Carrier 50GTN, 60GTN, 70GTN, 80GTN, 90GTN Service And Troubleshooting Manual

...
Controls, Start-Up, Operation,
Service, and Troubleshooting
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be hazardous due to system pressures, electrical compo­nents, and equipment location (roof, elevated structures, etc.). Only trained, qualified installers and servicemechanicsshould install, start up, and service this equipment.
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation and service. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
This unit uses a microprocessor-based electronic con­trol system. Do not use jumpers or other tools to short out components, or to bypass or otherwise depart from recommended procedures. Any short-to-ground of the control board or accompanying wiring may destroy the electronic modules or electrical components.
To prevent potential damage to heat exchanger tubes al­ways run fluid through heat exchangers when adding or removing refrigerant charge. Use appropriate brine so­lutions in cooler and condenser fluid loops to prevent the freezing of heat exchangers when the equipment is exposed to temperatures below 32 F (0° C).
DO NOT VENT refrigerant relief valves within a build­ing. Outlet from relief valves must be vented outdoors in accordance with the latest edition of ANSI/ASHRAE (American National Standards Institute/American Soci­ety of Heating, Refrigeration and Air Conditioning En­gineers) 15 (Safety Code for Mechanical Refrigeration). The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation. Provide ad­equate ventilation in enclosed or low overhead areas. Inhalation of high concentrations of vapor is harmful and may cause heart irregularities, unconsciousness or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products are hazardous.
DO NOT attempt to unbraze factory joints when ser­vicing this equipment. Compressor oil is flammable and there is no way to detect how much oil may be in any of the refrigerant lines. Cut lines with a tubing cutter as required when performing service. Use a pan to catch any oil that may come out of the lines and as a gage for how much oil to add to system. DO NOT re-use com­pressor oil.
CONTENTS
Page
SAFETY CONSIDERATIONS ...................1
GENERAL ...................................2
INTRODUCTION ..............................2
MAJOR SYSTEM COMPONENTS ............3-10
General ......................................3
Main Base Board (MBB) ......................3
Expansion Valve (EXV) Board .................3
Compressor Expansion Board (CXB) ..........3
Scrolling Marquee Display ....................3
Energy Management Module (EMM) ...........3
Enable/Off/Remote Contact Switch ............3
Emergency On/Off Switch ....................3
Reset Button ................................3
Board Address ...............................3
Control Module Communication ..............3
Carrier Comfort Network Interface ............3
OPERATING DATA .........................11-46
Sensors ....................................11
• T1 — COOLER LEAVING FLUID SENSOR
• T2 — COOLER ENTERING FLUID SENSOR
• T3,T4 — SATURATED CONDENSING TEMPERATURE SENSORS
• T5,T6 — COOLER SUCTION TEMPERATURE SENSORS
• T7,T8 — COMPRESSOR SUCTION GAS TEMPERATURE SENSORS
• T9 — OUTDOOR-AIR TEMPERATURE SENSOR
• T10 — REMOTE SPACE TEMPERATURE SENSOR
Thermostatic Expansion Valves (TXV) ........15
Compressor Protection Control System
(CPCS) or Control Relay (CR) ..............15
Compressor Current Protection Board
(CGF) and Control Relay (CR) ..............15
Electronic Expansion Valve (EXV) ............16
Energy Management Module .................16
Capacity Control ............................16
• MINUTES LEFT FOR START
• MINUTES OFF TIME
• LOADING SEQUENCE
• LEAD/LAG DETERMINATION
• CAPACITY SEQUENCE DETERMINATION
• CAPACITY CONTROL OVERRIDES
30GTN,GTR040-420
Air-Cooled Reciprocating Liquid Chillers
with
ComfortLink™
Controls
50/60 Hz
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5c
PC 903 Catalog No. 533-099 Printed in U.S.A. Form 30GTN-1T Pg 1 5-99 Replaces: New
CONTENTS (cont)
Page
Head Pressure Control ......................27
• COMFORTLINK™ UNITS (With EXV)
• UNITS WITH TXV
Pumpout ...................................27
• EXV UNITS
• TXV UNITS
Marquee Display Usage .....................29
Service Test ................................29
Configuring and Operating Dual Chiller
Control ...................................29
Temperature Reset ..........................43
Demand Limit ...............................45
• DEMAND LIMIT (2-Stage Switch Controlled)
• EXTERNALLY POWERED DEMAND LIMIT
(4 to 20 mA Controlled)
• DEMAND LIMIT (CCN Loadshed Controlled)
TROUBLESHOOTING ......................46-51
Compressor Protection Control System
(CPCS) Board .............................46
Compressor Ground Current (CGC) Board
(30GTN,R130-210, 230A-315A, and
330A/B-420A/B) ...........................46
EXV Troubleshooting ........................46
• STEP 1 − CHECK PROCESSOR EXV OUTPUTS
• STEP 2 — CHECK EXV WIRING
• STEP 3 — CHECK RESISTANCE OF EXV MOTOR
WINDINGS
• STEP 4 — CHECK THERMISTORS THAT
CONTROL EXV
• STEP 5 — CHECK OPERATION OF THE EXV
Alarms and Alerts ...........................47
SERVICE ..................................52-64
Electronic Components .....................52
Compressors ...............................52
• COMPRESSOR REMOVAL
• OIL CHARGE
Cooler ......................................52
• COOLER REMOVAL
• REPLACING COOLER
• SERVICING THE COOLER
Condenser Coils ............................55
Condenser Fans ............................55
Refrigerant Feed Components ...............56
• ELECTRONIC EXPANSION VALVE (EXV)
• MOISTURE-LIQUID INDICATOR
• FILTER DRIER
• LIQUID LINE SOLENOID VALVE
• LIQUID LINE SERVICE VALVE
Thermistors ................................57
• LOCATION
• REPLACING THERMISTOR T2
• REPLACING THERMISTORS T1,T5,T6,T7, AND T8
• THERMISTORS T3 AND T4
• THERMISTOR/TEMPERATURE SENSOR CHECK
Safety Devices ..............................63
• COMPRESSOR PROTECTION
• LOW OIL PRESSURE PROTECTION
• CRANKCASE HEATERS
• COOLER PROTECTION
Relief Devices ..............................64
• HIGH-SIDE PROTECTION
• LOW-SIDE PROTECTION
• PRESSURE RELIEF VALVES
Other Safeties ..............................64
PRE-START-UP .............................64
System Check ..............................64
START-UP AND OPERATION ...............65,66
Actual Start-Up .............................65
Page
Operating Limitations .......................65
• TEMPERATURES
• VOLTAGE
• MINIMUM FLUID LOOP VOLUME
• FLOW RATE REQUIREMENTS
Operation Sequence ........................66
APPENDIX A — CCN TABLES ..............67-74
START-UP CHECKLIST ..............CL-1 to CL-8
GENERAL
Unit sizes 230-420 are modular units which are shipped as separate sections (modules A and B). Installation instruc­tions specific to these units are shipped inside the individual modules. See Table 1 for a listing of unit sizes and modular combinations. For modules 230B-315B, follow all general instructions as noted for unit sizes 080-110. For all remain­ing modules, follow instructions for unit sizes 130-210.
INTRODUCTION
This publication contains Start-Up, Service, Controls, Op­eration, andT roubleshootinginformation for the 30GTN,R040­420 liquid chillers with ComfortLink controls.
The 30GTN,R chillers are equipped with electronic ex­pansion valves (EXVs) or, on size 040-110 FIOP (factory­installed option) units, conventional thermostatic expansion valves (TXVs). The size 040-110 FIOP chillers are also equipped with liquid line solenoid valves (LLSV).
NOTE: TXVs are not available on modular units.
Differences in operations and controls between standard and 040-110 FIOP units are noted in appropriate sections in this publication. Refer to the Installation Instructions and the Wiring Diagrams for the appropriate unit for further details.
This unit uses a microprocessor-based electronic con­trol system. Do not use jumpers or other tools to short out or bypass components or otherwise depart from recommended procedures. Any short-to-ground of the control board or accompanying wiring may destroy the board or electrical component.
Table 1 — Unit Sizes and Modular Combinations
UNIT MODEL
30GTN,R
NOMINAL
TONS
SECTION A
UNIT 30GTN,R
SECTION B
UNIT 30GTN,R
40 40 45 45 50 50 60 60 70 70 80 80 90 90
100 100
110 110 130 125 150 145 170 160 190 180 210 200 230 220 150 080 245 230 150 090 255 240 150 100 270 260 170 100 290 280 190 110 315 300 210 110 330 325 170 170 360 350 190 190/170* 390 380 210 190 420 400 210 210
*60 Hz units/50 Hz units.
2
MAJOR SYSTEM COMPONENTS
General —
The 30GTN,R air-cooled reciprocating chill­ers contain the ComfortLink™ electronic control system that controls and monitors all operations of the chiller.
The control system is composed of several components as listed in the sections below. See Fig. 1 for typical control box drawing. See Fig. 2-4 for control schematics.
Main Base Board (MBB) — See Fig. 5. The MBB is
the heart of the ComfortLink control system. It contains the major portion of operating software and controls the opera­tion of the machine. The MBB continuously monitors input/ output channel information received from its inputs and from all other modules. The MBB receives inputs from ther­mistors T1-T6, T9, and T10. See Table 2. The MBB also receives the feedback inputs from compressors A1, A2, B1 and B2, and other status switches. See Table 3. The MBB also controls several outputs. Relay outputs controlled by the MBB are shown in Table 4. Information is transmitted be­tween modules via a 3-wire communication bus or LEN (Lo­cal Equipment Network). The CCN (Carrier Comfort Net­work) bus is also supported. Connections to both LEN and CCN buses are made at TB3. See Fig. 5.
Expansion Valve (EXV) Board — The electronic
expansion valve (EXV) board receives inputs from ther­mistors T7 and T8. See Table 2. The EXV board commu­nicates with the MBB and directly controls the expansion valves to maintain the correct compressor superheat.
CompressorExpansionBoard(CXB) — The com-
pressor expansion board (CXB) receives the feedback in­puts from compressorsA3,B3andA4. See Table3.The CXB board communicates the status to the MBB and controls the outputs for these compressors. The CXB board can also be used as an accessory to control up to two field-installed ac­cessory unloaders on 080-110, 130 (60 Hz), and 230B-315B sizes.
ScrollingMarquee Display — This device is the key-
pad interface used for accessing chiller information, reading sensor values, and testing the chiller.The marquee display is a 4-key, 4-character,16-segment LED (light-emitting diode) display. Eleven mode LEDs are located on the display as well as an Alarm Status LED. See Marquee Display Usage section on page 29 for further details.
Energy Management Module (EMM) — The EMM
module is available as a factory-installed option or as a field­installed accessory. The EMM module receives 4 to 20 mA inputs for the temperature reset, cooling set point reset and demand limit functions. The EMM module also receives the switch inputs for the field-installed 2-stage demand limit and ice done functions. The EMM module communicates the sta­tus of all inputs with the MBB, and the MBB adjusts the control point, capacity limit, and other functions according to the inputs received.
Enable/Off/RemoteContactSwitch — The Enable/
Off/Remote Contact switch is a 3-position switch used to control the chiller. When switched to the Enable position the chiller is under its own control. Move the switch to the Off position to shut the chiller down. Move the switch to the Remote Contact position and a field installed dry contact can be used to start the chiller. The contacts must be rated for dry circuit application capable of handlinga5vdc,1to 20 mA load. In the Enable and Remote Contact (dry con­tacts closed) positions, the chiller is allowed to operate and respond to the scheduling configuration, CCN configuration and set point data. See Fig. 6.
Emergency On/Off Switch — The Emergency On/
Off switch should only be used when it is required to shut the chiller offimmediately. Power to the MBB, EMM, CXB, and marquee display is interrupted when this switch is off and all outputs from these modules will be turned off. The EXV board is powered separately, but expansion valves will be closed as a result of the loss of communication with the MBB. There is no pumpout cycle when this switch is used. See Fig. 6.
Reset Button — A reset button is located on the fuse/
circuit breaker panel for unit sizes 130-210 and associated modules. The reset button must be pressed to reset either Circuit Ground Fault board in the event of a trip.
BoardAddresses— The Main Base Board (MBB) has
a 3-position Instance jumper that must be set to ‘1.’Allother boards have 4-position DIP switches. All switches are set to ‘On’ for all boards.
Control Module Communication
RED LED — Proper operation of the control boards can be visually checked by looking at the red status LEDs (light­emitting diodes).Whenoperatingcorrectly, the redstatusLEDs should be blinking in unison at a rate of once every 2 sec­onds. If the red LEDs are not blinking in unison, verify that correct power is being supplied to all modules. Be sure that the Main Base Board (MBB) is supplied with the current software. If necessary, reload current software. If the prob­lem still persists, replace the MBB. A board LED that is lit continuously or blinking at a rate of once per second or faster indicates that the board should be replaced.
GREEN LED — The MBB has one green LED. The Local Equipment Network (LEN) LED should always be blinking whenever power is on. All other boards have a LEN LED which should be blinking whenever power is on. Check LEN connections for potential communication errors at the board J3 and/or J4 connectors. Communication between modules is accomplished by a 3-wire sensor bus. These 3 wires run in parallel from module to module. The J4 connector on the MBB provides both power and communication directly to the marquee display only.
YELLOW LED — The MBB has one yellow LED. The Carrier Comfort Network (CCN) LED will blink during times of network communication.
Carrier Comfort Network (CCN) Interface — The
30GTN,R chiller units can be connected to the CCN if de­sired.Thecommunicationbuswiringis a shielded, 3-conductor cable with drain wire and is supplied and installed in the field. The system elements are connected to the communi­cation bus in a daisy chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system elements on either side of it. This is also required for the negative and signal ground pins of each system element. Wiring connections for CCN should be made atTB3.Consultthe CCN Contractor’sManual for further information.
NOTE: Conductors and drain wire must be 20 AWG (Amer­ican Wire Gage) minimum stranded, tinned copper. In­dividual conductors must be insulated with PVC, PVC/ nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating tem­perature range of −20 C to 60 C is required. Wire manu­factured byAlpha (2413 or 5463),American(A22503),Belden (8772), or Columbia (02525) meets the above mentioned requirements.
3
It is important when connecting to a CCN communication bus that a color coding scheme be used for the entire net­work to simplify the installation. It is recommended that red be used for the signal positive, black for the signal negative, and white for the signal ground. Use a similar scheme for cables containing different colored wires.
At each system element, the shields of its communication bus cables must be tied together. If the communication bus is entirely within one building, the resulting continuous shield must be connected to a ground at one point only. If the com­munication bus cable exits from one building and enters an­other, the shields must be connected to grounds at the light­ning suppressor in each building where the cable enters or exits the building (one point per building only). To connect the unit to the network:
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white
(ground), and black (−) conductors. (Substitute appropri­ate colors for different colored cables.)
3. Connect the red wire to (+) terminal on TB3 of the plug,
the white wire to COM terminal, and the black wire to the (−) terminal.
4. The RJ14 CCN connector on TB3 can also be used, but
is only intended for temporary connection (for example, a laptop computer running Service Tool).
IMPORTANT: A shorted CCN bus cable will prevent some routines from running and may prevent the unit from starting. If abnormal conditions occur, unplug the connector.If conditions return to normal, check the CCN connector and cable. Run new cable if necessary. A short in one section of the bus can cause problems with all system elements on the bus.
Table 2 — Thermistor Designations
THERMISTOR
NO.
PIN
CONNECTION
POINT
THERMISTOR INPUT
T1 J8-13,14 (MBB) Cooler Leaving Fluid T2 J8-11,12 (MBB) Cooler Entering Fluid
T3 J8-21,22 (MBB)
Saturated Condensing Temperature, Ckt A
T4 J8-15,16 (MBB)
Saturated Condensing Temperature, Ckt B
T5 J8-24,25 (MBB)
Cooler Suction Temperature, Ckt A (EXV Only)
T6 J8-18,19 (MBB)
Cooler Suction Temperature, Ckt B (EXV Only)
T7 J5-11,12 (EXV)
Compressor Suction Gas Temperature, Ckt A (EXV Only)
T8 J5-9,10 (EXV)
Compressor Suction Gas Temperature, Ckt B (EXV Only)
T9 J8-7,8 (MBB)
Outdoor-Air Temperature Sensor (Accessory)
T10 J8-5,6 (MBB)
Remote Space Temperature Sensor (Accessory)
LEGEND
EXV — Electronic Expansion Valve MBB — Main Base Board
Table 3 — Status Switches
STATUS SWITCH
PIN
CONNECTION
POINT
040-060 (50 Hz) 040-070 (60 Hz)
070
(50 Hz)
080, 230B
090-110,
245B-315B
130
(60 Hz)
130 (50 Hz)
150, 230A-255A
170,190,
270A,290A,330A/B,
360A/B, 390B
210, 315A,
390A, 420A/B
Oil Pressure, Ckt B J7-1, 2 (MBB) Not Used* OPSB OPSB OPSB OPSB OPSB OPSB Oil Pressure, Ckt A J7-3, 4 (MBB) Not Used* OPSA OPSA OPSA OPSA OPSA OPSA
Remote On/Off TB5-13, 14 Field-Installed Relay Closure
Compressor Fault
Signal, B3
J5-8, 12 (CXB) Not Used Not Used Not Used Not Used Not Used CR-B3 CR-B3
Compressor Fault
Signal, B2
J9-2, 12 (MBB) Not Used Not Used CPCS-B2 CR-B2 CR-B2 CR-B2 CR-B2
Compressor Fault
Signal, B1
J9-8, 12 (MBB) CR/CPCS-B1† CPCS-B1 CPCS-B1 CR-B1 CR-B1 CR-B1 CR-B1
Compressor Fault
Signal, A4
J5-5, 12 (CXB) Not Used Not Used Not Used Not Used Not Used Not Used CR-A4
Compressor Fault
Signal, A3
J5-11, 12 (CXB) Not Used Not Used Not Used Not Used CR-A3 CR-A3 CR-A3
Compressor Fault
Signal, A2
J9-5, 12 (MBB) Not Used CPCS-A2 CPCS-A2 CR-A2 CR-A2 CR-A2 CR-A2
Compressor Fault
Signal, A1
J9-11, 12 (MBB) CR/CPCS-A1† CPCS-A1 CPCS-A1 CR-A1 CR-A1 CR-A1 CR-A1
LEGEND
CPCS — Compressor Protection Control System CR Control Relay CXB Compressor Expansion Board MBB — Main Base Board OPS Oil Pressure Switch, Circuit A or B
*The OPS can also be added as an accessory.
†The CPCS can be added as an accessory.
4
Table 4 — Output Relay
RELAY NO. DESCRIPTION
K0 (MBB)
Energize Compressor A1 and OFM1 (040-110*) Energize Liquid Line Solenoid Valve for Ckt A (if used)
(040-110*)
Energize Compressor A1, OFM5, and OFM7 (130-210*)
K1 (MBB)
Energize Compressor B1 and OFM2 (040-110*) Energize Liquid Line Solenoid Valve for Ckt B (if used)
(040-110*)
Energize Compressor B1, OFM6, and OFM8 (130-210*)
K2 (MBB)
Energize Unloader A1 (040-170*) No Action (190-210*)
K3 (MBB)
Energize Unloader B1 (040-070†, 080-170*) No Action (190,210*)
K4 (MBB)
No Action (040-060, 50 Hz; 040-070, 60 Hz) Energize Compressor A2 (070, 50 Hz; 080-210*)
K5 (MBB)
No Action (040-080*) Energize Compressor B2 (090-210*)
K6 (MBB) Alarm K7 (MBB) Cooler Pump
K8 (MBB)
Energize First Stage of Condenser Fans:
040-050 — OFM3 060-110* — OFM3, OFM4 130 (60 Hz) — OFM1,OFM2
Energize First Stage of Ckt A Condenser Fans:
130 (50 Hz), 150,170* — OFM1 190,210* — OFM1,OFM11
K9 (MBB)
Energize First Stage of Condenser Fans:
040-050 — OFM4 060-090* — OFM5, OFM6 100,110* — OFM5,OFM6,OFM7,OFM8 130 (60 Hz) — OFM3,OFM4,OFM9,OFM10
Energize First Stage of Ckt B Condenser Fans:
130 (50 Hz), 150,170* — OFM2 190,210* — OFM2,OFM12
K10 (MBB) Hot Gas Bypass
K1 (CXB)
No Action (040-110*; 130, 60 Hz) Energize Compressor A3 (130, 50 Hz; 150-210*)
K2 (CXB)
No Action (040-150*) Energize Compressor B3 (170-210*)
K3 (CXB)
Energize Compressor A4 (210*) Energize Accessory Unloader A2 (080-110*)
K4 (CXB) Energize Accessory Unloader B2 (080-110*) K5 (CXB)
Energize Second Stage of Ckt A Condenser Fans:
130 (50 Hz), 150-210* — OFM3,OFM9
K6 (CXB)
Energize Second Stage of Ckt B Condenser Fans:
130 (50 Hz), 150-210* — OFM4,OFM10
LEGEND
OFM — Outdoor-Fan Motor
*And associated modular units.
†Field-installed accessory unloader.
LEGEND FOR FIG. 1-4
C—Compressor Contactor CB Circuit Breaker CCN Carrier Comfort Network CGF Compressor Ground Fault CHT Cooler Heater Thermostat CKT Circuit CLHR Cooler Heater Relay CPCS Compressor Protection and Control System CWF Chilled Water Flow Switch CWP Chilled Water Pump CR Control Relay CXB Compressor Expansion Board EQUIP GND — Equipment Ground FB Fuse Block FC Fan Contactor FCB Fan Circuit Breaker FIOP Factory-Installed Option Package EMM Energy Management Module EXV Electronic Expansion Valve FCB Fan Circuit Breaker HPS High-Pressure Switch LCS Loss-of-Charge Switch MBB Main Base Board NEC National Electrical Code OAT Outdoor-Air Temperature OPS Oil Pressure Switch PL Plug PW Part Wind SN Sensor (Toroid) SPT Space Temperature TRAN Transformer SW Switch TB Terminal Block TDR Time Delay Relay TXV Thermostatic Expansion Valve UL Unloader XL Across-the-Line
5
Fig.1—Typical Control Box (080-110 and Associated Modular Units Shown)
6
Fig.2—24VControl Schematic, Unit Sizes 040-070
7
Fig.3—24VControl Schematic, Unit Sizes 080-110, 230B-315B
8
Fig.4—24VControl Schematic, Unit Sizes 130-210, 230A-315A, 330A/B-420A/B
9
CEPL130346-01
STATUS
LEN
J1
J2
J4
J3
J5
J6
J7
J8
J9
J10
CCN
RED LED - STATUS GREEN LED -
LEN (LOCAL EQUIPMENT NETWORK)
YELLOW LED ­CCN (CARRIER COMFORT NETWORK)
Fig. 5 — Main Base Board
EMERGENCY ON/OFF SWITCH
ENABLE/OFF/REMOTE CONTACT SWITCH
RESET BUTTON (30GTN,R130-210 AND ASSOCIATED MODULES ONLY)
GFI-CONVENIENCE OUTLET ACCESSORY ON 208/230V 460 AND 575V ONLY
Fig. 6 — Enable/Off/Remote Contact Switch, Emergency On/Off Switch,
and Reset Button Locations
10
OPERATING DATA
Sensors —
The electronic control uses 4 to 10 ther­mistors to sense temperatures for controlling chiller opera­tion. See Table 2. These sensors are outlined below. See Fig.7-10forthermistor locations. Thermistors T1-T9 are 5kVat 25 C (77 F) and are identical in temperature versus resistance and voltage drop performance. Thermistor T10 is a10kVat 25 C (77 F) and has a different temperature vs resistance and voltage drop performance. See Thermistors section on page 55 for temperature-resistance-voltage drop characteristics.
T1 — COOLER LEAVING FLUID SENSOR — This ther­mistor is located in the leaving fluid nozzle. The thermistor probe is inserted into a friction-fit well. The sensor well is located directly in the refrigerant path.
T2 — COOLER ENTERING FLUID SENSOR — This ther­mistor is located in the cooler shell in the first baffle space in close proximity to the cooler tube bundle.
T3, T4 — SATURATED CONDENSING TEMPERATURE SENSORS — These 2 thermistors are clamped to the out­side of a return bend of the condenser coils.
T5, T6 — COOLER SUCTION TEMPERATURE SEN­SORS — These thermistors are located next to the refrig­erant inlet in the cooler head, and are inserted into a friction­fit well. The sensor well is located directly in the refrigerant path. These thermistors are not used on units with TXVs.
T7, T8 — COMPRESSOR SUCTION GAS TEMPERA­TURE SENSORS — These thermistors are located in the lead compressor in each circuit in a suction passage after the refrigerant has passed over the motor and is about to enter the cylinders. These thermistors are inserted into friction-fit wells. The sensor wells are located directly in the refrigerant path. These thermistors are not used on units with TXVs.
T9 — OUTDOOR-AIR TEMPERATURE SENSOR — Sen­sor T9 is an accessory sensor that is remotely mounted and used for outdoor-air temperature reset.
LEGEND EXV — Electronic Expansion Valve *And associated modular units.
Fig. 7 — Cooler Thermistor Locations
040-110*
130-210*
11
040-070
080-110AND ASSOCIATED MODULAR UNITS 130-210 AND ASSOCIATED MODULAR UNITS*
*When thermistor is viewed from perspective where the compressor is on the left and the cooler is on the right.
Fig. 8 — Thermistor T3 and T4 Locations
12
LEGEND
EXV — Electronic Expansion Valve
Fig. 9 — Compressor Thermistor Locations (T7 and T8)
Fig. 10 — Typical Thermistor Location (30GTN,R210, 315A, 390A, 420A/B Shown)
13
T10 — REMOTE SPACE TEMPERATURE SENSOR — Sensor T10 (part no. HH51BX006) is an accessory sensor that is remotely mounted in the controlled space and used for space temperature reset. The sensor should be installed as a wall-mounted thermostat would be (in the conditioned space where it will not be subjected to either a cooling or heating source or direct exposure to sunlight, and 4 to 5 ft above the floor). The push button override button is not sup­ported by the ComfortLink™ Controls.
Space temperature sensor wires are to be connected to ter­minals in the unit main control box. The space temperature sensor includes a terminal block (SEN) and a RJ11 female connector.TheRJ11 connector is used to tap into the Carrier Comfort Network (CCN) at the sensor.
To connect the space temperature sensor (Fig. 11):
1. Using a 20 AWG twisted pair conductor cable rated for
the application, connect 1 wire of the twisted pair to one SEN terminal and connect the other wire to the other SEN terminal located under the cover of the space temperature sensor.
2. Connect the other ends of the wires to terminals 5 and 6
on TB5 located in the unit control box.
Units on the CCN can be monitored from the space at the sensor through the RJ11 connector, if desired. To wire the RJ11 connector into the CCN (Fig. 12):
IMPORTANT: The cable selected for the RJ11 con­nector wiring MUST be identical to the CCN commu­nication bus wire used for the entire network. Refer to table below for acceptable wiring.
MANUFACTURER
PART NO.
Regular Wiring Plenum Wiring
Alpha 1895
American A21451 A48301
Belden 8205 884421
Columbia D6451
Manhattan M13402 M64430
Quabik 6130
1. Cut the CCN wire and strip ends of the red (+), white
(ground), and black (−) conductors. (If another wire color scheme is used, strip ends of appropriate wires.)
2. Insert and secure the red (+) wire to terminal 5 of the
space temperature sensor terminal block.
3. Insert and secure the white (ground) wire to terminal 4 of the space temperature sensor.
4. Insert and secure the black (−) wire to terminal 2 of the space temperature sensor.
5. Connect the other end of the communication bus cable to the remainder of the CCN communication bus.
SPT (T10) PART NO. HH51BX006
SENSOR
SEN
SEN
TB5
5
6
Fig. 11 — Typical Space Temperature
Sensor Wiring
T-55 SPACE SENSOR
CCN+
CCN GND
CCN-
TO CCN COMM 1 BUS (PLUG) AT UNIT
1
2
3
4
5
6
Fig. 12 — CCN Communications Bus Wiring
to Optional Space Sensor RJ11 Connector
14
Thermostatic Expansion Valves (TXV)
Model 30GTN,R040-110 units are available from the fac­tory with conventional TXVs with liquid line solenoids. The liquid line solenoid valves are not intended to be a mechani­cal shut-off.When service is required, use the liquid line serv­ice valve to pump down the system.
NOTE: This option is not available for modular units.
The TXV is set at the factory to maintain approximately 8 to 12° F (4.4 to 6.7° C) suction superheat leaving the cooler by monitoring the proper amount of refrigerantintothecooler. All TXVs are adjustable, but should not be adjusted unless absolutely necessary. When TXV is used, thermistors T5, T6, T7, and T8 are not required.
The TXV is designed to limit the cooler saturated suction temperature to 55 F (12.8 C). This makes it possible for unit to start at high cooler fluid temperatures without overload­ing the compressor.
Compressor Protection Control System (CPCS) or Control Relay (CR) —
Each compressor has its own CPCS module or CR. See Fig. 13 for CPCS module. The CPCS or CR is used to control and protect the compressors and crankcase heaters. The CPCS and CR provide the fol­lowing functions:
• compressor contactor control/crankcase heater
• crankcase heater control
• compressor ground current protection (CPCS only)
• status communication to processor board
• high-pressure protection
One large relay is located on the CPCS board. This relay controls the crankcase heater and compressor contactor, and also provides a set of signal contacts that the microprocessor monitors to determine the operating status of the compres­sor. If the processor board determines that the compressor is not operating properly through the signal contacts, it will lock the compressor off by deenergizing the proper 24-v control relay on the relay board. The CPCS board contains logic that can detect if the current-to-ground of any compressor wind­ing exceeds 2.5 amps. If this condition occurs, the CPCS shuts down the compressor.
Ahigh-pressureswitchiswiredinseriesbetweentheMBB and the CR or CPCS. On compressor A1 and B1 a loss-of­charge switch is also wired in series with the high-pressure switch. If the high-pressure switch opens during operation of a compressor, the compressor will be stopped, the failure
will be detected through the signal contacts, and the com­pressor will be locked off. If the lead compressor in either circuit is shut down by the high-pressure switch, loss-of­charge switch, ground current protector, or oil safety switch, all compressors in that circuit are shut down.
NOTE: The CR operates the same as the CPCS, except the ground current circuit protection is not provided.
Compressor Ground Current Protection Board (CGF) and Control Relay (CR) —
The 30GTN,R130­210, and associated modular units (see Table 1) contain one compressor ground current protection board (CGF) for each refrigeration circuit. The CGF contains logic that can detect if the current-to-ground of any compressor winding exceeds
2.5 amps. If this occurs, the lead compressor in that circuit is shut down along with other compressors in that circuit.
