Carlo Gavazzi RCI Data Sheet

Industrial Relay
C US
Type RCI Monostable
Product Description Ordering Key RCI 003 A 24V
The RCI is an industrial relay that can be used in a wide range of applications. It is
available in 2 or 3 change over contacts configurations.
Type Contact Code Coil Type Coil Voltage
Product Selection Type Selection
Type Contact Code Coil Type Coil Voltage
RCI
002 - DPDT A - AC 12V, 24V, 48V, 120V, 240V AC
003 - 3PDT D - DC 5V, 6V, 12V, 24V, 48V, 110V DC
Product Selection
Part Number Contact Code Coil voltage Stock Code RCI002A12V RCI002A24V
RCI002A48V RCI002A120V RCI002A240V
RCI002D5V
RCI002D6V RCI002D12V RCI002D24V RCI002D48V
RCI002D110V
DPDT
2 change over
contacts, 8-pins
12 VAC D 24 VAC A
48 VAC D 120 VAC A 240 VAC A
5 VDC A
6 VDC D 12 VDC A 24 VDC A 48VDC D
110 VDC D
Part Number Contact Code Coil voltage Stock Code RCI003A12V RCI003A24V
RCI003A48V RCI003A120V RCI003A240V
RCI003D5V
RCI003D6V RCI003D12V RCI003D24V RCI003D48V
RCI003D110V
3PDT
3 change over
contacts, 11-pins
12 VAC D 24 VAC A
48 VAC D 120 VAC A 240 VAC A
5 VDC A
6 VDC D 12 VDC A 24 VDC A 48VDC D
110 VDC D
Contact Characteristics
Arrangement: DPDT, 3PDT
Contact Rating:
NO: 10A 250VAC/30VDC
NC: 5A 250VAC/30VDC
Hp rating at 240VAC 1/3 Hp
Maximum Switching Voltage: 250VAC / 250VDC
Minimum Switching Current: 100mA 5VDC
Material : AgSnO2
Contact Resistance: 100 mOhms (at 6 VDC 1A)
Reaction Time to Close: 20ms
Reaction Time to Open: 20ms
Electrical Life: 100,000 cycles (1800 per hour)
Mechanical Life 10,000,000 cycles (18,000 per hour)
Specifications are subject to change without notice — September-2016 1
ElectricalIndustrial Relay
Type RCI Monostable
Coil Characteristics
AC Coil DC Coil
Coil Code
12V 24V
48V 120V 240V
Nominal
Voltage
VAC VAC VA C W ±10% VA
12V 24V 72
48V 288 110/120V 1650 220/240V 6800
Pick-up Drop-out
at +23°C
80% 30%
Coil
Resistance
18
Coil
Power
aprox.
2.8
Coil Code
5V
6V 12V 24V 48V
110V
Nominal
Voltage
VAC VAC VAC W ±10% VA
5V
6V 22.5 12V 90 24V 360 48V 1440
110V 7000
Pick-up Drop-out
at +23°C
80% 10%
Coil
Resistance
15.6
Minimum and Maximum Coil Voltage vs Ambient Temperature
AC Coil DC Coil
1- Maximum coil voltage vs. temperature
2- Minimum coil voltage vs. temperature
Insulation Environmental Specifications
Coil
Power
aprox.
1.6
Between Open Contacts (1mA leakage)
1000 VAC for 1 minute
1200 VAC for 1 second
Between Contact and Coil and 1500 VAC for 1 minute
Contact to Contact (1mA leakage) 1700 VAC for 1 second
Operational Temperature
Operational Humidity
Storage Temperature
Storage Humidity
Dimensions
RCI002 RCI003
Diagram
RCI002 RCI003
-40°C ~ +55°C
35% ~ 85%
-40°C ~ +55°C
20% ~ 85%
Specifications are subject to change without notice — September-2016 2
Loading...
+ 1 hidden pages