Carrier 17EX User Manual

17EX
Externally Geared Centrifugal Liquid Chillers
50/60 Hz
1500 to 2250 Nominal Tons (5280 to 7910 kW)
Start-Up,Operation,andMaintenanceInstructions
SAFETY CONSIDERATIONS
Centrifugal liquid chillers are designed to provide safe and reliable service when operated within design speci­fications. When operating this equipment, use good judg­ment and safety precautions to avoid damage to equip­ment and property or injury to personnel.
Be sure you understand and follow the procedures and safety precautions contained in the chiller instructions as well as those listed in this guide.
DO NOT VENT refrigerant relief valves within a building. Outlet from rupture disc or relief valve must be vented outdoors in ac­cordance with the latest edition of ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning Engineers) 15. The accumulation of refrigerant in an enclosed space can displace oxy­gen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ASHRAE 15, especially for enclosed and low overhead spaces. Inhalation of high concentrations of vapor is harmful and may cause heart irregulari­ties, unconsciousness, or death. Misuse can be fatal.Vaporisheavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a chiller for any purpose. Oxygen gas reacts violently with oil, grease, and other common substances.
NEVER EXCEED specified test pressures, VERIFY the allowable test pressure by checking the instruction literature and the design pressures on the equipment nameplate.
DO NOT USE air for leak testing. Use only refrigerant or dry nitrogen.
DO NOT VALVE OFF any safety device. BE SURE that all pressure relief devices are properly installed and
functioning before operating any machine.
DO NOT WELD OR FLAME CUT any refrigerant line or vessel until all refrigerant (liquid andvapor)hasbeenremovedfromchiller. Traces of vapor should be displaced with dry air or nitrogen and the work area should be well ventilated. Refrigerant in contact with
an open flame produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig chiller sections or the entire assembly.
DO NOT work on high-voltage equipment unless you are a quali­fied electrician.
DO NOTWORKON electrical components, including control pan­els, switches, starters, or oil heater until you are sure ALLPOWER IS OFF and no residual voltage can leak from capacitors or solid­state components.
LOCK OPENANDTAGelectrical circuits during servicing.IF WORK IS INTERRUPTED, confirm that all circuits are deenergized be­fore resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it into the eyes. USE SAFETY GOGGLES. Wash any spills from the skin with soap and water .If any enters the eyes, IMMEDIATELYFLUSH EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refrigerant cyl­inder. Dangerous overpressure can result. When necessary to heat refrigerant, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or attempt to refill them. It is DANGEROUS AND ILLEGAL. When cylinder is emptied, evacuate remaining gas pressure, loosen the collar and unscrew and discard the valve stem. DO NOT INCINERATE.
CHECK THE REFRIGERANT TYPE before adding refrigerant to the chiller.The introduction of the wrong refrigerant can cause dam­age or malfunction to this chiller.
Operation of this equipment with refrigerants other than those cited herein should comply withASHRAE-15 (latest edition). Con­tact Carrier for further information on use of this chiller with other refrigerants.
DO NOTATTEMPTTO REMOVE fittings, covers,etc., while chiller is under pressure or while chiller is running. Be sure pressure is at 0 psig (0 kPa) before breaking any refrigerant connection.
CAREFULLY INSPECT all relief devices, rupture discs, and other relief devices AT LEAST ONCE A YEAR. If chiller operates in a corrosive atmosphere, inspect the devices at more frequent intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief device when corrosion or build-up of foreign material (rust, dirt, scale, etc.) is found within the valve body or mechanism. Replace the device.
DO NOT install relief devices in series or backwards. USE CARE when working near or in line with a compressed spring.
Sudden release of the spring can cause it and objects in its path to act as projectiles.
RUN WATERPUMPS when removing, transferring, or charg­ing refrigerant.
DO NOT STEP on refrigerant lines. Broken lines can whip about and cause personal injury.
DO NOT climb over a chiller. Use platform, catwalk, or staging. Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move inspection covers or other heavy components. Even if com­ponents are light, use such equipment when there is a risk of slip­ping or losing your balance.
BE AWARE that certain automatic start arrangements CAN EN­GAGE THE STARTER. Open the disconnect ahead of the starter in addition to shutting off the machine or pump.
USE only repair or replacement parts that meet the code require­ments of the original equipment.
DO NOTVENT OR DRAIN waterboxes containingindustrial brines, liquid, gases, or semisolids without permission of your process con­trol group.
DO NOT LOOSEN waterbox cover bolts until the waterbox has been completely drained.
DO NOT LOOSEN a packing gland nut before checking that the nut has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for cor­rosion, rust, leaks, or damage.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5d
PC 211 Catalog No. 531-721 Printed in U.S.A. Form 17EX-1SS Pg 1 7-97 Replaces: New
CONTENTS
Page
Page
SAFETY CONSIDERATIONS ......................1
INTRODUCTION ABBREVIATIONS 17EX CHILLER FAMILIARIZATION
Chiller Identification Label System Components Cooler Condenser Compressor Control Center Motor Starter (Purchased Separately) Economizer/Storage Vessel
REFRIGERATION CYCLE OIL COOLING CYCLE
Compressor Oil Cooling External Gear Oil Cooling LUBRICATION CYCLE Compressor Lubrication Cycle External Gear Lubrication Cycle
STARTERS CONTROLS
Definitions
........................................5
................................5
...............................5
.................5
.......................5
............................5
....................................5
...................................5
.................................5
..............5
......................5
.......................5-8
...........................8
.........................8
........................8
..........................8,9
...................8
..................9
....................................9
.................................11-43
....................................11
ANALOG SIGNAL
DIGITAL SIGNAL
VOLATILE MEMORY
General PIC System Components
......................................11
.......................12
PROCESSOR/SENSOR INPUT/OUTPUT MODULE (PSIO)
STARTER MANAGEMENT MODULE (SMM)
LOCAL INTERFACE DEVICE (LID)
SIX-PACK RELAY BOARD
EIGHT-INPUT MODULES
FOUR-IN/TWO-OUT (4-IN/2-OUT) MODULE
OIL HEATER CONTACTOR (1C)
COMPRESSOR OIL PUMP CONTACTOR (2C) AND GEAR
OIL PUMP CONTACTOR (5C)
HOT GAS BYPASS CONTACTOR RELAY (3C) (Optional)
OIL AUXILIARY RELAY (4C)
CONTROL TRANSFORMERS (T1-T4)
CONTROL AND OIL HEATER VOLTAGE
SELECTOR (S1)
OIL DIFFERENTIAL PRESSURE/POWER SUPPLY
MODULE
LID Operation and Menus
.......................16
GENERAL
ALARMS AND ALERTS
LID DEFAULT SCREEN MENU ITEMS
MENU STRUCTURE
TO VIEW OR CHANGE POINT STATUS
OVERRIDE OPERATIONS
TO VIEW OR CHANGE TIME SCHEDULE OPERATION
TO VIEW AND CHANGE SET POINTS
SERVICE OPERATION
PIC System Functions
..........................32
CAPACITY CONTROL
ENTERING CHILLED WATER CONTROL
DEADBAND
PROPORTIONAL BANDS AND GAIN
DEMAND LIMITING
CHILLER TIMERS
OCCUPANCY SCHEDULE
Safety Controls
...............................33
SHUNT TRIP
Default Screen Freeze .........................33
Auxiliary Compressor Oil Pump Control Auxiliary Gear Oil Pump Control Shaft Seal Oil Control Ramp Loading Control Capacity Override High Discharge Temperature Control Oil Sump Temperature Control Oil Cooler Remote Start/Stop Controls Spare Safety Inputs Spare Alarm Contacts Condenser Pump Control Condenser Freeze Prevention Tower-Fan Relay Auto. Restart After Power Failure Water/Brine Reset Demand Limit Control, Option (Requires Optional
8-Input Module) Surge Prevention Algorithm Surge Protection Lead/Lag Control
....................................36
..........................33
.........................33
.............................35
..................35
.....................36
...........................36
.........................36
......................36
...................36
..............................36
.............................37
.............................37
....................37
..............................38
.............................38
..........33
................33
.............35
................36
COMMON POINT SENSOR INSTALLATION
CHILLER COMMUNICATION WIRING
LEAD/LAG OPERATION
FAULTED CHILLER OPERATION
LOAD BALANCING
AUTO. RESTART AFTER POWER FAILURE
Ice Build Control
..............................40
ICE BUILD INITIATION
START-UP/RECYCLE OPERATION
TEMPERATURE CONTROL DURING ICE BUILD
TERMINATION OF ICE BUILD
RETURN TO NON-ICE BUILD OPERATIONS
Attach to Network Device Control
...............41
ATTACHING TO OTHER CCN MODULES
Service Operation
.............................42
TO ACCESS THE SERVICE SCREENS
TO LOG OFF
HOLIDAY SCHEDULING
START-UP/SHUTDOWN/RECYCLE SEQUENCE Local Start-Up Shutdown Sequence Automatic Soft Stop Amps Threshold Chilled Water Recycle Mode Safety Shutdown
BEFORE INITIAL START-UP Job Data Required Equipment Required Using the Economizer/Storage Vessel and Pumpout
System Remove Shipping Packaging
................................43
...........................44
............44
....................44
..............................45
...................45-57
............................45
...........................45
....................................45
...................45
...43-45
MOTOR
EXTERNAL GEAR
Motor Electrical Connection Motor Auxiliary Devices Open Oil Circuit Valves Tighten All Gasketed Joints and Guide Vane
Shaft Packing Check Chiller Tightness Refrigerant Tracer Leak Test the Chiller Standing Vacuum Test Chiller Dehydration
...............................46
.............................46
...........................46
............................49
....................45
........................46
........................46
........................46
.........................49
2
CONTENTS
Page
Page
Inspect Water Piping ..........................50
Check Optional Pumpout Compressor Water
Piping Check Relief Devices Inspect Wiring
