Carlo Gavazzi RGC Data sheet

Solid State Relays 1-Phase with Integrated Heatsink Zero Cross or Instant On Switching
Types RGC Solid State Contactor ‘E’ Connection
• Product width ranging from 17.5mm up to 70mm
• Rated operational voltage: up to 660 VAC
• Rated operational current: up to 85 AAC @ 40°C
• 18000 A
• Design according to EN/IEC60947-4-2, EN/IEC60947-4-3, EN/IEC62314, UL508, CSA 22-2 No. 14-13
• Integrated voltage transient protection with varistor
• 100 kA short circuit current rating according to UL508
2
s for the I2t and 1200 Vp blocking voltage
1 2
Product Description
This new range of solid state contactors presents a unique opportunity to maximize effi­ciency in panel space and is an evolution of solid state switches for which Carlo Gavazzi is very well known.
The nominal current ratings are at 40˚C. The smallest
1. RGC..32 models are not VDE approved
2. Germanischer Lloyd approval applicable only to models RGC1....15.KE,
RGC1...20.KE, RGC1..25..KE and RGC1....30.KE
width is 17.5mm and is rated at 37 AAC. Power and control teminals allow for safe loop­ing of cables.
Voltage transient protection is standard across the output with a varistor. Specifications are stated at 25°C unless otherwise noted.
Ordering Key
RGC 1 A 60 A 30 K K E _
Solid state relay Number of poles Switching mode Rated operational voltage Control voltage Rated operational current Connection type for control Connection type for power Connection configuration Option
Ordering Key (Refer to page 2 and 3 for available part numbers)
1 Phase SSR Rated voltage, Control voltage Rated Connection Connection Connection with heatsink Blocking voltage current at 40˚C
RGC1A: ZC RGC1B: IO
24-190 VDC 25: 25AAC, 1800A²s M: Pluggable (OTP) 30: 30AAC, 1800A²s spring-loaded 32: 30 AAC, 18000A 32: 37 AAC, 18000A 40: 40AAC, 3200A²s 42: 43AAC, 18000A²s 60: 60AAC, 3200A²s 62: 65AAC, 18000A²s 90: 85AAC, 6600A²s 92: 85AAC, 18000A²s
4
23: 230V +10% - 15%, 800Vp D: 3 or 4-32VDC 15: 20AAC, 525A²s K: Screw K: Screw E: Contactor P: Overtemperature
4
60: 600V +10% -15%, 1200Vp A: 20 - 275VAC, 20: 23AAC, 525A²s G: Box clamp G: Box clamp protection
3
control pow er configuration Option
5
2
s
2
s
3. Refer to Derating Curves
4. ZC = Zero cross switching, IO= Instant ON switching
5. Default control connection for RGC...P is Box Clamp. See Connections Specifications
Specifications are subject to change without notice (22.05.2018) 1
RGC...E
Selection Guide
Rated voltage, Control voltage Connection Rated operational current @ 40oC (I2t value) Blocking voltage, control/power Product width Switching mode 20 AAC (525A²s) 23 AAC (525A²s) 25 AAC (1800A²s) 30 AAC (1800A²s)
230V, 800Vp 3-32VDC Screw/Screw RGC1A23D15KKE RGC1A23D20KKE RGC1A23D25KKE RGC1A23D30KKE ZC Spring/Screw RGC1A23D15MKE RGC1A23D20MKE RGC1A23D25MKE RGC1A23D30MKE
Spring/Screw RGC1A23A15MKE RGC1A23A20MKE RGC1A23A25MKE RGC1A23A30MKE
40 AAC (3200A²s) 43 AAC (18000A²s) 60 AAC (3200A²s) 65 AAC (18000A²s)
3-32VDC Screw/Box RGC1A23D40KGE RGC1A23D42KGE RGC1A23D60KGE RGC1A23D62KGE 20-275VAC, 24-190VDC Screw/Box RGC1A23A40KGE RGC1A23A42KGE RGC1A23A60KGE RGC1A23A62KGE
20 AAC (525A²s) 23 AAC (525A²s) 25 AAC (1800A²s) 30 AAC (1800A²s)
600V, 1200Vp 4-32VDC Screw/Screw RGC1A60D15KKE RGC1A60D20KKE RGC1A60D25KKE RGC1A60D30KKE ZC Spring/Screw RGC1A60D15MKE RGC1A60D20MKE RGC1A60D25MKE RGC1A60D30MKE
Spring/Screw RGC1A60A15MKE RGC1A60A20MKE RGC1A60A25MKE RGC1A60A30MKE
20-275VAC, 24-190VDC Screw/Screw RGC1A23A15KKE RGC1A23A20KKE RGC1A23A25KKE RGC1A23A30KKE
20-275VAC, 24-190VDC Screw/Screw RGC1A60A15KKE RGC1A60A20KKE RGC1A60A25KKE RGC1A60A30KKE
17.5mm, low depth 17.5mm 17.5mm, low depth 22.5mm
35mm 35mm 70mm 70mm
17.5mm, low depth 17.5mm 17.5mm, low depth 22.5mm
30 AAC (18000A²s) 37 AAC (18000A²s)
4-32VDC Screw/Screw RGC1A60D32KKE - Spring/Screw RGC1A60D32MKE - Screw/Box - RGC1A60D32KGE Spring/Box - RGC1A60D32MGE
40 AAC (3200A²s) 43 AAC (18000A²s) 60 AAC (3200A²s) 65 AAC (18000A²s)
4-32VDC Screw/Box RGC1A60D40KGE RGC1A60D42KGE RGC1A60D60KGE RGC1A60D62KGE Spring/Box RGC1A60D40MGE RGC1A60D42MGE - RGC1A60D62MGE
Spring/Box RGC1A60A40MGE RGC1A60A42MGE - RGC1A60A62MGE
20 AAC (525A²s) 23 AAC (525A²s) 25 AAC (1800A²s) 30 AAC (1800A²s)
600V, 1200Vp 4-32VDC Screw/Screw RGC1B60D15KKE RGC1B60D20KKE RGC1B60D25KKE RGC1B60D30KKE IO
40 AAC (3200A²s) 43 AAC (18000A²s) 60 AAC (3200A²s) 65 AAC (18000A²s)
4-32VDC Screw/Box RGC1B60D40KGE RGC1B60D42KGE RGC1B60D60KGE RGC1B60D62KGE
20-275VAC, 24-190VDC Screw/Box RGC1A60A40KGE RGC1A60A42KGE RGC1A60A60KGE RGC1A60A62KGE
17.5mm, low depth 17.5mm, low depth
35mm 35mm 70mm 70mm
17.5mm, low depth 17.5mm 17.5mm, low depth 22.5mm
35mm 35mm 70mm 70mm
2 Specifications are subject to change without notice (22.05.2018)
RGC...E
Selection Guide - RGC..P (Integrated Overtemperature Protection)
Rated voltage, Control voltage Connection Rated operational current @ 40oC (I2t value) Blocking voltage, control / power Product width Switching mode 30 AAC (1800A²s)
22.5mm
600V, 1200Vp 5-32VDC Box/Screw RGC1A60D30GKEP ZC
43 AAC (18000A²s) 65AAC (18000A²s) 85AAC (6600A²s) 85AAC (18000A²s)
5-32VDC Box/Box RGC1A60D42GGEP RGC1A60D62GGEP RGC1A60D90GGEP RGC1A60D92GGEP
20-275VAC, 24-190VDC Box/Screw RGC1A60A30GKEP
35mm 70mm 70mm + fan 70mm + fan
20-275VAC, 24-190VDC Box/Box RGC1A60A42GGEP RGC1A60A62GGEP RGC1A60A90GGEP RGC1A60A92GGEP
Output Voltage Specifications
RGC..23.. RGC..60..
