Carrier 40MKCF, 24AHA4, 124ANS, 40MKQF, 25HHA4 Service Manual

...
40MKCF / 24AHA4 / 124ANS 40MKQF / 25HHA4 / 224ANS Under Ceiling/Floor Cons ole D uctless System Sizes 18 to 54
Service Manual
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS 1.........................
MODEL / SERIAL NUMBER NOMENCLATURES 2........
STANDARD FEATURES AND ACCESSORIES 3...........
DIMENSIONS 6--7...................................
ELECTRICAL DATA 9................................
POWER AND CONNECTING CABLES 10................
CONNECTION DIAGRAMS 11.........................
WIRING DIAGRAMS 12...............................
REFRIGERATION CYCLE DIAGRAMS 16................
REFRIGERANT LINES 17.............................
SYSTEM EVACUATION AND CHARGING 17.............
SEQUENCE OF OPERATION 18........................
TROUBLESHOOTING 19..............................
DISSASSEMBLY 26..................................
APPENDIX 30.......................................
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air--conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install, start--up, and service this equipment.
Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment.
Read this manual thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety information. This is the safety--alert
!
!
symbol instructions or manuals, be alert to the potential for personal injury. Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage.
. When you see this symbol on the unit and in
NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not bury more than 36 in (914 mm) of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in (152 mm) vertical rise to the valve connections on the outdoor units. If more than the recommended length is buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at start--up.
WARNING
!
WARNING
EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal injury, and/or property damage.
Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion.
CAUTION
INTRODUCTION
This service manual provides the necessary information to service, repair, and maintain the MK family of air conditioners and heat pumps. Section 2 of this manual is an appendix with data required to perform troubleshooting. Use the Table of Contents to locate a desired topic.
MODEL / SERIAL NUMBER NOMENCLATURES
INDOOR UNIT
--- ---
40= FAN COIL UNIT
40 MK 318
BCF
MK =MODEL
SYSTEM TYPE C = COOLING ONLY Q=HEATPUMP
MAXIMUM NUMBER OF FAN COIL UNITS THAT CAN BE CONNECTED TO THE OUTDOOR UNIT B=1:1
NOMINAL CAPACITY 18 = 1--- 1/2 TONS 24 = 2 TONS 30 = 2 -- - 1/2 TONS 34 = 2 -- - 5/6 TONS 36 = 3 TONS 48 = 4 TONS 54 = 4 1/2 TONS
01 15
VOLTAGE 3 = 208/230---1---60
NOT USED
INDOOR FAN COIL TYPE
F= UNDER CEILING --- FLOOR CONSOLE
V
00001
Week of Manufacture
Year of Manufacture
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program For verification of certification for individual products, go to www.ahridirectory.org.
Serial Number
Manufacturing Site
®
2
STANDARD FEATURES AND ACCESSORIES
Table 1—Standard Features and Accessories
Ease Of Installation
Indoor and Outdoor Compact Size S Outdoor Unit Wall Mounting Kit A Outdoor Unit Stacking Kit A Indoor Mounting Bracket S
Comfort Features
Convertible Under Ceiling -- Floor Console S
Microprocessor Controls S
Wireless Remote Control S Automatic Air Sweep S Air Direction Control S Auto Restart Function S Cold Blow Protection On Heat Pumps S
Turbo Mode S Silence Mode S Follow Me S
Energy Saving Features
Sleep Mode S Stop/Start Timer S
46 °F Heating Mode (Heating Setback) S
Safety And Reliability
3 Minute Time Delay For Compressor S Over Current Protection For Compressor S Crankcase Heater (standard on sizes 30 and 36 Heat Pump) A Indoor Coil Freeze Protection S Indoor Coil High Temperature Protection On Heat Pumps S Condenser High Temperature Protection On Heat Pumps S Accumulator On Heat Pumps S
Ease Of Service And Maintenance
Cleanable Filters S Diagnostics S Liquid Line Pressure Taps S Suction And Discharge Pressure Taps S
Application Flexibility
Low Ambient Controls (--20F) (-- 28.9C) A 3--Phase on sizes 34 & 54 (AC) and 36 & 48 (HP) S Wind Baff le s A Condensate Pumps A Wired Controls A
Legend
SStandard A Accessory
Table 2—Optional Accessories
Ordering No. Descriptions For M odels
KSACN0101AAA Wired Remote Control All Sizes
53DS--900 ---- --118 Condensate Pump (230v) All Sizes
KSALA0801AAA
KSALA0901AAA
KAACH1401AAA Crankcase Heater 24AHA4 Sizes 18 -- 36 (208/230V)
KAACH1501AAA Crankcase Heater 24AHA4 Size 36 (460V--3)
KAACH1201AAA Crankcase Heater 24AHA4 Size 48 (208/230V)
KAACH1901AAA Crankcase Heater 24AHA4/25HHA4 Size 48 (460V--3)
KAACH1601AAA Crankcase Heater 25HHA4 Size 48 (208/230V)
KAAWS0101AAA
KHAIR0201AAA
KSAHS1501AAA
53DS--900 ---- --087 Wind Baffle 24AHA4 Sizes 18 & 24
53DS--900 ---- --071 Wind Baffle
53DS--900 ---- --088 Wind Baffle 25HHA4 Size 48
53DS--900 ---- --075 Stacking Kit 24 AHA4 Sizes 18, 24
53DS--900 ---- --076 Stacking Kit 24 AHA4 Sizes 30 -- 48
53DS--900 ---- --077 Wall Mount Kit 24AHA4 Sizes 18, 24
53DS--900 ---- --078 Wall Mount Kit 24AHA4/25HHA4 Sizes 30 -- 48
KAALS0201LLS
KHALS0401LLS
Low Ambient Control (for cooling -- 20F)
Low Ambient Control (for cooling -- 20F)
Winter Start Kit (for low ambient on cooling only systems)
Isolation Relay (Required when using Low Ambient cooling with HP)
Hard Start Kit (Capacitor & Relay )
Liquid Line Solenoid for Cooling Only
Liquid Line Solenoid for Heat Pump
24AHA4/25HHA4 (208/230V)
24AHA4 (460V--3)
24AHA4 All Sizes
25HHA4 All Sizes
24AHA4/25HHA4 (208/230V--1)
24AHA4 Sizes 30 -- 48 / 25HHA4 Sizes 30 & 36
24AHA4 All Sizes -- Required for Long Line Applications
25HHA4 All Sizes -- Required for Long Line Applications
INDOOR UNIT ACCESSORIES
Condensate Pump
On ductless fan coils, the condensate pump has a lift capability of 12 ft. (3.6 m) on the discharge side with the pump mounted in the fan coil or 6 ft. (1.8 m) on the suction side if the pump is remote mounted. The pump is recommended when adequate drain line pitch cannot be provided, or when the condensate must move up to exit.
Wired Remote Controller
For applications where the use of wireless remote control is not desired, the MK units can be controlled by means of a wired wall--mounted control with an LCD display.
