Carrier 16JB User Manual

Carrier
Application Data
Application Detail
5qP£È.S<£ù£5 ¡sy
Hermetic Absorption Liquid Chillers
16JB

GENERAL

Application details in this publication cover various methods of applying the 16JB absorption machine to meet liquid chilling needs. Throughout this publication, the chilled liquid will be water.
Subjects covered are chilled water temperature control, condenser water temperature control, system design for steam and hot water machines, and general information.

CHILLED WATER TEMPERATURE CONTROL

The absorption machine is basically a water
chiller that can be connected to any conventional
open or closed system. However, circulation of
chilled water must be continuous during operation of the machine and during the shutdown dilution cycle. Chilled water flow may be restricted at partial load.
For fine chilled water temperature control within narrow limits, such as required in precision
control of industrial processes or maintenance of laboratory conditions, the chilled water system
machine to adjust slowly to changes in load. Normal air-conditioning applications are not subject to such requirements.
Systems having large storage volumes of chilled water transmit load changes to the machine slowly, allowing accurate chilled water temperature con trol. Small storage systems transmit load changes rapidly, making temperature control more diffi
cult. For fine temperature control, the chilled water system volume should be at least ten times the gpm flow through the cooler. If a tank is added to the system for extra storage volume, it should be located in the line from the load to the cooler.»
Two-Pipe Cooling-Heating Systems — When
machines are used in conjunction with a two-pipe
cooling-heating system, certain precautionary steps should be taken during changeover from heating to
cooling.
Maximum water temperature permitted thru the evaporator is 130 F because of the possibility of tube stress. If system water temperature is above 80 F but less than 130F at changeover time, evaporator flow should be throttled to prevent machine overload.
It is recommended that hot water temperatures be reset, based on outside air temperature. If a reset-type control is used, the entering hot water temperature at changeover will normally be lower than 130 F.

