Carlo Gavazzi RN 1 A 23 A 50 Catalog Page

Specifications are subject to change without notice (21.11.2003) 1
• AC Solid State Contactor, 1- and 2 poles
• Zero switching (RN1A) for heating and motor applications
• Instant-on switching (RN1B)
• Rated operational current: 1-pole: 30 A, 50 A and 63 A 2-pole: 2 x 15 A and 2 x 25 A
• Transient overvoltage protection built-in
• LED-indication
• IP 20 protection
• DIN-rail mountable
Product Description
Ordering Key
RN 1 A 23 A 50
The SOLITRON Solid State Contactor is designed for industrial heating and motor control applications.
The Solid State Contactor is capable of switching 1-, 2-, and 3-phase applications with loads up to 63 A AC51 load and up to 24 A AC53a load. The Solid State Con­tactor is designed for DIN­rail mounting with integrated heatsink and overvoltage
protection. The heatsink is moved to the front for optimal convection cooling in the panel. Cable ducting system will not stop the airflow.
The contactor elements are soldered directly on to the direct copper bonded sub­strate (DCB-technology). AC or DC controlled versions are available. Built-in LED status indication for applied control voltage.
Solid State Relay Number of poles Switching type
A: Zero switching B: Instant on switching
Rated operational voltage Control voltage Rated operational current
Solid State Relays 1- and 2 Pole SOLITRON With Integrated Heatsink
Type Selection, 1 Pole
Rated operational Control voltage Rated operational current voltage AC51: 30 A AC51: 50 A AC51: 63 A
AC53a: 6 A AC53a: 12 A AC53a: 24 A
230 VAC 5-32 VDC RN 1A23D30 RN 1A23D50 RN 1A23D63
5-32 VDC RN 1B23D30 RN 1B23D50 RN 1B23D63 24-230 ± 15% VAC/DC RN 1A23A30 RN 1A23A50 RN 1A23A63
400/480 VAC 5-32 VDC RN 1A48D30 RN 1A48D50 RN 1A48D63
5-32 VDC RN 1B48D30 RN 1B48D50 RN 1B48D63 24-230 ± 15% VAC/DC RN 1A48A30 RN 1A48A50 RN 1A48A63
Type Selection, 2 Pole
Rated operational Control voltage Rated operational current voltage AC51: 2 x 15 A AC51: 2 x 25 A
AC53a: 2 x 6 A AC53a: 2 x 12 A
230 VAC 5-32 VDC RN 2A23D30 RN 2A23D50
5-32 VDC RN 2B23D30 RN 2B23D50 24-265 VAC/DC RN 2A23A30 RN 2A23A50
400/480 VAC 5-32 VDC RN 2A48D30 RN 2A48D50
5-32 VDC RN 2B48D30 RN 2B48D50 24-265 VAC/DC RN 2A48A30 RN 2A48A50
2 Specifications are subject to change without notice (21.11.2003)
General Specifications
RN..23... RN..48...
Operational voltage range 24 to 265 VAC 42 to 530 VAC Non-rep. peak voltage 800 V
p
1200 V
p
Varistor voltage 275 VAC 510 VAC Operational frequency range 45 to 65 Hz 45 to 65 Hz Power factor at rated voltage ≥ 0.5 ≥ 0.5 Approvals UL, CSA UL, CSA CE-marking Yes Yes
Norms fulfilled EN 60947-1 Low-voltage switchgear and control gear. Part 1- General Rules
EN 61000-6-2 Generic Immunity Standard. Industrial Environment
Input Specifications
RN....D RN....A..
