Centrifugal liquid chillers are designed to provide safe
and reliable service when operated within design specifications. When operating this equipment, use good judgment and safety precautions to avoid damage to equipment and property or injury to personnel.
Be sure you understand and follow the procedures and
safety precautions contained in the chiller instructions
as well as those listed in this guide.
DO NOT VENT refrigerant relief valves within a building. Outlet
from rupture disc or relief valve must be vented outdoors in accordance with the latest edition of ASHRAE (American Society of
Heating, Refrigeration, and Air Conditioning Engineers) 15. The
accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ASHRAE 15,
especially for enclosed and low overhead spaces. Inhalation of high
concentrations of vapor is harmful and may cause heart irregularities, unconsciousness, or death. Misuse can be fatal.Vaporisheavier
than air and reduces the amount of oxygen available for breathing.
Product causes eye and skin irritation. Decomposition products are
hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a chiller
for any purpose. Oxygen gas reacts violently with oil, grease, and
other common substances.
NEVER EXCEED specified test pressures, VERIFY the allowable
test pressure by checking the instruction literature and the design
pressures on the equipment nameplate.
DO NOT USE air for leak testing. Use only refrigerant or dry
nitrogen.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly installed and
functioning before operating any machine.
DO NOT WELD OR FLAME CUT any refrigerant line or vessel
until all refrigerant (liquid andvapor)hasbeenremovedfromchiller.
Traces of vapor should be displaced with dry air or nitrogen and
the work area should be well ventilated. Refrigerant in contact with
an open flame produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig chiller sections or
the entire assembly.
DO NOT work on high-voltage equipment unless you are a qualified electrician.
DO NOTWORKON electrical components, including control panels, switches, starters, or oil heater until you are sure ALLPOWER
IS OFF and no residual voltage can leak from capacitors or solidstate components.
LOCK OPENANDTAGelectrical circuits during servicing.IF WORK
IS INTERRUPTED, confirm that all circuits are deenergized before resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it into the
eyes. USE SAFETY GOGGLES. Wash any spills from the skin
with soap and water .If any enters the eyes, IMMEDIATELYFLUSH
EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refrigerant cylinder. Dangerous overpressure can result. When necessary to heat
refrigerant, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or
attempt to refill them. It is DANGEROUS AND ILLEGAL. When
cylinder is emptied, evacuate remaining gas pressure, loosen
the collar and unscrew and discard the valve stem. DO NOT
INCINERATE.
CHECK THE REFRIGERANT TYPE before adding refrigerant to
the chiller.The introduction of the wrong refrigerant can cause damage or malfunction to this chiller.
Operation of this equipment with refrigerants other than those
cited herein should comply withASHRAE-15 (latest edition). Contact Carrier for further information on use of this chiller with other
refrigerants.
DO NOTATTEMPTTO REMOVE fittings, covers,etc., while chiller
is under pressure or while chiller is running. Be sure pressure is at
0 psig (0 kPa) before breaking any refrigerant connection.
CAREFULLY INSPECT all relief devices, rupture discs, and other
relief devices AT LEAST ONCE A YEAR. If chiller operates in a
corrosive atmosphere, inspect the devices at more frequent
intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief
device when corrosion or build-up of foreign material (rust, dirt,
scale, etc.) is found within the valve body or mechanism. Replace
the device.
DO NOT install relief devices in series or backwards.
USE CARE when working near or in line with a compressed spring.
Sudden release of the spring can cause it and objects in its path to
act as projectiles.
RUN WATERPUMPS when removing, transferring, or charging refrigerant.
DO NOT STEP on refrigerant lines. Broken lines can whip about
and cause personal injury.
DO NOT climb over a chiller. Use platform, catwalk, or staging.
Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or
move inspection covers or other heavy components. Even if components are light, use such equipment when there is a risk of slipping or losing your balance.
BE AWARE that certain automatic start arrangements CAN ENGAGE THE STARTER. Open the disconnect ahead of the starter
in addition to shutting off the machine or pump.
USE only repair or replacement parts that meet the code requirements of the original equipment.
DO NOTVENT OR DRAIN waterboxes containingindustrial brines,
liquid, gases, or semisolids without permission of your process control group.
DO NOT LOOSEN waterbox cover bolts until the waterbox has
been completely drained.
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or
other items have been removed before rotating any shafts.
DO NOT LOOSEN a packing gland nut before checking that the
nut has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for corrosion, rust, leaks, or damage.
PROVIDE A DRAIN connection in the vent line near each pressure relief device to prevent a build-up of condensate or rain
water.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
Tab 5d
PC 211Catalog No. 531-721Printed in U.S.A.Form 17EX-1SSPg 17-97Replaces: New
Chiller Identification Label
System Components
Cooler
Condenser
Compressor
Control Center
Motor Starter (Purchased Separately)
Economizer/Storage Vessel
Auxiliary Compressor Oil Pump Control
Auxiliary Gear Oil Pump Control
Shaft Seal Oil Control
Ramp Loading Control
Capacity Override
High Discharge Temperature Control
Oil Sump Temperature Control
Oil Cooler
Remote Start/Stop Controls
Spare Safety Inputs
Spare Alarm Contacts
Condenser Pump Control
Condenser Freeze Prevention
Tower-Fan Relay
Auto. Restart After Power Failure
Water/Brine Reset
Demand Limit Control, Option (Requires Optional
8-Input Module)
Surge Prevention Algorithm
Surge Protection
Lead/Lag Control
....................................36
..........................33
.........................33
.............................35
..................35
.....................36
...........................36
.........................36
......................36
...................36
..............................36
.............................37
.............................37
....................37
..............................38
.............................38
..........33
................33
.............35
................36
• COMMON POINT SENSOR INSTALLATION
• CHILLER COMMUNICATION WIRING
• LEAD/LAG OPERATION
• FAULTED CHILLER OPERATION
• LOAD BALANCING
• AUTO. RESTART AFTER POWER FAILURE
Ice Build Control
..............................40
• ICE BUILD INITIATION
• START-UP/RECYCLE OPERATION
• TEMPERATURE CONTROL DURING ICE BUILD
• TERMINATION OF ICE BUILD
• RETURN TO NON-ICE BUILD OPERATIONS
Attach to Network Device Control
...............41
• ATTACHING TO OTHER CCN MODULES
Service Operation
.............................42
• TO ACCESS THE SERVICE SCREENS
• TO LOG OFF
• HOLIDAY SCHEDULING
START-UP/SHUTDOWN/RECYCLE SEQUENCE
Local Start-Up
Shutdown Sequence
Automatic Soft Stop Amps Threshold
Chilled Water Recycle Mode
Safety Shutdown
BEFORE INITIAL START-UP
Job Data Required
Equipment Required
Using the Economizer/Storage Vessel and Pumpout
System
Remove Shipping Packaging
................................43
...........................44
............44
....................44
..............................45
...................45-57
............................45
...........................45
....................................45
...................45
...43-45
• MOTOR
• EXTERNAL GEAR
Motor Electrical Connection
Motor Auxiliary Devices
Open Oil Circuit Valves
Tighten All Gasketed Joints and Guide Vane
Shaft Packing
Check Chiller Tightness
Refrigerant Tracer
Leak Test the Chiller
Standing Vacuum Test
Chiller Dehydration
Set Up Chiller Control Configuration
Input the Design Set Points
Input the Local Occupied Schedule
(OCCPC01S)
Input Service Configurations
................................54
.....................54
....................54
.............54
• PASSWORD
• INPUT TIME AND DATE
• CHANGE LID CONFIGURATION IF NECESSARY
• MODIFY CONTROLLER IDENTIFICATION IF
NECESSARY
• INPUT EQUIPMENT SERVICE PARAMETERS IF
NECESSARY
• MODIFY EQUIPMENT CONFIGURATION IF
