Specifications are subject to change without notice (04.02.00) 1
• Zero switching AC Solid State Relay
• Direct copper bonding (DCB) technology
• LED indication
• Built-in varistor
• Input range: 5 - 32 VDC
• Rated operational current: 15 and 30 AACrms
• Rated operational voltage: 3 x 220, 400 and 480
VACrms
• Non-repetitive voltage: Up to 1200 Vp
• Opto-insulation: > 4000 VACrms
Product Description
Ordering Key
RN 3 A 40 D 30
The SOLITRON Solid State
Contactor is designed for
industrial heating and motor
control applications. The
Solid State Contactor is
capable of switching 3-phase
loads by using only 2 switching elements for loads up to
3 x 30 AACrms AC1 load in
Star (excl. Neutral) or Delta
connections. The Solid State
Contactor is designed for
DIN-rail mounting with inte-
grated heatsink and overvoltage protection. The heatsink
is moved to the front for optimal convection cooling in the
panel.
The contactor elements are
soldered directly to the direct
copper bonded substrate
(DCB-technology). DC control versions are availiable.
Built-in LED status indication
for applied control voltage.
Solid State Relay
Number of phases
Switching mode
Rated operational voltage
Control voltage
Rated operational current
Solid State Relays
3-Phase, 2 Pole
SOLITRON
With Integrated Heatsink
Type Selection
Rated operational Control voltage Rated operational
voltage current
22: 3 x 220 VACrms D: 5 to 32 VDC 15: 15 AACrms
40: 3 x 400 VACrms 30: 30 AACrms
48: 3 x 480 VACrms
Type Selection, 2 Pole
Rated operational Control voltage Rated operational current
voltage 3 x 15 AAC 3 x 30 AAC
22: 3 x 220 VAC rms 5-32 VDC RN3A22D15 RN3A22D30
40: 3 x 400 VAC rms 5-32 VDC RN3A40D15 RN3A40D30
48: 3 x 480 VAC rms 5-32 VDC RN3A48D15 RN3A48D30
2 Specifications are subject to change without notice (04.02.00)
General Specifications
Input Specifications
Output Specifications
Thermal Specifications
RN 3 A
RN3A22... RN3A40... R3A48...
Operational voltage range 24 - 265 VAC 42 - 440 VAC 42 - 530 VAC
Non-rep. peak voltage 650 Vp 800 Vp 1200 Vp
Varistor voltage 275 VAC 420 VAC 510 VAC
Zero voltage turn-on < 20 V < 20 V < 20 V
Operational frequency range 45 - 65 Hz 45- 65 Hz 45 - 65 Hz
Power factor > 0.5 > 0.5 > 0.5
CE-marking Yes Yes Yes
Norm fullfilled EN 50082-2 EN 50082-2 EN50082-2
Response time pick-up < 10 ms
Response time drop-out < 20 ms
Green LED indication Yes
Control voltage range 5-32 VDC
Pick-up voltage 4.5 VDC
Drop-out voltage 1 VDC
Input current @ 24 VDC < 10 mA
RN3A..D15 RN3A..D30
Rated operational current AC1, Ta = 30°C 3 x 15 AACrms 3 x 30 AACrms
AC1, Ta = 40°C 3 x 12.5 AACrms 3 x 25 AACrms
AC1, Ta = 50°C 3 x 11.5 AACrms 3 x 23 AACrms
AC1, Ta = 60°C 3 x 10 AACrms 3 x 20 AACrms
AC3, Ta = 30°C 3 x 6 AACrms 3 x 12 AACrms
Minimum operational current 200 mA 200 mA
Rep. overload current (t = 1 s) < 55 AACrms < 125 AACrms
Non-rep. surge current (t = 20 ms) 250 Ap 600 Ap
Off-state leakage current at
rated voltage and frequency < 6 mA < 6 mA
I2t for fusing (t = 10 ms) 310 A2s 1800 A2s
Critical dI/dt 100 A/ms 100 A/ms
On-state voltage drop at rated current < 1.6 Vrms < 1.6 Vrms
Critical dV/dt 500 V/ms 500 V/ms
Zero crossing detection Yes Yes
RN3A..D15 RN3A..D30
Operating temperature range -20° to + 70°C (-4° to + 158°F) -20° to + 70°C (-4° to + 158°F)
Storage temperature range -40° to + 100°C (-40° to + 212°F) -40° to + 100°C (-40° to + 212°F)
Junction temperature < 125 °C (257°F) < 125°C (257°F)