 kPa). The cause of this alert may be low refrigerant charge, plugged liquid line filter drier, or sticking EXV. Check head pressure operation. If not equipped, consider adding low ambient tem­perature head pressure control.
Add wind baffles if required.
A140 (Reverse Rotation Detected) power up, for suction pressure change on the first activated cir­cuit. The unit control determines failure as follows:
1. The suction pressure of both circuits is sampled 5 seconds before the compressor is brought on, right when the com­pressor is brought on and 5 seconds afterwards.
2. The rate of suction pressure change from 5 seconds be­fore the compressor is brought on to when the compres­sor is brought on is calculated.
3. The rate of suction pressure change from when the compressor is brought on to 5 seconds afterwards is calculated.
4. With the above information, the test for reverse rotation is made. If the suction pressure change 5 seconds after com­pression is greater than the suction pressure change 5 sec­onds before compression – 1.25, then there is a reverse rotation error.
This alarm will disable mechanical cooling and will require
manual reset. A150 (Unit is in Emergency Stop)
stop command is received, the alarm is generated and the unit will be immediately stopped.
If the CCN point name "EMSTOP" in the system table is set to emergency stop, the unit will shut down immediately and broadcast an alarm back to the CCN, indicating that the unit is down. This alarm will clear when the variable is set back to "enable."
A151 (Illegal Configuration) invalid configuration has been entered. The following are ille­gal configurations.
• Invalid unit size has been entered.
• Dual thermostat configured for single-circuit unit.
• Dual thermostat and switch demand limit configure
• AUX board incorrect revision.
• Unit configuration set to invalid type. A152 (Unit Down Due to Failure)
due to alerts and/or alarms. Reset is automatic when all alarms are cleared. This alarm indicates the unit is at 0% capacity.
— A test is made once, on
— If the CCN emergency
— An A151 alarm indicates an
— Both circuits are off
T153 (Real Time Clock Hardware Failure) has been detected with MBB real time clock hardware. Try re­setting the power and check the indicator lights. If the alarm continues, the board should be replaced.
A154 (Serial EEPROM Hardware Failure) has been detected with the EEPROM on the MBB. Try resetting the power and check the indicator lights. If the alarm continues, the board should be replaced.
T155 (Serial EEPROM Storage Failure Error) has been detected with the EEPROM storage on the MBB. Try resetting the power and check the indicator lights. If the alert continues, the board should be replaced.
A156 (Critical Serial EEPROM Storage Failure Error) problem has been detected with the EEPROM storage on the MBB. Try resetting the power and check the indicator lights. If the alarm continues, the board should be replaced.
A157 (A/D Hardware Failure) ed with A/D conversion on the boards. Try resetting the power and check the indicator lights. If the alarm continues, the board should be replaced.
A172 (Loss of Communication with the EXV Board) This alarm indicates that there are communications problems with the EXV board. The alarm will automatically reset.
T173 (Energy Management Module Communication Fail­ure) — This alert indicates that there are communications problems with the energy management. All functions per­formed by the EMM will stop, which can include demand lim­it, reset and capacity input. The alarm will automatically reset.
T174 (4 to 20 mA Cooling Set Point Input Failure) alert indicates a problem has been detected with cooling set point 4 to 20 mA input. The input value is either less than 2 mA or greater than 22 mA.
T175 (Loss of Communication with the AUX Board) This alarm indicates that there are communications problems with the AUX board. All functions performed by the AUX board will stop, which can include digital scroll unloader oper­ation and low ambient head pressure control. The alarm will automatically reset.
T176 (4 to 20 mA Reset Input Failure) cates a problem has been detected with reset 4 to 20 mA input. The input value is either less than 2 mA or greater than 22 mA. The reset function will be disabled when this occurs.
T177 (4 to 20 mA Demand Limit Input Failure) alert indicates a problem has been detected with demand limit 4 to 20 mA input. The input value is either less than 2 mA or greater than 22 mA. The reset function will be disabled when this occurs.
T500, T501 (Current Sensor Board Failure — A xx Circuit A)
T503, T504 (Current Sensor Board Failure — B xx Circuit B) — Alert codes 500, 501, 503, and 504 are for compressors A1, A2, B1, and B2 respectively. These alerts occur when the output of the CSB is a constant high value. These alerts reset automatically. If the problem cannot be resolved, the CSB must be replaced.
— A problem has been detect-
— A problem
— A problem
— A problem
— A
— This
— This alert indi-
— This
73
Page 74
APPENDIX A — DISPLAY TABLES
Run Status Mode and Sub-Mode Directory
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
AUTO VIEW OF RUN STATUS
EWT xxx.x ºF Entering Fluid Temp
LWT xxx.x ºF Leaving Fluid Temp SETP xxx.x ºF Active Set Point CTPT xxx.x ºF Control Point
LOD.F xxx Load/Unload Factor
0=Service Test
1=Off Local 2=Off CCN 3=Off Time
4=Off Emrgcy
5=On Local 6=On CCN 7=On Time
1 - 12 (1 = January,
2 = February, etc.)
VIEW
RUN
HOUR
STAT Control Mode
LD.PM Lead Pump
OCC YES/NO Occupied
LS.AC YES/NO Low Sound Active
MODE YES/NO Override Modes in Effect
CAP xxx Percent Total Capacity
STGE x Requested Stage ALRM xxx Current Alarms & Alerts
TIME xx.xx Time of Day 00:00-23:59
MNTH xx Month of Year
DATE xx Day of Month 01-31
YEAR xx Year of Century
UNIT RUN HOUR AND START HRS.U xxxx HRS Machine Operating Hours STR.U xxxx Machine Starts HR.P1 xxxx HRS Pump 1 Run Hours HR.P2 xxxx HRS Pump 2 Run Hours
CIRC AND COMP RUN HOURS HRS.A xxxx HRS Circuit A Run Hours HRS.B xxxx HRS Circuit B Run Hours HR.A1 xxxx HRS Compressor A1 Run Hours HR.A2 xxxx HRS Compressor A2 Run Hours HR.B1 xxxx HRS Compressor B1 Run Hours HR.B2 xxxx HRS Compressor B2 Run Hours
74
Page 75
APPENDIX A — DISPLAY TABLES (cont)
Run Status Mode and Sub-Mode Directory (cont)
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
COMPRESSOR STARTS
ST.A1 xxxx Compressor A1 Starts
STRT
PM
VERS
ST.A2 xxxx Compressor A2 Starts ST.B1 xxxx Compressor B1 Starts ST.B2 xxxx Compressor B2 Starts
PREVENTIVE MAINTENANCE
PUMP PUMP MAINTENANCE
SI.PM xxxx HRS Pump Service Interval P.1.DN xxxx HRS Pump 1 Service Countdown P.2.DN xxxx HRS Pump 2 Service Countdown P.1.MN YES/NO Pump 1 Maintenance Done User Entry P.2.MN YES/NO Pump 2 Maintenance Done User Entry
PMDT PUMP MAINTENANCE DATES P.1.M0 MM/DD/YY HH:MM P.1.M1 MM/DD/YY HH:MM P.1.M2 MM/DD/YY HH:MM P.1.M3 MM/DD/YY HH:MM P.1.M4 MM/DD/YY HH:MM P.2.M0 MM/DD/YY HH:MM P.2.M1 MM/DD/YY HH:MM P.2.M2 MM/DD/YY HH:MM P.2.M3 MM/DD/YY HH:MM P.2.M4 MM/DD/YY HH:MM
STRN STRAINER MAINTENANCE
SI.ST xxxx HRS Strainer Srvc Interval
S.T.DN xxxx HRS Strainer Srvc Countdown
S.T.MN YES/NO Strainer Maint. Done User Entry
ST.DT STRAINER MAINTENANCE DATES S.T.M0 MM/DD/YY HH:MM S.T.M1 MM/DD/YY HH:MM S.T.M2 MM/DD/YY HH:MM S.T.M3 MM/DD/YY HH:MM S.T.M4 MM/DD/YY HH:MM
COIL COIL MAINTENANCE
SI.CL xxxx HRS Coil Cleaning Srvc Int C.L.DN xxxx HRS Coil Service Countdown C.L.MN YES/NO Coil Cleaning Maint.Done User Entry
CL.DT COIL MAINTENANCE DATES C.L.M0 MM/DD/YY HH:MM C.L.M1 MM/DD/YY HH:MM C.L.M2 MM/DD/YY HH:MM C.L.M3 MM/DD/YY HH:MM C.L.M4 MM/DD/YY HH:MM
SOFTWARE VERSION NUMBERS
MBB CESR131460-XXXXX
EXV CESR131172-XXXXX
AUX1 CESR131333-XXXXX
EMM CESR131174-XXXXX
MARQ CESR131171-XXXXX
NAVI CESR130227-XXXXX
75
Page 76
APPENDIX A — DISPLAY TABLES (cont)
Service Test Mode and Sub-Mode Directory
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
To enable Service Test mode, move
TEST Service Test Mode
OUTPUTS EXV.A xxx% EXV % Open EXV.B xxx% EXV % Open
FAN1 ON/OFF Fan 1 Relay FAN2 ON/OFF Fan 2 Relay FAN3 ON/OFF Fan 3 Relay FAN4 ON/OFF Fan 4 Relay
OUTS
CMPA
CMPB
FAN5 ON/OFF Fan 5 Relay
FAN6 ON/OFF Fan 6 Relay V.HPA xx Var Head Press % V.HPB xx Var Head Press %
CLP.1 ON/OFF Cooler Pump Relay 1
CLP.2 ON/OFF Cooler Pump Relay 2
UL.TM xx Comp A1 Unload Time
CL.HT ON/OFF Cooler/Pump Heater
RMT.A ON/OFF Remote Alarm Relay
CIRCUIT A COMPRESSOR TEST CC.A1 ON/OFF Compressor A1 Relay UL.TM xx Comp A1 Unload Time CC.A2 ON/OFF Compressor A2 Relay
MLV ON/OFF Minimum Load Valve Relay
CIRCUIT B COMPRESSOR TEST CC.B1 ON/OFF Compressor B1 Relay CC.B2 ON/OFF Compressor B2 Relay
Enable/Off/Remote contact switch to
OFF. Change TEST to ON.