NECESSARY
• CHECK VOLTAGE SUPPLY
• PERFORM AN AUTOMATED CONTROL TEST
Check Pumpout System Controls and Optional
Pumpout Compressor
High Altitude Locations
Charge Refrigerant Into Chiller
........................56
........................57
..................57
• TRIMMING REFRIGERANT CHARGE
INITIAL START-UP
Preparation
Manual Operation of the Guide Vanes
Dry Run to Test Start-Up Sequence
Check Motor Rotation
...........................57-62
..................................57
............58
..............58
.........................58
• INITIAL MOTOR START-UP
Disc Coupling Installation and Alignment
.........59
• IMPORTANT INFORMATION
Check Oil Pressure and Compressor Stop
Calibrate Motor Current Demand Setting
To Prevent Accidental Start-Up
Hot Alignment Check
Doweling
Check Chiller Operating Condition
Instruct the Operator
....................................61
.........................61
..........................62
..................61
...............61
........61
..........61
• COOLER-CONDENSER
• ECONOMIZER/STORAGE VESSEL
• PUMPOUT SYSTEM
• COMPRESSOR ASSEMBLY
• COMPRESSOR LUBRICATION SYSTEM
EXTERNAL GEAR LUBRICATION SYSTEM
• CONTROL SYSTEM
• AUXILIARY EQUIPMENT
• CHILLER CYCLES
• MAINTENANCE
• SAFETY DEVICES AND PROCEDURES
• CHECK OPERATOR KNOWLEDGE
• THIS MANUAL
OPERATING INSTRUCTIONS
Operator Duties
...............................62
..................62,63
Prepare the Chiller for Start-Up .................62
Starting the Chiller
Check the Running System
Stopping the Chiller
After Limited Shutdown
Extended Shutdown
After Extended Shutdown
Cold Weather Operation
Manual Guide Vane Operation
Refrigeration Log
PUMPOUT AND REFRIGERANT TRANSFER
PROCEDURES
Preparation
Operating the Optional Pumpout
Compressor
..................................63
........................... 62
.....................62
...........................62
........................63
...........................63
......................63
........................63
...................63
.............................63
............................63-67
................................63
• READING REFRIGERANT PRESSURES
Transferring Refrigerant into the
Economizer/Storage Vessel
Transferring Refrigerant into
the Cooler/Condenser/Compressor Section
Return Chiller to Normal Operating
Conditions
GENERAL MAINTENANCE
Refrigerant Properties
Adding Refrigerant
Removing Refrigerant
Adjusting the Refrigerant Charge
Refrigerant Leak Testing
Leak Rate
Test After Service, Repair, or Major Leak
.................................67
............................67
....................................67
...................66
.....67
....................67-75
.........................67
.........................67
................67
.......................67
.........67
• REFRIGERANT TRACER
• TO PRESSURIZE WITH DRY NITROGEN
Repair the Leak, Retest, and Apply
Standing Vacuum Test
Checking Guide Vane Linkage
Contact Seal Maintenance
.......................68
..................68
......................68
• SEAL DISASSEMBLY
• SEAL REASSEMBLY
Chiller Alignment
.............................71
• ALIGNMENT METHODS
• PRELIMINARY ALIGNMENT
• NEAR FINAL ALIGNMENT
• FINAL ALIGNMENT
• HOT ALIGNMENT CHECK
• DOWELING
WEEKLY MAINTENANCE
Check the Lubrication System
SCHEDULED MAINTENANCE
Service Ontime
Inspect the Control Center
Check Safety and Operating Controls Monthly
Changing the Oil Filters
...............................76
.......................76
..................76
..................76-83
.....................76
.....76
........................76
• COMPRESSOR OIL FILTER
• EXTERNAL GEAR OIL FILTER
Oil Specifications
Oil Changes
.............................77
..................................77
• COMPRESSOR OIL
• EXTERNAL GEAR OIL
• MOTOR SLEEVE BEARING AND PUMPOUT
COMPRESSOR OIL
Inspect Refrigerant Float System
Inspect Relief Valves and Piping
Coupling Maintenance
Motor Maintenance
Water Leaks
Water Treatment
Inspect the Starting Equipment
Check Pressure Transducers
Pumpout System Maintenance
..................................82
..............................82
.................83
...................83
..................83
• OPTIONAL PUMPOUT COMPRESSOR OIL CHARGE
• PUMPOUT SAFETY CONTROL SETTINGS
Ordering Replacement Chiller Parts
..............83
• MOTOR REPLACEMENT PARTS
• EXTERNAL GEAR REPLACEMENT PARTS
TROUBLESHOOTING GUIDE
Overview
Checking the Display Messages
Checking Temperature Sensors
....................................83
..................83-99
.................84
.................84
• RESISTANCE CHECK
• VOLTAGE DROP
• CHECK SENSOR ACCURACY
• DUAL TEMPERATURE SENSORS
Checking Pressure Transducers ................84
• OIL DIFFERENTIAL PRESSURE/POWER SUPPLY
MODULE CALIBRATION
• TROUBLESHOOTING TRANSDUCERS
• TRANSDUCER REPLACEMENT
Control Algorithms Checkout Procedure
Control Test
Control Modules
.................................85
..............................96
.........85
• RED LEDs
• GREEN LEDs
Notes on Module Operation
Processor/Sensor Input/Output Module (PSIO)
....................96
....97
• INPUTS
• OUTPUTS
Starter Management Module (SMM)
..............97
• INPUTS
• OUTPUTS
Options Modules (8-Input)
Four-In/Two-Out Module
.....................98
.......................98
• INPUTS
• OUTPUTS
Replacing Defective Processor Modules
.........98
• INSTALLATION OF NEW PSIO MODULE
PHYSICAL DATA AND WIRING SCHEMATICS
INDEX
INITIAL START-UP CHECKLIST FOR 17EX
....................................115-120
EXTERNALLY GEARED CENTRIFUGAL LIQUID
CHILLER
..........................CL-1 to CL-12
....99-114
4
INTRODUCTION
Before initial start-up of the 17EX unit, those involved in
the start-up, operation, and maintenance should be thoroughly familiar with these instructions and other necessary
job data. This book is outlined so that you may become familiar with the control system before performing start-up procedures. Procedures in this manual are arranged in the sequencerequiredforproperchillerstart-upand
operation.
This unit uses a microprocessor controlled system. Do
not short or jumper between terminations on circuit boards
or modules; control or board failure may result.
Be aware of electrostatic discharge (static electricity) when
handling or making contact with circuit boards or module connections. Always touch a chassis (grounded) part
to dissipate body electrostatic charge before working inside the control center.
Use extreme care when handling tools near boards and
when connecting or disconnecting terminal plugs.
Circuit boards can easily be damaged. Always hold boards
by the edges and avoid touching components and
connections.
This equipment uses, and can radiate, radio frequency
energy. If not installed and used in accordance with
the instruction manual, it may cause interference to
radio communications. It has been tested and found to
comply with the limits for a Class A computing device
pursuant to Subpart J of Part 15 of FCC Rules, which
are designed to provide reasonable protection against such
interference when operated in a commercial environment. Operation of this equipment in a residential area
is likely to cause interference, in which case the user, at
his own expense, will be required to take whatever measures may be required to correct the interference.
Always store and transport replacement or defective boards
in anti-static shipping bag.
ABBREVIATIONS
Frequently used abbreviations in this manual include:
CCN— Carrier Comfort Network
CCW— Counterclockwise
CHW— Chilled Water
CHWR — Chilled Water Return
CHWS — Chilled Water Supply
CW— Clockwise
ECW— Entering Chilled Water
ECDW — Entering Condenser Water
EMS— Energy Management System
HGBP — Hot Gas Bypass
I/O— Input/Output
LCD— Liquid Crystal Display
LCDW — Leaving Condenser Water
LCW— Leaving Chilled Water
LED— Light-Emitting Diode
LID— Local Interface Device
OLTA— Overload Trip Amps
PIC— Product Integrated Control
PSIO— Processor Sensor Input/
tification label is located on the right side of the chiller control center panel. The label contains information on model
number, refrigerant charge, rated voltage, etc.
The iden-
System Components (Fig. 2) — The components
include the cooler and condenser heat exchangers in separate vessels, compressor,compressorandgear lubrication packages, control center,speedincreasereconomizer/storage vessel,
motor, and starter. The compressor drive consists of an external gear (speed increaser) and an electric motor. All connections from pressure vessels have external threads to enable each component to be pressure tested with a threaded
pipe cap during factory assembly.
