Carrier 120 Series, 58CMA Installation, Start-up, And Operating Instructions Manual

HEATUNG & COOUNG
\isitx__ _.carrier.com
Installation, Start-up,
and Operating tnstructions
NOTE: Read the entire instruction manual be%re starting the installation
This symbol --> indicates a change since last issue.
TABLE OF CONTENTS
58CNA
Series 120
NuMtipoise OiMFurnace
SAFETY CONSIDERATIONS ..................................................... 1
INTRODUCTION .......................................................................... 2
LOCATION .................................................................................... 3
General ...................................................................................... 3
Location Relative to Cooling Equipment ................................ 3
INSTALLATION ........................................................................... 3
Air fPr Combustion and Ventilation ........................................ 3
Geneial ...................................................................................... 4
Unconf]ned Space ..................................................................... 4
( onf]ned Space ......................................................................... 4
All Air t_'om Inside the Structure ....................................... 4
All Air from Outside of Structure ...................................... 5
Duct Work Recommendations ..................... 5
Venting ......................................... 5
Oil Burner ..................................... 6
Oil Connections ................................ 6
Barometric Draft Control ......................... 6
Electrical Connections ............................ 6
Horizontal or Downf]ow Installation .................. 7
Filters ......................................... 7
START-UP, ADJUSTMENT, AND SAFETY CHECKOUT 7
Operational Checkout ............................. 7
Combustion Check ................................ 7
Fan Adjustment Check ........................... l0
Limit Control Check ............................... 10
For Year-Round Air Conditioning .................... i0
Heating ......................................... l 0
Cooling ........................................... 10
Constant Blower Switch ........................... 10
MAINTENANCE ................................... 11
General ......................................... 11
Oil Burner .......................................... 1l
Heat Exchanger and Flue Pipe ....................... i 1
Blower Removal ................................ 11
O0o
t_ oq
A97247
Fig. 1--580MA Multipoise OH Furnace
For use with grade 1 or 2 Fuel Oil. Do not use Gasoline, Crankcase Oil, or any Oil containing Gasoline! Failure to fbllow this warning could lead to sooting, fire, explosion, and/or severe bodily harm.
Never bum garbage or paper in the heating system and never leave rags, paper, or any flammable items around d_e unit
Failure to fbllow this caution will result in minor unit or property damage
SAFETY CONSJDERAT{ONS
FOR YOUR SAFETY
DO NOT STORE OR USE GASOLINE OR OTHER
FLAMMABLE VAPORS AND LIQUIDS IN THE
VICINITY OF THIS OR ANY OTHER APPLIANCE.
DO NOT ATTEMPT TO START THE BURNER WHEN EXCESS OIL HAS ACCUMI_ LATED, WHEN
THE FURNACE IS FULL OF VAPOR, OR WHEN THE COMBUSTION CHAMBER IS VERY HOT
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 101 Catalog No 535-80123 Printed in U.S.A. Form 58CMA-5SI Pg 1 11-03 Replaces: 58CMA-4SI
These instlq./ctions are intended to be used by qualified personnel who have been trained in installing this type of
furnace. Installation of this f_amace by an unqualified person may lead to equipment damage and/or a hazardous condition which may lead to bodily ham_.
All local and national code requirements governing installation of oil buruing equipment, wiring, and flue connections must be followed. Some of the codes (issued by the Canadian Standards Association, d'*e National Fire Protection Agency, and/or d'm American National Standards Institute) that may be applicable are:
- A
i
I __ FOR J DIAM VENT
'-- TOP KNOCK-OUT
fi!i!i!b
20"
19.(%
IIII
-----_ 3" _,_--------- E --------------_
KNOCK-OUT BOTH SIDES- 7
i _
7_
J _ii .............................../
FOR J DIAM VENT/
B
r
--G-q
_ y II
',)) _ OIL INLET
_JA_'._" (BOTH SIDES)
L
i , , EgE% O'Ays
_- ..... \ / i II (BOTH SIDES)
] ""---_L -- rq_ _ .88 DIAM TYP
Dimensions (IN.)
UNIT SIZE
105o12 t20-20
ANSI/NFPA 81:
ANSlINFPA 211: CHIMNEYS, FIREPLACES, VENTS,
ANSlINFPA 90B:
ANSl/NFPA 70: NATIONAL ELECTRICAL CODE
CSA B139:
CA8 C22.1: CANADIAN ELECTRICAL CODE
Only d-ie latest issues of these codes should be use& and are
available l_'om either _he National Fire Protection Agency, Bat= teryrnarch Park, Quincy, MA 02269 or The (anadian Standards Association, 178 Rexdale Bird, Rexdale, Ontario M9W 1R3
Recognize safety irRormation. This is the safety°alert symbol z_ When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury.
