Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 03111 2
Switching Power Supply
Type SPD 18W
DIN rail mounting
Overload 110 – 140%
Input Fuse T2A/250VAC internal
1)
Overvoltage Protection 125 – 145%
Controls and Protections
General data (@ nominal line, full load, 25°C )
Norms and Standards
1)
Fuse not replaceable by user
Output Short Circuit Hiccup mode
Internal surge voltage protection
Varistor
(IEC 61000-4-5)
Input data
Rated input voltage 100 - 240VAC
Voltage range
AC 90 - 264VAC
DC 120 - 375VDC
Rated input current
Vi: 115VAC, Io nom 335-500mA
Inrush current
Vi= 115VAC 10A
Vi= 230VAC 18A
Power dissipation
(Vi : 230VAC, Io nom)
5V Model 5.0W
12V Model 4.65W
15V Model 4.25W
24V Model 4.45W
Frequency range 47- 63Hz
Leakage current
Input-Output 0.25mA
Input-FG 3.5mA
Ambient temperature -20°C to 71°C
Derating (>61°C to +71°C) 2.5%/°C
Ambient humidity 20 ~ 95%RH
Storage -25°C to +85°C
Protection degree IP20
Cooling Free air convection
Insulation voltage
Input-Output
3.000VAC/4242VDC min
Input-FG
1.500VAC/2121VDC min
Insulation resistance I/O 100MΩ min (@ 500VDC)
MTBF (Bellcore issue 6 @ 40°C, GB)
5V Model 795000 Hours
12V Model 797000 Hours
15V Model 796000 Hours
24V Model 800000 Hours
Case material Plastic: PC, UL94-V0
Pollution degree 2
Altitude 2000m
Dimensions LxWxD mm(inch)
90(3.60)x22.5(0.89)x114(4.49)
Weight 150g
Vibration resistance meet IEC 60068-2-6
(Mounting by rail: 10-500Hz,
2G, along X, Y, Z each Axis,
60 min for each Axis)
Shock resistance meet IEC 60068-2-27
(15G, 11ms, 3 Axis, 6 faces,
3 times for each face)
UL / cUL UL508 listed, UL60950-1,
UL1310 Class 2 Power
(only 5V, 12V w/o Class 2)
Recognized, ISA 12.12.01
(Class 1, Division 2,
Groups A, B, C and D)
TUV EN 60950-1, CB scheme
CCC
GB4943, GB9254, GB17625.1
CE EN 61000-6-3, EN 55022
Class B, EN 61000-3-2,
EN 61000-3-3,
EN 61000-6-2,
EN 55024,
EN 61000-4-2 Level 4,
EN 61000-4-3 Level 3,
EN 61000-4-4 Level 4,
EN 61000-4-5 L-N Level 3,
L/N-FG Level 4,
EN 61000-4-6 Level 3,
EN 61000-4-8 Level 4,
EN 61000-4-11,
ENV 50204 Level 2,
EN 61204-3