Move switch to ENABLE
Temperature Mode and Sub-Mode Directory
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
ENTERING AND LEAVING UNIT TEMPERATURES
CEWT xxx.x °F Cooler Entering Fluid
UNIT
CIR.A
CIR.B
CLWT xxx.x °F Cooler Leaving Fluid
OAT xxx.x °F Outside Air Temperature SPT xxx.x °F Space Temperature
DLWT xxx.x °F Lead/Lag Leaving Fluid
TEMPERATURES CIRCUIT A SCT.A xxx.x °F Saturated Condensing Tmp SST.A xxx.x °F Saturated Suction Temp RGT.A xxx.x °F Compr Return Gas Temp
D.GAS xxx.x °F Discharge Gas Temp
SH.A xxx.x ΔF Suction Superheat Temp
TEMPERATURES CIRCUIT B SCT.B xxx.x °F Saturated Condensing Tmp SST.B xxx.x °F Saturated Suction Temp RGT.B xxx.x °F Compr Return Gas Temp
SH.B xxx.x ΔF Suction Superheat Temp
Pressures Mode and Sub-Mode Directory
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
PRESSURES CIRCUIT A
PRC.A
PRC.B
DP.A xxx.x PSIG Discharge Pressure SP.A xxx.x PSIG Suction Pressure
PRESSURES CIRCUIT B DP.B xxx.x PSIG Discharge Pressure SP.B xxx.x PSIG Suction Pressure
76
Page 77
APPENDIX A — DISPLAY TABLES (cont)
Set Points Mode and Sub-Mode Directory
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION RANGE COMMENT
COOLING SET POINTS
COOL
HEAD
FRZ
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
GEN.I
CRCT
4-20
CSP.1 xxx.x °F Cooling Set Point 1 –20 to 70 Default: 44 F CSP.2 xxx.x °F Cooling Set Point 2 –20 to 70 Default: 44 F CSP.3 xxx.x °F ICE Set Point –20 to 32 Default: 32 F
HEAD PRESSURE SET POINTS H.DP xxx.x °F Head Set Point 85 to 120 Default: 95 F F.ON xxx.x °F Fan On Set Point Default: 95 F
F.OFF xxx.x °F Fan Off Set Point Default: 72 F
B.OFF xx.x Base Fan Off Delta Temp 10 to 50 Default: 23 F
F.DLT xxx Fan Stage Delta 0 to 50 Default: 15 F
BRINE FREEZE SET POINT
BR.FZ xx.x °F Brine Freeze Point –20 to 34 Default: 34 F
Inputs Mode and Sub-Mode Directory
GENERAL INPUTS
STST ON/OFF Start/Stop Switch
FLOW ON/OFF Cooler Flow Switch PM.F.1 ON/OFF Cooler Pump 1 Interlock PM.F.2 ON/OFF Cooler Pump 2 Interlock
HT.RQ ON/OFF Heat Request
DLS1 ON/OFF Demand Limit Switch 1 DLS2 ON/OFF Demand Limit Switch 2 ICED ON/OFF Ice Done
DUAL ON/OFF Dual Set Point Switch
CIRCUIT INPUTS FKA1 ON/OFF Compressor A1 Feedback FKA2 ON/OFF Compressor A2 Feedback FKA3 ON/OFF Compressor A3 Feedback FKA4 ON/OFF Compressor A4 Feedback FKB1 ON/OFF Compressor B1 Feedback FKB2 ON/OFF Compressor B2 Feedback FKB3 ON/OFF Compressor B3 Feedback FKB4 ON/OFF Compressor B4 Feedback
4-20 MA INPUTS
DMND xx.x 4-20 ma Demand Signal
RSET xx.x 4-20 ma Reset Signal
CSP xx.x 4-20 ma Cooling Set Point
77
Page 78
APPENDIX A — DISPLAY TABLES (cont)
Outputs Mode and Sub-Mode Directory
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
GENERAL OUTPUTS FAN1 ON/OFF Fan 1 Relay FAN2 ON/OFF Fan 2 Relay FAN3 ON/OFF Fan 3 Relay FAN4 ON/OFF Fan 4 Relay FAN5 ON/OFF Fan 5 Relay
GEN.O
A.EXV
B.EXV
CIR.A
CIR.B
FAN6 ON/OFF Fan 6 Relay
V.HPA ON/OFF Fan Speed Circuit A
V.HPB ON/OFF Fan Speed Circuit B C.WP1 ON/OFF Cooler Pump Relay 1 C.WP2 ON/OFF Cooler Pump Relay 2
CLHT ON/OFF Cooler/Pump Heater
MLV.R ON/OFF Minimum Load Valve Relay
OUTPUTS CIRCUIT A EXV EXV.A ON/OFF EXV % Open APPR ON/OFF Circuit A Approach AP.SP ON/OFF Approach Setpoint
X.SH.R SH Reset at Max Unl-Dig S.SH.R Digload to Start SH RST
SH_R Amount of SH Reset
OVR.A ON/OFF EXVA Override SPH.A ON/OFF Suction Superheat Temp ASH.S ON/OFF Active Superheat Setpt AMP.S ON/OFF Active Mop Setpt PLM.A ON/OFF Cir A EXV Position Limit
SPR.1 ON/OFF Spare 1 Temperature
OUTPUTS CIRCUIT A EXV EXV.B ON/OFF EXV % Open APPR ON/OFF Circuit B Approach AP.SP ON/OFF Approach Setpoint
OVR.B ON/OFF EXVB Override SPH.B ON/OFF Suction Superheat Temp ASH.S ON/OFF Active Superheat Setpt AMP.S ON/OFF Active Mop Setpt PLM.B ON/OFF Cir B EXV Position Limit
SPR.2 ON/OFF Spare 2 Temperature
OUTPUTS CIRCUIT A CC.A1 ON/OFF Compressor A1 Relay DPE.R ON/OFF Comp A1 Load Percent CC.A2 ON/OFF Compressor A2 Relay CC.A3 ON/OFF Compressor A3 Relay CC.A4 ON/OFF Compressor A4 Relay
OUTPUTS CIRCUIT B CC.B1 ON/OFF Compressor B1 Relay CC.B2 ON/OFF Compressor B2 Relay CC.B3 ON/OFF Compressor B3 Relay CC.B4 ON/OFF Compressor B4 Relay
78
Page 79
APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
DISPLAY CONFIGURATION
TEST ON/OFF Test Display LEDs
METR ON/OFF Metric Display Off = English On = Metric
Default: 0
DISP
UNIT
OPT1
LANG X Language Selection
PAS.E ENBL/DSBL Password Enable
PASS XXXX Service Password
UNIT CONFIGURATION
SIZE Unit Size SZA.1 XX Compressor A1 Size SZA.2 XX Compressor A2 Size SZA.3 XX Compressor A3 Size SZA.4 XX Compressor A4 Size SZB.1 XX Compressor B1 Size SZB.2 XX Compressor B2 Size SZB.3 XX Compressor B3 Size SZB.4 XX Compressor B4 Size
SH.SP XX Suction Superheat Setpt
FAN.S X Number of Fans Default: 5
EXV YES/NO EXV Module Installed
A1.TY YES/NO Compressor A1 Digital Default: No
MAX.T XX Maximum A1 Unload Time
UNIT OPTIONS 1 HARDWARE
FLUD X Cooler Fluid Default: Water
2 = Medium Temperature Brine
MLV.S YES/NO Minimum Load Valve Select
CSB.E ENBL/DSBL Csb Boards Enable Default: Enable
CPC ON/OFF Cooler Pump Control Default: Off PM1E YES/NO Cooler Pump 1 Enable PM2E YES/NO Cooler Pump 2 Enable
PM.P.S YES/NO Cooler Pmp Periodic Strt Default: No
PM.SL X Cooler Pump Select Default: Automatic
PM.DY XX MIN Cooler Pump Shutdown Dly 0 to 10 minutes, Default: 1 min. PM.DT XXXX HRS Pump Changeover Hours Default: 500 hours
ROT.P YES/NO Rotate Cooler Pumps Now User Entry
EMM YES/NO EMM Module Installed CND.T X Cnd HX Typ:0=RTPF 1=MCHX MOPS XX EXV MOP Set Point
APPR XX Config Approach Set Point
0 = English 1 = Espanol 2 = Francais
3 = Portuguese
