Carlo Gavazzi RN 3 A 40 D 30 Catalog Page

Specifications are subject to change without notice (04.02.00) 1
• Zero switching AC Solid State Relay
• Direct copper bonding (DCB) technology
• LED indication
• Built-in varistor
• Input range: 5 - 32 VDC
• Rated operational current: 15 and 30 AACrms
• Non-repetitive voltage: Up to 1200 Vp
• Opto-insulation: > 4000 VACrms
Product Description
Ordering Key
RN 3 A 40 D 30
The SOLITRON Solid State Contactor is designed for industrial heating and motor control applications. The Solid State Contactor is capable of switching 3-phase loads by using only 2 switch­ing elements for loads up to 3 x 30 AACrms AC1 load in Star (excl. Neutral) or Delta connections. The Solid State Contactor is designed for DIN-rail mounting with inte-
grated heatsink and overvolt­age protection. The heatsink is moved to the front for opti­mal convection cooling in the panel. The contactor elements are soldered directly to the direct copper bonded substrate (DCB-technology). DC con­trol versions are availiable. Built-in LED status indication for applied control voltage.
Solid State Relay Number of phases Switching mode Rated operational voltage Control voltage Rated operational current
Solid State Relays 3-Phase, 2 Pole
SOLITRON
With Integrated Heatsink
Type Selection
Rated operational Control voltage Rated operational voltage current
22: 3 x 220 VACrms D: 5 to 32 VDC 15: 15 AACrms 40: 3 x 400 VACrms 30: 30 AACrms 48: 3 x 480 VACrms
Type Selection, 2 Pole
Rated operational Control voltage Rated operational current voltage 3 x 15 AAC 3 x 30 AAC
22: 3 x 220 VAC rms 5-32 VDC RN3A22D15 RN3A22D30 40: 3 x 400 VAC rms 5-32 VDC RN3A40D15 RN3A40D30 48: 3 x 480 VAC rms 5-32 VDC RN3A48D15 RN3A48D30
2 Specifications are subject to change without notice (04.02.00)
General Specifications
Input Specifications
Output Specifications
Thermal Specifications
RN 3 A
RN3A22... RN3A40... R3A48...
Operational voltage range 24 - 265 VAC 42 - 440 VAC 42 - 530 VAC Non-rep. peak voltage 650 Vp 800 Vp 1200 Vp Varistor voltage 275 VAC 420 VAC 510 VAC Zero voltage turn-on < 20 V < 20 V < 20 V Operational frequency range 45 - 65 Hz 45- 65 Hz 45 - 65 Hz Power factor > 0.5 > 0.5 > 0.5 CE-marking Yes Yes Yes Norm fullfilled EN 50082-2 EN 50082-2 EN50082-2
Response time pick-up < 10 ms Response time drop-out < 20 ms
Green LED indication Yes
Control voltage range 5-32 VDC Pick-up voltage 4.5 VDC Drop-out voltage 1 VDC Input current @ 24 VDC < 10 mA
RN3A..D15 RN3A..D30
Rated operational current AC1, Ta = 30°C 3 x 15 AACrms 3 x 30 AACrms
AC1, Ta = 40°C 3 x 12.5 AACrms 3 x 25 AACrms AC1, Ta = 50°C 3 x 11.5 AACrms 3 x 23 AACrms AC1, Ta = 60°C 3 x 10 AACrms 3 x 20 AACrms AC3, Ta = 30°C 3 x 6 AACrms 3 x 12 AACrms
Minimum operational current 200 mA 200 mA Rep. overload current (t = 1 s) < 55 AACrms < 125 AACrms Non-rep. surge current (t = 20 ms) 250 Ap 600 Ap Off-state leakage current at
rated voltage and frequency < 6 mA < 6 mA I2t for fusing (t = 10 ms) 310 A2s 1800 A2s Critical dI/dt 100 A/ms 100 A/ms On-state voltage drop at rated current < 1.6 Vrms < 1.6 Vrms Critical dV/dt 500 V/ms 500 V/ms Zero crossing detection Yes Yes
RN3A..D15 RN3A..D30
Operating temperature range -20° to + 70°C (-4° to + 158°F) -20° to + 70°C (-4° to + 158°F) Storage temperature range -40° to + 100°C (-40° to + 212°F) -40° to + 100°C (-40° to + 212°F) Junction temperature < 125 °C (257°F) < 125°C (257°F)
Specifications are subject to change without notice (04.02.00) 3
Insulation
Rated insulation voltage input to output 4000 VACrms
Rated insulation voltage output to case 4000 VACrms
Dimensions
Dimensions with RHN1 (3x15 A)
(H x W x D) 120 x 45 x 110 mm
Dimensions with RHN2 (3x30 A)
(H x W x D) 120 x 90 x 110 mm
Housing Specifications
Mounting DIN - rail 35 mm Weight with RHN1 470 g Weight with RHN2 780 g Housing material Glass reinforced Noryl
SE1GFN1
LED window material PC Lexan 141 R Base plate Aluminium, nickel plated Potting compound Polyurethane,
Casco Nobel
Terminals Screw with captive wire
clamp
Power and control terminals 4 mm
2
or 2 x 2.5 mm
2
AWG12 or 2 X AWG 14 Min. 0.5 mm2, AWG 20
Mounting torque max. 0.6 Nm Heatsink compound used Dow Corning 340
Environment Specifications
Humidity max. 95%, no condensation
RN 3 A
Dimensions
4
120
45
33,7
103
71,6
37
30
20
70
60
4
120
93
72
45
89
103
71,6
37
20
70
30
60
Note: all dimensions in mm
Note: all dimensions in mm
RHN 1
RHN 2
4 Specifications are subject to change without notice (04.02.00)
RN 3 A
Applications
L1
L3
L2
T1
T2
T3
A2
A1
A2
L1
L2
L3
+A1
1
6
4
2
5
3
Economic switching of inductive and resistive Loads
3-phase 2 pole switching allows a very economical handling of heavy loads which have to be run in a 3-phase configuration either as a star connection or a delta connection of the loads. With 2-pole switching and the integration of a contactor instead of switching all 3-phases a substancial space and cost saving in the panel can be achieved as one third of the heatsinks can be taken out and also the ven­tilation of the panel can be reduced.
3-Phase, 2 pole Switching Principle
With SOLITRON RN.3.A.. 3-phase Relays switching with 2-poles and the integra­tion of a contactor the electric configuration is splitted into a saftey part and a control part. In the saftey part the isolation of the lkoad from the mains is assured by a small contactor mounted in series with the Solid State Relay. The contactor can be a very economical type as the switching is done by the Solid State Relay. As the contactors are already switched, when the Solid State Relay is in control of the power, no burning of the contacts will occur.
Wiring Diagram
3-phase, 2-pole RN...
Functional Diagram
3-phase, 2-pole RN...
+A1
-A2
Control input
L1
T3
L3
T2
L2
T1
Accessories
Fuses For further information refer to “General Accessories”.
Star Connection
Delta Connection
Safety part
Control part
L2
L1
+A
1
Control
input
-A2
T2
T1
L3
T3
Loading...