A
35
39-1/2
B
48-3/4
53
C D E F G
30-1/4 16-5/8 20 22 12 32-1/4 18-3/4 24 28 12-9/32
Fig. 2--DimensionN Drawing
INSTALLATION OF OIL BURNING EQUIPMENT
AND SOLID FUEL BURNING APPLIANCES
WARM AIR HEATING AND AIR CONDITIONING SYSTEMS
INSTALLATION CODE FOR OIL BURNING EQUIPMENT
K
H
14 16
Understand the signal words DANGER, WARNING, CAUTION and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death CAUTION is used to identify unsafB practices which would result in minor personal inju_ or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
INTRODUCTION
-->
)'he model 58CMA Furnaces are available in 2 sizes. Each size unit is capable of 3 heat/airflow combinations by a simple nozzle
change. Unit 105=12 covers inputs of 70,000, 91,000, arid 105,000 Bmh, and unit 120o20 covers inputs of 119,000, 140,000 arid
154,000 Btuh This eliminates the need to stock 6 separate units
This furnace is a multipoise unit. It may be installed in the upflow, downflow or horizontal configuration.
The [_l_rnace is shipped as a packaged unit, complete with burner and controls. It requires a line voltage (115 vac) connection to control box, a thermostat hook-up as shown on wiring diagram, oil line connection(s), adequate duct work_ and connection to a properly sized vent.
J 5
6
K L
1-1/2 1-3/4 1-5/8 1-1/2
A98037
Table 1--Minimum Clearances To Combustib{e Materials (In.)
UNIT APPLICATION UPFLOW DOWNFLOW HORIZONTAL
Furnace 0 2 2
Sides Supply Plenum and Warm-Air Duct Within 6 ft
Back Service Clearance 0 1 0
Top Horizontal Warm-Air Duct Within 6 ft of
Bottom 0 0* 0* FJue Horizontally or Below Pipe 4 4 4
Pipe Vertically Above Pipe 9 9 9 Front 8 8 24
* Use approved subbase for combustible floor. NOTE: Adequate service clearances should be provided over and above these dimensions as required
of Furnace 1 2 1
Furnace Casing or Plenum 2 2 2
Furnace 2 2 3
The air handling capacity of this furnace is designed %r cooling airflow. Rot'or to Table 12 _br expected airflows at various external
duct static pressures.
LOCATION
Step l--General
This t:urnace is not water tight and is not designed fbr outdoor installation. This t:urnace shall be installed in such a manner
as to protect electrical components tiom water. Outdoor installation would lead to a hazardous electrical condition and
to premature _;amace _hilure.
Do not use this t'urnace as a construction heater. Use of this furnace as a construction heater exposes furnace to abnomxa]
conditions, contaminated combustion air, and tack of air filters. Failure to follow this warning can lead to premature
furnace failure and/or vent fi_ilure which could result in a fire hazard and/or bodily harm.
For attic installation, it is important to keep insulation 12 in or more away fiom any _/mace openings. Some types of
insulating materials may be combustibles and may cause a fire haza*d and proper w damage
This furnace is approved ['or reduced clearances to combustible constn/ction, therefore, it may be installed in a closet or similar enclosure Since this unit may be installed in an upflow, counter° flow, or horizontal position, it may be located in a basement or on the same level as area to be heated. [n any case, unit should always
be installed level
In a basement, or when installed on floor (as in a crawlspace), it is
recommended that unit be installed on a concrete pad that is 1 in
to 2 in thick When installed in counterflow position, furnace must not be
installed on combustible flooring, unless approved subbase is used. Also, since flue pipe is in a counterflow position, Downflow Conversion/Vent Guard Kit MUST be used, (Also, read page 9.)
When installed in a horizontal position, t:m'nace may be suspended
by using an angle iron frame, as tong as total weight of both
furnace and fi'ame are allowed _br in support calculations. (Other methods of suspending are acceptable.) When installed in the
Horizontal Position, this fi/rnace must not be installed on combus= tible flooring, unless the approved Horizontal Subbase is used.
The required n_ininmm clearances %r furnace are specified in Table 1.
The _i/rnace should be located as close as possible to chinmey or vent in order to keep vent connections short and direct The Da'nace should also be located as near as possible to center of air
distribution system.
Step 2--Location Relative to Cooling Equipment
When installing f_/mace with cooling equipment for year-round operation, the t'ollowing recommendations must be followed _br series or parallel airflow:
1. In series airflow applications, coil is mounted after furnace in an enclosure in supply-air stream. The [:urnace blower is used for both heating and cooling airflow.
The coil MI. ST be installed on air discharge side of furnace Under no circumstances should airflow be such that cooled,
conditioned air can pass over _itmace heat exchanger. This will cause condensation in heat exchanger and possible _hilure of heat exchanger which could lead to a fire hazard and/or a hazardous condition which may lead to bodily harm. Heat exchanger _itilure due to improper installation may not be covered by warranty
2 In parallel airflow applications, dampers must be provided to
direct air over f_/mace heat exchanger when heat is desired and over cooling coil when cooling is desired.
INPORTANT: The dampers should be adequate to prevent cooled air fi'om entering furnace. If manually operated, dampers must be
equipped with a means to prevent operation of either cooling unit or _i/rnace unless damper is in full cooi or heat position.
mNSTALLATION
Step l--Air for Combustion and Ventilation
Installation of this filrnace in an area where it will receive contaminated combustion air must be avoided Such contami=
nation would include the following: ammonia, chlorine, hy&ogen sulfide, halogenated hy&ocarbons, carbon tetra° chloride, cleaning solvents, hy&ochloric acid, water soften° ing chemicals, and similar chemicals. Failure to fbllow this warning will lead to premature resting of heat exchanger and possible premature furnace fbilure and/or vent fhilure which could result in fire hazard and/or bodily harm.