....................................50
..........................50
................................50
CHECK INSULATION RESISTANCE
Motor Pre-Start Checks External Gear Pre-Start Checks Carrier Comfort Network Interface Check Starter
.................................53
........................51
.................51
...............53
MECHANICAL STARTERS
SOLID-STATE STARTERS
Compressor Oil Charge Power Up the Controls and
Check the Compressor Oil Heater
........................54
.............54
SOFTWARE VERSION
Set Up Chiller Control Configuration Input the Design Set Points Input the Local Occupied Schedule
(OCCPC01S)
Input Service Configurations
................................54
.....................54
....................54
.............54
PASSWORD
INPUT TIME AND DATE
CHANGE LID CONFIGURATION IF NECESSARY
MODIFY CONTROLLER IDENTIFICATION IF
NECESSARY
INPUT EQUIPMENT SERVICE PARAMETERS IF
NECESSARY
MODIFY EQUIPMENT CONFIGURATION IF
NECESSARY
CHECK VOLTAGE SUPPLY
PERFORM AN AUTOMATED CONTROL TEST
Check Pumpout System Controls and Optional
Pumpout Compressor High Altitude Locations Charge Refrigerant Into Chiller
........................56
........................57
..................57
TRIMMING REFRIGERANT CHARGE
INITIAL START-UP Preparation Manual Operation of the Guide Vanes Dry Run to Test Start-Up Sequence Check Motor Rotation
...........................57-62
..................................57
............58
..............58
.........................58
INITIAL MOTOR START-UP
Disc Coupling Installation and Alignment
.........59
IMPORTANT INFORMATION
Check Oil Pressure and Compressor Stop Calibrate Motor Current Demand Setting To Prevent Accidental Start-Up Hot Alignment Check Doweling Check Chiller Operating Condition Instruct the Operator
....................................61
.........................61
..........................62
..................61
...............61
........61
..........61
COOLER-CONDENSER
ECONOMIZER/STORAGE VESSEL
PUMPOUT SYSTEM
COMPRESSOR ASSEMBLY
COMPRESSOR LUBRICATION SYSTEM
EXTERNAL GEAR LUBRICATION SYSTEM
CONTROL SYSTEM
AUXILIARY EQUIPMENT
CHILLER CYCLES
MAINTENANCE
SAFETY DEVICES AND PROCEDURES
CHECK OPERATOR KNOWLEDGE
THIS MANUAL
OPERATING INSTRUCTIONS Operator Duties
...............................62
..................62,63
Prepare the Chiller for Start-Up .................62
Starting the Chiller Check the Running System Stopping the Chiller After Limited Shutdown Extended Shutdown After Extended Shutdown Cold Weather Operation Manual Guide Vane Operation Refrigeration Log
PUMPOUT AND REFRIGERANT TRANSFER
PROCEDURES Preparation Operating the Optional Pumpout
Compressor
..................................63
........................... 62
.....................62
...........................62
........................63
...........................63
......................63
........................63
...................63
.............................63
............................63-67
................................63
READING REFRIGERANT PRESSURES
Transferring Refrigerant into the
Economizer/Storage Vessel Transferring Refrigerant into
the Cooler/Condenser/Compressor Section Return Chiller to Normal Operating
Conditions GENERAL MAINTENANCE
Refrigerant Properties Adding Refrigerant Removing Refrigerant Adjusting the Refrigerant Charge Refrigerant Leak Testing Leak Rate Test After Service, Repair, or Major Leak
.................................67
............................67
....................................67
...................66
.....67
....................67-75
.........................67
.........................67
................67
.......................67
.........67
REFRIGERANT TRACER
TO PRESSURIZE WITH DRY NITROGEN
Repair the Leak, Retest, and Apply
Standing Vacuum Test Checking Guide Vane Linkage Contact Seal Maintenance
.......................68
..................68
......................68
SEAL DISASSEMBLY
SEAL REASSEMBLY
Chiller Alignment
.............................71
ALIGNMENT METHODS
PRELIMINARY ALIGNMENT
NEAR FINAL ALIGNMENT
FINAL ALIGNMENT
HOT ALIGNMENT CHECK
DOWELING
WEEKLY MAINTENANCE Check the Lubrication System
SCHEDULED MAINTENANCE Service Ontime Inspect the Control Center Check Safety and Operating Controls Monthly Changing the Oil Filters
...............................76
.......................76
..................76
..................76-83
.....................76
.....76
........................76
COMPRESSOR OIL FILTER
EXTERNAL GEAR OIL FILTER
Oil Specifications Oil Changes
.............................77
..................................77
COMPRESSOR OIL
EXTERNAL GEAR OIL
MOTOR SLEEVE BEARING AND PUMPOUT
COMPRESSOR OIL
Inspect Refrigerant Float System Inspect Relief Valves and Piping Coupling Maintenance Motor Maintenance
........................78
............................78
................78
................78
CLEANLINESS
SLEEVE BEARINGS
3
CONTENTS (cont)
Page
Page
Motor Handling/Rigging ........................81
Motor Storage External Gear Storage
................................81
.........................81
SHORT-TERM STORAGE (Indoors)
LONG-TERM STORAGE (Indoors)
EXTENDED DOWNTIME
Compressor Bearing Maintenance External Gear Maintenance Inspect the Heat Exchanger Tubes
...............82
.....................82
...............82
COOLER
CONDENSER
Water Leaks Water Treatment Inspect the Starting Equipment Check Pressure Transducers Pumpout System Maintenance
..................................82
..............................82
.................83
...................83
..................83
OPTIONAL PUMPOUT COMPRESSOR OIL CHARGE
PUMPOUT SAFETY CONTROL SETTINGS
Ordering Replacement Chiller Parts
..............83
MOTOR REPLACEMENT PARTS
EXTERNAL GEAR REPLACEMENT PARTS
TROUBLESHOOTING GUIDE Overview Checking the Display Messages Checking Temperature Sensors
....................................83
..................83-99
.................84
.................84
RESISTANCE CHECK
VOLTAGE DROP
CHECK SENSOR ACCURACY
DUAL TEMPERATURE SENSORS
Checking Pressure Transducers ................84
OIL DIFFERENTIAL PRESSURE/POWER SUPPLY
MODULE CALIBRATION
TROUBLESHOOTING TRANSDUCERS
TRANSDUCER REPLACEMENT
Control Algorithms Checkout Procedure Control Test Control Modules
.................................85
..............................96
.........85
RED LEDs
GREEN LEDs
Notes on Module Operation Processor/Sensor Input/Output Module (PSIO)
....................96
....97
INPUTS
OUTPUTS
Starter Management Module (SMM)
..............97
INPUTS
OUTPUTS
Options Modules (8-Input) Four-In/Two-Out Module
.....................98
.......................98
INPUTS
OUTPUTS
Replacing Defective Processor Modules
.........98
INSTALLATION OF NEW PSIO MODULE
PHYSICAL DATA AND WIRING SCHEMATICS INDEX
INITIAL START-UP CHECKLIST FOR 17EX
....................................115-120
EXTERNALLY GEARED CENTRIFUGAL LIQUID CHILLER
..........................CL-1 to CL-12
....99-114
4
INTRODUCTION
Before initial start-up of the 17EX unit, those involved in the start-up, operation, and maintenance should be thor­oughly familiar with these instructions and other necessary job data. This book is outlined so that you may become fa­miliar with the control system before performing start-up pro­cedures. Procedures in this manual are arranged in the se­quence required for proper chiller start-up and operation.
This unit uses a microprocessor controlled system. Do not short or jumper between terminations on circuit boards or modules; control or board failure may result.
Be aware of electrostatic discharge (static electricity) when handling or making contact with circuit boards or mod­ule connections. Always touch a chassis (grounded) part to dissipate body electrostatic charge before working in­side the control center.
Use extreme care when handling tools near boards and when connecting or disconnecting terminal plugs. Circuit boards can easily be damaged. Always hold boards by the edges and avoid touching components and connections.
This equipment uses, and can radiate, radio frequency energy. If not installed and used in accordance with the instruction manual, it may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environ­ment. Operation of this equipment in a residential area is likely to cause interference, in which case the user, at his own expense, will be required to take whatever mea­sures may be required to correct the interference.
Always store and transport replacement or defective boards in anti-static shipping bag.
ABBREVIATIONS
Frequently used abbreviations in this manual include:
CCN — Carrier Comfort Network CCW — Counterclockwise CHW — Chilled Water CHWR — Chilled Water Return CHWS — Chilled Water Supply CW — Clockwise ECW — Entering Chilled Water ECDW — Entering Condenser Water EMS — Energy Management System HGBP — Hot Gas Bypass I/O — Input/Output LCD — Liquid Crystal Display LCDW — Leaving Condenser Water LCW — Leaving Chilled Water LED — Light-Emitting Diode LID — Local Interface Device OLTA — Overload Trip Amps PIC — Product Integrated Control PSIO — Processor Sensor Input/
Output Module RLA — Rated Load Amps SCR — Silicon Control Rectifier SMM — Starter Management Module TXV — Thermostatic Expansion Valve
17EX CHILLER FAMILIARIZATION
Chiller Identification Label (Fig. 1) —
tification label is located on the right side of the chiller con­trol center panel. The label contains information on model number, refrigerant charge, rated voltage, etc.
The iden-
System Components (Fig. 2) — The components
include the cooler and condenser heat exchangers in sepa­rate vessels, compressor,compressorandgear lubrication pack­ages, control center,speedincreasereconomizer/storage vessel, motor, and starter. The compressor drive consists of an ex­ternal gear (speed increaser) and an electric motor. All con­nections from pressure vessels have external threads to en­able each component to be pressure tested with a threaded pipe cap during factory assembly.
Cooler — This vessel (also known as the evaporator) is
located underneath the condenser, next to the economizer/ storage vessel. The cooler is maintained at lower tempera­ture and pressure so that evaporating refrigerant can remove heat from water flowing through its internal tubes.
Condenser — The condenser operates at a higher tem-
perature and pressure than the cooler and has water flowing through its internal tubes in order to remove heat from the refrigerant.
Compressor — This component maintains system tem-
perature and pressure differences and moves the heat­carrying refrigerant from the cooler to the condenser.