Ahigh-pressureswitchiswiredinseriesbetweentheMBB and the CR or CPCS. On compressor A1 and B1 a loss-of­charge switch is also included with the high-pressure switch. The lead compressor in each circuit also has the CGF con­tacts described above. If any of these switches open during operation of a compressor, the CR relay is deenergized, stop­ping the compressorandsignalingtheprocessorat the MBB-J9 inputs to lock out the compressor. If the lead compressor in either circuit is shut down by high-pressure switch, com­pressor ground fault, oil pressure switch, or the loss-of­charge switch, all compressors in that circuit are also shut down.
Fig. 13 — Compressor Protection Control
System Module
15
Electronic Expansion Valve(EXV) (See Fig. 14) — Standard units are equipped with a bottom seal EXV .This
device eliminates the use of the liquid line solenoid pump­down at unit shutdown.An O-ring has been added to bottom of orifice assembly to complete a seal in the valve on shut­down. This is not a mechanical shut-off. When service is re­quired, use the liquid line service valve to pump down the system.
High pressure refrigerant enters bottom of valve where it passes through a group of machined slots in side of orifice assembly.As refrigerant passes through the orifice, it drops in pressure. To control flow of refrigerant, the sleeve slides up and down along orifice assembly, modulating the size of orifice. The sleeve is moved by a linear stepper motor that moves in increments controlled directly by the processor.As stepper motor rotates,themotionistranslatedintolinear move­ment of lead screw. There are 1500 discrete steps with this combination. The valve orifice begins to be exposed at 320 steps. Since there is not a tight seal with the orifice and the sleeve, the minimum position for operation is 120 steps.
Two thermistors are used to determine suction superheat. One thermistor is located in the cooler and the other is lo­cated in the cylinder end of the compressor after refrigerant has passed over the motor. The difference between the 2 thermistors is the suction superheat. These machines are set up to provide approximately 5 to 7 F (2.8 to 3.9 C) super­heat leaving the cooler. Motor cooling accounts for approxi­mately 22 F (12.2 C), resulting in a superheat entering com­pressor cylindersofapproximately30F (16.7 C). This increases performance of cooler by reducing the amount of superheat needed.
Because the valves are controlled by the EXV module, it is possible to track the position of the valve. Valve position can be used to control head pressure and system refrigerant charge.
The EXV is used to limit the maximum cooler saturated suction temperature to 55 F (12.8 C). This makes it possible for the chiller to start at high cooler fluid temperatures with­out overloading the compressor.
Energy Management Module (Fig. 15) — This
factory-installed option or field-installed accessory is used for the following types of temperature reset, demand limit, and/or ice features:
• 4 to 20 mA leaving fluid temperature reset (requires field-
supplied 4 to 20 mA generator)
• 4 to 20 mA cooling set point reset (requires field-supplied
4 to 20 mA generator)
• Discrete inputs for 2-step demand limit (requires field-
supplied dry contacts capable of handlinga5vdc,1to 20 mA load)
• 4 to 20 mA demand limit (requires field-supplied 4 to 20
mA generator)
• Discrete input for Ice Done switch (requires field-supplied
dry contacts capable of handling a 5 vdc, 1 to 20 mAload)
See Demand Limit and Temperature Reset sections on pages 43 and 45 for further details.
Capacity Control — The control system cycles com-
pressors, unloaders, and hot gas bypass solenoids to main­tain the user-configured leaving chilled fluid temperature set point. Entering fluid temperature is used by the Main Base Board (MBB) to determine the temperature drop across the cooler and is used in determining the optimum time to add or subtract capacity stages. The chilled fluid temperature set point can be automatically reset by the return temperature
reset or space and outdoor-air temperature reset features. It can also be reset from an external 4 to 20 mA signal (re­quires Energy Management Module FIOP/accessory).
With the automatic lead-lag feature in the unit, the control determines randomly which circuit will start first, A or B. At the first call for cooling, the lead compressor crankcase heater will be deenergized, a condenser fan will start, and the com­pressor will start unloaded.
NOTE: The automatic lead-lag feature is only operative when an even number of unloaders is present. The 040-070 units require an accessory unloader for the lead-lag feature to be in effect.
If the circuit has been off for 15 minutes, and the unit is a TXV unit, liquid line solenoid will remain closed during start-up of each circuit for 15 seconds while the cooler and suction lines are purged of any liquid refrigerant. For units with EXVs, the lead compressor will be signaled to start. The EXV will remain at minimum position for 10 seconds before it is allowed to modulate.
After the purge period, the EXV will begin to meter the refrigerant, or the liquid line solenoid will open allowing the TXV to meter the refrigerant to the cooler. If the off-time is less than 15 minutes, the EXV will be opened as soon as the compressor starts.
The EXVswillopengradually to provide a controlledstart-up to prevent liquid flood-back to the compressor. During start­up, the oil pressure switch is bypassed for 2 minutes to al­low for the transient changes during start-up. As additional stages of compression are required, the processor control will add them. See Tables 5A and 5B.
If a circuit is to be stopped, the control will first start to close the EXV or close the liquid line solenoid valve.
For units with TXVs, the lag compressor(s) will be shut down and the lead compressor will continue to operate for 10 sec­onds to purge the cooler of any refrigerant.
For units with EXVs, the lag compressor(s) will be shut down and the lead compressor will continue to run. After the lag compressor(s) has shut down, the EXV is signaled to close. The lead compressor will remain on for 10 seconds after the EXV is closed.
During both algorithms (TXV and EXV), all diagnostic conditions will be honored. If a safety trip or alarm condi­tion is detected before pumpdown is complete, the circuit will be shut down.
Fig. 14 — Electronic Expansion Valve (EXV)
16
The capacity routine runs every 30 seconds. The routine attempts to maintain the Control Point at the desired set point. Each time it runs, the control reads the entering and leaving fluid temperatures. The control determines the rate at which conditions are changing and calculates 2 variables based on these conditions. Next, a capacity ratio is calculated using the 2variablestodeterminewhether or not to make any changes to the current stages of capacity.Thisratiovalueranges from
−100 to + 100%. If the next stage of capacity is a compres­sor, the control starts (stops) a compressor when the ratio reaches + 100% (−100%). If the next stage of capacity is an unloader,thecontroldeener gizes(energizes) an unloader when the ratio reaches + 60% (−60%). Unloaders are allowed to cycle faster than compressors, to minimize the number of starts and stops on each compressor. A delay of 90 seconds occurs after each capacity step change.
CEBD430351-0396-01C
TEST 1
CEPL130351-01
PWR
TEST 2
J1
J2
J4 J3
J5
J6
J7
LEN
STATUS
RED LED - STATUS
GREEN LED ­LEN (LOCAL EQUIPMENT NETWORK)
Fig. 15 — Energy Management Module
17
Table 5A — Part Load Data Percent Displacement, Standard Units
UNIT
30GTN,GTR
CONTROL
STEPS
LOADING SEQUENCE A LOADING SEQUENCE B %
Displacement
(Approx)
Compressors
%
Displacement
(Approx)
Compressors
040 (60 Hz)
1 25 A1* — 250A1 — — 3 75 A1*, B1 — 4 100 A1,B1
040 (50 Hz) 045 (60 Hz)
1 24 A1* — 247A1 — — 3 76 A1*,B1 — 4 100 A1,B1
045 (50 Hz) 050 (60 Hz)
1 31 A1* — 244A1 — — 3 87 A1*,B1 — 4 100 A1,B1
050 (50 Hz) 060 (60 Hz)
1 28 A1* — 242A1 — — 3 87 A1*,B1 — 4 100 A1,B1
060 (50 Hz) 070 (60 Hz)
1 33 A1* — 250A1 — — 3 83 A1*,B1 — 4 100 A1,B1
070 (50 Hz)
1 19 A1* — 227A1 — — 3 65 A1*,B1 — 4 73 A1,B1 — 5 92 A1*,A2,B1 — 6 100 A1,A2,B1
080, 230B (60 Hz)
1 22 A1* 30 B1* 234A1 44B1 3 52 A1*,B1* 52 A1*,B1* 4 67 A1*,B1 63 A1,B1* 5 78 A1,B1 78 A1,B1 6 89 A1*,A2,B1 85 A1,A2,B1* 7 100 A1,A2,B1 100 A1,A2,B1
080, 230B (50 Hz)
1 17 A1* 25 B1* 225A1 38B1 3 42 A1*,B1* 42 A1*,B1* 4 54 A1*,B1 50 A1, B1* 5 62 A1,B1 62 A1,B1 6 79 A1*,A2,B1* 79 A1*,A2,B1* 7 92 A1*,A2,B1 88 A1,A2,B1* 8 100 A1,A2,B1 100 A1,A2,B1
090, 245B (60 Hz)
1 18 A1* 18 B1* 227A1 27B1 3 35 A1*,B1* 35 A1*,B1* 4 44 A1*,B1 44 A1,B1 5 53 A1,B1 53 A1,B1 6 56 A1*,A2,B1* 62 A1*,B1*,B2 7 65 A1*,A2,B1 71 A1,B1*,B2 8 74 A1,A2,B1 80 A1,B1,B2
9 82 A1*,A2,B1*,B2 82 A1*,A2,B1*,B2 10 91 A1*,A2,B1,B2 91 A1,A2,B1*,B2 11 100 A1,A2,B1,B2 100 A1,A2,B1,B2
090, 245B (50 Hz)
1 14 A1* 14 B1*
221A1 21B1
3 29 A1*,B1* 29 A1*,B1*
4 36 A1*,B1 36 A1,B1*
5 43 A1,B1 43 A1,B1
6 61 A1*,A2,B1* 53 A1*,B1*,B2
7 68 A1*,A2,B1 60 A1,B1*,B2
8 75 A1,A2,B1 67 A1,B1,B2
9 86 A1*,A2,B1*,B2 86 A1*,A2,B1*,B2 10 93 A1*,A2,B1,B2 93 A1,A2,B1*,B2 11 100 A1,A2,B1,B2 100 A1,A2,B1,B2
100, 255B,
270B (60 Hz)
1 16 A1* 16 A1*
223A1 23A1
3 31 A1*,B1* 31 A1*,B1*
4 39 A1*,B1 39 A1*,B1
5 46 A1,B1 46 A1,B1
6 58 A1*,A2,B1* 58 A1*,A2,B1*
7 66 A1*,A2,B1 66 A1*,A2,B1
8 73 A1,A2,B1 73 A1,A2,B1
9 85 A1*,A2,B1*,B2 85 A1*,A2,B1*,B2 10 92 A1*,A2,B1,B2 92 A1*,A2,B1,B2 11 100 A1,A2,B1,B2 100 A1,A2,B1,B2
*Unloaded compressor. NOTE: These capacity control steps may vary due to lag compressor sequencing.
18
Table 5A — Part Load Data Percent Displacement, Standard Units (cont)
UNIT
30GTN,GTR
CONTROL
STEPS
LOADING SEQUENCE A LOADING SEQUENCE B
%
Displacement
(Approx)
Compressors
%
Displacement
(Approx)
Compressors
100, 255B,
270B (50 Hz)
1 13 A1* 13 B1* 220A1 20B1 3 26 A1*,B1* 26 A1*,B1* 4 33 A1,B1 33 A1,B1 5 40 A1,B1 40 A1,B1 6 57 A1*,A2,B1* 57 A1*,B1*,B2 7 63 A1*,A2,B1 63 A1,B1*,B2 8 70 A1,A2,B1 70 A1,B1,B2
9 87 A1*,A2,B1*,B2 87 A1*,A2,B1*,B2 10 93 A1*,A2,B1,B2 93 A1,A2,B1*,B2 11 100 A1,A2,B1,B2 100 A1,A2,B1,B2
110, 290B,
315B (60 Hz)
1 14 A1* 14 B1*
221A1 21B1
3 29 A1*,B1* 29 A1*,B1*
4 36 A1*,B1 36 A1,B1*
5 43 A1,B1 43 A1,B1
6 61 A1*,A2,B1* 53 A1*,B1*,B2
7 68 A1*,A2,B1 60 A1,B1*,B2
8 75 A1,A2,B1 67 A1,B1,B2
9 86 A1*,A2,B1*,B2 86 A1*,A2,B1*,B2 10 93 A1*,A2,B1,B2 93 A1,A2,B1*,B2 11 100 A1,A2,B1,B2 100 A1,A2,B1,B2
110, 290B,
315B (50 Hz)
1 17 A1* 17 B1*
225A1 25B1
3 33 A1*,B1* 33 A1*,B1*
4 42 A1*,B1 42 A1,B1*
5 50 A1,B1 50 A1,B1
6 58 A1*,A2,B1* 58 A1*,B1*,B2
7 67 A1*,A2,B1 67 A1,B1*,B2
8 75 A1,A2,B1 75 A1,B1,B2
9 83 A1*,A2,B1*,B2 83 A1*,A2,B1*,B2 10 92 A1*,A2,B1,B2 92 A1,A2,B1*,B2 11 100 A1,A2,B1,B2 100 A1,A2,B1,B2
130 (60 Hz)
1
2
3
4
5
6
7
8
9 10 11
14 21 28 35 42 58 64 71 87 93
100
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
14 21 28 35 42 58 64 71 87 93
100
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
130 (50 Hz)
1
2
3
4
5
6
7
8
9 10 11 12 13 14
10 14 26 35 39 44 53 57 69 78 82 87 96
100
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
16 25 26 31 39 51 56 64 69 74 82 87 91
100
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
150, 230A, 245A,
255A (60 Hz)
1
2
3
4
5
6
7
8
9 10 11 12 13 14
11 15 29 38 42 44 53 58 71 80 85 86 95
100
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
18 27 29 33 42 55 60 69 71 75 85 86 91
100
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
*Unloaded compressor. NOTE: These capacity control steps may vary due to lag compressor sequencing.
19
Table 5A — Part Load Data Percent Displacement, Standard Units (cont)
UNIT
30GTN,GTR
CONTROL
STEPS
LOADING SEQUENCE A LOADING SEQUENCE B
%
Displacement
(Approx)
Compressors
%
Displacement
(Approx)
Compressors
150, 230A, 245A,
255A (50 Hz)
1 2 3 4 5 6 7 8
9 10 11 12 13 14
13 20 26 33 40 46 53 60 66 73 80 86 93
100
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
13 20 26 33 40 46 53 60 66 73 80 86 93
100
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
170, 270A,
330A/B (60 Hz)
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17
11 17 23 28 33 39 45 50 56 61 67 73 78 83 89 95
100
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1*,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
11 17 23 28 33 39 45 50 56 61 67 73 78 83 89 95
100
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1*,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1*,A2,A3,B1*,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
170, 270A,
330A/B,360B (50 Hz)
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17
9 14 19 23 28 33 37 42 52 57 61 72 76 81 91 96
100
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1*,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
9 14 19 23 28 38 43 47 52 57 61 72 76 81 91 96
100
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1*,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1*,A2,A3,B1*,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
190, 290A, 360A/B,
390B (60 Hz)
1 2 3 4 5 6
13 25 41 56 78
100
A1
A1,B1
A1,A2,B1
A1,A2,B1,B2
A1,A2,A3,B1,B2
A1,A2,A3,B1,B2,B3
13 25 41 56 78
100
B1
A1,B1
A1,B1,B2
A1,A2,B1,B2
A1,A2,B1,B2,B3
A1,A2,A3,B1,B2,B3
190, 290A, 360A,
390B (50 Hz)
1 2 3 4 5 6
17 33 50 67 83
100
A1
A1,B1
A1,A2,B1
A1,A2,B1,B2
A1,A2,A3,B1,B2
A1,A2,A3,B1,B2,B3
17 33 50 67 83
100
B1
A1,B1
A1,B1,B2
A1,A2,B1,B2
A1,A2,B1,B2,B3
A1,A2,A3,B1,B2,B3
210, 315A, 390A,
420A/B (60 Hz)
1 2 3 4 5 6 7
11 25 36 56 67 86
100
A1
A1,B1
A1,A2,B1
A1,A2,B1,B2
A1,A2,A3,B1,B2
A1,A2,A3,B1,B2,B3
A1,A2,A3,A4,B1,B2,B3
14 25 44 56 75 86
100
B1
A1,B1
A1,B1,B2
A1,A2,B1,B2
A1,A2,B1,B2,B3
A1,A2,A3,B1,B2,B3
A1,A2,A3,A4,B1,B2,B3
210, 315A, 390A,
420A/B (50 Hz)
1 2 3 4 5 6 7
9 26 35 51 67 84
100
A1
A1,B1
A1,A2,B1
A1,A2,B1,B2
A1,A2,A3,B1,B2
A1,A2,A3,B1,B2,B3
A1,A2,A3,A4,B1,B2,B3
16 26 42 51 67 84
100
B1
A1,B1
A1,B1,B2
A1,A2,B1,B2
A1,A2,B1,B2,B3
A1,A2,A3,B1,B2,B3
A1,A2,A3,A4,B1,B2,B3
*Unloaded compressor. NOTE: These capacity control steps may vary due to lag compressor sequencing.
20
Table 5B — Part Load Data Percent Displacement, With Accessory Unloaders
UNIT
30GTN,GTR
CONTROL
STEPS
LOADING SEQUENCE A LOADING SEQUENCE B %
Displacement
(Approx)
Compressors
%
Displacement
(Approx)
Compressors
040 (60 Hz)
1 25 A1* 25 B1* 250A1 50B1 3 75 A1*,B1 75 A1,B1* 4 100 A1,B1 100 A1,B1
040 (50 Hz) 045 (60 Hz)
1 24 A1* 37 B1* 247A1 53B1 3 61 A1*,B1* 61 A1*,B1* 4 76 A1*,B1 84 A1,B1* 5 100 A1,B1 100 A1,B1
045 (50 Hz) 050 (60 Hz)
1 31 A1* 38 B1* 244A1 56B1 3 69 A1*,B1* 69 A1*,B1* 4 87 A1*,B1 82 A1,B1* 5 100 A1,B1 100 A1,B1
050 (50 Hz) 060 (60 Hz)
1 28 A1* 38 B1* 242A1 58B1 3 67 A1*,B1* 67 A1*,B1* 4 87 A1*,B1 80 A1,B1* 5 100 A1,B1 100 A1,B1
060 (50 Hz) 070 (60 Hz)
1 33 A1* 33 B1* 250A1 50B1 3 67 A1*,B1* 66 A1*,B1* 4 83 A1*,B1 83 A1,B1* 5 100 A1,B1 100 A1,B1
070 (50 Hz)
1 19 A1* 31 B1* 227A1 47B1 3 49 A1*,B1* 49 A1*,B1* 4 65 A1*,B1 57 A1,B1* 5 73 A1,B1 73 A1,B1 6 76 A1*,A2,B1* 76 A1*,A2,B1* 7 92 A1*,A2,B1 84 A1,A2,B1* 8 100 A1,A2,B1 100 A1,A2,B1
080, 230B (60 Hz)
1 11 A1† 15 B1† 2 22 A1* 30 B1* 334A1 44B1 4 41 A1†,B1* 48 A1,B1† 5 55 A1†,B1 63 A1,B1* 6 67 A1*,B1 78 A1,B1 7 78 A1,B1 85 A1,A2,B1* 8 89 A1*,A2,B1 100 A1,A2,B1 9 100 A1,A2,B1
080, 230B (50 Hz)
1 8 A1† 13 B1† 2 17 A1* 25 B1* 325A1 38B1 4 33 A1†,B1* 50 A1,B1* 5 46 A1†,B1 62 A1,B1 6 54 A1*,B1 67 A1*,A2,B1† 7 62 A1,B1 75 A1,A2,B1† 8 71 A1†,A2,B1* 88 A1,A2,B1*
9 84 A1†,A2,B1 100 A1,A2,B1 10 92 A1*,A2,B1 — 11 100 A1,A2,B1
090, 245B (60 Hz)
1 9 A1† 9 B1†
2 18 A1* 18 B1*
327A1 27B1
4 35 A1†,B1 35 A1,B1†
5 44 A1*,B1 44 A1,B1*
6 53 A1,B1 53 A1,B1
7 56 A1†,A2,B1 62 A1,B1†,B2
8 65 A1*,A2,B1 71 A1,B1*,B2
9 74 A1,A2,B1 80 A1,B1,B2 10 82 A1†,A2,B1,B2 82 A1,A2,B1†,B2 11 91 A1*,A2,B1,B2 91 A1,A2,B1*,B2 12 100 A1,A2,B1,B2 100 A1,A2,B1,B2
*Unloaded compressor. †Two unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
21
Table 5B — Part Load Data Percent Displacement, With Accessory Unloaders (cont)
UNIT
30GTN,GTR
CONTROL
STEPS
LOADING SEQUENCE A LOADING SEQUENCE B
%
Displacement
(Approx)
Compressors
%
Displacement
(Approx)
Compressors
090, 245B (50 Hz)
1 7 A1† 7 B1† 2 14 A1* 14 B1* 321A1 21B1 4 29 A1†,B1 29 A1,B1† 5 36 A1*,B1 36 A1,B1* 6 43 A1,B1 43 A1,B1 7 49 A1†,A2,B1† 46 A1*,B1†,B2 8 54 A1†,A2,B1* 53 A1,B1†,B2
9 61 A1†,A2,B1 60 A1,B1*,B2 10 68 A1*,A2,B1 67 A1,B1,B2 11 75 A1,A2,B1 72 A1†,A2,B1†,B2 12 79 A1†,A2,B1*,B2 79 A1*,A2,B1†,B2 13 86 A1†,A2,B1,B2 86 A1,A2,B1†,B2 14 93 A1*,A2,B1,B2 93 A1,A2,B1*,B2 15 100 A1,A2,B1,B2 100 A1,A2,B1,B2
100, 255B,
270B (60 Hz)
1 8 A1† 8 B1†
2 16 A1* 16 B1*
323A1 23B1
4 31 A1†,B1 31 A1,B1†
5 39 A1*,B1 39 A1,B1*
6 46 A1,B1 46 A1,B1
7 50 A1†,A2,B1* 50 A1*,B1†,B2
8 58 A1†,A2,B1 58 A1,B1†,B2
9 66 A1*,A2,B1 66 A1,B1*,B2 10 73 A1,A2,B1 73 A1,B1,B2 11 77 A1†,A2,B1*,B2 77 A1*,A2,B1†,B2 12 85 A1†,A2,B1,B2 85 A1,A2,B1†,B2 13 92 A1*,A2,B1,B2 92 A1,A2,B1*,B2 14 100 A1,A2,B1,B2 100 A1,A2,B1,B2
100, 255B,
270B (50 Hz)
1 7 A1† 7 B1†
2 13 A1* 13 B1*
320A1 20B1
4 26 A1†,B1 26 A1,B1†
5 33 A1*,B1 33 A1,B1*
6 40 A1,B1 40 A1,B1
7 43 A1†,A2,B1† 43 A1†,B1†,B2
8 50 A1†,A2,B1* 50 A1*,B1†,B2
9 57 A1†,A2,B1 57 A1,B1†,B2 10 63 A1*,A2,B1 63 A1,B1*,B2 11 70 A1,A2,B1 70 A1,B1,B2 12 74 A1†,A2,B1†,B2 74 A1†,A2,B1†,B2 13 80 A1†,A2,B1*,B2 80 A1*,A2,B1†,B2 14 89 A1†,A2,B1,B2 87 A1,A2,B1†,B2 15 93 A1*,A2,B1,B2 93 A1,A2,B1*,B2 16 100 A1,A2,B1,B2 100 A1,A2,B1,B2
110, 290B,
315B (60 Hz)
1 7 A1† 7 B1†
2 14 A1* 14 B1*
321A1 21B1
4 29 A1†,B1 29 A1,B1†
5 36 A1*,B1 36 A1,B1*
6 43 A1,B1 43 A1,B1
7 47 A1†,A2,B1† 46 A1*,B1†,B2
8 54 A1†,A2,B1* 53 A1,B1†,B2
9 61 A1†,A2,B1 60 A1,B1*,B2 10 68 A1*,A2,B1 67 A1,B1,B2 11 75 A1,A2,B1 72 A1†,A2,B1†,B2 12 79 A1†,A2,B1*,B2 79 A1*,A2,B1†,B2 13 86 A1†,A2,B1,B2 86 A1,A2,B1†,B2 14 93 A1*,A2,B1,B2 93 A1,A2,B1*,B2 15 100 A1,A2,B1,B2 100 A1,A2,B1,B2
110, 290B,
315B (50 Hz)
1 8 A1† 8 B1†
2 17 A1* 17 B1*
325A1 25B1
4 33 A1†,B1 33 A1,B1†
5 42 A1*,B1 42 A1,B1*
6 50 A1,B1 50 A1,B1
7 58 A1†,A2,B1 58 A1,B1†,B2
8 67 A1*,A2,B1 67 A1,B1*,B2
9 75 A1,A2,B1 75 A1,B1,B2 10 83 A1†,A2,B1,B2 83 A1,A2,B1†,B2 11 92 A1*,A2,B1,B2 92 A1,A2,B1*,B2 12 100 A1,A2,B1,B2 100 A1,A2,B1,B2
*Unloaded compressor.
†Two unloaders, both unloaded. NOTE: These capacity control steps may vary due to lag compressor sequencing.
22
Table 5B — Part Load Data Percent Displacement, with Accessory Unloaders (cont)
UNIT
30GTN,GTR
CONTROL
STEPS
LOADING SEQUENCE A LOADING SEQUENCE B
%
Displacement
(Approx)
Compressors
%
Displacement
(Approx)
Compressors
130 (60 Hz)
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17
8 14 21 22 28 35 42 44 51 58 64 71 73 80 87 93
100
A1†
A1*
A1
A1†,B1*
A1†,B1 A1*,B1
A1,B1
A1†,A2,B1†
A1†,A2,B1*
A1†,A2,B1
A1,A2,B1
A1,A2,B1 A1†,A2,B1†,B2 A1†,A2,B1*,B2
A1†,A2,B1,B2 A1*,A2,B1,B2
A1,A2,B1,B2
8 14 21 22 28 35 42 44 51 58 64 71 73 80 87 93
100
B1†
B1*
B1
A1*,B1†
A1,B1†
A1,B1*
A1,B1 A1†,B1†,B2 A1*,B1†,B2
A1,B1†,B2
A1,B1*,B2
A1,B1,B2
A1†,A2,B1†,B2
A1*,A2,B1†,B2
A1,A2,B1†,B2
A1,A2,B1*,B2
A1,A2,B1,B2
130 (50 Hz)
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19
6 10 14 22 31 35 39 40 49 53 57 65 74 78 82 83 91 96
100
A1†
A1*
A1
A1†,B1*
A1†,B1 A1*,B1
A1,B1
A1†,A2,B1*
A1†,A2,B1
A1*,A2,B1
A1,A2,B1
A1†,A2,B1*,B2
A1†,A2,B1,B2 A1*,A2,B1,B2
A1,A2,B1,B2
A1†,A2,A3,B1*,B2
A1†,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
8 16 25 31 39 43 47 56 64 65 74 82 83 91
100
— — — —
B1†
B1*
B1
A1,B1*
A1,B1
A1*,B1†,B2
A1,B1†,B2
A1,B1*,B2
A1,B1,B2
A1,A2,B1†,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1,A2,A3,B1†,B2
A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
— — — —
150, 230A, 245A,
255A (60 Hz)
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17
6 11 15 24 33 38 42 49 53 58 66 75 80 85 91 95
100
A1†
A1*
A1
A1†,B1*
A1†,B1 A1*,B1
A1,B1
A1†,A2,B1
A1*,A2,B1
A1,A2,B1
A1†,A2,B1*,B2
A1†,A2,B1,B2 A1*,A2,B1,B2
A1,A2,B1,B2
A1†,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
9 18 27 33 42 46 51 60 69 75 86 91
100
— — — —
B1†
B1*
B1
A1,B1*
A1,B1
A1*,B1†,B2
A1,B1†,B2
A1,B1*,B2
A1,B1,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
— — — —
150, 230A, 245A,
255A (50 Hz)
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
6 13 20 26 33 40 46 53 60 66 73 80 86 93
100
A1†
A1
*A1 A1†,B1 A1*,B1
A1,B1 A1†,A2,B1 A1*,A2,B1
A1,A2,B1 A1†,A2,B1,B2 A1*,A2,B1,B2
A1,A2,B1,B2
A1†,A2,A3,B1,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
6 13 20 26 33 40 46 53 60 66 73 80 86 93
100
B1† B1*
B1 A1,B1† A1,B1*
A1,B1
A1,B1†,B2
A1,B1*,B2
A1,B1,B2 A1,A2,B1†,B2 A1,A2,B1*,B2
A1,A2,B1,B2 A1,A2,A3,B1†,B2 A1,A2,A3,B1*,B2
A1,A2,A3,B1,B2
*Unloaded compressor.
†Two unloaders, both unloaded. NOTE: These capacity control steps may vary due to lag compressor sequencing.
23
Table 5B — Part Load Data Percent Displacement, With Accessory Unloaders (cont)
UNIT
30GTN,GTR
CONTROL
STEPS
LOADING SEQUENCE A LOADING SEQUENCE B
%
Displacement
(Approx)
Compressors
%
Displacement
(Approx)
Compressors
170, 270A,
330A/B (60 Hz)
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
6 11 17 17 23 28 33 34 39 45 50 51 56 61 67 67 73 78 83 84 89 95
100
A1† A1*
A1
A1†,B1*
A1†,B1 A1*,B1
A1,B1
A1†,A2,B1*
A1†,A2,B1 A1*,A2,B1
A1,A2,B1
A1†,A2,B1*,B2
A1†,A2,B1,B2 A1*,A2,B1,B2
A1,A2,B1,B2
A1†,A2,A3,B1*,B2
A1†,A2,A3,B1,B2 A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1†,A2,A3,B1*,B2,B3
A1†,A2,A3,B1,B2,B3 A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
6 11 17 17 23 28 33 34 39 45 50 51 56 61 67 67 73 78 83 84 89 95
100
B1†
B1*
B1
A1*,B1†
A1,B1†
A1,B1*
A1,B1
A1*,B1†,B2
A1,B1†,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1†,B2
A1,A2,B1†,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1†,B2,B3
A1,A2,B1†,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1*,A2,A3,B1†,B2,B3
A1,A2,A3,B1†,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
170, 270A,
330A/B, 360B (50 Hz)
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
5
9 14 14 19 23 28 28 33 37 42 43 48 52 57 61 63 67 72 76 81 82 87 91 96
100
A1† A1*
A1
A1†,B1*
A1†,B1
A1*,B1
A1,B1
A1†,A2,B1*
A1†,A2,B1 A1*,A2,B1
A1,A2,B1
A1†,A2,B1†,B2
A1†,A2,B1*,B2
A1†,A2,B1,B2 A1*,A2,B1,B2
A1,A2,B1,B2
A1†,A2,A3,B1†,B2
A1†,A2,A3,B1*,B2
A1†,A2,A3,B1,B2 A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1†,A2,A3,B1†,B2,B3
A1†,A2,A3,B1*,B2,B3
A1†,A2,A3,B1,B2,B3 A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
5
9 14 14 19 23 28 29 34 38 43 47 48 52 57 61 63 67 72 76 81 82 87 91 96
100
B1†
B1*
B1
A1*,B1†
A1,B1†
A1,B1*
A1,B1 A1†,B1†,B2 A1*,B1†,B2
A1,B1†,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1†,B2
A1,A2,B1†,B2
A1,A2,B1*,B2
A1,A2,B1,B2 A1†,A2,B1†,B2,B3 A1*,A2,B1†,B2,B3
A1,A2,B1†,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3 A1†,A2,A3,B1†,B2,B3 A1*,A2,A3,B1†,B2,B3
A1,A2,A3,B1†,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B3,B3
190, 290A, 360A/B,
390B (60 Hz)
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17
9 13 18 21 25 33 37 41 49 53 56 71 74 78 93 96
100
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1*,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
9 13 18 21 25 33 37 41 49 53 56 71 74 78 93 96
100
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1*,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1*,A2,A3,B1*,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
*Unloaded compressor.