Donotblockcombustion-airopeningsinthefurnace,Any
blockagewillresultinimpropercombustionwhichmayresult
inafirehazardan_orcausebodilyharm
Step 2--General This fhrnace should be installed in a location in which fi_cilities %r
ventilation permit satisfi_cto_- combustion of oil, proper venting,
and maintenance of ambient temperature at safe limits under
normal conditions of use. The location should not interfere with proper circulation of air within the confined space. (See NFPA=3 !,
Section 1.5.) In addition to air needed for combustion, process air shall be
provided as required for: cooling of equipment or material,
controlling dew point, heating, @ing, oxidation or dilution, safety exhaust, and odor contml.
In addition to air needed for combustion, air shall be supplied for ventilation, including all air required for comfort and proper working conditions fbr personnel.
The barometric draft regulator (included with Nrnace) shall be
installed in same room or enclosure as furnace in such a manner as to prevent any diffkrence in pressure between regulator and
combustion=air supply. Air requirements for operation of exhaust Rms, kitchen ventilation
systems, clothes dwers, and fireplaces shall be considered in
determining the adequacy of a space to provide combustion=air requirements.
The tack of a proper amotmt of combustion air can lead to serious
Nrnace operational problems. Some of these problems are:
1. Excessive oil burner after-drip, and oil Nines.
2. Sooting.
3. Melted oil burner ignitor/relay control.
4. Air band or air mrbulator settings more open than nom_al
5. Lockouts on start=up
The requirements _br combustion and ventilation air depend upon whether furnace is tocated in a (ONFINED or [N(ONFINED
space.
Step a--Unconfined Space An unconfined space must have at 1east 50 cu k for each 1000
Bmh of total input [br all the appliances (such as furnaces, clothes
dwers, water heate*s, etc) in the space.
In unconfined spaces in buildings of conventional fi'ame, brick, or
stone construction, infiltration MAY be adequate to provide air for
combustion, ventilation, and dilution of flue gases This detem?i= nation must be made on an individual installation basis and must
take into consideration the overall volume of'unconfined space, the number of windows and ventilation openings, the number of doors to the outside, internal doors which can close offunconfined space,
and overall tighmess of building constluction Conside*ation must
also be given to the amount of storage items (fi/rniture, boxes, etc.) within the unconfined space which take away l"romthe air volume
(See Table 2.) Many new buildings and homes (and older ones that have been
weatherized) MUST BE considered as being of tight construction, therefore, infiltration will not be sufficient to supply necessary air
fbr combustion and ventilation.
Table 2--Mimmum Floor Area
For Unconfined Space
88CMA FURNACE MINIMUM SQ FTWBTH
INPUT BTUH 7-tt2 FT CEILING
70,000 467 9%000 607
108,000 700 lt9,000 793 140,000 933 154,000 1026
A building can be considered as being of tight constluction when: * Walls and ceilings exposed to outside atmosphere have a
continuous water vapor retarder with a rating of 1 perm or tess with openings gasketed or sealed, and/or
* Weatherstripping has been added on operable windows arid
doors and/or
* Caulking or sealants are applied to areas such as joints around
window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetra=
tions tbr plumbing, electrical, arid fhel lines, and at other openings
If combustion and ventilation air must be supplied to an uncon= fined space from outside, an opening with a FREE AREA of riot tess than 1 sq in. per 1000 Bmh of total input of all appliances within unconfined space (but not tess than 100 sq in.) must be
provided. This opening must be located such that it can not be blocked at any time.
Step 4--Confined Space A confined space has a volmne of less than 50 cu fl per 1000 Btuh
of the total input rating for all appliances installed in that space When Nrnace is installed in a closet or enclosure, 2 ventilation
openings, with OPEN AREA as dimensioned in example below are required for combustion air. The openings should be located about 6 in. from top and bottom of enclosure at ti'ont of fhrnace.
(See Table 3.)
TaRe a--Combustion Air
From Confined Space
58CMA FURNACE LENGTH
INPUT NTUH {BN.)
70,000-t 0S,000 16
t19,000 20
NOTE: In calculating free area, consideration shall be given to blocking effect of louvers, grilles, or screens protecting openings.
Screens used shall not be smaller than 1/4-in. mesh and shall be readily accessible for cleaning. If free area through a louver or grille is known, it shall be used in calculating size and free area
specified. If design and free area are not known, it may be assumed that wood louvers have 20 percent free area and metal louvers and grilles have 60 percent free area. Louvers shall be fixed in open position or interlocked with fi/mace so they open automatically at
furnace start=up and remain open during It/mace operation. The size of the openings depends upon whether the air comes from
outside of the structure or an unconfined space inside the strt/cmre. ALL AIR FROM INSIDE THE STRUCTURE
For a confined space, where air is taken from an interior space, 2 pem_anent openings of equal area are required. One opening must be within 12 in of ceiling arid the other within 12 in of floor. Each
HEIGHT
(BN.)
g
q0
openingmusthaveafleeareaofatleastIsqin,per1000Bmhof totalinputratingbutnotlessthan100sqin.(See_able4.)
DLCT WORK RECOMMENDATIONS
TaRe 4_Combustion Air
From Unconfined Space
88CNA FURNACE
INPUT BTUN
70,000 100
91,000 100 t05,000 105 119,000 119
t40,000 140 154, 000 154
ALL AIR FROM OUTSIDE OF STRUCTURE
If outside air is supplied to a confined space, then the 2 openings must be equal and located as above.
