Carrier 25HPA530H0030010, 25HPA548H0030010, 25HPA560H0030010, 25HPA430A0030010, 25HPA436A0030010 Installation Guide

...
Installation Instructions
_rn to the Expertg
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or
other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or
your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or
accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes
and National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety-alert symbol ,/k When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand these signal words: DANGER. WARNING, and CAUTION. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor
personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation,
reliability, or operation.
INSTALLATION RECOMMENDATIONS
NOTE: In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where unit operation sound may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropri-
ate for unit capacity.
3. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
4. Leave some slack between structure and unit to absorb vi-
bration.
5. When passing refrigerant tubes through the wall, seal opening with RTV or other pliable silicon-based caulk. (See Fig. 1.)
6. Avoid direct tubing contact with water pipes, duct work,
floor joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which conms in direct contact
with tubing. (See Fig. 1.)
8. Ensure that tubing insulation is pliable and completely surrounds vapor tube.
9. When necessary, use hanger straps which are 1 in. (25.4 mm) wide and conform to shape of tubing insulation. (See
Fig. 1.)
10. Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation.
NOTE: Avoid contact belween tubing and struclure
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury
or death. Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
IMPORTANT: Maximum liquid-line size is 3/8-in. OD for all residential applications including long line.
IMPORTANT: Always install the factory-supplied liquid-line filter drier. Obtain replacement filter driers from your distributor
or branch.
THROUGH THE WALL
1' (254 mm)MIN_l I_
SUSPENSION
Fig. 1 - Connecting Tubing Installation
When outdoor unit is connected to factory-approved indoor unit. outdoor unit contains system refrigerant charge for operation with
ARI rated indoor unit when connected by 15 ft/4.57 m. of field-supplied or factory accessory tubing. For proper unit
operation, check refrigerant charge using charging information located on control box cover and/or in the Check Charge section
of this instruction.
LIQUID TUBE
A94028
INSTALLATION
Check Equipment and Job Site Unpack Unit
Move to final location. Remove carton taking care not to damage unit.
Inspect Equipment
File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating plate on unit corner panel. It contains information needed to properly install unit.
Check rating plate to be sure unit matches job specifications.
Install on a Solid, Level Mounting Pad
If conditions or local codes require tire unit be attached to pad, tiedown bolts should be used and fastened through knockouts
provided in unit base pan. Refer to unit mounting pattern in Fig. 2 to determine base pan size and knockout hole location.
For hurricane tie downs, contact distributor for details and PE Certification (Professional Engineer), if required.
On rooftop applications, mount on level platform or frame. Place unit above a load-bearing wall and isolate unit and tubing set from structure. Arrange supporting members to adequately
support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications.
Roof mounted units exposed to winds above 5 mph may require wind baffles. Consult the Service Manual - Residential Split
System Air Conditioners and Heat Pumps for wind baffle construction.
NOTE: Unit must be level to within _+2 ° (_+3/8 in./ft.) per compressor manufacturer specifications.
Clearance Requirements
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 30 in. (762 mm)
clearance to service end of unit and 48 in. (1219.2 mm) above unit. For proper airflow, a 6 in. (152.4 mm) clearance on 1 side of
unit and 12 in. (304.8 mm) on all remaining sides must be maintained. Maintain a distance of 24 in. (609.6 mm) between
units. Position so water, snow, or ice from roof or eaves cannot fall directly on unit.
3/8-1N DIA. TIEDOWN KNOCKOUTS tN BASEPAN (2) PLACES
Operating Ambient
The minimum outdoor operating ambient in cooling mode is 55°F/12.78°C without low ambient cooling enabled, and the
maximum outdoor operating ambient in cooling mode is 125°F/51.67°C. The maximum outdoor operating ambient in
heating mode is 66 °F/18.89°C.
Elevate Unit
UNIT OPERATION HAZARD Failure to follow this caution may result in equipment
damage or improper operation. Unit must be kept free of an accumulation of water and/or ice
in the basepan.
Elevate unit per local climate and code requirements to provide clearance above estimated snowfall level and ensure adequate
drainage of unit. If using accessory support feet. use installation instructions from kit for installation.
EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment
damage or improper operation. To prevent damage to the unit. ensure that it is located with
the supports such that the unit is stable in all circumstances including adverse conditions.
Make Piping Connections
PERSONAL INJURY / ENVIRONMENTAL HAZARD
Failure to fnllow this warning could result in personal injury
or death. Relieve pressure and recover all refrigerant before system
repair or final unit disposal.
Use all service ports and open all flow-control devices,
including solenoid valves.
B
FFtOM TOP
UNIT BASE PAN
DIMENSIONS
in. (mm)
29 1/2 X 33
(749.3 X 838.2)
36 1/2 X 4O
(927.1 X 1016)
TIEDO_ N KNOCKOUT LOCATIONS in.(ram)
z
A B C
10 1/16 5 5/8 23 3/4
(255.6) (142.9) (603.3)
9 5/8 6 13/16 28 3/4
(244.5) (173.0) (730.3)
A05177
Fig. 2 - Tiedown Knockout Requirements
On rooftop applications, locate unit at least 6 in. above roof surface.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
If ANY refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical rise at service valve. Refrigerant tubing lengths up to 36 in.(914.4 mm) may be buried without further
special consideration. Do not bury lines longer than 36 in. (914.4 mm).
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
To prevent damage to unit or service valves, observe the following:
Use a brazing shield.
Wrap service valves with wet cloth or use a heat sink material.
