Carlo Gavazzi RSE..-B, RSE..-C, RSE..-CR1 T Series Models

59
CARLO GAVAZZI Automation Components Specifications are subject to change without notice.
Soft starting and stopping of 3-phase motors. Starting / stopping time and initial torque can be independently adjusted by built­in potentiometers. Switching of 1-phase transformers to minimise inrush current.
Soft Starter
Dimensions (mm) H x W x D Features
Control Specifications
Control input range
Max. input current
Rated insulation voltage Dielectric voltage Inpulse withstand volt.
Output Specifications
Rated operational current
Overload current profile
Operational voltage
General Specifications
Frequency range Ramp up / Ramp down Initial torque
Kick-start Ramp profiles Over-temp. protection Relay output
Connections Capacity max. power Capacity max. control Operating temperature Storage temperature Degree of protection Approvals/Marks
References
Motor Control: 3-phase/2-pole switching
Transformer switching: 1 pole switching
Types
* Other options available on request: Single pole up to 12 A/400 V/4.7 kW (RSE..-BS), Relay output on 25 A 400 V/15 kW (RSE..-C10).
Motor Control - Soft Start and Stop Transformer
2 Pole Switching Switching
RSE..-B RSE..-C RSE..-CR1 TSE..
80 x 90 x 103 User selected ramp profiles
A1-A2: 24-110VAC/DC A1-A3: 110-480VAC A1-A2: 12 mA A1-A3: 5 mA 630 Vm 2 kVrms 4 kV (1.2/50 µs)
AC53b: integral by­passing of semiconductor 25 A
25 A:AC-53b:4-3:120
127/220 Vrms [RSE22..] 230/400 Vrms [RSE40..] 227/480 Vrms [RSE48..] 346/600 Vrms [RSE60..]
50-60 Hz
0.5-20s / 0.5-20s 50%±5% on max. 5 % on min. 200 ms Pump compressor Yes Over-temperature End of ramp Wrong phase sequence Screw terminals 10 mm or 2x 6 mm
2.5 mm
-20°C to +50°C
-50°C to +85°C IP 20 CE - UL - CSA
25 A
RSE2225-CR1
(5.5 kW)
RSE4025-CR1
(11 kW)
RSE2485-CR1
(15 kW)
RSE6025-CR1
(15 kW)
80 x 45 x 103 Reduces inrush current
4-32 VDC
12 mA
AC51: <16 A AC51: >16 A with external thyristor module
90/135 Vrms [TSE.110.] 160/270 Vrms [TSE.230.] 280/440 Vrms [TSE.400.] 350/550 Vrms [TSE.480.]
45-65 Hz
Trasformer selector
Load can be single phase transformer with El-cut strip-wound core or toroidal core with any secondary load or it can be a parallel connection of different types of 1- phase transformers Screw terminals
2.5 mm
2.5 mm 0°C to +50°C
-50°C to +85°C IP 20 CE
16 A
TSE6-1A1113100 TSE6-1A2113100 TSE6-1A3113100 TSE6-1A4113100
30 A / 50 A / 63 A
TSE6-1A1213100 TSE6-1A2213100 TSE6-1A3213100 TSE6-1A4213100
80 x 90 x 103 Up to 11.0 kW at 400VAC
A1-A2: 24-110VAC/DC A1-A3: 110-480VAC A1-A2: 12 mA A1-A3: 5 mA 630 Vm 2 kVrms 4 kV (1.2/50 µs)
AC53b: integral by­passing of semiconductor 25 A
25 A:AC-53b:4-3:120
127/220 Vrms [RSE22..] 230/400 Vrms [RSE40..] 227/480 Vrms [RSE48..] 346/600 Vrms [RSE60..]
50-60 Hz
0.5-10s / 0.5-20s 50%±5% on max. 5 % on min. No General purpose Yes No
Screw terminals 10 mm or 2x 6 mm
2.5 mm
-20°C to +50°C
-50°C to +85°C IP 20 CE - UL - CSA
25 A
RSE2225-C
(5.5 kW)
RSE4025-C
(11 kW)
RSE4825-C
(15 kW)
RSE6025-C
(15 kW)
80 x 45 x 103 Up to 5.5 kW at 400VAC
A1-A2: 24-110VAC/DC A1-A3: 110-480VAC A1-A2: 12 mA A1-A3: 5 mA 630 Vm 2 kVrms 4 kV (1.2/50 µs)
AC53b: integral by­passing of semiconductor 3 A [RSE..03..] 12 A [RSE..12..] 3 A:AC-53b:3-5:30 12 A:AC-53b:3-5:180 127/220 Vrms [RSE22..] 230/400 Vrms [RSE40..] 227/480 Vrms [RSE48..] 346/600 Vrms [RSE60..]