STEAM MACHINES

Boilers — Generally, any boiler capable of modu
lating its input to maintain design operating steam pressure within 1 psi under varying loads, is suit able for application with the absorption machine. This generally includes all gas- and oil-fired boilers.
Some oil-fired boilers are conversions from coal-fired to oil-fired and may have control systems which are too sluggish to give proper response to machine load changes. Direct control of oil feed rate normally ensures proper response.
Coal-fired boilers, due to slow buildup and shutdown characteristics, should be used only when the absorption machine represents less than
15% of boiler operating load. This generally limits coal-fired boiler applications to large industrial jobs where process steam is generated in large quantities year-round.
BOILER CAPACITY — Minimum boiler capacity for use with the absorption machine is equal to full load steam consumption, plus sufficient capacity to offset piping radiation losses. In the absence of a detailed study of radiation and vent losses, a minimum 10% safety factor should be used.
Pressure Reducing Valves — Maximum unit ratings
are based on 14 psig steam pressure at the generator inlet. Operation at higher inlet pressures or with more than 100 F superheat is not per
missible. Higher inlet pressures may lead to over
concentration.
Where steam supply pressures are above 15 psig (14 psig + 1 psig for control) and below 20 psig, the steam control valve can be used to reduce the pressure. If steam supply is above 20 psig, a pressure reducing valve must be provided between the steam supply and the control valve inlet. A safety relief valve should be provided between the
steam control valve and the generator inlet. This valve must be set in accordance with paragraph UG-133 (f) of the ASME code to relieve at a pressure not exceeding 17 to 18 psig or the setting determined by apphcable local codes.
Further specific details relative to pressure reducing stations should follow accepted standards, such as the ASHRAE Guide and manufacturer’s recommendation. For applications on high-pressure district heating, the steam utility should be con
sulted for local codes or standards.
Steam Piping should be sized to avoid excessive
pressure drop or excessive velocities. Recommenda tions and pipe sizing tables are given in the Carrier System Design Manual. It is recommended that lines be sized on the basis of design system flow for the machine plus a 10 to 20% safety factor to allow for normal radiation losses.
© Carrier Corporation 1971
Form 16JB-2XA
Start-Up Demand — Steam demand by the absorp
tion machine is greatest at start-up (see Table 1 for values).
Table 1 — Maximum Condensate Flow (Ib/hr)
VALVE VALVE INLET STEAM PRESSURE
SIZE (in.)
2
2Y2
3 4 5
20 psig
2450 2025 4825 4000
8175 6760 14540 12025 21650
14 psig
17900
12 psig 10 psig
1880 1750 3710 3430
6285 5810 11190 10350 16655 15400
When boiler capacity is unable to keep up with start-up demand, the steam pressure will fall off. On boilers serving only the absorption machine, this reduction in steam pressure will have no adverse effect on the absorption machine other than to lengthen start-up time. However, the increased steam demand may have an adverse effect on the boiler, causing it to run dry and fail. As steam pressure is reduced, the steam control valve pressure drop will eventually limit the de mand on the boiler provided the steam control valve is properly sized.
On boilers serving other loads simultaneously, the start-up demand can reduce boiler pressure sufficiently to cause adverse effects on other steam-driven equipment. When a reduction in boiler pressure cannot be tolerated without up setting other equipment, the boiler capacity avail able for absorption machine operation (with other loads deducted) must equal or exceed the start-up demands. If it does not, the start-up demand can be reduced by using demand Hmit controls, or installing a back-pressure regulator in the steam line(s) between the boiler and the control valve(s).
VALVE LOCATION AND PIPING - The steam
control valve should be located a minimum of 3 ft
away from the generator inlet. This is dictated by good piping practice, to allow equal distribution of steam in the generator tube bundle. Unequal distribution of steam in the tube bundle may cause a loss of capacity. Recommended steam supply
piping for low-pressure steam applications is illustrated in Fig. 1.
STEAM CONTROt
NOTE; Separate supoiy piping "for each end of machine sizes
16JB077 thro '24,
Fig. 1 — Low-Pressure Steam (2 to 15 psig)
Supply Piping
Machine sizes 16JB077 thru 16JB124 have steam supply inlets on each end. These are to be considered as two generators and should be piped
from a common steam header as in multiple machine installations (see Fig. 2). Each inlet should then be piped in accordance with Fig. 1.
HEADER FOR N0.2 END
NOTES:
1. Piping appiies to moitipie macbiries connected in paraiief
(3 shown).
2. Each end most be consdered as a separate generator.
3. The feed to each end of each generator should be piped as
shown in rig. 1.
Fig. 2 — Steam Piping For 16JB077 thru 124
Steam piping to the absorption machine should be designed and supported to allow for thermal expansion without imposing undue stresses on the generator inlet. The machine is not designed for, nor expected to act as, a piping support or anchor
for withstanding thermal stresses.
Condensate Systems — Satisfactory operation of
the absorption machine requires a condensate
handling system designed with the specific char­acteristics of the absorption machine in mind. The following is intended to supplement available reference data on condensate systems such as Carrier System Design Manual, ASHRAE Guide and individual manufacturer’s recommendations.
ATMOSPHERIC CONDENSATE RETURN
SYSTEMS (VENTED) - These systems usually consist of steam traps, vented receiver, condensate pump, and condensate cooler. Fig. 3 illustrates
typical atmospheric condensate return systems. On
larger machines, with dual steam generators, the condensate outlet from each generator must be
piped thru separate steam traps. Trap Selection — Steam traps should be located as
far below the generator outlet as possible. Actual pressure drop available for trap selection will depend on exact trap location below the generator
FROM SEMERATOR (LEFT END)
MACHINE Sizes 16J8077 THRU IZA

