Carlo Gavazzi RGC1S, RGS1S Selection Guide

RGC1S, RGS1S
Selection Guide: RGC1S (with integrated heatsink)
ated output voltage, Connection Control Configuration Rated operational current
R
locking voltage control/ power voltage
B
00VAC, 1200Vp Box Clamp/ Screw 4 - 32VDC E RGC1S60D20GKEP RGC1S60D25GKEP RGC1S60D30GKEP RGC1S60D31GKEP
6
ated output voltage, Connection Control Configuration Rated operational current
R
3AAC (525A
2
Blocking voltage control/ power voltage 40AAC (6600A
2
) 23AAC (1800A
s
2
s) 60AAC (6600A2s) 85AAC (6600A2s)
(I2t value in brackets)
2
) 30AAC (1800A
s
(I2t value in brackets)
2
) 30AAC (6600A
s
2
)
s
600VAC, 1200Vp BoxClamp/ Box Clamp 4 - 32VDC E RGC1S60D41GGEP RGC1S60D61GGEP RGC1S60D90GGEP
U RGC1S60D41GGUP RGC1S60D61GGUP -
Selection Guide: RGS1S (with no heatsink)
Rated output voltage, Connection Control Configuration Rated operational current (I Blocking voltage control/ power voltage 23AAC (525A
600VAC, 1200Vp Box Clamp / Screw 4 - 32VDC E RGS1S60D20GKEP RGS1S60D30GKEP RGS1S60D31GKEP
Rated output voltage, Connection Control Configuration Rated operational current (I
locking voltage control/ power voltage
B
600VAC, 1200Vp BoxClamp/ Box Clamp 4 - 32VDC E RGS1S60D61GGEP
U RGS1S60D61GGUP
0AAC (6600A
6
2
s) 30AAC (1800A2s) 30AAC (6600A2s)
2
)
s
t value in brackets)
t value in brackets)
Output Voltage Specifications
Operational Voltage Range 42-600 VAC
+10% -15% on max Blocking Voltage 1200 Vp Internal Varistor 625V
Output Specifications
RGC1S..20 RGC1S..25 RGC1S..30 RGC1S..31 RGC1S..41 RGC1S..61 RGC1S..90 RGS1S..20 RGS1S..30 RGS1S..31 RGS1S..61
Rated operational current
2
AC-51 @ Ta=25°C RGC1S 25.5 AAC 23.8 AAC 30 AAC 30 AAC 49 AAC 75 AAC 85 AAC AC-51 @ Ta=40°C RGC1S 23 AAC 23.8 AAC 30 AAC 30 AAC 40 AAC 60 AAC 85 AAC Max. AC-51 rating RGS1S 23 AAC n/a 30 AAC 30 AAC n/a 60 AAC n/a Minimum TEACH Current
3
1.2 AAC 1.2 AAC 1.2 AAC 1.2 AAC 1.2 AAC 5 AAC 5 AAC Minimum partial load current 0.2 AAC 0.2 AAC 0.2 AAC 0.2 AAC 0.2 AAC 0.83 AAC 0.83 AAC Detectable partial load failure >16.67% from current setpoint for more than 120ms Rep. overload current - UL508,
PF=0.9
TAMB=40°C, tON=1s, tOFF=9s, 50cycles 60 AAC 60 AAC 84 AAC 84 AAC 126 AAC 144 AC 168 AAC
Max.off-state leakage current 3 mAAC 3 mAAC 3 mAAC 3 mAAC 3 mAAC 3 mAAC 3 mAAC
Max. Transient Surge Current (Itsm) t=10ms 325 Ap 600 Ap 600 Ap 1150 Ap 1150 Ap 1150 Ap 1150 Ap
I²t for fusing (t=10ms) Minimum 525 A²s 1800 A²s 1800 A²s 6600 A²s 6600 A²s 6600 A²s 6600 A²s Critical dv/dt (@ Tj init = 40
o
C) 1000 V/us 1000 V/us 1000 V/us 1000 V/us 1000 V/us 1000 V/us 1000 V/us
2: refer to derating curves for RGC models and heatsink selection tables for RGS models 3: refer to EMC specifications
2 Specifications are subject to change without notice (18.03.2013)
Loading...