†Two unloaders, both unloaded. NOTE: These capacity control steps may vary due to lag compressor sequencing.
24
Table 5B — Part Load Data Percent Displacement, With Accessory Unloaders (cont)
UNIT
30GTN,GTR
CONTROL
STEPS
LOADING SEQUENCE A LOADING SEQUENCE B
%
Displacement
(Approx)
Compressors
%
Displacement
(Approx)
Compressors
190, 290A, 360A,
390B (50 Hz)
1 2 3 4 5 6 7 8 9
10
11 12 13 14 15 16 17
11 17 22 28 33 39 44 50 55 61 67 72 78 83 89 94
100
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1*,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
11 17 22 28 33 39 44 50 55 61 67 72 78 83 89 94
100
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1*,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1*,A2,A3,B1*,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
210, 315A, 390A,
420A/B (60 Hz)
1 2 3 4 5 6 7 8 9
10
11 12 13 14 15 16 17 18 19 20
8 11 17 22 25 28 33 36 48 52 56 59 63 67 78 83 86 92 97
100
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1*,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
A1*,A2,A3,A4,B1*,B2,B3
A1*,A2,A3,A4,B1,B2,B3
A1,A2,A3,A4,B1,B2,B3
9 14 17 21 25 37 40 44 48 51 56 67 71 75 78 82 86 92 96
100
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1*,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1*,A2,A3,B1*,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
A1*,A2,A3,A4,B1*,B2,B3
A1,A2,A3,A4,B1*,B2,B3
A1,A2,A3,A4,B1,B2,B3
210, 315A, 390A,
420A/B (50 Hz)
1 2 3 4 5 6 7 8 9
10
11 12 13 14 15 16 17 18 19 20
7
9 17 23 26 27 32 35 43 48 51 59 65 67 75 81 84 92 97
100
A1*
A1
A1*,B1*
A1*,B1
A1,B1
A1*,A2,B1*
A1*,A2,B1
A1,A2,B1
A1*,A2,B1*,B2
A1*,A2,B1,B2
A1,A2,B1,B2
A1*,A2,A3,B1*,B2
A1*,A2,A3,B1,B2
A1,A2,A3,B1,B2
A1*,A2,A3,B1*,B2,B3
A1*,A2,A3,B1,B2,B3
A1,A2,A3,B1,B2,B3
A1*,A2,A3,A4,B1*,B2,B3
A1*,A2,A3,A4,B1,B2,B3
A1,A2,A3,A4,B1,B2,B3
11 16 17 20 26 34 36 42 43 46 51 59 62 67 75 78 84 92 94
100
B1*
B1
A1*,B1*
A1,B1*
A1,B1
A1*,B1*,B2
A1,B1*,B2
A1,B1,B2
A1*,A2,B1*,B2
A1,A2,B1*,B2
A1,A2,B1,B2
A1*,A2,B1*,B2,B3
A1,A2,B1*,B2,B3
A1,A2,B1,B2,B3
A1*,A2,A3,B1*,B2,B3
A1,A2,A3,B1*,B2,B3
A1,A2,A3,B1,B2,B3
A1*,A2,A3,A4,B1*,B2,B3
A1,A2,A3,A4,B1*,B2,B3
A1,A2,A3,A4,B1,B2,B3
*Unloaded compressor.
†Two unloaders, both unloaded. NOTE: These capacity control steps may vary due to lag compressor sequencing.
25
MINUTES LEFT FOR START — This value is displayed only in the network display tables (i.e., Service Tool, Comfortworkst) and represents the amount of time to elapse before the unit will start its initialization routine. This value can be zero without the machine running in many situations. This can include being unoccupied,ENABLE/OFF/REMOTE CONTACT switch in the OFF position, CCN not allowing unit to start, Demand Limit in effect, no call for cooling due to no load, and alarm or alert conditions present. If the ma­chine should be running and none of the above are true, a minimum off time (DELY, see below) may be in effect. The machine should start normally once the time limit has expired.
MINUTES OFF TIME (DELY, Configuration Mode under OPT2) — This user configurable time period is used by the control to determine how long unit operation is delayed after power is applied/restored to the unit. It is also used to delay compressor restarts after the unit has shut offitsloweststage of capacity. Typically, this time period is configured when multiple machines are located on a single site. For example, this gives the user the ability to prevent all the units from restarting at once after a power failure. A value of zero for this variable does not mean that the unit should be running.
LOADING SEQUENCE — The 30GTN,R compressor ef­ficiency is greatest at partial load. Therefore, the following sequence list applies to capacity control.
1. The next compressor will be started with unloaders en­ergized on both lead compressors.
2. All valid capacity combinations using unloaders will be used as long as the total capacity is increasing.
LEAD/LAG DETERMINATION (LLCS, Configuration Mode under OPT2) — This is a configurable choice and is factory set to be automatic (for sizes 080-420) or Circuit A leading (for 040-070sizes).For040-070sizes, the value can be changed to Automatic or Circuit B only if an accessory unloader is added to compressor B1. For 080-420 sizes, the value can be changed to Circuit A or Circuit B leading, as desired. Set at automatic, the control will sum the current number of logged circuit starts and one-quarter of the current operating hours for each circuit. The circuit with the lowest sum is started first. Changes to which circuit is the lead circuit and which is the lag are also made when total machine capacity is at 100% or when there is a change in the direction of capacity (increase or decrease) and each circuit’s capacity is equal.
CAPACITY SEQUENCE DETERMINATION (LOAD, Con­figuration Mode under OPT2) —Thisisconfigurableasequal circuit loading or staged circuit loading with the default set at equal. The control determines the order in which the steps of capacity for each circuit are changed. This control choice does NOT have any impact on machines with only 2 compressors.
CAPACITY CONTROLOVERRIDES—The following over­rides will modify the normal operation of the routine.
Deadband Multiplier — Theuserconfigurable Deadband Mul­tiplier (Z.GN, Configuration Mode under SLCT) has a de­fault value of 1.0. The range is from 1.0 to 4.0. When set to other than 1.0, this factor is applied to the capacity Load/ Unload Factor. The larger this value is set, the longer the control will delay between adding or removing stages of
capacity. Figure 16 shows how compressor starts can be re­duced over time if the leaving water temperature is allowed to drift a larger amount above and below the set point. This value should be set in the range of 3.0 to 4.0 for systems with small loop volumes.
First Stage Override — If the current capacity stage is zero, the control will modify the routine with a 1.2 factor on add­ing the first stage to reduce cycling. This factor is also ap­plied when the control is attempting to remove the last stage of capacity.
Slow Change Override — The control prevents the capacity stages from being changed when the leaving fluid tempera­ture is close to the set point (within an adjustable deadband) and moving towards the set point.
Ramp Loading (CRMP, Configuration Mode under SLCT) — Limits the rate of change of leaving fluid temperature. If the unit is in a Cooling mode and configured for Ramp Load­ing, the controlmakes2comparisonsbefore deciding to change stages of capacity. The control calculates a temperature dif­ference between the control point and leaving fluid tempera­ture. If the difference is greater than 4° F (2.2° C) and the rate of change (°F or °C per minute) is more than the con­figured Cooling Ramp Loading value (CRMP), the control does not allow any changes to the current stage of capacity.
Low Entering Fluid Temperature Unloading — When the entering fluid temperature is below the control point, the con­trol will attempt to remove 25% of the current stages being used. If exactly 25% cannot be removed, the control re­moves an amount greater than 25%, but no more than nec­essary. The lowest stage will not be removed.
Low Cooler Suction Temperature — To avoid freezing the cooler, the control will compare the circuit Cooler Suction temperature (T5/T6) with a predetermined freeze point. For water circuits, the freeze point is 34 F (1.1 C). For brine circuits, the freeze point is 8° F (4.4° C) below the cooling set point (lower of 2 cooling set points for dual configura­tion). If the cooler suction temperature is below the freeze point, the unit capacity may not be allowed to increase. If the Cooler Suction temperature falls 24 to 29° F (13.3 to
16.1° C) below the freeze point minus 2.0 F (1.1 C) for 5 minutes, Mode 7 (Circuit A) or Mode 8 (Circuit B) is ini­tiated and no additional lag compressor stages will be added. If the Cooler Suction temperature falls 30° F (16.7° C) or more below the freeze point minus 2.0 F (1.1 C) for 10 min­utes, the circuit will shut down.
Cooler Freeze Protection — The control will try to prevent shutting the chiller down on a Cooler Freeze Protection alarm by removing stages of capacity. The control uses the same freeze point logic as described in the Low Cooler Suction Temperature section above. If the cooler leaving fluid tem­perature is less than the freeze point plus 2.0 F (1.1 C), the control will immediately remove one stage of capacity. This can be repeated once every 30 seconds.
MOP (Maximum Operating Pressure) Override — The control monitors saturated condensing and suction tempera­ture for each circuit. Based on a maximum operating set point (saturated suction temperature), the control may lower the EXV position when system pressures approach the set parameters.
26
Head Pressure Control
COMFORTLINK™UNITS (With EXV) — The Main Base Board (MBB) controls the condenser fans to maintain the lowest condensing temperature possible, and thus the high­est unit efficiency. The fans are controlled by the saturated condensing temperature set from the factory. The fans can also be controlled by a combination of the saturated con­densing temperature, EXV position and compressor super­heat. Fan control is a configurable decision and is determined by the Head Pressure Control Method (HPCM) setting in the Configuration Mode under the OPT1 sub-mode. For EXV control (HPCM = 2), when the position of the EXV is fully open, T3 and T4 are less than 78 F (25.6 C), and superheat is greater than 40 F (22.2 C), fan stages will be removed. When the valve is less than 40% open, or T3 and T4 are greater than 113 F (45 C), fan stages will be added. At each change of the fan stage, the system will wait one minute to allow the head pressure to stabilize unless either T3 or T4 is greater than 125 F (51.6 C), in which case all MBB-controlled fans will start immediately. This method allows the unit to run at very low condensing temperatures at part load.
During the first 10 minutes after circuit start-up, MBB­controlled fans are not turned on until T3 and T4 are greater than the head pressure set point plus 10 F (5.6 C). If T3 and T4 are greater than 95 F (35 C) just prior to circuit start-up, all MBB-controlled fan stages are turned on to prevent ex­cessive discharge pressure during pull-down. Fan sequences are shown in Fig. 17.
UNITS WITH TXV — The logic to cycle MBB-controlled fans is based on saturated condensing temperature only, as sensed by thermistors T3 and T4 (see Fig. 8 and 10). When either T3 or T4 exceeds the head pressure set point, the MBB will turn on an additional stage of fans. For the first 10 min­utes of each circuit operation, the head pressure set point is raised by 10° F (5.6° C). It will turn off a fan stage when T3 and T4 are both below the head pressure set point by 35° F (19.4° C). At each change of a fan stage the control will wait for one minute for head pressure to stabilize unless T3 and
T4 is greater than 125 F (51.6 C), in which case all MBB­controlled fans start immediately. If T3 and T4 are greater than 95 F (35.0 C) just prior to circuit start-up, all MBB­controlled fan stages are turned on to prevent excessive dis­charge pressure during pull-down. Fan sequences are shown in Fig. 17.
Motormastert Option — For low-ambient operation, the lead fan(s) in each circuit can be equipped with the Motor­master III head pressure controller option or accessory. Wind baffles and brackets must be field-fabricated for all units us­ing accessory Motormaster III controls to ensure proper cool­ing cycle operation at low-ambient temperatures. The fans controlled are those that are energized with the lead com­pressor in each circuit. All sizes use one controller per cir­cuit. Refer to Fig. 17 for condenser fan staging information.
Pumpout
EXV UNITS — When the lead compressor in each circuit is started or stopped, that circuit goes through a pumpout cycle to purge the cooler and refrigerant suction lines of refrigerant. If a circuit is starting within 15 minutes of the last shutdown, the pumpout cycle will be skipped.
The pumpout cycle starts immediately upon starting the lead compressor and keeps the EXV at minimum position for 10 seconds. The EXV is then opened an additional per­centage and compressor superheatcontrolbegins.At this point, the EXV opens gradually to provide a controlled start-up to prevent liquid flood-back to the compressor.
At shutdown, the pumpout cycle continuously closes the EXV until all lag compressors are off and the EXV is at 0%. The lead compressor continues to run for an additional 10 seconds and is then shut off.
TXV UNITS — Pumpout is based on timed pumpout. On a command for start-up, the lead compressor starts. After 15 seconds, the liquid line solenoid opens. At shutdown, the liquid line solenoid closes when the lead compressor has stopped.
47 46 45 44
43 42 41
0 200 400 600 800 1000
TIME (SECONDS)
2 STARTS
3 STARTS
DEADBAND EXAMPLE
LWT (F)
MODIFIED DEADBAND
STANDARD DEADBAND
8
7
6
5
LWT (C)
LEGEND
LWT — Leaving Water
Temperature
Fig. 16 — Deadband Multiplier
27
FAN ARRANGEMENT
FAN
NO.
FAN RELAY NORMAL CONTROL
30GTN,R040-050
1 Compressor No. A1 2 Compressor No. B1 3 A1 First Stage of Condenser Fans 4 B1 Second Stage of Condenser Fans
30GTN,R060-090, 230B, 245B
1 Compressor No. A1
2 Compressor No. B1 3, 4 A1 First Stage of Condenser Fans 5, 6 B1 Second Stage of Condenser Fans
30GTN,R100,110, 255B-315B
1 Compressor No. A1
2 Compressor No. B1 3, 4 A1 First Stage of Condenser Fans
5, 6, 7, 8 B1 Second Stage of Condenser Fans
30GTN,R130 (60 Hz)
POWER
5, 7 Compressor No. A1 6, 8 Compressor No. B1 1, 2 A1 First Stage of Condenser Fans
3, 4, 9, 10 B1 Second Stage of Condenser Fans
30GTN,R130 (50 Hz), 150-210, 230A-315A, 330A/B-420A/B†
POWER
5, 7 Compressor No. A1 6, 8 Compressor No. B1
1, 11 A1 First Stage of Condenser Fans, Circuit A
3, 9 A2 Second Stage of Condenser Fans, Circuit A
2, 12 B1 First Stage of Condenser Fans, Circuit B 4, 10 B2 Second Stage of Condenser Fans, Circuit B
*Control box.
†Fan numbers 11 and 12 do not apply to 30GT130-170 and associated modular units (see Table 1).
Fig. 17 — Condenser Fan Sequence
28
Marquee Display Usage (See Fig. 18 and Tables 6-24) —
The Marquee display module provides
the user interface to the ComfortLink™ control system. The display has up and down arrow keys, an ESCAPE
key,and
an ENTER
key. These keys are used to navigate through the differentlevelsofthedisplaystructure.SeeTable 6. Press the ESCAPE
key until the display is blank to move through
the top 11 mode levels indicated by LEDs on the left side of the display.
Pressing the ESCAPE
and ENTER keys simulta-
neously will scroll a clear language text description across the display indicating the full meaning of each display ac-
ronym. Pressing the ESCAPE
and ENTER keys when the
display is blank (Mode LED level) will return the Marquee display to its default menu of rotating display items. In ad­dition, the password will be disabled requiring that it be en­tered again before changes can be made to passwordprotected items.
Clear language descriptions in English, Spanish, French, or Portuguese can be displayed when properly configuring the LANG variable in the Configuration Mode, under DISP submode. See Table 15.
NOTE: When the LANG variable is changed to 1, 2, or 3, all appropriate display expansions will immediately change to the new language. No power-off or control reset is re­quired when reconfiguring languages.
When a specific item is located, the display will flash show­ing the operator, the item, followed by the item value and then followed by the item units (if any). Press the
ENTER
key to stop the display at the item value. Items in
the Configuration and Service Testmodes are password pro­tected. The display will flash PASS and WORD when re-
quired. Use the ENTER
and arrow keys to enter the 4 dig-
its ofthepassword.The default password is 1111. The password can only be changed through CCN devices such as ComfortWorks and Service Tool.
Changing item values or testing outputs is accomplished in the same manner. Locate and display the desired item.
Press ENTER
to stop the display at the item value. Press
the ENTER key again so that the item value flashes. Use the arrow keys to change the value or state of an item and press the ENTER
key to accept it. Press the ESCAPE key
and the item, value, or units display will resume. Repeat the process as required for other items.
See Tables 6-24 for further details.
Service Test (See Table 8) — Both main power and
control circuit power must be on.
The Service Test function should be used to verify proper operation of compressors, unloaders, hot gas bypass (if in­stalled), cooler pump and remote alarm relays, EXVs and condenser fans. To use the Service Test mode, the Enable/ Off/RemoteContactswitchmustbeinthe OFF position. Use the display keys and Table 8 to enter the mode and display
TEST. Press ENTER
twice so that OFF flashes, Enter the password if required. Use either arrow key to change the TEST value to the On position and press ENTER
. Press
ESCAPE and the button to enter the OUTS or COMP
sub-mode.
Test the condenser fan, cooler pump, and alarm relays by changing the item values from OFF to ON. These discrete outputs are turned off if there is no keypad activity for 10 minutes. Use arrow keys to select desired percentage when testing expansion valves. When testing compressors, the lead compressor must be started first. All compressor outputs can be turned on, but the control will limit the rate by staging one compressor per minute. Compressor unloaders and hot gas bypass relays/solenoids (if installed) can be tested with compressors on or off. The relays under the COMP sub­mode will stay on for 10 minutes if there is no keypad ac­tivity. Compressors will stay on until they are turned off by the operator. The Service Test mode will remain enabled for as long as there is one or more compressors running. All safeties are monitored during this test and will turn a com­pressor,circuitorthemachineoff if required. Any other mode or sub-mode can be accessed, viewed, or changed during the TEST mode. The MODE item (Run/status mode under sub­mode VIEW) will display ‘‘0’’ as long as the Service mode is enabled. The TESTsub-mode value must be changed back to OFF before the chiller can be switched to Enable or Re­mote contact for normal operation.
Configuring and Operating Dual Chiller Con­trol (See Table17) —
The dual chiller routine is avail­able for the control of two units supplying chilled fluid on a common loop. This control is designed for a parallel fluid flow arrangement only. One chiller must be configured as the Master, the other chiller as the Slave. The Master chiller Leaving Fluid Temperature thermistor (T1) must be in­stalled in the common leaving chilled water line after the piping has joined from both chillers. See Fig. 19 for ther­mistor location.
To configure the two chillers for operation, follow the ex­ample shown in Table 17. The Master chiller will be con­figured with a slave at address 6. Also in this example, the Master will be configured to use Lead/Lag Balance to even out the chiller runtimes weekly.The Lag Start Delay feature will be set to 10 minutes. The Master and Slave chillers can­not have the same CCN address (CCNA, Configuration mode under OPT2). Both chillers must have the control method variable (CTRL, Configuration mode under OPT2) set to ‘3.’ In addition, the chillers must both be connected together on the same CCN bus. Connections can be made to the CCN screw terminals on TB3 in both chillers. The Master chiller will determine which chiller will be Lead and which will be Lag. The Master controls the Slave by forcing the Slave’s CHIL_S_S (CCN) variable, control point (CTPT) and de­mand limit.
The Master chiller is now configured for dual chiller op­eration. To configure the Slave chiller, only the LLEN and MSSL variables need to be set. Enable the Lead/Lag chiller enable variable (LLEN) as shown Table 17. Similarly, set the Master/Slave Select variable (MSSL) to SLVE.Thevari­ables LLBL, LLBD, an LLDY are not used by the Slave chiller.
Run Status Service Test Temperature Pressures Setpoints Inputs Outputs Configuration Time Clock Operating Modes Alarms
Alarm Status
ENTER
MODE
ESCAPE
Fig. 18 — Scrollling Marquee Display
29
Table 6 — Marquee Display Menu Structure)
RUN
STATUS
SERVICE
TEST
TEMPERATURES PRESSURES
SET
POINTS
INPUTS OUTPUTS CONFIGURATION
TIME
CLOCK
OPERATING
MODES
ALARMS
Auto Display (VIEW)
Manual
Mode
On/Off
(TEST)
Unit
Temperatures
(UNIT)
Ckt A
Pressures
(PRC.A)
Cooling (COOL)
Unit
Discrete
(GEN.I)
Unit
Discrete
(GEN.O)
Display
(DISP)
Unit Time
(TIME)
Modes
(MODE)
Current (CRNT)
Machine
Hours/Starts
(RUN)
Ckt A/B Outputs (OUTS)
Ckt A
Temperatures
(CIR.A)
Ckt B
Pressures
(PRC.B)
Head
Pressure
(HEAD)
Ckt A/B
(CRCT)
Ckt A
(CIR.A)
Machine
(UNIT)
Unit Date
(DATE)
Reset
Alarms
(RCRN)
Compressor
Run Hours
(HOUR)
Compressor
Tests
(COMP)
Ckt B
Temperatures
(CIR.B)
Unit
Analog
(4-20)
Ckt B
(CIR.B)
Options 1
(OPT1)
Schedule
(SCHD)
Alarm History (HIST)
Compressor
Starts
(STRT)
Options 2
(OPT2)
Reset History (RHIS)
Temperature
Reset
(RSET)
Set Point
Select
(SLCT)
LEGEND
Ckt — Circuit
MASTER CHILLER
SLAVE
CHILLER
LEAVING FLUID
INSTALL MASTER CHILLER LEAVING FLUID THERMISTOR (T1) HERE
RETURN FLUID
Fig. 19 — Dual Chiller Thermistor Location
30
Table 7 — Run Status Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY ITEM EXPANSION COMMENT
VIEW
ENTER
EWT XXX.X °F ENTERING FLUID TEMP
LWT XXX.X °F LEAVING FLUID TEMP SETP XXX.X °F ACTIVE SETPOINT CTPT XXX.X °F CONTROL POINT
MODE X CONTROL MODE 0 = SERVICE TEST
1 = OFF — LOCAL 2 = OFF — CCN 3 = OFF — TIME 4 = OFF — EMRGCY 5 = ON — LOCAL 6=ON—CCN 7 = ON — TIME
OCC YES/NO OCCUPIED
CAP XXX % PERCENT TOTAL CAPACITY
STGE XX REQUESTED STAGE
ALRM XX CURRENT ALARMS & ALERTS
TIME XX.XX TIME OF DAY 00.0 — 23.59
MNTH XX MONTH OF YEAR 1=JAN,2=FEB, etc.