Fig. 3 — Typical Atmospheric (Vented) Condensate Return System

outlet, and trap outlet pressure. A vacuum breaker is factory installed to ensure that operating steam pressure in the generator does not fall below
atmospheric pressure. Use the following formulas to determine available trap pressure drop:
Trap pressure drop = trap inlet ~ trap outlet psig.
Trap inlet pressure = 0 psig + hydrostatic head to trap inlet -- condensate leg pressure
drop.
Trap design outlet pressure receiver pres sure + line pressure drop from trap outlet to receiver.
In determining trap outlet pressure, discount
any liquid head drop to the receiver. This line may
not run full. If there is liquid lift from trap outlet to the receiver, it must be added to trap outlet pressure.
Either float-and-thermostat or inverted-bucket traps may be used, provided the trap is recom mended by the manufacturer for rapid handhng of noncondensables. For fast start-up with inverted­bucket traps, install an external thermostatic air vent around the trap.
Traps should be sized for capacity to handle more condensate than twice the design full-load
steam rate. See steam trap manufacturer’s recom mendations. Maximum load on the trap will occur during start-up when generator pressure falls to atmospheric (0 psig) and steam condenses rapidly.
At this time, pressure drop across the steam
control valve is maximum. If boiler capacity is large enough, the control valve inlet pressure will stay at design, then flow rate will be limited by control valve capacity.
Table 1 gives maximum condensate flow for different inlet steam pressures. Interpolate for intermediate pressures.
If steam demand on start-up can be held within a controlled limit, the trap(s) may be sized accordingly.
When traps are undersized, condensate wiU back up in the generator with loss in machine
capacity and may cause dangerous water hammer.
Depending on boiler size, the boiler water makeup
system could operate and add water to the boiler. Sooner or later, excess water would return to the boiler room and either overflow the hot well to
drain, or if it flows directly into the boiler, it may
control.
Condensate Cooler is used on some atmospheric
condensate systems to reduce or eliminate loss of
flash steam from the open receiver vent. The
condensate cooler must be sized for handling and
condensing flash steam as well as cooHng the
condensate. Condensate is normally cooled to
about 180 F. Pressure drop thru the condensate
cooler should be very low, as it must be added to trap outlet pressure. If there is a liquid leg down to the condensate receiver, the condensate cooler and trap should be located at the bottom of this leg.
When a condensate cooler is used, it is desirable to use either cold boiler feed water or other cold water source which can benefit by heat rejected from hot condensate. Cooling tower bleed water
can be used, but it may be heavy with dissolved solids and may rapidly foul the cooler. Tower makeup water can be used when large cooling towers are part of the system. Extra load to the tower would be insignificant.
Receiver and Condensate Pumps — When open receivers are used, the vent should be directed outside the equipment space to eliminate fogging.
Be careful in using small receivers and close­connected condensate pumps. Some commercially available systems may work well on standard heating systems but can present problems in handling condensate from absorption machines.
The basic difference in absorption machine oper
ation lies in higher condensate temperatures and
greater amounts of flash vapor. Commercial
Absorption machines commonly located close
condensate cooling. During full load, condensate
may be delivered to the trap at close to 12 psig and 240 F. This creates large amounts of flash steam at the trap outlet and in the condensate receiver. Very hot condensate drawn into the condensate pump may cause cavitation.
To minimize these effects, the following guides
are offered:
1. If equipped with a vented receiver, the inlet line to the receiver should enter above the receiver water level. Flash steam can go directly out the vent without creating turbulence or frothing.
2. Locate the condensate pump as far below receiver water level as possible to give maxi mum Net Positive Suction Head (NPSH) to the pump.
3. If pump suction pipe is located at bottom of the receiver, use a vortex breaker at the receiver outlet.
4. Locate pump suction at opposite end of re
ceiver from the condensate inlet. This will
minimize agitation and frothing at pump inlet.
5. A properly selected condensate cooler, as previously described, will eliminate problems with flashing.
VACUUM PUMP CONDENSATE RETURN SYSTEMS are sometimes used to return con densate from space heating installations. The vacuum pump maintains the condensate return system at a subatmospheric pressure and permits the heating system to operate with subatmospheric pressure when the heating load is small.
It is generally impractical to use an existing vacuum pump condensate return system. Con densate from the absorption machine is far higher in temperature than condensate from the original heating system for which the vacuum return pump
■; was selected. Hot condensate forms excessive quantities of flash vapor when released into the vacuum return system and will usually cause vapor lock in either the return piping or the vacuum return pump, or both. When the existing
condensate return system is a vacuum pump type, the recommended method of returning condensate from the machine is a separate wet-return system,
if possible.
As an alternate choice, condensate can be discharged thru a steam trap to an atmospheric vent receiver. The receiver discharges flash-cooled condensate thru a second trap into the vacuum-
return system.
If a condensate cooler is used, condensate may be cooled to an acceptable level and discharged
#
into the vacuum pump condensate return system. If this method is used, it is desirable to use either cold boiler feed water or any other cold water source which will benefit by heat rejected from hot condensate.
CLOSED CONDENSATE RETURN
SYSTEM
(PRESSURIZED)
16JB010-068 — Many manufacturers have high­temperature condensate units, generally suited for use with most of the Carrier absorption machine Une. Because the condensate units are usually quite high, some of the smaller machines may not be high enough to provide liquid head for gravity flow. In these cases, the closed system should not be used. A typical unit consists of a closed ASME Code receiver and centrifugal pump for returning hot condensate to the boiler. This system has the advantage of complete condensate recovery with out flash losses often experienced in atmospheric return systems.
These systems require very careful application to the absorption machine. There are two common types of closed condensate systems :
1
CLOSED CONDENSATE RECEIVER 1
1 til TO L-b^-eoa^
CLOSED CONDENSATE RECEIVER
TO lA S
NOTE' Each J5IKÌ 5s similar toOf) l&lóOliKSeS machìnes.
Fig. 4 — Closed Condensate Return System
П r~
1
-------------------------------------
(16JB077-124)

