Carlo Gavazzi RM1E Specifications

Page 1
Solid State Relays Industrial, 1-Phase Analog Switching Type RM1E
• AC Solid State Relay
• Analog switching (phase-angle control) for resistive and slightly inductive load applications
• 4 - 20mA or 0 -10V control input
• Rated operational current: 25, 50, 75, 100 and 125 AACrms
• Rated operational voltage: Up to 600 VACrms
• Variable intensity LED-indication according to input current
• Polarized lockable control connector for safe connection for voltage controlled version
RM1E..AA
RM1E..V
Product De scrip tion
The analog switching relay works in accordance with the phase angle control prin ci ple, i.e., the output switching point in the AC sine wave depends on the control input which can be either 4-20mA or 0-10VDC. 4 mA or 0VDC correspond to
zero output power whilst 20 mA or 10VDC correspond to full output power (near linear power response). The relay switches off every time the out­put cur rent cross es zero, and switches ON in ac cord ance with the ap plied control input.
Ordering Key
Solid State Relay Number of Poles Switching mode Rated operational voltage Control input Rated operational current
RM 1E 60 AA 50
Type Selection
Switching mode Rated operational Rated operational Control input voltage current
E: Analog switching 23: 230 VACrms* 25: 25 AACrms AA: 4 - 20 mADC 40: 400 VACrms 50: 50 AACrms V: 0-10VDC** 48: 480 VACrms 75: 75 AACrms 60: 600 VACrms 100: 100 AACrms 125: 125 AACrms
* For nominal operational voltage of 110VACrms, use RM1E23... ** RM1E..V.. require an external supply voltage
Selection Guide
Rated Blocking Control Rated operational current op. voltage voltage input 25 A 50 A 75A 100 A 125 A
230 VAC 650 Vp 4 - 20 mA RM1E23AA25 RM1E23AA50 RM1E23AA100 RM1E23AA125 0-10 VDC RM1E23V25 RM1E23V50 RM1E23V100 RM1E23V125 400 VAC 850 Vp 4 - 20 mA RM1E40AA25 RM1E40AA50 RM1E40AA100 480 VAC 1200 Vp 4 - 20 mA RM1E48AA25 RM1E48AA50 RM1E48AA75 RM1E48AA100 RM1E48AA125 0-10 VDC RM1E48V25 RM1E48V50 RM1E48V100 RM1E48V125 600 VAC 1400 Vp 4 - 20 mA RM1E60AA25 RM1E60AA50 RM1E60AA100 0-10 VDC RM1E60V25 RM1E60V50 RM1E60V100
General Spec i fi ca tions
RM 1E 23 ... RM 1E 40 ... RM 1E 48 ... RM 1E 60 ...
Operational voltage range RM1E..AA.. 90 to 280 VAC 340 to 460 VAC 200 to 550 VAC 410 to 660 VAC RM1E..V.. 90 to 265 VAC - 200 to 550 VAC 410 to 660 VAC
Blocking voltage 650 Vp 850 Vp 1200 V Operational frequency range 45 to 65 Hz 45 to 65 Hz 45 to 65 Hz 45 to 65 Hz Power factor > 0.75 > 0.75 > 0.75 > 0.75 Approvals CE-marking Yes Yes Yes Yes*
* Heatsink must be connected to ground for 600V types
Specifications are subject to change without notice (06.09.2017) 1
UR, cUR, CSA, EAC UR, cUR, CSA, EAC UR, cUR, CSA, EAC UR, cUR, CSA, EAC
p
1400 Vp
Page 2
RM1E
Output Spec i fi ca tions
RM1E...25 RM1E...50 RM1E...75 RM1E...100 RM1E...125
Rated operational current AC51 Ta=25 ˚C 25 AACrms 50 AACrms 75 AACrms 100 AACrms 125 AACrms AC53a Ta=25 ˚C 5 AACrms 15 AACrms 20 AACrms 20 AACrms 30AACrms Minimum operational current 150 mA 250 mA 400 mA 400 mA 500 mA Rep. overload current t=1s 55 AACrms 125 AACrms 150 AACrms 150 AACrms 200 AACrms Non-rep. surge current t=10ms 325 Ap 600 A
p
1150 Ap 1150 A
p
1900 A
p