1. If combustion air is taken through a pem_anent opening directly communicating with the outdoors, the opening shall
have a n_ininmm flee area of 1 sq in. per 4000 Bmh of total
input rating for all equipment in the enclosure.
2. If con_bustion air is taken from outdoors through vertical ducts, the openings and ducts MUST have at least 1 sq in. of flee area per 4000 Btuh of the total input %r all equipment
within the confined space. (See Table 5j
FREE AREA PER
OPENING
{SQ BN.)
Table 5--Combustion Air From Outdoors
Through Vertica! Ducts
58CMA FURNACE ROUND PIPE
INPUT BTUN (SQ IN.} (BN. DIAI_4}
70,000 17.5 5 91,000 22.8 6
105,000 26.3 6 119,000 29.8 6 140,000 35.0 6 154,000 38.5 6
3. If combustion air is taken from outdoors through horizontal ducts, the openings and ducts MUST have at least 1 sq in. of fi'ee area per 2000 Btuh of the total input %r all equipment
within the confined space. (See Table 6j
FREE AREA PER
OPENING
Table 6--Combustion Air From Outdoors
Through Horizontal Ducts
58CNA FURNACE FREE AREA PER OPENING ROUND PiPE
INPUT BTUN {SQ IN.} (IN. DIAM}
70,000 35.0 7 91,000 45.5 8
t05,000 52.5 9 119,000 59.5 9
t40,000 70.0 10 184,000 77.0 10
When ducts are used to supply air, they must be of the same cross sectional area as flee area of openings to which they connect
The mininmm dimension of rectangular air ducts must not be tess than 3 in.
When supply ducts carw air circulated by fi/mace to areas outside spaces containing fi/rnace, return air MUST also be handled by a duct sealed to furnace casing and tem_inating outside space containing _/rnace. IncmTect duct work termi= nation and sealing wilt create a hazardous condition which could lead to bodily ham_.
Return=air grilles and warm air registers MUST NOT be obstructed. Failure to follow this caution will result in
premature failure of the heat exchanger,
The proper sizing of warm air ducts is necessa W to ensure satisfbctory furnace operation. Duct work should be in accordance with the latest editions of NFPA=90A (Installation of Air Condi- tioning and Ventilating Systems) and NFPA-90B (Wam_ Air Heating and Air Conditioning Systems) or Canadian equivalent.
The supply duct work should be attached to flanged front opening provided at discharge end of furnace. The return-air duct work should be attached to flanged rear opening of furnace. See Fig. 2 for dimensions of these openings.
NOTE: The back (blower access opening) should not be used %r remrn air.
The following recommendations should be followed when install- ing duct work:
1. Install locking=type dampers in al! branches of individual ducts to balance out system. Dampers should be adjusted to
impose proper static at outlet of _i/rnace.
2. A flexible duct connec[or of noncombustible material should be installed at unit on both supply- and return=air systems. In
applications where extremely quiet operation is necessaw, the first 10 f_ (if possible) of supply and return ducts should be internally lined with acoustical material.
3. In cases where return=air grille is located close to fire inlet, there should be at least one 90 ° air mrn between fire inlet and
grille. Further reduction in sound level can be accomplished by installing acoustical air turning vanes or lining duct as
described in item 2 above.
4 When a single air grille is used, duct between grille and
ii/mace must be the same size as return opening in fire, ace
VENTING Venting of filrnace should be to the outside and in accordance with
local codes or requirements of local utility-. OIL=FIRED APPLIANCES SHALL BE CONNECTED TO
FLUES HAVING SUFFICIENT DRAFT AT ALL TIMES TO ENSURE SAFE AND PROPER OPERATION OF APPLIAN(E.
For additional venting irKormation, refer to ANSIiNFPA 211 Chimney Fireplaces, Vents_ and Solid Fuel Burnino_liances
an&or CSA B139 Installation (7ode. This fl/rnace is certified fbr use with Type "L" vent (maximum flue
gas temperature 575°F). Vent System Inspection Be[bre _i/mace is installed, it is highly recommended that any
existing vent system be completely inspected. For any chimney or vent, this should include the following:
1. Inspection for any deterioration in chinmey or vent. If dete- rioration is discovered, chimney n-rest be repaired or vent must be replaced.
TuNe 7--Electrical Data
UNIT SBZE
t05-12 26 15 120-20 26 20
Permissible limits of voEtage range at which unit will operate satisfactorily. 1 Length shown Js as measured 1 way alor_g wire path betweer_ u_it and service panel for maximum 2 percer_t vo{tage drop. $ Time-delay fuse is recommer_ded
VOLTS--
HERTZ-- PHASE--
115--60--1 115--60--1
OPERATING
VOLTAGE RANGE
Max.* Min.*
132 104 132 104
MAX UNIT
AMPS
12.2
15.7
MIN
WIRE
GAGE
14 12
MAX WIRE
LENGTH (FT)
MAX FUSE OR
CKT BKR AMPS
2. Inspection to ascertain that vent system is clear and fi'ee of obstructions. Any blockage must be cleared befbre installing
fLli"nace,
3. Cleaning chimney or vent if previously used fbr venting a solid fuel burning appliance or fireplace.
4. Confirming that all unused chimney or vent connections are
properly sealed.