HOT WATER MACHINES

The 16JB hot water absorption machines are furnished with pneumatic controls only. Fig. 5 schematically illustrates the capacity control
valves, controls and control panel. There are two commonly used piping systems, depending on the
temperature of the supply hot water.
The first type will operate under pressurized conditions. The pressure between the generator and receiver is equalized and condensate flows by gravity to the closed receiver located below the generator outlet. It is essential that under these conditions the vacuum breaker on the 16JB generator should be blocked. This is to prevent air from building up in the closed receiver. Also, the closed receiver should be equipped with a device that is capable of releasing the air that is in the system after a shutdown period. A thermostatic vent is usually suppUed for this purpose. In this type of system, the pumps on the receiver can pump under vacuum.
The second type of closed system consists of a closed receiver with atmospheric condensate pumps. Therefore, the receiver is usually equalized with the steam chest. In this type of system, the vacuum breaker and the generator must be left open so that the receiver cannot go into the vacuum range. A steam trap is usually recommended.
16JB077-124 — Because the 16JB077-124 units have two steam inlets, these machines must be considered as having two generators when applying a closed condensate system. Each end of the machine operates at a different steam pressure. This could cause the condensate to back up into the generator and cause dangerous water hammer if the condensate system were not properly designed.
Each end of the machine should be considered similar to the system on 16JB010-068 units (see Fig. 4).
077 THRU 124 SIZES ONLY
EPS — Electric-Pneumatic Switch PE — Pressure-Electric Switch