DATE XX DAY OF MONTH 01 — 31 YEAR XXXX YEAR OF CENTURY
RUN
ENTER
HRS.U XXXX MACHINE OPERATING HOURS STR.U XXXX MACHINE STARTS
HOUR
ENTER
HRS.A XXXX CIRCUIT A RUN HOURS HRS.B XXXX CIRCUIT B RUN HOURS HR.A1 XXXX COMPRESSOR A1 RUN HOURS HR.A2 XXXX COMPRESSOR A2 RUN HOURS HR.A3 XXXX COMPRESSOR A3 RUN HOURS HR.A4 XXXX COMPRESSOR A4 RUN HOURS HR.B1 XXXX COMPRESSOR B1 RUN HOURS HR.B2 XXXX COMPRESSOR B2 RUN HOURS HR.B3 XXXX COMPRESSOR B3 RUN HOURS HR.B4 XXXX COMPRESSOR B4 RUN HOURS
STRT
ENTER
ST.A1 XXXX COMPRESSOR A1 STARTS ST.A2 XXXX COMPRESSOR A2 STARTS ST.A3 XXXX COMPRESSOR A3 STARTS ST.A4 XXXX COMPRESSOR A4 STARTS ST.B1 XXXX COMPRESSOR B1 STARTS ST.B2 XXXX COMPRESSOR B2 STARTS ST.B3 XXXX COMPRESSOR B3 STARTS ST.B4 XXXX COMPRESSOR B4 STARTS
31
Table 8 — Service Test Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY ITEM EXPANSION COMMENT
TEST
ENTER
ON/OFF SERVICE TEST MODE Use to Enable/Disable Manual Mode
OUTS
ENTER
FR.A1 ON/OFF FAN A1 RELAY Fan 3 (040-050)
Fans 3,4 (060-110, 230B-315B) Fans 1,2 (130 [60 Hz]) Fan 1 (130 [50 Hz], 150, 170, 230A- 270A,
330A/B, 360B [50 Hz])
Fans 1,11 (190-210, 290A, 315A,
360A, 360B [60 Hz], 390A/B-420A/B)
FR.A2 ON/OFF FAN A2 RELAY Fans 3,9 (130 [50 Hz], 150-210,
230A-315A, 330A/B-420A/B)
EXV.A 0-100% EXV % OPEN
FR.B1 ON/OFF FAN B1 RELAY Fan 4 (040-050)
Fans 5,6 (060-090, 230B-245B) Fans 5,6,7,8 (100,110, 255B-315B) Fans 3,4,9,10 (130 [60 Hz]) Fan 2 (130 [50 Hz], 150, 170, 230A- 270A,
330A/B, 360B [50 Hz])
Fans 2,12 (190-210,290A,315A,
360A, 360B [60 Hz] ,390A/B-420A/B)
FR.B2 ON/OFF FAN B2 RELAY Fans 4,10 (130 [50 Hz], 150-210, 230A-315A,
330A/B-420A/B)
EXV.B 0-100% EXV % OPEN CLR.P ON/OFF COOLER PUMP RELAY RMT.A ON/OFF REMOTE ALARM RELAY
COMP
ENTER
CC.A1 ON/OFF COMPRESSOR A1 RELAY CC.A2 ON/OFF COMPRESSOR A2 RELAY CC.A3 ON/OFF COMPRESSOR A3 RELAY CC.A4 ON/OFF COMPRESSOR A4 RELAY
UL.A1 ON/OFF UNLOADER A1 RELAY
UL.A2 ON/OFF UNLOADER A2 RELAY HGBP ON/OFF HOT GAS BYPASS RELAY CC.B1 ON/OFF COMPRESSOR B1 RELAY CC.B2 ON/OFF COMPRESSOR B2 RELAY CC.B3 ON/OFF COMPRESSOR B3 RELAY CC.B4 ON/OFF COMPRESSOR B4 RELAY
UL.B1 ON/OFF UNLOADER B1 RELAY
UL.B2 ON/OFF UNLOADER B2 RELAY
LEGEND
EXV — Electronic Expansion Valve
32
Table9—Temperature Mode and Sub-Mode Directory
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
UNIT
ENTER
CEWT XXX.X °F COOLER ENTERING FLUID CLWT XXX.X °F COOLER LEAVING FLUID
OAT XXX.X °F OUTSIDE AIR TEMPERATURE SPT XXX.X °F SPACE TEMPERATURE
CIR.A
ENTER
SCT.A XXX.X °F SATURATED CONDENSING TMP SST.A XXX.X °F SATURATED SUCTION TEMP SGT.A XXX.X °F COMPRESSOR SUCTION TEMP SUP.A XXX.X °F SUCTION SUPERHEAT TEMP
CIR.B
ENTER
SCT.B XXX.X °F SATURATED CONDENSING TMP SST.B XXX.X °F SATURATED SUCTION TEMP SGT.B XXX.X °F COMPRESSOR SUCTION TEMP SUP.B XXX.X °F SUCTION SUPERHEAT TEMP
Table 10 — Pressure Mode and Sub-Mode Directory
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
PRC.A
ENTER
DP.A
XXX.X
PSIG
DISCHARGE PRESSURE
SP.A
XXX.X
PSIG
SUCTION PRESSURE
PRC.B
ENTER
DP.B
XXX.X
PSIG
DISCHARGE PRESSURE
SP.B
XXX.X
PSIG
SUCTION PRESSURE
Table 11 — Set Point Mode and Sub-Mode Directory
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
COOL
ENTER
CSP.1 XXX.X °F COOLING SETPOINT 1 Default: 44 F CSP.2 XXX.X °F COOLING SETPOINT 2 Default: 44 F
HEAD
ENTER
HD.P.A XXX °F HEAD PRESSURE SETPOINT A Default: 113 F
HD.P.B XXX °F HEAD PRESSURE SETPOINT B Default: 113 F
Table 12 — Reading and Changing Chilled Fluid Set Point
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
COOL
ENTER
CSP.1 44.0 °F COOLING SETPOINT 1 Default: 44° F
ENTER
44.0 °F Scrolling stops
ENTER
44.0 °F Value flashes Select 46.0
ENTER
46.0 °F Change accepted
ESCAPE
CSP.1 46.0 °F COOLING SETPOINT 1 Item/Value/Units scrolls again
33
Table 13 — Inputs Mode and Sub-Mode Directory
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
GEN.I
ENTER
STST STRT/STOP START/STOP SWITCH Enable/Off/Remote Contact Switch Input
FLOW ON/OFF COOLER FLOW SWITCH
DLS1 ON/OFF DEMAND LIMIT SWITCH 1 DLS2 ON/OFF DEMAND LIMIT SWITCH 2
ICED ON/OFF ICE DONE
DUAL ON/OFF DUAL SETPOINT SWITCH
CRCT
ENTER
FKA1 ON/OFF COMPRESSORA1 FEEDBACK FKA2 ON/OFF COMPRESSORA2 FEEDBACK FKA3 ON/OFF COMPRESSORA3 FEEDBACK FKA4 ON/OFF COMPRESSORA4 FEEDBACK OIL.A OPEN/CLSE OIL PRESSURE SWITCH A FKB1 ON/OFF COMPRESSOR B1 FEEDBACK FKB2 ON/OFF COMPRESSOR B2 FEEDBACK FKB3 ON/OFF COMPRESSOR B3 FEEDBACK FKB4 ON/OFF COMPRESSOR B4 FEEDBACK OIL.B OPEN/CLSE OIL PRESSURE SWITCH B
4-20
ENTER
DMND XX.X MA 4-20 MA DEMAND SIGNAL
RSET XX.X MA 4-20 MA RESET SIGNAL
CSP XX.X MA 4-20 MA COOLING SETPOINT
34
Table 14 — Outputs Mode and Sub-Mode Directory
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
GEN.O
ENTER
C.PMP ON/OFF COOLER PUMP RELAY H.GAS ON/OFF HOT GAS BYPASS RELAY
CIR.A
ENTER
FR.A1 ON/OFF FANA1 RELAY
FR.A2 ON/OFF FANA2 RELAY CC.A1 ON/OFF COMPRESSOR A1 RELAY CC.A2 ON/OFF COMPRESSOR A2 RELAY CC.A3 ON/OFF COMPRESSOR A3 RELAY CC.A4 ON/OFF COMPRESSOR A4 RELAY
UL.A1 ON/OFF UNLOADER A1 RELAY
UL.A2 ON/OFF UNLOADER A2 RELAY
EXV.A XXX.X % EXV % OPEN
CIR.B
ENTER
FR.B1 ON/OFF FAN B1 RELAY
FR.B2 ON/OFF FAN B2 RELAY CC.B1 ON/OFF COMPRESSOR B1 RELAY CC.B2 ON/OFF COMPRESSOR B2 RELAY CC.B3 ON/OFF COMPRESSOR B3 RELAY CC.B4 ON/OFF COMPRESSOR B4 RELAY
UL.B1 ON/OFF UNLOADER B1 RELAY
UL.B2 ON/OFF UNLOADER B2 RELAY
EXV.B XXX.X % EXV % OPEN
LEGEND
EXV — Electronic Expansion Valve
Table 15 — Configuration Mode and Sub-Mode Directory
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
DISP
ENTER
TEST ON/OFF TEST DISPLAY LEDS
METR ON/OFF METRIC DISPLAY Off = English
On = Metric
LANG X LANGUAGE SELECTION Default: 0
0 = English 1 = Espanol 2 = Francais 3 = Portugues
LEGEND
CCN — Carrier Comfort Network EMM — Energy Management Module EXV — Electronic Expansion Valve LCW — Leaving Chilled Water
35
Table 15 — Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
UNIT
ENTER
TYPE X UNIT TYPE Default: 1
1 = Air Cooled TONS XXX UNIT SIZE CAP.A XXX CIRCUIT A % CAPACITY Unit Size 60 Hz 50 Hz
040 50 43 045 43 46 050 46 43 060 43 50 070 50 57 080* 56 62 090* 50 54 100* 50 50 110* 54 50 130* 50 52 150* 50 60 170* 50 48 190* 50 50 210* 50 52
*And associated modular units. CMP.A X NUMBER CIRC A COMPRESSOR CYL.A X COMPRESSOR A1 CYLINDERS 4 = 040, 045 (60 Hz)
6 = 045 (50 Hz), 050-420
CMP.B X NUMBER CIRC B COMPRESSOR CYL.B X COMPRESSOR B1 CYLINDERS 4 = 040 (60 Hz)
6 = 040 (50 Hz), 045-420
EXV YES/NO EXV MODULE INSTALLED
SH.SP D F EXV SUPERHEAT SETPOINT 29 SH.OF D F EXV SUPERHEAT OFFSET Default: 0
Range: −30 to 30 F REFG X REFRIGERANT 1 = R-22
FAN.S X FAN STAGING SELECT 1 = 2 Stage Independent (190-210, 290A,
315A, 360B [60 Hz], 390A/B-420A/B)
2 = 3 Stage Independent (130 [50 Hz], 150, 170,
230A-270A, 330A/B, 360B [50 Hz])
3 = 2 Stage Common (040-090,
230B,245B)
4 = 3 Stage Common (100-110,
130 [60 Hz], 255B-315B)
OPT1
ENTER
FLUD X COOLER FLUID Default: 1
1 = Water
2 = Medium Temperature Brine
3 = Low Temperature Brine
(Not Supported) HGB.S YES/NO HOT GAS BYPASS SELECT HPCM X HEAD PRESS. CONT. METHOD Default: 2
1 = EXV Control 2 = Set Point Control 3 = Set Point Circuit A, EXV Circuit B 4 = EXV Circuit A, Set Point Circuit B
HPCT X HEAD PRESS. CONTROL TYPE Default: 1
1 = No Control 2 = Air Cooled
PRTS YES/NO PRESSURE TRANSDUCERS CURRENTLY NOT SUPPORTED PMP.I ON/OFF COOLER PUMP INTERLOCK Default: On
CPC ON/OFF COOLER PUMP CONTROL Default: Off CA.UN X NO. CIRCUIT A UNLOADERS CB.UN X NO. CIRCUIT B UNLOADERS
EMM YES/NO EMM MODULE INSTALLED
LEGEND
CCN — Carrier Comfort Network EMM — Energy Management Module EXV — Electronic Expansion Valve LCW — Leaving Chilled Water
36
Table 15 — Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
OPT2
ENTER
CTRL X CONTROL METHOD Default: 0
0 = Switch 1 = 7 Day Schedule 2 = Occupancy 3 = CCN Control
CCNA XXX CCN ADDRESS Default: 1
Range: 1 to 239
CCNB XXX CCN BUS NUMBER
Default: 0 Range: 0 to 239
BAUD X CCN BAUD RATE Default: 3
1 = 2400 2 = 4800 3 = 9600 4 = 19,200 5 = 38,400
LOAD X LOADING SEQUENCE SELECT Default: 1
1 = Equal 2 = Staged
LLCS X LEAD/LAG CIRCUIT SELECT Default: 1 (size 080-420) 2 (size 040-070)
1 = Automatic 2 = Circuit A Leads 3 = Circuit B Leads
LCWT XX.X DF HIGH LCW ALERT LIMIT Default: 60
Range: 2 to 60 F
DELY XX MIN MINUTES OFF TIME Default: 0 Minutes
Range: 0 to 15 Minutes
RSET
ENTER
CRST X COOLING RESET TYPE 0 = No Reset
1=4to20mAInput 2 = Outdoor Air Temperature 3 = Return Fluid 4 = Space Temperature
CRT1 XXX.X °F NO COOL RESET TEMP Default: 125 F
Range: 0 to 125 F
CRT2 XXX.X °F FULL COOL RESET TEMP Default: 0° F
Range: 0 to 125 F
DGRC XX.X DF DEGREES COOL RESET Default: 0° F
Range: −30 to 30 F
DMDC X DEMAND LIMIT SELECT Default: 0
0 = None 1 = Switch 2=4to20mAInput 3 = CCN Loadshed
DM20 XXX % DEMAND LIMIT AT 20 MA Default: 100%
Range: 0 to 100%
SHNM XXX LOADSHED GROUP NUMBER Default: 0
Range: 0 to 99
SHDL XXX % LOADSHED DEMAND DELTA Default: 0%
Range: 0 to 60%
SHTM XXX MIN MAXIMUM LOADSHED TIME Default: 60 minutes
Range: 0 to 120 minutes
DLS1 XXX % DEMAND LIMIT SWITCH 1 Default: 80%
Range: 0 to 100%
DLS2 XXX % DEMAND LIMIT SWITCH 2 Default: 50%
Range: 0 to 100%
LLEN ENBL/DSBL LEAD/LAG CHILLER ENABLE Default: Disable MSSL SLVE/MAST MASTER/SLAVE SELECT Default: Master
SLVA XXX SLAVE ADDRESS Default: 0
Range: 0 to 239
LLBL ENBL/DSBL LEAD/LAG BALANCE SELECT Default: Disable
LLBD XXX HRS LEAD/LAG BALANCE DELTA Default: 168 hours
Range: 40 to 400 Hours
LLDY XX MIN LAG START DELAY
Default: 5 minutes Range: 0 to 30 minutes
SLCT
ENTER
CLSP X COOLING SETPOINT SELECT Default: 0
0 = Single 1 = Dual Switch 2 = Dual Clock 3=4to20mAInput
RL.S ENBL/DSBL RAMP LOAD SELECT Default: Enable
CRMP X.X COOLING RAMP LOADING Default: 1.0
Range: 0.2 to 2.0
Z.GN X.X DEADBAND MULTIPLIER Default: 1.0
Range: 1.0 to 4.0
37
Table 16 — Example of Temperature Reset (Outdoor Air) Configuration
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
RSET
ENTER
CRST 0 COOLING RESET TYPE 0 = No reset
1=4to20mAinput 2 = Outdoor Air Temp 3 = Return Fluid 4 = Space Temperature
ENTER
0 Scrolling stops
ENTER
0 Value flashes 2 Select 2
ENTER
2 Change accepted
ESCAPE
CRST 2 Item/Value/Units scrolls again
CRT1 125 Range: 0 to 125 F
ENTER
125 Scrolling stops
ENTER
125 Value flashes
75 Select 75
ENTER
75 Change accepted
ESCAPE
CRT1 75 Item/Value/Units scrolls again CRT2 0 Range: 0 to 125 F
ENTER
0 Scrolling stops
ENTER
0 Value flashes
50 Select 50
ENTER
50 Change accepted
ESCAPE
CRT2 50 Item/Value/Units scrolls again
DGRC 0 Range: −30 to 30 F
ENTER
0 Scrolling stops
ENTER
0 Value flashes
10 Select 10
ENTER
10 Change accepted
ESCAPE
DGRC 10 Item/Value/Units scrolls again
NOTE: The example below shows how to configure the chiller for temperature reset by an accessory outdoor-air temperature sensor. The chiller will be configured for a full reset of 10 degrees at 50 F and no reset at 75 F.
38
Table 17 — Example of Configuring Dual Chiller Control
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
RSET
ENTER
CRST 0
LLDY 5 LAG START DELAY
ENTER
5 Scrolling stops
ENTER
5 Value flashes
10 Select 10
ENTER
10 Change accepted
ESCAPE
LLDY 10 LLBD 168 LEAD/LAG BALANCE DELTA No change needed. Default set for weekly changeover LLBL DSBL LEAD/LAG BALANCE SELECT
ENTER
DSBL Scrolling stops
ENTER
DSBL Value flashes ENBL Select Enable
ENTER
ENBL Change accepted
ESCAPE
LLBL ENBL SLVA 0 SLAVE ADDRESS
ENTER
0 Scrolling stops
ENTER
0 Value flashes 6 Select 6
ENTER
6 Change accepted
ESCAPE
SLVA 6
MSSL MAST MASTER/SLAVE SELECT No change needed. Default set for Master
LLEN DSBL LEAD/LAG CHILLER ENABLE
ENTER
DSBL Scrolling stops
ENTER
DSBL Value flashes
MAST Select Master
ENTER
LLEN MAST Change accepted
ESCAPE
LLEN MAST LEAD/LAG CHILLER ENABLE Item/Value/Units scrolls again
39
Table 18 — Example of Compressor Lead/Lag Configuration
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
OPT2
ENTER
CTRL 0 CONTROL METHOD CCNA 1 CCNB 0 BAUD 3 LOAD 1
LLCS 1 LEAD/LAG CIRCUIT SELECT DEFAULT: 2 (040-070); 1 (080-420)
ENTER
1 Scrolling stops
ENTER
1 Value flashes 3 Select 3
NOTE: Options 1 and/or 3 not valid for sizes 040-070 with­out Circuit B accessory unloader installed
ENTER
3 Change accepted
ESCAPE
LLCS 3 LEAD/LAG CIRCUIT SELECT Item/Value/Units scrolls again
Table 19 — Time Clock Mode and Sub-Mode Directory
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
TIME
ENTER
HH.MM XX.XX HOUR AND MINUTE Military (00.00-23.59)
DATE
ENTER
MNTH XX MONTH 1=Jan, 2=Feb, etc.
DOM XX DATE OF MONTH Range 1-31
DAY X DAY OF WEEK 1=Mon, 2=Tue, etc.
YEAR XXXX YEAR OF CENTURY
SCHD
ENTER
MON.O XX.XX MONDAY OCCUPIED TIME Range: 00.00 to 23.59
Default: 00.00
MON.U XX.XX MONDAY UNOCCUPIED TIME Range: 00.00 to 23.59
Default: 00.00
TUE.O XX.XX TUESDAY OCCUPIED TIME Range: 00.00 to 23.59
Default: 00.00
TUE.U XX.XX TUESDAY UNOCCUPIED TIME Range: 00.00 to 23.59
Default: 00.00
WED.O XX.XX WEDNESDAY OCCUPIED TIME Range: 00.00 to 23.59
Default: 00.00
WED.U XX.XX WEDNESDAY UNOCC TIME Range: 00.00 to 23.59
Default: 00.00
THU.O XX.XX THURSDAY OCCUPIED TIME Range: 00.00 to 23.59
Default: 00.00
THU.U XX.XX THURSDAY UNOCCUPIED TIME Range: 00.00 to 23.59
Default: 00.00
FRI.O XX.XX FRIDAY OCCUPIED TIME Range: 00.00 to 23.59
Default: 00.00
FRI.U XX.XX FRIDAY UNOCCUPIED TIME Range: 00.00 to 23.59
Default: 00.00
SAT.O XX.XX SATURDAY OCCUPIED TIME Range: 00.00 to 23.59
Default: 00.00
SAT.U XX.XX SATURDAY UNOCCUPIED TIME Range: 00.00 to 23.59
Default: 00.00
SUN.O XX.XX SUNDAY OCCUPIED TIME Range: 00.00 to 23.59
Default: 00.00
SUN.U XX.XX SUNDAY UNOCCUPIED TIME Range: 00.00 to 23.59
Default: 00.00
40
Table 20 — Setting an Occupied Time Schedule
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
SCHD
ENTER
MON.O 00.00 MONDAY OCCUPIED TIME TIME IN MILITARY FORMAT (HH.MM)
ENTER
00.00 Scrolling stops
ENTER
00.00 Hours flash
07.00 Select 7 AM
ENTER
07.00 Change accepted, minutes flash
07.30 Select 30
ENTER
07.30 Change accepted
ESCAPE
MON.O 07.30 MONDAY OCCUPIED TIME Item/Value/Units scrolls again
Table 21 — Operating Mode and Sub-Mode Directory
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
MODE
ENTER
MD01 ON/OFF FSM CONTROLLING CHILLER MD02 ON/OFF WSM CONTROLLING CHILLER MD03 ON/OFF MASTER/SLAVE CONTROL MD04 ON/OFF LOW SOURCE PROTECTION MD05 ON/OFF RAMP LOAD LIMITED MD06 ON/OFF TIMED OVERRIDE IN EFFECT MD07 ON/OFF LOW COOLER SUCTION TEMP A MD08 ON/OFF LOW COOLER SUCTION TEMP B MD09 ON/OFF SLOW CHANGE OVERRIDE MD10 ON/OFF MINIMUM OFF TIME ACTIVE
MD11 ON/OFF LOW SUCTION SUPERHEATA MD12 ON/OFF LOW SUCTION SUPERHEAT B MD13 ON/OFF DUAL SETPOINT MD14 ON/OFF TEMPERATURE RESET MD15 ON/OFF DEMAND LIMIT IN EFFECT MD16 ON/OFF COOLER FREEZE PROTECTION MD17 ON/OFF LO TMP COOL/HI TMP HEAT MD18 ON/OFF HI TMP COOL/LO TMP HEAT
LEGEND
FSM — Flotronic™ System Manager WSM — Water System Manager
41
Table 22 — Operating Modes
MODE NO. ITEM EXPANSION DESCRIPTION
01 FSM CONTROLLING CHILLER Flotronic™ System Manager (FSM) is controlling the chiller 02 WSM CONTROLLING CHILLER Water System Manager (WSM) is controlling the chiller 03 MASTER/SLAVE CONTROL Lead/Lag Chiller control is enabled. 04 LOW SOURCE PROTECTION Not currently supported. 05 RAMP LOAD LIMITED Ramp load (pulldown) limiting in effect. In this mode, the rate
at which leaving fluid temperature is dropped is limited to a predetermined value to prevent compressor overloading. See CRMP set point in the Set Point Select (SLCT) section of the Configuration mode. The pulldown limit can be modified, if de­sired, to any rate from 0.2° F to 2° F (0.1 to 1 C)/minute.
06 TIMED OVERRIDE IN EFFECT Timed override is in effect. This isa1to4hour temporary
override of the programmed schedule, forcing unit to Occupied mode. Override can be implemented with unit under Local (En­able) or CCN control. Override expires after each use.
07 LOW COOLER SUCTION TEMP A Circuit A capacity may be limited due to operation of this mode.
Control will attempt to correct this situation for up to 10 minutes before shutting the circuit down. The control may decrease ca­pacity when attempting to correct this problem. See Alarms and Alerts section for more information.
08 LOW COOLER SUCTION TEMP B Circuit B capacity may be limited due to operation of this
mode. Control will attempt to correct this situation for up to 10 minutes before shutting the circuit down. The control may decrease capacity when attempting to correct this problem. See Alarms and Alerts section for more information.
09 SLOW CHANGE OVERRIDE Slow change override is in effect. The leaving fluid temperature
is close to and moving towards the control point.
10 MINIMUM OFF TIME ACTIVE Chiller is being held off by Minutes Off Time (DELY) found un-
der Options 2 (OPT2) section of Configuration mode.
11 LOW SUCTION SUPERHEAT A Circuit A capacity may be limited due to operation of this mode.
Control will attempt to correct this situation for up to 5 minutes before shutting the circuit down. See Alarms and Alerts section for more information.
12 LOW SUCTION SUPERHEAT B Circuit B capacity may be limited due to operation of this
mode. Control will attempt to correct this situation for up to 5 minutes before shutting the circuit down. See Alarms and Alerts section for more information.
13 DUAL SETPOINT Dual set point mode is in effect. Chiller controls to CSP.1 dur-
ing occupied periods and CSP.2 during unoccupied periods. Both CSP.1 and CSP.2 are located under COOL in the Set Point mode.
14 TEMPERATURE RESET Temperature reset is in effect. In this mode, chiller is using
temperature reset to adjust leaving fluid set point upward and is currently controlling to the modified set point. The set point can be modified based on return fluid, outdoor-air-temperature, space temperature, or 4 to 20 mA signal.
15 DEMAND LIMIT IN EFFECT Demand limit is in effect. This indicates that the capacity of the
chiller is being limited by demand limit control option. Because of this limitation, the chiller may not be able to produce the de­sired leaving fluid temperature. Demand limit can be controlled by switch inputs ora4to20mAsignal.
16 COOLER FREEZE PROTECTION Cooler fluid temperatures are approaching the Freeze point
(see Alarms and Alerts section for definition). The chiller will be shut down when either fluid temperature falls below the Freeze point.
17 LO TMP COOL/HI TMP HEAT Chiller is in Cooling mode and the rate of change of the leaving
fluid is negative and decreasing faster than -0.5° F per minute. Error between leaving fluid and control point exceeds fixed amount. Control will automatically unload the chiller if necessary.
18 HI TMP COOL/LO TMP HEAT Chiller is in Cooling mode and the rate of change of the leaving
fluid is positive and increasing. Error between leaving fluid and control point exceeds fixed amount. Control will automatically load the chiller if necessary to better match the increasing load.
42
Table 23 — Alarms Mode and Sub-Mode Directory
SUB-MODE KEYPAD ENTRY ITEM ITEM EXPANSION COMMENT
CRNT
ENTER
AXXX or TXXX CURRENTLY ACTIVE ALARMS
Alarms are shown as AXXX. Alerts are shown as TXXX.
RCRN
ENTER
YES/NO RESETALL CURRENT ALARMS
HIST
ENTER
AXXX or TXXX ALARM HISTORY
Alarms are shown as AXXX. Alerts are shown as TXXX.
RHIS
ENTER
YES/NO RESET ALARM HISTORY
Table 24 — Example of Reading and Clearing Alarms
SUB-MODE KEYPAD ENTRY ITEM ITEM EXPANSION COMMENT
CRNT
ENTER
AXXX or TXXX CURRENTLY ACTIVE ALARMS
ACTIVE ALARMS (AXXX) OR ALERTS (TXXX) DISPLAYED.
CRNT
ESCAPE
RCRN
NO Use to clear active alarms/alerts
ENTER
NO NO Flashes
YES Select YES
ENTER
NO Alarms/alerts clear, YES changes to NO
Temperature Reset — The control system is capable
of handling leaving-fluid temperature reset based on return cooler fluid temperature. Because the change in temperature through the cooler is a measure of the building load, the re­turn temperature reset is in effect an average building load reset method. The control system is also capable of tempera­ture reset based on outdoor-airtemperature(OAT), space tem­perature (SPT), or from an externally powered 4 to 20 mA signal. Accessory sensors must be used for OAT and SPT reset (HH79NZ014 for OAT and HH51BX006 for SPT). The Energy Management Module (EMM) must be used for tem­perature reset usinga4to20mAsignal.
To use the return reset, four variables must be configured. In the Configuration mode under the sub-mode RSET, items CRST, CRT1, CRT2, and DGRC must be set properly. See Table 25 on page 42 for correct configuration. See Fig. 2-4 for wiring details.
Under normal operation, the chiller will maintain a con­stant leaving fluid temperature approximately equal to the chilled fluid set point. As the cooler load varies, the entering cooler fluid will change in proportion to the load as shown in Fig. 20. Usually the chiller size and leaving-fluid tem­perature set point are selected based on a full-load condi­tion.Atpartload, the fluid temperature set point may be colder than required. If the leaving fluid temperature was allowed to increase at part load, the efficiency of the machine would increase.
Return temperature reset allows for the leaving tempera­ture set point to be reset upward as a function of the return fluid temperature or, in effect, the building load.
LEGEND
EWT — Entering Water (Fluid) Temperature LWT — Leaving Water (Fluid) Temperature
Fig. 20 — Standard Chilled Fluid Temperature
Control — No Reset
43
Table 25 — Configuring Temperature Reset
MODE
GREEN LED)
KEYPAD
ENTRY
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
CONFIGURATION
ENTER
DISP
ENTER
TEST ON/OFF TEST DISPLAY LEDs
UNIT
ENTER
TYPE X UNIT TYPE
OPT1
ENTER
FLUD X COOLER FLUID
OPT2
ENTER
CTRL X CONTROL METHOD
RSET
ENTER
CRST X COOLING RESET TYPE 0 = No Reset
1 = 4 to 20 mA Input (EMM required)
(Connect to EMM J6-2,5)
2 = Outdoor-Air Temperature
(Connect to TB5-7,8) 3 = Return Fluid (Connect to TB5-5,6) 4 = Space Temperature
CRT1 XXX.X F NO COOL RESET TEMP
Default: 125 F (51.7 C) Range: 0 to125 F Set to 4.0 for CRST= 1
CRT2 XXX.X F FULL COOL RESET TEMP
Default: 0° F (−17.8 C) Range: 0 to 125 F Set to 20.0 for CRST=1
DGRC XX.X °F DEGREES COOL RESET
Default: 0° F (0° C) Range: −30 to 30° F (−16.7 to 16.7 C)
The following are examples of outdoor air and space tem­perature resets:
LEGEND
LWT — Leaving Water (Fluid) Temperature
LEGEND
LWT — Leaving Water (Fluid) Temperature
44
Demand Limit — Demand Limit is a feature that allows
the unit capacity to be limited during periods of peak energy usage. There are 3 types of demand limiting that can be con­figured. The first typeisthrough2-stageswitchcontrol,which will reduce the maximum capacity to 2 user-configurable per­centages. The second typeisby4to20mAsignal input which will reduce the maximum capacity linearly between 100% ata4mAinput signal (no reduction) down to the user­configurable level at a 20 mA input signal. The third type uses the CNN Loadshed module and has the ability to limit the current operating capacity to maximum and further re­duce the capacity if required.
NOTE: The 2-stage switch control and 4 to 20 mA input signal types of demand limiting require the Energy Manage­ment Module (EMM).
To use Demand Limit, select the type of demand limiting to use. Then configure the Demand Limit set points based on the type selected.
DEMAND LIMIT (2-Stage Switch Controlled) — To con­figure Demand Limit for 2-stage switch control set the De­mand Limit Select (DMDC) to 1. Then configure the 2 De­mand Limit Switch points (DLS1 and DLS2) to the desired capacity limit. See Table 26. Capacity steps are controlled by 2 relay switch inputs field wired to TB6 as shown in Fig. 2-4.
For Demand Limit by 2-stage switch control, closing the first stage demand limit contact will put the unit on the first demand limit level. The unit will not exceed the percentage of capacity entered as Demand Limit Switch 1 set point. Clos­ing contacts on the second demand limit switch prevents the unit from exceeding the capacity entered as Demand Limit Switch 2 set point. The demand limit stage that is set to the
lowest demand takes priority if both demand limit inputs are closed. If the demand limit percentage does not match unit staging, the unit will limit capacity to the closest capacity stage.
To disable demand limit configure the DMDC to 0. See
Table 25. EXTERNALLY POWERED DEMAND LIMIT (4 to 20 mA
Controlled) — To configure Demand Limit for 4 to 20 mA control set the Demand Limit Select (DMDC) to 2. Then configure the Demand Limit at 20 mA (DM20) to the maxi­mum loadshed value desired. The control will reduce allow­able capacity to this level for the 20 mA signal. See Table26 and Fig. 21.
DEMAND LIMIT (CCN Loadshed Controlled) — To con­figure Demand Limit for CCN Loadshed control set the De­mand Limit Select (DMDC) to 3. Then configure the Load­shed Group Number (SHNM), Loadshed Demand Delta (SHDL), and Maximum Loadshed Time (SHTM). See Table 26.
The Loadshed Group number is established by the CCN system designer. The PIC (product integrated control) will respond to a Redline command from the Loadshed control. When the Redline command is received, the current stage of capacity is set to the maximum stages available. Should the loadshed control send a Loadshed command, the PIC will reduce the current stages by the value entered for Loadshed Demand delta. The Maximum Loadshed Time is the defines the maximum length of time that a loadshed condition is al­lowed to exist. The control will disable the Redline/Loadshed command if no Cancel command has been received within the configured maximum loadshed time limit.
Table 26 — Configuring Demand Limit
MODE
KEYPAD
ENTRY
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY ITEM EXPANSION COMMENT
CONFIGURATION
ENTER
DISP
ENTER
TEST ON/OFF Test Display LEDs
UNIT
ENTER
TYPE X Unit Type
OPT1
ENTER
FLUD X Cooler Fluid
OPT2
ENTER
CTRL X Control Method
RSET
ENTER
CRST X Cooling Reset Type
CRT1 XXX.X °F
No Cool Reset
Temperature
CRT2 XXX.X °F
Full Cool Reset
Temperature
DGRC XX.X DF Degrees Cool Reset
DMDC X Demand Limit Select
Default: 0 0 = None 1 = Switch 2=4to20mAInput 3 = CCN Loadshed
DM20 XXX %
Demand Limit at
20 mA
Default: 100% Range: 0 to 100
SHNM XXX
Loadshed Group
Number
Default: 0 Range: 0 to 99
SHDL XXX%
Loadshed Demand
Delta
Default: 0% Range: 0 to 60%
SHTM XXX MIN
Maximum Loadshed
Time
Default: 60 min. Range: 0 to 120 min.
DLS1 XXX %
Demand Limit
Switch 1
Default: 80% Range: 0 to 100%
DLS2 XXX%
Demand Limit
Switch 2
Default: 50% Range: 0 to 100
45
TROUBLESHOOTING
Compressor Protection Control System (CPCS) Board —
The compressor protection board controls the
compressor and compressor crankcase heater.
The ground current protection is provided by the com-
pressor board.
The large relay located on the board is used to provide a
feedback signal to the Main Base Board.
The operation of the compressor board can be checked using the Service Testprocedure.When the Service Test step is turned on, the compressor board is energized. All safeties are continuouslymonitored.Thecrankcase heater will be turned offandthecompressorcontactorwillbe turned on.The feed­back contacts will close and the Main Base Board (MBB) will read the feedback status.
If the board does not perform properly, use standard wir­ing troubleshooting procedures to check the wiring for open circuits. Refer to Alarms and Alerts section on page 45 for alarm or alert codes for possible causes for failure.
If a compressorshort-to-groundexists,thecompressor board may detect the short before the circuit breaker trips. If this is suspected, check the compressor for short-to-ground fail­ures with an ohmmeter. The ground current is sensed with a current toroid (coil) around all 3 or 6 wires between the main terminal block and the compressor circuit breaker(s).
Compressor Ground Current (CGC) Board (30GTN,R130-210, 230A-315A, and 330A/B­420A/B) —
One board is used for each circuit of these units. Each board receives input from up to 4 toroids wired in series, one toroid per compressor. With 24 v supplied at terminals A and B, a current imbalance (compressor ground current) sensed by any toroid causes the NC (normally closed) contacts to open, shutting down the lead compressor in the affectedcircuit.All other compressors in that circuit shutdown as a result. The NC contacts remain open until the circuit is reset by momentarily deenergizing the board using the push­button switch.
If the NC contacts open, it is necessary to remove toroids from the T1-T2 circuit to determine which toroid is causing the trip. The chiller circuit can then be put back on line after the circuit breaker of the faulty compressor is opened. The compressor problem can then bediagnosedbynormaltrouble­shooting procedures.
EXV Troubleshooting— If it appears that the EXV is
not properly controlling operating suction pressure or super­heat, there are a number of checks that can be made using
the quick test and initialization features built into the ComfortLink™ control.
Follow the procedure below to diagnose and correct EXV
problems. STEP1—CHECKPROCESSOR EXV OUTPUTS — Check
EXV output signals at the J6 and J7 terminals of the EXV board.
Turnunit power off. Connect the positive lead of the meter to terminal 3 on connector J6 on the EXV board. Set meter for approximately 20 vdc. Turn unit power on. Enter and enable the Service Test mode. Locate the appropriate valve under ‘OUTS.’ Select the desired percentage and press En­ter to move the valve. The valve will overdrive in both di­rections when either 0% or 100% are entered. During this time, connect the negative test lead to terminals 1, 2, 4, and 5 in succession. The voltage should fluctuate at each pin. If it remains constant at a voltage or at 0 v, replace the EXV board. If the outputs are correct, then check the EXV.
