Centrifugal liquid chillers are designed to provide safe
and reliable service when operated within design specifications. When operating this equipment, use good judgment and safety precautions to avoid damage to equipment and property or injury to personnel.
Be sure you understand and follow the procedures and
safety precautions contained in the chiller instructions
as well as those listed in this guide.
DO NOT VENT refrigerant relief valves within a building. Outlet
from rupture disc or relief valve must be vented outdoors in accordance with the latest edition of ASHRAE (American Society of
Heating, Refrigeration, and Air Conditioning Engineers) 15. The
accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ASHRAE 15,
especially for enclosed and low overhead spaces. Inhalation of high
concentrations of vapor is harmful and may cause heart irregularities, unconsciousness, or death. Misuse can be fatal.Vaporisheavier
than air and reduces the amount of oxygen available for breathing.
Product causes eye and skin irritation. Decomposition products are
hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a chiller
for any purpose. Oxygen gas reacts violently with oil, grease, and
other common substances.
NEVER EXCEED specified test pressures, VERIFY the allowable
test pressure by checking the instruction literature and the design
pressures on the equipment nameplate.
DO NOT USE air for leak testing. Use only refrigerant or dry
nitrogen.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly installed and
functioning before operating any machine.
DO NOT WELD OR FLAME CUT any refrigerant line or vessel
until all refrigerant (liquid andvapor)hasbeenremovedfromchiller.
Traces of vapor should be displaced with dry air or nitrogen and
the work area should be well ventilated. Refrigerant in contact with
an open flame produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig chiller sections or
the entire assembly.
DO NOT work on high-voltage equipment unless you are a qualified electrician.
DO NOTWORKON electrical components, including control panels, switches, starters, or oil heater until you are sure ALLPOWER
IS OFF and no residual voltage can leak from capacitors or solidstate components.
LOCK OPENANDTAGelectrical circuits during servicing.IF WORK
IS INTERRUPTED, confirm that all circuits are deenergized before resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it into the
eyes. USE SAFETY GOGGLES. Wash any spills from the skin
with soap and water .If any enters the eyes, IMMEDIATELYFLUSH
EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refrigerant cylinder. Dangerous overpressure can result. When necessary to heat
refrigerant, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or
attempt to refill them. It is DANGEROUS AND ILLEGAL. When
cylinder is emptied, evacuate remaining gas pressure, loosen
the collar and unscrew and discard the valve stem. DO NOT
INCINERATE.
CHECK THE REFRIGERANT TYPE before adding refrigerant to
the chiller.The introduction of the wrong refrigerant can cause damage or malfunction to this chiller.
Operation of this equipment with refrigerants other than those
cited herein should comply withASHRAE-15 (latest edition). Contact Carrier for further information on use of this chiller with other
refrigerants.
DO NOTATTEMPTTO REMOVE fittings, covers,etc., while chiller
is under pressure or while chiller is running. Be sure pressure is at
0 psig (0 kPa) before breaking any refrigerant connection.
CAREFULLY INSPECT all relief devices, rupture discs, and other
relief devices AT LEAST ONCE A YEAR. If chiller operates in a
corrosive atmosphere, inspect the devices at more frequent
intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief
device when corrosion or build-up of foreign material (rust, dirt,
scale, etc.) is found within the valve body or mechanism. Replace
the device.
DO NOT install relief devices in series or backwards.
USE CARE when working near or in line with a compressed spring.
Sudden release of the spring can cause it and objects in its path to
act as projectiles.
RUN WATERPUMPS when removing, transferring, or charging refrigerant.
DO NOT STEP on refrigerant lines. Broken lines can whip about
and cause personal injury.
DO NOT climb over a chiller. Use platform, catwalk, or staging.
Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or
move inspection covers or other heavy components. Even if components are light, use such equipment when there is a risk of slipping or losing your balance.
BE AWARE that certain automatic start arrangements CAN ENGAGE THE STARTER. Open the disconnect ahead of the starter
in addition to shutting off the machine or pump.
USE only repair or replacement parts that meet the code requirements of the original equipment.
DO NOTVENT OR DRAIN waterboxes containingindustrial brines,
liquid, gases, or semisolids without permission of your process control group.
DO NOT LOOSEN waterbox cover bolts until the waterbox has
been completely drained.
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or
other items have been removed before rotating any shafts.
DO NOT LOOSEN a packing gland nut before checking that the
nut has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for corrosion, rust, leaks, or damage.
PROVIDE A DRAIN connection in the vent line near each pressure relief device to prevent a build-up of condensate or rain
water.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
Tab 5d
PC 211Catalog No. 531-721Printed in U.S.A.Form 17EX-1SSPg 17-97Replaces: New
Chiller Identification Label
System Components
Cooler
Condenser
Compressor
Control Center
Motor Starter (Purchased Separately)
Economizer/Storage Vessel
Auxiliary Compressor Oil Pump Control
Auxiliary Gear Oil Pump Control
Shaft Seal Oil Control
Ramp Loading Control
Capacity Override
High Discharge Temperature Control
Oil Sump Temperature Control
Oil Cooler
Remote Start/Stop Controls
Spare Safety Inputs
Spare Alarm Contacts
Condenser Pump Control
Condenser Freeze Prevention
Tower-Fan Relay
Auto. Restart After Power Failure
Water/Brine Reset
Demand Limit Control, Option (Requires Optional
8-Input Module)
Surge Prevention Algorithm
Surge Protection
Lead/Lag Control
....................................36
..........................33
.........................33
.............................35
..................35
.....................36
...........................36
.........................36
......................36
...................36
..............................36
.............................37
.............................37
....................37
..............................38
.............................38
..........33
................33
.............35
................36
• COMMON POINT SENSOR INSTALLATION
• CHILLER COMMUNICATION WIRING
• LEAD/LAG OPERATION
• FAULTED CHILLER OPERATION
• LOAD BALANCING
• AUTO. RESTART AFTER POWER FAILURE
Ice Build Control
..............................40
• ICE BUILD INITIATION
• START-UP/RECYCLE OPERATION
• TEMPERATURE CONTROL DURING ICE BUILD
• TERMINATION OF ICE BUILD
• RETURN TO NON-ICE BUILD OPERATIONS
Attach to Network Device Control
...............41
• ATTACHING TO OTHER CCN MODULES
Service Operation
.............................42
• TO ACCESS THE SERVICE SCREENS
• TO LOG OFF
• HOLIDAY SCHEDULING
START-UP/SHUTDOWN/RECYCLE SEQUENCE
Local Start-Up
Shutdown Sequence
Automatic Soft Stop Amps Threshold
Chilled Water Recycle Mode
Safety Shutdown
BEFORE INITIAL START-UP
Job Data Required
Equipment Required
Using the Economizer/Storage Vessel and Pumpout
System
Remove Shipping Packaging
................................43
...........................44
............44
....................44
..............................45
...................45-57
............................45
...........................45
....................................45
...................45
...43-45
• MOTOR
• EXTERNAL GEAR
Motor Electrical Connection
Motor Auxiliary Devices
Open Oil Circuit Valves
Tighten All Gasketed Joints and Guide Vane
Shaft Packing
Check Chiller Tightness
Refrigerant Tracer
Leak Test the Chiller
Standing Vacuum Test
Chiller Dehydration
Set Up Chiller Control Configuration
Input the Design Set Points
Input the Local Occupied Schedule
(OCCPC01S)
Input Service Configurations
................................54
.....................54
....................54
.............54
• PASSWORD
• INPUT TIME AND DATE
• CHANGE LID CONFIGURATION IF NECESSARY
• MODIFY CONTROLLER IDENTIFICATION IF
NECESSARY
• INPUT EQUIPMENT SERVICE PARAMETERS IF
NECESSARY
• MODIFY EQUIPMENT CONFIGURATION IF
NECESSARY
• CHECK VOLTAGE SUPPLY
• PERFORM AN AUTOMATED CONTROL TEST
Check Pumpout System Controls and Optional
Pumpout Compressor
High Altitude Locations
Charge Refrigerant Into Chiller
........................56
........................57
..................57
• TRIMMING REFRIGERANT CHARGE
INITIAL START-UP
Preparation
Manual Operation of the Guide Vanes
Dry Run to Test Start-Up Sequence
Check Motor Rotation
...........................57-62
..................................57
............58
..............58
.........................58
• INITIAL MOTOR START-UP
Disc Coupling Installation and Alignment
.........59
• IMPORTANT INFORMATION
Check Oil Pressure and Compressor Stop
Calibrate Motor Current Demand Setting
To Prevent Accidental Start-Up
Hot Alignment Check
Doweling
Check Chiller Operating Condition
Instruct the Operator
....................................61
.........................61
..........................62
..................61
...............61
........61
..........61
• COOLER-CONDENSER
• ECONOMIZER/STORAGE VESSEL
• PUMPOUT SYSTEM
• COMPRESSOR ASSEMBLY
• COMPRESSOR LUBRICATION SYSTEM
EXTERNAL GEAR LUBRICATION SYSTEM
• CONTROL SYSTEM
• AUXILIARY EQUIPMENT
• CHILLER CYCLES
• MAINTENANCE
• SAFETY DEVICES AND PROCEDURES
• CHECK OPERATOR KNOWLEDGE
• THIS MANUAL
OPERATING INSTRUCTIONS
Operator Duties
...............................62
..................62,63
Prepare the Chiller for Start-Up .................62
Starting the Chiller
Check the Running System
Stopping the Chiller
After Limited Shutdown
Extended Shutdown
After Extended Shutdown
Cold Weather Operation
Manual Guide Vane Operation
Refrigeration Log
PUMPOUT AND REFRIGERANT TRANSFER
PROCEDURES
Preparation
Operating the Optional Pumpout
Compressor
..................................63
........................... 62
.....................62
...........................62
........................63
...........................63
......................63
........................63
...................63
.............................63
............................63-67
................................63
• READING REFRIGERANT PRESSURES
Transferring Refrigerant into the
Economizer/Storage Vessel
Transferring Refrigerant into
the Cooler/Condenser/Compressor Section
Return Chiller to Normal Operating
Conditions
GENERAL MAINTENANCE
Refrigerant Properties
Adding Refrigerant
Removing Refrigerant
Adjusting the Refrigerant Charge
Refrigerant Leak Testing
Leak Rate
Test After Service, Repair, or Major Leak
.................................67
............................67
....................................67
...................66
.....67
....................67-75
.........................67
.........................67
................67
.......................67
.........67
• REFRIGERANT TRACER
• TO PRESSURIZE WITH DRY NITROGEN
Repair the Leak, Retest, and Apply
Standing Vacuum Test
Checking Guide Vane Linkage
Contact Seal Maintenance
.......................68
..................68
......................68
• SEAL DISASSEMBLY
• SEAL REASSEMBLY
Chiller Alignment
.............................71
• ALIGNMENT METHODS
• PRELIMINARY ALIGNMENT
• NEAR FINAL ALIGNMENT
• FINAL ALIGNMENT
• HOT ALIGNMENT CHECK
• DOWELING
WEEKLY MAINTENANCE
Check the Lubrication System
SCHEDULED MAINTENANCE
Service Ontime
Inspect the Control Center
Check Safety and Operating Controls Monthly
Changing the Oil Filters
...............................76
.......................76
..................76
..................76-83
.....................76
.....76
........................76
• COMPRESSOR OIL FILTER
• EXTERNAL GEAR OIL FILTER
Oil Specifications
Oil Changes
.............................77
..................................77
• COMPRESSOR OIL
• EXTERNAL GEAR OIL
• MOTOR SLEEVE BEARING AND PUMPOUT
COMPRESSOR OIL
Inspect Refrigerant Float System
Inspect Relief Valves and Piping
Coupling Maintenance
Motor Maintenance
Water Leaks
Water Treatment
Inspect the Starting Equipment
Check Pressure Transducers
Pumpout System Maintenance
..................................82
..............................82
.................83
...................83
..................83
• OPTIONAL PUMPOUT COMPRESSOR OIL CHARGE
• PUMPOUT SAFETY CONTROL SETTINGS
Ordering Replacement Chiller Parts
..............83
• MOTOR REPLACEMENT PARTS
• EXTERNAL GEAR REPLACEMENT PARTS
TROUBLESHOOTING GUIDE
Overview
Checking the Display Messages
Checking Temperature Sensors
....................................83
..................83-99
.................84
.................84
• RESISTANCE CHECK
• VOLTAGE DROP
• CHECK SENSOR ACCURACY
• DUAL TEMPERATURE SENSORS
Checking Pressure Transducers ................84
• OIL DIFFERENTIAL PRESSURE/POWER SUPPLY
MODULE CALIBRATION
• TROUBLESHOOTING TRANSDUCERS
• TRANSDUCER REPLACEMENT
Control Algorithms Checkout Procedure
Control Test
Control Modules
.................................85
..............................96
.........85
• RED LEDs
• GREEN LEDs
Notes on Module Operation
Processor/Sensor Input/Output Module (PSIO)
....................96
....97
• INPUTS
• OUTPUTS
Starter Management Module (SMM)
..............97
• INPUTS
• OUTPUTS
Options Modules (8-Input)
Four-In/Two-Out Module
.....................98
.......................98
• INPUTS
• OUTPUTS
Replacing Defective Processor Modules
.........98
• INSTALLATION OF NEW PSIO MODULE
PHYSICAL DATA AND WIRING SCHEMATICS
INDEX
INITIAL START-UP CHECKLIST FOR 17EX
....................................115-120
EXTERNALLY GEARED CENTRIFUGAL LIQUID
CHILLER
..........................CL-1 to CL-12
....99-114
4
Page 5
INTRODUCTION
Before initial start-up of the 17EX unit, those involved in
the start-up, operation, and maintenance should be thoroughly familiar with these instructions and other necessary
job data. This book is outlined so that you may become familiar with the control system before performing start-up procedures. Procedures in this manual are arranged in the sequencerequiredforproperchillerstart-upand
operation.
This unit uses a microprocessor controlled system. Do
not short or jumper between terminations on circuit boards
or modules; control or board failure may result.
Be aware of electrostatic discharge (static electricity) when
handling or making contact with circuit boards or module connections. Always touch a chassis (grounded) part
to dissipate body electrostatic charge before working inside the control center.
Use extreme care when handling tools near boards and
when connecting or disconnecting terminal plugs.
Circuit boards can easily be damaged. Always hold boards
by the edges and avoid touching components and
connections.
This equipment uses, and can radiate, radio frequency
energy. If not installed and used in accordance with
the instruction manual, it may cause interference to
radio communications. It has been tested and found to
comply with the limits for a Class A computing device
pursuant to Subpart J of Part 15 of FCC Rules, which
are designed to provide reasonable protection against such
interference when operated in a commercial environment. Operation of this equipment in a residential area
is likely to cause interference, in which case the user, at
his own expense, will be required to take whatever measures may be required to correct the interference.
Always store and transport replacement or defective boards
in anti-static shipping bag.
ABBREVIATIONS
Frequently used abbreviations in this manual include:
CCN— Carrier Comfort Network
CCW— Counterclockwise
CHW— Chilled Water
CHWR — Chilled Water Return
CHWS — Chilled Water Supply
CW— Clockwise
ECW— Entering Chilled Water
ECDW — Entering Condenser Water
EMS— Energy Management System
HGBP — Hot Gas Bypass
I/O— Input/Output
LCD— Liquid Crystal Display
LCDW — Leaving Condenser Water
LCW— Leaving Chilled Water
LED— Light-Emitting Diode
LID— Local Interface Device
OLTA— Overload Trip Amps
PIC— Product Integrated Control
PSIO— Processor Sensor Input/
tification label is located on the right side of the chiller control center panel. The label contains information on model
number, refrigerant charge, rated voltage, etc.
The iden-
System Components (Fig. 2) — The components
include the cooler and condenser heat exchangers in separate vessels, compressor,compressorandgear lubrication packages, control center,speedincreasereconomizer/storage vessel,
motor, and starter. The compressor drive consists of an external gear (speed increaser) and an electric motor. All connections from pressure vessels have external threads to enable each component to be pressure tested with a threaded
pipe cap during factory assembly.
Cooler — This vessel (also known as the evaporator) is
located underneath the condenser, next to the economizer/
storage vessel. The cooler is maintained at lower temperature and pressure so that evaporating refrigerant can remove
heat from water flowing through its internal tubes.
Condenser — The condenser operates at a higher tem-
perature and pressure than the cooler and has water flowing
through its internal tubes in order to remove heat from the
refrigerant.
Compressor — This component maintains system tem-
perature and pressure differences and moves the heatcarrying refrigerant from the cooler to the condenser.
Control Center — The control center is the user inter-
face for controlling the chiller and regulates the chiller capacity as required to maintain proper leaving chilled
water temperature. The control center:
• registers cooler, condenser, and lubricating system
pressures
• shows chiller operating and alarm shutdown conditions
• records the total chiller operating hours and how many hours
the chiller has been running
• sequences chiller start, stop, and recycle under microprocessor control
• provides access to other CCN (Carrier Comfort Network)
devices
MotorStarter (Purchased Separately) — The starter
allows the proper start and disconnect of electrical energy
for the compressor-motor, oil pump, oil heater, and control
panels.
Economizer/Storage Vessel — During normal op-
eration, this vessel functions as an economizer,returning flash
gas to the second stage of the compressor and increasing the
efficiency of the refrigeration cycle. During periods of shutdown and service, the economizer/storage vessel can serve
as a storage tank for the refrigerant.
REFRIGERATION CYCLE (Fig. 3)
The 17EX chiller can be used to chill either water or brine.
The data in this book applies to either application. Applications using corrosive brines may require using special tubes,
tubesheet, and waterbox materials which are special order
items.
5
Page 6
LEGEND
NIH — Nozzle-In-Head
*Any available cooler size can be combined with any available condenser size.
NOTE: For details on motor size designations, see below.
ASME
‘U’ STAMP
ARI (Air Conditioning
and Refrigeration
Institute)
PERFORMANCE
CERTIFIED
(60 Hz Only)
Fig. 1 — Model Number Identification
6
Page 7
40
39
38
37
36
35
1 2 3 4 5 6 7 8 9 10 11 12 1314
15
34
1—Condenser
2—Cooler Suction Pipe
3—Compressor Suction Elbow
4—Guide Vane Actuator
5—Condenser Discharge Pipe
6—Compressor Discharge Elbow
7—Two-Stage Compressor
8—Economizer Gas Line to Compressor
The chiller compressor continuously draws large quantities of refrigerant vapor from the cooler at a rate determined
by the amount of guide vane opening. This compressor suction reduces the pressure within the cooler, allowing the liquid refrigerant to boil vigorously at a fairly low temperature
(typically 38 to 42 F [3 to 6 C]).
The liquid refrigerant obtains the energy needed to vaporize by removing heat from the water or brine in the cooler
tubes. The cold water or brine can then be used in air conditioning and/or other processes.
After removing heat from the water or brine, the refrigerant vapor enters the first stage of the compressor, is
compressed, and flows into the compressor second stage. Here
it is mixed with flash-economizer gas and is further
compressed.
Compression raises the refrigerant temperature above
that of the water flowing through the condenser tubes.
When the warm (typically 98 to 102 F [37 to 40 C]) refrigerant vapor comes into contact with the condenser tubes, the
relatively cool condensing water (typically 85 to 95 F
[29 to 35 C]) removes some of the heat, and the vapor condenses into a liquid.
The liquid refrigerant passes through an orifice into the
FLASC chamber.The coolest condenser water flows through
the FLASC and allows a lower saturated temperature and
pressure. Part of the entering liquid refrigerant will flash to
vapor once it has passed through the FLASC orifice, thereby
cooling the remaining liquid. The vapor is then recondensed
by the condenser water flowing through the FLASC
chamber.
The subcooled liquid refrigerant drains into a high-side
valve chamber that meters the refrigerant liquid into a flash
economizer chamber. Pressure in this chamber is intermediate between condenser and cooler pressures. At this lower
pressure, some of the liquid refrigerant flashes to gas, further cooling the remaining liquid. The flash gas, having absorbed heat, is returned directly to the compressor second
stage. Here it is mixed with discharge gas that is already compressed by the first-stage impeller. Since the flash gas has to
pass through only half the compression cycle to reach condenser pressure, there is a savings in power.
The cooled liquid refrigerant in the economizer is metered through the low-side valve chamber, reducing the refrigerant pressure. Pressure in the cooler is lower than in the
economizer. Some of the liquid flashes as it passes through
the low side float valve. The cycle is now complete.
OIL COOLING CYCLE
Compressor Oil Cooling —
water cooled. Water flow through the oil cooler is manually
adjusted by a plug valve to maintain an operating temperature at the reservoir of approximately 145 F (63 C). An oil
heater in the reservoir helps to prevent oil from being diluted by the refrigerant. The heater is controlled by the PIC
(Product Integrated Control) and is energized when the oil
temperature is outside the operating temperature range of 150
to 160 F (66 to 71 C).
The compressor oil is
External Gear Oil Cooling — The external gear oil
is also water cooled. Water flow through the gear oil cooler
is manually adjusted by a plug valve to maintain an operating temperature of approximately 130 F (54 C). If so equipped,
an oil heater in the reservoir helps to maintain the oil temperature under cold ambient operating conditions. The heater
is controlled by an internal thermostat.
LUBRICATION CYCLE
Compressor Lubrication Cycle (Refer to item
numbers shown in Fig. 4) —
pump and oil reservoir are contained in the compressor base.
Oil is pumped through an oil cooler and filter to remove heat
and any foreign particles. A portion of the oil is then directed to the shaft-end bearing and the shaft seal. The balance of the oil lubricates the thrust and journal bearings and
the thrust end seal. The bearing and transmission oil returns
directly to the reservoir to complete the cycle. Contact-seal
oil leakage, however,iscollected in an atmospheric float chamber to be pumped back to the main reservoir as the oil
accumulates.
Oil may be charged into the compressor oil reservoir
(Item 8) through a charging valve (Item 6) which also functions as an oil drain. If there is refrigerant in the chiller, however, a hand pump will be required for charging at this
connection.
An oil-charging elbow (Item 3) on the seal-oil return chamber allows oil to be added without pumping. The seal-oil return pump (Item 4) automatically transfers the oil to the main
reservoir. Sight glasses (11) on the reservoir wall permit observation of the oil level.
Amotor-drivenoil pump (Item 10) discharges oil to an oil
cooler/filter (Item 16) at a rate and pressure controlled by an
oil regulator (Item 10). The differential oil pressure (bearing
supply versus oil reservoir) is registered on the control panel.
Water flow through the oil cooler is manually adjusted by
a plug valve (Item 17) to maintain the oil at an operating
temperature of approximately 145 F (63 C). During shutdown, the oil temperature is also maintained at 150 to
160 F (65 to 71 C) by an immersion heater (Item 7) in order
to minimize absorption of refrigerant by the oil.
Upon leaving the cooler section of the oil cooler/filter, the
oil is filtered (Item 15) and a portion is directed to the sealend bearing (Item 1) and the shaft seal (Item 2). The remainder lubricates thrust (Item 14) and journal bearings (Item 12).
Thrust bearing temperature is indicated on the PIC controls.
Oil from both circuits returns by gravity to the reservoir.
The shaft seal of the open compressor drive must be kept
full of lubrication oil, even when the chiller is not operating,
to prevent loss of refrigerant.
If the chiller is not operating and the oil pump has not
operated during the last 12 hours, the control system automatically runs the oil pump for one minute in order to keep
the contact seal filled with oil.
IMPORTANT: If the control power is to be deenergized for more than one day,the chiller refrigerant should
be pumped over to the economizer/storage vessel.
The compressor oil
8
Page 9
LEGEND
TXV — Thermostatic Expansion Valve
*The FX compressor and the gear have a water cooled oil cooler.
Liquid
Liquid/Vapor
Vapor
Fig. 3 — Refrigeration, Cycle
External Gear Lubrication Cycle (Refer to Item
numbers shown in Fig. 5) —
tained in the gear base.The external gear oil pump is mounted
below the gear with the cooler/filter. Oil is pumped through
an oil cooler/filter to remove heat and any foreign particles.
A portion of the oil is directed to the gear bearings and gear
mesh spray.The remainder is bypassed to the sump. The bearing and transmission oil returns directly to the reservoir to
complete the cycle.
Oil may be charged into the external gear oil reservoir as
described in the section, External Gear Pre-Start Checks,
page 51. Observe the oil level in the oil level glass (Item 4)
on the reservoir wall.
A motor driven oil pump (Item 10) discharges oil to the
oil cooler/filter (Item 12). The pump has an internal pressure
regulator to protect the pump in the event of an obstruction
downstream. Water flow through the oil cooler is manually
adjusted by a plug valve (Item 14) to maintain the oil at an
operating temperature of approximately 130 F (54 C).
Oil reservoir is con-
Upon leaving the cooler section (Item 13) of the oil cooler/
filter, the oil is filtered (Item 11) and is directed to the pressure control valve (Item 7). Before entering the pressure control
valve, the oil pressure (Item 16) and temperature (Item 8)
are monitored by the PIC.
A portion of the oil then lubricates the gear bearings
(Item 2). Another portion is directed through an orifice
(Item 5) to the gear mesh spray (Item 3) to lubricate the gear
mesh (Item 1) during operation. Oil from both circuits returns by gravity to the reservoir.
STARTERS
All starters, whether supplied by Carrier or the customer,
must meet Carrier Starter Specification Z-375. This specification can be obtained from a Carrier Sales Representative. The purpose of this specification is to ensure the compatibility of the starter and the chiller.Many styles of compatible
starters are available, including solid-state , auto-transformer,
full-voltage, and, in the case of low-voltage main power supply, wye-delta closed transition.
ANALOG SIGNAL — An analog signal varies in proportion to the monitored source. It quantifies values between
operating limits. (Example: A temperature sensor is an analog device because its resistance changes in proportion to
the temperature, generating many values.)
DIGIT ALSIGNAL— A digital (discrete) signal is a 2-position
representation of the value of a monitored source.
(Example: A switch is a digital device because it only indicates whether a value is above or below a set point or boundary by generating an on/off,high/low, or open/closed signal.)
VOLATILE MEMORY — Volatile memory is memory in-
capable of being sustained if power is lost and subsequently
restored.
The memories of the PSIO and LID modules are volatile. If the battery in a module is removed or damaged,
all programming will be lost.
General — The 17EX externally geared open-drive cen-
trifugal liquid chiller contains a microprocessor-based control center that monitors and controls all operations of the
chiller.The microprocessor control system matches the cooling capacity of the chiller to the cooling load while providing state-of-the-art chiller protection. The system controls
cooling load within the set point plus the deadband by sensing the leaving chilled water or brine temperature and regulating the inlet guide vane via a mechanically linked actuator motor.The guide vane is a variable flow prewhirl assembly
that controls the refrigeration effect in the cooler by regulating the amount of refrigerant vapor flow into the compressor.An increase in guide vane opening increases capacity.Adecrease in guide vane opening decreases capacity.Chiller
protection is provided by the processor which monitors the
digital and analog inputs and executes capacity overrides or
safety shutdowns, if required.
11
Page 12
PIC System Components — The Product Integrated
Control (PIC) is the control system on the chiller. See
T able1. The PIC controls the operation of the chiller by monitoring all operating conditions. The PIC can diagnose a problem and let the operator know what the problem is and what
to check. It promptly positions the guide vanes to maintain
leaving chilled water temperature. It can interface with auxiliary equipment such as pumps and cooling tower fans to
turn them on only when required. It continually checks all
safeties to prevent any unsafe operating condition. It also
regulates the oil heater while the compressor is off and the
hot gas bypass valve, if installed. See Fig. 6-10 for the locations of sensors, transducers, and other devices controlled
and/or monitored by the PIC system.
The PIC can be interfaced with the Carrier Comfort
Network (CCN) if desired. It can communicate with other
PIC-equipped chillers and other CCN devices.
The PIC consists of 4 modules housed inside one of 3 locations: the control center, the power panel, or the starter
cabinet. The component names and the control voltage of
each location are listed below (also see Table 1):
• control center
— all extra low-voltage wiring (24 v or less)
REAR
• power panel
— 115 v control voltage
— up to 600 v for oil pump power
• starter cabinet
— chiller power wiring (per job requirement)
Table 1 — Major PIC Components and
Panel Locations*
PIC COMPONENT
Processor Sensor Input/Output Module
(PSIO)
Starter Management Module (SMM)Starter Cabinet
Local Interface Device (LID)Control Center
6-Pack Relay BoardControl Center
8-Input Modules (Optional)Control Center
4-In/2-Out ModulePower Panel
Oil Differential Pressure/Power Supply
Module
Oil Heater Contactor (1C)Power Panel
Compressor Oil Pump Contactor (2C)Power Panel
Gear Oil Pump Contactor (5C)Power Panel
Hot Gas Bypass Relay (3C) (Optional)Power Panel
Control Transformers (T1-T4)Power Panel
Control and Oil Heater Voltage Selector (S1) Power Panel
Temperature SensorsSee Fig. 7
Pressure TransducersSee Fig. 7
*See Fig. 6-10.
PANEL
LOCATION
Control Center
Control Center
1—Gear Oil Pressure Sensor
2—Thrust Bearing Temperature and
Impeller Displacement Cable
3—Discharge Temperature Sensor
4—Guide Vane Conduit and Cable
5—High Pressure Cutout Switch
LEGEND
6—Compressor Oil Cooler
Solenoid Conduit
7—Oil Heater Conduit
8—Motor Space Heater Conduit
9—Gear Oil Temperature Sensor
10 — Motor High Temperature Switch Cable
11 — Motor Water Cooling Leak Detector
12 — Discharge Oil Pressure Sensor
TEWAC — Totally Enclosed Water-to-Air Cooled
Fig. 6 — 17EX Controls and Sensor Locations
12
Cable (TEWAC Motor Only)
Page 13
LEGEND
13 — Condenser Pressure Transducer
14 — Condenser Entering Water
Temperature Sensor
15 — Condenser Entering and Leaving Water
Temperature Cable
16 — Oil Suction Pressure Sensor
17 — Oil Pump Conduit
18 — Oil Pump Sensor
19 — PIC Control Panel
20 — Condenser Leaving Water
Temperature Sensor
21 — Gear Oil Cooler Solenoid Conduit
LEGEND
22 — Cooler Temperature Cable
23 — Cooler Leaving Water Temperature Sensor
24 — Cooler Entering Water Temperature Sensor
25 — Cooler Pressure Sensor
26 — Refrigerant Charging Valve
Fig. 6 — 17EX Controls and Sensor Locations (cont)
13
Page 14
Fig. 6 — 17EX Controls and Sensor Locations (cont)
Fig. 10 — 17EX Chiller Power Panel and Controls Connections
Page 16
PROCESSOR/SENSOR INPUT/OUTPUT MODULE (PSIO)
— This module contains all the operating software needed
to control the chiller. The 17EX uses 5 pressure transducers
and 8 thermistors to sense pressures and temperatures. These
inputs are connected to the PSIO module. The PSIO also
provides outputs to the guide vane actuator, compressor and
gear oil pumps, oil heater, hot gas bypass (optional), and alarm
contact. The PSIO communicates with the LID, the SMM,
and the optional 8-input modules for user interface and starter
management.
ST ARTER MANAGEMENT MODULE (SMM) — This module is located within the starter cabinet. This module initiates PSIO commands for starter functions such as start/
stop of the compressor; start/stop of the condenser and chilled
water pumps; start/stop of the tower fan, spare alarm contacts, and the shunt trip. The SMM monitors starter inputs
such as flow switches, line voltage, remote start contact, spare
safety, condenser high pressure, oil pump interlock, motor
current signal, starter 1M and run contacts, and the kW transducer input (optional). The SMM contains logic capable of
safely shutting down the chiller if communication with
the PSIO is lost.
LOCALINTERFACE DEVICE (LID) — The LID is mounted
to the control center and allows the operator to interface with
the PSIO or other CCN devices. It is the input center for all
local chiller set points, schedules, set-up functions, and options. The LID has a STOP button, an alarm light, 4 buttons
for logic inputs, and a display. The function of the 4 buttons
or ‘‘softkeys’’ are menu driven and are shown on the display
directly above the key.
SIX-PACK RELAY BOARD (6-Pack Relay Board) — This
device is a cluster of 6 pilot relays located in the control
center. It is energized by the PSIO for the compressor oil
pump, oil heater, alarm, optional hot gas bypass relay, auxiliary oil pump.
EIGHT-INPUT (8-Input) MODULES — One optional module is factory installed in the control center panel when ordered. There can be up to 2 of these modules per chiller with
8 spare inputs each. They are used whenever chilled water
reset, demand reset, or reading a spare sensor is required.
The sensors or 4 to 20 mA signals are field-installed.
The spare temperature sensors must have the same
temperature/resistance curve as the other temperature sensors on this unit. These sensors are rated 5,000 ohm at 75 F
(25 C).
FOUR-IN/TWO-OUT(4-IN/2-OUT) MODULE —Thismodule monitors and controls the external gear lubrication system. It energizes the gear oil pump and is located in the power
panel.
OIL HEATER CONTACTOR (1C) — This contactor is located in the power panel and operates the heater at 115 v. It
is controlled by the PIC to maintain oil temperature during
chiller shutdown.
COMPRESSOR OILPUMP CONTACTOR(2C)ANDGEAR
OIL PUMP CONTACTOR (5C) — These contactors are located in the power panel. They operate all 200 to 575-v oil
pumps. The PIC energizes the contactor to turn on the oil
pumps as necessary.
HOTGASBYPASSCONTACTORRELAY (3C)
(Optional) — This relay, located in the power panel, controls the opening of the hot gas bypass valve. The PIC energizes the relay during low load, high lift conditions.
OIL AUXILIARY RELAY (4C) — This relay opens the oil
cooler solenoid valve and interlocks the oil pump with the
compressor (special order).
CONTROL TRANSFORMERS (T1-T4) — These transformers are located in the power panel and convert
incoming control voltage to either 21 vac power for the PSIO
module and options modules, or 24 vac power for 3 power
panel contactor relays and a control solenoid valve.
CONTROL AND OIL HEATER VOLTAGE SELECTOR
(S1) — It is necessary to use 115 v incoming control power
in the power panel. The switch must be set to the 115-v
position.
OIL DIFFERENTIAL PRESSURE/POWERSUPPLY
MODULE — This module, which is located in the control
center, provides 5 vdc power for the transducers and LID
backlight. This module outputs the difference between two
pressure transducer input signals. The module subtracts oil
supply pressure from transmission sump pressure and outputs the difference as an oil differentialpressure signal to the
PSIO. The PSIO converts this signal to differential oil pressure. To calibrate this reading, refer to the Troubleshooting,
Checking Pressure Transducers section on page 84.
LID Operation and Menus (Fig. 11-17)
GENERAL
• The LID display automatically reverts to the default screen
(Fig. 11) after 15 minutes if no softkey activity takes place
and if the chiller is not in PUMPDOWN mode
• When not displaying the default screen, the upper righthand corner of the LID displays the name of the screen
that you have entered (Fig. 12).
• The LID may be configured in English or SI units, through
the LID configuration screen.
• Local Operation — Pressing the LOCAL
the PIC in LOCAL operation mode, and the control ac-
cepts modification to programming from the LID only. The
PIC uses the Local Time Schedule to determine chiller start
and stop times.
• CCN Operation — Pressing the CCN softkey places the
PIC in the CCN operation mode, and the control accepts
modifications from any CCN interface or module (with the
proper authority), as well as the LID. The PIC uses the
CCN time schedule to determine start and stop times.
Fig. 11 — LID Default Screen
ALARMS AND ALERTS — An alarm (*) or alert (!) status
is indicated on the default screen and the status tables. An
alarm (*) shuts down the compressor. An alert (!) notifies
the operator that an unusual condition has occurred. The chiller
continues to operate when an alert is shown.
Alarms are indicated when the control center alarm light
(!) flashes. The primary alarm message is viewed on the default screen and an additional, secondary, message and
troubleshooting information are sent to the ALARM HISTORY table.
softkey places
16
Page 17
NOTE: When an alarm is detected, the LID default screen
freezes (stops updating) at the time of alarm. The freeze enables the operator to view the chiller conditions at the time
of the alarm. The status tables show the updated informa-
tion. Once all alarms have been cleared (by pressing the
RESET
softkey), the default LID screen returns to normal
operation.
Fig. 12 — LID Service Screen
LID DEFAULT SCREEN MENU ITEMS — To perform
any of the operations described below, the PIC must be powered up and have successfully completed its self test.
The default screen menu selection offers four options
(STATUS, SCHEDULE, SETPOINT, and SERVICE). The
STATUS menu allows viewing and limited calibration/
modification of control points and sensors, relays and contacts, and the options board. The SCHEDULE menu allows
viewing and modification of the Local Control, CCN Control, and Ice Build time schedules. Numerous set points including Base Demand Limit, LCW, ECW, and Ice Build can
be adjusted under the SETPOINT menu. The SERVICE menu
can be used to revise alarm history, control test, control algorithm status, equipment configuration, equipment service,
time and date, attach to network, log out of device, controller identification, and LID configurations. Figures 15 and 16
provide additional information on the menu structure.
Press the MENU
softkey to select from the 4 options.
To view or change parameters within any menu structure,
use the SELECT
softkey to choose the desired table or
item. The softkey modification choices displayed will depend on whether the selected item is a discrete point, analog point, or an override point. Press the softkey that corresponds to your configuration selection or press the
QUIT softkey. If the QUIT softkey is depressed, the
configuration will not be modified. Use the following softkeys to access and select the desired section.
MENU STRUCTURE — To perform any of the operations
described below, the PIC must be powered up and have successfully completed its self test.
• Press MENU
to select from the four available options.
• Press NEXT or PREVIOUS to highlight the desired
entry.
• Press SELECT to access the highlighted point.
• Press QUIT to leave the selected decision or field without saving any changes.
• Or, press ENTER to leave the selected decision or field
and save changes.
TOVIEWOR CHANGE POINT STATUS (Fig. 13) — Point
Status is the actual value of all of the temperatures, pressures, relays, and actuators sensed and controlled by the PIC.
1. On the Menu screen, press STATUS
to view the list of
Point Status tables.
2. Press NEXT or PREVIOUS to highlight the desired
status table. The list of tables is:
• STATUS01 — Status of control points and sensors
• STATUS02 — Status of relays and contacts
• STATUS03 — Status of both optional 8-input modules
and sensors
• STATUS04 — Gear oil temperature and pressure
• Press the softkey that corresponds to the desired menu
structure.
Fig. 13 — Example of Point Status Screen
(Status01)
17
Page 18
3. Press SELECT to view the desired Point Status table.
4. OnthePointStatustablepressNEXTor
PREVIOUS
until desired point is displayed on the screen.
Override Indication — An override value is indicated by
‘ ‘SUPVSR,’’‘‘SERVC,’’or ‘‘BEST’’ flashing next to the point
value on the Status table.
TO VIEW OR CHANGE TIME SCHEDULE OPERATION
(Fig. 14)
1. On the Menu screen, press SCHEDULE
.
For Discrete Points — Press START or STOP ,
or NO ,ONor OFF , etc. to select the desired
YES
state.
ForAnalogPoints—PressINCREASEor
DECREASE
to select the desired value.
5. Press ENTER to register new value.
OVERRIDE OPERATIONS
NOTE: When overriding or changing metric values, it is nec-
essary to hold the softkey down for a few seconds in order
to see a value change, especially on kilopascal values.
To Remove an Override
1. OnthePointStatustablepressNEXTor
PREVIOUS
to highlight the desired point.
2. Press NEXT or PREVIOUS to highlight one of the
following schedules.
OCCPC01S — LOCAL Time Schedule
OCCPC02S — ICE BUILD Time Schedule
OCCPC03-99S — CCN Time Schedule (Actual
number is defined in CONFIG table.)
3. Press SELECT to access and view the time schedule.
4. Press NEXT or PREVIOUS to highlight the desired period or override that you wish to change.
5. Press SELECT to access the highlighted period or
override.
2. Press SELECT to access the highlighted point.
3. Press RELEASE to remove the override and return the
point to the PIC’s automatic control.