Fig. 5 — Pneumatic Control Schematic

Piping For Water Temperature of 300 F Or Below

— Fig. 6 gives suggested hot water piping when supply hot water is 300 F or below. The capacity of the machine is controlled by regulating the flow of hot water through the generator. Either a two-way or three-way capacity control valve (CV) can be used. Machine sizes 16JB077-124 require two capacity control valves if partial load effi
ciency of double generators is to be utilized.
cw
ASR
ncfTmTSR
<5cJ«3RA70R
PlPtNS rOR MACHINE SiZES 16>® 077 THRO 124,
OR TWO St^íGt£-£^íO MACHINES fN PARAiXEL.
“Acid for 3-way vaive usaae. Pipe MC port (when 3-way valve
useO) to generator irvieris).
Fig. 6 — Suggested Piping For Hot Water Machines
Using Supply Hot Water 300 F or Below
A three-way valve is recommended to ensure a
constant system flow of hot water supply re
gardless of load. A two-way valve is suitable when
throttling of supply hot water at partial load does not adversely affect the boiler or primary circu lating pump.
Piping
Fig. 7
For Water Temperature Above 300 F —
gives suggested hot water piping when supply High-Temperature Hot Water (HTHW) is above 300 F. The three-way valve — CVl, diverts HTHW and allows cooler recirculated hot water to maintain design hot water temperature (300 F max).
Machine capacity is controlled by regulating the flow of hot water thru the generator. As machine load decreases, the chilled water controller senses the lower chilled water temperature and acts upon the three-way diverting valve(s) CV2 (CV2 + CV3) to reduce the supply of hot water to the generator. The recirculating pump, however, is actually pumping a constant gpm.
The sensor for CVl should be located, if possible, on the discharge side of the recirculating pump. The recirculating pump should be sized for design hot water at a head equal to the pressure drop through the generator and recirculating loop piping.
An alarm should be used to warn of excessive entering hot water temperatures. Excessive tem peratures could develop if control valve calibration were lost.
P(PiN<3 FOR MftCHiNE SIZES 077 THRU t24 OR TWO SiNGL£-EN0 MACHINES iNRARALLEL
Fig. 7 — Suggested Piping For Hot Water Machines
Using Supply Hot Water Above 300 F
RECIRCULATING WATER CALCULATIONS ­Assume for example purposes;
Available supply hot water temp = 400 F Design quantity of hot water needed = 243 gpm Design entering hot water temp = 300 F Design leaving hot water temp = 229 F
1. Determine the design hot water temperature drop (ATi) thru the machine.
AT 1 = ent hot water (F) — Ivg hot water (F)
- 300 F - 229 F = 71 F
2. Determine the temperature drop of 400 F water (AT2) thru the machine.
AT2 = supply hot water (F) — Ivg hot water (F)
- 400 F^ 229 F = 171 F
3. Determine the amount (gpm) of 400 F water required.
Gpm of 400 F water
gpm of 300 F water
ATI AT2
243 X-
71
171
= 101 gpm
Determine the amount (gpm) of recirculated
229 F water required to meet design quantity
of water needed: Gpm of 229 F water - gpm of 300 F water
— gpm of 400 F water = 243 - 101
- 142 gpm
VALVE SIZING — The hot water capacity control valve CV2, should be sized to handle full design flow on machine sizes 010-068. Valves CV2 and CVS on machine sizes 077-124 are each sized at
one-half design flow. The pressure drop and sizing formula used in sizing the valve(s) should be
consistent with valve manufacturer’s recommenda tions. The three-way diverting valve should be sized to handle the design supply of high-temperature
hot water (HTHW) and must be suitable for high temperature duty.
Methods Other Than Recirculation to lower supply
hot water temperature to acceptable levels (300 F max) are:
1. A water-to-water heat exchanger
2. A hot water-to-steam converter
Rupture Disc — All 16JB hot water machines are
provided with a rupture disc on the generator shell for safety reasons. A generator tube failure could subject the shell to hot water supply working pressure.
RELIEF PIPING — Some apphcations have relief piping installed from the rupture disc discharge to a location where high-temperature steam and lithium bromide will not cause damage or injury.
Relief piping must include access to the rupture disc, allowing replacement in case of failure. Piping must be supported independent of the machine.
Hot Water Inlet Pressure — It is necessary to ensure
that generator hot water pressure is higher than
saturation pressure corresponding to the inlet hot
water temperature.
Minimum pressures are approximately equal to
10 psi plus the saturation pressure corresponding
to inlet water temperature. Using a recommended
minimum pressure will ensure that hot water inlet pressure drops will not cause the pressure in the lines to drop below saturation pressure. This could cause flashing and water hammer.
3. Winter Operation — If the absorption machine is to be applied under winter operating
conditions, an indoor cooling tower sump should be provided to protect the cooling tower water from freezing.

GENERAL INFORMATION

Insulation — Machine cold surfaces, subject to
sweating and corrosion, are factory insulated. Refer to Fig. 8 and Table 2 for details.
d> 6 é
¡S3 FACTORY INSULATION
LEGEND
1 — Refrigeract Pump Housing 2 — EvaporaTor Shell 3 — Refrigerant Suction Piping

