Carrier 30MPA User Manual

Page 1
Fig. 1 — 30MPA Unit
a30-5029
Fig. 2 — 30MPW Unit
a30-5030
30MPA,MPW015-045
with Scroll Compressors
and COMFORTLINK™ Controls
Installation Instructions
AQUASNAP
®
Liquid Chillers
CONTENTS
Page
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1,2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Step 1 — Inspect Shipment . . . . . . . . . . . . . . . . . . . . 2
Step 2 — Position the Unit . . . . . . . . . . . . . . . . . . . . . 2
Step 3 — Place the Unit. . . . . . . . . . . . . . . . . . . . . . . . 7
Step 4 — Check Compressor Mounting. . . . . . . . 7
Step 5 — Make Piping Connections. . . . . . . . . . . . 7
• 30MPA SYSTEM CONDENSER
• 30MPW CONDENSER DESCRIPTION
• 30MPW CONDENSER
• EVAPORATOR DESCRIPTION
• EVAPORATOR PIPING
•AIR SEPARATION
Step 6 — Fill the Chilled Water Loop. . . . . . . . . . .13
• WATER SYSTEM CLEANING
• FILLING THE SYSTEM
Step 7 — Make Electrical Connections. . . . . . . . .14
•FLOW SWITCH
• CONTROL BOX, POWER SECTION
• CONTROL BOX, CONTROLS SECTION
• CONTROL BOX, FIELD CONTROL WIRING SECTION
• UNBALANCED 3-PHASE SUPPLY VOLTAGE
.
WARNING
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation. There may be more than one disconnect switch. Tag all discon­nect locations to alert others not to restore power until work is completed.
GENERAL
These installation instructions cover the 30MPA, MPW units
with ComfortLink controls. The 30MPA units are condenserless units and the 30MPW units are all fluid cooled.
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment (Fig. 1
and 2) can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated struc­tures, etc.). Model number structure is shown in Fig. 3.
Only trained, qualified installers and service technicians
should install, start up, and service this equipment.
When working on the equipment, observe precautions in the
literature and on tags, stickers, and labels attached to the equipment.
Follow all safety codes.
Wear safety glasses and work gloves.
Use care in handling, rigging, and setting bulky
equipment.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300054-01 Printed in U.S.A. Form 30MP-1SI Pg 1 910 1-10 Replaces: New
Page 2
INSTALLATION
30MP
A0306 -
30MP – Aquasnap® Liquid Chiller with ComfortLink™ Controls
Condenser Option A – Chiller without Condenser (Air-Cooled)
Design Revision Level
W – Chiller with Condenser (Water-Cooled)
- – Initial Release
Voltage Options 1 – 575-3-60
5 – 208/230-3-60 6 – 460-3-60
Unit Size – Nominal Tons (kW) 015 – 15 (54) 040 – 40 (138) 020 – 20 (71) 045 – 45 (161) 030 – 30 (108)
2 – 380-3-60
0
Sound/Mounting Options 0 – None 1 – S
ound Enclosure Panels
3 – Height Adjustment Kit
4 – Height Adjustment Kit, Sound Enclosure Panels 9 – Mobility Kit (Wheels) B – Mobility Kit (Wheels), Sound Enclosure Panels D – Height Adjustment Kit, Mobility Kit (Wheels) F – Height Adjustment Kit, Mobility Kit (Wheels), Sound Enclosure Panels
0
Comfort Cooling/Medium Temp Brine Options 0 – Comfort Cooling Duty (32-60 F) (Std) 7 – Medium Temperature Brine (15-32 F)
0
Capacity Control Options 0 – Standard 1 – Hot Gas Byp
ass
0
Disconnect Options 0 – Standard (Terminal Block) 1 – Non-Fused Disconnect Switch
0
Controls/Interface Options 0 – Scrolling Marquee Display (Std) 5 – Scrolling Marquee Display, EMM
5
Packaging Options
5 – Bag B – Export Crate
Fig. 3 — 30MP Model Number Nomenclature
LEGEND
EMM — Energy Management Module LON — Local Operating Network UPC — Unitary Protocol Controller
a30-5038
Location —
er because of sensitive control mechanisms and electronic devices. Locate unit indoors. See Fig. 4 and 5 for unit dimen­sional details.
When considering location, consult National Electrical Code (NEC) and local code requirements. Allow sufficient space for wiring, piping, and service. Install unit in an area where it will not be exposed to ambient temperatures below 50 F (10 C).
Allow 36 in. (914 mm) in front of the unit for control box access door. Additional clearance may be required per local codes. Prior to installation determine which direction compres­sor will be removed, and leave 3 to 4 ft (914 to 1219 mm) clearance for removal.
On all units leave 3 ft (0.9 m) of clearance behind the unit to make water/brine connections to the evaporator, accessing the TXV (thermostatic expansion valve), fluid thermistors, and proof of flow switch.
On all units, leave 2 ft (610 mm) on one side for making re­frigeration connections (30MPA) or fluid connections (30MPW) to condenser. See Fig. 4 and 5.
The floor must be strong enough to support the unit operat­ing weight (see Tables 1A and 1B and Fig. 4-6). If necessary, add a supporting structure (steel beams or reinforced concrete slabs) to the floor to transfer weight to nearest beams.
Do not store units in an area exposed to weath-
Additional weight of factory-installed sound enclosure op-
tion is 75 lb (34 kg).
CAUTION
Be sure interconnecting piping and electrical conduits
Step 1 — Inspect Shipment — Inspect unit for dam-
age or missing parts. If damaged, or if shipment is incomplete, file a claim immediately with the shipping company.
are suspended freely, and are not in contact with any adjacent walls. Be sure unit capillaries are not rubbing against anything. Damage to unit or walls may result.
