Carolina TIMBER GLOW 24”, TIMBER GLOW 30” User Instructions

Page 1
CAROLINA TIMBER GLOW (24” & 30”)
VENT-FREE OR VENTED GAS LOGS
FOR NATURAL OR LIQUID PETROLEUM (L.P.)
WITH OPTIONAL HEAT SHIELD MODEL (19HS)
WARNING: If the following information in this manual is not followed exactly, a fire
-DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
-WHAT TO DO IF YOU SMELL GAS * Do not try to light any appliance. * Do not touch any electrical switch; do not use any phone in your building. * Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions. * If you cannot reach the gas supplier, call the fire department.
-Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
-This appliance is intended for supplemental heating.
This is an unvented and vented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate air for combustion and ventilation must be provided. Refer to Section V.
This appliance may be installed in an aftermarket, permanently located, manufactured (mobile) home, where not prohibited by local codes.
This appliance is equipped for (natural or propane) gas. Field conversion is not permitted.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
CAROLINA
New Buck Corporation P.O. Box 69 200 ETHAN ALLEN DRIVE Spruce Pine, NC 28777
Revised January 2013
Page 2
Page 3
TABLE OF CONTENTS
SECTION I: Safety Information ........................................................................................ 1
SECTION II: Residential Installation-Unvented Gas Logs ............................................. 4
Clearances ........................................................................................................................... 5
Gas Connection ................................................................................................................... 6
Preparing Log Kit ............................................................................................................... 6
Gas Pressure Check ............................................................................................................. 8
Lighting Instructions-Millivolt Valve (SIT) ....................................................................... 9
Flame Check ..................................................................................................................... 13
Heat Output ....................................................................................................................... 13
SECTION III: Installation-Heat Shield ............................................................................ 14
Wiring Diagram ................................................................................................................ 16
SECTION IV: Installation-After Market Mobile Home ................................................... 18
SECTION V: Producing Adequate Air For Combustion And Ventilation ....................... 18
Air For Combustion And Ventilation From Inside Building ............................................ 21
Air For Combustion And Ventilation From Outdoors ...................................................... 22
SECTION VI: Vented Logs .............................................................................................. 23
Important Safeguards ........................................................................................................ 25
Cleaning ............................................................................................................................ 25
Troubleshooting ................................................................................................................ 26
Servicing and Replacement Parts ...................................................................................... 31
Warranty ........................................................................................................................... 33
Owner Registration Card ................................................................................... Back Cover
Page 4
SECTION I
SAFETY INFORMATION
WARNINGS
IMPORTANT: READ THIS OWNER'S MANUAL CAREFULLY AND
COMPLETELY BEFORE TRYING TO ASSEMBLE, OPERATE, OR SERVICE THE APPLIANCE. IMPROPER USE OF THESE LOGS CAN CAUSE SERIOUS INJURY OR DEATH FROM BURNS, FIRE, EXPLOSION, AND CARBON MONOXIDE POISONING.
NOTE: When burning any unit or appliance that combust fuel for heat, such as
coal, oil, wood or natural and (L.P.) liquid petroleum gas. We highly recommend
Early signs of carbon monoxide poisoning resemble the flu, with headaches, dizziness, and/or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Turn off gas. Have burner serviced. Some people (such as pregnant women, persons with heart or lung disease, persons with anemia, those under the influence of alcohol, and those at high altitudes) are more affected by carbon monoxide than others. Make certain you understand and read all Warnings. Keep this manual for reference. It is your guide to safe and proper opera­tion of these logs.
1. Install log set only in a solid-fuel-burning masonry fireplace or U.L. listed pre­ fabricated fireplace constructed of non-combustible materials.
2. The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54.
3. This appliance may be installed in an After Market* Manufactured (Mobile) Home, where not prohibited by state or local codes. (* After Market: Completion of sale, not for purpose of resale from the manufacturer.)
NOTE: This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
NOTE: See Section IV for Mobile Home Installation and Section V for Air For Combustion And Ventilation.
IMPORTANT: VENT-FREE HEATERS ADD MOISTURE TO THE AIR. ALTHOUGH THIS IS BENEFICIAL, INSTALLING HEATER IN ROOMS WITHOUT ADEQUATE AIR FOR COMBUSTION AND VENTILATION MAY CAUSE MILDEW TO FORM FROM TOO MUCH MOISTURE.
4. Never install the log set:
-in a recreational vehicle.
-where curtains, furniture, clothing, or other flammable objects are less than 42" from the front of the heater.
-in high traffic areas or in windy areas. NOTE: These log sets comply with both the ANSI Z21.11.2a-2008 "Unvented Room Heater" and ANSI Z21.60b-2004 CGA 2.26b-2004 Decorative Appliance For "Solid Fuel Burning Fireplace".
WARNING: ANY CHANGE TO THIS HEATER OR ITS CONTROLS CAN BE DANGEROUS.
the use of smoke and carbon monoxide detectors in your home.
Page 1
Page 5
5. Two models are available. One specific model for propane (LP), and one for natural gas. Use the correct gas type for your home. This unit is not field convertible.
6. If these gas logs are for use with propane gas, do not place propane supply tank(s) inside any structure. Locate propane supply tank(s) outdoors.
7. If you smell gas:
-Shut off gas supply.
-Do not try to light any appliance.
-Do not touch any electrical switch; do not use any phone in your building.
-Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
-If you cannot reach your gas supplier, call the fire department.
8. This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate air for combustion and ventilation." See Section V “Producing Adequate Air For Combustion And Ventilation”, page 18.
9. Surface of gas logs becomes very hot when operating. Keep children and adults away from hot surface. Gas logs will remain hot for some time after shutdown. Allow surface to cool before touching.
10. Never place any objects on these gas logs.
11. These gas logs MUST NOT BE USED with glass doors in the closed position.
12. If equipped, fresh air damper must be closed.
13. Keep appliance area clean and free from combustible materials, gasoline, and other flammable vapors and liquids. Keep burner and control compartment clean. See installation and operating instructions accompanying heater.
14. If burner shuts off, do not relight until you provide fresh outside air. If burner keeps shutting off, have unit serviced.
