Carrier 16JT810, 16JT816, 16JT812, 16JT814, 16JT818 Start Up & Operation Manual

...
Start-Up, Operation, and
Maintenance Instructions
SAFETY CONSIDERATIONS
Absorption liquid chillers provide safe and reliable serv­ice whenoperatedwithin design specifications. When op­erating this equipment, use good judgment and safety precautions to avoid damage to equipment and property or injury to personnel.
DO NOT USE OXYGEN or air to purge lines, leak test, or pressurize a machine. Use nitrogen.
NEVER EXCEED specifiedtest pressures. For the 16JTchiller, the maximum pressure is 12 psig (83 kPa).
WEAR goggles and suitable protective clothing when han­dling lithium bromide, octyl alcohol, inhibitor, lithium hy­droxide, and hydrobromic acid. IMMEDIATELY wash any spills from the skin with soap and water. IMMEDIATELY FLUSH EYES with water and consult a physician.
DO NOT USE eyebolts or eyebolt holes to rig machine sec­tions or the entire assembly.
DO NOT work on high-voltage equipment unless you are a qualified electrician.
DO NOT WORK ON electrical components, including con­trol panels or switches, until you are sure ALL POWER IS OFF and no residual voltage can leak from capacitors or solid­state components.
LOCK OPEN AND TAG electrical circuits during servic­ing. IF WORK IS INTERRUPTED, confirm that all circuits are deenergized before resuming work.
NEVER DISCONNECT safety devices or bypass electric in­terlocks and operate the machine. Also, never operate the machine when any safety devices are not adjusted and func­tioning normally.
DO NOT syphon lithium bromide or any other chemical by mouth.
BE SURE all hydrogen has been exhausted before cutting into purge chambers. Hydrogen mixed with air can explode when ignited.
WHEN FLAMECUTTING OR WELDING on an absorp­tion machine, some noxious fumes may be produced. Ven­tilate the area thoroughly to avoid breathing concentrated fumes.
DO NOT perform any welding or flamecutting to a machine while it is under a vacuum or pressurized condition.
NEVER APPLY an open flame or live steam to a refrigerant cylinder. Dangerous overpressure can result. When neces­sary to heat a cylinder, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or at­tempt to refill them. It is DANGEROUS AND ILLEGAL. When cylinder is emptied, evacuate remaining gas pressure, loosen the collar and unscrew and discard the valve stem. DO NOT INCINERATE.
DO NOTATTEMPT TO REMOVE fittings, covers, etc., while machine is under pressure or while machine is running.
DO NOT climb over a machine. Use platform, catwalk, or staging. Follow safe practices when using ladders.
DO NOT STEP ON machine piping. It might break or bend and cause personal injury.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move inspection covers or other heavy components. Even if components are light, use such equipment when there is a risk of slipping or losing your balance.
VALVE OFF AND TAG steam, water, or brine lines before opening them.
DO NOT LOOSEN waterbox cover bolts until the water box has been completely drained.
DO NOT VENT OR DRAIN waterboxes containing indus­trial brines, liquid, gases, or semisolids without permission of your process control group.
BE AWARE that certain automatic start arrangements can engage starters. Open the disconnects ahead of the starters in addition to shutting off the machine or pump.
USE only repaired or replacement parts that meet the code requirements of the original equipment.
DO NOT ALLOW UNAUTHORIZED PERSONS to tamper with machine safeties or to make major repairs.
PERIODICALLY INSPECT all valves, fittings, piping, and relief devices for corrosion, rust, leaks, or damage.
PROVIDE A DRAIN connection in the vent line near each pressure relief device to prevent a build-up of condensate or rain water.
IMMEDIATELY wipe or flush the floor if lithium bromide or octyl alcohol is spilled on it.
16JT
60 Hz
Double-Effect Hermetic Absorption Liquid Chillers
Units 810-880, 080-150, 080L-150L
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5b
PC 211 Catalog No. 531-607 Printed in U.S.A. Form 16JT-2SS Pg 1 4-93 Replaces: 16JT-1SS
CONTENTS
Page
SAFETY CONSIDERATIONS ...................1
INTRODUCTION ..............................3
MACHINE DESCRIPTION .....................3-9
Basic Absorption Cycle ......................3
Double-Effect Reconcentration ................3
Machine Construction ........................3
Flow Circuits ................................6
Equilibrium Diagram and Chiller
Solution Cycle .............................7
• PLOTTING THE SOLUTION CYCLE
Purge System ................................9
MACHINE CONTROLS .....................10-19
Start-Stop Systems .........................10
• SEMI-AUTOMATIC START-STOP
• FULL AUTOMATIC START-STOP
Control Wiring ..............................10
Control Panel ...............................10
Typical Control Sequence, Normal Start ......14
Typical Control Sequence, Normal Stop ......16
Typical Control Sequence,
Abnormal Stop ............................17
Capacity Control ............................18
• CONTROLLER
High Concentration Limit ....................19
Low Concentration Limit ....................19
High-Stage Generator Level Limit ............19
BEFORE INITIAL START-UP ................19-22
Job Data and Tools Required ................19
Inspect Field Piping .........................20
Inspect Field Wiring .........................20
Standing Vacuum Test ......................20
• LONG INTERVAL TEST
• SHORT INTERVAL TEST
Machine Evacuation .........................21
Solution and Refrigerant Charging ...........21
• HANDLING LITHIUM BROMIDE SOLUTION
• CHARGING SOLUTION
• CHARGING FOR CONDITIONS OTHER THAN NOMINAL
• INITIAL REFRIGERANT CHARGING
INITIAL CONTROL CHECKOUT
AND ADJUSTMENT ......................22-24
Preparation .................................22
Energize Control Circuit .....................22
Check Solution and Refrigerant
Pump Starters ............................22
Check Pump Starter Overloads ..............22
Check Low-Temperature Cutout ..............22
Check Cycle-Guard™ Valve ..................23
Check Solution Thermoswitch ...............23
Check High-Stage Generator
Temperature Thermoswitch ................23
Check High-Stage Generator
Pressure Switch ..........................23
Check Rotation of Solution and
Refrigerant Pumps ........................23
Check Capacity Control Operation ...........23
Completion .................................24
INITIAL START-UP .........................25-27
Preliminary Check ..........................25
• PREPARATION
Page
Final Adjustment of Capacity Controls .......25
• WITH THE MANUAL PROCEDURE
• WITH THE AUTOMATIC PROCEDURE
Final Refrigerant Charge Adjustment .........25
Check Machine Shutdown ...................27
Check Low-Evaporator Level Operation ......27
Determine Noncondensable
Accumulation Rate ........................27
OPERATING INSTRUCTIONS ...............27-30
Operator Duties .............................27
Before Starting Machine .....................27
Start Machine ...............................27
Start-Up After Limited Shutdown .............28
Start-Up After Extended Shutdown ...........28
Start-Up After Below Freezing
Conditions ................................28
Machine Shutdown — Normal Conditions ....28
Machine Shutdown — Below Freezing
Conditions ................................28
Actions After Abnormal Shutdown ...........29
Actions After Power Interruption .............29
PERIODIC SCHEDULED MAINTENANCE ......29
Every Day of Operation ......................29
Every Month of Operation ...................29
Every 2 Months of Operation ................29
Every 6 Months of Operation ................29
Every Year of Operation .....................29
Every 3 Years of Operation ..................29
Every 5 Years or 20,000 Hours
of Operation ..............................29
MAINTENANCE PROCEDURES .............29-40
Log Sheets .................................29
Purge Manual Exhaust Procedure ............31
Absorber Loss Determination ................31
Noncondensable Accumulation Rate .........31
Machine Leak Test ..........................33
Machine Evacuation .........................33
Solution or Refrigerant Sampling ............34
• SOLUTION SAMPLE
• REFRIGERANT SAMPLE
Solution Analysis ...........................34
Inhibitor ....................................34
Adding Octyl Alcohol ........................35
Removing Lithium Bromide from
Refrigerant ...............................35
Refrigerant Charge Adjustment ..............35
Capacity Control Adjustment ................35
Low-Temperature Cutout Adjustment .........35
Cycle-Guard™ System Operation ............35
Thermoswitch Adjustment ...................36
Low-Refrigerant Level Operation .............36
Internal Service .............................36
Service Valve Diaphragm Replacement .......36
Hermetic Pump Inspection ...................36
• DISASSEMBLY
• INSPECTION
• REASSEMBLY
• COMPLETION
Solution Decrystallization ...................40
Condensing Water Tube Scale ...............40
Water Treatment ............................40
TROUBLESHOOTING GUIDE ...............41,42
2
INTRODUCTION
Everyone involved in the start-up, operation, and main­tenance of the 16JT machine should be thoroughly familiar with the following instructions and other necessary job data before initial start-up, and before operating the machine and its control system or performing machine maintenance. Pro­cedures are arranged in the sequence required for proper ma­chine start-up and operation.
MACHINE DESCRIPTION
BasicAbsorptionCycle —
The 16JT absorption chiller uses water as the refrigerant in vessels maintained under a deep vacuum. The chiller operates on the simple principle that under low absolute pressure (vacuum), water takes up heat and vaporizes (boils) at a low temperature. For ex­ample, at the very deep vacuum of 0.25 in. (6.4 mm) of mer­cury absolute pressure, water boils at the relatively cool temperature of only 40 F (4 C). To obtain the energy re­quired for this boiling, it takes heat from, and therefore chills, another fluid (usually water). The chilled fluid then can be used for cooling purposes.
To make the cooling process continuous, the refrigerant vapor must be removed as it is produced. For this, a solution of lithium bromide salt in water is used to absorb the water vapor. Lithium bromide has a high affinity for water, and will absorb it in large quantities under the right conditions. The removal of the refrigerant vapor by absorption keeps the machine pressure low enough for the cooling vaporiza­tion to continue. However, this process dilutes the solution and reduces its absorption capacity.Therefore the diluted lithium bromide solution is pumped to separate vessels where it is heated to release (boil off) the previously absorbed water. Relatively cool condensing water from a cooling tower or other source removes enough heat from this vapor to con­dense it again into liquid for reuse in the cooling cycle. The reconcentrated lithium bromide solution is returned to the original vessel to continue the absorption process.
Double-Effect Reconcentration — The 16JT re-
concentrates solution in 2 stages to improve the operating eff iciency.Approximately half of the diluted solution is pumped to a high-temperature vessel (high stage) where it is heated directly from high-pressure steam for reconcentration. The other half of the solution flows to a low-temperature vessel (low stage) where it is heated for reconcentration by hot wa­ter vapor released in the high-temperature vessel. The low stage acts as the condenser for the high stage, so the heat energy first applied in the high-stage vessel is used again in
the low-stage vessel. This cuts the heat input to almost half of that required for an absorption chiller with a single re­concentrator.
Machine Construction — The major sections of
the machine are contained in several vessels (Fig.1-6, and Table 1).
The large lower shell contains the evaporator and ab­sorber sections. The evaporator and absorber are positioned side by side in units 16JT810-880, but the evaporator is positioned above the absorber in units 16JT080-150, 080L-150L. In the evaporator section, the refrigerant water vaporizes and cools the chilled water for the air conditioning or cooling process. In the absorber, vaporized water from the evaporator is absorbed by lithium bromide solution.
The smaller vessel above the evaporator/absorber assem­bly is the high-stage generator. Here, approximately half of the diluted solution from the absorber is heated and recon­centrated to recover slightly over half of the water previ­ously absorbed.
The other shell above the evaporator/absorber assembly contains the low-stage generator and condenser. The other half of the diluted solution is heated and reconcentrated in the low-stage generator by high temperature water vapor from the high-stage generator. The water vapor released from the solution in this process is condensed to liquid in the con­denser section.
This chiller also has: two solution heat exchangers and a steam condensate heat exchanger to improve operating economy; an external purgesystem to maintain machine vacuum by the removal of noncondensables; hermetic pumps to cir­culate the solution and refrigerant; and various operational, capacity, and safety devices to provide automatic, reliable machine performance.
Table 1 — 16JT Description
UNIT 16JT
ABSORBER/
EVAPORATOR
SOLUTION
PUMPS
PURGE POINTS
AND
EDUCTORS
810-854 Side-by-side 1 1
857,865 Side-by-side 1 2
873,880 Side-by-side 2 2
080-120 Over-and-under 2 4
135, 150 Over-and-under 2 or 3 4 080L-120L Over-and-under 2 4 135L,150L Over-and-under 2 or 3 4
3
1
8
7
65
2 (NOT SHOWN)
34
LEGEND
1—High-Stage Generator 2—Low-Stage Generator 3—Condenser 4—Purge Storage Chamber
5—Control Panel 6—Solution Heat Exchanger 7—Absorber 8—Evaporator
Fig.1—Typical Machine Components, 16JT810-880
2
1
8
7
3
4
5
6
LEGEND
1—High-Stage Generator 2—Low-Stage Generator 3—Condenser 4—Purge Storage Chamber
5—Control Panel 6—Solution Heat Exchanger 7—Absorber 8—Evaporator
Fig.2—Typical Machine Components, 16JT080-150, 080L-150L
4
Fig. 3 — 16JT810-880 Machine Components, External Schematic (Typical)
LEGEND
1—Rupture Disk 2—Refrigerant Condensate Line 3—Auxiliary Evacuation Valve 4—Storage Chamber for Purge 5—Purge Separation Chamber 6—Strong Solution Overflow Line 7—Strong Solution Line 8—Low-Temperature Generator-
Condenser Shell
9—High-Refrigerant Level Switches 10 — Cycle-Guard™ Valve 11 — Refrigerant Pump 12 — Low-Refrigerant Level Switch 13 — J-Loop Box 14 — Purge Exhaust Valve 15 — Purge Solution Return Line 16 — Purge Solution Return Valve 17 — Control Panel 18 — Low-Temperature Heat Exchanger 19 — Strong Solution Line to Absorber 20 — Absorber Waterbox 21 — Evaporator Waterbox 22 — Condenser Waterbox 23 — Condensate (Drain) Heat Exchanger 24 — Condensate (Drain) Outlet 25 — Condensate (Drain) Trap 26 — High-Temperature Generator Shell 27 — Steam Box 28 — Solution Pump 29 — Solution Pump (Larger Sizes Only) 30 — High-Temperature Heat Exchanger 31 — Weak Solution Line 32 — Absorber-Evaporator Shell
Fig. 4 — 16JT080-150 and 16JT080L-150L Machine Components, External Schematic (Typical)
5
FlowCircuits — Figures 5 and 6 illustrate the basic flow
circuits of the 16JT absorption chiller.
The liquid to be chilled is passed through the evaporator tube bundle and is cooled by the evaporation of refrigerant water sprayed over the outer surface of the tubes by the re­circulating refrigerant pump. The refrigerant vapors are drawn into the absorber section and are absorbed by the lithium bromide-water solution sprayed over the absorber tubes. The heat picked up from the chilled liquid is transferred from the absorbed vapor to cooling water flowing through the ab­sorber tubes.
The solution in the absorber becomes diluted as it absorbs water, and loses its ability to continue the absorption. It is then transferred by the solution pump to the generator sec­tions to be reconcentrated. Approximately half of the weak (diluted) solution goes to the high-stage generator where it is heated directly by high-pressure steam to boil out its ab­sorbed water. This vapor passes to the low-stage generator tubes. In the low-stage generator, the rest of the weak so­lution is heated by the high-temperature vapor from the high­stage generator, to boil out its absorbed water.
This water vapor from the low-stage generator solution passes into the condenser section and condenses on tubes containing cooling water.This is the same cooling water which had just flowed through the absorber tubes. The condensed high-temperature water from the low-stage generator tubes also passes over the condenser tubes where it is
cooled to the condenser temperature. The combined con­densed refrigerant liquid from the two generators now flows back to the evaporator to begin a new refrigerant cycle.
The strong (reconcentrated) solution flows from the two generators back to the absorber spray headers to begin a new solution cycle. On the way, it passes through solution heat exchangers where heat is transferred from the hot, strong so­lution to the cooler, weak solution being pumped to the gen­erators. Solution to and from the high-stage generator passes through both a high-temperature heat exchanger and a low-temperature heat exchanger. Solution to and from the low-stage generator passes through only the low-temperature heat exchanger, mixed with the high-stage generator solu­tion. This heat transfer improves solution cycle efficiency by preheating the relatively cool, weak solution before it enters the generators, and precooling the hotter, strong solution be­fore it enters the absorber. The efficiency is further improved by transferring heat to the cooler, weak solution from the hot steam condensate in the condensate drain heat exchanger and trap.