Unit is top heavy. Unit may tip if handled without care. Damage to unit or injury may result.
CAUTION
Step 2 — Position the Unit — The unit may be
moved by means of rollers under the rails or a forklift truck. If accessory mobility kit is to be used, install this accessory
after bringing unit into building and before moving the unit to its final location per installation instructions provided with the accessory. The factory-installed mobility kit option consists of 4 swivel-type wheels that are field-mounted to the legs of the unit. See Fig. 7.
NOTE: The wheels are equipped with a thumb-screw brake.
2
Page 3
52.30
1328[]
STD UNIT 55.00
1397[]
OPTIONAL SOUND ENCLOSURE 57.00 [1448]
29.13
740[]
STD UNIT 32.00
813[]
62.50
1588[]
OPTIONAL SOUND ENCLOSURE 32.12 [816]
MOBILITY KIT
(WHEEL) OPTIONAL
3.85
98[]
E
D
F
OPTIONAL SOUND ENCLOSURE 48.42 [1230]
OPTIONAL
SOUND
ENCLOSURE
65.05
[1652]
4.00 [102]
ISOLATOR-OPTIONAL
C
B
A
4.03
102[]
1.75
44[]
4.46
[113]
UNIT
OPERATING
WEIGHT (lb)
ABCDEF
NO.OF
COMPRESSORS
30MPA015 626 (284 kg)
17.80 (452 mm)
25.10 (638 mm)
31.49 (800 mm)
5.54 (141 mm)
6.44 (164 mm)
18.50 (470 mm)
230MPA020 635 (288 kg)
17.60 (447 mm)
25.20
(640 mm)
31.39 (797 mm)
30MPA030 722 (327 kg)
17.00 (432 mm)
26.00 (660 mm)
30.69 (780 mm)
5.87 (149 mm)
11.12 (282 mm)
17.95 (456 mm)
30MPA040 913 (414 kg)
17.50 (445 mm)
25.90 (658 mm)
33.50 (851 mm)
5.99 (152 mm)
11.00 (279 mm)
17.72 (450 mm)
3
30MPA045 934 (424 kg)
17.40 (442 mm)
26.00 (660 mm)
33.49 (851 mm)
COMPRESSOR
(SEE TABLE FOR QTY)
OUT
IN
OPTIONAL SOUND
ENCLOSURE
FIELD CONNECTION
(4) 7/8" K.O
NON-FUSED
DISCONNECT
(OPTIONAL)
1/4" FPT
ACCESS
P,T
ACCESS
PORTS
1/4" SAE
FLARE RELIEF
CONNECTION
POWER
ENTRY
WATER CONNECTIONS
(IN/OUT)
2" VICTAULIC (015-020)
2 1/2" VICTAULIC (030-045)
COOLER
COOLER
COOLER
CONTROL PANEL END
OPPOSITE CONTROL PANEL END
MOUNTING HOLES 9/16"
-
MOUNTING HOLES 9/16"
-
IN
OUT
040,045 TON
ONLY
FORK POCKETS
SCROLLING
MARQUEE DISPLAY
REMOTE CONDENSER
CONNECTION
LIQ. LINE
ISOLATION VALVE
LIQ. LINE
SOLENOID
VALVE
CONTROL BOX
ACCESS DOOR
CLEARANCE
36"(914)
ENSURE CLEARANCE
PER LOCAL CODES
CONTROL PANEL
END OF UNIT
Fig. 4 — Dimensions — 30MPA015-045 Units
NOTES:
1. Operating weight includes weight of water and refrigerant.
2. Denotes center of gravity.
3. Dimensions are shown in inches. Dimensions in [ ] are in
millimeters.
4. Allow 36-in. (914 mm) clearance on control panel end, opposite
control panel end and above the unit. All clearances must be in
accordance with local codes.
5. Denotes accessory or factory-installed option.
a30-5032
3
Page 4
Fig. 5 — Dimensions — 30MPW015-045 Units
NOTES:
1. Operating weight includes weight of water and refrigerant.
2. Denotes center of gravity.
3. Dimensions are shown in inches. Dimensions in [ ] are in
millimeters.
4. Allow 36-in. (914 mm) clearance on control panel end, opposite
control panel end and above the unit. All clearances must be in
accordance with local codes.
5. Denotes accessory or factory-installed option.
a30-5033
910
4
Page 5
Table 1A — 30MPA Air-Cooled and 30MPW Liquid-Cooled Units — English
UNIT 30MPA,MPW 015 020 030 040 045 NOMINAL TONS 15 20 30 40 45 OPERATING WT (lb)
MPA 626 635 722 913 934 MPW 680 704 862 1099 1190
REFRIGERANT (lb) R-410A
MPA ————— MPW 11.6 15.2 23.1 29.4 34.4
COMPRESSOR Scroll, Hermetic
Quantity 22233 Speed (rpm) 3500 3500 3500 3500 3500 Compressor Nominal Tons 7.510151315 Oil Charge (pt) 10.6 13.8 13.8 20.6 20.6 Capacity Control — Standard
No. of Steps 22233 Minimum Step Capacity (%) 50 50 50 33 33
Capacity Control — Optional Hot Gas Bypass
No. of Steps 33344 Minimum Step Capacity (%) 18 25 34 21 22
EVAPORATOR
Weight (lb, empty) 27.5 40.3 91.8 122.3 128.3 Net Fluid Volume (gal.) 0.8 1.2 2.4 3.2 3.4 Maximum Refrigerant Pressure (psig) 650 650 650 650 650 Maximum Fluid-Side Pressure (psig) 300 300 300 300 300
Water Connections (in.)