15. An unvented room heater having input rating of more than 10,000 BTU per hour shall not be installed in a bedroom or bathroom.
16. Maintain clearance around air openings. WARNING
This appliance is equipped for (natural or propane) gas. Field conversion is not permitted.
Page 2
Page 6
17. Do not use the appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
18. Turn off the gas logs and let cool before servicing.
19. The logs are made of light weight refractory. When removing or replacing logs handle from the end of the log.
20. Make sure any safety screen or guard (if any) that was removed for servicing is in place before operating gas logs.
21. Strong drafts, such as a ceiling fan placed directly in front of the fireplace, may create sooting. Sooting may discolor walls.
22. Installation and repair should be done by a qualified service person. The heater and the gas logs should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding materials, etc. It is important that the control compartment, burners, and circulating air passageways of these gas logs be kept clean and clear.
23. Do not use these gas logs for burning trash or cooking. Never place matches, paper, garbage, or any other material on top of logs or into the flames.
24. Do not install or operate these gas logs in areas where impurities in the air exist (such as tobacco smoke and heavy cooking grease). Particles from impurities may discolor walls.
25. The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
26. The appliance must be isolated from the gas piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG.
27. Any outside air ducts and/or ash dumps in the fireplace shall be permanently closed at time of appliance installation.
28. Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
29. Do not place clothing or other flammable material on or near the appliance.
WARNING: State or local codes may only allow operation of this appliance in a vented configuration. Check your state on local codes.
Page 3
Page 7
16"
13"
10"
FIGURE 1
ANGLE MANTEL
MAX. OF 2 1/2"
21"
17"
14"
FLAT MANTEL
4" *
SECTION II
RESIDENTIAL INSTALLATION OF GAS LOGS
FIREPLACE PREPARATION
The fireplace needs to be prepared before installing the gas logs. A. Turn off the gas supply to the fireplace.
B. Any outside air ducts on the fireplace shall be permanently closed at the time of the appliance installation.
WARNING: BEFORE INSTALLING IN A SOLID FUEL BURNING FIREPLACE, THE CHIMNEY FLUE AND FIREBOX MUST BE CLEANED OF SOOT, CREOSOTE, ASHES AND LOOSE PAINT BY A QUALIFIED CHIMNEY CLEANER.
WARNING: DO NOT ALLOW FANS TO BLOW DIRECTLY INTO THE FIREPLACE. AVOID ANY DRAFTS THAT ALTER BURNER FLAME PATTERN.
LOCATION
Centrally locate the gas logs in the fireplace. Place them deep enough into the fireplace to accomplish adequate draft (if use as a vented gas log set is planned). Ensure that the front of the logs sit inside the front edge of the fireplace.
For your convenience, we have furnished two holes in the rear bottom bar of the burner base to fasten it to the floor if you deem it necessary.
NOTE: IF THE EXISTING FIREPLACE IS EQUIPPED WITH A SCREEN IT MUST BE IN PLACE WHEN THE APPLIANCE IS OPERATING. THE SCREEN SHALL HAVE ADEQUATE OPENING(S) FOR INTRODUCTION OF AIR FOR COMBUSTION AND VENTILATION.
NOTE: MAINTAIN PROPER CLEARANCE FOR PURPOSE OF SERVICING, PROPER INSTALLATION, AND OPERATION.
Mantel Minimum Clearances for a listed Zero Clearance Firebox or a Masonry Fireplace.
* WARNING: Canopy model number
MAPSFPC must be used at all times unless a 10-inch mantel is installed at 36-inches above the fireplace opening. (Can be obtained from your local dealer or purchased from the factory.)
Page 4
Page 8
WARNING: THIS APPLIANCE IS FOR INSTALLATION ONLY IN A SOLID
FUEL BURNING MASONRY OR UL127 FACTORY BUILT FIREPLACE OR IN A LISTED VENTLESS FIREBOX ENCLOSURE.
IT HAS BEEN DESIGN CERTIFIED FOR THESE INSTALLATIONS. EXCEPTION: DO NOT INSTALL THIS APPLIANCE IN A FACTORY BUILT FIREPLACE THAT INCLUDES INSTRUCTIONS STATING IT HAS NOT BEEN TESTED OR SHOULD NOT BE USED WITH UNVENTED GAS LOGS.
INSTALLATION AND CLEARANCES
To ensure a safe installation into an existing solid fuel burning fireplace, the following instructions must be carefully followed.
NOTE: Gas control knobs are located on right side facing unit.
1) Side wall Minimum Clearances: Clearance from the right and left side of the fireplace opening to any adjacent combustible wall should not be less than 10".
2) Ceiling Clearances: The ceiling height should not be less than 42" from the top of the fireplace opening.
3) Mantel Minimum Clearances: For clearances from top of heater to mantel or mantel supports see Figure 1.
4) Front Minimum Clearances: No objects should be placed within 24" from the front of the fireplace opening.
MINIMUM FIREPLACE DIMENSIONS FOR CAROLINA TIMBER GLOW LOG SET FOR SOLID FUEL BURNING FIREPLACE OR MASONRY FIREPLACE AND PREFAB OR MANUFACTURED FIREPLACES.
NOTE: When using logsets with the Model 19HS heat shield see page 28 for clearances.
MODEL HEIGHT OF WIDTH OF WIDTH AT DEPTH OF OPENING OPENING REAR FIREPLACE AT FRONT
24” Logs 17” 32” 26” 15” 30” Logs 17” 36” 28” 15”
WARNING: ANY CHANGE TO THIS HEATER OR ITS CONTROLS CAN BE
DANGEROUS.
WARNING: Cutting any sheet metal parts of the solid-fuel burning fireplace or
listed vent less firebox enclosure in which the unvented fireplace insert (log set) is to be installed is prohibited.
NOTE: Smoke shelves, shields and baffles may be removed if attached by mechanical fasteners. NOTE: Refractory, glass doors, screen rails, screen mesh and solid-fuel log grates (if applicable) can be removed from the fire place before installing the unvented fireplace insert. NOTE: Glass doors must be in the open position, and screens must be in place in the closed position when the appliance is in use.