Operational voltage range 24-240 VAC, 42-600 VAC, +10%, -15% on max +10% -15% on max
Blocking voltage 800Vp 1200 Vp Internal varistor 275V 625V
General Specifications
Latching voltage (across L1-T1) 20V
Operational frequency range 45 to 65Hz
Power factor > 0.5 @ Vrated Touch Protection IP20 Control input status continuously ON Green LED,
when control input is applied Pollution degree 2
(non-conductive pollution with possibilities of condensation)
Rated impulse withstand 6 kV (1.2/50μs) for voltage, Uimp Over-voltage category III
(fixed installations) Isolation Input to Output RGC... 4000 Vrms
RGC...D..P 2500 Vrms RGC...A..P 4000 Vrms Input and Output RGC... 4000 Vrms to case RGC...D..P 4000 Vrms RGC...A..P 4000 Vrms Input to Fan/ Alarm Output RGC...A..P 2500 Vrms
Specifications are subject to change without notice (22.05.2018) 3
RGC...E
Output Specifications
RGC..15.. RGC..20.. RGC..25.. RGC..30.. Rated operational current
6
RGC..32..KE
RGC..32..GE
AC-51 rating @ Ta=25°C 20 AAC 25.5 AAC 30 AAC 30 AAC 30 AAC 43 AAC AC-51 rating @ Ta=40°C 20 AAC 23 AAC 25 AAC 30 AAC 30 AAC 37 AAC AC-53a rating @ Ta=40°C 5 AAC 5 AAC 5 AAC 8 AAC 5 AAC 5 AAC Number of motor starts per hour
(x:6, Tx:6s, F:50%) at 40˚C
7
30 30 30 30 30 30 Min. operational current 150 mAAC 150 mAAC 250 mAAC 250 mAAC 500 mAAC 500 mAAC Rep. overload current -
(Motor Rating) PF = 0.4 - 0.5 UL508: T
=40°C, tON=1s, t
AMB
=9s,
OFF
50 cycles 51 AAC 60 AAC 51 AAC 84 AAC 51 AAC 51 AAC
Maximum transient surge current (I
), t=10ms 325 Ap 325 Ap 600 Ap 600 Ap 1900 Ap 1900 Ap
TSM
Maximum off-state leakage current at rated voltage 3 mAAC 3 mAAC 3 mAAC 3 mAAC 3 mAAC 3 mAAC
I²t for fusing (
t=10ms), Minimum 525 A²s 525 A²s 1800 A²s 1800 A²s 18000 A²s 18000 A²s
Crititcal dv/dt (@ Tj init = 40°C) 1000 V/μs 1000 V/μs 1000 V/μs 1000 V/μs 1000 V/μs 1000 V/μs
RGC..40.. RGC..42.. RGC..60.. RGC..62.. RGC..90.. RGC..92.. Rated operational current
6
AC-51 rating @ Ta=25°C 47 AAC 50 AAC 70 AAC 75 AAC 85 AAC 85 AAC AC-51 rating @ Ta=40°C 40 AAC 43 AAC 60 AAC 65 AAC 85 AAC 85 AAC AC-53a rating @ Ta=40°C 13 AAC 16 AAC 14.8 AAC 20 AAC 18 AAC 20 AAC Number of motor starts per hour
(x:6, Tx:6s, F:50%) at 40˚C
7
30 30 30 30 30 30 Min. operational current 400 mAAC 500 mAAC 400 mAAC 500 mAAC 400 mAAC 500 mAAC Rep. overload current -
(Motor Rating) PF = 0.4 - 0.5 UL508: T
=40°C, tON=1s, t
AMB
=9s,
OFF
50cycles 126 AAC 126 AAC 126 AAC 168 AAC 168 ACC 168 AAC
Maximum transient surge current (I
), t=10ms 800 Ap 1900 Ap 800 Ap 1900 Ap 1150 Ap 1900 Ap
TSM
Maximum off-state leakage current at rated voltage 3 mAAC 3 mAAC 3 mAAC 3 mAAC 3 mAAC 3 mAAC
I²t for fusing (
t=10ms), Minimum 3200 A²s 18000 A²s 3200 A²s 18000 A²s 6600 A²s 18000 A²s
Crititcal dv/dt (@ Tj init = 40°C) 1000 V/μs 1000 V/μs 1000 V/μs 1000 V/μs 1000 V/μs 1000 V/μs
6. See Derating Curves
7. Overload profile for AC-53a; Ie: AC-53a: x-Tx: F-S, where Ie = nominal current (AC-53a AAC), x = overload current factor, Tx = duration of overload current (s), F = duty cycle (%), S = number of starts per hour. Example; 5A: AC-53a: 6 - 6 : 50 - 30 = max. 30 starts for the RGC..15 with an overload profile of 30A for 6 seconds with a duty cycle of 50%
Overtemperature Alarm Specifications for RGC...P
RGC..D..P RGC..A..P Output type PNP open collector Potential Free Normal state Closed Closed Maximum current rating 50 mADC 50 mADC Rated voltage (EN61131-2: 2003) Rated voltage, Us RGC...D9xGGEP 24VDC ± 10% N/A Fan rating, U
f RGC...A9xGGEP N/A 24VDC ±10%, 50mA nominal
Alarm voltage drop Typical 2.8VDC 1.8VDC Maximum 4VDC 3.5VDC
Visual Indication Continous Red LED Continous Red LED Reverse polarity protection 24VDC 24VDC
8. DC supply for alarm signal should be supplied from a Class 2 power source
9. Maximum voltage to be applied between 11+ and 12- (Ua) terminals should be 35VDC maximum with reference to A2-
4 Specifications are subject to change without notice (22.05.2018)
8, 9
, Ua 24VDC -15%, +20% 24VDC -15%, +20%
RGC...E
Input Specifications
RGC..D.. RGC..A..