Fig. 8 — Machine Cold Surfaces

CONDENSING WATER TEMP CONTROL

If the absorption machine is to be applied under conditions where the condensing water temperature can fall below 55 F, condensing water temperature control is required. This can be accomplished by:
1. Fan Cycling — On a single-cell coohng tower, the tower fan can be shut off when the temperature of the water reaches 55 F. This allows the temperature of the tower water to warm up using the heat rejected from the machine. In order to ensure against rapid fan cycling, which can cause fan motor problems, it is recommended that the cooling tower water temperature be allowed to rise to design temperature before fan operation is resumed.
2. Multiple-Cell Tower — The temperature of a multiple-cell tower can be controlled by shutting off the number of operating cells. This creates an effect similar to shutting the fan off in a single-cell tower. The controls should be adjusted to shut off in stages to 55 F and come on again in predetermined stages.
Table 2 — Insulation For Cold Surfaces
EVAP
UNIT
SHELL
16JB
TTlff“
012 014
018 021
024 028
032 036 041
047
“054~
057 061
068
w
084 097
107 115
124
^Quantity of insulation specified is adequate to cover cooler water
boxes and covers on both ends of machine
REFRIG PUMP(S)
(ft2)
75 3 6 10 ft
96 3 6 11 ft 12
114
147
177
188
216
275 8 16
328
360 8
(ft 2)
REFRIG
Suction
(ft2)
3 6 12 ft 15
3
4 6 12 ft
4 9 15 ft 21
4 10
8 17 60 ft
LINES
2 in.
Disch
6 12 ft 17
13 ft
48 ft 21
19
60 ft
COOLER WATER BOXES AND COVERS*
(ft2)
9
20
24
24
27
The generator shell and some of the machine
piping will become hot during operation. If insula tion is to be used as a safety precaution, or to reduce ambient temperature in the machine room,
we recommend insulating the surfaces shown in
Fig. 9. Hot-surface dimensions are given in Table 3.
Generator insulation can be either blanket-type
or low-pressure boiler insulation. Insulation used
for piping is generally standard low-pressure steam
pipe insulation.
Table 3 — Insulation For Hot Surfaces*
GENt
UNIT
SHELL
16JB
010 012 014
018 021
024 028
032 036
041 047
054 057
061 068
077 084
097
107 115
124
•Refer to Fig. 10 for location of hot surfaces. fl nciudes outiet box and ends
EXCH
(ft 2)
(ft 2)
62
67 45
72
77 55
82
98
98 60
152
184 no 18 4
184
GEN —Generator
HT EXCH — Heat Exchanger
STRONG
HT
SOL LINE
Lgth
Size
(in.)
(ft)
40 7 3 20
7 3 21 2 12
50 8
60
55 8 4
102
1 18
4 22
9 4
10 4
10 4
16 4 44 2 3 4
20 4 49
WEAK
SOL LINE
Lgth
Size (in.)
(ft)
V/2
2
23
2'/2
24
3 16 4
22 3 10 4
24 3
3
47
3
GEN
OVERFLOW
(GO) TUBE
Lgth
(ft)
1 1
13 4
15 4
12
4
4
Size (in.)
3
4
4
4
4
HOT SURFACES THAT CAN BE INSULATED
LEGEND
1 — Generator Shell (refer to Table 4 for sq ft surface area) 2 — Steam Supply Line 3 — Condensate Line 4 — Weak Solution Line (to generator) 5 — Strong Solution Line (from generator)
6 — Generator Overfiow Tube (only hot during abnormal
conditions)
7 — Heat Exchanger