Inlet and Outlet (Victualic) 222 Drain (NPT)
CONDENSER (30MPW Only)
Weight (lb, empty) 34.9 43.6 104.6 136.7 188.3 Net Fluid Volume (gal.) 1.2 1.6 2.9 4.1 5.9 Maximum Refrigerant Pressure (psig) 650 650 650 650 650 Maximum Fluid-Side Pressure (psig) 300 300 300 300 300
Water Connections (in.)
Inlet and Outlet (Victualic) 222
1
/
2
1
/
2
CHASSIS DIMENSIONS (in.)
Length 55 55 55 55 55 Width 32 32 32 32 32 Height 63 63 63 63 63
MINIMUM SYSTEM FLUID VOLUME (gal. per Ton)
Normal Air Conditioning Standard 66644 Optional Hot Gas Bypass 44433 Low Outdoor Ambient Cooling Operation (30MPA Units) Standard 10 10 10 88 Optional Hot Gas Bypass 77766
CAPACITY STEPS
Step 1 100% 100% 100% 100% 100% Step 2 50% 50% 50% 67% 67% Step 3 18%* 25%* 34%* 33% 33% Step 4 21%* 22%*
MINIMUM FLOW RATES (gpm)
Evaporator 22 28 43 55 64 Condenser 22 28 43 55 64
MAXIMUM FLOW RATES (gpm)
Evaporator 74 97 148 188 220 Condenser 74 97 148 188 220
* With optional hot gas bypass. NOTES:
1. Operating weight includes refrigerant operating charge and weight of fluid in the heat exchangers.
2. 30MPW units are shipped with full operating charge.
1
/
2
1
/
2
1
/
2
2 1/
1
2 1/
2
/
2
2
21/
21/
2
1
/
2
2
5
Page 6
Table 1B — 30MPA Air-Cooled and 30MPW Liquid-Cooled Units — SI
UNIT 30MPA,MPW 015 020 030 040 045 NOMINAL KW 54 71 108 138 161 OPERATING WT (kg)
MPA 284288 327 414 424 MPW 308 319 391 499 540
REFRIGERANT (kg) R-410A
MPA ————— MPW 5.2 6.9 10.5 13.3 15.6
COMPRESSOR Scroll, Hermetic
Quantity 22233 Speed (r/s) 58 58 58 58 58 Compressor Nominal kW 26 35 53 45 53 Oil Charge (L) 5.0 6.5 6.5 9.8 9.8 Capacity Control — Standard
No. of Steps 22233 Minimum Step Capacity (%) 50 50 50 33 33
Capacity Control — Optional Hot Gas Bypass
No. of Steps 33344 Minimum Step Capacity (%) 18 25 34 21 22
EVAPORATOR
Weight (kg, empty) 12.5 18.3 41.6 55.5 58.2 Net Fluid Volume (L) 2.9 4.6 8.9 12.0 13.0 Maximum Refrigerant Pressure (kPa) 44824482448244824482 Maximum Fluid-Side Pressure (kPa) 2068 2068 2068 2068 2068
Water Connections (in.)
Inlet and Outlet (Victualic) 222 Drain (NPT)
CONDENSER (30MPW)
Weight (kg, empty) 15.8 19.8 47.4 62.0 85.4 Net Fluid Volume (L) 4.5 5.9 11.1 15.4 22.4 Maximum Refrigerant Pressure (kPa) 44824482448244824482 Maximum Fluid-Side Pressure (kPa) 2068 2068 2068 2068 2068
Water Connections (in.)
Inlet and Outlet (Victualic) 1
1
/
2
1
/
2
11/
1
/
2
2
CHASSIS DIMENSIONS (mm)
Length 1397 1397 1397 1397 1397 Width 813 813 813 813 813 Height 1600 1600 1600 1600 1600
MINIMUM SYSTEM FLUID VOLUME (L per kW)
Normal Air Conditioning Standard 23 23 23 15 15 Optional Hot Gas Bypass 15 15 15 11 11 Low Outdoor Ambient Cooling Operation (30MPA Units) Standard 38 38 38 30 30 Optional Hot Gas Bypass 25 25 25 23 23
CAPACITY STEPS
Step 1 100% 100% 100% 100% 100% Step 2 50% 50% 50% 67% 67% Step 3 18%* 25%* 34%* 33% 33% Step 4 21%* 22%*
MINIMUM FLOW RATES (L/s)
Evaporator 1.4 1.8 2.7 3.5 4.0 Condenser 1.4 1.8 2.7 3.5 4.0
MAXIMUM FLOW RATES (L/s)
Evaporator 4.7 6.1 9.3 11.9 13.9 Condenser 4.7 6.1 9.3 11.9 13.9
* With optional hot gas bypass. NOTES:
1. Operating weight includes refrigerant operating charge and weight of fluid in the heat exchangers.
2. 30MPW units are shipped with full operating charge.
1
/
2
1
/
2
2 1/
1
2
/
2
21/
2
1
/
2
222
6
Page 7
B
A
C
D
CONTROL PANEL SIDE
WEIGHT DISTRIBUTION AT EACH MOUNTING
HOLE — Lb (kg)
UNIT 30MP
MOUNTING HOLE
ABCD A015 156 (71) A020 159 (72) A030 181 (82) A040 228 (104) A045 234 (106)
W015 170 (77) W020 176 (80) W030 216 (98) W040 275 (125) W045 298 (135)
Fig. 6 — Mounting Hole Weight Distribution
a30-5040
Fig. 7 — Mobility Kit
a30-5041
Step 3 — Place the Unit
NOTE: These units are not suitable for unprotected outdoor use.