The weak solution flowing to the generators passes through a flow control valve which is positioned by a float in the high-stage generator overflow box. The purpose of the valve is to automatically maintain optimum solution flow to the two generators at all operating conditions for maximum efficiency.
LEGEND
EA Refrigerant Pump Overload Cutout EA1 — Refrigerant Pump Overload Cutout EA2 — Solution Pump Overload Cutout EA3 — Solution Spray Pump Motor Overload Cutout EA4 — Vacuum Pump Motor Overload FA1 Chilled Water Low-Flow Cutout I/P Current/Pneumatic Transducer LC Refrigerant Cutout Level Switches
(High, Mid, Low)
PA1 High-Pressure Switch (High-Stage
Temperature Generator)
P1 Compound Gage (High-Temperature
Generator)
PWS1 — Absorber Pressure Switch
SA Pneumatic Supply Air TA1 Chilled-Water Low-Temperature Cutout TA3 Refrigerant Pump Motor Coil High-
Temperature Cutout
TA4 Solution Pump Motor Coil High-
Temperature Cutout
TA5 Solution High-Temperature Cutout TC2 Cooling Water Temperature Cutout TIC Chilled Water Outlet Temperature Control TI 1-4 — Weak Solution Thermometers TI 5-8 — Strong Solution Thermometers TI 9-10 — Refrigerant Thermometers
TSW1 — Automatic Start-Stop Thermostat TSW2 — Cycle-Guard™ Thermostat
Control Wiring Piping Connections
Valve
NOTES:
1. Spray pump and second solution pump are lo­cated on large sizes only.
2. Vacuum pump is optional.
3. Electric capacity control is shown. (Pneumatic is optional.)
*The LCD valve is physically located with the float in the high stage generator overflow box, not
where it is schematically shown in the illustration.
Fig.5—Typical Flow Circuits, with Data Points, Shown for 16JT080-150,080L-150L Arrangements
6
During high load operation, some abnormal conditions can cause the lithium bromide concentration to increase above normal, with the strong solution concentration close to crys­tallization (see Equilibrium Diagram and Chiller Solution Cycle.) If, for some reason, the machine controls do not pre­vent strong solution crystallization during abnormal operat­ing conditions and flow blockage does occur, the strong­solution overflow pipe will reverse or limit the crystallization until the cause can be corrected. The overflow pipe is lo­cated between the low-temperature generator discharge box and the absorber, bypassing the heat exchanger, as shown in Fig. 5.
If crystallization occurs, it generally takes place in the shell side of the low-temperature heat exchanger,blocking the flow of strong solution from the generator. The strong solution then backs up in the discharge box and spills over into the overflow pipe, which returns it directly to the absorber sump. The solution pump then returns the hot solution through the heat exchanger tubes, automatically heating and decrystal­lizing the shell side.
Equilibrium Diagram and Chiller Solution Cycle —
The solution cycle can be illustrated by plotting it on a basic equilibrium diagram for lithium bromide in so­lution with water (Fig. 7). The diagram is also used for per­formance analyses and troubleshooting.
The left scale on the diagram indicates solution and water vapor pressures at equilibrium conditions. The right scale indicates the corresponding saturation (boiling or condens­ing) temperatures for both the refrigerant (water) and the solution.
The bottom scale represents solution concentration, ex­pressed as percentage of lithium bromide by weight in so­lution with water. For example, a lithium bromide concen­tration of 60% means 60% lithium bromide and 40% water by weight.
The curved lines running diagonally left to right are so­lution temperature lines (not to be confused with the hori­zontal saturation temperature lines). The single curved line beginning at the lower right represents the crystallization line. The solution becomes saturated at any combination of tem­perature and concentration to the right of this line, and it will begin to crystallize (solidify) and restrict flow.
The slightly sloped lines extending from the bottom of the diagram are solution-specific gravity lines. The concentra­tion of a lithium bromide solution sample can be determined by measuring its specific gravity with a hydrometer and read­ing its solution temperature. Then, plot the intersection point for these 2 values and read straight down to the percent lithium bromide scale. The corresponding vapor pressure can also be determined by reading the scale straight to the left of the point, and its saturation temperature can be read on the scale to the right.
PLOTTING THE SOLUTION CYCLE —An absorption so­lution cycle at typical full load conditions is plotted in Fig. 7 from Points 1 through 13. The corresponding values for these typical points are listed in Table 2. Note that these values will vary with different loads and operating conditions.
Point 1 represents the strong solution in the absorber, as it begins to absorb water vapor after being sprayed from the absorber nozzles. This condition is internal and cannot be measured.
Point 2 represents the diluted (weak) solution after it leaves the absorber and before it enters the low-temperature heat exchanger.This includes its flow through the solution pump. This point can be measured with a solution sample from the pump discharge.
Point 3 represents the weak solution leaving the low­temperature heat exchanger. It is at the same concentration as Point 2, but at a higher temperature after gaining heat from the strong solution. This temperature can be measured.
Point 4 represents the weak solution leaving the drain heat exchanger. It is at the same concentration as Point 3, but at a higher temperature after gaining heat from the steam con­densate. This temperature can be measured. At this point the weak solution first flows through the level control device (LCD) valve and then it is split, with approximately half going to the low-stage generator, and the rest going on to the high­temperature heat exchanger.
Point 5 represents the weak solution in the low-stage gen­erator after being preheated to the boiling temperature. The solution will boil at temperatures and concentrations corre­sponding to a saturation temperature established by the va­por condensing temperature in the condenser. This condition is internal and cannot be measured.
Point 6 represents the weak solution leaving the high­temperature heat exchanger and entering the high-stage gen­erator.It is at the same concentration as Point 4 but at a higher temperature after gaining heat from the strong solution. This temperature can be measured.
Point 7 represents the weak solution in the high-stage gen­erator after being preheated to the boiling temperature. The solution will boil at temperatures and concentrations corre­sponding to a saturation temperature established by the va­por condensing temperature in the low-stage generator tubes. This condition is internal and cannot be measured.
Point 8 represents the strong solution leaving the high-stage generator and entering the high-temperature heat exchanger after being reconcentrated by boiling out refrigerant. It can be plotted approximately by measuring the temperatures of the leaving strong solution and the condensed vapor leaving the low-stage generator tubes (saturation temperature). This condition cannot be measured accurately.
Point 9 represents the strong solution from the high-temperature heat exchanger as it flows between the two heat exchangers. It is the same concentration as Point 8 but at a cooler tem­perature after giving up heat to the weak solution. The tem­perature can be measured on those models which have sepa­rate solution heat exchangers.
LCD — Level Control Device TC — Temperature Control (Capacity Control)
Fig.6—Typical Flow Circuits, (Simplified)
Arrangement Shown for 16JT810-880
7
Point 10 represents the strong solution leaving the low-stage generator and entering the low-temperature heat exchanger. It is at a weaker concentration than the solution from the high-stage generator, and can be plotted approximately by measuring the temperatures of the leaving strong solution and vapor condensate (saturation temperature). This condi­tion cannot be measured accurately.
Point 11 represents the mixture of strong solution from the high-temperature heat exchanger and strong solution from the low-stage generator as they both enter the low-temperature heat exchanger. The temperature can be measured on those models which have separate solution heat exchangers.
Point 12 represents the combined strong solution before it leaves the low-temperature heat exchanger after giving up heat to the weak solution. This condition is internal and can­not be measured.
Point 13 represents the strong solution leaving the low­temperature heat exchanger and entering the absorber spray nozzles, after being mixed with some weak solution in the heat exchanger. The temperature can be measured, but the concentration cannot be sampled. After leaving the spray nozzles, the solution is somewhat cooled and concentrated as it flashes to the lower pressure of the absorber, at Point 1.
Table2—Typical Full Load Cycle Equilibrium Data
POINT
SOLUTION TEMPERATURE VAPOR PRESSURE
SOLUTION PERCENTAGE
(Lithium Bromide)
SATURATED TEMPERATURE
F C in. Hg mm Hg F C
1 110 43 0.24 6 62.2 40 4 2 95 35 0.24 6 58.0 40 4 3 149 65 1.10 29 58.0 83 28 4 160 71 1.50 39 58.0 93 34 5 167 75 2.00 50 58.0 100 38 6 277 136 19.00 490 58.0 191 88 7 289 143 24.00 600 58.0 200 93 8 318 159 24.00 600 63.6 200 93
9 167 75 110 28 63.6 82 28 10 180 82 2.00 49 61.3 100 38 11 176 80 1.60 40 62.2 93 34 12 117 47 0.31 8 62.2 46 8 13 111 44 0.28 7 61.5 43 6
LCD — Level Control Device TC — Temperature Control (Capacity Control)
Fig. 7 — Equilibrium Diagram and Chiller Solution Cycle
8
Purge System — The basic components and flow cir-
cuits of the motorless purge are shown in Fig. 8 and 9.
The purge system automatically removes noncondens­ables from the machine and transfers them to a storage cham­ber where they cannot affect machine operation. Noncondensables are gases such as N
2,O2
, and H2which will not condense at the normal chiller operating tempera­tures and pressures and, because they reduce the machine vacuum, they reduce the machine capacity.
Some hydrogen (H
2
) gas is liberated within the machine during normal operation and its rate of generation is con­trolled by the solution inhibitor. The presence of most other gases in the machine would occur either through a leak (the machine is under a deep vacuum) or by entrainment in the refrigerant and solution at initial charging. During opera­tion, any noncondensables accumulate in the absorber, which is the lowest pressure area of the machine.
For purging, the gases are continuously drawn from the absorber into the lower pressure of eductors, where they are entrained in solution flowing from the solution pump. The mixture then continues on to the purge storage tank. The non­condensables are released in a separator and the solution flows back to the absorber by way of the generator overflow pipe.
Noncondensables accumulate in the purge storage tank where they are isolated from the rest of the machine. The storage chamber is initially filled with solution that is dis­placed as the chamber gradually fills with noncondensables. These gases then must be periodically exhausted from the storage chamber by a manual procedure. This is begun by closing a solution return valve to force solution from the pump into the chamber to compress the noncondensables to above atmospheric pressure. Then an exhaust valve is opened to bleed the noncondensables to the atmosphere through solu­tion in an exhaust bottle. This operation is described in the Maintenance Procedures, Purge Manual Exhaust Procedure section, page 31.
Some chillers also have an optional, permanently in­stalled vacuum pump system (as shown in Fig. 5) to remove noncondensables directly from the absorber for machine evacuation at initial start-up and after service work.
The pump is wired into the chiller control circuit for power.
LEGEND
1—Storage Chamber 6—Check Valve 2—Auxiliary Valve 7—Exhaust Liquid Seal Bottle 3—Eductor Device 8—Solution Return Valve 4—Solution from Solution 9—Separation Chamber
Pump 10 — Exhaust Valve
5—Solution Returning to
Absorber
Fig. 8 — Purge System, 16JT810-880
LEGEND
1—Storage Chamber 7—Eductor 2—Solution Return Valve 8—Hermetic Solution Pumps 3—Eductor 9—Separation Chamber 4—Eductor 10 — Exhaust Bottle 5—J-Loop Box 11 — Exhaust Valve 6—Eductor
NOTE: Number of eductors varies from one on smaller sizes to 4 on larger sizes.
Fig. 9 — Purge System, 16JT080-150, 080L-150L
9
MACHINE CONTROLS
Start-Stop Systems —
The type of start-stop system is selected by the customer. The most commonly used sys­tems are described below. Review the descriptions and de­termine which type applies to your system.
SEMI-AUTOMATIC START-STOP— In this basic system, auxiliary equipment is wired into the machine control cir­cuit and the machine is started and stopped manually with the machine’s Start and Stop buttons. Twovariations are used:
WithPilot Relays — The coils for the chilled water and con­densing water pump starters (or other auxiliary equipment) are wired into the machine control circuit so that the aux­iliary equipment operates whenever the machine operates. The starter contacts and starter overloads remain in the ex­ternal pump circuits. The flow interlocks for each pump are also wired into the machine control circuit and must be closed in order for the machine to operate.
WithManual Auxiliaries — Withthis system, the auxiliaries must be started manually and independently from the ma­chine start, and they must be operating before the ma-chine can start. As with the pilot relay system above, the
flow interlocks are in the machine control circuit and must be closed for the machine to operate.
FULL AUTOMATIC START-STOP — This system is ba­sically the same as the semi-automatic system with pilot re­lays described above. Machine and auxiliary start and stop, however,are controlled by a field-supplied thermostat, timer, or other automatic device, and the machine Start and Stop manual switch and indicator lights remain in the STARTmode.
As with all the Start-Stop systems, the machine’s Start but­ton must be depressed and released on initial start, and after power interruption. After an abnormal shutdown, the Stop button must be depressed to reset the circuit and silence the alarm buzzer before depressing Start.
Control Wiring — See Fig. 10 and 11 for typical wiring
schematics and component identification. NOTE: These schematics do not show all the options or varia-
tions that are available.
Control Panel — The control panel includes the con-
troller, switches, pilot lights, and relays that operate the ma­chine (Fig. 12 and 13).
LEGEND FOR FIGURES 10 AND 11
1X1,2 — Start-Stop Relays 1Y1,2 — Shutdown Dilution Relays 2X Run Relay 2T1 Time Delay Relay, Chilled Water Flow 3-1 Manual Start Switch Button 3-5 Manual Stop Switch Button 3-BZ Alarm Buzzer Stop Button 3-VP Manual Vacuum Pump On-Off Buttons 3X Auto Start Relay 4X Safety Device Relay 4Y Safety Interlock Relay 20RV — Cycle-Guard™ Valve 23C Low Load Limit Switch 26CW — Low Chilled Water Temperature Limit 26GH — Generator Solution High-Temperature Limit 26MX — Hermetic Pump Fault Relay 26RP — Refrigerant Pump Motor High-Temperature LImit 26SH — Absorber Solution High-Temperature Limit 26SP1 — Solution Pump No. 1 Motor High-Temperature Limit 26SP2 — Solution Pump No. 2 Motor High-Temperature Limit 26SSP — Solution Spray Pump Motor High-Temperature LImit 30X1,2 — Safety Stop Interlock Relays 33RD — Refrigerant Dilution Level Switch 33RH — Refrigerant High-Level Switch 33RHX — Refrigerant High-Level Relay 33RL — Refrigerant Low-Level Switch 33RM — Refrigerant Mid-Level Switch 33RMX — Dilution Level Control Relay 33W Generator Level Control Relay 43R Remote-Local Switch 43RV — Cycle-Guard Auto.-Manual Selector Switch 51CP — Condensing Water Pump Overload 51CT — Cooling Tower Fan Overload 51EP — Chilled Water Pump Overload 51RP — Refrigerant Pump Overload Relay 51SP-1 — Solution Pump No. 1 Overload Relay 51SP-2 — Solution Pump No. 2 Overload Relay (Larger Sizes Only) 51SSP — Solution Spray Pump Overload Relay (Some Larger Chillers) 51VP — Vacuum Pump Overload Relay (Optional) 62T1 Time Delay Relay, Shutdown Dilution 62T2 Time Delay Relay, Refrigerant Pump Start-Stop 62T3 Time Delay Relay, Capacity Control Soft Start 62T6 Time Delay Relay, Solution Pump Start-Stop 63GH — Generator High-Pressure Limit 63GX — Generator Fault Relay 69CW — Low-Chilled Water Flow Switch 88EP — Chilled Water Pump Starter 88CP — Condensing Water Pump Starter 88CT — Cooling Tower Fan Starter 88RP — Refrigerant Pump Starter 88SP-1 — Solution Pump No. 1 Starter 88SP-2 Solution Pump No. 2 Starter (Larger Chillers Only) 88SSP Solution Spray Pump Starter (Some Larger Chillers)
88VP — Vacuum Pump Starter (Optional) ABS — Absorber Pressure Switch ABSX — Absorber Pressure Switch Relay BZ Alarm Buzzer BZX — Alarm Buzzer Relay CWX — Low Water Flow or Temperature Fault Relay HM Hour Meter LIX Load Limiter Relay MCB — Main Circuit Breaker RTD — Temperature Sensor RY1 Auxiliary System Run Relay T1,T2 — Water Pump Time Delay Relay TIC Temperature Indicating Capacity Controller TR Transformer Z—Surge Suppressor
Terminals on Control Panel Terminal Strip Component Connection (Unmarked) Component Connection (Marked) External Terminal
GL — Run Light
OL1 — Low Water Flow or Temperature Alarm Light
OL2 — Hermetic Pump Fault Alarm Light
OL3 — Generator Fault Alarm Light
OL4 — Vacuum Pump Fault Alarm Light
RL — Stop Light
WL1 — Shutdown Dilution On Light
WL2 — High-Refrigerant Level Light
NOTES FOR FIG. 10
1. The following items are not by Carrier:
• Chilled water pump, condensing water pump starters and discon­nects
• Rigid or flexible conduit and junction boxes for wire and piping;
coded, except as noted
2. Solution and refrigerant pump starters are across-the-line definite purpose type.
3. Solution and refrigerant pump motors arehermetic, 3-phase and op­erate ±10% of rated voltage.
Rated Voltage Hz (Cycle)
200/220 60 400/440 60
575 60
4. Controls are for 1-phase, 60 Hz, 110 v. The maximum permissible current rating which all holding relays have is 12 amps inrush, 3 amps continuous, and 0.8 amps interruption. Make sure that the wiring does not exceed above values.
