Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 121109 2
Rated input voltage 110/240
Voltage range
AC in 90 - 264VAC
DC in 120 - 375VDC
Rated input current 1.65A / 1.4A
Power dissipation 15W
Frequency range 47- 63 Hz
Internal Voltage Surge Protection
Varistor
(acc. to IEC61000-4-5)
Input Data
Input Fuse T3.15/250VAC internal
1)
Output Short Circuit fold forward
Rated Overload Protection 102 - 108%
Over voltage protection (auto recovery)
24.5V to 25.5V
Input Voltage Surge Protection
Varistor
Controls and Protections
Ambient temperature -25°C to 71°C
Derating (>61°C to +71°C) 2.5% / °C
Ambient humidity 20 to 95%RH
Storage -25°C to +85°C
Pollution degree 2
Protection degree IP20
Cooling Free air convection
General Data (@ nominal line, full load, 25°C )
Insulation voltage
Input / Output 3.000VAC / 4242VDC
Input / FG 1500VAC / 2121VDC
Insulation resistance 100MΩ min
Shock resistance acc. to IEC 60068-2-27
(15G, 11ms, 3 Axis, 6 Faces, 3 times for each Face)
Vibration resistance acc. to IEC 60068-2-6
(Mounting by rail: 10-500 Hz, 2G, along
X, Y, Z each Axis, 60 min for each Axis)
UL / cUL UL 508 Listed
UL 60950-1,
UL 1310 Class 2 Power
Recognized ISA 12.12.01
(Class I, Division 2, Groups
A, B, C and D in progress)
TUV EN 60950-1,
CB scheme
EN 61558-1,
EN 61558-2-17 (acc.to EN 60204)
Approvals and EMC
1)
Fuse not replaceable by user
Leakage Current
Input / Output 0.25mA
Input / FG 3.5mA
Inrush current
Vi= 115VAC 30A
Vi= 230VAC 60A
P. F.C . 0.7
Power ready
Threshold at start up
Min. 17.6VDC - Max.19.4VDC
(contact closed)
Contact rating at 60VDC 0.3A
Insulation 500VDC
Switching frequency
Min. 45kHz
Max. 60kHz
MTBF (Bellcore Issue 6@40°C), GB
493,000h
Altitude during operation 3.000m
Case material Plastic
Dimensions L x W x D 90 x 54 x 114mm
Weight 430g
CE EN 61000-6-3,
EN 55022 Class B,
EN 61000-3-2, EN 61000-3-3
EN 61000-6-2, EN 55024,
EN 61000-4-2 Level 4,
EN 61000-4-3 Level 3
EN 61000-4-4 Level 4,
EN 61000-4-5 L-N Level 3,
L / N-FG Level 4
EN 61000-4-6 Level 3,
EN 61000-4-8 Level 4,
EN 61000-4-11
ENV 50204 Level 2,
EN 61204-3
Switching Power Supply
Type SPD 90W
DIN rail mounting