Multi-Gard Fiberglass is a multi-cell raceway system for bridge crossing
applications consisting of 20' overall lengths of either standard wall, heavy wall
or bullet resistant 4" fiberglass outer shell with 3 x 1 1/2" or 4 x 1 1/4" nominal pre-
lubed innerducts preinstalled. In addition, fixed bends with "cutthrough" resistant
engineered plastic innerducts are available along with many other accessories
for terminating, cable pulling, and cable blowing.
Features
• Preinstalled silicone lined PVC innerducts reduce coefficient of friction for
easy cable pulling or jetting.
• Anti-reversing gaskets on coupling body allow easy push in hard to pull
out sealing system.
• Jettable using high-speed air blowing systems.
• Oring gasket at base of bell reduces risk of water entering system.
• Inward tapering holes on coupling body give quick and easy innerduct
alignment.
• Marked innerduct and marked hole on coupling body ensure proper
innerduct alignment.
• Couplings in standard and slip sleeve reduce waste.
• Transition adapters to allow transition between different outerducts.
• Deep bell provides strong joint.
• Internal spacers keep innerducts straight.
• Staging materials to job site is simplified.
• Standard Wall .070" provides basic mechanical and UV protection.
• Heavy Wall .090" provides enhanced mechanical protection where
physical abuse might be experienced.
• Bullet Resistant .250" provides heavy duty protection.
20' Overall Length Fiberglass Multi-Cell with Bell
Part No.Description
MSSS4S-
020
MSSS3S-
020
MHSS4S-
020
MHSS3S-
020
MBSS4S-
020
MBSS3S-
020
4-Cell Standard
.070
3-Cell Standard
.070
4-Cell4.394.181.311.191140'338
3-Cell Heavy Wall
.090
4-Cell Bullet Res.
.250
3-Cell Bullet Res.
.250
Bell (A)
Dim.
4.314.141.311.191140'240
4.314.141.661.501140'253
4.394.181.661.501140'340
5.004.251.311.191140'450
5.004.251.661.501140'450
Outerduct
(B)Dim.
Innerduct Dim.
O.D.
Innerduct Dim.
I.D.
Pkg.
Qty
Wt. per 100 ft.
(lbs.)
Standard Multi-Gard supplied with grey and one white tracer innerduct. Add C for
multi-colored innerduct
(3-cell white/grey/orange) (4-cell white/orange/green/grey)
Multi-Gard fixed bends use the same coupling design as straight sections. All
bends are provided with engineered plastic innerducts to avoid rope cut-through
into adjacent innerducts.
Part No.DescriptionPkg. Qty. Wt. Ea.
M _ _ HN4S 4-cell 1.19 I.D.**
M _ _ HN3S 3-cell 1.50 I.D.**
Pos. 1
M = Multi-Cell
Pos. 2
Outerduct
Outerduct
S = Standard
H = Heavy Wall
B = Bullet Res.
Pos. 3 (A)
Degree
3 = 11 _
5 = 22 _
7 = 45
9 = 90
Pos. 4 Radius Pos. 5
H = 4ft.N = 4"
Pos. 6
Cells
4 = 4-Cell
3 = 3-Cell
Pos. 7
Innerduct
S = Smooth
Pkg Qty and Wt ea.
Epoxy Kits
Apply epoxy to plain end and bell before insertion for a water tight joint and to
avoid joint pull-out.
Termination kits allow for sealing inner and outerducts. Each kit contains
innerduct sealing plugs with tie rope. Standard terminators allow for end
terminations.
Part No.
4-Cell
MXT14 MXT13Terminator11.5
Product
Pos. 1
M = Multi-Cell X = Standard T = Terminator 1 = Standard w/ plugs
Part No.
3-Cell
Outerduct
Pos. 2
Description Pkg. Qty. Wt. ea.
Description
Pos. 3
Type
Pos. 4
Cells
Pos. 5
3 = 3-Cell
4 = 4-Cell
Couplings Fiberglass Multi-Cell
Couplings are provided in standard sleeve for joining two uninstalled plain ends
and slip couplings for repair of unoccupied Multi-Gard.
Transition adapters allow different outerducts to be coupled together while
maintaining same innerduct. (See PVC section for transitioning to PVC MultiGard.)
Part No.DescriptionPkg. Qty Wt. ea.
M _ A _ _ Transition Adapters**
Product
Pos. 1
M = Multi-Cell
Outerduct
Pos. 2Pos. 3
B = F/G BR
H = F/G HW
M = F/G Std.
A = Adapter R = Galv. Steel
Outerduct
Pos. 4
Cells
Pos. 5
3 = 3-Cell
4 = 4-Cell
Split Anchor Ring
Use split anchor rings on either side of support anchors to keep Multi-Gard
stationary.
Expansion Joints allow for thermal expansion and contraction of outerduct.
Fiberglass expansion joints are recommended every 150 feet on bridge crossing
applications.
Part No. DescriptionPkg. Qty. Wt. ea.
M _ EC4 4-Cell 6" Stroke**
M _ EC3 3-Cell 6" Stroke**
Pos. 1
Product
M = Multi-Cell
Pos. 2
Outerduct
S = Standard
H = Heavy Wall
B = Bullet Res.
X = Type C PVC
F = Type 40 PVC
Pos. 3Pos. 4
E = Expansion C = Coupling
Pos.5
Cells
4 = 4-Cell
3 = 3-Cell
Assembly Instructions
The Multi-Gard Fiberglass system is designed for easy assembly:
1. Place plain end of one 20' section into gasketed coupling body 1/2" to the
gasket depth of another 20' section.
2. Check for alignment and apply epoxy to outside of plain end.
3. Push sections together with a firm push by hand until plain end seats fully
into belled end.
25701 Science Park Drive
Cleveland, Ohio 44122
216-464-3400
1-800-3CARLON (322-7566)
www.carlon.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.