Fig. 14 — Example of Time Schedule
Operation Screen
18
Page 19
CCN
Start Chiller In CCN Control
Start Chiller In Local Control
DEFAULT SCREEN
LOCALRESET
MENU
(SOFTKEYS)
Clear Alarms
NEXT
NEXT
START
INCREASE
ENABLE
STATUS
List the
Status Tables
STATUS
STATUS
STATUS
STATUS
PREVIOUS
PREVIOUS
STOPRELEASE
DECREASE
DISABLE
SCHEDULESETPOINT
01
02
03
04
SELECT
SELECT
RELEASE
RELEASE
Access Main Menu
SERVICE
EXIT
EXIT
ENTER
ENTER
ENTER
(SELECT A T ABLE)
(SELECT A POINT
ON THE TABLE)
(MODIFY A
DISCRETE POINT) or
(MODIFY AN
ANALOG POINT) or
(MODIFY CONTROL
OPTIONS)
Select a Schedule
NEXT
Select a Time Period/Override
NEXT
Modify a Schedule Time
INCREASE
Add/Eliminate a Day
ENABLE
123
List the Schedules
OCCPC01S - Local Time Schedule
OCCPC02S - Ice Build Time Schedule
OCCPC03S-99S - CCN Time Schedule
• To modify — PSIO CCN Address • To View — PSIO Software Version
LID CONFIGURATION
DECREASE
LEGEND
CCN— Carrier Comfort Network
HGBP — Hot Gas Bypass
LID— Local Interface Device
NOTE: SERVICE TABLES:
SERVICE1: — Capacity Override
— Type of Chilled Medium
— Alert Temperature
— Flow Verification
— Deadband
— Recycle Restart Time
— Surge/HGBP Operation
— Motor Voltage, RLA, and Frequency
— Starter Type
— Condenser Freeze Safety
— Soft Stop Configuration
— Start to Stop Timer
— Gear Oil Pump Configuration
ENTER
Default Screen
CCN
EXIT
(last 2 digits on part number indicate software version)
LID Configuration Table
INCREASE
• To Modify — LID CCN Address
LOCAL
DECREASE
— English or S.I. Metric Units
— Password
RESET
ENTER
SERVICE2: — 8-input Modules
SERVICE3: — Proportional Inc each Band
MENU
— 20 mA Power Source
— Proportional Dec each Band
— Proportional ECW Gain
— Maximum Guide Vane Opening
EXIT
• To View — LID Software Version
(last 2 digits of part number
indicate software version)
Fig. 16 — 17EX Service Menu Structure (cont)
21
Page 22
6. a. Press INCREASE or DECREASE to change the
time values. Override values are in one-hour incre-
ments, up to 4 hours.
b. Press ENABLE to select days in the day-of-week
fields. Press DISABLE
to eliminate days from the
period.
7. Press ENTER to register the values and to move
horizontally (left to right) within a period.
8. Press EXIT to leave the period or override.
9. Either return to Step 4 to select another period or
override, or press EXIT
again to leave the cur-
rent time schedule screen and save the changes.
4. Press SELECT to modify the highlighted set point.
5. Press INCREASE or DECREASE to change the selected set point value.
6. Press ENTER to save the changes and return to the
previous screen.
10. Holiday Designation (HOLIDEF table) may be found in
the Service Operation section, page 42.You must assign
the month, day, and duration for the holiday.The Broadcast function in the BRODEF table also must be enabled for holiday periods to function.
TO VIEW AND CHANGE SET POINTS (Fig. 17)
1. To view the Set Point table, at the Menu screen press
SETPOINT
.
2. There are 4 set points on this screen: Base Demand Limit;
LCW Set Point (leaving chilled water set point); ECW
Set Point (entering chilled water set point); and ICE BUILD
set point. Only one of the chilled water set points can be
active at one time, and the type of set point is activated
in the Service menu. ICE BUILD is also activated and
configured in the Service menu.
3. Press NEXT or PREVIOUS to highlight the desired
set point entry.
Fig. 17 — Example of Set Point Screen
SERVICE OPERATION — To view the menu-driven programs available for Service Operation, see the Service Operation section, page 42. For examples of LID display screens,
see Table 2.
LEGEND FOR TABLE 2 — LID DISPLAY DATA
CCN— Carrier Comfort Network
CHWR — Chilled Water Return
CHWS — Chilled Water Supply
Compr — Compressor
Dec— Decrease
Ecw— Entering Chilled Water
HGBP — Hot Gas Bypass
Inc— Increase
LCW— Leaving Chilled Water
mA— Milliamps
P—Pressure
PIC— Product Integrated Controls
Refrig — Refrigerant
T—Temperature
Temp— Temperature
22
Page 23
Table 2 — LID Display Data
NOTES:
IMPORTANT: The following notes apply to all Table 2
examples.
1. Only 12 lines of information appear on the LID screen at any one
time. Pressthe NEXT
or to view items below or above the current screen. If you have a
chiller with a backlit LID, press the NEXT
forward; press the PREVIOUS
2. Toaccess the information shown in Examples 6 through 14, enter
your 4-digit password after pressing the SERVICE
softkeys arepressed for 15 minutes, the LIDautomatically logs off
(to prevent unrestricted access to PIC controls) and reverts to the
default screen. If this happens, you must reenter your password
to access the tables shown in Examples 6 through 14.
3. Termsin the Description column of these tables are listed as they
appear on the LID screen.
4. The LID may be configured in English or Metric (SI) units using
theLIDCONFIGURATIONscreen. See the ServiceOperation section, page 42, for instructions on making this change.
To access this display from the LID default screen:
1. PressMENU
2. Press STATUS
3. Press SELECT
or PREVIOUS softkey to highlightapoint
softkey twice to page
softkey twice to page back.
softkey.If no
EXAMPLE1—STATUS01 DISPLAY SCREEN
.
(STATUS01 will be highlighted).
.
5. The items in the Reference Point Name column
the LID screen
Building Supervisor software. They are listed in these tables as a
convenience to the operator if it is necessary to cross reference
CCN/BS documentation or use CCN/BS programs. For more information, see the 17EX CCN literature.
6. Reference Point Names shown in these tables in all capital letters
can be read by CCN and Building Supervisor software. Of these
capitalized names, those preceded by an asterisk can also be
changed (that is, written to) by the CCN, Building Supervisor software and the LID. Capitalized Reference Point Names preceded
by two asterisks can be changed only from the LID. Reference
Point Names in lower case type can be viewed by CCN or Building Supervisor software only by viewing the whole table.
7. Alarms and Alerts: An asterisk
screen
tion point in the far right field of the LID screen indicates an alert
state. The asterisk (or exclamation point) indicates that the value
on that line has exceeded (or is approaching) a limit. For more
information on alarms and alerts, see the Alarms and Alerts section, page 16.
. They are data or variable names used in CCN or
in the far right field of a LID status
indicates that the chiller is in an alarm state; an exclama-
do not appear on
DESCRIPTIONRANGEUNITS
Control ModeReset.Off. Local. CCNMODE
Run StatusTimeout. Recycle. Startup.STATUS
Occupied ?No/YesOCC
Alarm StateNormal/AlarmALM
*Chiller Start/StopStop/StartCHIL S S
Base Demand Limit40-100%DLM
*Active Demand Limit40-100%DEM LIM
Compressor Motor Load0-999%CA L
Current0-999%CA P
Amps0-9999AMPSCA A
*Target Guide Vane Pos0-100%GV TRG
Actual Guide Vane Pos0-100%GV ACT
Water/Brine: Setpoint10-120 (–12.2-48.9)DEG F (DEG C)SP
*Control Point10-120 (–12.2-48.9)DEG F (DEG C)LCW STPT
Entering Chilled Water–40-245 (–40-118)DEG F (DEG C)ECW
Leaving Chilled Water–40-245 (–40-118)DEG F (DEG C)LCW
Entering Condenser Water–40-245 (–40-118)DEG F (DEG C)ECDW
Leaving Condenser Water–40-245 (–40-118)DEG F (DEG C)LCDW
Evaporator Refrig Temp–40-245 (–40-118)DEG F (DEG C)ERT
Evaporator Pressure–6.7-420 (–46-2896)PSI (kPa)ERP
Condenser Refrig Temp–40-245 (–40-118)DEG F (DEG C)CRT
Condenser Pressure–6.7-420 (–46-2896)PSI (kPa)CRP
Discharge Temperature–40-245 (–40-118)DEG F (DEG C)CMPD
Bearing Temperature–40-245 (–40-118)DEG F (DEG C)MTRB
Motor Winding Temp†–40-245 (–40-118)DEG F (DEG C)MTRW
Motor Winding Hi
Temp Cutout
Oil Sump Temperature–40-245 (–40-118)DEG F (DEG C)OILT
Oil Pressure Transducer†–6.7-420 (–46-2896)PSI (kPa)OILP
Oil Pressure**–6.7-420 (–46-2896)PSID (kPad)OILPD
Line Voltage: Percent0-999%V P
*Remote Contacts InputOff/OnREMCON
Total Compressor Starts0-65535c starts
Starts in 12 Hours0-8STARTS
Compressor Ontime0-500000.0HOURSc hrs
*Service Ontime0-32767HOURSS HRS
*Compressor Motor kW0-9999kWCKW
†Information is applicable to hermetic chillers (19EX) only.
**Oil pressure is read directly from a differential pressure module on 17EX chillers.
NOTE: values preceded by an asterisk (*) can be forced (changed by an operator) from the LID screen
or from another control device (such as a Carrier Comfort Network [CCN] terminal).
To access this display from the LID default screen:
1. PressMENU
2. Press STATUS
3. Scroll down to highlight STATUS02.
4. Press SELECT
.
.
.
Table 2 — LID Display Data (cont)
DESCRIPTION
Hot Gas Bypass RelayXOFF/ONHGBR
*Chilled Water PumpXOFF/ONCHWP
Chilled Water FlowXNO/YESEVFL
*Condenser Water PumpXOFF/ONCDP
Condenser Water FlowXNO/YESCDFL
Compressor Start RelayXOFF/ONCMPR
Compressor Start ContactXOPEN/CLOSED1CR AUX
Compressor Run ContactXOPEN/CLOSEDRUN AUX
Starter Fault ContactXOPEN/CLOSEDSTR FLT
Pressure Trip ContactXOPEN/CLOSEDPRS TRIP
Single Cycle DropoutXNORMAL/ALARMV1 CYCLE
Oil Pump RelayXOFF/ONOILR
Oil Heater RelayXOFF/ONOILH
Motor Cooling Relay†XOFF/ONMTRC
Auxiliary Oil Pump RelayXOFF/ONAUXOILR
*Tower Fan RelayXOFF/ONTFR
Compr. Shunt Trip RelayXOFF/ONTRIPR
Alarm RelayXNORMAL/ALARMALM
Spare Prot Limit InputXALARM/NORMALSPR PL
†Information is applicable to hermetic machines only.
NOTE: values preceded by an asterisk (*) can be forced (changed by an operator) from the LID screen
or from another control device (such as a Carrier Comfort Network [CCN] terminal).
To access this display from the LID default screen:
*Temp Reset 4-20 mA4-20mARES OPT
*Common CHWS Sensor–40-245 (–40-118)DEG F (DEG C)CHWS
*Common CHWR Sensor–40-245 (–40-118)DEG F (DEG C)CHWR
*Remote Reset Sensor–40-245 (–40-118)DEG F (DEG C)R RESET
*Temp Sensor — Spare 1–40-245 (–40-118)DEG F (DEG C)SPARE1
*Temp Sensor — Spare 2–40-245 (–40-118)DEG F (DEG C)SPARE2
*Temp Sensor — Spare 3–40-245 (–40-118)DEG F (DEG C)SPARE3
OPTIONS BOARD 2
*4-20 mA — Spare 14-20mASPARE1 M
*4-20 mA — Spare 24-20mASPARE2 M
*Temp Sensor — Spare 4–40-245 (–40-118)DEG F (DEG C)SPARE4
*Temp Sensor — Spare 5–40-245 (–40-118)DEG F (DEG C)SPARE5
*Temp Sensor — Spare 6–40-245 (–40-118)DEG F (DEG C)SPARE6
*Temp Sensor — Spare 7–40-245 (–40-118)DEG F (DEG C)SPARE7
*Temp Sensor — Spare 8–40-245 (–40-118)DEG F (DEG C)SPARE8
*Temp Sensor — Spare 9–40-245 (–40-118)DEG F (DEG C)SPARE9
NOTE: values preceded by an asterisk (*) can be forced (changed by an operator) from the LID screen
or from another control device (such as a Carrier Comfort Network [CCN] terminal).
REFERENCE POINT NAME
(ALARM HISTORY)
24
Page 25
EXAMPLE4—STATUS04 DISPLAY SCREEN
To access this display from the LID default screen:
1. PressMENU
2. Press STATUS
3. Scroll down to highlight STATUS04.
4. Press SELECT
.
.
.
Table 2 — LID Display Data (cont)
DESCRIPTIONRANGEUNITS
Main Gear Oil PumpOFF/ONMAINPMP1
Auxiliary Gear Oil PumpOFF/ONAUXPMP2
Gear Oil Pressure−6.7 to 420 (−46 to 2896)psi (kPa)GEAROILP
Gear Oil Temperature−40 to 245 (−40 to 118)DEG F (DEG C)GEAROILT
EXAMPLE 5 — SETPOINT DISPLAY SCREEN
To access this display from the LID default screen:
1. PressMENU
2. Press SETPOINT
DESCRIPTIONCONFIGURABLE RANGEUNITSREFERENCE POINT NAMEDEFAULT VALUE
Base Demand Limit40-100%DLM100
LCW Setpoint20-120 (–6.7-48.9)DEG F (DEG C)lcw sp
ECW Setpoint20-120 (–6.7-48.9)DEG F (DEG C)ecw sp60.0 (15.6)
ICE BUILD Setpoint20- 60 (–6.7-15.6)DEG F (DEG C)ice sp
.
.
REFERENCE POINT NAME
(ALARM HISTORY)
50.0 (10.0)
40.0 ( 4.4)
25
Page 26
Table 2 — LID Display Data (cont)
EXAMPLE 6 — CONFIGURATION (CONFIG) DISPLAY SCREEN
To access this display from the LID default screen:
1. PressMENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT
5. Scroll down to highlight CONFIG.
6. Press SELECT
DESCRIPTIONCONFIGURABLE RANGEUNITSREFERENCE POINT NAMEDEFAULT VALUE
RESET TYPE 1
Degrees Reset at 20 mA–30-30 (–17-17)DEG F (DEG C)deg 20ma
RESET TYPE 2
Remote Temp (No Reset)–40-245 (–40-118)DEG F (DEG C)res rt1
Remote Temp (Full Reset)–40-245 (–40-118)DEG F (DEG C)res rt265 (18)
Degrees Reset–30-30 (–17-17)DEG F (DEG C)res rt10D(6D)
RESET TYPE 3
CHW Delta T (No Reset)0-15 (0-8)DEG F (DEG C)restd 1
CHW Delta T (Full Reset)0-15 (0-8)DEG F (DEG C)restd 20D(0D)
Degrees Reset–30-30 (–17-17)DEG F (DEG C)deg chw5D(3D)
Select/Enable Reset Type0-3res sel
ECW CONTROL OPTIONDISABLE/ENABLEecw opt
Demand Limit At 20 mA40-100%dem 20ma40
20 mA Demand Limit OptionDISABLE/ENABLEdem selDISABLE
To access this display from the LID default screen:
1. PressMENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT
5. Scroll down to highlight LEAD/LAG.
6. Press SELECT
DESCRIPTIONCONFIGURABLE RANGEUNITSREFERENCE POINT NAMEDEFAULT VALUE
LEAD/LAG SELECT
DISABLE =0, LEAD =1,
LAG =2, STANDBY =3
Load Balance OptionDISABLE/ENABLEloadbalDISABLE
Common Sensor OptionDISABLE/ENABLEcommsensDISABLE
LAG Percent Capacity25-75%lagper
LAG Address1-236lagadd
LAG START Timer2-60MINlagstart10
LAG STOP Timer2-60MINlagstop10
PRESTART FAULT Timer0-30MINpreflt5
STANDBY Chiller OptionDISABLE/ENABLEstndoptDISABLE
STANDBY Percent Capacity25-75%stndper
STANDBY Address1-236stnd add
.
.
.
.
LEAD/LAG CONFIGURATION SCREEN
0-3leadlag0
50
92
50
93
27
Page 28
Table 2 — LID Display Data (cont)
EXAMPLE 8 — SERVICE1 DISPLAY SCREEN
To access this display from the LID default screen:
1. PressMENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT
5. Scroll down to highlight SERVICE1.
6. Press SELECT
DESCRIPTIONCONFIGURABLE RANGEUNITSREFERENCE POINT NAMEDEFAULT VALUE
Motor Temp Override*150-200 (66-93)DEG F (DEG C)mt over
Cond Press Override90-200 (620-1379)PSI (kPa)cpover
Refrig Override Delta T2-5 (1-3)DEG F (DEG C)ref over3D (1.6D)
Chilled MediumWater/BrinemediumWATER
Brine Refrig Trippoint8-40 (–13.3-4)DEG F (DEG C)br trip
Compr Discharge Alert125-200 (52-93)DEG F (DEG C)cd alert
Bearing Temp Alert165-210 (74-99)DEG F (DEG C)tb alert175 (79)
Water Flow Verify Time0.5-5MINwflow t
Oil Press Verify Time15-300SECoilpr t15
Water/Brine Deadband0.5-2.0 (0.3-1.1)DEG F (DEG C)cw db
Recycle Restart Delta T2.0-10.0 (1.1-5.6)DEG F (DEG C)rcycrdt5 (2.8)
Recycle Shutdown Delta0.5-4.0 (.27-2.2)rcycsdt1.0 (0.6)
Surge Limit/HGBP Option0/1srg hgbp
Select: Surge=0, HGBP=1
Surge/HGBP Delta T10.5-15 (0.3-8.3)DEG F (DEG C)hgb dt1
Surge/HGBP Delta P130-170 (207-1172)PSI (kPa)hgb dp150 (345)
Min. Load Points (T1/P1)
Surge/HGBP Delta T20.5-15 (0.3-8.3)DEG F (DEG C)hgb dt2
Surge/HGBP Delta P230-170 (207-1172)PSI (kPa)hgb dp285 (586)
Full Load Points (T2/P2)
Surge/HGBP Deadband1-3 (0.6-1.6)DEG F (DEG C)hgb dp
Surge Delta Percent Amps10-50%surge a
Surge Time Period1-5MINsurge t2
Demand Limit Source0/1dem src
Select: Amps=0, Load=1
Amps Correction Factor1-8corfact3
Motor Rated Load Amps1-9999AMPSa fs
Motor Rated Line Voltage1-9999VOLTSv fs460
Meter Rated Line kW1-9999kWkw fs600
Line Frequency0/1HZfreq0
Select: 0=60 Hz, 1=50 Hz
Compr Starter TypeREDUCE/FULLstarterREDUCE
Condenser Freeze Point–20-35 (–28.9-1.7)DEG F (DEG C)cdfreeze34 (1)
Soft Stop Amps Threshold40-100%softstop100
Stop to Start Timer3-50MINstopmtr20
Spare Temp 4 Enable0-4spr4 en
Spare Temp 4 Alert–40-245 (–40-118)DEG F (DEG C) spr4 al245 (118)
Spare Temp 5 Enable0-4spr5 en0
Spare Temp 5 Alert–40-245 (–40-118)DEG F (DEG C) spr5 al
Spare Temp 6 Enable0-4spr6 en0
Spare Temp 6 Alert–40-245 (–40-118)DEG F (DEG C) spr6 al
Spare Temp 7 Enable0-4spr7 en0
Spare Temp 7 Alert–40-245 (–40-118)DEG F (DEG C) spr7 al245 (118)
Spare Temp 8 Enable0-4spr8 en
Spare Temp 8 Alert–40-245 (–0-118)DEG F (DEG C) spr8 al245 (118)
Spare Temp 9 Enable0-4spr9 en0
Spare Temp 9 Alert–40-245 (–40-118)DEG F (DEG C) spr9 al
NOTE: This screen provides the means to generate alert messages based on exceeding the ‘‘Temp’’threshold for each point listed. If the ‘‘Enable’’
is set to 1, a value above the ‘‘Temp’’ threshold generates an alert message. If the ‘‘Enable’’ is set to 2, a value below the ‘‘Temp Alert’’ threshold
generates an alert message. If the ‘‘Enable’’ is set to 0, alert generation is disabled. If the ‘‘Enable’’ is set to 3, a value above the ‘‘Temp’’ threshold
generates an alarm. If the ‘‘Enable’’ is set to 4, a value below the ‘‘Temp’’ threshold generates an alarm.
.
.
.
.
DESCRIPTIONCONFIGURABLE RANGEUNITSREFERENCE POINT NAME DEFAULT VALUE
0
0
245 (118)
0
245 (118)
245 (118)
0
0
245 (118)
245 (118)
0
245 (118)
EXAMPLE 10 — SERVICE3 DISPLAY SCREEN
To access this display from the LID default screen:
1. PressMENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT
5. Scroll down to highlight SERVICE3.
DESCRIPTIONCONFIGURABLE RANGEUNITSREFERENCE POINT NAMEDEFAULT VALUE
To access this display from the LID default screen:
1. PressMENU
2. Press SERVICE
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT
5. Scroll down to highlight MAINT01.
DESCRIPTIONRANGE/STATUSUNITSREFERENCE POINT NAME
CAPACITY CONTROL
Control Point10-120 (–12.2-48.9)DEG F (DEG C)ctrlpt
Leaving Chilled Water–40-245 (–40-118)DEG F (DEG C)LCW
Entering Chilled Water–40-245 (–40-118)DEG F (DEG C)ECW
Control Point Error–99-99 (–55-55)DEG F (DEG C)cperr
ECW Delta T–99-99 (–55-55)DEG F (DEG C)ecwdt
ECW Reset–99-99 (–55-55)DEG F (DEG C)ecwres
LCW Reset–99-99 (–55-55)DEG F (DEG C)lcwres
Total Error + Resets–99-99 (–55-55)DEG F (DEG C)error
Guide Vane Delta–2-2%gvd
Target Guide Vane Pos0-100%GVTRG
Actual Guide Vane Pos0-100%GVACT
Proportional Inc Band2-10gv inc
Proportional Dec Band2-10gv dec
Proportional ECW Gain1-3gv ecw
Water/Brine Deadband0.5-2 (0.3-1.1)DEG F (DEG C)cwdb
NOTE: Overriding is not supported on this maintenance screen.Active overrides show the associated point in alert (*). Reference point names with
capital letters can be read by CCN and Building Supervisor software.
.
.
.
EXAMPLE 12 — MAINTENANCE (MAINT02) DISPLAY SCREEN
To access this display from the LID default screen:
1. PressMENU
2. Press SERVICE
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT
5. Scroll down to highlight MAINT02.
6. Press SELECT
OVERRIDE/ALERT STATUS
MOTOR WINDING TEMP†–40-245 (–40-118)DEG F (DEG C)MTRW
Override Threshold150-200 (66-93)DEG F (DEG C)mt over
CONDENSER PRESSURE–6.7-420 (–42-2896)PSI (kPa)CRP
Override Threshold90-245 (621-1689)PSI (kPa)cp over
EVAPORATOR REFRIG TEMP–40-245 (–40-118)DEG F (DEG C)ERT
Override Threshold2-45 (1-7.2)DEG F (DEG C)rt over
DISCHARGE TEMPERATURE–40-245 (–40-118)DEG F (DEG C)CMPD
Alert Threshold125-200 (52-93)DEG F (DEG C)cd alert
BEARING TEMPERATURE–40-245 (–40-118)DEG F (DEG C)MTRB
Alert Threshold175-185 (79-85)DEG F (DEG C)tb alert
†Information is applicable to hermetic machines (19EX) only.
NOTE: Overriding is not supported on this maintenance screen.Active overrides show the associated point in alert (*). Reference point names with
capital letters can be read by CCN and Building Supervisor software.
.
.
.
.
DESCRIPTIONRANGE/STATUSUNITSREFERENCE POINT NAME
30
Page 31
Table 2 — LID Display Data (cont)
EXAMPLE 13 — MAINTENANCE (MAINT03) DISPLAY SCREEN
To access this display from the LID default screen:
1. PressMENU
2. Press SERVICE
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT
5. Scroll down to highlight MAINT03.
6. Press SELECT
SURGE/HGBP ACTIVE ?NO/YES
Active Delta P0-200 (0-1379)PSI (kPa)dp a
Active Delta T0-200 (0-111)DEG F (DEG C)dt a
Calculated Delta T0-200 (0-111)DEG F (DEG C)dt c
Surge Protection Counts0-12spc
NOTE: Override is not supported on this maintenance screen. Only values with capital letter reference point names are variables available for read
operation.
To access this display from the LID default screen:
1. PressMENU
2. Press SERVICE
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
LAG Start Time0-60MINlagstart
LAG Stop Time0-60MINlagstop
Prestart Fault Time0-30MINpreflt
Pulldown: Delta T/Minx.xxD DEGF(DDEG C)pull dt
LEAD CHILLER in ControlNo/Yesleadctrl
LAG CHILLER: ModeReset,Off,Local,CCNlagmode
STANDBY CHILLER: ModeReset,Off,Local,CCNstdmode
NOTES:
1. Values on this screen cannot be ‘‘forced’’ (that is, changed by an operator, from the LID or from any other device [such as a CCN terminal]).
2. D = delta degrees.
Current ModeDISABLE,LEAD,LAG,STANDBY, CONFIGllmode
Satisfied?No/Yespull sat
Run StatusTimeout,Recycle,Startup,Ramping,Running
Start/StopStop,Start,Retainlag s s
Recovery Start RequestNo/Yeslag rec
Run StatusTimeout,Recycle,Startup,Ramping,Running
Recovery Start RequestNo/Yesstd rec
Start/StopStop,Start,Retainstd s s
Demand,Override,Shutdown,Abnormal,Pumpdown
Demand,Override,Shutdown,Abnormal,Pumpdown
lagstat
stdstat
31
Page 32
PIC System Functions
NOTE: In the rest of this manual, words not part of paragraph headings and printed in all capital letters can be viewed
on the LID (e.g., LOCAL, CCN, RUNNING, ALARM, etc.).
Words printed both in capital letters and italics can also be
viewed on the LID and are parameters (CONTROL MODE,COOLING SETPOINT,OVERRIDE THRESHOLD, etc.) with
associated values (e.g., modes, temperatures, pressures, percentages, on, off, etc.). Words printed in all capital letters
and in a box represent softkeys on the LID control panel
(e.g., ENTER
the information that can appear on the LID screens.
Figures 11-17 give an overview of LID operation and menus.
CAPACITY CONTROL — The PIC controls the chiller capacity by modulating the inlet guide vanes in response to
chilled water temperature changes away from the WATER/
BRINE CONTROL POINT. The WATER/BRINE CONTROL
POINT may be changed by a CCN network device or is de-
termined when the PIC adds any active chilled water reset to
the chilled water SET POINT. The PIC uses the PROPOR-
TIONAL INC (Increase) BAND, PROPORTIONAL DEC
(Decrease) BAND, and the PROPORTIONAL ECW (Entering Chilled Water)GAIN to determine how quickly or slowly
to respond. WATER/BRINE CONTROL POINT may be viewed/
overridden from the STATUS menu, STATUS01 screen.
ENTERING CHILLED WATER CONTROL — If this option is enabled, the PIC uses the ENTERING CHILLED WA-
TER temperature to modulate the vanes instead of theLEAVING
CHILLED WATER temperature. The ENTERING CHILLED
WATER control option may be viewed/modified from the
CONFIG screen, accessed from the EQUIPMENT CONFIGURATION table.
DEADBAND — This is the tolerance on the chilled water/
brine temperature WATER/BRINE CONTROL POINT. If the
water temperature goes outside the WATER/BRINE DEAD-BAND, the PIC opens or closes the guide vanes in response
until it is within tolerance. The PIC may be configured with
a 0.5° to 2° F (0.3° to 1.1° C) deadband. WATER/BRINEDEADBAND may be viewed or modified from the
SERVICE1 screen, accessed from the EQUIPMENT
SERVICE table.
For example, a 1° F (0.6° C) deadband setting controls
the water temperature within ±0.5° F (0.3° C) of the control
point. This may cause frequent guide vane movement if the
chilled water load fluctuates frequently. A value of
1° F (0.6° C) is the default setting.
PROPORTIONALBANDSAND GAIN — Proportional band
is the rate at which the guide vane position is corrected in
proportion to how far the chilled water/brine temperature is
from the control point. Proportional gain determines how
quickly the guide vanes react to how quickly the temperature is moving from WATER/BRINE CONTROL POINT. Pro-
portional bands and gain values can be viewed/modified from
the SER VICE3screen (accessed from the EQUIPMENT CONFIGURATION table) and the MAINT01 screen (accessed from
the CONTROL ALGORITHM STATUS table).
The Proportional Band — There are two response modes,
one for temperature response above the control point, the
other for response below the control point.
The first type is called PROPORTIONAL INC BAND, and
it can slow or quicken vane response to chilled water/brine
temperature above the WATER/BRINE DEADBAND.Itcan
be adjusted from a setting of 2 to 10; the default setting is
6.5. PROPORTIONAL DEC BAND can slow or quicken vane
response to chilled water temperature below deadband plus
the control point. It can be adjusted on the LID from a setting of 2 to 10, and the default setting is 6.0. Increasing either of these settings causes the vanes to respond more slowly
than at a lower setting.
and EXIT ). See Table 2 for examples of
The PROPORTIONAL ECW GAIN can be adjusted at the LID
display from a setting of 1.0 to 3.0, with a default setting of
2.0. Increase this setting to increase guide vane response to
a change in entering chilled water temperature.
DEMAND LIMITING — The PIC responds to the ACTIVEDEMAND LIMIT set point by limiting the opening of the
guide vanes. It compares the set point to either COMPRES-
SOR MOTORLOADorCOMPRESSORMOTORLOADCURRENT (percentage), depending on how the control is con-
figured for the DEMAND LIMIT SOURCE which is accessed
on the SERVICE1 screen. The default setting is current
limiting. The ACTIVE DEMAND LIMIT may be viewed on
the STATUS01 screen.
CHILLER TIMERS — The PIC maintains 2 runtime clocks,
known asCOMPRESSORONTIME andSERVICEONTIME. COMPRESSOR ONTIME indicates the total lifetime compressor run hours. This timer can register up to
500,000 hours before the clock turns back to zero.The SERV-ICE ONTIME is a resettable timer that can be used to indicate the hours since the last service visit or any other event.
The time can be changed from the LID to whatever value is
desired. This timer can register up to 32,767 hours before it
rolls over to zero.
The chiller also maintains a start-to-start timer and a stopto-start timer. These timers limit how soon the chiller can be
started. See the Start-Up/Shutdown/Recycle Sequence section, page 43, for operational information.
OCCUPANCY SCHEDULE — The chiller schedule, described in the Time Schedule Operation section, page 18,
determines when the chiller can run. Each schedule consists
of 1 to 8 occupied/unoccupied time periods, set by the operator. These time periods can be enabled (or not enabled)
on each day of the week and for holidays. The day begins
with 0000 hours and ends with 2400 hours. The chiller is in
an occupied state unless an unoccupied time period is in
effect.
NOTE: To determine whether or not the chiller is in an occupied state and can be started, access the STATUS01 screen
and scroll to the OCCUPIED? parameter. If the value in the
right column is YES, the chiller is in an occupied state and
can turn on or can be started. If the value is NO, the chiller
is in an unoccupied state; that is, it can shut down or cannot
be started without performing an override.
The schedules can be set to follow the building schedule
or to be in an occupied state 100% of the time. The schedules also can be bypassed by forcing the CHILLER START/STOP parameter on the STATUS01 screen to START. For
more information on forced starts, see Local Start-Up,
page 43. The schedules also can be overridden to keep the
chiller in an occupied state for up to 4 hours, on a one-time
basis.
NOTE: A parameter value can be 9forced9 (changed by an
operator) from the LID screen or from another control device such as a CCN terminal. For example, if the CHILLERSTART/STOP parameter is set to START, the operator can
go to the LID and change the value to STOP to 9force9 the
chiller to stop.
Figure 14 shows a schedule for a typical office building
time schedule, with a 3-hour,off-peak cool down period from
midnight to 3 a.m., following a weekend shutdown. For example, holiday periods are set to be unoccupied 24 hours per
day.The building operates Monday through Friday, 7:00 a.m.
to 6:00 p.m., with a Saturday schedule of 6:00 a.m. to
1:00 p.m., and includes the Monday midnight to 3:00 a.m.
weekend cool-down schedule.
32
Page 33
NOTE: This schedule is for illustration only, and is not intended to be a recommended schedule for chiller operation.
Depending on its operating mode, the chiller uses the fol-
lowing occupancy schedules:
• LOCAL mode — Occupancy Schedule 01(OCCPC01 on
the SCHEDULE screen).
• ICE BUILD mode — Occupancy Schedule 02 (OCCPC02 on the SCHEDULE screen).
• CCN mode — Occupancy Schedule 03-99 (OCCPC02OCCPC99 on the SCHEDULE screen).
The CCN schedule number is specified on the CONFIG
screen, which is accessed from the EQUIPMENT CONFIGURATION table. The schedule number can be any value
from 03 to 99. If this schedule number is changed on the
CONFIG screen, the operator must use the ATTACHTONETWORK DEVICE screen to upload the new number into the
schedule screen. See Fig. 12.
Safety Controls — The PIC monitors all safety control
inputs, and if required, shuts down the chiller or limits the
guide vanes to protect the chiller from possible damage from
several conditions, including:
• high bearing temperature
• high motor winding temperature
• high discharge temperature
• low compressor oil pressure
• low gear oil pressure
• high gear oil temperature
• low cooler refrigerant temperature/pressure
• condenser high pressure or low pressure
• inadequate water/brine cooler and condenser flow
• high, low, or loss of voltage
• excessive motor acceleration time
• excessive starter transition time
• lack of motor current signal
• excessive motor amps
• excessive compressor surge
• temperature and transducer faults
Starter faults or optional protective devices within the starter
can shut down the chiller. These devices depend on what
options have been purchased.
Default Screen Freeze — When the chiller is in an
alarm state, the default LID display freezes; that is, it stops
updating. The first line of the LID default screen displays a
primary alarm message; the second line displays a secondary alarm message. The LID default screen freezes to allow
the operator to see the condition of the chiller at the time ofthe alarm. Knowledge of the operating state of the chiller at
the time an alarm occurs is useful when troubleshooting. Current chiller information can be viewed on the STATUS screens
(see Table 2, Examples 1-4). Once all existing alarms are
cleared by pressing the RESET
screen returns to normal operation.
softkey, the default LID
Auxiliary Compressor Oil Pump Control — The
compressor oil pump (optional) is controlled by the PIC. If,
during start-up, the main oil pump cannot raise pressure to
18 psi (124 kPa), the auxiliary oil pump (optional) is energized. During compressor operation, the auxiliary oil pump
is energized if the oil pressure falls below the alert threshold
(18 psi [124 kPa]). Once the auxiliary compressor oil pump
is running, it stays on until the compressor is turned off and
is deenergized along with the main oil pump after the postlubrication period.
Auxiliary Gear Oil Pump Control — The optional
auxiliary gear oil pump is controlled by the PIC. During startup, if the main gear oil pump cannot raise the oil pressure at
least 20 psi (139 kPa), the auxiliary gear oil pump is energized. If, after 30 seconds, the required oil pressure has not
been established, the PIC initiates an alarm and does not allow the chiller to start. During operation, the auxiliary gear
oil pump is energized if the oil pressure falls below the alert
threshold (15 to 20 psi [103 to 139 kPa]). Once the auxiliary
gear oil pump is running, it stays on until the compressor is
turned off and is deenergized with the main gear oil pump
after the post-lubrication period.
Shaft Seal Oil Control — For all open-drive chillers,
the shaft seal must be bathed in oil at all times, especially
when the chiller is not running. This ensures that refrigerant
will not leak past the seal. The PIC energizes the compressor
oil pump for one minute if the oil pump has not operated
during the past 12 hours.
If a compressor motor overload or ground fault occurs,
check the motor for grounded or open phases before attempting a restart.
If the PIC control initiates a safety shutdown, the control
displays a primary and secondary alarm message on the LID,
energizes an alarm relay in the starter, and blinks the alarm
light on the control panel. The alarm information is stored in
memory and can be viewed on the LID by accessing the
ALARM HISTORY table along with a troubleshooting
message.
To give a more specific operating condition warning, the
operator can also define alert limits on various monitored
inputs. Safety contact and alert limits are defined in Table 3.
Alarm and alert messages are listed in the Troubleshooting
Guide section, page 83.
SHUNT TRIP — The PIC can include an optional shunt trip
function that acts as a safety trip. The shunt trip is wired
from an output on the SMM to the motor circuit breaker. If
the PIC tries to shut down the compressor using normal shutdown procedures but is unsuccessful for 30 seconds, the shunt
trip output is energized and trips off the circuit breaker. If
ground fault protection has been applied to the starter, the
ground fault trip also energizes the shunt trip to trip the circuit breaker.
IMPORTANT: If control power is turned offfor more
than 12 hours, the refrigerant charge must be pumped
into the economizer/storage vessel. Because the oil heater
is also turned off during this time, storing the refrigerant prevents refrigerant from migrating into the oil.
RampLoading Control — Ramp loading control slows
down the rate at which the compressor loads up. It prevents
the compressor from loading up during the short time between chiller start-up and the time the chilled water loop has
to be brought down to normal design conditions. Ramp loading helps to reduce electrical demand by slowly bringing the
chilled water temperature to the control point temperature.
The total power draw during this period stays almost
unchanged.
The PIC bases ramp loading on either the chilled water
temperature or on motor load. See the Table 2, Example 6
(CONFIG screen).
1. The temperature ramp loading rate is an operator-
configured value that limits the rate at which either the
leaving chilled water or entering chilled water temperature decreases (TEMP PULLDOWN DEG/MIN parameter on the CONFIG screen). The lowest temperature ramp
rate is used the first time the chiller is started (at commissioning). The lowest temperature ramp rate is also used
if chiller power has been off for 3 hours or more (even if
the motor ramp load control method has been selected).
33
Page 34
Table 3 — Protective Safety Limits and Control Settings
MONITORED PARAMETERLIMITAPPLICABLE COMMENTS
TEMPERATURE SENSORS
OUT OF RANGE
PRESSURE TRANSDUCERS
OUT OF RANGE
COMPRESSOR DISCHARGE
TEMPERATURE
BEARING TEMPERATURE.220 F (104.4 C)Preset, alert setting configurable
EVAPORATOR REFRIGERANT
TEMPERATURE
(Temp converted from Pressure
Reading)
.110% for 30 secondsPreset
,10% with compressor runningPreset
.10% with compressor offPreset
.45 seconds
.10 seconds
Energizes condenser pump relay if condenser refrigerant temperature or condenser entering water temperature is below the
configured condenser freeze point temperature. Deenergizes
when the temperature is5F(3C)above condenser freeze point
temperature.
Water from motor cooling is leaking
Cut-Out > 150 F (66 C)
Must be outside range for 2 seconds.
Ratio = Input Voltage ÷ Voltage Reference
Preset, configure chilled medium for water
(Service1 table)
Configure chilled medium for brine (Service1
table). Adjust brine refrigerant trippoint for
proper cutout
Preset (Read voltage at terminals 34 and 35
on PSIO module)
Preset
Preset, no calibration needed
Preset
Preset, based on transformed line voltage to
24 vac rated-input to the Starter Management
Module. Also monitored at PSIO power input.
For chillers with reduced voltage mechanical
and solid-state starters
For chillers with full voltage starters
(Configured on Service1 table)
CONDENSER FREEZE POINT configured in
Service01 table with a default setting of
34F(1C).
Water sensors are installed only on open-drive
motors that use water cooling. (Totally enclosed,
water-to-air cooled [TEWAC] motors)
Preset
Adjustable
Preset
Adjustable
FLOW SWITCHES (Field Supplied)
Operate water pumps with chiller off. Manually reduce water flow and observe
switch for proper cutout. Safety shutdown occurs when cutout time exceeds
3 seconds.
CUT-OFF
SETTING
ADJUSTMENT
SCREW
Carrier Part No. HK06ZC033
Carrier Part No. HK06ZC001
NOTE: Dimensions in parentheses are in
millimeters.
34
Page 35
2. The motor load ramp loading rate is an operator-configured
value that limits the rate at which the compressor motor
current or compressor motor load increases. (LOAD PULL-DOWN %/MIN on the CONFIG screen).
To select the ramp type, highlight the SELECT RAMPTYPE parameter on the CONFIG screen and select either
0(TEMP)or1(LOAD). Motor load (1) is the default ramp
loading control type.
Capacity Override (See Table4) — Capacity over-
rides can prevent some safety shutdowns caused by exceeding the motor amperage limit, refrigerant low temperature
safety limit, motor high temperature safety limit, and condenser high pressure limit. In all of these cases, there are
2 stages of compressor vane control.
1. The guide vanes are kept from opening further, and the
status line on the LID displays the reason for the
override.
2. The guide vanes are closed until the condition decreases
below the first step set point. Then, the vanes are released
to normal capacity control.
Whenever the motorcurrentdemandlimitsetpoint is reached,
it activates a capacity override, again using the 2-step process. Exceeding 110% of the rated load amps for more than
30 seconds initiates a safety shutdown.