Off-state leakage current < 3 mA < 3 mA < 3 mA < 3 mA < 3 mA I2t for fusing t= 10 ms 525 A2s 1800 A2s 6600 A2s 6600 A2s 18000 A²s Critical dV/dt off-state min. 1000 V/µs 1000 V/µs 1000 V/µs 1000 V/µs 1000 V/µs
Input Spec i fi ca tions
RM1E..AA.. Current controlled input
Control current range (A1-A2) 4-20 mADC Pick up current 4.2 mADC Drop out current 4.1 mADC Response time (input to output) ≤ 20 ms Voltage drop < 10 VDC @ 20 mA Dynamic impedance ≥ 330 Ω Max. allowable input current 50 mA Reverse polarity protected Yes
Note: The use of twisted pair cable for the control input is recommended
Output Power Dissipation
140
120
100
RM1E..V.. Voltage controlled input
Supply voltage, Vss (A3-A2) 24 VDC ±20% Max. supply current 15 mA @ 19.2 VDC
20 mA @ 30 VDC Control voltage, Vcc (A1-A2) 0-10VDC Pick up voltage 0.2 VDC Drop out voltage 0.1VDC Control input current 0.15 mA @10 VDC Response time (input to output) ≤ 20 ms Supply reverse protected Yes
RM1E..125
RM1E..100
80
60
Power dissipation in W
40
RM1E..25
20
0
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125
RM1E..50
RM1E.60..50
Load current per pole in AACrms
RM1E..75
2 Specifications are subject to change without notice (06.09.2017)
Page 3
RM1E
Electromagnetic Compatibility
Immunity EN60947-4-3
Electrostatic Discharge (ESD)
Immunity IEC/EN 61000-4-2
Air discharge, 8kV Performance Criteria 2
Contact, 4kV Performance Criteria 2
Electrical Fast Transient
(Burst) Immunity IEC/EN 61000-4-4
Output: 2kV, 5kHz Performance Criteria 1
Input: 1kV, 5kHz Performance Criteria 1 Electrical Surge Immunity IEC/EN 61000-4-5
Output, line to line, 1kV Performance Criteria 2
Output, line to earth, 1kV Performance Criteria 2
Output, line to earth, 2kV Performance Criteria 2 with external varistor
Input, line to line, 1kV Performance Criteria 2
Input, line to earth, 2kV Performance Criteria 2
EMC Emission EN60947-4-3
Radio Interference Voltage Emission (Conducted) IEC/EN 55011
0.15 - 30MHz Class A (industrial) with filters IEC/EN 60947-4-3 Class A (industrial) with filters
Radiated Radio Frequency Immunity IEC/EN 61000-4-3
10V/m, 80 - 1000 MHz Performance Criteria 1 10V/m, 1.4 - 2.0GHz Performance Criteria 1 3 V/m, 2.0 - 2.7GHz Performance Criteria 1
Conducted Radio Frequency Immunity IEC/EN 61000-4-6
10V/m, 0.15 - 80 MHz Performance Criteria 1
Voltage Dips Immunity IEC/EN 61000-4-11 0% for 0.5 , 1 cycle Performance Criteria 2 40% for 10 cycles Performance Criteria 2 70% for 25 cycles Performance Criteria 2 80% for 250 cycles Performance Criteria 2
Voltage Interruptions Immunity IEC/EN 61000-4-11 0% for 5000ms Performance Criteria 2
Radio Interference Field Emission (Radiated) IEC/EN 55011
30 - 1000MHz Class B
Notes:
- Control input lines must be installed together to maintain products’ susceptibility to Radio Frequency interference.
- Performance Criteria 1: No degradation of performance or loss of function is allowed when the product is operated as intended.
- Performance Criteria 2: During the test, degradation of performance or partial loss of function is allowed. However, when the test is complete the product should return operating as intended by itself.
- Performance Criteria 3: Temporary loss of function is allowed, provided the function can be restored by manual operation of the controls.