Cooler — This vessel (also known as the evaporator) is
located underneath the condenser, next to the economizer/
storage vessel. The cooler is maintained at lower temperature and pressure so that evaporating refrigerant can remove
heat from water flowing through its internal tubes.
Condenser — The condenser operates at a higher tem-
perature and pressure than the cooler and has water flowing
through its internal tubes in order to remove heat from the
refrigerant.
Compressor — This component maintains system tem-
perature and pressure differences and moves the heatcarrying refrigerant from the cooler to the condenser.
Control Center — The control center is the user inter-
face for controlling the chiller and regulates the chiller capacity as required to maintain proper leaving chilled
water temperature. The control center:
• registers cooler, condenser, and lubricating system
pressures
• shows chiller operating and alarm shutdown conditions
• records the total chiller operating hours and how many hours
the chiller has been running
• sequences chiller start, stop, and recycle under microprocessor control
• provides access to other CCN (Carrier Comfort Network)
devices
MotorStarter (Purchased Separately) — The starter
allows the proper start and disconnect of electrical energy
for the compressor-motor, oil pump, oil heater, and control
panels.
Economizer/Storage Vessel — During normal op-
eration, this vessel functions as an economizer,returning flash
gas to the second stage of the compressor and increasing the
efficiency of the refrigeration cycle. During periods of shutdown and service, the economizer/storage vessel can serve
as a storage tank for the refrigerant.
REFRIGERATION CYCLE (Fig. 3)
The 17EX chiller can be used to chill either water or brine.
The data in this book applies to either application. Applications using corrosive brines may require using special tubes,
tubesheet, and waterbox materials which are special order
items.
5
LEGEND
NIH — Nozzle-In-Head
*Any available cooler size can be combined with any available condenser size.
NOTE: For details on motor size designations, see below.
ASME
‘U’ STAMP
ARI (Air Conditioning
and Refrigeration
Institute)
PERFORMANCE
CERTIFIED
(60 Hz Only)
Fig. 1 — Model Number Identification
6
40
39
38
37
36
35
1 2 3 4 5 6 7 8 9 10 11 12 1314
15
34
1—Condenser
2—Cooler Suction Pipe
3—Compressor Suction Elbow
4—Guide Vane Actuator
5—Condenser Discharge Pipe
6—Compressor Discharge Elbow
7—Two-Stage Compressor
8—Economizer Gas Line to Compressor
The chiller compressor continuously draws large quantities of refrigerant vapor from the cooler at a rate determined
by the amount of guide vane opening. This compressor suction reduces the pressure within the cooler, allowing the liquid refrigerant to boil vigorously at a fairly low temperature
(typically 38 to 42 F [3 to 6 C]).
The liquid refrigerant obtains the energy needed to vaporize by removing heat from the water or brine in the cooler
tubes. The cold water or brine can then be used in air conditioning and/or other processes.
After removing heat from the water or brine, the refrigerant vapor enters the first stage of the compressor, is
compressed, and flows into the compressor second stage. Here
it is mixed with flash-economizer gas and is further
compressed.
Compression raises the refrigerant temperature above
that of the water flowing through the condenser tubes.
When the warm (typically 98 to 102 F [37 to 40 C]) refrigerant vapor comes into contact with the condenser tubes, the
relatively cool condensing water (typically 85 to 95 F
[29 to 35 C]) removes some of the heat, and the vapor condenses into a liquid.
The liquid refrigerant passes through an orifice into the
FLASC chamber.The coolest condenser water flows through
the FLASC and allows a lower saturated temperature and
pressure. Part of the entering liquid refrigerant will flash to
vapor once it has passed through the FLASC orifice, thereby
cooling the remaining liquid. The vapor is then recondensed
by the condenser water flowing through the FLASC
chamber.
The subcooled liquid refrigerant drains into a high-side
valve chamber that meters the refrigerant liquid into a flash
economizer chamber. Pressure in this chamber is intermediate between condenser and cooler pressures. At this lower
pressure, some of the liquid refrigerant flashes to gas, further cooling the remaining liquid. The flash gas, having absorbed heat, is returned directly to the compressor second
stage. Here it is mixed with discharge gas that is already compressed by the first-stage impeller. Since the flash gas has to
pass through only half the compression cycle to reach condenser pressure, there is a savings in power.
The cooled liquid refrigerant in the economizer is metered through the low-side valve chamber, reducing the refrigerant pressure. Pressure in the cooler is lower than in the
economizer. Some of the liquid flashes as it passes through
the low side float valve. The cycle is now complete.
OIL COOLING CYCLE
Compressor Oil Cooling —
water cooled. Water flow through the oil cooler is manually
adjusted by a plug valve to maintain an operating temperature at the reservoir of approximately 145 F (63 C). An oil
heater in the reservoir helps to prevent oil from being diluted by the refrigerant. The heater is controlled by the PIC
(Product Integrated Control) and is energized when the oil
temperature is outside the operating temperature range of 150
to 160 F (66 to 71 C).
The compressor oil is
External Gear Oil Cooling — The external gear oil
is also water cooled. Water flow through the gear oil cooler
is manually adjusted by a plug valve to maintain an operating temperature of approximately 130 F (54 C). If so equipped,
an oil heater in the reservoir helps to maintain the oil temperature under cold ambient operating conditions. The heater
is controlled by an internal thermostat.
LUBRICATION CYCLE
Compressor Lubrication Cycle (Refer to item
numbers shown in Fig. 4) —
pump and oil reservoir are contained in the compressor base.
Oil is pumped through an oil cooler and filter to remove heat
and any foreign particles. A portion of the oil is then directed to the shaft-end bearing and the shaft seal. The balance of the oil lubricates the thrust and journal bearings and
the thrust end seal. The bearing and transmission oil returns
directly to the reservoir to complete the cycle. Contact-seal
oil leakage, however,iscollected in an atmospheric float chamber to be pumped back to the main reservoir as the oil
accumulates.
Oil may be charged into the compressor oil reservoir
(Item 8) through a charging valve (Item 6) which also functions as an oil drain. If there is refrigerant in the chiller, however, a hand pump will be required for charging at this
connection.
An oil-charging elbow (Item 3) on the seal-oil return chamber allows oil to be added without pumping. The seal-oil return pump (Item 4) automatically transfers the oil to the main
reservoir. Sight glasses (11) on the reservoir wall permit observation of the oil level.
Amotor-drivenoil pump (Item 10) discharges oil to an oil
cooler/filter (Item 16) at a rate and pressure controlled by an
oil regulator (Item 10). The differential oil pressure (bearing
supply versus oil reservoir) is registered on the control panel.
Water flow through the oil cooler is manually adjusted by
a plug valve (Item 17) to maintain the oil at an operating
temperature of approximately 145 F (63 C). During shutdown, the oil temperature is also maintained at 150 to
160 F (65 to 71 C) by an immersion heater (Item 7) in order
to minimize absorption of refrigerant by the oil.
Upon leaving the cooler section of the oil cooler/filter, the
oil is filtered (Item 15) and a portion is directed to the sealend bearing (Item 1) and the shaft seal (Item 2). The remainder lubricates thrust (Item 14) and journal bearings (Item 12).
Thrust bearing temperature is indicated on the PIC controls.
Oil from both circuits returns by gravity to the reservoir.
The shaft seal of the open compressor drive must be kept
full of lubrication oil, even when the chiller is not operating,
to prevent loss of refrigerant.
If the chiller is not operating and the oil pump has not
operated during the last 12 hours, the control system automatically runs the oil pump for one minute in order to keep
the contact seal filled with oil.
IMPORTANT: If the control power is to be deenergized for more than one day,the chiller refrigerant should
be pumped over to the economizer/storage vessel.
The compressor oil
8
LEGEND
TXV — Thermostatic Expansion Valve
*The FX compressor and the gear have a water cooled oil cooler.
Liquid
Liquid/Vapor
Vapor
Fig. 3 — Refrigeration, Cycle
External Gear Lubrication Cycle (Refer to Item
numbers shown in Fig. 5) —
tained in the gear base.The external gear oil pump is mounted
below the gear with the cooler/filter. Oil is pumped through
an oil cooler/filter to remove heat and any foreign particles.