The compressor high lift (surge prevention) set point causes
a capacity override as well. When the surge prevention set
point is reached, the PIC normally prevents the guide vanes
from opening. See the Surge Prevention Algorithm section,
page 37. If the chiller is equipped with the hot gas bypass
option, the PIC opens the hot gas bypass valve instead of
holding the guide vanes.
HighDischarge TemperatureControl— If the dis-
charge temperature increases above 200 F (93 C), the guide
vanes are proportionally opened to increase gas flow through
the compressor.If the leaving chilled water temperature drops
5° F (2.8° C) below the control point temperature, chiller
enters the RECYCLE mode.
OilSump TemperatureControl— The oil sump tem-
perature control is regulated by the PIC which uses the oil
heater relay when the chiller is shut down.
As part of the pre-start checks executed by the controls,
the PIC compares the oil sump temperature to the evaporator refrigerant temperature. If the difference between these 2
temperatures is 50 F (27.8 C) or less, the start-up is delayed
until the oil temperature difference is 50 F (27.8 C) or more.
Once this temperature is confirmed, the start-up continues.
The oil heater relay is energized whenever the chiller compressor is off and the oil sump temperature is less than
150 F (65.6 C) or the oil sump temperature is less than the
cooler refrigerant temperature plus 70° F (39° C). The oil
heater is turned off when the oil sump temperature is either
• more than 160 F (71.1 C)
• or the oil sump temperature is more than 155 F (68.3 C)
and more than the cooler refrigerant temperature plus
75° F (41.6° C).
The oil heater is always off during start-up or when the
compressor is running.
When a power failure to the PSIO module has occurred
for more than 3 hours (i.e., initial start-up), the compressor
guide vane opening is slowed down to prevent excessive oil
foaming that may result from refrigerant migration into the
oil sump during the power failure. The vane opening is slowed
via temperature ramp loading to a value of 2° F (1.1° C) per
minute.
OVERRIDE
CAPACITY
CONTROL
HIGH CONDENSER
PRESSURE
LOW REFRIGERANT
TEMPERATURE
(Refrigerant Override
Delta Temperature)
HIGH COMPRESSOR
LIFT
(Surge Prevention)
MANUAL
GUIDE VANE
TARGET
MOTOR LOAD —
ACTIVE
DEMAND LIMIT
LEGEND
HGBP — High Gas Bypass
P1— Minimum Pressure Load
P2— Maximum Pressure Load
T1— Minimum Temperature Load
T2— Maximum Temperature Load
View/Modify
on LID Screen
Equipment
Equipment
Equipment
Algorithm
Table 4 — Capacity Overrides
FIRST STAGE SETPOINT
Default ValueConfigurable RangeValueValue
Service1
Service1
Service1
Control
Maint01
Status01100%40 to 100%
125 psig
(862 kPa)
,3° F (1.6° C)
(Above Trippoint)
Min: T1 — 1.5° F
(0.8° C)
P1 — 50 psid
(345 kPad)
Max: T2 — 10° F
(5.6° C)
P2 — 85 psid
(586 kPad)
Automatic0 to 100%None
90 to 200 psig
(620 to 1379 kPa)
2° to 5° F
(1° to 3° C)
0.5° to 15° F
(0.3° to 8.3° C)
30 to 170 psid
(207 to1172 kPad)
0.5° to 15° F
(0.3° to 8.3° C)
30 to 170 psid
(207 to 1172 kPad)
SECOND STAGE
SETPOINT
.Override
Set Point
+ 4 psid (28 kPad)
<Trippoint
+ Override
DT –1° F
(0.56° C)
None
>5% of
Set Point
OVERRIDE
TERMINATION
,Override
Set Point
.Trippoint
+ Override
DT +2° F
(1.2° C)
Within
Lift Limits
Plus Surge/
HGBP
Deadband
Setting
Release of
Manual
Control
2% Lower
Than
Set Point
35
Page 36
Oil Cooler — The oil for the external gear and the com-
pressor must be cooled while the compressor is running. The
compressor oil cooler is a water-cooled, helical, tube-inshell type heat exchanger. A plug valve is manually set to
maintain proper temperatures. Set the valve to maintain a
145 F (63 C) oil sump temperature while the compressor is
running.
The gear oil cooler is a water-cooled, helical tube-in-shell
type heat exchanger. A plug valve is manually set to maintain proper temperatures. Set the valve to maintain the oil
temperature leaving the cooler at 130 F (54 C) while the compressor is running.
RemoteStart/Stop Controls — A remote device, such
as a time clock with a set of contacts, may be used to start
and stop the chiller. However, the device should not be programmed to start and stop the chiller more than 2 or 3 times
every 12 hours. If more than 8 starts in 12 hours occur, the
Excessive Starts alarm is displayed, and the chiller is prevented from starting. The operator must reset the alarm at
the LID in order to override the starts counter and start the
chiller. If the automatic restart after a power failure (AUTOREST ARTOPTION ) is not activated (disabled) when a power
failure occurs and the remote contact is closed, the PIC control activates an alarm because of the loss of voltage.
The contacts for remote starting are wired into the starter
at terminal strip TB5, terminals 8A and 8B. See the certified
drawings for further details on contact ratings. The contacts
must be dry (no power).
Spare Safety Inputs — Normally closed (NC) digital
inputs for additional field-supplied safeties may be wired to
the spare protective limits input channel in place of the factoryinstalled jumper. (Wire multiple inputs in series.) Opening
any contact results in a safety shutdown and LID display.
Refer to the certified drawings for safety contact ratings.
Analog temperature sensors may also be added to the options modules, if installed. These may be programmed to activate an alert on the CCN network, but not shut down the
chiller.
SpareAlarmContacts — Twospare sets of alarm con-
tacts are provided in the starter. The contact ratings are provided in the certified drawings. The contacts are located on
terminal strip TB6, terminals 5A and 5B, and terminals 5C
and 5D.
Condenser Pump Control — The chiller monitors
the condenser pressure (CONDENSER PRESSURE parameter on the STATUS01 screen) and may turn on the condenser pump if the pressure becomes too high whenever the
compressor is shut down. The condenser pressure override
(CONDPRESSURE OVERRIDEparameteronthe
SERVICE1 screen) is the value that determines this pressure
point. Its default value is 125 psi (862 kPa). If the condenser
pressure is greater than or equal to the condenser pressure
override, and the entering condenser water temperature (EN-TERINGCONDENSERWATERparameteronthe
STATUS01 screen) is less than 115 F (46 C), then the condenser pump energizes to try to decrease the pressure. The
pump turns offwhen the condenser pressure is 5psi (34 kPa)
less than the pressure override, or when the condenser refrigerant temperature (CONDENSER REFRIG TEMP on the
STATUS01 screen) is within 3° F (2° C) of the entering condenser water temperature.
Condenser Freeze Prevention — This control al-
gorithm helps prevent condenser tube freeze-up by energizing the condenser pump relay. If the pump is controlled by
the PIC, starting the pump helps prevent the water in the
condenser from freezing. Condenser freeze prevention can
occur whenever the chiller is not running except when it is
either actively in pumpdown or in pumpdown lockout with
the freeze prevention disabled.
When the condenser refrigerant temperature is less than
or equal to the condenser freeze point (CONDENSER FREEZEPOINT on the SERVICE1 screen), or the entering condenser
water temperature is less than or equal to the condenser freeze
point, then the condenser water pump (CONDENSER WA-TER PUMP on the STATUS02 screen) is energized until the
condenser refrigerant temperature is greater than the condenser freeze point plus 5° F (2.7° C). If the chiller is in
PUMPDOWN mode and the pump is energized, the PIC activates an alarm. If the chiller is not in PUMPDOWN mode
and the pump is energized, the PIC activates an alert. If the
chiller is in RECYCLE shutdown mode, the mode transitions to SHUTDOWN (non-recycle shutdown).
Tower-Fan Relay — This control can be used to assist
the condenser water temperature control system (field supplied). Low condenser water temperature can cause the chiller
to shut down on low refrigerant temperature. The tower fan
relay, located in the starter, is controlled by the PIC to energize and deenergize as the pressure differential between
cooler and condenser vessels changes. This function prevents low condenser water temperature and maximizes chiller
efficiency. The tower-fan relay can only accomplish this if
the relay has been added to the cooling tower temperature
controller.The tower-fan relay (TOWER FAN RELAY on the
STATUS02 screen) is turned on whenever the condenser water pump is running, flow is verified, and the difference between cooler and condenser pressure is more than 30 psid
(207 kPad) or entering condenser water temperature is greater
than 85 F (29 C). The tower-fan relay is deenergized whenever the condenser pump is off, flow is lost, the evaporator
refrigerant temperature is less than the override temperature,
or the differential pressure is less than 28 psid (193 kPad)
and entering condensing water is less than 80 F (27 C).
IMPORTANT:A field-supplied water temperature control system for condenser water should be installed.
The system should maintain the leaving condenser water temperature at 20° F (11° C) above the leaving chilled
water temperature.
The tower-fan relay control is not a substitute for a condenser water temperature control. When used with a water temperature control system, the tower-fan relay control can be used to help prevent low condenser water
temperatures and associated problems.
Auto. Restart After Power Failure — This option,
which may be viewed or modified on the CONFIG screen
(the AUTO RESTART OPTION parameter), can be enabled
or disabled. If this option is enabled, the chiller starts up automatically after a single cycle dropout; low, high, or no voltage; and the power is within ±10% of normal. The
15-minute start-to-start timer and the stop-to-start timer are
ignored during this type of start-up.
When power is restored after a power failure, and if the
compressor had been running, the oil pump is energized for
one minute before the evaporator pump is energized. The
Auto. Restart function then continues like a normal start-up.
36
Page 37
Water/Brine Reset — Three types of chilled water/
brine reset are available, Reset Type 1, Reset Type 2, and
Reset Type 3. They can be viewed or modified on the CONFIG screen (accessed from the EQUIPMENT CONFIGURATION table). See Table 2, Example 6.
The LID default screen status message indicates when a
reset is active. The WATER/BRINE CONTROL POINT tem-
perature on the STATUS01 table indicates the chiller’s current reset temperature.
To configure a reset type, input all configuration information for that reset type on the CONFIG screen. Then activate
the reset type by entering the reset type number in the SELECT/ENABLE RESET TYPE input line.
RESET TYPE 1 (Requires an optional 8-input module) —
Reset Type 1 is an automatic chilled water temperature reset
based ona4to20mAinput signal. The value for Rest Type
1 is user configurable (DEGREES RESET AT 20 mA). It is
a temperature that corresponds to a 20 mA signal. (4 mA
corresponds to 0° F [0° C]; 20 mA corresponds to the temperature entered by the operator.)
This reset type permits up to ±30° F (±16° C) of automatic reset to the chilled water/brine temperature set point,
based on the input froma4to20mAsignal. The signal is
hardwired into the No. 1 eight-input module.
If the 4 to 20 mA signal is externally powered from the
8-input module, the signal is wired to terminals J1-5(+) and
J1-6(–). If the signal is powered internally by the 8-input
module (for example, when using variable resistance), the
signal is wired to J1-7(+) and J1-6(–). The PIC must be
configured on the SERVICE2 screen to ensure that the
appropriate power source is identified. See Table 2,
Example 9, 20 mA POWER CONFIGURATION.
RESET TYPE 2 (Requires an optional 8-input module) —
Reset Type 2 is an automatic chilled water temperature reset
based on a remote temperature sensor input.
This reset type permits ±30° F (±16° C) of automatic reset to the set point based on a temperature sensor wired to
the No. 1 eight-input module (see wiring diagrams or certified drawings). The temperature sensor must be wired to
terminal J1-19 and J1-20.
Configure Reset Type 2 on the CONFIG screen (Table 2,
Example 6). Enter the temperature of the remote sensor at
the point where no temperature reset will occur (REMOTETEMP [NO RESET]). Next, enter the temperature at which
the full amount of reset will occur (REMOTE TEMP [FULLRESET]). Then, enter the maximum amount of reset required to operate the chiller (DEGREES RESET). Reset
Type 2 can now be activated.
RESET TYPE 3 — Reset Type 3 is an automatic chilled water temperature reset based on cooler temperature difference. This reset adds ±30° F (±16° C) based on the temperature difference between entering and leaving chilled water.
Reset Type 3 is the only reset available without the need for
a No. 1 eight-input module. No wiring is required for Reset
Type 3, because it already uses the cooler water sensors.
Configure Reset Type 3 on the CONFIG screen (Table 2,
Example 6). Enter the chilled water temperature difference
(the difference between entering and leaving chilled water)
at which no temperature reset occurs (CHW DELTA T [NORESET]). This chilled water temperature difference is usually the full design load temperature difference. Enter the
difference in chilled water temperature at which the full
amount of reset occurs (CHW DELTA T [FULL RESET]).
Next, enter the amount of reset (DEGREES RESET). Reset
Type 3 can now be activated.
be externally controlled witha4to20mAsignal from an
Energy Management System (EMS). The option (20 mA DE-MAND LIMIT OPTION) is enabled or disabled on the CONFIG screen (Table 2, Example 6). When enabled, the control
is set for 100% demand with 4 mA and an operator configured minimum demand set point at 20 mA (DEMAND LIMITAT 20 mA).
The EMS demand reset input is hardwired into the No. 1
8-input module. The signal may be internally powered by
the module or externally powered. If the signal is externally
powered, the signal is wired to terminals J1-1(+) and
J1-2(–). If the signal is internally powered, the signal is wired
to terminals J1-3(+) and J1-2(–). When enabled, the control
is set for 100% demand with 4 mA and an operator configured minimum demand set point at 20 mA (DEMAND LIMIT
AT 20 mA).
The demand limit may
Surge Prevention Algorithm — Surge occurs when
lift conditions become so high that the gas flow across the
impeller reverses. This condition can eventually cause chiller
damage. Lift is defined as the difference between the pressure at the impeller eye and the impeller discharge. The maximum lift that a particular impeller wheel can produce varies
with the gas flow across the impeller and the size of the
wheel.
The surge prevention algorithm is operator configurable
and can determine if lift conditions are too high for the compressor. If they are, the PIC takes corrective action. The algorithm also notifies the operator, via the LID, that chiller
operating conditions are marginal.
The surge prevention algorithm first determines if corrective action is necessary. This is done by checking 2 sets of
operator configured data points: the minimum load points
(MIN. LOAD POINTS [T1/P1]) and the maximum load
points (FULL LOAD POINTS [T2/P2]). See the SERVICE1
screen or Table 2, Example 8. These points have default settings. Information on how to modifiy the default minimum
and maximum load points can be found in the Input Service
Configurations section on page 54.
Figures 18 and 19 graphically display these settings and
the algorithm function. The 2 sets of load points (default settings) describe a line that the algorithm uses to determine
the maximum lift of the compressor. Whenever the actual
differential pressure between the cooler and condenser and
the temperature difference between the entering and leaving
chilled water are above the line on the graph (as defined by
the minimum and maximum load points) the algorithm goes
into a corrective action mode. If the actual values are below
the line, the algorithm takes no action.
Corrective action can be taken by making one of 2 choices.
If the optional hot gas bypass line is present, and the operator selects the hot gas bypass option on the SERVICE1
screen (selects 1 for the SURGE LIMIT/HGBP OPTION),
then the hot gas bypass valve can be energized. If the hot gas
bypass option is not present, then the SURGE LIMIT/HGBPOPTION is on the default setting (0), and the guide vanes
are held. (Also see Table 4, Capacity Overrides.) Both corrective actions reduce the lift experienced by the compressor
and help to prevent a surge condition.
ECW— Entering Chilled Water
HGBP — Hot Gas Bypass
LCW— Leaving Chilled Water
LEGEND
Fig. 18 — 17EX Hot Gas Bypass/Surge
Prevention With Default Settings (English)
parameter, Table 2, Example 13) can be monitored on the
MAINT03 screen. The SURGE TIME PERIOD parameter is
displayed and configured on the SERVICE1 screen. See
Table 2, Example 8. It has a default of 2 minutes.
Lead/Lag Control — Lead/lag is a control system pro-
cess that automatically starts and stops a lag or second chiller
in a 2-chiller system. Refer to Fig. 15 and 16 for menu, table,
and screen selection information. On chillers that have PSIO
software with lead/lag capability, it is possible to use the PIC
controls to perform the lead/lag function on 2 chillers.A third
chiller can be added to the lead/lag system as a standby chiller
to start up if the lead or lag chiller in the system has shut
down during an alarm condition and additional cooling is
required.
NOTE: Lead/lag parameters can be viewed and modified on
the LEAD/LAG CONFIGURATION screen, accessed from
the EQUIPMENT CONFIGURATION table. See Table 2,
Example 7. Lead/lag status during chiller operation is viewed
on the MAINT04 screen, accessed from the CONTROL
ALGORITHM STATUS table. See Table 2, Example 14.
Lead/Lag System Requirements:
• all chillers must have PSIO software capable of performing the lead/lag function
• water pumps MUST be energized from the PIC controls
• water flows should be constant
• CCN Time Schedules for all chillers must be identical
Operation Features:
• 2 chiller lead/lag
• addition of a third chiller for backup
• manual rotation of lead chiller
• load balancing if configured
• staggered restart of the chillers after a power failure
• chillers may be piped in parallel or in series chilled water
flow
ECW— Entering Chilled Water
HGBP — Hot Gas Bypass
LCW— Leaving Chilled Water
LEGEND
Fig. 19 — 17EX Hot Gas Bypass/Surge Prevention
With Default Settings (SI)
Surge Protection — Compressor surge can be de-
tected by the PIC based on operator configured settings. Surge
causes amperage fluctuations of the compressor motor. The
PIC monitors these amperage swings, and if the swing is
greater than the configured setting (SURGE DELTAPERCENT AMPS) in one second, then one surge event has
occurred. The setting is displayed and configured on the
SERVICE1 screen. Its default setting is 25% amps.
Asurge protection chiller shutdown occurs when the surge
protection counter reaches 12 within an operator specified
time period, known as the surge time period. The
surge protection count (SURGE PROTECTION COUNTS
COMMON POINT SENSOR INSTALLATION — Lead/
lag operation does not require a common chilled water point
sensor. Common point sensors can be added to the 8-input
option module, if desired. Refer to the certified drawings for
termination of sensor leads.
NOTE: If the common point sensor option is chosen on a
chilled water system, each chiller should have its own 8-input
option module and common point sensor installed. A chiller
uses its own common point sensor forcontrol when that chiller
is designated as the lead chiller. The PIC cannot read the
value of common point sensors installed on other chillers in
the chilled water system.
When installing chillers in series, use a common point sensor.If a common point sensor is not used, the leaving chilled
water sensor of the upstream chiller must be moved into the
leaving chilled water pipe of the downstream chiller.
If return chilled water control is required on chillers piped
in series, the common point return chilled water sensor should
be installed. If this sensor is not installed, the return chilled
water sensor of the downstream chiller must be relocated to
the return chilled water pipe of the upstream chiller.
To properly control the common supply point temperature
sensor when chillers are piped in parallel, the water flow through
the shutdown chiller(s) must be isolated so there is no water
bypass around the operating chiller. The common point sensor option must not be used if water bypass around the operating chiller is occurring.
CHILLER COMMUNICATION WIRING — Refer to the
chiller Installation Instructions and the Carrier Comfort Network Interface section on page 53 of this manual for information on chiller communication wiring.
38
Page 39
LEAD/LAG OPERATION — The PIC control has the capability to operate 2 chillers in the lead/lag mode. It also has
the additional capability to start a designated standby
chiller when either the lead or lag chiller is not operating
and capacity requirements are not being met. The lead/lag
option operates in CCN mode only. If any other chiller configured for lead/lag is set to the LOCAL or OFF modes, it
will be unavailable for lead/lag operation.
NOTE: Lead/lag configuration is viewed and edited on the
LEAD/LAG screen, accessed from the EQUIPMENT CONFIGURATION table of the SERVICE menu. See Table 2,
Example 7. Lead/lag status during chiller operation is viewed
on the MAINT04 screen, accessed from the CONTROL ALGORITHM STATUS table. See Table 2, Example 14.
Lead/Lag Chiller Configuration and Operation — A chiller
is designated the lead chiller when the LEAD/LAGSELECT parameter for that chiller is set to 1 on the LEAD/
LAG CONFIGURATION screen.Achiller is designated the
lag chiller when the LEAD/LAD SELECT parameter for that
chiller is set to 2. A chiller is designated the standby chiller
when the LEAD/LAG SELECT parameter for that chiller is
set to 3. Setting the LEAD/LAG SELECT parameter to 0 disables the lead/lag function in that chiller.
To configure the LAG ADDRESS parameter on the LEAD/
LAG CONFIGURATION screen, always use the address of
the other chiller on the system. Using this address makes it
easier to rotate the lead and lag chillers.
If improper address assignments are entered for the LAGADDRESS and STANDBY ADDRESS parameters, the
lead/lag is disabled and an alert (!) message displays on the
LID. For example, if the lag chiller’s address matches the
lead chiller’s address, the lead/lag function is disabled and
an alert (!) message displays. The lead/lag maintenance screen
(MAINT04) displays the message INVALID CONFIG in the
LEAD/LAG CONFIGURATIONand CURRENTMODEfields.
The lead chiller responds to normal start/stop controls such
as occupancy schedule, forced start/stop, and remote start
contact inputs. After completing start-up and ramp loading,
the PIC evaluates the need for additional capacity. If additional capacity is needed, the PIC initiates the start-up of the
chiller configured at the lag address. If the lag chiller is faulted
(in alarm) or is in the OFF or LOCAL modes, then the chiller
at the standby address (if configured) is requested to start.
After the second chiller is started and is running, the lead
chiller monitors conditions and evaluates whether the capacity has been reduced enough for the lead chiller to sustain the system alone. If the capacity is reduced enough for
the lead chiller to sustain the control point temperatures alone,
then the operating lag chiller is stopped.
If the lead chiller is stopped in CCN mode for any reason
other than an alarm (*) condition, then the lag and standby
chillers are stopped. If the configured lead chiller stops for
an alarm condition, then the configured lag chiller takes the
lead chiller’s place as the lead chiller and the standby chiller
serves as the lag chiller.
If the configured lead chiller does not complete the start-up
before the PRESTART FAULT TIMER (a user configured pa-
rameter on the LEAD/LAG screen) elapses, then the lag chiller
is started and the lead chiller shuts down. The lead chiller
then monitors the request to start from the acting lead chiller.
The pre-start fault timer is initiated at the time of a start request. This timer’s function is to provide a time-out if there
is a pre-start alert condition that prevents the chiller from
starting in a timely manner.
If the lag chiller does not achieve start-up before the
pre-start fault time elapses, then the lag chiller is stopped
and the standby chiller is requested to start, if configured
and ready.
Standby Chiller Configuration and Operation — The configured standby chiller is identified as such by having its LEAD/LAG SELECT parameter assigned a value of 3. The standby
chiller can only operate as a replacement for the lag chiller
if one of the other two chillers is in an alarm (*) condition
(as indicated on the LID panel). If both lead and lag chillers
are in an alarm (*) condition, the standby chiller defaults to
operate in CCN mode based on its configured occupancy schedule and remote contacts input.
Lag Chiller Start-Up Requirements — Before the lag chiller
can be started, the following conditions must be met.
1. Lead chiller ramp loading must be completed.
2. Lead chiller’s chilled water temperature must be
greater than the WATER/BRINECONTROL POINT (STATUS01 screen) plus half the WATER/BRINE DEAD-BAND (SERVICE1 screen).
NOTE: The chilled water temperature sensor may be the
leaving chilled water sensor, the return water sensor, the
common supply water sensor, or the common return water sensor, depending on which options are configured and
enabled.
3. Lead chiller ACTIVE DEMAND LIMIT (STATUS01
screen) value must be greater than 95% of full load amps.
4. Lead chiller temperature pulldown rate (TEMP PULL-DOWN DEG/MIN on the CONFIG screen) of the chilled
water temperature is less than 0.5° F (0.27° C) per minute.
5. The lag chiller status indicates it is in CCN mode and is
not faulted. If the current lag chiller is in an alarm condition, then the standby chiller becomes the active lag chiller,
if it is configured and available.
6. The configured time for the LAG START TIMER parameter has elapsed. The lag start timer starts when the lead
chiller ramp loading is completed. The LAG STARTTIMER
parameter is on the LEAD/LAG screen, which is accessed from the EQUIPMENT CONFIGURATION table.
See Table 2, Example 7.
When all the above requirements have been met, the lag
chiller is forced to a STARTUPmode. The PIC control then
monitors the lag chiller for a successful start. If the lag chiller
fails to start, the standby chiller, if configured, is started.
Lag Chiller Shutdown Requirements — The following conditions must be met in order for the lag chiller to be stopped.
1. Lead chiller COMPRESSOR MOTOR LOAD (STA-
TUS01 screen) value is less than the lead chiller percent
capacity plus 15%. See STATUS01 screen or Table 2,
Example 1.
NOTE: Lead chiller percent capacity = 100 – LAG PER-
CENT CAPACITY.
The LAG PERCENT CAPACITY value is configured on
the LEAD/LAG CONFIGURATION screen.
2. The lead chiller chilled water temperature is less than
the WATER/BRINE CONTROL POINT plus 1/2 of the
W ATER/BRINE DEADBAND. The WATER/BRINE DEADBAND parameter is on the SERVICE1 screen. See
Table 2, Example 8.
3. The configured lag stop time (LAG STOP TIMER param-
eter on the LEAD/LAG CONFIGURATION screen) has
elapsed. The lag start time starts when the LEAVING
CHILLED WATER temperature is less than the WATER/
BRINE CONTROL POINT plus 1/2 of the WATER/
BRINE DEADBAND, and the lead chiller COMPRESSOR
MOTOR LOAD is less than the lead chiller percent ca-
pacity plus 15%. The lag stop timer is ignored if the chilled
water temperature reaches 3° F (1.67° C) below the WA TER/
BRINE CONTROL POINT and the lead chiller COMPRESSOR MOTOR LOAD value is less than the lead chiller
percent capacity plus 15%.
39
Page 40
FAULTED CHILLER OPERATION — If the lead chiller
shuts down because of an alarm (*) condition, it stops communicating with the lag and standby chillers. After 30 seconds, the lag chiller becomes the acting lead chiller and starts
and stops the standby chiller, if necessary.
If the lag chiller faults when the lead chiller is also faulted,
the standby chiller reverts to a stand-alone CCN mode of
operation.
If the lead chiller is in an alarm (*) condition (indicated
on the LID ), the RESET
alarm, and the lead chiller is placed in CCN mode, the lead
chiller communicates and monitors the run status of the lag
and standby chillers. If both the lag and standby chillers are
running, the lead chiller does not attempt to start and does
not assume the role of lead chiller until either the lag or standby
chiller shuts down. If only one chiller is running, the lead
chiller waits for a start request from the operating chiller.
When the configured lead chiller starts, it assumes its role of
lead chiller.
LOAD BALANCING — When the LOAD BALANCE OP-TION (LEAD/LAG screen) is enabled, the lead chiller sets
the ACTIVE DEMAND LIMIT in the lag chiller to the lead
chiller’s COMPRESSOR MOTOR LOAD value. This value
has limits of 40% to 100%. When setting the lag chiller AC-TIVE DEMAND LIMIT ,the WATER/BRINECONTROL POINT
is modified to a value of 3° F (1.67° C) less than the lead
chiller’sW ATER/BRINECONTROLPOINT value. If the LOADBALANCE OPTION is disabled, the ACTIVE DEMAND LIMIT
and the WATER/BRINE CONTROL POINT are forced to the
same value as the lead chiller.
AUTO. RESTART AFTER POWER FAILURE— When an
auto. restart condition occurs, each chiller may have a delay
added to the start-up sequence, depending on its lead/lag configuration. The lead chiller does not have a delay. The lag
chiller has a 45-second delay. The standby chiller has a
90-second delay. The delay time is added after the chiller
water flow verification. The PIC controls ensure that the guide
vanes are closed.After the guide vane position is confirmed,
the delay for lag and standby chillers occurs before energizing the oil pump. The normal start-up sequence then continues. The auto. restart delay sequence occurs whether the
chiller is in CCN or LOCAL mode and is intended to stagger the compressor motor start-up times. This helps reduce
the in-rush of demand on the building power system.
softkey is pressed to clear the
Ice Build Control — Ice build control automatically sets
the chilled WATER/BRINE CONTROL POINT of the chiller
from a normal operation set point temperature to a temperature that allows an ice building operation for thermal
storage.
NOTE: For ice build control to operate properly, the PIC
controls must be placed in CCN mode.
The PIC can be configured for ice build operation by chang-
ing entries on the:
• CONFIG screen, accessed from the SERVICE menu
• OCCPC02S screen (ice build time schedule), accessed from
the SCHEDULE menu
• SETPOINT screen, accessed from the SETPOINT menu.
Figures 15 and 16 show how to access each screen.
The ice build time schedule defines the periods during which
the ice build option can be activated, if the ice build option
is enabled. If the ice build time schedule overlaps other schedules, the ice build time schedule takes priority. During an ice
build period, the WATER/BRINE CONTROL POINT is set to
the ICE BUILD SETPOINT (SETPOINT screen) for temperature control.
The ICE BUILD RECYCLE OPTION and ICE BUILDTERMINATION parameters are on the CONFIG screen. The
ice build recycle option can be enabled or disabled from this
screen; the ice build termination value can be set to 0, 1, or
2, depending on the factor that determines termination (temperature, contacts, or both). Ice build termination can occur
when:
• the ENTERING CHILLED WATERtemperature is less than
the ICE BUILD SETPOINT
• the REMOTE CONTACTS INPUT (STATUS01 screen) is
opened based on input from an ice level indicator
• the end of the ice build time schedule has been reached.
ICE BUILD INITIATION — The ice build option is acti-
vated via the ice build time schedule on the OCCPC02S screen.
If the current time is set asan ice build time on the OCCPC02S
screen and the ICE BUILD OPTION on the CONFIG screen
is enabled, then the ice build option is active and the following events automatically take place (unless overridden
by a higher authority CCN device):
1. CHILLER START/STOP is forced to START.
2. The WATER/BRINE CONTROL POINT is forced to the
ICE BUILD SETPOINT.
3. Any force (Auto) on the ACTIVE DEMAND LIMIT is
removed.
NOTE: Items 1-3 (shown above) do not occur if the chiller
is configured and operating as a lag or standby chiller for
lead/lag operation and is actively controlled by a lead chiller.
The lead chiller communicates the ICE BUILD SETPOINT,
desired CHILLER START/STOP state, and ACTIVE DE-MAND LIMIT to the lag or standby chiller as required for
ice build, if configured to do so.
START-UP/RECYCLE OPERATION — If the chiller is not
running when ice build activates, then the PIC checks the
followingparameters,basedontheICEBUILDTERMINATION value, to avoid starting the compressor
unnecessarily:
• if the ICE BUILD TERMINATION parameter is set to 0
(temperature only), and the ENTERING CHILLED WA-
TER temperature is less than or equal to the ICE BUILD
SETPOINT;
• if the ICE BUILD TERMINATION parameter is set to 1
(contacts only) and the remote contacts are open;
• if the ICE BUILD TERMINATION parameter is set to 3
(both temperature and contacts), the ENTERING CHILLED
W ATER temperature is less than or equal to the ICE BUILD
SETPOINT, and the remote contacts are open.
The ICE BUILD RECYCLE OPTION determines whether
or not the PIC goes into aRECYCLE mode. If the ICE BUILDRECYCLE OPTION is set to DSABLE (disable) when the
ice build terminates, the PIC reverts to normal temperature
control duty. If the ICE BUILD RECYCLE OPTION is set to
ENABLE, when ice build terminates, the PIC goes into an
ice build recycle mode and the chilled water pump relay remains energized to keep the chilled water flowing. If the EN-TERING CHILLED W A TER(brine) temperature increases above
the ICE BUILD SETPOINT plus the RECYCLE RESTARTDELTATvalue, the compressor restarts and controls the chilled
water/brine temperature to the ICE BUILD SETPOINT.
40
Page 41
TEMPERATURE CONTROL DURING ICE BUILD
—During ice build, the capacity control algorithm uses the
WATER/BRINE CONTROL POINT minus 5 F (2.7 C) to control the LEAVING CHILLED WATERtemperature. The ECW
CONTROL OPTION (see CONFIG screen), the 20 mA
DEMAND LIMIT, and any temperature reset option are ig-
nored during ice build.
TERMINATION OF ICE BUILD — Ice build termination
occurs under the following conditions:
1. Ice Build Time Schedule — The ice build function terminates when the current time is not designated as an ice
build time period.
2. Entering Chilled Water Temperature — Compressor operation terminates based on temperature if the ICE BUILDTERMINATION parameter on the CONFIG screen is set
to 0 (temperature only) and the ENTERING CHILLED
WATER temperature is less than the ICE BUILD SETPOINT.IftheICE BUILD RECYCLE OPTION is set to
ENABLE, a recycle shutdown occurs and recycle startup is based on a LEAVING CHILLED WATER tempera-
ture greater than the WATER/BRINE CONTROL POINT
plus RECYCLE RESTART DELTA T (see SERVICE1
screen).
3. Remote Contacts/Ice Level Input — Compressor operation terminates when the ICE BUILD TERMINATION parameter is set to 1 (contacts only) and the remote contacts
are open. In this case, the contacts are used for ice level
termination control. The remote contacts can still be opened
and closed to start and stop the chiller if the current time
is not a time designated as an ice build period. If the current time is designated as an ice build period, the contacts
are used to stop the ice build function.
4. Entering Chilled Water Temperature and Remote Contacts — Compressor operation terminates when the ICEBUILD TERMINATION parameter is set to 2 (both temperature and contacts) and the previously described conditions for ENTERING CHILLED WATERtemperature and
remote contacts have occurred.
NOTE: Overriding the CHILLER START/STOP, WATER/BRINE CONTROL POINT, and ACTIVE DEMAND LIMIT
values by CCN devices (with a priority less than 4) during
the ice build period is not possible. However, overriding can
be accomplished with CCN during two-chiller lead/lag
operation.
RETURN TO NON-ICE BUILD OPERATIONS — When
the ice build function terminates, the chiller returns to normal temperature control and start/stop schedule operation. If
the CHILLER START/STOP or WATER/BRINE CONTROLPOINT has been forced (with a priority less than 4), before
the start of ice build operation, then CHILLER START/STOP
and WATER/BRINE CONTROL POINT forces are removed;
that is, under these circumstances, the ice build operation
takes precedence over the force.
Attach to Network Device Control — One of the
selections on the SERVICE menu is ATTACH TO NETWORK DEVICE. See Fig. 12. This table serves the following purposes:
• uploads the occupancy schedule number (OCCPC03S), if
changed, as defined in the CONFIG screen (SCHEDULENUMBER).
• attaches the LID to any CCN device, if the chiller has been
connected to a CCN network. This may include other PIC
controlled chillers.
• uploads changes from a new PSIO or LID module or up-
graded software.
Figure 20 shows the ATTACH TO NETWORK DEVICE
table as it appears on the LID. The LOCAL entry is always
the PSIO module address of the chiller the LID is mounted
on. Whenever the controller identification of the PSIO is
changed, this change is reflected on the bus and address for
the LOCAL DEVICE of the ATTACH TO DEVICE screen
automatically.
NAME DESCRIPTOR
Fig. 20 — Example of Attach to Network
Device Screen
Whenever the ATTACH TO NETWORK DEVICE table
is accessed, no information can be read from the LID on any
device until you attach one of the devices listed on the display. As soon as this screen appears, the LID erases information about the module to which it was attached to make
room for information on another device. Therefore, a CCN
module must be attached when this screen is entered.
To attach to a device listed on this screen, highlight it using the SELECT
softkey. Then press the ATTACH soft-
key.The message, UPLOADINGTABLES, PLEASE WAIT ,
flashes. The LID then uploads the highlighted device or module. If the device address cannot be found, the message, COMMUNICATION FAILURE, appears. The LID then reverts to
the ATTACH TO NETWORK DEVICE screen. Try another
device or check the address of the device that did not attach.
The upload process time for each CCN module is different.
In general, the uploading process takes 3 to 5 minutes.
NOTE: Before leaving the ATTACH TO NETWORK DEVICE screen, select the LOCAL device. Otherwise, the LID
will be unable to display information on the local chiller.
ATTACHINGTO OTHER CCN MODULES — If the chiller
PSIO has been connected to a CCN network or other PIC
controlled chillers through CCN wiring, the LID can be used
to view or change parameters on the other controllers. Other
PIC chillers can be viewed and set points changed (if the
other unit is in CCN control) if desired from this particular
LID module.
To view the other devices, access the ATTACH TO
NETWORK DEVICE table. Move the highlight bar to any
device number. Press the SELECT
softkey to change to the
bus number and address of the module to be viewed. Press
the ENTER
softkey. Press the EXIT softkey to return to
the ATTACH TO NETWORK DEVICE table. If the device
number is not valid, the message, COMMUNICATION FAILURE, displays. Enter a new address number or check the
wiring. If the device is communicating properly, the message, UPLOAD IN PROGRESS, displays and the new device can now be viewed.
Whenever there is a question regarding which CCN device the LID is currently showing, check the device name
descriptor on the upper left hand corner of the LID screen.
See Fig. 20.When the CCN device has been viewed, use the
ATTACH TO NETWORK DEVICE table to attach to the
PSIO that is on the chiller. From the ATTACH TO NETWORK DEVICE table , highlight LOCAL, and press the
SELECT
softkey.Then, press the ATTACH softkey to up-
load the LOCAL device. The PSIO will upload.
41
Page 42
NOTE: The LID does not automatically re-attach to the PSIO
module on the chiller. Access the ATTACH TO NETWORK
DEVICEtable, scrolltoLOCAL,andpress the
ATTACH
softkey to upload the local device. The software
for the local chiller will now be uploaded.
Service Operation — Figure 16 shows an overview of
the service menu.
TO ACCESS THE SERVICE SCREENS
1. On the MENU screen, press the SERVICE
softkeys now correspond to the numerals 1, 2, 3, and 4.
NOTE: The factory-set password is1-1-1-1.Seethe
Input Service Configurations section, page 54, for information on how to change a password.
2. Press the four digits of your password, one at a time. An
asterisk (*) appears as you enter each digit.
If the password is incorrect, an error message is displayed. If this occurs, return to Step 1 and try to access
the SERVICE tables again. If the password is correct, the
softkey labels change to NEXT
SELECT
, and EXIT , and the LID screen displays the
following SERVICE tables:
• Alarm History
• Control Test
• Control Algorithm Status
• Equipment Configuration
• Equipment Service
• Time and Date
• Attach to Network Device
• Log Out of Device
• Controller Identification
• LID Configuration
See Fig. 16 for additional screens and tables available form
the SERVICE tables listed above. Use the EXIT
return to the MENU screen.
TO LOG OFF — Access the LOG OUT OF DEVICE table
from the SERVICEmenu. The LID exits the SERVICEmenu.
T ore-enter the SERVICE menu, you must re-enter your password as described above.
NOTE: To prevent unauthorized persons from accessing the
LID service screens, the LID automatically signs off and
password-protects itself if a key has not been pressed for
15 minutes. The sequence is as follows. Fifteen minutes after the last key is pressed, the default screen displays, the
LID screen light goes out (analogous to a screen saver), and
the LID logs out of the password-protected SERVICE menu.
Other screens and menus, such as the STATUS screen can
be accessed without the password by pressing the appropriate softkeys.
HOLIDAY SCHEDULING (Fig. 21) — The time schedules
may be configured for special operation during holiday periods. When modifying a time period, an ‘‘H’’ at the end of
the days of the week field signifies that the period is applicable to a holiday. (See Fig. 14.)
The broadcast function must be activated for the holidays
configured on the HOLIDEF screen to work properly. Access the BRODEF screen from the EQUIPMENT CONFIGURATION table and set the parameter that activates the
BRODEF function to YES. Note that, when the chiller is
connected to a CCN network, only one chiller or CCN device can be configured to be the broadcast device. The controller that is configured to be the broadcaster is the device
responsible for transmitting holiday, time, and daylightsavings dates throughout the network.
softkey.The
, PREVIOUS ,
softkey to
EF, EX, FA CHLR HOLDY01S CONFIGURATION SELECT
Fig. 21 — Example of Holiday Period Screen
To view or change the holiday periods for up to 18 dif-
ferent holidays, perform the following operation:
1. At the Menu screen, press SERVICE
to access the
SERVICE menu.
2. If not logged on, follow the instructions for entering your
password. See the section, ToAccess the Service Screens,
page 42. Once logged on, pressNEXTuntil
EQUIPMENT CONFIGURATION is highlighted.