Page 5
Page 9
GAS CONNECTION
Check gas type. Use only the type of gas indicated on the valve rating plate. If the type of gas listed on the plate is not your type of gas supply, DO NOT INSTALL. Contact your dealer for proper model. Always use an external regulator for all LP heaters to reduce the supply tank pressure to a maximum of 13" W.C. This is in addition to the regulator furnished with the heater.
Warning: Connection directly to an unregulated LP tank can cause an explosion.
The normal gas connection is 3/8" N.P.T. made at the right side facing the log set. If a left side connection is desired, the connecting pipe may be routed under the rear of the burner base to terminate at the right hand side for connection to the inlet of the valve. NOTE: The connecting pipe must be internally tinned copper tubing for use with natural gas. Test for leaks using a solution of soap and water after completing the connection. DO NOT
USE OPEN FLAME. NOTE: If the factory-built fireplace has no gas access hole(s) provided, an access hole of 1.5
inch (37.5mm) diameter or less may be drilled through the lower sides or bottom of the fire box in a proper workmanlike manner. This access hole must be plugged with non-combustible insulation after the gas supply line has been installed.
PREPARING LOG KIT
Open the cartons containing the Burner Base and the logs. Inside one of the cartons you will find the Burner Base. The logs are boxed separately.
MODEL
LOG PLACEMENT FOR CAROLINA TIMBER GLOW LOG SET:
1) Place rear log #1 on rear log supports. The log has alignment notches on each rear corner.
2) Place front log #2 on front bottom andirons. Center from side to side.
3) Next place middle log #3 in front of the rear burner tube and behind the front burner tube. The ends of the log are flat and will set on the base at each end. The face of the log is curved, so that the long goes down and just behind the front burner tube.
4) Last, place the top “V” log #4 on top of the middle log and the front log. The two (2) ends
of the “V” log should be setting on the front log and the other end should be pined on the
middle log. Solid fuels shall not be burned in the same fireplace where an unvented room heater has been installed. NOTE: The following label has been provided with this appliance and must be read and then attached to the floor of the fireplace or firebox area beneath the appliance. The label is a pill and stick label, make sure the area is cleaned before attaching the label to it.
CAROLINA TIMBER GLOW: 1)
Rear Log, 2) Front Log, 3) Middle Log, 4) Top “V” Log
WARNING: POSITIONING OF LOGS IS VERY CRITICAL (See Figure 2).
.
WARNING: This solid-fuel burning fireplace or listed ventless enclosure has been
converted for use with an unvented fireplace insert only. A solid-fuel burning fire­place cannot be used for burning wood or solid fuels unless all original parts have been replaced, and the fireplace re-approved by the authority having jurisdiction. A ventless firebox enclosure cannot be used with an unvented gas log unless all original parts have been replaced, and the ventless firebox enclosure re-approved by the au­thority having jurisdiction.
Page 6
Page 10
Log Placement For CAROLINA TIMBER GLOW Log Set (24” & 30”)
(1)
(4)
(3)
(2)
Figure 2
WARNING: Failure to position the parts in accordance with these diagrams or
failure to use only parts specifically approved with this heater may result in property damage or personal injury.
Page 7
Page 11
GAS PRESSURE CHECK
Check the inlet pressure to the burner to ensure that it is as shown in the table below. NOTE: The pressure check point is located on right side of valve facing the burner.
The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5kPa).
The appliance must be isolated from the gas supply piping system by closing its equipment shut­off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
MODEL CAROLINA TIMBER GLOW Gas Natural Propane (LP) Maximum Heat Input 40,000 40,000 Minimum Heat Input 29,000 29,000 Gas Inlet Pressure: Maximum 10.5 ins.W.C. 13.0 ins. W.C. Minimum 4.5 ins. W.C. 10.5 ins. W.C. Manifold Pressure 3.5 ins. W.C. 10.0 ins. W.C.
NOTE: On initial installation it may be required to bleed out air in the gas lines. Do this by holding the control knob and turning the knob to the pilot position for about 30 seconds.
The pressure should be checked with the heater burning and the control set on high. After measuring the pressure, close pressure tap screw, ensuring there are no leaks. Regulator pressure check screw is located above “OFF/ PILOT/ON” knob at right upper corner of valve.
WARNING
This appliance is equipped for (natural or propane) gas. Field conversion is not permitted.
Page 8
Page 12
OPERATING INSTRUCTIONS
Before operating this appliance, proceed through the following checklist.
1. Read and understand these instructions before operating this appliance.
2. Check that there are no gas leaks. If you smell gas do not attempt to light this appliance.
3. Verify that log placement is correct.
LIGHTING INSTRUCTIONS
SIT-MILLIVOLT VALVE
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
A. This appliance has a pilot which must be lit by hand. When lighting the pilot follow these
instructions exactly. If piezo fails, then light the pilot using matches. Refer to the match lighting instructions.
B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle to the floor.
WHAT TO DO IF YOU SMELL GAS: * Do not try to light any appliance. * Do not touch any electric switch; do not use any phone in your building. * Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. * If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it. Call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any or part of it has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Page 9
Page 13
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information on the reverse side of this label.
2. Make sure manual shutoff valve is fully closed, if equipped with thermostat, set to the lowest setting.
3. Turn off all electrical power to the appliance.
4. Push in gas control knobslightly and turn clockwise to the “OFF” position.
REMOTE CONTROL OR WALL THERMOSTAT
NOTE: Knob cannot be turned from “PILOT” to “OFF” unless knob is pushed in slightly. Do
not force..
5. Wait (5) five minutes to clear out any gas. Then smell for gas, including near the floor. If
you smell gas , STOP! Follow “B” in the safety information on the reverse side of this
label. If you don’t smell gas, go to the next step.
6. Find Pilot: follow metal tube from gas control. The pilot is located behind the rear burner tube and in front of the rear log. Fully open the manual shutoff valve.
7. Press in and turn knob on gas control counterclockwise to “PILOT” and continue pressing in the knob for (15) fifteen seconds.