Control voltage range 24 (-10%) - 190 VDC
RGC..60.. 4 - 32 VDC 20-275 VAC, 24 (-10%) - 190 VDC
RGC...P (Uc) 5 - 32 VDC 20-275 VAC, 24 (-10%) - 190 VDC
Pick-up voltage RGC..23.. 3.0 VDC 20 VAC/DC RGC..60.. 3.8 VDC RGC...P 5 VDC 20 VAC/ 24VDC
Drop-out voltage 1 VDC 5 VAC/DC Maximum Reverse voltage 32 VDC ­Response time pick-up (RGC1A..)
@ 230VAC/110VDC
Response time pick-up (RGC1B..) 350µs @ 24 VDC N/A Response time drop-out 0.5 cycle Input current @ 40°C See diagrams below See diagrams below
10. DC control to be supplied by class 2 power source according to UL1310
11. For GL approved models control range for RGC1.23... is 4-32VDC and for RGC1.60... 5-32VDC
RG..A..
10, 11
RGC..23.. 3 - 32 VDC 20 - 275 VAC,
0.5 cycle + 500µs @ 24VDC 2 cycles
+ 500µs @ 24VDC
0.5 cycle + 40ms @ 230VAC/110VDC
RGC1 .. A : input current vs input voltage
RGC1 .. A : input current vs input voltage
40mA
40mA
35mA
35mA
30mA
30mA
25mA
25mA
RGC .. A
20mA
20mA
15mA
15mA
10mA
5mA
0mA
0VAC 50VAC100VAC 150VA C 200VAC 250VA C 300VAC
40mA
40mA
35mA
35mA
30mA
30mA
25mA
25mA
20mA
20mA
15mA
15mA
RGC..A..P (Active Protection)
RGC..A..P (Active Protection)
RGC1 .. A : input current vs input voltage
RGC1 .. A : input current vs input voltage
RGC .. A
RGC .. A
RGC..A..P (Normal Operation)
10mA
5mA
0mA
0VDC 50VDC100VDC150VDC200VDC250VDC
RGC..A..P (Normal Operation)
Specifications are subject to change without notice (22.05.2018) 5
RGC...E
Input Specifications (cont.)
RG..D..
A1 Characteristics: DC input current vs Input voltage
25.0mA
25.0mA
20.0mA
20.0mA
15.0mA
15.0mA
10.0mA
10.0mA
5.0mA
x: Input currents for all models except RGC1..D90GGEP and RGC1..D92GGEP
20.0mA
20.0mA
15.0mA
15.0mA
10.0mA
10.0mA
RGC..D..P (Normal Operation)
RGC..D..P (Active Protection)
2V 4V 6V 8V 10V12V 14V16V 18V20V 22V 24V 26V 28V 30V 32V 34V
RGC..D9xGGEP (Normal Operation)
A1 Characteristics: DC input current vs Input voltage
IN1 Characteristics: DC input current vs Input voltage
IN1 Characteristics: DC input current vs Input voltage
x
y
x
5.0mA
5.0mA
0.0mA
RGC..D9xGGEP (Active Protection)
2V 4V 6V 8V 10V 12V 14V 16V 18V 20V 22V 24V 26V 28V 30V 32V 34V
y: input currents valid only for RGC1..D90GGEP and RGC1..D92GGEP
Motor Ratings: HP (UL508) / kW (EN/IEC60947-4-2) @ 40°C
115 VAC 230 VAC 400 VAC 480 VAC 600 VAC
RGC..15 RGC..20 ½HP / 0.18kW 1½HP / 0.37kW 2HP / 0.75kW 3HP / 1.1kW 3HP / 1.5kW RGC..25 RGC..30 ¾HP / 0.37kW 2HP / 1.1kW 3HP / 1.5kW 5HP / 2.2kW 5HP / 3.7kW RGC..32 RGC..40 1HP / 0.56kW 3HP / 1.5kW 5HP / 2.2kW 5HP / 3.7kW 7½HP / 4kW RGC..42 1½HP / 0.56kW 3HP / 1.5kW 5HP / 2.2kW 7½HP / 3.7kW 10HP / 4kW RGC..60 1½HP / 0.56kW 3HP / 1.5kW 5HP / 3kW 7½HP / 4kW 10HP / 4kW RGC..62 2HP / 0.75kW 5HP / 1.5kW 7½HP / 4kW 10HP / 4kW 15HP / 5.5kW RGC..90 2HP / 0.75kW 5HP / 1.5kW 7½HP / 4kW 10HP / 4kW 15HP / 5.5kW RGC..92 2HP / 0.75kW 5HP / 1.5kW 7½HP / 4kW 10HP / 4kW 15HP / 5.5kW
1
/3HP / 0.18kW 1HP / 0.37kW 2HP / 0.75kW 3HP / 1.1kW 3HP / 1.5kW
1
/3HP / 0.18kW 1HP / 0.37kW 2HP / 0.75kW 3HP / 1.1kW 3HP / 1.5kW
1
/3HP / 0.18kW 1HP / 0.37kW 2HP / 0.75kW 3HP / 1.1kW 3HP / 1.5kW
6 Specifications are subject to change without notice (22.05.2018)
RGC...E
Detailed Over temperature Alarm Procedure (for RGC...P)
ALARM Signal and Fan (applicable to RGC..D90GGEP) (applicable to RGC..D92GGEP)
ALARM Signal only
ALARM Signal onlyALARM Signal and FAN
START
START
Is Chip
Is Chip
temperature >
temperature >
115°C ?
115°C ?
Y
Y
FAN: ON
FAN: ON
Chip
Is Chip
temperature <
temperature <
85°C ?
85°C ?
Y
Y
FAN: OFF
FAN: OFF
N
N
N
N
temperature
temperature
limitreached?
limitreached?
SSRoutput: OFF
SSRoutput: OFF Red LED: ON
Red LED: ON AlarmSignal: ON
AlarmSignal: ON
Is Chip
temperature <
80°C?