Fig. 9 — Machine Hot Surfaces

isolation — 16JB machines are not in themselves a
major source of vibration ; and isolation equipment is not supplied with the machine unless requested on the order. It is possible, however, for a machine to receive and transmit vibrations from
other sources that are imperfectly isolated such as condensing water pumps, chilled water pumps, or other piping. Isolation packages are available from a number of manufacturers. Specifications for Carrier machines are given in Table 4.
Table 4 — Isolation Pad and Soleplate
Specifications
UNIT
16JB
010 012 014
018
021
024 028
032
036
041
047 054
057
061
068 077
084 097
107 115
124
NOTE: Higher isolation efficiencies may be obtained with double-layer pads. Double-layer pads, factory-fused together, are available from various manufacturers. If two single-layer pads are used, a metal divider equal to pad dimensions should be inserted between iayers.
NO. (EACH)
OF PADS AND SOLEPLATES
4 9 X 6 X %
4 9 X 10 X %
4
4
4
4
4
6
6
6
PAD
DIMENSIONS
(in.)
9 X 12 X Vs
9 X 14 X %
9 X 18 X %
12 X 18 X Vs
14 X 18 X %
12 X 18 X %
15 X 18 X Vs
16 X 18 X % 17 X 19 X
SOLEPLATE DIMENSIONS
(in.)
10 X 7 X V2
10 X 11 X V2
10
X 13 X %
10 X 1 5 X
10 X 19 X %
13 X 19 X %
15 X 19 X h
13 X 19 X %
16 X 19 X %
(4
‘/ 2
The integral shipping skids, or base rails, are normally left on the machine. However, the base rails may be removed, if desired, but not until the
machine is in final position. When isolation pads are used, they should be located under the corners of the machine, atop soleplates with 1/2-in. min imum thickness (see Fig. 10). The soleplate ensures
machine contact on the floor only at the corners when base rails are left on. Shims may be inserted under the soleplates for leveling the machine. Grouting is optional.
Outdoor Installation — Outdoor installation of the
16JB absorption machine creates a number of special problems which must be resolved. Such applications should be considered only when the customer has qualified operating personnel,
familiar with the maintenance of mechanical equip ment located outdoors. Standard machines require protection from weather. A simple, heated structure is preferred. If this is not possible, protection from the weather must be provided by machine modifications.
WEATHERPROOFING -- Pneumatic control sys tems are recommended for outdoor installations.
No. 4 Waterproofing Specifications.
FREEZE PROTECTION — When the machine area may be subjected to temperatures below 40 F and if the machine is to be shut down for an extended time during these low-temperature periods, all water circuits and tube bundles should be drained, then filled with ethylene glycol. Table 5 lists storage volumes of 16JB header and tube bundles.
This data can be used when calculating the
quantity of ethylene glycol needed to provide adequate freeze protection.
Fig. 10 — Typical isolation Assembly
Explosionproof Machines — 16JB standard absorp
tion machines can be factory equipped with explosionproof electric motors and controls suitable for Class 1, Group D hazardous locations
specified by the National Electrical Code. Modi
fications to the standard control system are
described in the controls application publications.
Table 5 Header and Tube Bundle Storage
Volumes (gal.)
UNIT
EVAPORATOR ABSORBER CONDENSER
16JB
010 012 014
018 021
024 028
032 036
041 047
054 057
061 068
077 ^ 084
097
107 115
124
GEN — Generator
106 108
129 179 68
158
198 271
228
25 27 28 30 35 17 17
43 46 48 51
57 64 69
76 83
96
30 16 16
62
83 90
104 117 59
150 57 74
215 129
310 186 150
14
24 26
32 36
42 46 43
52 49
163 138
HOT
WATER
GEN
14
23 25
30 34
39
56
87
106
Tube Removal — Clearance for tube removal
should be considered when planning a piping system. The 16JB machines are designed so all
tubes are accessible for cleaning or servicing should
the need arise. Refer to Fig. 11 for tube pulling
clearance dimensions and data. Evaporator,
absorber and condenser tubes may be pulled from
either end.
UNIT
16J8
010,0i2.0U
0t8,02t 024,028 032,036 041,047
i 16-lOli i 1 17- Oii i 16-U’4
£’.7- 2\ 054,057 r 6- 3% 061,068
i 21- Sy, ; 7- 3ii 077,084 i 32- 2 i 6- 314 097,107
} 32- 2
115,124 ; 2 /—SO /<
'Weights given are for each cover. NOTE: Minimym space for tube removai !Din>er;sion O) may be tocated on either end.
CLEARANCE DIMENSIONS (ft
A 8 c
: 3-
7- sy. ; 14-2 \ 4- 4Vi 7- 914 ; 5- Oti i 6- 3
s 6- n
8- 9y ' 14-2
10- H4 ; 14-2
;i- 6‘/*
■•-10 13- 214 1:- 4
> 7— 1 ^
12-tOy 13- 9y
Certified dimension drawings are available on request.

Fig. 11 — Tube Pulling Clearance Data

— in.)
i D
E
4- S
; 14-2
.5- 1 5-10 ; 4- 0 < 88 6-10 ; 5- 0
: 14-2 8- 6 ; 5- 3
i 19-3
: 19-3 : 29-1
8- 7 i 5- 0 9- 3 8- .5
i 29-1 9" 5 j 6— 6 193
• 29—^ 9- 9
COVER PLATE WEIGHTS* (lb)
F ; 2- 8 i 3- 6
Comlertser(G)
45 50
; Absorber(H) Evaporator{J)
: 100 ;
177 ; 177 275 ; 275
87
t
>
>
!07
169 i 318 ;
; 5-11 ¡69
; 325 : i 460 ;
; 389 i
i 5— 0 153 1 310 i
“T ssT" r
I 6- G
•93
1 438 t
'•■DO
32.5 460 384
471
384 471
566
10
Manufacturer reserves the right to change any product specifications without notice.
CARRIER AIR CONDITIONING COMPANY • SYRACUSE, NEW YORK
Tab 15
Form 16JB-2XA New
Printed in U.S.A. 6-71 Codes MA and ML Catalog No. 511-602
Loading...