Carrier
initiai Start-Up Instructions
Heritìetic Cpfìtrifugal Liguid Chillers
INTRODUCTION
All persons involved in start-up and operation
of the 19DG Machine should understand these
instructions and all applicable Job Data before
initial start-up. The instructions are arranged in the
proper sequence for machine start-up.
Job Data Required
1. Machine assembly, wiring and piping prints.
2. Starter details
3. 19DG Installation Instructions
4. 19DG Operating and Maintenance Ins
Equipment Required
1. Mechanic’s tools
2.
Volt-ohmmeter and clamp
3.
Manometer, absolute pressu'
4.
Leak detector, halide or el№tf^ic
5.
Refrigerant drum charging valve (F
6.
5/8-in. SAE X 3/4-in. MPT ada rter
7.
Five to ten ft of copper tub!
to fit 5/8-in. SAE connection;
INITIAL PREPIAR
CAUTION; Do not síai^iítempressor or oil
pump, even for a rotation check, unless
compressor has been charged with oil and
machine charged with refrigerant.
Machine Tightness — A shipping vacuum was
applied to the refrigerant side of the 19DG
Machine before shipment from the factory. Over a
period of time, during shipment or storage, part of
this vacuum may be lost. The loss of a small
amount of vacuum may be acceptable and within
Carrier’s machine tightness standards. To deter
mine if the vacuum loss is acceptable;
1. Record and date vacuum reading shown on the
compressor-mounted oil reservoir gage (Eig. 1).
2. Determine vacuum leak rate by comparing this
reading with reading taken when machine was
received. Use the formula:
^ , vacuum difference
Leak rate ==
3. If leak rate is 0.05 in. Hg or less per 24 hours,
machine is sufficiently tight. If leak rate
exceeds 0.05 in. Hg per 24 hours, perform
Refrigerant Pressure Test and correct leakage.
EXCESSIVE OR TOTAL VACUUM LOSS can be
caused by accidental opening of a valve or other
connection. If this is suspected, proceed as follows;
1. Install a mercury manometer (absolute pressure
type) at the cooler charging valve (Eig. 1). A
-----------------------------------no. of days between readings
plastic hose
/
)
dial gage
leakage act
time.\
Pull a\yaci|ium on the machin'd"equal to 25-in.
the leak rate is 0.05 in. Hg or less per 24
hours, the machine is sufficiently tight. Perform
Machine Dehydration.
If the leak rate exceeds 0.05 in. Hg per 24
hours, perform Refrigerant Pressure Test and
correct leakage. Perform all steps under
Machine Dehydration.
Remove the mercury manometer from cooler
charging valve.
REFRIGERANT PRESSURE TEST
Pull a vacuum equal to 5 in. Hg ref 30-in. bar.
(12.5 psia) using machine purge pump, and
following operation no. 2 described on the
purge valve operation plate (Fig. 1). An
external vacuum pump connected to the cooler
charging valve may be used, if desired.
2. Charge approximately one gallon of Refrigerant
11 thru the cooler charging valve. Refer to
Charging Refrigerant for procedure.
3. Increase pressure to 8 to 10 psig with dry air or
nitrogen thru the cooler charging valve. Do not
exceed 10 psig.
4. Test all joints, valves, fittings, etc., with a halide
or electronic leak detector.
5. Repair any leaks found. Retest to ensure repair.
MACHINE DEHYDRATION — The refrigerant
side of the 19DG Machine is dehydrated at the
factory. It is usually not necessary to repeat
dehydration at initial start-up. However, if the
machine has been open for a considerable length of
time due to compressor removal, or if there has
been excessive loss of shipping vacuum, it is
-
recommended that dehydration he repeated.
Dehydration is readily accomplished at normal
room temperature. If room temperature is high,
dehydration takes place more quickly. At low
room temperature, dehydration is extremely diffi
cult and special techniques must be applied.
Contact your Carrier representative.
Do not start compressor or oil pump even for a
rotation check while machine is und.er dehy
dration vacuum.
annot indicate the small amot
;eptable during a short p^ridd of
■in. bar. (2.^pS'ia). Use an external
mp or enprgize the purge pump (Pig.
jratira^Aio. 2 described on the purge
mrfplate (Pig. 1).
e stand with this vacuum for 24
more. Then perform leak rate test
outlined.
2/o7
7^
© Carrier Corporation 1971 Form 19DG-3SS
1 ~ Chiliec! Waier Temperature Probe
2 — Gii Heater Thermoster (l-i:cicter>)
3 — 0!l Heater Indicator Light
4 — Motor Rotation Sight Glasses
5 - Gil Level Sight Glass
6 — Oil Reservoir Pressure Gage
7 — Searing Returr'.-'Gil Temperature Gage
8 — Gil Reservoir Temperature Gage
9— Knockouts lot Field Wiring
10 — Oil Pump Pressure Gage
11 — Refrigerant Level Sight Glasses
12 — Refrigerant Float Charrilaer
13 — Cooler Charging Valve
14 — Purge Water. Level Sight Glass
15— Purge Water Drain Vaive
16 — Purge Pressure Gage
17 — Purge Valve Operation Plats
18 - O i ! Cooler Solenoid Valve and Plug Cock
Fig. 1 — 19DG Machine Components
2
19 — Lub: ication Assembiv
20 — Oil Charging Valve
21 — Oil Pressure Regulating Vaive
(fsionadjustabie)
22 — Chilled Water Low-Temperature Cutout
23—Refrigerant Low-Temperature Cutout
24 ~ Thermowell
25 — Purge Pump (Hidden)
25 — Purge Gperar ing Valves
Perform dehydration as follows:
1. Connect dehydration pump to the cooler
charging valve (Fig. 1).