A07892
Fig. 1 – Condensate Pump Accessory
Fig. 2 – Wall Mounted Control with LCD Display
3
SPECIFICATIONS
Table 3—Specifications Cooling Only Under Ceiling Systems
Size 18 24 30 34 34 34 54 54 54
Outdoor Model
System
Indoor Model 40MKCB18F-- --3 40MKCB34F--- -3 40MKCB34F--- -3 40MKCB 34F----3 40MKCB 34F--- -3 40MKCB34F--- -3 40MKCB54F--- -3 40MKCB54F-- -- 3 4 0 MK C B 5 4 F -- -- 3
Energy Star NO NO NO NO NO NO NO NO NO
Cooling Rated
Performance
Operating
Refrigeran t
Compressor
* Liquid line needs to be insulated
Capacity
SEER 14 14 14 14 14 14 14 14 14
EER 12.2 12.2 12.2 12.2 12.2 12.2 11 .7 11.7 11.7
Wireless Remote Controller
(F/ C Convertible )
Controls
Wire d Remote Controller (
_F/_C Convertibl e)
Cooling Outdoor DB Min -- Max
Range
Cooling Indoor DB Min --Max
Total Piping Length Ft. 200’ 200’ 200’ 200’ 200’ 200’ 200’ 200’ 200’
Drop (OD above ID) Ft. 200’ 200’ 200’ 200’ 200’ 200’ 200’ 200’ 200’
Lift (OD below ID) Ft. 65’ 65’ 65’ 65’ 65’ 65’ 65’ 65’ 65’
Outdoor Pipe Conne ction Size -­Liquid
Outdoor Pipe
Piping
Conne ction Size -­Suction
Indoor Pipe Conne ction Size -­Liquid
Indoor Pipe Conne ction Size -­Suction
Type R-- 410A R--410A R-- 410A R--410A R-- 410A R--410A R-- 410A R--410A R--410A
Design Pressure PSIG 550 550 550 550 550 550 550 550 550
Mete ring De vice Type B Accurat or
Charge Lb. 6.4 6.5 8.6 8.9 8.9 8.9 9 9 9
Face Area Sq. Ft. 7.3 7.3 12.1 12.1 12.1 12.1 12.1 12.1 12.1
No. R ows 2 2 2 2 2 2 2 2 2
Outdoor
Coil
Fins per inch 20 20 20 20 20 20 20 20 20
Circuits 3 3 3 3 3 3 3 3 3
Face Area (sq. ft.) Sq. Ft. 2.5 4.1 4.1 4.1 4.1 4.1 4.35 4.35 4.35
No. R ows 3 3 3 3 3 3 4 4 4
Indoor
Coil
Fins per inch 19 19 19 19 19 19 19 19 19
Circuits 7 8 8 8 8 8 6 6 6
Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Model
Outdoor Volta ge, Phase, Cycle
Indoor Voltage, Phase, Cycle
Power Supply Indoor a nd outdoor uni ts have dedic ated power supply
Electrical
MCA (Outdoor) A. 11.8 14.1 18.3 18.8 12.5 7.6 24.3 18.3 8.4
MOCP - - F use Rating (Outdoor)
MCA (Indoor) A. 3 3 3 3 3 3 3 3 3
MOCP - - F use Rating (Indoor)
Unit Width In. 36.9 36.9 44.5 44.5 44.5 44.5 44.5 44.5 44.5
Unit Height In. 31.1 31.1 37.1 37.1 37.1 37.1 37.1 37.1 37.1
Outdoor
Unit Depth In. 14.6 14.6 17.1 17.1 17.1 17.1 17.1 17.1 17.1
Net Weight Lbs. 146 148 183 184 184 184 213 213 213
Airflow CFM 1,285 1,285 1,900 2,615 2,615 2,615 2,615 2,615 2,615
Unit Width In. 42.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0 65.0
Unit Height In. 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3 9.3
Unit Depth In. 26.6 26.6 26.6 26.6 26.6 26.6 26.6 26.6 26.6
Net Weight Lbs. 59.7 91.9 91.9 91.9 91.9 91.9 98.8 98.8 98.8
Number of Fan Speeds 3 3 3 3 3 3 3 3 3
Indoor
Airflow (lowest to highest )
Sound Pressure (lowest to hi ghest)
Air throw Data Ft. 26 29 29 29 29 29 29 29 29
** Refer to Ductless Split System Long Line Guide for additional information. Long Line accessories required beyond 80 ft. (24.4 m).
24AHA418A003
124ANS018000
Btu/h 17,100 24,000 28,600 33,200 33,200 33,200 53,000 53,000 53,000
Standard Standard Standard Standard Standard Standard Standard Sta ndard Standard
Optional Optional Optional Optional Optional Optional Optional Optional O ptiona l
24AHA424A003
124ANS024000
24AHA430A003
124ANS030000
24AHA436A003
124ANS036000
_F 55~125 ( -- 20_F w / L ow--Ambient Kit)
64~90 64~90 64~90 64~90 64~90 64~90 64~90 64~90 64~90
_F
In. 3/8” 3/ 8” 3/8” 3/8” 3/8” 3/8” 3/8” 3/8” 3/8”
In. 5/8” 3/ 4” 3/4” 7/8” 7/8” 7/8” 7/8” 7/8” 7/8”
In. 3/8” 3/ 8” 3/8” 3/8” 3/8” 3/8” 3/8” 3/8” 3/8”
In. 5/8” 3/ 4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4” 3/4”
ZP16K6E-- PFV-- 130 ZP20K6E--PFV--130 ZP25K5E--PFV--130 ZP29K5E-- PFV-- 130 ZP29K5E-- TF5--130 ZP29K5E--TFD- -130 ZP40K6E--PFV--130 ZP40K6E--TF5--130 ZP40K6E--TFD-- 130
V/Ph/
208/230-- 1--60 208/230--1 -- 60 208/230-- 1--60 208/230--1 -- 60 208/230-- 3-- 60 460--3--60 208/230--1-- 60 208/230--3--60 460--3--60
Hz
V/Ph/
208/230-- 1--60 208/230--1 -- 60 208/230-- 1--60 208/230--1 -- 60 208/230-- 1-- 60 208/230-- 1--60 208/230-- 1-- 60 208/ 230--1--60 208/230--1--60
Hz
A. 20 25 30 30 20 15 40 30 15
A. 15 15 15 15 15 15 15 15 15
CFM 405/515/695 975/1335/1130 975/1335/1 130 975/1335/1 130 975/1335/1 130 975/1335/1 130 1310/1400/1470 1310/1400/1470 1310/1400/1470
dB(A) 42/ 48/53 50/52/55 50/52/55 50/52/55 50/52/55 50/52/55 55/57/59 55/57/59 55/57/59
CoolingOnlyOnly
24AHA436A005
124APS036000
24AHA436A006
124AES036000
24AHA448A003
124ANS048000
24AHA448A005
124APS048000
24AHA448A006
124AES048000
4
SPECIFICATIONS (CONT)
Table 4—Specifications Heat Pump Under Ceiling Systems
System
Performance
Controls
Operating
Range
Piping
Refrigerant
Outdoor
Coil
Indoor
Coil
Compressor
Electrical
Outdoor
Indoor
Size 30 36 36 36 48 48 48
Outdoor Model Indoor Model 40MKQB36F--3 40MKQB36F--3 40MKQB36F--3 40MKQB36F--3 40MKQB48F--3 40MKQB48F--3 40MKQB48F--3
Energy Star NO NO NO NO NO NO NO Cooling Rated
Capacity SEER 14 14 14 14 14 14 14 EER 11.5 11 11 11 11.7 11.7 11.7 Heating Rated