10
Fig. 10 — Typical Wiring Diagram
11
Fig. 10 — Typical Wiring Diagram (cont)
12
Fig. 11 — Typical Control Wiring
13
Typical Control Sequence, Normal Start (Fig. 10 and 14)
1. When power is supplied to the chiller control panel and the chiller is not in operation, the Stop light (RL) is on.
2. To start up machine, the Cycle-Guard™ switch (43-RV) should be placed in the AUTO. position.
When the Start button is depressed, start relay (3X) latches the ready state. If the Local/Remote switch is in the local position, the Run light (GL) also goes on and the run re­lay (2X) energizes to start the chiller. If the switch is in the remote position, the Run light will go on and 2X will start the chiller only when the remote control start con­tacts close.
The run relay (2X) also starts the chilled water pump if it is tied into the chiller control circuit for auto. start/stop and its water pump safety contacts are closed.
3. If the low load contacts (23C) in the temperature con­troller are closed with a demand for cooling, the start re­lays (1X1 and 1X2) are energized to turn off the Stop light (RL) and lock out the shutdown dilution function (62T1). Relay 1X2 also starts the cooling water pump and cooling tower fan if they are tied into the chiller control circuit for auto. start/stop and their interlocks and safeties are closed.
4. When the chilled water flow switch (69CW) closes, the pump interlock timer (2T1) energizes and closes its con­tacts in about 2 seconds. If, at that time, the chilled water and cooling water pump contacts (88EP and 88CP), and the low-chilled water temperature safety (26CW) are all closed, the systemwater pump safety interlock relay (CWX) is energized.
When the absorber pressure switch relay (ABSX), ma­chine pump safeties (26MX), and 1X1 contacts are also closed, interlock relays (1Y1 and 1Y2) are energized for self-latching and for normal operation of the refrigerant and solution pumps, generator level control, and Cycle­Guard operation.
5. Ifthe safeties for the generator conditions (63GX) are also closed, the safety device relay (4X) energizes to latch in the safety interlock relay (4Y), and to lock out the safety stop relays (30X1 and 30X2), and the alarm buzzer (BZ). The 4X relay also switches the Cycle-Guard valve (20RV) to automatic level switch control, and releases the capac­ity control valve from the closed position. However, the load limiter relay (LIX) is initially deenergized, keeping the valve at a mid-open position for a soft start.After about 15 minutes, time delay relay 62T3 contacts close to en­ergize LIX, releasing the capacity control valve to nor­mal full range control, unless LIX remains deenergized by the open contacts of the high refrigerant level relay (33RHX).
If the solution level in the high-stage generator is not too high for normal operation, as determined by the level con­trol electrode and relay (33W), thegenerator pump(s) (88SP) starts when 1Y2 closes. If it is too high, the pump(s) will start after the generator solution has fallen to a normal level.
If the evaporator refrigerant level is above the low-level safety switch (33RL) when start relay 1X1 is energized, the refrigerant pump start delay timer (62T2) energizes. After approximately 5minutes, the refrigerant pump (88RP) starts if 1Y2 is also closed. If the evaporator level is too low,the timer is not energized until the generator can con­centrate the solution enough to raise the refrigerant level above the low-level switch.
3-1 (ON) Start Chiller 3-1 (OFF) Stop Chiller 3-BZ Buzzer Silencer BZ Alarm Buzzer 3-VP (ON) Optional Start Vacuum Pump 3-VP (OFF) — Optional Stop Vacuum Pump 43-R Remote Local Switch GL Chiller Running Lamp HM Running Hour Meter OL1 Low Flow, Low Chilled Water Temperature Lamp OL2 Hermetic Pump Fault Lamp OL3 Generator Fault Lamp OL4 Optional Vacuum Pump Fault Lamp RL Chiller Stopped Lamp TIC Temperature Indicating Controller WL1 Refrigerant High Level Lamp WL2 Dilution Operation Lamp
Fig. 12 — Typical Control Panel Door
LEGEND
1-23 Auxiliary Relays 2T1 Time Delay Relay 33W Generator Level Control Relay 43-RV — Cycle-Guard Auto. Man. 88RP Refrigerant Pump Starter 88SP1 — Solution Pump Starter, No. 1 88SP2 — Solution Pump Starter, No. 2 (Large Sizes Only) 88SSP — Solution Spray Pump Starter (Some Larger Sizes Only) 88VP Optional Vacuum Pump Starter EF1,2 — Fuses MCB Main Circuit Breaker TB Field Wiring Terminals TR Transformer
Fig. 13 — Typical Control Panel Components
Arrangement
14
LEGEND
BZ — Alarm Buzzer GL — Run Light OL1 — Chilled and Cooling Water Fault Indicator Light OL2 — Refrigerant and Solution Pump Fault Indicator Light OL3 — High-Stage Generator Fault Indicator Light RL — Stop Light
Fig. 14 — Typical Control Sequence, Normal Start
15
Typical Control Sequence, Normal Stop (Fig. 10 and 15)
1. If the Local Remote switch is in the remote position, the shutdown sequence begins when the remote control con­tacts open. The run relay (2X) deenergizes, and the Run light (GL) is turned off, ready for auto restart. When the machine Stop button is depressed, with the Local/Remote switch in either position, the start relay (3X) and run re­lay (2X) are deenergized, and the Run light (GL) is turned off.
2. Start relays (1X1 and 1X2) deenergize to begin the shut­down sequence, and alarm latching relay (4Y) de-energizes to lock out the alarm shutdown relays (30X1 and 30X2). Normally closed 1X1 contacts turn the Stop light (RL) on.
3. Normally open 1X2 contacts deenergize the safety de­vice relay (4X) and timer 62T3. This deenergizes LIX and normally open 4X contacts drive the capacity control valve to the closed position.
4. Other normally closed 1X1 contacts start the shutdown dilution timer (62T1) and illuminate the Dilution light
(WL1). When 4X relay deenergizes, its normally closed contacts energize the Cycle-Guard™ valve to transfer re­frigerant into the solution for dilution. The refrigerant pump and Cycle-Guard valve continue to be energized until the evaporator refrigerant drops to the dilution level switch, which opens to deenergize the refrigerant pump delay-start timer (62T2). The normally open timer con­tacts then stop the Cycle-Guard valve and refrigerant pump. (Normally open 1X1 contacts transferred control of the 62T2 timer from the evaporator low-level switch to the dilution level switch when 1X1 was deenergized.)
5. When shutdown timer (62T1) times out after about 15 minutes, its contacts open to deenergize interlock relays (1Y1 and 1Y2). Normally open 1Y1 and 1Y2 contacts unlatch the relays to keep them open, and others open to stop the solution pump(s), as well as the refrigerant pump and Cycle-Guard if they have not already stopped. The chilled water pump, cooling water pump, and cooling tower fan stop if they are tied into the chiller control circuit for auto. start/stop. When 62T1 times out, it also shuts off the Dilution light.
GL — Run Light WL1 — Dilution Light RL — Stop Light
*When chilled water, cooling water and/or cooling tower fan are not interlocked during auto. start-stop cycle, they must be manually stopped after
completion of the dilution cycle.
NOTE: Leave steam supply valve open during auto.-stop.
Fig. 15 — Typical Control Sequence, Normal Stop
16
Typical Control Sequence, Abnormal Stop (Fig. 10 and 16)
1. Abnormal shutdown occurs automatically when any of the chiller safety devices sense a condition which might be potentially damaging to the chiller. The safeties are grouped in 4 categories, each with its own fault relay:
a. High-temperature generator problems (faultrelay 63GX),
with shutdown dilution
b. Hermetic pump motor high-temperature or overloads
(fault relay 26MX), without shutdown dilution
c. Water system flow interlocks or low-chilled water
temperature (fault relay CWX), without shutdown dilution
d. Highabsorber pressure (ABSX), without shutdown di-
lution
2. When a safety is activated, its contacts open to de­energize the fault relay for its group. The fault relay’snor­mally closed contacts illuminate the indicator light for groups a, b, or c and normally open contacts deenergizethe safety device relay (4X) and timer 62T3. This deenergizes load limiter relay LIX.
3. Normally open 4X contacts drive the capacity control valve to the closed position.
4. Normally closed 4X contacts energize shutdown alarm relays (30X1 and 30X2), and energize the alarm buzzer. These relays remain energized through 4Y self-latching contacts.
5. The 30X1 contacts open to deenergize start relays (1X1 and 1X2). Tobegin the shutdown sequence, normally closed 1X1 contacts turn the Stop light (RL) on.
6. The2X run relay remains energized, as does the Run light (GL). If the chilled water pump is tied into the chiller control circuit for auto. start/stop, the 2X relay will keep it running unless it has stopped on its own safety.
7a. If there are problems with high absorber pressure (relay
ABSX) or with the hermetic pumps (relay 26MX) or with the cooling or chilled water (relay CWX), interlock re-
lays 1Y1 and 1Y2 immediately deenergize. Normally open 1Y2 contacts immediately stop the solution and refrig­erant pumps without shutdown dilution. If the cooling water pump and cooling tower fan are tied into the chiller control circuit for auto. start/stop, then other normally open 1Y2 contacts also stop them.
b. For problems with the high-temperature generator (re-
lay 63GX), interlock relays (1Y1 and 1Y2) remain en­ergized to keep all pumps operating. Normally closed 1X1 contacts start the shutdown dilution timer (62T1).
GL — Run Light OL1 — Chilled and Cooling Water Fault Indicator Light OL2 — Refrigerant and Solution Pumps Fault Indicator Light OL3 — High-Stage Generator Fault Indicator Light RL — Stop Light WL1 — Dilution Light
Fig. 16 — Typical Control Sequence, Abnormal Stop
17
Normally closed 4X contacts energizethe Cycle- Guard™ valve to transfer refrigerant into the solution for dilu­tion. The refrigerant pump and Cycle-Guard valve will continue to be energized until the evaporator refrigerant drops to the dilution level switch, which opens to de­energizethe refrigerant pump delay start timer (62T2).The normally open timer contacts then stop the Cycle-Guard valve and refrigerant pump. (Normally open 1X1 con­tacts transferred control of the 62T2 timer from the evapo­rator low-level switch to the dilution level switch when 1X1 was deenergized.)
When shutdown timer (62T1) times out after about 15 minutes, its contact opens to deenergize interlock re­lays (1Y1 and 1Y2). Normally open 1Y2 contacts stop the solution pump(s), as well as refrigerant pump and Cycle-Guard valve if they have not already stopped. The chilled water pump, cooling water pump, and cooling tower fan also stop if they are tied into the chiller con­trol circuit for auto. start/stop. When 62T1 times out, it also shuts off the Dilution light.
8. The Stop button may be depressed to silence the buzzer, turn off the fault indicator light, and reset the control cir­cuit for restart; or, the Alarm Buzzer stop button (3-BZ) may be depressed to silence the buzzer while the control circuit remains in the shutdown alarm mode for troubleshooting.
Capacity Control — This is the controller that governs
the positioning of a capacity control valve and senses the leaving chilled water temperature to determine the required valve positioning. This valve regulates the flow of steam or hot water to the generator, matching machine capacity to the load, and maintains the selected chilled water temperature.
At full-load conditions, the capacity control valve is wide open. As the load is reduced and the chilled water tempera­ture starts to fall below design temperature, the valve throttles the steam or hot water flow until, at no-load condition, the valve is fully closed.
During start-up and shutdown periods, and with pro­longed Cycle-Guard operation, the chiller control circuit over­rides the signal to the steam valve to limit the valve opening.
The 16JT is available with either electronic or pneumatic capacity control valve actuators, but both are positioned by a microprocessor-based controller.
A temperature sensor inserted in the chilled water outlet pipe continuously measures chilled water temperature and provides a proportional signal to the controller in the ma­chine control panel. The signal is electronically converted by the controller which provides a variable signal for the valve actuator.
CONTROLLER — The microprocessor-based controller can be field programmed by using its own interface keys, dis­play,and alternate inputs and outputs for many control varia­tions, but is normally set up for proportional valve position­ing in direct relationship to changes in the leaving chilled water temperature.
When the AUTO. mode has been selected on the control­lerAUTO.-MAN.button for normal automatic operation, both the temperature control set point and the actual chilled water temperature are shown on the controller display.The control temperature set point can be raised or lowered in that mode by pressing the up or down arrows on the controller.
When the MAN. mode has been selected on the controller AUTO.-MAN. button, the control signal to the capacity con­trol valve is displayed as 0 to 100% open, and the valve can be manually opened or closed in that mode by pressing the up () or down (Ä) arrows on the controller.
Electronic ValveActuator (Fig. 17) — The proportional mil­liamp output signal from the controller is supplied directly to the electronic valve actuator for positioning control. When safety device relay (4X) is deenergized in a chiller shutdown condition, its contacts remain open so that the actuator sees a ‘‘0’’ amp signal and remains closed. When the load limiter relay (LIX) is deenergized during chiller start-up or Cycle­Guard operation, the current limiter is in control and pro­vides a preset control signal to hold the actuator at a mid­open position for a preset time delay period.
LEGEND
Wiring Terminals
NOTE: See Fig. 10 for Control Circuit Connections.
Fig. 17 — Electronic Valve Actuator
18
Pneumatic ValveActuator (Fig. 18) — The proportional mil­liamp output signal from the controller is converted to a pro­portional pneumatic signal in the current/pneumatic (I/P) transducer mounted on the valve operator. When safety de­vice relay (4X) is deenergized in a chiller shutdown condi­tion, its contacts remain open so that the transducer sees a ‘‘0’’ amp signal. The pneumatic control signal is therefore bled off, so the actuator sees a ‘‘0’’ psig signal and remains closed.
When the load limiter relay (LIX) is deenergized during chiller startup or Cycle-Guard™ operation, the current lim­iter is in control and provides a preset control signal to hold the actuator at a mid-open position for a preset time delay period.
High Concentration Limit — During high load op-
eration, some abnormal conditions can cause the concentra­tion of the lithium bromide solution to increase above nor­mal.When this happens, the Cycle-Guard valve opens to transfer a small amount of refrigerant into the solution circuit to limit the concentration. This is necessary to keep the strong so­lution concentration from crystallizing.
The Cycle-Guard valve is controlled by the evaporator re­frigerant level, which has a direct relationship to solution concentration. As the concentration increases (the solution has less water), so does the refrigerant level. And, because solution crystallization is also related to temperature, a so­lution thermostat is used with two evaporator refrigerant level switches to provide stepped control of the Cycle-Guard valve with varying condensing water temperatures.
With normal condensing water temperatures, the Cycle­Guard valve is controlled by the higher level switch (33RH) through the refrigerant level relay (33RHX). But with lower condensing water temperatures, and with corresponding lower solution temperatures, thermoswitch (26SH) contacts close to control the Cycle-Guard valve at the lower level switch (33RM) and, therefore, at a slightly lower solution concen­tration. A High Refrigerant Level light (WL2) goes on when the 33RHX level relay energizes for Cycle-Guard operation. Also, 33RHX relay contacts open to drive the capacity con­trol valve to a mid-open position (LIX), to reduce heat sup­ply to the generator until the high level has been corrected.