T otestCircuitB outputs, follow the same procedure above, except connect the positive lead of the meter to terminal 3 on connector J7 on the EXV board and the negative lead to terminals 1, 2, 4, and 5 in succession.
STEP2—CHECKEXVWIRING — Check wiring to EXVs from J6 and J7 terminal strips on EXV board.
1. Check color coding and wire connections. Make sure that
wires are connected to correct terminals at J6 and J7 ter­minal strips and EXV plug connections. Check for cor­rect wiring at driver board input and output terminals. See Fig. 2-4.
2. Check for continuity and tight connection at all pin
terminals.
3. Check plug connections at J6 and J7 terminal strips and
at EXVs. Be sure EXV connections are not crossed.
STEP3—CHECK RESISTANCEOFEXVMOTOR WIND­INGS — Remove plug at J6 and/or J7 terminal strip and check resistance between common lead (red wire, terminal D) and remaining leads A, B, C, and E. Resistance should be 25 ohms ± 2 ohms.
STEP4—CHECK THERMISTORS THAT CONTROLEXV — Check thermistors that control processor output voltage pulses to the EXVs. Circuit A thermistor is T7, and circuit B thermistor is T8. Refer to Fig. 9 and 10 for location.
1. Use service test to determine if thermistors are shorted or
open.
2. Refer to Thermistors section on page 57 for details on
checking thermistor calibration.
50% CAPACITY AT 20 mA
75% CAPACITY AT 12 mA
100% CAPACITY AT 4 mA
0
2
4
6
8
10
12
14
16 18
20
DEMAND LIMIT SIGNAL – 4 - 20 mA INPUT (VOLTS DC)
100
80
60
40
20
0
MAX. ALLOWABLE LOAD (%)
Fig. 21—4to20mADemand Limiting
46
3. Make sure that thermistor leads are connected to the proper pin terminals at the J5 terminal strip on EXV board and that thermistor probes are located in proper position in the refrigerant circuit.
When these checks have been completed, the actual op­eration of the EXV can be checked by using the procedures outlined in Step 5 — Check Operation of the EXV section below.
STEP 5 — CHECK OPERATION OF THE EXV — Use the following procedure tochecktheactualoperationofthe EXVs. The ENABLE/OFF/REMOTE contact switch must be in the OFF position.
1. Close the liquid line service valve for the circuit to be
checked and run through the appropriate service test to pump down the low side of the system. Run lead com­pressor for at least 30 seconds to ensure all refrigerant has been pumped from the low side and that the EXV has been driven fully open (1500 steps).
NOTE: Do not use the Emergency ON-OFF switch to re­cycle the control during this step.
2. Turnoff the compressor circuit breaker(s) and the control
circuit power and then turntheEmergencyON/OFFswitch to the OFF position. Close compressor service valves and remove any remaining refrigerant from the low side of the system.
3. Remove screws holding top cover of EXV. Carefully re-
move topcover,using caution to avoid damage totheO-ring seal and motor leads. If EXV plug was disconnected dur­ing this process, reconnect it after the cover is removed.
4. Note position of lead screw (see Fig. 14). If valve has
responded properly to processor signals in Step 5.1 above, the valve should be fully open and the lead screw should protrude approximately
1
⁄4in. to3⁄4in. above the top of
the motor.
5. Recycle the control by turning the control circuit power
on and switching the Emergency ON-OFF switch to the ON position. This puts the control in initialization mode. During the first 60 seconds of the initialization mode, each valve is driven to the fully closed position (1500 steps) by the processor. With the cover lifted off the EXV valve body, observe the operation of the valve motor and lead screw.The motor shouldturninthe counterclockwise (CCW) direction and the lead screw should move down into the motor hub until the valve isfullyclosed.Leadscrewmove­ment should be smooth and uniform from the fully open to the fully closed position.
6. When test has been completed, carefully reassemble
expansion valve. Be careful not to damage motor or O-ring when reassembling valve. Open compressor serv­ice valves and close compressor circuit breakers. Open
liquid lineservicevalve.Turn the ENABLE/OFF/REMOTE contact switch and allow unit to operate. Verify proper operation of unit.
This process of opening and closing the EXV (EXV.A/ EXV.B under OUTS) can be repeated by using these Service Test steps and recycling the control as described in the pre­ceding steps. If the valve does not operate as described when properly connected to the processor and receiving the cor­rect signals, it should be replaced.
If operating problems persist after reassembly, they may be due to out-of-calibration thermistor(s) or intermittent con­nections between the EXVboardterminalsandtheEXVplug. Recheck all wiring connections and voltage signals.
Other possible causes of improper refrigerant flow con­trol could be restrictions in the liquid line. Check for plugged filter drier(s), restricted metering slots in the EXV, or par­tially closed liquid line service valves. Formation of ice or frost on the lower body of the EXV is one symptom of re­stricted metering slots. Clean or replace the valve if neces­sary.Wrap a wet cloth around the valve if it is to be replaced to prevent the heat from damaging the internal components of the valve.
NOTE: Frosting of the valve is normal during service test and at initial start-up. The frost should dissipate after 5 to 10 minutes operation of a system that is operating properly.
NOTE: The EXV orifice is a screw-in type and may be re­moved for inspection and cleaning. Once the top cover has been removed, the EXV motor may be taken out by remov­ing the 2 cap screws securing motor to valve body. Pull mo­tor, lead screw, and the slide assembly up off the orifice as­sembly. See Fig. 14. A slot has been cut in top of orifice assembly to facilitate removal using a large screwdriver.Turn orifice assembly counterclockwise to remove.
When cleaning or reinstalling orifice assembly, be careful not to damage orifice assembly seals. The bottom seal acts as a liquid shut-off, replacing a liquid line solenoid valve.
Reassembly of valve is made easier by screwing the slide and lead screw assembly out of the motor. Align hole in top of slide with the guide pin in orifice assembly and gently push slide and lead screw onto orifice assembly about half­way. Screw motor onto lead screw and secure EXV motor with cap screws. Be careful not to twist or pull on wires from EXV motor to valve cover pin connections. Check EXV op­eration in quick step steps.
Alarms and Alerts — These are warnings of abnormal
or fault conditions, and may cause either one circuit or the whole unit to shut down. They are assigned code numbers as described in Table 27.
47
Table 27 — Alarm and Alert Codes
ALARM/
ALERT
CODE
ALARM
OR
ALERT
DESCRIPTION
WHY WAS THIS
ALARM
GENERATED?
ACTION TAKEN
BY CONTROL
RESET
METHOD
PROBABLE
CAUSE
51 Alert Circuit A, Compressor 1
Failure
Compressor feedback signal does not match relay state
Circuit A shut down. Manual High-pressure or loss-of-
charge switch open, faulty control relay or CPCS board, loss of condenser air, liquid valve closed, op­eration beyond capability.
52 Alert Circuit A, Compressor 2
Failure
Compressor feedback signal does not match relay state
Circuit A shut down. Circuit restarted in 1 minute. Compressor A2 not used until alarm is reset.
Manual High-pressure switch open,
faulty control relay or CPCS board, loss of condenser air, liquid valve closed, op­eration beyond capability.
53 Alert Circuit A, Compressor 3
Failure
Compressor feedback signal does not match relay state
Circuit A shut down. Circuit restarted in 1 minute. Compressor A3 not used until alarm is reset.
Manual High-pressure switch open,
faulty control relay or CPCS board, loss of condenser air, liquid valve closed, op­eration beyond capability.
54 Alert Circuit A, Compressor 4
Failure
Compressor feedback signal does not match relay state
Circuit A shut down. Circuit restarted in 1 minute. Compressor A4 not used until alarm is reset.
Manual High-pressure switch open,
faulty control relay or CPCS board, loss of condenser air, liquid valve closed, op­eration beyond capability.
55 Alert Circuit B, Compressor 1
Failure
Compressor feedback signal does not match relay state
Circuit B shut down. Manual High-pressure or loss-of-
charge switch open, faulty control relay or CPCS board, loss of condenser air, liquid valve closed, op­eration beyond capability.
56 Alert Circuit B, Compressor 2
Failure
Compressor feedback signal does not match relay state
Circuit B shut down. Circuit restarted in 1 minute. Compressor B2 not used until alarm is reset.
Manual High-pressure switch open,
faulty control relay or CPCS board, loss of condenser air, liquid valve closed, op­eration beyond capability.
57 Alert Circuit B, Compressor 3
Failure
Compressor feedback signal does not match relay state
Circuit B shut down. Circuit restarted in 1 minute. Compressor B3 not used until alarm is reset.
Manual High-pressure switch open,
faulty control relay or CPCS board, loss of condenser air, liquid valve closed, op­eration beyond capability.
60 Alarm Cooler Leaving Fluid
Thermistor Failure (T1)
Thermistor outside range of −40 to 245 F (−40 to 118 C)
Chiller shutdown after pumpdown complete.
Automatic Thermistor failure, damaged
cable/wire or wiring error.
61 Alarm Cooler Entering Fluid
Thermistor Failure (T2)
Thermistor outside range of −40 to 245 F (−40 to 118 C)
Chiller shutdown after pumpdown complete.
Automatic Thermistor failure, damaged
cable/wire or wiring error.
64 Alert Circuit A Saturated Con-
densing Thermistor Fail­ure (T3)
Thermistor outside range of −40 to 245 F (−40 to 118 C)
Circuit A shutdown after pumpdown com­plete. (EXV only)
Automatic Thermistor failure, damaged
cable/wire or wiring error.
65 Alert Circuit B Saturated Con-
densing Thermistor Fail­ure (T4)
Thermistor outside range of −40 to 245 F (−40 to 118 C)
Circuit B shutdown after pumpdown complete.
Automatic Thermistor failure, damaged
cable/wire or wiring error.
66 Alert Circuit A Saturated Suc-
tion Thermistor Failure (T5)
Thermistor outside range of −40 to 245 F (−40 to 118 C)
Circuit A shutdown after pumpdown com­plete. (EXV only)
Automatic Thermistor failure, damaged
cable/wire or wiring error.
67 Alert Circuit B Saturated Suc-
tion Thermistor Failure (T6)
Thermistor outside range of −40 to 245 F (−40 to 118 C)
Circuit B shutdown after pumpdown complete.
Automatic Thermistor failure, damaged
cable/wire or wiring error.
68 Alert Compressor A1 Suction
Gas Thermistor Failure (T7)
Thermistor outside range of −40 to 245 F (−40 to 118 C)
Circuit A shutdown after pumpdown com­plete. (EXV only).
Automatic Thermistor failure, damaged
cable/wire or wiring error.
69 Alert Compressor B1 Suction
Gas Thermistor Failure (T8)
Thermistor outside range of −40 to 245 F (−40 to 118 C)
Circuit B shutdown after pumpdown com­plete. (EXV only).
Automatic Thermistor failure, damaged
cable/wire or wiring error.
73 Alert Outside Air Thermistor
Failure (T9)
Thermistor outside range of −40 to 245 F (−40 to 118 C)
Temperature reset dis­abled. Chiller runs un­der normal control/set points.
Automatic Thermistor failure, damaged
cable/wire or wiring error.
74 Alert Space Temperature
Thermistor Failure (T10)
Thermistor outside range of −40 to 245 F (−40 to 118 C)
Temperature reset dis­abled. Chiller runs un­der normal control/set points.
Automatic Thermistor failure, damaged
cable/wire or wiring error.
77 Alert Circuit A Saturated
Suction Temperature exceeds Cooler Leaving Fluid Temperature
Saturated suction is greater than leaving fluid temperature for more than 5 minutes
Circuit A shutdown after pumpdown complete.
Automatic Faulty expansion valve or
EXV board, faulty cooler suction thermistor (T5) or leaving fluid thermistor (T1).
78 Alert Circuit B Saturated
Suction Temperature exceeds Cooler Leaving Fluid Temperature
Saturated suction is greater than leaving fluid temperature for more than 5 minutes
Circuit B shutdown after pumpdown complete
Automatic Faulty expansion valve or
EXV board, faulty cooler suction thermistor (T6) or leaving fluid thermistor (T1).
48
Table 27 — Alarm and Alert Codes (cont)
ALARM/
ALERT
CODE
ALARM
OR
ALERT
DESCRIPTION
WHY WAS THIS
ALARM
GENERAED?
ACTION TAKEN
BY CONTROL
RESET
METHOD
PROBABLE
CAUSE
112 Alert Circuit A High Suction
Superheat
If EXV is greater than 98%, suction superheat is greater than 75 F (41.7 C) and saturated suction tem­perature is less than MOP for 5 minutes
Circuit A shutdown after pumpdown complete.
Manual Faulty expansion valve
or EXV board, low re­frigerant charge, plugged filter drier, faulty suction gas ther­mistor (T7) or cooler thermistor (T5).
113 Alert Circuit B High Suction
Superheat
If EXV is greater than 98%, suction superheat is greater than 75 F (41.7 C) and saturated suction tem­perature is less than MOP for 5 minutes
Circuit B shutdown after pumpdown complete.
Manual Faulty expansion valve
or EXV board, low re­frigerant charge, plugged filter drier, faulty suction gas ther­mistor (T8) or cooler thermistor (T6).
114 Alert Circuit A Low Suction
Superheat
If EXV is greater than 10%, and either suction superheat is less than 19 F (10.6 C) or saturated suction temperature is greater than MOP for 5 minutes
Circuit A shutdown after pumpdown complete.
Automatic restart after first daily occurrence. Manual restart thereafter.
Faulty expansion valve or EXV board, faulty suction gas thermistor (T7) or cooler ther­mistor (T5).
115 Alert Circuit B Low Suction
Superheat
If EXV is greater than 10%, and either suction superheat is less than 19 F (10.6 C) or saturated suction temperature is greater than MOP for 5 minutes
Circuit B shutdown after pumpdown complete.
Automatic restart after first daily occurrence. Manual restart thereafter.
Faulty expansion valve or EXV board, faulty suction gas thermistor (T8) or cooler ther­mistor (T6).
116 Alert Circuit A Low Cooler
Suction Temperature
1. If the saturated suction temperature is 24 to 29° F (13.3 to 16.1° C) below cooler LWT and is also 2° F (1.1° C) less than freeze*
2. If the saturated suction temperature is 30° F (16.7° C) below cooler LWT and is also 2° F (1.1° C) less than freeze* for 10 minutes
1. Mode 7 initiated. No additional capacity in­creases. Alert not tripped.
2. Circuit shutdown without going through pump­down.
1. Automatic reset if corrected.
2. Manual
Faulty expansion valve or EXV board, low re­frigerant charge, plugged filter drier, faulty suction gas ther­mistor (T7) or cooler thermistor (T5), low cooler fluid flow.
117 Alert Circuit B Low Cooler
Suction Temperature
1. If the saturated suction temperature is 24 to 29° F (13.3 to 16.1° C) below cooler LWT and is also 2° F (1.1° C) less than freeze*
2. If the saturated suction temperature is 30° F (16.7° C) below cooler LWT and is also 2° F (1.1° C) less than freeze* for 10 minutes
1. Mode 8 initiated. No additional capacity in­creases. Alert not tripped.
2. Circuit shutdown without going through pump­down.
1. Automatic reset if corrected.
2. Manual
Faulty expansion valve or EXV board, low re­frigerant charge, plugged filter drier, faulty suction gas ther­mistor (T8) or cooler thermistor (T6), low cooler fluid flow.
118 Alert Circuit A Low Oil
Pressure
Oil pressure switch open after 1 minute of continu­ous operation
Circuit shutdown without going through pumpdown.
Manual Oil pump failure, low
oil level, switch failure or compressor circuit breaker tripped.
119 Alert Circuit B Low Oil
Pressure
Oil pressure switch open after 1 minute of continu­ous operation
Circuit shutdown without going through pumpdown.
Manual Oil pump failure, low
oil level, switch failure or compressor circuit breaker tripped.
LEGEND
CCN Carrier Comfort Network CPCS — Compressor Protection Control System CXB Compressor Expansion Board EMM — Energy Management Module EXV Electronic Expansion Valve FSM Flotronic™ System Manager MBB — Main Base Board MOP — Maximum Operating Pressure WSM — Water System Manager
*Freeze is defined as 34° F (1.1 C) for water. For brine fluids, freeze is CSP.1 −8° F (4.4 C) for single set point and lower of CSP.1/CSP.2
−8° F (4.4 C) for dual set point configuration. NOTE: The following table shows illegal configurations:
1 Zero compressors in a circuit 2 Four compressors in a circuit with two unloaders
3
Four compressors in a circuit with one unloader and hot gas bypass
4 Two unloaders and hot gas bypass in a circuit. 5 More than one compressor quantity difference between circuits 6 Fluid type of low temperature brine
7
Air cooled head pressure control with common fan staging and different head pressure control methods for each circuit.
49
Table 27 — Alarm and Alert Codes (cont)
ALARM/ ALEERT
CODE
ALARM
OR
ALERT
DESCRIPTION
WHY WAS THIS
ALARm
GENERATED?
ACTION TAKEN
BY CONTROL
RESET
METHOD
PROBABLE
CAUSE
150 Alarm Emergency Stop CCN emergency stop
command received
Chiller shutdown with­out going through pumpdown.
Automatic once CCN command for EMSTOP returns to normal
CCN Network command.
151 Alarm Illegal Configuration One or more of the
illegal configurations shown in the Note be­low exists.
Chiller is not allowed to start.
Manual once configu­ration errors are corrected
Configuration error. See Note on page 49.
152 Alarm Unit Down Due to
Failure
Both circuits are down due to alarms/alerts.
Chiller is unable to run. Automatic once
alarms/alerts are cleared that prevent the chiller from starting.
Alarm notifies user that chiller is 100% down.
153 Alarm Real Time Clock Hard-
ware Failure
Internal clock on MBB fails
Occupancy schedule will not be used. Chiller defaults to Local On mode.
Automatic when cor­rect clock control restarts.
Main Base Board failure.
154 Alarm Serial EEPROM Hard-
ware Failure
Hardware failure with MBB
Chiller is unable to run. Manual Main Base Board
failure.
155 Alert Serial EEPROM Stor-
age Failure
Configuration/storage failure with MBB
No Action Manual Potential failure of
MBB. Download cur­rent operating soft­ware. Replace MBB if error occurs again.
156 Alarm Critical Serial
EEPROM Storage Failure
Configuration/storage failure with MBB
Chiller is not allowed to run.
Manual Main Base Board
failure.
157 Alarm A/D Hardware Failure Hardware failure with
peripheral device
Chiller is not allowed to run.
Manual Main Base Board
failure.
170 Alert Loss of Communica-
tion with CXB
MBB loses communi­cation with CXB
Compressors A3, A4 and B3 and unloaders A2/B2 unable to operate.
Automatic Wiring error, faulty
wiring or failed CXB module.
172 Alarm Loss of Communica-
tion with EXV
MBB loses communi­cation with EXV
Chiller shutdown with­out going through pumpdown.
Automatic Wiring error, faulty
wiring or failed EXV module.
173 Alert Loss of Communica-
tion with EMM
MBB loses communi­cation with EMM
4 to 20 mA tempera­ture reset disabled. Demand Limit set to 100%. 4 to 20 mA set point disabled.
Automatic Wiring error, faulty
wiring or failed Energy Manage­ment Module (EMM).
174 Alert 4 to 20 mA Cooling Set
Point Input Failure
If configured with EMM and input less than 2 mA or greater than 22 mA
Set point function dis­abled. Chiller controls to CSP1.
Automatic Faulty signal generator,
wiring error, or faulty EMM.
176 Alert 4 to 20 mA Tempera-
ture Reset Input Fail­ure
If configured with EMM and input less than 2 mA or greater than 22 mA
Reset function dis­abled. Chiller returns to normal set point control.
Automatic Faulty signal generator,
wiring error, or faulty EMM.
177 Alert 4 to 20 mA Demand
Limit Input Failure
If configured with EMM and input less than 2 mA or greater than 22 mA
Demand limit function disabled. Chiller re­turns to 100% demand limit control.
Automatic Faulty signal generator,
wiring error, or faulty EMM.
200 Alarm Cooler Pump Interlock
Failure to Close at Start-Up
If configured for cooler pump control and cooler pump interlock not closed within 1 minute after pump is started
Cooler pump shut off. Chiller shutdown with­out going through pumpdown.
Manual Failure of cooler pump
or controls.
201 Alarm Cooler Pump Interlock
Opened During Normal Operation
If configured for cooler pump control and inter­lock opens while cooler pump relay is on
Cooler pump shut off. Chiller shutdown with­out going through pumpdown.
Manual Failure of cooler pump
or controls.
202 Alarm Cooler Pump Interlock
Closed When Pump is Off
If configured for cooler pump control and inter­lock closes while cooler pump relay is off
Chiller is not allowed to start.
Manual Failure of cooler pump
relay or interlock, welded contacts.
50
Table 27 — Alarm and Alert Codes (cont)
ALARM/ ALEERT
CODE
ALARM OR
ALERT
DESCRIPTION
WHY WAS THIS
ALARm
GENERATED?
ACTION TAKEN
BY CONTROL
RESET
METHOD
PROBABLE
CAUSE
203 Alert Loss of Communica-
tion with Slave Chiller
Master MBB loses communication with Slave MBB
Dual chiller control dis­abled. Chiller runs as a stand-alone machine.
Automatic Wiring error, faulty wir-
ing, failed Slave MBB module, power loss at Slave chiller, wrong slave address.
204 Alert Loss of Communica-
tion with Master Chiller
Slave MBB loses com­munication with Master MBB
Dual chiller control dis­abled. Chiller runs as a stand-alone machine
Automatic Wiring error, faulty wir-
ing, failed Master MBB module, power loss at Master chiller.
206 Alert High Leaving Chilled
Water Temperature
LWT read is greater than LCW Alert Limit, Total capacity is 100% and LWT is greater than LWT reading one minute ago
Alert only. No action taken.
Automatic Building load greater
than unit capacity, low water/brine flow or compressor fault. Check for other alarms/alerts.
207 Alarm Cooler Freeze Protec-
tion
Cooler EWT or LWT is less than freeze*
Chiller shutdown with­out going through pumpdown. Cooler pump continues to run (if control enabled).
Automatic for first occurrence of day. Manual reset thereafter.
Faulty thermistor (T1/ T2), low water flow.
208 Alarm Low Cooler Fluid Flow Cooler EWT is less
than LWT by 3° F (1.7° C) for 1 minute after a circuit is started
Chiller shutdown with­out going through pumpdown. Cooler pump shut off (if con­trol enabled).
Manual Faulty cooler pump,
low water flow, plugged fluid strainer.
950 Alert Loss of Communica-
tion with WSM
No communications have been received by MBB within 5 minutes of last transmission
WSM forces removed. Chiller runs under own control.
Automatic Failed module, wiring
error, failed trans­former, loose connec­tion plug, wrong address.
951 Alert Loss of Communica-
tion with FSM
No communications have been received by MBB within 5 minutes of last transmission
FSM forces removed. Chiller runs under own control.
Automatic Failed module, wiring
error, failed trans­former, loose connec­tion plug, wrong address.
LEGEND
CCN Carrier Comfort Network CPCS — Compressor Protection Control System CXB Compressor Expansion Board EMM — Energy Management Module EXV Electronic Expansion Valve FSM Flotronic™ System Manager MBB — Main Base Board MOP — Maximum Operating Pressure WSM — Water System Manager
*Freeze is defined as 34° F (1.1 C) for water. For brine fluids, freeze is CSP.1 −8° F (4.4 C) for single set point and lower of CSP.1/CSP.2
−8° F (4.4 C) for dual set point configuration. NOTE: The following table shows illegal configurations:
1 Zero compressors in a circuit 2 Four compressors in a circuit with two unloaders
3
Four compressors in a circuit with one unloader and hot gas bypass
4 Two unloaders and hot gas bypass in a circuit. 5 More than one compressor quantity difference between circuits 6 Fluid type of low temperature brine
7
Air cooled head pressure control with common fan staging and different head pressure control methods for each circuit.
51
SERVICE
ELECTRIC SHOCK HAZARD. Turn off all power to unit before servicing.
The ENABLE/OFF/REMOTE CONTACT switch on control panel does not shut off con­trol power; use field disconnect.
Electronic Components
CONTROLCOMPONENTS— Unit uses an advanced elec­tronic control system that normally does not require service. For details on controls refer to Operating Data section.
30GTN,R040-110,AND 230B-315B UNIT CONTROLBOX — When facing compressors, main control box is at left end of unit. All incoming power enters through main box. Con­trol box contains power components and electronic controls.
Outer panels are hinged and latched for easy opening. Re­move screws to remove inner panels. Outer panels can be held open for service and inspection by using door re­tainer on each panel. To use door retainers: remove bottom pin from door retainer assembly, swing retainer out horizon­tally,andengagepin in one of the retainer ears and the hinge assembly.
30GTN,R130-210, 230A-315A,AND330A/B-420A/B UNIT CONTROLAND MAIN POWER BOXES—The main power box is on the cooler side of the unit, and the control box is on the compressor side. Outer panels are hinged and latched for easy opening. Remove screws to remove inner panels.
Compressors — If lead compressor on either refriger-
ant circuit becomes inoperativeforanyreason,circuitis locked offandcannotbe operated due to features built into the elec­tronic control system. Do not attempt to bypass controls to
force compressors to run.
COMPRESSOR REMOVAL — Access to the pump end of the compressor is from the compressor side of the unit. Access to the motor end of the compressor is from the inside of the unit. All compressors can be removed from the com­pressor side of the unit.
IMPORTANT:All compressor mounting hardware and support brackets removed during servicing must be re­installed prior to start-up.
Following the installation of the new compressor: Tighten discharge valves to —
Compressor(s)
20 to 25 ft-lb (27 to 34 N-m) 06E250
80 to 90 ft-lb (109 to 122 N-m) 06E265,275,299 Tighten suction valves to —
80 to 90 ft-lb (109 to 122 N-m) 06E250
90 to 120 ft-lb (122 to 163 N-m) 06E265,275,299 Tighten the following fittings to —
120 in.-lb (13.5 N-m) High-Pressure Switch OIL CHARGE (Refer to Table 28) — All units are factory
charged with oil. Acceptable oil level for each compressor is from
1
⁄8to3⁄8of sight glass.
When additional oil or a complete charge is required, use only Carrier-approved compressor oil.
Approved oils are as follows: Petroleum Specialties, Inc. — Cryol 150 (factory oil charge) Texaco, Inc. — Capella WF-32 Witco Chemical Co. — Suniso 3GS
Table 28 — Oil Charge
COMPRESSOR
OIL REQUIRED
Pts L
06E250 14 6.6 06E265 19 9.0 06E275 19 9.0 06E299 19 9.0
Do not reuse drained oil or any oil that has been exposed
to atmosphere.
Cooler — The cooler is easily accessible from the cooler
side of the unit. The refrigerant feed components are acces­sible from the control box end of the unit.
COOLER REMOVAL — Cooler can be removed from the cooler side of the unit as follows:
Open and tag all electrical disconnects before any work begins. Note that cooler is heavy and both fluid-side and refrigerant-side may be under pressure.
1. To ensure the refrigerant is in the condenser, follow this procedure:
a. Open the circuit breakers and close the discharge valves
for the lag compressors in both circuits.
Do not close the discharge valve ofanoperatingcom­pressor. Severe damage to the compressor can result.
b. Afterthelag compressor dischargeservicevalves have
been closed, close the liquid line service valve for one circuit. Allow the lead compressor to pump down that circuit until it reaches approximately 10 to 15 psig (68.8 to 103.2 kPa).
c. Assoon as the system reaches that pressure, shut down
the lead compressor by opening the compressor cir­cuit breaker, then quickly close the discharge service valve for that compressor.
d. Repeat the procedure for the other circuit.
2. Close the shutoff valves, if installed, in the cooler fluid lines. Remove the cooler fluid piping.
3. Cooler may be under pressure. Open the air vent at the top of the cooler, and open the drain on the bottom of the cooler (near the leaving fluid outlet) to drain the cooler. Both the drain and the air vent are located on the leaving fluid end of cooler. See Fig. 22. Remove the cooler waterside strainer.
4. Disconnect the conduit and cooler heater wires, if equipped. Remove all thermistors from the cooler, being sure to la­bel all thermistors as they are removed. Thermistor T1 is a well-type thermistor, and thermistor T2 is immersed directly in the fluid. See Fig. 22.
5. Remove the insulation on the refrigerant connection end of the cooler.
6. Unbolt the suction flanges from the cooler head. Save the bolts.
7. Remove the liquid lines by breaking the silver-soldered joints at the cooler liquid line nozzles.
8. On 30GTN,GTR080-110 and 230B-315B units, remove the vertical support(s) under the condenser coil in front of the cooler.Providetemporarysupportasneeded. Save all screws for reinstallation later.
9. Remove the screws in the cooler feet. Slide the cooler slightly to the left to clear the refrigerant tubing. Save all screws.
52
Removing the cooler can be accomplished inoneof2ways, depending on the jobsite. Either continue sliding the cooler toward the end of the unit opposite the tubing and carefully remove, or pivot the cooler and remove it from the cooler side of the unit.
REPLACING COOLER — To replace the cooler:
1. Insertnewcoolercarefullyintoplace. Reattach the screws
into the cooler feet (using saved screws). On 30GTN,GTR080-110 and 230B-315B units, reattach the 2 vertical supports under the condenser coil in front of the cooler using screws saved.
2. Replace the liquid lines and solder at the cooler liquid
line nozzles.
3. Reboltthesuction flanges onto the cooler head using bolts
saved during removal. Use new gaskets for the suction line flanges. Use compressor oil to aid in gasket sealing and tighten the suction flange bolts to 70 to 90 ft-lb (94 to 122 N-m).
NOTE: The suction flange has a 4-bolt pattern. See Carrier specified parts for replacement part number, if necessary.
4. Using adhesive, reinstall the cooler insulation on the re-
frigerant connection end of the cooler.
5. Reinstall the thermistors. Refer to Thermistors section on
page 57, and install as follows: a. Apply pipe sealant to the
1
⁄4-in. NPT threads on the replacement coupling for the fluid side, and install it in place of the original.
Do not use the packing nut to tighten the coupling. Damage to the ferrules will result.
b. Reinstall thermistor T1 well, and insert thermistor T1
into well.
c. Install thermistor T2 (entering fluid temperature) so that
it is not touching an internal refrigerant tube, but so that it is close enough to sense a freeze condition. The recommended distance is
1
⁄8in. (3.2 mm)fromthecooler tube.T ightenthepacking nut finger tight, and thentighten 11⁄4turns more using a back-up wrench.
