• Control voltages: 3-32 VDC, 20-275 VAC (24-190VDC)
• Input connection: Screw terminal or pluggable spring
• Output connection: Screw clamp/screw terminal
• Design according to IEC/EN60947-4-2, IEC/EN60947-4-3,
IEC/EN62314, UL508, CSA22.2 No. 14-10
• Integrated voltage transient protection with varistor
• RoHS compliant
• Short circuit rating: 100 kA
• VDE approval
Product Description
Aim of this solid state switching
device is to switch heater loads
and motor loads frequently.
The range offers solutions up
to 90AAC in 17.5mm width.
Output connections are via a
screw connection, having a
captivated washer allowing for
safe looping. Input connection
is provided either via a screw
connection having a captivated
washer or via a pluggable
spring loaded input. Other
optionswithintegrated
heatsink are available in RGC
ranges.
Specifications are at a surrounding temperature of 25°C
unless otherwise specified.
Ordering Key
Solid State Relay
Number of poles
Switching Mode
Rated Operational Voltage
Control voltage
Rated Operational current
Connection type for control
Connection type for power
Connection configuration
Option
RGS 1 A 60 D 75 K K E _
Ordering Key
1Phase SSRRatedControlRatedConnectionConnectionConnectionOptions
with no heatsinkVoltageVoltageCurrentControlPowerConfiguration
1: The thermal pad with suffix 'HT' is available with any RGS part no. upon request. The above are some examples of RGS selection with attached thermal pad.
Selection Guide (RGS mounted on heatsink RHS37A)
Rated OutputBlockingConnectionControlRated operational current @ 40˚C
Conducted Radio FrequencyIEC/EN 61000-4-6
Immunity
10V/m, 0.15 - 80 MHzPerformance Criteria 1
Voltage Dips ImmunityIEC/EN 61000-4-11
0% for 10ms/20msPerformance Criteria 2
40% for 200msPerformance Criteria 2
70% for 500msPerformance Criteria 2
Voltage Interruptions Immunity IEC/EN 61000-4-11
0% for 5000msPerformance Criteria 2
Radio Interference
Field Emission (Radiated)IEC/EN 55011
30 - 1000MHzClass A (industrial)
Filtering - IEC/EN 55011 Class A compliance (for class B compliance contact us)
Part NumberSuggested filter for complianceMaximum Heater current
RGS1A23..25100 nF / 275 V / X125 A
RGS1A23..50220 nF / 275 V / X130 A
330 nF / 275 V / X135 A
RGS1A23..51150 nF / 275 V / X120 A
220 nF / 275 V / X135 A
RGS1A23..75330 nF / 275 V / X135 A
RGS1A23..71/90/91330 nF / 275 V / X135 A
RGS1A60..25150 nF / 760 V / X125 A
220 nF / 760 V / X130 A
RGS1A60..50330 nF / 760 V / X130 A
RGS1A60..51220 nF / 760 V / X130 A
RGS1A60..75220 nF / 760 V / X130 A
RGS1A60..71/90/91220 nF / 760 V / X130 A
Note:
• Control input lines must be installed together to maintain products' susceptability to Radio Frequency interference.Use of AC solid state relays may,
according to the application and the load current, cause conducted radio interferences. Use of mains filters may be necessary for cases where the user must
meet E.M.C requirements. The capacitor values given inside the filtering specification tables should be taken only as indications, the filter attenuation will
depend on the final application. DC input type require surge suppression for full compliance to EN55011.
• Performance Criteria 1: No degradation of performance or loss of function is allowed when the product is operated as intended.
• Performance Criteria 2: During the test, degradation of performance or partial loss of function is allowed. However when the test is complete the
product should return operating as intended by itself.
• Performance Criteria 3: Temporary loss of function is allowed, provided the function can be restored by manual operation of the controls.