Control Center — The control center is the user inter-
face for controlling the chiller and regulates the chiller ca­pacity as required to maintain proper leaving chilled water temperature. The control center:
• registers cooler, condenser, and lubricating system pressures
• shows chiller operating and alarm shutdown conditions
• records the total chiller operating hours and how many hours the chiller has been running
• sequences chiller start, stop, and recycle under micro­processor control
• provides access to other CCN (Carrier Comfort Network) devices
MotorStarter (Purchased Separately) — The starter
allows the proper start and disconnect of electrical energy for the compressor-motor, oil pump, oil heater, and control panels.
Economizer/Storage Vessel — During normal op-
eration, this vessel functions as an economizer,returning flash gas to the second stage of the compressor and increasing the efficiency of the refrigeration cycle. During periods of shut­down and service, the economizer/storage vessel can serve as a storage tank for the refrigerant.
REFRIGERATION CYCLE (Fig. 3)
The 17EX chiller can be used to chill either water or brine. The data in this book applies to either application. Appli­cations using corrosive brines may require using special tubes, tubesheet, and waterbox materials which are special order items.
5
LEGEND NIH — Nozzle-In-Head *Any available cooler size can be combined with any available condenser size.
NOTE: For details on motor size designations, see below.
ASME
‘U’ STAMP
ARI (Air Conditioning
and Refrigeration
Institute)
PERFORMANCE
CERTIFIED
(60 Hz Only)
Fig. 1 — Model Number Identification
6
40
39
38
37
36
35
1 2 3 4 5 6 7 8 9 10 11 12 13 14
15
34
1—Condenser 2—Cooler Suction Pipe 3—Compressor Suction Elbow 4—Guide Vane Actuator 5—Condenser Discharge Pipe 6—Compressor Discharge Elbow 7—Two-Stage Compressor 8—Economizer Gas Line to Compressor
9—Compressor Housing Access Cover 10 — High-Speed Coupling (Hidden) 11 — External Gear (Speed Increaser) 12 — Low-Speed Coupling (Hidden) 13 — Open-Drive Compressor Motor 14 — Compressor Motor Terminal Box 15 — Low-Side Float Box Cover 16 — Gear Oil Pump 17 — Gear Oil Cooler/Filter 18 — Refrigerant Charging/Service Valve 19 — Refrigerant Liquid Line to Cooler 20 — Power Panel 21 — Oil Level Sight Glasses (2)
33
32
31
17EX WITH EXTERNAL GEAR (SPEED INCREASER)
Fig.2—Typical 17EX Chiller Components
30
LEGEND
29
26
22 — Oil Drain and Charging Valve 23 — Oil Heater (Hidden) 24 — Compressor Oil Pump 25 — Compressor Oil Cooler/Filter 26 — Local Interface Display Control Panel 27 — Cooler Relief Valves (Behind Compressor,
28 — Economizer Storage Vessel 29 — Economizer/Storage Vessel Relief Valves 30 — Pumpout Unit 31 — Cooler 32 — High Side Float Box Cover 33 — Cooler Waterbox Drain 34 — Take-Apart Connections 35 — Cooler Marine Waterbox 36 — Cooler Waterbox Vent 37 — Condenser Waterbox Drain 38 — Refrigerant Liquid Line to Economizer/
39 — Condenser Marine Waterbox 40 — Condenser Waterbox Vent
27
28
25
24
Hidden)
Storage Vessel
22
23
20
21
17
18
19
16
7
The chiller compressor continuously draws large quanti­ties of refrigerant vapor from the cooler at a rate determined by the amount of guide vane opening. This compressor suc­tion reduces the pressure within the cooler, allowing the liq­uid refrigerant to boil vigorously at a fairly low temperature (typically 38 to 42 F [3 to 6 C]).
The liquid refrigerant obtains the energy needed to va­porize by removing heat from the water or brine in the cooler tubes. The cold water or brine can then be used in air con­ditioning and/or other processes.
After removing heat from the water or brine, the refrig­erant vapor enters the first stage of the compressor, is compressed, and flows into the compressor second stage. Here it is mixed with flash-economizer gas and is further compressed.
Compression raises the refrigerant temperature above that of the water flowing through the condenser tubes. When the warm (typically 98 to 102 F [37 to 40 C]) refrig­erant vapor comes into contact with the condenser tubes, the relatively cool condensing water (typically 85 to 95 F [29 to 35 C]) removes some of the heat, and the vapor con­denses into a liquid.
The liquid refrigerant passes through an orifice into the FLASC chamber.The coolest condenser water flows through the FLASC and allows a lower saturated temperature and pressure. Part of the entering liquid refrigerant will flash to vapor once it has passed through the FLASC orifice, thereby cooling the remaining liquid. The vapor is then recondensed by the condenser water flowing through the FLASC chamber.
The subcooled liquid refrigerant drains into a high-side valve chamber that meters the refrigerant liquid into a flash economizer chamber. Pressure in this chamber is interme­diate between condenser and cooler pressures. At this lower pressure, some of the liquid refrigerant flashes to gas, fur­ther cooling the remaining liquid. The flash gas, having ab­sorbed heat, is returned directly to the compressor second stage. Here it is mixed with discharge gas that is already com­pressed by the first-stage impeller. Since the flash gas has to pass through only half the compression cycle to reach con­denser pressure, there is a savings in power.
The cooled liquid refrigerant in the economizer is me­tered through the low-side valve chamber, reducing the re­frigerant pressure. Pressure in the cooler is lower than in the economizer. Some of the liquid flashes as it passes through the low side float valve. The cycle is now complete.
OIL COOLING CYCLE
Compressor Oil Cooling —
water cooled. Water flow through the oil cooler is manually adjusted by a plug valve to maintain an operating tempera­ture at the reservoir of approximately 145 F (63 C). An oil heater in the reservoir helps to prevent oil from being di­luted by the refrigerant. The heater is controlled by the PIC (Product Integrated Control) and is energized when the oil temperature is outside the operating temperature range of 150 to 160 F (66 to 71 C).
The compressor oil is
External Gear Oil Cooling — The external gear oil
is also water cooled. Water flow through the gear oil cooler is manually adjusted by a plug valve to maintain an oper­ating temperature of approximately 130 F (54 C). If so equipped, an oil heater in the reservoir helps to maintain the oil tem­perature under cold ambient operating conditions. The heater is controlled by an internal thermostat.
LUBRICATION CYCLE
Compressor Lubrication Cycle (Refer to item numbers shown in Fig. 4) —
pump and oil reservoir are contained in the compressor base. Oil is pumped through an oil cooler and filter to remove heat and any foreign particles. A portion of the oil is then di­rected to the shaft-end bearing and the shaft seal. The bal­ance of the oil lubricates the thrust and journal bearings and the thrust end seal. The bearing and transmission oil returns directly to the reservoir to complete the cycle. Contact-seal oil leakage, however,iscollected in an atmospheric float cham­ber to be pumped back to the main reservoir as the oil accumulates.
Oil may be charged into the compressor oil reservoir (Item 8) through a charging valve (Item 6) which also func­tions as an oil drain. If there is refrigerant in the chiller, how­ever, a hand pump will be required for charging at this connection.
An oil-charging elbow (Item 3) on the seal-oil return cham­ber allows oil to be added without pumping. The seal-oil re­turn pump (Item 4) automatically transfers the oil to the main reservoir. Sight glasses (11) on the reservoir wall permit ob­servation of the oil level.
Amotor-drivenoil pump (Item 10) discharges oil to an oil cooler/filter (Item 16) at a rate and pressure controlled by an oil regulator (Item 10). The differential oil pressure (bearing supply versus oil reservoir) is registered on the control panel.
Water flow through the oil cooler is manually adjusted by a plug valve (Item 17) to maintain the oil at an operating temperature of approximately 145 F (63 C). During shut­down, the oil temperature is also maintained at 150 to 160 F (65 to 71 C) by an immersion heater (Item 7) in order to minimize absorption of refrigerant by the oil.
Upon leaving the cooler section of the oil cooler/filter, the oil is filtered (Item 15) and a portion is directed to the seal­end bearing (Item 1) and the shaft seal (Item 2). The remain­der lubricates thrust (Item 14) and journal bearings (Item 12). Thrust bearing temperature is indicated on the PIC controls. Oil from both circuits returns by gravity to the reservoir.
The shaft seal of the open compressor drive must be kept full of lubrication oil, even when the chiller is not operating, to prevent loss of refrigerant.
If the chiller is not operating and the oil pump has not operated during the last 12 hours, the control system auto­matically runs the oil pump for one minute in order to keep the contact seal filled with oil.
IMPORTANT: If the control power is to be deener­gized for more than one day,the chiller refrigerant should be pumped over to the economizer/storage vessel.
The compressor oil
8
LEGEND
TXV — Thermostatic Expansion Valve
*The FX compressor and the gear have a water cooled oil cooler.
Liquid Liquid/Vapor Vapor
Fig. 3 — Refrigeration, Cycle
External Gear Lubrication Cycle (Refer to Item numbers shown in Fig. 5) —
tained in the gear base.The external gear oil pump is mounted below the gear with the cooler/filter. Oil is pumped through an oil cooler/filter to remove heat and any foreign particles. A portion of the oil is directed to the gear bearings and gear mesh spray.The remainder is bypassed to the sump. The bear­ing and transmission oil returns directly to the reservoir to complete the cycle.
Oil may be charged into the external gear oil reservoir as described in the section, External Gear Pre-Start Checks, page 51. Observe the oil level in the oil level glass (Item 4) on the reservoir wall.
A motor driven oil pump (Item 10) discharges oil to the oil cooler/filter (Item 12). The pump has an internal pressure regulator to protect the pump in the event of an obstruction downstream. Water flow through the oil cooler is manually adjusted by a plug valve (Item 14) to maintain the oil at an operating temperature of approximately 130 F (54 C).
Oil reservoir is con-
Upon leaving the cooler section (Item 13) of the oil cooler/ filter, the oil is filtered (Item 11) and is directed to the pres­sure control valve (Item 7). Before entering the pressure control valve, the oil pressure (Item 16) and temperature (Item 8) are monitored by the PIC.