Specifications are subject to change without notice (06.09.2017) 3
Page 4
RM1E
X
X
X
X
X
Connection Specifications
Connection terminals L1, T1 A1, A2
Stripping length (X) 12 mm 8 mm
Connection Type M5 screw with captivated washer RM1E..AA..: M3 screw with captivated washer RM1E..V..: 3 pins, pitch 2.54mm square pin 0.64’ Accessory: RCS3-100-1 terminated cable
Rigid (solid & stranded) UR rated data 1x 2.5 - 6.0 mm² 2x 2.5 - 6.0 mm² 1x 0.5 - 2.5 mm² 2x 0.5 - 2.5 mm² 1x 14 - 10 AWG 2x 14 - 10 AWG 1x 18 - 12 AWG 2x 18 - 12 AWG
Flexible with end sleeve 2x 1.0 - 2.5 mm² 1x 1.0 - 4.0 mm² 2x 2.5 - 4.0 mm² 1x 0.5 - 2.5 mm² 2x 0.5 - 2.5 mm² 1x 18 - 12 AWG 2x 18 - 14 AWG 1x 18 - 12 AWG 2x 18 - 12 AWG 2x 14 - 12 AWG
Flexible without end sleeve 2x 1.0 - 2.5 mm² 1x 1.0 - 6.0 mm² 2x 2.5 - 6.0 mm² 1x 18 - 10 AWG 2x 18 - 14 AWG 2x 14 - 10 AWG
Torque specification Pozidrive 2 Pozidrive 1
2.4 Nm (21.2 lb-in) 0.5 Nm (4.4 lb-in)
Aperture for termination lug 12 mm 7.5 mm
X
Housing Specifications
Functional Di a gram
Weight 25 A, 50 A Approx. 60 g 75 A, 100 A, 125 A Approx. 100 g
A2(-)
Housing material Noryl, black Baseplate
IC
IO
25 A, 50 A Aluminium 75 A, 100 A, 125 A Copper, nickel-plated
A1(+)
Relay Mounting screws M5 Mounting torque 1.5-2.0 Nm
(Brown) A3(+)
(Black) A2(-)
IC
(Blue) A1(+)
IO
RM1E..AA..
RM1E..V..
4 Specifications are subject to change without notice (06.09.2017)
L1
T1
L1
T1
Page 5
RM1E
Thermal Spec i fi ca tions
Operating temperature -20° to +70°C Storage temperature
-20° to +100°C (-4˚ to +212 ˚F)
Junction temperature ≤125°C (257 ˚F)
(4˚ to +158 ˚F)
Isolation
Rated isolation voltage Input to output ≥ 4000 Vrms
Output to case ≥ 4000 Vrms
Heatsink Dimensions (load current versus ambient temperature)
With the output fully ON (360° conduction angle)
RM1E..25
Load current [A]
25.0 3.23 2.80 2.37 1.94 1.51 1.09
22.5 3.70 3.21 2.73 2.24 1.75 1.26
20.0 4.30 3.74 3.17 2.61 2.05 1.49
17.5 5.07 4.41 3.76 3.10 2.44 1.78
15.0 6.12 5.33 4.54 3.75 2.96 2.17
12.5 7.58 6.61 5.64 4.66 3.69 2.72
10.0 9.80 7.19 6.14 5.08 4.02 2.97
7.5 13.5 11.80 10.09 8.37 6.66 4.94
5.0 - 18.3 15.7 13.04 10.39 7.74
2.5 - - - - - 7
20 30 40 50 60 70
Thermal resistance [°C/W]
Ambient temp. [°C]
T
A
RM1E..50
Load current [A]
50.0 1.25 1.07 0.88 0.70 0.52 0.34
45.0 1.46 1.25 1.04 0.84 0.63 0.42
40.0 1.73 1.49 1.25 1.01 0.77 0.52
35.0 2.08 1.80 1.51 1.23 0.94 0.66
30.0 2.56 2.22 1.87 1.53 1.18 0.84
25.0 3.24 2.81 2.38 1.95 1.52 1.09
20.0 4.26 3.71 3.15 2.59 2.03 1.47
15.0 5.99 5.22 4.45 3.67 2.90 2.12
10.0 9.49 8.27 7.06 5.85 4.64 3.43
5.0 - 17.5 15.0 12.4 9.91 7.39
20 30 40 50 60 70
Thermal resistance [°C/W]
Ambient temp. [°C]
T
A
RM1.60..50
Load current [A]