Capacity HSPF 8.2 8.2 8.2 8.2 8.2 8.2 8.2 COP W/W 4.1 4.1 4.1 4.1 3.8 3.8 3.8 Wireless Remote Controller
(°F/°C Conv ertible) Wired RemoteController (°F/°C
Convertible) Cooling OutdoorDB
Min -Max Heating OutdoorDB
Min -Max Cooling IndoorDB
Min -Max Heating IndoorDB
Min -Max Total Piping Length Ft. 200' 200' 200' 200' 200' 200' 200' Drop (OD above ID) Ft. 200' 200' 200' 200' 200' 200' 200' Lift (ODbelow ID) Ft. 65' 65' 65' 65' 65' 65' 65' Outdoor Pipe
Connection Size ­Liquid
Outdoor Pipe Connection Size ­Suction
Indoor Pipe Connection Size ­Liquid
Indoor Pipe Connection Size ­Suction
Type R-410A R-410A R-410A R-410A R-410A R-410A R-410A DesignPressure PSIG 550 550 550 550 550 550 550 MeteringDevice Type B Accurator Charge Lb. 12.1 12.3 12.3 12.3 10.95 10.95 10.95 Face Area Sq. Ft. 12.1 12.1 12.1 12.1 14.1 14.1 14.1 No. Rows 2 2 2 2 2 2 2 Fins perinch 20 20 20 20 20 20 20 Circuits 6 5 5 5 6 6 6 Face Area(sq. ft.) Sq. Ft. 4.4 4.4 4.4 4.4 4.4 4.4 4.4 No. Rows 4 4 4 4 4 4 4 Fins perinch 19 19 19 19 19 19 19 Circuits 6 6 6 6 6 6 6 Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Model ZP24K5E-PFV-130 ZP29K5E-PFV-130 ZP29K5E-TF5-130 ZP29K5E-TFD-130 ZP42K5E-PFV-130 ZP42K5E-TF5-130 ZP42K5E-TFD-130 Outdoor Voltage,
Phase, Cycle Indoor Voltage,
Phase, Cycle Power Supply Indoor andoutdoor units havededicated power supply MCA (Outdoor) A. 17.2 19 12.8 7.6 28.8 18.6 8.6 MOCP -Fuse Rating
(Outdoor) MCA (Indoor) A. 3 3 3 3 3 3 3 MOCP -Fuse Rating
(Indoor) Unit Width In. 44.5 44.5 44.5 44.5 44.5 44.5 44.5 Unit Height In. 37.1 37.1 37.1 37.1 43.1 43.1 43.1 Unit Depth In. 17.1 17.1 17.1 17.1 17.1 17.1 17.1 Net Weight Lbs. 196 197 197 197 246 246 246 Airflow CFM 2,615 2,615 2,615 2,615 2,785 2,785 2,785 Unit Width In. 65.0 65.0 65.0 65.0 65.0 65.0 65.0 Unit Height In. 9.3 9.3 9.3 9.3 9.3 9.3 9.3 Unit Depth In. 26.6 26.6 26.6 26.6 26.6 26.6 26.6 Net Weight Lbs. 98.8 98.8 98.8 98.8 98.8 98.8 98.8 No. ofFan Speeds 3 3 3 3 3 3 3 Airflow(lowest to
highest) Sound Pressure
(lowest tohighest) Air throwData Ft. 29 29 29 29 29 29 29
V/Ph/Hz 208/230-1-60 208/230-1-60 208/230-3-60 460-3-60 208/230-1-60 208/230-3-60 460-3-60
V/Ph/Hz 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
25HHA430A003 224ANS030000
Btu/h 29,000 34,200 34,200 34,200 46,400 46,400 46,400
Btu/h 29,000 34,200 34,200 34,200 46,400 46,400 46,400
Standard Standard Standard Standard Standard Standard Standard
Optional Optional Optional Optional Optional Optional Optional
°F 55~125 (-20°F w / Low-AmbientKit)
°F 17~ 75 17~75 17~75 17~75 17~75 17~75 17~75
°F 64~ 90 64~90 64~90 64~90 64~90 64~90 64~90
°F 32~ 80 32~80 32~80 32~80 32~80 32~80 32~80
In. 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8"
In. 3/4" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8"
In. 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8"
In. 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4"
A. 30 30 20 15 50 30 15
A. 15 15 15 15 15 15 15
CFM 1310/1400/1470 1310/1400/1470 1310/1400/1470 1310/1400/1470 1310/1400/1470 1310/1400/1470 1310/1400/1470
dB(A) 55/57/59 55/57/59 55/57/59 55/57/59 55/57/59 55/57/59 55/57/59
25HHA436A003 224ANS036000
25HHA436A005 224APS036000
HEAT PUMP
25HHA436A006 224AES036000
25HHA448A003 224ANS048000
25HHA448A005 224APS048000
25HHA448A006 224AES048000
* Liquid line needs to be insulated
** Refer to Ductless Split System Long Line Guide for additional information. Long Line accessories required beyond 80 ft. (24.4 m).
5
DIMENSIONS -- INDOOR
Unit:
H
D
W
Bracket:
W
Hook
D
Fig. 3 – 40MKCB**F, 40MKQB**F Unit and Bracket Dimensions
Table 5—Dimensions Indoor
Indoor UnitSize
BTU/Hr
AC
18K 9.3 (235) 42.0 (1068) 26.6 (675) 59.7 (27.1)
24K - 34K 9.3 (235) 65.0 (1650) 26.6 (675) 91.9 (41.7)
54K 9.3 (235) 65.0 (1650) 26.6 (675) 98.8 (44.8)
HP
30K - 48K 9.3 (235) 65.0 (1650) 26.6 (675) 98.8 (44.8)
Bracket
18K AC - 38.7 (983) 8.7 (220) -
24K - 54KAC/HP - 61.6 (1565) 8.7 (220) -
Height (H)
in (mm)
Width (W)
in (mm)
Depth (D)
in (mm)
Operating Weight
lb (kg)
A0150266
6
DIMENSIONS -- OUTDOOR
Fig. 4 – Outdoor Unit Dimensions
Table 6—Dimensions Indoor
Dimensions in (mm)
UNIT A B C D E F G H J K L M N P
31.1
36.9
Cooling
Only
Heat
Pump
24AHA418
24AHA424
24AHA430
24AHA436
24AHA448
25HHA430
25HHA436
25HHA448
(791)
31.1
(791)
37.1
(943)
37.1
(943)
37.1
(943)
37.1
(943)
37.1
(943)
43.1
(1095)
(938)
36.9
(938)
44.5
(1130)
44.5
(1130)
44.5
(1130)
44.5
(1130)
44.5
(1130)
44.5
(1130)
14.6
(370)16(406)
14.6
(370)16(406)
17.1
(433)
17.1
(433)
17.1
(433)
17.1
(433)
17.1
(433)
17.1
(433)
18.4
(468)
18.4
(468)
18.4
(468)
18.4
(468)
18.4
(468)
18.4
(468)
23.4
(595)
23.4
(595)
30.5
(775)
30.5
(775)
30.5
(775)
30.5
(775)
30.5
(775)
30.5
(775)
17.2
(437)
17.2
(437)
19.6
(498)
19.6
(498)
19.6
(498)
19.6
(498)
19.6
(498)
19.6
(498)
23.1
(587)
23.1
(587)
29.1
(740)
29.1
(740)
29.1
(740)
29.1
(740)
29.1
(740)
35.1
(892)
NOTE: Dimensions shown in feet--inches. Dimensions in ( ) are millimeters.