A portion of the oil then lubricates the gear bearings (Item 2). Another portion is directed through an orifice (Item 5) to the gear mesh spray (Item 3) to lubricate the gear mesh (Item 1) during operation. Oil from both circuits re­turns by gravity to the reservoir.
STARTERS
All starters, whether supplied by Carrier or the customer, must meet Carrier Starter Specification Z-375. This speci­fication can be obtained from a Carrier Sales Representa­tive. The purpose of this specification is to ensure the com­patibility of the starter and the chiller.Many styles of compatible starters are available, including solid-state , auto-transformer, full-voltage, and, in the case of low-voltage main power sup­ply, wye-delta closed transition.
9
13
COMPRESSOR OIL PRESSURE LEAVING FILTER LINE
12
JOURNAL BEARING
CHECK VALVE
15
OIL FILTER
16
OIL COOLER/ FILTER
17
PLUG VALVE
SHAFT DISPLACEMENT & BRG TEMP. CUTOUT CONNECTIONS
TO PIC CONTROLLER
8
MAIN OIL RESERVOIR
14
THRUST BEARING
COAST DOWN RESERVOIRS
1
SEAL-END BEARING
2
SHAFT SEAL
3
OIL CHARGING ELBOW
11
SIGHT GLASSES
10
OIL PUMP & PRESS. REGULATOR
TO POWER PANEL
9
OIL THERMISTOR
7
OIL HEATER
6
DRAIN & CHARGING VALVE
Fig. 4 — 17EX Compressor Lubrication Cycle
5
COMPRESSOR OIL SUCTION PRESSURE
4
PUMP, SEAL OIL RETURN
10
1—Gear Mesh 2—Bearings 3—Gear Mesh Spray 4—Oil Level Glass 5—Orifice 6—Oil Supply Pressure
Transducer
7—Pressure Control Valve NOTE: The oil reservoir is at the base of the gear box.
Fig. 5 — External Gear Oil Lubrication Cycle (Plan View)
8—Oil Supply Temperature Thermistor
9—Oil Pump Motor 10 — Oil Pump and Pressure Regulator 11 — Oil Filter 12 — Oil Cooler/Filter 13 — Oil Cooler 14 — Plug Valve
CONTROLS
Definitions
ANALOG SIGNAL — An analog signal varies in propor­tion to the monitored source. It quantifies values between operating limits. (Example: A temperature sensor is an ana­log device because its resistance changes in proportion to the temperature, generating many values.)
DIGIT ALSIGNAL— A digital (discrete) signal is a 2-position representation of the value of a monitored source. (Example: A switch is a digital device because it only in­dicates whether a value is above or below a set point or bound­ary by generating an on/off,high/low, or open/closed signal.)
VOLATILE MEMORY — Volatile memory is memory in- capable of being sustained if power is lost and subsequently restored.
The memories of the PSIO and LID modules are vola­tile. If the battery in a module is removed or damaged, all programming will be lost.
General — The 17EX externally geared open-drive cen-
trifugal liquid chiller contains a microprocessor-based con­trol center that monitors and controls all operations of the chiller.The microprocessor control system matches the cool­ing capacity of the chiller to the cooling load while provid­ing state-of-the-art chiller protection. The system controls cooling load within the set point plus the deadband by sens­ing the leaving chilled water or brine temperature and regu­lating the inlet guide vane via a mechanically linked actua­tor motor.The guide vane is a variable flow prewhirl assembly that controls the refrigeration effect in the cooler by regu­lating the amount of refrigerant vapor flow into the com­pressor.An increase in guide vane opening increases capac­ity.Adecrease in guide vane opening decreases capacity.Chiller protection is provided by the processor which monitors the digital and analog inputs and executes capacity overrides or safety shutdowns, if required.
11
PIC System Components — The Product Integrated
Control (PIC) is the control system on the chiller. See T able1. The PIC controls the operation of the chiller by moni­toring all operating conditions. The PIC can diagnose a prob­lem and let the operator know what the problem is and what to check. It promptly positions the guide vanes to maintain leaving chilled water temperature. It can interface with aux­iliary equipment such as pumps and cooling tower fans to turn them on only when required. It continually checks all safeties to prevent any unsafe operating condition. It also regulates the oil heater while the compressor is off and the hot gas bypass valve, if installed. See Fig. 6-10 for the lo­cations of sensors, transducers, and other devices controlled and/or monitored by the PIC system.
The PIC can be interfaced with the Carrier Comfort Network (CCN) if desired. It can communicate with other PIC-equipped chillers and other CCN devices.
The PIC consists of 4 modules housed inside one of 3 lo­cations: the control center, the power panel, or the starter cabinet. The component names and the control voltage of each location are listed below (also see Table 1):
• control center
— all extra low-voltage wiring (24 v or less)
REAR
• power panel — 115 v control voltage — up to 600 v for oil pump power
• starter cabinet — chiller power wiring (per job requirement)
Table 1 — Major PIC Components and
Panel Locations*
PIC COMPONENT
Processor Sensor Input/Output Module
(PSIO)
Starter Management Module (SMM) Starter Cabinet Local Interface Device (LID) Control Center 6-Pack Relay Board Control Center 8-Input Modules (Optional) Control Center 4-In/2-Out Module Power Panel Oil Differential Pressure/Power Supply
Module
Oil Heater Contactor (1C) Power Panel Compressor Oil Pump Contactor (2C) Power Panel Gear Oil Pump Contactor (5C) Power Panel Hot Gas Bypass Relay (3C) (Optional) Power Panel Control Transformers (T1-T4) Power Panel Control and Oil Heater Voltage Selector (S1) Power Panel Temperature Sensors See Fig. 7 Pressure Transducers See Fig. 7
*See Fig. 6-10.
PANEL
LOCATION
Control Center
Control Center
1—Gear Oil Pressure Sensor 2—Thrust Bearing Temperature and
Impeller Displacement Cable
3—Discharge Temperature Sensor 4—Guide Vane Conduit and Cable 5—High Pressure Cutout Switch
LEGEND
6—Compressor Oil Cooler
Solenoid Conduit
7—Oil Heater Conduit 8—Motor Space Heater Conduit 9—Gear Oil Temperature Sensor
10 — Motor High Temperature Switch Cable
11 — Motor Water Cooling Leak Detector 12 — Discharge Oil Pressure Sensor
TEWAC — Totally Enclosed Water-to-Air Cooled
Fig. 6 — 17EX Controls and Sensor Locations
12
Cable (TEWAC Motor Only)
LEGEND
13 — Condenser Pressure Transducer 14 — Condenser Entering Water
Temperature Sensor
15 — Condenser Entering and Leaving Water
Temperature Cable
16 — Oil Suction Pressure Sensor
17 — Oil Pump Conduit 18 — Oil Pump Sensor 19 — PIC Control Panel 20 — Condenser Leaving Water
Temperature Sensor
21 — Gear Oil Cooler Solenoid Conduit
LEGEND
22 — Cooler Temperature Cable 23 — Cooler Leaving Water Temperature Sensor 24 — Cooler Entering Water Temperature Sensor 25 — Cooler Pressure Sensor 26 — Refrigerant Charging Valve
Fig. 6 — 17EX Controls and Sensor Locations (cont)
13
Fig. 6 — 17EX Controls and Sensor Locations (cont)
Fig. 7 — Control Sensors (Temperature)
Fig. 8 — Control Sensors
(Pressure Transducer, Typical)
LEGEND
LID Local Interface Device PIC Product Integrated Controls PSIO — Processor Sensor Input/Output Module
1—Optional 8-Input Module for Spare Inputs to Control
Interface (One of Two Available)
2—PSIO 3—LID Input/Output Interface Panel Display 4—Oil Differential Pressure/Power Supply Module (Hidden) 5—LID Light (Hidden) 6—6-Pack Relay Board 7—Circuit Breakers (4)
Fig. 9 — Control Center (Front View);
Shown with Options Module
14
15
LEGEND
EQUIP GND — Equipment Ground GRD Ground M—Motor TEWAC Totally Enclosed Water-to-
Air Cooled
Fig. 10 — 17EX Chiller Power Panel and Controls Connections
PROCESSOR/SENSOR INPUT/OUTPUT MODULE (PSIO) — This module contains all the operating software needed to control the chiller. The 17EX uses 5 pressure transducers and 8 thermistors to sense pressures and temperatures. These inputs are connected to the PSIO module. The PSIO also provides outputs to the guide vane actuator, compressor and gear oil pumps, oil heater, hot gas bypass (optional), and alarm contact. The PSIO communicates with the LID, the SMM, and the optional 8-input modules for user interface and starter management.
ST ARTER MANAGEMENT MODULE (SMM) — This mod­ule is located within the starter cabinet. This module ini­tiates PSIO commands for starter functions such as start/ stop of the compressor; start/stop of the condenser and chilled water pumps; start/stop of the tower fan, spare alarm con­tacts, and the shunt trip. The SMM monitors starter inputs such as flow switches, line voltage, remote start contact, spare safety, condenser high pressure, oil pump interlock, motor current signal, starter 1M and run contacts, and the kW trans­ducer input (optional). The SMM contains logic capable of safely shutting down the chiller if communication with the PSIO is lost.
LOCALINTERFACE DEVICE (LID) — The LID is mounted to the control center and allows the operator to interface with the PSIO or other CCN devices. It is the input center for all local chiller set points, schedules, set-up functions, and op­tions. The LID has a STOP button, an alarm light, 4 buttons for logic inputs, and a display. The function of the 4 buttons or ‘‘softkeys’’ are menu driven and are shown on the display directly above the key.
SIX-PACK RELAY BOARD (6-Pack Relay Board) — This device is a cluster of 6 pilot relays located in the control center. It is energized by the PSIO for the compressor oil pump, oil heater, alarm, optional hot gas bypass relay, aux­iliary oil pump.
EIGHT-INPUT (8-Input) MODULES — One optional mod­ule is factory installed in the control center panel when or­dered. There can be up to 2 of these modules per chiller with 8 spare inputs each. They are used whenever chilled water reset, demand reset, or reading a spare sensor is required. The sensors or 4 to 20 mA signals are field-installed.