50.0 0.99 0.81 0.63 0.44 0.26 0.08
45.0 1.28 1.07 0.86 0.65 0.44 0.23
40.0 1.64 1.40 1.15 0.91 0.67 0.42
35.0 2.11 1.82 1.54 1.25 0.96 0.67
30.0 2.60 2.25 1.90 1.55 1.20 0.85
25.0 3.30 2.86 2.43 1.99 1.55 1.11
20.0 4.36 3.79 3.22 2.65 2.08 1.51
15.0 6.1 5.4 4.6 3.77 2.97 2.18
10.0 9.76 8.52 7.3 6.0 4.8 3.54
5.0 -- -- 15.47 12.85 10.24 7.6
20 30 40 50 60 70
Thermal resistance [°C/W]
Ambient temp. [°C]
RM1E...75
Load current [A]
75.0 1.00 0.88 0.75 0.63 0.50 0.38
67.5 1.15 1.00 0.86 0.72 0.57 0.43
60.0 1.33 1.16 1.00 0.83 0.66 0.50
52.5 1.56 1.37 1.17 0.98 0.78 0.59
45.0 1.88 1.65 1.41 1.18 0.94 0.71
37.5 2.33 2.04 1.75 1.46 1.17 0.87
30.0 3.01 2.64 2.26 1.88 1.51 1.13
22.5 4.16 3.64 3.12 2.60 2.08 1.56
15.0 6.46 5.66 4.85 4.04 3.23 2.42
7.5 13.42 11.74 10.06 8.39 6.71 5.03
T
A
20 30 40 50 60 70
Thermal resistance [°C/W]
Ambient temp. [°C]
T
A
Specifications are subject to change without notice (06.09.2017) 5
Page 6
RM1E
29.6
28.9
58.2
47.5
44.8
12.3
5.2
2 x M5
1.84 Pitch 2.54
LED
Heatsink Dimensions (load current versus ambient temperature)
RM1E..100 RM1E..125
Load current [A]
Thermal resistance [°C/W]
Load current [A]
Thermal resistance [°C/W]
100.0 0.60 0.52 0.43 0.34 0.26 0.17
90.0 0.74 0.64 0.54 0.44 0.34 0.24
80.0 0.91 0.79 0.68 0.56 0.45 0.33
70.0 1.09 0.96 0.82 0.68 0.55 0.41
60.0 1.33 1.16 1.00 0.83 0.66 0.50
50.0 1.66 1.45 1.24 1.04 0.83 0.62
40.0 2.16 1.89 1.62 1.35 1.08 0.81
30.0 3.01 2.64 2.26 1.88 1.51 1.13
20.0 4.73 4.14 3.55 2.96 2.37 1.78
10.0 9.94 8.70 7.45 6.21 4.97 3.73
20 30 40 50 60 70
Ambient temp. [°C]
Dimensions
125.0 0.63 0.55 0.47 0.40 0.32 0.24
112.5 0.73 0.64 0.54 0.45 0.36 0.27
100.0 0.84 0.74 0.63 0.52 0.42 0.32
87.5 0.99 0.87 0.74 0.62 0.50 0.37
75.0 1.20 1.05 0.90 0.75 0.60 0.45
62.5 1.48 1.30 1.11 0.93 0.74 0.56
50.0 1.92 1.68 1.44 1.20 0.96 0.72
37.5 2.65 2.32 1.98 1.65 1.32 0.99
25.0 4.12 3.60 3.09 2.57 2.06 1.54
12.5 8.55 7.48 6.41 5.34 4.27 3.21
T
A
20 30 40 50 60 70
Ambient temp. [°C]
T
A
APPLY
HEATSINK
COMPOUND
RM1E..AA RM1E..V
All dimensions in mm All dimensions in mm
6 Specifications are subject to change without notice (06.09.2017)
Page 7
RM1E
Applications
RM1E..AA.. RM1E..V..
4 to 20 mA
I
in
A2
A1
L1 L1
U
line
T1 T1
Transfer Characteristics
Outout power as a function of control output
Control current (mA)
4 0 0
8 2.5 25
12 5 50
16 7.5 75
20 10 99
Control voltage (VDC)
Output power
This relay is suitable for control of heaters, lighting and slightly inductive loads such as small fans. The relay can also be used for soft turn-on of high-power incandescent lamps.
Heatsink Selection
Ordering Key
(Black) (Blue) (Brown)
0-10VDC
+24VDC
0V
A2 (GRD) A1 (Vcc) A3 (Vss)
U
line
RHS..