Default: 7
Max = 12 (010,015)
Max = 10 (018-060)
1 = Water
0 = Automatic 1 = Pump 1 Starts first 2 = Pump 2 Starts first
79
Page 80
APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
UNIT OPTIONS 2 CONTROLS
Default: 0
2 = Occupancy
3 = CCN Control
Default: 1 1 = Equal
2 = Staged
Default: 1
1 = Automatic 2 = Circuit A Leads 3 = Circuit B Leads
Default: 60
Range: 2 to 60 F
Default: 0 Minutes
Range: 0 to 15 Minutes
0 = Mode Disable
1 = Fan Noise Only
Default: 100%
Range: 0 to 100%
Default: 1
Range: 0 to 239
Default: 1
Range: 0 to 239
Default: 3
1 = 2400 2 = 4800
3 = 9600 4 =19,200 5 =38,400
Default:12
Range: 0 to 50
Default:12
Range: 0 to 50
Default:12
Range: 0 to 50
Default:12
Range: 0 to 50
OPT2
CCN
HP.A
HP.B
CTRL X Control Method
LOAD X Loading Sequence Select
LLCS X Lead/Lag Circuit Select
LCWT XX High LCW Alert Limit
DELY XX Minutes Off Time
ICE.M ENBL/DSBL Ice Mode Enable Default: Disable
LS.MD X Low Sound Mode Select Default: 0
LS.ST 00:00 Low Sound Start Time Default: 00:00
LS.ND 00:00 Low Sound End Time Default: 00:00
LS.LT XXX % Low Sound Capacity Limit
CCN NETWORK CONFIGS
CCNA XXX CCN Address
CCNB XXX CCN Bus Number
BAUD X CCN Baud Rate
HEAD PRESSURE CMP. DELTA
A1.DT XX SCT Delta For Comp A1
A2.DT XX SCT Delta For Comp A2
HEAD PRESSURE CMP. DELTA
B1.DT XX SCT Delta For Comp B1
B2.DT XX SCT Delta For Comp B2
0 = Enable/Off/Remote Switch
2 = Fan/Compressor Noise
80
Page 81
APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
CIR A EXV CONFIGURATION
Default: 50
0 to 100
Default: 8
0 to 100
Default: 200
0 to 65535
Default: 0
0 to 100
Default: 0
0 to 65535
Default: 167
0 to 65535
Default: 1
0 = UNIPOLAR
1 = BIPOLAR
Default: 115
50 to 140
Default: 10
0 to 30
Default: 5
0 to 30
Default: 10
0 to 100
Default: 10
0 to 100
Default: 10
0 to 100
Default: 10
0 to 100
Default: 50
0 to 100
Default: 8
0 to 100
Default: 200
0 to 65535
Default: 0
0 to 100
Default: 0
0 to 65535
Default: 167
0 to 65535
Default: 1
0 = UNIPOLAR
1 = BIPOLAR
EXV.A
EXV.B
STR.A XXX EXV CIrc.A Start Pos
MIN.A XXX EXV Circ.A Min Position
RNG.A XXXXX EXVA Steps In Range 0 to 65535
SPD.A XXXXX EXVA STeps Per Second
POF.A XXX EXVA Fail Position In %
MIN.A XXXXX EXVA Minimum Steps
MAX.A XXXXX EXVA Maximum Steps 0 to 65535
OVR.A XXX EXVA Overrun Steps
TYP.A 0,1 EXVA Stepper Type
H.SCT XXX High SCT Threshold
X.PCT XX Open EXV X% On 2nd Comp
X.PER XX Move EXV X% On DISCRSOL
A.PCT XXX Pre-open EXV - Fan Adding
M.PCT XXX Pre-close EXV - Fan Sub
S.PCT XXX Pre-close EXV - Lag Shut
DELY XXX Lag Start Delay
CIR B EXV CONFIGURATION
STR.B XXX EXV CIrc.B Start Pos
MIN.B XXX EXV Circ.B Min Position
RNG.B XXXXX EXVB Steps In Range 0 to 65535
SPD.B XXXXX EXVB STeps Per Second
POF.B XXX EXVB Fail Position In %
MIN.B XXXXX EXVB Minimum Steps
MAX.B XXXXX EXVB Maximum Steps 0 to 65535
OVR.B XXX EXVB Overrun Steps
TYP.B 0,1 EXVB Stepper Type
81
Page 82
APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
MOTORMASTER
MMR.S YES/NO Motormaster Select Default: NO
Default: 1
Range: 1 to 4
Default: 0.1
Range: -20 to 20
Default: 0.0
Range: -20 to 20
Default: 0
0 = No Reset
1 = 4 to 20 mA Input
3 = Return Fluid
4 = Space Temperature
Default: 0.0 ΔF
Range: -30 to 30 ΔF
Default: 125 F
Range: 0° to125 F
Default: 0 F
Range: 0° to125 F
Default: 0.0 ΔF
Range: -30 to 30 ΔF
Default: 10.0 ΔF
Range: 0° to125 F
Default: 0 ΔF
Range: 0° to125 F
Default: 0.0 ΔF
Range: -30 to 30 ΔF
Default: 0 0 = None
1 = Switch
2 - 4 to 20 mA Input
3 = CCN Loadshed
Default: 100%
Range: 0 to 100%
Default: 0
Range: 0 to 99
Default: 0%
Range: 0 to 60%
Default: 60 minutes
Range: 0 to 120 minutes
Default: 80%
Range: 0 to 100%
Default: 50%
Range: 0 to 100%
Default: 2
Range: 0 to 239
Default: Master Leads
0 = Master Leads
1 = Slave Leads
2 = Automatic
Default: 168 hours
Range: 40 to 400 hours
Default: 5 minutes
Range: 0 to 30 minutes
CHANGED)
MM
RSET
P.GAN XX Head Pressure P Gain
I.GAN XX.X Head Pressure I Gain
D.GAN XX.X Head Pressure D Gain
MIN.S XX Minimum Fan Speed Default: 5
RESET COOL TEMP
CRST X Cooling Reset Type
MA.DG XX.XΔF 4-20 - Degrees Reset
RM.NO XXX.X °F Remote - No Reset Temp
RM.F XXX.X °F Remote - Full Reset Temp
RM.DG XX.X °F Remote - Degrees Reset
RT.NO XXX.XΔF Return - No Reset Temp
RT.F XXX.XΔF Return - Full Reset Temp
RT.DG XX.X °F Return - Degrees Reset
DMDC X Demand Limit Select
DM20 XXX% Demand Limit at 20 mA
SHNM XXX Loadshed Group Number
SHDL XXX% Loadshed Demand Delta
SHTM XXX Maximum Loadshed Time
DLS1 XXX% Demand Limit Switch 1
DLS2 XXX% Demand Limit Switch 2
LLEN ENBL/DSBL Lead/Lag Chiller Enable Default: Disable
MSSL SLVE/MAST Master/Slave Select Default: Master
SLVA XXX Slave Address
LLBL X Lead/Lag Balance Select
LLBD XXX Lead/Lag Balance Delta
LLDY XXX Lag Start Delay
PARA YES Parallel Configuration
2 = Outdoor Air Temperature
Default: YES (CANNOT BE
82
Page 83
APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
SETPOINT AND RAMP LOAD
Default: Single
0 = Single
1 = Dual Switch
2 = Dual CCN Occupied
3 = 4 to 20 mA
Input (requires EMM)
Default: 1.0
Range: 0.3 to 2
Default: 1
Range: 1 to 99
Default: 1
Range: 1 to 4
SLCT
SERV
BCST
CLSP X Cooling Set Point Select
RL.S ENBL/DSBL Ramp Load Select Default: Enable
CRMP ENBL/DSBL Cooling Ramp Loading
SCHD XX Schedule Number
Z.GN X.X Deadband Multiplier
SERVICE CONFIGURATION EN.A1 YES/NO Enable Compressor A1 EN.A2 YES/NO Enable Compressor A2 EN.B1 YES/NO Enable Compressor B1 EN.B2 YES/NO Enable Compressor B2
BROADCAST CONFIGURATION
T.D.B ON/OFF CCN Time/Date Broadcast
OAT.B ON/OFF CCN OAT Broadcast
G.S.BC ON/OFF Global Schedule Broadcst
BC.AK ON/OFF CCN Broadcast Ack'er
83
