4 Specifications are subject to change without notice (10.10.2006)
Alarm Operation
1.1 Current Setpoint
The current setpoint is the
nominal operating current that
is expected when all the heater
loads are functioning properly.
If the heater loads are faulty or
the supply voltage is not close
to the nominal level, the wrong
setpoint will be stored.
1.2 Initialisation
When the device is shipped,
no setpoint is stored in the
flash memory. Both green
and red LEDs will flash intermittently to indicate that a
setpoint must be stored
using the TEACH procedure.
1.3 Local Functions
Local functions can be activated by using the push
button on the front of the
device. While an alarm is
being issued by any SSR
connected to the common
alarm line, no local commands are accepted.
1.3.1 Local TEACH
Press and hold the push button for approximately 3 seconds. The red LED will flash
after each second. After the
LED flashes 3 times, release
the button. If the “teach” command has been accepted the
heater loads are automatically
switched ON. The red LED will
flash quickly 10 times. When
the current setpoint has been
stored successfully, the red
and green LEDs will scroll intermittently to indicate that the
TEACH procedure has been
completed.
It is very important to hold
the button down for only 3
flashes of the red LED to
make a successful TEACH.
If the TEACH procedure is
not successful, the device
will automatically reset to
factory default (i.e. no setpoint stored).
1.3.2 Local RESET
When an alarm has occurred
the device can be locally
RESET by pressing the push
button for 1 second. The red
LED will flash once. This will
reset the alarm. If the alarm
condition has been cleared
the device will return to normal operation. If the alarm
condition is still active, the
device will automatically go
back to alarm status.
1.3.3 Local TEST
In the absence of a signal on
the “control input” terminal, a
local TEST can be made by
pressing and holding the button for 5 seconds. After the red
LED flashes 5 times, release
the button. The device will
switch ON the loads for 1 second. This test detects if there is
an under-current or heater
break alarm condition.
1.4 Remote Setup
Procedure
Remote functions can be
activated with a PLC or any
other logic controller by
applying timed pulses to the
alarm terminal: >10V for
RJCS...PO and <10V for
RJCS...NO.
1.4.1 Remote TEACH
Apply a 3 second pulse. The
red LED will flash after each
second. After the LED flashes 3 times and the “teach”
command has been accepted, the heater loads (of all
SSRs connected to the
same alarm line) are automatically switched ON and
the red LED will flash quickly
10 times. When the current
setpoint has been stored
successfully, the red and
green LEDs will scroll intermittently to indicate that the
TEACH procedure has been
completed.
1.4.2 Remote RESET/
UNBLOCK
When an alarm has occurred
the device can be remotely
RESET by applying a 1 second pulse. A 1 second pulse
will also unblock local
TEACH of all SSRs connected to the similar alarm line.
The red LED will flash once.
This will reset the alarm. If
the alarm condition has been
cleared the device will return
to normal operation. If the
alarm condition is still active,
the device will automatically
go back to alarm status.
1.4.3 Remote BLOCK
Applying a 5 second pulse
will induce the device to
block local TEACH. After
this, no local TEACH com-
mands are accepted. To
unblock this situation, a
remote RESET must be
issued. If 24V supply is
removed, local TEACH
BLOCK is lost. Another
REMOTE BLOCK should be
issued.
2 Alarms
2.1 Alarm DELAY
A potentiometer on the front
of the device allows a time
delay on the heater change
alarm between 2s and 40s
for the RJCS1A... and
between 0 and 40s for the
RJCSR1A...
For an alarm signal to occur,
the alarm condition must
persist throughout this time
period. The alarm output is
enabled only after this time
delay has passed. However,
if the control input is disabled for a period of time
equal to four times the delay
setting, the internal alarm
delay count is reset automatically.
2.2 Relay remains OFF due
to Line Voltage Loss or
Thyristor Open Circuit
Failure.
The device generates one
pulse with duration of 7 seconds on the alarm terminal.
This alarm is non-latching.
The red LED remains ON
after this alarm condition
until a RESET is issued.
2.3 Heater Change.
A Heater Change alarm is
given if the current measured through the device is
13% less than the Current
Setpoint stored in the flash
memory. For the RJCSR1A...,
the heater change alarm is
given also in the case the
current measured through
the device is 13% more than
the current setpoint stored in
flash memory. The device
generates one pulse with
duration of 8 seconds on the
alarm terminal. The alarm
signal is non-latching. The
red LED remains ON after
this alarm condition until a
RESET is made. If the measured current changes to
within 10% of the Current
Setpoint, before the Alarm
DELAY time has elapsed,
the Alarm DELAY timer is
reset.
2.4 Over-temperature or
Over-current.
This alarm occurs if any one
of following two conditions
is true:
1. The device detects an
internal over-temperature
condition at any time during
operation and switches off
the output. The red LED
flashes intermittently.
2. A current above the nominal device rating is measured during current setpoint TEACH. This action
erases the current setpoint
from flash memory and both
red and green LEDs will flash
intermittently until a TEACH
procedure with an acceptable current is carried out.
In both cases, the device
generates one pulse with
duration of 9 seconds on the
alarm terminal. The alarm
signal is non-latching.
2.5 Thyristor Short Circuit.
The device generates one
pulse with duration of 10
seconds on the alarm terminal. The alarm signal is nonlatching.
The red LED remains ON
after this alarm condition
until a RESET is made.
2.6 Alarms Connected in
Parallel to one PLC Input
and one PLC Output.
For REMOTE operation, up
to 50 devices can be connected in parallel to at least
one PLC input. This PLC
input must also be connected in parallel to the PLC output. The PLC input must be
programmed to detect
alarms while the PLC output
must be programmed to
supply the pulses required
for REMOTE Setup. When
more than one device is present, pulses from the PLC
output or alarm pulses from
any device will cause the red
LEDs on all devices in parallel to flash intermittently for a
max. of 6.25 seconds. After
this time, if there is a device
in alarm condition, only the
red LED of that device will
be ON.
RJCS