6. Install the cooler heater and conduit (if equipped), con­necting the wires as shown in the unit wiring schematic located on the unit.
7. Close the air vent at the top of the cooler, and close the drain on the bottom of the cooler near the leaving fluid outlet. Both the drain and the air vent are located on the leaving fluid end of the cooler. See Fig. 22.
8. Reconnect the cooler fluid piping and strainer, and open the shutoff valves (if installed). Purge the fluid of all air before starting unit.
9. Openthe dischargeservicevalves,close the circuit break­ers, and open the liquid line service valves for the compressors.
SERVICING THE COOLER — When cooler heads and par­tition plates are removed, tube sheets are exposed showing ends of tubes.
Certain tubes in the 10HB coolers cannot be removed. Eight tubes in the bundle are secured inside the cooler to the baffles and cannot be removed. These tubes are marked by a dimple on the tube sheet. See Fig. 23. If
any of these tubes have developed a leak, plug the tube(s) as described under Tube Plugging section on page 54.
Fig. 22 — Cooler Thermistor Locations
53
Tube Plugging — A leaky tube can be plugged until retub­ing can be done. The number of tubes plugged determines how soon cooler must be retubed. Tubes plugged in the fol­lowing locations will affect the performance of the unit: Any tube in the area, particularly the tube that thermistor T2 is adjacent to, will affectunitreliabilityandperformance.Ther­mistor T2 is used in the freeze protection algorithm for the controller.Ifseveraltubes require plugging, check with your local Carrier representative to find out how number and lo­cation can affect unit capacity.
Figure 24 shows an Elliott tube plug and a cross-sectional
view of a plug in place.
Use extreme care when installing plugs to prevent dam­age to the tube sheet section between the holes.
Retubing (See Table 29) — When retubing is to be done, obtain service of qualified personnel experienced in boiler maintenance and repair.Moststandardprocedurescanbefol­lowed when retubing the 10HB coolers. An 8% crush is rec­ommended when rolling replacement tubes into the tube sheet. An 8% crush can be achieved by setting the torque on the gun at 48 to 50 in.-lb (5.4 to 5.6 N-m).
The following Elliott Co. tube rolling tools are required:
B3400 Expander Assembly B3401 Cage B3405 Mandrel B3408 Rolls
Place one drop of Loctite No. 675 or equivalent on top of tube prior to rolling. This material is intended to ‘‘wick’’ into the area of the tube that is not rolled into the tube sheet, and prevent fluid from accumulating between the tube and the tube sheet.
Table 29 — Plugs
COMPONENTS FOR
PART NUMBER
PLUGGING
For Tubes
Brass Pin 853103-500* Brass Ring 853002-570*
ForHoleswithoutTubes
Brass Pin 853103-1* Brass Ring 853002-631*
Loctite No. 675†
Locquic ‘‘N’’†
*Order directly from: Elliott Tube Company,
Dayton, Ohio
†Can be obtained locally.
Tube information follows:
in. mm
• Tube sheet hole diameter ............0.631 16.03
• TubeOD.........................0.625 15.87
• Tube ID after rolling ...............0.581 14.76
(includes expansion due to to to clearance) 0.588 14.94
NOTE: Tubes next to gasket webs must be flush with tube sheet (both ends).
SIZES 040-050 SIZES 060,070
SIZES 080,090* SIZES 100,110*
SIZES 130,150* SIZES 170,190*
SIZE 210*
*And associated modular units (see Table 1).
Fig. 23 — Typical Tube Sheets, Cover Off (Non-Removable Tubes)
Fig. 24 — Eliott Tube Plug
54
Tightening Cooler Head Bolts Gasket Preparation — When reassembling cooler heads, al-
ways use new gaskets. Gaskets are neoprene-based and are brushed with a light film of compressor oil. Do not soak gas- ket or gasket deterioration will result. Use new gaskets within 30 minutes to prevent deterioration. Reassemble cooler nozzle end or plain end cover of the cooler with the gaskets. Torque all cooler bolts to the following specification and sequence:
5
⁄8-in. Diameter Perimeter Bolts ......150to170ft-lb
(201 to 228 N-m)
1
⁄2-in. Diameter Flange Bolts ..........70to90ft-lb
(94 to 121 N-m)
1. Install all bolts finger tight.
2. Bolt tightening sequence is outlined in Fig. 25. Follow the numbering or lettering sequence so that pressure is evenly applied to gasket.
3. Apply torque in one-third steps until required torque is reached. Load all bolts to each one-third step before pro­ceeding to next one-third step.
4. No less than one hour later, retighten all bolts to required torque values.
5. After refrigerant is restored to system, check for refrig­erant leaks with soap solution or Halide device.
6. Replace cooler insulation.
Condenser Coils
COIL CLEANING — Clean coils with a vacuum cleaner, fresh water,compressedair, or a bristle brush (not wire). Units
installed in corrosive environments should have coil clean­ing as part of a planned maintenance schedule. In this type of application, all accumulations of dirt should be cleaned off the coil.
Do not use high-pressure water or air to clean coils — fin damage may result.
Condenser Fans — Each fan is supported by a formed
wire mount bolted to fan deck and covered with a wire guard. The exposed end of fan motor shaft is protected from weather by grease. If fan motor must be removed for service or replacement, be sure to regrease fan shaft and reinstall fan guard. For proper performance, fan should be positioned as in Fig. 26A and 26B (standard and low-noise applications). Tighten setscrews to 15 6 1 ft-lb (20 6 1.3 N-m).
If the unit is equipped with the high-static fan option, the fan must be set from the top of the fan deck to the plastic ring or center of the fan to a distance of 2.13 in. 6 0.12 in. (54 6 3 mm). This is differentfromstandardfans,sincethere is no area available to measure from the top of the orifice ring to the fan hub itself. See Fig. 27.
IMPORTANT: Check for proper fan rotation (clock­wise viewed from above). If necessary, switch any 2 power leads to reverse fan rotation.
SIZES 080,090* WITH 18-BOLT HEADS
SIZES 080,090* WITH 14-BOLT HEADS
SIZES 100,110* WITH 22-BOLT HEADS
SIZES 100,110* WITH 16-BOLT HEADS
SIZES 130,150*
SIZES 170,190*
SIZE 210*
*And associated modular units.
Fig. 25 — Cooler Head Bolt Tightening Sequence (Typical Tube Sheet)
55
Refrigerant Feed Components — Each circuit has
all necessary refrigerant controls. ELECTRONIC EXPANSION VALVE(EXV) —Acutaway
view of valve is shown in Fig. 28.
High-pressure liquid refrigerant enters valve through bot­tom. A series of calibrated slots have been machined in side of orifice assembly .As refrigerant passes through orifice, pres­sure drops and refrigerant changes to a 2-phase condition (liquid and vapor). To control refrigerant flow for different operating conditions, a sleeve moves up and down over ori­fice and modulates orifice size. Asleeveis moved by a linear stepper motor.Steppermotormovesinincrementsandiscon­trolled directly by EXV module. As stepper motor rotates, motion is transferred into linear movement by lead screw. Through stepper motor and lead screw, 1500 discrete steps of motion are obtained. The large number of steps and long stroke results in very accurate control of refrigerant flow.The minimum position for operation is 120 steps.
The EXV module controls the valve. The lead compressor in each circuit has a thermistor located in the suction mani­fold after the compressor motor and a thermistor located in a well where the refrigerant enters the cooler. The ther­mistors measure the temperature of the superheated gas en­tering the compressor cylinders and the temperature of the refrigerant entering the cooler. The difference between the temperature of the superheated gas and the cooler suction temperature is the superheat. The EXV module controls the position of the electronic expansion valve stepper motor to maintain 29 F (16 C) superheat.
The superheat leaving cooler is approximately 3° to 5° F (2° to 3° C), or less.
Because EXV status is communicated to the Main Base Board (MBB) and is controlled by the EXV modules (see Fig. 27), it is possible to track the valve position. By this means, head pressure is controlledandunitisprotectedagainst loss of charge and a faulty valve. During initial start-up, EXV is fully closed. After initialization period, valve position is tracked by the EXV module by constantly monitoring amount of valve movement.
The EXV is also used to limit cooler saturated suction tem­perature to 50 F (10 C). This makes it possible for the chiller to start at higher cooler fluid temperatures without overload­ing the compressor. This is commonly referred to as MOP (maximum operating pressure).
If it appears that EXV is not properly controlling circuit operation to maintain correct superheat, there are a number of checks that can be made using test functions and initial­ization features built intothemicroprocessorcontrol.SeeServ­ice Test section on page 29 to test EXVs.
DIMENSION
FAN TYPE
Standard Low Noise (Optional)
A 0.509 (13 mm) 1.509 (38 mm) B 0.889 (22 mm) 1.139 (29 mm)
NOTE: Fan rotation is clockwise as viewed from top of unit.
Fig. 26A — Condenser Fan Adjustment —
Standard 50 and 60 Hz Units and
60 Hz Low Noise Fan Option Units
PLASTIC FAN PROPELLER
CLEARANCE OF 0.25 INCHES (6.4 MM)
FAN DECK SURFACE
FAN ORIFICE
Fig. 26B — Condenser Fan Adjustment —
50 Hz Low Noise Fan Option Units
NOTE: Dimensionsare in millimeters.Dimensionsin [ ] areininches.
Fig. 27 — Condenser Fan Adjustment,
Units with High-Static Fan Option
Fig. 28 — Electronic Expansion Valve (EXV)
56
NOTE: The EXV orifice is a screw-in type that can be re­moved for inspection and cleaning. Once the top cover has been removed, the EXV motor may be taken out by remov­ing the 2 cap screws securing motor to valve body. Pull mo­tor, lead screw, and the piston sleeve up off the orifice as­sembly. See Fig. 28. A slot has been cut in top of orifice assembly to facilitate removal using a large screwdriver.Turn orifice assembly counterclockwise to remove.
When cleaning or reinstalling orifice assembly, be careful not to damage orifice assembly seals. The bottom seal acts as a liquid shut-off, replacing a liquid line solenoid valve.
Reassembly of valve is made easier by screwing the pis­ton sleeve and lead screw assembly out of the motor. Align hole in top of piston sleeve with the guide pin in orifice as­sembly and gently push piston sleeve and lead screw onto orifice assembly about half way.Screw motor onto lead screw and secure EXV motor with cap screws. Be careful not to twist or pull on wires from EXV motor to valve cover pin connections. Check EXV operation using test functions de­scribed in the Service Test section on page 29.
MOISTURE-LIQUID INDICATOR — Clear flow of liquid refrigerant indicates sufficient charge in system. Bubbles in the sight glass indicate undercharged system or presence of noncondensables. Moisture in system measured in parts per million (ppm), changes color of indicator:
Green — moisture is below 45 ppm;
Yellow-green (chartreuse) — 45 to 130 ppm (caution);
Yellow (wet) — above 130 ppm.
Change filter drier at first sign of moisture in system.
IMPORTANT: Unit must be in operation at least 12 hours before moisture indicator can give an accu­rate reading. Withunit running, indicating element must be in contact with liquid refrigerant to give true reading.
FILTER DRIER — Whenever moisture-liquid indicator shows presence of moisture, replace filter drier(s). There is one fil­ter drier on each circuit. Refer to Carrier Standard Service Techniques Manual, Chapter 1, Refrigerants, for details on servicing filter driers.
LIQUID LINE SOLENOID VALVE — All TXV units have a liquid line solenoid valve to prevent liquid refrigerant mi­gration to low side of system during the off cycle.
LIQUID LINE SERVICE VALVE — This valve is located immediately ahead of filter drier, and has a
1
⁄4-in. Schrader connection for field charging. In combination with compres­sor discharge service valve, each circuit can be pumped down into the high side for servicing.
Thermistors — Electronic control uses 4 to 10 ther-
mistors to sense temperatures used to control the operation of chiller.
Thermistors T1-T9 are identical in their temperature vs resistance and voltage drop performance. Thermistor T10 is a10kVinput channel and has a different set of temperature vs resistance and voltage drop performance. Resistances at various temperatures are listed in Tables 30A-31B.
LOCATION — General locations of thermistor sensors are shown in Fig. 7-10. See Table 2 for pin connection points.
Sensor T2 is installed directly in the fluid circuit. Re­lieve all pressure or drain fluid before removing.
REPLACING THERMISTOR T2
1. Remove and discard original sensor and coupling. Do not
disassemble new coupling. Install assembly as received. See Fig. 30.
2. Apply pipe sealant to
1
⁄4-in. NPT threads on replacement coupling, and install in place of original. Do not use the packing nut to tighten coupling. Damage to ferrules will result.
3. Thermistor T2 (entering fluid temperature) should not be touching an internal refrigerant tube, but should be close enough to sense a freeze condition. Recommended distance is
1
⁄8in. (3.2 mm) from cooler tube. Tightenpack­ing nut finger tight to position ferrules, then tighten 11⁄4turns more using a back-up wrench. Ferrules are now attached to the sensor, which can be withdrawn from cou­pling for service.
3
3
1
2
4
5
1 2 3
4
5
1 2 3
4
5
1
2
4 5
BRN WHT RED
BLK
GRN
A E D
B C
PL-EXVB
EXV-B
BRN WHT RED
BLK
GRN
J7
J6
PL-EXVA
C
B
D
A E
EXV-A
ELECTRONIC EXPANSION VALVES (EXVs)
Fig. 29 — Printed Circuit Board Connector
FLUID-SIDE TEMPERATURE SENSOR (T1) AND
REFRIGERANT TEMPERATURE SENSOR (T5, T6, T7, T8)
FLUID-SIDE TEMPERATURE SENSOR (T2)
NOTE: Dimensions in ( ) are in millimeters.
Fig. 30 — Thermistors (Temperature Sensors)
57
REPLACING THERMISTORS T1, T5, T6, T7, AND T8 — Add a small amount of thermal conductive grease to ther­mistor well. Thermistors are friction-fit thermistors, which must be slipped into receivers located in the cooler leaving fluid nozzle for T1, in the cooler head for T5 and T6 (EXV units only), and in the compressor pump end for T7 and T8 (EXV units only).
THERMISTORS T3 AND T4 — These thermistors are lo­cated on header end of condenser coil. They are clamped on a return bend.
THERMISTOR/TEMPERATURE SENSOR CHECK — A high quality digital volt-ohmmeter is required to perform this check.
1. Connect the digital voltmeter across the appropriate thermistor terminals at the J8 terminal strip on the Main Base Board for thermistors T1-T6, T9, T10; or the J5 ter­minal strip on the EXV Board for thermistors T7 and T8 (see Fig. 31). Using the voltage reading obtained, read the sensor temperature from Tables 30A-31B. To check thermistor accuracy, measure temperature at probe loca­tion with an accurate thermocouple-type temperature mea­suring instrument. Insulate thermocouple to avoid ambi­ent temperatures from influencing reading. Temperature measured by thermocouple and temperature determined from thermistor voltage reading should be close, ± 5° F (3° C) if care was taken in applying thermocouple and taking readings.
2. If a more accurate check is required, unit must be shut down and thermistor removed and checked at a known temperature (freezing point or boiling point of water) us­ing either voltage drop measured across thermistor at the J8 or J5 terminals, by determining the resistance with chiller shut down and thermistor disconnected from J8 or J5. Compare the values determined with the value read by the control in the Temperatures mode using the Mar­quee display.
1 2
3
4
1 2
3 4
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
BLU BLU PNK PNK
TB5 TB5 TB5 TB5
5
6 7 8
T10
T9
REMOTE SPACE TEMP (ACCESSORY)
5 6
7 8
9
10
1
2 3 4
1 2 3 4
5
6 1
2
3 4
5
6
2
1
4
6
3
5
T5
T3
T4
T6
T2
T1
COOLER ENTERING FLUID TEMP
OUTDOOR-AIR TEMP (ACCESSORY)
COOLER LEAVING FLUID TEMP
SATURATED CONDENSING TEMP­CIRCUIT B
SATURATED SUCTION TEMP­CIRCUIT B*
SATURATED CONDENSING TEMP­CIRCUIT A
SATURA TED SUCTION TEMP­CIRCUIT A*
MAIN BASE BOARD
J8
T1-T6, T9, T10 THERMISTORS
J5
EXV BOARD
12
11
10 9
8
7
6
5
4
32
1
12
11 10 9
T8
8
T7
7
CKTA* CKTB*
COMPRESSOR RETURN GAS TEMP
T7, T8 THERMISTORS
*Not used on FIOP (Factory-Installed Option) unit with TXV (Ther-
mostatic Expansion Valve).
Fig. 31 — Thermistor Connections to J5 and J8
Processor Boards
58
Table 30A — 5K Thermistor Temperatures (°F) vs Resistance/Voltage Drop
(For Thermistors T1-T9)
TEMP
(F)
VOLTAGE
DROP
(V)
RESISTANCE
(Ohms)
−25 4.538 98,010
−24 4.523 94,707
−23 4.508 91,522
−22 4.493 88,449
−21 4.476 85,486
−20 4.460 82,627
−19 4.444 79,871
−18 4.427 77,212
−17 4.409 74,648
−16 4.391 72,175
−15 4.373 69,790
−14 4.354 67,490
−13 4.335 65,272
−12 4.316 63,133
−11 4.296 61,070
−10 4.276 59,081
−9 4.255 57,162
−8 4.234 55,311
−7 4.213 53,526
−6 4.191 51,804
−5 4.169 50,143
−4 4.146 48,541
−3 4.123 46,996
−2 4.100 45,505
−1 4.076 44,066 0 4.052 42,679 1 4.027 41,339 2 4.002 40,047 3 3.976 38,800 4 3.951 37,596 5 3.924 36,435 6 3.898 35,313 7 3.871 34,231 8 3.844 33,185 9 3.816 32,176
10 3.788 31,202 11 3.760 30,260 12 3.731 29,351 13 3.702 28,473 14 3.673 27,624 15 3.643 26,804 16 3.613 26,011 17 3.583 25,245 18 3.552 24,505 19 3.522 23,789 20 3.490 23,096 21 3.459 22,427 22 3.428 21,779 23 3.396 21,153 24 3.364 20,547 25 3.331 19,960 26 3.299 19,393 27 3.266 18,843 28 3.234 18,311 29 3.201 17,796 30 3.168 17,297 31 3.134 16,814 32 3.101 16,346 33 3.068 15,892 34 3.034 15,453 35 3.000 15,027 36 2.966 14,614 37 2.933 14,214 38 2.899 13,826 39 2.865 13,449 40 2.831 13,084 41 2.797 12,730 42 2.764 12,387 43 2.730 12,053 44 2.696 11,730 45 2.662 11,416 46 2.628 11,112 47 2.594 10,816 48 2.561 10,529 49 2.527 10,250 50 2.494 9,979 51 2.461 9,717 52 2.427 9,461 53 2.395 9,213 54 2.362 8,973 55 2.329 8,739 56 2.296 8,511 57 2.264 8,291 58 2.232 8,076
TEMP
(F)
VOLTAGE
DROP
(V)
RESISTANCE
(Ohms)
59 2.200 7,868 60 2.168 7,665 61 2.137 7,468 62 2.105 7,277 63 2.074 7,091 64 2.043 6,911 65 2.013 6,735 66 1.982 6,564 67 1.952 6,399 68 1.923 6,238 69 1.893 6,081 70 1.864 5,929 71 1.835 5,781 72 1.806 5,637 73 1.778 5,497 74 1.749 5,361 75 1.722 5,229 76 1.694 5,101 77 1.667 4,976 78 1.640 4,855 79 1.613 4,737 80 1.587 4,622 81 1.561 4,511 82 1.535 4,403 83 1.510 4,298 84 1.485 4,196 85 1.460 4,096 86 1.436 4,000 87 1.412 3,906 88 1.388 3,814 89 1.365 3,726 90 1.342 3,640 91 1.319 3,556 92 1.296 3,474 93 1.274 3,395 94 1.253 3,318 95 1.231 3,243 96 1.210 3,170 97 1.189 3,099 98 1.169 3,031
99 1.148 2,964 100 1.128 2,898 101 1.109 2,835 102 1.089 2,773 103 1.070 2,713 104 1.051 2,655 105 1.033 2,597 106 1.015 2,542 107 0.997 2,488 108 0.980 2,436 109 0.963 2,385 110 0.946 2,335 111 0.929 2,286 112 0.913 2,239 113 0.896 2,192 114 0.881 2,147 115 0.865 2,103 116 0.850 2,060 117 0.835 2,018 118 0.820 1,977 119 0.805 1,937 120 0.791 1,898 121 0.777 1,860 122 0.763 1,822 123 0.750 1,786 124 0.736 1,750 125 0.723 1,715 126 0.710 1,680 127 0.698 1,647 128 0.685 1,614 129 0.673 1,582 130 0.661 1,550 131 0.650 1,519 132 0.638 1,489 133 0.627 1,459 134 0.616 1,430 135 0.605 1,401 136 0.594 1,373 137 0.584 1,345 138 0.573 1,318 139 0.563 1,291 140 0.553 1,265 141 0.543 1,240 142 0.534 1,214
TEMP
(F)
VOLTAGE
DROP
(V)
RESISTANCE
(Ohms)
143 0.525 1,190 144 0.515 1,165 145 0.506 1,141 146 0.497 1,118 147 0.489 1,095 148 0.480 1,072 149 0.471 1,050 150 0.463 1,029 151 0.455 1,007 152 0.447 986 153 0.440 965 154 0.432 945 155 0.424 925 156 0.417 906 157 0.410 887 158 0.403 868 159 0.396 850 160 0.389 832 161 0.382 815 162 0.376 798 163 0.369 782 164 0.363 765 165 0.357 750 166 0.351 734 167 0.345 719 168 0.339 705 169 0.333 690 170 0.327 677 171 0.322 663 172 0.316 650 173 0.311 638 174 0.306 626 175 0.301 614 176 0.295 602 177 0.291 591 178 0.286 581 179 0.281 570 180 0.276 561 181 0.272 551 182 0.267 542 183 0.263 533 184 0.258 524 185 0.254 516 186 0.250 508 187 0.246 501 188 0.242 494 189 0.238 487 190 0.234 480 191 0.230 473 192 0.226 467 193 0.223 461 194 0.219 456 195 0.216 450 196 0.212 445 197 0.209 439 198 0.205 434 199 0.202 429 200 0.199 424 201 0.196 419 202 0.192 415 203 0.189 410 204 0.186 405 205 0.183 401 206 0.181 396 207 0.178 391 208 0.175 386 209 0.172 382 210 0.169 377 211 0.167 372 212 0.164 367 213 0.162 361 214 0.159 356 215 0.157 350 216 0.154 344 217 0.152 338 218 0.150 332 219 0.147 325 220 0.145 318 221 0.143 311 222 0.141 304 223 0.138 297 224 0.136 289 225 0.134 282
59
Table 30B — 5K Thermistor Temperatures (°C) vs Resistance/Voltage Drop
(For Thermistors T1-T9)
TEMP
(C)
VOLTAGE
DROP
(V)
RESISTANCE
(Ohms)
−32 4.547 100 260
−31 4.520 94 165
−30 4.493 88 480
−29 4.464 83 170
−28 4.433 78 125
−27 4.402 73 580
−26 4.369 69 250
−25 4.335 65 205
−24 4.300 61 420
−23 4.264 57 875
−22 4.226 54 555
−21 4.187 51 450
−20 4.146 48 536
−19 4.104 45 807
−18 4.061 43 247
−17 4.017 40 845
−16 3.971 38 592
−15 3.924 38 476
−14 3.876 34 489
−13 3.827 32 621
−12 3.777 30 866
−11 3.725 29 216
−10 3.673 27 633
−9 3.619 26 202
−8 3.564 24 827
−7 3.509 23 532
−6 3.453 22 313
−5 3.396 21 163
−4 3.338 20 079
−3 3.279 19 058
−2 3.221 18 094
−1 3.161 17 184 0 3.101 16 325 1 3.041 15 515 2 2.980 14 749 3 2.919 14 026 4 2.858 13 342 5 2.797 12 696 6 2.737 12 085 7 2.675 11 506 8 2.615 10 959 9 2.554 10 441
10 2.494 9 949 11 2.434 9 485 12 2.375 9 044 13 2.316 8 627 14 2.258 8 231 15 2.200 7 855
TEMP
(C)
VOLTAGE
DROP
(V)
RESISTANCE
(Ohms)
16 2.143 7 499 17 2.087 7 161 18 2.031 6 840 19 1.976 6 536 20 1.923 6 246 21 1.870 5 971 22 1.817 5 710 23 1.766 5 461 24 1.716 5 225 25 1.667 5 000 26 1.619 4 786 27 1.571 4 583 28 1.525 4 389 29 1.480 4 204 30 1.436 4 028 31 1.393 3 861 32 1.351 3 701 33 1.310 3 549 34 1.270 3 404 35 1.231 3 266 36 1.193 3 134 37 1.156 3 008 38 1.120 2 888 39 1.085 2 773 40 1.051 2 663 41 1.019 2 559 42 0.987 2 459 43 0.956 2 363 44 0.926 2 272 45 0.896 2 184 46 0.868 2 101 47 0.841 2 021 48 0.814 1 944 49 0.788 1 871 50 0.763 1 801 51 0.739 1 734 52 0.716 1 670 53 0.693 1 609 54 0.671 1 550 55 0.650 1 493 56 0.629 1 439 57 0.609 1 387 58 0.590 1 337 59 0.571 1 290 60 0.553 1 244 61 0.536 1 200 62 0.519 1 158 63 0.502 1 118
TEMP
(C)
VOLTAGE
DROP
(V)
RESISTANCE
(Ohms)
64 0.487 1 079 65 0.471 1 041 66 0.457 1 006 67 0.443 971 68 0.429 938 69 0.415 906 70 0.403 876 71 0.390 836 72 0.378 805 73 0.367 775 74 0.355 747 75 0.345 719 76 0.334 693 77 0.324 669 78 0.314 645 79 0.305 623 80 0.295 602 81 0.287 583 82 0.278 564 83 0.270 547 84 0.262 531 85 0.254 516 86 0.247 502 87 0.239 489 88 0.232 477 89 0.226 466 90 0.219 456 91 0.213 446 92 0.207 436 93 0.201 427 94 0.195 419 95 0.189 410 96 0.184 402 97 0.179 393 98 0.174 385
99 0.169 376 100 0.164 367 101 0.160 357 102 0.155 346 103 0.151 335 104 0.147 324 105 0.143 312 106 0.139 299 107 0.135 285
60
Table 31A — 10K Thermistor Temperatures (°F) vs Resistance/Voltage Drop
(For Thermistor T10)
TEMP
(F)
VOLTAGE
DROP
(V)
RESISTANCE
(Ohms)
−25 4.758 196,453
−24 4.750 189,692
−23 4.741 183,300
−22 4.733 177,000
−21 4.724 171,079
−20 4.715 165,238
−19 4.705 159,717
−18 4.696 154,344
−17 4.686 149,194
−16 4.676 144,250
−15 4.665 139,443
−14 4.655 134,891
−13 4.644 130,402
−12 4.633 126,183
−11 4.621 122,018
−10 4.609 118,076
−9 4.597 114,236
−8 4.585 110,549
−7 4.572 107,006
−6 4.560 103,558
−5 4.546 100,287
−4 4.533 97,060
−3 4.519 94,020
−2 4.505 91,019
−1 4.490 88,171 0 4.476 85,396 1 4.461 82,729 2 4.445 80,162 3 4.429 77,662 4 4.413 75,286 5 4.397 72,940 6 4.380 70,727 7 4.363 68,542 8 4.346 66,465 9 4.328 64,439
10 4.310 62,491
11 4.292 60,612 12 4.273 58,781 13 4.254 57,039 14 4.235 55,319 15 4.215 53,693 16 4.195 52,086 17 4.174 50,557 18 4.153 49,065 19 4.132 47,627 20 4.111 46,240 21 4.089 44,888 22 4.067 43,598 23 4.044 42,324 24 4.021 41,118 25 3.998 39,926 26 3.975 38,790 27 3.951 37,681 28 3.927 36,610 29 3.903 35,577 30 3.878 34,569 31 3.853 33,606 32 3.828 32,654 33 3.802 31,752 34 3.776 30,860 35 3.750 30,009 36 3.723 29,177 37 3.697 28,373 38 3.670 27,597 39 3.654 26,838 40 3.615 26,113 41 3.587 25,396 42 3.559 24,715 43 3.531 24,042 44 3.503 23,399 45 3.474 22,770 46 3.445 22,161 47 3.416 21,573 48 3.387 20,998 49 3.357 20,447 50 3.328 19,903 51 3.298 19,386 52 3.268 18,874 53 3.238 18,384 54 3.208 17,904 55 3.178 17,441 56 3.147 16,991 57 3.117 16,552 58 3.086 16,131 59 3.056 15,714 60 3.025 15,317
TEMP
(F)
VOLTAGE
DROP
(V)
RESISTANCE
(Ohms)
61 2.994 14,925 62 2.963 14,549 63 2.932 14,180 64 2.901 13,824 65 2.870 13,478 66 2.839 13,139 67 2.808 12,814 68 2.777 12,493 69 2.746 12,187 70 2.715 11,884 71 2.684 11,593 72 2.653 11,308 73 2.622 11,031 74 2.592 10,764 75 2.561 10,501 76 2.530 10,249 77 2.500 10,000 78 2.470 9,762 79 2.439 9,526 80 2.409 9,300 81 2.379 9,078 82 2.349 8,862 83 2.319 8,653 84 2.290 8,448 85 2.260 8,251 86 2.231 8,056 87 2.202 7,869 88 2.173 7,685 89 2.144 7,507 90 2.115 7,333 91 2.087 7,165 92 2.059 6,999 93 2.030 6,838 94 2.003 6,683 95 1.975 6,530 96 1.948 6,383 97 1.921 6,238 98 1.894 6,098
99 1.867 5,961 100 1.841 5,827 101 1.815 5,698 102 1.789 5,571 103 1.763 5,449 104 1.738 5,327 105 1.713 5,210 106 1.688 5,095 107 1.663 4,984 108 1.639 4,876 109 1.615 4,769 110 1.591 4,666 111 1.567 4,564 112 1.544 4,467 113 1.521 4,370 114 1.498 4,277 115 1.475 4,185 116 1.453 4,096 117 1.431 4,008 118 1.409 3,923 119 1.387 3,840 120 1.366 3,759 121 1.345 3,681 122 1.324 3,603 123 1.304 3,529 124 1.284 3,455 125 1.264 3,383 126 1.244 3,313 127 1.225 3,244 128 1.206 3,178 129 1.187 3,112 130 1.168 3,049 131 1.150 2,986 132 1.132 2,926 133 1.114 2,866 134 1.096 2,809 135 1.079 2,752 136 1.062 2,697 137 1.045 2,643 138 1.028 2,590 139 1.012 2,539 140 0.996 2,488 141 0.980 2,439 142 0.965 2,391 143 0.949 2,343 144 0.934 2,297 145 0.919 2,253 146 0.905 2,209
TEMP
(F)
VOLTAGE
DROP
(V)
RESISTANCE
(Ohms)
147 0.890 2,166 148 0.876 2,124 149 0.862 2,083 150 0.848 2,043 151 0.835 2,003 152 0.821 1,966 153 0.808 1,928 154 0.795 1,891 155 0.782 1,855 156 0.770 1,820 157 0.758 1,786 158 0.745 1,752 159 0.733 1,719 160 0.722 1,687 161 0.710 1,656 162 0.699 1,625 163 0.687 1,594 164 0.676 1,565 165 0.666 1,536 166 0.655 1,508 167 0.645 1,480 168 0.634 1,453 169 0.624 1,426 170 0.614 1,400 171 0.604 1,375 172 0.595 1,350 173 0.585 1,326 174 0.576 1,302 175 0.567 1,278 176 0.558 1,255 177 0.549 1,233 178 0.540 1,211 179 0.532 1,190 180 0.523 1,169 181 0.515 1,148 182 0.507 1,128 183 0.499 1,108 184 0.491 1,089 185 0.483 1,070 186 0.476 1,052 187 0.468 1,033 188 0.461 1,016 189 0.454 998 190 0.447 981 191 0.440 964 192 0.433 947 193 0.426 931 194 0.419 915 195 0.413 900 196 0.407 885 197 0.400 870 198 0.394 855 199 0.388 841 200 0.382 827 201 0.376 814 202 0.370 800 203 0.365 787 204 0.359 774 205 0.354 762 206 0.349 749 207 0.343 737 208 0.338 725 209 0.333 714 210 0.328 702 211 0.323 691 212 0.318 680 213 0.314 670 214 0.309 659 215 0.305 649 216 0.300 639 217 0.296 629 218 0.292 620 219 0.288 610 220 0.284 601 221 0.279 592 222 0.275 583 223 0.272 574 224 0.268 566 225 0.264 557
61
Table 31B — 10K Thermistor Temperatures (°C) vs Resistance/Voltage Drop
(For Thermistor T10)
TEMP
(F)
VOLTAGE
DROP
(V)
RESISTANCE
(Ohms)
−32 4.762 200,510
−31 4.748 188,340
−30 4.733 177,000
−29 4.716 166,342
−28 4.700 156,404
−27 4.682 147,134
−26 4.663 138,482
−25 4.644 130,402
−24 4.624 122,807
−23 4.602 115,710
−22 4.580 109,075
−21 4.557 102,868
−20 4.533 97,060
−19 4.508 91,588
−18 4.482 86,463
−17 4.455 81,662
−16 4.426 77,162
−15 4.397 72,940
−14 4.367 68,957
−13 4.335 65,219
−12 4.303 61,711
−11 4.269 58,415
−10 4.235 55,319
−9 4.199 52,392
−8 4.162 49,640
−7 4.124 47,052
−6 4.085 44,617
−5 4.044 42,324
−4 4.003 40,153
−3 3.961 38,109
−2 3.917 36,182
−1 3.873 34,367 0 3.828 32,654 1 3.781 31,030 2 3.734 29,498 3 3.686 28,052 4 3.637 26,686 5 3.587 25,396 6 3.537 24,171 7 3.485 23,013 8 3.433 21,918 9 3.381 20,883
10 3.328 19,903 11 3.274 18,972 12 3.220 18,090 13 3.165 17,255 14 3.111 16,464
TEMP
(F)
VOLTAGE
DROP
(V)
RESISTANCE
(Ohms)
15 3.056 15,714 16 3.000 15,000 17 2.944 14,323 18 2.889 13,681 19 2.833 13,071 20 2.777 12,493 21 2.721 11,942 22 2.666 11,418 23 2.610 10,921 24 2.555 10,449 25 2.500 10,000 26 2.445 9,571 27 2.391 9,164 28 2.337 8,776 29 2.284 8,407 30 2.231 8,056 31 2.178 7,720 32 2.127 7,401 33 2.075 7,096 34 2.025 6,806 35 1.975 6,530 36 1.926 6,266 37 1.878 6,014 38 1.830 5,774 39 1.784 5,546 40 1.738 5,327 41 1.692 5,117 42 1.648 4,918 43 1.605 4,727 44 1.562 4,544 45 1.521 4,370 46 1.480 4,203 47 1.439 4,042 48 1.400 3,889 49 1.362 3,743 50 1.324 3,603 51 1.288 3,469 52 1.252 3,340 53 1.217 3,217 54 1.183 3,099 55 1.150 2,986 56 1.117 2,878 57 1.086 2,774 58 1.055 2,675 59 1.025 2,579 60 0.996 2,488 61 0.968 2,400
TEMP
(F)
VOLTAGE
DROP
(V)
RESISTANCE
(Ohms)
62 0.940 2,315 63 0.913 2,235 64 0.887 2,157 65 0.862 2,083 66 0.837 2,011 67 0.813 1,943 68 0.790 1,876 69 0.767 1,813 70 0.745 1,752 71 0.724 1,693 72 0.703 1,637 73 0.683 1,582 74 0.663 1,530 75 0.645 1,480 76 0.626 1,431 77 0.608 1,385 78 0.591 1,340 79 0.574 1,297 80 0.558 1,255 81 0.542 1,215 82 0.527 1,177 83 0.512 1,140 84 0.497 1,104 85 0.483 1,070 86 0.470 1,037 87 0.457 1,005 88 0.444 974 89 0.431 944 90 0.419 915 91 0.408 889 92 0.396 861 93 0.386 836 94 0.375 811 95 0.365 787 96 0.355 764 97 0.345 742 98 0.336 721
99 0.327 700 100 0.318 680 101 0.310 661 102 0.302 643 103 0.294 626 104 0.287 609 105 0.279 592 106 0.272 576 107 0.265 561
62
Safety Devices — Chillers contain many safety de-
vices and protection logic built into electronic control. Fol­lowing is a brief summary of major safeties.