5. Verification tiaat chimney is properly lined and sized per the applicable codes. (Refer to list of codes in Safkty Consider- ations section.)
Mason_ Chimneys
This Nmace can be vented into an existing masonry chimney. This Nmace must not be vented into a chimney servicing a solid Net
burning appliance. Before venting Nmace into a chimney, the
chimney MUST be checked fk)r deterioration and repaired if
necessary. The chimney must be properly lined and sized per local
or national codes.
If Nrnace is vented into a common chinmey, the chinmey must be of sufficient area to accommodate the total flue products of all appliances vented into chimney.
The fbllowing requirements are provided for a safe venting system:
1. Be sure that chimney flue is clear of any dirt or debris.
2. Be sure that chimney is not servicing an open fireplace.
3. Never reduce pipe size below the outlet size of Nmace. (See
Fig. 2.)
4. All pipe should be supported using proper clamps and/or stlaps. These supports should be at least every 4 ft.
5. Ail horizontal runs of pipe should have at least 1/4-in. per ft of
upward slope.
6. All runs of pipe should be as short as possible with as f)w
rams as possible.
7. Seams should be tightly joined and checked for leaks.
8. The flue pipe must not extend into chimney but be flush with inside wall.
9. The chimney n-rest extend 3 ft above highest point where it passes through the roof of a building and at least 2 t't higher than any portion of a building within a horizontal distance of
10 ft. It shall also be extended at least 5 ft above highest connected equipment flue collar.
10. Check local codes for any variance. Factory=Built Chimneys Listed _actory-built chimneys may be used. Refer to chimney
manui_acmrer's instructions fbr proper installation.
OIL BURNER
This fl/mace is supplied with a high-pressure atomizing retention
head-type burner (fk_ruse with grade 1 or 2 ft_el oil) The motmting
flange is fixed to burner air robe and no adjustment is required for insertion length.
OIL CONNECTIONS
Complete instructions for installing fuel oil piping can be _bund in oil burner Installation Instrtlctions included with furnace
Oil line entry holes are provided in side panels. Two holes are provided in each location so that a 2-pipe system may be used if
desired. An oil filter should be used with all oil burners and should be
installed as close to burner as possible.
BAROMETRIC DRAFT CONTROL
The barometric draft control shipped with furnace MUST be used with [_urnace to ensure proper operation. Instructions fk}r installing control are packed with control.
ELE( TRI( AL CONNECTIONS
N
The unit cabinet must have an uninterrupted or unbroken electrical ground to minimize personal injury if an electrical fault should occur. A green ground screw is provided in
contIol box for this connection.
115-v Wiring
Befk_re proceeding with electrical connections, make certain that voltage, fiequency, and phase correspond to that specified on unit
rating plate. Also, check to be sure that service provided by utility is sufficient to handle load imposed by this equipment. Refer to rating plate or Table 7 fbr equipment electrical specifications
Make all electrical connections in accordance with National Electrical Code (NEC) ANSI NFPA 70-2001 and any local codes
or ordinances that might apply For Canadian installations, all electrical connections must be made in accordance with Canadian
Electlical Code CSA C22.1 or subauthorities having jurisdiction.
Do not connect ahmfumm wire between disconnect switch and furnace Use only copper wire. Failure to fkfllow this
caution will lead to intermittent electrical operation andor fire hazard.
The contlol system depends on correct polarity of power supply. Connect HOT wire (H) and NEUTRAL wire (N) as shown in Fig.
3 or4.
A separate line voltage supply MUST be used with a fused disconnect switch or circuit breaker between main power panel and unit. (See Fig 3 or 4)
Metallic conduit (where required/used) may terminate at side panel of unit. It is not necessa_ to extend conduit inside unit f?om side panel to contlol box.
When replacing any original furnace wiring, use only 105_>( No
14 AWG copper wire.
24°V Wiring Instructions %r wiring thermostat (field supplied) are packed in
thermostat box Make them_ostat connections as shown in Fig. 3 or 4 at 24=v terminal board on ihn timer board.
Accessories When installing optional accessories to this appliance, follow
manufacturer's Installation Instructions included with accessory. Od-ler than wiring fbr themaostat, wire with a minimum of type "T" insulation (63C>F rise) nmst be used for accessories.
HORIZONTAL OR DOVv_FLOW INSTALLATION For horizontal installation, determine which "side" will become the
"top", when d_e unit is laid down. Remove the flue pipe clearance knock=out fi'om the top of that side panel. Install the flue elbow so that it exits the cabinet of d_e ft/mace through that opening.
For counterflow installation, the flue pipe must exit the cabinet through 1 of the side panel openings (as above), then extended up the side of the furnace. Insure that adequate clearances to con>
bustibles are observed. Downflow Conversion/Vent Guard Kit
MUST be used. Remove burner by loosening mounting nuts and mrn oil burner
slightly counterclockwise to unlock the key hole burner flange. Prevent putting undue strain on burner wiring. (It may be neces= saV to disconnect burner wiring in some cases.)
To reinstall burner, insert on the four burner studs on key hole
burner flange and turn it clockwise to lock it and dghten nuts.
IMPORTANT: Burner retest always be installed in the upright
position with ignition control on top.
