Carrier 17DA User Manual

Page 1
Number One
AirConditbning Mater
Division of Carrier Corporation
e
Carrier Parkway • Syracuse. N.Y. 13221
Open Centrifugal Refrigeration Machines
Centrifugal liquid chillers are designed to provide safe and reliable service when operated within design speci fications. When operating this equipment, use good judgment and safety precautions to avoid damage to equipment and property or injury to personnel.
Be sure you understand and follow the procedures and
safety precautions contained in the machine instructions
as well as those listed in this guide.
A DANGER
DO NOT USE OXYGEN to purge lines or to pressurize a machine for any purpose. Oxygen gas reacts violently with oil, grease and other common substances.
NEVER EXCEED specified test pressures. VERIFY the allowable test pressure by checking the instruction literature and the design pressures on the equipment
nameplate. DO NOT VALVE OFF any safety device. BE SURE that all pressure relief devices are properly
installed and functioning before operating any machine.
A WARNING
DO NOT USE eyebolts or eyebolt holes to rig machine
sections or the entire assembly. DO NOT work on high voltage equipment unless you are
a qualified electrician. DO NOT WORK ON electrical components, including
control panels, switches, starters or oil heater until you are sure ALL POWER IS OFF and no residual voltage can leak from capacitors or solid-state components.
LOCK OPEN AND TAG electrical circuits during servic ing. IF WORK IS INTERRUPTED, confirm that all circuits are de-energized before resuming work.
DO NOT syphon refrigerant by mouth. AVOID SPILLING liquid refrigerant on skin or getting it
into the eyes. USE SAFETY GOGGLES. Wash any spills
from the skin with soap and water. If any enters the eyes, IMMEDIATELY FLUSH EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a
refrigerant cylinder. Dangerous overpressure can result. When necessary to heat refrigerant, use only warm (110 F/43 C) water.
DO NOT REUSE disposable (nonreturnable) cylinders nor attempt to refill them. It is DANGEROUS AND ILLEGAL. When cylinder is emptied, bleed off remain ing gas pressure, loosen the collar and unscrew and
discard the valve stem. DO NOT INCINERATE.
CHECK THE REFRIGERANT TYPE before charging
machine. High pressure refrigerant in a low pressure machine can cause vessels to rupture if the relief devices cannot handle the refrigerant volume.
DO NOT ATTEMPT TO REMOVE fittings, covers, etc.
while machine is under pressure or while machine is running. Be sure pressure is at zero psig before breaking any refrigerant connection.
CAREFULLY INSPECT all relief valves, rupture discs
and other relief devices AT LEAST ONCE A YEAR. If
machine operates in a corrosive atmosphere, inspect the
devices at more frequent intervals. DO NOT ATTEMPT TO REPAIR OR RECONDITION
any relief valve when corrosion or build-up of foreign material (rust, dirt, scale, etc.) is found within the valve body or mechanism. Replace the valve.
DO NOT VENT refrigerant relief valves within a building; vent to outside. The accumulation of refriger
ant in an enclosed space can displace oxygen and cause asphyxiation.
DO NOT install relief valves in series or backwards. USE CARE when working near or in line with a.
compressed spring. Sudden release of the spring can cause it and objects in its path to act as projectiles.
A CAUTION
DO NOT STEP on refrigerant lines. Broken lines can whip about and cause personal injury.
DO NOT climb over a machine. Use platform, catwalk or staging. Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move inspection covers or other heavy compo nents. Even if components are light, use such equipment when there is a risk of slipping or losing your balance.
DO NOT WELD OR FLAME CUT any refrigerant line or vessel untü all refrigerant has been removed from the vessel.
BE AWARE that certain automatic start arrangements CAN ENGAGE THE STARTER. Open the disconnect ahead of the starter in addition to shutting off the machine or pump.
USE only repair or replacement parts that meet the code
requirements of the original equipment.
DO NOT VENT OR DRAIN water boxes containing
industrial brines, liquid, gases or semisolids without
permission of your Process Control Group.
DO NOT LOOSEN water box cover bolts until the water
box has been completely drained.
DOUBLE-CHECK that coupling nut wrenches, dial
indicators or other items have been removed before
rotating any shafts.
DO NOT LOOSEN a packing gland nut before checking that the nut has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings and piping for corrosion, rust, leaks or damage.
PROVIDE A DRAIN connection in the vent line near each pressure relief device to prevent a build-up of condensate or rain water.
© Carrier Corporation 1978
Form 17DA-2SS
Page 2

