Carlo Gavazzi SPD 5W Data Sheet

1 Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 3111
Output Performances
• Universal AC input full range
• Installation on DIN rail 7.5 or 15mm
• Short circuit protection
• Overload protection
• High efficiency
• LED indication for DC low
• Internal input filter
• CE, TUV approved and cULus Listed
Product De scrip tion
The Switching power supplies SPD series are specially designed to be used in all automation application where the installation is on a DIN rail
and compact dimensions and performance are a must.
Switching Power Supply Type SPD 5W DIN rail mounting
Optional FeaturesApprovals
Description Code
Spring connectors B
Line regulation ± 1% Load regulation ± 2% Minimum load 0 Turn on time (full resistive load) 1000ms max Transient recovery time 2ms Ripple and noise 50mVpp Output voltage accuracy ± 1% Temperature coefficient ± 0.03%/°C Hold up time Vi= 115VAC 30ms
Vi= 230VAC 130ms
Voltage fall time (I
0
nom) 150ms max
Output Data
Model Mounting ( D = Din rail ) Output voltage Output power Input Type Optional features
Input type: 1= single phase
Ordering Key
SP D 12 05 1 B
Rated continuous loading
5V Model
1.0A @ 5VDC/0.85A @ 5.75VDC
12V Model
0.42A @ 12VDC/0.36A @ 13.8VDC
15V Model
0.34A @ 15VDC/0.28A @ 17.25VDC
24V Model
0.21A @ 24VDC/0.17A @28.8VDC
Reverse voltage
5V Model VDC 7.5 12V Model VDC 18 15V Model VDC 22 24V Model VDC 35
Capacitor load 7000µF Voltage rise time at 150ms max
full resistive load
MODEL NO.
INPUT
VOLTAGE
OUTPUT
WATTAGE
OUTPUT
VOLTAGE
OUTPUT
CURRENT
EFF.
(min.)
EFF.
(typ.)
EFF.
(avg.)
Single Output Models
SPD05
90~264 VAC 5 WATTS + 5 VDC 1000 mA 67% 83% 69%
SPD12
90~264 VAC 5 WATTS +12 VDC 420 mA 70% 86% 72%
SPD24
90~264 VAC 5 WATTS +15 VDC 340 mA 70% 87% 72%
SPD48
90~264 VAC 5 WATTS +24 VDC 210 mA 70% 87% 72%
g
t
e
r
p
a
r
u
ü
a
f
t
B
Rheinland
Product Safety
T
d
y
e
p
v
e
o
r
a
p
p
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 03111 2
Rated input voltage 100 - 240VAC Voltage range
AC 90 - 265VAC DC 120 - 370VDC
Rated input current
(Vi : 115VAC, Io nom) Typ. 115mA
Max. 200mA
Inrush current
Vi= 115VAC 10A Vi= 230VAC 18A
Input Data
Switching Power Supply Type SPD 5W DIN rail mounting
Overload 110 – 135% Input fuse T2A/250VAC internal
1)
Output short circuit Hiccup mode
Controls and Protections
Ambient temperature -20°C to 71°C Derating (>61°C to +71°C) 2.5%/°C Ambient humidity 20 ~ 95%RH Storage -25°C to +85°C Protection degree IP20 Cooling Free air convection Insulation voltage
Input-Output
3.000VAC/4242VDC min
Input-FG
1.500VAC/2121VDC min
Insulation resistance I/O 100MΩ min (@ 500VDC)
General Data (@ nominal line, full load, 25°C )
Vibration resistance meet IEC 60068-2-6
(Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis)
Shock resistance meet IEC 60068-2-27
(15G, 11ms, 3 Axis, 6 faces, 3 times for each face)
UL / cUL UL508 listed, UL60950-1,
UL1310 Class 2 Power (only 5V, 12V w/o Class 2) Recognized, ISA 12.12.01 (Class 1, Division 2, Groups A, B, C and D)
TUV EN 60950-1, CB scheme CCC
GB4943, GB9254, GB17625.1
Norms and Standards
1)
Fuse not replaceable by user
Power dissipation
(Vi : 230VAC, Io nom)
5V Model 2.2W 12V Model 1.9W 15V Model 2.1W 24V Model 1.8W
Frequency range 47- 63Hz Leakage current
Input-Output 0.25mA Input-FG 3.5mA
Over voltage protection 125 - 145% Internal surge voltage protection
Varistor
(IEC 61000-4-5)
MTBF (Bellcore issue 6 @ 40°C, GB)
5V Model 802000 Hours 12V Model 805000 Hours 15V Model 808000 Hours 24V Model 812000 Hours
Case material Plastic: PC, UL94-V0 Pollution degree 2 Altitude 4850m Dimensions LxWxD mm(inch)
90(3.60)x22.5(0.89)x114(4.49)
Weight 120g
CE EN 61000-6-3, EN 55022
Class B, EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 L-Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3