The concentrations at which the Cycle-Guard valve is ac­tivated are determined by the amount of refrigerant that is charged into the machine. This charge should be trimmed at start-up, and should be checked periodically during opera­tion for correct Cycle-Guard operation.
Low Concentration Limit— During low-load opera-
tion with low condensing water temperatures, the normal di­lution of the solution lowers the refrigerant level in the evaporator. Before the level becomes low enough to cause pump cavitation and damage to the hermetic pump motor, the evaporator low-level switch (33RL) opens to deenergize 62T2, which, temporarily stops the refrigerant pump. This will happen only when the condensing water temperature falls below the design limit. When the refrigerant level subse­quently rises enough to close the low-level switch, the re­frigerant pump start-delay timer (62T2) is energized. After about 5 minutes, the timer contacts close to start the refrig­erant pump and resume normal operation.
High-StageGenerator Level Limit — Asensing elec-
trode with a level relay (33W) monitors the solution level in the high-stage generator. If the level is too high, 33W relay contacts stop the solution pump(s), which allow solution to drain normally from the generator. When the solution level drops below the electrode level, the relay restarts the solu­tion pump(s).
BEFORE INITIAL START-UP
Job Data and Tools Required
1. Job specifications and job sheets, including list of ap­plicable design temperatures and pressures
2. Machine assembly and field layout drawings
3. Controls and wiring drawings
4. 16JT Installation Instructions
5. Mechanic’s hand tools
6. Absolute pressure gage or water-filled wet-bulb vacuum indicator graduated with 0.1-in. (2 mm) of mercury in­crements. Do not use manometer or gage containing
mercury.
LEGEND
Wiring Terminals Air Tubing Provided
Air Tubing to be Done at Site by Contractor
NOTE: See Fig. 10 for Control Circuit Connections.
Fig. 18 — Pneumatic Valve Actuator
19
7. Auxiliary evacuation pump, 5 cfm (2.5 l/s) or greater, with oil trap, flexible connecting hose and connection fittings
8. Compound pressure gage, 30-in. vacuum to 30 psig (75 cm vacuum to 200 kPa)
9. Digital volt-ohmmeter and clamp-on ammeter
10. Liquid charging hose consisting of flexible
3
⁄4-in. (20- mm) hose connected to a 3-ft (1-m) long x1⁄2-in. (15-mm) pipe trimmed at a 45-degree angle at one end, with a1⁄2-in. MPT connector
11. Leak detector
12. Hydrometer and insertion thermometer
Inspect Field Piping — Refer to the field piping dia-
grams (Fig. 19) and inspect the chilled water and cooling water piping.
1. Verify that location and flow direction of the water lines are as specified on the drawings and as marked on the machine.
2. Check that all water lines are vented and properly sup­ported to prevent stress on waterbox covers or nozzles.
3. Make sure all waterbox drains are installed.
4. Ensure that water flow through the evaporator and con­denser meet job requirements. Measure the pressure drops across both cooler and condenser.
5. Make sure chilled water temperature sensors are installed in the leaving chilled water piping. Also check that ap­propriate thermometers or temperature wells and pres­sure gage taps have been installed in both entering and leaving sides of the evaporator, absorber, and condenser water piping.
Inspect Field Wiring — Refer to the field and ma-
chine wiring diagrams and inspect the wiring for both power supply and connections to other system equipment (cooling tower, water supply pumps, auto. start if used, etc.)
Do not apply power to hermetic pumps or attempt to start the machine until it has been charged with lithium bromide solution and refrigerant. The pumps will be se­verely damaged if rotated without the full liquid charge.
1. Examine wiring for conformance to job wiring diagrams and applicable electrical codes.
2. Check pump and motor nameplates and control panel for agreement with supply voltage and frequency (Hz).
3. Verify correct overload and fuse sizes for all motors.
4. Check that electrical equipment and controls are properly grounded in accordance with applicable electrical codes.
5. Make sure customer/contractor has verified proper op­eration of water pumps, cooling tower fan, and associ­ated auxiliary equipment.This includes ensuring that motors are properly lubricated and have proper electrical supply and proper rotation.
Standing Vacuum Test — Before machine is ener-
gized or placed in operation, check for air leaks with a stand­ing vacuum test. Examine the 2 test procedures described below and select the one that applies to your job application.
LONG INTERVAL TEST — Use this test procedure if an absolute pressure reading has been recorded at least 4 weeks previously and the reading was not more than 1 in. (25 mm) of mercury.
1. Connect an absolute pressure gage to the auxiliary evacu­ation valve and record the pressure reading. (Do not use mercury gage.)
2. If the pressure has increased by more than 0.1 in. (2.5 mm) of mercury since the initial reading, an air leak is indicated. Leak test the machine as described in the Maintenance Procedures section, page 33, then perform the short interval test which follows.
Pressure Gage Thermometer
Manual Valve
Fig. 19 — Typical Piping
20
SHORT INTERVAL TEST — Use this test procedure if:
1. No previous absolute pressure readings have been re­corded, OR
2. Previous absolute pressure reading was made less than 4 weeks ago, or reading indicated a machine pressure of more than 1 in. (25 mm) of mercury, OR
3. Machine had to be leak tested after long interval test.
Procedure
1. Connect absolute pressure gage to auxiliary evacuation valve and record pressure reading.
2. If the reading is more than 1 in. (25 mm) of mercury ab­solute, evacuate the machine as described in the Main­tenance Procedures section, page 33.
3. Record the absolute pressure reading and the ambient temperature.
4. Let machine stand for at least 24 hours.
5. Note the absolute pressure reading when ambient tem­perature is within 15° F (8° C) of the ambient tempera­ture recorded in Step 3.
6. If there is any noticeable increase in pressure, an air leak is indicated. Leak test the machine as described in Main­tenance Procedures section, then repeat short interval vacuum test to ensure results.
Machine Evacuation — When machine absolute pres-
sure is greater than 1 in. (25 mm) of mercury absolute, ma­chine must be evacuated as described in Maintenance Pro­cedures section, page 33.
Solution and Refrigerant Charging
HANDLING LITHIUM BROMIDE SOLUTION
Lithium bromide and its lithium chromate inhibitor can irritate the skin and eyes. Wash off any solution with soap and water. If solution enters the eye, wash the eye with fresh water and consult a physician immediately. Lithium bromide is a strong salt solution; do not syphon by mouth.
Liquid materials that are added to lithium bromide solution such as lithium hydroxide, hydrobromic acid, octyl alcohol, and lithium chromate inhibitor, are clas­sified as hazardous materials. These materials, and any lithium bromide solution they are in, must be handled in accordance with current Occupational Safety and Health Administration (OSHA) and Environmental Protection Agency (EPA) regulations.
Solutions of lithium bromide and water are nontoxic, non­flammable, nonexplosive, and can easily be handled in open containers. The solution is chemically stable and does not undergo any appreciable change in properties even after years of use in the absorption machine. Its general chemical prop­erties are similar to those of table salt.
Because lithium bromide salt can corrode metal in the pres­ence of air, wipe off any solution spilled on metal parts or tools and rinse the part with fresh water as soon as possible. After rinsing, coat the tools wih a light film of oil to prevent rust. After emptying metal containers of solution, rinse the container with fresh water to prevent corrosion. Immedi­ately wipe or flush the floor if lithium bromide or octyl al­cohol is spilled on it.
Lithium bromide should be stored only in the original con­tainer or in a completely clean container. Used lithium bro­mide solution should be disposed of by a reputable chemical disposal company.
CHARGING SOLUTION — Solution is drawn into the ab­sorber through the solution pump service valve while the
pump is off. To minimize the chance of air entering the ma­chine, the solution should not be drawn in directly from a small container.Avacuum pump should be in operation while the solution is being charged into the chiller to remove en­trained noncondensables.
1. Connect a flexible hose to a
1
⁄2-in. MPT adapter and a
1
⁄2-in. (15-mm) pipe. Fill both pipe and hose with water
to minimize any air entry into the machine.
2. Insert the
1
⁄2-in. (15-mm) pipe into the container (be sure it goes to the bottom), and connect the flexible hose to the solution pump service valve (Fig. 20). The lithium bromide container must have yellow, ‘‘Lithium Chro­mate Inhibitor’’ markings, and a 55% concentration so­lution must be used.
3. Open the service valve. Continue charging until solution level is near the bottom of the container. Do not allow air
to be drawn into machine.
4. Repeat with other containers as required until the amount specified in Table 3 has been charged into the chiller.
CHARGING FOR CONDITIONS OTHER THAN NOMI­NAL — The solution quantity can be adjusted to compen­sate for other than nominal values for design chilled water temperature, condensing water temperature or flow. The so-
lution quantity can be increased or decreased by up to 10% of the nominal charge listed in Table 3. Adjust quantity as follows:
1. Increase (decrease) the nominal solution charge by 1% for each degree F (.56° C) that the design chilled water temperature is below (above) 44 F (7 C).
2. Increase (decrease) the nominal solution charge by 1% for each 2° F (1.1° C) that the design condensing water temperature is above (below) 85 F (29 C).
3. Increasethe nominal solution charge by 1% for each 10% reduction in design condensing water flow below nomi­nal 100%.
4. Do not adjust nominal charge for changes in steam pressure.
INITIAL REFRIGERANT CHARGING — The refrigerant charge must be either distilled or deionized water. Do not use tap water without first having it tested for the following requirements:
pH 7.0 ± 0.2 at 77 F (25 C) Hardness CaCO
3
2.0 ppm or less Silica 0.2 ppm or less Ammonia NH4+ None Specific Resistance 5 x 105ohms/cm
at 77 F (25 C)
Fig. 20 — Charging Solution and Refrigerant
21
To charge refrigerant into the evaporator, fill clean solu­tion containers with the distilled or deionized water. Charge the water through the refrigerant pump service valve, fol­lowing the appropriate steps in Charging Solution section.
Charge in at least the amount listed in Table 3 under Ini­tial Refrigerant amount. This charge must be adjusted after start-up to achieve optimal Cycle-Guard™ control condi­tions to limit the maximum solution concentration (which prevents solution crystallization). However, any extra re­frigerant should be limited because the normal refrigerant pump discharge pressure is below atmospheric pressure and a vacuum bottle is required to remove refrigerant (see Final Refrigerant Charge Adjustment section, page 25).
Table 3 — Nominal Machine Charges*
UNIT 16JT
LiBr SOLUTION INITIAL REFRIGERANT
Gal Kg Gal Kg
810,812,814 137 840 87 330 816,818,821 200 1225 106 400
824 246 1505 92 350 828 257 1575 92 350 832 309 1890 114 430 836 314 1925 114 430 841 366 2240 137 520 847 400 2450 137 520 854 440 2695 165 625 857 463 2835 165 625 865 514 3150 203 770 873 560 3430 232 880 880 623 3815 285 1080
080 754 4620 177 670 090 846 5180 201 760 100 903 5530 215 815 110 1017 6230 202 765 120 1097 6720 206 780 135 1263 7740 238 900
150 1377 8435 271 1025 080L 823 5040 197 745 090L 922 5650 211 800 100L 1006 6160 225 850 110L 1114 6825 219 830 120L 1200 7350 238 900 135L 1380 8450 277 1050 150L 1504 9210 304 1150
*Based on 55% concentration of solution, 44 F (7 C) leaving chilled water,
85 F (29 C) entering condensing water.
INITIAL CONTROL CHECKOUT
AND ADJUSTMENT
The checkout procedures in this section are for semi­automatic control systems. The purpose of the checkout is to ensure that control circuits have not been affected by ship­ping or installation damage or altered in the process of mak­ing field wiring connections.
NOTE: Some thermoswitch adjustments are scaled in Cel­sius, hence that is the temperature stated first in some of the instructions in this manual.
Follow the checkout sequence in detail. Machine must be charged with solution and refrigerant before starting checkout. Chilled water and condensing water circuits must be filled and operative, but the manual steam or hot water valve must remain closed.
Do not rotate hermetic pumps until machine is charged
with lithium bromide-water solution and refrigerant.
Preparation
1. Open the control panel and place the main circuit breaker
in OFF position (Fig. 13) to deenergize the control circuit and pump motor.
2. Disconnect leads for solution pump motor and refriger-
ant pump motor at secondary starter terminals. Wrap the ends of the disconnected wires with electrical tape and
mark for proper identification at reinstallation.
3. If starters for condensing water pump and chilled water pump are operated by manual start-stop, temporarily place an insulated jumper between terminals P1 and P2 to over­ride the external interlock. Remove fuses from starters for the condensing water pump motor and chilled water pump motor. (Starters for these motors are field supplied on external voltage lines and are not located in control panel.)
If condensing and chilled water flow switches are used, manually block the switches closed.
IMPORTANT: Do not open manual steam or hot water valves.
Energize Control Circuit
1. Place the main circuit breaker in the ON position to en-
ergize control circuit. (Stop light turns red.)
2. Depress the Stop button to clear any safety fault condi-
tions and to prepare the control circuit for starting.
3. Place the control panel settings in the following
positions:
SETTINGS POSITION
Capacity Control AUTO. Cycle Guard Switch AUTO. Local/Remote Switch LOCAL
4. Depress the Start button momentarily to start the ma-
chine. The Run light turns green and the start cycle be­gins.With normal operation, the solution pump starts im­mediately and the refrigerant pump starts after about 5 minutes.
Check Solution and Refrigerant Pump Starters
1. Make sure the solution and refrigerant pump starters are
energized.
2. Depress the Stop button momentarily (Run light de-
energizes). Both starters remain energized for approxi­mately 15 minutes during dilution cycle (Dilution light energizes).
Check Pump Starter Overloads
1. Depress the Start button, and wait for the pumps to start.
2. Pushthe trip bar on the side of the refrigerant pump starter
overload. All pump starters deenergize, the alarm buzzer sounds, and the fault light identifies the fault category.
3. Depress the Stop button (to silence the alarm) and the
starter reset bar.
4. Repeat Steps1-3with other control panel starters. Refer
to the wiring diagrams for the set point of each starter.
5. Starters for auxiliary equipment must be similarily checked,
according to the manufacturers’ instructions.
Check Low-Temperature Cutout
1. Turn the differential adjustment screw until differential
set point is at 4 C (7.2 F).
2. Place control sensing bulb in a water bath maintained at
9° F (5° C) below design leaving chilled water tempera­ture (but not below 36 F [2 C]). This is the correct low­temperature cutout setting.
3. Depress the Start button.
Slowly turn cutout adjustment knob clockwise until con­tacts open. Chilled water, condensing water, solution and refrigerant pump starters, and Run light should de­energize, the alarm buzzer should sound, and the fault light should identify the fault category.
22
Depress the Stop button to silence the alarm. Marks on the indicator plate are for reference only and
are not calibrated in degrees.
4. Allow water bath to warm until contacts close. Depress the Start button. Starters and Run light should energize. Contacts should have a 7.2° F (4° C) differentialbetween opened and closed positions.
Cutout Temperature = Cut-in Temperature − Differential
5. Fill low-temperature cutout well (located on chilled wa­ter nozzle) with heat conductive compound. Insert sens­ing element into well.
NOTE: Usually low-temperature cutouts are preset at the factory, with contacts set to open at 36 F (2 C) and to close at 43 F (6 C).
Check Cycle-Guard™ Valve — (This valve is lo-
cated between refrigerant pump discharge line and solution pump inlet.)
1. Place Cycle-Guard switch in MANUAL position. Cycle­Guard valve should energize (denoted by an audible click).
2. Use clamp-on ammeter to check current in wire to Cycle­Guard valve. Current reading should be 0.2 amps or less.
3. Place Cycle-Guard switch in AUTO. position. Cycle­Guard valve should deenergize.
4. Place jumper wire between panel terminal RC
and
41 in the panel to simulate high evaporator level. Ter-
minal RO
is hot. Cycle-Guard light and valve should
energize.
5. Remove jumper wire between panel terminal RO
and
41 . Cycle-Guard light and valve should deenergize.
Check Solution Thermoswitch
1. Place jumper wire between panel terminal RO and ter­minal 15 to simulate mid-level switch operation. Ter-
minal RO
is hot.