The spare temperature sensors must have the same temperature/resistance curve as the other temperature sen­sors on this unit. These sensors are rated 5,000 ohm at 75 F (25 C).
FOUR-IN/TWO-OUT(4-IN/2-OUT) MODULE —Thismod­ule monitors and controls the external gear lubrication sys­tem. It energizes the gear oil pump and is located in the power panel.
OIL HEATER CONTACTOR (1C) — This contactor is lo­cated in the power panel and operates the heater at 115 v. It is controlled by the PIC to maintain oil temperature during chiller shutdown.
COMPRESSOR OILPUMP CONTACTOR(2C)ANDGEAR OIL PUMP CONTACTOR (5C) — These contactors are lo­cated in the power panel. They operate all 200 to 575-v oil pumps. The PIC energizes the contactor to turn on the oil pumps as necessary.
HOT GAS BYPASS CONTACTOR RELAY (3C) (Optional) — This relay, located in the power panel, con­trols the opening of the hot gas bypass valve. The PIC en­ergizes the relay during low load, high lift conditions.
OIL AUXILIARY RELAY (4C) — This relay opens the oil cooler solenoid valve and interlocks the oil pump with the compressor (special order).
CONTROL TRANSFORMERS (T1-T4) — These trans­formers are located in the power panel and convert
incoming control voltage to either 21 vac power for the PSIO module and options modules, or 24 vac power for 3 power panel contactor relays and a control solenoid valve.
CONTROL AND OIL HEATER VOLTAGE SELECTOR (S1) — It is necessary to use 115 v incoming control power in the power panel. The switch must be set to the 115-v position.
OIL DIFFERENTIAL PRESSURE/POWER SUPPLY MODULE — This module, which is located in the control center, provides 5 vdc power for the transducers and LID backlight. This module outputs the difference between two pressure transducer input signals. The module subtracts oil supply pressure from transmission sump pressure and out­puts the difference as an oil differentialpressure signal to the PSIO. The PSIO converts this signal to differential oil pres­sure. To calibrate this reading, refer to the Troubleshooting, Checking Pressure Transducers section on page 84.
LID Operation and Menus (Fig. 11-17)
GENERAL
• The LID display automatically reverts to the default screen (Fig. 11) after 15 minutes if no softkey activity takes place and if the chiller is not in PUMPDOWN mode
• When not displaying the default screen, the upper right­hand corner of the LID displays the name of the screen that you have entered (Fig. 12).
• The LID may be configured in English or SI units, through the LID configuration screen.
• Local Operation — Pressing the LOCAL the PIC in LOCAL operation mode, and the control ac-
cepts modification to programming from the LID only. The PIC uses the Local Time Schedule to determine chiller start and stop times.
• CCN Operation — Pressing the CCN softkey places the PIC in the CCN operation mode, and the control accepts
modifications from any CCN interface or module (with the proper authority), as well as the LID. The PIC uses the CCN time schedule to determine start and stop times.
Fig. 11 — LID Default Screen
ALARMS AND ALERTS — An alarm (*) or alert (!) status is indicated on the default screen and the status tables. An alarm (*) shuts down the compressor. An alert (!) notifies the operator that an unusual condition has occurred. The chiller continues to operate when an alert is shown.
Alarms are indicated when the control center alarm light (!) flashes. The primary alarm message is viewed on the de­fault screen and an additional, secondary, message and troubleshooting information are sent to the ALARM HIS­TORY table.
softkey places
16
NOTE: When an alarm is detected, the LID default screen freezes (stops updating) at the time of alarm. The freeze en­ables the operator to view the chiller conditions at the time of the alarm. The status tables show the updated informa-
tion. Once all alarms have been cleared (by pressing the
RESET
softkey), the default LID screen returns to normal
operation.
Fig. 12 — LID Service Screen
LID DEFAULT SCREEN MENU ITEMS — To perform any of the operations described below, the PIC must be pow­ered up and have successfully completed its self test.
The default screen menu selection offers four options (STATUS, SCHEDULE, SETPOINT, and SERVICE). The STATUS menu allows viewing and limited calibration/ modification of control points and sensors, relays and con­tacts, and the options board. The SCHEDULE menu allows viewing and modification of the Local Control, CCN Con­trol, and Ice Build time schedules. Numerous set points in­cluding Base Demand Limit, LCW, ECW, and Ice Build can be adjusted under the SETPOINT menu. The SERVICE menu can be used to revise alarm history, control test, control al­gorithm status, equipment configuration, equipment service, time and date, attach to network, log out of device, control­ler identification, and LID configurations. Figures 15 and 16 provide additional information on the menu structure.
Press the MENU
softkey to select from the 4 options. To view or change parameters within any menu structure, use the SELECT
softkey to choose the desired table or
item. The softkey modification choices displayed will de­pend on whether the selected item is a discrete point, ana­log point, or an override point. Press the softkey that cor­responds to your configuration selection or press the
QUIT softkey. If the QUIT softkey is depressed, the
configuration will not be modified. Use the following soft­keys to access and select the desired section.
MENU STRUCTURE — To perform any of the operations described below, the PIC must be powered up and have suc­cessfully completed its self test.
• Press MENU
to select from the four available options.
• Press NEXT or PREVIOUS to highlight the desired entry.
• Press SELECT to access the highlighted point.
• Press QUIT to leave the selected decision or field with­out saving any changes.
• Or, press ENTER to leave the selected decision or field and save changes.
TOVIEWOR CHANGE POINT STATUS (Fig. 13) — Point Status is the actual value of all of the temperatures, pres­sures, relays, and actuators sensed and controlled by the PIC.
1. On the Menu screen, press STATUS
to view the list of
Point Status tables.
2. Press NEXT or PREVIOUS to highlight the desired
status table. The list of tables is:
• STATUS01 — Status of control points and sensors
• STATUS02 — Status of relays and contacts
• STATUS03 — Status of both optional 8-input modules and sensors
• STATUS04 — Gear oil temperature and pressure
• Press the softkey that corresponds to the desired menu structure.
Fig. 13 — Example of Point Status Screen
(Status01)
17
3. Press SELECT to view the desired Point Status table.
4. On the Point Status table press NEXT or PREVIOUS
until desired point is displayed on the screen.
Override Indication — An override value is indicated by ‘ ‘SUPVSR,’’‘‘SERVC,’’or ‘‘BEST’’ flashing next to the point value on the Status table.
TO VIEW OR CHANGE TIME SCHEDULE OPERATION (Fig. 14)
1. On the Menu screen, press SCHEDULE
.
For Discrete Points — Press START or STOP ,
or NO ,ONor OFF , etc. to select the desired
YES
state.
For Analog Points Press INCREASE or
DECREASE
to select the desired value.
5. Press ENTER to register new value.
OVERRIDE OPERATIONS NOTE: When overriding or changing metric values, it is nec-
essary to hold the softkey down for a few seconds in order to see a value change, especially on kilopascal values.
To Remove an Override
1. On the Point Status table press NEXT or PREVIOUS
to highlight the desired point.
2. Press NEXT or PREVIOUS to highlight one of the following schedules.
OCCPC01S — LOCAL Time Schedule OCCPC02S — ICE BUILD Time Schedule OCCPC03-99S — CCN Time Schedule (Actual
number is defined in CONFIG table.)
3. Press SELECT to access and view the time schedule.
4. Press NEXT or PREVIOUS to highlight the de­sired period or override that you wish to change.
5. Press SELECT to access the highlighted period or override.
2. Press SELECT to access the highlighted point.
3. Press RELEASE to remove the override and return the point to the PIC’s automatic control.
Fig. 14 — Example of Time Schedule
Operation Screen
18
CCN
Start Chiller In CCN Control
Start Chiller In Local Control
DEFAULT SCREEN
LOCAL RESET
MENU
(SOFTKEYS)
Clear Alarms
NEXT
NEXT
START
INCREASE
ENABLE
STATUS
List the Status Tables
STATUS STATUS STATUS STATUS
PREVIOUS
PREVIOUS
STOP RELEASE
DECREASE
DISABLE
SCHEDULE SETPOINT
01 02 03 04
SELECT
SELECT
RELEASE
RELEASE
Access Main Menu
SERVICE
EXIT
EXIT
ENTER
ENTER
ENTER
(SELECT A T ABLE) (SELECT A POINT
ON THE TABLE) (MODIFY A
DISCRETE POINT) or (MODIFY AN
ANALOG POINT) or (MODIFY CONTROL
OPTIONS)
Select a Schedule
NEXT
Select a Time Period/Override
NEXT
Modify a Schedule Time
INCREASE
Add/Eliminate a Day
ENABLE
123
List the Schedules
OCCPC01S - Local Time Schedule OCCPC02S - Ice Build Time Schedule OCCPC03S-99S - CCN Time Schedule
(ENTER A 4-DIGIT PASSWORD)
4
Select the Setpoint
Modify the Setpoint
1 2 3 4 5 6 7 8
Override
SELECT
SELECT
ENTER
ENTER
PREVIOUS
PREVIOUS
DECREASE
DISABLE
Display the Setpoint Table
NEXT
INCREASE
Base Demand Limit
LCW Setpoint
ECW Setpoint
Ice Build Setpoint
PREVIOUS
DECREASE
EXIT
EXIT
EXIT
EXIT
(ANALOG VALUES)
(DISCRETE VALUES)
List the Service Tables
SELECT
QUIT
EXIT
ENTER
Select a Service Table
NEXT
Fig. 15 — 17EX LID Menu Structure
19
• ALARM HISTORY
• CONTROL TEST
• CONTROL ALGORITHM STATUS
• EQUIPMENT CONFIGURATION
• EQUIPMENT SERVICE
• TIME AND DATE
• ATTACH TO NETWORK DEVICE
• LOG OUT OF DEVICE
• CONTROLLER IDENTIFICATION
• LID CONFIGURATION
PREVIOUS
SEE FIGURE 16
SELECT
EXIT
SERVICE TABLE
NEXT
PREVIOUS
ALARM HISTORY
CONTROL TEST
CONTROL ALGORITHM STA TUS
List the Control Algorithm Status Tables
MAINT01 (Capacity Control) MAINT02 (Override Status) MAINT03 (Surge/HGBP Status) MAINT04 (Lead/Lag Status) WSMDEFME (Water System Manager Control Status) OCCDEFM (Time Schedule Status)
SELECT
Display Alarm History
(The table holds up to 25 alarms and alerts with the last alarm at the top of the screen.)
