Carlo Gavazzi RA.... .....S Catalog Page

Specifications are subject to change without notice (08.09.00) 1
Product Description Ordering Key
Solid State Relays System Monitoring Relays (Sense Relay)
Type RA.... .....S
•System (line and load) monitoring relay
•Zero switching
•Rated operational voltage: 120, 230, 400 and 480 VACrms
•High surge current capability
•Alarm output signal
•LED indication for alarm and supply
The system monitoring solid state relay (sense relay) pro­vides an alarm output in the event of a circuit failure. Internal circuits monitor:
- line voltage/line current
- correct functioning of the SSR
- SSR input status
The relay is designed for applications where immediate fault detection is required. A red LED indicates an alarm, a green LED indicates DC control supply OK (half LED light intensity) resp. relay switched ON (full LED light intensity).
Solid State Relay Switching mode Rated operational voltage Rated operational current Control input Non-rep. peak voltage Alarm output type Sense SSR
RA 23 25 H 06 NO S
Switching mode Rated operational Rated operational Control Non-rep. peak Alarm output
voltage current input voltage type
A: Zero switching 12: 120 VACrms 25: 25 AACrms H: Active high 06: 650 V
p
NO: NPN, NO
23: 230 VACrms 50: 50 AACrms L: Active low 10: 1000 V
p
NC: NPN, NC
40: 400 VACrms 90: 90 AACrms 12: 1200 V
p
PO: PNP, NO
48: 480 VACrms 110: 110 AACrms PC: PNP, NC
Rated Control Alarm Rated operational current op. input output voltage type 25 AACrms 50 AACrms 90 AACrms 110 AACrms
120 Active high NPN, NO RA 1225 H06NOS RA 1250 H06NOS RA 1290 H06NOS RA 12110 H06NOS VACrms NPN, NC RA 1225 H06NCS RA 1250 H06NCS RA 1290 H06NCS RA 12110 H06NCS
PNP, NO RA 1225 H06POS RA 1250 H06POS RA 1290 H06POS RA 12110 H06POS PNP, NC RA 1225 H06PCS RA 1250 H06PCS RA 1290 H06PCS RA 12110 H06PCS
Active low NPN, NO RA 1225 L06NOS RA 1250 L06NOS RA 1290 L06NOS RA 12110 L06NOS
NPN, NC RA 1225 L06NCS RA 1250 L06NCS RA 1290 L06NCS RA 12110 L06NCS PNP, NO RA 1225 L06POS RA 1250 L06POS RA 1290 L06POS RA 12110 L06POS PNP, NC RA 1225 L06PCS RA 1250 L06PCS RA 1290 L06PCS RA 12110 L06PCS
230 Active high NPN, NO RA 2325 H06NOS RA 2350 H06NOS RA 2390 H06NOS RA 23110 H06NOS VACrms NPN, NC RA 2325 H06NCS RA 2350 H06NCS RA 2390 H06NCS RA 23110 H06NCS
PNP, NO RA 2325 H06POS RA 2350 H06POS RA 2390 H06POS RA 23110 H06POS PNP, NC RA 2325 H06PCS RA 2350 H06PCS RA 2390 H06PCS RA 23110 H06PCS
Active low NPN, NO RA 2325 L06NOS RA 2350 L06NOS RA 2390 L06NOS RA 23110 L06NOS
NPN, NC RA 2325 L06NCS RA 2350 L06NCS RA 2390 L06NCS RA 23110 L06NCS PNP, NO RA 2325 L06POS RA 2350 L06POS RA 2390 L06POS RA 23110 L06POS PNP, NC RA 2325 L06PCS RA 2350 L06PCS RA 2390 L06PCS RA 23110 L06PCS
Type Selection
Selection Guide
2 Specifications are subject to change without notice (08.09.00)
Supply voltage range 20 to 32 VDC Supply current @ 24 VDC 40 mA DC Response time pick-up @ 50 Hz
10 ms
Response time drop-out @ 50 Hz
10 ms
Active high control input
Pick-up voltage Typ. 7 VDC Drop-out voltage Typ. 6.8 VDC Input current (Vc = 32 V) 4 mA
Active low control input
Pick-up voltage Typ. Vcc - 10 VDC Drop-out voltage Typ. Vcc - 10 VDC Input current (Vcc = 32 V) 4 mA
RA.... .....S
PNP Alarm output
Alarm output voltage open 0 VDC Alarm output voltage @ 100 mA
Vcc - 2 VDC
Alarm output current 100 mA
NPN Alarm output
Alarm output voltage open 32 VDC Alarm output voltage @ 100 mA
2 VDC
Alarm output current 100 mA
General Specifications
Control Specifications
Output Specifications
Selection Guide (cont.)