8. With control knob pressed in , push down (in) and release the igniter button (igniter button
is located on the left hand side of the front of the appliance). This will light the pilot. If needed, keep repeating this step until pilot lights.
9. Keep control knob pressed in for (1) one minute after lighting pilot. After (1) minute,
release the control knob and it will pop back up. Pilot should remain lit. If pilot goes out, repeat steps 1 through 9.
If the knob does not pop up when released, stop and immediately call your service
technician or gas supplier.
Page 10
Page 14
* If the pilot will not stay lit after several tries, turn the gas control knob to “OFF” and call
your service technician or gas supplier.
10. Turn control knob counterclockwise to “ON”.
12. If using unit without wall thermostat place (Auto Off Manual)switch into the manual position. If using wall thermostat place Auto Off Manual Switch into the auto position and place thermostat to a setting higher than the room temperature.
13. Turn on all electrical power to the appliance.
14. Your heater is equipped with a HI & LO control. Turn clockwise for Low and counterclockwise for High.
15. Set thermostat to desired.
CAUTION
DO NOT TRY TO ADJUST HEATING LEVELS BY USING THE MANUAL SHUTOFF VALVE.
TO TURN OFF GAS TO APPLIANCE
SHUTTING OFF UNIT
1. If equip with thermostat set to lowest setting.
2. Turn control knob clockwise to the “OFF” .
3. Turn off all electric power to the appliance if service is to be performed.
SHUTTING OFF BURNER ONLY (Pilot stays lit.)
1. Turn control knob clockwise to the “PILOT” position.
CAUTION: Hot while in operation. Do Not Touch. Keep children, clothing, furniture,
gasoline, and other liquids having flammable vapors away.
CAUTION: DO NOT TRY TO ADJUST HEATING LEVELS BY USING THE
MANUAL SHUTOFF VALVE.
WARNING: Improper installation, adjustment, alteration, service or maintenance can
cause property damage, personal injury, or loss of life. Refer to owner’s information manual
provided with this appliance. Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
IMPORTANT: Always operate the appliance at the completely “ON” or the completely
“OFF” positions. Never use the heater at a setting between these positions as this can result in
improper combustion and excessive carbon monoxide emissions.
Page 11
Page 15
MANUAL LIGHTING PROCEDURE
1. If the pilot cannot be ignited with the piezo, it can be manually lit with the use of a paper
match and lighter rod.
2. Place the match in the holder and light. With the left hand, depress the control knob
counterclockwise to “PILOT”. Hold in.
3. Take rod and light match and ignite pilot. The pilot is located behind the right hand side of
the front log.
4. Continue to hold the control knob for an additional 1 (one) minute to ensure the pilot is lit.
Page 12
Page 16
BURNER & PILOT FLAME CHECK
A periodic check of the flames should be made. The pilot flame should always be present when the gas logs are in operation. See figure below.
Rear Flames: The flames at the rear should be yellow in color, and should extend about 4" to 5" above the large rear log for natural gas logs and about 6" for propane (LP) gas log sets.
Front Flame: The flame should be blue in color and sweeping from bottom of the middle log and producing a red glow on the lugs (burn area). NOTE: Allow approximately ten (10) minutes to achieve proper glow on middle log.
BURN PILOT
PROPER FLAME
PROPANE
NATURAL
WHEN USED AS A HEATING APPLIANCE
The heat output into the room can be controlled by the position of the flue damper, when used
as “vented gas logs”. See Section VI - Vented Models.
The heat output is controlled by the “ON/OFF” switch or wall thermostat, not by the control
knob. The gas logs are either “ON” or “OFF”.
The gas logs may be used as non-vent gas logs only where permitted by local state and city codes. If non-vent gas logs are not permitted, then the fireplace vent area required by local codes must be met. In the absence of local codes, the latest edition of the National Fuel Gas Code (ANSI
Z223.1) must be met.
HEAT OUTPUT
Page 13
Page 17
SECTION III
INSTALLATION OF LOGSET WITH
(OPTIONAL) HEAT SHIELD MODEL 19HS
For installation of gas supply see “Fireplace and Gas Connection” in Section II, page 8.
NOTE: Centrally locate the Heat Shield in the fireplace and place it deep enough into the fireplace to accomplish adequate draft (if use as a vented heater is planned). Ensure that the Heat Shield front is inside the front edge of the fireplace, see Figure 8. Using the screws and anchor provided, fasten the Heat Shield to the floor of the fireplace. On each side of floor frame of Heat Shield base, there is a “go through hole”. Position the Heat Shield as described above. Mark the hole for drilling. See Figure 8.
NOTE: When using Carolina Timber Glow Log Set with optional Heat Shield the following minimum fireplace dimensions must be met: 24” Logs Front 32”-Rear 26”-Height 20”-Depth 20 1/2” 30” Logs Front 36”-Rear 28”-Height 20”-Depth 20 1/2”
Blower Motor Floor Frame(s)
Mantel Figure 8
“Go Through Holes” for fastening the 19HS to the fireplace floor. Fireplace Heat Shield
To avoid any movement of the gas log set during operation, screw the base to the floor of the fireplace using the screws provided. Then follow log positioning in Section II.
NOTE: For the first few hours of burning, you will have a paint and burning smell. It is recommended to leave the fan off during this period. You may also want to raise a window or open the doors.
Figure 8
Area For Log Base Placement (Center)
Mantel
“Flush”
Page 14
Page 18
REPLACEMENT PARTS
For (OPTIONAL) HEAT SHIELD MODEL 19HS
Always include correct name, part number, and model number of the heater when ordering service parts.
KEY# PART DESCRIPTION PART NUMBER
1. BLOWER PE-A2-40-01.
Rating: .120 volts/60HZ/ .54 Amps
2. 110 THERMOSTAT PE 400132
3. CHROME SHIELD PO HS14
4. POWER CORD PE 400240
Page 15
Page 19
WARNING: CHILDREN AND ADULTS SHOULD BE ALERTED TO THE
MOTOR
THERMOSTAT
GREEN
JUMPER
WHITE
BLACK
JUMPER
JUMPER
POWER CORD
HAZARDS OF HIGH SURFACE TEMPERATURES AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION. YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THESE GAS LOGS.
