Specifications are subject to change without notice (30.09.2005) 1
Rated opera- Non-rep. Control Rated operational current
tional voltage voltage voltage 25A 50A 75A 100A
230VACrms 650V
p
3 - 32VDC RM1A23D25 RM1A23D50 RM1A23D75 RM1A23D100
20 to 280VAC RM1A23A25 RM1A23A50 RM1A23A75 RM1A23A100
22 to 48VDC
400VACrms 850V
p
4 - 32VDC RM1A40D25 RM1A40D50 RM1A40D75 RM1A40D100
20 to 280VAC RM1A40A25 RM1A40A50 RM1A40A75 RM1A40A100
22 to 48VDC
480VACrms 1200V
p
4 - 32VDC RM1A48D25 RM1A48D50 RM1A48D75 RM1A48D100
20 to 280 VAC RM1A48A25 RM1A48A50 RM1A48A75 RM1A48A100
22 to 48VDC
600VACrms 1400V
p
4 - 32VDC RM1A60D25 RM1A60D50 RM1A60D75 RM1A60D100
20 to 280VAC RM1A60A25 RM1A60A50 RM1A60A75 RM1A60A100
22 to 48VDC
• Zero switching (RM1A) or instant-on
switching (RM1B) AC Solid State Relay
• Direct copper bonding (DCB) technology
• LED indication
• Built-in varistor 230, 400, 480, 600V
• Clip-on IP 20 protection cover
• Self-lifting terminals
• Housing free of moulding mass
• 2 input ranges: 3-32* VDC and 20-280VAC/22-48VDC
• Operational ratings: Up to 100AACrms and 600VACrms
• Non-repetitive voltage: Up to 1400V
p
• Opto-insulation: > 4000VACrms
Product Description
The industrial, 1-phase relay
with antiparallel thyristor output is the most widely used
industrial SSR due to its multiple application possibilities.
The relay can be used for
resistive, inductive and
capacitive loads. The zero
switching relay switches ON
when the sinusoidal curve
crosses zero and switches
OFF when the current crosses zero. The instant-on relay
Solid State Relay
Number of poles
Switching mode
Rated operational voltage
Control voltage
Rated operational current
Ordering Key
Solid State Relays
with DC control input can be
used for phase control. The
built-in varistor secures transient protection for the heavy
industrial applications, and
the LED indicates the status
of the control input. The clipon cover is securing touch
protection to IP 20. Protected output terminals can handle cables up to 16mm
2
.
Type Selection
Switching mode Rated operational Control voltage Rated operational
voltage current
A: Zero Switching 23: 230VACrms A: 20-280VAC/22-48VDC 25: 25AACrms
B: Instant-on switching 40: 400VACrms D: 3-32VDC* 50: 50AACrms
(DC Control only) 48: 480VACrms
*4 to 32VDC for 400, 480 and 600VAC types 75: 75AACrms
60: 600VACrms
*4 to 32VDC for RM1B types 100: 100AACrms
Selection Guide
Industrial, 1-Phase ZS (IO) w. LED and Built-in Varistor
Types RM 23, RM 40, RM 48, RM 60
RM 1 A 23 D 25