3. Press the SELECT softkey to access the EQUIPMENT CONFIGURATION tables.
4. Press NEXT until HOLIDEF is highlighted. This is
the holiday definition table.
5. Press SELECTto access the HOLIDEF screen.
This screen lists 18 holiday tables.
6. Press NEXT to highlight the holiday table that you
wish to view or change. Each table is one holiday pe-
riod, starting on a specific date, and lasting up to 99 days.
42
Page 43
7. Press SELECT to access the holiday table. The LID
screen now shows the holiday start month and day, and
how many days the holiday period will last. See Fig. 24.
8. Press NEXT or PREVIOUS to highlight HOLIDAYSTART MONTH, START DAY,orDURATION.
9. PressSELECTto modify the month, day, or
duration.
10. Press INCREASE or DECREASE to change the selected value.
If the checks are successful, the chilled water/brine pump
relay is energized. Five seconds later, the condenser pump
relay is energized. One minute later the PIC monitors the
chilled water and condenser water flow switches, and waits
until the WATER FLOW VERIFY TIME (operator config-
ured, default 5 minutes) to confirm flow. See the SERVICE1
screen or Table2, Example 8.After flow is verified, the chilled
water/brine temperature is compared to WATER/BRINE CON-TROL POINT plus DEADBAND. If the temperature is less
than or equal to this value, the PIC turns off the condenser
pump relay and goes into a RECYCLE mode.
If the water/brine temperature is high enough, the start-up
sequence continues and checks the guide vane position. If
the guide vanes are more than 6% open, the start-up waits
until the PIC closes the vanes. If the vanes are closed, and
the oil pump pressure is less than 3 psid (21 kPad), the oil
pump relay is then energized. The PIC then waits a minimum of 15 seconds (maximum 5 minutes) to verify that the
compressor oil pressure (OIL PRESSURE on the STATUS01 screen) has reached 15 psid (103 kPad). At the same
time, the PIC waits up to 30 seconds to verify that the gear
oil pressure (GEAR OIL PRESSURE on the STATUS04
screen) has reached 24 psi (166 kPa). After the oil pressures
are verified, the PIC waits 10 seconds, and then the
compressor start relay (1CR) is energized to start the
compressor.
11. Press ENTER to save the changes.
12. Press EXIT to return to the previous menu.
START-UP/SHUTDOWN/
RECYCLE SEQUENCE (Fig. 22)
Local Start-Up —
is initiated by pressing the LOCAL
on the default LID screen. Local start-up can proceed if the
OCCUPIED ? parameter on the STATUS01 table is set to
YES and after the internal 15-minute start-to-start timer and
the stop-to-start inhibit timer have expired.
The CHILLER START/STOP parameter on the STA-
TUS01 screen may be overridden to start, regardless of the
time schedule, in order to start the chiller locally. Also, the
remote contacts may be enabled through the LID and closed
to initiate a start-up.
Whenever the chiller is in LOCAL control mode, the PIC
waits for the current time to coincide with an occupied time
period as configured in the local time schedule (OCCPC01S)
and for the remote contacts to close, if enabled. The PIC
then performs a series of pre-start checks to verify that all
pre-start alerts and safeties are within the limits shown in
Table 3. The RUN STATUS line on the STATUS01 screen
now reads STARTUP.
Local start-up (or a manual start-up)
menu softkey which is
LEGEND
A—START INITIATED — Prestart checks made; chilled water
B—Condenser water pump started (5 seconds after A).
C—Water flows verified (one minute to 5 minutes maximum
E—Compressor motor starts, compressor ontime and service
F—SHUTDOWN INITIATED — Compressor motor stops, guide
G—After the post-lube period, oil and evaporator pumps deener-
O/A — Restart permitted (both inhibit timers expired) (minimum of
pump started.
afterA). Chilledwater temperature checkedagainst controlpoint.
Guide vaneschecked for closure. Oil pumpsstarted; tower fan
control enabled.
300 seconds maximum, after C; for gear, within 30 seconds
after C).
ontime starts, 15-minute inhibit timer starts (10 seconds
after D). Start-in-12 hours counter advances by one.
vanesclose, compressor ontimeand service ontimestops,stopto-start inhibit timer starts.
gized. Post-lube configurable to between one and 5 minutes
after Step F.
15 minutes after E; minimum of 1 minute after F).
Fig. 22 — Control Sequence
43
Page 44
If any of these requirements are not met, the PIC aborts
the start and displays the applicable pre-start mode of failure
on the LID default screen. A pre-start failure does not advance the STARTSIN 12 HOURS counter(STATUS01 screen).
Any failure after the 1CR relay has energized causes a safety
shutdown, advances the STARTS IN 12 HOURS counter by
one, and displays the applicable shutdown status on the LID
display.
Shutdown Sequence — The chiller shuts down if any
of the following occurs:
• the STOP button on the control panel is pressed for at least
one second. The alarm light blinks once to confirm the
stop command.
• a recycle condition is present (see Chilled Water Recycle
Mode section).
• the OCCUPIED ? parameter on the STATUS01 screen reads
NO; that is, the chiller is not scheduled to run at the current time and date.
• the remote contact opens.
• the CHILLER START/STOP status is overridden to STOP
from the CCN network or the LID.
When a stop signal occurs, the shutdown sequence first
stops the compressor by deactivating the start relay.A status
message, SHUTDOWN IN PROGRESS, COMPRESSOR
DEENERGIZED, displays. The guide vanes are then brought
to the closed position. The oil pump relay and the chilled
water/brine pump relay are shut down 60 seconds after the
compressor stops. The condenser water pump shuts down
when the condenser refrigerant temperature is less than the
condenser pressure override minus 5 psi (34 kPa) or is less
than or equal to the entering condenser water temperature
plus 3° F (2° C). The stop-to-start timer now begins to count
down. If the value of the start-to-start timer is still greater
than the value of the start-to-stop timer, then the start-tostart time is displayed on the LID.
There are certain conditions during shutdown that can change
this sequence:
• if the COMPRESSOR MOTOR LOAD (STATUS01 screen)
is greater than 10% after shutdown or the starter contacts
remain energized, the oil pump and chilled water pump
remain energized and the alarm is displayed
• if the ENTERING CONDENSER WA TER(STATUS01 screen)
temperature is greater than 115 F (46 C) at shutdown, the
condenser pump is deenergized after the 1CR compressor
start relay
• if the chiller shuts down due to low refrigerant tempera-
ture, the chilled water pump keeps running until the LEAV-
ING CHILLED WATER temperature is greater than the
WATER/BRINE CONTROL POINT plus 5° F (3° C).
Automatic Soft StopAmps Threshold — The au-
tomatic soft stop amps threshold is an operator configured
value that closes the guide vanes of the compressor automatically when a non-recycle, non-alarm stop signal occurs
before the compressor motor is deenergized.
If the STOP button on the control panel is pressed, the
guide vanes close to a preset amperage percent or until the
guide vane is less than 2% open. The compressor then shuts
off.
If the chiller enters an alarm state or if the compressor
enters a RECYCLE mode, the compressor is deenergized
immediately.
To activate the automatic soft stop amps threshold, access
the SERVICE1screen. Set the SOFT STOP AMPS THRESH-OLD parameter value to the percent of amps at which the
motor will shut down. The default setting is 100% amps (no
soft stop).
When the automatic soft stop amps threshold is being applied, a status message, SHUTDOWN IN PROGRESS, COMPRESSOR UNLOADING, displays.
Chilled Water Recycle Mode — When the compres-
sor is running under light load conditions, the chiller
may cycle off and wait until the load increases to restart
again. This cycling is normal and is known as recycle. A
recycle shutdown is initiated when any of the following
occurs:
• when the chiller is operating under the control of the leav-
ing chilled water temperature (that is, when the ECW CON-TROL OPTION on the CONFIG screen is disabled), the
differencebetween the LEAVINGCHILLED WATER tem-
perature and ENTERING CHILLED WATER temperature
is less than the RECYCLE SHUTDOWN DELTA T (found
in the SERVICE1 table) and the LEAVING CHILLED WA-TER TEMP is below the WA TER/BRINECONTROL POINT,
and the WATER/BRINE CONTROL POINT has not in-
creased in the last 5 minutes
• when the chiller is operating under the control of the en-
tering chilled water temperature (that is, the ECW CON-
TROL OPTION is enabled), the difference between the
ENTERING CHILLED WA TERtemperature and the LEAVING CHILLED WATER temperature is less than the
RECYCLE SHUTDOWN DELTA T (found in the SERV-
ICE1 table) and the ENTERING CHILLED WATER tem-
perature is below the WATER/BRINE CONTROL POINT,
and the WATER/BRINE CONTROL POINT has not in-
creased in the last 5 minutes
• when the LEAVING CHILLED WA TERtemperature is within
3° F (2° C) of the BRINE REFRIG TRIPPOINT.
(See the SERVICE1 screen.)
When the chiller is in RECYCLE mode, the chilled water
pump relay remains energized so that the chilled water temperature can be monitored for increasing load. The recycle
control uses the RECYCLE RESTART DELTA T value
to check when the compressor should be restarted. This is an
operator-configured value that defaults to 5° F (3° C). The
value can be viewed/modified on the SERVICE1 screen. The
compressor restarts when:
• the chiller is operating under leaving chilled water tem-
perature control and the LEAVING CHILLED WATER
temperature is greater than the WATER/BRINE CON-TROL POINT plus the RECYCLE RESTART DELTA T; or
• the chiller is operating under entering chilled water tem-
perature control and the ENTERING CHILLED WATER
temperature is greater than the WATER/BRINE CON-TROL POINT plus the RECYCLE RESTART DELTA T.
Once these conditions are met, the compressor initiates a
start-up, with a normal start-up sequence.
An alert condition may be generated if 5 or more recycles
occur in less than 4 hours. Because excessive recycling can
reduce chiller life, compressor recycling caused by extremely low loads should be reduced. To accomplish this,
use the time schedule to shut the chiller down during periods
of known low load operation or increase the chiller load by
running the fan systems. If the hot gas bypass is installed,
adjust the values to ensure that hot gas is energized during
light load conditions. Increase the RECYCLE RESTARTDELT AT value on the SERVICE1 screen to lengthen the time between restarts.
The chiller should not be operated below design minimum load without a hot gas bypass installed on the
chiller.
44
Page 45
Safety Shutdown — A safety shutdown is identical to
a manual shutdown with the exception that the LID displays
the reason for the shutdown, the alarm light blinks continuously, and the spare alarm contacts are energized. A safety
shutdown requires that the RESET
order to clear the alarm. If the alarm continues, the alarm
light continues to blink. Once the alarm is cleared, the operator must press the CCN
the chiller.
Do not reset starter loads or any other starter safety for
30 seconds after the compressor has stopped. Voltage
output to the compressor start signal is maintained for
10 seconds to determine starter fault.
or LOCAL softkeys to restart
softkey be pressed in
BEFORE INITIAL START-UP
Job Data Required
• list of applicable design temperatures and pressures (product data submittal)
• certified drawings of the chiller
• starting equipment details and wiring diagrams
• diagrams and instructions for special controls or options
• installation instructions
• pumpout unit instructions
Remove Shipping Packaging— Remove any pack-
aging material from the control center, power panel, guide
vane actuator, motor and bearing temperature sensor covers,
and the factory-mounted starter.
MOTOR
The motor may be provided with a shipping brace or
shipping bolt (normally painted yellow) to prevent shaft
movement during transit. It must be removed prior to
operation. See Fig. 24.
Equipment Required
• mechanic’s tools (refrigeration)
• digital volt-ohmmeter (DVM)
• clamp-on ammeter
• electronic leak detector
• absolute pressure manometer or wet-bulb vacuum indicator (Fig. 23)
• 500 v insulation tester (megohmmeter) for compressor motors with nameplate voltage of 600 v or less, or a
5000 v insulation tester for compressor motor rated above
600 v
fer Procedures section, page 63 for: pumpout system preparation, refrigerant transfer, and chiller evacuation.
Refer to the Pumpout and Refrigerant Trans-
Fig. 24 — Shipping Bolt on Open Drive Motor
The motor should be inspected for any temporary, yellow
caution tags with legends that convey information concerning actions necessary before the motor can be safely operated.Any slushing compound on the shaft or other parts must
be removed using a petroleum type solvent. Observe proper
safety precautions.
NOTE: If a shipping bolt was used to restrain the rotor, the
Westinghouse logo must be installed over the hole in the endcover.The logo, the gasket, and hardware can be found with
the parts that have been shipped loose. (Usually these are
packed inside the main power lead box.)
EXTERNALGEAR — Remove any packaging material that
may be on the external gear. Be sure that the breather is in
place and free of any obstructions.
Motor Electrical Connection — All interconnect-
ing wiring for controls and grounding should be in strict compliance with both the (NEC) National Electrical Code and
any local requirements.
The main lead box furnished with the motor has been sized
to provide adequate space for making up connections between the motor lead cables and the incoming power cables.
The bolted joints between the motor lead and the power cables
must be made and insulated in a workman-like manner following the best trade practices.
Fabricated motors are provided with 2 stainless steel grounding pads drilled and tapped with the NEMA (National Electrical Manufacturers Association) 2-hole pattern (two
tapped holes on 13⁄4in. centers). Fan cooled cast frames are
provided with a special grounding bolt. The motor should be
grounded by a proper connection to the electrical system ground.
1
⁄2-13
45
Page 46
The rotation direction of the motor is shown either on the
motor nameplate or on the certified drawing. Information on
the required phase rotation of the incoming power for this
motor may also be found on the nameplate or drawing. If
either is unknown, the correct sequence can be determined
as follows. While the motor is uncoupled from the load, start
the motor and observe the direction of rotation. Allow the
motor to achieve full speed before disconnecting it from the
power source. Refer to Motor Pre-Start Checks (page 51)
for information concerning initial start-up. If the resulting
rotation is incorrect, it can be reversed by interchanging any
2 incoming cables.
Motor Auxiliary Devices — Auxiliary devices such
as resistance temperature detectors, thermocouples, thermoguards, etc., generally terminate on terminal blocks located
in the auxiliary terminal box on the motor. Other devices
may terminate on their own enclosures elsewhere on the motor.Such information can be obtained by referring to the certified drawing. Information regarding terminal designations
and the connection of auxiliary devices can be obtained from
the auxiliary drawings referenced by the outline drawing.
If the motor is provided with internal space heaters, to
ensure proper heater operation, the incoming voltage supplied to them must be exactly as shown by either the nameplate on the motor or the outline drawing. Exercise caution
any time contact is made with the incoming space heater circuit, because space heater voltage is often automatically applied when the motor is shut down.
Open Oil Circuit Valves — Check that the oil filter
isolation valves for both the compressor and external gear
are open by removing the valve cap and checking the valve
stem. (See Scheduled Maintenance, Changing the Oil Filters, page 76.)
Do not use air or oxygen as a means of pressurizing the
chiller. Some mixtures of HFC-134a and air can undergo combustion.
Leak Test the Chiller — Due to regulations regarding
refrigerant emissions and the dif ficulties associated with separating contaminants from refrigerant, Carrier recommends
the following leak test procedures. See Fig. 25 for an outline
of the leak test procedures. Refer to Tables 5A and 5B for
refrigerant pressure/temperature values and to the Pumpout
and Refrigerant Transfer Procedures section, page 63.
1. If the pressure readings are normal for the chiller
condition:
a. Evacuate the nitrogen holding charge from the ves-
sels, if present.
b. Raise the chiller pressure, if necessary, by adding re-
frigerant until the pressure is at an equivalent saturated pressure for the surrounding temperature. Follow
the pumpout procedures in the Pumpout and Refrigerant Transfer Procedures section, page 63.
Never charge liquid refrigerant into the chiller if the pressure in the chiller is less than 35 psig (241 kPa). Charge
as a gas only, with the cooler and condenser pumps running, until this pressure is reached, using PUMPDOWN/
LOCKOUT and TERMINATE LOCKOUT mode on the
PIC. Flashing of liquid refrigerant at low pressures can
cause tube freeze-up and considerable damage.
Tighten All Gasketed Joints and Guide Vane
Shaft Packing —
by the time the chiller arrives at the jobsite. Tighten all gasketed joints and the guide vane shaft packing to ensure a
leak-tight chiller.
NOTE: Check the chiller cold alignment. Refer to Chiller
Alignment in the General Maintenance section, page 71.
Gaskets and packings normally relax
Check Chiller Tightness — Figure 25 outlines the
proper sequence and procedures for leak testing.
17EX chillers may be shipped with the refrigerant contained in the economizer/storage vessel and the oil charge
shipped in the compressor. The cooler/condenser vessels have
a 15 psig (103 kPa) refrigerant charge. Units may also be
ordered with the refrigerant shipped separately, along with a
15 psig (103 kPa) nitrogen-holding charge in each vessel.
To determine if there are any leaks, the chiller should be
charged with refrigerant. Use an electronic leak detector to
check all flanges and solder joints after the chiller is pressurized. If any leaks are detected, follow the leak test
procedure.
If the chiller is spring isolated, keep all springs blocked in
both directions in order to prevent possible piping stress and
damage during the transfer of refrigerant from vessel to vessel during the leak test process or any time refrigerant is transferred. Adjust the springs when the refrigerant is in operating condition and when the water circuits are full.
RefrigerantTracer— Carrier recommends using an en-
vironmentally acceptable refrigerant tracer for leak testing
with an electronic detector.
Ultrasonic leak detectors also can be used if the chiller is
under pressure.
Run the chiller water pumps whenever transferring, removing, or charging refrigerant.
c. Leak test chiller as outlined in Steps3-9.
2. If the pressure readings are abnormal for chiller
conditions:
a. Prepare to leak test chillers shipped with refrigerant
(Step 2h).
b. Check for large leaks by connecting a nitrogen bottle
and raising the pressure to 30 psig (207 kPa). Soap
test all joints. If the test pressure holds for 30 minutes,
prepare to test for small leaks (Steps 2g - h).
c. Plainly mark any leaks that are found.
d. Release the pressure in the system.
e. Repair all leaks.
f. Retest the joints that were repaired.
g. After successfully completing the test for large leaks,
remove as much nitrogen, air, and moisture as pos-
sible, given the fact that small leaks may be present in
the system. This can be accomplished by following
the dehydration procedure, outlined in the Chiller
Dehydration section, page 49.
h. Slowly raise the system pressure to the equivalent satu-
rated pressure for the surrounding temperature but no
less than 35 psig (241 kPa) by adding HFC-134a
refrigerant. Proceed with the test for small leaks
(Steps 3-9).
3. Check the chiller carefully with an electronic leak detector, or soap bubble solution.
4. Leak Determination — If an electronic leak detector indicates a leak, use a soap bubble solution, if possible, to
confirm it. Total all leak rates for the entire chiller. Leakage for the entire chiller at rates greater than the EPA (Environmental Protection Agency) guidelines or local codes
must be repaired. Note the total chiller leak rate on the
start-up report. This leak rate repair is only for new startups. See page 67 in General Maintenance section for recommendations on checking leak rates and leak repairs for
operating chillers.
5. If no leak is found during the initial start-up procedures,
complete the transfer of refrigerant gas (see Pumpout and
Refrigerant Transfer Procedures section, page 63.)
6. If no leak is found after a retest:
a. Transfer the refrigerant to the economizer/storage ves-
sel or other storage tank and perform a standing vacuum
test as outlined in the Standing Vacuum Test section,
this page.
b. If the chiller fails this test, check for large leaks
(Step 2b).
c. Dehydrate the chiller if it passes the standing vacuum
test. Follow the procedure in the Chiller Dehydration
section, below. Charge chiller with refrigerant (see
Pumpout and Refrigerant Transfer Procedures section,
page 63).
7. If a leak is found, pump the refrigerant back into the
economizer/storage vessel or other storage tank.
8. Transfer the refrigerant until the chiller pressure is
18 in. Hg (41 kPa absolute).
9. Repair the leak and repeat the procedure, beginning from
Step 2g to ensure a leak-tight repair. (If chiller is opened
to the atmosphere for an extended period, evacuate it before repeating the leak test.)
StandingVacuumTest— When performing the stand-
ing vacuum test or chiller dehydration, use a manometer or
a wet bulb indicator. Dial gages cannot indicate the small
amount of acceptable leakage during a short period of time.
1. Attach an absolute pressure manometer or wet bulb indicator to the chiller.
2. Evacuate the vessel (see Pumpout and Refrigerant Transfer Procedures section, page 63) to at least 18 in. Hg vac,
ref 30-in. bar (41 kPa), using a vacuum pump or the pumpout unit.
3. Valve off the pump to hold the vacuum and record the
manometer or indicator reading.
4. a. If the leakage rate is less than 0.05 in. Hg (0.17 kPa)
in 24 hours, the chiller is sufficiently tight.
b. If the leakage rate exceeds 0.05 in. Hg (0.17 kPa) in
24 hours, repressurize the vessel and test for leaks. If
refrigerant is available in the other vessel, pressurize
by following Steps 2-10 of Return Chiller To Normal
Operating Conditions section, page 67. If not, use nitrogen and a refrigerant tracer. Raise the vessel pressure in increments until the leak is detected. If refrigerant is used, the maximum gas pressure is approximately
70 psig (483 kPa) at normal ambient temperature.
5. Repair the leak, retest, and proceed with dehydration.
Do not start or megohm-test the compressor motor or
oil pump motor, even for a rotation check, if the chiller
is under dehydration vacuum. Insulation breakdown and
severe damage may result.
Dehydration is readily accomplished at room temperatures. Using a cold trap (Fig. 26) may substantially reduce
the time required to complete the dehydration. The higher
the room temperature, the faster dehydration takes place. At
low room temperatures, a very deep vacuum is required for
boiling off any moisture. If low ambient temperatures are
involved, contact a qualified service representative for the
dehydration techniques required.
Perform dehydration as follows:
1. Connect a high capacity vacuum pump (5 cfm
[0.002 m
3
/s] or larger is recommended) to the refrigerant
charging valve (Fig. 6). Tubingfromthe pump to the chiller
should be as short and as large in diameter as possible to
provide the least resistance to gas flow.
2. Use an absolute pressure manometer or a wet bulb vacuum
indicator to measure the vacuum. Open the shutoff valve
to the vacuum indicator only when taking a reading. Leave
the valve open for 3 minutes to allow the indicator vacuum
to equalize with the chiller vacuum.
3. Open all isolation valves (if present), if the entire chiller
is to be dehydrated.
4. With the chiller ambient temperature at 60 F (15.6 C) or
higher,operate thevacuum pump until the manometer reads
29.8 in. Hg vac, ref 30 in. bar. (0.1 psia)(–100.61 kPa) or
a vacuum indicator reads 35 F (1.7 C). Operate the pump
an additional 2 hours.
Do not apply a greater vacuum than 29.82 in. Hg vac
(757.4 mm Hg) or go below 33 F (0.56 C) on the wet
bulb vacuum indicator. At this temperature/pressure, isolated pockets of moisture can turn into ice. The slow rate
of evaporation (sublimation) of ice at these low temperatures/
pressures greatly increases dehydration time.
5. Valve off the vacuum pump, stop the pump, and record
the instrument reading.
6. After a 2-hour wait, take another instrument reading. If
the reading has not changed, dehydration is complete. If
the reading indicates a vacuum loss, repeat Steps 4 and 5.
7. If the reading continues to change after several attempts,
perform a leak test up to the maximum 180 psig
(1241 kPa) pressure. Locate and repair the leak, and repeat dehydration.
Chiller Dehydration — Dehydration is recommended
if the chiller has been open for a considerable period of time,
if the chiller is known to contain moisture, or if there has
been a complete loss of chiller holding charge or refrigerant
pressure.
Fig. 26 — Dehydration Cold Trap
49
Page 50
Inspect Water Piping — Refer to the piping diagrams
provided in the certified drawings and the piping instructions in the 17EX Installation Instructions manual. Inspect
the piping to the cooler and condenser. Be sure that flow
directions are correct and that all piping specifications have
been met.
Piping systems must be properly vented, with no stress on
the waterbox nozzles and covers. Water flows through the
cooler and condenser must meet job requirements. Measure
the pressure drop across the cooler and condenser.
Water must be within design limits, clean, and treated
to ensure proper chiller performance and reduce the potential of tube damage due to corrosion, scaling, or erosion. Carrier assumes no responsibility for chiller damage resulting from untreated or improperly treated
water.
CheckOptional Pumpout Compressor WaterPiping —
to ensure that the pumpout condenser water has been piped
in. Check for field-supplied shutoff valves and controls as
specified in the job data. Check for refrigerant leaks on fieldinstalled piping.
If the optional pumpout system is installed, check
Check Relief Devices — Be sure that relief devices
have been piped to the outdoors in compliance with the latest edition of ANSI/ASHRAE (American National Standards Institute/American Society of Heating, Refrigeration,
andAir Conditioning Engineers) Standard 15 and applicable
local safety codes. Piping connections must allow for access
to the valve mechanism for periodic inspection and leak
testing.
Relief valves are set to relieve at the 225 psig (1551 kPa)
chiller design pressure.
Inspect Wiring
Do not check voltage supply without proper equipment
and precautions. Serious injury may result. Follow power
company recommendations.
Do not apply any kind of test voltage, including to check
compressor oil pump even for a rotation check, if the
chiller is under a dehydration vacuum. Insulation breakdown and serious damage may result.
1. Examine wiring for conformance to job wiring diagrams and to all applicable electrical codes.
2. Compare the ampere rating on the starter nameplate with
the compressor nameplate. The overload trip amps must
be 108% to 120% of the rated load amps.
3. The starter for a centrifugal compressor motor must contain the components and terminals required for PIC refrigeration control. Check the certified drawings.
4. Check the voltage to the following components and compare to the nameplate values: compressor and gear oil
pump contactors, pumpout compressor starter, and power
panel.
5. Be sure that fused disconnects or circuit breakers have
been supplied for the compressor and gear oil pumps,
power panel, and pumpout unit.
6. Check that all electrical equipment and controls are properly grounded in accordance with job drawings, certified drawings, and all applicable electrical codes.
7. Make sure that the customer’s contractor has verified
the proper operation of the pumps, cooling tower fans,
and associated auxiliary equipment. This includes ensuring that motors are properly lubricated, have proper
electrical supply, and have proper rotation.
8. Tighten all wiring connections to the plugs on the SMM,
8-input, and PSIO modules.
9. Ensure that the voltage selector switch inside the power
panel is switched to the incoming voltage rating, 115 v.
The 230 v alternative is not used.
10. On chillers with free-standing starters, inspect the power
panel to ensure that the contractor has fed the wires into
the bottom of the panel. Wiring into the top of the panel
can cause debris to fall into the contactors. Clean and
inspect the contactors if this has occurred.
Voltage to terminals LL1 and LL2 comes from a control transformer in a starter built to Carrier specifications. Do not connect an outside source of control power
to the compressor motor starter (terminals LL1 and LL2).
An outside power source will produce dangerous voltage at the line side of the starter, because supplying voltage at the transformer secondary terminals produces input level voltage at the transformer primary terminals.
CHECK INSULATION RESISTANCE — Before applying
operating voltage to the motor, whether for checking rotation direction or for actual operation, measure the resistance
of the stator winding insulation.
The test voltage, based on the motor operating voltage, is
as follows:
Operating VoltageDC Test Voltage
0-900500
901- 70001000
7001-145002500
This is particularly important if the motor may have been
exposed to excessive dampness either during transit or while
in storage. A ‘‘megger’’type instrument can be used to measure the insulation resistance. The test voltage should be applied between the entire winding (all winding leads connected
together) and ground for approximately one minute with the
winding at ambient temperature. The recommended minimum insulation resistance is determined as follows:
RM =KV + 1
Where
RM =Recommended minimum insulation resis-
tance in megohms at 104° F (40° C) of the
entire winding.
KV =Rated motor terminal to terminal voltage in
kilovolts (1000 volts = 1 KV).
On a new winding, where the contaminant-causing low
insulation resistance is generally moisture, drying the winding through the proper application of heat normally increases the insulation resistance to an acceptable level.
The following methods are acceptable for applying heat to
a winding:
1. If the motor is equipped with space heaters, energize the
heaters to heat the winding.
50
Page 51
2. Direct current (as from a welder) can be passed through
the winding. The total current should not exceed approximately 50% of the rated full load current. If the motor
has only 3 leads, 2 must be connected together to form
one circuit through the winding. In this case, one phase
carries the full applied current and each of the others carries half of the applied current. If the motor has 6 leads
(3 mains and 3 neutrals), the 3 phases should be connected into one series circuit.
3. Heated air can be blown either directly into the motor or
into a temporary enclosure surrounding the motor. The
source of heated air should preferably be electrical vs.
fueled (such as kerosene), since a malfunction of the fuel
burner could result in carbon entering the motor. Exercise caution when heating the motor with any source of
heat other than self-contained space heaters. Raise the winding temperature at a gradual rate to allow any entrapped
moisture to vaporize and escape without rupturing the insulation. The entire heating cycle should extend over 15
to 20 hours.
Insulation resistance measurements can be made while the
winding is being heated. However, they must be corrected to
104 F (40 C) for evaluation since the actual insulation resistance decreases with increasing temperature. For a new
winding, the insulation resistance approximately halves for
each 18° F (10° C) increase in insulation temperature above
the dew point.
Motor Pre-Start Checks — To prevent damage to the
motor, the following steps must be taken before initial startup:
1. Remove the shaft shipping brace (if supplied).
2. For sleeve bearing motors, the oil reservoir must be filled
with oil to the correct level. Use a rust and oxidation inhibited, turbine grade oil. The viscosity of the oil must be
32 ISO (150 SSU) at 100 F (37.7 C). Oil capacity in each
of the two bearings is 0.6 gal. (2.3 L) per bearing. Use of
Carrier Oil Specification PP16-0 is approved, Carrier Part
No. PP23BZ091 (Mobil DTE Light or Texaco Regal
R+O32).
3. If possible, the shaft should be turned over by hand to
ensure that there is free rotation. On sleeve bearing motors, the shaft should be moved to both extremes of its
end play while it is being rotated, and the oil rings should
be viewed through the viewing ports in the top of the bearing housing to verify free ring rotation.
4. On fan-cooled motors, the area around the external fan
inlet should be checked for loose debris that could be drawn
into the fan during operation.
5. All external, factory-made, bolted joints should be checked
for any looseness that may have occurred in transit. Refer
to Table 6 for recommended bolt torques.
Table 6 — Recommended Motor Fastener
Bolt size1⁄
GradeSAE GR 5
Torque*
Ft-lbs3.5712 31 63 115 180 275 550960
N.m4.7 9.5 16 42 85 156 244 373 746 1302
Tightening Torques
5
3
1
5
4
(
⁄
16
(
⁄
8
(
3
⁄
2
(
⁄
8
(
⁄
4
(
7
⁄8(1( 11⁄3( 11⁄
2
External Gear Pre-Start Checks
There are 2 service valves on the external gear oil lines.
See Fig. 27. Open both valves before starting the chiller.
External gears are shipped without oil. Before start-up,
the gear must be filled with the proper type and amount
of oil.
Before starting the external gear, check for any signs of
mechanical damage, such as damaged piping or accessories.
Then, follow the procedures listed below.
1. Fill the gear and auxiliary sump (if applicable) with oil
to the level indicated next to the sight glass. Fill the gear
to the proper level as follows. Make sure all external piping, gear oil cooler, and pumps are filled before confirming the final oil level. Fill to the oil level indicated next
to the glass sight gage.
Add oil through the gear inspection cover.The inspection
cover must be removed in order to add oil. Take care to
seal the cover when it is replaced.
Never attempt to add or replace oil while the external gear is running unless a vertical sight glass is
in use and the running oil level has been established
and marked on the sight glass. Do not fill beyond
the indicated oil level. Excess lubrication increases
the churning effect and may result in overheating and
subsequent thinning of oil and possible damage to
the rotating components.
2. The viscosity of the oil must be 68 ISO. Use of Carrier
oil, specification PP16-2 is approved (Mobil DTE Heavy
Medium or Texaco Regal UR & 068; Carrier Part No.
PP23BB005).
3. Check that all electrical connections have been made and
are in working order. Check that all accessories are properly mounted.
4. Turn the gear shafts by hand with a spanner wrench to
confirm that there are no obstructions to rotation.
5. Check that all couplings are properly aligned, mounted,
and keyed on the shaft extension.
6. Check that the inspection cover is securely fastened. See
Table 7 for recommended torque values.
7. For units operating in cold ambient temperatures, op-
tional heaters must be turned on and the oil temperature
must be allowed to rise to at least 60 F (16 C) before
start-up.
8. Start the chiller under as light a load as possible. Check
(
for oil leaks, unusual sounds, excessive vibration, and excessive heat. If an operating problem develops, shut down
immediately and correct the problem before restarting.
Bolt size M4 M6 M8 M10 M12 M10 M12 M16
GradeDIN 8.8DIN 12.9
Torque*
*Torque values based upon dry friction.
Ft-lbs281535654592225
N.m2.71120478861125305
51
Page 52
Fig. 27 — External Gear Lubrication System
52
Page 53
Table 7 — Recommended Compressor and
External Gear Fastener Tightening Torques
FASTENER
DIAMETER (in.)
UNCMinimumMaximum
1
⁄
4
5
⁄
16
3
⁄
8
7
⁄
16
1
⁄
2
9
⁄
16
5
⁄
8
3
⁄
4
7
⁄
8
1515(698.3)643(871.9)
11⁄
8
1
1
⁄
4
13⁄
8
11⁄
2
3
1
⁄
4
22750 (3729.0)3437 (4660.6)
1
2
⁄
4
21⁄
2
23⁄
4
*Dry fastener.
NOTE: The torque values listed are to be used for end covers, seal
cages, shaft guards, inspection covers, and housing split line bolts,
unless otherwise specified on the drawing or assembly instructions.
Comfort Network (CCN) communication bus wiring is supplied and installed by the electrical contractor. It consists of
shielded, 3-conductor cable with drain wire.
The system elements are connected to the communication
bus in a daisy chain arrangement. The positive pin of each
system element communication connector must be wired to
the positive pins of the system element on either side of it;
the negative pins must be wired to the negative pins; the signal ground pins must be wired to signal ground pins.
To attach the CCN communication bus wiring, refer to
the certified drawings and wiring diagrams. The wire is inserted into the CCN communications plug (COMM1) on the
PSIO module. This plug also is referred to as J5.
NOTE: Conductors and drain wire must be 20AWG (American Wire Gage) minimum stranded, tinned copper. Individual conductors must be insulated with PVC, PVC/nylon,
vinyl, Teflon,or polyethylene.An aluminum/polyester 100%
foil shield and an outer jacket of PVC, PVC/nylon, chrome
vinyl, or Teflonwith a minimum operating temperature range
of –20 C to 60 C is required. See table below for cables that
meet the requirements.
MANUFACTURERCABLE NO.
Alpha2413 or 5463
AmericanA22503
Belden8772
Columbia02525
When connecting the CCN communication bus to a system element, a color code system for the entire network is
recommended to simplify installation and checkout. The following color code is recommended:
SIGNAL
GroundWHITE2
CCN BUS CONDUCTOR
TYPE
INSULATION COLOR
+RED1
–BLACK3
PSIO MODULE
COMM 1 PLUG (J5) PIN NO.
Check Starter
BE AWARE that certain automatic start arrangements
can engage the starter. Open the disconnect ahead of
the starter in addition to shutting offthe chiller and pump.
Use the instruction and service manual supplied by the
starter manufacturer to verify that the starter has been installed correctly.
The main disconnect on the starter front panel may not
deenergize all internal circuits. Open all internal and remote disconnects before servicing the starter.
Whenever a starter safety trip device activates, wait at least
30 seconds before resetting the safety. The microprocessor
maintains its output to the 1CR relay for 10 seconds after
starter safety shutdown to determine the fault mode of
failure.
MECHANICAL STARTERS
1. Check all field wiring connections for tightness, clear-
ance from moving parts, and correct connection.
2. Check the contactor(s) to be sure they move freely.Check
the mechanical interlock between contactors to ensure that
the 1S and 2M contactors cannot be closed at the same
time. Check all other electro-mechanical devices, such as
relays and timers, for free movement. If the devices do
not move freely, contact the starter manufacturer for replacement components.
3. Some dashpot-type magnetic overload relays must be filled
with oil at the jobsite. If the starter is equipped with devices of this type, remove the fluid cups from these magnetic overload relays. Add dashpot oil to the cups per instructions supplied with the starter.The oil is usually shipped
in a small container attached to the starter frame near the
relays. Use only dashpot oil supplied with the starter. Do
not substitute.
Factory-filled dashpot overload relays need no oil at startup, and solid-state overload relays do not have oil.
4. Reapply starter control power (not main chiller power)to
check the electrical functions. When using a reducedvoltage starter (such as a wye-delta starter) check the transition timer for proper setting. The factory setting is
30 seconds (±5 seconds), timed closing. The timer is adjustable in a range between 0 and 60 seconds, and settings other than the nominal 30 seconds may be chosen
as needed (typically 20 to 30 seconds).
When the timer has been set, check that the starter (with
relay 1CR closed) goes through a complete and proper
start cycle.
SOLID-STATE STARTERS
The solid-state starter is at line voltage when AC power
is connected. Pressing the Stop button does not remove
voltage. Use caution when adjusting the potentiometers
on the equipment.
53
Page 54
1. Check that all wiring connections are properly terminated to the starter.
2. Verify that the ground wire to the starter is installed properly and is of sufficient size.
3. Verify that the motors are properly grounded to the starter .
4. Check that all the relays are properly seated in their
sockets.
5. Verify that the proper AC input voltage is brought into
the starter per the certified drawings.
6. Verify that the initial factory settings (i.e., starting torque,
ramp potentiometers, etc.) are set per the manufacturer’s
instructions.
Compressor Oil Charge — If oil is added, it must
meet Carrier’s specification for centrifugal compressor use
as described in the Scheduled Maintenance, Oil Specifications section (page 77).
Oil may be added through the compressor oil drain and
charging valve (Fig. 2, Item 22) using a pump. The pump
must be able to lift from 0 to 150 psig (0 to 1034 kPa), or
above chiller pressure. However, an oil charging elbow on
the seal-oil return chamber (Fig. 4, Item 3) allows oil to be
added without pumping. The seal oil return pump automatically transfers the oil to the main oil reservoir.
Oil should only be charged or removed when the chiller
is shut down. Maximum oil level is the middle of the upper
sight glass.
Power Up the Controls and Check the Compressor Oil Heater —
ible in the compressor before energizing the controls.A separate
disconnect energizes the oil heater and the control circuit.
When first powered, the LID should display the default screen
within a short period of time.
The oil heater is energized by powering the control circuit. This should be done several hours before start-up to
minimize oil-refrigerant dilution. The oil heater is controlled by the PIC and is powered through a contactor in the
power panel. Starters contain a separate circuit breaker to
power the heater and the control circuit. This arrangement
allows the heater to energize when the main motor circuit
breaker is off for service work or extended shutdowns. The
oil heater relay status can be viewed on the STATUS02screen
on the LID. Oil sump temperature can be viewed on the LID
default screen.
SOFTWARE VERSION — The software version is always
labeled on the PSIO module and on the back side
of the LID module. The software number also appears on
both the CONTROLLER IDENTIFICATIONand LID CONFIGURATION tables. See Fig. 15.
Be sure that an oil level is vis-
Set Up Chiller Control Configuration
Do not operate the chiller before the control configurations have been checked and a Control Test has been
satisfactorily completed. Protection by safety controls
cannot be assumed until all control configurations have
been confirmed.
Input the Design Set Points — To modify the set
points, access the SETPOINT menu. (Press the MENU
SETPOINT
base demand limit and the leaving chilled water, entering
chilled water, and ice build set points. See Fig. 15 for the
SETPOINT menu structure.
The PIC can control a set point according to ether the leaving or entering chilled water temperature. Tochange the type
of control, access the CONFIG screen. Scroll down to highlight ECW CONTROL OPTION. To control the set point ac-
cording to the leaving chilled water, press the DISABLE
softkey; to control the set point according to the entering
chilled water, press the ENABLE
softkeys.) From this menu, you can modify the
softkey.
and
Inputthe Local OccupiedSchedule (OCCPC01S)
To set up the occupied time schedule according to the
—
site requirements, access the SCHEDULE screen on the LID.
(Press the MENU
fault, factory-set schedule is 24 hours, occupied 7 days per
week including holidays. For more information about how
to set up a time schedule, see the Controls section, page 11.
If the ice build option is being used, configure the ice build
schedule (OCCPC02S).