Carrier recommends that these units be located in the base­ment or on the ground floor. However, if it is necessary to lo­cate the unit on an upper floor, be sure the structure has been designed to support the unit weight. If necessary, add structural support to floor. Also, be sure the surface for installation is level. Refer to Fig. 4 and 5 for space requirements and weight distribution.
Only electrical power connections, water connections for condenser, fluid connections for evaporator, and strainer instal­lation are required for 30MPW installation. Installation of
30MPA units varies only in field piping required for the remote condenser.
When the unit is in its final position, remove the packaging
and remove the mobility kit wheels (if equipped). Remove
3
/8-in. wheel nuts to remove wheels from unit legs. Level the
unit (using a level), and bolt the unit to the floor or pad.
If unit is to be mounted on unit external vibration isolators, follow the mounting instructions included with the accessory vibration isolator.
If unit has accessory leveling kit installed, follow the in­structions provided with the accessory to make sure unit is lev­el and in the correct position.
Step 4 — Check Compressor Mounting — As
shipped, units with two compressors are held down with 6 bolts through rubber grommets. All units with three compresors are held down with 8 bolts per pair through grommets. After unit is installed, verify mounting bolt torque 7 to10 ft-lb (9 to 14 Nm).
Step 5 — Make Piping Connections — See
Fig. 8 and 9 for typical piping applications. 30MPA SYSTEM CONDENSER — For detailed condenser
piping installation instructions for 30MPA systems, refer to separate instructions packaged with the remote condenser units.
Condenser refrigerant piping for 30MPA units should be sized to minimize the amount of refrigerant required.
The 30MPA units that use air-cooled evaporative condens­ers must have adequate means for head pressure control when operating below 60 F (15.6 C).
Carrier recommends that a field-supplied pressure relief de­vice be installed in each discharge line of 30MPA units. Most local codes require the discharge line relief valve to be vented directly to the outdoors. The vent must not be smaller than the discharge line relief valve outlet.
30MPW CONDENSER DESCRIPTION — All 30MPW units use a brazed-plate heat-exchanger-type condenser. These heat exchangers are made of embossed plates of acid-resistant stainless steel. Every other plate is reversed so that the ridges of the herringbone pattern intersect one another on adjacent plates, forming a lattice of contact points. These plates are vacuum-brazed together to form a compact and pressure­resistant heat exchanger.
After brazing, the impressions in the plates form 2 separate systems of channels where the refrigerant and water flows are counterflow. The number of plates varies depending on unit tonnage. The condensers provide approximately 10º to 12º F (6º to 8º C) liquid subcooling at the standard Air Conditioning, Heating and Refrigeration Institute (AHRI) rating condition.
30MPW CONDENSER — When facing the unit control box, the condenser is the uninsulated heat exchanger located on the left-hand side. The water connections are on the right-hand side of the heat exchanger with the LIQUID-IN connection at the bottom, and the LIQUID-OUT connection at the top.
A strainer with a minimum of 40 mesh must be installed within 10 ft (3 m) of the condenser water inlet to prevent debris from clogging or damaging the heat exchanger. The strainer is required for operation and is available as an accessory.
To install the victaulic coupling (see Fig. 10):
1. Lubricate the gasket lips and stretch the gasket over the end of the heat exchanger coupling. Avoid twisting the gasket when installing.
2. Bring the pipe and heat exchanger coupling ends together into alignment. Slide the gasket so that it is centered over the ends. Apply a light film of lubricant to the gasket, or to the outside diameter of the pipe. Avoid twisting the gasket during installation.
7
Page 8
NOTES:
1. Chiller must be installed level to maintain proper compressor oil return.
2. Wiring and piping shown are general points-of-connection guides only and are not intended for a spe-
cific installation. Wiring and piping shown are for a quick overview of system and are not in accordance
with recognized standards. Units should be installed using certified drawings.
3. All wiring must comply with applicable local and national codes.
4. All piping must follow standard piping techniques. Refer to Carrier System Design Manual or appropri-
ate ASHRAE (American Society of Heating, Refrigerating, and Air Conditioning Engineers) handbook
for details.
5. See Tables 1A and 1B for minimum system fluid volume. This system may require the addition of a
holding tank to ensure adequate volume.
6. A strainer with a minimum of 40 mesh must be installed within 10 ft (3 m) of the evaporator fluid inlet to
prevent debris from clogging or damaging the heat exchanger. This strainer is required and is available
as an accessory.
7. Piping, wiring, switches, vents, strainers, drains, and vibration isolation are all field-supplied.
Fig. 8 — Typical Piping with Liquid-Cooled 30MPW Chiller
a30-4997
8
Page 9
NOTES:
1. Chiller must be installed level to maintain proper compressor oil return.
2. Wiring and piping shown are general points-of-connection guides only and are not intended for a specific installation. Wiring and pip­ing shown are for a quick overview of system and are not in accor­dance with recognized standards. Units should be installed using certified drawings.
3. All wiring must comply with applicable local and national codes.
4. All piping must follow standard piping techniques. Refer to Carrier System Design Manual part 3, Carrier E20-II software Refrigerant Piping program, or appropriate ASHRAE (American Society of Heating, Refrigerating, and Air Conditioning Engineers) handbook for details on proper piping sizes and design.
5. See Tables 1A and 1B for minimum system fluid volume. This sys­tem may require the addition of a holding tank to ensure adequate volume.
6. Hot gas lines should rise above refrigerant level in condenser cir­cuit. Double riser may be required; check unit minimum capacity.