50-60 Hz
0.5-7.5s / 0.5-10s 70-100% on max. 5 % on min. No General purpose No No
Screw terminals 2 x 2.5 mm x 4 2 x 2.5 mm x 4
-20°C to +50°C
-50°C to +85°C IP 20 CE - UL - CSA
3 A
RSE2203-B
(0.55 kW)
RSE4003-B
(1.1 kW)
RSE4803-B
(1.5 kW)
RSE6003-B
(2.2 kW)
12 A
RSE2212-B
(3.0 kW)
RSE4012-B
(5.5 kW)
RSE4812-B
(5.75 kW)
RSE6012-B
(0.55 kW)
60
Output module can be 200,400,480,600 VAC.
*Correct heatsink assembly required.
For further details please consult datasheet.
Dimensions (mm) H x W x D Features
Control Specifications
Control input range
Max. input current Control supply Max supply current
Output Specifications
Rated operational current
Operational voltage
General Specifications
Ramp up / Ramp down Initial torque Bypass contactor supply Connections Operating temperature Storage temperature Approvals/Marks
References
RSC..HD..+RSO... RSC..AA..+RSO... RZ3A RR2ITypes
Switching Reversing
Soft starting and stopping of 3-phase motors (RSC...+RSO..). Phase angle control of 3-phase heaters (RSC.AA..+RSO).
Switching and reversing (RZ.., RR..).
74 x 103 x 65 Output for external bypass contactor
10-32 VDC
1 mA 10-32 VDC 180 mA
AC53a: 5 Arms [RSO..25] 15 Arms [RSO..50] 30 Arms [RSO..90] 40 Arms [RSO..110]
150-250Vrms [RSO22..] 220-420Vrms [RSO40..] 400-510Vrms [RSO48..] 400-625Vrms [RSO60..]
0.5-30 s / 0.5-30 s 10-75% Vcc-8VDC@150mA max. Screw type with clamp
-20°C to +70°C
-40°C to +100°C CE - UL - CSA
Control module RSC-HD0M60 Output module: 400VAC 25A: RSO4025 (4kW*) 50A: RSO4025 (11kW*) 90A: RSO4025 (15kW*) 110A: RSO4025 (22kW*)
74 x 103 x 41 3-phase switching
4-32 VDC [RZ3A..D.] 5 VDC [RZ3A..LD.] 24-265 Vrms [RZ3A..D.] 23 / 15 /15 mA
AC51: 25 / 40 / 55 / 75 Arms AC53a: 5 / 8 / 15 / 20 Arms I2t for fusing (t=10 ms) 265/450/1800/6600 A2s 24-440Vrms [RZ3A..40.] 42-660Vrms [RZ3A..60.] 850 Vp [RZ3A..40.] 1200 Vp [RZ3A..60.]
3-phase,zero switching, built-in transient overvolt. protect.,LED status indic. Screw type with clamp
-30°C to +80°C
-40°C to +100°C CE - UL - CSA
25 A / 50 A / 75 A 3 x 400 Vrms: RZ3A40D.. RZ3A40LD.. RZ3A40A.. 3 x 600 Vrms: RZ3A60D.. RZ3A60LD.. RZ3A60A..
74 x 103 x 41 Reversing with interlock
10-40 VDC [RR2I..HAP] 90-140Vrms VDC [RR2I..LAP] 180-265 Vrms [RR2I..HAP]
35 / 29 /15 mA
AC51:
10 / 25 / 40 Arms AC53a:
1.5 / 3.5 / 6 Arms
I2t for fusing (t=10 ms)
72 / 265 / 450 A2s 120-440Vrms [RR2I..40.] 120-530Vrms [RR2I..48.] 1200 Vp [RR2I..40.] 1400 Vp [RR2I..48.
3-phase,built-in transient overvolt. protect.,interlock revers., LED status indic.
Screw type with clamp
-20°C to +70°C
-40°C to +100°C
CE - UL - CSA
10 A / 25 A / 40 A
2 x 400 Vrms:
RR2I4005.. (0.5kW)
RR2I4015.. (1.5kW)
RR2I4030.. (3.0kW)
2 x 480 Vrms:
RR2I4805.. (0.5kW)
RR2I4805.. (1.5kW)
RR2I4805.. (3.0kW)
74 x 103 x 65 User controlled analogue input
0-20 mA (A-input) 4-20 mA (B-input)
10-32 VDC 180 mA
AC53a: 5 Arms [RSO..25] 15 Arms [RSO..50] 30 Arms [RSO..90] 40 Arms [RSO..110]
150-250Vrms [RSO22..] 220-420Vrms [RSO40..] 400-510Vrms [RSO48..] 400-625Vrms [RSO60..]
User controlled User controlled
Screw type with clamp
-20°C to +70°C
-40°C to +100°C CE - UL - CSA
Control module RSC-AAM60 Output module: 400VAC 25A: RSO4025 (4kW*) 50A: RSO4025 (11kW*) 90A: RSO4025 (15kW*) 110A: RSO4025 (22kW*)
3-Phase Control Devices
Motor Control 3 Pole Switching
Loading...