CONTENTS

PAGE
INTRODUCTION 2
General 2 Factory Test 2 Job Data 2 Essential Tools 3
INSPECT AND ADJUST 3
Machine Room 3 Drive Arrangement 3 Piping 3 Wiring 3
Auxiliary Equipment Wiring 3 Turbine Drive Wiring 3 Gas Engine Drive Wiring 3
Safety Controls 3
Motor Drive 4 Turbine or Gas Engine Drive 4 Pumpout System 4
LEAK TEST AND DEHYDRATION 4 CHARGE MACHINE WITH WATER 4 CHARGE MACHINE WITH OIL 5 FINAL PREOPERATION ALIGNMENT
CHECK 5
OPERATE DRIVE 5
SET PURGE VALVES AND SWITCHES 5 CHECK WATER SUPPLY 5 CHECK AIR SUPPLY, PNEUMATIC
MACHINES 5
START-UP 5
Preoperation Settings 5 Drive Operation 5 Compressor Operation 5 Charge Refrigerant 6
HOT ALIGNMENT CHECK AND
DOWELING 7
INSTRUCT CUSTOMER OPERATOR 7

INTRODUCTION

General — All persons concerned with the start-up
and operation of the centrifugal refrigeration machine should be familiar with the equipment involved. This instruction book is intended to cover general rules for start-up procedures.
Because of machine variations it is not possible to prepare an instruction book covering all minor details. This instruction book will fulfill normal requirements. Additional information may be ob tained by application to Carrier Machinery and Systems Division Service Supervisor in the nearest district office.
Special attention should be given to precaution ary instructions emphasized in this book to avoid start-up difficulties. These precautions are, in general, applicable to all sizes of 17DA centrifugal refrigeration machines.
Instructions for the prime mover if not in
cluded with Carrier Air Conditioning instructions should be obtained from the manufacturer.
Factory Test — Prior to shipment, the compressor
is completely assembled and tested. Performance as to lubrication, speed balance and general mechani cal operation has been determined to be satisfactory.
Job Data — consists of:
1. 17DA Start-Up Instructions
2. Blueprints showing: a. Machine assembly
b. Machine wiring
c. Machine piping d. Special controls, if any, and related wiring
3. 17DA Installation Instructions
4. 17DA Operation and Maintenance Instructions
%
5. Manufacturer’s Installation and Start-Up In structions for: a. Drive b. Gear (if applicable)
Page 3
Table 1 — Essential Tools
ITEM USE
1. Mechanic's tools
2. Día! indicators
3. Volt-ohmmeter 3. Calibrate controls
4. Drum charging valve
5. 5/8-inch SAE X 3/4-inch MPT adopter
6. 5 to 10 ft length of 5/8-lnch soft copper tubing with 5/8-inch flare nut on each end
7. Halide leak detector or electronic leak detector'
8. Low-pressure indicator such as: a. Absolute pressure manometer or b. Vacuum indicator
9. Portable dehydration vacuum pump — 5 or 7.5 cfm capacity
10. 1/2-inch flare plug
1. Machine piping connections, control calibration
2. Check alignment 4, Refrigerant charging connection
5. Cooler charging valve
6. Charging line
7. Leak testing machine
8. Check machine dehydration
9. Dehydrating machine
10. Block purge suction line during leak testing
Essential Tools — See Table 1 for tools and
materials required to perform initial start-up.