28.1
(713)13(330)
28.1
(713)14(356)
34.1
13.7
(865)
(348)
34.1
13.7
(865)
(348)
34.1
14.5
(865)
(368)
34.1
13.7
(865)
(348)
34.1
13.7
(865)
(348)
40.1
14.5
(1018)
(368)
6.6
(168)
6.8
(171)
8.1
(206)
8.1
(206)
8.5
(216)
8.1
(206)
8.1
(206)
8.5
(216)
11.3
(286)
11.6
(295)
15.9
(403)
15.9
(403)
18.9
(479)
15.9
(403)
15.9
(403)
18.9
(479)
0.6
(16)
0.8
(19)
0.8
(19)
0.9
(22)
0.9
(22)
0.8
(19)
0.9
(22)
0.9
(22)
2.9
(73)
2.9
(73)
3.4
(86)
3.4
(86)
3.4
(86)
3.4
(86)
3.4
(86)
3.4
(86)
5.8
(148)
5.8
(148)
6.4
(162)
6.4
(162)
6.4
(162)
5.5
(140)
5.5
(140)
5.5
(140)
OPERATING
WEIGHT Ibs. (kg)
146 (66)
148 (67)
183 (83)
184 (83)
213 (97)
196 (89)
197 (89)
246
(112)
7
CLEARANCES -- INDOOR
≥35mm
≥ 35mm
CLEARANCES -- OUTDOOR
D
≥ 35mm
Fig. 5 – 40MKCB**F, 40MKQB**F Unit Clearance
A
B
C
Air-inlet
≥1000mm
A0150267
Air-outlet
E
Fig. 6 – Outdoor Unit Clearance
Table 7—Outdoor Clearances
UNIT Coil Facing Wall -- in. (mm) Fan Facing Wall -- in. (mm)
A 24 (610) 24 (610) B 24 (610) 24 (610)
C 20 (508) 6 (152) D 6 (152) 8 (203)
E 6 (152) 20 (508)
A08436
8
ELECTRICAL DATA
Table 8—24AHA4/124ANS Electrical Data
UNIT SIZE -- --
voltage,series
1 8 -- -- 3 0 2 4 -- -- 3 0 62.9 10.9 0.5 14.1 25 3 0 -- -- 3 0 73 14.1 0.7 18.3 30 3 6 -- -- 3 0 77 14.1 1.2 18.8 30 4 8 -- -- 3 0 124 18.5 1.2 24.3 40 3 6 -- -- 5 0 4 8 -- -- 5 0 83.1 13.7 1.2 18.3 30 3 6 -- -- 6 0 4 8 -- -- 6 0 41 6.2 0.6 8.4 15
UNIT SIZE -- --
voltage,series MAX MIN LRA RLA FLA
3 0 -- -- 3 0 3 6 -- -- 3 0 77 14.2 1.2 19 30 4 8 -- -- 3 0 117 21.8 1.45 28.8 50 3 6 -- -- 5 0 4 8 -- -- 5 0 83.1 13.7 1.45 18.6 30 3 6 -- -- 6 0 4 8 -- -- 6 0 41 6.2 0.8 8.6 15
Indoor Unit Size
BTU/Hr
18K 208--230 --1--60 187 253 0.71 1 15
24K -- 34K 208 --230-- 1 --60 187 253 0.7x2 3 15
54K 208--230 --1--60 187 253 0.95 x 2 3 15
V/PH
208/230/1 253 197
208/230/3 253 197
460/3 506 414
V/PH
208/230/1 253 197
208/230/3 253 197
460/3 506 414
V--Ph--Hz
OPER VOLTS* COMPR FAN
MCA
MAX MIN LRA RLA FLA
56.3 9 0.5 11.8 20
71 9 1.2 12.5 20
38 5.6 0.6 7.6 15
Table 9—25HHA4/224ANS Electrical Data
OPER VOLTS* COMPR FAN
MCA
64 12.8 1.2 17.2 30
71 9.3 1.2 12.8 20
38 5.6 0.6 7.6 15
Table 10—40MKCB**F Electrical Data
Voltage Range Fan Power
Min (V) Max (V) FLA (A) MinCktAmp(A)
MAX FUSE**
or
CKT BRK
AMPS
MAX FUSE**
or
CKT BRK
AMPS
Max Fuse CB Amp
(A)
Table 11—40MKQB**F Electrical Data
Indoor Unit Size
BTU/Hr
30K-- 48K 208 --230--1 -- 60 187 253 0.95 x2 3 15
LEGEND FLA --- F u l l L o a d A m p s H A C R --- Heating, Air Conditioning, Refrigeration L R A --- Locke d Rotor Amps N E C --- National Electrical Co de RLA --- RatedLoadAmps(compressor)
*Permissible limits of the voltage range at which the unit will operate satisfactorily
**T i m e --- De l ay f us e.
Complies with 2007 requirements of ASHRAE Standards 90.1
V--Ph--Hz
Min (V) Max (V) FLA (A)
Voltage Range Fan Power
Min Ckt Amp
(A)
Max Fuse CB
Amp (A)
9
POWER AND CONNECTING CABLES -- FIELD SUPPLIED
Recommended Connection Method for Power and Communication Wiring (To minimize communication wiring interference)
Power
The main power is supplied to both, the indoor and the outdoor units. The field supplied connecting cable consists of three (3) wires. Two wires are high voltage AC power and one is a ground wire.
Consult your local building codes and the NEC (National Electrical Code) or CEC (Canadian Electrical Code) for special requirements.
All wires must be sized per NEC or CEC and local codes. Use Electrical Data table MCA (minimum circuit amps) and MOCP (maximum over current protection) to correctly size the wires and the disconnect fuse or breakers respectively.
Per caution note, only copper conductors with a minimum 300 volt rating and 2/64--inch thick insulation must be used.
Communication Wiring:
A separate shielded copper conductor only, with a minimum 300 volt rating and 2/64--inch thick insulation, must be used as the communication wire from the outdoor unit to the indoor unit. To minimize voltage drop of the communication wire, use the wire size and maximum lengths shown in Table 12.
Wiring:
Table 12—Maximum Lengths
Wire Size Length ft. (m)
18AWG 50 ft. (15 m) 16AWG 50ft. (15 m) to 100 ft. (30 m)
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
S Wires should be sized based on NEC and local codes.
S Use copper conductors only with a minimum 300 volt
rating and 2/64--inch thick insulation.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
S Be sure to comply with local codes while running wire
from indoor unit to outdoor unit.
S Every wire must be connected firmly. Loose wiring
may cause terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
S No wire should be allowed to touch refrigerant tubing,
compressor or any moving parts.
S Disconnecting means must be provided and shall be
located within sight and readily accessible from the air conditioner.
S Connecting cable with conduit shall be routed through
hole in the conduit panel.
CAUTION
CAUTION
10
CONNECTION DIAGRAMS
Fig. 7 – 40MKCB**F/24AHA4 or 124ANS Connecting Diagram
A150280
Fig. 8 – 40MKQB**F / 25HHA4 or 224ANS Connecting Diagram
NOTE:
1. Do not use a thermostat wire for any connection between indoor and outdoor units.
2. All connections bet ween the indoor and outdoor units must be as shown in Fig. 7 and 8. The connect ions are se nsitive to polarity and results in a fault code.
A150282
11
WIRING DIAGRAMS
1
ON
1
ON
FACTO RY SETTING
Mode
CEILING
FLOOR
FACTO RY SETTING
2
C
Y
Notes:
1.T o be wire d in acc ordance with Na tional E lectric N.E .C . and lo cal c odes.
2.U se C opper conductors only. Use c onductors s uitable for a t least 7 5°C (1 67°F ).
3. If a ny of the o riginal wires, a s supplied must be replace d, use the s ame o r equiva lent wire.
Fig. 9 – 40MKCB**F Wiring Diagram
Le gend:
................Model specic fea ture
C AP : C apac itor
Live wire L 1/Null line L2
C N 1: CN 2/3: Transformer C N 25: C ontrols signal interface( C) C N 7: S enso r C N 20: N etwork module interface C N 12: V ertical s wing motor inter face C N 13: horiz ontal s wing motor i nterface C N 10: D isplay board in terface C N 15: C ompres sor signal in terface C N 11: Water level d etection sw itch C N 16: Motor i nterface R T1: R oom tempe rature s enso r R T2: P ipe tempera ture s ensor T3/4 :Tra ns former G M1/3: L evel s wing motor G M 2: V ertical s wing motor XS/XP : Connectors
24V
interfac e
interface
FAN2
WHITE
WHITE
CAP2
OUTDOOR UNIT SCHEMATIC DIAGRAM
Fig. 10 – 24AHA4/124ANS Wiring Diagram 208/230V 1 Phase
C
12
Fig. 11 – 24AHA4/124ANS Wiring Diagram 208/230 -- 460V 3 Phase
1
ON
1
ON
FACTO RY SETTING
MODE
FLOOR
Legen d:
................Model spec ic fe ature
CAP: Capac itor CN 1:
Live w ire L1 /Null line L2 CN 2/ 3: Tr ansfor mer CN 25 :Contr ols signal interface(R /C) CN 7: Sens or CN 20 : Netw ork module interface CN 12 : Ver tical s wing motor i nterface CN 13 : horiz ontal s wing motor interfa ce CN 10 : Disp lay board in terfac e CN 15 : Sign al inte rface( Y/O) CN 1 1: Wa ter level dete ction s witch CN 16 : Moto r interface RT1: Room temp erature sens or RT2: Pipe t empe rature senso r T3/4 : Trans forme r GM1/3 : Leve l swin g motor
2
L2
L1
C
O
R
Y
GM 2: Vertical s wing motor XS/XP : Con nectors
24V
interface
interface
ON
MODE
FLOOR
FACTO RY SETTING
Notes :
1.T o be wired in acco rdanc e with National Electr ic N.E .C. a nd loc al codes.
