• Variable intensity LED-indication according to input current
• Integral snubber network
• Polarized lockable control connector for safe connection for
voltage controlled version
RM1E..AA
RM1E..V
Product De scrip tion
The analog switching relay
works in accordance with the
phase angle control prin ci ple,
i.e., the output switching point
in the AC sine wave depends
on the control input which can
be either 4-20mA or 0-10VDC.
4 mA or 0VDC correspond to
zero output power whilst 20
mA or 10VDC correspond to
full output power (near linear
power response). The relay
switches off every time the output cur rent cross es zero, and
switches ON in ac cord ance
with the ap plied control input.
Ordering Key
Solid State Relay
Number of Poles
Switching mode
Rated operational voltage
Control input
Rated operational current
RM 1E 60 AA 50
Type Selection
Switching mode Rated operational Rated operational Control input
voltage current
RM 1E 23 ... RM 1E 40 ... RM 1E 48 ... RM 1E 60 ...
Operational voltage range
RM1E..AA.. 90 to 280 VAC 340 to 460 VAC 200 to 550 VAC 410 to 660 VAC
RM1E..V.. 90 to 265 VAC - 200 to 550 VAC 410 to 660 VAC
Blocking voltage 650 Vp 850 Vp 1200 V
Operational frequency range 45 to 65 Hz 45 to 65 Hz 45 to 65 Hz 45 to 65 Hz
Power factor > 0.75 > 0.75 > 0.75 > 0.75
Approvals
CE-marking Yes Yes Yes Yes*
* Heatsink must be connected to ground for 600V types
Specifications are subject to change without notice (06.09.2017) 1
Rated operational current
AC51 Ta=25 ˚C 25 AACrms 50 AACrms 75 AACrms 100 AACrms 125 AACrms
AC53a Ta=25 ˚C 5 AACrms 15 AACrms 20 AACrms 20 AACrms 30AACrms
Minimum operational current 150 mA 250 mA 400 mA 400 mA 500 mA
Rep. overload current t=1s 55 AACrms 125 AACrms 150 AACrms 150 AACrms 200 AACrms
Non-rep. surge current t=10ms 325 Ap 600 A
p
1150 Ap 1150 A
p
1900 A
p
Off-state leakage current < 3 mA < 3 mA < 3 mA < 3 mA < 3 mA
I2t for fusing t= 10 ms 525 A2s 1800 A2s 6600 A2s 6600 A2s 18000 A²s
Critical dV/dt off-state min. 1000 V/µs 1000 V/µs 1000 V/µs 1000 V/µs 1000 V/µs
Input Spec i fi ca tions
RM1E..AA..
Current controlled input
Control current range (A1-A2) 4-20 mADC
Pick up current 4.2 mADC
Drop out current 4.1 mADC
Response time (input to output) ≤ 20 ms
Voltage drop < 10 VDC @ 20 mA
Dynamic impedance ≥ 330 Ω
Max. allowable input current 50 mA
Reverse polarity protected Yes
Note: The use of twisted pair cable for the control input is recommended
Output Power Dissipation
140
120
100
RM1E..V..
Voltage controlled input
Supply voltage, Vss (A3-A2) 24 VDC ±20%
Max. supply current 15 mA @ 19.2 VDC
20 mA @ 30 VDC
Control voltage, Vcc (A1-A2) 0-10VDC
Pick up voltage 0.2 VDC
Drop out voltage 0.1VDC
Control input current 0.15 mA @10 VDC
Response time (input to output) ≤ 20 ms
Supply reverse protected Yes
Conducted Radio Frequency
Immunity IEC/EN 61000-4-6
10V/m, 0.15 - 80 MHz Performance Criteria 1
Voltage Dips ImmunityIEC/EN 61000-4-11
0% for 0.5 , 1 cycle Performance Criteria 2
40% for 10 cycles Performance Criteria 2
70% for 25 cycles Performance Criteria 2
80% for 250 cycles Performance Criteria 2
Voltage Interruptions Immunity IEC/EN 61000-4-11
0% for 5000ms Performance Criteria 2
Radio Interference
Field Emission (Radiated) IEC/EN 55011
30 - 1000MHz Class B
Notes:
- Control input lines must be installed together to maintain products’ susceptibility to Radio Frequency interference.