INSPECT AND ADJUST

Machine Room — All installation work as outlined
in 17DA Installation Instructions book should be
completed, and all construction debris must be removed from the immediate area of the machinery prior to initial start-up of the machine.
Drive Arrangement — Inspect drive mounting,
location, couphng, speed rating, etc., for agreement with job blueprints and specifications. Gear assem bly (if used) must agree with installation recom
mendations outlined in gear manufacturer’s
instructions.
Piping — Check the following installations:
1. Refrigerant pumpout system
2. External or auxiliary oil system
3. All bypass lines and valves
4. Turbine drive piping, i.e. a. Blowdown valves for each turbine stage
installed per manufacturer’s instructions.
b. Oil lubrication piping for speed control
installed in agreement with blueprints.
c. Steam supply Une condensate traps properly
installed to keep condensate out of turbine.
d. Proper supports on steam supply and ex
haust line to prevent stress or strain on the turbine at operating temperatures.
5. Gas engine drive piping — Check the following piping for agreement with job blueprints: a. Gas pressure reducing valves with shutoff
valves. Engine coolant piping with coolant thermo
b.
static valve installed so that water flows in
direction marked on valve.
c.
Oil cooler package piping Exhaust piping
d.
WARNING: Exhaust piping is critical. Refer to drive manufacturer’srecominen­dations for installation of exhaust piping.
Wiring — Refer to job wiring blueprints. All wiring
must agree with these prints. AUXILIARY EQUIPMENT WIRING - Check the
following:
1. Brine pump
2. Condenser water pump
3. CooHng tower fan motor
4. Auxiliary oil pump
5. Oil heater
6. Overload selections in all motor starters. Over load values must agree with motor nameplate data.
TURBINE DRIVE WIRING - Check the following:
1. Turbine solenoid trip mechanism. Auxiliary oil pump if used. Check pump starter
2. for proper voltage, amperage, and overload
setting. Operate pump to determine direction of rotation. Do not operate dry of oil.
3.
Check job drawings for other electrical devices
used with the turbine. Ensure that their wiring agrees with the job wiring blueprints.
GAS ENGINE DRIVE WIRING - All wiring must agree with job wiring blueprints. Refer to engine
manufacturer’s instructions for starting techniques.
Safety Controls — It is good machinery practice to
preset safety controls using standard temperature
sources; i.e., ice baths, warm circulating oil baths with standard calibrated thermometers. All con trols must be rechecked during machine operation and given final calibration as required. See Table 2
Control Settings and Fig. 1 17DA Safety Instru ment Panel.
Check the following safety controls as shown
on job blueprints:
1. Main drive de-energizing devices, i.e. a. Starter holding coil b. Turbine solenoid trip, etc.
2. Brine low-temperature cutout
3. Refrigerant low-pressure cutout
Page 4
Table 2 — Control Settings
CONTROL
Low Chilled Water Temperature
Cutout High Discharge Gas Temperature Cutout High Thrust Bearing Temperature High Condenser Pressure Cutout
Low Cooler Pressure Cutout
Low Seal Oil Pressure Cutout
Low Bearing Oil Pressure Cutout Control Panel
Auxiliary Oil Pump
Differential Pressure
Control Switch
4.
Oil low-pressure switches
Condenser high-pressure cutout
5. Check the following optional safety devices:
6.
Cooler Water Box Compressor End Wall 240 F 115 C
Compressor Bearing Chamber 180 F 82.5 C Control Panel
Control Panel
Control Pane!
Control Panel
a. Brine flow switch
Condenser water flow switch
b.
Condenser refrigerant level switch
c.
Drive protection devices
d.
Pump interlocks
e. f.
Special interlocks, timers, etc.
COOLER SEAL OIL BEARING OIL
LOCATION
SETTING
British Values
38 F or 5 F lower than brine
temperature
165 psig
Vendor set at 35 psig. Reset 2 psi below normal suction pressure.
Open 11 psid Close 16 psid
Open 8 psig Close 13 psig
Open 27 psid Close 23 psid
Metric Values
1.7 C
11.6 kg/sq cm
2.45 kg/sq cm . 14 kg/sq cm
.76 kg/sq cm
1.16 kg/sq cm
.56 kg/sq cm .90 kg/sq cm
1.90 kg/sq cm
1.60 kg/sq cm
PUMPOUT SYSTEM — The low-pressure cutout should be set at the saturated pressure of Refrigerant-12 at 34 F. A manual bypass switch is required to allow complete evacuation of the cooler. See Table 3.
Table 3 — Pumpout System Settings
SATURATED CONDITIONS
PUMPOUT
SYSTEM SETTING
Normal Condensing
Pressure
Low-Pressure Cutout
High-Pressure Cutout
Relief Valve 181.0
REFRIGERANT 12
Pressure
(psig)
Maximum
T emperature
136.4 no
31.5
157.7
(F)
34 120 130
COOLER AUXOIL LOW SEAL LOW BEARING LOW-PRESS. PUMP OIL PRESS. OIL PRESS. CUTOUT CONTROL CUTOUT CUTOUT
Fig. 1 — 17DA Safety Instrument Panel
MOTOR DRIVE — Disconnect the main motor leads at the starter to check out the safety controls without operating the motor. Disconnecting the leads to the starter holding coil will accomplish the same purpose. Place a volt-ohmmeter across the open leads. The volt-ohmmeter will indicate when the safety control circuit is de-energized as each safety control is tripped.
TURBINE OR GAS ENGINE DRIVE - These drives are shut down by interruption of power to their respective control valves or other devices. Apply a volt-ohmmeter across these open leads and
check out all safety controls as just described.