2. Place control sensing bulb on temperature cutout in wa­ter bath maintained at ambient temperature. Slowly turn switch adjustment screw clockwise until contacts close. Cycle-Guard valve should energize. Note the difference (if any) between actual thermometer reading and the read­ing on the thermoswitch adjustment scale.
Using any temperature differential described above as a correction factor, set adjustment screw to close at 47 C (117 F). The switch has a fixed differential of 3° C (5.4° F).
3. Remove jumper wire between panel terminal RO
and
terminal 15 . Cycle-Guard valve should deenergize.
4. Fill thermowell (located on the absorber strong solution line between heat exchanger and spray header) with heat conductive compound and insert sensing element into it.
Check High-Stage Generator Temperature Thermoswitch —
The switch is factory set to open on a rise in temperature above 170 C (338 F) and close on a cooling below 163 C (325 F). Verify the approximate scale position setting (170 C [338 F]) and closed switch contacts. The switch range is 50 to 320 C (122 to 608 F).
NOTE: The switch operation setting cannot be easily checked in the field. It requires a precise scale adjustment so do not reposition if not necessary.
Check High-Stage Generator Pressure Switch — The switch is factory set to open on a rise in pressure
above −20 mm Hg G (−0.8 in. Hg) and close with a
reduction in pressure below −205 mm Hg G (−8 in. Hg). Verify the approximate scale position setting (−20 mm Hg G [−0.8 in. Hg]) and closed switch contacts. The switch range is −500 mm Hg G (−20 in. Hg) to 580 kPa (85 psig).
NOTE: The switch operation setting cannot be easily checked in the field without breaking machine vacuum. It re­quires a precise scale adjustment, so do not reposition if not necessary.
Check Rotation of Solution and Refrigerant Pumps
1. Place main circuit breaker in OFF position and reconnect pump motor wires previously disconnected.
2. Place main circuit breaker in ON position.
3. Installcompound pressure gage on refrigerant pump serv­ice valve, depress Start button, and check pump dis­charge pressure.
4. Place the main circuit breaker in OFF position and re­verse any two motor power leads at starter to reverse pump rotation.
5. Place the main circuit breaker in ON position and de­press Start button. Compare the noise of both rotation di­rections and check discharge pressure. Correct rotation is the direction that produces the highest discharge pressure reading and the least noise.
6. Repeat Steps3-5forrotation of solution pump(s).
7. To check chilled water pump and condensing water pump rotation, refer to pump manufacturers’ instructions.
Check Capacity Control Operation (Fig. 21) —
The microprocessor-based controller is programmable for a particular application by using its interface keys, display, and selectable inputs and outputs. It can be set up for many dif­ferent control variations. It is supplied originally configured with default values for typical use, and is custom configured in the factory when it is mounted in the chiller control panel.
Proportional capacity control valve positioning is usually in direct relationship to changes in the leaving chilled water temperature at a selected control temperature. Variations can include such things as remote set point, dual set points, auto. chiller start at a selected chilled water temperature, dual in­puts, and computer control input and output interfaces.
The following checkout and adjustment procedure is for standard use. The standard 16JT configuration set-up list, with temperature measurement in degrees F, and 110 V, 60 Hz control power, is shown in Table 4. See the UDC 3000 Uni­versal Digital Controller product manual for specific de­scription, configuration, operation, and troubleshooting in­formation.
Do not depress the AUTO. TUNE and RUN/HOLD keys
or use the SET UP and FUNCTION keys for reviewing
the configuration without a thorough understanding of
their use because the configuration could be inadvert-
ently altered. Also, do not intentionally change any con-
figuration without a thorough understanding of both the
method and the resulting effects.
1. Verify factory customized configuration by checking the
controller displays: The letter F (Fahrenheit) in the up­per left area; either an A (automatic control) or MAN. (manual control) in the upper right area; and the actual temperature at the sensor in the middle right area of the display.
The lower display will show the letters SP (set point) and the set point temperature when in the A (AUTO.) mode, and the letters OUT (for output) and a value in the range of 0.0 to 100.0 (percent output signal to the
23
valve actuator) in the MAN. (MANUAL) mode. Press the MAN./AUTO. button to switch between the two modes. The actual output value is not important at this time. (Pref­erably, the temperatures have been configured for dis­play [and processing] with the decimal located for tenths of a degree, but that is not critical.)
The red bars on the right of the temperature display in­dicate deviation between actual and set point tempera­tures in ±10% increments of the sensor span. The LOWR DISPbutton will allow the following values to be shown in either MAN. or AUTO. in the lower display: the set point (SP); the deviation between the actual and set point temperatures; and the OUT control signal in percent of range. A flashing code indicates a wiring fault or miss­ing configuration.
NOTE: For the following procedure, the up arrow () and the down arrow (Ä) are used to increase or de­crease the set point, output, and set-up configuration val­ues, respectively. To quickly make large changes to set point or manual control output values, press the arrow indicative of the direction of change, then press the op­posite arrow to move the adjustment one digit to the left. To move the adjustment an additional digit to the left, continue pressing the arrow indicative of the direction of change, and then press the opposite arrow again.
2a. Place the controller in theAUTOMATIC mode by press-
ing the AUTO./MAN. button until A is displayed.
b. Use the arrows to change the temperature set point (SP)
on the lower display to a few degrees below the actual temperature on the middle display in order to open the capacity control valve signal.
c. Press the chiller START button. The capacity control valve
should open to a mid-open position (soft start) for the time period set on adjustable time delay relay 62T3, typi­cally about 15 minutes. The valve limit position can be varied by adjusting the high limit setting knob under the cover of the current limiter (see Fig. 17 or Fig. 18).
3. After completion of the 62T3 soft-start time period, place the controller in the MANUAL mode by pressing the AUTO.-MAN. button until MAN. is displayed. Use the arrows to verify that the capacity control valve will open and close in proportion to the output signal (OUT) over its entire range. ‘‘OUT’’ is displayed as 0.0 to 100.0% of the 4 to 20 mA output control signal.
4a. Return the controller to the AUTOMATIC mode by press-
ing the AUTO.-MAN. button until A is displayed.
b. Use the arrows to change the temperature set point (SP)
close to the actual temperature on the upper display,and wait briefly to allow the OUT signal to stabilize. Then use the up arrow to change the set point several degrees above the actual temperature to verify that the control valve OUT signal will gradually change towards the closed position. Next, use the down arrow to change the set point several degrees below the actual temperature to verify that the control valve output signal will gradually change towards the open position.
5. Use the arrows to reset the set point temperature at the desired chilled water control temperature for normal op­eration. Leave the controller in the A (AUTO.) mode.
Completion — Replace fuses from starters for condens-
ing water pump motor and chilled water pump motor, then unblock water flow switches. Also, remove jumper wire from terminals P1 and P21 and any other jumpers which might have been connected for controls checkout.
Table 4 — Standard Controller Configurations
SET UP FUNCTION SELECTION TUNING PROP BD
RATE MIN RSET RPM LOCKOUT
10.0
0.00
1.00 + CONF
SET POINT RAMP SP RAMP DISABL AUTOTUNE AT ENABL
AT ERROR
DISABL NONE
ALGORITHM CONTALG
INPUT 2 OUT ALG
PID A DISABL CURRNT
INPUT 1 DECIMAL
UNITS IN 1 TYPE IN1HI IN1LO BIAS IN 1 FILTER 1 BURNOUT PWR FREQ
XXX.X DEG F 100 LO
300.0
0.0
0.0 10 NONE 60 HZ
CONTROL PID SETS
SP SOURC RATIO BIAS POWER UP SP HILIM SP LOLIM ACTION OUTHILIM OUTLOLIM DROPOFF FAILSALE PBorGAIN MINorRPM
1 ONLY 1LOCAL
1.0
0.0 A LSP
100.0
41.0 DIRECT
100.0
0.0
5.0
0.0 PB PCT RPM
OPTIONS AUX OUT
REM SW
DISABL NONE
COM ComSTATE DISABL ALARMS A1S1VAL
A1S1TYPE A1S2TYPE A2S1TYPE A2S2TYPE A1S1 H L AL HYST
40.5* PV* NONE NONE NONE LO*
2.0*
*Used for low chilled water temperature cutout. NOTE: Controller configuration selections not listed here have been
automatically deleted from the controller set-up display by the above configuration selections. Selections which have been changed from original default values are underlined.
Fig. 21 — Operator Interface
24
INITIAL START-UP
The following start-up procedures are based on a semi­automatic system in which all pumps energize when the start­stop switch is placed in the START position.
Preliminary Check — Check the operation of auxil-
iary equipment and status of system before starting the ab­sorption machine.
PREPARATION
1. Add the amount of octyl alcohol specified in Table 5 through
the solution pump service valve. (Refer to Maintenance Procedures, Adding Octyl Alcohol section, page 35.) Do not allow air to be drawn into machine.
2. Supply power to control panel, chilled water, and con-
densing water pumps. Open manual steam supply valves, chilled water valves, and cooling water valves.
3. Place the capacity control and Cycle-Guard™ settings in
AUTO. position and Local/Remote switch in the Local position. Depress the Start button.
4. When the solution is warm (strong solution below 140 F
[60 C]), place the capacity control auto.-man. button in MANUALposition and depress the down arrow until valve is fully closed.
5. Determinethe machine absorber loss as described in Main-
tenance Procedures, Absorber Loss Determination sec­tion, page 31.
If absorber loss is 5° F (2.8° C) or less, place capacity control valve on AUTO. and allow machine to operate.
If the absorber loss is greater than 5° F (2.8° C), evacuate the machine (see Maintenance Procedures, Machine Evacu­ation section, page 33) to remove any noncondensables that might prevent normal operation. As an alternate pro­cedure, limit steam pressure to keep strong solution tem­perature under 140 F (60 C) and allow the purge to re­move the noncondensables.
After the absorber loss has been reduced to below 5° F (2.8° C) by either of the above procedures, place ma­chine on automatic operation, with capacity control but­ton in AUTO. position and steam pressure normal. The purge will evacuate the machine to the normal absorber loss of 2° F (1.1° C) or less.
Table 5 — Octyl Alcohol Initial Charge
16JT
OCTYL ALCOHOL
Gal L
810,812,814 1 3.8
816,818,821,824 2 7.6
828,832,836 2 7.6 841,847,854 3 11.4 857,865,873 4 15.2
880 5 19.0
080 6 22.7 080L,090 7 26.5 090L,100 8 30.3 100L,110 10 37.9 110L,120 12 45.5 120L,135 14 53.1 135L,150 16 60.6
150L 18 68.2
Final Adjustment of Capacity Controls — Al-
low the chiller to operate long enough with a fairly stable load for the system to reach equilibrium. V erifythat the chilled water temperature is close to the set point and the system is stable (with little capacity control valve cycling or search­ing). See Initial Control Checkout and Adjustment, Check Capacity Control Operation section, page 23, for set point and control adjustment procedures.
The controller tuning parameters have been factory-
configured for control stability with typical applications.
However, if necessary, the parameters can be adjusted for improved stability with either manual or automatic recon­figuration procedures.
WITH THE MANUAL PROCEDURE, the configuration for proportional band, rate, and reset are adjusted until the sys­tem is stable.
WITH THE AUTOMATIC PROCEDURE, the controller has AUTOTUNE capability to automatically calculate and ad­just a particular cooling system’s optimal tuning parameters.
See the UDC 3000 Unviersal Digital Controller product manual for specific description, configuration, operation, and troubleshooting information.
Final Refrigerant Charge Adjustment — The ad-
justment should be made after:
1. Machine is operating with stable temperatures at 40 to
100% of full load.
2. Absorber loss is 3° F (1.7° C) or less.
3. Refrigerant specific gravity is 1.02 or less.
The refrigerant charge is adjusted so that the Cycle­Guard™ system can limit maximum solution concentration and avoid solution crystallization. Proceed as follows:
1. Place Cycle-Guard Switch (43RV) in the AUTO. posi-
tion. Then, if the Cycle-Guard valve remains off at least 10 minutes, proceed to Step 2. If not, gradually reduce
the load on the chiller (to reduce the solution concentra­tion) until the Cycle-Guard valve remains off. The valve will be energized when the refrigerant high level light is ON.
2. Remove a solution sample from the solution pump
service valve and measure the specific gravity and temperature.
3. Locate the intersection point of the specific gravity and
temperature values on equilibrium diagram (Fig. 22A or 22B). Read down from this point to the solution concen­tration scale to determine the percent lithium bromide by weight in the weak solution.
chine by comparison of chilled water temperature spread, and flow in relation to design. Enter Table 6 at this per­cent load and find the corresponding weak solution con­centrations required for refrigerant charge adjustment.
Table6—WeakSolution Concentrations for
Adjusting Refrigerant Charge
REFRIGERANT
LEVEL
PERCENT LOAD ON MACHINE
100 90 80 70 60 50 40
Weak Solution Concentration (%)
High 60 60.4 60.8 61.2 61.6 61.9 62.2
Mid 58 58.4 58.7 59.1 59.4 59.8 60.1
NOTE: Concentrations listed in Table 6 are for nominal design con­ditions. For special design conditions, obtain the special concentra­tion settings from the factory.
5. Adjust machine operating conditions until machine op-
erates with stable temperatures at either of the weak so­lution concentrations (±0.1%) listed in Table 6 under the selected percent load.
To increase the concentration: a. Increase the load. b. Lowerchilled water temperature (set point adjuster set-
ting).
c. Raise condensing water temperature (or throttle con-
densing water flow).
After adjusting conditions, repeat Steps 2 and 3 to verify solution concentration.
25
Fig. 22A — Equilibrium Diagram for Lithium Bromide in Solution (F)
Fig. 22B — Equilibrium Diagram for Lithium Bromide in Solution (C)
26
6. The refrigerant charge can be adjusted at either refriger­ant level. In Table 6, use the refrigerant level that corre­sponds to the weak solution concentration in the machine at the percent load determined in Step 4. Proceed as fol­lows, at the appropriate refrigerant level (Fig. 23):
HIGH LEVEL — Remove temperature cutout wire from
terminal 15
.
MID LEVEL — Install jumper between terminals
15
and 41 .
7. Checkstatus of Cycle-Guard™ valve. If it is open, gradu­ally remove water from refrigerant pump service valve until Cycle-Guard valve closes. (See Solution or Refrig­erant Sampling section, page 34.) If Cycle-Guard valve is closed, add small quantities of water to machine until Cycle-Guard valve opens. Water can be drawn into the machine through the refrigerant pump service valve when the refrigerant pump is off.The pump can be stopped with­out a dilution cycle by pressing the trip bar on the pump starter overload, then depressing the Stop button and the overload reset. Fill the charging hose with water before opening the pump service valve. Do not allow any air to
be drawn into the machine.
Turnthe refrigerant pump on after adding water .The Cycle­Guard valve cannot be energized while the pump is off.
Add or remove water to change the solution concentra­tion as needed. When adding or removing water, allow
approximately 10 minutes for temperatures and concen­trations to stabilize. Periodically check weak solution con­centration while adjusting refrigerant charge. Readjust machine conditions, if necessary, to maintain controlled concentration.
8. Remove jumpers from thermoswitch terminals 15
and
41
. Replace wire connections removed in Step 6.
9. If solution charge has been increased (decreased) for de­sign conditions other than nominal, decrease (increase) refrigerant charge by an equal amount. (Refer to Solution and Refrigerant Charging— Charging for Conditions Other than Nominal, page 21.)
Check Machine Shutdown — Depress the Stop but-
ton momentarily. The capacity control valve closes and the Cycle-Guard valve opens to dilute the solution. When the solution has been sufficientlydiluted, a refrigerant level switch shuts down the machine.
Depending on solution concentration before shutdown, the shutdown can take up to 20 minutes. If machine does not shut down correctly, check operation of capacity controls, refrigerant level switches, Cycle-Guard valve, and machine wiring.
Check Low-Evaporator Level Operation — Af-
ter machine has completed a normal shutdown:
1. Depress the Start button to start the machine. Place the capacity control AUTO.-MAN. button in MAN. and use
(Ä) to keep the valve closed.
2. Wait 5 minutes for the refrigerant pump to start then place the Cycle-Guard switch in MANUAL to transfer refrig­erant from the evaporator, lowering the refrigerant level until it reaches the low-level switch. The refrigerant pump should stop. If the pump becomes noisy, it might be in cavitation from a low-level switch malfunction. Do NOT allow the pump to remain in operation with this condition.