Page 84
APPENDIX A — DISPLAY TABLES (cont)
Time Clock Mode and Sub-Mode Directory
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
TIME
DATE
DST
HOL.L LOCAL HOLIDAY SCHEDULES
HD.01
HD.02
HD.03
HD.04
HD.05
HD.06
HD.07
HD.08
HH.MM XX.XX Hour and Minute Military (00:00 - 23:59)
MONTH, DATE, DAY, AND YEAR
MNTH XX Month of Year
DOM XX Day of Month Range: 01 -31
DAY X Day of Week
YEAR XXXX Year of Century
STR.M XX Month Default: 4 Range 1- 12
STR.W X Week Default: 1 Range 1- 5
STR.D X Day Default: 7 Range 1- 7
MIN.A XX Minutes to Add Default: 60 Range 0 - 99 STP.M XX Month Default: 10 Range 1- 12
STP.W XX Week Default: 5 Range 1- 5
STP.D XX Day Default: 7 Range 1- 7 MIN.S XX Minutes to Subtract Default: 60 Range 0 - 99
MON XX Holiday Start Month
DAY XX Start Day LEN XX Duration (days)
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
TIME OF DAY
DAYLIGHT SAVINGS TIME
HOLIDAY SCHEDULE 01
HOLIDAY SCHEDULE 02
HOLIDAY SCHEDULE 03
HOLIDAY SCHEDULE 04
HOLIDAY SCHEDULE 05
HOLIDAY SCHEDULE 06
HOLIDAY SCHEDULE 07
HOLIDAY SCHEDULE 08
1 - 12 (1 = January,
2 = February, etc.)
1 - 7 (1 = Sunday,
2 = Monday, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
84
Page 85
APPENDIX A — DISPLAY TABLES (cont)
Time Clock Mode and Sub-Mode Directory (cont)
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
HOLIDAY SCHEDULE 09
HD.09
HD.10
HD.11
HD.12
HD.13
HD.14
HD.15
HD.16
HD.17
HD.18
HD.19
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
HOLIDAY SCHEDULE 10
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
HOLIDAY SCHEDULE 11
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
HOLIDAY SCHEDULE 12
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
HOLIDAY SCHEDULE 13
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
HOLIDAY SCHEDULE 14
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
HOLIDAY SCHEDULE 15
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
HOLIDAY SCHEDULE 16
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
HOLIDAY SCHEDULE 17
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
HOLIDAY SCHEDULE 18
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
HOLIDAY SCHEDULE 19
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
85
Page 86
APPENDIX A — DISPLAY TABLES (cont)
Time Clock Mode and Sub-Mode Directory (cont)
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
HOLIDAY SCHEDULE 20
HD.20
HD.21
HD.22
HD.23
HD.24
HD.25
HD.26
HD.27
HD.28
HD.29
HD.30
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
HOLIDAY SCHEDULE 21
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
HOLIDAY SCHEDULE 22
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
HOLIDAY SCHEDULE 23
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
HOLIDAY SCHEDULE 24
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
HOLIDAY SCHEDULE 25
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
HOLIDAY SCHEDULE 26
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
HOLIDAY SCHEDULE 27
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
HOLIDAY SCHEDULE 28
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
HOLIDAY SCHEDULE 29
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
HOLIDAY SCHEDULE 30
MON XX Holiday Start Month
DAY XX Start Day 01-31 LEN XX Duration (days)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
1 - 12 (1 = January,
2 = February, etc.)
86
Page 87
APPENDIX A — DISPLAY TABLES (cont)
Time Clock Mode and Sub-Mode Directory (cont)
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
SCH.N Schedule Number 0 SCH.L LOCAL OCCUPANCY SCHEDULE
OCCUPANCY PERIOD 1 OCC.1 XX:XX Period Occupied Time Military (00:00 - 23:59) UNC.1 XX:XX Period Unoccupied Time Military (00:00 - 23:59)
MON.1 YES/NO Monday In Period
TUE.1 YES/NO Tuesday In Period
PER.1
PER.2
PER.3
PER.4
PER.5
WED.1 YES/NO Wednesday In Period
THU.1 YES/NO Thursday In Period
FRI.1 YES/NO Friday In Period
SAT.1 YES/NO Saturday In Period SUN.1 YES/NO Sunday In Period HOL.1 YES/NO Holiday In Period
OCCUPANCY PERIOD 2 OCC.2 XX:XX Period Occupied Time Military (00:00 - 23:59) UNC.2 XX:XX Period Unoccupied Time Military (00:00 - 23:59)
MON.2 YES/NO Monday In Period
TUE.2 YES/NO Tuesday In Period
WED.2 YES/NO Wednesday In Period
THU.2 YES/NO Thursday In Period
FRI.2 YES/NO Friday In Period
SAT.2 YES/NO Saturday In Period SUN.2 YES/NO Sunday In Period HOL.2 YES/NO Holiday In Period
OCCUPANCY PERIOD 3 OCC.3 XX:XX Period Occupied Time Military (00:00 - 23:59) UNC.3 XX:XX Period Unoccupied Time Military (00:00 - 23:59)
MON.3 YES/NO Monday In Period
TUE.3 YES/NO Tuesday In Period
WED.3 YES/NO Wednesday In Period
THU.3 YES/NO Thursday In Period
FRI.3 YES/NO Friday In Period
SAT.3 YES/NO Saturday In Period SUN.3 YES/NO Sunday In Period HOL.3 YES/NO Holiday In Period
OCCUPANCY PERIOD 4 OCC.4 XX:XX Period Occupied Time Military (00:00 - 23:59) UNC.4 XX:XX Period Unoccupied Time Military (00:00 - 23:59)
MON.4 YES/NO Monday In Period
TUE.4 YES/NO Tuesday In Period
WED.4 YES/NO Wednesday In Period
THU.4 YES/NO Thursday In Period
FRI.4 YES/NO Friday In Period
SAT.4 YES/NO Saturday In Period SUN.4 YES/NO Sunday In Period HOL.4 YES/NO Holiday In Period
OCCUPANCY PERIOD 5 OCC.5 XX:XX Period Occupied Time Military (00:00 - 23:59) UNC.5 XX:XX Period Unoccupied Time Military (00:00 - 23:59)
MON.5 YES/NO Monday In Period
TUE.5 YES/NO Tuesday In Period
WED.5 YES/NO Wednesday In Period
THU.5 YES/NO Thursday In Period
FRI.5 YES/NO Friday In Period
SAT.5 YES/NO Saturday In Period SUN.5 YES/NO Sunday In Period HOL.5 YES/NO Holiday In Period
87
Page 88
APPENDIX A — DISPLAY TABLES (cont)
Time Clock Mode and Sub-Mode Directory (cont)
