Carlo Gavazzi RZ3A Catalog Page

Specifications are subject to change without notice (01.10.2003) 1
Rated operational Control Rated operational current voltage voltage 3 x 25 A 3 x 40 A 3 x 55 A 3 x 75 A
400 VACrms 5 VDC RZ3A40LD25 RZ3A40LD40 RZ3A40LD55 RZ3A40LD75
4-32 VDC RZ3A40D25 RZ3A40D40 RZ3A40D55 RZ3A40D75 24-275 VAC/24-50 VDC RZ3A40A25 RZ3A40A40 RZ3A40A55 RZ3A40A75
600 VACrms 5 VDC RZ3A60LD25 RZ3A60LD40 RZ3A60LD55 RZ3A60LD75
4-32 VDC RZ3A60D25 RZ3A60D40 RZ3A60D55 RZ3A60D75 24-275 VAC/24-50 VDC RZ3A60A25 RZ3A60A40 RZ3A60A55 RZ3A60A75
Notes
Switching Rated operational Rated operational Control Option mode voltage current voltage
A: Zero Switching 40: 400 VACrms 25: 3 x 25 AACrms LD: 5 VDC P: Over-
60: 600 VACrms 40: 3 x 40 AACrms D: 4-32 VDC temperature
55: 3 x 55 AACrms A: 24-275 VAC/24-50 VDC protection and 75: 3 x 75 AACrms alarm output
(available only for A and D input)
Selection Guide
Solid State Relay Number of poles Switching mode Rated opertional voltage Control voltage Rated opertional current Options
A Solid State Relay family designed to switch various loads such as heating ele­ments, motors and transform­ers. The relay is capable of switching high voltages up to 600 VACrms.
For higher reliability and load cycle capability three semi­conductor power units are sol­dered directly on to the direct copper bonded (DCB) sub-
strate. AC- or DC-controlled versions are available. Built-in LED sta­tus indication for applied con­trol voltage and over-tempera­ture alarm (optional). A version that can be controlled with 5 VDC @ 15 mA (max) is also available (LD).
The series covers a range of load currents up to 75 AACrms.
Solid State Relays Industrial, 3-Phase ZS Type RZ3A
• 3-phase Solid State Relay
• Zero switching
• Rated operational current: 3 x 25, 40, 55 or 75 A
• Rated operational voltage: Up to 600 VAC
• Control voltage 5 VDC, 4-32 VDC or 24-275 VAC
• Integral snubber networks
• Over-temperature protection option with alarm output
• IP 10 back-of-hand protection
• LED indication of control input and over-temperature alarm status
Ordering Key
Product Description
Type Selection
RZ 3 A 60 D 75 P
Rated insulation voltage
Input to output 4000 VACrms Output to case 4000 VACrms
Operating temperature -30° to +80°C (-22° to +158° F) Storage temperature -40° to +100°C (-40° to + 212° F) Junction temperature +125°C (+ 257˚F)
Thermal Specifications
Insulation
2 Specifications are subject to change without notice (01.10.2003)
RZ3A..25.. RZ3A..40.. RZ3A..55.. RZ3A..75..
Rated operational current
AC51 @ Ta=25°C 25 Arms 40 Arms 55 Arms 75 Arms
AC53a @ Ta=25°C 5 Arms 8 Arms 15 Arms 20 Arms Minimum operational current 150 mArms 150 mArms 150 mArms 150 mArms Rep. overload current t=1 s 37 Arms 60 Arms < 125 Arms < 150 Arms Non-rep. surge current
t = 10 ms
230 A
p
300 A
p
600 A
p
1000 A
p
Off-state leakage current < 3 mArms < 3 mArms < 3 mArms < 3 mArms I2t for fusing t = 10 ms 265 A2s 450 A2s 1800 A2s 6600 A2s Critical dI/dt @ 50 Hz 100 A/µs 100 A/µs 100 A/µs 100 A/µs On-state voltage drop 1.6 Vrms 1.6 Vrms 1.6 Vrms 1.6 Vrms Critical dV/dt off-state 500 V/µs 500 V/µs 500 V/µs 500 V/µs
RZ3A40.. RZ3A60..
Operational voltage ranges 24-440 VAC 42-660 VAC Non-rep. peak voltage 850 V
p
1200 V
p
Operational frequency range 45 to 65 Hz 45 to 65 Hz Overvoltage category III III Pollution degree 3 2 Approvals UL, cUL, CSA UL, cUL,CSA CE-marking Yes Yes
General Specifications
RZ3A
Input Specifications
RZ3A..LD.. RZ3A..D.. RZ3A..A..
Control voltage range 5 VDC 4-32 VDC 24-275 VAC/24-50 VDC Pick-up voltage 4.5 VDC 3.8 VDC 18 VAC/20 VDC Drop-out voltage 1.2 VDC 1.2 VDC 9 VAC/DC Input current
15 mA 23 mA 15 mA
Response time pick-up
Power output = 50 Hz 10 ms 10 ms 20 ms
Response time drop-out
Power output = 50 Hz 10 ms 10 ms 30 ms
All data at 25°C
Output Specifications
Over-temperature Protection (Option: ...P)
*After over-temperature condition is removed, SSR can be reset by switching OFF the control input for more than 20 ms and switching back ON: this will
*switch ON the SSR output
SSR Input
Green LED
Red LED
SSR Output
Alarm status
Over-temperature
sensing
Closed
Open
Over-temperature
detection
Over-temperature protection is ON
SSR output disabled
Loading...
+ 2 hidden pages