• Heatsinks and fans
• 5.40oC/W to 0.12oC/W thermal resistance
• DIN, panel or thru wall mounting
• Single or multiple SSR mounting
Heatsink Range Overview: http://www.productselection.net/PDF/UK/ssr_accessories.pdf
Heatsink Selector Tool: http://www.productselection.net/heatsink/heatsinkselector.php?LANG=UK
Specifications are subject to change without notice (06.09.2017) 7
Page 8
RM1E
Short Circuit Protection
Protection Co-ordination, Type 1 vs. Type 2:
Type 1 protection implies that after a short circuit, the device under test will no longer be in a functioning state. In type 2 co-ordination the device under test will still be functional after the short circuit. In both cases, however, the short circuit has to be interrupted. The fuse between enclosure and supply shall not open. The door or cover of the enclosure shall not be blown open. There shall be no damage to conductors of terminals and the conductors shall not separate from terminals. Therese shall be no breakage or cracking of insulating bases to the extent that the integrity of the mounting of live parts is impaired. Discharge of parts or any risk of fire shall not occur.
The product variants listed in the table hereunder are suitable for use on a circuit capable of delivering not more than 65,000A rms Symmetrical Amperes, 600Volts maximum when protected by fuses. Tests at 65,000A were performed with Class J, fast acting: please refer to the table below for maximum allowed ampere rating of the fuse. Use fuses only.
Co-ordination Type 1 (UL508)
Part No. Prospective short Max. fuse Class Voltage [VAC] circuit current [kArms] size [A]
RM1E..25.. 65 30 J / CC 600 RM1E..50.. 65 30 J 600
20 HSJ20 (Mersen*) 600 RM1E..75.. 65 100 J 600 RM1E..100.. 65 80 J 600 60 HSJ60 (Mersen*) 600 RM1E..125.. 65 125 J 600 60 HSJ60 (Mersen*) 600
Co-ordination Type 2 (IEC/EN60947-4-3)
Part No. Prospective short Max. fuse Brand Model Size circuit current [kArms] size [A]
RM1E.xx.25.. (xx =23,40,48) 10 25 Mersen* 6.9gRB 10-25 10.3 x 38 RM1E.60..25.. 10 20 Mersen* 6.9gRB 10-20 10.3 x 38 RM1E.xx.50.. (xx = 23,40) 10 50 Mersen* 6.9zz CP gRC 14x51/50 14 x 51 RM1E.xx.50.. (xx = 48,60) 10 50 Mersen* 6.9zz CP gRC 22x58/50 22 x 58 RM1E.xx.75.. (xx = 23,40,48,60) 10 63 Mersen* 6.9zz CP gRC 22x58/63 22 x 58 RM1E.xx.100.. (xx = 23,40,48) 10 100 Mersen* 6.9zz CP gRC 22x58/100 22 x 58 RM1E.xx.100.. (xx = 23,40,48) 10 80 Mersen* 6.9zz CP gRC 22x58/80 22 x 58 RM1E.xx.125.. (xx = 23 or 48) 10 125 Mersen* 6.921 CP URGD 27x60/125 27 x 60
zz = 00, without fuse trip indication zz = 21, with fuse trip indication
* Formerly Ferraz Shawmut
8 Specifications are subject to change without notice (06.09.2017)
Page 9
RM1E
Type 2 Protection with Miniature Circuit Breakers (M.C.B.s)
Solid State Relay ABB Model no. for ABB Model no. for Wire cross Minimum length of type Z - type M. C. B. B - type M. C. B. sectional area [mm2] Cu wire conductor [m]* (rated current) (rated current)
RM1E..25.. 1-pole
S201-Z4 (4A) S201-B2 (2A) 1.0 21.0 S201-Z6 UC (6A) S201-B2 (2A) 1.0 21.0
1.5 31.5
RM1E..50.. 1-pole
S201-Z10 (10A) S201-B4 (4A) 1.0 7.6
1.5 11.4
2.5 19.0
S201-Z16 (16A) S201-B6 (6A) 1.0 5.2
1.5 7.8
2.5 13.0
4.0 20.8
S201-Z20 (20A) S201-B10 (10A) 1.5 12.6
2.5 21.0
S201-Z25 (25A) S201-B13 (13A) 2.5 25.0
4.0 40.0
2-poles
S202-Z25 (25A) S202-B13 (13A) 2.5 19.0
4.0 30.4
RM1E..75.. 1-pole RM1E..100..
