Carlo Gavazzi SPD 10W Data Sheet

1 Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 03111
• Universal AC input full range
• Installation on DIN rail 7.5 or 15mm
• Short circuit protection
• Overload protection
• High efficiency
• LED indicator for DC power ON
• Power Ok output
• Internal input filter
• CE, TUV approved and cULus Listed
Product De scrip tion
The Switching power supplies SPD series are specially designed to be used in all automation application where the
installation is on a DIN rail and compact dimensions and performance are a must.
Switching Power Supply Type SPD 10W DIN rail mounting
Model Mounting ( D = Din rail ) Output voltage Output power Input Type Optional features
Input type: 1= single phase
Ordering Key
SP D 24 10 1 B
Output Performances
Optional Features
Approvals
Description Code
Spring connectors B
Line regulation ± 1% Load regulation ± 2% Minimum load 0 Turn on time (full resistive load) 1000ms Vi nom, Io nom with 3500µF 1500ms Transient recovery time 2ms Ripple and noise 50mVpp Output voltage accuracy + 1% Temperature coefficient ± 0.03%/°C Hold up time Vi= 115VAC 25ms
Vi= 230VAC 100ms
Voltage fall time (I
0
nom) 150ms max
Output Data
Rated continuous loading
5V Model
2A @ 5VDC/1.7A @ 5.75VDC
12V Model
0.84A@12VDC/0.72A@13.8VDC
15V Model
0.67A @ 15VDC/0.58A @ 17.25VDC
24V Model
0.42A @ 24VDC/0.34A @ 28.8VDC
Reverse voltage
5V Model 7.5VDC 12V Model 18VDC 15V Model 22VDC
24V Model 35VDC Capacitor load 3500µF Voltage rise time at 500ms
(full resistive load)
Vi nom, Io nom with 3500µF 150ms
Class I, Div 2 UL 1310 UL 60950-1
MODEL NO.
INPUT
VOLTAGE
OUTPUT
WATTAGE
OUTPUT
VOLTAGE
OUTPUT
CURRENT
EFF.
(min.)
EFF.
(typ.)
Single Output Models
SPD05
90~264 VAC 10 WATTS + 5 VDC 2000 mA 71% 73%
SPD12
90~264 VAC 10 WATTS +12 VDC 840 mA 73% 75%
SPD15
90~264 VAC 10 WATTS +15 VDC 670 mA 74% 76%
SPD24
90~264 VAC 10 WATTS +24 VDC 420 mA 74% 76%
T
B
Product Safety
y
p
a
Rheinland
e
g
t
e
r
p
a
r
u
ü
f
t
d
e
v
o
r
a
p
p
Specifications are subject to change without notice. Pictures are just an example. For special features and/or customization, please ask to our sales network. 03111 2
Switching Power Supply Type SPD 10W DIN rail mounting
Rated input voltage 100 - 240VAC Voltage range
AC 90 - 264VAC DC 120 - 375VDC
Rated input current
(Vi : 115VAC, Io nom) Typ. 200mA
Max. 300mA
Inrush current
Vi= 115VAC 10A Vi= 230VAC 18A
Input Data
Overload 110 – 145% Input fuse T2A/250VAC internal
1)
Output short circuit Hiccup mode
Controls and Protections
Ambient temperature -20°C to 71°C Derating (>61°C to +71°C) 2.5%/°C Ambient humidity 20 ~ 95%RH Storage -25°C to +85°C Protection degree IP20 Cooling Free air convection Insulation voltage
Input-Output
3.000VAC/4242VDC min
Input-FG
1.500VAC/2121VDC min
Insulation resistance I/O 100MΩ min (@ 500VDC)
General Data (@ nominal line, full load, 25°C )
Vibration resistance meet IEC 60068-2-6
(Mounting by rail: 10-500Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis)
Shock resistance meet IEC 60068-2-27
(15G, 11ms, 3 Axis, 6 faces, 3 times for each face)
UL / cUL UL508 listed, UL60950-1,
UL1310 Class 2 Power Recognized, ISA 12.12.01 (Class 1, Division 2, Groups A, B, C and D)
TUV EN 60950-1, CB scheme CCC
GB4943, GB9254, GB17625.1
Norms and Standards
1)
Fuse not replaceable by user
Power dissipation
(Vi : 230VAC, Io nom)
5V Model 4.0W 12V Model 3.4W 15V Model 3.3W
24V Model 2.8W Frequency range 47- 63Hz Leakage current
Input-Output 0.25mA
Input-FG 3.5mA
Over voltage protection 125-145% Internal surge voltage protection
Varistor
(IEC 61000-4-5)
MTBF (Bellcore issue 6 @ 40°C, GB)
5V Model 801000 Hours
12V Model 803000 Hours
15V Model 805000 Hours
24V Model 808000 Hours Case material Plastic: PC, UL94-V0 Pollution degree 2 Altitude 2000m Dimensions LxWxD mm(inch)
90(3.60)x22.5(0,89)x114(4.49)
Weight 120g
CE EN 61000-6-3, EN 55022
Class B, EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3, EN 61000-4-4 Level 4, EN 61000-4-5 L-Level 3, L/N-FG Level 4, EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11, ENV 50204 Level 2, EN 61204-3