If a CCN system is being installed or if a secondary time
schedule is required, configure the CCN occupancy schedule (OCCPC03S to OCCPC99S). This task is normally done
using a CCN Building Supervisor terminal, but it can also
be done at the LID. For more information on CCN functions, see 17EX CCN supplement. Also, in this manual, see
the section on Occupancy Schedule, page 32.
and SCHEDULE softkeys.) The de-
Input Service Configurations — The following con-
figurations are done from the SERVICE menu:
• password
• input time and date
• LID configuration
• controller identification
• service parameters
• equipment configuration
• automated control test
PASSWORD — You must enter a password whenever you
access the SERVICE screens. The default, factory-set password is1-1-1-1.Thepassword may be changed from the
LID CONFIGURATION screen. To change the password:
1. Press the MENU
password and highlight LID CONFIGURATION. Press
the SELECT
CONFIGURATION screen can be changed: BUS #,
ADDRESS #, BAUD RATE, US IMP/METRIC, and
PASSWORD.
2. Use the ENTER
first digit of the password is highlighted on the LID screen.
3. To change the digit, press theINCREASE
DECREASE
press the ENTER
4. The next digit is highlighted. Change it and the third and
fourth digits in the same way you changed the first.
and SERVICE softkeys. Enter your
softkey. Only the last 5 entries on the LID
softkey to scroll to PASSWORD. The
or
softkey.When you see the digit you want,
softkey.
As you configure the 17EX chiller, write down all configuration settings. A log, such as the one shown on pages
CL-1 to CL-12, is a convenient way to list configuration
values.
54
Page 55
5. After the last digit is changed, the LID goes to the
BUS # parameter. Press the EXIT
softkey to leave the
screen, record your password change, and return to the
SERVICE menu.
BE SURE TO REMEMBER YOUR PASSWORD.
Retain a copy of the password for future reference.
If you forget your password, you will not be able to
access the SERVICE menu unless you install and
download a new PSIO module.
INPUT TIME AND DATE — Access the Time and Date
table on the SERVICE menu. Input the present time of day,
date, and day of the week. HOLIDAY TODAY should only
be configured to YES if the present day is a holiday.
CHANGE THE LID CONFIGURATION IF NECESSARY
— From the LID CONFIGURATION screen, the LID CCN
address, units (English or SI), and password can be changed.
If there is more than one chiller at the jobsite, change the
LID address on each chiller so that each chiller has its own
address. Note and record the new address. Change the screen
to SI units as required, and change the password if desired.
To Change the LID Display From English to Metric Units
— By default, the LID displays information in English units.
To change to metric units:
1. Press the MENU and SERVICE softkeys. Enter your password and highlight LID CONFIGURATION. Press the
SELECT softkey.
2. Use the ENTER softkey to scroll to US IMP/METRIC.
3. Press the softkeys that correspond to the units you want
displayed on the LID (e.g., US or METRIC ).
MODIFY CONTROLLER IDENTIFICATION IF NECESSARY — The PSIO module address can be changed from
the CONTROLLER IDENTIFICATION screen. If there is
more than one chiller at the site, change the controller address for each chiller. Write the new address on the PSIO
module for future reference.
INPUT EQUIPMENT SERVICE PARAMETERS IF NECESSARY— The EQUIPMENT SER VICEtable has 3 screens:
SERVICE1, SERVICE2, and SERVICE3.
Configure SERVICE1 Table —Access the SERVICE1 table
to modify or view the following:
Chilled MediumWater or Brine?
Brine Refrigerant Trippoint Usually 3° F (1.7° C) below design
Surge Limiting or
Hot Gas Bypass Option
Minimum Load Points
(T1/P1)
Full Load Points
(T2/P2)
Motor Rated Load AmpsPer job data
Motor Rated Line VoltagePer job data
Motor Rated Line kWPer job data (if kW meter installed)
Line Frequency50 or 60 Hz
Compressor Starter TypeReduced voltage or full?
Stop-to-Start TimerFollow motor vendor recommenda-
NOTE:Other valuesareleft atthe defaultvalues. Thesemaybe changed
by the operator as required. SERVICE2 and SERVICE3 tables can
be modified by the owner/operator as required.
refrigerant temperature
Is HGBP installed?
Per job data — See Modify Load
Per job data — See Modify Load
tion for time between starts. See
certified prints for correct value.
Points section
Points section
Modify Minimum and Maximum Load Points (DT1/P1;
D T2/P2) If Necessary —These pairs of chiller load points,
located on the SERVICE1table, determine when to limit guide
vane travel or to open the hot gas bypass valve when surge
prevention is needed. These points should be set based on
individual chiller operating conditions.
If, after configuring a value for these points, surge prevention is operating too soon or too late for conditions, these
parameters should be changed by the operator.
Example of configuration:
Chiller operating parameters:
Refrigerant used: HFC-134a
Estimated Minimum Load Conditions:
44 F (6.7 C) LCW
45.5 F (7.5 C) ECW
43 F (6.1 C) Suction Temperature
70 F (21.1 C) Condensing Temperature
Estimated Maximum Load Conditions:
44 F (6.7 C) LCW
54 F (12.2 C) ECW
42 F (5.6 C) Suction Temperature
98 F (36.7 C) Condensing Temperature
Calculate Maximum Load — Tocalculate the maximum load
points, use the design load condition data. If the chiller full
load cooler temperature difference is more than 15° F
(8.3° C), estimate the refrigerant suction and condensing temperatures at this difference. Use the proper saturated pressure and temperature for the particular refrigerant used.
Calculate Minimum Load — Tocalculate the minimum load
conditions, estimate the temperature difference that the cooler
will have at 20% load, then estimate what the suction and
condensing temperatures will be at this point. Use the proper
saturated pressure and temperature for the particular refrigerant used.
If surge prevention occurs too soon or too late, make the
following adjustments:
LOAD
At low loads
(,50%)
At high loads
(.50%)
SURGE PREVENTION SURGE PREVENTION
OCCURS TOO SOONOCCURS TOO LATE
Increase P1 by
10 psid (70 kPad)
Increase P2 by
10 psid (70 kPad)
Decrease P1 by
10 psid (70 kPad)
Decrease P2 by
10 psid (70 kPad)
MODIFY EQUIPMENT CONFIGURATION IF NECESSARY — The EQUIPMENT CONFIGURATION table has
a number of screens to select, view, and/or modify. See
Fig. 16 for the menu structure of this table. Carrier provides
certified drawings that have the configuration values required for specific jobsites. Modify these values only if
requested.
CONFIG Screen Modifications — Change the values on this
screen according to your job data. See certified drawings for
the correct values. Modifications can include:
• chilled water reset
• entering chilled water control (Enable/Disable)
• 4 to 20 mA demand limit
• auto. restart option (Enable/Disable)
• remote contact option (Enable/Disable)
LEAD/LAG Screen Modifications — Change the values on
this screen according to your job data. See certified drawings for specific values. Modifications can include:
• lead/lag selection
• load balance option
• common sensor option
• lag start/stop timers
• standby chiller option
Owner-Modified CCN Tables—The following tables are de-
scribed for reference only. For detailed information on CCN
operations, consult the CCN supplement for your chiller.
• OCCDEFCS Screen Modifications — This table contains
the local and CCN time schedules, which can be modified
here, or on the SCHEDULE screen as described
previously.
• HOLIDEF Screen Modifications — This table configures
the days of the year that holidays are in effect. See the
holiday paragraphs in the Controls section for more
details.
• BRODEF Screen Modifications — This table defines the
outside-air temperature sensor and humidity sensor if one
is to be installed. It also defines the start and end of daylight savings time. Enter the dates for the start and end of
daylight savings, if required for your location. BRODEF
also activates the Broadcast function, which enables the
holiday periods defined on the LID to take effect.
• Other Tables — The ALARMDEF, CONS-DEF, RUNTDEF, and WSMALMDF screens contain information for
use with a CCN system. See the applicable CCN manual
for more information on these screens. These screens can
only be changed from a CCN Building Supervisor
terminal.
CHECKVOLTAGESUPPLY—Access the STATUS 01 screen
and read the LINE VOLTAGE: ACTUAL value. This reading
should be equal to the incoming power to the starter. Use a
voltmeter to check incoming power at the starter power leads.
If the readings are not equal, an adjustment can be made by
selecting the LINE VOLTAGE: ACTUAL parameter and then
increasing or decreasing the value so that the value appearing on the LID is calibrated to match the incoming power
voltage reading. Voltage can be calibrated only between 90
and 100% of the rated line voltage.
PERFORMAN AUTOMATED CONTROLTEST — Check
the safety controls status by performing an automated controls test.Access the CONTROL TEST table from the SERVICE menu. This table has the following screens:
Automated TestAs described above, a complete
PSIO ThermistorsChecks all PSIO thermistors only.
Options ThermistorsChecks all options board thermistors.
TransducersChecks all transducers.
Guide Vane ActuatorChecks the guide vane operation.
PumpsChecks operation of pump output;
Discrete OutputsActivates all on/off outputs, all
Pumpdown/LockoutPumpdown prevents the low
Terminate LockoutCharges refrigerant and enables
FX Gear Oil Pump I/OActivates external gear main oil pump
control test.
either all pumps can be
activated or individual pumps.
Also tests the associated input
such as flow or pressure.
at once or individually.
refrigerant alarm during
evacuation so refrigerant
can be removed from the unit,
locks the compressor off. and
starts the water pumps.
the chiller to run after pumpdown
lockout.
and auxiliary oil pump (if supplied).
Automated Test — Before running this test, be sure that the
compressor is in the OFF mode and the 24-v input to the
SMM is in range (per line voltage percent on STATUS01
screen). Put the compressor in OFF mode by pressing the
STOP pushbutton on the LID.
The automated test starts with a check of the PSIO thermistors and proceeds through the rest of the tests listed in
the table below. The test not only checks readings, such as
temperature and pressure readings, but also lets the operator
know if certain devices, such as pumps or relays, are on or
off and if all outputs and inputs are functioning. It also sets
the refrigerant type.
As each test is executed, the LID display shows which
test is running as well as other pertinent data. At the end of
each test, the LID displays, OK TO CONTINUE? If a test
indicates a problem, error, or device malfunction, the operator can choose to address the problem as the test is being
done or note the problem and proceed to the next test.
NOTE: If during the control test the guide vanes do not open,
check to see that the low pressure alarm is not active. (This
causes the guide vanes to close.)
NOTE: The oil pump test will not energize the oil pump if
cooler pressure is below –5 psig (–35 kPa).
When the test is finished, or the EXIT
softkey is pressed,
the test stops and the CONTROL TEST menu is displayed.
If a specific automated test procedure is not completed, access that test by scrolling to it and selecting it to test the
function when ready. The CONTROL TEST menu is described in more detail in Table 8.
Check Pumpout System Controls and Optional
Pumpout Compressor —
trols include an on/off switch, a 3-amp fuse, the compressor
overloads, an internal thermostat, a compressor contactor, and
a refrigerant high pressure cutout. The high pressure cutout
is factory set to open at 161 psig (1110 kPa) and reset at
130 psig (896 kPa). Check that the water-cooled condenser
has been connected. Loosen the compressor holddown bolts
to allow free spring travel. Open the compressor suction and
discharge service valves. Check that oil is visible in the compressor sight glass. Add oil if necessary.
The pumpout system con-
56
Page 57
Table 8 — Control Test Menu Functions
TESTS TO BEDEVICES TESTED
PERFORMED
1. Automated Tests*Operates the secondthrough seventh
2. PSIO ThermistorsEntering chilled water
3. Options Thermistors Common chilled water supply sensor
4. TransducersEvaporator pressure
5. Guide Vane Actuator Open
6. PumpsAll pumps or individual pumps may be
7. Discrete OutputsAll outputs or individual outputs may
8. Pumpdown/Lockout When using pumpdown/lockout,
9. Terminate LockoutStarts pumps and monitors flows.
10. FX Gear Oil
Pump I/O
*During anyof the tests that arenot automated, an out-of-range read-
ing will have an asterisk (*) next to the reading and a message will
be displayed.
†On open-drive chillers, differential pressure is the only oil pressure
displayed.
tests
Leaving chilled water
Entering condenser water
Leaving condenser water
Discharge temperature
Bearing temperature
Motor winding temperature
Oil sump temperature
Common chilled water return sensor
Remote reset sensor
Temperature sensor — Spare 1
See the Pumpout and Refrigerant Transfer Procedures
(page 63) and Pumpout System Maintenance sections
(page 83) for details on transferring refrigerant, oil specifications, etc.
HighAltitude Locations — Because the chiller is ini-
tially calibrated at sea level, it is necessary to recalibrate the
pressure transducers if the chiller is to be operated at a high
altitude location. Please see the calibration procedure in the
Troubleshooting Guide section.
Charge Refrigerant into Chiller
The transfer, addition, or removal of refrigerant in spring
isolated chillers may place severe stress on external piping if springs have not been blocked in both up and down
directions.
The 17EX chiller may have the refrigerant already charged
in the economizer/storage vessels. If chiller is not shipped
fully charged, refrigerant is shipped separately to conform
with transportation regulations. The 17EX may be ordered
with a nitrogen holding charge of 15 psig (103 kPa). Evacuate the entire chiller, and charge chiller from refrigerant
cylinders.
The full refrigerant charge on the 17EX will vary with
chiller components and design conditions as indicated on the
job data specifications. An approximate charge may be found
in Physical Data and Wiring Schematics section, page 99.
The full chiller charge is printed on the chiller identification
label.
Always operate the condenser and chilled water pumps
during charging operations to prevent water in heat exchanger tubes from freezing.
Use the CONTROLS TEST terminate lockout function to
monitor conditions and start the pumps.
If the chiller has been shipped with a holding charge, add
refrigerant through the refrigerant charging valve (Fig. 6) or
to the pumpout charging connection. First evacuate the nitrogen holding charge from the vessels. Charge the refrigerant as a gas until the system pressure exceeds 35 psig
(141 kPa). After the chiller is beyond this pressure, the refrigerant should be charged as a liquid until all the recommended refrigerant charge has been added.
TRIMMING REFRIGERANT CHARGE — The 17EX is
shipped with the correct charge for the design duty of the
chiller.Trimming the charge can best be accomplished when
the chiller is operating at design load. To trim, check the
temperature differencebetween the leaving chilled water temperature and the cooler refrigerant temperature at full load
design conditions. If necessary, add or remove refrigerant to
bring the temperature difference to design conditions or a
minimum differential.
INITIAL START-UP
Preparation—
1. Power is on to the main starter, oil pump relay (which
energizes both the compressor and gear oil pumps), tower
fan starter, oil heater relay, and the chiller control
center.
2. Cooling tower water is at proper level and at or below
design entering temperature.
Before starting the chiller,check that the:
57
Page 58
3. Chiller is charged with refrigerant and all refrigerant and
all oil valves are in their proper operating position.
4. Gear oil, compressor oil, and motor bearing oil are at the
proper levels in the reservoir sight glasses.
5. Compressor oil reservoir temperature is above 140 F
(60 C) or refrigerant temperature plus 50° F (28° C).
6. Valves in the evaporator and condenser water circuits are
open.
NOTE: If the water pumps are not automatic, make sure
water is circulating properly.
7. Check the starter to be sure it is ready to start and that all
safety circuits have been reset. Be sure to keep the starter
door closed.
Do not permit water or brine that is warmer than 110 F
(43 C) to flow through the cooler or condenser. Refrigerant overpressure may discharge through the relief devices and result in the loss of refrigerant charge.
8. To prevent accidental start-ups, the CHILLER START/STOP parameter is set to STOP at the factory.Access the
STATUS01 screen and scroll to the CHILLER START/
STOP parameter. Press the RELEASE
softkey to enable
the chiller to start.
5. Check the main contactor for proper operation.
6. The PIC will activate an alarm for motor amps not sensed.
Reset this alarm and continue with the initial start-up.
Check Motor Rotation
INITIAL MOTOR START-UP
Initial Uncoupled Start-Up — The initial start-up of the mo-
tor should be made with the motor uncoupled. Verify that oil
has been added to each bearing housing to the correct level.
1. If the motor is equipped with unidirectional fans (refer to
the certified drawing) and verification of rotation direction is required, do the following:
a. Start the motor and observe the rotation direction. See
Fig. 28.
b. Allow the motor to achieve full speed before discon-
necting it from the power source.
c. If the rotation direction must be changed, refer to the
Before Initial Start-Up, Motor Electrical Connection
section, page 45. Otherwise, the motor can be restarted immediately after it has coasted to a stop.
Manual Operation of the Guide Vanes — Manual
operation of the guide vanes helps to establish a steady motor current when calibrating the motor amps value.
To manually operate the guide vanes, override the target
guide vane position (TARGET GUIDE VANE POS param-
eter on the STATUS01 screen). Manual control is also indicated on the default screen on the run status line.
1. Access the STATUS01 screen and look at the TARGET
GUIDE VANE POS parameter. (Refer to Fig. 13). If the
compressor is off, the value reads zero.
2. Move the highlight bar to the TARGET GUIDE VANE
POS parameter and press the SELECT
3. Press ENTER
to override the automatic target. The screen
softkey.
reads a value of zero. The word SUPVSR! flashes to indicate that manual control is in effect. The default screen
also indicates that the guide vanes are in manual control.
4. To return the guide vanes to automatic mode, press the
SELECT
softkey; then press the RELEASE softkey.
After a few seconds, the word SUPVSR! disappears.
Dry Run to Test Start-Up Sequence
1. Disengage the main motor disconnect on the starter front
panel. This should only disconnect the motor power .Power
to the controls, oil pumps, and starter control circuit should
still be energized.
2. Look at the default screen on the LID. The status mes-
sage in the upper left corner should read, MANUALLY
STOPPED. Press the CCN or LOCAL softkey to start.
If MANUALLY STOPPED is not on the default screen
access the SCHEDULE screen and override the schedule
or change the occupied time. Then, press the LOCAL
softkey to begin the start-up sequence.
3. Check that the chilled water and condenser water pumps
have energized.
4. Check that the oil pumps have started and have pressur-
ized the lubrication system. After the oil pumps have run
about 15 seconds, the starter energizes and goes through
its start-up sequence.
Fig. 28 — Correct Motor Rotation
2. After the initial start-up, monitor the bearing temperatures closely. Verify the free rotation of the oil rings on
the sleeve bearings by observing them through the viewing port in the top of the housing. The rate of rise in bearing temperature is more indicative of impending trouble
than the actual temperature. If the rate of rise in temperature is excessive or if the motor exhibits excessive vibration or noise, shut it down immediately and conduct a
thorough investigation to find the cause before operating
the motor again. If the bearing temperatures rise and motor operation appears to be normal, continue operating
the motor until the bearing temperatures stabilize.
The recommended limits on bearing temperature rise over
ambient temperature are listed below:
Sleeve Bearing Temperature
As Measured By
A permanently installed
detector
A temporary detector on top
of the bearing sleeve near the
oil ring
Temperature Rise
Over Ambient
Temperature
72° F (40° C)
63° F (35° C)
NOTE: When operating flood-lubricated sleeve bearings,
the bearing temperature must not be allowed to exceed
185 F (85 C) total temperature.
58
Page 59
Under normal conditions, for the self-lubricating bearing, the rate of temperature rise should be from 20°
to 25° F (11° to 14° C) during the first 10 minutes
after starting up and approximately 40° F (22° C)
over 30 minutes. The rate of bearing temperature rise
is a function of the natural ventilation and operating
conditions.
When the rate of bearing temperature rise is less than
2° F (1.1° C) per half-hour, the bearing temperature
is considered to be stabilized.
If the total bearing temperature exceeds 195 F
(91 C), the motor should be shut down immediately.
3. Any abnormal noise or vibration should be immediately
investigated and corrected. Increased vibration (with the
motor uncoupled from its load) can indicate a change in
balance due to a mechanical failure or loose rotor part, a
stator winding problem, a foundation problem, or a change
in motor alignment.
4. Verify that the magnetic center indicator aligns with the
shaft.
Initial Coupled Start-Up — After initial uncoupled start-up,
take the following steps to ensure safe coupled operation:
1. Follow the procedure stated in the General Maintenance,
ChillerAlignment section to align the motor to the driven
chiller.
2. Prepare the coupling for operation according to the Disc
Coupling Installation andAlignmentinstructions, this page.
Note any match marks on the couplings and assemble accordingly. For sleeve bearing motors, verify that the correct limited end float coupling has been installed. The end
float limits can be found on the certified drawing.
3. Ensure that all personnel are at a safe distance from rotating parts. Start the motor in accordance with instructions supplied with the motor control.
4. If the motor rotor fails to start turning in a second or two,
shut off the power supply immediately. This can result
from:
a. too low a voltage at the motor terminals
b. the load is too much for the rotor to accelerate
c. the load is frozen up mechanically
d. all required electrical connections are not made
e. single-phase power has been applied
f. any combination of the above.
Investigate thoroughly and take corrective action before
attempting a restart.
5. Carefully observe the vibration of the bearing housing and
any abnormal noise generator. Note that coupled motor
vibration may not be the same as uncoupled vibration
amounts. If coupled vibration is excessive, recheck the
mounting and alignment.
6. Carefully observe the bearing temperature rise and the
movement of the oil ring.
If the bearing temperatures rise and motor operation appears normal, operation should continue until the bearing
temperatures stabilize.
7. If possible, check the motor line currents for balance.
Note that each start time an induction motor starts, it is
subjected to the full inrush of current along with heating of
the stator and rotor windings. Each acceleration and repeated start can produce more heat than is produced and dissipated by the motor under full load. The starting duty for
which the motor is designed is shown on a nameplate mounted
on the motor. Do not exceed this amount if long motor life
is expected.
Abnormally low terminal voltage, excessive load torque,
and/or excessive load inertia during motor start-up can cause
lengthened acceleration times during which rotor ventilation
is reduced. This can cause rotor damage or can lead to shortened rotor life.
The temperature rating of the motor is shown on the main
nameplate as a temperature rise above an ambient temperature. If there is a service factor, it is also shown. If the motor
temperature switch opens, investigate the situation before attempting to continue operation.
If the motor is a TEWAC (Totally Enclosed Water-to-Air
Cooled) design, the maximum inlet water temperature and
the water flow rate or gpm (gallons per minute) at the air
cooler must be as shown on the certified drawing. Otherwise, the discharge air temperature from the cooler (actually
the ambient air for the motor as shown by the main nameplate) could be too high for the motor to properly cool.
Disc Coupling Installation andAlignment — Be-
fore installing the disc coupling, inspect it for any signs of
damage during shipment. Check that all parts are available,
as ordered. Cradle or support the coupling components during handling to avoid damage. Wrap the components for protection. Keep flanges free of nicks and burrs. Read all the
instructions and review this procedure before beginning the
actual installation. Some steps apply only to certain types of
couplings (e.g., high speed coupling).
Use only the bolts and nuts supplied by the coupling
manufacturer.
1. Installing the Coupling Hubs (Keyed Mounting).
a. Check the hub bore and shaft for nicks and burrs; dress
if necessary.
b. For taper bores, check the fit of the bore to the shaft.
c. Fit keys precisely to the keyways in the shaft and hub.
Each key should have a tight fit on the sides with a
slight clearance on top. To maintain dynamic balance,
the keys should fill the keyways exactly and not be too
short or too long.
d. Clean the hub bore and shaft.
e. Heat the hub to expand the bore. DO NOT allow the
hub temperature to exceed 600 F (300 C). DO NOT
apply an open flame to any part of the coupling. Car-
rier recommends using an oven to heat the hub.
To avoid the risk of explosion, fire, or damage to
the coupling and equipment and/or injury to personnel, do not use an open flame or oil bath to expand the hub. If heat is used at anytime for installation, DO NOT ALLOW the hub temperature to
exceed 600 F (300 C).
f. Place the hub in the proper position on the shaft. Hold
the hub in place as it cools. For tapered bores, verify
the hub advance and install the shaft retaining nut.
59
Page 60
2. Offset and Angular Alignment — Reverse dial indication
or optical methods of alignment (such as lasers) are recommended. A cold alignment and a hot check (with corrections, if necessary) are required. The hub flange OD
can be used to mount the alignment equipment and is machined to be concentric to the coupling bore. It can be
used as the reference diameter.
3. FinalAssembly — The terminology used to identify parts
and the order of assembly may differ from one coupling
style to another. Follow the instructions that apply to the
coupling you are installing.
High Speed Coupling (Spacer Style):
a. Place the spacer in position between the hub flanges.
Place the disc packs between the flanges on both ends
of the coupling.
b. Insert the disc pack bolt into the reamed hole of the
hub and through the disc pack bushing. See Fig. 29
(compressor side). The flat of the bolt head acts as a
bolt lock with the hub body. Make sure the spacer is
properly indexed for the large flange holes to receive
the bolt ends. Tap the bolts lightly for full engagement
until the heads rest on the hub flange surface. Repeat
for the other bolts.
c. Place the spacing washers and disc pack nuts on the
bolts. Tightenall nuts evenly and in an alternating fashion to the torque specified in Table 9.
d. Place a spacing washer over a disc pack bolt. Insert
the bolt through the large hub flange hole and the disc
pack bushing. See Fig. 29 (gear side). Tap the bolts
lightly for full engagement. Repeat for the other bolts.
e. Place the disc pack nuts on the bolts. Tighten all nuts
evenly and in an alternating fashion to the torque specified in Table 9.
Low Speed Coupling (Close-Coupled Style):
a. Place the disc pack and adapter in position over the
hub body diameter. The reamed holes in the adapter
should be aligned with the large clearance holes in the
hub as in the upper portion of Fig. 30. The large clearance holes in the adapter should be aligned with the
reamed holes in the hub as shown in the lower portion
of Fig. 30.
PACK
DISC
PACK
BOLT
HUB
MOTOR
SIDE
FLANGE BOLTFLANGE NUT
ADAPTERSDISK
SPACING
WASHER
DISC
PACK
NUT
GEAR
SIDE
SHAFT
PREPARATION
(0.19 IN.
[4.83 mm]
NOTES:
1. Compressor shaft should be in the thrust position and gear shaft
shouldbe on geometriccenter whencoupling is positionedas shown.
2. The taper is 1 inch per side for the driven unit bore (compressor
side).
Fig. 29 — Typical High Speed Coupling for 17FX
Compressor/External Gear (Spacer Style)
Table 9 — Disc Pack Nut Tightening Torques
Coupling
Size
2041/2-2055754560
3045/8-1811515590120
*Light machine oil.
Nut
Size
Tightening
ft-lb
Torque
(dry)
N-m
Tightening
ft-lb
Torque
(lubed)*
N-M
NOTE: Motor rotor should be positioned on the mechanical center
and gear shaft should be on geometric center when coupling is positioned as shown.
Fig. 30 — Typical Low Speed Coupling for 17FX
Compressor/External Gear (Close Coupled)
b. Loosely assemble the disc pack bolts, nuts, and spac-
ing washers. Half of the bolts attach the adapter to the
disc pack. Refer to Fig. 30. These bolts are interspersed by bolts that attach the disc pack to the hub.
c. Tighten all nuts evenly and in an alternating fashion to
the torque specified in Table 9.
d. Bring the driving and driven equipment together until
the flanges of the adapters just begin to touch. If there
is a gap between the flanges at any point, adjust the
axial position of the equipment until the amount of
gap is cut in half to minimize the amount of axial misalignment.
e. Rotate the equipment shafts until the flange holes are
aligned.
f. Bolt the flanges together using the flange bolts and nuts.
See Fig. 30. Tighten all flange nuts evenly and in a
alternating fashion to the torque specified in Table 10.
Table 10 — Flange Nut Tightening Torques
(Low Speed Couplings Only)
Coupling
Size
3045/16-2420271824
*Light machine oil.
Nut
Size
Tightening
ft-lb
Torque
(dry)
N-m
Tightening
ft-lb
Torque
(lubed)*
N-M
60
Page 61
4. General Recommendations
a. Both disc couplings are designed to operate for ex-
tended periods without the need for lubrication or maintenance. Visual inspection of the disc packs is enough
to assess the operational condition of the coupling.
b. All machinery should be monitored to detect unusual
or changing vibration levels. Both couplings, under normal operating conditions, have no wearing parts and
retain their original balance quality.Any change in vibration levels should be investigated, and remedial action should be taken immediately.
5. Removal
a. Disassemble the coupling in the reverse order of the
applicable assembly procedure.
b. Keyed couplings — Install a puller on the hub using
the tapped holes provided in the hub face. Pull the hub
off the shaft.
IMPORTANT INFORMATION:
Coupling guards protect personnel. ALL COUPLINGS
MUST BE COVERED WITH A GUARD ACCORDING TO OSHA (Occupational Safety and Health
Administration) REQUIREMENTS. Safety guards are
included with this product and must be installed at all
times.
1. Recheck alignment after all foundation bolts and mechanical connections are tightened.
2. Make sure all fasteners are properly installed and
tightened.
3. Take the time to double check your work.
4. Only authorized disc coupling manufacturer replacement
parts are to be used.
5. Call the disc coupling manufacturer for any clarifications
or questions.
The self-locking nuts on the disc pack bolts should
be replaced after they have been assembled and removed from the bolts 5 times.
Check Oil Pressure and Compressor Stop
1. When the motor is up to full speed, note the differential
compressor oil pressure reading on the LID default screen.
It should be between 18 and 30 psid (124 to 206 kPad).
2. Press the Stop button and listen for any unusual sounds
from the compressor as it coasts to a stop.
Calibrate Motor Current Demand Setting
1. Make sure that the MOTOR RATED LOAD AMPS parameter on the SERVICE1 screen has been configured.
Place an ammeter on the line that passes through the motor load current transfer on the motor side of the power
factor correction capacitors (if provided).
2. Start the compressor and establish a steady motor current
value between 70% and 100% RLA by manually overriding the guide vane target value (TARGET GUIDE VANEPOS parameter on the STATUS01 screen) and setting the
chilled water set point (WATER/BRINE SETPOINT on the
STATUS01 screen) to a low value. Do not exceed 105%
of the nameplate RLA (rated load amps).
3. When a steady motor current value in the desired range
is reached, compare the MOTOR RATED LOAD AMPS
value on the STATUS01 screen to the actual amps shown
on the ammeter on the starter. Adjust the amps value on
the STATUS01 screen to match the actual value on the
starter ammeter, if there is a difference. Highlight the amps
value; then, press the SELECT
INCREASE
to that indicated on the ammeter. Press ENTER
the values are equal.
4. Release the target guide vane position to automatic mode.
See the section on Manual Operation of the Guide Vanes,
page 58, for instructions on how to do this.
or DECREASE softkey to bring the value
softkey. Press the
when
To Prevent Accidental Start-Up— The PIC can be
configured so that starting the unit is more difficult than just
pressing the LOCAL
ice or whenever necessary. Access the STATUS01
screen, and highlight the CHILLER START/STOP param-
eter. Override the value by pressing SELECT
STOP
pears. When attempting to restart the chiller, remember to
release the override. Access the STATUS01 screen and highlight CHILLER START/STOP. The 3 softkeys represent 3
choices:
• START - forces the chiller ON.
• STOP - forces the chiller OFF
• RELEASE - puts the chiller under remote or schedule
control.
RELEASE
additional information, see Local Start-Up, page 43.
mand is in effect.
and ENTER softkeys. The word SUPVSR ap-
To return the chiller to normal control, press the
softkey; then, press the ENTER softkey. For
The default LID screen message indicates which com-
or CCN softkeys during chiller serv-
and then the
Hot Alignment Check — The operating temperatures
of various chiller components can affect the alignment of the
compressor with the heat exchangers, gear, and driver. When
all the chiller components have reached operating temperature (after running at nearly full load for 4 to 8 hours), make
a hot alignment check.
Using proper equipment and procedures, make the hot alignment check with either assembled or disassembled couplings. The procedures are detailed in the General Maintenance section, page 67.
A clamping tool, Part No. TS-170, is available for checking alignment without disassembling the couplings. Check
with your local Carrier representative.
Never operate the compressor or drive with the coupling guards removed. Serious injury can result from
contact with rotating equipment.
Doweling — The size, quantity, and location of dowels
vary considerably with type and arrangement of gear and
drive. Check your job data for specific doweling instructions. Typical doweling practices are described in the General Maintenance section.
Check Chiller Operating Condition — Check to
be sure that chiller temperatures, pressures, water flows, and
oil and refrigerant levels indicate that the system is functioning properly.
61
Page 62
Instruct the Operator — Check to be sure that the op-
erator(s) understands all operating and maintenance procedures. Point out the various chiller parts and explain their
function as part of the complete system.
COOLER-CONDENSER — Relief devices, temperature sensor locations, pressure transducer locations, Schrader fittings, waterboxes and tubes, and vents and drains.
PUMPOUT SYSTEM — Transfer valves and pumpout system, refrigerant charging and pumpdown procedure, lubrication, and relief devices.
COMPRESSORASSEMBLY— Guide vane actuator, transmission, oil cooling system, temperature and pressure sensors, oil sight glasses, integral oil pump, isolatable oil filter,
extra oil and motor temperature sensors, synthetic oil, and
compressor serviceability.
COMPRESSOR LUBRICATION SYSTEM — Oil pump,
cooler filter, oil heater, oil charge and specification, operating and shutdown oil level, temperature and pressure, oil charging connections, and seal oil chambers.
EXTERNALGEAR LUBRICATION SYSTEM — Oil pump,
cooler/filter,oil charge and specification, operating and shutdown oil level, temperature and pressure, and oil charging
procedures.
CONTROL SYSTEM — CCN and local start, reset, menu,
softkey functions, LID operation, occupancy schedule, set
points, safety controls, and auxiliary and optional controls.
AUXILIARYEQUIPMENT — Starters and disconnects, separate electrical sources, pumps, and cooling tower.
CHILLER CYCLES — Refrigerant, motor cooling, lubrication, and oil reclaim cycles.
MAINTENANCE — Scheduled, routine, and extended shutdowns; importance of a log sheet, water treatment, tube cleaning, and maintaining a leak-free chiller.
CHECK OPERATOR KNOWLEDGE — Start, stop,and shutdown procedures, safety and operating controls, refrigerant
and oil charging, and job safety.
THIS MANUAL — Be sure that the operator is familiar with
the contents of this manual.
OPERATING INSTRUCTIONS
Operator Duties
1. Become familiar withchiller refrigeration and related equipment before operating the chiller.
2. Prepare the system for start-up, start and stop the chiller,
and place the system in a shutdown condition.
3. Maintain a log of operating conditions and document any
abnormal readings.
4. Inspect the equipment, make routine adjustments, and perform a controls test. Maintain the proper oil and refrigerant levels.
5. Protect the system from damage during shutdown
periods.
6. Maintain the set point, time schedules, and other PIC
functions.
Prepare the Chillerfor Start-Up — Follow the steps
described in the Initial Start-Up section, page 57.
Starting the Chiller
1. Start the water pumps if they are not automatic.
2. On the LID default screen, press the LOCAL
CCN
softkey to start the system. If the schedule indicates that the current time and date have been established
as a run time and date (a condition referred to as ‘‘occupied’’) and the 3- and 15-minute start timers have expired, the start sequence will start. Follow the procedure
described in the Start-Up/Shutdown/Recycle Sequence
section, page 43.
or
Check the Running System — After the compres-
sor starts, monitor the LID display and observe the parameters for normal operating conditions:
1. The oil reservoir temperature should be above 150 F
(66 C) or refrigerant temperature plus 70° F (38° C) during shutdown and above 125 F (52 C) during compressor
operation.
2. The bearing oil temperature (BEARING TEMPERA-TURE on the STATUS01 screen) should be 150 to 200 F
(65 to 93 C). If the bearing oil temperature reads more
than 210 F (99 C) with the oil pump running, stop the
chiller and determine the cause of the high temperature.
Do not restart the chiller until corrected.
3. The oil level should be visible in the lower sight glass
when the compressor is running. At shutdown, oil level
should be halfway in the lower sight glass.
4. The oil pressure should be between 18 and 30 psid (124
to 207 kPad) differential, as seen on the LID default
screen. Typically the reading will be 18 to 25 psid (124
to 172 kPad) at initial start-up.
5. The condenser pressure and temperature vary withthechiller
design conditions. Typically the pressure ranges between
57 and 135 psig (393 and 930 kPa) with a corresponding
temperature range of 60 to 105 F (15 to 41 C) for R-134a.
The condenser entering water temperature should be controlled to remain below the specified design entering water temperature to save on compressor kilowatt requirements. The leaving condenser water temperature should
be at least 20° F (11° C) above leaving chilled water
temperature.
6. Cooler pressure and temperature also vary with the design conditions. Typical cooler pressure ranges between
30 and 40 psig (206 and 275 kPa); temperature ranges
between 34 and 45 F (1 and 8 C) for R-134a).
7. The compressor may operate at full capacity for a short
time after the pulldown ramping has ended, even though
the building load is small. The active electrical demand
setting can be overridden to limit the compressor IkW, or
the pulldown rate can be decreased to avoid a high demand charge for the short period of high demand
operation. Pulldown rate can be based on kW rate (LOADPULLDOWN %/MIN) or temperature rate (TEMP PULLDOWN DEG/MIN) These parameters may be accessed
on the CONFIG screen (see Table 2, Example 6).
8. The oil pump is energized once every 12 hours during
shutdown periods to ensure that the shaft seal is filled
with oil.
Stopping the Chiller
1. The occupancy schedule starts and stops the chiller automatically once the time schedule is set up.
2. Pressing the Stop button on the control panel for one second causes the alarm light to blink once to confirm that
the button has been pressed. Then, the compressor follows the normal shutdown sequence as described in the
Controls section. The chiller is now in the OFF mode.
The chiller will not restart until theCCN
LOCAL
softkey is pressed.
or
62
Page 63
NOTE: If the chiller fails to stop, in addition to action that
the PIC initiates, the operator should close the guide vanes
by overriding the guide vane target to zero (to reduce chiller
load) and then by opening the main disconnect. Do not attempt to stop the chiller by opening an isolating knife switch.
High intensity arcing may occur. Do not restart the chiller
until the problem is diagnosed and corrected.
After Limited Shutdown — No special preparations
should be necessary. Follow the regular preliminary checks
and starting procedures. Control power must be maintained
in order to keep the oil temperature hot and all control safeties operational. The oil pump operates occasionally to keep
the contact seal filled with oil to prevent refrigerant loss.
ExtendedShutdown — The refrigerant should be trans-
ferred into the economizer/storage vessel (see Pumpout and
Refrigerant Transfer Procedures, this page) in order to reduce chiller pressure and the possibility of leaks. Maintain
a holding charge of 5 to 10 lbs (2.27 to 4.5 kg) of refrigerant
within the cooler/condenser/compressor sections, to prevent
air from leaking into the chiller.
If freezing temperatures are likely to occur in the chiller
area, drain the chilled water, condenser water, and the pumpout condenser water circuits to avoid freeze-up. Keep the
waterbox drains open.
Leave the oil charge in the chiller with the oil heater and
controls energized to maintain the minimum oil reservoir
temperature.
After Extended Shutdown — Be sure that the water
system drains are closed. It may be advisable to flush the
water circuits to remove any soft rust which may have formed.
This is a good time to brush the tubes if necessary.
Check the cooler pressure on the LID default screen, and
compare it to the original holding charge that was left in the
chiller. If (after adjusting for ambient temperature changes)
any loss in pressure is indicated, check for refrigerant leaks.
See the Check Chiller Tightness section, page 46.
Recharge the chiller by transferring refrigerant from
the economizer/storage vessel. Follow the Pumpout and Refrigerant Transfer Procedures section, this page. Observe
freeze-up precautions.
Carefully make all regular preliminary and running system checks. Perform a controls test before start-up. If the
compressor oil level appears abnormally high, the oil may
have absorbed refrigerant. Make sure that the oil temperature is above 150 F (66 C) or above the cooler refrigerant
temperature plus 70° F (39° C).
Cold Weather Operation — When the entering con-
denser water temperature is very low, the PIC can automatically cycle the cooling tower fans off to keep the temperature up. Provide a way to control the condenser water
temperature to the chiller either by arranging a tower bypass
piping system and/or adding a tower water temperature control system.
Manual Guide Vane Operation — It is possible to
operate the guide vane manually in order to check control
operations or control the guide vanes in an emergency. This
is done by overriding the target guide vane position. Access
the STATUS01 screen on the LID and highlight TARGETGUIDE VANE POS. To control the position, enter the desired percentage of guide vane opening. Zero percent is fully
closed; 100% is fully open. To release the guide vanes to
automatic operation, press the RELEASE
NOTE: Manual guide vane control allows the operator to
manipulate the guide vane position and override the pulldown rate during start-up. However, motor current above the
electrical demand setting, capacity overrides, and chilled water temperature below the control point will override manual
softkey.
guide vane control and close the guide vanes, if necessary.
For descriptions of capacity overrides and set points, see the
Controls section.
Refrigeration Log — A refrigeration log, such as the
one shown in Fig. 31, is a convenient way to track routine
inspection and maintenance and provides a continuous record
of chiller performance. It is an aid in scheduling routine maintenance and in diagnosing chiller problems.