A portion of the oil is directed to the gear bearings and gear
mesh spray.The remainder is bypassed to the sump. The bearing and transmission oil returns directly to the reservoir to
complete the cycle.
Oil may be charged into the external gear oil reservoir as
described in the section, External Gear Pre-Start Checks,
page 51. Observe the oil level in the oil level glass (Item 4)
on the reservoir wall.
A motor driven oil pump (Item 10) discharges oil to the
oil cooler/filter (Item 12). The pump has an internal pressure
regulator to protect the pump in the event of an obstruction
downstream. Water flow through the oil cooler is manually
adjusted by a plug valve (Item 14) to maintain the oil at an
operating temperature of approximately 130 F (54 C).
Oil reservoir is con-
Upon leaving the cooler section (Item 13) of the oil cooler/
filter, the oil is filtered (Item 11) and is directed to the pressure control valve (Item 7). Before entering the pressure control
valve, the oil pressure (Item 16) and temperature (Item 8)
are monitored by the PIC.
A portion of the oil then lubricates the gear bearings
(Item 2). Another portion is directed through an orifice
(Item 5) to the gear mesh spray (Item 3) to lubricate the gear
mesh (Item 1) during operation. Oil from both circuits returns by gravity to the reservoir.
STARTERS
All starters, whether supplied by Carrier or the customer,
must meet Carrier Starter Specification Z-375. This specification can be obtained from a Carrier Sales Representative. The purpose of this specification is to ensure the compatibility of the starter and the chiller.Many styles of compatible
starters are available, including solid-state , auto-transformer,
full-voltage, and, in the case of low-voltage main power supply, wye-delta closed transition.
ANALOG SIGNAL — An analog signal varies in proportion to the monitored source. It quantifies values between
operating limits. (Example: A temperature sensor is an analog device because its resistance changes in proportion to
the temperature, generating many values.)
DIGIT ALSIGNAL— A digital (discrete) signal is a 2-position
representation of the value of a monitored source.
(Example: A switch is a digital device because it only indicates whether a value is above or below a set point or boundary by generating an on/off,high/low, or open/closed signal.)
VOLATILE MEMORY — Volatile memory is memory in-
capable of being sustained if power is lost and subsequently
restored.
The memories of the PSIO and LID modules are volatile. If the battery in a module is removed or damaged,
all programming will be lost.
General — The 17EX externally geared open-drive cen-
trifugal liquid chiller contains a microprocessor-based control center that monitors and controls all operations of the
chiller.The microprocessor control system matches the cooling capacity of the chiller to the cooling load while providing state-of-the-art chiller protection. The system controls
cooling load within the set point plus the deadband by sensing the leaving chilled water or brine temperature and regulating the inlet guide vane via a mechanically linked actuator motor.The guide vane is a variable flow prewhirl assembly
that controls the refrigeration effect in the cooler by regulating the amount of refrigerant vapor flow into the compressor.An increase in guide vane opening increases capacity.Adecrease in guide vane opening decreases capacity.Chiller
protection is provided by the processor which monitors the
digital and analog inputs and executes capacity overrides or
safety shutdowns, if required.
11
PIC System Components — The Product Integrated
Control (PIC) is the control system on the chiller. See
T able1. The PIC controls the operation of the chiller by monitoring all operating conditions. The PIC can diagnose a problem and let the operator know what the problem is and what
to check. It promptly positions the guide vanes to maintain
leaving chilled water temperature. It can interface with auxiliary equipment such as pumps and cooling tower fans to
turn them on only when required. It continually checks all
safeties to prevent any unsafe operating condition. It also
regulates the oil heater while the compressor is off and the
hot gas bypass valve, if installed. See Fig. 6-10 for the locations of sensors, transducers, and other devices controlled
and/or monitored by the PIC system.
The PIC can be interfaced with the Carrier Comfort
Network (CCN) if desired. It can communicate with other
PIC-equipped chillers and other CCN devices.
The PIC consists of 4 modules housed inside one of 3 locations: the control center, the power panel, or the starter
cabinet. The component names and the control voltage of
each location are listed below (also see Table 1):
• control center
— all extra low-voltage wiring (24 v or less)
REAR
• power panel
— 115 v control voltage
— up to 600 v for oil pump power
• starter cabinet
— chiller power wiring (per job requirement)
Table 1 — Major PIC Components and
Panel Locations*
PIC COMPONENT
Processor Sensor Input/Output Module
(PSIO)
Starter Management Module (SMM)Starter Cabinet
Local Interface Device (LID)Control Center
6-Pack Relay BoardControl Center
8-Input Modules (Optional)Control Center
4-In/2-Out ModulePower Panel
Oil Differential Pressure/Power Supply
Module
Oil Heater Contactor (1C)Power Panel
Compressor Oil Pump Contactor (2C)Power Panel
Gear Oil Pump Contactor (5C)Power Panel
Hot Gas Bypass Relay (3C) (Optional)Power Panel
Control Transformers (T1-T4)Power Panel
Control and Oil Heater Voltage Selector (S1) Power Panel
Temperature SensorsSee Fig. 7
Pressure TransducersSee Fig. 7
*See Fig. 6-10.
PANEL
LOCATION
Control Center
Control Center
1—Gear Oil Pressure Sensor
2—Thrust Bearing Temperature and
Impeller Displacement Cable
3—Discharge Temperature Sensor
4—Guide Vane Conduit and Cable
5—High Pressure Cutout Switch
LEGEND
6—Compressor Oil Cooler
Solenoid Conduit
7—Oil Heater Conduit
8—Motor Space Heater Conduit
9—Gear Oil Temperature Sensor
10 — Motor High Temperature Switch Cable
11 — Motor Water Cooling Leak Detector
12 — Discharge Oil Pressure Sensor
TEWAC — Totally Enclosed Water-to-Air Cooled
Fig. 6 — 17EX Controls and Sensor Locations
12
Cable (TEWAC Motor Only)
LEGEND
13 — Condenser Pressure Transducer
14 — Condenser Entering Water
Temperature Sensor
15 — Condenser Entering and Leaving Water
Temperature Cable
16 — Oil Suction Pressure Sensor
17 — Oil Pump Conduit
18 — Oil Pump Sensor
19 — PIC Control Panel
20 — Condenser Leaving Water
Temperature Sensor
21 — Gear Oil Cooler Solenoid Conduit
LEGEND
22 — Cooler Temperature Cable
23 — Cooler Leaving Water Temperature Sensor
24 — Cooler Entering Water Temperature Sensor
25 — Cooler Pressure Sensor
26 — Refrigerant Charging Valve
Fig. 6 — 17EX Controls and Sensor Locations (cont)
13
Fig. 6 — 17EX Controls and Sensor Locations (cont)
Fig. 10 — 17EX Chiller Power Panel and Controls Connections
PROCESSOR/SENSOR INPUT/OUTPUT MODULE (PSIO)
— This module contains all the operating software needed
to control the chiller. The 17EX uses 5 pressure transducers
and 8 thermistors to sense pressures and temperatures. These
inputs are connected to the PSIO module. The PSIO also
provides outputs to the guide vane actuator, compressor and
gear oil pumps, oil heater, hot gas bypass (optional), and alarm
contact. The PSIO communicates with the LID, the SMM,
and the optional 8-input modules for user interface and starter
management.
ST ARTER MANAGEMENT MODULE (SMM) — This module is located within the starter cabinet. This module initiates PSIO commands for starter functions such as start/
stop of the compressor; start/stop of the condenser and chilled
water pumps; start/stop of the tower fan, spare alarm contacts, and the shunt trip. The SMM monitors starter inputs
such as flow switches, line voltage, remote start contact, spare
safety, condenser high pressure, oil pump interlock, motor
current signal, starter 1M and run contacts, and the kW transducer input (optional). The SMM contains logic capable of
safely shutting down the chiller if communication with
the PSIO is lost.
LOCALINTERFACE DEVICE (LID) — The LID is mounted
to the control center and allows the operator to interface with
the PSIO or other CCN devices. It is the input center for all
local chiller set points, schedules, set-up functions, and options. The LID has a STOP button, an alarm light, 4 buttons
for logic inputs, and a display. The function of the 4 buttons
or ‘‘softkeys’’ are menu driven and are shown on the display
directly above the key.