Rated control voltage range
RN1 5 to 32 VDC 24 to 265 VAC/DC
RN2 2 x 5 to 32 VDC 2 x 24 to 265 VAC/DC Pick-up voltage 4 VDC 14 VAC/DC Drop-out voltage 3 VDC 6 VAC/DC Reverse voltage max. 32 VDC ­Input current
RN1 < 9 mA < 12 mA
RN2 < 9 mA per pole < 12 mA per pole Response time
Pick-up time max. (50 Hz)
RN1A 10 ms 20 ms RN.B < 1 ms -
Drop-out time max. (50 Hz)
RN.A 10 ms 20 ms RN.B 10 ms -
Input-ON indication (LED, green) Yes Yes
Output Specifications
RN.....30 RN.....50 RN.....63
Rated operational current
RN1A.. AC51 @Ta=30°C 30 A 50 A 63 A
@Ta=40°C 30 A 50 A 50 A “ @Ta=50°C 23 A 38 A 40 A “ @Ta=60°C 20 A 30 A 30 A
AC53a @Ta=40°C 6 A 12 A 24 A
RN2A.. AC51 @Ta=30°C 2 x 15 A 2 x 25 A -
@Ta=40°C 2 x 15 A 2 x 25 A ­“ @Ta=50°C 2 x 11.5 A 2 x 19 A ­“ @Ta=60°C 2 x 10 A 2 x 15 A -
AC53a @Ta=40°C 2 x 6 A 2 x 12 A ­Zero crossing detection Yes Yes Yes Min. operational current 200 mA 200 mA 200 mA Rep. overload current t=1 s
(Tj init.=25°C) 55 AACrms 125 AACrms 150 AACrms
Non-rep. surge current t=10 ms
(Tj init.=25°C) 250 A
p
600 A
p
1000 A
p
Off-state leakage current, @ rated voltage and frequency
(Tj.=125°C, max.) < 1 mA < 1 mA < 1 mA
I2t for fusing t=1 to 10 ms 310 A2s 1800 A2s 5000 A2s Critical dV/dt off-state 500 V/µs 500 V/µs 500 V/µs
RN 1 A 23 A 50
Specifications are subject to change without notice (21.11.2003) 3
Thermal Specifications
RN.....30 RN.....50 RN.....63
Operational temperature -20 to +70°C (-4 to +158°F) -20 to +70°C (-4 to +158°F) -20 to +70°C (-4 to +1580F) Storage temperature
-40 to +100°C (-40 to +212°F) -40 to +100°C (-40 to +212°F) -40 to +100°C (-40 to +212°F)
Insulation
Rated impulse withstand voltage
Input to output 4000 V
imp
Rated impulse withstand voltage
Output to heatsink 4000 V
imp
Dimensions
Dimensions (H x W x D)
RN..30 120 x 45 x 110 mm RN..50 120 x 90 x 110 mm RN..63 120 x 90 x 110 mm
Housing Specifications
Mounting DIN-rail 35 mm Weight with RHN1 470 g Weight with RHN2 780 g Housing material Noryl SEI, GFN1, Black
LED window material PC Lexan 141R Base plate Aluminium, nickel-plated Potting compound Polyurethane, Casco Nobel Terminals Screw with captive wire
clamp
Control terminals nominal 4 mm
2
or 2 x 2.5 mm
2
AWG 12 or 2 x AWG 14
Min. 0.5 mm
2
, AWG 20 Mounting torque max. 0.6 Nm Power terminals nominal 10 mm
2
or 2 x 6 mm
2
AWG 6 or 2 x AWG 10
Min. 1 mm
2
, AWG 16
Mounting torque max. 2.0 Nm Heatsink compound used Electrolube HTS
Environment Specifications
Humidity max. 95%, no condensation
Wiring Diagrams
RN 1 A 23 A 50
1-pole RN...
2-pole RN...
Control input
Control input
Control input
L+/L A
1
~
- - - /
L-/L A
2
L
1
T
1
~
- - - /
~
- - - /
L+/L A
1
L-/L A
4
L
1
T
1
L
2
T
2
L-/L A
2
L+/L A
3
4 Specifications are subject to change without notice (21.11.2003)
RN 1 A 23 A 50
Functional Diagrams
1-pole RN...
2-pole RN...
Control input
L+/L
~
- - - /
L-/L
A
1
A
2
L
1
T
1
L
1
T
1
L
2
T
2
A
1
A
2
Control input 1
Control input 2
~
- - - /
~
- - - /
L+/L
L-/L
L+/L
L-/L
A
3
A
4
Applications
Single and double pole relay application Line-Neutral Line-Line
Double pole relay in 3-phase application Delta and star application (Economy Switch)
L
1
L2/N
L
1
L
2
L
3
Two single pole relays in 3-phase application Delta and star. (Economy Switch)
L
1
L
2
L
3
Terminal Layout
1-pole RN..
2-pole RN..
L
1
A
1
A
3
A
1
L
2
L
1
T
1
A
2
T
1
A
4
A
2
T
2
RN..30
Specifications are subject to change without notice (21.11.2003) 5
Applications (cont.)
RN 1 A 23 A 50
3 single pole relays in 3-phase application Delta, Star, Star with neutral
Single and double pole relay in 3-phase application Delta, Star, Star with neutral
Dimensions
L
1
L
2
L
3
N
L
1
L
2
L
3
N
4
120
45
33,7
103
71,6
37
30
20
70
60
4
120
93
72
45
89
103
71,6
37
20
70
30
60
Note: all dimensions in mm Note: all dimensions in mm