SSR output: ON Red LED: OFF Alarm Signal: OFF FAN: OFF
Chip
Chip
START
START
Chip
Chip
temperature
temperature
limit reached?
limit reached?
SSRoutput: OFF
SSRoutput: OFF Red LED: ON
Red LED: ON AlarmSignal: ON
AlarmSignal: ON
N
N
Y
Y
Chip
Chip
temperature <
temperature <
80°C?
80°C?
SSR output: ON
SSR output: ON Red LED: OFF
Red LED: OFF Alarm Signal: OFF
Alarm Signal: OFF
N
N
Y
Y
N
N
Y
Y
N
Y
CAUTION
• Alarm condition resets whenever the voltage signal is removed from terminal A1 (+)
• In the case of RGC1A60D9xGGEP, if the voltage signal is not applied across A1(+) and A2 (-) terminals, the overtemperature detection and functionality is lost (including fan operation and alarm signalling)
• In the case of RGC1A60A9xGGEP it is necessary to supply IN2 and IN3 with 24VDC for fan operation.
• Alarm procedure for RGC1A60A9xGGEP follows ‘Alarm signal only’ flow since fan is continously operating.
• Alarm condition automatically resets ONLY when power semiconductor temperature < 80˚C
• Temperatures indicated are typical figures.
Specifications are subject to change without notice (22.05.2018) 7
RGC...E
Output Power Dissipation
100
90
80
70
60
50
40
PowerDissipationinW
30
20
RGC..15,20
RGC..25,30
RGC..40,60
RGC..90
RGC..32,42,62,92
10
0
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85
LoadCurrentinAACrms
8 Specifications are subject to change without notice (22.05.2018)
RGC...E
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
0 10 20 30 40 50 60 70 80
LoadCurrentinAACrms
SurroundingAmbientTemperaturein°C
RGC..32.GE
RGC..32.KE
RGC..30
RGC..25
RGC..20
RGC..15
0
10
20
30
40
50
60
70
80
90
0 10 20 30 40 50 60 70 80
LoadCurrentinAACrms
SurroundingAmbientTemperatureinoC
RGC..92 RGC..90
RGC..62
RGC..60
RGC..42
RGC..40
Current Derating (UL508)
RGC...P models max. operating temperature is + 70˚C
Specifications are subject to change without notice (22.05.2018) 9
RGC...E
e
20
e
5mm
0
5
10
15
20
25
30
01020304050607080
Load Current in AAC
Surrounding Ambient Temperature in °C
0mm
5mm
10mm
22.5mm & over
Derating vs. Spacing Curves
RGC.. 15..
25
20
15
nt in AAC
Load Curr
RGC.. 20..
nt in AAC
Load Curr
10
5
0
0 10 20 30 40 50 60 70 80
Surrounding Ambient Temperature in °C
35
30
25
15
10
5
0
0 10 20 30 40 50 60 70 80
Surrounding Ambient Temperature in °C
0mm
5mm
10mm & over
0mm
10mm
20mm & over
RGC.. 25.
10 Specifications are subject to change without notice (22.05.2018)
RGC...E
25
n
35
40
45
50
nt in AAC
0mm
10mm &
10
15
20
25
30
0 10 20 30 40 50 60 70 80
Load Curre
Surrounding Ambient Temperature in °C
over
Stand alone unit
LoadCurrentinAAC
0mm
5mm
20mm
Standalone
Derating vs. Spacing Curves
RGC.. 30..
35
30
t in AAC
20
Load Curre
15
10
0 10 20 30 40 50 60 70 80
Surrounding Ambient Temperature in °C
0mm
5mm
10mm & over
Stand alone unit
RGC.. 32..
RGC.. 40..
40
35
30
25
20
15
10
5
0
0 10 20 30 40 50 60 70 80
SurroundingAmbientTemperaturein°C
0mm
5mm
20mm
Standalone
Specifications are subject to change without notice (22.05.2018) 11
RGC...E
60
65
70
nt in AAC
0mm
30
35
40
45
50
55
0 10 20 30 40 50 60 70 80
Load Curr
e
Surrounding Ambient Temperature in °C
10mm & over
Stand alone unit
Derating vs. Spacing Curves
RGC.. 42.
RGC.. 60..
RGC.. 62.
12 Specifications are subject to change without notice (22.05.2018)
7
5
80
85
90
nt in AAC
0mm
50
55
60
65
70
5
0 10 20 30 40 50 60 70
Load Curr
e
Surrounding Ambient Temperature in °C
10mm & over
Stand alone unit
RGC...E
Derating vs. Spacing Curves
RGC.. 90GGEP, RGC..92GGEP
Environmental Specifications
Operating temperature12 -40°C to 80°C (-40˚F to +176˚F) Storage temperature -40°C to 100°C (-40˚F to +212˚F) EU RoHS compliant Yes China RoHS compliant Refer to Environmental
Information (page 29) Impact resistance
(EN50155, EN61373) 15/11 g/ms Vibration resistance
(2-100Hz, IEC60068-2-6, EN50155, EN61373) 2g per axis
Weight RGC..15 approx. 260g RGC..20 approx. 315g RGC..25 approx. 260g RGC..32 approx. 260g RGC..32..GE approx. 269g
Agency Approvals and Conformances
Conformance IEC/EN 62314 IEC/EN 60947-4-2 IEC/EN 60947-4-3
Relative humidity 95% non-condensing @ 40˚C UL flammability rating
(housing) UL 94 V0 Glow wire ignition temperature and Glow wire flammability index conform to EN 60335-1 requirements
Installation altitude 0 - 1000m. Above 1000m derate linearly by 1% of FLC per 100m up to maximum of 2000m
RGC..30 (P) approx. 375g (412g) RGC..4x (P) approx. 515g (581g) RGC..6x (P) approx. 972g (1020g) RGC..9x P approx. 1100g
Agency Approvals UL508 Listed (E172877) cUL Listed (E172877) VDE 0660-109 GL
Short Circuit Current Rating 100kA, UL508
13
14
12. Operating temperature range for RGC..P (overtemperature protection) is -30˚C to 70˚C (-22˚F to 158˚F)
13. Applicable to models RGC1...15.KE, RGC1...20.KE, RGC1..25..KE and RGC1...30.KE
14. RGC..32 models are not VDE approved
Specifications are subject to change without notice (22.05.2018) 13
RGC...E
Electromagnetic Compatibility
EMC Immunity EN 60947-4-3 Electrostatic Discharge (ESD) Immunity IEC/EN 61000-4-2
Air discharge, 8kV Performance Criteria 1 Contact, 4kV Performance Criteria 1
Electrical Fast Transient (Burst) Immunity IEC/EN 61000-4-4