SIX-PACK RELAY BOARD (6-Pack Relay Board) — This
device is a cluster of 6 pilot relays located in the control
center. It is energized by the PSIO for the compressor oil
pump, oil heater, alarm, optional hot gas bypass relay, auxiliary oil pump.
EIGHT-INPUT (8-Input) MODULES — One optional module is factory installed in the control center panel when ordered. There can be up to 2 of these modules per chiller with
8 spare inputs each. They are used whenever chilled water
reset, demand reset, or reading a spare sensor is required.
The sensors or 4 to 20 mA signals are field-installed.
The spare temperature sensors must have the same
temperature/resistance curve as the other temperature sensors on this unit. These sensors are rated 5,000 ohm at 75 F
(25 C).
FOUR-IN/TWO-OUT(4-IN/2-OUT) MODULE —Thismodule monitors and controls the external gear lubrication system. It energizes the gear oil pump and is located in the power
panel.
OIL HEATER CONTACTOR (1C) — This contactor is located in the power panel and operates the heater at 115 v. It
is controlled by the PIC to maintain oil temperature during
chiller shutdown.
COMPRESSOR OILPUMP CONTACTOR(2C)ANDGEAR
OIL PUMP CONTACTOR (5C) — These contactors are located in the power panel. They operate all 200 to 575-v oil
pumps. The PIC energizes the contactor to turn on the oil
pumps as necessary.
HOTGASBYPASSCONTACTORRELAY (3C)
(Optional) — This relay, located in the power panel, controls the opening of the hot gas bypass valve. The PIC energizes the relay during low load, high lift conditions.
OIL AUXILIARY RELAY (4C) — This relay opens the oil
cooler solenoid valve and interlocks the oil pump with the
compressor (special order).
CONTROL TRANSFORMERS (T1-T4) — These transformers are located in the power panel and convert
incoming control voltage to either 21 vac power for the PSIO
module and options modules, or 24 vac power for 3 power
panel contactor relays and a control solenoid valve.
CONTROL AND OIL HEATER VOLTAGE SELECTOR
(S1) — It is necessary to use 115 v incoming control power
in the power panel. The switch must be set to the 115-v
position.
OIL DIFFERENTIAL PRESSURE/POWERSUPPLY
MODULE — This module, which is located in the control
center, provides 5 vdc power for the transducers and LID
backlight. This module outputs the difference between two
pressure transducer input signals. The module subtracts oil
supply pressure from transmission sump pressure and outputs the difference as an oil differentialpressure signal to the
PSIO. The PSIO converts this signal to differential oil pressure. To calibrate this reading, refer to the Troubleshooting,
Checking Pressure Transducers section on page 84.
LID Operation and Menus (Fig. 11-17)
GENERAL
• The LID display automatically reverts to the default screen
(Fig. 11) after 15 minutes if no softkey activity takes place
and if the chiller is not in PUMPDOWN mode
• When not displaying the default screen, the upper righthand corner of the LID displays the name of the screen
that you have entered (Fig. 12).
• The LID may be configured in English or SI units, through
the LID configuration screen.
• Local Operation — Pressing the LOCAL
the PIC in LOCAL operation mode, and the control ac-
cepts modification to programming from the LID only. The
PIC uses the Local Time Schedule to determine chiller start
and stop times.
• CCN Operation — Pressing the CCN softkey places the
PIC in the CCN operation mode, and the control accepts
modifications from any CCN interface or module (with the
proper authority), as well as the LID. The PIC uses the
CCN time schedule to determine start and stop times.
Fig. 11 — LID Default Screen
ALARMS AND ALERTS — An alarm (*) or alert (!) status
is indicated on the default screen and the status tables. An
alarm (*) shuts down the compressor. An alert (!) notifies
the operator that an unusual condition has occurred. The chiller
continues to operate when an alert is shown.
Alarms are indicated when the control center alarm light
(!) flashes. The primary alarm message is viewed on the default screen and an additional, secondary, message and
troubleshooting information are sent to the ALARM HISTORY table.
softkey places
16
NOTE: When an alarm is detected, the LID default screen
freezes (stops updating) at the time of alarm. The freeze enables the operator to view the chiller conditions at the time
of the alarm. The status tables show the updated informa-
tion. Once all alarms have been cleared (by pressing the
RESET
softkey), the default LID screen returns to normal
operation.
Fig. 12 — LID Service Screen
LID DEFAULT SCREEN MENU ITEMS — To perform
any of the operations described below, the PIC must be powered up and have successfully completed its self test.
The default screen menu selection offers four options
(STATUS, SCHEDULE, SETPOINT, and SERVICE). The
STATUS menu allows viewing and limited calibration/
modification of control points and sensors, relays and contacts, and the options board. The SCHEDULE menu allows
viewing and modification of the Local Control, CCN Control, and Ice Build time schedules. Numerous set points including Base Demand Limit, LCW, ECW, and Ice Build can
be adjusted under the SETPOINT menu. The SERVICE menu
can be used to revise alarm history, control test, control algorithm status, equipment configuration, equipment service,
time and date, attach to network, log out of device, controller identification, and LID configurations. Figures 15 and 16
provide additional information on the menu structure.
Press the MENU
softkey to select from the 4 options.
To view or change parameters within any menu structure,
use the SELECT
softkey to choose the desired table or
item. The softkey modification choices displayed will depend on whether the selected item is a discrete point, analog point, or an override point. Press the softkey that corresponds to your configuration selection or press the
QUIT softkey. If the QUIT softkey is depressed, the
configuration will not be modified. Use the following softkeys to access and select the desired section.
MENU STRUCTURE — To perform any of the operations
described below, the PIC must be powered up and have successfully completed its self test.
• Press MENU
to select from the four available options.
• Press NEXT or PREVIOUS to highlight the desired
entry.
• Press SELECT to access the highlighted point.
• Press QUIT to leave the selected decision or field without saving any changes.
• Or, press ENTER to leave the selected decision or field
and save changes.
TOVIEWOR CHANGE POINT STATUS (Fig. 13) — Point
Status is the actual value of all of the temperatures, pressures, relays, and actuators sensed and controlled by the PIC.
1. On the Menu screen, press STATUS
to view the list of
Point Status tables.
2. Press NEXT or PREVIOUS to highlight the desired
status table. The list of tables is:
• STATUS01 — Status of control points and sensors
• STATUS02 — Status of relays and contacts
• STATUS03 — Status of both optional 8-input modules
and sensors
• STATUS04 — Gear oil temperature and pressure
• Press the softkey that corresponds to the desired menu
structure.
Fig. 13 — Example of Point Status Screen
(Status01)
17
3. Press SELECT to view the desired Point Status table.
4. OnthePointStatustablepressNEXTor
PREVIOUS
until desired point is displayed on the screen.
Override Indication — An override value is indicated by
‘ ‘SUPVSR,’’‘‘SERVC,’’or ‘‘BEST’’ flashing next to the point
value on the Status table.
TO VIEW OR CHANGE TIME SCHEDULE OPERATION
(Fig. 14)
1. On the Menu screen, press SCHEDULE
.
For Discrete Points — Press START or STOP ,
or NO ,ONor OFF , etc. to select the desired
YES
state.
ForAnalogPoints—PressINCREASEor
DECREASE
to select the desired value.
5. Press ENTER to register new value.
OVERRIDE OPERATIONS
NOTE: When overriding or changing metric values, it is nec-
essary to hold the softkey down for a few seconds in order
to see a value change, especially on kilopascal values.
To Remove an Override
1. OnthePointStatustablepressNEXTor
PREVIOUS
to highlight the desired point.
2. Press NEXT or PREVIOUS to highlight one of the
following schedules.
OCCPC01S — LOCAL Time Schedule
OCCPC02S — ICE BUILD Time Schedule
OCCPC03-99S — CCN Time Schedule (Actual
number is defined in CONFIG table.)
3. Press SELECT to access and view the time schedule.
4. Press NEXT or PREVIOUS to highlight the desired period or override that you wish to change.
5. Press SELECT to access the highlighted period or
override.
2. Press SELECT to access the highlighted point.
3. Press RELEASE to remove the override and return the
point to the PIC’s automatic control.