2.Use Copp er con ductors onl y. Use c onductors s uitable for at lea st 75° C(167 °F).
3. If a ny of the original wires , as s upplied must be replace d, use the s ame o r equ ivalent wire.
Fig. 12 – 40MKQB**F Wiring Diagram
13
OUTDOOR UNIT SCHEMATIC DIAGRAM
Fig. 13 – 25HHA4/224ANS Wiring Diagram 208/230V 1 Phase
Fig. 14 – 25HHA4/224ANS Wiring Diagram 208/230V 3 Phase
14
Fig. 15 – 25HHA4/224ANS Wiring Diagram 460V 3 Phase
15
REFRIGERAT I ON CYCLE DIAGRAMS
FIELD
PIPING
FLARE CONNECTION
COOLING EXPANSION DEVICE
TINU ROODTUOTINU ROODNI
LIQUID
SERVICE VALVE
HEAT EXCHANGER (EVAPORATOR)
HEAT EXCHANGER (EVAPORATOR)
FLARE CONNECTION
FLARE CONNECTION
COOLING EXPANSION DEVICE
SERVICE VALVE W/GAUGE PORT
SUCTION LINE
FIELD
PIPING
Fig. 16 Cooling Only
FIELD
PIPING
LIQUID HTG
SERVICE VALVE
COMPRESSOR
HEATING EXPANSION DEVICE
HEAT EXCHANGER (CONDENSER)
TINU ROODTUOTINU ROODNI
LIQUID
TWO PHASE
HEAT EXCHANGER (CONDENSER)
FLARE CONNECTION
SERVICE VALVE W/ GAUGE PORT
FIELD
PIPING
Fig. 17 Heat Pumps
SUCTION
ACCUMULATOR
SUCTION DISCHARGE
COMPRESSOR
REVERSING
VALV E
COOLING HEATING
16
REFRIGERANT LINES
t
General refrigerant line sizing:
3. The outdoor units are shipped with a full charge of R410A refrigerant. All charges, line sizing, and capacities are based on runs of 25 ft. (7.6 m). For runs over 25 ft. (7.6 m), refer to the Residential Long Line Guide.
4. Minimum refrigerant line length between the indoor and outdoor units is 10 ft. (3 m).
5. Refrigera nt lines should not be buried in the ground. If it is necessary to bury the lines, not more than 36--in (914 mm) should be buried. Provide a minimum 6--in (152 mm) vert ical rise to the service valve s to preve nt re frige r ant migrat ion.
6. Both lines must be insulated. Use a minimum of 1/2--in (12.7 mm) thick insulation. Closed--cell insulation is recommended in all long--line applications.
7. Special consideration should be give n to isolating interconnecting tubing from the building structure. Isolate the tubing so that vibration or noise does not transmit into the structure.
IMPORTANT: Both refrigerant lines must be insulated
separately.
S The following maximum lengths are allowed:
Table 13 – Maximum Refrigerant Line Lengths
Unit Size
18K--56K 250 (76.2) 65 (19.8) 200 (61)
Note: For lengths greater than 25 ft. (7.6 m), refer to the Residential
Long Line Guide.
*Maximum actual length not to exceed 200 ft. (61 m). Total equivalent
length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
Max Line
Length* ft(m)
S The following are the piping sizes.
Indoor Units Outdoor Units
40MKCB18F----3
40MKCB34F----3
40MKCB34F----3
40MKCB34F----3
40MKCB54F----3
40MKQB36F----3
40MKQB36F----3
40MKQB48F----3
Note: Both lines need to be insulated using at least 1/2 inch closed
foam insulation.
Refrigerant Charge
System
Typ e
Cooling
Only
Heat
Pump
The above additional charge is required amount for line lengths up to
25 ft. (7.6 m). For line lengths exceeding 25 ft. (7.6 m), additional charge will be required. Refer to the Residential Long Line Guide.
24AHA418 124ANS018
24AHA424 124ANS024
24AHA430 124ANS030
24AHA436 124ANS036
24AHA448 124ANS048
25HHA430224A
NS030
25HHA436 224ANS036
25HHA448 224ANS048
Table 15 – Charge Requirements
Nominal Capacity
kBTU/Hr
018 24AHA418A003 124ANS018000 40MKCB18F-- --3 12
024 24AHA424A003 124ANS024000 40MKCB34F-- --3 12
030 24AHA430A003 124ANS030000 40MKCB34F-- --3 12
034 24AHA436A003/5/6 124ANS036000 40MKCB34F----3 8
054 24AHA448A003/5/6 124ANS048000 40MKCB54F----3 12
030 25HHA430A003 224ANS030000 40MKQB36C----3 11
036 25HHA436A003/5/6 224ANS036000 40MKQB36C-- --3 14
048 25HHA448A003/5/6 224ANS048000 40MKQB48C-- --3 11
Max Elevation
(ID over OD) ft( m)
Max Elevation
(OD o ver ID) ft (m)
Table14–PipeSizes
Indoor Unit Tube
Sizes (in)
Liquid Vap o r Liquid Vap o r Liquid Vap or
3/8
OutdoorUnit Indoor Unit
TXV Kit Tube
Sizes (in)
5/8
3/4 3/4 3/4
3/4 3/4 3/4
3/4 3/4 7/8
3/8
3/4 7/8 7/8
3/4 3/4 3/4
3/4 3/4 7/8
3/4 7/8 7/8
OutdoorUnit Tube
5/8
Size (in)
3/8
Chargeto
Sub--cooling
Delta fro m
Rating Plate
Val u e
5/8
Metering Device
The 40MKC(Q)*F unit uses a TXV. The outdoor unit uses a type B accurator. The cooling metering device is installed with the indoor unit, while the heating metering device is installed with the outdoor unit. One metering device is required for the cooling only system and two are required for the heat pump systems. Refer to Table 16 for a breakdown of each unit’s metering devices.
Table 16 – Metering Device
System Size
kBTU/hr
018 TXV - ­024 TXV - ­030 TXV TXV 0.055" 034 TXV - ­054 TXV - ­036 - TXV 0.063" 048 - TXV 0.073"
Cooling Only HeatPumps
40MKCB**C 40MKQB**C 25HHA4/224ANS
SYSTEM EVACUATION AND CHARGING
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used if the procedure outlined below is followed. Always break a vacuum with dry nitrogen.
SYSTEM VACUUM AND CHARGE
Using Vacuum Pump
1. Completely tighten flare nuts A, B, C, D, connect manifold gage charge hose to a charge port of the low side service valve (see Fig. 18).