Outdoorunitsmaybeconnectedto indoorsectionusing accessorytubingpackageorfield-suppliedrefrigerantgrade
tubingofcorrectsizeandcondition.Fortubingrequirements beyond80ft/24.38m,substantialcapacityandperformance
lossescanoccur.FollowingtherecommendationsintheLong
Pumpswillreducetheselosses.RefertoTable1foraccessory requirements.RefertoTable2forfieldtubingdiameters.
Ifrefrigeranttubesorindoorcoilareexposedtoatmosphere,they mustbeevacuatedto500micronstoeliminatecontaminationand
moistureinthesystem.
LineGuidelineforSplit-SystemAir ConditionersandHeat
Table1--AccessoryUsage
ACCESSORY COOLING APPLICATIONS LONG LINE APPLICATIONS* SEA COAST APPLICATIONS
Accumulator Standard Standard Standard
Compressor Start Assist Yes Yes No
Capacitor and Relay
Crankcase Heater Yes Yes No
Evaporator Freeze Thermostat No No
Isolation Relay (for non-Infinity systems only) No No
Liquid Line Solenoid Valve No No
Motor Master@ Control or Yes
Low Ambient Switch (for non-Infinity systems only)
Support Feet Recommended No Recommended
For tubing line sets between 80 and 200 ft (24.38 and 60.96 m) and/or 20 ft (6.09 m) vertical differential, refer to Residential Split-System Long_ine Application Guideline
REQUIRED FOR LOW-AMBIENT REQUIRED FOR REQUIRED FOR
(Below 55°F / 12.8°C) (Over 80 ft. / 24,38 m) (Within 2 miles / 3.22 kin)
Yes
(for non-Infinity systems only)
Yes
See Long- Line Application
Guideline
No No
Table 2--Refrigerant Connections and Recommended Liquid and Va
UNIT SIZE
Connection Diameter
018, 024
030, 036 042, 048
060
Notes:
1 Tube diameters are for total equivalent lengths up to 80 ft (24.38 m) 2 Do not apply capillary tube or fixed orifice indoor coils to these uNts * For Tubing Set {engths between 80 and 200 ft (24.38 and 60.95 m) horizontal or 20 ft (610 m) vertical differential (250 ft./76.2 re)Total Equivalent Length),
refer to the Longline Guideline- Air Conditioners and Heat Pumps using Puron ® Refrigerant.
3/8 3/8
3/8 3/8
LIQUID
Tube Diameter
3/8 3/8
3/8 3/8
ISO 9001:2000
_or Tube Diameters (In.)
VAPOR
(up to 80 ft/24.38 m)
Connection Diameter Rated Tube Diameter
5/8 5/8
3/4 3/4
7/8 7/8
7/8 1 1/8
Pu ron
the_nvironmertaNysoundrefiigerant
IdealHumidi .
ARI 9_nd_rd _10/240
Unitary Nest P_mp_
@
Thinks. Heats. Saves.
Ready for use in a Hybrid Heat Duet Fuel system
®
This product has been designed and manufactured to meet Energy Star@ criteria for energy efficiency when
m_ched with appropriate coil components¸ However, proper refrigerant charge and proper air flow are critical
to achieve rated capacity and efficiency¸ Installation o1 this product should follow all manufactedn 9 refrigerant
charging and air flow instructions¸ Failure 1o confirm proper charge and air {few may reduce energy
efficiency and shorten equipment life,
Outdoor Unit Connected to Factory Approved Indoor Unit
These outdoor units are carefully evaluated and listed with specific indoor coils for proper system performance.
Install Adapter Tube
1. Remove plastic retainer holding outdoor piston in liquid service valve.
2. Check outdoor piston size with matching number listed on unit rating plate.
3. Locate plastic bag taped to unit containing adapter tube.
4. Remove Teflon <_seal from bag and install on open end of liquid service valve. (See Fig. 3.)
5. Remove adapter tube from bag and connect threaded nut to liquid service valve. Tighten nut finger-tight and then with wrench an additional 1/2 turn (15 ft-lb). DO NOT
OVER TIGHTEN!
TEFLON ® SEAL
PISTON
A05226
Fig. 3 - Liquid Service Valve with Sweat Adapter Tube
Refrigerant Tubing and Sweat Connections
Connect vapor tube to fitting on outdoor unit vapor service valves (see Table 2). Connect liquid tubing to adapter tube on
liquid service valve. Use refrigerant grade tubing.
UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment
damage or improper operation. Service valves must be wrapped in a heat-sinking
material such as a wet cloth while brazing.
UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment
damage or improper operation. Installation of filter drier in liquid line is required.
Install Liquid Line Filter Drier Indoor
Refer to Fig. 4 and install filter drier as follows:
1. Braze 5 in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to 5 in. (127 mm) long liquid tube from step 1.
4. Connect and braze liquid refrigerant tube to the filter drier.
A05227
Fig. 4 - Liquid Line Filter Drier
Leak Testing
Leak test all joints: indoors, outdoors, and refrigerant tubing.
Evacuate Refrigerant Tubing and Indoor Coil
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. An alternate
triple evacuation method may also be used. See Service Manual for Triple Evacuation Method.
IMPORTANT: Always break a vacuum with dry nitrogen.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of
accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air
and liquid water. (See Fig. 5. )
5OOO 4500 4000 3500
3000
e,,,,,
2500
2000
1500 1000
5OO
0 1 2 3 4 5 6
MINUTES
Fig. 5 - Deep Vacuum Graph
VACUUM TIGHT
TOO WET TIGHT
DRY SYSTEM
A95424
Loading...
+ 8 hidden pages