Keep a record of the chiller pressures, temperatures, and
liquid levels on a log similar to Fig. 31. It is possible to automatically record PIC data by using CCN devices such as
the Data Collection module and a Building Supervisor terminal. Contact your Carrier representative for more
information.
PUMPOUT AND REFRIGERANT TRANSFER
PROCEDURES
Preparation —
an optional pumpout compressor.The refrigerant can be pumped
for service work to either the cooler/condenser/compressor
sections or the economizer/storage vessel by using the pumpout system. The following procedures describe how to transfer refrigerant from vessel to vessel and perform chiller
evacuations.
To prevent tube freeze-up, always be sure that the condenser and cooler water pumps are operating whenever
charging, transferring, or removing refrigerant from the
chiller.
If the chiller water pumps are controlled by the PIC, access the CONTROL TEST table on the LID and use the
PUMPDOWN/LOCKOUT screen or TERMINATE LOCKOUT screen to perform the functions described below. If the
chiller water pumps are not controlled by the PIC, they must
be turned on and off manually.
When performing pumpout, do not leave the compressor unattended for long periods of time or loss of compressor oil may result. Periodically check oil level.
The 17EX may come equipped with
Operating the Optional Pumpout Compressor
1. Be sure that the suction and the discharge service valves
on the optional pumpout compressor are open (back seated)
during operation. Figure 32 shows the location of these
valves (valves 2, 3, 4, 5, and 8). Rotate the valve stem
fully counterclockwise to open. Front seating the valve
closes the refrigerant line and opens the gage port to compressor pressure.
2. Make sure that the compressor holddown bolts have been
loosened to allow free spring travel.
3. Open therefrigerant inlet valve on the pumpout compressor.
4. Oil should be visible in the compressor sight glass under
all operating conditions and during shutdown. If oil is
low, add oil as described under Pumpout System Maintenance section, page 83. The pumpout unit control wiring schematic is detailed in Fig. 33. The Optional Pumpout System is detailed in Fig. 34.
READING REFRIGERANT PRESSURES during pumpout
or leak testing:
1. The LID display on the chiller control center is suitable
for determining refrigerant-side pressures and low (soft)
vacuum. To measure evacuation or dehydration pressures, use a quality vacuum indicator or manometer to
ensure the desired range and accuracy.This can be placed
on the Schrader connections on each vessel by removing
the pressure transducer.
REC. 1REC. 2REC. 3REC. 4REC. 5REC. 6REC. 7REC. 8REC. 9
TIME
DATE
OPERATOR INITIALS
COOLER
Refrigerant
Pressure
Temperature
Water
Pressure In
Pressure Out
Pressure GPM
Temperature In
Temperature Out
CONDENSER
Refrigerant
Pressure
Temperature
Water
Pressure In
Pressure Out
Pressure GPM
Temperature In
Temperature Out
COMPRESSOR
Bearing Temperature
Oil
Pressure Differential
Temperature (Reservoir)
Level
Motor
FLA
Amps (or Vane Position)
EXTERNAL GEAR
Bearing Temperature
Oil
Pressure Differential
Temperature (Reservoir)
Level
Motor
FLA
Aps (or Vane Position
REMARKS: On an attached sheet, Indicate shutdowns on safety controls, repairs made, and oil or refrigerant added or removed. Include amounts.
Include time, date, operator initials for each remark.
Fig. 31 — Refrigeration Log
64
Page 65
NOTE: Locationof pumpout compressor may varydepending on machine arrangement.
9
DRIVE END
COOLER
ISOLATION
VALVE
CHILLER
11
7
CHARGER VALVE
REAR VIEW
10
COMPRESSOR END
Fig. 32 — Pumpout Unit Location and Valve Number Locations
65
Page 66
COMPRESSOR MOTOR
HzPhVoltsMax. RLA
5034004.7
329810.9
32309.5
60
34604.7
33753.8
Fig. 33 — Pumpout Unit Wiring Schematic
LEGEND
1—Compressor Motor
2—Control Circuit
C—Contactor
OL— Compressor Overload
RLA— Rated Load Amps
T’stat — Internal Thermostat
Circuit Disconnect
Disconnect
Compressor Terminal
Contactor Terminal
Overload Terminal
Pumpout Unit Terminal
VENT VALVE
VALVES
VALVES
CONDENSER
WATER
CONNECTIONS
(FIELD PIPING)
CONDENSER
DISCHARGE VALVE
CONTROL BOX
(WIRING BY
CONTRACTOR)
COMPRESSOR
Fig. 34 — Optional Pumpout Compressor
2. To determine economizer/storage vessel pressure, attach
a 30 in.-0-400 psi (-101-0-2760 kPa) gage to the vessel.
3. Refer to Fig. 32 for valve locations and numbers.
Transfer, addition, or removal of refrigerant in springisolated chillers may place severe stress on external piping if springs have not been blocked in both up and down
directions.
Transferring Refrigerant into the Economizer/
Storage Vessel —
moving refrigerant from the cooler/condenser/compressor sections into the economizer/storage vessel. This is normally
done to prepare for service work on the cooler, condenser, or
the compressor components or for long-term chiller
shutdown.
These steps describe the method of
1. Isolate and push refrigerant into the economizer/storage
vessel with the pumpout compressor.
a. Valve positions: (Blank spaces indicate open valves).
VALVE1234567891011
CONDITIONCCCC C C
b. Turn off the chiller water pumps and pumpout con-
denser water.
c. Turn on pumpout compressor to push liquid out of the
cooler/condenser/compressor section.
d. When all liquid has been pushed into the economizer/
storage vessel, close the cooler isolation valve 7.
e. Access the CONTROL TEST table on the LID. Select
the PUMPDOWN/LOCKOUT screen. From this screen,
turn on the chiller water pumps and view the chiller
pressures.
f. Turn off pumpout compressor.
2. Evacuate refrigerant gas from the cooler/condenser/
compressor vessel.
a. Valve positions: close valves 2 and 5, open valves 3
and 4.
VALVE12345678910 11
CONDITIONCCCCCC C
b. Turn on the pumpout condenser water.
c. Run the pumpout compressor until the suction reaches
15 in. Hg (50 kPa abs). Monitor pressures on the LID
and on the refrigerant gages.
d. Close valve 1.
e. Turn off pumpout compressor.
f. Close valves 3, 4, and 6. (All valves are now closed.)
g. Turn off pumpout condenser water.
h. Use the PUMPDOWN LOCKOUT screen on the LID
to turn off the chiller water pumps and to lock out the
chiller compressor from operation.
66
Page 67
Transferring Refrigerant into the Cooler/
Condenser/CompressorSection —
scribe how to transfer refrigerant from the economizer/
storage vessel into the cooler/condenser/compressor section.
This is normally done to prepare for service work on the
economizer/storage vessel.
1. Isolate and push refrigerant into the cooler/condenser/
compressor section:
a. Valve positions:
VALVE1234567891011
CONDITIONCCCCCC
b. Turn off chiller water pumps and pumpout condenser
water.
c. Turn on the pumpout compressor to push refrigerant
out of the economizer/storage vessel.
d. When all liquid refrigerant is out of the economizer/
storage vessel, close the cooler isolation valve 7.
e. Turn off the pumpout compressor.
2. Evacuate refrigerant from the economizer/storage vessel.
a. Access the CONTROL TEST table on the LID. Select
the PUMPDOWN LOCKOUT screen. From this screen,
turn on the chiller water pumps and monitor vessel
pressures.
b. Valve positions: Close valves 3 and 4, open valves 2
and 5.
VALVE12345678910 11
CONDITIONCCCCC C C
c. Turn on the pumpout condenser water.
d. Run the pumpout compressor until the suction reaches
15 in. Hg (50 kPa abs). Monitor pressures on the LID
and on refrigerant gages.
e. Close valve 6.
f. Turn off the pumpout compressor.
g. Close valves 1, 2, and 5 (all valves are now closed).
h. Turn off the pumpout condenser water.
i. From the CONTROL TEST table on the LID, turn off
the chiller water pumps and lock out the chiller compressor from operation.
These steps de-
Return Chiller to Normal Operating Conditions
1. Be sure that the vessel that was opened has been evacuated and dehydrated.
2. Access the CONTROL TEST table. From this table, select the TERMINATE LOCKOUT function to view the
vessel pressures and to turn on chiller water pumps.
3. Open valves 1, 3, and 6.
VALVE1234567891011
CONDITIONCCCCCCCC
4. Slowly open valve 5, gradually increasing pressure
in the evacuated vessel to 35 psig (141 kPa)
for HFC-134a. Feed refrigerant slowly to prevent
freeze-up.
5. Perform a leak test at 35 psig (141 kPa).
6. Open valve 5 fully. Let the vessel pressures equalize.
VALVE12345678910 11
CONDITIONCCCCCC C
7. Open valves 9 and 10.
8. Open valve 7 to equalize liquid refrigerant levels.
9. Close valves 1, 3, 5, and 6.
VALVE1234567891011
CONDITION CCCCCCCC
10. Continue to use the TERMINATE/LOCKOUT function
on the LID to turn off water pumps and enable the compressor to operate.
GENERAL MAINTENANCE
Refrigerant Properties —
the standard refrigerant in the 17EX.At normal atmospheric
pressure, HFC-134a boils at −14 F (−25 C) and must, therefore, be kept in pressurized containers or storage tanks. The
refrigerant is practically odorless when mixed with air. This
refrigerant is non-combustible at atmospheric pressure. Read
the Material Safety Data Sheet (MSDS) and the latest ASHRAE
Safety Guide for Mechanical Refrigeration to learn more about
safe handling of this refrigerant.
Refrigerant HFC-134a will dissolve oil and some nonmetallic materials, dry the skin, and, in heavy concentrations, may displace enough oxygen to cause asphyxiation. When handling this refrigerant, protect the hands
and eyes and avoid breathing fumes.
Refrigerant HFC-134a is
Adding Refrigerant — Follow the procedures de-
scribed in Charge Refrigerant into Chiller section, page 57.
Use the PUMPDOWN LOCKOUT function on the CONTROL TEST table to turn on the chiller water pumps
and lock out the compressor when transferring refrigerant. Liquid refrigerant may flash into a gas and cause
possible freeze-up when the chiller pressure is below
30 psig (207 kPa) for HFC-134a. If the water pumps are
not controlled by the PIC, they must be controlled
manually.
Removing Refrigerant — When the optional pump-
out system is used, the 17EX refrigerant charge may be transferred into the economizer/storage vessel or another storage
vessel. Follow procedures in the Pumpout and Refrigerant
Transfer Procedures section when removing or transferring
refrigerant.
Adjusting the Refrigerant Charge — If it is nec-
essary to add or remove refrigerant to improve chiller performance, follow theproceduresundertheTrimming Refrigerant
Charge section.
Refrigerant Leak Testing — Because HFC-134a is
above atmospheric pressure at room temperature, leak testing can be performed with refrigerant in the chiller. Use an
electronic detector, soap bubble solution, or ultra-sonic leak
detector. To keep false readings to a minimum, be sure that
the room is well ventilated and free from concentration of
refrigerant. Before making any necessary repairs to a leak,
transfer all refrigerant from the leaking vessel.
LeakRate — The ASHRAE recommendation is that chill-
ers should be immediately taken off line and repaired if the
refrigerant leak rate for the entire chiller is more than 10%
of the operating refrigerant charge per year.
Additionally,Carrier recommends that leaks totalling less
than the above rate but more than a rate of 1 lb (0.5 kg) per
year should be repaired during annual maintenance or whenever the refrigerant is pumped over for other service work.
Test After Service, Repair, or Major Leak — If
all refrigerant has been lost or if the chiller has been opened
for service, the chiller or the affected vessels must be pressure and leak tested. Refer to the Leak Test Chiller section
(page 46) to perform a leak test.
67
Page 68
Refrigerant HFC-134a MUST NOT be mixed with air
or oxygen and pressurized for leak testing. In general,
this refrigerant should not be allowed to be present
with high concentrations of air or oxygen above atmospheric pressures, because the mixture can undergo
combustion.
REFRIGERANT TRACER — Use an environmentally acceptable refrigerant as a tracer for leak test procedures.
TO PRESSURIZE WITH DRY NITROGEN — Another
method of leak testing is to pressurize with nitrogen only
and use a soap bubble solution or an ultrasonic leak detector
to determine if leaks are present. This should only be done
if all refrigerant has been evacuated from the vessel.
1. Connect a copper tube from the pressure regulator on the
cylinder to the refrigerant charging valve. Never apply
full cylinder pressure to the pressurizing line. Follow the
listed sequence.
2. Open the charging valve fully.
3. Slowly open the cylinder regulating valve.
4. Observe the pressure gage on the chiller and close the
regulating valve when the pressure reaches test level. Donot exceed 140 psi (965 kPa).
5. Close the charging valve on the chiller. Remove the copper tube if no longer required.
Repair the Leak, Retest, and Apply Standing
Vacuum Test —
leaks with an electronic leak detector, soap bubble solution,
or an ultrasonic leak detector. Bring the chiller back to atmospheric pressure, repair any leaks found, and retest.
After retesting and finding no leaks, apply a standing vacuum
test, and then dehydrate the chiller. Refer to the Standing
Vacuum Test and Chiller Dehydration in the Before Initial
Start-Up section, page 49.
After pressurizing the chiller, test for
Checking Guide Vane Linkage — Refer to Fig. 35.
If slack develops in the drive chain, eliminate backlash as
follows:
1. With the chiller shut down (guide vanes closed), remove
the chain guard, loosen the actuator holddown bolts, and
remove the chain.
2. Loosen the vane sprocket set screw and rotate the sprocket
wheel until the set screw clears the existing spotting hole.
3. Withthe set screw still loose, replace the chain, and move
the vane actuator to the left until all the chain slack is
taken up.
4. Tighten the actuator holddown bolts and retighten the set
screw in the new position.
5. Realign the chain guard as required to clear the chain.
Contact Seal Maintenance (Refer to Fig. 36) —
During chiller operation, oil thatlubricatesthesealseepsthrough
the space between the contact sleeve (Item 18) and the lock
nut (Item 15). This oil slowly accumulates in an atmospheric oil chamber and is automatically returned to the system by a seal oil return pump.
Oil should never leak around the outer diameter of the
contact sleeve (Item 18). If oil is found in this area, O-ring
(Item 12) should be checked and replaced.
The oil passing through the shaft seal carries with it some
absorbed refrigerant. As the oil reaches the atmosphere, the
absorbed refrigerant is released from the oil as a vapor. For
this reason, a detector will indicate the presence of a slight
amount of refrigerant around the compressor shaft whenever the chiller is running.
Fig. 35 — Electronic Vane Actuator Linkage
During shutdown, no refrigerant should be detected except for minute outgassing from residual oil in the seal area.
There should be no oil seepage. If oil flow or the presence
of refrigerant is noted while the chiller is shut down, a seal
defect is indicated. Arrange for a seal assembly inspection
by a qualified serviceman to determine the cause of the leakage and make the necessary repairs.
SEAL DISASSEMBLY(Fig. 36) — Contact seal disassembly and repair should be performed only by well qualified
compressor maintenance personnel. These disassembly instructions are included only as a convenient reference for
the authorized serviceman.
For ease of disassembly, refer to Fig. 36 while following
these instructions.
3. The snap ring (Item 16) used forsealassembly/disassembly
is clipped over three screws (Item 41) on the windage
baffle (Item 7). Remove the snap ring and put it aside
for now.
4. Remove the screws holding the windage baffle and the
shaft end labyrinth (Item 8).
5. Remove the contact sleeve key (Item 11).
6. Using a snap ring tool, install the snap ring (Item 16) in
the groove on the end of the contact sleeve (Item 18), as
shown in Fig. 36.
7. Remove the tubing between the coupling (Item 20) and
the atmospheric oil chamber. Loosen the bolts (Item 6)
holding the coupling guard mounting ring (Item 4) and
the seal housing (Item 3). The spring contact sleeve
(Item 17) will push the housing out until the snap ring
(Item 16) contacts the seal housing (Item 3). To avoid
binding, loosen the bolts in a circular pattern until the
spring stops pushing out on the housing. Then, remove
2 bolts that are 180 degrees apart. Replace them with a
1/2-13 all-thread rod to support the housing while the
rest of the bolts are removed.
8. Remove the rest of the bolts, and remove the seal
housing.
68
Page 69
LEGEND
1—Lubricating Tube
2A — O-Ring
2B — O-Ring
3—Seal Housing
4—Coupling Guard Mounting Ring
5—Plain
6—Hex Head Bolt,
7—Windage Baffle
8—Shaft End Labyrinth
9—Screw
10 — Screw, 10-24 ×
11 — Key, Contact Sleeve
12 — O-Ring
13 — Compressor Shaft
14 — O-Ring
15 — Lock Nut
16 — Snap Ring (Service tool only; must be removed for operation)
17 — Spring Contact Sleeve
18 — Contact Sleeve
19 — Outer Carbon Ring
20 — Coupling (Connection to atmospheric oil chamber)
21 — Rotating Contact Ring
22 — Diaphragm Retainer
23 — Inner Seal Retaining Screw, 10-24×1lg(14Required)
24 — Gasket
25 — Diaphragm
26 — Inner Carbon Ring
27 — Inner Seal Spring
28 — Inner Seal Retainer
29 — Seal Gland Sleeve
30 — Spacer
31 — Journal Bearing Housing
32 — Journal Bearing
33 — Inner Seal Shim
34 — Inner Carbon Guide Ring
35 — O-Ring
36 — Inner Carbon Key
37 — Screw, 10-24 × 1
38 — Retaining Ring
39 — Seal Shoulder
40 — Compressor End Wall
41 — Thread Cut Screw, 8-32 ×
42 — Screw,
1
⁄2-in. Washer (8 Required)
1
⁄2-13×4lg(8Required)
1
⁄4-20×3⁄4lg (4 Required)
1
⁄2lg
1
⁄4lg (2 Required)
1
5
⁄16-18×13⁄4lg (2 Required)
⁄4lg (3 Required)
Fig. 36 — Contact Seal
NOTE: Adjust shims (Item 33) to maintain .525 ± .01 in. (13.3 ± .3 mm) dimensionwith shaftthrust toward driveand check
carbon for +.06 minimum travel.
69
Page 70
9. Place a clean, lint-free cloth on a smooth, sturdy work
surface. Place the seal housing assembly on the cloth
with the face of the contact sleeve in contact with the
cloth. While one person pushes down on the housing to
compress the spring, another person must remove the
snap ring. Then, slowly let the seal housing rise until
the spring is fully extended.
10. Remove Items 2B and 12 (O-rings).
11. Slide the outer carbon ring (Item 19) off the shaft.
12. Remove the lubricating tube (Item 1) and gasket
(Item 24).
13. Remove the inner carbon key (Item 36).
14. Remove the inner seal retaining screws (Item 23) and
the diaphragm retainer (Item 22).
15. Using a spanner wrench, loosen the lock nut (Item 15).
The lock nut has a right-hand thread. Remove the lock
nut. The inner seal spring (Item 27) may push the contact ring part way out as the lock nut is loosened.
16. Carefully slide the rotating contact ring (Item 21) off
the shaft. The ring slips onto the shaft with a very close
tolerance and is prone to sticking. Slide it slowly to avoid
a tight jam. To release, tap gently with a SOFT hammer.
17. Remove O-ring (Item 14). This O-ring will be crushed
into a triangular shape. Since it is not an ordinary O-ring
gland, this is normal.Always replace with a new O-ring.
18. The seal gland sleeve (Item 29) can be removed, but it
is generally not necessary to do so. If the seal gland is
removed, make sure it is reinstalled with the bevel (that
contains the O-ring) facing outward.
19. The inner carbon ring (Item 26), the diaphragm
(Item 25), the inner carbon guide ring (Item 34), and the
inner seal spring (Item 27) can be removed as an assembly.The carbon ring is held to the guide ring by raised
barbs on the guide ring. Carefully pull the carbon ring
from the guide ring. The diaphragm can now be removed from the guide ring. Inspect the diaphragm for
wear.
20. To remove the inner seal retainer (Item 28) and O-ring
(Item 35), use 4 screws (Item 23) in the 4 threaded holes
spaced evenly around the seal retainer to jack the part
out of position.
If the inner seal shims are damaged, carefully measure them
so that a shim package of the same thickness can be installed.Thethicknessof the shim package should not be changed
unless the compressor shaft and/or thrust bearing are replaced. Replacing either of these items could affect the float
of the inner seal. This float is adjusted by varying the thickness of the shim pack.
This completes the disassembly of the seal.
Clean all parts to be reused with solvent, coat with oil and
place in a protected area until needed.
SEAL REASSEMBLY (Fig. 36) — Be sure that all gasket
surfaces are clean and that all holes, including oil holes, are
properly aligned between the gasket and mating flange. Coat
the gasket with oil-graphite mixture to prevent sticking.
1. Install the inner seal retainer (Item 28) and O-ring
(Item 35). Then, remove the bolts to allow installation
of the inner seal assembly.
2. Replace the seal gland sleeve (Item 29) if it has been
removed. Make sure that the plain side is against the
shaft shoulder and that the beveled side is facing
outward.
NOTE: If the seal gland sleeve is oriented improperly,
refrigerant will leak under the contact ring.
3. Place the diaphragm (Item 25) over the inner seal retainer (Item 28). Withthe best lapped sealing face of the
carbon away from the diaphragm and the notch for the
key centered between two of the bolt holes in the diaphragm, gently push the inner carbon ring (Item 26) into
the inner carbon guide ring until it is tight against the
diaphragm. Make sure that the diaphragm is not wrinkled
or folded between the carbon and the retainer. Place the
spring (Item 27) over the back of the guide ring. Place
this assembly into the seal, and make sure that the carbon face can travel a minimum of 0.06 inches (1.5 mm)
in each direction from the outside edge of the seal gland
sleeve (Item 29).
4. Install the O-ring (Item 14). Slide the rotating contact
ring (Item 21) into position against the seal gland sleeve.
Install the lock nut (Item 15) and tighten it with a
spanner.
5. Gently rotate the inner seal assembly to line up the bolt
holes in the diaphragm with the bolt holes in the inner
seal retainer (Item 28). Place the diaphragm retainer over
the diaphragm with the beveled side toward the diaphragm. Install the 14 one-inch long screws (Item 23),
leaving the top 2 holes on either side of the notch in the
carbon open. Tighten to 2 ft-lb.
6. Install the inner carbon key (Item 36) using the 1-1/4-in.
screws (Item 37). Tighten to 2 ft-lb.
7. Install the lubricating tube (Item 1) and gasket (Item 24).
8. Lightly coat the outer carbon ring with compressor oil.
Then, slide the outer carbon ring (Item 19) into position
against the rotating contact ring.
9. Install O-ring (Item 12).
10. Place the contact sleeve (Item 18) face down on a clean,
lint-free cloth on a smooth, hard, work surface, and place
the contact sleeve spring over the sleeve. Lightly coat
the outside surface of the contact sleeve with compressor oil. While one person places the seal housing
(Item 3) over the contact sleeve and presses the spring
down, another person must install the snap ring
(Item 16) in the groove around the small end of the contact sleeve. Once the snap ring is firmly seated in the
groove, slowly let the seal housing rise until the snap
ring rests against the housing. Rotate the sleeve in the
seal housing until the key slot in the sleeve is in line
with the bolt hole for the contact sleeve key (Item 11).
11. Install the O-ring (Item 2B) into its groove, and place
the seal housing into position on the compressor. Guide
rods can help accomplish this task. Place the coupling
guard mounting ring (Item 4) over the seal housing, and
fasten both in place with 8 hex-head bolts (Item 6). Draw
in the housing against the seal spring by tightening the
bolts in steps in a crisscross pattern to draw the housing
evenly.
12. Once the bolts have been tightened, remove the snap
ring from the contact sleeve, and set it aside.
13. Install the contact sleeve key (Item 11).
14. Install the shaft end labyrinth (Item 8) and the windage
baffle using screws (Item 9). The split lines of the labyrinth and windage baffle should be located 90 degrees
apart.
15. Mount the snap ring (Item 16) on the screws (Item 41)
near the inside surface of the windage baffle.
16. Reconnect the tubing from the atmospheric oil chamber
to the coupling (Item 20).
The reassembly of the seal is complete.
Run the oil pump to fill the seal, and rotate the shaft sev-
eral times by hand before leak testing.
70
Page 71
Chiller Alignment
ALIGNMENT METHODS — There are several established
procedures for aligning shafts. The dial indicator method is
presented here since it is considered to be one of the most
accurate and reliable. Another faster and easier method for
alignment involves using laser alignment tools and computers. Follow the laser tool manufacturer’s guidelines when
using the laser technique.
Where job conditions such as close-spaced shafts prohibit
the use of dial indicators for coupling face readings, other
instruments such as a taper gage may be used. The same procedures described for the dial indicator may be used with the
taper gage.
Shafts placed in perfect alignment in the non-operating
(cold) condition will always move out of alignment to some
extent as the chiller warms to operating temperature. In most
cases, this shaft misalignment is acceptable for the initial run-in
period before hot check and alignment can be made (see Hot
Alignment Check section, page 61).
NOTE: The physical configuration of the 17FX compressor
makes the oil sump temperature a more significant factor in
alignment than the suction and discharge temperatures. Therefore, warm the sump oil to operating temperature (approximately 140 F [60 C]), if possible, before beginning alignment procedures.
General
1. Final shaft alignment must be within .002-in. (.05-mm)
TIR (Total Indicated Runout) in parallel. Angular alignment must be within 0.00033 inches per inch of traverse
(0.00033 mm per mm of traverse) across the coupling face
(or inch of indicator swing diameter) at operating tem-peratures. For example, if a bracket-mounted indicator
moves through a 10-in. diameter circle when measuring
angular misalignment, the allowable dial movement will
be 10 times 0.00033 for a total of 0.0033 in. (0.0033 mm).
2. Follow the alignment sequence specified in the Near
Final Alignment section.
3. All alignment work is performed on gear and drive equip-
ment. Once the compressor is bolted in a perfectly level
position and is piped to the cooler and condenser, it must
not be moved prior to hot check.
4. All alignment checks must be made with the equipment
hold-down bolts tightened.
5. In setting dial indicators on zero and when taking read-
ings, both shafts should be tight against their respective
thrust bearings.
6. The space between coupling hub faces must be held to
the dimensions in Fig. 29 and 30.
7. Accept only repeatable readings.
High Speed Coupling Alignment
1. Move the gear with the coupling attached into alignment
with the compressor coupling. The compressor must be
in the thrust position and the gear must be centered between the thrust collars when determining gear position
relative to the compressor.Adjust the jackscrews to reach
close alignment. Follow the procedures outlined in the
Correcting Angular Misalignment and Correcting Parallel Misalignment sections.
2. A 5-in. long spacer hub is supplied between the gear and
compressor.Maintain the exact hub-to-hub distance specified in Fig. 29.
3. Where the shaft ends are very close, a taper gage may be
used in place of the dial indicator.
4. Get the gear alignment as close as possible by using the
jackscrew adjustment.
Low Speed Coupling Alignment
1. Move the motor with the coupling attached into alignment with the gear coupling. The motor must be in its
mechanical center and the gear must be centered between
the thrust collars when determining the motor position
relative to the gear. Adjust the jackscrews to reach close
alignment. Follow the procedure outlined in the Correcting Angular Misalignment and Correcting Parallel Misalignment sections.
2. Maintain the exact hub-to-hub distance as specified in
Fig. 30.
3. Where the shaft ends are very close, a taper gage may be
used in place of the dial indicator.
4. Get the motor alignment as close as possible by using the
jackscrew adjustment.
NOTE: The drive shaft end-float at final drive position must
not allow the coupling hub faces to make contact or the coupling shroud to bind.
PRELIMINARYALIGNMENT — To get within dial indicator range, roughly align the equipment as shown in Fig. 37
and as described below.
Place a straight edge across the OD of one coupling to the
OD of the other. Measure the gap between the straight edge
and the OD of the second coupling with a feeler gage. Then,
by adding or removing shims at each corner, raise or lower
the equipment by the measured amount.
In a similar manner, measure the shaft offset from side to
side and jack the equipment over as required to correct.
Fig. 37 — Checking Preliminary Alignment
NEAR FINAL ALIGNMENT — Once the chiller components are within dial indicator range, the adjustments for misalignment should be made in a specific sequence. The four
positions of alignment described below are arranged in the
recommended order.
1. Angular in elevation — This alignment is adjusted
with shims and is not readily lost in making the other
adjustments.
71
Page 72
2. Parallel in elevation — This alignment is also made with
shims, but it cannot be made while there is angular misalignment in elevation.
3. Angular in plan — This position can easily be lost if placed
ahead of the two adjustments in elevation.
4. Parallel in plan — This adjustment cannot be made while
there is still angular misalignment in plan and can easily be
lost if elevation adjustments are made.
Correcting Angular Misalignment
Preparation — Shaft angular misalignment is measured on
the face of the coupling hubs or on brackets attached to each
shaft (see Fig. 38 and 39). Brackets are preferred since they
extend the diameter of the face readings.
Attach a dial indicator to one coupling hub or shaft and
place the indicator button against the face of the opposite
hub. Position the indicator so that the plunger is at approximately mid-position when the dial is set to zero. Both shafts
should be held tightly against their thrust bearings when the
dial is set and when readings are taken.
To be sure that the indicator linkage is tight and the button
is on securely, rotate the coupling exactly 360 degrees. The
dial reading should return to zero. Accept only repeatable
readings.
Fig. 38 — Measuring Angular Misalignment
in Elevation
Fig. 39 — Measuring Angular Misalignment
in Elevation Using Brackets
Measurement— Occasionally,coupling faces may not be perfectly true or may have been damaged in handling. To compensate for any such runout, determine the actual or ‘‘net’’
shaft misalignment as follows:
Check the opening at the top and at the bottom of the coupling faces (or at each side when making plan adjustment).
Rotate both shafts exactly 180 degrees and recheck the openings. Record the difference. (Example below is in inches.)
72
Page 73
If the larger opening remains the same but changes from
side to side, the shafts are in perfect alignment. The change
in opening is due entirely to coupling runout, as above, or to
a burr or other damage to the coupling face.
If the larger opening remains the same, and remains
on the same side, the amount is entirely shaft (net)
misalignment.
If the larger opening remains on the same side but changes
amount, misalignment and runout are present. Add the two
amounts and then divide by two to get the actual or net
misalignment.
Obtain:
D — coupling face diameter in inches (or indicator but-
ton circle)
L — distance between front and rear holddown bolts
(inches)
M — net misalignment in inches
And:
Divide L, the bolt distance, by D, the coupling diameter.
Multiply the result by M, the net misalignment.
L
S=× M
D
Example: Face diameter 5 in. (D). Distance between front
and rear holddown bolts 30 in. (L). Net misalignment in elevation .012 in. (M).
30 divided by 5 is 6
6 multiplied by .012 is .072 in.
S = .072 in.
If the larger opening between coupling faces is at the top,
place .072 in. of shim under each rear foot or remove
.072 in. from the front footings to bring the couplings into
angular alignment in elevation.
Tighten the holddown bolts and recheck the net
misalignment.
The height of the shaft above the footings and the distance the shaft extends beyond the equipment will not affect
the calculations.
Determine the angular adjustment in plan by the same method
of calculation. At this point, however, the procedure should
include a correction for the change in coupling gap which
always occurs in adjusting angular alignment (Fig. 40). By
selecting the proper pivot point (see Fig. 41), the coupling
gap can be kept at the dimension specified in the job data.
1. Pivot on the front bolt at the closed side of the couplings
to shorten the gap; pivot on the front bolt at the open side
to lengthen it. It may sometimes be advantageous to pivot
half the required amount on one front footing and half on
the other.
2. Place a dial indicator against the rear foot as indicated in
Fig. 41.
3. Place a screw jack on the other rear foot to move the equip-
ment towards the indicator.
If the larger opening changes amount and also changes
from side to side, subtract the smaller amount from the larger
and divide by two to obtain the net misalignment.
Adjustment — Having obtained the net misalignment, the
amount by which the equipment must be moved can now be
calculated.
To determine:
S — amount of movement (in plan) or the thickness of
shim (in elevation) required.
S—Thickness of Shim Required
L—Distance Between Front and
Rear Holddown Bolt in Inches
D—Diameter of Coupling in Inches
M—Net Misalignment in Inches
Fig. 40 — Alignment Formula
73
Page 74
4. Loosen all holddown bolts except the pivot bolt. Turn the
screw jack until the rear end of the equipment moves against
the indicator by the desired amount.
5. Tighten the holddown bolts and recheck the indicator. If
the reading has changed, loosen the three bolts and readjust. It may be necessary to over or undershoot the desired reading to allow for the effect of bolt tightening.
Fig. 41 — Adjusting Angular Misalignment in Plan
Correcting Parallel Misalignment
Preparation — Attach the dial indicator to one shaft or cou-
pling hub and place the indicator button on the outside diameter of the other hub. The reach of the dial from one hub
to the other should be parallel to the shafts, and the dial button shaft should point directly through the center of the shaft
on which it rests. Compress the plunger to about midposition and set the dial at zero.
Check the tightness of the dial button and the indicator
linkage by rotating the shaft to which the indicator is attached 360 degrees. The dial should return to zero. Check
for repeatability.
Check for runout by rotating the hub on which the dial
button rests 180 degrees. If the runout exceeds .001 total indicator reading, the hub should be removed and the shaft
checked. Shaft runout must not exceed .001 TIR.
The effect of hub runout can be eliminated by locating a
position on the half coupling where two readings 180 degrees apart read zero. Rotate the coupling so that one zero
point is at the top and the other at the bottom when checking
for misalignment in elevation. Place the zero points side to
side in a similar manner when checking for misalignment in
plan.
Measurement — With dial set at zero in the top position,
rotate the shaft to which the indicator is attached 180 degrees. If the dial reading is plus, the shaft on which the button rests is low. If the reading is minus, the shaft on which
the button rests is high.
Never accept a single reading. Look for repeatability. Rotate the shaft several times to see if the reading remains the
same. It is good practice to reverse the procedure and read
from zero at the bottom.
Always rotate the shafts in the same direction when taking readings. Backlash in the coupling teeth could cause some
differences.
Adjustment — Divide the total indicator reading by two to
obtain the exact amount of shaft offset. As illustrated in
Fig. 42, the indicator will read the total of A plus B but the
required shaft adjustment is only half of this as indicated
by C.
Add or remove identical amounts of shims at all footings
to bring the shaft to the proper elevation. Tighten all the holddown bolts and recheck the readings. Parallel alignment must
be within .002 TIR.
To correct parallel misalignment in plan, use a screw jack
and dial indicator as shown in Fig. 42. With a front holddown bolt as the pivot, move the rear of the equipment over.
Then, with the rear holddown bolt on the same side acting
as the pivot, move the front end of the equipment over by
the same amount.
FINAL ALIGNMENT — The procedures and tolerance requirements for final alignment are the same as those described in the Near Final Alignment section. Final alignment
is performed just prior to grouting and chiller hot check. All
piping, including water and steam, must be completed, but
the water and refrigerant charges need not be in place.
HOT ALIGNMENT CHECK
General — When all chiller components have reached op-
erating temperature (after running near full load for from 4
to 8 hours), a hot alignment check must be made. Hot alignment check may be made with couplings assembled or
disassembled.
Disassembled Couplings
1. Shut down chiller.
2. With chiller hot, quickly disassemble couplings.
3. Check angular and parallel alignment in plan and eleva-
tion as described in the Near Final Adjustment section.
Record the indicator readings (see page CL-12) and make
necessary adjustments to bring alignment within .002 in.
TIR and .00033 inches per in. of coupling face traverse
(or in. of indicator swing). Follow procedures described
in the Near Final Alignment section.
4. Reinstall couplings and run chiller until it again reaches
operating temperature.
5. Repeat steps 1 through 4 until alignment remains within
specified tolerances.
Assembled Couplings — If there is room on the shaft between coupling and component to clamp a sturdy bracket,
the arrangement illustrated in Fig. 43 maybe used. The clamps
must have room to rotate with the shaft.
This method is quicker because the couplings do not have
to be disassembled. In addition, eccentricity or coupling face
runout are not problems since both shafts rotate together.
74
Page 75
Fig. 42 — Correcting Parallel Misalignment
When using brackets, the diameter in the alignment formula (see Near Final Alignment, Connecting Angular Misalignment section) will be that of the circle through which
the dial indicator rotates.
1. Shut down the chiller.
2. With chiller at operating temperature, quickly install
brackets.
3. Check that alignment is within .002 in. TIR and
.00033 in. per in. of traverse (0.00033 mm per mm of
traverse) across the diameter of measurement. Adjust alignment as required. (Refer to Near Final Alignment
section.)
4. Remove brackets and run chiller until operating tempera-
ture is again reached.
Fig. 43 —Alignment Check —Assembled Coupling
5. Recheck the alignment per steps 1 through 4 until it remains within the specified tolerances.
Be surethatcoupling guardsare replaced after these checks.
DOWELING
Techniques — After a hot alignment check has been com-
pleted, the compressor, gear and drive must be doweled to
their sole plates. Doweling permits exact repositioning of components if they have to be moved.
1. Doweling must be completed with equipment at maximum operating temperature (full load).
2. Use No. 8 taper dowels to dowel the compressor, gear,
and drive to the base. Use a
13
⁄32-in. drill and No. 8 taper
reamer with straight flutes. Drill pilot hole and then expand the pilot hole to final dimension.
1
3. Fit dowel so that
⁄16-in. of taper is left above the equipment foot. If dowel holes are re-reamed as a result of realignment, be sure dowels are tight and do not bottom.
4. Place dowels as nearly vertical as possible.
5. Coat the dowels with white lead or other lubricant to prevent rusting.
6. Tap dowel lightly into position with a small machinist’s
hammer. A ringing sound will indicate proper seating.
Dowel the suction end of the compressor base, the two
feet at the high speed end of the gear, and the drive feet in
accordance with the drive manufacturer’s instructions. The
number of dowels used in the drive is usually four, but some
manufacturers require more.
75
Page 76
WEEKLY MAINTENANCE
Check the Lubrication System —
on the compressor reservoir sight glass, and observe the level
each week while the chiller is shut down.
If the level goes below the lower sight glass, the oil reclaim system will need to be checked for proper operation.
If additional oil is required, add oil as follows:
Oil may be added through the oil drain and charging valve
(Fig. 2, Item 22) using a pump. However, an oil charging
elbow on the seal-oil return chamber (Fig. 4) allows oil to be
added without pumping. The seal oil return pump automatically transfers the oil to the main oil reservoir. A pump is
required for adding oil against refrigerant pressure. The oil
charge is approximately 20 gallons (76 L) for FX (size 531-
599) style compressors. The added oil must meet Carrier’s
specifications. Refer to Changing theOilFiltersandOilChanges
sections. Any additional oil that is added should be logged
by noting the amount and date. Any oil that is added due to
oil loss that is not related to service will eventually return to
the sump, and must be removed when the level is high.
An oil heater is controlled by the PIC to maintain oil temperature above 150 F (65.5 C) or refrigerant temperature plus
70° F (38.9° C) (see the Controls section) when the compressor is off. The LID STATUS02 screen displays whether
the heater is energized or not (OIL HEATER RELAY). If the
PIC shows that the heater is ON, but the sump is not heating
up, the power to the oil heater may be off or the oil level
may be too low. Check the oil level, the oil heater contactor
voltage, and oil heater resistance.
The PIC does not permit compressor start-up if the oil temperature is too low. The PIC continues with start-up only
after the temperature is within limits.
After the initial start or a 3-hour power failure, the PIC
allows the chiller to start once the oil is up to proper temperature, but uses a slow ramp load rate of 2° F (1.6° C) per
minute.
Be sure that the isolation valves on the oil line near the
filter(s) (Fig. 44) are fully open before operating the compressor.
There are no lubrication requirements for the FX disc
coupling.
Check the oil level in the gear reservoir and observe the
level each week. If additional oil is required, add oil as described in the Oil Changes section on page 77. The added oil
must meet Carrier specifications. (SeeTable 11.)Do not overfill the reservoir.Any additional oil added or removed should
be logged by noting the amount and date.
Mark the oil level
Check the oil level in the motor bearings and observe the
level each week. If additional oil is required, add oil as described in the Oil Changes section on page 77. The added oil
must meet Carrier specifications. (See Table 11.) Any additional oil added or removed should be logged by noting the
amount and date.
SCHEDULED MAINTENANCE
Establish a regular maintenance schedule based on the actual chiller requirements such as chiller load, run hours, and
water quality. The time intervals listed in this section are offered as guides to service only.
Service Ontime — The LID displays a SERVICE ON-
TIME value on the STATUS01 screen. This value should
be reset to zero by the service person or the operator each
time major service work is completed so that time span between service can be tracked and viewed.