Output: 2kV, 5kHz Performance Criteria 1 Input: 1kV, 5kHz Performance Criteria 1 Electrical Surge Immunity IEC/EN 61000-4-5
(for RGC...E) Output, line to line, 1kV Performance Criteria 1 Output, line to earth, 2kV Performance Criteria 1 Input, line to line, 1kV Performance Criteria 2 Input, line to earth, 2kV Performance Criteria 2
EMC Emission EN 60947-4-3 Radio Interference
Voltage Emission (Conducted) IEC/EN 55011
0.15 - 30MHz Class A (industrial) with filters
- see filter information
Electrical Surge Immunity IEC/EN 61000-4-5 (for RGC...EP)
Output, line to line, 1kV Performance Criteria 1 Output, line to earth, 2kV Performance Criteria 1 DC lines, line to line, 500V Performance Criteria 2 DC lines, line to earth, 500V Performance Criteria 2 Signal lines, line to earth, 1kV Performance Criteria 2
Radiated Radio Frequency Immunity IEC/EN 61000-4-3
10V/m, 80 - 1000 MHz Performance Criteria 1 10V/m, 1.4 - 2 GHz Performance Criteria 1 3V/m, 2 - 2.7 GHz Performance Criteria 1
Conducted Radio Frequency IEC/EN 61000-4-6 Immunity
10V/m, 0.15 - 80 MHz Performance Criteria 1 Voltage Dips Immunity IEC/EN 61000-4-11 0% for 0.5, 1 cycle Performance Criteria 2 40% for 10 cycles Performance Criteria 2 70% for 25 cycles Performance Criteria 2 80% for 250 cycles Performance Criteria 2 Voltage Interruptions Immunity IEC/EN 61000-4-11
0% for 5000ms Performance Criteria 2
Radio Interference Field Emission (Radiated) IEC/EN 55011
30 - 1000MHz Class A (industrial)
14 Specifications are subject to change without notice (22.05.2018)
RGC...E
Filtering - EN / IEC 55011 Class A compliance (for class B compliance contact us)
Part Number Suggested filter for compliance Maximum Heater current
RGC1A23..15 68nF/ 275 V / X1 20A RGC1A23..20 68nF/ 275 V / X1 20A RGC1A23..25, RGC1A23..30 220 nF / 275V / X1 30A RGC1A23..40 220 nF / 275V / X1 30A
330 nF / 275V / X1 45A RGC1A23..60 220 nF / 275V / X1 30A
330 nF / 275V / X1 45A RGC1A23..42, RGC1A23..62 330 nF / 275V / X1 35A
680 nF / 275V / X1 65A RGC1A60..15 100 nF / 760V / X1 20A RGC1A60..20 100 nF / 760V / X1 20A RGC1A60..25, RGC1A60..30 220 nF / 760V / X1 30A RGC1A60..40 220 nF / 760V / X1 25A
330 nF / 760V / X1 45A RGC1A60..60 220 nF / 760V / X1 25A
330 nF / 760V / X1 45A RGC1A60..32, RGC1A60..42, 330 nF / 760V / X1 40A
RGC1A60..62, RGC1A60..9x 680 nF / 760V / X1 65A
Note:
• Control input lines must be installed together to maintain products’ susceptability to Radio Frequency interference.
• Use of AC solid state relays may, according to the application and the load current, cause conducted radio interferences. Use of mains filters may be necessary for cases where the user must meet E.M.C requirements. The capacitor values given inside the filtering specification tables should be taken only as indications, the filter attenuation will depend on the final application.
• Performance Criteria 1: No degradation of performance or loss of function is allowed when the product is operated as intended.
• Performance Criteria 2: During the test, degradation of performance or partial loss of function is allowed. However when the test is complete the product should return operating as intended by itself.
• Performance Criteria 3: Temporary loss of function is allowed, provided the function can be restored by manual operation of the controls.
Filter Connection Diagrams
1 Phase
L1
L2
L3
N
3 Phase
SSR
SSR
SSR
R
d
R
d
R
d
LOAD
R
= 1MΩ, 0.5W
d
Filter has to be connected across both LOAD and SSR
Specifications are subject to change without notice (22.05.2018) 15
RGC...E
L1
L1
Functional Diagram (Without OTP)
DC control
+
A1
()
A2( )
AC control
A1
()
A2( )
~
-
+ ~
-
REGULATION
REGULATION
T1
ZC
IO
T1
ZC
Connection Diagram (Without OTP)
L1
L2/N
Control input
* depends on system requirements
*
Load
16 Specifications are subject to change without notice (22.05.2018)
Load
Control input
L1
L2/N
*
Load
L1
L2/N
*
12L1
T1
hc ti w SetatSd
i
lo SGR
FAULT
CON TRO L
A1
A2
GNDG
N
D
S
U
P
PL
Y
ALAR
M
A
LA
R
M
11 +
12 -
RGC...E
Connection Diagram (with OTP)
DC Control
RGC1...D30GKEP, RGC1...D4xGGEP, RGC1...D6xGGEP
RGC1...D9xGGEP
Uc: 5 - 32 VDC Ua: max 35VDC Alarm Output: max. 50mA
A1, A2: Control voltage 11, 12: Alarm output
Uc: 5 - 32 VDC Us: 24 VDC Alarm Output: max. 50mA
Note: Fan is internally supplied
A1, A2: Supply voltage IN1: Control voltage OUT: Alarm output
AC Control
RGC1...A30GKEP, RGC1...A4xGGEP, RGC1...A6xGGEP
* depends on system requirements
Uc: 24 - 275 VAC 24 - 190 VDC Ua: max 35VDC Alarm Output: max. 50mA
A1, A2: Control voltage 11, 12: Alarm output
RGC1...A9xGGEP
Uc: 24 - 275 VAC 24 - 190 VDC Ua: max. 35 VDC Alarm Output: max. 50mA U
f: 24 VDC (needs to be
supplied externally)
A1, A2: Control voltage 11, 12: Alarm output IN2, IN3: Fan supply
Specifications are subject to change without notice (22.05.2018) 17
RGC...E
17.8
98.5 51
35.5
9.5
17.8
9.5
5
3.2
35.5
45.5
5
3.2
109.5
92
1069890
1069890
43.8
43.8
Terminal Layout and Dimensions
RGC...15KKE, RGC...25KKE, RGC...32KKE
RGC...15MKE, RGC...25MKE, RGC..32MKE
12L1
hctiwS etatS diloS GR
A1 L1
T1A2
ON
A2
A1
T1
1/L1: Supply connection 2/T1: Load connection A1 (+): Positive control signal A2 (-): Control ground : Protective earth
Housing width tolerance +0.5mm, -0mm…as per DIN43880.