WARNING: Clothing or other flammable material should not be placed on or near this
appliance.
NOTE: If any of the original wire as supplied with the appliance must be replaced, it must be replaced with a wire of at least a 105o C. temperature rating.
NOTE: Installation and repair should be done by a qualified service person. This heater should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments and circulating air passageways of the heater be kept clean.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.
WIRING DIAGRAM
(For Optional Heat Shield Model 19HS)
Page 16
Page 20
WARNING: ELECTRICAL GROUNDING INSTRUCTION: THIS APPLIANCE
IS EQUIPPED WITH A THREE-PRONG GROUNDING PLUG FOR YOUR PROTECTION AGAINST SHOCK HAZARD. IT SHOULD BE PLUGGED DIRECTLY INTO A PROPERLY GROUNDED THREE-PRONG RECEPTACLE.
WARNING: Do not use a blower insert, heat exchanger insert or other accessories
not approved for use with this heater.
WARNING: The motor is permanently lubricated. Do not add any type of lubri-
cant.
Page 17
Page 21
SECTION IV
AFTER MARKET MOBILE HOME
INSTALLATION
THIS APPLIANCE MAY BE INSTALLED IN AN AFTERMARKET*, PERMANENTLY LOCATED, MANUFACTURED (MOBILE) HOME, WHERE NOT PROHIBITED BY LOCAL CODES. *After Market: Completion of sale, not for the purpose of resale from the
manufacturer.
THIS APPLIANCE IS ONLY FOR USE WITH THE TYPE OF GAS INDICATED ON THE RATING PLATE. THIS APPLIANCE IS NOT CONVERTIBLE FOR USE WITH OTHER GASES.
NOTE: For mobile home installation follow “Residential Installation”, Section II, page 6.
SECTION V
PRODUCING ADEQUATE AIR FOR
COMBUSTION AND VENTILATION
This heater shall not be installed in a room or a space unless the required volume of indoor combustion air is provide by the method described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54, the International Fuel Gas Code, or applicable local codes.
The National Fuel Gas Code, ANSI Z223.1 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 BTU per hour (4.8m 3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 BTU per hour (4.8m 3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space.
WARNING: IF THE AREA IN WHICH THE HEATER MAY BE OPERATED DOES NOT MEET THE REQUIRED VOLUME FOR INDOOR COMBUSTION AIR, COMBUSTION AND VENTILATION AIR SHALL BE PROVIDED BY ONE OF THE METHODS DESCRIBED IN THE NATIONAL FUEL GAS CODE, ANSI Z223.1/NFPA 54, THE INTERNATIONAL FUEL GAS CODE, OR APPLICABLE CODES.
WARNING: IF THE AREA IN WHICH THE HEATER MAY BE OPERATED IS SMALLER THAN THAT DEFINED AS AN UNCONFINED SPACE OR IF THE BUILDING IS OF UNUSUALLY TIGHT CONSTRUCTION, PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR BY ONE OF THE METHODS DESCRIBED IN THE NATIONAL FUEL GAS CODE, ANSI Z223.1/NFPA 54 AIR FOR COMBUSTION AND VENTILATION, OR APPLICABLE LOCAL CODES.
Unusually tight construction is defined as construction where: a) Walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder
with a rating of 1 perm (6 x 10 b) Weather stripping has been added on openable windows and doors. c) Caulking or sealants are applied to areas such as joints around window and door frames,
between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.
-11
kg per pa-sec-m2) or less with openings gasketed or sealed.
Page 18
Page 22
NOTICE
SOME AREAS IN THE UNITED STATES HAVE HIGHER REQUIREMENTS FOR CUBIC FEET PER 1000 BTU/ HOUR INPUT. (EX. CINCINNATI, OHIO CODES REQUIRE 70 CUBIC FEET). CHECK YOUR LOCAL CODE BEFORE INSTALLATION.
DETERMINING FRESH-AIR FLOW FOR
HEATER LOCATION
DETERMINE IF YOU HAVE A CONFINED OR UNCONFINED SPACE
Use this worksheet to determine if you have confined or unconfined space.
SPACE: Includes the room in which you will install heater plus adjoining rooms with doorless passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x width x height). Length x Width x Height =_________cu.ft.(volume of space) EXAMPLE: 20 ft.(Length) x 16 ft.(Width) x 8 ft.(ceiling Height)= 2560 cu. ft. (volume of space) If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.
2. Divide the space volume by 50 cubic feet to determine the maximum BTU/Hr the
space can support.
_________(volume of space)/50 cu. ft. =maximum BTU/Hr the space can support)
EXAMPLE: 2560 cu. ft. (volume of space /50 cu. Ft .= 51.2 or 51200 (maximum BTU/Hr the space can support)
3. Add the BTU/Hr of all fuel burning appliances in the space.
Vent-free heater _______________BTU/Hr Gas water heater* _______________BTU/Hr Gas furnace _______________BTU/Hr Vented gas heater _______________BTU/Hr Gas fireplace logs _______________BTU/Hr Other gas appliances* + _______________BTU/Hr Total = _______________BTU/Hr
Page 19
Page 23
Example: Gas water heater 40000 BTU/Hr Vent-free heater + 18000 BTU/Hr Total = 58000 BTU/Hr
*Does not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
4. Compare the maximum BTU/Hr the space can support with the actual amount of BTU/Hr used. ____________BTU/Hr (maximum the space can support) ____________BTU/Hr (actual amount of BTU/Hr used) Example: 51200 BTU/Hr (maximum the space can support) 58000 BTU/Hr (actual amount of BTU/Hr used)
The space in the above example is a confined space because the actual BTU/Hr used is more than the maximum BTU/Hr the space can support. You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See “Air For Combustion And Ventilation From Inside Building”, page 35. B. Vent room directly to the outdoors. See “Air For Combustion And Ventilation From Outdoors”, page 36. C. Install a lower BTU/Hr heater, if lower BTU/Hr size makes room unconfined.
If the actual BTU/Hr used is less than the maximum BTU/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.