- Performance Criteria 1: No degradation of performance or loss of function is allowed when the product is operated as intended.
- Performance Criteria 2: During the test, degradation of performance or partial loss of function is allowed. However, when the test is complete the product
should return operating as intended by itself.
- Performance Criteria 3: Temporary loss of function is allowed, provided the function can be restored by manual operation of the controls.
Specifications are subject to change without notice (06.09.2017) 3
Page 4
RM1E
X
X
X
X
X
Connection Specifications
Connection terminalsL1, T1 A1, A2
Stripping length (X) 12 mm 8 mm
Connection Type M5 screw with captivated washer RM1E..AA..:M3 screw with captivated washer
RM1E..V..:3 pins, pitch 2.54mm square pin 0.64’
Accessory: RCS3-100-1 terminated cable
4 Specifications are subject to change without notice (06.09.2017)
L1
T1
L1
T1
Page 5
RM1E
Thermal Spec i fi ca tions
Operating temperature -20° to +70°C
Storage temperature
-20° to +100°C (-4˚ to +212 ˚F)
Junction temperature ≤125°C (257 ˚F)
(4˚ to +158 ˚F)
Isolation
Rated isolation voltage
Input to output ≥ 4000 Vrms
Output to case ≥ 4000 Vrms
Heatsink Dimensions (load current versus ambient temperature)
With the output fully ON (360° conduction angle)
RM1E..25
Load
current [A]
25.03.232.802.371.941.511.09
22.53.703.212.732.241.751.26
20.04.303.743.172.612.051.49
17.55.074.413.763.102.441.78
15.06.125.334.543.752.962.17
12.57.586.615.644.663.692.72
10.09.807.196.145.084.022.97
7.513.5 11.80 10.09 8.376.664.94
5.0-18.315.713.04 10.397.74
2.5-----7
203040506070
Thermal resistance
[°C/W]
Ambient temp. [°C]
T
A
RM1E..50
Load
current [A]
50.01.251.070.880.700.520.34
45.01.461.251.040.840.630.42
40.01.731.491.251.010.770.52
35.02.081.801.511.230.940.66
30.02.562.221.871.531.180.84
25.03.242.812.38 1.951.521.09
20.04.263.713.152.592.031.47
15.05.99 5.22 4.45 3.67 2.902.12
10.09.498.277.065.854.643.43
5.0-17.515.012.49.917.39
203040506070
Thermal resistance
[°C/W]
Ambient temp. [°C]
T
A
RM1.60..50
Load
current [A]
50.00.990.810.630.440.260.08
45.01.281.070.860.650.440.23
40.01.641.401.150.910.670.42
35.02.111.821.541.250.960.67
30.02.602.251.901.551.200.85
25.03.302.862.431.991.551.11
20.04.363.793.222.652.081.51
15.06.15.44.63.772.972.18
10.09.768.527.36.04.83.54
5.0----15.47 12.85 10.247.6
203040506070
Thermal resistance
[°C/W]
Ambient temp. [°C]
RM1E...75
Load
current [A]
75.01.000.880.750.630.500.38
67.51.151.000.860.720.570.43
60.01.331.161.000.830.660.50
52.51.561.371.170.980.780.59
45.01.881.651.411.180.940.71
37.52.332.041.751.461.170.87
30.03.012.642.261.881.511.13
22.54.163.643.122.602.081.56
15.06.465.664.854.043.232.42
7.513.42 11.74 10.068.396.715.03
T
A
203040506070
Thermal resistance
[°C/W]
Ambient temp. [°C]
T
A
Specifications are subject to change without notice (06.09.2017) 5
Page 6
RM1E
29.6
28.9
58.2
47.5
44.8
12.3
5.2
2 x M5
1.84
Pitch 2.54
LED
Heatsink Dimensions (load current versus ambient temperature)
RM1E..100RM1E..125
Load
current [A]
Thermal resistance
[°C/W]
Load
current [A]
Thermal resistance
[°C/W]
100.0 0.600.520.430.340.260.17
90.00.740.640.540.440.340.24
80.00.910.790.680.560.450.33
70.01.090.960.820.680.550.41
60.01.331.161.000.830.660.50
50.01.661.451.241.040.830.62
40.02.161.891.621.351.080.81
30.03.012.642.261.881.511.13
20.04.734.143.552.962.371.78
10.09.948.707.456.214.973.73
203040506070
Ambient temp. [°C]
Dimensions
125.0 0.630.550.470.400.320.24
112.5 0.730.640.540.450.360.27
100.0 0.840.740.630.520.420.32
87.50.990.870.740.620.500.37
75.01.201.050.900.750.600.45
62.51.481.301.110.930.740.56
50.01.921.681.441.200.960.72
37.52.652.321.981.651.320.99
25.04.123.603.092.572.061.54
12.58.557.486.415.344.273.21
T
A
203040506070
Ambient temp. [°C]
T
A
APPLY
HEATSINK
COMPOUND
RM1E..AARM1E..V
All dimensions in mmAll dimensions in mm
6 Specifications are subject to change without notice (06.09.2017)
Page 7
RM1E
Applications
RM1E..AA..RM1E..V..