FILTERS
Never operate unit without a fiher or with filter access door removed. Failure to adhere to this warning could lead to a
hazardous condition which could lead to equipment damage and bodily harm
An external filter rack is provided as standard equipment with furnace A sufficient clearance should be provided tbr air filter
access See Table S i\_r filter rack flange dimensions for return air duct
Tab{e 8--Filter and Flange (In.)
UNIT AIR NLTER FLANGE OPENING SIZE SBZE SRZE
10x24x1
105-12 or 15 X 23
16X25X1
t20-20 20 X 30 X 1 19 X 20
START-UP, ADJUSTMENT, AND SAFETY CHECKOUT
Step l--Operational Checkout
4. Blower access door is secured in place
5. Valve on oil supply line is open. 6 RESET BUTTON on primaD" control is pushed down
7 Flame observation door and 2 cleanout access doors located at
fi'ont of unit are closed.
8. Thermostat is set for heating mode and set above room temperature
If all of the above items have been perfbrmed, set main electrical switch to ON position and burner should start. When burner starts, proceed to Combustion Check section.
Step 2--Combustion Check In order to obtain optimum per%rmance from oil burner, the
following setup procedures must be followed:
1 A test kit to measure smoke, stack draft, over-fire draft, oil
pmnp pressure, (02, and stack temperatures MUST be used in order to obtain proper air band setting. Although all of the
above measurements are required _br optimum setup and efficiency data, the most impmlant readings that must be taken
are smoke number, over-fire &aft, stack draft, and pmnp pressure
2. The proper smoke nmnber has been established by engineer- ing tests to be between 0 and 1. This degree of smoke emission is commonly referred to as a "trace" of smoke. It is recom- mended m use a Bacharach hue spot smoke test set or
equivalent.
3. In order to ensure proper draft through fhrnace, a barometric draft regulator (supplied with furnace) retest be installed.
In order fbr this device to fhnction properly, barometric damper must be mounted with hinge pins horizontal and face of damper vertical. (See instructions included with damper.) The draft regu- lator should be adjusted after furnace has been firing fbr at least 5
minutes, and set between -0.025 and -0.035 in. wc. (See Table 9.)
4. The over-fire &aft, which is taken through observation door (located in center line above burner in ii'ont panel of furnace), is a measurement necessary to detem_ine if there is a blockage
between oil burner and flue outlet.
There should be a total pressure drop of between 0.020 and 0.05 in. wc through furnace as shown in Table 9. The over-fire draft must be set within the range shown in Table 9.
TaRe 9--Furnace Draft Conditions (In. WC)
FURNACE FLUE OVER-FIRE TOTAL RESTRICTION
iNPUT DRAFT DRAFT THROUGH
{BTUH) MINIMUt'V] MAXIMUM HEAT EXCHANGER
70,000 -0.025 0.010 0.020 to 0.035 91,000 -0.025 0.020 0.030 to 0.045
108,000 -0.025 0.025 0.035 to 0.050 110,000 -0.025 0.025 0.035 to 0.050 140,000 -0.025 0.025 0.035 to 0.050 154,000 -0.025 0.025 0.035 to 0.050
DO NOT TAMPER WITH UNIT OR CONTROLS (7ALL
YOUR SERVICE TECHNI(IAN. Failure to follow this warning could result in personal and/or property damage
Installation of fmnace is now complete Run through the ibltowing checkout and ensure each item has been peribm_e&
1. (orrect nozzle size has been selected for desired input rate.
2. Blower wheel support is removed.
3. Electrical wiring is completed according to Fig. 3 or 4.
A reading outside the range shown in Table 9 (for example +0.1 in. wc) would indicate that f_lraace is in an extremely high-pressure condition in primary section. This condition may be caused by any
of the following problems:
a. Excessive combustion air due to air shutter being too wide
open.
b A lack of flue &aft (chimney effect) or some other
blockage, such as soot, in secondary section of heat exchanger.
,,ll_
VERSION EN FRANCAIS INCLUS DANS MANUEL D'INSTALLATION.
,HI_GND
1H(_) 115 VAC I_/60HZ POWER SUPPLY
RED _LNU_
BLACK
BLUE
UNU_
LIMIT
OIL INPUT : 0.65 USGPH COOLING CAPACITY : 2 1/2
to 5 TONS MAX
Go
STANDARD HEAT / COOL WIRING DIAGRAM WITH ELECTRONIC FAN TIMER. OIL INPUT: 0.75 USOPH. COOLING CAPACITY: 5 TONS MAX.
_: USE JUMPER ONLY WHEN THE COOLING AND HEATING SPEEDS ARE
SAME. _ USE ONLY OIL PRIMARY CONTROL EQUIPPED WITH VALVE ON DELAY
(PRE PURGE) R7184B, P OR U. _*_ USE CONSTANT IGNITION ONLY. NEVER USE THE INTERRUPTED IGNITION
AND/OR THE BLUE WIRE ON R7184 CONTROL.
FOR HUMIDIFIER, REMOVE THE DUMMY TERMINAL MARKED BUM. FOR ELECTRONIC AIR CLEANER, REMOVE THE DUMMY TERMINAL MARKED EAC.