3. Return the Cycle-Guard switch and capacity control but­ton toAUTO. for normal operation. When enough refrig­erant has been recovered from the solution to raise the evaporation level above the low-level switch, the refrig­erant pump restarts.
Determine Noncondensable Accumulation Rate — After approximately 200 hours of machine operation, the
rate of noncondensable accumulation in the purge should be measured to be sure that the machine does not have an air leak. If a leak is indicated, it must be corrected as soon as possible to minimize internal corrosion damage. Refer to Main­tenance Procedures, NoncondensableAccumulation Rate sec­tion on page 31 for checking procedures.
OPERATING INSTRUCTIONS
Operator Duties
1. Become familiar with absorption machine and related equip­ment before operating. See Introduction and Machine De­scription sections, pages 3-9.
2. Start and stop machine as required.
3. Inspect equipment; make routine adjustments; maintain machine vacuum and proper refrigerant level; exhaust purge as required.
4. Keep log of operating conditions and recognize abnor­mal readings.
5. Protect system against damage during shutdown.
Before Starting Machine — Be sure that:
1. Power is on to condensing water and chilled water pump starters, cooling tower fan, and absorption machine con­trol panel (chiller Stop light is on).
2. Cooling tower has proper water level.
3. Chilled and condensing water circuits are full and valves are open.
4. Correct steam or hot water supply is available.
5. Air supply for pneumatic controls is adequate.
6. Alarm indicator lights are off.
Start Machine — If machine has manual auxiliary start,
first energize the auxiliaries.
To re-energize the control circuit after a safety shutdown,
depress the Stop button and then the Start button.
Now follow one of the 2 procedures described below as
it applies to your machine:
• Start-UpAfter Limited Shutdown — If machine has been
shut down for less than 3 weeks
• Start-UpAfter Extended Shutdown — If machine has been
shut down for 3 weeks or more
TCO — Temperature Cutout
Fig. 23 — Refrigerant Levels Connection
27
Start-Up After Limited Shutdown
1. Place the capacity control, Cycle-Guard,™ and Local­Remote settings in the position indicated in Table 7.
Table 7 — Start-Up Setting Positions
SETTINGS POSITION
Capacity Control AUTO. Cycle-Guard Switch AUTO. Local-Remote Switch AS APPROPRIATE
2. Depress the Start button.
Machine should start in normal manner and the Run light should be on. The refrigerant pump will start about 5 min­utes after chiller starts; the solution typically heats up to nor­mal operating conditions within 20 to 30 minutes.
If, however, machine does not lower leaving chilled water temperature to design, noncondensables may be present. In this case, take an absorber loss reading (see Maintenance Pro­cedures, Absorber Loss Determination section, page 31).
If absorber loss is 5° F (3° C) or less, the chilled water temperature should drop to design within a short period as the automatic purge evacuates the machine. A completely evacuated machine normally has an absorber loss of 2° F (1° C) or less.
If absorber loss is greater than 5° F (3° C), follow the pro­cedure for Start-Up After Extended Shutdown.
Start-Up After Extended Shutdown
1. Start the machine in the normal manner by placing the
capacity control and Cycle-Guard settings in the posi­tions indicated in Table 7.
2. Depress the Start button.
When refrigerant pump starts and solution is warm (strong solution approximately 100 to 130 F [38 to 55 C]), place capacity control operation button in MANUAL position and press the positioning button (Ä) to shut the steam valve.
3. Determine machine absorber loss (see Maintenance Pro-
cedures, Absorber Loss Determination section, page 31). If absorber loss is 5° F (3° C) or less, open capacity con­trol valve by placing capacity control button in AUTO. position and allow machine to operate. The purge will evacuate the machine to the normal absorber loss of 2° F (1° C) or less.
If absorber loss is more than 5° F (3° C), evacuate ma­chine to remove noncondensables that can prevent nor­mal operation (see Maintenance Procedures, Machine Evacuation section, page 33). An alternative procedure is to limit steam pressure so that low-stage generator strong solution temperature remains below 140 F (60 C) while machine purge removes the noncondensables.
4. Whenabsorber loss is reduced to 5° F (3° C) or less, place capacity control switch in AUTO. position, return steam pressure to normal and allow purge to establish the nor­mal 2° F (1° C) or less absorber loss rate.
5. After evacuation, check the noncondensable accumula­tion rate to determine machine tightness (see Mainte­nance Procedures, Noncondensable Accumulation Rate section, page 31).
Start-Up After Below-Freezing Conditions —
Refill all water circuits if previously drained. Then follow procedure for Start-Up After Extended Shutdown.
Remove solution from the refrigerant circuit by following the procedure, Removing Lithium Bromide from Refriger­ant, page 35.
Machine Shutdown — Normal Conditions
1. Depress the Stop buttonmomentarily.Machinegoes through
automatic dilution for about 15 minutes and shuts down.
2. Closethe main steam valve and stop system pumps. Leave
machine in this condition until the next start-up.
Machine Shutdown — Below Freezing Conditions
1. Depress the Stop button momentarily. Wait until auto-
matic dilution is complete (about 15 minutes) and all ma­chine pumps stop.
2. Close the main steam valve and stop system pumps.
3. Completely drain all tube bundles and flush all tubes with
an antifreeze chemical such as glycol.
4. a. The refrigerant circuit requires special treatment. Fill
a hose with water (to avoid letting air into the ma­chine), and connect it between the solution pump and refrigerant pump service valves.
b. Start the machine and open both service valves. Keep
the steam valve closed. If the machine has a refrig­erant pump with above atmospheric discharge pres­sure, it must be stopped for this procedure.
c. Allow solution pump to run for 10 minutes. This will
transfer lithium bromide solution into the refrigerant, lowering the refrigerant freezing point. Close the serv­ice valves and remove the hose.
d. Leave the machine running with all machine pumps
operating for about one minute to be sure lithium bromide has been mixed throughout the refrigerant circuit.
e. Depress the Stop button.
28
Actions After Abnormal Shutdown — Abnormal
stop occurs automatically when any of the safety devices in Table 8 sense a condition which might be potentially dam­aging to the chiller. When this happens the steam valve closes completely, the alarm buzzer sounds, and the type of prob­lem is indicated by one of the three fault lights. Also, both the Stop and Run lights will be on.
The buzzer can be silenced and the circuit reset for restart by depressing the Stop button, but this should be done only after noting which fault light is on; or the alarm buzzer stop button may be depressed to silence the buzzer while the con­trol circuit remains in a shutdown alarm mode for trouble­shooting. If the fault is a type which does not allow shut­down dilution, the condition should be corrected and the chiller either restarted, or started and stopped for normal
dilution, as quickly as possible to avoid solution crystalli­zation when the machine cools down.
Actions After Power Interruption — If the control
power is interrupted during operation, the chiller stops im­mediately without the normal shutdown sequence and dilu­tion. The capacity control valve might be open so the steam supply valve should be closed immediately.
Solution crystallization can occur if the concentration is high (e.g., chiller was operating with a relatively large load). If so, depress the Start button to restart the machine as soon as possible after the power is restored. The machine will not restart automatically when power is recovered. If the chiller cannot be operated because of crystallization, follow the de­crystallization instructions in the Maintenance Procedures sec­tion, page 40.
Table 8 —Automatic Stop Safety Devices
CONDITION
CONTROL SAFETY SHUTDOWN SAFETY
SYMBOL RELAY DILUTION INDICATOR
Low chilled water flow (below 50%) 69CW CWX No LD1 Low chilled water temperature (below 36 F [2 C]) 26CW CWX No LD1 Chilled water pump auxiliary contact 88EP CWX No LD1 Cooling water pump auxiliary contact 88CP CWX No LD1
Solution pump motor high temperature 26SP 26MX No LD2 Refrigerant pump motor high temperature 26RP 26MX No LD2 Solution pump motor current overload 51SP 26MX No LD2 Refrigerant pump motor current overload 51RP 26MX No LD2
High-stage generator high pressure (above −.8 in. Hg [−20 mm]) 63GH 63GX Yes LD3 High-stage generator high temperature (above 338 F [170 C]) 26GH 63GX Yes LD3 High absorber pressure (above — 400 mm Hg [−15.8 in. Hg]) ABS ABSX No NONE
PERIODIC SCHEDULED MAINTENANCE
Normal preventive maintenance for 16JT absorption chill­ers requires periodic, scheduled inspection and service. Each item in the list below is detailed in the Maintenance Proce­dures section.
Every Day of Operation
1. Log machine and sytem readings.
2. Exhaust purge.
Every Month of Operation
1. Determine absorber loss.
2. Determine noncondensable accumulation rate.
3. Check capacity control adjustment.
Every 2 Months of Operation
1. Check low-temperature cutout.
2. Check Cycle-Guard™ operation.
Every 6 Months of Operation
1. Check refrigerant charge.
2. Check octyl alcohol.
Every Year of Operation
1. Have solution analyzed.
2. Check tubes for scale and fouling.
Every 3Yearsof Operation — Replace service valve
diaphragms.
Every 5 Years or 20,000 Hours of Operation —
(Whichever comes first.)
1. Inspect hermetic pumps.
2. Filter or regenerate the solution if necessary.
MAINTENANCE PROCEDURES
LogSheets —
Readings of machine and system pressure­temperature conditions should be recorded daily to aid the operator in recognizing both normal and abnormal machine conditions. The record also aids in planning a preventive main­tenance schedule and in diagnosing machine problems.Atypi­cal log sheet is shown in Fig. 24.
29
ENGINEER DATE
JOB NAME MACHINE SIZE SERIAL NO.
TIME OF DATA PURGE EXHAUST AMOUNT/NUMBER
CHILLED WATER
Temperature Entering Temperature Leaving Pressure Entering Pressure Leaving
COOLING WATER
Temperature Entering Absorber Temperature Leaving Absorber Temperature Leaving Condenser Pressure Entering Absorber Pressure Leaving Absorber Pressure Leaving Condenser
STEAM/ HOT WATER
Supply Pressure Pressure/Temperature to Machine Valve Position Condensate/Leaving Water Temperature
REFRIG­ERANT
Pump Discharge Temperature Specific Gravity High-Stage Vapor Condensing Temperature Low-Stage Vapor Condensing Temperature Cycle-Guard™ Operation?
WEAK SOLUTION
Actual Temperature Sample Temperature Specific Gravity Concentration Saturation Temperature Alcohol in Sample? Temperature Leaving Low-Temperature
Heat Exchanger Temperature Leaving High-Temperature
Heat Exchanger
STRONG SOLUTION
Temperature Leaving High-Stage Generator Temperature Leaving Low-Stage Generator Temperature To Sprays Temperature Leaving High-Stage Heat
Exchanger
Fig. 24 — Typical 16JT Maintenance Record Log Sheet
30
Purge Manual Exhaust Procedure (Fig. 25) —
See also Machine Description section, pages 3-9, for expla­nation of the purge operation, component identification, and illustrations.
NOTE: The following does not apply to optional vacuum pump operation.
NEVER LEAVE the machine during purging opera­tion. A failure to close the exhaust valve will disable the machine, and could cause crystallization of the solution.
OPERATE THE VALVES in the correct sequence. NEVER LET AIR leak into the machine. MAKE SURE that the tip of the vinyl tube is at the bot-
tom of the plastic bottle at all times. NEVER SPILL any solution from the plastic bottle.
If spilled on personnel or the floor, follow the warning pertaining to Handling Lithium Bromide Solution, page 21.
1. Exhaust purge only when machine and solution pump are operating, because the exhaust pressure is supplied by the solution pump.
2. Keep end of plastic tube below the liquid level in plastic bottle.
3. Close the solution return valve.
4. Wait approximately 5 minutes for storage chamber pres­sure to rise above atmospheric.
5. Slowly open the exhaust valve. If the liquid level in the exhaust bottle drops, close valve and wait approximately 2 minutes.
6. Slowly reopen the exhaust valve. If bubbles appear in the exhaust bottle, leave exhaust valve open until bubbles stop and solution level in bottle begins to rise. Close valve; purge is now exhausted.
7. Open the solution return valve to resume purge operation.
8. Slowly open the exhaust valve and allow solution in the bottle to be drawn into the purge tube. Lower the solution level until bottle is one-third to one-half full. Close ex­haust valve before solution level in bottle nears the tube end. Do not allow air to be drawn into the purge tube.
9. Log the date and time of purge evacuation to provide an indication of changes in the rate of noncondensable accumulation.
Absorber Loss Determination — Take absorber
loss readings when machine is operating with stable temperatures.
1. Make sure that Cycle-Guard™ valve is closed and has not operated for at least 10 minutes before taking readings.
2. Fill thermometer wells on discharge lines of solution and refrigerant pumps with oil or heat conductive compound and insert thermometers.
3. Take refrigerant and solution samples (see Solution or Re­frigerant Sampling, page 34), and determine the specific gravity and temperature of each sample. The samples can be returned to the machine through the purge exhaust bottle.
4. Using the equilibrium diagram (Fig. 22A or 22B), plot the intersection point of the specific gravity and tem­perature of the solution sample. Extend this point
horizontally to the right and read the saturation tempera­ture. Repeat with refrigerant sample, using Fig. 26A or 26B and reading to the left for saturation temperature.
5. Subtract the solution saturation temperature from the re­frigerant saturation temperature. The difference is the ab­sorber loss. Repeat the readings with a second sample to verify steady state conditions. (On larger chillers with mul­tiple solution pumps, determine saturation temperature for each pump.) If the absorber loss is greater than 5° F (3° C), machine evacuation is necessary because exces­sive noncondensables may interfere with normal opera­tion before they can be removed by the purge (see Ma­chine Evacuation section, page 33).
For probable causes and suggested remedies for high ab-
sorber loss, refer to the Troubleshooting Guide, pages 41 and
42.
NoncondensableAccumulation Rate — The most
important maintenance item on the absorption machine is the maintenance of machine vacuum within acceptable lim­its. Machine vacuum tightness can be checked by determin­ing the rate at which noncondensables accumulate. Some noncondensables are normally generated within the ma­chine; but an air leak or the need for additional inhibitor is indicated if the accumulation rate increases.
After machine evacuation or other service, operate ma­chine for at least 200 hours before determining noncondens­able accumulation rate. Then proceed as follows (Fig. 27):
1. Fill a length of flexible tubing with water and connect to
the purge exhaust connection. Insert free end into a con­tainer of water. Exhaust purgecompletely (see PurgeManual Exhaust Procedure section, on this page).
2. Operate machine for 24 hours with purge operating
normally.
3. Fill a 2-pint (1000 cm
3
) bottle with water and invert it in
a clean container filled with water.
4. Insert the free end of water-filled hose into the bottle.
5. Followthe purge exhaust procedure. Noncondensables dis-
place water in the inverted bottle. Continue until bub­bling in the bottle ceases and only solution flows from exhaust tubing.
Fig. 25 — Purge Exhaust Assembly
31
Fig. 26A — Equilibrium Diagram for Lithium Bromide in Refrigerant (F)
Fig. 26B — Equilibrium Diagram for Lithium Bromide in Refrigerant (C)
32
6. Close exhaust valve and mark liquid level on inverted bottle. Remove bottle from container.
7. Return purge to normal operation. Replace exhaust bottle (Fig. 25). Open solution return valve (Fig. 8 and 9).
8. Measure the amount of noncondensables removed. If a graduated bottle is used, the amount (volume) of noncon­densables removed is indicated by mark on bottle. If a nongraduated bottle is used, empty the bottle and then fill the bottle with liquid to the exhaust mark. Pour the liquid into a graduated container to measure the volume dis­placed.
9. If the operating accumulation rate has increased substan­tially from previous rates, machine has an air leak or re­quires additional inhibitor. Have a solution sample ana­lyzed (see SolutionAnalysis section, page 34, to determine the proper corrective action. If a leak is indicated, it must
be found and repaired as soon as possible to minimize internal corrosion damage.)
Machine Leak Test — All joints welded at machine
installation must be leak tested before initial start-up of ma­chine. Joints must also be leak tested after repair. If there is any indication of air leakage, leak test the entire machine.
1. Be sure auxiliary evacuation valve, purge exhaust valve, and all pump service valves are closed.
2. Breakmachine vacuum with dry nitrogen. Pressurize ma­chine to 6 psig (40 kPa) with tracer gas. Charge the ni­trogen and refrigerant through the auxiliary evacuation valve.