All other tolerances ± 0.5mm.
All dimensions in mm.
18 Specifications are subject to change without notice (22.05.2018)
17.8
98.5 51
35.5
9.5
5
3.2
1069890
43.8
17.8
98.5 51
35.5
9.5
17.8
9.5
5
3.2
35.5
45.5
5
3.2
109.5
92
1069890
1069890
43.8
43.8
RGC...E
Terminal Layout and Dimensions (cont).
RGC..32KGE
RGC..32MGE
1/L1: Supply connection 2/T1: Load connection A1 (+): Positive control signal A2 (-): Control ground : Protective earth
12L1
hctiwS etatS diloS GR
A1 L1
T1A2
ON
A2
A1
L11
T12
T1
Housing width tolerance +0.5mm, -0mm…as per DIN43880.
All other tolerances ± 0.5mm.
All dimensions in mm.
Specifications are subject to change without notice (22.05.2018) 19
RGC...E
17.8 136
51
35.5
9.5
17.8
22.5
9.5
5
3.2
136
51
35.5
9.5
5
3.2
35.5
45.5
5
3.2
17.8
147
129.5
1069890
1069890
1069890
43.8
43.8
43.8
Terminal Layout and Dimensions (cont).
RGC...20KKE
RGC...20MKE
12L1
hctiwS etatS diloS GR
A1 L1
T1A2
ON
A2
A1
T1
RGC...30KKE
1/L1: Supply connection 2/T1: Load connection A1 (+): Positive control signal A2 (-): Control ground : Protective earth
Housing width tolerance +0.5mm, -0mm…as per DIN43880.
All other tolerances ± 0.5mm.
All dimensions in mm.
20 Specifications are subject to change without notice (22.05.2018)
22.5
9.5
3.2
5
147
129.5
35.6
136
51
43.7
5
3.2
5
3.2
35.6
147
129.5
27.2
27.2
43.8
106
98
90
106
98
90
43.8
43.8
RGC...E
Terminal Layout and Dimensions (cont.)
RGC...30MKE
12L1
h c
A1 L1
t
i w S
e ta t S
d i
l o
T1A2
S
G
R
ON
A2
A1
RGC...40KGE, RGC...42KGE
RGC...40MGE, RGC...42MGE
T1
1/L1: Supply connection 2/T1: Load connection A1 (+): Positive control signal A2 (-): Control ground : Protective earth
Housing width tolerance +0.5mm, -0mm…as per DIN43880.
All other tolerances ± 0.5mm. All dimensions in mm.
Specifications are subject to change without notice (22.05.2018) 21
RGC...E
136
5
69.1
35.6
27.2
3.2 106
98
90
43.8
51
43.7
h c
t
i w S
e ta t S
d i
l o S
G
R
ON
A1 L1
T1A2
A1
A2
12L1
T1
22.5
9.5
3.2
5
147
129.5
35.6
136
51
43.7
5
3.2
5
3.2
35.6
147
129.5
27.2
27.2
43.8
106
98
90
106
98
90
43.8
43.8
Terminal Layout and Dimensions (cont.)
RGC...60KGE, RGC...62KGE
RGC...62MGE
1/L1: Supply connection 2/T1: Load connection A1 (+): Positive control signal
A2 (-): Control ground : Protective earth
Housing width tolerance +0.5mm, -0mm…as per DIN43880.
All other tolerances ± 0.5mm.
All dimensions in mm.
22 Specifications are subject to change without notice (22.05.2018)
RGC...E
136
5
69.1
35.6
27.2
3.2
22.5
5
5
163
35.5
78
22.5
9.5
163
78
35.5
17.8
9.5
106
98
90
106
98
90
106
98
90
43.8
51
43.7
12L1
T1
h c t
i w S
e t a
t S
d i
l o S G
R
F
AU
L
T
CONTROL
A1
A2
GNDGND
SUPP
L
Y
ALARM
ALARM
11+
12 -
Terminal Layout and Dimensions (cont.)
RGC...30GKEP
12L1
1/L1: Supply connection 2/T1: Load connection A1 (+): Positive control signal
A2 (-): Control ground 11 + : Alarm output (+) 12 - : Alarm output (-)
: Protective earth
ALARM
11+
h c t
i w S
e t a
t S
d i
l o S G
R
ALARM
12 -
CONTROL
F
AU
L
SUPP
L
Y
A1
T
A2
GNDGND
T1
Housing width tolerance +0.5mm, -0mm…as per DIN43880.
All other tolerances ± 0.5mm.
All dimensions in mm.
Specifications are subject to change without notice (22.05.2018) 23
167.8
5
35.6
27.2
69.1
27.2
69.1
27.2
126
98
90
60.5
5
163
43.7
78
5
163
78
43.7
106
98
90
106
98
90
60.5
163
78
43.7
RGC...E
Terminal Layout and Dimensions (cont.)
RGC...40GGEP, RGC...42GGEP
A1A211+
12-
A1A211+
12-
IN3IN2
RGC...60GGEP, RGC...62GGEP
A1A211+
12-
A1A211+
12-
A1A211+
12-
IN3IN2
IN3IN2
IN3IN2
RGC...90GGEP, RGC...92GGEP
ALARM
SUPPLY
CONTROL
A1
OUT
IN
1
hctiwS etatS diloS G
CONTROL
R
FAULT
A2
3
IN
2
IN
FAN -
FAN +
GND
GND
A1A211+
12-
A1A211+
12-
IN3IN2
IN3IN2
RGC...D9xGGEP RGC...A9xGGEP
1/L1: Supply connection 2/T1: Load connection A1 (+): Positive control signal (Positive supply in case of RGC1A60D9xGGEP) A2 (-): Control ground IN1: Control signal (only for RGC1A60D9xGGEP) IN2: Fan + supply (only for RGC1A60A9xGGEP) IN3: Fan - supply (only for RGC1A60A9xGGEP) 11 + : Alarm output (+) OUT, 12 - : Alarm output (-) : Protective earth
Housing width tolerance +0.5mm, -0mm…as per DIN43880.