2. Connect charge hose to vacuum pump.
3. Fully open the low side of manifold gage (see Fig. 19).
4. Start the vacuum pump.
5. Evacuate using either deep vacuum or triple evacuation method.
6. After evacuation is complete, fully close the low side of manifold gage and stop operation of vacuum pump. Maintain a MICRON value of 500 MICRONS or less for 30 minutes to ensure a completely dry system.
7. The factory charge contained in the outdoor unit is good for up to 25 ft. (8 m) of line length. For refrigerant lines longer than 25 ft. (8 m), add char ge, up to the maximum allowable lengt h, as specified in the residential Long Line Applicat i on Guide.
8. Disconnect charge hose from charge connection of the low side service valve.
9. Fully open service valves B and A.
10. Securely tighten caps of service valves.
Outdoor Unit
Service Valve
CAUTION
Refrigerant
Low Side
A
High Side
B
Fig. 18 Service Valve
Indoor Uni
C
D
A07360
17
500 microns
Low side valve
Charge hose
Manifold Gage
High side valve
Charge hose
Vacuum pump
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
Low side valve
A07361
Fig. 19 Manifold
Deep Vacuum
Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water (see Fig. 20).
5000 4500 4000 3500 3000 2500 2000
MICRONS
1500 1000
500
01234567
MINUTES
LEAK IN SYSTEM
VACUUM TIGHT TOO WET
TIGHT DRY SYSTEM
A95424
Fig. 20 Deep Vacuum Graph
Triple Evacuation
Method
The triple evacuation method should only be used when vacuum pump is only capable of pumping down to 28 in. of mercury vacuum and system does not contain any liquid water. Refer to Fig. 21 and proceed as follows:
1. Pump system down to 500 MICRONS and allow pump to continue operating for an additional 15 minutes.
2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and open until system pressure is 2 psig.
4. Close service valve and allow system to stand for 1 hr. During this time, dry nitrogen will be able to diffuse throughout the system absorbing moisture.
5. Repeat this procedure as indicated in Fig. 21. System will then be free of any contaminants and water vapor.
CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS DEEP VACUUM)
RELEASE CHARGE INTO SYSTEM
A95425
Fig. 21 Triple Evacuation Method
SEQUENCE OF OPERATION
Interface
A wireless remote control, supplied with the unit, is the interface between the fan coil and the user. The wireless remote control has the following characteristics:
S Capable of displaying _Cand_F with _F being the default
setting. To change the default setting, refer to the Owner’s Manual.
S The remote control setpoint range is from 62_F(17_C) to
86_F(30_C) inch increments of 1_F(1_C).
S The wireless remote control has an operating range of 25 ft.
(7.62 m).
S The same remote control can be used to control more than one
unit.
S If the remote control is lost, damaged, or the batteries are
exhausted, the system can be operated by using the manual button (forced Auto) located on the front panel (see Fig. 22).
MANUAL
A150284
Fig. 22 Manual Button Location on Unit
18
TROUBLESHOOTING
This section provides the required flow charts to troubleshoot problems that may arise.
NOTE: Information required in the diagnoses can be found either on the wiring diagrams or in the appendix.
Required
The following tools are needed when diagnosing the units:
S Digital multimeter S Screw drivers (Phillips and straight head) S Needle--nose pliers
Recommended
Tools:
Steps
1. Refer to the diagnostic hierarchy charts below and determine the problem at hand.
2. Go to the chart listed in the diagnostic hierarchy and follow the steps in the chart for the selected problem.
For eas e of servic e, the indoor unit is equipped with diagnostic code display LEDs in the indoor unit s . This diagnosti c displa y is a combination of flashing LEDs on the display panel or the front of the unit. If possible, always check the diagnostic codes displayed on the indoor unit. Once a fai l ure occurs with the indoor unit in operation, the green LED on the indoor unit flashe s at interval s of 0.5 seconds.
The fault code is deduced from the number of times the green LED flashes, blocking unit operati on. Bet w een one fla sh cycle and the next one, a pause of 3 to 4 seconds el apses.
The diagnostic codes for the indoor units are listed in the appendix. Problems may occur that are not covered by a diagnostic code, however are covered by the diagnostic flow charts. These problems are typical air conditioning mechanical or electrical issues that can be corrected using standard air conditioning repair techniques.
INDOOR UNIT DIAGNOSTIC
CODES
Table 17 – Fault Codes
No. Malfunction Running lamp Timer lamp Defrosting lamp Alarm lamp
Open or short circuit of
1
T1 temperature sensor
Open or short circuit of
2
T2 temperature sensor
3 Indoor EEPROM
4 Water--level alarm X X X
Refrigerant leakage
5
detection
NOTE: O (on) X(off) (flash at 5Hz) (flash at 0.5Hz)
X
X X E2
X X X E3
X X E7
X X
For problems requiring measurements at the control boards please note the following:
For Heat Pump Units
Only:
1. Always disconnect the main power.
2. When possible check the outdoor board first.
3. Start by removing the outdoor unit top cover.
4. Reconnect the main power
5. Probe the outdoor board inputs and outputs with a digital multi--meter referring to the wiring diagrams.
6. Connect the red probe to hot signal and the black probe to the ground or negative.
7. Note that some of the DC voltage signals are pulse and
ForCoolingonlyandHeatPumps
1. If it is necessary to check the indoor unit board you must start by disconnecting the main power.
2. Next remove the front cover of the unit and then control box cover.
3. Carefully remove the indoor board from the control box, place it face up on a plastic surface (not metal).
4. Reconnect the main power and repeat steps 5, 6, and 7.
5. Disconnect main power before reinstalling board to avoid shock hazard and board damage.
gives continuously variable readings.
Display
(digital tube)
E8
EC
19
1. --- Open or short circuit of T1 or T2 temperature sensor --- diagnosis and solution
Check th
d
d
l
l
Error Code E1 Malfunction conditions Indoor room temperature T1 and sensor evaporator temperature sensor T2 is abnormal
Check the connecons
between temperature
sensor and PCB. Are the
sensor an
e connecons
etween temperature
PCB re the
connecons good?
onnecons goo
Yes
Measure the resistance value
easurethe resistance value
of the sensor via Appendix 1
the sensor via Appendix
Is it normal?
s it norma
Yes
Replace the indoor PCB
Rep
ace the indoor PCB
No
Correct the connecons.No
orrect the connecons
Replace the sensor.
20
2. --- EEPROM parameter error --- diagnosis and solution
Error Code E7 Malfunction conditions Indoor PCB main chip does not receive feedback from EEPROM chip.
Possible Causes
Troubleshooting:
• Installation mistake
• Defective PCB
Shut off the power supply and
turn it on 5 seconds later. Is it
still displaying the error code?
Yes
If the EEPROM chip is welded on main PCB, replace the main PCB directly. Otherwise, check
No
Correct the connection. whether the EEPROM chip is plugged into main PCB well.
Yes
Replace the main PCB.
A14480
21
3 . --- W a t e r --- l e v e l a l a r m --- d i a gn os is a n d s ol u t io n
h
ll
ll
f
h
h
mp
f
n
ill
lved
ff
e
ill displayi
de
Error Code E8 Malfunction conditions If the sampling voltage is not 5V, the LED displays the failure.
Possible Causes
• Wiring mistake
• Water--- level switch faulty
•Waterpumpfaulty
• Indoor PCB faulty
Power off, then restart the unit 2 minutes
Power o
later. Is it still displaying the error code?
aters it st
then restart the unit
ng the error co
minut
Yes
If the water-level switch
Ifthe waterevel switc
is inserted well?
nserted we
Yes
If the water-level switch
I
the waterevel switc
is broken?
roken
No
Replace the water pump, If
eplacethewater
malfunction is still not
malfunctio
solved
so
u
I
t
not
Yes
Replace the indoor main PCB
eplace the indoor main PCB
No
Yes
Insert the water-level switch well
nsert the waterevel switch we
Replace the water-level switch
eplace the waterevel switc
22
4 . --- R ef ri ge ra nt L e a k a g e D e t e c t i o n --- d i a g n os i s a n d s o l u t i o n ( EC )
Error Code EC
Define the evaporator co i l tem p.T2 of the com pres s o r just sta rt s running as Tcool . In the beginni ng 5
Malfunction decision conditions
minutes after the com pres s or st art s up, if T2 <Tcool---35.6° F(Tcool--- 2° C) does not kee p conti nuous 4 seconds and this sit uat i on happens 3 time s , the displ ay area show s “EC” and AC turns off.