7. Trap should be installed on hot gas lines to prevent condenser oil and refrigerant vapor migration from accumulating in compressor during off cycle.
8. Pitch all horizontal lines downward in the direction of refrigerant flow.
9. Provide support to liquid and gas lines near the connections to the condenser coil.
10. For pressure relief requirements, see latest revision of ASHRAE Standard 15, Safety Code for Mechanical Refrigeration.
11. A strainer with a minimum of 40 mesh must be installed within 10 ft (3 m) of the evaporator fluid inlet to prevent debris from clogging or damaging the heat exchanger. This strainer is required and is avail­able as an accessory.
12. Piping, wiring, switches, vents, strainers, drains, and vibration iso­lation are all field-supplied.
Fig. 9 — Typical Piping with 30MPA Unit and 09DP Remote Air-Cooled Condenser
09DP AIR-COOLED CONDENSER
a30-4998
9
Page 10
3. Install the inside coupling half over the gasket and then
Fig. 10 — Install the Victualic Coupling
a30-1245
install the outer half. Connect with nuts and bolts. Tighten the nuts equally on both sides. Ensure there is no gap be­tween the two halves of the coupling.
4. Alternately tighten the nuts with a wrench to draw the coupling halves together uniformly. The joint is now complete.
30MPW UNITS — In order to minimize the water pressure drop in the system, use as few bends as possible in the field water piping, and run the lines as short as possible. Size the water lines according to the available pump pressure (not neces­sarily the connection size), especially on cooling tower applica­tions. See Carrier System Design Manual, Part 3, Piping Design. See Fig. 11 for condenser pressure drops.
Set water regulating valve, if installed, to maintain design head pressure. Do not adjust to compensate for high head pres­sures caused by fouled condensers, excess refrigerant, or the presence of noncondensables. Due to changes in water temper­ature, it may be necessary to adjust the valve seasonally. After adjusting for design head pressure, shut unit down. The water regulating valve should shut off the flow of water in a few min­utes. If it does not, raise head pressure setting. Make sure that the capillary tube from each water regulating valve is connect­ed to the proper condenser access fitting.
Provide a means for draining the system in the winter (if not used) and for maintenance.
Water leaving the condenser is under pressure and should not be connected directly into sewer lines. Check local codes.
EVAPORATOR DESCRIPTION — All 30MP units use a brazed-plate heat-exchanger type evaporator. The heat ex­changer is constructed essentially the same as the brazed-plate condenser used on 30MPW units. See 30MPW Condenser De­scription section on page 7 for more details. Similar to the con­denser, the evaporator can only be chemically cleaned. See Fig. 12 for evaporator pressure drops.
EVAPORATOR PIPING — Plan evaporator fluid piping for minimum number of changes in elevation, and for the fewest number of bends possible. Install manual or automatic vent valve at high points in the line. Maintain system pressure by using a pressure tank or a combination of relief and reducing valves.
A strainer with a minimum of 40 mesh must be installed within 10 ft of the evaporator fluid inlet to prevent debris from clogging or damaging the heat exchanger. This strainer is re­quired and is available as an accessory.
See Carrier System Design Manual, Part 3, Piping Design, for chilled fluid piping details.
The evaporator fluid inlet and outlet connections are vict­ualic. The fluid enters at the top connection and leaves at the bottom connection. Procedures for making the connections are the same as for the 30MPW condensers. See 30MPW Con­denser section on page 7 for more details.
Run the pump for 10 minutes, then clean the strainer before starting the unit.
An evaporator flow switch is standard on all units. This is a thermal dispersion type switch that is installed in the evapora­tor fluid outlet. The switch is set to open when the evaporator fluid flow drops below the minimum set point.
For variable primary flow applications, it may be necessary to adjust the flow switch set point to avoid nuisance trips. Con­tact Carrier service engineering for the mthod needed to adjust the switch.
See Table 1 for minimum flow rates and loop volume.
The thermistors used to sense entering and leaving fluid temperature are factory-installed in the evaporator entering and leaving fluid nozzles.
AIR SEPARATION — For proper system operation, it is essential that water loops be installed with proper means to manage air in the system. Free air in the system can cause noise, reduce terminal output, stop flow, or even cause pump failure due to pump cavitation. For closed systems, equipment should be provided to eliminate all air from the system.
The amount of air that water can hold in solution depends on the pressure and temperature of the water/air mixture. Air is less soluble at higher temperatures and at lower pressures. Therefore, separation can best be done at the point of highest water temperature and lowest pressure. Typically, this point would be on the suction side of the pump as the water is return­ing from the system or terminals. Generally speaking, this is the best place to install an air separator, if possible.
1. Install automatic air vents at all high points in the system. (If the 30MP unit is located at the high point of the system, a vent can be installed on the piping entering the heat exchanger on the ¼-in. NPT female port.)
2. Install an air separator in the water loop, at the place where the water is at higher temperatures and lower pressures — usually in the chilled water return piping. On a primary-secondary system, the highest temperature water is normally in the secondary loop, close to the decoupler. Preference should be given to that point on the system (see Fig. 13). In-line or centrifugal air separators are readily available in the field.
It may not be possible to install air separators at the place of lowest pressure and highest temperature. In such cases, prefer­ence should be given to the points of highest temperature. It is important that pipe be sized correctly so that free air can be moved to the point of separation. Generally, a water velocity of at least 2 feet per second will keep free air entrained and prevent it from forming air pockets.
Automatic vents should be installed at all physically elevat­ed points in the system so that air can be eliminated during system operation. Provision should also be made for manual venting during the water loop fill. It is important that the automatic vents be located in accessible locations for maintenance purposes, and that they be located where they can be prevented from freezing.