All other tolerances ± 0.5mm. All dimensions in mm.
24 Specifications are subject to change without notice (22.05.2018)
X
X
X
X
X
X
X
X
X
X
X
X
RGC...E
Connection Specifications
POWER CONNECTIONS: 1/L1, 2 /T1 Use 75°C copper (Cu) conductors
Stripping Length (X) 12mm 11mm Connection type M4 screw with captivated washer M5 screw with box clamp Rigid (Solid & Stranded)
UL / cUL rated data
X
2 x 2.5..6 mm 2 x 14.. 10 AWG
Flexible with end sleeve 2 x 1.0 ... 2.5mm
2 x 14.. 12 AWG
Flexible without 2 x 1.0 ... 2.5mm end sleeve 2 x 2.5.. 6mm
2 x 18.. 14 AWG 2 x 14.. 10 AWG
Torque specifications Pozidriv 2 Posidriv 2 UL: 2Nm (17.7lb-in) UL: 2.5Nm (22lb-in) IEC: 1.5 - 2.0Nm (13.3 - 17.7lb-in)
Aperture for termination lug 12.3mm N/A
Protective Earth (PE) Connection
M5, 1.5Nm (13.3 lb-in)
RGC...KKE ; RG..GKEP. ; RG...MKE RG...KGE ; RG...GGEP ; RG...MGE
2 x 2.5..4mm
2
2 x 18.. 14 AWG
2
1 x 2.5..6 mm 1 x 14.. 10 AWG 1 x 14...3 AWG
2
1 x 1.0..4mm
1 x 18.. 12 AWG 1 x 14.. 6 AWG
2
2
1 x 1.0.. 6mm
1 x 18.. 10 AWG 1 x 12.. 3 AWG
2
2
2
1 x 2.5..25mm2
1 x 2.5..16mm
2
1 x 4.. 25mm2
IEC: 2.5 - 3.0Nm (22-26.6lb-in)
Note: M5 PE screw not provided with SSR. PE connection required when product is intended to be used in Class 1 applications according to EN/IEC 61140.
CONTROL CONNECTIONS: A1(+), A2(-)
Use 60/75°C copper (Cu) conductors
RG...KKE, RG..KGE RG....MKE, RG...MGE
Torque specifications M3, Pozidriv 1 UL: 0.5Nm (4.4lb-in) IEC: 0.5 - 0.6Nm (4.4 - 5.3lb-in)
Stripping Length (X) 8mm 12 - 13mm Rigid (Solid & Stranded)
UL/ cUL rated data
2 x 0.5..2.5mm 2 x 18..12 AWG
Flexible with end sleeve 2 x 0.5..2.5mm 2 x 18..12AWG
X
2
1 x 0.5..2.5mm
1 x 18..12 AWG 1 x 24...12 AWG
2
1 x 0.5..2.5mm2
1 x 18..12AWG
2
1 x 0.2...2.5mm2
CONTROL CONNECTIONS: A1(+), A2(-), IN1, IN2, IN3, 11 (+), 12(-), OUT Use 60/75°C copper (Cu) conductors RG...GGEP Torque specifications M3, Pozidriv 1
UL: 0.5Nm (4.4lb-in) IEC: 0.4 - 0.5Nm (3.5 - 4.4lb-in)
Stripping Length (X) 6mm 6mm Rigid (Solid & Stranded)
UL/ cUL rated data
2 x 1.0..2.5mm 2 x 18..14 AWG
Flexible with end sleeve 2 x 1.0..2.5mm 2 x 18..14 AWG
X
2
1 x 1.0 ..2.5mm
1 x 18..14 AWG
2
1 x 1.0..2.5mm2
1 x 18..14AWG
2
Specifications are subject to change without notice (22.05.2018) 25
RGC...E
Installation Instructions
Y1 = 50mm
RGC RGC
20mm
Y2 = 100mm
X
Mounting on DIN rail
Mounting on DINrail
Dismounting from DIN rail
Dismountingfrom DINrail
20mm
X
X= 20mm
X = Refer to Derating vs. Spacing Curves
RGC
50mm
Short Circuit Protection
Protection Co-ordination, Type 1 vs Type 2:
Type 1 protection implies that after a short circuit, the device under test will no longer be in a functioning state. In type 2 co-ordination the device under test will still be functional after the short circuit. In both cases, however the short circuit has to be interrupted. The fuse between enclosure and supply shall not open. The door or cover of the enclosure shall not be blown open. There shall be no damage to conductors or terminals and the condcutors shall not separate from terminals. There shall be no breakage or cracking of insulating bases to the extent that the integrity of the mounting of live parts is impaired. Discharge of parts or any risk of fire shall not occur.
The product variants listed in the table hereunder are suitable for use on a circuit capable of delivering not more than 100,000A rms Symmetrical Amperes, 600 Volts maximum when protected by fuses. Tests at 100,000A were performed with Class J fuses, fast acting; please refer to the table below for maximum allowed ampere rating of the fuse. Use fuses only.
Tests with Class J fuses are representative of Class CC fuses.