EXIT
List the Control Tests
Select a Test
NEXT
Automated T est
PSIO Thermistors
Options Thermistor
Transducers
Guide Vane Actuator
Pumps
Discrete Outputs
Pumpdown Lockout
Terminated Lockout
• FX Gear Oil Pump I/O
PREVIOUS
SELECT
EXIT
Select a Table:
NEXT
OCCDEFM (Time Schedule Status)
Data Select Table
NEXT
EQUIPMENT CONFIGURATION List the Equipment Configuration Tables
PREVIOUS
PREVIOUS
OCCPC01S (Local Status) OCCPC02S (CCN, ICE BUILD Status) OCCPC03S (CCN Status)
SELECT
SELECT
EXIT
MAINT01 (Capacity Control Algorithm) MAINT02 (Override Status)\ MAINT03 (Surge/HGBP Status) MAINT04 (LEAD/LAG Status) WSMDEFM2 (Water System Manager Control Status)
EXIT
Maintenance T able Data
• CONFIG
• LEAD/LAG
• OCCDEFCS
• HOLIDEF
• BRODEF
• WSMALMDF
• ALARMDEF
• CONS_DEF
• RUNT_DEF
Select a Table
NEXT
PREVIOUS
SELECT
EXIT
CONTINUED ON NEXT PAGE
Select a Parameter
NEXT
Modify a Parameter
INCREASE
ENABLE
YES
PREVIOUS
DECREASE
DISABLE
NO
Fig. 16 — 17EX Service Menu Structure
20
SELECT
QUIT QUIT QUIT
EXIT
ENTER ENTER ENTER
(ANALOG VALUES)
(DISCRETE VALUES)
(DISCRETE VALUES)
SERVICE MENU CONTINUED FROM PREVIOUS PAGE
EQUIPMENT SERVICE (See Table 2, Examples 8, 9, and 10)
Service Tables: (See Note)
SERVICE1
SERVICE2
SERVICE3
Select a Service Table
NEXT
Select a Service Table Parameter
NEXT
Modify a Service Table Parameter
INCREASE
ENABLE
NO
TIME AND DATE
ATTACH TO NETWORK DEVICE
Select a Device
NEXT
Modify Device Address
INCREASE
Use to attach LID to another CCN network or device
Attach to "LOCAL" to enter this machine
To upload new tables
PREVIOUS
PREVIOUS
DECREASE
DISABLE
YES
List Network Devices
Local
• Device 1
• Device 2
• Device 3
• Device 4
• Device 5
PREVIOUS
DECREASE
SELECT
SELECT
QUIT QUIT QUIT
• Device 6
• Device 7
• Device 8
• Device 9
SELECT
ENTER
EXIT
EXIT
ENTER ENTER ENTER
ATTACH
EXIT
(ANALOG VALUES) (DISCRETE VALUES) (DISCRETE VALUES)
Display Time and Date Table:
To Modify — Time — Day of Week
INCREASE
DECREASE
— Date — Holiday Today
ENTER
EXIT
LOG OUT OF DEVICE
CONTROLLER IDENTIFICATION PSIO Controller
Identification Table
INCREASE
To modify — PSIO CCN Address • To View — PSIO Software Version
LID CONFIGURATION
DECREASE
LEGEND
CCN Carrier Comfort Network HGBP — Hot Gas Bypass LID Local Interface Device
NOTE: SERVICE TABLES:
SERVICE1: — Capacity Override
Type of Chilled MediumAlert TemperatureFlow VerificationDeadbandRecycle Restart TimeSurge/HGBP OperationMotor Voltage, RLA, and FrequencyStarter TypeCondenser Freeze SafetySoft Stop ConfigurationStart to Stop TimerGear Oil Pump Configuration
ENTER
Default Screen
CCN
EXIT
(last 2 digits on part number indicate software version)
LID Configuration Table
INCREASE
To Modify — LID CCN Address
LOCAL
DECREASE
— English or S.I. Metric Units — Password
RESET
ENTER
SERVICE2: — 8-input Modules
SERVICE3: — Proportional Inc each Band
MENU
20 mA Power Source
Proportional Dec each BandProportional ECW GainMaximum Guide Vane Opening
EXIT
To View — LID Software Version (last 2 digits of part number
indicate software version)
Fig. 16 — 17EX Service Menu Structure (cont)
21
6. a. Press INCREASE or DECREASE to change the time values. Override values are in one-hour incre-
ments, up to 4 hours.
b. Press ENABLE to select days in the day-of-week
fields. Press DISABLE
to eliminate days from the
period.
7. Press ENTER to register the values and to move horizontally (left to right) within a period.
8. Press EXIT to leave the period or override.
9. Either return to Step 4 to select another period or override, or press EXIT
again to leave the cur-
rent time schedule screen and save the changes.
4. Press SELECT to modify the highlighted set point.
5. Press INCREASE or DECREASE to change the se­lected set point value.
6. Press ENTER to save the changes and return to the previous screen.
10. Holiday Designation (HOLIDEF table) may be found in the Service Operation section, page 42.You must assign the month, day, and duration for the holiday.The Broad­cast function in the BRODEF table also must be en­abled for holiday periods to function.
TO VIEW AND CHANGE SET POINTS (Fig. 17)
1. To view the Set Point table, at the Menu screen press
SETPOINT
.
2. There are 4 set points on this screen: Base Demand Limit;
LCW Set Point (leaving chilled water set point); ECW Set Point (entering chilled water set point); and ICE BUILD set point. Only one of the chilled water set points can be active at one time, and the type of set point is activated in the Service menu. ICE BUILD is also activated and configured in the Service menu.
3. Press NEXT or PREVIOUS to highlight the desired
set point entry.
Fig. 17 — Example of Set Point Screen
SERVICE OPERATION — To view the menu-driven pro­grams available for Service Operation, see the Service Op­eration section, page 42. For examples of LID display screens, see Table 2.
LEGEND FOR TABLE 2 — LID DISPLAY DATA
CCN Carrier Comfort Network CHWR — Chilled Water Return CHWS — Chilled Water Supply Compr — Compressor Dec Decrease Ecw Entering Chilled Water HGBP — Hot Gas Bypass Inc Increase LCW Leaving Chilled Water mA Milliamps P—Pressure PIC Product Integrated Controls Refrig — Refrigerant T—Temperature Temp Temperature
22
Table 2 — LID Display Data
NOTES:
IMPORTANT: The following notes apply to all Table 2 examples.
1. Only 12 lines of information appear on the LID screen at any one time. Pressthe NEXT or to view items below or above the current screen. If you have a chiller with a backlit LID, press the NEXT forward; press the PREVIOUS
2. Toaccess the information shown in Examples 6 through 14, enter your 4-digit password after pressing the SERVICE
softkeys arepressed for 15 minutes, the LIDautomatically logs off (to prevent unrestricted access to PIC controls) and reverts to the default screen. If this happens, you must reenter your password to access the tables shown in Examples 6 through 14.
3. Termsin the Description column of these tables are listed as they appear on the LID screen.
4. The LID may be configured in English or Metric (SI) units using theLIDCONFIGURATIONscreen. See the ServiceOperation sec­tion, page 42, for instructions on making this change.
To access this display from the LID default screen:
1. Press MENU
2. Press STATUS
3. Press SELECT
or PREVIOUS softkey to highlightapoint
softkey twice to page
softkey twice to page back.
softkey.If no
EXAMPLE1—STATUS01 DISPLAY SCREEN
. (STATUS01 will be highlighted).
.
5. The items in the Reference Point Name column
the LID screen
Building Supervisor software. They are listed in these tables as a convenience to the operator if it is necessary to cross reference CCN/BS documentation or use CCN/BS programs. For more in­formation, see the 17EX CCN literature.
6. Reference Point Names shown in these tables in all capital letters can be read by CCN and Building Supervisor software. Of these capitalized names, those preceded by an asterisk can also be changed (that is, written to) by the CCN, Building Supervisor soft­ware and the LID. Capitalized Reference Point Names preceded by two asterisks can be changed only from the LID. Reference Point Names in lower case type can be viewed by CCN or Build­ing Supervisor software only by viewing the whole table.
7. Alarms and Alerts: An asterisk
screen
tion point in the far right field of the LID screen indicates an alert state. The asterisk (or exclamation point) indicates that the value on that line has exceeded (or is approaching) a limit. For more information on alarms and alerts, see the Alarms and Alerts sec­tion, page 16.
. They are data or variable names used in CCN or
in the far right field of a LID status
indicates that the chiller is in an alarm state; an exclama-
do not appear on
DESCRIPTION RANGE UNITS
Control Mode Reset.Off. Local. CCN MODE Run Status Timeout. Recycle. Startup. STATUS
Occupied ? No/Yes OCC Alarm State Normal/Alarm ALM *Chiller Start/Stop Stop/Start CHIL S S Base Demand Limit 40-100 % DLM *Active Demand Limit 40-100 % DEM LIM Compressor Motor Load 0-999 % CA L
Current 0-999 % CA P
Amps 0-9999 AMPS CA A *Target Guide Vane Pos 0-100 % GV TRG Actual Guide Vane Pos 0-100 % GV ACT Water/Brine: Setpoint 10-120 (–12.2-48.9) DEG F (DEG C) SP * Control Point 10-120 (–12.2-48.9) DEG F (DEG C) LCW STPT Entering Chilled Water –40-245 (–40-118) DEG F (DEG C) ECW Leaving Chilled Water –40-245 (–40-118) DEG F (DEG C) LCW Entering Condenser Water –40-245 (–40-118) DEG F (DEG C) ECDW Leaving Condenser Water –40-245 (–40-118) DEG F (DEG C) LCDW Evaporator Refrig Temp –40-245 (–40-118) DEG F (DEG C) ERT Evaporator Pressure –6.7-420 (–46-2896) PSI (kPa) ERP Condenser Refrig Temp –40-245 (–40-118) DEG F (DEG C) CRT Condenser Pressure –6.7-420 (–46-2896) PSI (kPa) CRP Discharge Temperature –40-245 (–40-118) DEG F (DEG C) CMPD Bearing Temperature –40-245 (–40-118) DEG F (DEG C) MTRB Motor Winding Temp† –40-245 (–40-118) DEG F (DEG C) MTRW Motor Winding Hi
Temp Cutout
Oil Sump Temperature –40-245 (–40-118) DEG F (DEG C) OILT Oil Pressure Transducer† –6.7-420 (–46-2896) PSI (kPa) OILP Oil Pressure** –6.7-420 (–46-2896) PSID (kPad) OILPD Line Voltage: Percent 0-999 % V P
*Remote Contacts Input Off/On REMCON Total Compressor Starts 0-65535 c starts Starts in 12 Hours 0-8 STARTS Compressor Ontime 0-500000.0 HOURS c hrs *Service Ontime 0-32767 HOURS S HRS *Compressor Motor kW 0-9999 kW CKW
†Information is applicable to hermetic chillers (19EX) only.