3. Use dry nitrogen to raise machine pressure to 12 psig (80 kPa). Do not exceed 12 psig (80 kPa).
4. Leak test all joints with an electronic leak detector.
5. Correct all leaks; retest to ensure repair.
6. Release machine pressure and perform machine evacuation.
Machine Evacuation — Evacuation is required for the
removal of excessive noncondensables from the machine. The machine must be evacuated after air has entered the machine during service work or when absorber loss is greater than 5° F (3° C) during operation.
1. Connect an auxiliary evacuation device to the auxiliary evacuation valve (Fig. 28). Use a line size at least equal to the connection size on the auxiliary device and keep the line as short as possible. A check valve must be used
on the suction lines. Be sure all connections are vacuum tight.
A vacuum pump oil trap can also serve as a cold trap if it has a center well to hold dry ice or a mixture of salt and ice. Any water vapor that can contaminate the oil in the vacuum pump is condensed and removed by the cold trap. The cold trap reduces the time required for evacuation and eliminates the need for frequent replacement of the pump oil charge.
2. Start evacuation device. After one minute, open auxiliary evacuation valve. If the machine is not operating, reduce machine absolute pressure to the pressure equivalent of the saturation temperature of the refrigerant. If the ma­chine is operating, evacuate until absorber loss is 5° F (3° C) or less.
3. Close auxiliary evacuation valve and turn off the auxil­iary evacuation device.
4. Machine evacuation can remove octyl alcohol. Check a solution sample for the presence of octyl alcohol and add if necessary (see Adding Octyl Alcohol, page 35.)
Fig. 27 — Collecting Noncondensables
Fig. 28 — Machine Evacuation Device
33
Solution or Refrigerant Sampling — (See precau-
tions pertaining to handling lithium bromide solution as described in Solution and Refrigerant Charging section, page 21.)
Take solution or refrigerant samples from the pump serv-
ice valve while the pump is operating.
Before taking a sample for analysis or absorber loss de­termination, be sure machine is operating with steady load and that Cycle-Guard™ valve has not been energized within 10 minutes prior to sampling.
Attach a hose adapter to the pump service valve. Do not use copper or brass fittings when taking samples for analy­sis; copper oxide can form and contaminate samples.
The solution pump normally discharges at above atmo­spheric pressure, but the refrigerant pump discharges at a vacuum, so the respective sampling procedures are different.
SOLUTION SAMPLE
1. Fill a length of flexible tubing with water and connect
one end to the hose adapter. Place the free end in a con­tainer of water. Be sure end is submerged (Fig. 29).
2. Openvalve slightly.When container water level rises, wait
several seconds to purge the water from the tube. Then remove tube end from water and fill sample container.
3. Turn off service valve and remove hose and adapter. REFRIGERANT SAMPLE (Fig. 30)
1. Connect a clean, empty vacuum container to the pump
service valve with a length of flexible hose.
2. Connect a vacuum pump to the vacuum container with a
flexible hose and isolation valve.
3. Pull a deep vacuum on the container and close the iso-
lation valve.
4. Openthe service valve slightly to drain refrigerant sample
into the container.
5. Turn offservice valve, remove hose and adapter, and dis-
connect vacuum pump.
SolutionAnalysis — Laboratory analysis of a solution
sample gives indication of change in solution alkalinity and depletion of inhibitor, and may indicate the degree of ma­chine leak tightness.
Have the solution analyzed at least once a year or when­ever there is an indication of a noncondensable problem. Take the sample from the solution pump service valve while the machine is running (see Solution or Refrigerant Sampling section, this page). The sample concentration should be be­tween 58% and 62% by weight for best results.
Solution analysis should be done by an approved lab­oratory. The analysis interpretation and the adjustment rec­ommendations should be made by a trained absorption specialist.
Inhibitor — The initial charge of lithium bromide in-
cludes a lithium chromate inhibitor. The inhibitor is used in conjunction with alkalinity control to minimize the amount of hydrogen normally generated within the machine. Exces­sive hydrogen generation interferes with machine perfor­mance.
The inhibitor is gradually depleted during machine opera­tion and occasional replenishment is necessary. Solution al­kalinity also changes over a period of time and must be ad­justed (see Solution Analysis, on this page).
IMPORTANT:Altering the inhibitor or using solution and internal surface treatments not specified by the equip­ment manufacturer may result in performance deterio­ration and damage to the absorption machine.
Fig. 29 — Adding or Removing Fluid
Fig. 30 — Refrigerant Sampling Technique
34
Adding Octyl Alcohol — Octyl alcohol may be re-
quired when leaving chilled water temperature starts to rise above design temperature without alteration of the control set point. Since the rise in temperature can also be caused by fouled tubes or other problems, use the following procedure to determine whether a lack of octyl alcohol is the cause:
1. Removea sample of solution from the solution pump serv­ice valve (see Solution or Refrigerant Sampling section, page 34). If the solution has no odor of alcohol (very pun­gent), add about
1
⁄2gal. (2 L) of octyl alcohol.
The addition of octyl alcohol also may be required after the machine has been evacuated or after an extended pe­riod of operation.
Use only octyl alcohol. Other types of alcohol have a detrimental effect on machine performance.
2. Fill a length of flexible tubing with water and connect one end to the solution pump service valve (see Fig. 29). Insert the other end in a container of octyl al­cohol. Stop the solution pump. The pump can be stopped without a dilution cycle by pressing the trip bar on the pump starter overload, then pressing the Stop button and the overload reset. Then open the service valve to allow alcohol to be drawn into the machine. Close valve before air can be drawn into the hose. Restart the chiller and solution pump.
Removing Lithium Bromide from Refrigerant —
During normal operation, some lithium bromide may be carried over into the refrigerant. Lithium bromide in the re­frigerant is automatically transferred back to the absorber by the Cycle-Guard™ valve when it is needed. The refrigerant flows through the Cycle-Guard valve into the solution cir­cuit and separation is made in the generator in the normal manner.
Lithium bromide recovery can also be initiated by placing the Cycle-Guard switch in MANUAL position while the ma­chine is running and the capacity control valve is open. When the refrigerant specific gravity drops below 1.02, return the Cycle-Guard switch toAUTO.to close the Cycle-Guard valve.
RefrigerantCharge Adjustment — Checkthe evapo-
rator refrigerant (water) charge after every 6 months of op­eration. An increase in the amount of water in the machine indicates tube leakage. Furthermore, the correct refrigerant charge must be maintained for accurate operation of the Cycle­Guard system.
For charge adjustment, refer to Initial Start-Up, Final Re­frigerant Charge Adjustment section, page 25.
Capacity ControlAdjustment — Check the leaving
chilled water temperature. If design temperature is not being maintained, reset the control set point in the machine control panel (see Check Capacity Control Operation section, page 23).
If machine still fails to maintain design temperature, re­fer to the Troubleshooting section entitled Problem/Symptom — Leaving Chilled WaterT emperatureToo High or TooLow, page 41.
Low-Temperature Cutout Adjustment— This ma-
chine safety serves to prevent freeze-up damage to the evapo­rator tubes. Check the cutout periodically to confirm trip at the selected setting.
NOTE: If the cutout sensor has been exposed to tempera­tures above 120 F (49 C), the control must be recalibrated.
1. Remove the control sensing element from its well in the
chilled water pipe. Immerse the element in a container of cool water. Slowly stir crushed ice into the water so that the temperature goes down at a rate not exceeding 1° F (0.5° C) per minute.
2. Observe the cutout temperature. It should be 9° F (5° C)
below design leaving chilled water temperature or a mini­mum of 36 F (2 C). If control fails to cut out by 36 F
(2 C), stop machine immediately and recalibrate control
as described in Check Low-Temperature Cutout section, page 22.
3. When control cuts out, machine shuts down immediately
without going through dilution cycle. Control cuts in when sensing element warms up 7.2° F (4° C).
If necessary, reset cutout adjustment knob and recali­brate. Restart machine by depressing the Stop button and then the Start button. Replace sensing elements in wells.
Cycle-Guard™ System Operation — To check op-
eration, place Cycle-Guard switch in MANUAL position. The Cycle-Guard transfer valve energizes. The flow of refriger­ant will cause the transfer line between valve and solution pump inlet to feel cold to the touch. This line should not feel cold when the transfer valve is closed (not energized). If the line is cold when valve is deenergized, the valve is leaking and must be repaired. Return Cycle-Guard switch to AUTO. position.
During normal operation, the Cycle-Guard valve is con­trolled by a thermoswitch (26SH), which senses the strong solution temperature as it flows to the absorber spray header and by 2 refrigerant level switches (33RH and 33RM), lo­cated in the evaporator.
For nominal operating conditions, switch 26SH closes on temperature drops below 118 F (48 C). Special operating con­ditions may require special settings.
Level switches 33RH and 33RM close with rising refrig­erant levels that correspond to increasing solution concen­trations of approximately 59.5% and 60.0% respectively, for nominal full load operating conditions. (See Maintenance Pro­cedures entitled Refrigerant ChargeAdjustment and Thermo­switch Adjustment, pages 35 and 36.)
Cycle-Guard system malfunction makes the machine sus­ceptible to solution crystallization. SeeTroubleshootingGuide, Solution Crystallization During Operation, page 42.
35
ThermoswitchAdjustment— Checkthe 26SH thermo-
switch while machine is operating.
1. Athermowell is located on the absorber spray supply pipe near the thermoswitch sensing bulb well. Place heat con­ductive compound or oil in the thermowell and insert a thermometer with a range of about 0° to 300 F or about 0° 150 C).
2. Turn the thermoswitch adjustment knob fully counter­clockwise and then slowly clockwise until the contacts close. Note the difference (if any) between the actual ther­mometer reading and the reading on the thermoswitch ad­justment scale as the contacts close. Allow for this dif­ference in setting the thermoswitchcontrol point. (Example: As switch contacts close, thermometer reads 110 F (43.3 C) and thermoswitch scale reads 107 F (41.7 C), an error of 3° F (1.6° C). Tohave contacts close at a selected temperature of 118 F (47.8 C), knob must be set at scale reading of 115 F (46.1 C).
Allowing for anytemperature difference as described above, set adjustment knob as required to make contacts close at 118 F (48 C) thermowell temperature.
NOTE: Special operating conditions may require other thermoswitch settings. Check job data. Use same adjust­ment procedure.
Low-Refrigerant Level Operation — During low-
load operation, with low condensing water temperature, the normal dilution of the solution will lower the refrigerant level in the evaporator. If the level goes down enough to open the low refrigerant level switch 33RL, the refrigerant pump stops to prevent cavitation in the refrigerant pump and subsequent pump motor failure.
To check the operation of the low-level switch, first place the capacity control in MANUAL and Ä position (which closes the steam valve) and the Cycle-Guard switch in MANUAL. This will transfer refrigerant to the solution cir­cuit, lowering the refrigerant level in the evaporator. When the refrigerant level reaches the low-level switch, the refrig­erant pump stops. Then return both the Cycle-Guard switch and the capacity control to AUTO. positions. If the pump becomes noisy, it might be in cavitation from a low level switch malfunction. Do NOT allow the pump to remain in operation with this condition.
Internal Service — To prevent corrosion from air in-
side the machine, break vacuum with nitrogen when open­ing the machine for maintenance or repair.
While the machine is open, it is good practice to mini­mize the amount of air entering by continuously feeding ni­trogen into the machine at approximately 1 psig (7 kPa) pressure.
Perform service work promptly and efficiently and close the machine as soon as possible. Do not rely on the inhibitor for corrosion protection unless all lithium bromide and re­frigerant have been removed and the machine has been com­pletely flooded with a lithium chromate inhibitor-water solution prior to machine opening.
Leak test the machine thoroughly after the machine has been closed up.
When flamecutting or welding on an absorption ma­chine, some noxious fumes may be produced. Ventilate the area thoroughlyto avoid breathing concentrated fumes.
Never cut into the purge chamber unless the purge has been exhausted to remove any hydrogen gas that might be present in the chamber. Hydrogen can form an explosive mixture in the air.
Service Valve DiaphragmReplacement — Tore-
place valve diaphragms:
1. Break machine vacuum with nitrogen. Solution and re­frigerant can be transferred to opposite sumps within the machine or removed from the machine. If removed from the machine, store it in clean containers for recharging.
2. Remove old valve diaphragms and replace. Torque valve bolts to approximately 3 lb-ft.
3. Test all affectedconnections for leakage (see Machine Leak Test section, page 33).
4. Reevacuate machine after servicing (see Machine Evacu­ation section, page 33).
5. Replace solution and refrigerant in machine (the samequan­tity that was removed).
Hermetic Pump Inspection — Figure 31 is a sec-
tional structural schematic of a typical refrigerant or solu­tion pump used on the 16JT chiller.These centrifugal pumps are hermetic and do not require seals. The rotor assembly is enclosed in a thin stainless steel can, and some of the pump discharge liquid (refrigerant or solution) is circulated around the rotor assembly for cooling the motor and for lubricating the bearings. The following instructions are general proce­dures for a typical pump version. Details will vary slightly for different pump models.
Never run hermetic pump motor dry. Even momentary operation without machine filled with liquid will dam­age bearings and overheat the motor. Use only the cur­rent value specified in the control circuit diagram when setting the pump starter overloads.
DISASSEMBLY
Disconnect all primary power to the pumps; lock and tag all disconnect switches.
1. Break vacuum with nitrogen if not already performed.
2. Removesolution and refrigerant from the machine. Store in clean containers until recharging.
36
LEGEND
1—Circulation Pipe 2—O-Ring Gasket 3—Bolt 4—Bolt 5—Motor End Cover 6—Motor End Cover
Gasket
7—Radial Bearing (B) 8—Thrust Bearing (B)
9—Thrust Collar (B) 10 — Pin 11 — Terminal Box 12 — Motor Frame 13 — Stator 14 — Stator Liner
(Stator Can)
15 — Rotor Liner
(Rotor Can)
16 — Rotor 17 — Shaft 18 — Plug 19 — Bolt 20 — Bolt (Jack Screw) 21 — Nut 22 — Casing Flange
Gasket
23 — Pump Casing 24 — Bolt 25 — Impeller 26 — Set Screw 27 — Motor Side
Wear Ring
28 — Set Screw 29 — Pump Casing
Wear Ring
30 — Lock Washer 31 — Lock Screw 32 — Key 33 — Wear Ring Housing 34 — Radial Bearing (A) 35 — Thrust Bearing (A) 36 — Thrust Collar (A) 37 — Pin 38 — Nut 39 — O-Ring Gasket 40 — Bolt
Fig. 31 — 16JT Refrigerant and Solution Pump Schematic (Typical)
37
3. Open the motor wiring terminal box (Item 11) and dis­connect the motor power leads. Mark the leads to en­sure proper reassembly.
4. Remove nuts (Item 21) holding motor adapter flange to pump casing (Item 23). With the larger motors which have a hanger support, disconnect the hanger. Place match­ing orientation marks on the two flanges.
NOTE: Use blocking to support the weight of the motor before moving it and before removing hanger support.
5. If pump has a circulation pipe (Item 1) connected to the pump discharge pipe, disconnect the circulation pipe at this time.
6. Use jack screw to loosen motor from pump casing. Pull motor straight back from pump casing until impeller (Item 25) has cleared the housing.
7. Remove and discard casing flange gasket (Item 22).
8. Straighten locking tabs on impeller locking washer (Item 30), and remove locking screw (Item 31). Prevent impeller from rotating while removing the locking screw.
9. Removeimpeller with impeller/gear puller. Remove shaft key (Item 32).
10. Remove bolts (Item 24) for motor wear ring housing (Item 33), and, using one bolt as a jack screw, carefully loosen the wear ring housing fromthe motor adapter flange. Place matching orientation marks on the two pieces. Pull the wear ring housing straight back from the motor while supporting the impeller shaft (Item 17), being careful to not damage the bearings or the stator and rotor cans (Items 14 and 15).
11. Remove the impeller end radial and thrust bearings (Items 34 and 35), and mark them for both location and direction (i.e., which end of the bearing faces the im­peller end of the motor).
12. While continuing to support the impeller shaft, pull the rotor (Item 16) straight out of the rotor cavity, being care­ful to not damage the bearings or the stator and rotor cans.
