• Zero switching AC Solid State Relay
• Direct copper bonding (DCB) technology
• LED indication
• Built-in varistor
• Input range: 5 - 32 VDC
• Rated operational current: 15 and 30 AACrms
• Rated operational voltage: 3 x 220, 400 and 480
VACrms
• Non-repetitive voltage: Up to 1200 Vp
• Opto-insulation: > 4000 VACrms
Product Description
Ordering Key
RN 3 A 40 D 30
The SOLITRON Solid State
Contactor is designed for
industrial heating and motor
control applications. The
Solid State Contactor is
capable of switching 3-phase
loads by using only 2 switching elements for loads up to
3 x 30 AACrms AC1 load in
Star (excl. Neutral) or Delta
connections. The Solid State
Contactor is designed for
DIN-rail mounting with inte-
grated heatsink and overvoltage protection. The heatsink
is moved to the front for optimal convection cooling in the
panel.
The contactor elements are
soldered directly to the direct
copper bonded substrate
(DCB-technology). DC control versions are availiable.
Built-in LED status indication
for applied control voltage.
Solid State Relay
Number of phases
Switching mode
Rated operational voltage
Control voltage
Rated operational current
Solid State Relays
3-Phase, 2 Pole
SOLITRON
With Integrated Heatsink
Type Selection
Rated operational Control voltage Rated operational
voltage current
22: 3 x 220 VACrms D: 5 to 32 VDC 15: 15 AACrms
40: 3 x 400 VACrms 30: 30 AACrms
48: 3 x 480 VACrms
Type Selection, 2 Pole
Rated operational Control voltage Rated operational current
voltage 3 x 15 AAC 3 x 30 AAC
22: 3 x 220 VAC rms 5-32 VDC RN3A22D15 RN3A22D30
40: 3 x 400 VAC rms 5-32 VDC RN3A40D15 RN3A40D30
48: 3 x 480 VAC rms 5-32 VDC RN3A48D15 RN3A48D30

2 Specifications are subject to change without notice (04.02.00)
General Specifications
Input Specifications
Output Specifications
Thermal Specifications
RN 3 A
RN3A22... RN3A40... R3A48...
Operational voltage range 24 - 265 VAC 42 - 440 VAC 42 - 530 VAC
Non-rep. peak voltage 650 Vp 800 Vp 1200 Vp
Varistor voltage 275 VAC 420 VAC 510 VAC
Zero voltage turn-on < 20 V < 20 V < 20 V
Operational frequency range 45 - 65 Hz 45- 65 Hz 45 - 65 Hz
Power factor > 0.5 > 0.5 > 0.5
CE-marking Yes Yes Yes
Norm fullfilled EN 50082-2 EN 50082-2 EN50082-2
Response time pick-up < 10 ms
Response time drop-out < 20 ms
Green LED indication Yes
Control voltage range 5-32 VDC
Pick-up voltage 4.5 VDC
Drop-out voltage 1 VDC
Input current @ 24 VDC < 10 mA
RN3A..D15 RN3A..D30
Rated operational current AC1, Ta = 30°C 3 x 15 AACrms 3 x 30 AACrms
AC1, Ta = 40°C 3 x 12.5 AACrms 3 x 25 AACrms
AC1, Ta = 50°C 3 x 11.5 AACrms 3 x 23 AACrms
AC1, Ta = 60°C 3 x 10 AACrms 3 x 20 AACrms
AC3, Ta = 30°C 3 x 6 AACrms 3 x 12 AACrms
Minimum operational current 200 mA 200 mA
Rep. overload current (t = 1 s) < 55 AACrms < 125 AACrms
Non-rep. surge current (t = 20 ms) 250 Ap 600 Ap
Off-state leakage current at
rated voltage and frequency < 6 mA < 6 mA
I2t for fusing (t = 10 ms) 310 A2s 1800 A2s
Critical dI/dt 100 A/ms 100 A/ms
On-state voltage drop at rated current < 1.6 Vrms < 1.6 Vrms
Critical dV/dt 500 V/ms 500 V/ms
Zero crossing detection Yes Yes
RN3A..D15 RN3A..D30
Operating temperature range -20° to + 70°C (-4° to + 158°F) -20° to + 70°C (-4° to + 158°F)
Storage temperature range -40° to + 100°C (-40° to + 212°F) -40° to + 100°C (-40° to + 212°F)
Junction temperature < 125 °C (257°F) < 125°C (257°F)

Specifications are subject to change without notice (04.02.00) 3
Insulation
Rated insulation voltage
input to output 4000 VACrms
Rated insulation voltage
output to case 4000 VACrms
Dimensions
Dimensions with RHN1 (3x15 A)
(H x W x D) 120 x 45 x 110 mm
Dimensions with RHN2 (3x30 A)
(H x W x D) 120 x 90 x 110 mm
Housing Specifications
Mounting DIN - rail 35 mm
Weight with RHN1 470 g
Weight with RHN2 780 g
Housing material Glass reinforced Noryl
SE1GFN1
LED window material PC Lexan 141 R
Base plate Aluminium, nickel plated
Potting compound Polyurethane,
Casco Nobel
Terminals Screw with captive wire
clamp
Power and control terminals 4 mm
2
or 2 x 2.5 mm
2
AWG12 or 2 X AWG 14
Min. 0.5 mm2, AWG 20
Mounting torque max. 0.6 Nm
Heatsink compound used Dow Corning 340
Environment Specifications
Humidity max. 95%, no condensation
RN 3 A
Dimensions
4
120
45
33,7
103
71,6
37
30
20
70
60
4
120
93
72
45
89
103
71,6
37
20
70
30
60
Note: all dimensions in mm
Note: all dimensions in mm
RHN 1
RHN 2

4 Specifications are subject to change without notice (04.02.00)
RN 3 A
Applications
L1
L3
L2
T1
T2
T3
A2
A1
A2
L1
L2
L3
+A1
1
6
4
2
5
3
Economic switching of inductive and resistive Loads
3-phase 2 pole switching allows a very economical handling of heavy loads which
have to be run in a 3-phase configuration either as a star connection or a delta
connection of the loads. With 2-pole switching and the integration of a contactor
instead of switching all 3-phases a substancial space and cost saving in the panel
can be achieved as one third of the heatsinks can be taken out and also the ventilation of the panel can be reduced.
3-Phase, 2 pole Switching Principle
With SOLITRON RN.3.A.. 3-phase Relays switching with 2-poles and the integration of a contactor the electric configuration is splitted into a saftey part and a
control part. In the saftey part the isolation of the lkoad from the mains is assured
by a small contactor mounted in series with the Solid State Relay. The contactor
can be a very economical type as the switching is done by the Solid State Relay.
As the contactors are already switched, when the Solid State Relay is in control
of the power, no burning of the contacts will occur.
Wiring Diagram
3-phase, 2-pole RN...
Functional Diagram
3-phase, 2-pole RN...
+A1
-A2
Control
input
L1
T3
L3
T2
L2
T1
Accessories
Fuses
For further information refer to “General Accessories”.
Star Connection
Delta Connection
Safety
part
Control
part
L2
L1
+A
1
Control
input
-A2
T2
T1
L3
T3