**Oil pressure is read directly from a differential pressure module on 17EX chillers. NOTE: values preceded by an asterisk (*) can be forced (changed by an operator) from the LID screen
or from another control device (such as a Carrier Comfort Network [CCN] terminal).
Actual 0-9999 VOLTS V A
Ramping. Running. Demand. Override. Shutdown. Abnormal. Pumpdown
Normal/Alarm MTRW
REFERENCE POINT NAME
(ALARM HISTORY)
23
EXAMPLE2—STATUS02 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press STATUS
3. Scroll down to highlight STATUS02.
4. Press SELECT
.
.
.
Table 2 — LID Display Data (cont)
DESCRIPTION
Hot Gas Bypass Relay X OFF/ON HGBR *Chilled Water Pump X OFF/ON CHWP Chilled Water Flow X NO/YES EVFL *Condenser Water Pump X OFF/ON CDP Condenser Water Flow X NO/YES CDFL Compressor Start Relay X OFF/ON CMPR Compressor Start Contact X OPEN/CLOSED 1CR AUX Compressor Run Contact X OPEN/CLOSED RUN AUX Starter Fault Contact X OPEN/CLOSED STR FLT Pressure Trip Contact X OPEN/CLOSED PRS TRIP Single Cycle Dropout X NORMAL/ALARM V1 CYCLE Oil Pump Relay X OFF/ON OILR Oil Heater Relay X OFF/ON OILH Motor Cooling Relay† X OFF/ON MTRC Auxiliary Oil Pump Relay X OFF/ON AUXOILR *Tower Fan Relay X OFF/ON TFR Compr. Shunt Trip Relay X OFF/ON TRIPR Alarm Relay X NORMAL/ALARM ALM Spare Prot Limit Input X ALARM/NORMAL SPR PL
†Information is applicable to hermetic machines only. NOTE: values preceded by an asterisk (*) can be forced (changed by an operator) from the LID screen
or from another control device (such as a Carrier Comfort Network [CCN] terminal).
To access this display from the LID default screen:
1. Press MENU
2. Press STATUS
3. Scroll down to highlight STATUS03.
4. Press SELECT
.
.
.
POINT TYPE
INPUT OUTPUT
EXAMPLE3—STATUS03 DISPLAY SCREEN
UNITS
REFERENCE POINT NAME
(ALARM HISTORY)
DESCRIPTION RANGE UNITS
OPTIONS BOARD 1 *Demand Limit 4-20 mA 4-20 mA DEM OPT
*Temp Reset 4-20 mA 4-20 mA RES OPT *Common CHWS Sensor –40-245 (–40-118) DEG F (DEG C) CHWS *Common CHWR Sensor –40-245 (–40-118) DEG F (DEG C) CHWR *Remote Reset Sensor –40-245 (–40-118) DEG F (DEG C) R RESET *Temp Sensor — Spare 1 –40-245 (–40-118) DEG F (DEG C) SPARE1 *Temp Sensor — Spare 2 –40-245 (–40-118) DEG F (DEG C) SPARE2 *Temp Sensor — Spare 3 –40-245 (–40-118) DEG F (DEG C) SPARE3
OPTIONS BOARD 2 *4-20 mA — Spare 1 4-20 mA SPARE1 M
*4-20 mA — Spare 2 4-20 mA SPARE2 M *Temp Sensor — Spare 4 –40-245 (–40-118) DEG F (DEG C) SPARE4 *Temp Sensor — Spare 5 –40-245 (–40-118) DEG F (DEG C) SPARE5 *Temp Sensor — Spare 6 –40-245 (–40-118) DEG F (DEG C) SPARE6 *Temp Sensor — Spare 7 –40-245 (–40-118) DEG F (DEG C) SPARE7 *Temp Sensor — Spare 8 –40-245 (–40-118) DEG F (DEG C) SPARE8 *Temp Sensor — Spare 9 –40-245 (–40-118) DEG F (DEG C) SPARE9
NOTE: values preceded by an asterisk (*) can be forced (changed by an operator) from the LID screen or from another control device (such as a Carrier Comfort Network [CCN] terminal).
REFERENCE POINT NAME
(ALARM HISTORY)
24
EXAMPLE4—STATUS04 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press STATUS
3. Scroll down to highlight STATUS04.
4. Press SELECT
.
.
.
Table 2 — LID Display Data (cont)
DESCRIPTION RANGE UNITS
Main Gear Oil Pump OFF/ON MAINPMP1 Auxiliary Gear Oil Pump OFF/ON AUXPMP2 Gear Oil Pressure −6.7 to 420 (−46 to 2896) psi (kPa) GEAROILP Gear Oil Temperature −40 to 245 (−40 to 118) DEG F (DEG C) GEAROILT
EXAMPLE 5 — SETPOINT DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SETPOINT
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
Base Demand Limit 40-100 % DLM 100 LCW Setpoint 20-120 (–6.7-48.9) DEG F (DEG C) lcw sp ECW Setpoint 20-120 (–6.7-48.9) DEG F (DEG C) ecw sp 60.0 (15.6) ICE BUILD Setpoint 20- 60 (–6.7-15.6) DEG F (DEG C) ice sp
.
.
REFERENCE POINT NAME
(ALARM HISTORY)
50.0 (10.0)
40.0 ( 4.4)
25
Table 2 — LID Display Data (cont)
EXAMPLE 6 — CONFIGURATION (CONFIG) DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT
5. Scroll down to highlight CONFIG.
6. Press SELECT
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
RESET TYPE 1 Degrees Reset at 20 mA –30-30 (–17-17) DEG F (DEG C) deg 20ma
RESET TYPE 2 Remote Temp (No Reset) –40-245 (–40-118) DEG F (DEG C) res rt1 Remote Temp (Full Reset) –40-245 (–40-118) DEG F (DEG C) res rt2 65 (18) Degrees Reset –30-30 (–17-17) DEG F (DEG C) res rt 10D(6D)
RESET TYPE 3 CHW Delta T (No Reset) 0-15 (0-8) DEG F (DEG C) restd 1 CHW Delta T (Full Reset) 0-15 (0-8) DEG F (DEG C) restd 2 0D(0D) Degrees Reset –30-30 (–17-17) DEG F (DEG C) deg chw 5D(3D)
Select/Enable Reset Type 0-3 res sel ECW CONTROL OPTION DISABLE/ENABLE ecw opt
Demand Limit At 20 mA 40-100 % dem 20ma 40 20 mA Demand Limit Option DISABLE/ENABLE dem sel DISABLE
Auto Restart Option DISABLE/ENABLE astart DISABLE Remote Contacts Option DISABLE/ENABLE r contact Temp Pulldown Deg/Min 2-10 tmp ramp
Load Pulldown %/Min 5-20 kw ramp 10 Select Ramp Type: 0/1 ramp opt 1
Temp=0,Load=1
Loadshed Group Number 0-99 ldsgrp 0 Loadshed Demand Delta 0-60 % ldsdelta 20 Maximum Loadshed Time 0-120 MIN maxldstm 60
CCN Occupancy Config:
Schedule Number 3-99 occpcxxe 3 Broadcast Option DISABLE/ENABLE occbrcst DISABLE
ICE BUILD Option DISABLE/ENABLE ibopt DISABLE ICE BUILD TERMINATION
0 =Temp, 1 =Contacts, 2 =Both 0-2 ibterm 0
ICE BUILD Recycle Option DISABLE/ENABLE ibrecyc DISABLE
NOTE: D = delta degrees.
.
.
.
.
10D(6D) 85 (29)
10D(6D)
0 DISABLE
DISABLE 3
26
Table 2 — LID Display Data (cont)
EXAMPLE 7 — LEAD/LAG CONFIGURATION DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT
5. Scroll down to highlight LEAD/LAG.
6. Press SELECT
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
LEAD/LAG SELECT
DISABLE =0, LEAD =1, LAG =2, STANDBY =3
Load Balance Option DISABLE/ENABLE loadbal DISABLE Common Sensor Option DISABLE/ENABLE commsens DISABLE LAG Percent Capacity 25-75 % lag per LAG Address 1-236 lag add LAG START Timer 2-60 MIN lagstart 10 LAG STOP Timer 2-60 MIN lagstop 10 PRESTART FAULT Timer 0-30 MIN preflt 5 STANDBY Chiller Option DISABLE/ENABLE stndopt DISABLE STANDBY Percent Capacity 25-75 % stnd per STANDBY Address 1-236 stnd add
.
.
.
.