Fig. 14 — Example of Time Schedule
Operation Screen
18
CCN
Start Chiller In CCN Control
Start Chiller In Local Control
DEFAULT SCREEN
LOCALRESET
MENU
(SOFTKEYS)
Clear Alarms
NEXT
NEXT
START
INCREASE
ENABLE
STATUS
List the
Status Tables
STATUS
STATUS
STATUS
STATUS
PREVIOUS
PREVIOUS
STOPRELEASE
DECREASE
DISABLE
SCHEDULESETPOINT
01
02
03
04
SELECT
SELECT
RELEASE
RELEASE
Access Main Menu
SERVICE
EXIT
EXIT
ENTER
ENTER
ENTER
(SELECT A T ABLE)
(SELECT A POINT
ON THE TABLE)
(MODIFY A
DISCRETE POINT) or
(MODIFY AN
ANALOG POINT) or
(MODIFY CONTROL
OPTIONS)
Select a Schedule
NEXT
Select a Time Period/Override
NEXT
Modify a Schedule Time
INCREASE
Add/Eliminate a Day
ENABLE
123
List the Schedules
OCCPC01S - Local Time Schedule
OCCPC02S - Ice Build Time Schedule
OCCPC03S-99S - CCN Time Schedule
• To modify — PSIO CCN Address • To View — PSIO Software Version
LID CONFIGURATION
DECREASE
LEGEND
CCN— Carrier Comfort Network
HGBP — Hot Gas Bypass
LID— Local Interface Device
NOTE: SERVICE TABLES:
SERVICE1: — Capacity Override
— Type of Chilled Medium
— Alert Temperature
— Flow Verification
— Deadband
— Recycle Restart Time
— Surge/HGBP Operation
— Motor Voltage, RLA, and Frequency
— Starter Type
— Condenser Freeze Safety
— Soft Stop Configuration
— Start to Stop Timer
— Gear Oil Pump Configuration
ENTER
Default Screen
CCN
EXIT
(last 2 digits on part number indicate software version)
LID Configuration Table
INCREASE
• To Modify — LID CCN Address
LOCAL
DECREASE
— English or S.I. Metric Units
— Password
RESET
ENTER
SERVICE2: — 8-input Modules
SERVICE3: — Proportional Inc each Band
MENU
— 20 mA Power Source
— Proportional Dec each Band
— Proportional ECW Gain
— Maximum Guide Vane Opening
EXIT
• To View — LID Software Version
(last 2 digits of part number
indicate software version)
Fig. 16 — 17EX Service Menu Structure (cont)
21
6. a. Press INCREASE or DECREASE to change the
time values. Override values are in one-hour incre-
ments, up to 4 hours.
b. Press ENABLE to select days in the day-of-week
fields. Press DISABLE
to eliminate days from the
period.
7. Press ENTER to register the values and to move
horizontally (left to right) within a period.
8. Press EXIT to leave the period or override.
9. Either return to Step 4 to select another period or
override, or press EXIT
again to leave the cur-
rent time schedule screen and save the changes.
4. Press SELECT to modify the highlighted set point.
5. Press INCREASE or DECREASE to change the selected set point value.
6. Press ENTER to save the changes and return to the
previous screen.
10. Holiday Designation (HOLIDEF table) may be found in
the Service Operation section, page 42.You must assign
the month, day, and duration for the holiday.The Broadcast function in the BRODEF table also must be enabled for holiday periods to function.
TO VIEW AND CHANGE SET POINTS (Fig. 17)
1. To view the Set Point table, at the Menu screen press
SETPOINT
.
2. There are 4 set points on this screen: Base Demand Limit;
LCW Set Point (leaving chilled water set point); ECW
Set Point (entering chilled water set point); and ICE BUILD
set point. Only one of the chilled water set points can be
active at one time, and the type of set point is activated
in the Service menu. ICE BUILD is also activated and
configured in the Service menu.
3. Press NEXT or PREVIOUS to highlight the desired
set point entry.
Fig. 17 — Example of Set Point Screen
SERVICE OPERATION — To view the menu-driven programs available for Service Operation, see the Service Operation section, page 42. For examples of LID display screens,
see Table 2.
LEGEND FOR TABLE 2 — LID DISPLAY DATA
CCN— Carrier Comfort Network
CHWR — Chilled Water Return
CHWS — Chilled Water Supply
Compr — Compressor
Dec— Decrease
Ecw— Entering Chilled Water
HGBP — Hot Gas Bypass
Inc— Increase
LCW— Leaving Chilled Water
mA— Milliamps
P—Pressure
PIC— Product Integrated Controls
Refrig — Refrigerant
T—Temperature
Temp— Temperature
22
Table 2 — LID Display Data
NOTES:
IMPORTANT: The following notes apply to all Table 2
examples.
1. Only 12 lines of information appear on the LID screen at any one
time. Pressthe NEXT
or to view items below or above the current screen. If you have a
chiller with a backlit LID, press the NEXT
forward; press the PREVIOUS
2. Toaccess the information shown in Examples 6 through 14, enter
your 4-digit password after pressing the SERVICE
softkeys arepressed for 15 minutes, the LIDautomatically logs off
(to prevent unrestricted access to PIC controls) and reverts to the
default screen. If this happens, you must reenter your password
to access the tables shown in Examples 6 through 14.
3. Termsin the Description column of these tables are listed as they
appear on the LID screen.
4. The LID may be configured in English or Metric (SI) units using
theLIDCONFIGURATIONscreen. See the ServiceOperation section, page 42, for instructions on making this change.
To access this display from the LID default screen:
1. PressMENU
2. Press STATUS
3. Press SELECT
or PREVIOUS softkey to highlightapoint
softkey twice to page
softkey twice to page back.
softkey.If no
EXAMPLE1—STATUS01 DISPLAY SCREEN
.
(STATUS01 will be highlighted).
.
5. The items in the Reference Point Name column
the LID screen
Building Supervisor software. They are listed in these tables as a
convenience to the operator if it is necessary to cross reference
CCN/BS documentation or use CCN/BS programs. For more information, see the 17EX CCN literature.
6. Reference Point Names shown in these tables in all capital letters
can be read by CCN and Building Supervisor software. Of these
capitalized names, those preceded by an asterisk can also be
changed (that is, written to) by the CCN, Building Supervisor software and the LID. Capitalized Reference Point Names preceded
by two asterisks can be changed only from the LID. Reference
Point Names in lower case type can be viewed by CCN or Building Supervisor software only by viewing the whole table.
7. Alarms and Alerts: An asterisk
screen
tion point in the far right field of the LID screen indicates an alert
state. The asterisk (or exclamation point) indicates that the value
on that line has exceeded (or is approaching) a limit. For more
information on alarms and alerts, see the Alarms and Alerts section, page 16.
. They are data or variable names used in CCN or
in the far right field of a LID status
indicates that the chiller is in an alarm state; an exclama-
do not appear on
DESCRIPTIONRANGEUNITS
Control ModeReset.Off. Local. CCNMODE
Run StatusTimeout. Recycle. Startup.STATUS
Occupied ?No/YesOCC
Alarm StateNormal/AlarmALM
*Chiller Start/StopStop/StartCHIL S S
Base Demand Limit40-100%DLM
*Active Demand Limit40-100%DEM LIM
Compressor Motor Load0-999%CA L
Current0-999%CA P
Amps0-9999AMPSCA A
*Target Guide Vane Pos0-100%GV TRG
Actual Guide Vane Pos0-100%GV ACT
Water/Brine: Setpoint10-120 (–12.2-48.9)DEG F (DEG C)SP
*Control Point10-120 (–12.2-48.9)DEG F (DEG C)LCW STPT
Entering Chilled Water–40-245 (–40-118)DEG F (DEG C)ECW
Leaving Chilled Water–40-245 (–40-118)DEG F (DEG C)LCW
Entering Condenser Water–40-245 (–40-118)DEG F (DEG C)ECDW
Leaving Condenser Water–40-245 (–40-118)DEG F (DEG C)LCDW
Evaporator Refrig Temp–40-245 (–40-118)DEG F (DEG C)ERT
Evaporator Pressure–6.7-420 (–46-2896)PSI (kPa)ERP
Condenser Refrig Temp–40-245 (–40-118)DEG F (DEG C)CRT
Condenser Pressure–6.7-420 (–46-2896)PSI (kPa)CRP
Discharge Temperature–40-245 (–40-118)DEG F (DEG C)CMPD
Bearing Temperature–40-245 (–40-118)DEG F (DEG C)MTRB
Motor Winding Temp†–40-245 (–40-118)DEG F (DEG C)MTRW
Motor Winding Hi
Temp Cutout
Oil Sump Temperature–40-245 (–40-118)DEG F (DEG C)OILT
Oil Pressure Transducer†–6.7-420 (–46-2896)PSI (kPa)OILP
Oil Pressure**–6.7-420 (–46-2896)PSID (kPad)OILPD
Line Voltage: Percent0-999%V P
*Remote Contacts InputOff/OnREMCON
Total Compressor Starts0-65535c starts
Starts in 12 Hours0-8STARTS
Compressor Ontime0-500000.0HOURSc hrs
*Service Ontime0-32767HOURSS HRS
*Compressor Motor kW0-9999kWCKW
†Information is applicable to hermetic chillers (19EX) only.