DNS 0925 Rev.A
x >_>_ LGNITOR
_L2
BURNER MOTOR
VALVE
>_ T OIL '_
VALVE CAD CELL
LO _ 3APACITOR
Oz
PRIMARY
WHITK
L_kL_DS
BLACK
BLUE
OIL INPUT : 0.50 USOPH COOLING CAPACITY : 2 TONS
Fig. 3--Wiring Diagram (I05-12) A03164
BLUE *Jumper
FOR HUMIDIFIER, REMOVE THE DUMMY TERMINAL MARKED HUM. FOR ELECTRONIC AIR CLEANER, REMOVE THE DUMMY TERMINAL MARKED EAC
DNS 0926 Rcv.A
Fig. 4--Wiring Diagram (120-20) A03165
OIL INPUT : 1.10 USGPH COOLING CAPACITY : 5 TONS
c. _se of an oversized nozzle input & Pump pressure over values listed iu Table 10.
5_
The CO 2 and stack temperature instruments enable you to obtain data required to determine thermal efficiency of _;ar=
*lace
6_
An oil filter should be installed as close to burner as possible with ALL oil burners and is essential on lower firing rate bumers_ We recommend the use of a tow pressure drop oil
filter such as the General Filter, Inc. model #lA-25A or equivalenL
--> ?.
The oil pressure regulator is factory set to give oil pressure of 130 psi J:br the model having 105,000 BTUH input and 130 psi
fbr d'*e model having 119,000 BTUH input. The firing rate noted on nameplate may be obtained using the nozzles and pump pressures indicated in Tahle 10.
--> TaMe 10--Sumer Input and Nozzle Size and Pump
Pressure
FURNACE
INPUT NOZZLE
(BTUH)
70,000 0.50 0.50-70VV 100
91,000 0.65 0.55-70B 140 105,000 0.75 0.65-70B 133 120,000 0.85 0.75-70B 128 140,000 1.00 0.85-70B 138 15&000 1.10 0.85-70B 167
8. On a new iustallation, air entrapped in oil lille leading fiom tank to nozzle must be thoroughly purged in order to prevent
excessive after &ip. The oil pump is provided with a special fitting which allows purging of ally air between tank and oil
pump. Tile proper procedt/re for performing this operation is
as £dlows: a. Place a piece of clear plastic 1/4 in. diameter robing over
b. Start oil burner, then open purge fitting and allow burner to
c. Tighten purge fitting. Allow oil to run to nozzle and fire
d. If purging takes longer than 15 sec and no flame has been
e. For detailed information on operation of prima_ contloL
After all the setup procedures mentioned above have been corn= pleted, the burner should be allowed to operate and an inspection
rein'or should be used to observe the flame pattern at tip of nozzle. Any irregularities such as burning to 1 side or pulsating flame
patterns should be connected by changing nozzle.
Step 3--Fan Adjustment Check
_his f_lruace is equipped with a 4=speed direct-drive motor to
deliver a temperature rise within range specified on rating plate, between remm and supply plenums, at external duct static pressure noted on rating plate
INPUT REAL PUMP
USGPN PRESSURE
purge fitdng on oil pump.
run until purge robe is completely fi'ee of air bubbles.
burner.
established, burner stops. Push reset button on fi'out of primary control to restart burner
refer to instructions included with iq/rnace.
SPECIFBCAT_ON
PUMP PRESSURE
100 140
130 130 140 170
When operating furnace in heating mode, static pressure and temperature rise (supply=air temperatme minus return=air temperature) nlust be within those limits specified on rating label. Failure to follow this warning could lead to severe ftm]ace damage.
Adjust fan speed A(COPdDING TO OIL INPUT SELE(TED so that temperature rise is within rise range specified on rating plate. (See Table 110 Consult wiring diagram for speed changes on
direct=&ive motor
Tab{e 11--Speed Selection
UNiT SIZE
105-t2/
120_20 91,000/140,000 Med-High
To adjust fire off time, set DIP switches ou coutloi board to obtaiu desired timing. (See Fig. 5.)
60 Sec 90 Sec 120 Sec 150 Sec
DELAY OFF DIP SWITCH SETTINGS
FURNACE RECOMMENDED
iNPUT BLOWER
(BTUH) SPEED
70,000/119,000 Med-Low
105,000/154,000 High
A95115
Fig. 5--Fan Off Time DIP Switch Settings
(Slack Box Represents Switch Posit{on)
Step 4--Limit Controm Check After furnace has beer* iu operation _br at least 15 minutes, restrict
return-air supply by blocking filters or closing return registers and allow furnace to shut down or* high limit. The burner should shut
off. and main blower should contkme to rnn. Remove restriction, and burner should come back on in a f_w
minutes.
Step 5--For Year-Round Air Conditioning This fitmace is designed £_r use in cor_juncfion with cooling
equipment to provide year-round air couditioniug_ The blower has been sized fbr both heating and cooling, however, fan motor speed
may need to be changed to obtain necessary cooling airflow
Step 6--Heating The blower speed is _i_ctory set to deliver required airflow at
normal duct static pressure.
Step 7--Cooling The blower speed may be field adjusted to deliver required airflow
for cooliug application. (See Table 12)
Step 8--Constant Blower Switch This _hruace is equipped with a coustant low=speed blower option.
Whenever room themlostat is not calling for heating or cooling, blower runs on tow speed in order to provide air circulation_ If constant blower option is not desired, the rocker switch on top of cabinet may be used to mm off constant speed.