10
Page 11
120
1
100
80
Drop (kPa)
40
60
Water Pressur
e
20
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Liters/second
12 3
5
4
40
35
1
5
4
3
2
25
30
Drop ()
15
20
Water Pressure
5
10
0
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240
GPM
Fig. 11 — Condenser Water Pressure Drop
ENGLISH
SI
LEGEND
1 — 30MP015 2—30MP020 3—30MP030 4—30MP040 5—30MP045
a30-5037
a30-5036
11
Page 12
120
3
100
1
80
Drop (kPa)
40
60
Water Pressur
e
20
0
012345678910111213
Liters/second
1
2
3
4
5
0
5
10
15
20
25
30
35
40
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
Water Pressure Drop ()
GPM
15
4
3
2
Fig. 12 — Evaporator Water Pressure Drop
ENGLISH
SI
LEGEND
1 — 30MP015 2—30MP020 3—30MP030 4—30MP040 5—30MP045
a30-5035
a30-5034
12
Page 13
Step 6 — Fill the Chilled Water Loop
Distribution Pump
Expansion Tank(s)
Air Separator with Vent
Decoupler
Chiller 1
Chiller 2
Zone 1
Zone 2
Zone 3
NOTE: Expansion tanks must be disconnected for chillers placed parallel in the primary water loop.
Fig. 13 — Typical Air Separator and Expansion Tank Location on Primary-Secondary Systems
a30-3226
WATER SYSTEM CLEANING — Proper water system cleaning is of vital importance. Excessive particulates in the water system can cause excessive pump seal wear, reduce or stop flow, and cause damage of other components. Water quality should be maintained within the limits indicated in Table 2. Failure to maintain proper water quality may result in heat exchanger failure.
CAUTION
Failure to properly clean all piping and components of the chilled water system before unit start-up may result in plugging of the heat exchanger, which can lead to poor per­formance, nuisance alarms and damage from freezing. Freezing damage caused by an improperly cleaned system represents abuse and may impair or otherwise negatively affect the Carrier product warranty.
1. Install a temporary bypass around the chiller to avoid cir­culating dirty water and particulates into the pump pack­age and chiller during the flush. Use a temporary circulat­ing pump during the cleaning process. Also, be sure that there is capability to fully drain the system after cleaning. (See Fig 14.)
2. Be sure to use a cleaning agent that is compatible with all system materials. Be especially careful if the system contains any galvanized or aluminum components. Both detergent-dispersant and alkaline-dispersant cleaning agents are available.
3. It is a good idea to fill the system through a water meter. This provides a reference point for the future for loop volume readings, but it also establishes the correct quantity of cleaner needed in order to get the required concentration.
4. Use a feeder/transfer pump to mix the solution and fill the system. Circulate the cleaning system for the length of time recommended by the cleaning agent manufacturer.
a. After cleaning, drain the cleaning fluid and flush the
system with fresh water.
b. A slight amount of cleaning residue in the system can
help keep the desired, slightly alkaline, water pH of 8 to 9. Avoid a pH greater than 10, since this will adversely affect pump seal components.
c. A side stream filter is recommended (see Fig. 15)
during the cleaning process. Filter side flow rate should be enough to filter the entire water volume every 3 to 4 hours. Change filters as often as neces­sary during the cleaning process.
Alkalinity (HCO
Sulfate (SO
HCO Electrical Conductivity 10 – 500S/cm pH 7.5 – 9.0 Ammonium (NH Chorides (Cl Free chlorine (Cl
Hydrogen Sulfide (H
Free (aggressive) Carbon Dioxide (CO
Total Hardness (dH) 4.0 – 8.5 Nitrate (NO
Iron (Fe) Less than 0.2 ppm Aluminum (Al) Less than 0.2 ppm Manganese (Mn) Less than 0.1 ppm
*Sulfides in the water quickly oxidize when exposed to air, requiring that
†Dissolved carbon dioxide can either be calculated from the pH and
FILLING THE SYSTEM — The initial fill of the chilled water system must accomplish three purposes:
The pressure created by an operating pump affects system pressure at all points except one — the connection of the compression tank to the system. This is the only location in the system where pump operation will not give erroneous pressure indications during the fill. Therefore, the best location to install the fill connection is close to the expansion tank. An air vent should be installed close by to help eliminate air that enters during the fill procedure.
13
d. Remove temporary bypass when cleaning is
complete.
Table 2 — Water Quality Characteristics
and Limitations
WATER CHARACTERISTIC QUALITY LIMITATION
-
/SO
3
no agitation occur as the sample is taken. Unless tested immediately at the site, the sample will require stabilization with a few drops of one Molar zinc acetate solution, allowing accurate sulfide determination up to 24 hours after sampling. A low pH and high alkalinity cause system problems, even when both values are within the ranges shown. The term pH refers to the acidity, basicity, or neutrality of the water supply. Below 7.0, the water is considered to be acidic. Above 7.0, water is considered to be basic. Neutral water contains a pH of 7.0.
total alkalinity values, shown below, or measured on the site using a test kit. Dissolved Carbon Dioxide, PPM = TA x 2 = Total Alkalinity, PPM as CaCO
-
) 70 – 300 ppm
3
2-
) Less than 70 ppm
4
2-
4
) Less than 2 ppm
3
-
) Less than 300 ppm
) Less than 1 ppm
2
S)* Less than 0.05 ppm
2
)†
2
) Less than 100 ppm
3
Greater than 1.0
Less than 5 ppm
.
3
[(6.3-pH)/0.3]
where TA
1. The entire piping system must be filled with water.
2. The pressure at the top of the system must be high enough to vent air from the system (usually 4 psig is adequate for most vents).