Inspect the Control Center — Maintenance is lim-
ited to general cleaning and tightening of connections. Vacuum
the cabinet to eliminate dust build-up. If the chiller controls
malfunction, refer to the Troubleshooting Guide section for
control checks and adjustments.
Be sure power to the control center is off when
cleaning and tightening connections inside the control
center.
Check Safety and Operating Controls Monthly
To ensure chiller protection, the automated control test
—
should be done at least once per month. SeeTable 3 for safety
control settings.
Changing the Oil Filters
COMPRESSOR OIL FILTER — Change this oil filter annually or whenever the chiller is open for repairs. The 17FX
compressor has an isolatable filter so that the filter may be
changed without removing refrigerant from the chiller. Use
the following procedure.
1. Make sure the compressor is off and that the compressor
disconnect is open.
2. Disconnect the power to the oil heater and oil pump.
3. Close the valves to the filter.
4. Relieve the pressure from within the filter by using the
pressure connection on the oil feed line valve to the compressor. Run a hose from the connection to a bucket to
catch the oil.
*Water out line is hidden behind oil out line.
Fig. 44 — Typical Compressor or Gear Oil Cooler/Filter
76
Page 77
5. Open the drain located on the shell of the cooler/filter.
Run a hose from the drain to a bucket to catch the oil.
6. Once the pressure has been relieved and the oil drained,
loosen the bolts that hold the cover on the filter body.
Remove the old filter cartridges and replace with a new
filter cartridge.Assemble the filter assembly (filters, spacer,
and stopper assembly), and make sure that the spring is
centered against the filter assembly as shown in Fig. 44.
7. Replace the drain fitting, using standard practices to ensure a leak-tight joint. Evacuate the air from the cooler/
filter assembly.
8. Once the assembly has been evacuated, open the isolation valves.
9. Connect power to the oil heater and oil pump. The oil
heater should turn on and warm the oil to 140 to 150 F
(60 to 66 C). Operate the oil pump for 2 minutes.Add oil,
if required, to keep the level up in the lower sight glass.
Oil should be visible in the reservoir sight glass during all
operating and shutdown conditions.
EXTERNAL GEAR OIL FILTER — Change the oil filter
annually or whenever the chiller is open for repairs. The 17EX
external gear lubrication system has an isolatable filter. Use
the following procedure.
1. Make sure that the compressor is off and the compressor
disconnect is open.
2. Disconnect the power to the oil heater, if equipped, and
to the oil pump.
3. Close the line valves to the filter.
4. Relieve any pressure from within the filter by using the
pressure connection on the oil feed line valve to the compressor. Run a hose from the connection to a bucket to
catch the oil.
5. Open the drain located on the shell of the cooler/filter.
Run a hose from the connection to a bucket to catch the
oil.
6. Once the pressure has been removed and the oil drained,
loosen the bolts that hold the cover on the filter body.
Remove the oil filter cartridges and replace with new cartridges. Assemble the filter assembly (filters, spacer, and
stopper assembly), and make sure that the spring is centered against the filter assembly, as shown in Fig. 44.
7. Replace the drain fitting, using standard practices to ensure a leak-tight joint.
8. Open the isolation valves.
9. Connect power to the oil heater,if equipped, and oil pump.
Operate the oil pump for 2 minutes. Add oil, if required,
to keep the level up in the sight glass.
Oil should be visible in the reservoir sight glass during all
operating and shutdown conditions.
Oil Specifications — If oil is to be added, it must meet
the Carrier specifications shown in Table 11.
Oil Changes — Carrier recommends changing the oil
after the first year of operation and every three to five years
thereafter as a minimum. Carrier also recommends a yearly
oil analysis. However, if a continuous oil monitoring system
is functioning and a yearly oil analysis is performed, the time
between oil changes can be extended.
COMPRESSOR OIL
1. Open the control and oil heater circuit breaker.
2. Drain the oil reservoir by opening the oil charging valve,
(Fig. 2, Item 22). Slowly open the valve against refrigerant pressure.
3. Change the oil filter at this time. See the Changing the
Oil Filters section, page 76.
4. Charge the chiller with approximately 20 gallons (76 L)
of oil for FX (size 531-599) style compressors in order to
bring the level to the middle of the upper sight glass
(Fig. 2, Item 21). Turn on the power to the oil heater and
let the PIC warm it up to at least 140 F (60 C). Operate
the oil pump manually, through the control test, for 2 minutes. The oil level should be between the lower sight glass
and one-half full in the upper sight glass for shutdown
conditions.
EXTERNAL GEAR OIL — Proper lubrication is vital to
maintain gear drive performance.After 500 hours or 4 weeks
of initial operation, whichever is first, the external gear drive
should be thoroughly drained, flushed, and refilled with the
proper lubricant. Under normal operating conditions, the lubricant should be changed every 2500 hours or 6 months,
whichever comes first. This change frequency can be extended if an oil sample analysis indicates a very limited degradation or contamination.
Table 11 — 17EX Chiller Oil Specifications
SPECIFICATIONCOMPRESSOR
Oil Type*Inhitited Polyolester-Based
Viscosity at
100 F (37 C)
Carrier Part NumberPP23BZ107PP23BZ091PP23BB005PP23BZ103
Carrier Specification PP47-12PP16-0PP16-2PP47-31
Recommended
Manufacturer
Capacity20 gal (76 L)0.6 gal (2.3 L) per bearing17 gal (41.6L)Compressor:
LEGEND
SSU — Saybolt Universal Seconds
*Oil type specified for chillers using HFC-134a refrigerant.
Synthetic Compressor Oil
ISO 68
(300 SSU)
ICI, Emkarate RL68HMobil, DTE Light
MOTOR SLEEVE
BEARINGS
Mineral-Based, Rust and
Oxidation Inhibited Turbine
Grade Oil
ISO 32
(150 SSU)
Texaco, Regal R & 0432
Sun Oil, Sunvis 932
Chevron, GST ISO 32
Rust and Oxidation
Inhibited Oil
ISO 68
(300 SSU)
Mobil Oil, DTE Heavy Medium
Texaco, Regal UR & 068
Chevron, OC #68
NOCO, Turbine T-68
EXTERNAL
GEAR
PUMPOUT
COMPRESSOR
AND OIL
SEPARATOR
Reciprocating
Compressor Oil
ISO 68
(300 SSU)
Castrol Icematic SW68
ICI Emkarate RL68HP
4.5 pints (2.6 L)
Oil Separator:
1 pint (0.6 L)
77
Page 78
The lubricant should be drained while the gear is at operating temperature. The gear drive should be cleaned with
a flushing oil. Used lubricant and flushing oil should be completely removed from the system to avoid contaminating new
oil.
To change the oil in the external gear:
1. Make sure that the compressor is off and the disconnect
for the compressor is open.
2. Disconnect the power to the oil heater, if equipped, and
the oil pump.
3. Open the drain located on the shell of the cooler/filter.
Run a hose from the drain to a bucket to catch the oil.
4. Once the pressure has been removed and the oil drained,
loosen the bolts that hold the cover on the filter body.
Remove the old filter cartridges. Assemble the filter assembly (filters, spacer, and stopper assembly), and make
sure that the spring is centered against the filter assembly
as shown in Fig. 44.
5. Replace the drain fitting, using standard practices to en-
sure a leak-tight joint.
6. Open the isolation valves and add new oil. Refer to
Table 11 for oil specifications.
7. Connect power to the oil heater, if equipped, and the oil
pump. Operate the oil pump for 2 minutes. Add oil, if
required, to keep the level up in the sight glass.
MOTOR SLEEVE BEARING AND PUMPOUT COMPRESSOR OIL — For instructions on changing the motor
sleeve bearing oil, refer to the section on Motor Maintenance, this page.
For instructions on changing the optional pumpout compressor and oil separator oil, refer to the section on Pumpout
System Maintenance, page 83.
Inspect Refrigerant Float System — Inspect the
refrigerant float system once every 5 years or when the
economizer/storage vessel is opened for service. Transfer the
refrigerant into the cooler vessel or into a storage tank. There
are two floats on the 17EX, one on each side of theeconomizer/
storage vessel. Remove the float access covers. Clean the
chambers and valve assembly thoroughly. Be sure that the
valves move freely. Make sure that all openings are free of
obstructions. Examine the cover gaskets and replace if necessary. See Fig. 45 for a view of both floats.
InspectRelief ValvesandPiping — The relief valves
on this chiller protect the system against the potentially dangerous effects of overpressure. To ensure against damage to
the equipment and possible injury to personnel, these devices must be kept in peak operating condition.
As a minimum, the following maintenance is required.
1. At least once a year, disconnect the vent piping at the
valve outlet and carefully inspect the valve body and mechanism for any evidence of internal corrosion or rust, dirt,
scale, leakage, etc.
2. If corrosion or foreign material is found, do not attempt
to repair or recondition. Replace the valve.
3. If the chiller is installed in a corrosive atmosphere or the
relief valves are vented into a corrosive atmosphere, make
valve inspections at more frequent intervals.
Coupling Maintenance — Proper coupling mainte-
nance is important since the coupling supports the outboard
end of the compressor high speed shaft. Clean and inspect
both couplings for wear yearly. Misalignment causes undue
noise and wear. Check alignment yearly, or more often if
vibration or heating occur. Refer to Chiller Alignment section, page 71.
Never operate the drive without the coupling guards in
place. Contact with a rotating shaft or coupling can cause
serious injury.
Motor Maintenance — A carefully planned and ex-
ecuted program of inspection and maintenance will do much
to ensure maximum motor availability and minimum maintenance cost. If it becomes necessary to repair, recondition,
or rebuild the motor, it is recommended that the nearest Westinghouse repair facility be consulted.
In addition to a daily observation of the appearance and
operation of the motor, it is recommended that a general inspection procedure be established to periodically check the
following items:
• cleanliness, both external and internal
• stator and rotor (squirrel-cage) windings
• bearings
Fig. 45 — Typical Float Valve Arrangement
78
Page 79
CLEANLINESS — On open ventilated motors, screens and
louvers over the inlet air openings should not be allowed to
accumulate any build-up of dirt, lint, etc., that could restrict
free air movement. Screens and louvers should never be cleaned
or disturbed while the motor is in operation because any dislodged dirt or debris can be drawn directly into the motor.
If the motor is equipped with air filters, they should be
replaced (disposable type) or cleaned and reconditioned (permanent type) at a frequency that is dictated by conditions. It
is better to replace or recondition filters too often than not
often enough.
Washing motors using a water spray is not recommended. Manual or compressed air cleaning is preferred. If it becomes necessary to spray-wash a motor,
it should be done with extreme care. Do not aim high
pressure sprays directly at air inlet openings, conduit connections, shaft seals, or gasketed surfaces to prevent the
possibility of forcing water inside the chiller.
The stator windings of motors with open ventilation systems can become contaminated with dirt and other substances brought into the motor by the ventilating air. Such
contaminants can impair cooling of the winding by clogging
the air passages in the winding end-turns and vent ducts through
the stator core and by reducing heat transfer from the winding insulation surfaces to the cooling air. Conducting contaminants can change or increase electrical stresses on the
insulation, and corrosive contaminants can chemically attack and degrade the insulation. This may lead to shortened
insulation life and stator failure.
Several satisfactory methods of cleaning stator windings
and stator cores are offered below:
Compressed Air — Low pressure (30 psi maximum), clean
(no oil) dry air can be used to dislodge loose dust and particles in inaccessible areas such as air vent ducts in the stator
core and vent passages in the winding end-turns. Excessive
air pressure can damage insulation and drive contaminants
into inaccessible cracks and crevices.
Vacuum — Vacuum cleaning can be used, both before and
after other methods of cleaning, to remove loose dirt and
debris. It is a very effective way to remove loose surface
contamination from the winding without scattering it. Vacuum
cleaning tools should be nonmetallic to avoid any damage to
the winding insulation.
Wiping — Surface contamination on the winding can be removed by wiping, using a soft, lint-free wiping material. If
the contamination is oily, the wiping material can be moistened (not dripping wet) with a safety-type petroleum solvent, such as Stoddard solvent. In hazardous locations, a solvent
such as inhibited methyl chloroform may be used, but must
be used sparingly and immediately removed. While this solvent is non-flammable under ordinary conditions, it is toxic.
Proper health and safety precautions should be followed while
using it.
Solvents of any type should never be used on windings
provided with abrasion protection. Abrasion protection is a
grey, rubber-like coating applied to the winding end-turns.
Adequate ventilation must always be provided in any
area where solvents are being used to avoid the danger
of fire, explosion, or health hazards. In confined areas
(such as pits) each operator should be provided with an
air line respirator, a hose mask, or a self-contained breathing apparatus. Operators should wear goggles, aprons,
and suitable gloves. Solvents and their vapors should
never be exposed to open flames or sparks and should
always be stored in approved safety containers.
SLEEVE BEARINGS
Oil Changing — The oil reservoirs of the self lubricated bear-
ings should be drained and refilled every 6 months. More
frequent changes may be needed if severe oil discoloration
or contamination occurs. In conditions where contamination
does occur, it may be advisable to flush the reservoir with
kerosene to remove any sediment before new oil is added.
Proper care must be taken to thoroughly drain the reservoir
of the flushing material before refilling it with the new oil.
Refill the reservoir to the center of the oil sight glass with
a rust and oxidation inhibited, turbine grade oil. The viscosity of the oil must be 32 ISO (150 SSU) at 100 F (37.7 C).
Oil capacity in each of the 2 bearings is 0.6 gal. (2 l) per
bearing. Use of Carrier Oil Specification PP16-0 is approved (refer to Table 11).
Disassembly — The bearing sleeve is spherically seated and
self-aligning. The opposite drive end bearing is normally insulated for larger motors (or when specified). On some motors, the insulation is bonded to the spherical seat of the bearing
housing. Use extreme care when removing the sleeve from
the insulated support to avoid damaging this insulation.
Note that some bolts and tapped holes associated with the
bearing housings, bearing sleeves, and seals are metric.
The following procedure is recommended for removing
the bearing sleeve.
1. Remove the oil drain plug in the housing bottom and
drain the oil sump.
2. Remove all instrumentation sensors that are in contact
with the bearing sleeve. These include resistance temperature detectors, thermocouples, temperature relay bulbs,
thermometers, etc.
3. Remove the end cover.
4. Remove the socket head bolts holding the bearing cap
and the inner air seal together at the horizontal split. The
front end cover plate must also be removed if the front
bearing is being disassembled. Remove the bearing cap
and top half of the inner air seal by lifting straight up to
avoid damaging the labyrinth seals. Place themon a clean,
dry surface to avoid damage to the parting surfaces.
5. Remove any split bolts that may be holding the two bearing halves together. Remove the top half of the bearing
sleeve using suitable eyebolts in the tapped holes provided. Lift the bearing top straight up and avoid any contact with the shoulders of the shaft journals that might
damage the thrust faces of the bearing. Place on a clean,
dry surface, taking care to prevent damage to either the
parting surfaces or the locating pins that are captive in
the top bearing half.
6. Remove the 4 screws at the partings in the oil ring and
dismantle the ring by gently tapping the dowel pin ends
with a soft-faced mallet. Remove the ring halves and
immediately reassemble them to avoid any mixup in parts
or damage to the surfaces at the partings.
79
Page 80
7. When removing the labyrinth seals, note the position of
the anti-rotation button located on the inside of the top
half of the seal. Pull up the garter spring surrounding
the floating labyrinth seal and carefully slip out the top
half. Rotate the garter spring until the lock is visible.
Twist counterclockwise to disengage the lock, remove
the garter spring, then rotate the lower half of the seal
out of the groove in the bearing housing while noting
the orientation of the oil drain holes. Note the condition
of these floating labyrinth seals. If they are cracked or
chipped, they must be replaced. Do not attempt to reuse
a damaged seal.
8. To remove the bottom bearing half, the shaft must be
raised a slight amount to relieve pressure on the bearing. On the rear end, this can be done by jacking or lifting on the shaft extension. (Care must be taken to protect the shaft from damage.) On the front end, jacking
or lifting can be done using bolts threaded into the tapped
holes provided in the shaft end.
NOTE: Lift only enough to free the bearing; overlifting the shaft can cause difficulty in removing the
bearing.
9. Roll the bottom bearing half to the top of the shaft journal and then lift it using suitable eyebolts threaded into
the holes provided. Again, avoid any contact with the
shaft shoulders that could damage the bearing thrust faces.
Place the lower bearing half on a clean, dry surface to
protect the parting surfaces.
Use extreme care when rolling out the lower bearing half. Keep the hands and fingers well clear of
any position where they might be caught by the bearing half if it were accidentally released and rotated
back to its bottom position. Serious personal injury
could result.
10. Protect the shaft journal by wrapping it with clean, heavy
paper or cardboard.
Reassembly — Bearing reassembly is basically a reversal of
the disassembly procedures outlined above, with the following additional steps.
Curil-T is the only approved compound for use in the
assembly of the bearings on this motor. Other products
may harden and impede the operation.
During the reassembly of the bearing parts, a thin layer
of Curil-T should be applied to all gasketed and machined interface surfaces. This suggestion does not apply to the machined surfaces of the bearing liner halves.
1. The interior of the bearing housing should be cleaned
and then flushed with clean oil or kerosene.
2. The bearing halves and the shaft journal should be wiped
clean using lint-free cloth soaked with clean oil.
3. All parts should be carefully inspected for nicks, scratches,
etc., in any contact surfaces. Such imperfections should
be removed by an appropriate method such as stoning,
scraping, filing, etc., followed by thorough cleaning.
4. Apply afew drops of oil to the journal and bearing saddles.
5. Roll the bottom half of the bearing into place and lower
the shaft.
6. Before installing the floating labyrinth seal halves, observe their condition. Do not attempt to use a cracked or
chipped seal. The bottom half seal has a set of drilled
holes in its side face. These must be placed at the bottom toward the inside of the bearing so that accumulating oil may drain back into the housing.
7. Put a small bead of Curil-T around the bottom seal half
outside diameters on both sides adjacent to the garter
spring groove. This prevents oil from bypassing the seal
around its outside.
8. Place the bottom seal half on top of the shaft (ensuring
that the proper orientation of the drain holes is provided) and roll it into position. Install the top half of the
seal making sure that the anti-rotation button is located
in the proper position on the inboard side of the bearing.
Insert the garter spring pulling up on both ends to permit engaging the lock. Run a small bead of Curil-Taround
the outside diameters on both sides adjacent to the garter spring groove on this half also.
9. Carefully reassemble the two oil ring halves. Inspect the
dowel pins for burrs and straightness and make any corrections required. Do not force the ring halves together.
Excessive force may alter the roundness or flatness of
the ring which can change its oil delivery performance.
Apply locking compound to the oil ring screws prior to
reassembly.
10. Assemble the top half of the bearing liner making sure
that the match marks on the liner halves align with one
another.Failure to ensure alignment of match marks can
cause misalignment and possible damage to bearings and
journal surfaces. Reinstall any split bolts, if supplied,
between the bearing halves.
11. Some of the pipe plugs in the housing are metric thread
type and have a copper, lead, or similar material washer.
If these plugs are removed, be careful not to lose the
washers. Before reassembly, inspect the washers and replace them if required.
12. Before installing the bearing cap, observe the position
of the floating labyrinth seal. The ‘‘tab’’ must be on top
to engage the pocket. Failure to position the seal properly will result in damage when the cap is assembled.
13. Carefully lower the bearing housing cap over the floating seals. Keep the bearing cap level to avoid binding
and possibly damaging the seals. The bearing cap should
seat evenly on the bearing housing base.
When seating the bearing shell, apply a thin layer of
lubricating oil at the spherical surface of the liner. Slowly
roll the lower bearing liner into the bearing housing making sure that the split surfaces of the liner and the housing are flush. Gradually lower the shaft onto the bearing. The weight of the shaft will help rotate the bearing
liner so that the babbitt surface of the liner will match
the slope of the journal. Sometimes it is necessary to
use a rubber mallet to tap lightly on the bearing housing
while slowly rolling the shaft to help this seating
operation.
Do not force the bearing cap down. Damage could
occur to the labyrinth seals.
If the bearing cap does not seat completely, remove and
reset the floating labyrinth seal position. When installing upper bearing cap, the floating labyrinth seals sometimes rotate and the anti-rotation ‘‘tab’’ does not seat in
its holder, thus preventing the bearing housing from seating properly. This procedure should be repeated until
the bearing cap seats properly.
80
Page 81
14. Reinstall the bearing housing split bolts. Before torquing bearing housing cap bolts, rotate the shaft by hand
while bumping the bearing housing with a rubber or rawhide mallet in the horizontal and axial planes to allow
the bearings to align themselves to the shaft journals.
15. Torque the bearing housing cap bolts by following the
torque values as provided in Table 6 on page 51.
Motor Handling/Rigging — Each motor is provided
with lifting lugs, welded to the four corners of the motor
frame, for lifting the assembled chiller. The motor should
always be lifted by using the lifting lugs located on all four
corners of the motor frame. (See Fig. 46.)
Spreader bars of adequate capacity and number must be
used to avoid applying any pressure against the top air
housing with the lifting plugs.
provide proper protection while the motor is being stored.
The motor should be stored under cover in a clean, dry location and should be protected from rapid temperature changes.
Since moisture can be very detrimental to electrical components, the motor temperature should be maintained at approximately 5° F (3° C) above the dew point temperature by
providing either external or internal heat. If the motor is
equipped with space heaters, they should be energized at the
voltage shown by the space heater nameplate attached to the
motor.Incandescent light bulbs can be placed within the motor to provide heat. However, if used, they must not be allowed to come in contact with any parts of the motor because
of the concentrated hot spot that could result.
This motor has been provided with a shaft shipping brace
or shipping bolt (normally painted yellow) to prevent shaft
movement during transit, it must be removed to allow shaft
rotation (refer to Before Initial Start-Up, Remove Shipping
Packaging section, page 45). It is very important that this
brace be reinstalled exactly as it was originally, before the
motor is moved from storage or any time when the motor is
being transported. This prevents axial rotor movement that
might damage the bearings.
Motors equipped with sleeve bearings are shipped from
the factory with the bearing oil reservoirs drained. In storage, the oil reservoirs should be properly filled to the center
of the oil level gage with a good grade of rust inhibiting oil
(refer to the certified drawing for oil viscosity and any special requirements). To keep the bearing journals well oiled
and to prevent rusting, the motor shaft should be rotated several revolutions every 2 weeks. While the shaft is rotating it
should be pushed to both extremes of the endplay to allow
for oil flow over the entire length of the journals.
Fig. 46 — Motor Riggings
If the motor is lifted with the top air housing removed, the
angle of the lifting slings with the horizontal should never
be less than 45 degrees.
Withthe exclusion of the TEWACcooler, the top air housing is provided with
3
⁄4-10 tapped holes for lifting devices to
be installed in order to remove the air housing from the motor. The top air housing can be detached by removing the
enclosure holddown bolts, located in the inside corners of
the enclosure. These enclosure holddown bolts are accessed
through the louver/screens located on the front and rear end
of the chiller or through access panels bolted to the sides of
the enclosure.
Uneven lifting must always be avoided. When single
point lifting is to be used, slings of equal lengths must
always be used to avoid uneven lifting.
Under no circumstances should the motor be lifted using the shaft as an attachment point.
NOTE: Refer to weights specified on certified drawing to
determine proper lifting equipment required for specific components or assemblies.
Motor Storage — If the chiller is to be placed in ex-
tended shutdown, certain precautions must be taken to
External Gear Storage — All internal and unpainted
external surfaces of the gear drives have been treated with a
rust preventative at the factory before shipment. The protective life of the rust preventative varies with temperature
fluctuations, atmospheric moisture content, degree of exposure to the elements during storage, and degree of contact
with other objects.
Inspect all machined surfaces, and spray or add rust inhibitor to exposed metal surfaces that may have had the protective coating removed during shipping and handling.
T obe sure that the gear drive operates satisfactorily at startup, take certain precautions when you receive it. The expected length of storage and the storage atmosphere dictate
the maintenance schedule to be followed. The gear must always be stored in its operating position, level on its mounting feet, and free of loads or weights on input and output
shafts.
SHORT-TERM STORAGE (Indoors) — If the units are to
be stored for 30 days or less, observe the following precautions.
• Store the unit in a clean, dry location with the factory pack-
ing intact and with as nearly a constant temperature as
possible.
• Elevate the unit a minimum of 6 in. above the floor level.
• Avoid areas that are subject to extremes in temperature,
vibration, and humidity.
LONG-TERM STORAGE (Indoors) — If the unit is to be
stored for more than 30 days, observe the following precautions. Store in a clean, dry location. Elevate the unit at a
minimum of 6 in. above the ground floor level. Avoid areas
that are subject to extremes in temperature, vibration, and
humidity. In addition, do one of the following:
• Remove the breather and replace it with pipe plugs. Pack
the entire seal area with grease to form a vapor barrier and
seal with tape.
81
Page 82
Fill the gear drive to the recommended oil level with heated
Shell VSI grade 68 oil or its equivalent, heated between
110 and 120 F (43 and 49 C). Do not overfill. Immediately
close the openings to keep the vapors in the housing.
Inspect the unit every 30 days and spray or add rust inhibitor suitable for anticipated storage conditions, as
required.
Drain and replace the oil with the recommended oil type
prior to start-up.
• Remove the breather and replace it with a pipe plug. Pack
the entire seal area with grease to form a vapor barrier and
seal it with tape.
A vapor-phase rust inhibitor, such as Daubert Chemical,
Non-Rust Motorstor VCi-10 or its equivalent, may be added
to the recommended oil type in the amount of 2% of the
total sump capacity. Fill the unit to the recommended level.
Do not overfill.
Inspect the unit every 30 days and spray or add rust inhibitor suitable for anticipated storage conditions, as
required.
The unit may run without changing this oil mixture.
EXTENDED DOWNTIME — Consider the length of downtime the unit will undergo. The lubricating oil used in the
unit should protect the interior parts for up to 30 days of
shutdown. If the unit will be shut down longer than 30 days,
it must be operated a minimum of 30 minutes every 30 days
to distribute the lubricant to all interior parts.
If it is impractical to operate the unit every 30 days, the
long-term storage instructions described above must be followed. All seals applied for this storage condition must be
removed before operating the unit.
Compressor Bearing Maintenance — The key to
good bearing maintenance is proper lubrication. Use the proper
grade of oil, maintained at recommended level, temperature,
and pressure. Inspect the lubrication system regularly and
thoroughly.
Only a trained service technician should remove and
examine the bearings. The bearings should be examined on
a scheduled basis for signs of wear. The frequency of examination is determined by the hours of chiller operation,
load conditions during operation, and the condition of the
oil and the lubrication system. Excessive bearing wear can
sometimes be detected through increased vibration or increased bearing temperature. If either symptom appears, contact an experienced and responsible service organization for
assistance.
External Gear Maintenance — Perform the re-
quired maintenance and recommended intervals. Good preventive maintenance prolongs the life of the unit.
Daily
• Inspect for leaks and loose connections.
• Check the oil level.
• Check the oil temperature and pressure.
• Check for unusual noise and/or vibration.
Weekly — Check the oil filter.
Monthly
• Obtain oil sample analysis.
• Clean or replace oil filters.
• Check the foundation mounting bolts for tightness.
• Clean the air filter.
• Check the operation of all auxiliary equipment.
Semi-Annually
• Check gear tooth wear.
• Check the oil and replace it if necessary.
• Check the coupling alignment.
Annually
• Check the heat exchanger for corrosion and clogged tubes.
• Check the bearing clearance and end play.
Disassembly andAssembly Instructions — The following in-
structions apply to standard high speed gear units.
• Required Equipment: In addition to standard mechanic’s
tools, have the following equipment on hand: hoist, sling,
torque wrench, feeler gages, and dial indicator.
• General Instructions: Clean external surfaces of the gear
unit before removing the cover to prevent contaminants
from falling into it. Record the mounting dimensions and
the location of accessories for reference when reassembling. To remove the gear from its operating area, disconnect all connected equipment and lift the gear from its
foundation using 4 lifting lugs.
Inspect the Heat Exchanger Tubes
COOLER — Inspect and clean the cooler tubes at the end of
the first operating season. Because these tubes have internal
ridges, a rotary-type tube cleaning system is necessary to fully
clean the tubes. Upon inspection, the tube condition determines the scheduled frequency for cleaning and indicates
whether water treatment is adequate in the chilled water/
brine circuit. Inspect the entering and leaving chilled water
temperature sensors for signs of slime, corrosion, or scale.
Replace the sensor if corroded or remove any scale if found.
CONDENSER — Since this water circuit is usually an opentype system, the tubes may be subject to contamination and
scale. Clean the condenser tubes with a rotary tube cleaning
system at least once per year and more often if the water is
contaminated. Inspect the entering and leaving condenser water sensors for signs of slime, corrosion, or scale. Replace
the sensor if corroded or remove any scale if found.
Higher than normal condenser pressures, together with the
inability to reach full refrigeration load, usually indicate dirty
tubes or air in the chiller. If the refrigeration log indicates a
rise above normal condenser pressures, check the condenser
refrigerant temperature against the leaving condenser water
temperature. If this reading is more than what the design difference is supposed to be, then the condenser tubes may be
dirty, or water flow may be incorrect. Because HFC 134a is
a high-pressure refrigerant, air usually does not enter the chiller;
rather, the refrigerant leaks out.
During the tube cleaning process, use brushes especially
designed to avoid scraping and scratching the tube wall. Contact your Carrier representative to obtain these brushes. Do
not use wire brushes.
Hard scale may require chemical treatment for its prevention or removal. Consult a water treatment specialist
for proper treatment.
WaterLeaks— Waterin the refrigerant is indicated dur-
ing chiller operation by the refrigerant moisture indicator on
the refrigerant motor cooling line. Water leaks should be repaired immediately.
The chiller must be dehydrated after repair of water leaks.
See Chiller Dehydration section, page 49.
WaterTreatment— Untreated or improperly treated wa-
ter may result in corrosion, scaling, erosion, or algae. The
services of a qualified water treatment specialist should be
obtained to develop and monitor a treatment program.
82
Page 83
Water must be within design flow limits, clean, and treated
to ensure proper chiller performance and reduce the potential of tube damage due to corrosion, scaling, erosion, and algae. Carrier assumes no responsibility for
chiller damage resulting from untreated or improperly
treated water.
Inspect the Starting Equipment — Before work-
ing on any starter, shut off the chiller, and open all disconnects supplying power to the starter.
The disconnect on the starter front panel does not deenergize all internal circuits. Open all internal and remote disconnects before servicing the starter.
Never open isolating knife switches while equipment is
operating. Electrical arcing can cause serious injury.
Inspect the starter contact surfaces for wear or pitting on
mechanical-type starters. Do not sandpaper or file silverplated contacts. Follow the starter manufacturer’s instructions for contact replacement, lubrication, spare parts
ordering, and other maintenance requirements.
Periodically vacuum or blow off accumulated debris on
the internal parts with a high-velocity, low-pressure blower.
Power connections on newly installed starters may relax
and loosen after a month of operation. Turn power off and
retighten. Recheck annually thereafter.
Loose power connections can cause voltage spikes, overheating, malfunctioning, or failures.
Check Pressure Transducers — Prior to start-up
and once a year, the pressure transducers should be checked
against a pressure gage reading. Check all three transducers:
oil pressure, condenser pressure, and cooler pressure.
Note the evaporator and condenser pressure readings on
the STATUS01 screen on the LID. Attach an accurate set of
refrigeration gages to the cooler and condenser Schrader fittings. Compare the two readings. If there is a difference in
readings, the transducer can be calibrated, as described in
the Troubleshooting Guide section.
Pumpout System Maintenance — For compres-
sor maintenance details, refer to the 06D, 07D Installation,
Start-Up, and Service Instructions.
OPTIONALPUMPOUTCOMPRESSOR OIL CHARGE —
Use oil conforming to Carrier specifications for reciprocating compressor usage. See Table 11.
Oil should be visible in the compressor sight glass both
during operation and at shutdown. Always check the oil
level before operating the compressor.Before adding or changing oil, relieve the refrigerant pressure as follows:
1. Attach a pressure gage to the gage port of either com-
pressor service valve (Fig. 34).
2. Close the suction service valve and open the discharge
line to the storage tank or the chiller.
3. Operate the compressor until the crankcase pressure drops
to 2 psig (13 kPa).
4. Stop the compressor and isolate the system by closing
the discharge service valve.
5. Slowly remove the oil return line connection. Add oil as
required.
6. Replace the connection and reopen the compressor service valves.
PUMPOUT SAFETY CONTROL SETTINGS (Fig. 47) —
The pumpout system high-pressure switch should open at
161 psig (1110 kPa) and close at 130 psig (896 kPa). Check
the switch setting by operating the pumpout compressor and
slowly throttling the pumpout condenser water.
Fig. 47 — Controls for Optional Pumpout
Compressor
Ordering Replacement Chiller Parts — When or-
dering Carrier specified parts, the following information must
accompany an order:
• chiller model number and serial number
• name, quantity, and part number of the part required
• delivery address and method of shipment
MOTOR REPLACEMENT PARTS — Replacement or renewal parts information for the motor and any auxiliary devices can be obtained from the nearest Westinghouse Motor
Company sales office. A complete description of the needed
part(s) is necessary, together with the complete motor nameplate reading for positive motor identification.
EXTERNAL GEAR REPLACEMENT PARTS — Replacement or renewal parts information for the external gear and
any auxiliary devices can be obtained from the nearest Nuttall or Lufkin sales office.Acomplete description of theneeded
part(s) is necessary, together with the complete gear nameplate reading for positive identification.
TROUBLESHOOTING GUIDE
Overview —
erator and the technician troubleshoot a 17EX chiller.
• By using the LID display, the actual operating conditions
of the chiller can be viewed while the unit is running.
• The CONTROL ALGORITHM STATUS table includes
screens with information that can be used to diagnose problems with chilled water temperature control, chilled water
The PIC has many features to help the op-
83
Page 84
temperature control overrides, hot gas bypass, surge algorithm status, and time schedule operation. Refer to
Fig. 14 and Table 2, Examples 11-14.
• The control test feature checks for proper operation and
tests the temperature sensors, pressure transducers, theguide
vane actuator, oil pumps, water pumps, tower control, and
other on/off outputs while the compressor is stopped. It
also has the ability to lock off the compressor and turn on
water pumps for pumpout operation. The LID display shows
the required temperatures and pressures during these operations. Refer to Fig. 16 for the CONTROL TEST menu
structure and to the Control Testsection, page 85, for more
information on this feature.
• Other SERVICE menu tables can access configured items,
such as chilled water resets, override set points, etc.
• If an operating fault is detected, an alarm message is generated and displayed on the LID default screen. A more
detailed message, along with a diagnostic message, is also
stored in the ALARM HISTORY table in the PIC.
Checking the Display Messages — The first area
to check when troubleshooting the 17EX is the LID display.
If the alarm light is flashing, check the primary and secondary message lines on the LID default screen (Fig. 11). These
messages indicate where the fault is occurring. The ALARM
HISTORY table on the SERVICE menu also carries an alarm
message to further expand on this alarm. For a complete list
of alarm messages, see Table 12. If the alarm light starts to
flash while accessing a menu screen, depress the EXIT
key to return to the default LID screen to read the failure
message. The compressor does not run while an alarm condition exists unless the alarm type is an unauthorized start or
a failure to shut down.
soft-
Checking Temperature Sensors — All tempera-
ture sensors are thermistors. This means that the resistance
of the sensor varies with temperature. All sensors have the
same resistance characteristics. Determine sensor temperature by measuring voltage drop if the controls are powered,
or resistance if the controls are powered off. Compare the
readings to the values listed in Table 14A or 14B.
RESISTANCE CHECK — Turn off the control power and
disconnect the terminal plug of the sensor in question from
the module. Witha digital ohmmeter,measure the sensor resistance between the receptacles designated by the wiring
diagram. The resistance and corresponding temperature are
listed in Table14A or 14B. Check the resistance of both wires
to ground. This resistance should be infinite.
VOLTAGE DROP — Using a digital voltmeter, the voltage
drop across any energized sensor can be measured while the
control is energized. Table 14A or 14B lists the relationship
between temperature and sensor voltage drop (volts dc measured across the energized sensor). Exercise care when measuring voltage to prevent damage to the sensor leads, connector plugs, and modules. The sensor wire should also be
checked at the sensor plug connection. Check the sensor wire
by removing the condenser at the sensor and measure for
5 vdc back to the module, if the control is powered.
Relieve all refrigerant pressure or drain the water prior
to replacing the temperature sensors.
CHECK SENSOR ACCURACY — Place the sensor in a
medium of a known temperature and compare that temperature to the measured reading. The thermometer used to determine the temperature of the medium should be of laboratory quality with 0.5° F (.25° C) graduations. The sensor
in question should be accurate to within 2° F (1.2° C).
See Fig. 6 for sensor locations. The sensors are immersed
directly in the refrigerant or water circuits. The wiring at each
sensor is easily disconnected by unlatching the connector.
These connectors allow only one-way connection to the sensor. When installing a new sensor, apply a pipe sealant or
thread sealant to the sensor threads.
DUAL TEMPERATURE SENSORS — There are 2 sensing
elements on each of the bearing temperature sensors for servicing convenience. In case one of the dual sensors is damaged, the other one can be used by moving a wire.
The number 1 terminal in the sensor terminal box is the
common line. To use the second sensor, move the wire from
the number 2 position to the number 3 position.
CheckingPressureTransducers— The 17EX chiller
has 5 transducers. These transducers sense cooler pressure,
condenser pressure, compressor oil supply pressure, oil sump,
and gear oil supply pressure. The compressor oil supply pressure and the oil transmission sump pressure differenceis calculated by a differential pressure power supply module. The
PSIO then reads this differential. In effect, then, the
PSIO reads 3 pressure inputs. The cooler and condenser
transducers are used by the PIC to determine refrigerant
temperatures.
All pressure inputs can be calibrated, if necessary.It is not
usually necessary to calibrate at initial start-up. However, at
high altitude locations, calibration of the transducer will be
necessary to ensure the proper refrigerant temperature/
pressure relationship. Each transducer is supplied with 5 vdc
power from a power supply .If the power supply fails, a transducer voltage reference alarm occurs. If the transducer reading is suspected of being faulty, check the supply voltage. It
should be 5 vdc ± .5 v. If the supply voltage is correct, the
transducer should be re-calibrated or replaced.
To calibrate oil pressure differential, refer to Oil Pressure
Differential Calibration at the end of this section.
Calibration can be checked by comparing the pressure readings from the transducer against an accurate refrigeration gage.
These readings are all viewed or calibrated from the
STATUS01 screen on the LID. The transducer can be checked
and calibrated at 2 pressure points. These calibration points
are 0 psig (0 kPa) and between 240 and 260 psig (1655 to
1793 kPa). To calibrate these transducers:
1. Shut down the compressor.
2. Disconnect the transducer in question from its Schrader
fitting.
NOTE: If the cooler or condenser vessels are at 0 psig
(0 kPa) or are open to atmospheric pressure, the transducers can be calibrated for zero without removing the
transducer from the vessel.
3. Access the STATUS01 screen, and view theparticular trans-
ducer reading; it should read 0 psi (0 kPa). If the reading
is not 0 psi (0 kPa), but within ± 5 psi (35 kPa), the
value may be zeroed by pressing the SELECT
while the parameter for the transducer is highlighted.
Then, press the ENTER
to zero.
If the transducer value is not within the calibration range,
the transducer returns to the original reading. If the LID
pressure value is within the allowed range (noted above),
check the voltage ratio of the transducer. To obtain the
voltage ratio, divide the voltage (dc) input from the transducer by the supply voltage signal, measured at the PSIO
terminals J7-J34 and J7-J35. For example, the condenser
transducer voltage input is measured at PSIO terminals
J7-1 and J7-2. The voltage ratio must be between
0.80 vdc and 0.11 vdc for the software to allow calibration. Pressurize the transducer until the ratio is within range.
Then attempt calibration again.
softkey.The value will now go
softkey
84
Page 85
4. A high pressure point can also be calibrated between 240
and 260 psig (1655 and 1793 kPa) by attaching a regulated 250 psig (1724 kPa) pressure (usually from a nitrogen cylinder). The high pressure point can be calibrated
by accessing theappropriate transducer on the
STATUS01 screen, highlighting the transducer, pressing
the SELECT
softkey, and then increasing or decreasing
the value to the exact pressure on the refrigerant gage.
Press ENTER
to finish. High altitude locations must compensate the pressure so that the temperature/pressure relationship is correct.