LEAK TEST AND DEHYDRATION

Check the absolute pressure on the refrigerant
side of the machine. The final operation of the
17DA Installation Instruction is to leak test the machine and dehydrate it to the point where it maintains a pressure of 0.21 psia (equivalent to
29.48 in. mercury vacuum referenced to a 30 in. barometer). Refer to Carrier Standard Service Tech niques, Form SM-1.
If the machine absolute pressure is higher than the above values, repeat the Evacuation and De hydration pumpdown operations until the machine
proves to have a leak rate or vacuum loss at a rate less than 0.1 in. mercury column in 24 hr.

CHARGE MACHINE WITH WATER

When the machine has been proved leak tight
and dry, it may be filled with water, brine or other process fluid as the case may be. Vent aU lines and
check for leaks.
It is advisable to install indicators on the
coupling halves between the compressor and drive
Page 5
or gear to check for alignment drift while charging with water and refrigerant. The weight of these materials will always cause a shift in the position of the machine components. Before and after indi
cator readings will give a good clue to the direction
final alignment should take.

CHARGE MACHINE WITH OIL

The 17DA machine has an integral lubrication system mounted on the common base with the compressor. A parallel auxiliary oil pump system
may also be furnished. Charge the oil system with
35 gal. of oil per Carrier Specification PP16-0 (Table 4). If oil other than this is used, the
replacement oil must be nearly equivalent.
Ensure that there is adequate lubrication prior to the operation of all equipment. Check the gear and drive manufacturer’s instructions for proper initial lubrication procedure. If the drive machinery is to be operated before operating the
compressor, disconnect the shaft coupling and' secure the shroud to prevent damage to the drive shaft or the coupling.
Oil pressure from the main oil pump is set at a
pressure 35 psi greater than the back-of-seal oil pressure. If, for any reason, the oil pressure falls to 23 psi above the back-of-seal oil pressure, the auxiliary oil pump starts and maintains oil pressure at a safe level.
Table 4 — Oil Specification (Carrier PP16-0)
CHARACTERISTIC VALUE
Viscosity at 100 F Viscosity at 210 F Viscosity Index, minimum
Pour Point, maximum 0 F Flash Point, minimum
Neut. No., maximum .1 mg. KOFl/gm.
Rust Inhibiting Characteristics
Oxidation Resistance
SSU — Saybolt Seconds Universal

FINAL PREOPERATION ALIGNMENT CHECK

150 - 160 SSU
40 - 45 SSU 90
400 F
Thematerial shall passthe ASTM Rust Test D665-54. Procedure A will be used with a test period of24hr.
Thematerial shall passthe ASTM Oxidation Test
D943-54 for a minimum of
1500 hr. The acid number at the end of the test period shall not exceed
2.0 mg. of KOH per gram of oil.
Prior to operating the compressor and speed increasing gear (if used), coupling alignment and separation must be checked.
1. Ensure that coupling alignment is within coupling manufacturer’s specified tolerances.
2. The hub separation tolerances are normally
stamped on coupling and vary depending on coupling size.
3. When checking hub separation, electric motor shaft must be in center position of shaft float.
If realignment is required, follow instructions
supplied by coupling manufacturer. Carrier Standard Service Techniques, Form SM-15, Rev A, also de tails realignment techniques.

OPERATE DRIVE

It is good practice to operate the drive sep arately before operating compressor. Refer to drive manufacturer’s instructions for drive protection devices and settings. Check turbine overspeed at this time. Reassemble couplings after operating drive separately.