RA12...06..S RA23...06..S RA40...10..S RA48...12..S
Operational voltage range 60 to 140 VACrms 170 to 250 VACrms 150 to 440 VACrms 180 to 530 VAC Non-rep. peak voltage 600 V
p
600 V
p
1000 V
p
1200 V
p
Zero voltage turn-on 15 V 15 V 15 V 25 V Operational frequency range 45 to 65 Hz 45 to 65 Hz 45 to 65 Hz 45 to 65 Hz Power factor cos ϕ 0.5 @ 120 VACrms 0.5 @ 230 VACrms 0.5 @ 400 VACrms 0.5 @ 400 VACrms
Approvals UL, CSA UL, CSA UL, CSA UL, CSA CE-marking Yes Yes Yes Yes
RA..25.06..S RA..50.06..S RA..90.10..S RA..110.12..S
Rated operational current AC 1 25 Arms 50 Arms 90 Arms 110 Arms Min. operational load current 200 mA 200 mA 200 mA 200 mA Non-rep. surge current t=10 ms
250 A
p
600 A
p
1000 A
p
1500 A
p
Off-state leakage current @ rated voltage and frequency 6 mA 6 mA 6 mA 6 mA
I2t for fusing t=1-10 ms 310 A2s 1800 A2s 5000 A2s 11250 A2s Critical dv/dt 500 V/µs 500 V/µs 500 V/µs 500 V/µs
Rated Control Alarm Rated operational current op. input output voltage type 25 AACrms 50 AACrms 90 AACrms 110 AACrms
400 Active high NPN, NO RA 4025 H10NOS RA 4050 H10NOS RA 4090 H10NOS RA 40110 H10NOS VACrms NPN, NC RA 4025 H10NCS RA 4050 H10NCS RA 4090 H10NCS RA 40110 H10NCS
PNP, NO RA 4025 H10POS RA 4050 H10POS RA 4090 H10POS RA 40110 H10POS PNP, NC RA 4025 H10PCS RA 4050 H10PCS RA 4090 H10PCS RA 40110 H10PCS
Active low NPN, NO RA 4025 L10NOS RA 4050 L10NOS RA 4090 L10NOS RA 40110 L10NOS
NPN, NC RA 4025 L10NCS RA 4050 L10NCS RA 4090 L10NCS RA 40110 L10NCS PNP, NO RA 4025 L10POS RA 4050 L10POS RA 4090 L10POS RA 40110 L10POS PNP, NC RA 4025 L10PCS RA 4050 L10PCS RA 4090 L10PCS RA 40110 L10PCS
480 Active high NPN, NO RA 4825 H12NOS RA 4850 H12NOS RA 4890 H12NOS RA 48110 H12NOS VACrms NPN, NC RA 4825 H12NCS RA 4850 H12NCS RA 4890 H12NCS RA 48110 H12NCS
PNP, NO RA 4825 H12POS RA 4850 H12POS RA 4890 H12POS RA 48110 H12POS PNP, NC RA 4825 H12PCS RA 4850 H12PCS RA 4890 H12PCS RA 48110 H12PCS
Active low NPN, NO RA 4825 L12NOS RA 4850 L12NOS RA 4890 L12NOS RA 48110 L12NOS
NPN, NC RA 4825 L12NCS RA 4850 L12NCS RA 4890 L12NCS RA 48110 L12NCS PNP, NO RA 4825 L12POS RA 4850 L12POS RA 4890 L12POS RA 48110 L12POS PNP, NC RA 4825 L12PCS RA 4850 L12PCS RA 4890 L12PCS RA 48110 L12PCS
Loading...
+ 3 hidden pages