4 to
20 mA
I
in
A2
A1
L1L1
U
line
T1T1
Transfer Characteristics
Outout power as a function of control output
Control current (mA)
400
82.525
12550
167.575
201099
Control voltage (VDC)
Output power
This relay is suitable for control of heaters, lighting and
slightly inductive loads such as small fans. The relay can also
be used for soft turn-on of high-power incandescent lamps.
Heatsink Selection
Ordering Key
(Black)
(Blue)
(Brown)
0-10VDC
+24VDC
0V
A2 (GRD)
A1 (Vcc)
A3 (Vss)
U
line
RHS..
• Heatsinks and fans
• 5.40oC/W to 0.12oC/W thermal resistance
• DIN, panel or thru wall mounting
• Single or multiple SSR mounting
Heatsink Range Overview:
http://www.productselection.net/PDF/UK/ssr_accessories.pdf
Specifications are subject to change without notice (06.09.2017) 7
Page 8
RM1E
Short Circuit Protection
Protection Co-ordination, Type 1 vs. Type 2:
Type 1 protection implies that after a short circuit, the device under test will no longer be in a functioning state. In type 2
co-ordination the device under test will still be functional after the short circuit. In both cases, however, the short circuit has
to be interrupted. The fuse between enclosure and supply shall not open. The door or cover of the enclosure shall not be
blown open. There shall be no damage to conductors of terminals and the conductors shall not separate from terminals.
Therese shall be no breakage or cracking of insulating bases to the extent that the integrity of the mounting of live parts is
impaired. Discharge of parts or any risk of fire shall not occur.
The product variants listed in the table hereunder are suitable for use on a circuit capable of delivering not more than
65,000A rms Symmetrical Amperes, 600Volts maximum when protected by fuses. Tests at 65,000A were performed with
Class J, fast acting: please refer to the table below for maximum allowed ampere rating of the fuse. Use fuses only.
Co-ordination Type 1 (UL508)
Part No. Prospective short Max. fuse Class Voltage [VAC]
circuit current [kArms] size [A]
zz = 00, without fuse trip indication
zz = 21, with fuse trip indication
* Formerly Ferraz Shawmut
8 Specifications are subject to change without notice (06.09.2017)
Page 9
RM1E
Type 2 Protection with Miniature Circuit Breakers (M.C.B.s)
Solid State Relay ABB Model no. for ABB Model no. for Wire cross Minimum length of
type Z - type M. C. B. B - type M. C. B. sectional area [mm2] Cu wire conductor [m]*
(rated current) (rated current)
* Between MCB and Load (including return path which goes back to the mains).
Note: A prospective current of 6kA and a 230/400V power supply system is assumed for the above suggested specifications. For cables with different cross
section than those mentioned above please consult Carlo Gavazzi’s Technical Support Group.
Specifications are subject to change without notice (06.09.2017) 9
Page 10
Environmental Information
The declaration in this section is prepared in compliance with People’s Republic of China Electronic Industry Standard SJ/
T11364-2014: Marking for the Restricted Use of Hazardous Substances in Electronic and Electrical Products.
Part NameToxic or Harardous Substances and Elements
Lead
(Pb)
Power Unit AssemblyxOOOOO
O: Indicates that said hazardous substance contained in homogeneous materials fot this part are below the limit requirement of GB/T 26572.
X: Indicates that said hazardous substance contained in one of the homogeneous materials used for this part is above the
limit requirement of GB/T 26572.