Solid State Relays
Low Voltage AC/DC Control: 5 to 24 V
Types RM 23M, RM 40M, RM 48M, RM 60M
• Zero switching AC Solid State Relay
• Low voltage AC/DC control: 5 to 24 V
• Direct copper bonding (DCB) technology
• LED indication
• Built-in varistor
• Clip-on IP 20 protection cover
• Self-lifting terminals
• Housing free of moulding mass
• Operational ratings: Up to 100AACrms and
600VACrms
• Opto-isolation: > 4000VACrms
Product De scrip tion
The industrial, 1-phase relay
with antiparallel thyristor output is the most widely used
SSR due to its multiple application possibilities. This relay
has been designed to interface low voltage AC or DC
control systems with high
voltage resistive, inductive
and capacitive loads. The
zero switching relay switches
ON when the sinusoidal curve
crosses zero and switches
OFF when the current crosses zero. The built-in varistor
secures transient protection
for the heavy industrial applications, and the LED indicates the status of the control input. The clip-on cover
is securing touch safety to
IP 20. Protected output terminals can take cables up to
16 mm2.
Ordering Key
Solid State Relay
Number of poles
Switching mode
Rated operational voltage
Control voltage
Rated operational current
RM 1 A 23 M 25
Type Selection
Switching mode Rated operational Control voltage Rated operational
voltage current
A: Zero Switching 23: 230VACrms M: 5 to 24VDC/AC 25: 25AACrms
40: 400VACrms 50: 50AACrms
48: 480VACrms 75: 75AACrms
60: 600VACrms 100: 100AACrms
Selection Guide
Rated opera- Blocking Control Rated op er a tion al current
tional voltage voltage voltage 25 AACrms 50 AACrms 75 AACrms 100 AACrms
230VACrms 650Vp 5 to 24VDC/AC RM1A23M25 RM1A23M50 RM1A23M75 RM1A23M100
400VACrms 850Vp 5 to 24VDC/AC RM1A40M25 RM1A40M50 RM1A40M75 RM1A40M100
480VACrms 1200Vp 5 to 24VDC/AC RM1A48M25 RM1A48M50 RM1A48M75 RM1A48M100
600VACrms 1400Vp 5 to 24VDC/AC RM1A60M25 RM1A60M50 RM1A60M75 RM1A60M100
General Spec i fi ca tions
RM1A23M RM1A40M RM1A48M RM1A60M
Operational voltage range 24 to 265VACrms 42 to 440VACrms 42 to 530VACrms 42 to 660VACrms
Blocking voltage ≥ 650Vp ≥ 850Vp ≥ 1200Vp ≥ 1400V
Zero voltage turn-on ≤ 15V ≤ 15V ≤ 15V ≤ 15V
Operational frequency range 45 to 65Hz 45 to 65Hz 45 to 65Hz 45 to 65Hz
Power factor
Approvals UL, CSA, EAC UL, CSA, EAC UL, CSA, EAC UL, CSA, EAC
CE-marking Yes Yes Yes Yes *
* Heatsink must be connected to ground.
> 0.5 @ 230VACrms > 0.5 @ 400VACrms > 0.5 @ 480VACrms > 0.5 @ 600VACrms
1 Specifications are subject to change without notice (26.07.2017)
p
RM23M, RM40M, RM48M, RM60M
Input Specifications
Absolute max. input voltage 37VDC
28VAC
Pick-up voltage 4.0VDC
4.0VAC
Drop out voltage 2.0VDC
2.0VAC
Input current
@ 5 VAC ≤ 10mA
@ 24 VAC ≤ 18mA
@ 5 VDC ≤ 9mA
@ 24 VDC ≤ 12mA
Response time pick-up ≤ 1 cycle
Response time drop-out
≤ 2.5 cycles
Isolation
Rated isolation voltage ≥ 4000VACrms
Input to output
Rated isolation voltage ≥ 4000VACrms
Output to case
Housing Specifications
Weight
25 A, 50 A Approx. 60g
75 A, 100 A Approx. 100g
Housing material Noryl GFN 1, black
Baseplate
25 A, 50 A Aluminium
75 A, 100 A Copper, nickel-plated
Potting compound None
Relay
Mounting screws M5
Mounting torque 1.5-2.0Nm
Control terminal
Mounting screws M3 x 9
Mounting torque 0.5Nm
Power terminal
Mounting screws M5 x 9
Mounting torque 2.4Nm
Thermal Specifications
RM1...M25 RM1...M50 RM1.60M50 RM1...M75 RM1...M100
Operating temperature range -20° to 70°C -20° to 70°C -20° to 70°C -20° to 70°C -20° to 70°C
Storage temperature range -40° to 100°C -40° to 100°C -40° to 100°C -40° to 100°C -40° to 100°C
Junction temperature ≤ 125°C ≤ 125°C ≤ 125°C ≤ 125°C ≤ 125°C
Rth junction to case ≤ 0.80K/W ≤ 0.50K/W ≤ 0.72K/W ≤ 0.35K/W ≤ 0.30K/W
Rth junction to ambient ≤ 20.0K/W ≤ 20.0K/W ≤ 20.0K/W ≤ 20.0K/W ≤ 20.0K/W
Output Specifications
RM1A..M25 RM1A..M50 RM1A..M75 RM1A..M100
Rated operational current
AC51 @ Ta=25°C 25Arms 50Arms 75Arms 100Arms
AC53a @ Ta=25°C 5Arms 15Arms 20Arms 30Arms
Min. operational current 150mA 250mA 400mA 500mA
Rep. overload current t=1 s < 55AACrms < 125AACrms < 150AACrms < 200AACrms
Non-rep. surge current t=10ms 325Ap 600Ap 1150Ap 1900Ap
Off-state leakage current @
rated voltage and frequency < 3mArms < 3mArms < 3mArms < 3mArms
I2t for fusing t=10ms < 525A2s < 1800A2s < 6600A2s < 18000A2s
On-state voltage drop @ rated current 1.6Vrms 1.6Vrms 1.6Vrms 1.6Vrms
Critical dV/dt off-state min. 500V/µs 500V/µs 500V/µs 500V/µs
Zero crossing detection Yes Yes Yes Yes
Specifications are subject to change without notice (26.07.2017) 2