S T2 Sensor faulty
Supposed Causes
S Indoor PCB faulty S System problems, such as leakage of blocking
Troubleshooting:
ADDITIONAL INFORMATION FOR CRITICAL PARTS:
Temperature sensor troubleshooting
Disconnect the temperature sensor from the PCB, and measure the resistance value with a multimeter.
Temperature sensors:
1. Room temperature (T1) sensor,
2. Indoor coil temperature (T2) sensor,
3. Outdoor coil temperature (T3) sensor,
4. Outdoor ambient temperature (T4) sensor,
5. Compressor discharge temperature (T5) sensor
Indoor Fan Motor
Measure the resistance value of each winding by using the multimeter.
23
DISASSEMBLY OF UNDER CEILING--FLOOR CONSOLE I NDOOR UNIT
NOTE: All the operations should be performed after powered off.
No. Parts name Procedures Remarks
1 Remove the
air outlet
grilles.
1) Pull the grille locker till
the screws appears, and
release these screws.
2 Remove the
side cover
2) Remove the air return
grille (watch the lockers
under the grilles).
1) After remove the filter
grille, release the screw
fixing the side cover.
2) Push the side cover
upward to remove it.
1
2
24
3 Remove the
r
f
control
PCB
1) Release 2 screws fixing
the control box, and then
take it out.
2) Screw off the 2 screws to
remove the cover of the
control box
Main PCBFan Capacitor Transformer
3) Disconnect the fan motor
wire, louver motor wire,
room temperature and
evaporator temperature
wire, and display board
wire to remove the
electronic control box
4) Disconnect all the wires
of plugs connected to the
PCB
Control wires fo
outdoor unit
Indoor fan control
Power cord terminal
Power input
Input/output o
transformer
25
5) Remove the PCB from
,
the fixing pins
Swing motor control
To Display board
Temperature
sensors T1
T2
3Remove the
fan motor
and fan
wheel
1) Remove the stickers
stick to the volute shell
2) Remove the below volute
shell
Stickers
Press the clips to take off the volute shell
Press
3) Disassemble the fan
motor fixing clamps to
remove the fan motor
assembly and fan wheel
assembly
The fan motor assembly and fan wheel assembly can be removed after took off the 2screws used to fix the fan motor fixing clamps.
26
4) Release the screws
locking the fan wheel on
the shaft, you can
remove the fan wheels.
Take off the screw
to remove the fan
wheel
4 Remove the
display
PCB
1) Release the 2 screws
(both sides) and push the
panel upwards to remove
it
2) Release 11 screws (5 at
the front and 6 at both
sides).
Release the screw
Push it upwards
3) Remove the front panel.
The display board is on
the back.
4) Release 2 screws fixing
the display PCB
27
5) Unplug the wires
5** Remove the
vertical
swing
motor
6 Remove 2
horizontal
swing
motors (on
both sides
off the unit)
1) Remove the drain pan
assembly
2) Remove the air outlet
grille assembly by
screwing of 8 screws
3) Release 2 screws fixing
the swing motor to
remove it
1) Remove the motor
protective cover
2) Screw off the 2 fixing
screws to remove swing
motor
Release the 2 screws
release 8 screws
2 screws
7 Remove the
evaporator
assembly
1) Remove the 4 screws (2
on left side and 2 on right
side) fixing the
evaporator on both sides
of the unit.
28
2) Remove the evaporator
Note: ** means there is no this part in some models.
29
APPENDIX
APPENDIX TABLE OF CONTENTS
DESCRIPTION NUMBER
Control Board Input/Output Values A1.......................................................................
Temperature Sensor Values (Temperature vs. Resistance) for T1, T2, T3, T4 A2........................................
Temperature Sensor Values (Temperature vs. Resistance) for T5 A3.................................................
Temperature Conversion A4................................................................................
A1
Table 18 – Control Board Input/Output Values
CONNECTOR CONTROL BOARD INPUT or OUTPUT VALUE
CN 1 Live wire L1/Null line L2 Input Voltage: AC 230V
CN 2 Transformer interface Input AC 230V
CN3 Transformer interface Output AC12V
CN 25 Controls 24V signal interface (R/C) Input AC 24V
CN 7 Sensor interface Output 3V DC
CN 20 Network module interface Output 5V DC
CN 12 Vertical swing motor interface Output 12V DC
CN 13 horizontal swing motor interface Output 12V DC
CN 10 Display board interface Output 12V DC
CN 15 Signal interface(Y/O) Output 24V AC
CN 11 Water level detection switch Output 5V DC
CN 16 Motor interface Voltage: AC 230V
A2
_C _F KOhm _C _F KOhm _C _F KOhm _C _F KOhm
-- 2 0 -- 4 115.266 20 68 12.6431 60 140 2.35774 100 212 0.62973
-- 1 9 -- 2 108.146 21 70 12.0561 61 142 2.27249 101 214 0.61148
-- 1 8 0 101.517 22 72 11.5 62 144 2.19073 102 216 0.59386
-- 1 7 1 96.3423 23 73 10.9731 63 145 2.11241 103 217 0.57683
-- 1 6 3 89.5865 24 75 10.4736 64 147 2.03732 104 219 0.56038
-- 1 5 5 84.219 25 77 10 65 149 1.96532 105 221 0.54448
-- 1 4 7 79.311 26 79 9.55074 66 151 1.89627 106 223 0.52912
-- 1 3 9 74.536 27 81 9.12445 67 153 1.83003 107 225 0.51426
-- 1 2 10 70.1698 28 82 8.71983 68 154 1.76647 108 226 0.49989
-- 1 1 12 66.0898 29 84 8.33566 69 156 1.70547 109 228 0.486
-- 1 0 14 62.2756 30 86 7.97078 70 158 1.64691 11 0 230 0.47256
-- 9 16 58.7079 31 88 7.62411 71 160 1.59068 111 232 0.45957
-- 8 18 56.3694 32 90 7.29464 72 162 1.53668 112 234 0.44699
-- 7 19 52.2438 33 91 6.98142 73 163 1.48481 113 235 0.43482
-- 6 21 49.3161 34 93 6.68355 74 165 1.43498 114 237 0.42304
-- 5 23 46.5725 35 95 6.40021 75 167 1.38703 115 239 0.41164
-- 4 25 44 36 97 6.13059 76 169 1.34105 116 241 0.4006
-- 3 27 41.5878 37 99 5.87359 77 171 1.29078 117 243 0.38991
-- 2 28 39.8239 38 100 5.62961 78 172 1.25423 118 244 0.37956