13. Remove the bolts (Items 3 and 40) from the circulating pipe connecting flange(s), if not previously done, to dis­connect the pipe from the end of the motor.
14. Remove and discard O-rings (Items 2 and 39).
15. Remove the bolts (Item 4) on the motor end cover (Item 5) and use one as a jacking screw to loosen the end cover from the motor end flange. Place matching orientation marks on the two pieces. Remove the cover.
16. Remove the motor end radial and thrust bearings (Items 7 and 8), and mark them for both location and direction (i.e., which end of the bearing faces the im­peller end of the motor).
17. NOTE: Remove and discard motor end cover gasket (Item 6).
NOTE: Do not remove the plug (Item 18) on the top of the motor (Item 12) except when leak testing or drying the mo­tor windings.
INSPECTION
1. Check circulation passages in motor and circulating pipe. Clean if necessary.
2. Inspect rotor and stator cans for scratches, rubbing, or punc­tures. Severe damage will require motor replacement.
3. Inspect the radial bearing cavities in the motor end cover and wear ring housing. If the internal surface is rough or worn more than the maximum diameter in Table 9, re­place the part.
Table 9 — Maximum Radial Bearing Cavity
Measurement
MOTOR SIZE MAX. DIAMETER (D)
kW in. mm
1.5 1.27 32.3
3.7 1.51 38.3
5.5 1.98 50.3
7.5 1.98 50.3
4. Inspect the radial and thrust bearings. If the surface is very rough or deeply scratched, or if worn to a thickness less than listed in Table10, replace the bearing. The thrust bearing on the impeller end normally receives the great­est wear.
Table 10 — Minimum Bearing Thickness
Measurement
MOTOR SIZE
MIN. RADIAL
THICKNESS (T1)
MIN. THRUST
THICKNESS (T2)
kW in. mm in. mm
1.5 0.13 3.3 0.18 4.6
3.7 0.15 3.8 0.18 4.6
5.5 0.19 4.8 0.22 5.6
7.5 0.19 4.8 0.22 5.6
38
5. Check the impeller wear surfaces. If very rough or worn to outside diameters less than listed in Table 11, replace the impeller.
Table 11 — Maximum Wear Ring
Inner Diameters
MOTOR SIZE
MAX. MOTOR RING
(D1)
MAX. CASING RING
(D2)
kW in. mm in. mm
1.5 3.47 88.2 3.00 76.2
3.7 3.95 100.2 3.95 100.2
5.5 3.95 100.2 3.95 100.2
7.5 3.95 100.2 3.95 100.2
6. Check the wear rings. If the wear surfaces are very rough or deeply scratched, or are worn to inner diameters less than listed in Table 12, replace the wear ring. They are retained by setscrews (Items 26 and 27).
Table 12 — Minimum Impeller Wear Diameters
MOTOR SIZE
MIN. MOTOR SIDE
(D1)
MIN. MOTOR SIDE
(D2)
kW in. mm in. mm
1.5 3.45 87.6 2.98 75.6
3.7 3.92 99.6 3.92 99.6
5.5 3.92 99.6 3.92 99.6
7.5 3.92 99.6 3.92 99.6
7. Check the condition of the thrust collars (Items 9 and 36) on the rotor shaft. If very rough, deeply scratched, or se­verely worn, they should be replaced. They are retained by pins (Items 10 and 37).
8. Check the condition of the radial bearing sleeve faces on the rotor shaft. If very rough, deeply scratched, or se­verely worn, they should be replaced. They are retained by pins.
9. Check the motor insulation resistance. If less than 10 milliamps, the windings must be dried.
REASSEMBLY
1. Clean all parts, gasket surfaces, and O-ring grooves. Use new gaskets (Items 6 and 22) and new O-rings (Items 2 and 39).
2. Install motor end radial bearing (Item 7) in the motor end cover (Item 5) and apply a small amount of gasket paste to both sides of the gasket (Item 6). Mount the motor end cover and gasket, aligning the match marks applied dur­ing disassembly. The internal flow passage ‘‘A’’ should be at the top as the pump is installed on the chiller.
3. Place thrust bearings (Items 8 and 35) against their re­spective thrust collars on the rotor shaft (Item 17). Care­fully guide rotor (Item 16) into position within the stator (Item 13) to avoid damage to the bearings, rotor liner (Item
15), and stator can (item 14).
4. Install radial bearing (Item 34) and motor side wear ring (Item 27) in the wear ring housing (Item 33). Mount the wear ring housing, aligning the match marks applied dur­ing disassembly. The internal flow passage ‘‘A’’ should be at the top as the pump is installed on the chiller.
5. Install impeller (Item 25) with impeller key (Item 32), lock washer (Item 30) and locking screw (Item 31). Bend washer tabs over flats of locking screw head.
6. Turn impeller by hand to be sure it rotates easily.
7. Install new O-rings (Items 2 and 39) in flanges for cir­culation pipe (Item 1) and mount pipe in place.
8. Install pump casing wear ring (Item 29) if not already in place.
9. Apply a small amount of gasket paste to both sides of gasket (Item 22) and position on pump casing flange. Slide motor stator housingand adaptor flange assembly into pump casing, aligning the match marks applied during disas­sembly.Use blocking to support the motor stator until all bolts have been tightened and the motor support, if used, has been reconnected.
COMPLETION
1. Leak test affected joints to be sure all pump connections are tight. (See Machine Leak Test section, page 33.)
2. Evacuate machine (see Machine Evacuation section, page 33).
3. Recharge machine with same quantity of solution and re­frigerant as removed.
4. Reconnect motor power leads to motor wires in same ar­rangement as when disconnected and replace junction box cover.
5. Restore power supply to pump and chiller controls.
6. Record inspection date and results.
39
Solution Decrystallization — Crystallization occurs
when strong solution concentration and temperature cross over to the right of the crystallation line on the equilibrium diagram (Fig. 22A and 22B). It should not occur if machine controls are correctly adjusted and machine is properly operated. Refer to the Troubleshooting Guide, pages 41 and 42, for probable causes and remedies.
If crystallization occurs, it generally takes place in the shell side of the low-temperature heat exchanger and blocks the flow of strong solution from the low-stage generator. The strong solution then overflows into a pipe that returns it di­rectly to the absorber sump. The solution pump(s) then re­turns the hot solution through the heat exchanger tubes, au­tomatically heating and decrystallizing the shell side.
If crystallization results from a long, unscheduled shut­down (such as from a power failure) without proper dilu­tion, the solution pump(s) may become bound and fail to rotate. This will cause the overloads to trip out. In such a case, decrystallize as follows:
1. Heat the solution pump casing and adjacent lines with
steam.
Under no circumstances apply heat directly to pump motor or controls when warming the casing. Do not apply direct heat to any flange connections; high tem­perature can deteriorate the gasket material.
2. Rotation of a hermetic pump cannot be viewed directly.
Check the solution pump rotation by installing a com­pound gage on the pump service valve and reading dis­charge pressure. Reset the pump overloads in the control panel if they are tripped.
If the pump is rotating normally, the gage will show a reading above atmospheric pressure. If the pump casing and discharge line are completely blocked, the gage will show zero atmospheric pressure. If the pump interior is only partially blocked, a deep vacuum will indicate that the pump is not rotating.
3. Continue heating the casing until gage pressure shows above
atmospheric pressure with pump overloads reset. Do not
reset pump overloads more than once in any 7-minute period.
If the heat exchanger is also blocked, the decrystalliza­tion process will begin as soon as the solution pump starts rotating and the adjacent weak solution lines have de­crystallized. If the heat exchanger or adjacent piping does not decrystallize automatically, heat the blocked area ex­ternally with steam or a soft torch flame. Crystallization in purge piping can be broken up by applying heat in the same manner.
4. If the strong solution line from heat exchanger to ab­sorber spray nozzles is blocked, turn off the condensing water pump and operate the machine with capacity con­trol valve open. Turn the Cycle-Guard™ switch to MANUAL to dilute the solution. The entire unit will pick up heat and the crystallization will dissolve. Do not heat solution leaving absorber above 140 F (60 C) to avoid overheating the solution pump motor. If severe crystalli­zation is present, it may take 4 to 6 hours to fully decrystallize.
When heating the machine in this manner, remove the low-temperature cutout (LTCO) and thermoswitch sens­ing bulbs from their wells and insulate them to prevent overheating. When machine temperatures return to nor­mal, recalibrate the LTCO and thermoswitches (see Low­Temperature Cutout Adjustment and Thermoswitch Ad­justment section, pages 35 and 36).
CondensingWaterTubeScale isindicated if the tem-
perature difference between condensing water leaving the con­denser and refrigerant condensate from the condenser is greater than the normal 4 to 7° F (2 to 4° C) difference at full load (capacity control valve fully open). Scale reduces heat trans­fer,increases steam consumption, and limits machine capac­ity.Scale can also cause serious corrosion damage to the tubes.
Soft scale can be removed from tubes with cleaning brushes, specially designed to avoid scraping or scratching the tube walls. The brushes are available through your Carrier rep­resentative. Do not use wire brushes.
Hard scale may require chemical treatment for its pre­vention or removal. Consult a water treatment specialist for proper treatment.
WaterTreatment— Untreated or improperly treated wa-
ter may result in corrosion, scaling, erosion, or algae. The services of a qualified water treatment specialist should be obtained to develop and monitor a treatment program.
Water must be within designflow limits, clean, and treated to ensure proper machine performance and reduce the potential of tubing damage due to corrosion, scaling, or erosion. Carrier assumes no responsibility for chiller dam­age resulting from untreated or improperly treated water.
40
TROUBLESHOOTING GUIDE
PROBLEM/SYMPTOM PROBABLE CAUSE REMEDY
Machine Will Not Start or Shuts Down
(Panel RUN light out, pumps off.)
No power to control panel Check for building power failure. Check main circuit
breaker.
Control panel fuse blown Examine circuits for ground or short.
Replace fuse. Control panel main circuit breaker open Close main circuit breaker. Control panel switches not set correctly Depress Stop button after safety shutdown.
Place capacity control and Cycle-Guard™ selections
in AUTO. and depress Start button. Chilled water or condensing water pump
overloads or flow switches open
Check chilled water and condensing water pumps,
starters and valves. Solution pump overloads open Push overload reset button. Measure pump discharge
pressure to check for solution crystallization
(see Solution Decrystallization section on page 40). Refrigerant pump overloads open Push overload reset button. Low temperature cutout Depress Start button after chilled water has warmed
at least 7° F (4° C). Measure chilled water temperature.
Recalibrate or replace switch if temperature is above
set point. Check capacity control setting and operation
if temperature is below switch setting (see Check
Capacity Control Operation section on page 23). High generator solution temperature
or pressure, high absorber pressure.
Check cooling water temperature and flow.
Check absorber pressure.
Leaving Chilled Water Temperature Too High
(Machine running, chilled water temperature above design.)
Steam control valve not open Verify capacity control is positioned at AUTO.
Check capacity control operation per Initial Control
Checkout and Adjustment section, pages 22-24. Set point too high Reset temperature control in control panel. Excessive cooling load (machine
at capacity)
Check for cause of excessive load.
Excessive chilled water flow (above design)
Check pressure drop per selection data and reset flow.
Low condensing water flow (below design) Check pressure drop per selection data and reset flow. High supply condensing water
temperature (above design)
Check cooling tower operation and temperature controls.
Low steam pressure (below design) Raise to design per selection data. Inadequate steam condensate drainage
(condensate backs up into tube bundle)
Check operation of steam traps, strainers, valves, and
condensate receivers. Fouled tubes (poor heat transfer) Clean tubes. Determine if water treatment is necessary. Machine needs octyl alcohol Check solution sample and add octyl alcohol if necessary
(see Adding Octyl Alcohol section on page 35). Noncondensables in machine Check absorber loss (see Absorber Loss Determination
section on page 31). If above 5° F (3° C), see Causes and
Remedies under Inadequate Purging (high absorber loss)
section on page 42. Capacity control malfunction Check calibration and operation of capacity controls (see
Check Capacity Control Operation section on page 23). Solution crystallization
(solution flow blockage)
See Causes and Remedies under Solution Crystallization
on page 42. Low refrigerant level Check the low-level switch operation and check for low
condensing water temperature. Cycle-Guard control malfunction
(low solution concentration)
Check refrigerant charge and thermoswitch calibration.
(See Refrigerant Charge Adjustment, Cycle-Guard Sys-
tem Operation and Thermoswitch Adjustment sections
on pages 35 and 36). Verify Cycle-Guard switch in AUTO.
Leaving Chilled Water Temperature Too Low
(Machine running, chilled water temperature below design.)
Set point too low Reset temperature control in control panel. Capacity control malfunction Check calibration and operation of capacity control (see
Check Capacity Control Operation section on page 23).
Leaving Chilled Water Temperature Fluctuates
(Machine running, capacity control hunting.)
Chilled water flow or load cycling Check chilled water system, controls and load. Condensing water flow or temperature
cycling
Check condensing water temperature control and
cooling tower operation. Steam pressure cycling Check steam pressure control. Inadequate steam condensate drainage
(condensate backs up into tube bundle)
Check operation of steam traps, strainer, valves,
and condensate receivers. Capacity control malfunctions Check calibration and operation of capacity control (see
Check Capacity Control Operation section on page 23).
41
TROUBLESHOOTING GUIDE (cont)
PROBLEM/SYMPTOM PROBABLE CAUSE REMEDY
Inadequate Purging (Low machine capacity and
high absorber loss — see Absorber Loss Determination, page 31.)
Air leakage in vacuum side of machine (high noncondensable accumulation rate)
Have solution analyzed for indication of air leaks. Leak test and repair if necessary (see Noncondensable Accumu­lation Rate, Solution Analysis, and Machine Leak Test sections on pages 31, 34, and 31, respectively).
Inhibitor depleted (high noncondensable accumulation rate)
Have solution analyzed. Add inhibitor and adjust solution alkalinity if necessary (see Noncondensable Accumulation Rate, Solution Analysis, and Inhibitor sections on pages 31, 32, respectively).
Purge valves not positioned correctly Check valve positions (see Purge Manual Exhaust Procedure
section on page 31).
Purge solution supply lines crystallized (not able to exhaust purge)
Heat solution supply lines (see Purge Manual Exhaust proce­dure and Solution Decrystallization sections on pages 31 and 40).
Solution Crystallization During Operation
(Strong solution overflow pipe hot.)
Cycle-Guard™ control malfunction (solution overconcentration)
Check refrigerant charge, thermoswitch calibration, and transfer valve operation. (see Refrigerant Charge Adjust­ment, Cycle-Guard System Operation, and Thermoswitch Adjustment sections on pages 35, 35, and 36, respectively).
Noncondensables in machine (high absorber loss)
Check absorber loss (see Absorber Loss Determination section on page 31). If above 5° F (2.8° C), see Causes and Remedies under Inadequate Purging above.
High steam pressure or hot water temperature (above design)
See Machine Selection Data provided with the machine. Set at design.
Absorber tubes fouled (poor heat transfer)
Clean tubes. Determine if water treatment is necessary.
Octyl alcohol depletion Check solution sample and add octyl alcohol if necessary
(see Adding Octyl Alcohol section on page 35).
Solution Crystallization at Shutdown
(Crystallization symptoms when machine is started.)
Insufficient solution dilution at shutdown After shutdown, restart machine and measure concentration
of weak solution (see Solution or Refrigerant Sampling sec­tion on page 34). If above 56%, checkdilution level switch and Cycle-Guard transfer valve.
Abnormal Noise from Solution Pump
Cavitation of solution pump (low solution level in absorber)
Open the Cycle-Guard valve manually (toggle switch 43-RV) for about 3 minutes while machine is running.
Abnormal Noise from Refrigerant Pump
Temperature of cooling water supply below 59 F (15 C).
Raise cooling water temperature above 59 F (15 C). Stop the machine and then restart it about 20 minutes later.
Frequent Cycle-Guard Operation
Fouled absorber or evaporator tubes Clean tubes. Excessive noncondensable gas
(high absorber loss)
See Inadequate Purging.
Refrigerant overcharge or tube leak. Remove refrigerant to trim charge, per start-up instructions.
Repair tube leak.
42
Copyright 1993 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5b
PC 211 Catalog No. 531-607 Printed in U.S.A. Form 16JT-2SS Pg 44 4-93 Replaces: 16JT-1SS
Loading...