COMPRESSOR PROTECTION Circuit Breaker — One manual-reset, calibrated-trip mag-
netic circuit breaker for eachcompressorprotectsagainstover ­current. Do not bypass or increase size of a breaker to cor­rect problems. Determine cause for trouble and correct before resetting breaker. Circuit breaker must-trip amps (MTA) are listed on individual circuit breakers, and on unit label diagrams.
30GTN,R070 (50 Hz), 080-110 and 230B-315B Compres­sor Protection Board (CPCS) — The CPCS is used to con­trol and protect compressors and crankcase heaters. Board provides following features:
• compressor contactor control
• crankcase heater control
• ground current protection
• status communication to processor board
• high-pressure protection
One large relay is located on CPCS board that controls crankcase heater and compressor contactor. In addition, this relay provides a set of contacts that the microprocessor moni­tors to determine operating status of compressor. If the MBB determines that compressor is not operating properly through signal contacts, control locks compressor off.
The CPCS contains logic that can detect if current-to­ground of any winding exceeds 2.5 amps; if so, compressor shuts down.
A high-pressure switch with a trip pressure of 426 ± 7 psig (2936 ± 48 kPa) is mounted on each compres­sor; switch setting is shown in Table 32. Switch is wired in series with the CPCS. If switch opens, CPCS relay opens, processor detects it through signal contacts, and compressor locks off.A loss-of-charge switch is also wired in series with the high-pressure switch and CPCS.
If any of these switches opens during operation, the com­pressor stops and the failure is detected by the MBB when signal contacts open. If lead compressor in either circuit is shut down by high-pressure switch, ground current protec­tor, loss of charge switch, or oil pressure switch, all com­pressors in the circuit are locked off.
30GTN,R130-210, 230A-315A AND 330A/B-420A/B — A control relay in conjunction with a ground fault module re­places the function of the CPCS (above). To reset, press the push-button switch near the Marquee display).
Table 32 — Pressure Switch Settings,
psig (kPa)
SWITCH CUTOUT CUT-IN
High Pressure
426±7
(2936 ± 48)
320±20
(2205 ± 138)
Loss-of-Charge 7 (48.2) 22 (151.6)
LOW OIL PRESSURE PROTECTION — Lead compressor in each circuit is equipped with a switch to detect low oil pressure. Switch is connected directly to processor board. Switch is set to open at approximately 5 psig (35 kPa) and to close at 9 psig (62 kPa) maximum. If switch opens when compressor is running, CR or processor board stops all com­pressors in circuit. During start-up, switch is bypassed for 2 minutes.
CRANKCASE HEATERS — Each compressor has a 180-w crankcase heater to prevent absorption of liquid re­frigerant by oil in crankcase when compressor is not run­ning. Heater power source is auxiliary control power, inde­pendent ofmainunitpower. This assures compressorprotection even when main unit power disconnect switch is off.
IMPORTANT: Never open any switch or disconnect that deenergizes crankcase heaters unless unit is being serviced or is to be shut down for a prolonged period. After a prolonged shutdown or service, energize crank­case heaters for 24 hours before starting unit.
COOLER PROTECTION Freeze Protection — Cooler can be wrapped withheatercables
as shown in Fig. 32, which are wired through an ambient temperature switch set at 36 F (2 C). Entire cooler is cov­ered with closed-cell insulation applied over heater cables. Heaters plus insulation protect cooler against low ambient temperature freeze-up to 0° F (−18 C).
IMPORTANT:If unit is installed in an area where am­bient temperatures fall below 32 F (0° C), it is rec­ommended that inhibited ethylene glycol or other suit­able corrosion-inhibitive antifreeze solution be used in chilled-liquid circuit.
Low Fluid Temperature — Main Base Board is programmed to shut chiller down if leaving fluid temperature drops below 34 F (1.1 C) for water or more than 8° F (4.4° C) below set point for brine units. The unit will shut down without a pumpout. When fluid temperaturerisesto6°F(3.3°C)above leaving fluid set point, safety resets and chiller restarts. Re­set is automatic as long as this is the first occurrence.
Loss of Fluid Flow Protection — Main Base Board contains internal logic that protects cooler against loss of cooler flow. Entering and leaving fluid temperature sensors in cooler de­tect a no-flow condition. Leaving sensor is located in leaving fluid nozzle and entering sensor is located in first cooler baffle space in close proximity to cooler tubes, as shown in Fig. 20. When there is no cooler flow and the compressors start, leaving fluid temperature does not change. However, entering fluid temperature drops rapidly as refrigerant enters cooler through EXV. Entering sensor detects this tempera­ture drop and when entering temperature is 3° F (1.6° C) below leaving temperature, unit stops and is locked off.
Loss-of-Charge — A pressure switch connected to high side of each refrigerant circuit protects against total loss-of­charge. Switch settings are listed in Table 32. If switch is open, unit cannot start; if it opens during operation, unit locks out and cannot restart until switch is closed. Low charge is also monitored by the processor when an EXV is used. The loss-of-charge switch is wired in series with the high­pressure switch on each circuit’s lead compressor.
LEGEND
T—Thermistor
Fig. 32 — Cooler Heater Cables
63
Relief Devices — Fusible plugs are located in each cir-
cuit to protect against damage from excessive pressures. HIGH-SIDE PROTECTION — One device is located be-
tween condenser and filter drier; a second is on filter drier. These are both designed to relieve pressure on a temperature rise to approximately 210 F (99 C).
LOW-SIDE PROTECTION — A device is located on suc­tion line and is designed to relieve pressure on a temperature rise to approximately 170 F (77 C).
PRESSURE RELIEF VALVES (208/230, 460, 575 v; 60 Hz Units Only) — Valves are installed in each circuit (one per circuit). The valves are designed to relieve at 450 psig (3103 kPa). These valves should not be capped. If a valve relieves, it should be replaced. If valve is not re­placed, it mayrelieveatalowerpressure, or leak due to trapped dirt from the system which may prevent resealing.
The pressure relief valves are equipped with a
3
⁄8-in. SAE flare for field connection. Some local building codes require that relieved gases be removed. This connection will allow conformance to this requirement.
Other Safeties — There are several other safeties that
are provided by microprocessor control. For details refer to Alarms and Alerts section on page 47.
PRE-START-UP
IMPORTANT: Before beginning Pre-Start-Up or Start-Up, complete Start-Up Checklist for ComfortLink™ Chiller Systems at end of this publi­cation (page CL-1).TheChecklist assures proper start-up of a unit, and provides a record of unit condition, ap­plication requirements, system information, and op­eration at initial start-up.
Do not attempt to start the chiller until following checks
have been completed.
System Check
1. Checkall auxiliary components, such as the chilled fluid circulating pump, air-handlingequipment,orotherequip­ment to which the chiller supplies liquid. Consult manu­facturer’s instructions. If the unit has field-installed ac­cessories, be sure all are properly installed and wired correctly. Refer to unit wiring diagrams.
2. Backseat (open) compressor suction and discharge shut­offvalves.Closevalves one turn to allow refrigerant pres­sure to reach the test gages.
3. Open liquid line service valves.
4. Fill the chiller fluid circuit with clean water (with recommended inhibitor added) or other noncorrosive fluid to be cooled. Bleed all air out of high points of system. An air vent is included with the cooler. If out­door temperatures are expected to be below 32 F
(0° C), sufficient inhibited ethylene glycol or other suit­able corrosion-inhibited antifreeze should be added to the chiller water circuit to prevent possible freeze-up.
5. Check tightness of all electrical connections.
6. Oil should be visible in the compressor sight glass. See Fig. 31.Anacceptableoillevelinthecompressorisfrom
1
⁄8to3⁄8of sight glass. Adjust the oil level as required. No oil should be removed unless the crankcase heater has been energized for at least 24 hours. See Oil Charge section on page 52 for Carrier-approved oils.
7. Electrical power source must agree with unit nameplate.
8. Crankcase heaters must be firmly locked into compres-
sors, and must be on for 24 hours prior to start-up.
9. Fan motors are 3 phase. Check rotation of fans during the service test. Fan rotation is clockwise as viewed from top of unit. If fan is not turning clockwise, reverse 2 of the power wires. For low noise fan option on 50 Hz chill­ers, fans rotate counterclockwise as viewed from top of unit. If fan is not turning counterclockwise, reverse 2 of the power wires.
10. Check compressor suspension. Mounting rails must be floating freely on the springs.
11. Perform service test to verify proper settings.
*Lead compressor only.
Fig. 33 — Compressor Connections
(Lead Compressor Shown)
64
START-UP AND OPERATION
NOTE: Refer to Start-Up Checklist on pages CL-1 to CL-8.
Actual Start-Up — Actual start-up should be done
only under supervision of a qualified refrigeration mechanic.
1. Besureallservicevalvesare open. Units are shipped from factory with suction, discharge, and liquid line serv­ice valves closed.
2. Using the Marquee display,setleaving-fluid set point (CSP.1 is Set Point mode under sub-mode COOL). No cooling range adjustment is necessary.
3. Ifoptionalcontrolfunctions or accessories are being used, the unit must be properly configured. Refer to Operating Data section for details.
4. Start chilled fluid pump.
5. T urnENABLE/OFF/REMOTECONTACT switch to EN­ABLE position.
6. Allow unit to operate and confirm that everything is func­tioning properly. Check to see that leaving fluid tempera­ture agrees with leaving set point (CSP.1 or CSP.2), or if reset is used, with the control point (CTPT) in the Run Status mode under the sub-mode VIEW.
Operating Limitations
TEMPERATURES (See Table 33) — If unit is to be used in an area with high solar radiation, mounted position should be such that control box is not exposed to direct solar radiation. Exposure to direct solar radiation could affect the temperature switch controlling cooler heaters.
Table 33 — Temperature Limits for Standard Units
TEMPERATURE F C
Maximum Ambient Temperature 125 52 Minimum Ambient Temperature 0 −18 Maximum Cooler EWT* 95 35 Maximum Cooler LWT 70 21 Minimum Cooler LWT† 38 3.3
LEGEND
EWT — Entering Fluid (Water) Temperature LWT — Leaving Fluid (Water) Temperature
*For sustained operation, EWT should not exceed 85 F (29.4 C).
†Unit requires modification below this temperature.
Low-Ambient Operation — If operating temperatures be­low 0° F (−18 C) are expected, refer to separate installation instructions for low-ambient operation using accessoryMotor­mastert III control. Contact your Carrier representative for details.
NOTE: Wind baffles and brackets must be field-fabricated for all units using accessory Motormaster III controls to en­sure proper cooling cycle operation at low-ambient tempera­tures. See Installation Instructions shipped with the Motor­master III accessory for more details.
Brine duty application (below 38 F [3.3 C] LCWT) for chiller normally requires factory modification. Contact your Carrier representative for applicable LCWT range for standard water-cooled chiller in a specific application.
VOLTAGE Main Power Supply — Minimum and maximum acceptable
supply voltages are listed in the Installation Instructions.
Unbalanced 3-Phase Supply Voltage — Never operate a mo­tor where a phase imbalance between phases is greater than 2%. To determine percent voltage imbalance:
max voltage deviation
from avg voltage
% Voltage Imbalance = 100 x
average voltage
The maximum voltage deviation is the largest difference between a voltage measurement across 2 legs and the aver­age across all 3 legs.
Example: Supply voltage is 240-3-60.
AB = 243 v BC = 236 v AC = 238 v
1. Determine average voltage:
243 + 236 + 238
Average voltage =
3
717
=
3
= 239 v
2. Determine maximum deviation from average voltage:
(AB) 243 − 239=4v (BC) 239 − 236 = 3 v (AC) 239 − 238=1v
Maximum deviation is 4 v.
3. Determine percent voltage imbalance:
4
% Voltage Imbalance = 100 x
239
= 1.7%
This voltage imbalance is satisfactory as it is below the maximum allowable of 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility com­pany immediately.Donot operate unit until imbalance condition is corrected.
Control Circuit Power — Electronic control includes logic to detect low controlcircuitvoltage.Acceptable voltage ranges are shown in the Installation Instructions.
MINIMUM FLUID LOOP VOLUME — To obtain proper temperature control, loop fluid volume must be at least 3 gallons per ton (3.25 L per kW) of chiller nominal capac­ity for air conditioning and at least 6 gallons per ton (6.5 L per kW) for process applications or systems that must op­erate at low ambient temperatures (below 32 F [0° C]). Refer to application information in Product Data literature for details.
FLOW RATE REQUIREMENTS — Standard chillers should be applied with nominal flow rates approximating those listed in Table 34. Higher or lower flow rates are permissible to obtain lower or higher temperature rises. Minimum flow rates must be exceeded to assure turbulent flow and proper heat transfer in the cooler.
Operation below minimum flow rate could subject tubes to frost pinching in tube sheet, resulting in failure of cooler.
65
Consult application data section in the Product Data lit­erature and job design requirements to determine flow rate requirements for a particular installation.
Table 34 — Nominal and Minimum Cooler
Fluid Flow Rates
30GTN,R
UNIT
SIZE
NOMINAL FLOW
RATE*
MINIMUM FLOW
RATE (See Notes)
Gpm L/s Gpm L/s
040 86 5.43 36.8 2.32 045 101 6.37 37.7 2.38 050 123 7.76 37.7 2.38 060 151 9.53 47.5 3.00
070 173 10.91 47.5 3.00 080,230B 192 12.11 66.7 4.20 090,245B 216 13.62 59.5 3.75
100,255B,270B 240 15.14 84.1 5.30 110,290B,315B 264 16.65 84.1 5.30
130 300 18.9 110 6.9
150,230A-255A 348 21.9 110 6.9
170,270A,330A/B,
360B (50 Hz)
384 24.2 120 7.5
190,290A,360A/B (60 Hz),
360A (50 Hz),390B
432 27.2 120 7.5
210,315A,390A,420A/B 480 30.2 148 9.3
LEGEND
ARI Air Conditioning and Refrigeration Institute Gpm — Gallons per minute (U.S.) L/s Liters per second N—Liters per kW V—Gallons per ton
*Nominalflowrates requiredatARIconditionsare 44F(6.7 C)leaving-
fluid temperature, 54 F (12.2 C) entering-fluid temperature, 95 F (35 C) ambient. Fouling factor is .00001 ft
2
hr F/Btu (.000018 m
2
K/W).
NOTES:
1. Minimum flow based on 1.0 fps (0.30 m/s) velocity in cooler with­out special cooler baffling.
2. Minimum Loop Volumes: Gallons=VxARICap. in tons Liters = N x ARI Cap. in kW
APPLICATION V N
Normal Air Conditioning 3 3.25 Process Type Cooling 6 to 10 6.5 to 10.8 Low Ambient Unit Operation 6 to 10 6.5 to 10.8
Operation Sequence — During unit off cycle, crank-
case heaters are energized. If ambient temperature is below 36 F (2 C), cooler heaters (if equipped) are energized.
The unit is started by putting the ENABLE/OFF/REMOTE CONTACT switch in ENABLE or REMOTE position. When the unit receives a call for cooling (either from the internal
control or CCN network command or remote contact clo­sure), the unit stages up in capacity to maintain the cooler fluid set point. The first compressor starts 1
1
⁄2to 3 minutes
after the call for cooling.
The lead circuit can be specifically designated or ran­domly selected by the controls, depending on how the unit is field configured (for 040-070 sizes, Circuit A leads unless an accessory unloader is installed on Circuit B). A field con­figuration is also available to determine if the unit should stage up both circuits equally or load one circuit completely before bringing on the other.
When the lead circuit compressor starts, the unit starts with a pumpout routine. On units with the electronic expansion valve (EXV), compressor starts and continues to run with the EXV at minimum position for 10 seconds to purge the refrigerant lines andcoolerofrefrigerant.The EXV then moves to 23% and the compressor superheat control routine takes over,modulatingthe valve to feed refrigerant into the cooler.
On units with thermostatic expansion valve (TXV) (30GTN,R040,045 units with brine option), head pressure control is based on set point control. When the lead com­pressor starts, the liquid line solenoid valve (LLSV) is kept closed for 15 seconds by a time delay relay. The micro­processor stages fans to maintain the set point temperature specified by the controller. There is no pumpout sequence during shutdown of TXV controlled chillers.
On all other units (EXV units), the head pressure is con­trolled by fan cycling. The desired head pressure set point is entered, and is controlled by EXV position or saturated con­densing temperature measurement (T3 and T4). For proper operation, maintain set point of 113 F (45 C) as shipped from factory.The default head pressure control method is set point control. The head pressure control can also be set to EXV control or a combination of the 2 methods between circuits.
For all units, if temperature reset is being used, the unit controls to a higher leaving-fluid temperature as the build­ing load reduces. If demand limit is used, the unit may tem­porarily be unable to maintain the desired leaving-fluid tem­perature because of imposed power limitations.
On EXV units, when the occupied period ends, or when the building load drops low enough, the lag compressors shut down.Theleadcompressorscontinueto run as the EXV closes, and until the conditions of pumpout are satisfied. If a fault condition is signaled requiring immediate shutdown, pumpout is omitted.
Loading sequence for compressors is shown in Tables 5A and 5B.
66
APPENDIX A — CCN TABLES
UNIT (Configuration Settings)
DESCRIPTION STATUS DEFAULT UNITS POINT
1 Unit Type 1 = Air Cooled
2 = Water Cooled 3 = Split System 4 = Heat Machine 5 = Air Cooled Heat Reclaim
1 UNIT TYP
2 Unit Size 15 to 300 20 TONS SIZE 3 Circuit A1% Capacity 0 to 100 50 % CAP A 4 Number Circ A Compressor 1 to 4 1 NUMCA 5 Compressor A1 Cylinders 4 or 6 6 NUM CYLA 6 Number Circ B Compressor 1 to 4 1 NUMCB 7 Compressor B1 Cylinders 4 or 6 6 NUM CYLB 8 EXV Module Installed No/Yes Yes EXV BRD 9 EXV Superheat Setpoint 10 to 40 29.0 ^F SH SP
10 EXV MOP 40 to 80 50.0 °F MOP SP
11 EXV Superheat Offset − 20 to 20 0.0 ^F SH OFFST 12 EXV Circ. A Min Position 0 to 100 8.0 % EXVAMINP 13 EXV Circ. B Min Position 0 to 100 8.0 % EXVBMINP 14 Refrigerant 1 = R22