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
OCCUPANCY PERIOD 6 OCC.6 XX:XX Period Occupied Time Military (00:00 - 23:59) UNC.6 XX:XX Period Unoccupied Time Military (00:00 - 23:59)
MON.6 YES/NO Monday In Period
TUE.6 YES/NO Tuesday In Period
PER.6
PER.7
PER.8
OVR
WED.6 YES/NO Wednesday In Period
THU.6 YES/NO Thursday In Period
FRI.6 YES/NO Friday In Period
SAT.6 YES/NO Saturday In Period SUN.6 YES/NO Sunday In Period HOL.6 YES/NO Holiday In Period
OCCUPANCY PERIOD 7 OCC.7 XX:XX Period Occupied Time Military (00:00 - 23:59) UNC.7 XX:XX Period Unoccupied Time Military (00:00 - 23:59)
MON.7 YES/NO Monday In Period
TUE.7 YES/NO Tuesday In Period
WED.7 YES/NO Wednesday In Period
THU.7 YES/NO Thursday In Period
FRI.7 YES/NO Friday In Period
SAT.7 YES/NO Saturday In Period SUN.7 YES/NO Sunday In Period HOL.7 YES/NO Holiday In Period
OCCUPANCY PERIOD 8 OCC.8 XX:XX Period Occupied Time Military (00:00 - 23:59) UNC.8 XX:XX Period Unoccupied Time Military (00:00 - 23:59)
MON.8 YES/NO Monday In Period
TUE.8 YES/NO Tuesday In Period
WED.8 YES/NO Wednesday In Period
THU.8 YES/NO Thursday In Period
FRI.8 YES/NO Friday In Period
SAT.8 YES/NO Saturday In Period SUN.8 YES/NO Sunday In Period HOL.8 YES/NO Holiday In Period
SCHEDULE OVERRIDE
OVR.T X Timed Override Hours Default: 0 Range 0-4 hours
OVR.L X Override Time Limit Default: 0 Range 0-4 hours T.OVR YES/NO Timed Override User Entry
88
Page 89
APPENDIX A — DISPLAY TABLES (cont)
Operating Mode and Sub-Mode Directory
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
MODES CONTROLLING UNIT MD01 ON/OFF CSM Controlling Chiller MD02 ON/OFF WSM Controlling Chiller MD03 ON/OFF Master/Slave Control MD05 ON/OFF Ramp Load Limited MD06 ON/OFF Timed Override in effect MD07 ON/OFF Low Cooler Suction TempA MD08 ON/OFF Low Cooler Suction TempB MD09 ON/OFF Slow Change Override MD10 ON/OFF Minimum OFF time active MD13 ON/OFF Dual Set Point
MODE
MD14 ON/OFF Temperature Reset MD15 ON/OFF Demand Limited MD16 ON/OFF Cooler Freeze Protection MD17 ON/OFF Low Temperature Cooling MD18 ON/OFF High Temperature Cooling MD19 ON/OFF Making Ice MD20 ON/OFF Storing Ice MD21 ON/OFF High SCT Circuit A MD22 ON/OFF High SCT Circuit B MD23 ON/OFF Minimum Comp. On Time MD24 ON/OFF Pump Off Delay Time MD25 ON/OFF Low Sound Mode
Alarms Mode and Sub-Mode Directory
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
CURRENTLY ACTIVE ALARMS
CRNT
RCRN YES/NO Reset All Current Alarms
HIST
AXXX TXXX PXXX
AXXX TXXX PXXX
Current Alarms 1-25
ALARM HISTORY
Alarm History 1-20
Alarms are hown as AXXX Alerts are shown as TXXX
Alarms are shown as AXXX
Alerts are shown as TXXX
89
Page 90
APPENDIX B — CCN TABLES
CCN DISPLAY TABLES — A_UNIT (General Unit Parameters)
DESCRIPTION VALUE UNITS POINT NAME FORCIBLE
Control Mode 0 = Test
Occupied No/Yes OCC N CCN Chiller Start/Stop CHIL_S_S Y Low Sound Active No/Yes LSACTIVE N Alarm State Normal/Aler t/Alarm ALM N Active Demand Limit 0 to 100 % DEM_LIM Y Override Modes in Effect No/Yes MODE N Percent Total Capacity 0 to 100 % CAP_T N Requested Stage 0 to 99 STAGE N Active Set Point –20 to 70 FSP N Control Point –20 to 70 F CTRL_PNT Y Entering Fluid Temp snnn.n FEWT N Leaving Fluid Temp snnn.n FLWT N Emergency Stop Enable/Emstop Enable EMSTOP Y Minutes Left for Start 00:00 to 15:00 minutes MIN_LEFT N PUMPS Cooler Pump Relay 1 Off/On COOLPMP1 N Cooler Pump Relay 2 Off/On COOLPMP2 N Cooler Pump 1 Interlock Open/Close PMP1_FBK N Cooler Pump 2 Interlock Open/Close PMP2_FBK N Cooler Flow Switch Open/Close COOLFLOW N Lead Pump LEADPUMP Y Rotate Cooler Pumps Now No/Yes ROT_PUMP Y
1 = Local Off 2 = CCN Off 3 = Clock Off 4 = Emergency Stop 5 = Local On 6 = CCN On 7 = Clock On 8 = Heat Enabled 9 = Pump Delay
STAT N
Heat/Cool Select Heat/Cool HC_SEL N
CCN DISPLAY TABLES — CIRCA_AN (Circuit A Analog Parameters)
DESCRIPTION VALUE UNITS POINT NAME FORCIBLE
CIRCUIT A ANALOG VALUES Percent Total Capacity 0-100 % CAPA_T N Percent Available Cap. 0-100 % CAPA_A N Discharge Pressure nnn.n PSIG DP_A N Suction Pressure nnn.n PSIG SP_A N Head Setpoint nnn.n °F HSP N Saturated Condensing Tmp snnn.n FTMP_SCTAN Saturated Suction Temp snnn.n F TMP_SSTA N EXV % Open nnn % EXV_A N Var Head Press Output nnn.n milliamps VHP_ACT N Compr Return Gas Temp nnn.n FTMP_RGTAN Discharge Gas Temp nnn.n °F DISGAS N Suction Superheat Temp nnn.n FSH_AN Spare 1 Temperature nnn.n °F SPR1_TMP N
90
Page 91
APPENDIX B — CCN TABLES (cont)
CCN DISPLAY TABLES — CIRCADIO (Circuit A Discrete Inputs/Outputs)
DESCRIPTION VALUE UNITS POINT NAME FORCIBLE
CIRC. A DISCRETE OUTPUTS Compressor A1 Relay On/Off K_A1_RLY N Compressor A2 Relay On/Off K_A2_RLY N Minimum Load Valve Relay On/Off MLV_RLY N
CIRC. A DISCRETE INPUTS Compressor A1 Feedback On/Off K_A1_FBK N Compressor A2 Feedback On/Off K_A2_FBK N
CCN DISPLAY TABLES — CIRCB_AN (Circuit B Analog Parameters)
DESCRIPTION VALUE UNITS POINT NAME FORCIBLE
CIRCUIT B ANALOG VALUES Percent Total Capacity 0-100 % CAPB_T N Percent Available Cap. 0-100 % CAPB_A N Discharge Pressure nnn.n PSIG DP_B N Suction Pressure nnn.n PSIG SP_B N Head Setpoint nnn.n °F HSP N Saturated Condensing Tmp snnn.n FTMP_SCTBN Saturated Suction Temp snnn.n F TMP_SSTB N EXV % Open nnn % EXV_B N Var Head Press Output nnn.n milliamps VHP_ACT N Compr Return Gas Temp nnn.n FTMP_RGTBN Suction Superheat Temp nnn.n FSH_BN Spare 2 Temperature nnn.n °F SPR2_TMP N
CCN DISPLAY TABLES — CIRCBDIO (Circuit B Discrete Inputs/Outputs)
DESCRIPTION VALUE UNITS POINT NAME FORCIBLE
CIRC. B DISCRETE OUTPUTS Compressor B1 Relay On/Off K_B1_RLY N Compressor B2 Relay On/Off K_B2_RLY N Minimum Load Valve Relay On/Off MLV_RLY N
