Carlo Gavazzi RGC2P, RGC3P Catalog Page

Solid State Relays 3-Phase with Integrated Heatsink Proportional Switching Controllers
Types RGC2P, RGC3P
• 2-pole and 3-pole analog switching solid state contactors
• Rated operational voltage: up to 600VAC
• Rated operational current: up to 75AAC
• Control inputs: 0-20mA, 4-20mA, 12-20mA, 0-5V, 1-5V, 0-10V
• Local setting through external potentiometer
• Switching modes: phase angle or distributed full cycles (1, 4 or 16 full cycles)
• Soft start feature with selectable ramp time up to 5 seconds
• Integrated varistor protection on output
• Monitoring for SSR and load malfunction
• EMR alarm output for alarm indication
• 100kA short circuit current rating according to UL508
• DIN or panel mount
• RoHS compliant
Product Description
This series gives the possibility to control output power of 3-phase loads with an analog control input. The RGC2P is a 2-phase switching product whilst the RGC3P switches all 3 phases.
Input types cover a wide range of current and voltage ranges. Local setting by an external potentiometer is also possible. Switching modes cover phase angle control, distributed full cycle control and soft start for limiting inrush current of loads having a high temperature
coefficient, such as short wave infrared heaters.
Detection of mains loss, load loss, SSR short circuit and over­temperature is integrated in some models. Alarm condition is signalled through an EMR output and is visually indicated by the alarm LED. Additional LEDs indicate input and load status.
Specifications are at a surrounding temperature of 25°C unless otherwise specified.
Ordering Key
Solid state relay Number of switched poles Type of switching Rated operational voltage Control input Rated operational current Switching mode External supply Integrated fan Monitoring features
Ordering Key (Refer to page 4 for valid part numbers)
SSR with heatsink
RGC2:
2-pole switching + 1-pole direct
RGC3:
3-pole switching
FC = Full Cycle OTP = Over Temperature Protection EMR = Electromechanical Relay
1. Input types I and V require an external supply Us
2. Refer to Derating Curves
Type of switching
P: Proportional 60:
Rated voltage (Ue), Blocking voltage
180 - 660VAC, 1200Vp
Control
1
input
AA:
4-20mADC
I:
0-20mADC 4-20mADC 12-20mADC
V:
0-5VDC 1-5VDC 0-10VDC
Rated current/ pole @
40°C
20: 20AAC 25: 25AAC 30: 30AAC 40: 40AAC 65: 65AAC 75: 75AAC
RGC 3 P 60 V 65 C1 D F M
Switching
2
mode
E: Phase Angle
C1: 1 FC ON,
1FC OFF @ 50% input
C4: 4 FC ON, 4FC OFF @ 50% input
C16: 16 FC ON, 16FC OFF @ 50% input
S: Soft Start
S16: Soft Start +
mode C16
External supply (Us)
D: 24VAC/DC
A: 90 - 250VAC
Features
P: Integrated
over temperature protection (OTP), mains loss with EMR alarm output
F: Integrated fan
M: Monitoring
for Mains loss, Load loss, SSR short circuit, open circuit and OTP with EMR alarm output
Specifications are subject to change without notice (18.02.2014) 1
RGC2P, RGC3P
General Specifications
RGC..AA.. RGC..I.. RGC..V..
Latching voltage (across each pole L-T) 20V Operational frequency range 45 to 65Hz Power factor > 0.7 @ rated voltage Output Power 0 to 100% Touch Protection IP20 CE marking Yes Pollution degree 2 (non-conductive pollution with possibilities of condensation) Over-voltage category III (fixed installations) LED status indication
Control ON Green Green Green
Supply ON n/a Green Green
Load ON n/a Yellow Yellow
Alarm ON Green, flashing
Isolation
Input & Output to Case 4000Vrms 4000Vrms 4000Vrms Input to Output 2500Vrms 2500Vrms 2500Vrms External supply to input
Us to A1, A2, A3, A4, A5, Uf, 11, 12, 14, C1, C2 n/a 1500Vrms 1500Vrms
External supply & input to EMR
Us, A1, A2, A3, A4, A5, Uf, C1, C2 to 11, 12, 14 n/a 1500Vrms 1500Vrms
<4mA, flashing 0.5s ON, 0.5s OFF Full intensity Full intensity >4mA, intensity varies with input
Flashing 0.5s ON, 0.5sOFF Flashing 0.5s ON, 0.5sOFF
N according to load status ON accordingto load status
3
O
Red, flashing
3
Red, flashing
3
3: Refer to LED Indications
Output Voltage Specifications
Operational voltage range
Line to line voltage, L1/L2/L3 180-660 VAC
Permissible voltage unbalance 10% between L1/L2/L3 Blocking voltage 1200Vp Leakage current @ rated voltage 5mAAC per pole Internal Varistors
(across each pole) Yes
Specifications are subject to change without notice (18.02.2014) 5
Loading...