WARNING
YOU MUST PROVIDE ADDITIONAL
AIR FOR COMBUSTION AND VENTILATION IN A CONFINED SPACE
Page 20
Page 24
AIR FOR COMBUSTION AND VENTILATION
FROM INSIDE BUILDING
This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (See options 1 and 2, Figure
9). You can also remove door into adjoining room (See option 3, Figure 9).
WARNING
REWORK WORKSHEET, ADDING THE SPACE OF THE ADJOINING UNCONFINED SPACE. THE COMBINED SPACES MUST HAVE ENOUGH FRESH AIR TO SUPPLY ALL APPLIANCES IN BOTH SPACES.
NOTE: Each opening shall have a minimum free area of 1 square inch per 1000 BTUs per hour of the total input rating of all gas utilization equipment in the confined space, but not less than 100 square inch.
Figure 9
Page 21
Page 25
Ventilated Attic
Outlet Air
Inlet Air
Ventilated Crawl Space
To Crawl Space
To Attic
Outlet Air
Inlet Air
THIS HEATER MUST HAVE ADEQUATE AMOUNT OF AIR FOR PROPER OPERATION. IF NOT, POOR FUEL COMBUSTION COULD RESULT. READ THE FOLLOWING INSTRUCTIONS TO ENSURE PROPER AMOUNT OF AIR FOR THIS AND OTHER FUEL-BURNING APPLIANCES IN YOUR HOME.
Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air For Combustion and Ventilation for required size of ventilation grills or ducts.
IMPORTANT: Do not provide openings for inlet air into attic if attic has a thermostat­controlled power vent. Heated air entering the attic will activate the power vent.
WARNING
AIR FOR COMBUSTION AND VENTILATION
FROM OUTDOORS
Figure 10
Page 22
Page 26
SECTION VI
VENTED
(1) This appliance must be installed only in a solid-fuel burning fireplace with a working flue and constructed of non-combustible materials.
(2) A minimum of 34 sq. in. (Min. 6" chimney) , permanent flue opening must be provided by either the fireplace chimney or chimney damper to vent the flue gases.
(3) Solid fuels shall not be burned in a fireplace where a decorative appliance is installed. (4) Any chimney damper must be fixed in a manner which will maintain the minimum
permanent vent opening at all times.
Figure 11
NOTE: See chart on page 24.
MINIMUM FIREPLACE DIMENSIONS FOR CAROLINA TIMBER GLOW LOG SET FOR SOLID FUEL BURNING FIREPLACE OR MASONRY FIREPLACE AND PREFAB OR MANUFACTURED FIREPLACES.
MODEL HEIGHT OF WIDTH OF WIDTH AT DEPTH OF OPENING OPENING REAR FIREPLACE AT FRONT
CAROLINA 17” 34” 27” 15” TIMBER GLOW
WARNING: A fireplace screen must be in place when the appliance is operating and,
unless other provisions for combustion air are provided, the screen shall have an opening (s) for introduction of combustion air.
Page 23
Page 27
(5) See: GAS PRESSURE CHECK, page 8. (6) See: OPERATING INSTRUCTIONS, pages 9-12. (7) See: BURNER & PILOT FLAME CHECK, for proper flame pattern, page 13. (8) See: CLEANING INSTRUCTIONS, pages 13 and 25. NOTE: Visually check the pilot and burner flames annually, and monthly during seasons that
the appliance is operating frequently. See page 13. NOTE: The installation of appliances designed for manufactured home (US only) or mobile home installation must conform with the Standard CAN/CSA Z240 MH, Mobile Housing, in Canada, or with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the United States, or when such a standard is not applicable, ANSI/NCSBCS A225.1/ NFPA 501A, Manufactured Home Installations Standard.
WARNING: Do not use this appliance if any part has been under water. Immediately
call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
WARNING: Keep the appliance area clear and free from combustible materials, gaso-
line and other flammable vapors and liquids.
When using as a vented log set, refer to chart below to calculate minimum damper opening.
FOR MASONRY BUILT FIREPLACES, FREE OPENING AREA OF CHIMNEY DAMPER FOR VENTING COMBUSTION PRODUCTS FROM DECORATIVE APPLIANCES FOR INSTALLATION N SOLID FUEL BURNING FIREPLACES.
Appliance Input Rate (kBTU/hr)
20 30 40 50 60 70 80 90 100 110 120
Chimney
Minimum Opening** (sq. in.)
Height* (ft)
6 17.6 25.7 33.8 41.7 49.2 56.6 64.0 71.4 78.8 86.2 93.5
8 16.5 23.7 31.2 38.7 45.5 52.4 59.7 66.9 74.1 81.3 88.6 10 15.1 21.7 28.7 35.2 41.7 48.2 54.3 60.2 66.1 72.0 77.9 15 14.1 19.9 26.1 32.0 37.7 43.2 48.8 54.1 59.4 64.6 69.9 20 12.9 18.5 23.7 28.8 34.3 39.8 44.4 49.1 53.8 58.4 63.0 30 12.2 16.9 21.6 26.5 31.2 35.9 40.3 44.5 48.6 52.7 56.6
* Height is from hearth to top of chimney and the minimum height is 6 feet. ** Chart shows minimum opening (sq. in.) for a given height and input rate.
Page 24
Page 28
IMPORTANT SAFEGUARDS
Although your gas logs are very realistic in appearance, it is not a real burning fireplace and must not be used for burning solid fuel.
To avoid irreparable damage to the heater or personal injury, matches, paper, garbage, or any other material must not be placed or thrown on top of the logs or into the flames.
To avoid personal injury, do not touch hot surfaces when the heater is operating. Close supervision is necessary when the heater is being operated near children.
WARNING: IN THE EVENT OF THE LOG BEING REMOVED, CARE SHOULD BE
TAKEN TO NOT DAMAGE THE LOGS.
THE HEATER IS INTENDED FOR USE AS A GAS HEATER MOUNTED IN A VENTED OR VENT-FREE FIREPLACE AS DESCRIBED IN THESE INSTRUCTIONS. IT SHOULD NOT BE USED FOR ANY OTHER PURPOSE.
CLEANING
NOTE: An annual examination and cleaning of the venting system of the solid-fuel burning fireplace, must be done by a qualified agency.