**Oil pressure is read directly from a differential pressure module on 17EX chillers.
NOTE: values preceded by an asterisk (*) can be forced (changed by an operator) from the LID screen
or from another control device (such as a Carrier Comfort Network [CCN] terminal).
To access this display from the LID default screen:
1. PressMENU
2. Press STATUS
3. Scroll down to highlight STATUS02.
4. Press SELECT
.
.
.
Table 2 — LID Display Data (cont)
DESCRIPTION
Hot Gas Bypass RelayXOFF/ONHGBR
*Chilled Water PumpXOFF/ONCHWP
Chilled Water FlowXNO/YESEVFL
*Condenser Water PumpXOFF/ONCDP
Condenser Water FlowXNO/YESCDFL
Compressor Start RelayXOFF/ONCMPR
Compressor Start ContactXOPEN/CLOSED1CR AUX
Compressor Run ContactXOPEN/CLOSEDRUN AUX
Starter Fault ContactXOPEN/CLOSEDSTR FLT
Pressure Trip ContactXOPEN/CLOSEDPRS TRIP
Single Cycle DropoutXNORMAL/ALARMV1 CYCLE
Oil Pump RelayXOFF/ONOILR
Oil Heater RelayXOFF/ONOILH
Motor Cooling Relay†XOFF/ONMTRC
Auxiliary Oil Pump RelayXOFF/ONAUXOILR
*Tower Fan RelayXOFF/ONTFR
Compr. Shunt Trip RelayXOFF/ONTRIPR
Alarm RelayXNORMAL/ALARMALM
Spare Prot Limit InputXALARM/NORMALSPR PL
†Information is applicable to hermetic machines only.
NOTE: values preceded by an asterisk (*) can be forced (changed by an operator) from the LID screen
or from another control device (such as a Carrier Comfort Network [CCN] terminal).
To access this display from the LID default screen:
*Temp Reset 4-20 mA4-20mARES OPT
*Common CHWS Sensor–40-245 (–40-118)DEG F (DEG C)CHWS
*Common CHWR Sensor–40-245 (–40-118)DEG F (DEG C)CHWR
*Remote Reset Sensor–40-245 (–40-118)DEG F (DEG C)R RESET
*Temp Sensor — Spare 1–40-245 (–40-118)DEG F (DEG C)SPARE1
*Temp Sensor — Spare 2–40-245 (–40-118)DEG F (DEG C)SPARE2
*Temp Sensor — Spare 3–40-245 (–40-118)DEG F (DEG C)SPARE3
OPTIONS BOARD 2
*4-20 mA — Spare 14-20mASPARE1 M
*4-20 mA — Spare 24-20mASPARE2 M
*Temp Sensor — Spare 4–40-245 (–40-118)DEG F (DEG C)SPARE4
*Temp Sensor — Spare 5–40-245 (–40-118)DEG F (DEG C)SPARE5
*Temp Sensor — Spare 6–40-245 (–40-118)DEG F (DEG C)SPARE6
*Temp Sensor — Spare 7–40-245 (–40-118)DEG F (DEG C)SPARE7
*Temp Sensor — Spare 8–40-245 (–40-118)DEG F (DEG C)SPARE8
*Temp Sensor — Spare 9–40-245 (–40-118)DEG F (DEG C)SPARE9
NOTE: values preceded by an asterisk (*) can be forced (changed by an operator) from the LID screen
or from another control device (such as a Carrier Comfort Network [CCN] terminal).
REFERENCE POINT NAME
(ALARM HISTORY)
24
EXAMPLE4—STATUS04 DISPLAY SCREEN
To access this display from the LID default screen:
1. PressMENU
2. Press STATUS
3. Scroll down to highlight STATUS04.
4. Press SELECT
.
.
.
Table 2 — LID Display Data (cont)
DESCRIPTIONRANGEUNITS
Main Gear Oil PumpOFF/ONMAINPMP1
Auxiliary Gear Oil PumpOFF/ONAUXPMP2
Gear Oil Pressure−6.7 to 420 (−46 to 2896)psi (kPa)GEAROILP
Gear Oil Temperature−40 to 245 (−40 to 118)DEG F (DEG C)GEAROILT
EXAMPLE 5 — SETPOINT DISPLAY SCREEN
To access this display from the LID default screen:
1. PressMENU
2. Press SETPOINT
DESCRIPTIONCONFIGURABLE RANGEUNITSREFERENCE POINT NAMEDEFAULT VALUE
Base Demand Limit40-100%DLM100
LCW Setpoint20-120 (–6.7-48.9)DEG F (DEG C)lcw sp
ECW Setpoint20-120 (–6.7-48.9)DEG F (DEG C)ecw sp60.0 (15.6)
ICE BUILD Setpoint20- 60 (–6.7-15.6)DEG F (DEG C)ice sp
.
.
REFERENCE POINT NAME
(ALARM HISTORY)
50.0 (10.0)
40.0 ( 4.4)
25
Table 2 — LID Display Data (cont)
EXAMPLE 6 — CONFIGURATION (CONFIG) DISPLAY SCREEN
To access this display from the LID default screen:
1. PressMENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT
5. Scroll down to highlight CONFIG.
6. Press SELECT
DESCRIPTIONCONFIGURABLE RANGEUNITSREFERENCE POINT NAMEDEFAULT VALUE
RESET TYPE 1
Degrees Reset at 20 mA–30-30 (–17-17)DEG F (DEG C)deg 20ma
RESET TYPE 2
Remote Temp (No Reset)–40-245 (–40-118)DEG F (DEG C)res rt1
Remote Temp (Full Reset)–40-245 (–40-118)DEG F (DEG C)res rt265 (18)
Degrees Reset–30-30 (–17-17)DEG F (DEG C)res rt10D(6D)
RESET TYPE 3
CHW Delta T (No Reset)0-15 (0-8)DEG F (DEG C)restd 1
CHW Delta T (Full Reset)0-15 (0-8)DEG F (DEG C)restd 20D(0D)
Degrees Reset–30-30 (–17-17)DEG F (DEG C)deg chw5D(3D)
Select/Enable Reset Type0-3res sel
ECW CONTROL OPTIONDISABLE/ENABLEecw opt
Demand Limit At 20 mA40-100%dem 20ma40
20 mA Demand Limit OptionDISABLE/ENABLEdem selDISABLE
To access this display from the LID default screen:
1. PressMENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT
5. Scroll down to highlight LEAD/LAG.
6. Press SELECT
DESCRIPTIONCONFIGURABLE RANGEUNITSREFERENCE POINT NAMEDEFAULT VALUE
LEAD/LAG SELECT
DISABLE =0, LEAD =1,
LAG =2, STANDBY =3
Load Balance OptionDISABLE/ENABLEloadbalDISABLE
Common Sensor OptionDISABLE/ENABLEcommsensDISABLE
LAG Percent Capacity25-75%lagper
LAG Address1-236lagadd
LAG START Timer2-60MINlagstart10
LAG STOP Timer2-60MINlagstop10
PRESTART FAULT Timer0-30MINpreflt5
STANDBY Chiller OptionDISABLE/ENABLEstndoptDISABLE
STANDBY Percent Capacity25-75%stndper
STANDBY Address1-236stnd add
.