CIRC. B DISCRETE INPUTS Compressor B1 Feedback On/Off K_B1_FBK N Compressor B2 Feedback On/Off K_B2_FBK N
91
Page 92
APPENDIX B — CCN TABLES (cont)
CCN DISPLAY TABLES — OPTIONS (Unit Parameters)
DESCRIPTION VALUE UNITS POINT NAME FORCIBLE
FAN S Fan 1 Relay Off/On FAN_1 N Fan 2 Relay Off/On FAN_2 N Cooler/Pump Heater Off/On COOL_HTR N
UNIT ANALOG VALUES Cooler Entering Fluid snnn.n FCOOL_EWTN Cooler Leaving Fluid snnn.n FCOOL_LWTN Lead/Lag Leaving Fluid snnn.n F DUAL_LWT N
TEMPERATURE RESET 4-20 mA Reset Signal nn.n mA RST_MA N Outside Air Temperature snnn.n FOAT Y Space Temperature snnn.n F SPT Y
DEMAND LIMIT 4-20 mA Demand Signal nn.n mA LMT_MA N Demand Limit Switch 1 Off/On DMD_SW1 N Demand Limit Switch 2 Off/On DMD_SW2 N CCN Loadshed Signal 0 = Normal
1 = Redline 2 = Loadshed
DL_STAT N
MISCELLANEOUS Heat Request Off/On HEAT_REQ N Dual Setpoint Switch Off/On DUAL_IN N Cooler LWT Setpoint snnn.n FLWT_SPN Ice Done Off/On ICE_DONE N
CCN CONFIGURATION TABLES — UNIT (Unit Configuration)
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
Unit Size nnn tons SIZE Compressor A1 Size nnn tons SIZE_A1 Compressor A2 Size nnn tons SIZE_A2 Compressor B1 Size nnn tons SIZE_B1 Compressor B2 Size nnn tons SIZE_B2 Suction Superheat Setpt nn.n 9.0 FSH_SP Number of Fans n FAN_TYPE Compressor A1 Digital? No/Yes No CPA1TYPE Maximum A1 Unload Time nn 12 sec MAXULTME
CCN CONFIGURATION TABLES — OPTIONS1 (Options 1 Configuration)
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
Cooler Fluid 1 = Water
Minimum Load Vlv Select No/Yes No MLV_FLG CSB Board Enable Dsable/Enable Enable CSB_ENA Cooler Pump Control Off/On Off CPC Cooler Pump 1 Enable No/Yes No PMP1_ENA Cooler Pump 2 Enable No/Yes No PMP2_ENA Cooler Pmp Periodic Strt No/Yes No PUMP_PST Cooler Pump Select 0 = Automatic, 1 =
Cooler Pump Shutdown Dly 0 to 10 1 minutes PUMP_DLY Pump Changeover Hours 10 to 2000 100 hours PMP_DLTA EMM Module Installed No/Yes No EMM_BRD Cnd HX Typ: 0=RTPF 1=MCHX 0/1 1 COILTYPE EXV MOP Set Point nn.n °F MOP_SP Config Approach Setpoint nn.n °F IAPPROSP
2 = Med. Brine
Pump 1, 2 = Pump 2
1FLUIDTYP
0 PMP_SLCT
92
Page 93
APPENDIX B — CCN TABLES (cont)
CCN CONFIGURATION TABLES — OPTIONS2 (Options 2 Configuration)
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
Control Method 0 = Switch
Loading Sequence Select 1 = Equal Loading
Lead/Lag Circuit Select 1 = Automatic
Cooling Setpoint Select 0 = Single
Ramp Load Select Enable/Dsable Enable RAMP_EBL Heat Cool Select Cool/Heat Cool HEATCOOL High LCW Alert Limit 2 to 60 60.0 F LCW_LMT Minutes off time 0 to 15 0 min DELAY Deadband Multiplier 1.0 to 4.0 1.0 Z_GAIN Ice Mode Enable Enable/Dsable Dsable ICE_CNFG Low Sound Mode Select 0 = Disabled
Low Sound Start Time 00:00 to 23:59 00:00 LS_START Low Sound End Time 00:00 to 23:59 00:00 LS_END Low Sound Capacity Limit 0 to 100 100 % LS_LIMIT
2 = Occupancy 3 = CCN
2 = Staged Loading
2 = Circuit A Leads 3 = Circuit B Leads
1 = Dual, remote switch controlled 2 = Dual CCN occupancy 3 = 4-20 mA input
1 = Fan only 2 = Capacity/Fans
0 CONTROL
1 SEQ_TYP
1 LEAD_TYP
0 CLSP_TYP
0LS_MODE
CCN CONFIGURATION TABLES — SCHEDOVR (Timed Override Setup)
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
Schedule Number 0 to 99 1 SCHEDNUM Override Time Limit 0 to 4 0 hours OTL Timed Override Hours 0 to 4 0 hours OVR_EXT Timed Override No/Yes No TIMEOVER
CCN CONFIGURATION TABLES — RESETCON (Temperature Reset and Demand Limit)
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
COOLING RESET Cooling Reset Type 0 = No Reset
4-20 MA RESET 4-20 – Degrees Reset –30 to 30 0.0 F 420_DEG
REMOTE RESET Remote – No Reset Temp 0 to 125 125.0 FREM_NO Remote – Full Reset Temp 0 to 125 0.0 FREM_FULL Remote – Degrees Reset –30 to 30 0.0 F REM_DEG
RETURN TEMPERATURE RESET Return – No Reset Temp 0 to 125 10.0 FRTN_NO Return – Full Reset Temp 0 to 125 0.0 FRTN_FULL Return – Degrees Reset –30 to 30 0.0 FRTN_DEG
1 = 4-20 mA input 2 = External temp – OAT 3 = Return Fluid 4 = External temp - SPT
0CRST_TYP
DEMAND LIMIT Demand Limit Select 0 = None
Demand Limit at 20 mA 0 to 100 100 % DMT20MA Loadshed Group Number 0 to 99 0 SHED_NUM Loadshed Demand Delta 0 to 60 0 % SHED_DEL Maximum Loadshed Time 0 to 120 60 minutes SHED_TIM Demand Limit Switch 1 0 to 100 80 % DLSWSP1 Demand Limit Switch 2 0 to 100 50 % DLSWSP2
1 = External switch input 2 = 4-20 mA input 3 = Loadshed
0DMD_CTRL
93
Page 94
APPENDIX B — CCN TABLES (cont)
CCN CONFIGURATION TABLES — DUALCHIL (Dual Chiller Configuration Settings)
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
LEAD/LAG Lead/Lag Chiller Enable Enable/Dsable Dsable LL_ENA Master/Slave Select Master/Slave Master MS_SEL Slave Address 0 to 239 2 SLV_ADDR Lead/Lag Balance Select 0 = None 0 LL_BAL Lead/Lag Balance Delta 40 to 400 168 hours LL_BAL_D Lag Start Delay 0 to 30 5 minutes LL_DELAY Parallel Configuration Yes Yes PARALLEL
CCN CONFIGURATION TABLES — DISPLAY (Marquee Display SETUP)
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
Service Password nnnn 1111 PASSWORD Password Enable Enable/Disable Enable PASS_EBL Metric Display Off/On Off DISPUNIT Language Selection 0 = ENGLISH
1 = FRANCAIS 2 = ESPANOL 3 = PORTUGUES
CCN CONFIGURATION TABLES — EXVACONF (EXV Circuit A Configuration)
0LANGUAGE
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