CAUTION:BEFORE CLEANING OR MOVING LOGS OR OTHER PARTS
OF THE HEATER, BE SURE TO READ THE ABOVE SECTION ON “IMPORTANT SAFEGUARDS”.
All cleaning should be carried out when the heater is cold. Only limited cleaning will be required under normal use. Dusting the front of the base, the top of the piezo cover, or the control knob panel may be required occasionally. Do not use any cleaning fluids to clean the logs or any
other part of the heater.
If the flames show any unusual shapes or behavior, or if the burners fail to ignite properly, then the burner holes may require cleaning. If this occurs, it is preferable to contact your nearest dealer to get your heater serviced.
Alternatively, the heater can be cleaned by removing the top, front, and rear logs. Handle the logs gently so as not to damage them. Always lift each log by holding it carefully at each end. Use a vacuum cleaner to carefully remove dust and loose particles from the base, logs, and from around the burners.
WARNING: Failure to keep the primary air openings(s) of the burner(s) clean may
result in sooting and property damage.
Page 25
Page 29
TROUBLESHOOTING
WARNING
TURN OFF, UNPLUG HEATER AND LET COOL BEFORE SERVICING. ONLY A QUALIFIED SERVICE PERSON SHOULD SERVICE AND REPAIR HEATER.
CAUTION
NEVER USE A WIRE, NEEDLE, OR SIMILAR OBJECT TO CLEAN ODS/ PILOT. THIS CAN DAMAGE ODS/PILOT.
OBSERVED PROBLEM
When igniter button is pressed, there is no spark at ODS/PILOT
OBSERVED PROBLEM
When igniter button is pressed, there is spark at ODS/PILOT but no ignition
POSSIBLE CAUSE
1. Igniter electrode positioned incorrectly
2. Igniter electrode broken
3. Igniter electrode not connected to igniter cable
4. Igniter cable pinched or wet
5. Piezo igniter nut is loose
6. Broken igniter cable
7. Bad piezo igniter
POSSIBLE CAUSE
1. Gas supply turned off or manual shutoff valve is closed
2. Control knob not in “PILOT” position
3. Control knob not pressed in while in “PILOT” position
SOLUTION
1. Replace igniter
2. Replace igniter
3. Reconnect igniter cable
4. Free igniter cable if pinched by any metal or tubing. Keep igniter cable dry.
5. Tighten nut.
6. Replace piezo igniter cable
7. Replace igniter cable
SOLUTION
1. Turn on gas supply or open manual shutoff valve
2. Turn control knob to ”PILOT” position
3. Press in control knob while in “PILOT” position.
Page 26
Page 30
OBSERVED PROBLEM
ODS/PILOT lights but flame goes out when control knob is released
4. Air in gas lines when installed
5. Depleted gas supply
6. ODS/PILOTt is clogged
7. Gas regulator setting is not correct
POSSIBLE PROBLEM
1. Control knob is not fully pressed in
2. Control knob not pressed in long enough
3. Safety interlock system has been triggered (if equipped)
4. Manual shutoff valve not fully open
5. Thermocouple connection loose at control valve
6. Pilot flame not touching thermocouple, which allows thermocouple to cool, causing pilot flame to go out. This problem can be caused by one or both of the following:
A) low gas pressure B) dirty or partially
clogged ODS/PILOT
7. Control valve damaged
4. Continue to hold down control knob. Repeat igniting operation until air is removed.
5. Contact local propane gas company
6. Clean ODS/PILOTt or replace ODS/PILOTot assembly
7. Replace gas regulator
SOLUTION
1. Press in control knob completely
2. After ODS/PILOT lights keep control knob pressed 30 seconds
3. Wait 1 minute for safety interlock system to reset
4. Fully open manual shutoff valve
5. Hand tighten until snug, then tighten 1/4 turn
6. A) Contact local propane gas company
B) Clean ODS/PILOT (See
Cleaning and Maintenance), or replace ODS/PILOT assembly
7. Replace control valve
Page 27
Page 31
OBSERVED PROBLEM
Burner does not light after ODS/ PILOT is lit
Delayed ignition of burner
Burner backfiring during combustion
Slight smoke or odor during initial operation
Heater produces a whistling noise when burner is lit
POSSIBLE CAUSE
1. Burner orifice is clogged
2. Inlet gas pressure is too low
1. Manifold pressure is too low
2. Burner orifice is clogged
1. Burner orifice is clogged or damaged
2. Burner damaged
3. Gas regulator defective
1. Residues from manufacturing process
1. Turning control knob to “HI” position when burner is cold (if equipped with this type of valve)
2. Air in gas line
3. Air passageways on heater blocked
4. Dirty or partially clogged burner orifice
SOLUTION
1. Clean burner (see Cleaning and Maintenance) or replace burner orifice
2. Contact local propane gas company
1. Contact local propane gas company
2. Clean burner (see Cleaning and Maintenance) or replace burner orifice
1. Clean burner (see Cleaning and Maintenance) or replace burner orifice
2. Replace burner
3. Replace gas regulator
1. Problem will stop after a few hours of operation
1. Turn control knob to “LOW” position and allow to warm
for a minute
2. Operate burner until air is removed from line. Call local propane company to check gas line.
3. Observe minimum installation clearances
4. Clean burner or replace orifice
Page 28
Page 32
WARNING
IF YOU SMELL GAS: * SHUT OFF GAS SUPPLY * DO NOT TRY TO LIGHT APPLIANCE * DO NOT TOUCH ANY ELECTRICAL SWITCH; DO NOT USE ANY PHONE IN YOUR BUILDING * IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR’S PHONE. FOLLOW THE GAS SUPPLIER’S INSTRUCTIONS. * IF YOU CANNOT REACH YOUR GAS SUPPLIER, CALL THE FIRE DEPARTMENT.
IMPORTANT: Operating heater where impurities in the air exist may create odors. Cleaning supplies, paint, paint remover, cigarette smoke, cements and glues, new carpet or textiles, etc. create fumes. These fumes may mix with combustion air and create odors.