.
.
.
LEAD/LAG CONFIGURATION SCREEN
0-3leadlag0
50
92
50
93
27
Table 2 — LID Display Data (cont)
EXAMPLE 8 — SERVICE1 DISPLAY SCREEN
To access this display from the LID default screen:
1. PressMENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT
5. Scroll down to highlight SERVICE1.
6. Press SELECT
DESCRIPTIONCONFIGURABLE RANGEUNITSREFERENCE POINT NAMEDEFAULT VALUE
Motor Temp Override*150-200 (66-93)DEG F (DEG C)mt over
Cond Press Override90-200 (620-1379)PSI (kPa)cpover
Refrig Override Delta T2-5 (1-3)DEG F (DEG C)ref over3D (1.6D)
Chilled MediumWater/BrinemediumWATER
Brine Refrig Trippoint8-40 (–13.3-4)DEG F (DEG C)br trip
Compr Discharge Alert125-200 (52-93)DEG F (DEG C)cd alert
Bearing Temp Alert165-210 (74-99)DEG F (DEG C)tb alert175 (79)
Water Flow Verify Time0.5-5MINwflow t
Oil Press Verify Time15-300SECoilpr t15
Water/Brine Deadband0.5-2.0 (0.3-1.1)DEG F (DEG C)cw db
Recycle Restart Delta T2.0-10.0 (1.1-5.6)DEG F (DEG C)rcycrdt5 (2.8)
Recycle Shutdown Delta0.5-4.0 (.27-2.2)rcycsdt1.0 (0.6)
Surge Limit/HGBP Option0/1srg hgbp
Select: Surge=0, HGBP=1
Surge/HGBP Delta T10.5-15 (0.3-8.3)DEG F (DEG C)hgb dt1
Surge/HGBP Delta P130-170 (207-1172)PSI (kPa)hgb dp150 (345)
Min. Load Points (T1/P1)
Surge/HGBP Delta T20.5-15 (0.3-8.3)DEG F (DEG C)hgb dt2
Surge/HGBP Delta P230-170 (207-1172)PSI (kPa)hgb dp285 (586)
Full Load Points (T2/P2)
Surge/HGBP Deadband1-3 (0.6-1.6)DEG F (DEG C)hgb dp
Surge Delta Percent Amps10-50%surge a
Surge Time Period1-5MINsurge t2
Demand Limit Source0/1dem src
Select: Amps=0, Load=1
Amps Correction Factor1-8corfact3
Motor Rated Load Amps1-9999AMPSa fs
Motor Rated Line Voltage1-9999VOLTSv fs460
Meter Rated Line kW1-9999kWkw fs600
Line Frequency0/1HZfreq0
Select: 0=60 Hz, 1=50 Hz
Compr Starter TypeREDUCE/FULLstarterREDUCE
Condenser Freeze Point–20-35 (–28.9-1.7)DEG F (DEG C)cdfreeze34 (1)
Soft Stop Amps Threshold40-100%softstop100
Stop to Start Timer3-50MINstopmtr20
Spare Temp 4 Enable0-4spr4 en
Spare Temp 4 Alert–40-245 (–40-118)DEG F (DEG C) spr4 al245 (118)
Spare Temp 5 Enable0-4spr5 en0
Spare Temp 5 Alert–40-245 (–40-118)DEG F (DEG C) spr5 al
Spare Temp 6 Enable0-4spr6 en0
Spare Temp 6 Alert–40-245 (–40-118)DEG F (DEG C) spr6 al
Spare Temp 7 Enable0-4spr7 en0
Spare Temp 7 Alert–40-245 (–40-118)DEG F (DEG C) spr7 al245 (118)
Spare Temp 8 Enable0-4spr8 en
Spare Temp 8 Alert–40-245 (–0-118)DEG F (DEG C) spr8 al245 (118)
Spare Temp 9 Enable0-4spr9 en0
Spare Temp 9 Alert–40-245 (–40-118)DEG F (DEG C) spr9 al
NOTE: This screen provides the means to generate alert messages based on exceeding the ‘‘Temp’’threshold for each point listed. If the ‘‘Enable’’
is set to 1, a value above the ‘‘Temp’’ threshold generates an alert message. If the ‘‘Enable’’ is set to 2, a value below the ‘‘Temp Alert’’ threshold
generates an alert message. If the ‘‘Enable’’ is set to 0, alert generation is disabled. If the ‘‘Enable’’ is set to 3, a value above the ‘‘Temp’’ threshold
generates an alarm. If the ‘‘Enable’’ is set to 4, a value below the ‘‘Temp’’ threshold generates an alarm.
.
.
.
.
DESCRIPTIONCONFIGURABLE RANGEUNITSREFERENCE POINT NAME DEFAULT VALUE
0
0
245 (118)
0
245 (118)
245 (118)
0
0
245 (118)
245 (118)
0
245 (118)
EXAMPLE 10 — SERVICE3 DISPLAY SCREEN
To access this display from the LID default screen:
1. PressMENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT
5. Scroll down to highlight SERVICE3.
DESCRIPTIONCONFIGURABLE RANGEUNITSREFERENCE POINT NAMEDEFAULT VALUE
To access this display from the LID default screen:
1. PressMENU
2. Press SERVICE
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT
5. Scroll down to highlight MAINT01.
DESCRIPTIONRANGE/STATUSUNITSREFERENCE POINT NAME
CAPACITY CONTROL
Control Point10-120 (–12.2-48.9)DEG F (DEG C)ctrlpt
Leaving Chilled Water–40-245 (–40-118)DEG F (DEG C)LCW
Entering Chilled Water–40-245 (–40-118)DEG F (DEG C)ECW
Control Point Error–99-99 (–55-55)DEG F (DEG C)cperr
ECW Delta T–99-99 (–55-55)DEG F (DEG C)ecwdt
ECW Reset–99-99 (–55-55)DEG F (DEG C)ecwres
LCW Reset–99-99 (–55-55)DEG F (DEG C)lcwres
Total Error + Resets–99-99 (–55-55)DEG F (DEG C)error
Guide Vane Delta–2-2%gvd
Target Guide Vane Pos0-100%GVTRG
Actual Guide Vane Pos0-100%GVACT
Proportional Inc Band2-10gv inc
Proportional Dec Band2-10gv dec
Proportional ECW Gain1-3gv ecw
Water/Brine Deadband0.5-2 (0.3-1.1)DEG F (DEG C)cwdb
NOTE: Overriding is not supported on this maintenance screen.Active overrides show the associated point in alert (*). Reference point names with
capital letters can be read by CCN and Building Supervisor software.
.
.
.
EXAMPLE 12 — MAINTENANCE (MAINT02) DISPLAY SCREEN
To access this display from the LID default screen:
1. PressMENU
2. Press SERVICE
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT
5. Scroll down to highlight MAINT02.
6. Press SELECT
OVERRIDE/ALERT STATUS
MOTOR WINDING TEMP†–40-245 (–40-118)DEG F (DEG C)MTRW
Override Threshold150-200 (66-93)DEG F (DEG C)mt over
CONDENSER PRESSURE–6.7-420 (–42-2896)PSI (kPa)CRP
Override Threshold90-245 (621-1689)PSI (kPa)cp over
EVAPORATOR REFRIG TEMP–40-245 (–40-118)DEG F (DEG C)ERT
Override Threshold2-45 (1-7.2)DEG F (DEG C)rt over
DISCHARGE TEMPERATURE–40-245 (–40-118)DEG F (DEG C)CMPD
Alert Threshold125-200 (52-93)DEG F (DEG C)cd alert
BEARING TEMPERATURE–40-245 (–40-118)DEG F (DEG C)MTRB
Alert Threshold175-185 (79-85)DEG F (DEG C)tb alert
†Information is applicable to hermetic machines (19EX) only.
NOTE: Overriding is not supported on this maintenance screen.Active overrides show the associated point in alert (*). Reference point names with
capital letters can be read by CCN and Building Supervisor software.
.
.
.
.
DESCRIPTIONRANGE/STATUSUNITSREFERENCE POINT NAME
30
Loading...
+ 90 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.