If the transducer reading returns to the previous value and
the pressure is within the allowed range, check the voltage ratio of the transducer. Refer to Step 3 above. The
voltage ratio for this high pressure calibration must be
between 0.585 and 0.634 vdc to allow calibration. Change
the pressure at the transducer until the ratio is within the
acceptable range. Then attempt to calibrate to the new
pressure input.
The PIC will not allow calibration if the transducer is too
far out of calibration. A new transducer must be installed
and re-calibrated.
OILDIFFERENTIALPRESSURE/POWER SUPPLYMODULE CALIBRATION — (See Fig. 48.) The oil reservoir in
the 17EX chiller is not common to cooler pressure. Therefore, a comparison of pump output to cooler pressure can
not be used to provide differential oil pressure information.
A different method has been developed.
Oil transmission sump pressure and oil supply pressure
are fed to a comparator circuit on a 5V power supply board.
The output of this circuit, which represents differential oil
pressure, is fed to the PSIO. The oil differential pressure is
calibrated to 0 psid (0 kPad) by selecting the oil pressure
input on the STATUS01 screen. Then, with the oil pump turned
OFF and the transducers connected, press the ENTER
key to zero the point. No high end calibration is needed or
possible.
soft-
17EX OIL PRESSURE INPUT
TROUBLESHOOTING TRANSDUCERS — When troubleshooting transducers, keep the negative lead of your voltohmmeter on terminal U4 of the power supply (or terminal
4 on power supplies without the comparator circuit).
Voltage VO1 = (VH1-VL1) + .467 ± .1 V
For all PIC transducers:
Measured pressure = (507.97 × (V
V
= transducer output ref. to neg. terminal
out
(4 or U4) i.e., VH1 to U4 or VL1 to U4
out/Vin
)) − 47.33
Vin= power supply output, i.e., U3 to U4
TRANSDUCER REPLACEMENT — Since the transducers are mounted on Schrader-type fittings, there is no need
to remove refrigerant from the vessel. Disconnect the transducer wiring by pulling up on the locking tab while pulling
up on the weather-tight connecting plug from the end of the
transducer. Do not pull on the transducer wires. Unscrew
the transducer from the Schrader fitting. When installing a
new transducer, do not use pipe sealer, which can plug the
sensor. Put the plug connector back on the sensor and snap
into place. Check for refrigerant leaks.
Make sure to use a backup wrench on the Schrader fitting whenever removing a transducer.
ControlAlgorithms Checkout Procedure — One
of the tables in the SERVICE menu is the CONTROL ALGORITHM STATUS table. This table has 6 screens that may
be viewed to see how a particular control algorithm is
operating, that is, to see what parameters and values the PIC
is using to control the chiller.
MAINT01Capacity
MAINT02Override
MAINT03Surge/
MAINT04LEAD/LAG
OCCDEFMTime
WSMDEFME Water
Control
Status
HGBP
Status
Status
Schedules
Status
System
Manager
Status
These maintenance tables are very useful in determining
guide vane position, reaction from load changes, control point
overrides, hot gas bypass reaction, surge prevention, etc.
Thevalues used tocalculatethe chilled
water/brine control point.
Detailsofall chilled water controloverride values
The surge and hot gas bypass control
algorithm status as well as the values
dealing with this control.
LEAD/LAG operation status.
The Local and CCN occupied sched-
ules,displayedin a waythatallows the
operator toquickly determine whether
the schedule is in an occupied period
or not.
The status of the WSM (water system
manager),a CCN module thatcan turn
on the chiller and change the chilled
water control point.
Fig. 48 — Oil Differential Pressure/Power
Supply Module
Control Test — The control test feature can check all
the thermistor temperature sensors, including those on the
Options modules, pressure transducers, pumps and their associated flow switches, the guide vane actuator, and other
control outputs, such as hot gas bypass. The tests can help
to determine whether a switch is defective, or a pump relay
is not operating, among other useful troubleshooting tests.
During pumpdown operations, the pumps are energized
to prevent freeze-up, and the vessel pressures and temperatures are displayed. The pumpdown/lockout feature prevents the compressor from starting up when there is no refrigerant in the chiller or when the vessels are isolated. The
operator then uses the terminate lockout screen to end the
pumpdown lockout after the pumpdown procedure is reversed and refrigerant is added.
85
Page 86
LEGEND FOR TABLE 12, A - N
1CR AUX— Compressor Start Contact
CA P
— Compressor Current
CCN— Carrier Comfort Network
CDFL— Condenser Water Flow
CHIL S S
— Chiller Start/Stop
CHW— Chilled Water
CMPD— Discharge Temperature
CRP— Condenser Pressure
ERT— Evaporator Refrigerant Temperature
EVFL— Chilled Water Flow
GV TRG
— Target Guide Vane Position
LED— Light-Emitting Diode
LID— Local Interface Device
OILPD— Oil Pressure
OILT— Oil Sump Temperature
PIC— Product Integrated Control
PRS TRIP
— Pressure Trip Contact
PSIO— Processor Sensor Input/Output Module
RLA— Rated Load Amps
RUN AUX
MANUALLY STOPPED — PRESSCCN OR LOCAL TO START
TERMINATE PUMPDOWN MODETO SELECT CCN OR LOCAL
SHUTDOWN IN PROGRESSCOMPRESSOR UNLOADINGChiller unloading before shutdown due to soft/stop feature.
SHUTDOWN IN PROGRESSCOMPRESSOR DEENERGIZED
ICE BUILDOPERATION COMPLETEChiller shutdown from Ice Build operation.
PIC in OFF mode, press the CCN or local softkey to
start unit.
Enter the CONTROL TEST table and select
to unlock compressor.
Chillercompressor isbeing commandedto stop.Water pumpsare deenergized within one minute.
READY TO START IN XX MINUNOCCUPIED MODE
READY TO START IN XX MINREMOTE CONTACTS OPENRemote contacts have stopped chiller. Close contacts to start.
READY TO START IN XX MINSTOP COMMAND IN EFFECT
READY TO START IN XX MINRECYCLE RESTART PENDINGChiller in recycle mode.
READY TO STARTUNOCCUPIED MODE
READY TO STARTREMOTE CONTACTS OPENRemote contacts have stopped chiller. Close contacts to start.
READY TO STARTSTOP COMMAND IN EFFECT
READY TO START IN XX MINREMOTE CONTACTS CLOSEDChiller timer counting down unit. Ready for start.
READY TO START IN XX MINOCCUPIED MODEChiller timer counting down unit. Ready for start.
READY TO STARTREMOTE CONTACTS CLOSEDChiller timers complete, unit start will commence.
READY TO STARTOCCUPIED MODEChiller timers complete, unit start will commence.
STARTUP INHIBITEDLOADSHED IN EFFECTCCN loadshed module commanding chiller to stop.
READY TO START IN XX MINSTART COMMAND IN EFFECT
Time schedule for PIC is unoccupied.
Chillers will start only when occupied.
Chiller START/STOP on STATUS01 manually forced to stop. Release value to start.
Time schedule for PIC is unoccupied. Chiller will start when occupied. Make sure the time and date have been set on the
SERVICE menu.
Chiller START/STOP on STATUS01 manually forced to stop. Release value to start.
Chiller START/STOP on STATUS01 has been manually forced to
start. Chiller will start regardless of time schedule or remote contact
status.
PRESTART ALERTHIGH MOTOR TEMPERATUREMTRW [VALUE] exceeded limit of [LIMIT]*.
PRESTART ALERTHIGH BEARING TEMPERATUREMTRB [VALUE] exceeded limit of [LIMIT]*.
PRESTART ALERTHIGH DISCHARGE TEMPCMPD [VALUE] exceeded limit of [LIMIT]*.
PRESTART ALERTLOW REFRIGERANT TEMPERT [VALUE] exceeded limit of [LIMIT]*. Check
PRESTART ALERTLOW OIL TEMPERATUREOILT [VALUE] exceeded limit of [LIMIT]*.
PRESTART ALERTLOW LINE VOLTAGEV P [VALUE] exceeded limit of [LIMIT]*.
PRESTART ALERTHIGH LINE VOLTAGEVP [VALUE] exceeded limit of [LIMIT]*.
PRESTART ALERTHIGH CONDENSER PRESSURECRP [VALUE] exceeded limit of [LIMIT]*. Check
PRESTART ALERTHIGH GEAR OIL TEMPGEAOILT [VALUE] exceeded limit of [LIMIT].*
*[LIMIT] is shown on the LID as temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE]
is the actual pressure, temperature, voltage, etc., at which the control tripped.
STARTUP IN PROGRESSOCCUPIED MODEChiller starting. Time schedule is occupied.
STARTUP IN PROGRESSREMOTE CONTACT CLOSEDChiller starting. Remote contacts are closed.
STARTUP IN PROGRESSSTART COMMAND IN EFFECT
AUTORESTART IN PROGRESSOCCUPIED MODEChiller starting. Time schedule is occupied.
AUTORESTART IN PROGRESSREMOTE CONTACT CLOSEDChiller starting. Remote contacts are closed.
AUTORESTART IN PROGRESSSTART COMMAND IN EFFECT
Chiller starting. Chiller START/STOP on STATUS01 manually forced
to start.
Chiller starting. Chiller START/STOP on STATUS01 manually forced
to start.
Check alert temperature set points on EQUIPMENT SERVICE table, SERVICE2 screen.
Check sensor for accuracy if reading is not
accurate.
87
Page 88
Table 12 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
G. START-UP FAILURES: This is an alarm condition. A manual reset is required to clear.
PRIMARY MESSAGESECONDARY MESSAGEALARM MESSAGE/PRIMARY CAUSEADDITIONAL CAUSE/REMEDY
FAILURE TO START LOW OIL PRESSUREOILPD [VALUE] exceeded limit of [LIMIT]*. Check
FAILURE TO START OIL PRESS SENSOR FAULTOILPD [VALUE] exceeded limit of [LIMIT]*. Check
FAILURE TO START LOW CHILLED WATER FLOWEVFL Evap Flow Fault: Check water pump/flow
FAILURE TO START LOW CONDENSER
FAILURE TO START STARTER FAULTSTR FLT Starter Fault: Check Starter for Fault
FAILURE TO START STARTER OVERLOAD TRIPSTR FLT Starter Overload Trip: Check amps
FAILURE TO START LINE VOLTAGE DROPOUTV P Single-Cycle Dropout Detected: Check volt-
FAILURE TO START HIGH CONDENSER
FAILURE TO START EXCESS ACCELERATION
FAILURE TO START STARTER TRANSITION
FAILURE TO START 1CR AUX CONTACT FAULT1CR AUX Starter Contact Fault: Check 1CR/1M
FAILURE TO START MOTOR AMPS NOT SENSEDCA PMotor Amps Not Sensed:Check motor load
FAILURE TO START CHECK REFRIGERANT TYPECurrent Refrigerant PropertiesAbnormal — Check
FAILURE TO START LOW OIL PRESSURELowOilPressure [LIMIT]:*Check oilpressure switch/
FAILURE TO START LOW GEAR OIL PRESSUREGEAROILP [VALUE] exceeded limit of [LIMIT].*
FAILURE TO START GEAR OIL PRESSURE SENSOR Gear OilPressureTransducer Out ofRange [VALUE]. Check calibration of transducer. Replace if
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set pointpredefined or selectedby the operatoras an override,alert, or alarmcondition. [VALUE]
is the actual pressure, temperature, voltage, etc., at which the control tripped.
WATER FLOW
PRESSURE
TIME
FAULT
oil pump system.
oil pressure sensor.
switch.
CDFL Cond. Flow Fault: Check water pump/flow
switch.
Source.
calibration/reset overload.
age supply.
High Condenser Pressure [LIMIT]:* Check switch
2C aux, and water temperature/flow.
CA P ExcessAcceleration:Check guidevane closure at start-up.
RUN AUX Starter Transition Fault: Check 1CR/
1M/Interlock mechanism.
aux. contacts.
signal.
Selection of refrigerant type.
pump and 2C aux.
Check gear oil pump/filter.
Check for closed oil supply valves. Check oil filter.
Check for low oil temperature. Check transducer
accuracy.
Check for excessive refrigerant in oil sump. Run oil
pump manually for 5 minutes. Check calibration of
oilpressure differentialamplifier modules.Check wiring. Replace transducers if necessary.
Check wiring to flow switch. Check through CONTROL TEST for proper switch operation.
Check wiring to flow switch. Check through CONTROL TEST for proper switch operation.
Astarter protective device has faulted. Check starter
for ground fault, voltage trip, temperature trip, etc.
Reset overloads, check ICR relay before restarting
chiller.
Check voltage supply.Check transformers for supply.Checkwith utilityif voltagesupply is erratic. Monitor must be installed to confirm consistent, singlecycle dropouts. Check low oil pressure switch.
Check for proper design condenser flow and temperature.Check condenserapproach. Check 2Cauxiliary contactson oil sump starter. Check high pressure switch.
Checkthat guidevanes areclosed atstart-up. Check
starter for proper operation. Reduce unit pressure
if possible.
Check starter for proper operation.
Run contact failed to close.
Check starter for proper operation.
Start contact failed to close.
Checkfor proper motor amps signal to SMM.Check
wiringfrom SMMto current transformer. Check main
motor circuit breaker for trip.
Pressures at transducers indicate another refrigerant type in control test. Makesure toaccess the ATTACHTO NETWORK DEVICE screen after specifying HFC-134a refrigerant type.
The oil pressure differential switch is open when the
compressortried tostart. Checkthe switchfor proper
operation.Also,check theoil pumpinterlock (2Caux)
in the power panel and the high condenser pressure switch.
FAILURE TO STOPDISCONNECT POWERRUN AUX Emergency: DISCONNECT
LOSS OF
COMMUNICATION
STARTER CONTACT
FAULT
POTENTIAL FREEZE UPCOND PRESS/TEMP
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set pointpredefined or selectedby the operatoras an override,alert, or alarmcondition. [VALUE]
is the actual pressure, temperature, voltage, etc., at which the control tripped.
UNIT SHOULD BE
STOPPED
TOO LOW
WITH STARTERLoss of Communication with Starter: Check
ABNORMAL 1CR OR
RUN AUX
TOO LOW
CA P Emergency: Compressor
running without control authorization.
ERT Emergency: Freeze-up
prevention.
POWER.
chiller.
1CR AUX Starter Contact Fault: Check
1CR/1M aux. contacts.
CRT [VALUE] exceeded limit of [LIMIT]*
Emergency: Freeze-up prevention.
Compressor is running with more than 10% RLA
and control is trying to shut it down. Turn power
offto compressorif unable tostop. Determinecause
before re-powering.
Determine cause. If pumping refrigerant out of
chiller, stop operation and go over pumpout
procedures.
Starter run and startcontacts are energized while
control tried to shut down. Disconnect power to
starter.
Checkwiring fromPSIO to SMM.Check SMMmodule troubleshooting procedures.
Starterrun andstart contacts energizedwhile chiller
was off. Disconnect power.
The condenser pressure transducer is reading a
pressure that could freeze the water in the condensertubes. Checkforcondenser refrigerantleaks,
bad transducers,or transferred refrigerant. Place
the unit in PUMPDOWN mode to eliminate the
alarm if vessel is evacuated.
88
Page 89
Table 12 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
RUNNING — RESET ACTIVECHW TEMP DIFFERENCE
RUNNING — TEMP CONTROLLEAVING CHILLED WATERDefault method of temperature control.
RUNNING — TEMP CONTROLENTERING CHILLED WATERECW control activated on CONFIG screen.
RUNNING — TEMP CONTROLTEMPERATURE RAMP LOADINGRamp loading in effect. Use SERVICE1 screen to modify.
RUNNING — DEMAND LIMITEDBY DEMAND RAMP LOADINGRamp loading in effect. Use SERVICE1 screen to modify.
RUNNING — DEMAND LIMITEDBY LOCAL DEMAND SETPOINTDemand limit set point is , actual demand.
RUNNING — DEMAND LIMITEDBY 4-20MA SIGNAL
RUNNING — DEMAND LIMITEDBY LOADSHED/REDLINE
RUNNING — TEMP CONTROLHOT GAS BYPASS
RUNNING — DEMAND LIMITEDBY LOCAL SIGNALActive demand limit manually overridden on STATUS01 table.
RUNNING — TEMP CONTROLICE BUILD MODEChiller is running under Ice Build temperature control.
RUN CAPACITY LIMITEDHIGH CONDENSER PRESSURECRP [VALUE] exceeded limit of [LIMIT]*.
RUN CAPACITY LIMITEDHIGH MOTOR TEMPERATUREMTRW [VALUE] exceeded limit of [LIMIT]*.
RUN CAPACITY LIMITEDLOW EVAP REFRIG TEMPERT[VALUE]exceeded limit of [LIMIT]*. Check
RUN CAPACITY LIMITEDHIGH COMPRESSOR LIFTSurge Prevention Override; lift too high for
RUN CAPACITY LIMITEDMANUAL GUIDE VANE TARGETGV TRGRun Capacity Limited: Manual guide
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set pointpredefined or selectedby the operatoras an override,alert, or alarmcondition. [VALUE]
is the actual temperature, pressure, voltage, etc., at which the control tripped.
Condenser pressure override.
Motor temperature override.
refrigerant charge level.
compressor.
vane target.
Reset program active based on CONFIG screen setup.RUNNING — RESET ACTIVEREMOTE SENSOR CONTROL
Demand limit is active based on CONFIG screen setup.RUNNING — DEMAND LIMITEDBY CCN SIGNAL
Hot gas bypass option is energized. See surge prevention in the
control section.
See Capacity Overrides, Table 4.
Correct operating condition, modify setpoint, or release override.
PROTECTIVE LIMITLOW REFRIGERANT TEMPERT [VALUE] exceeded limit of [LIMIT]*.
PROTECTIVE LIMITHIGH MOTOR TEMPERATUREMTRW [VALUE]exceeded limit of [LIMIT]*.
PROTECTIVE LIMITHIGH BEARING TEMPERATUREMTRB [VALUE] exceeded limit of [LIMIT]*.
PROTECTIVE LIMITLOW OIL PRESSUREOILPD [VALUE] exceeded limit of [LIMIT]*.
PROTECTIVE LIMITNO MOTOR CURRENTCA P Loss of Motor Current: Check
PROTECTIVE LIMITPOWER LOSSV P Power Loss: Check voltage
PROTECTIVE LIMITLOW LINE VOLTAGEV P [VALUE] exceeded limit of [LIMIT]*.
PROTECTIVE LIMITHIGH LINE VOLTAGEV P [VALUE] exceeded limit of [LIMIT]*.
PROTECTIVE LIMITLOW CHILLED WATER FLOWEVFL Flow Fault: Check evap pump/flow
PROTECTIVE LIMITLOW CONDENSER WATER FLOWCDFL Flow Fault: Check condenser pump/
PROTECTIVE LIMITHIGH CONDENSER PRESSUREHigh CondPressure [OPEN]*:Check switch,
PROTECTIVE LIMIT1CR AUX CONTACT FAULTCR AUX Starter Contact Fault: Check
PROTECTIVE LIMITRUN AUX CONTACT FAULTRUN AUX Starter Contact Fault: Check
PROTECTIVE LIMITCCN OVERRIDE STOPCHIL S S CCN Override Stop while in
PROTECTIVE LIMITSPARE SAFETY DEVICESRP PL Spare Safety Fault: Check
PROTECTIVE LIMITEXCESSIVE MOTOR AMPSCA P [VALUE]exceeded limit of [LIMIT]*.
PROTECTIVE LIMITEXCESSIVE COMPR SURGECompressor Surge: Check condenser wa-
PROTECTIVE LIMITSTARTER FAULTSTR FLT Starter Fault: Check starter for
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the
operator as an override, alert, or alarm condition. [VALUE] is the actual temperature, pressure, voltage, etc., at
which the control tripped. [OPEN] indicates that an input circuit is open.
supply.
Check voltage supply.
Check voltage supply.
switch.
flow switch.
oil pressure contact, and water temp/flow.
HighCond Pressure[VALUE]*:Checkswitch,
water flow, and transducer.
water flow, and transducer.
1CR/1M aux contacts.
1CR/1M aux contacts.
LOCAL run mode.
contacts.
High Amps; Check guide vane drive.
ter temp and flow.
fault source.
amps calibration/reset overload.
Checkdischarge temperatureimmediately.Check sensor for accuracy; check for propercondenser flowand
temperature; check oil reservoir temperature. Check
condenser for fouled tubes or air in chiller. Check for
proper guide vane actuator operation.
Check for proper amount of refrigerant charge; check
for proper water flow and temperatures. Check for
proper guide vane actuator operation.
Check motor temperature immediately. Check sensorfor accuracy.Checkfor proper condenser flow and
temperature. Check motor cooling system for restrictions. Check motor coolingsolenoid for proper operation. Check refrigerant filter.
Check for throttled oil supply isolation valves. Valves
should be wide open. Check oil cooler thermal expansion valve. Check sensor accuracy. Check journaland thrust bearings. Check refrigerant filter.Check
for excessive oil sump level.
Check powerto oil pump and oil level. Check for dirty
filtersor oilfoaming atstart-up. Checkfor thermaloverload cutout. Reduce ramp load rate if foaming noted.
NOTE: This alarm is not related to pressure switch
problems.
Check the oil pressure switch for proper operation.
Check oil pump for proper pressure. Check for excessive refrigerant in oil system.
Checkwiring: Checktorque setting onsolid-state starter.
Check for main circuit breaker trip. Check power supply to PSIO module.
Check 24-vac input on the SMM (terminals 23 and
24).Check transformersto SMM. Check power toPSIO
module. Check distribution bus. Consult power
company.
Perform pumps control test (from CONTROL TEST
table) and verify proper switch operation. Check all
water valves and pump operation.
Checkthe high-pressureswitch. Checkfor propercondenser pressures and condenser water flow. Check
for fouled tubes. Check the 2C aux. contact and the
oil pressure switch in the power panel. This alarm is
not caused by the transducer.
Checkwater flowin condenser.Checkfor fouledtubes.
Transducershould be checkedfor accuracy.Thisalarm
is not caused by the high pressure switch.
Checkwater flowin condenser.Checkfor fouledtubes.
Transducershould be checkedfor accuracy.Thisalarm
is not caused by the high pressure switch.
1CR auxiliary contact opened while chiller was running. Check starter for proper operation.
Run auxiliary contact opened while chiller was running. Check starter for proper operation.
CCN has signaled chiller to stop. Reset and restart
when ready. Ifthe signal wassent by the LID, release
the Stop signal on STATUS01 table.
Sparesafety inputhastripped orfactory-installed jumper
not present.
Checkmotor currentfor proper calibration. Check guide
vane drive and actuator for proper operation.
Check condenser flow and temperatures. Checkconfiguration of surge protection.
Check starter for possible ground fault, reverse rotation, voltage trip, etc.
Reset overloads and reset alarm. Check motor current calibration or overload calibration (do not fieldcalibrate overloads).
90
Page 91
Table 12 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
L. CHILLER PROTECT LIMIT FAULTS (cont)
Excessive numbers of the same fault can lead to severe chiller
damage. Seek service expertise.
PROTECTIVE LIMITLOW GEAR OIL PRESSUREGEAROILP [VALUE] exceeded imit of
PROTECTIVE LIMITHIGH GEAR OIL TEMPGEAOILT [VALUE] exceeded limit of
PROTECTIVE LIMITCCN OVERRIDE STOPCHIL S S CCN. Override stop while in
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by
the operator as an override, alert, or alarm condition. [VALUE] is the actual temperature, pressure, voltage,
etc., at which the control tripped. [OPEN] indicates that an input circuit is open.
RECYCLE ALERTHIGH AMPS AT SHUTDOWNHigh Amps atRecycle: Checkguide vane
SENSOR FAULT ALERTLEAVING COND WATER TEMPSensorFault: Checkleaving condenser
SENSOR FAULT ALERTENTERING COND WATER TEMPSensor Fault: Check entering condenser
LOW OIL PRESSURE
ALERT
AUTORESTART PENDINGPOWER LOSSV P Power Loss: Check voltage
AUTORESTART PENDINGLOW LINE VOLTAGEV P[VALUE]exceeded limit of[LIMIT]*.
AUTORESTART PENDINGHIGH LINE VOLTAGEV P[VALUE]exceeded limitof [LIMIT]*.
SENSOR ALERTHIGH DISCHARGE TEMPCMPD [VALUE] exceeded limit of
SENSOR ALERTHIGH BEARING TEMPMTRB [VALUE] exceeded limit of
SMM Communications FailureCheck thatPSIO communication plugs areconnectedcorrectly.Check SMM
High Oil Temperature While RunningCheck for proper oil level (too much oil). Check water supply to oil cooler.
Blank LID Screen (Minimal Contrast Visible)Increase contrast potentiometer. See Fig. 49. Check red LED on LID for
‘‘Communications Failure’’ Highlighted Message At
Bottom of LID Screen
Control Test DisabledPress the Stop pushbutton. The PIC must be in the OFF mode for the con-
Vanes Will Not Open in Control TestLow pressure alarm is active. Put chiller into PUMPDOWN mode or equal-
Oil Pump Does Not RunCheck oil pump voltage supply. Cooler vessel pressure under vacuum.
LID Default Screen Does Not UpdateThis is normal operation when an alarm is present. The screen freezes the
Chiller Does Not Stop When the STOP Button is PressedThe STOP button wiring connector on the LID module is not properly con-
LID Screen DarkLight bulb burned out. Replace as needed.
Chilled water set point set too high. Access set point on LID and verify.
Capacityoverride or excessive coolingload (chiller atdesigncapacity). Check
LIDstatusmessages. Check foroutsideair infiltration intoconditioned space.
Condenser temperature too high. Check for proper flow, examine cooling
tower operation, check for air or water leaks, check for fouled tubes.
Refrigerant level low. Check for leaks, add refrigerant, and trim charge.
Liquid bypass in waterbox. Examine division plates and gaskets for leaks.
Guide vanes fail to open. Use control test to check operation.
Chilled water control point too high. Access CONTROL ALGORITHM STA-
TUS table, MAINT01 screen, and check chilled water control operation.
Guide vanesfailto open fully.Be sure that the guide vanetargetis released.
Check guide vane linkage. Check limit switch in actuator.Check that sensor
is in the proper terminals.
Chilled water set point set too low. Access set point on LID and verify.
Chilled water control point too low. Access CONTROL ALGORITHM STA-
TUS tables, MAINT01 screen, and check chilled water control for proper
resets.
High discharge temperature keeps guide vanes open.
Guide vanes fail to close. Be sure that guide vane target is released. Check
Loose guide vane drive. Adjust chain drive.
Defective vane actuator. Check using control test feature.
Defective temperature sensor. Check sensor accuracy.
Check for proper oil level (not enough oil).
Check for proper communications wiring on PSIO module. Check that the
COMM1 communications wires from the LID are terminated to the COMM1
PSIO connection. Check for ground or short on CCN system wiring.
communicationplug.Check for proper SMMpower supply.See Control Modules section on page 96.
proper operation, (power supply). If LED is blinking, but green LED’s are
not, replace LID module, (memory failure). Check light bulb if backlit model.
LID is not properly addressed to the PSIO. Make sure that, on ATTACH TO
NETWORK DEVICE screen,.
dress.CheckLEDs on PSIO. Isred LED operating properly?Are greenLEDs
blinking? See Control Module troubleshooting section.
trol test feature to operate. Clear all alarms. Check line voltage percent on
STATUS01 screen. The percent must be within 90% to 110%. Check voltage input to SMM; calibrate starter voltage potentiometer for accuracy.
Turn the controller power off before servicing the controls. This ensures safety and prevents damage to the
controller.
The Processor/Sensor Input/Output module (PSIO), 8-input
(Options) modules, Starter Management Module (SMM),
4-in/2-out module, and the Local Interface Device (LID) module perform continuous diagnostic evaluations of the hardware to determine its condition. Proper operation of all modules
is indicated by LEDs (light-emitting diodes) located on the
side of the LID (Fig. 49); on the top horizontal surface of the
PSIO (Fig. 50), SMM, and 8-input modules; and on the 4-in/
2-out module.
RED LEDs
PSIO Module — If the LED is blinking continuously at a
2-second rate, it is indicating proper operation. If it is lit continuously it indicates a problem requiring replacement of the
module. Off continuously indicates that the power should be
checked. If the red LED blinks 3 times per second, a software error has been discovered and the module must be replaced. If there is no input power, check the fuses and the
circuit breaker. If the fuses are good, check for a shorted
secondary of transformer, or if power is present to the module, replace the module.
4-In/2-Out Module — If the LED is blinking, this module is
operating properly.Asteady red light indicates a module failure. Replace the 4-In/2-Out module.
GREEN LEDs — There are 1 or 2 green LEDs on each type
of module. These LEDs indicate communication status between different parts of the controller and the network modules as follows:
LID Module
Upper LED — Communication with CCN network, if present;
blinks when communication occurs.
Lower LED — Communication with PSIO module; must blink
every 5 to 8 seconds when the LID default screen is
displayed.
PSIO Module
GreenLED Closest to Communications Connection — Com-
munication with SMM and 8-input module; must blink
continuously.
Other Green LED — Communication with LID; must blink
every 3 to 5 seconds.
8-Input Modules and SMM — Communication with PSIO
module; blinks continuously.
4-In/2-Out Module — Communication with PSIO module;
blinks continuously.
NOTE: Address switches on this module can be at any position. Addresses are only changed through the LID screen for CCN.
Fig. 49 — LID Module (Rear View) and
LED Locations
Notes on Module Operation
1. The chiller operator monitors and modifies configurations in the microprocessor through the 4 softkeys and
the LID. Communication with the LID and the PSIO is
accomplished through the CCN bus (COMM1). The communication between the PSIO, SMM, both 8-input modules, and the 4-in/2-out module is accomplished through
the sensor bus (COMM3), which is a 3-wire cable. On
the sensor bus terminal strips, Terminal 1 of the PSIO
module is connected to Terminal 1 of each of the other
modules. Terminals 2 and 3 are connected in the same
manner, except for the connection to the 4-in/2-out module. See Fig. 51.
2. If a green LED is on continuously, check the communication wiring. If a green LED is off, check the red LED
operation. If the red LED is normal, check the module
address switches (Fig. 52-54). Proper addresses are set as
shown below:
If all modules indicate a communications failure, check
the communications plug on the PSIO module for proper
seating.Also check the wiring (CCN bus — 1:red, 2:wht,
3:blk; Sensor bus — 1:red, 2:blk, 3:clr/wht). If a good
connection is assured and the condition persists, replace
the PSIO module.
If only one 8-input module, the SMM, or the 4-in/2-out
module indicates a communication failure, check the communications plug on that module. If a good connection is
assured and the condition persists, replace the module.
All system operating intelligence rests in the PSIO module. Some safety shutdown logic resides in the SMM in
case communications are lost between the 2 modules. The
PSIO monitors conditions using input ports on the PSIO,
the SMM, the 8-input modules, and the 4-in/2-out modules. Outputs are controlled by the PSIO and SMM as
well.
3. Power is supplied to the modules within the control panel.
The transformers are located within the power panel, with
the exception of the SMM, which operates from a 24-vac
power source and has its own 24-vac transformer located
in the starter.
In the power panel, T1 supplies power 21-vac to the LID,
the PSIO, and the 5-vac power supply for the transducers. T3 supplies 24-vac power to the 4-in/2-out module.
T4 is another 21-vac transformer, which supplies power
to both 8-input modules (if present). T4 is capable of supplying power to two modules; if additional modules are
added, another power supply will be required.
Power is connected to Terminals 1 and 2 of the power
input connection on each module.
PSIO (J8)
1
2
3
+
GRD
-
SMM (J5)
1
2
3
+
GRD
-
8-INPUT (J5)
1
GRD
2
3
+
-
8-INPUT (J5)
+
1
GRD
2
-
3
4-IN/2-OUT (J3)
+
1
-
2
GRD
3
NOTE:Address switcheson this module can be at any position.Addresses can
only be changed through the LID or CCN.
Fig. 52 — Processor (PSIO) Module
Starter Management Module (SMM) (Fig. 53)
INPUTS — Inputs on strips J2 and J3 are a mix of analog
and discrete (on/off) inputs. The chiller application determines which terminals are used. Always refer to the individual unit wiring diagram for terminal numbers.
OUTPUTS — Outputs are 24 vdc and wired to strip J1. There
are 2 terminals used per output.
INPUTS — Each input channel has 3 terminals; only 2 of
the terminals are used. The chiller application determines which
terminals are normally used. Always refer to individual unit
wiring diagrams for terminal numbers.
OUTPUTS — Output is 20 vdc. There are 3 terminals per
output, only 2 of which are used, depending on the application. Refer to the unit wiring diagram.
NOTE: SMM address switches should be set as follows: S1 set at 3; S2 set
at 2.
Fig. 53 — Starter Management Module (SMM)
97
Page 98
Options Modules (8-Input) — The options modules
are optional additions to the PIC, and are used to add temperature reset inputs, spare sensor inputs, and demand limit
inputs. Each option module contains 8 inputs, each input meant
for a specific duty. See the wiring diagram for exact module
wire terminations. Inputs for each of the options modules
available include the following:
4 to 20 mA Auto. Demand Reset
4 to 20 mA Auto. Chilled Water Reset
Common Chilled Water Supply Temperature
Common Chilled Water Return Temperature
Remote Temperature Reset Sensor
Spare Temperature 1
Spare Temperature 2
Spare Temperature 3
Terminal block connections are provided on the options
modules. All sensor inputs are field wired and installed.
Options module 1 can be factory or field-installed. Options
module 2 is shipped separately and must be field installed.
For installation, refer to the unit or field wiring diagrams. Be
sure to address the module for the proper module number
(Fig. 54) and to configure the chiller for each feature being
used.
OPTIONS MODULE 1
OPTIONS MODULE 2
4 to 20 mA Spare 1
4 to 20 mA Spare 2
Spare Temperature 4
Spare Temperature 5
Spare Temperature 6
Spare Temperature 7
Spare Temperature 8
Spare Temperature 9
configurations. The inputs monitor the gear oil temperature
and pressure. InputAI#2 should be factory-set with the jumper
on (T). Inputs AI#3, and AI#4 should be factory set on (V).
OUTPUTS — The two analog outputs are each configurable
by on-board jumpers as 0 to 10 vdc (maximum current:
10 mA) or 4 to 20 mA (maximum load: 600 ohms) outputs.
The outputs control the relay that activates the gear oil pump
starter. Outputs AO#1 and AO#2 should be factory set with
the jumper on (V).
This module has a field-configurable DIP (dual in-line package) switch to designate its address. It should be factory set
with the following switches open: 1, 2, 3, 4, 6, and 8. Switches
5 and 7 should be closed.
Note the SIO bus wiring for this module. Unlike the standard PIC modules, Pin 2 is negative and Pin 3 is the ground
(or common). See Fig. 51.
Replacing Defective Processor Modules — The
replacement part number is printed on a small label on the
front of the PSIO module. The model and serial numbers are
printed on the unit nameplate located on an exterior corner
post. The proper software is factory-installed by Carrier in
the replacement module. When ordering a replacement processor module (PSIO), specify complete replacement part number, full unit model number, and serial number. This new
unit requires reconfiguration to the original chiller data by
the installer. Follow the procedures described in the Set Up
Chiller Control Configuration section on page 54. Electrical
shock can cause personal injury.Disconnect all electrical power
before servicing.
SWITCH SETTINGOPTIONS MODULE 1OPTIONS MODULE 2
S167
S242
Fig. 54 — Options Module
Four-In/Two-Out Module (Fig. 55)
INPUTS — The four analog inputs each have 3 terminals
and are configurable by movable on-board jumpers as thermistor (T), 4 to 20 mA (C), or 0 to 10 vdc (V)
Electrical shock can cause personal injury. Disconnect
all electrical power before servicing.
INSTALLATION OF NEW PSIO MODULE
1. Verify that the existing PSIO module is defective by using the procedure described in the Notes on Module Operation section, page 96, and the Control Modules section, page 96. Do not access theATTACHTO NETWORK
DEVICE screen if the LID displays a communication
failure.
2. Data regarding the PSIO configuration should have been
recorded and saved. This data must be reconfigured into
the LID. If this data is not available, follow the procedures described in the Set Up Chiller Control Configuration section, page 54. Record the TOTAL COMPRES-SOR STARTSand the COMPRESSOR ONTIME from the
STATUS01 table on the LID.
If a CCN Building Supervisor or Service Tool is present,
the module configuration should have already been uploaded into memory; then, when the new module is installed, the configuration can be downloaded from the
computer (if the software version is the same).
Any communication wires from other chillers or CCN
modules must be disconnected.
3. Check that all power to the unit is off. Carefully disconnect all wires from the defective module by unplugging the 6 connectors. It is not necessary to remove any
of the individual wires from the connectors.
4. Remove the defective PSIO by removing its mounting
screw with a long-shaft Phillips screwdriver and removing the module from the control box. Save the screw for
later use. The green ground wire is held in place with
the module mounting screw.
5. Package the defective module in the carton of the new
module for return to Carrier.
98
Page 99
6. Restore control system power (the LID displays, COMMUNICATION FAILURE at the bottom of the screen).
7. Access the SERVICE menu. Highlight and select
the ATTACH TO NETWORK DEVICE screen. Press
the ATTACH softkey. (The LID displays, UPLOADING TABLES. PLEASE WAIT; then, COMMUNICA-
TION FAILURE.) Press the EXIT
8. Turn off control power.
9. Mount the new module in the unit control box using a
long-shaft Phillips screwdriver and the screw saved in
Step 4 on page 98. Make sure that the green grounding
wire is reinstalled along with the mounting screw.
10. Connect the LID communication wires (CCN bus) and
the power wires. If CCN wiring has been attached to the
CCN bus, disconnect the wires. Attach the sensor bus
plug and the input and output plugs.
11. Carefully check all wiring connections before restoring
power.
12. Restore control power and verify that the red and green
LEDs on the PSIO are functioning properly.
13. The LID should indicate AVAILABLE MEMORY and
a value. This value should start to decrease. (If it does
not, check the LID wiring to the PSIO; ensure connection to the proper plug.) The bottom of the screen displays, UPLOADING TABLES, PLEASE WAIT.
14. After the PSIO tables have been uploaded into the LID,
access the STATUS01 screen. Move the highlight bar to
the TOTAL COMPRESSOR STARTS line. Press the
SELECT
DECREASE
softkey and then, using the INCREASE or
softkeys, change the value until it is the
softkey.
same as the value from the old module. Press the
ENTER
15. Move the highlight bar to the COMPRESSORONTIME line. Press the SELECT
ing the INCREASE
this value until it matches the old module run hours. Press
the SELECT
16. Change the address of the PSIO In the CONTROLLER
IDENTIFICATION table back to its previous value. Write
the address on the PSIO.
17. Use the configuration sheets (pages CL-3 to CL-11) to
input set point, configuration, and schedule information
into the PSIO. The TIME AND DATE table from the
SERVICE menu must also be set. A Building Supervisor terminal can be used to download the old configuration into the PSIO.
18. Access the CONTROL TEST table and perform the control tests to verify all that all tested functions are working properly.
If the software version has been updated, a CCN download of the configuration will not be allowed. Configure
the PSIO by hand, and upload the PSIO into the network using the ATTACH TO NETWORK DEVICE
screen.
19. Restore the chiller to normal operation; calibrate the motor amps.
softkey to save this value.
softkey and the, us-
or DECREASE softkeys, change
softkey to save this value.
PHYSICAL DATA AND WIRING
SCHEMATICS
Tables 15-26 and Fig. 56-61 provide additional information regarding compressor fits and clearances, physical and
electrical data, and wiring schematics for operator convenience during troubleshooting.
Fig. 55 — 4-In/2-Out Module
99
Page 100
Fig. 56 — Model Number Nomenclature for Compressor Size (See Fig. 1 Also)
Table 15 — 17EX Heat Exchanger Economizer/Storage Vessel, Piping, and Pumpout Unit Weights*
configuration is used, referto Tables16 and 17to obtainthe additional dryand
water weights that must be added to the values shown in this table.
†Cooler and condenser weights shown are based on 2-pass, nozzle-in-head
(NIH) waterboxes with 150 psig (1034 kPa) covers. Includes components attached to cooler, but does not include suction/discharge, elbow, or other
interconnecting piping.
CONDENSER TOTAL WEIGHTCONDENSER CHARGE
Dry**Operating††RefrigerantWater
lbkglbkglbkglbkg
**Dryweight includesall components attached to economizer:covers, floatvalves,
brackets, control center (31 lb [14 kg]), and power panel (20 lb [9 kg]). Dry
weight does not include compressor weight, motor weight, or pumpout condensing unit weight. The pumpout condensing unit weight is 210 lb (95 kg).
For compressor and motor weights, refer to Tables 18 and 20A and 20B.
††Operating weight includes dry weight, refrigerant weight, and water weight.