EXV Circ. A Start Pos nnn.n 50.0 % EXVASTRT EXV Circ. A Min Position nnn.n 8.0 % EXVAMINP EXVA Steps in Range nnnnn 1596/2500 steps EVXARANG EXVA Steps Per Second nnnnn 200 steps EXVARATE EXVA Fail Position in % nnnn.nn 0 % EXVAPOSF EXVA Minimum Steps nnnnn 0 steps EXVAMINS EXVA Maximum Steps nnnnn 1596/2500 steps EXVAMAXS EXVA Overrun Steps nnnnn 167 steps EXVAOVRS EXVA Stepper Type nnn Bipolar EXVATYPE High SCT Threshold nnn.n 115 °F HIGH_SCT Open EXV X% on 2nd Comp nnn.n 10 % EXV_HSCT Open EXV X% on DISCRSOL nnn.n 5 % EXVDISCR Pre-Open EXV - Fan Adding nnn.n 10 % EXV_AFAN Pre-Close EXV - Fan Sub nnn.n 10 % EXV_MFAN Pre-Close EXV - Lag Shut nnn.n 10 % EXV_SLAG Lag Start Delay nnn 10 secs DELAYLAG
CCN CONFIGURATION TABLES — EXVBCONF (EXV Circuit B Configuration)
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
EXV Circ. B Start Pos nnn.n 50.0 % EXVBSTRT EXV Circ. B Min Position nnn.n 8.0 % EXVBMINP EXVB Steps in Range nnnnn 1596/2500 steps EVXBRANG EXVB Steps Per Second nnnnn 200 steps EXVBRATE EXVB Fail Position in % nnnn.nn 0 % EXVBPOSF EXVB Minimum Steps nnnnn 0 steps EXVBMINS EXVB Maximum Steps nnnnn 1596/2500 steps EXVBMAXS EXVB Overrun Steps nnnnn 167 steps EXVBOVRS EXVB Stepper Type nnn Bipolar EXVBTYPE
CCN CONFIGURATION TABLES — MM_CONF (Motormaster Configuration)
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
Motormaster Select No/Yes No MM_SLCT Head Pressure P Gain nnn.n 1.0 HP_PGAIN Head Pressure I Gain nnn.n 0.1 HP_IGAIN Head Pressure D Gain nnn.n 0.0 HP_DGAIN Minimum Fan Speed nnn.n 5.0 % MIN_VHP
94
Page 95
APPENDIX B — CCN TABLES (cont)
CCN SERVICE TABLES — SERVICE
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
SERVICE Brine Freeze Point nnn.n F BRN_FRZ Pump Service Interval nnnnn hours SI_PUMPS COMPRESSOR ENABLE Enable Compressor A1 Disable/Enable ENABLEA1 Enable Compressor A2 Disable/Enable ENABLEA2 Enable Compressor B1 Disable/Enable ENABLEB1 Enable Compressor B2 Disable/Enable ENABLEB2
CCN SETPOINT TABLES — SETPOINT
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
COOLING Cooling Setpoint 1 –20 to 70 44.0 FCSP1 Cooling Setpoint 2 –20 to 70 44.0 FCSP2 ICE Setpoint –20 to 32 32.0 FCSP3
RAMP LOADING Cooling Ramp Loading 0.2 to 2.0 1.0 CRAMP
Brine Freeze Point –20 to 34 34.0 F BRN_FRZ Head Setpoint FHSP Fan On Set Point F FANONSP Fan Off Set Point FFANOFFSP Fan Stage Delta FFSTGDLTA Base Fan Off Delta Temp FB_FANOFF
CCN MAINTENANCE TABLES — CIRA_EXV
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
EXV % Open nnn % EXV_A Circuit A Approach nnn.n delta F CIRA_APP Approach Setpoint nnn.n delta F APPRA_SP EXVA Override nnnnn EXVAOVRR Suction Superheat Temp nnn.n delta F SH_A Active Superheat Setpt nn.n delta F ACTSH_SP Active MOP Setpt nn.n delta F ACMOP_SP Cir A EXV Position Limit nnn % PLMA
95
Page 96
APPENDIX B — CCN TABLES (cont)
CCN MAINTENANCE TABLES — CIRB_EXV
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
EXV % Open nnn % EXV_B Circuit B Approach nnn.n delta F CIRB_APP Approach Setpoint nnn.n delta F APPRB_SP EXVB Override nnnnn EXVBOVRR Suction Superheat Temp nnn.n delta F SH_B Active Superheat Setpt nn.n delta F ACTSH_SP Active MOP Setpt nn.n delta F ACMOP_SP Cir B EXV Position Limit nnn % PLMB
CCN MAINTENANCE TABLES — STRTHOUR
DESCRIPTION VALUE UNITS POINT NAME
Machine Operating Hours nnnnnn hours HR_MACH Machine Starts nnnnnn CY_MACH
Circuit A Run Hours nnnnnn hours HR_CIRA
Compressor A1 Run Hours nnnnnn hours HR_A1 Compressor A2 Run Hours nnnnnn hours HR_A2
Circuit B Run Hours nnnnnn hours HR_CIRB
Compressor B1 Run Hours nnnnnn hours HR_B1 Compressor B2 Run Hours nnnnnn hours HR_B2
Circuit A Starts nnnnnn CY_CIRA
Compressor A1 Starts nnnnnn CY_A1 Compressor A2 Starts nnnnnn CY_A2
Circuit B Starts nnnnnn CY_CIRB
Compressor B1 Starts nnnnnn CY_B1 Compressor B2 Starts nnnnnn CY_B2
PUMP HOURS Pump 1 Run Hours nnnnnn hours HR_PUMP1 Pump 2 Run Hours nnnnnn hours HR_PUMP2
CCN MAINTENANCE TABLES — CURRMODS
DESCRIPTION VALUE POINT NAME
CSM controlling Chiller On/Off MODE_1 WSM controlling Chiller On/Off MODE_2 Master/Slave control On/Off MODE_3 Ramp Load Limited On/Off MODE_5 Timed Override in effect On/Off MODE_6 Low Cooler Suction TempA On/Off MODE_7 Low Cooler Suction TempB On/Off MODE_8 Slow Change Override On/Off MODE_9 Minimum OFF time active On/Off MODE_10 Dual Setpoint On/Off MODE_13 Temperature Reset On/Off MODE_14 Demand/Sound Limited On/Off MODE_15 Cooler Freeze Protection On/Off MODE_16 Low Temperature Cooling On/Off MODE_17 High Temperature Cooling On/Off MODE_18 Making ICE On/Off MODE_19 Storing ICE On/Off MODE_20 High SCT Circuit A On/Off MODE_21 High SCT Circuit B On/Off MODE_22 Minimum Comp. On Time On/Off MODE_23 Pump Off Delay Time On/Off MODE_24 Low Sound Mode On/Off MODE_25
96
Page 97
APPENDIX B — CCN TABLES (cont)
CCN MAINTENANCE TABLES — ALARMS
DESCRIPTION VALUE POINT NAME
Active Alarm #1 Axxx or Txxx ALARM01C Active Alarm #2 Axxx or Txxx ALARM02C Active Alarm #3 Axxx or Txxx ALARM03C Active Alarm #4 Axxx or Txxx ALARM04C Active Alarm #5 Axxx or Txxx ALARM05C Active Alarm #6 Axxx or Txxx ALARM06C Active Alarm #7 Axxx or Txxx ALARM07C Active Alarm #8 Axxx or Txxx ALARM08C Active Alarm #9 Axxx or Txxx ALARM09C Active Alarm #10 Axxx or Txxx ALARM10C Active Alarm #11 Axxx or Txxx ALARM11C Active Alarm #12 Axxx or Txxx ALARM12C Active Alarm #13 Axxx or Txxx ALARM13C Active Alarm #14 Axxx or Txxx ALARM14C Active Alarm #15 Axxx or Txxx ALARM15C Active Alarm #16 Axxx or Txxx ALARM16C Active Alarm #17 Axxx or Txxx ALARM17C Active Alarm #18 Axxx or Txxx ALARM18C Active Alarm #19 Axxx or Txxx ALARM19C Active Alarm #20 Axxx or Txxx ALARM20C Active Alarm #21 Axxx or Txxx ALARM21C Active Alarm #22 Axxx or Txxx ALARM22C Active Alarm #23 Axxx or Txxx ALARM23C Active Alarm #24 Axxx or Txxx ALARM24C Active Alarm #25 Axxx or Txxx ALARM25C