SET PURGE VALVES AND SWITCHES

Open all the purge service valves behind purge
console. Place purge operating valves in NORMAL­AUTOMATIC position (shown on chart inside console door). Place purge switch in AUTO, position.

CHECK WATER SUPPLY

Be certain that chilled water, condensing water and oil cooler water supplies are available and that pumps will run before operating compressor.

CHECK AIR SUPPLY, PNEUMATIC MACHINES

Make sure that control air is 35 psig.

START-UP

Preoperation Settings — Complete these settings
before starting compressor for first time.
Drive Operation — Refer to drive manufacturer’s
start-up instructions. Complete drive starting
requirements before operating compressor.
If drive is wired for automatic starting, it will start when compressor START button is pushed. Starting procedure of manually started drives may
be initiated after START button is pushed.
Compressor Operation
1. Place control switch in ON position. Con denser pressure, bearing temperature and refrigerant temperature indicating lights on control console should come on.
2. Place capacity control switch in MANUAL position.
3. Open oil cooler water plug cock. Check fqr water flow at open sight drain.
4. Open bleed valve on inboard side of the
compressor.
5. Open all valves and energize heater on seal oil drain pot.
6. Open all valves in chilled water and condenser water circuits.
Page 6
WARNING: No brine over lOOF must be allowed to flow thru the cooler.
7. Ensure that there is water in the cooling tower.
8. If the auxiliary equipment such as chilled water pump, condenser water pump, and
cooling tower fan are not wired into control console circuit, start these items manually
before starting the compressor.
9. Start oil pump.
10. Close bleed valve on inboard side of the compressor.
11.17DA compressors are equipped with an AUTO-MANUAL control station. The initial start should be on manual control from this station.
12. Start compressor. a. Bump electric motors by pushing the
START and STOP buttons in quick succession. Compressor rotation must be counterclockwise when viewed from drive end.
b. Run turbine or engine drives at slow
speed.
13. Listen carefully for unusual mechanical noise while coasting down.
14. Shut down.

Charge Refrigerant

WARNING: When liquid Refrigerant-12 is in jected into a low vacuum of 29.48 in. mercury
it will unmediately flash to a gas at a tempera ture lower than minus 100 F. It is for this reason that water must be circulating before
charging liquid refrigerant. Non circulating water would quickly freeze and damage the machine. If an auxiUaiy' refrigerant storage tank
(receiver) is furnished, liquid refrigerant may be
charged directly into this evacuated receiver
without danger.
Large machines run with liquid refrigerant in
the cooler so refrigerant is charged into the cooler
or low-pressure side of the machine. For general
instructions on how to handle refrigerant refer to
Carrier Standard Service Techniques, Form SM-1. Use the Charging by Weight method, cross check ing with the machine’s refrigerant sight glass pro vided on the back of the cooler shell, and the
suction pressure gage.
Charge refrigerant as follows:
1. Start Cooler and Condenser water circulating pumps.
2. Charge the first refrigerant in the vapor state, continuing until the machine pressure exceeds 35 psig. The refrigerant temperature corre sponding to this pressure is high enough to
prevent water freezing damage and will also satisfy the refrigerant low-pressure cutout safety switch setting (31.5 psig). Now turn the refrigerant bottles or drums over and begin charging the refrigerant in the liquid phase. Continue charging liquid refrigerant until about 2/3 of the estimated full load charge is in the machine.
3. Adjust control station to operate at MANUAL. Ensure that the guide vanes are closed as indicated on the main guide vane indicator.
4. Set Subcooler Level Controller as follows:
a. Set Proportional Band at 35%. b. Set Level-Set adjustment at 50%. When stable operation is achieved, readjust
Level-Set to maintain the Hquid level at the
midpoint of the sight glass on the Level
Controller. Recheck this level when full load is
reached and reset if necessary.
5. Start the compressor. Observe the machine’s operation for 15-20 min before increasing the
load. During this period, make the following
checks and adjustments : a. Check oil pressure. b. Adjust water flow thru oü cooler so that
bearing temperatures stay between 150 F and 170 F approximately.
c. Watch bearing temperatures carefully. This
is the first time that the machine has been run under refrigeration load. Bearing tem peratures may level off at some temperature
slightly higher than 170 F hsted above. This may be the normal stable condition for this bearing. High thrust bearing temperature will shut the machine down at 180 F.
6. Slowly open the guide vanes, by manual con trol, thus increasing the load. Do not exceed the current rating of the electric motor. Watch for other signs of overloading a turbine or engine drive.
7. Add Uquid refrigerant, trimming the charge off at the point where the machine reaches design operating temperature and pressure conditions.
WARNING: Excessive overcharge may cause liquid refrigerant carry-over into the com pressor, causing severe overload and possible compressor damage.
8. Shut the machine off. When the refrigerant level settles down, mark this optimum level on the sight glass. Maintain this shutdown level. To determine the approximate refrigerant charge for your machine, add the cooler charge to the applicable condenser charge as listed in Table 5.
Page 7
Table 5 — Typical 17DA Coder and Condenser
Refrigerant Charges (lb)
COOLER
SIZE
61 63 65 67 4,600 5,600
651* 3,500
671*
71 73 75 6,100 7,300 81 83
85
87 9,500
* Refrigerant 500