10
Table 12--Airflow Data (CF/vl)
UNIT BLOWER SBZE SPEED
High
105o12 Med-High
Med-Low
Low
High
120o20 Med-High
Med-Low
Low
NOTES:
1. Airflow values in cubic fi per minute (CFM) rounded to nearest 5 CFM.
2. Data taken with Nters in place
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
1425 1350 1305 1250 1170 1030 925 805 1130 1045 1000 950 885 820 745 670
840 810 770 740 685 635 580 509 725 730 740 745 730 715 690 665
2080 2041 1965 1864 1702 1576 1474 1336
1892 1859 1770 1675 1550 1449 1330 1217 1556 1475 1394 1318 1211 1134 1051 938 1221 1164 1081 998 926 855 782 653
EXTERNAL STATIC PRESSURE IN. WC
MAINTENANCE
The ability to properly per%tin maintenance on this equip° ment requires certain expertise, mechanical skills, tools, and
equipment If you do not possess these, do not attempt to perform any maintenance on this equipment other than those procedures recommended in the User's Manual. FAILETRE
TO FOLLOW THIS WARNING COULD RESULT IN
POSSIBLE DAMAGE TO THIS EQUIPMENT, SERIOUS
PERSONAL INJURY, OR DEATH.
Be%re per%rming any service ftmctions, unless operations
specifically require power to be on, make sure all utilities are
turned off upstream of appliance. Failure to comply with this warning will cause a fire hazard and/or bodily harm.
iiiiiiii_, iiiiil
To avoid personal injury, make sure electrical supply power
is off before servicing Failure to follow this warning could
lead to electrical shock, fire, or death.
Step l--General In order to keep this f'umace in good operating condition and to
maintain its wan'anty, the t_umace MUST be serviced on an annual
basis. This servicing includes a nozzle change, a burner inspection,
a visual check of robe passages through flue outlet and cleanout
ports, and a visual inspection of combustion chamber when burner
is removed. Depending on above inspection, service could also include a
cleaning and vacuuming of heat exchanger robes and possibly the heat exchanger drum section.
Removal of any heat exchanger components which are sealed by gaskets requires replacement of gasket.
Failure to replace any heat exchanger gaskets with new
gaskets when any heat exchanger plates or covers are re-
moved could lead to heat exchanger leakage, sooting, and/or
a hazardous condition capable of causing bodily ham_.
This furnace should never be operated without an air filter Disposable filters should be replaced at least once a year. If equipped to provide cooling, filters should be replaced a minin-mm of twice a year Permanent filters should be cleaned at least twice a year.
ALWAYS KEEP MAIN OIL VALVE TURNED OFF IF BURNER IS SHUT DOWN FOR AN EXTENDED PERIOD OF TIME
Step 2--OH Burner For optimum per%finance, oil burner nozzle should be replaced
once a year. Contact your service technician if you are unsure of this procedure.
The procedure for nozzle installation and/or replacement is out= lined in oil burner instrnction manual which came with t_m'nace
AfIer replacement of nozzle, burner should be adjusted in accor= dance with Combustion Check section of this instruction.
Step 3--Beat Exchanger and Flue Pipe Ordinarily, it is not necessary to clean heat exchanger or flue pipe
eve_ year, but it is necessary to have your service technician check unit before each heating season to determine whether cleaning or replacement of parts is required
If cleaning is necessary, the _bltowing steps should be performed:
1 Turn off all oil and electrical supplies upstleam of furnace
If _i/rnace has been in operation, some surfaces may be hot Allow time _br unit to cool dox_n personal inju_ will result, j
2 Disconnect flue pipe. 3 Remove flue collar panel located in I'ront part of ftmaace.
4. Remove bafl"le t'rom seconda_ heat exchanger.
5. Disconnect oil line and remove oil burner t'rom Nrnace.
6. Open 2 cleanout doors located in upper part of flout panel of _,/fnace.
7. Clean secondary tubes, and primary cylinder with stiff brush and vaCUllnl cleaner.
8. Befbre re-assembly, the heat exchanger and combustion charnher should be inspected to determine if replacement is required.
9. After cleaning, replace bane, flue collar plate, oil burner, and close the 2 cleanout access doors. Reconnect flue pipe and oil
line.
10. Re-adjust burner _br proper operation.
Step 4--Blower Removal
To remove blower t'rom fm'nace:
1. Turn off all oil and electrical supplies upstleam of furnace.
2. Remove burner access and blower door.
3. Remove blower retaining screw (on blower shell:).
11
r
1
4.Removeco\erfi'omcontrolboxanddisconnectthermostat andpowerwiresfromtheboard
5_Slideblox_er_k_rwardonrailstm_ardfiontofunit_
6, Reverse items 1 through 5 to reoinstalt blower, Refer to wiring
diagram (Fig, 3 or 4) of these insmlctions or diagram located on inside of blower door to properly rewire unit,
Copyright 2003 CARRIER Corp. _ 7310 W. Morris St Indianapolis. IN 46231 58cma5si
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
B°°k 1h_ PC 101 catalog No. 535-80123 Printed in U.S.A. Form 58CMA-5SI Pg 12 11-03 Replaces: 58CMA-4SI
Tab 16al 8a
Loading...