-- 1 30 37.1988 39 102 5.39689 79 174 1.2133 119 246 0.36954 0 32 35.2024 40 104 5.17519 80 176 1.17393 120 248 0.35982 1 34 33.3269 41 106 4.96392 81 178 1.13604 121 250 0.35042 2 36 31.5635 42 108 4.76253 82 180 1.09958 122 252 0.3413 3 37 29.9058 43 109 4.5705 83 181 1.06448 123 253 0.33246 4 39 28.3459 44 111 4.38736 84 183 1.03069 124 255 0.3239 5 41 26.8778 45 113 4.21263 85 185 0.99815 125 257 0.31559 6 43 25.4954 46 115 4.04589 86 187 0.96681 126 259 0.30754 7 45 24.1932 47 117 3.88673 87 189 0.93662 127 261 0.29974 8 46 22.5662 48 118 3.73476 88 190 0.90753 128 262 0.29216 9 48 21.8094 49 120 3.58962 89 192 0.8795 129 264 0.28482
10 50 20.7184 50 122 3.45097 90 194 0.85248 130 266 0.2777 11 52 19.6891 51 124 3.31847 91 196 0.82643 131 268 0.27078 12 54 18.7177 52 126 3.19183 92 198 0.80132 132 270 0.26408 13 55 17.8005 53 127 3.07075 93 199 0.77709 133 271 0.25757 14 57 16.9341 54 129 2.95896 94 201 0.75373 134 273 0.25125 15 59 16.1156 55 131 2.84421 95 203 0.73119 135 275 0.24512 16 61 15.3418 56 133 2.73823 96 205 0.70944 136 277 0.23916 17 63 14.6181 57 135 2.63682 97 207 0.68844 137 279 0.23338 18 64 13.918 58 136 2.53973 98 208 0.66818 138 280 0.22776 19 66 13.2631 59 138 2.44677 99 210 0.64862 139 282 0.22231
Table 19 – Temperature Sensor Resistance Value Table for T1, T2, T3, T4
30
A3
_C _F KOhm _C _F KOhm _C _F KOhm _C _F KOhm
-- 2 0 -- 4 542.7 20 68 68.66 60 140 13.59 100 212 3.702
-- 1 9 -- 2 511.9 21 70 65.62 61 142 13.11 101 214 3.595
-- 1 8 0 483 22 72 62.73 62 144 12.65 102 216 3.492
-- 1 7 1 455.9 23 73 59.98 63 145 12.21 103 217 3.392
-- 1 6 3 430.5 24 75 57.37 64 147 11.79 104 219 3.296
-- 1 5 5 406.7 25 77 54.89 65 149 11.38 105 221 3.203
-- 1 4 7 384.3 26 79 52.53 66 151 10.99 106 223 3.113
-- 1 3 9 363.3 27 81 50.28 67 153 10.61 107 225 3.025
-- 1 2 10 343.6 28 82 48.14 68 154 10.25 108 226 2.941
-- 1 1 12 325.1 29 84 46.11 69 156 9.902 109 228 2.86
-- 1 0 14 307.7 30 86 44.17 70 158 9.569 11 0 230 2.781
-- 9 16 291.3 31 88 42.33 71 160 9.248 111 232 2.704
-- 8 18 275.9 32 90 40.57 72 162 8.94 112 234 2.63
-- 7 19 261.4 33 91 38.89 73 163 8.643 113 235 2.559
-- 6 21 247.8 34 93 37.3 74 165 8.358 114 237 2.489
-- 5 23 234.9 35 95 35.78 75 167 8.084 115 239 2.422
-- 4 25 222.8 36 97 34.32 76 169 7.82 116 241 2.357
-- 3 27 211.4 37 99 32.94 77 171 7.566 117 243 2.294
-- 2 28 200.7 38 100 31.62 78 172 7.321 118 244 2.233
-- 1 30 190.5 39 102 30.36 79 174 7.086 119 246 2.174 0 32 180.9 40 104 29.15 80 176 6.859 120 248 2.117 1 34 171.9 41 106 28 81 178 6.641 121 250 2.061 2 36 163.3 42 108 26.9 82 180 6.43 122 252 2.007 3 37 155.2 43 109 25.86 83 181 6.228 123 253 1.955 4 39 147.6 44 111 24.85 84 183 6.033 124 255 1.905 5 41 140.4 45 113 23.89 85 185 5.844 125 257 1.856 6 43 133.5 46 115 22.89 86 187 5.663 126 259 1.808 7 45 127.1 47 117 22.1 87 189 5.488 127 261 1.762 8 46 121 48 118 21.26 88 190 5.32 128 262 1.717 9 48 115.2 49 120 20.46 89 192 5.157 129 264 1.674
10 50 109.8 50 122 19.69 90 194 5 130 266 1.632 11 52 104.6 51 124 18.96 91 196 4.849 12 54 99.69 52 126 18.26 92 198 4.703 13 55 95.05 53 127 17.58 93 199 4.562 14 57 90.66 54 129 16.94 94 201 4.426 15 59 86.49 55 131 16.32 95 203 4.294 16 61 82.54 56 133 15.73 96 205 4.167 17 63 78.79 57 135 15.16 97 207 4.045 18 64 75.24 58 136 14.62 98 208 3.927 19 66 71.86 59 138 14.09 99 210 3.812
Table 20 – Temperature Sensor Resistance Value Table for T5
Display Panel
Function indicators on indoor unit display panel
DEF./FAN lamp
Illuminates during DEFROST operation
Timer indicator
Illuminates during TIMER operation
Infrared signal receiver
Receives the signal from remote controller
Operation lamp indicator
Illuminates during operation
MANUAL
Fig. 23 Unit Display
Alarm indicator
Flashes when a failure is detected
Manual button
Service purpose switch - to be used by trained personnel only
Temperature indicator
Displays the room temperature
A150250
31
A4
Table 21 – Temperature Conversion
°C °F °C °F °C °F °C °F °C °F
-5 23 21 69.8 51 123.8 82 179.6 113 235.4
-4 24.8 22 71.6 52 125.6 83 181.4 114 237.2
-3 26.6 23 73.4 53 127.4 84 183.2 115 239
-2 28.4 24 75.2 54 129.2 85 185 116 240.8
-1 30.2 25 77 55 131 86 186.8 117 242.6
0 32 25.5 77.9 56 132.8 87 188.6 118 244.4
0.5 32.9 26 78.8 57 134.6 88 190.4 119 246.2
1 33.8 27 80.6 58 136.4 89 192.2 120 248
1.5 34.7 28 82.4 59 138.2 90 194 121 249.8
2 35.6 29 84.2 60 140 91 195.8 122 251.6
2.5 36.5 30 86 61 141.8 92 197.6 123 253.4
3 37.4 31 87.8 62 143.6 93 199.4 124 255.2
3.5 38.3 32 89.6 63 145.4 94 201.2 125 257
4 39.2 33 91.4 64 147.2 95 203 126 258.8
4.5 40.1 34 93.2 65 149 96 204.8 127 260.6
5 41 35 95 66 150.8 97 206.6 128 262.4
6 42.8 36 96.8 67 152.6 98 208.4 129 264.2
7 44.6 37 98.6 68 154.4 99 210.2 130 266
8 46.4 38 100.4 69 156.2 100 212 131 267.8
9 48.2 39 102.2 70 158 101 213.8 132 269.6
10 50 40 104 71 159.8 102 215.6 133 271.4
11 51.8 41 105.8 72 161.6 103 217.4 134 273.2
12 53.6 42 107.6 73 163.4 104 219.2 135 275
13 55.4 43 109.4 74 165.2 105 221 136 276.8
14 57.2 44 111.2 75 167 106 222.8 137 278.6
15 59 45 113 76 168.8 107 224.6 138 280.4
16 60.8 46 114.8 77 170.6 108 226.4 139 282.2
17 62.6 47 116.6 78 172.4 109 228.2 140 284
18 64.4 48 118.4 79 174.2 110 230 141 285.8
19 66.2 49 120.2 80 176 111 231.8 142 287.6
20 68 50 122 81 177.8 112 233.6 143 289.4
Copyright 2015 CAC/BDP. S 7310 W. Morris St. S Indianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Edition Da te: 09/15
32
C at a l o g N o . 40 MK C ( Q ) B --- F --- 0 1 S M
Replaces: New
Loading...