3. The pressure at all points in the system must be high enough to prevent flashing in the piping or cavitation in the pump.
Page 14
x
x
DILUTED
CLEANING
AGENT
SYSTEM
POT FEEDER AND TRANSFER PUMP
30MPUNIT
TO DRAIN
TEMPORARY PUMP
TEMPORARY BYPASS
Fig. 14 — Typical Set Up for Cleaning Process
a30-5047
SYSTEM
Fig. 15 — Cleaning Using a Side Stream Filter
a30-5048
POT FEEDER AND TRANSFER PUMP
TEMPORARY PUMP
TO DRAIN
SIDE STREAM
FILTER
DILUTED
CLEANING
AGENT
Ensure the following when filling the system:
1. Remove temporary bypass piping and cleaning/flushing equipment.
2. Check to make sure all drain plugs are installed.
3. Open the blow-down valve to flush the strainer.
Normally, a closed system needs to be filled only once. The actual filling process is generally a fairly simple procedure. All air should be purged or vented from the system. Thorough venting at the high points and circulation at room temperature for several hours is recommended.
NOTE: Local codes concerning backflow devices and other protection of the city water system should be consulted and followed to prevent contamination of the public water supply. This is especially important when antifreeze is used in the system.
Set Water Flow Rate
— Once the system is cleaned, pressur­ized, and filled, the flow rate through the chiller needs to be established.
NOTE: Carrier recommends a differential pressure gage when measuring pressures across the pumps or balancing valves. This provides for greater accuracy and reduces error build-up that often occurs when subtracting pressures made by different gages.
On primary/secondary systems, it is advisable to set the 30MP balancing valve to maintain design flow plus 10% through the chiller.
A rough estimate of water flow can also be obtained from measuring the pressure drop across the 30MP heat exchanger. Figures 11 and 12 show the relationship between gpm and heat exchanger pressure drop. It should be noted that these curves are for “clean” heat exchangers; they do not apply to heat ex­changers with fouling. Adjust the external balancing valve until the correct pressure drop is obtained for the required gpm.
x
30MPUNIT
x
TEMPORARY BYPASS
Step 7 — Make Electrical Connections — All
field wiring must comply with local code requirements. Electrical data for the complete unit and for the compressors is shown in Table 3. See Fig. 16 for field wiring connections. A field-supplied branch circuit disconnect switch that can be locked in either OPEN or OFF position must be installed.
Control circuit power is 24 v on all units. Factory-installed control transformer (TRAN 1) uses line voltage for all units. All control transformers are factory-installed and wired. For 208/230-3-60 units operating at 208-3-60 line voltage, TRAN1 primary connections must be moved to terminals H3 and H4.
Inside the control box are terminals for field power and ground (earth) wiring. A ground wire must be installed with each field power supply. Compressors are wired for across-the-line start. Refer to Table 3 for electrical data.
FLOW SWITCH — A condenser flow switch is available as an accessory for all 30MPW units, and can be field-installed. The Carrier flow switch accessory (part no. 30MP-900---004) is available for this purpose. Flow switch wiring terminals are located in the field wiring compartment of the control box. The flow switch should be wired between terminals LVT-16 and LVT-17 for all units.
CONTROL BOX, POWER SECTION — The electrical power supply is brought in through the top left-hand side of the control box. Pressure-lug connections on the terminal blocks are suitable for only for copper conductors.
The control box power section contains the following
components:
power terminal block
optional disconnect switch
compressor circuit breaker(s)
compressor contactor(s)
current sensor boards
control transformer
ground lug
neutral terminal (380-3-60 units only)
crankcase heater relay (30MPA units only)
•fuses CONTROL BOX, CONTROLS SECTION — The control
box controls section contains the following components:
main base board (MBB)
scrolling marquee display
optional energy management module
control-circuit breakers for 24-v circuits
control-circuit ON-OFF switch
unit Enable/Off/Remote contact switch
unit Alarm/Alert indicator light CONTROL BOX, FIELD CONTROL WIRING SEC-
TION — Inside this section is the low-voltage, field-wiring terminal strip (LVT). All low-voltage field-wiring connections are made to this terminal block. There are three knockouts provided for field wiring in this section. Connec­tions for condenser flow switch, chilled fluid pump interlock, condenser pump interlock, remote alarm output, condenser output, and dual chiller thermistor accessory are made at these locations. See Fig. 16 for specific location of connections.
The unit has the capability to control field-supplied devices. They are: alarm signal, condenser pump or condenser fan out­put, and chilled water pump output. The unit provide 24-v power with a minimum 5 va rating per output allowed.
UNBALANCED 3-PHASE SUPPLY VOLTAGE — Never
operate a compressor where a phase imbalance in the supply voltage is greater than 2%. Use the following formula to deter-
mine the percent voltage imbalance: % Voltage Imbalance =
100 x
max voltage deviation from average voltage
average voltage
14
7
/8-in. (22 mm)
Page 15
EXAMPLE: Supply voltage is 240-3-60.
AB = 243 v BC = 236 v AC = 238 v
Average Voltage =
243 + 236 + 238
3
= 239 v Determine maximum deviation from average voltage: (AB) 243 – 239 = 4 v (BC) 239 – 236 = 3 v
Table 3 — Electrical Data — 30MPA,MPW Units
UNIT SIZE
30MPA,MPW
015
020
030
040
045
ICF Maximum instantaneous current flow during starting. kcmil Thousand circular mils LRA Locked rotor amps. MCA Minimum circuit amps (for wire sizing). Complies with
MOCP — Maximum Overcurrent Protection NEC National Electrical Code (U.S.A.) Rec Fuse
*Supply Range — Units are suitable for use on electrical systems
where voltage supplied to the unit terminals is not below or above the listed range limits.