OBSERVED PROBLEM
Heater produces a clicking/ticking noise just after burner is lit or shut off
Heater produces unwanted odors
Heater shuts off in use (ODS operates)
Gas odor even when control knob is in OFF position
POSSIBLE CAUSE
1. Metal expands while heating or contracts while cooling
1. Heater burning vapors from paint, hair spray, glues, etc. (See Important above)
2. Low fuel supply
3. Gas leak (See WARNING above)
1. Not enough fresh air is available
2. Low line pressure
3. ODS/PILOT is partially clogged
1. Gas leak (See WARNING above)
2. Control valve defective
SOLUTION
1. This is common with most heaters. If noise is excessive, contact a qualified service person.
1. Ventilate room. Stop using odor causing products while heater is running.
2. Refill supply tank.
3. Locate and control all leaks.
See “Checking Gas
Connections”.
1. Open window/door for ventilation
2. Contact local propane company
3. Clean ODS/PILOT
1. Locate and correct all leaks (see Checking Gas Connections)
2. Replace control valve
Page 29
Page 33
OBSERVED PROBLEM
Gas odor during combustion
POSSIBLE CAUSE
1. Foreign matter between control valve and burner
2. Gas Leak. See “WARNING” statement at top of previous page
SOLUTION
1. Take apart gas tubing and remove foreign matter
2. Locate and correct all leaks (See “Checking Gas Connections”)
Page 30
Page 34
NOTE: You may want to have your chimney cleaned by a professional before installing unit.
SERVICING
Repair and replacement work should only be done by a qualified service person.
Always shut off the gas supply and make sure that heater is cool before beginning any service operation. Always check for gas leaks after servicing.
REPLACEMENT PARTS
A parts list with exploded view follows. Always include correct name, part number, and model number of the heater when ordering service parts.
KEY# PART DESCRIPTION PART NUMBER
SIT - MILLIVOLT
1. O.D.S. PILOT (L.P.) O.P. ASSEMBLY PE 8404C
1. O.D.S. PILOT (NAT) O.P. ASSEMBLY PE 8204C
2. GENERATOR ASSEMBLY
3. PILOT TUBE 3/16" MF 31612 ALMTUB
4. 12" GENERATOR WIRE
5. REAR BURNER PO RBTWM3 FRONT BURNER PO FBT003
6. INLET ELBOW
7. 3/8" COMP. NUT & SLEEVE PH 616 & PH 606
8. 3/8" BURNER SUPPLY TUBE
- 1 piece 6" PO T6-06
- 2 pieces 12" PO T6-12
9. 24" SWITCH WIRES PE 24JUMPER
10. CARLING SWITCH (AUTO/OFF/MANUAL) PE RC211RB
11. PIEZO STRIKER PE 124461
12. PIEZO 18" IGNITOR WIRE PE UL3573
13. MALE RUN TEE FITTING PH 64A-66
14. THERMO-COUPLE
15. MANIFOLD OUTLET CONNECTOR PH 68A-6C
16. ORIFICES L.P. REAR #53 PO 53 MVORF FRONT #56 PO 56 MVORF NATURAL REAR #49 PO 49 MVORF FRONT #41 PO 41 MVORF
17. 820 mv. S.I.T. VALVE LP - PE 820636 NAT - PE 820637 LEFT & RIGHT REAR AIR DEFLECTORS (NOT SHOWN) PST90015 OPTIONAL CANOPY (HOOD) MAPSFPC002
Page 31
Page 35
REV.
BY
M.B.DATE
10
12
9
15
11
13
8
16
7
17
6
5
14
3
4
Page 32
1
2
Page 36
NEW BUCK CORPORATION
P.O. BOX 69 ETHAN ALLEN DRIVE.
SPRUCE PINE, NC 28777
We reserve the right to amend these specifications at any time without notice. The only warranty applicable is our standard written warranty. We make no other warranty, expressed or implied.
LIMITED WARRANTY
VENT-FREE AND VENTED GAS LOGS
New Buck warrants this product to be free from defects in materials and components for two (2) years from the date of first purchase, provided that the product has been properly installed, operated and maintained in accordance with all applicable instructions. To make a claim under this warranty the Bill of Sale or canceled check must be presented.
This warranty is extended only to the original retail purchaser. This warranty covers only the cost of part(s) required to restore this heater to proper condition. Warranty part(s) MUST be obtained through authorized dealers of this product and/or New Buck who will provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty.The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit.
This warranty does not apply to parts that are not in original condition, because of normal wear and tear, or parts that fail or become damaged as a result of misuse, accidents, lack of proper maintenance or defects caused by improper installation.
What is not covered: * Removal and re-installation costs. * Labor costs for replacement or repairs. * Transportation or labor costs. * The cost of a service call to diagnose trouble. * Painted surfaces. * Damage or defect caused by improper installation, accident, misuse, abuse, or alteration.
TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT, THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND LIMITS THE DURATION OF ANY AND ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO ONE (1) YEAR FROM THE DATE OF FIRST PURCHASE. NEW BUCK LIABILITY IS HEREBY LIMITED TO THE PURCHASE PRICE OF THE PRODUCT AND NEW BUCK SHALL NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER INCLUDING INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Page 33
Page 37
Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation of incidental or consequential damages, so the above limitation on implied warran­ties, or exclusion or limitation on damages may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights that vary from state to state.
OWNER REGISTRATION CARD
The attached owner registration card must be completed in its entirety and mailed within 30 days from the date of installation in order for warranty coverage to begin to:
New Buck Corporation
P.O. Box 69
Spruce Pine, NC 28777
Email: info@buckstove.com PLEASE NOTE: The Owner Registration Card must contain the Authorized Carolina Timber Glow Dealer Number and the Certified Installer's number (if applicable) for warranty coverage to begin.
NAME_____________________________________________________________________
ADDRESS__________________________________________________________________
CITY_____________________________________STATE__________ZIP______________
CUSTOMER EMAIL ________________________________________________________
MODEL #__________________________________________________________________
SERIAL #_____________________DATE OF INSTALLATION______________________
INSTALLER'S NAME________________________________________________________
DEALER NAME______________________________________________________________