CCN MAINTENANCE TABLES — VERSIONS
DESCRIPTION VERSION VALUE
EXV CESR131172- nn-nn AUX CESR131333- nn-nn MBB CESR131460- nn-nn EMM CESR131174- nn-nn MARQUEE CESR131171- nn-nn NAVIGATOR CESR130227- nn-nn
CCN MAINTENANCE TABLES — LOADFACT
DESCRIPTION VALUE UNITS POINT NAME
CAPACITY CONTROL Load/Unload Factor snnn.n SMZ Control Point snnn.n F CTRL_PNT Entering Fluid Temp snnn.n FEWT Leaving Fluid Temp snnn.n FLWT
Ramp Load Limited On/Off MODE_5 Slow Change Override On/Off MODE_9 Cooler Freeze Protection On/Off MODE_16 Low Temperature Cooling On/Off MODE_17 High Temperature Cooling On/Off MODE_18 Minimum Comp. On Time On/Off MODE_23
97
Page 98
APPENDIX B — CCN TABLES (cont)
CCN MAINTENANCE TABLES — PM-PUMP
DESCRIPTION VALUE UNITS POINT NAME
Pump Service Interval nnnnnn hours SI_PUMPS Pump 1 Service Countdown nnnnnn hours P1_CDOWN Pump 1 Maintenance Done Yes/No P1_MAINT Pump 2 Service Countdown nnnnnn hours P2_CDOWN Pump 2 Maintenance Done Yes/No P2_MAINT Pump 1 Maintenance Date mm/dd/yy hh:mm PMP1_PM0 Pump 1 Maintenance Date mm/dd/yy hh:mm PMP1_PM1 Pump 1 Maintenance Date mm/dd/yy hh:mm PMP1_PM2 Pump 1 Maintenance Date mm/dd/yy hh:mm PMP1_PM3 Pump 1 Maintenance Date mm/dd/yy hh:mm PMP1_PM4 Pump 2 Maintenance Date mm/dd/yy hh:mm PMP2_PM0 Pump 2 Maintenance Date mm/dd/yy hh:mm PMP2_PM1 Pump 2 Maintenance Date mm/dd/yy hh:mm PMP2_PM2 Pump 2 Maintenance Date mm/dd/yy hh:mm PMP2_PM3 Pump 2 Maintenance Date mm/dd/yy hh:mm PMP2_PM4
CCN MAINTENANCE TABLES — PM-STRN
DESCRIPTION VALUE UNITS POINT NAME
Strainer Srvc Interval nnnnnn hours SI_STRNR Strainer Srvc Countdown nnnnnn hours ST_CDOWN Strainer Maint. Done Yes/No ST_MAINT Strainer Maint. Date mm/dd/yy hh:mm STRN_PM0 Strainer Maint. Date mm/dd/yy hh:mm STRN_PM1 Strainer Maint. Date mm/dd/yy hh:mm STRN_PM2 Strainer Maint. Date mm/dd/yy hh:mm STRN_PM3 Strainer Maint. Date mm/dd/yy hh:mm STRN_PM4
CCN MAINTENANCE TABLES — PM-COIL
DESCRIPTION VALUE UNITS POINT NAME
Coil Cleaning Srvc Inter nnnnnn hours SI_COIL Coil Service Countdown nnnnnn hours CL_CDOWN Coil Cleaning Maint.Done Yes/No CL_MAINT Coil Cleaning Maint.Date mm/dd/yy hh:mm COIL_PM0 Coil Cleaning Maint.Date mm/dd/yy hh:mm COIL_PM1 Coil Cleaning Maint.Date mm/dd/yy hh:mm COIL_PM2 Coil Cleaning Maint.Date mm/dd/yy hh:mm COIL_PM3 Coil Cleaning Maint.Date mm/dd/yy hh:mm COIL_PM4
CCN MAINTENANCE TABLES — TESTMODE
DESCRIPTION VALUE UNITS POINT NAME
Service Test Mode On/Off NET_CTRL Compressor A1 Relay On/Off S_A1_RLY Compressor A2 Relay On/Off S_A2_RLY Compressor B1 Relay On/Off S_B1_RLY Compressor B2 Relay On/Off S_B2_RLY Fan 1 Relay On/Off S_FAN_1 Fan 2 Relay On/Off S_FAN_2 Cooler Pump Relay 1 On/Off S_CLPMP1 Cooler Pump Relay 2 On/Off S_CLPMP2 Comp A1 Unload Time nn sec S_A1ULTM Minimum Load Valve Relay On/Off S_MLV Remote Alarm Relay On/Off S_ALM EXV % Open nn % S_EXV_A EXV % Open nn % S_EXV_B
98
Page 99
APPENDIX B — CCN TABLES (cont)
CCN MAINTENANCE TABLES — RUNTEST
DESCRIPTION VALUE UNITS POINT NAME
Percent Total Capacity nnn % CAPA_T Percent Available Cap. nnn % CAPA_A Discharge Pressure nnn.n psig DP_A Suction Pressure nnn.n psig SP_A Head Setpoint nnn.n FHSP Saturated Condensing Tmp nnn.n FTMP_SCTA Saturated Suction Temp nnn.n FTMP_SSTA Compr Return Gas Temp nnn.n FTMP_RGTA Discharge Gas Temp nnn.n FDISGAS Suction Superheat Temp nnn.n ^F SH_A Compressor A1 Relay On/Off K_A1_RLY Compressor A2 Relay On/Off K_A2_RLY Minimum Load Valve Relay On/Off MLV_RLY Compressor A1 Feedback On/Off K_A1_FBK Compressor A2 Feedback On/Off K_A2_FBK Percent Total Capacity nnn % CAPB_T Percent Available Cap. nnn % CAPB_A Discharge Pressure nnn.n psig DP_B Suction Pressure nnn.n psig SP_B Head Setpoint nnn.n FHSP Saturated Condensing Tmp nnn.n FTMP_SCTB Saturated Suction Temp nnn.n FTMP_SSTB Compr Return Gas Temp nnn.n FTMP_RGTB Suction Superheat Temp nnn.n ^F SH_B Compressor B1 Relay On/Off K_B1_RLY Compressor B2 Relay On/Off K_B2_RLY Minimum Load Valve Relay On/Off MLV_RLY
Compressor B1 Feedback On/Off K_B1_FBK Compressor B2 Feedback On/Off K_B2_FBK Fan 1 Relay On/Off FAN_1 Fan 2 Relay On/Off FAN_2
Outside Air Temperature nnn.n FOAT Space Temperature nnn.n F SPT Cooler Pump Relay 1 On/Off COOLPMP1 Cooler Pump Relay 2 On/Off COOLPMP2 Cooler Pump 1 Interlock Open/Closed PMP1_FBK Cooler Pump 2 Interlock Open/Closed PMP2_FBK Cooler Entering Fluid nnn.n F COOL_EWT Cooler Leaving Fluid nnn.n F COOL_LWT Compressor A1 Size nnn tons SIZE_A1 Compressor A2 Size nnn tons SIZE_A2 Compressor B1 Size nnn tons SIZE_B1 Compressor B2 Size nnn tons SIZE_B2 Cooler Flow Switch On/Off COOLFLOW
99
Page 100
APPENDIX B — CCN TABLES (cont)
CCN MAINTENANCE TABLES — DUALCHIL
DESCRIPTION VALUE UNITS POINT NAME
Dual Chiller Link Good? Yes/No DC_LINK Master Chiller Role Stand Alone,
Slave Chiller Role Stand Alone,
Lead Chiller Ctrl Point snnn.n F LEAD_CP Lag Chiller Ctrl Point snnn.n FLAG_CP Control Point snnn.n F CTRL_PNT
Cool EnteringFluid-Slave snnn.n FCOOLEWTS Cool Leaving Fluid-Slave snnn.n FCOOLLWTS Cooler Entering Fluid snnn.n F COOL_EWT Cooler Leaving Fluid snnn.n FCOOL_LWT Lead/Lag Leaving Fluid snnn.n F DUAL_LWT
Percent Avail.Capacity 0-100 % CAP_A Percent Avail.Cap.Slave 0-100 % CAP_A_S
Lag Start Delay Time hh:mm LAGDELAY Load/Unload Factor snnn.n SMZ Load/Unload Factor-Slave snnn.n SMZSLAVE Lead SMZ Clear Commanded Yes/No LEADSMZC Lag SMZ Clear Commanded Yes/No LAG_SMZC Lag Commanded Off? Yes/No LAG_OFF
Lead Chiller,
Lag Chiller
Lead Chiller,
Lag Chiller
MC_ROLE
SC_ROLE
Dual Chill Lead CapLimit 0-100 % DCLDCAPL Dual Chill Lag CapLimit 0-100 % DCLGCAPL
100
Loading...