2 = R134A
1 REFRIG T
15 Low Pressure Setpoint 3 to 60 10.0 PSI LOW PRES 16 Fan Staging Select 1 = 2 Stage indpt.
2 = 3 Stage indpt. 3 = 2 Stage common 4 = 3 Stage common
1 FAN TYPE
OPTIONS1 (Options Configuration)
DESCRIPTION STATUS DEFAULT POINT
1 Cooler Fluid 1 = Water
2 = Med. Brine 3 = Low Brine
1 FLUIDTYP
2 Hot Gas Bypass Select No/Yes No HGBV FLG 3 Head Press. Cont. Method 1 = EXV controlled
2 = Setpoint controlled 3 = Setpoint-A, EXV-B 4 = EXV-A, Setpoint-B
2 HEAD MET
4 Head Press. Control Type 0 = None
1 = Air Cooled 2 = Water Cooled
0 HEAD TYP
5 Pressure Transducers No/Yes No PRESS TY 6 Cooler Pump Interlock Off/On On LOCK FLG 7 Cooler Pump Control Off/On Off CPC 8 No. Circuit A Unloaders 0-2 1 NUNLA 9 No. Circuit B Unloaders 0-2 1 NUNLB
10 EMM Module Installed No/Yes No EMM BRD
67
CONFIGURATION SCREEN (TYPE 10)
OPTIONS2 (Options Configuration)
DESCRIPTION STATUS DEFAULT UNITS POINT
1 Control Method 0 = Switch
1 = 7 day sched. 2 = Occupancy 3 = CCN
0 CONTROL
2 Loading Sequence Select 1 = Equal loading
2 = Staged loading
1 SEQ TYPE
3 Lead/Lag Sequence Select 1 = Automatic
2 = Circuit A leads 3 = Circuit B leads
1 LEAD TYP
4 Cooling Setpoint Select 0 = Single
1 = Dual, remote switch controlled 2 = Dual, clock controlled 3 = 4-20 ma input
0 CLSP TYP
5 Ramp Load Select ON/OFF OFF RAMP EBL 6 High LCW Alert Limit 2 to 60 60.0 ^F LCW LMT 7 Minutes off time 0 to 15 0 min DELAY 8 Deadband Multiplier 1.0 to 4.0 1.0 Z GAIN
DISPLAY (STDU SETUP)
DESCRIPTION STATUS DEFAULT UNITS POINT
1 STDU Password nnnn 1111 PASSWORD 2 Password Enable enable/disable enable PASS EBL 3 Metric Display Off/On Off DISPUNIT 4 Language 0 = ENGLISH
1 = FRANCAIS 2 = ESPANOL 3 = PORTUGUES
0 LANGUAGE
CONFIG (TIMED OVERRIDE SETUP)
DESCRIPTION STATUS DEFAULT UNITS POINT
1 Schedule Number 0-99 0 SCHEDNUM 2 Override Time Limit 0-4 0 hours OTL 3 Timed Override Hours 0-4 0 hours OTL EXT
ALARMDEF (Alarm Definition Table)
DESCRIPTION STATUS DEFAULT UNITS POINT
1 Alarm Routing Control
ALRM_CNT
00000000 00000000
2 Equipment Priority
EQP_TYPE
0to7 4
3 Comm Failure Retry Time 1 to 240 10 min RETRY_TM 4 Re-alarm Time 1 to 255 30 min RE-ALARM 5 Alarm System Name XXXXXXXX 30_PIC ALRM_NAM
68
RESETCON (Temperature Reset and Demand Limit)
DESCRIPTION STATUS DEFAULT UNITS POINT
1 COOLING RESET 2 Cooling Reset Type 0 = No Reset
1 = 4-20 ma input 2 = External temp-OAT 3 = Return fluid 4 = External temp-SPT
0 CRST TYP
3 No Cool Reset Temp 0 to 125 0.0 °F CT NO 4 Full Cool Reset Temp 0 to 125 125.0 °F CT FULL 5 Degrees Cool Reset −30 to 30 0.0 ^F CT DEG 6 DEMAND LIMIT 7 Demand Limit Select 0 = None
1 = External switch input 2 = 4-20 ma input 3 = Loadshed
0 DMD CTRL
8 Demand Limit at 20mA 0 to 100 100 % DMT20MA 9 Loadshed Group Number 0 to 99 0 SHED NUM
10 Loadshed Demand Delta 0 to 60 0 % SHED DEL
11 Maximum Loadshed Time 0 to 120 60 min SHED TIM 12 Demand Limit Switch 1 0 to 100 80 % DLSWSP1 13 Demand Limit Switch 2 0 to 100 50 % DLSWSP2 14 LEAD/LAG 15 Lead/Lag Enable Enable/Disable Disable LL ENA 16 Master/Slave Select Slave/Master Master MS SEL 17 Slave Address 0 to 239 0 SLV ADDR 18 Lead/Lag Balance Select Enable/Disable Disable LL BAL 19 Lead/Lag Balance Delta 40 to 400 168 hours LL BAL D 20 Lag Start Delay 0 to 30 5 mins LL DELAY
BRODEFS (Broadcast POC Definition Table)
DESCRIPTION STATUS DEFAULT UNITS POINT
1 CCN Time/Date Broadcast Yes/No No CCNBC 2 CCN OAT Broadcast Yes/No No OATBC 3 Global Schedule Broadcst Yes/No No GSBC 4 CCN Broadcast Acker Yes/No No CCNBCACK 5 Daylight Savings Start 6 Month 1 to 12 1 STARTM 7 Week 1to5 1 STARTW 8 Day 1to7 0 STARTD
9 Minutes to add 0 to 99 0 min MINADD 10 Daylight Savings Stop 11 Month 1 to 12 1 STOPM 12 Week 1 to 5 1 STOPW 13 Day 1 to 7 0 STOPD 14 Minutes to subtract 0 to 99 0 min MINSUB
69
GENUNIT (General Unit Parameters)
DESCRIPTION STATUS UNITS POINT FORCEABLE
1 Control Mode 0 = Service Test
1 = OFF - local control 2 = OFF-CCN control 3 = OFF-timeclock 4 = Emergency stop 5 = ON-local control 6 = ON-CCN control 7 = ON-timeclock
MODE N
2 Occupied Yes/No OCC N 3 CCN Chiller Start/Stop CHIL S S
Y
4 Alarm State Normal ALM N 5 Active Demand Limit 0-100 % DEM LIM
Y
6 Percent Total Capacity 0-100 % CAP T
N
7 Requested Stage nn STAGE N 8 Load/Unload Factor snnn.n SMZ N 9 Active Setpoint snnn.n °F SP N
10 Control Point snnn.n °F CTRL PNT
Y
11 Entering Fluid Temp snnn.n °F EWT N 12 Leaving Fluid Temp snnn.n °F LWT N 13 Emergency Stop Enable/Emstop EMSTOP Y 14 Minutes Left for Start nn min MIN LEFT
N
CIRCA AN (Circuit A Analog values)
DESCRIPTION STATUS UNITS POINT FORCEABLE
1 Circuit AAnalog Values 2 Percent Total Capacity 0-100 % CAPA T
N
3 Percent Available Cap 0-100 % CAPA A
N
4 Discharge Pressure nnn.n PSI DP A
N
5 Suction Pressure nnn.n PSI SP A
N
6 Saturated Condensing Tmp snnn.n °F TMP SCTA
N
7 Saturated Suction Temp snnn.n °F TMP SSTA
N
8 Compressor Suction Temp snnn.n °F CTA TMP
N
9 Suction Superheat Temp snnn.n ^F SH A
N
10 EXV % Open 0-100.0 % EXV A
N
CIRCA DO (Circuit A Discrete Parameters)
DESCRIPTION STATUS UNITS POINT FORCEABLE
1 Circuit A Discretes 2 Fan A1 Relay ON/OFF FAN A1
N
3 Fan A2 Relay ON/OFF FAN A2
N
4 Oil Pressure Switch OPEN/CLOSE OILSW A
N
5 Compressor A1 Relay ON/OFF K A1 RLY
N
6 Compressor A2 Relay ON/OFF K A2 RLY
N
7 Compressor A3 Relay ON/OFF K A3 RLY
N
8 Compressor A4 Relay ON/OFF K A4 RLY
N
9 Unloader A1 Relay ON/OFF UNL A1
N
10 Unloader A2 Relay ON/OFF UNL A2
N
11 Hot Gas Bypass Relay ON/OFF HGAS N
70
CIRCB AN (Circuit B Analog Parameters)
DESCRIPTION STATUS UNITS POINT FORCEABLE
1 Circuit B Analog Values 2 Percent Total Capacity 0-100 % CAPB T
N
3 Percent Available Cap 0-100 % CAPB A
N
4 Discharge Pressure nnn.n PSI DP B
N
5 Suction Pressure nnn.n PSI SP B
N
6 Saturated Condensing Tmp snnn.n °F TMP SCTB
N
7 Saturated Suction Temp snnn.n °F TMP SSTB
N
8 Compressor Suction Temp snnn.n °F CTB TMP
N
9 Suction Superheat Temp snnn.n ^F SH B
N
10 EXV % Open 0-100.0 % EXV B
N
CIRCB DO (Circuit B Discrete Parameters)
DESCRIPTION STATUS UNITS POINT FORCEABLE
1 Circuit B Discretes 2 Fan B1 Relay ON/OFF FAN B1
N
3 Fan B2 Relay ON/OFF FAN B2
N
4 Oil Pressure Switch OPEN/CLOSE OILSW B
N
5 Compressor B1 Relay ON/OFF K B1 RLY
N
6 Compressor B2 Relay ON/OFF K B2 RLY
N
7 Compressor B3 Relay ON/OFF K B3 RLY
N
8 Compressor B4 Relay ON/OFF K B4 RLY
N
9 Unloader B1 Relay ON/OFF UNL B1
N
10 Unloader B2 Relay ON/OFF UNL B2
N
11 Hot Gas Bypass Relay ON/OFF HGAS N
OPTIONS (Unit Parameters)
DESCRIPTION STATUS UNITS POINT FORCEABLE
1 UNIT Analog Values 2 Cooler Entering Fluid snnn.n °F COOL EWT
N
3 Cooler Leaving Fluid snnn.n °F COOL LWT
N
4 Temperature Reset 5 4-20 MA Reset Signal nn.n ma RST MA
N
6 Outside Air Temperature snnn.n °F OAT Y 7 Space Temperature snn.n °F SPT Y 8 Demand Limit 9 4-20 MA Demand Signal nn.n ma LMT MA
N
10 Demand Limit Switch 1 ON/OFF DMD SW1
N
11 Demand Limit Switch 2 ON/OFF DMD SW2
N
12 CCN Loadshed Signal Normal/Redline/Shed DL STAT
N
13 Pumps 14 Cooler Pump Relay ON/OFF COOL PMP
N
15 Miscellaneous 16 Dual Setpoint Switch ON/OFF DUAL IN
N
17 Cooler Flow Switch ON/OFF COOLFLOW N 18 Ice Done ON/OFF ICE N
71
STRTHOUR
DESCRIPTION STATUS UNITS POINT
1 Machine Operating Hours nnnnn hours HR MACH 2 Machine Starts nnnnn CY MACH 3 4 Circuit A Run Hours nnnnn hours HR CIRA 5 Compressor A1 Hours nnnnn hours HR A1 6 Compressor A2 Hours nnnnn hours HR A2 7 Compressor A3 Hours nnnnn hours HR A3 8 Compressor A4 Hours nnnnn hours HR A4
9 Circuit B Run Hours nnnnn hours HR CIRB 10 Compressor B1 Hours nnnnn hours HR B1 11 Compressor B2 Hours nnnnn hours HR B2 12 Compressor B3 Hours nnnnn hours HR B3 13 Compressor B4 Hours nnnnn hours HR B4 14 15 Circuit A Starts nnnnn CY CIRA 16 Compressor A1 Starts nnnnn CY A1 17 Compressor A2 Starts nnnnn CY A2 18 Compressor A3 Starts nnnnn CY A3 19 Compressor A4 Starts nnnnn CY A4 20 Circuit B Starts nnnnn CY CIRB 21 Compressor B1 Starts nnnnn CY B1 22 Compressor B2 Starts nnnnn CY B2 23 Compressor B3 Starts nnnnn CY B3 24 Compressor B4 Starts nnnnn CY B4
ALARMS
DESCRIPTION STATUS UNITS POINT
1 Active Alarm #1 Axxx ALARM01C 2 Active Alarm #2 Axxx ALARM02C 3 Active Alarm #3 Axxx ALARM03C 4 Active Alarm #4 Axxx ALARM04C 5 Active Alarm #5 Axxx ALARM05C 6 Active Alarm #6 Axxx ALARM06C 7 Active Alarm #7 Axxx ALARM07C 8 Active Alarm #8 Axxx ALARM08C
9 Active Alarm #9 Axxx ALARM09C 10 Active Alarm #10 Axxx ALARM10C 11 Active Alarm #11 Axxx ALARM11C 12 Active Alarm #12 Axxx ALARM12C 13 Active Alarm #13 Axxx ALARM13C 14 Active Alarm #14 Axxx ALARM14C 15 Active Alarm #15 Axxx ALARM15C 16 Active Alarm #16 Axxx ALARM16C 17 Active Alarm #17 Axxx ALARM17C 18 Active Alarm #18 Axxx ALARM18C 19 Active Alarm #19 Axxx ALARM19C 20 Active Alarm #20 Axxx ALARM20C 21 Active Alarm #21 Axxx ALARM21C 22 Active Alarm #22 Axxx ALARM22C 23 Active Alarm #23 Axxx ALARM23C 24 Active Alarm #24 Axxx ALARM24C 25 Active Alarm #25 Axxx ALARM25C
NOTE: Alerts will displayed as Txxx
72
CURRMODS
DESCRIPTION STATUS UNITS POINT
1 FSM controlling chiller ON/OFF MODE 1 2 WSM controlling chiller ON/OFF MODE 2 3 Master/Slave control ON/OFF MODE 3 4 Low source protection ON/OFF MODE 4 5 Ramp Load Limited ON/OFF MODE 5 6 Timed Override in effect ON/OFF MODE 6 7 Low Cooler Suction TempA ON/OFF MODE 7 8 Low Cooler Suction TempB ON/OFF MODE 8 9 Slow Change Override ON/OFF MODE 9
10 Minimum OFF Time ON/OFF MODE 10
11 Low Suction Superheat A ON/OFF MODE 11 12 Low Suction Superheat B ON/OFF MODE 12 13 Dual Setpoint ON/OFF MODE 13 14 Temperature Reset ON/OFF MODE 14 15 Demand Limit in effect ON/OFF MODE 15 16 Cooler Freeze Prevention ON/OFF MODE 16 17 Lo Tmp Cool/Hi Tmp Heat ON/OFF MODE 17 18 Hi Tmp Cool/Lo Tmp Heat ON/OFF MODE 18
SETPOINT
DESCRIPTION STATUS UNITS POINT DEFAULTS
1 COOLING 2 Cool Setpoint 1 −20 to 70 °F CSP1 44 3 Cool Setpoint 2 −20 to 70 °F CSP2 44 4 RAMP LOADING 5 Cooling Ramp Loading 0.2 to 2.0 °F/min CRAMP 1.0 6 HEAD PRESSURE 7 Head Press. Stpt A 80 to 140 °F HSP A
113
8 Head Press. Stpt B 80 to 140 °F HSP B
113
LID DEFAULT SCREEN DEFINITION
TABLE TYPE 19 HEX
DESCRIPTION STATUS UNITS POINT DISPLAY
1 (SYSTEM PRIMARY MESSAGE) 2 (SYSTEM SECONDARY MESSAGE) 3 Machine Operating Hours nnnnn hours HR MACH
HR MACH
4 Entering Chilled Water snnn.n °F EWT EWT 5 Leaving Chilled Water snnn.n °F LWT LWT 6 Control Point snnn.n °F CTRL PNT
CTRL PNT
7 Percent Total Capacity 0-100 % CAP T CAP T 8 Active Demand Limit 0-100 % DEM_LIM DEM_LIM 9 Operating Setpoint snnn.n °F SP SP
10 Circuit A Total Cap 0-100 % CAPA T
CAPA T
11 Circuit B Total Cap 0-100 % CAPB T CAPB T 12 Machine Starts nnnnn CY MACH CY MACH
73
CSM/FSM EQUIPMENT TABLE (Type 621H, Block 2)
LINE DESCRIPTION POINT
1 Chiller Status
0 = Chiller is off 1 = Valid run state in CCN mode 2 = Recycle active 3 = Chiller is in Local Mode 4 = Power Fail Restart in Progress 5 = Shutdown due to fault 6 = Communication Failure
CHILSTAT
2 unused 3 Percent Total Capacity Running CAP T 4 Service Runtime HR MACH 5 unused 6 unused 7 unused 8 Power Fail Auto Restart ASTART 9 Percent Available Capacity On CAP A
WSM EQUIPMENT PART COOL SOURCE MAINTENANCE TABLE
SUPERVISOR MAINTENANCE TABLE
DESCRIPTION STATUS POINT
WSM Active? Yes WSMSTAT Chilled water temp 46.5 °F CHWTEMP Equipment status On CHLRST Commanded state Enable/Disable/None CHLRENA CHW setpoint reset value 2.0 ^F CHWRVAL Current CHW setpoint 44.0 °F CHWSTPT
OCCUPANCY MAINTENANCE TABLE
OCCUPANCY SUPERVISORY
DESCRIPTION STATUS POINT
Current Mode (1=Occup.) 0,1 MODE Current Occup. Period # 0-8 PER-NO Timed-Override in Effect Yes/No OVERLAST Time-Override Duration 0-4 hours OVR HRS Current Occupied Time 0:00 STRTTIME Current Unoccupied Time 0:00 ENDTIME Next Occupied Day NXTOCDAY Next Occupied Time 0:00 NXTOCTIM Next Unoccupied Day NXTUNDAY Next Unoccupied Time 0:00 NXTUNTIM Previous Unoccupied Day PRVUNDAY Previous Unoccupied Time 0:00 PRVUNTIM
74
Copyright 1999 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5c
PC 903 Catalog No. 533-099 Printed in U.S.A. Form 30GTN-1T Pg 76 5-99 Replaces: New
START-UP CHECKLIST FOR COMFORTLINK™ CHILLER SYSTEMS
(Remove and use for job file)
A. Preliminary Information
JOB NAME LOCATION INSTALLING CONTRACTOR DISTRIBUTOR START-UP PERFORMED BY
EQUIPMENT: Chiller: MODEL # SERIAL #
COMPRESSORS:
CIRCUIT A CIRCUIT B
1) M#
1) M# S# S# MTR# MTR#
2) M# 2) M# S# S# MTR# MTR#
3) M# 3) M# S# S# MTR# MTR#
4) M# S# MTR#
COOLER:
MODEL #
MANUFACTURED BY SERIAL # DATE TYPE OF EXPANSION VALVES (check one): EXV TXV
AIR-HANDLING EQUIPMENT:
MANUFACTURER MODEL # SERIAL # ADDITIONAL AIR-HANDLING UNITS AND ACCESSORIES
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
----------------------------------------------------------------------------------------
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5c
PC 903 Catalog No. 533-099 Printed in U.S.A. Form 30GTN-1T Pg CL-1 5-99 Replaces: New
B. Preliminary Equipment Check (YES or NO)
IS THERE ANY SHIPPING DAMAGE?
IF SO, WHERE
WILL THIS DAMAGE PREVENT UNIT START-UP? HAVE COMPRESSOR BASE RAIL ISOLATORS ALL BEEN PROPERLYADJUSTED? CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (refer to Installation Instructions) ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (refer to Installation Instructions) HAS THE GROUND WIRE BEEN CONNECTED? ARE ALL TERMINALS TIGHT?
CHECK AIR SYSTEMS (YES or NO) ARE ALLAIR HANDLERS OPERATING?
(refer to air-handling equipment Installation and Start-Up Instructions)
ARE ALL CHILLED FLUID VALVES OPEN? IS THE FLUID PIPING CONNECTED PROPERLY? HAS ALL AIR BEEN VENTED FROM THE COOLER LOOP? IS THE CHILLED WATER (FLUID) PUMP (CWP) OPERATING? IS THE CWP ROTATION CORRECT? CWP MOTOR AMPERAGE: Rated Actual
C. Unit Start-Up (insert check mark as each item is completed)
CHECK THAT THE CHILLER HAS BEEN PROPERLYINTERLOCKEDWITHTHEAUXILIARY CONTACTSOFTHECHILLED FLUID PUMP STARTER.
ASSURE THAT THE UNIT IS SUPPLIED WITH CORRECT CONTROL VOLTAGE POWER.
(115 V FOR 208/230, 460, AND 575 V UNITS; 230 V FOR 380 AND 380/415 UNITS) ASSURE CRANKCASE HEATERS HAVE BEEN ENERGIZED FOR A MINIMUM OF 24 HOURS PRIOR TO START-UP. ASSURE COMPRESSOR OIL LEVEL IS CORRECT. ASSURE BOTH LIQUID LINE SERVICE VALVES ARE BACKSEATED. ASSURE ALL COMPRESSOR DISCHARGE SERVICE VALVES ARE BACKSEATED. ASSURE ALL COMPRESSOR SUCTION SERVICE VALVES ARE BACKSEATED. LOOSEN COMPRESSOR SHIPPING HOLDDOWN BOLTS. LEAK CHECK THOROUGHLY: CHECK ALL COMPRESSORS, CONDENSER MANIFOLDS AND HEADERS, EXVs, TXVs,
SOLENOID VALVES, FILTER DRIERS, FUSIBLE PLUGS, THERMISTORS, AND COOLER HEADS, WITH GE H-10-B ELECTRONIC LEAK DETECTOR.
LOCATE, REPAIR, AND REPORT ANY R-22 LEAKS.
CL-2
C. Unit Start-Up (cont)
CHECK VOLTAGE IMBALANCE: AB AC BC
AB + AC + BC (divided by 3) = AVERAGE VOLTAGE = V MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =
(MAX. DEVIATION)
VOLTAGE IMBALANCE = x 100 = % VOLTAGE IMBALANCE
AVERAGE VOLTAGE
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START CHILLER! CALL LOCAL POWER COMPANY FOR ASSISTANCE.
ASSURE THAT INCOMING POWER VOLTAGE TO CHILLER MODULES IS WITHIN RATED UNIT VOLTAGE RANGE.
SYSTEM FLUID VOLUME IN LOOP: TYPE SYSTEM:
AIR CONDITIONING — MINIMUM 3 GALPERNOMINAL TON(3.25L PERkW) = GAL (L) PROCESS COOLING — MINIMUM6GALPER NOMINALTON (6.50 LPERkW) =
GAL (L)
CHECK PRESSURE DROP ACROSS COOLER.
FLUID ENTERING COOLER:
PSIG (kPa)
FLUID LEAVING COOLER:
PSIG (kPa) (PSIG DIFFERENCE) x 2.31 = FT OF FLUID PRESSURE DROP = PLOT COOLER PRESSURE DROP ON PERFORMANCE DATA CHART (LOCATED IN PRODUCT DATA
LITERATURE) TO DETERMINE TOTAL GPM (L/s). TOTAL GPM (L/s) =
UNIT’S RATED MIN GPM (L/s) =
GPM (L/s) PER TON = UNIT’S RATED MIN PRESSURE DROP =
(Refer to product data literature.) JOB’S SPECIFIED GPM (L/s) (if available): NOTE: IF UNIT HAS LOW FLUID FLOW, FIND SOURCE OF PROBLEM: CHECK FLUID PIPING, IN-LINE FLUID
STRAINER, SHUT-OFF VALVES, CWP ROTATION, ETC.
COOLER LOOP PROTECTION IF REQUIRED:
GALLONS (LITERS) OF BRINE ADDED: PIPING INCLUDES ELECTRIC TAPE HEATERS (Y/N):
VISUALLY CHECK MAIN BASE BOARD AND EXV BOARD FOR THE FOLLOWING:
INSPECT ALL THERMISTORS AND EXV CABLES FOR POSSIBLE CROSSED WIRES. CHECK TO BE SURE ALL WELL-TYPE THERMISTORS ARE FULLY INSERTED INTO THEIR RESPECTIVE
WELLS. ARE ALL CABLES AND PIN CONNECTORS TIGHT? (Y/N)
ARE EXV, EMM, AND CXB BOARDS (IF INSTALLED) AND DISPLAY CONNECTIONS TIGHT?
CL-3
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
----------------------------------------------------------------------------------------
C. Unit Start-Up (cont)
TO START THE CHILLER: (insert check mark as each item is completed)
TURN THE EMERGENCY ON/OFF SWITCH (SW2) TO ON POSITION. LEAVE THE ENABLE/OFF/REMOTE CONTACT SWITCH (SW1) IN THE OFF POSITION.
NOTE: USE ESCAPE KEY TO GO UP ONE LEVEL IN THE STRUCTURE. USE ARROW/ESCAPE KEYS TO ILLUMINATE CONFIGURATION LED. PRESS ENTER KEY AND ‘DISP’ WILL BE
DISPLAYED. PRESS DOWN ARROW KEY TO DISPLAY ‘UNIT’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW:
UNIT (Configuration Settings)
DESCRIPTION STATUS DEFAULT UNITS VALUE
Unit Type 1 = Air Cooled
2 = Water Cooled 3 = Split System 4 = Heat Machine 5 = Air Cooled Heat Reclaim
1
Unit Size 15 to 300 20 TONS Circuit A1% Capacity 0 to 100 50 % Number Circ A Compressor 1to4 1 Compressor A1 Cylinders 4or6 6 Number Circ B Compressor 1to4 1 Compressor B1 Cylinders 4or6 6 EXV Module Installed No/Yes Yes EXV Superheat Setpoint 10 to 40 29.0 ^F EXV Superheat Offset −20to20 0.0 ^F EXV Circ. A Min Position 0 to 100 8.0 % EXV Circ. B Min Position 0 to 100 8.0 % Refrigerant 1 = R22
2 = R134A
1
Fan Staging Select 1 = 2 Stage indpt.
2 = 3 Stage indpt. 3 = 2 Stage common 4 = 3 Stage common
1
PRESS ESCAPE KEY TO DISPLAY ‘UNIT’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT1’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW:
OPTIONS1 (Options Configuration)
DESCRIPTION STATUS DEFAULT VALUE
Cooler Fluid 1 = Water
2 = Med. Brine 3 = Low Brine
1
Hot Gas Bypass Select No/Yes No Head Press. Cont. Method 1 = EXV controlled
2 = Setpoint controlled 3 = Setpoint-A, EXV-B 4 = EXV-A, Setpoint-B
2
Head Press. Control Type 0 = None
1 = Air Cooled 2 = Water Cooled
0
Pressure Transducers No/Yes No Cooler Pump Interlock Off/On On Cooler Pump Control Off/On Off No. Circuit A Unloaders 0-2 1 No. Circuit B Unloaders 0-2 1 EMM Module Installed No/Yes No
CL-4
C. Unit Start-Up (cont)
PRESS ESCAPE KEY TO DISPLAY ‘OPT1’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT2’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW.
OPTIONS2 (Options Configuration)
DESCRIPTION STATUS DEFAULT UNITS VALUE
Control Method 0 = Switch
1 = 7 day sched. 2 = Occupancy 3 = CCN
0
CCN Address 1 to 239 1 CCN Bus Number 0 to 239 0 CCN Baud Rate 1 = 2400
2 = 4800 3 = 9600 4 = 19,200 5 = 38,400
3
Loading Sequence Select 1 = Equal loading
2 = Staged loading
1
Lead/Lag Sequence Select 1 = Automatic
2 = Circuit A leads 3 = Circuit B leads
1
High LCW Alert Limit 2 to 60 60.0 ^F Minutes off time 0to15 0 min
PRESS ESCAPE KEY TO DISPLAY ‘OPT2’. PRESS DOWN ARROW KEY TO DISPLAY ‘RSET’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW:
RESETCON (Temperature Reset and Demand Limit)
DESCRIPTION STATUS DEFAULT UNITS VALUE
COOLING RESET
Cooling Reset Type 0 = No Reset
1 = 4-20 ma input 2 = External temp-OAT 3 = Return fluid 4 = External temp-SPT
0
No Cool Reset Temp 0 to 125 0.0 °F Full Cool Reset Temp 0 to 125 125.0 °F Degrees Cool Reset −30 to 30 0.0 ^F
DEMAND LIMIT
Demand Limit Select 0 = None
1 = External switch input 2 = 4-20 ma input 3 = Loadshed
0
Demand Limit at 20mA 0 to 100 100 % Loadshed Group Number 0to99 0 Loadshed Demand Delta 0to60 0 % Maximum Loadshed Time 0 to 120 60 min Demand Limit Switch 1 0 to 100 80 % Demand Limit Switch 2 0 to 100 50 %
LEAD/LAG
Lead/Lag Enable Enable/Disable Disable Master/Slave Select Slave/Master Master Slave Address 0 to 239 0 Lead/Lag Balance Select Enable/Disable Disable Lead/Lag Balance Delta 40 to 400 168 hours Lag Start Delay 0 to 30 5 mins
CL-5
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
----------------------------------------------------------------------------------------
C. Unit Start-Up (cont)
PRESS ESCAPE KEY TO DISPLAY ‘RSET’. PRESS DOWN ARROW KEY TO DISPLAY ‘SLCT’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW:
SLCT (Cooling Setpoint Select)
DESCRIPTION STATUS DEFAULT UNITS VALUE
Cooling Setpoint Select 0 = Single
1 = Dual Switch 2 = Dual Clock 3=4to20mAInput
0
Ramp Load Select Enable/Disable Enable Cooling Ramp Loading 0.2 to 2.0 1.0 Deadband Multiplier 1.0 to 4.0 1.0
PRESS ESCAPE KEY SEVERAL TIMES TO GET TO THE MODE LEVEL (BLANK DISPLAY). USE THE ARROW KEYS TO SCROLL TO THE SET POINT LED. PRESS ENTER TO DISPLAY SETPOINTS. RECORD CONFIGURATION INFORMATION BELOW:
SETPOINT
DESCRIPTION STATUS UNITS DEFAULTS VALUE
COOLING
Cool Setpoint 1 −20 to 70 °F 44 Cool Setpoint 2 −20 to 70 °F 44
RAMP LOADING
Cooling Ramp Loading 0.2 to 2.0 °F/min 1.0
HEAD PRESSURE
Head Press. Stpt A 80 to 140 °F 113 Head Press. Stpt B 80 to 140 °F 113
USE ARROW/ESCAPE KEYS TO ILLUMINATE TEMPERATURES LED. PRESS ENTER TO DISPLAY ‘UNIT’. PRESS ENTER AND USE THE ARROW KEYS TO RECORD TEMPERATURES FOR T1 AND T2 BELOW. RECORD T9 AND T10 IF INSTALLED. PRESS ESCAPE TO DISPLAY ‘UNIT’ AGAIN AND PRESS THE DOWN ARROW KEY TO DISPLAY ‘CIR.A’. PRESS ENTER AND USE THE ARROW KEYS TO RECORD TEMPERATURES FOR T3, T5 AND T7 BELOW. PRESS ESCAPE TO DISPLAY ‘CIR.A’AGAIN AND PRESS THE DOWN ARROW KEY TO DISPLAY ‘CIR.B’. PRESS ENTER AND USE THE DOWN ARROW KEYS TO RECORD TEMPERATURES FOR T4, T6 AND T8 BELOW. USING A DC VOLTMETER, MEASURE AND RECORD THE VOLTAGE FOR EACH THERMISTOR AT THE LOCATION SHOWN.
TEMPERATURE VDC BOARD LOCATION
T1 (CLWT)
MBB, J8 PINS 13,14 T2 (CEWT) MBB, J8 PINS 11,12 T3 (SCT.A)
MBB, J8 PINS 21,22 T4 (SCT.B) MBB, J8 PINS 15,16 T5 (SST.A) MBB, J8 PINS 24,25 (EXV UNITS ONLY) T6 (SST.B)
MBB, J8 PINS 18,19 (EXV UNITS ONLY) T7 (SGT.A) EXV, J5 PINS 11,12 (EXV UNITS ONLY) T8 (SGT.B) EXV, J5 PINS 9,10 (EXV UNITS ONLY) T9 (OAT)
MBB, J8 PINS 7,8 T10 (SPT) MBB, J8 PINS 5,6
CL-6
C. Unit Start-Up (cont)
USE ESCAPE/ARROW KEYS TO ILLUMINATE CONFIGURATION LED. PRESS ENTER TO DISPLAY ‘DISP’. PRESS ENTER AGAIN TO DISPLAY ‘TEST’ FOLLOWED BY ‘OFF’. PRESS ENTER TO STOP DISPLAY AT ‘OFF’ AND ENTER AGAIN SO ‘OFF’ DISPLAY FLASHES. ‘PASS’ AND ‘WORD’ WILL FLASH IF PASSWORD NEEDS TO BE ENTERED. PRESS ENTER TO DISPLAY PASSWORD FIELD AND USE THE ENTER KEY FOR EACH OF THE FOUR PASSWORD DIGITS. USE ARROW KEYS IF PASSWORD IS OTHER THAN STANDARD. AT FLASHING ‘OFF’ DISPLAY, PRESS THE UP ARROW KEY TO DISPLAY ‘ON’ AND PRESS ENTER. ALL LED SEGMENTS AND MODE LEDS WILL LIGHT UP. PRESS ESCAPE TO STOP THE TEST. PRESS ESCAPE TO RETURN TO THE ‘DISP’ DISPLAY. PRESS THE ESCAPE KEY AGAIN AND USE THE ARROW KEYS TO ILLUMINATE THE SERVICE TEST LED. PRESS ENTER TO DISPLAY ‘TEST’. PRESS ENTER TO STOP DISPLAY AT ‘OFF’ AND ENTER AGAIN SO ‘OFF’ FLASHES. PRESS THE UP ARROW KEY AND ENTER TO ENABLE THE MANUAL MODE. PRESS ESCAPE AND DISPLAY NOW SAYS ‘TEST’ ‘ON’.
PRESSTHEDOWNARROW TODISPLAY ‘OUTS’. PRESSTHEENTERKEYTO DISPLAY‘FR.A1’. PRESS THE ENTER KEY TO STOP DISPLAY AT ‘OFF’ AND ENTER AGAIN SO ‘OFF’ FLASHES. PRESS THE UP ARROW KEY AND ENTER TO TURN THE OUTPUT ON. PRESS ENTER SO THE ‘ON’ DISPLAY FLASHES, PRESS THE DOWN ARROW KEY AND THEN ENTER TO TURN THE OUTPUT OFF. OUTPUTS WILL ALSO BE TURNED OFF OR SENT TO 0% WHEN ANOTHER OUTPUT IS TURNED ON. USE THE ARROW KEYS TO SELECT THE DESIRED PERCENTAGE FOLLOWED BY THE ENTER KEY WHEN TESTING EXPANSIONVALVES. CHECK OFF THE FOLLOWING THATAPPLYAFTER BEING TESTED:
FR.A1
(CHECK ROTATION) FR.A2 (CHECK ROTATION)
EXV.A
FR.B1 (CHECK ROTATION)
FR.B2
(CHECK ROTATION) EXV.B
CLR.P (TB5-10,12) RMT.A TB5-11,12)
USE ESCAPE KEY TO RETURN TO ‘OUTS’ DISPLAY. PRESS DOWN ARROW TO DISPLAY ‘COMP’. PRESS ENTER KEY TO DISPLAY ‘CC.A1’. NOTE THAT UNLOADERS AND HOT GAS BYPASS SOLENOIDS CAN BE TESTED WITHOUT TURNING THE COMPRESSOR(S) ON. MAKE SURE ALL SERVICE VALVES ARE OPEN AND COOLER PUMP HAS BEEN TURNED ON BEFORE STARTING COMPRESSORS. CHECK OFF EACH ITEM AFTER SUCCESSFUL TEST: LEAD COMPRESSORS (A1/B1) WILL BE TURNED ON BEFORE ANY LAG COMPRESSORS CAN BE STARTED. THE CONTROL WILL ONLY START ONE COMPRESSOR PER MINUTE. WHEN AT THE DESIRED ITEM, PRESS THE ENTER KEY TWICE TO MAKE THE ‘OFF’ FLASH. PRESS THE UP ARROW KEY AND ENTER TO TURN THE OUTPUT ON.
CC.A1
CC.A2 CC.A3 CC.A4 UL.A1 UL.A2 HGBP (IF INSTALLED) CC.B1
CC.B2 CC.B3 CC.B4 N/A UL.B1 UL.B2
TXV UNITS ONLY: CHECK AND ADJUST SUPERHEAT.
CL-7
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
----------------------------------------------------------------------------------------
Copyright 1999 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5c
PC 903 Catalog No. 533-099 Printed in U.S.A. Form 30GTN-1T Pg CL-8 5-99 Replaces: New
Loading...