Co-ordination type 1 (UL508)
Part No. Prospective short Max. fuse size [A] Class Voltage [VAC] circuit current [kArms]
RGC..15 100 30 J or CC max. 600 RGC..20 100 30 J or CC max. 600 RGC..25 100 30 J or CC max. 600
RGC..30 100 30 J or CC max. 600 RGC..32 100 80 J max. 600 RGC..40 100 40 J max. 600 RGC..42 100 90 J max. 600 RGC..60 100 40 J max. 600 RGC..62 100 90 J max. 600 RGC..90 100 40 J max. 600 RGC..92 100 90 J max. 600
26 Specifications are subject to change without notice (22.05.2018)
RGC...E
Co-ordination type 2 (IEC/EN 60947-4-2/ -4-3)
Part No. Prospective short Mersen (Ferraz Shawmut) Siba Voltage [VAC]
[kArms] size [A] Part number size [A] Part number
RGC..15 10 25 6.9xx CP GRC 14x51 /25 32 50 142 06.32 max. 600
100 25 6.9xx CP GRC 14x51 /25 32 50 142 06.32 max. 600
RGC..20 10 40 6.6xx CP URD 22x58 /40 32 50 142 06.32 max. 600
100 40 6.6xx CP URD 22x58 /40 32 50 142 06.32 max. 600
RGC..25 10 40 6.9xx CP GRC 22x58 /40 32 50 142 06.32 max. 600
100 40 6.6xx CP URD 22x58 /40 32 50 142 06.32 max. 600
RGC..30 10 40 6.9xx CP GRC 22x58 /40 32 50 142 06.32 max. 600
100 40 6.6xx CP URD 22x58 /40 32 50 142 06.32 max. 600
RGC..40 10 63 6.621 CP URGD 27x60 /63 63 50 194 20.63 max. 600
10 70 A70QS70-4 63 50 194 20.63 max. 600
100 63 6.621 CP URQ 27x60 /63 63 50 194 20.63 max. 600
RGC..32 10 63 6.9xx CP URC 14x51 /63 80 50 194 20.80 max. 600
RGC..42 10 70 A70QS70-4 80 50 194 20.80 max. 600
100 63 6.9xx CP URC 14x51 /63 80 50 194 20.80 max. 600
100 70 A70QS70-4 80 50 194 20.80 max. 600
RGC..60 10 80 6.621 CP URQ 27x60 /80 80 50 194 20.80 max. 600
up to 65AAC
100 n/a n/a 80 50 194 20.80 max. 600
RGC..62 10 100 6.9xx CP GRC 22x58 /100 100 50 194 20.100 max. 600
10 100 A70QS100-4 100 50 194 20.100 max. 600
100 100 6.621 CP URGD 27x60 /100 100 50 194 20.100 max. 600
100 100 A70QS100-4 100 50 194 20.100 max. 600
RGC..90 10 100 6.621 CP URQ 27x60 /100 100 50 194 20.100 max. 600
up to 80AAC
10 100 A70QS100-4 100 50 194 20.100 max. 600
100 n/a n/a 100 50 194 20.100 max. 600
RGC..92 10 125 6.621 CP URQ 27x60 /125 125 50 194 20.125 max. 600
10 125 A70QS125-4 125 50 194 20.125 max. 600
100 125 6.621 CP URQ 27x60 /125 125 50 194 20.125 max. 600
100 125 A70QS125-4 125 50 194 20.125 max. 600
circuit current Max fuse Max fuse
Specifications are subject to change without notice (22.05.2018) 27
RGC...E
Type 2 Protection with Miniature Circuit Breakers (M.C.B.s)
Solid State Relay ABB Model no. for ABB Model no. for Wire cross Minimum length of type Z - type M. C. B. B - type M. C. B. sectional area [mm2] Cu wire conductor [m]
16
(rated current) (rated current)
RGC..15 1 pole RGC..20 S201 - Z4 (4A) S201 - B2 (2A) 1.0 21.0
2
s) S201 - Z6 UC (6A) S201 - B2 (2A) 1.0 21.0
(525 A
1.5 31.5
RGC..25 1 pole RGC..30 S201 - Z10 (10A) S201-B4 (4A) 1.0 7.6 (1800 A2s) 1.5 11.4
2.5 19.0
S201 - Z16 (16A) S201-B6 (6A) 1.0 5.2
1.5 7.8
2.5 13.0
4.0 20.8
S201 - Z20 (20A) S201-B10 (10A) 1.5 12.6
2.5 21.0
S201 - Z25 (25A) S201-B13 (13A) 2.5 25.0
4.0 40.0
2 pole S202 - Z25 (25A) S202-B13 (13A) 2.5 19.0
4.0 30.4
RGC..40 1 pole (3200 A2s) S201 - Z25 (25A) S201-B13 (13A) 2.5 7.0
4.0 11.2
6.0 16.8
RGC..60 1 pole (3200 A2s) S201 - Z25 (25A) S201-B13 (13A) 2.5 7.0
4.0 11.2
6.0 16.8
RGC..90 1 pole
2
s) S201 - Z20 (20A) S201-B10 (10A) 1.5 4.2
(6600 A
2.5 7.0
4.0 11.2
S201 - Z32 (32A) S201-B16 (16A) 2.5 13.0
4.0 20.8
6.0 31.2
2 pole S202 - Z20 (20A) S202-B10 (10A) 1.5 1.8
2.5 3.0
4.0 4.8
S202 - Z32 (32A) S202-B16 (16A) 2.5 5.0
4.0 8.0
6.0 12.0
10.0 20.0
S202 - Z50 (50A) S202-B25 (25A) 4.0 14.8
6.0 22.2
10.0 37.0
RGC..32 1 pole RGC..42 S201-Z32 (32A) S201-B16 (16A) 2.5 3.0 RGC..62 4.0 4.8 RGC..92 6.0 7.2
2
(18000 A
S201-Z50 (50A) S201-B25 (25A) 4.0 4.8
s)
6.0 7.2
10.0 12.0
16.0 19.2
S201-Z63 (63A) S201-B32 (32A) 6.0 7.2
10.0 12.0
16.0 19.2
16. Between MCB and Load (including return path which goes back to the mains). Note: A prospective current of 6kA and a 230/400V power supply system is assumed for the above suggested specifications. For cables with different cross section than those mentioned above please consult Carlo Gavazzi’s Technical Support Group.
28 Specifications are subject to change without notice (22.05.2018)
RG...P19
The declaration in this section is prepared in compliance with People’s Republic of China Electronic Industry Standard SJ/ T11364-2014: Marking for the Restricted Use of Hazardous Substances in Electronic and Electrical Products.
Environmental Information
环境特性
RGC...E
Part Name Toxic or Harardous Substances and Elements
Power Unit Assembly x O O O O O
O: Indicates that said hazardous substance contained in homogeneous materials fot this part are below the limit require­ment of GB/T 26572.
X: Indicates that said hazardous substance contained in one of the homogeneous materials used for this part is above the limit requirement of GB/T 26572.
Lead
(Pb)
Mercury
(Hg)
Cadmium
(Cd)
Hexavalent
Chromium
(Cr(Vl))
Polybrominated biphenyls (PBB)
Polybrominated
diphenyl ethers
(PBDE)
零件名称 有毒或有害物质与元素
(Pb)
功率单元 x O O O O O
O:此零件所有材料中含有的该有害物低于GB/T 26572的限定。
X: 此零件某种材料中含有的该有害物高于GB/T 26572的限定。
(Hg)
(Cd)
六价铬
(Cr(Vl))
多溴化联苯
(PBB)
多溴联苯醚
(PBDE)
25
Specifications are subject to change without notice (22.05.2018) 29
RGC...E
Accessories
Control Plugs
Ordering Key
Pack of 10 spring loaded control plugs
* Refer to ‘Connection Specifications’ section for further details.
RGM25
30 Specifications are subject to change without notice (22.05.2018)