2. Ensure that all valves on the purge assembly are
closed. Valve identification numbers are listed
on the purge valve operation plate (Fig. 1).
3. Remove the A-B swing connection (see valve
operation plate) and connect a mercury
manometer (absolute pressure type) to the
bottom common connection.
4. Operate dehydration pump until manometer
reads 29.80 in. Hg ref 30-in. bar. (0.1 psia);
continue to operate pump for 2 more hours.
5. Close cooler charging valve; stop dehydration
pump; record manometer reading.
6. After a 2-hour wait, read manometer again. If
reading has not increased, dehydration is com
plete. If reading has increased, repeat steps 4
and 5.
7. If reading continues to rise after several dehy
dration attempts, check for a machine leak by
repeating the Refrigerant Pressure Test.
Inspect Piping — Refer to piping diagrams provided
in Job Data and inspect piping to cooler, condenser
and oil cooler. Ensure that flow direction is correct
in all cases and that all piping specifications are
met.
CHECK WATER ELOW — Water flow thru con
denser and cooler must meet job requirements.
Measure the water pressure drop across cooler or
condenser or across the pumps. Check to see that
water flow agrees with design flow.
Oil cooler water should meet the following
requirements:
Clean water
Max water temperature 85 F
Max inlet working pressure 200 psi
Water vel in tube, ft/sec 10 max — 6 min
Water flow, gal./min 7 max — 4 min
Water press, drop, psi diff 5 max — 2 min
Valves and/or controls Field supplied
Field Wiring — Prior to starting equipment,
refer to wiring diagrams in Job Data and check
power supply as follows:
1. Connect a voltmeter across power wires to
compressor motor starter and measure voltage.
Compare this reading with voltage rating on
compressor and starter nameplates.
WARNING; Do not attempt to check high
voltage supply without proper equipment.
Serious personal injury can result.
2. Check that ampere rating on starter nameplate
matches ampere rating on compressor motor
nameplate.
3. Ensure that voltage to oil pump starter agrees
with oil pump nameplate value.
4. Check that electrical supply to oil heater and
purge pump is 120 volts.
5. Test compressor motor and its power lead
insulation resistance with a 500-volt insulation
tester such as a megohmmeter. Proceed as
follows:
a. Open starter main disconnect switch.
b. Test the three phases of compressor motor,
phase-to-phase and phase-to-ground, with
tester connected on the motor side of the
starter contactor in the starter. Take a
resistance reading at a 10-second interval
and at a 60-second interval for each phase.
c. Divide the 60-second resistance reading by
the 10-second reading. This gives the polari
zation ratio. The polarization ratio must be
1.15:1 or higher. Both the 10-second and
60-second resistance reading must be 5.0
megohms or higher.
If readings are unsatisfactory, repeat tests at
motor terminals with motor power leads dis
connected. This will indicate whether fault is
in motor or in motor power leads.
Check Starter — Before starting the 19DG
Machine, open the main disconnect and then check
starter.
1. Remove contactor arc chutes. Be sure con
tactors move freely, and that shipping string is
removed. Replace arc chutes.
2. Check contactors for dirt and rust. Clean
contact magnet surfaces lightly with sandpaper.
Do not sandpaper or file silverplated contacts.
Apply a very thin coat of petroleum jelly to
magnet surfaces and then wipe it off. If starter
has been in a dusty atmosphere, vacuum clean
the cabinet and wipe with Unt-free cloth.
3. Remove fluid cups from magnetic overload
relays. Add dashpot oil to cups per instructions
on relay nameplate. Dashpot oil is shipped in
small vials usually attached to starter frame
near relays. Use only the dashpot oil shipped
with starter. Do not substitute. Overload relays
are factory set for 108% of motor full load
amperage and resetting is not normally
required.
4. Check transfer timer for proper time setting.
On Star-Delta starters, timers have adjustable
ranges of 10 seconds to 3 minutes and are
factory set at one minute. On Auto-
Transformer starters, timers have adjustable
ranges of zero to 60 seconds and are factory set
for 30 seconds.
5. With main disconnect switch open, manually
open and close main control relay (ICR) to be
sure it operates freely.
Oil Charge — The oil charge is shipped in the oil
reservoir. Check sight glass (Fig. 1) to be certain oil
is in the reservoir. If oil must be added, it must
meet Carrier’s oil specification as listed in the
19DG Operating and Maintenance Instructions.
Charge oil thru the oil reservoir charging valve
(Fig. 1). With machine at vacuum, oil is drawn
from the oil container. Continue charging until oil
reaches middle of sight glass (Fig. 1).