LEAD/LAG CONFIGURATION SCREEN
0-3 leadlag 0
50 92
50 93
27
Table 2 — LID Display Data (cont)
EXAMPLE 8 — SERVICE1 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT
5. Scroll down to highlight SERVICE1.
6. Press SELECT
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
Motor Temp Override* 150-200 (66-93) DEG F (DEG C) mt over Cond Press Override 90-200 (620-1379) PSI (kPa) cp over Refrig Override Delta T 2-5 (1-3) DEG F (DEG C) ref over 3D (1.6D) Chilled Medium Water/Brine medium WATER Brine Refrig Trippoint 8-40 (–13.3-4) DEG F (DEG C) br trip
Compr Discharge Alert 125-200 (52-93) DEG F (DEG C) cd alert Bearing Temp Alert 165-210 (74-99) DEG F (DEG C) tb alert 175 (79)
Water Flow Verify Time 0.5-5 MIN wflow t Oil Press Verify Time 15-300 SEC oilpr t 15
Water/Brine Deadband 0.5-2.0 (0.3-1.1) DEG F (DEG C) cw db Recycle Restart Delta T 2.0-10.0 (1.1-5.6) DEG F (DEG C) rcycrdt 5 (2.8) Recycle Shutdown Delta 0.5-4.0 (.27-2.2) rcycsdt 1.0 (0.6) Surge Limit/HGBP Option 0/1 srg hgbp Select: Surge=0, HGBP=1 Surge/HGBP Delta T1 0.5-15 (0.3-8.3) DEG F (DEG C) hgb dt1 Surge/HGBP Delta P1 30-170 (207-1172) PSI (kPa) hgb dp1 50 (345) Min. Load Points (T1/P1) Surge/HGBP Delta T2 0.5-15 (0.3-8.3) DEG F (DEG C) hgb dt2 Surge/HGBP Delta P2 30-170 (207-1172) PSI (kPa) hgb dp2 85 (586) Full Load Points (T2/P2) Surge/HGBP Deadband 1-3 (0.6-1.6) DEG F (DEG C) hgb dp
Surge Delta Percent Amps 10-50 % surge a Surge Time Period 1-5 MIN surge t 2
Demand Limit Source 0/1 dem src Select: Amps=0, Load=1 Amps Correction Factor 1-8 corfact 3 Motor Rated Load Amps 1-9999 AMPS a fs Motor Rated Line Voltage 1-9999 VOLTS v fs 460 Meter Rated Line kW 1-9999 kW kw fs 600
Line Frequency 0/1 HZ freq 0 Select: 0=60 Hz, 1=50 Hz
Compr Starter Type REDUCE/FULL starter REDUCE Condenser Freeze Point –20-35 (–28.9-1.7) DEG F (DEG C) cdfreeze 34 (1) Soft Stop Amps Threshold 40-100 % softstop 100 Stop to Start Timer 3-50 MIN stopmtr 20
External Gear Option ENABLE/DSABLE exg opt Mechanical Gear Oil Pump ENABLE/DSABLE mech pmp DSABLE Auxiliary Gear Oil Pump ENABLE/DSABLE aux pmp Gear Oil Pressure Alert 15-20 (103-138) PSI (kPa) gearp al 15 (103) Gear Oil Temperature Alert 130-145 (54-63) DEG F (DEG C) geart al 130 (54)
*Information is applicable to hermetic machines (19EX) only. NOTE: D = delta degrees.
.
.
.
.
200 (93) 125 (862)
33 (1) 200 (93)
5
1.0 (0.6)
0
1.5 (0.8)
10 (5.6)
1 (0.6) 25
0
200
ENABLE DSABLE
28
Table 2 — LID Display Data (cont)
EXAMPLE 9 — SERVICE2 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT
5. Scroll down to highlight SERVICE2.
6. Press SELECT
OPTIONS BOARD 1 20 mA POWER CONFIGURATION
External = 0, Internal = 1 RESET 20 mA Power Source 0,1 res 20 ma
DEMAND 20 mA Power Source 0,1 dem 20 ma 0 SPARE ALERT ENABLE
Disable = 0, 1 = High Alert, 2 = Low Alert, 3 = High Alarm, 4 = Low Alarm Temp = Alert Threshold
CHWS Temp Enable 0-4 chws en CHWS Temp Alert –40-245 (–40-118) DEG F (DEG C) chws al 245 (118) CHWR Temp Enable 0-4 chwr en 0 CHWR Temp Alert –40-245 (–40-118) DEG F (DEG C) chwr al Reset Temp Enable 0-4 rres en 0 Reset Temp Alert –40-245 (–40-118) DEG F (DEG C) rres al 245 (118) Spare Temp 1 Enable 0-4 spr1 en Spare Temp 1 Alert –40-245 (–40-118) DEG F (DEG C) spr1 al 245 (118) Spare Temp 2 Enable 0-4 spr2 en 0 Spare Temp 2 Alert –40-245 (–40-118) DEG F (DEG C) spr2 al Spare Temp 3 Enable 0-4 spr3 en 0 Spare Temp 3 Alert –40-245 (–40-118) DEG F (DEG C) spr3 al
OPTIONS BOARD 2 20 mA POWER CONFIGURATION
External = 0, Internal = 1 SPARE 1 20 mA Power Source 0,1 sp1 20 ma SPARE 2 20 mA Power Source 0,1 sp2 20 ma 0
SPARE ALERT ENABLE Disable = 0, 1 = High Alert, 2 = Low Alert, 3 = High Alarm, 4 = Low Alarm Temp = Alert Threshold
Spare Temp 4 Enable 0-4 spr4 en Spare Temp 4 Alert –40-245 (–40-118) DEG F (DEG C) spr4 al 245 (118) Spare Temp 5 Enable 0-4 spr5 en 0 Spare Temp 5 Alert –40-245 (–40-118) DEG F (DEG C) spr5 al Spare Temp 6 Enable 0-4 spr6 en 0 Spare Temp 6 Alert –40-245 (–40-118) DEG F (DEG C) spr6 al Spare Temp 7 Enable 0-4 spr7 en 0 Spare Temp 7 Alert –40-245 (–40-118) DEG F (DEG C) spr7 al 245 (118) Spare Temp 8 Enable 0-4 spr8 en Spare Temp 8 Alert –40-245 (–0-118) DEG F (DEG C) spr8 al 245 (118) Spare Temp 9 Enable 0-4 spr9 en 0 Spare Temp 9 Alert –40-245 (–40-118) DEG F (DEG C) spr9 al
NOTE: This screen provides the means to generate alert messages based on exceeding the ‘‘Temp’’threshold for each point listed. If the ‘‘Enable’’ is set to 1, a value above the ‘‘Temp’’ threshold generates an alert message. If the ‘‘Enable’’ is set to 2, a value below the ‘‘Temp Alert’’ threshold generates an alert message. If the ‘‘Enable’’ is set to 0, alert generation is disabled. If the ‘‘Enable’’ is set to 3, a value above the ‘‘Temp’’ threshold generates an alarm. If the ‘‘Enable’’ is set to 4, a value below the ‘‘Temp’’ threshold generates an alarm.
.
.
.
.
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
0
0
245 (118)
0
245 (118) 245 (118)
0
0
245 (118) 245 (118)
0
245 (118)
EXAMPLE 10 — SERVICE3 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT
5. Scroll down to highlight SERVICE3.
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
Proportional Inc Band 2-10 gv inc Proportional Dec Band 2-10 gv de 6.0 Proportional ECW Gain 1-3 gv ecw 2.0
Guide Vane Travel Limit 30-100 % gv lim
.
.
.
29
6.5
50
Table 2 — LID Display Data (cont)
EXAMPLE 11 — MAINTENANCE (MAINT01) DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT
5. Scroll down to highlight MAINT01.
DESCRIPTION RANGE/STATUS UNITS REFERENCE POINT NAME
CAPACITY CONTROL Control Point 10-120 (–12.2-48.9) DEG F (DEG C) ctrlpt Leaving Chilled Water –40-245 (–40-118) DEG F (DEG C) LCW Entering Chilled Water –40-245 (–40-118) DEG F (DEG C) ECW Control Point Error –99-99 (–55-55) DEG F (DEG C) cperr ECW Delta T –99-99 (–55-55) DEG F (DEG C) ecwdt ECW Reset –99-99 (–55-55) DEG F (DEG C) ecwres LCW Reset –99-99 (–55-55) DEG F (DEG C) lcwres Total Error + Resets –99-99 (–55-55) DEG F (DEG C) error Guide Vane Delta –2-2 % gvd Target Guide Vane Pos 0-100 % GV TRG Actual Guide Vane Pos 0-100 % GV ACT
Proportional Inc Band 2-10 gv inc Proportional Dec Band 2-10 gv dec Proportional ECW Gain 1-3 gv ecw Water/Brine Deadband 0.5-2 (0.3-1.1) DEG F (DEG C) cwdb
NOTE: Overriding is not supported on this maintenance screen.Active overrides show the associated point in alert (*). Reference point names with capital letters can be read by CCN and Building Supervisor software.
.
.
.
EXAMPLE 12 — MAINTENANCE (MAINT02) DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
2. Press SERVICE
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT
5. Scroll down to highlight MAINT02.
6. Press SELECT
OVERRIDE/ALERT STATUS MOTOR WINDING TEMP† –40-245 (–40-118) DEG F (DEG C) MTRW
Override Threshold 150-200 (66-93) DEG F (DEG C) mt over CONDENSER PRESSURE –6.7-420 (–42-2896) PSI (kPa) CRP Override Threshold 90-245 (621-1689) PSI (kPa) cp over EVAPORATOR REFRIG TEMP –40-245 (–40-118) DEG F (DEG C) ERT Override Threshold 2-45 (1-7.2) DEG F (DEG C) rt over DISCHARGE TEMPERATURE –40-245 (–40-118) DEG F (DEG C) CMPD Alert Threshold 125-200 (52-93) DEG F (DEG C) cd alert BEARING TEMPERATURE –40-245 (–40-118) DEG F (DEG C) MTRB Alert Threshold 175-185 (79-85) DEG F (DEG C) tb alert
†Information is applicable to hermetic machines (19EX) only. NOTE: Overriding is not supported on this maintenance screen.Active overrides show the associated point in alert (*). Reference point names with
capital letters can be read by CCN and Building Supervisor software.
.
.
.
.
DESCRIPTION RANGE/STATUS UNITS REFERENCE POINT NAME
30
Loading...
+ 90 hidden pages