S201-Z20 (20A) S201-B10 (10A) 1.5 4.2
2.5 7.0
4.0 11.2
S201-Z32 (32A) S201-B16 (16A) 2.5 13.0
4.0 20.8
6.0 31.2
2-poles
S202-Z20 (20A) S202-B10 (10A) 1.5 1.8
2.5 3.0
4.0 4.8
S202-Z32 (32A) S202-B16 (16A) 2.5 5.0
4.0 8.0
6.0 12.0
10.0 20.0
S202-Z50 (50A) S202-B25 (25A) 4.0 14.8
6.0 22.2
10.0 37.0
RM1E..125.. 1-pole
S201-Z50 (50A) S201-B25 (25A) 4.0 4.8
6.0 7.2
10.0 12.0
16.0 19.2
S201-Z63 (63A) S201-B32 (32A) 6.0 7.2
10.0 12.0
16.0 19.2
* Between MCB and Load (including return path which goes back to the mains). Note: A prospective current of 6kA and a 230/400V power supply system is assumed for the above suggested specifications. For cables with different cross section than those mentioned above please consult Carlo Gavazzi’s Technical Support Group.
Specifications are subject to change without notice (06.09.2017) 9
Page 10
Environmental Information
The declaration in this section is prepared in compliance with People’s Republic of China Electronic Industry Standard SJ/ T11364-2014: Marking for the Restricted Use of Hazardous Substances in Electronic and Electrical Products.
Part Name Toxic or Harardous Substances and Elements
Lead
(Pb)
Power Unit Assembly x O O O O O
O: Indicates that said hazardous substance contained in homogeneous materials fot this part are below the limit require­ment of GB/T 26572.
X: Indicates that said hazardous substance contained in one of the homogeneous materials used for this part is above the limit requirement of GB/T 26572.
Mercury
(Hg)
Cadmium
(Cd)
Hexavalent
Chromium
(Cr(Vl))
Polybrominated biphenyls (PBB)
Polybrominated
diphenyl ethers
(PBDE)
环境特性
这份申明根据中华人民共和国电子工业标准 SJ/T11364-2014:标注在电子电气产品中限定使用的有害物质
零件名称 有毒或有害物质与元素
(Pb)
功率单元 x O O O O O
(Hg)
(Cd)
六价铬
(Cr(Vl))
多溴化联苯
(PBB)
多溴联苯醚
(PBDE)
O:此零件所有材料中含有的该有害物低于GB/T 26572的限定。
X: 此零件某种材料中含有的该有害物高于GB/T 26572的限定。
25
10 Specifications are subject to change without notice (06.09.2017)
Page 11
FASTON Terminals
Fork Terminals
• Faston tabs
• Tab dimensions accord­ing to DIN 46342 part 1
• Pure tin-plated brass
• Terminal adaptors for 35mm2 cable
• Type RM635FK
• Pack size: 10 pieces
Ordering Key
Screw mounted Faston terminals
RAM Solid State Relay Faston terminals Tab orientation
Input Tab width: 4.8mm Output Tab width: 6.3mm
Faston terminals in packs of 20
RS, RM Solid State Relay Tab orientation
Ordering Key
RM terminal adaptor Touch protected (optional)
RM1E48V25 F 4
RM48 F4
*
0: Flat (0º) 4: Angled (45º)
** 48: 4.8mm faston for input 63: 6.3mm faston for output
RM635FK P
Other Accessories
• Graphite thermal pad with adhesive on one side
• Type KK071CUT
• Dimensions: 35 x 43 x
0.25mm
• Packing quantity: 50pcs.
All accessories can be ordered pre-assembled with Solid State Relays. Other accessories include DIN rail adaptors, fuses, varistors and spacers.
For futher information refer to Accessories datasheets at: www.productselection.net/PDF/UK/SSR_Accessories.pdf
Specifications are subject to change without notice (06.09.2017) 11
• Touch safety cover
• Type RMIP20
• IP20 protection degree
• Pack size: 20 pieces
Loading...