Solid State Relays
1-Phase with Integrated Heatsink
Zero Cross or Instant On Switching
Types RGC Solid State Contactor ‘E’ Connection
• Product width ranging from 17.5mm up to 70mm
• Rated operational voltage: up to 660 VAC
• Rated operational current: up to 85 AAC @ 40°C
• 18000 A
• Control voltages: 3-32 VDC, 20-275 VAC (24-190 VDC)
• Design according to EN/IEC60947-4-2, EN/IEC60947-4-3,
EN/IEC62314, UL508, CSA 22-2 No. 14-13
• Integrated voltage transient protection with varistor
• 100 kA short circuit current rating according to UL508
2
s for the I2t and 1200 Vp blocking voltage
12
Product Description
This new range of solid state
contactors presents a unique
opportunity to maximize efficiency in panel space and
is an evolution of solid state
switches for which Carlo
Gavazzi is very well known.
The nominal current ratings
are at 40˚C. The smallest
1. RGC..32 models are not VDE approved
2. Germanischer Lloyd approval applicable only to models RGC1....15.KE,
RGC1...20.KE, RGC1..25..KE and RGC1....30.KE
width is 17.5mm and is rated
at 37 AAC. Power and control
teminals allow for safe looping of cables.
Voltage transient protection
is standard across the output
with a varistor. Specifications
are stated at 25°C unless
otherwise noted.
Ordering Key
RGC 1 A 60 A 30 K K E _
Solid state relay
Number of poles
Switching mode
Rated operational voltage
Control voltage
Rated operational current
Connection type for control
Connection type for power
Connection configuration
Option
Ordering Key (Refer to page 2 and 3 for available part numbers)
1 Phase SSR Rated voltage, Control voltage Rated Connection Connection Connection
with heatsink Blocking voltage current at 40˚C
Rated voltage, Control voltage Connection Rated operational current @ 40oC (I2t value)
Blocking voltage, control / power Product width
Switching mode 30 AAC (1800A²s)
7. Overload profile for AC-53a;
Ie: AC-53a: x-Tx: F-S, where Ie = nominal current (AC-53a AAC), x = overload current factor, Tx = duration of overload current (s), F = duty cycle (%), S = number
of starts per hour. Example; 5A: AC-53a: 6 - 6 : 50 - 30 = max. 30 starts for the RGC..15 with an overload profile of 30A for 6 seconds with a duty cycle of 50%
Overtemperature Alarm Specifications for RGC...P
RGC..D..P RGC..A..P
Output type PNP open collector Potential Free
Normal state Closed Closed
Maximum current rating 50 mADC 50 mADC
Rated voltage (EN61131-2: 2003)
Rated voltage, Us RGC...D9xGGEP 24VDC ± 10% N/A
Fan rating, U
f RGC...A9xGGEP N/A 24VDC ±10%, 50mA nominal
Alarm voltage drop Typical 2.8VDC 1.8VDC Maximum 4VDC 3.5VDC
Visual Indication Continous Red LED Continous Red LED
Reverse polarity protection 24VDC 24VDC
8. DC supply for alarm signal should be supplied from a Class 2 power source
9. Maximum voltage to be applied between 11+ and 12- (Ua) terminals should be 35VDC maximum with reference to A2-
4Specifications are subject to change without notice (22.05.2018)
6 Specifications are subject to change without notice (22.05.2018)
RGC...E
Detailed Over temperature Alarm Procedure (for RGC...P)
ALARM Signal and Fan
(applicable to RGC..D90GGEP)
(applicable to RGC..D92GGEP)
ALARM Signal only
ALARM Signal onlyALARM Signal and FAN
START
START
Is Chip
Is Chip
temperature >
temperature >
115°C ?
115°C ?
Y
Y
FAN: ON
FAN: ON
Chip
Is Chip
temperature <
temperature <
85°C ?
85°C ?
Y
Y
FAN:OFF
FAN: OFF
N
N
N
N
temperature
temperature
limitreached?
limitreached?
SSRoutput: OFF
SSRoutput: OFF
Red LED: ON
Red LED: ON
AlarmSignal: ON
AlarmSignal: ON
Is Chip
temperature <
80°C?
SSR output: ON
Red LED: OFF
Alarm Signal: OFF
FAN: OFF
Chip
Chip
START
START
Chip
Chip
temperature
temperature
limit reached?
limit reached?
SSRoutput: OFF
SSRoutput: OFF
Red LED: ON
Red LED: ON
AlarmSignal: ON
AlarmSignal: ON
N
N
Y
Y
Chip
Chip
temperature <
temperature <
80°C?
80°C?
SSR output: ON
SSR output: ON
Red LED:OFF
Red LED: OFF
Alarm Signal: OFF
Alarm Signal: OFF
N
N
Y
Y
N
N
Y
Y
N
Y
CAUTION
• Alarm condition resets whenever the voltage signal is removed from terminal A1 (+)
• In the case of RGC1A60D9xGGEP, if the voltage signal is not applied across A1(+) and A2 (-) terminals, the overtemperature detection and functionality is
lost (including fan operation and alarm signalling)
• In the case of RGC1A60A9xGGEP it is necessary to supply IN2 and IN3 with 24VDC for fan operation.
• Alarm procedure for RGC1A60A9xGGEP follows ‘Alarm signal only’ flow since fan is continously operating.
• Alarm condition automatically resets ONLY when power semiconductor temperature < 80˚C
• Temperatures indicated are typical figures.
Specifications are subject to change without notice (22.05.2018) 7
RGC...E
Output Power Dissipation
100
90
80
70
60
50
40
PowerDissipationinW
30
20
RGC..15,20
RGC..25,30
RGC..40,60
RGC..90
RGC..32,42,62,92
10
0
0510152025303540455055606570758085
LoadCurrentinAACrms
8 Specifications are subject to change without notice (22.05.2018)
RGC...E
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
01020304050607080
LoadCurrentinAACrms
SurroundingAmbientTemperaturein°C
RGC..32.GE
RGC..32.KE
RGC..30
RGC..25
RGC..20
RGC..15
0
10
20
30
40
50
60
70
80
90
01020304050607080
LoadCurrentinAACrms
SurroundingAmbientTemperatureinoC
RGC..92
RGC..90
RGC..62
RGC..60
RGC..42
RGC..40
Current Derating (UL508)
RGC...P models max. operating temperature is + 70˚C
Specifications are subject to change without notice (22.05.2018) 9