HOT ALIGNMENT CHECK AND DOWELING

15-FT
TUBES
3,300 3,900 4,000 4,700 5,800
4,000
4,200 5,100 6,100 5,500
7,100 8,500 7,600 8,500
18-FT
TUBES
4,700 4,200
5,000
6,500
9,200 10,100 11,400
22-FT COND
TUBES
4,800 61 2200 5,800 .
6,800 Î 5,100 ' 6,100 7,500 8,000 73
8,900 10,400 11,200 12,400 13,900
SIZE WT
651* 2500 671*
REFRIG
63 65 67
71 2900
75 3400
81 3900 83 4400 85 5100 87 4900
2200
2700 2700
2500 2900
After the machine has been running at about
full load for four hours, its components will have
come up to steady state operating temperature conditions and the final hot alignment check may
be made.
Realign component locations until angular and parallel alignments are within coupling manu facturer’s specified tolerances.
Dowel all equipment into place as soon as the hot alignment check proves that the machine is within these running tolerances.
See Carrier Standard Service Techniques, Form
SM-15, Rev A, for these operations.

INSTRUCT CUSTOMER OPERATOR

The following is an outline guide for giving
operating instructions to the customer’s operator.
1. Present operator with copy of Operating and Maintenance Instructions.
2. Point out machine components and explain function and settings for each.
a. Controls
(1) Safety panel, gages and safety
switches
(2) Control station, manual-automatic
modes
Compressor
b.
(1) Oil reservoir (2) Seal (3) Guide Vanes (4) Auxiliary oil pump, filter and cooler (5) Bleed valve
Cooler
c.
(1) Refrigerant level sight glass (2) Pressure relieving valve
Condenser
d.
(1) Sub-cooler
(2) Leveltrol
e. Purge
(1) Operation
(2) Maintenance f. Drive and gear g. Pumpout system (if supplied) h. Auxiliary gages and thermometers
3. Refrigerant cycle a. Explain system b. Importance of log sheets
4. Describe compressor lubricating oil system.
a. Oil heater
b. Oil cooler
c. Pressure regulating valve, back pressure
valves, etc.
d. Auxiliary oil system (if supplied)
5. Point out safety and operating controls and explain function of each.
a. Standard controls b. Special controls
6. Instruct proper operating procedure.
a. Preparation for start-up (valves, electrical,
etc.)
b. Starting methods c. Running measurements and maintenance
of log d. Shutdown e. Extended shutdown
7. Review maintenance items. a. Daily b. Items to watch
c. Extended shutdown
d. Water treatment and strainer cleaning
8. Review spare parts lists.
9. Advise regarding Carrier Planned Service. a. Maintenance contracts b. Inspection Contracts c. Carrier Regional Service Schools
10. Review special features of machine. a. Operation of pumpout system and valve
settings
b. Drive maintenance and operating
precautions
c. Starter settings and location
11. Leave phone number of Machinery and Systems Division, Carrier Corp. for quick reference.
12. Review questions and answers on Operation and Maintenance Instructions.
13. Advise on start of Warranty Period.
Page 8
For replacement items use Carrier Specified Parts.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book
2
Tab 5d
Form 17DA-2SS Supersedes 1 7DA-1SS Printed in U.S.A.
11-78 PC 211 Catalog No. 531-733
Loading...