A Solid State Relay family designed to switch
various loads such as heating elements, motors
and transformers.
The relay is capable of switching high voltages up to
600 VACrms. The built-in varistor secures transient
protection for heavy industrial applications.
For higher reliability and load cycle capability three
semiconductor power units are soldered directly
on to the direct copper bonded (DCB) substrate.
AC- or DC-controlled versions are available. Builtin LED status indication for applied control voltage
and overtemperature alarm (optional).
The series covers a range of load currents up to
75 AACrms.
Main features
• 3-phase Solid State Relay
• Zero switching
• Rated operational current: 3 x 25, 55 or 75 A
• Rated operational voltage: Up to 690 VAC
• Control voltage, 4-32 VDC or 24-275 VAC
• Integral snubber network
• Built-in varistor
• Over-temperature protection option with alarm output
• IP 10 back-of-hand protection
• LED indication of control input and over-temperature
EN 61000-4-5
Output, line to line: 1 kV (PC1)
Output, line to earth: 2 kV (PC1)
Input, line to earth: 2 kV (PC1)
EN 61000-4-11
0% for 0.5, 1 cycle (PC2)
40% for 10 cycles (PC2)
70% for 25 cycles (PC2)
EN 61000-4-11
0% for 5000ms (PC2)
EN 55011
Class A: from 30 to 1000 MHz
From 0.15 to 30 MHz
EN 55011
Class A (industrial) with lters
EN 60947-4-3
Class A (no ltering needed)
Note:
• Performance Criteria 1 (PC1): no degradation of performance or loss of function is allowed when the product is operated
as intended.
• Performance Criteria 2 (PC2): during the test, degradation of performance or partial loss of function is allowed. However
when the test is complete the product should return operating as intended by itself.
• Performance Criteria 3 (PC3): temporary loss of function is allowed, provided the function can be restored by manual
operation of the controls.
• Control input lines must be installed together to maintain products' susceptability to Radio Frequency interference.
RZ3A DS ENG09/02/2017
Carlo Gavazzi LTD
6
Page 7
Over
Over-temperature protection (option: ...P)
RZ3A
SSR Input*
Green LED
SSR Output
-temperature
sensing
Red LED
Alarm status
Over-temperature
detection
Over-temperature protection is ON
SSR output disabled
Closed
Open
20ms
*After over-temperature condition is removed, SSR can be reset by switching OFF the control input for more
than 20 ms and switching back ON: this will switch ON the SSR output
Heatsink selection
Thermal resistance [K/W] of RZ3..25
Load current [A]
25.00.440.340.230.120.01--92
22.50.620.490.370.240.12--80
20.00.840.690.540.400.250.10-68
17.51.120.950.780.600.430.250.0858
15.01.511.301.090.880.670.460.2547
12.52.061.801.541.271.010.750.4838
10.02.752.402.061.721.371.030.6929
7.53.833.352.872.391.911.430.9621
5.06.015.264.513.763.012.251.5013
2.512.6211.049.467.896.314.733.156
20304050607080
Ambient temp. [°C]
Power dissipation [W]
RZ3A DS ENG09/02/2017
Carlo Gavazzi LTD
7
Page 8
Thermal resistance [K/W] of RZ3 ..55
RZ3A
Load current [A]
55.00.290.230.170.110.05--164
50.00.360.290.220.160.090.02-148
45.00.440.360.290.210.140.06-133
40.00.540.460.370.290.200.120.03118
35.00.670.580.480.380.280.190.09103
30.00.850.740.620.510.390.280.1687
25.01.100.960.820.680.550.410.2773
20.01.381.211.040.870.690.520.3558
15.01.851.621.391.160.930.700.4643
10.02.802.452.101.751.401.050.7029
5.05.624.924.213.512.812.111.4014
2.511.269.858.457.045.634.222.827
20304050607080
Thermal resistance [K/W] of RZ3 ..75
Load current [A]
75.00.270.220.170.120.070.02-201
70.00.320.270.210.160.100.05-184
65.00.380.320.260.200.140.080.02167
60.00.440.380.310.250.180.110.05151
55.00.520.450.380.300.230.160.08136
50.00.620.540.450.370.290.210.12121
45.00.740.640.550.460.360.270.17106
40.00.870.760.650.540.430.320.2292
35.01.010.890.760.630.510.380.2579
30.01.211.060.910.760.600.450.3066
25.01.491.301.110.930.740.560.3754
20.01.901.671.431.190.950.710.4842
15.02.602.281.951.631.300.980.6531
10.04.013.513.012.512.011.501.0020
5.08.247.216.185.154.123.092.0610
20304050607080
Ambient temp. [°C]
Ambient temp. [°C]
Power dissipation [W]
Power dissipation [W]
Alarm output specications
Collector - emitter voltage35 VDC
Emitter - collector voltage6 VDC
Collector current50 mA
Delay time on reset20 ms
RZ3A DS ENG09/02/2017
Carlo Gavazzi LTD
8
Page 9
Regulation
ZC
ZC
ZC
Over Temp
Circuit
A1 (~) (+)
A2 (~) (-)
B1 (+)
B2 (-)
Control
Input
AC/DC
Alarm
Output
T1
T2
T3
L1
L2
L3
Output
A
Output B
Output C
Connection Diagrams
RZ3A
Fig. 1 Terminal wiringFig. 2 Common alarm wiring
Connection specications
Relay
Mounting screws
Mounting torque
Control terminal
Mounting screws
Mounting torque
Wire size
Power terminal
Mounting screws
Mounting torque
Wire size
M5
≤ 1.5 Nm
M4
≤ 0.5 Nm
Max: 2 x 2.5 mm2 (AWG14)
Min: 2 x 1 mm
2
M5
2.5 Nm
Max: 2 x 6 mm2 (AWG8)
Min: 2 x 1 mm
2
B1
B2
B1
B2
B1
B2
A1
A2
A1
A2
A1
A2
Logic
Input
RZ3A DS ENG09/02/2017
Carlo Gavazzi LTD
9
Page 10
Active LowActive High
Alarm output connection
Forward voltage ≤35 VDC
Reverse voltage ≤6 VDC
Through current ≤50mA
Alarm reset: interrupt control input for more than 20ms