NOTES:
1. All units have one field power terminal block.
2. Maximum incoming wire size is as follows: For units with terminal block: 350 kcmil for unit sizes 030-045; 208/230-3-60 voltages. 2/0 for all other unit sizes; all voltages. For units with optional non-fused disconnect: 350 kcmil for unit sizes: 030-045; 208/230-3-60 voltages. 045; 380-3-60 voltage.
NEC, Section 430-24.
Recommended dual element fuse amps (150% of com-
pressor RLA). Size up to the next standard fuse size.
VOLTS
NAMEPLATE
(3 ph, 60 Hz)
208/230 187253
380 342 418 123 37.6 139.7 50 45 460 414 508 95 33.1 109.7 45 40 575 518 632 80 27.5 92.2 35 35
208/230 187253
380 342 418 145 53.4 168 .7 70 60 460 414 508 125 40.3 142.9 50 45 575 518 632 80 32.2 94.3 45 40
208/230 187253
380 342 418 196 76.5 230.0 110 90 460 414 508 179 60.5 205.9 8070 575 518 632 132 53.3 155.7 70 60
208/230 187253
380 342 418 139 87.4 192. 460 414 508 150 75.1 196.2 90 90 575 518 632 109 64.7 148.88070
208/230 187253
380 342 418 196 110.5 264.0 125 125 460 414 508 179 87.4 232.8 110 100 575 518 632 132 77.0 179.4 100 90
LEGEND
VOLTAGE* COMPRESSOR UNIT
Min Max
Quantity
2
2
2
3
3
(AC) 239 – 238 = 1 v Maximum deviation is 4 v.
Determine percent voltage imbalance: 4
% Voltage Imbalance = 100 x
239
=1.7%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local utility company immediately.
LRA (ea.)
195 66.4 224.5 90 80
239 80.6 274.8 110 90
340 125.6 395.8 175 150
300 166.7 402.6 200 200
340 181.4 451.6 225 200
3/0 for unit sizes: 015,020; 208/230-3-60 voltages. 020-040; 380-3-60 voltage. 030-045; 460-3-60 and 575-3-60 voltages. 2 AWG for unit sizes: 015; 380-3-60 voltage. 015-020; 460-3-60 and 575-3-60 voltages.
3. Additional control circuit power is not required.
4. Any field modification of factory wiring must be in compliance with all applicable codes. Field-installed power wires must be rated 75 C minimum.
5. Use copper conductors only.
6. Control circuit power supply is 24-v single phase. Control power is supplied by the factory-installed control transformer.
MCA ICF MOCP
8 110 100
Rec
Fuse
15
Page 16
Fig. 16 — Typical Low Voltage Control Wiring
NOTES:
1. Factory wiring is in accordance with UL 1995 standards. Field modifications or additions must be in
compliance with all applicable codes.
2. All units or modules have single point primary power connection. Main power must be supplied
from a field or factory supplied disconnect.
3. Wiring for main field supply must be rated 75 C. Use copper conductors only.
a. Incoming wire size range for terminal block with MCA up to 120 amps is 14 AWG (American
Wire Gage) to 2/0.
b. Incoming wire size range for terminal block with MCA from 120.1 amps to 310 amps is 6 AWG
to 350 kcmil.
c. Incoming wire size range for non-fused disconnect with MCA up to 50 amps is 10 AWG to
2 AWG.
d. Incoming wire size range for non-fused disconnect with MCA from 50.1 amps to 90 amps is 6
AWG to 3/0.
e. Incoming wire size range for non-fused disconnect with MCA from 90.1 amps to 250 amps is 4
AWG to 350 kcmil.
4. Refer to certified dimensional drawings for exact locations of the main power and control power
entrance locations.
5. Terminal 24 of the LVT is for controlof chilled water pump (CWP) starter. Terminal 20 of the LVT is
for control of condenser pump (CNP) starter or condenser fan relay (CFR). The maximum load
allowed for the relays is 5 VA sealed. 10 VA inrush at 24 VAC. Field power supply is required.
6. Terminal 25 of LVT is for an alarm relay. The maximum load allowed for alarm relay is 5 VA sealed,
10 VA inrush at 24 VAC. Field power supply is not required.
7. Make approprate connections to LVT as shown for energy management board options. The con-
tacts for demand limit and ice done options must be rated for dry circuit application capable of han-
dling 24 VAC load up to 50 mA. Installation of optional energy management board required.
8. Remove jumper between terminals 16 and 17 when field chilled water pump interlock (CWPI) is
installed.
9. Terminals 18 and 19 of LVT are for floating point control of condenser water valve (CWV). Teminal
18 commands valve closed. Terminal 19 commands valve open. The maximum load allowed for
condenser water valve is 5.5 VA at 24 VAC. Field power supply is not required.
10. All discrete inputs are 24 VAC.
LEGEND
ALMR — Alarm Relay (24 V) 5 VA Max
AWG — American Wire Gage
CFR — Condenser Fan Relay
CNFS — Condenser Flow Switch
CNP — Condenser Pump
CNPI — Condenser Pump Interlock
CWP — Chilled Water Pump
CWPI — Chilled Water Pump Interlock
CWV — Condenser Water Valve
EMM — Energy Management Module
LV T — Low Voltage Terminal Strip
NEC — National Electrical Code
OAT — Outside Air Temperature
SPT — Space Temperature
a30-5039
Copyright 2010 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300054-01 Printed in U.S.A. Form 30MP-1SI Pg 16 910 1-10 Replaces: New
Loading...